SMACNA Seismic Restraint Manual
Bob WasilewskiProject Manager, Technical Resources
SMACNA
![Page 2: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/2.jpg)
ANSI/SMACNA 001-2000Approved by ANSI July 31, 2000
![Page 3: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/3.jpg)
History
1976 – Guidelines for Seismic Restraint of Mechanical Systems(Sheet Metal Industry Fund of Los Angeles)
1982 – Guidelines for Seismic Restraints of Mechanical Systems and Plumbing Piping Systems(Sheet Metal Industry Fund of Los Angeles and The Plumbing and Piping Industry Council , Inc.)
![Page 4: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/4.jpg)
History1991 – Seismic Restraint Manual –Guidelines for Mechanical Systems(SMACNA)– Included larger ducts– Included conduit– Created Seismic Hazard Level (SHL)
1993 – Appendix E– Corrections and Clarifications– Specific Requirements for OSHPD– OSHPD Approval
![Page 5: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/5.jpg)
History
1998 – Second Edition
2000 – ANSI Approval
2000 – Addendum #1
![Page 6: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/6.jpg)
QUESTION??
What is the Issue?
![Page 7: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/7.jpg)
ANSWER
Physics!!
![Page 8: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/8.jpg)
PHYSICS
F = Ma
![Page 9: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/9.jpg)
Code Considerations
OLDER CODES1. BOCA
Fp = AvCcPacWc
2. SBCCIFp = AvCcPacWc
3. ICBOFp = ZIpCpWp
![Page 10: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/10.jpg)
All Codes Take the Form of
Fp = Cs Wp
Where Cs = A series of constants given in the building code
Cs is a measure of acceleration
![Page 11: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/11.jpg)
Current Codes
International Building Code (IBC) 2000-2003
Fp = 0.4ap SDS Wp (1 + 2Z/h)Rp/Ip
Uniform Building Code (UBC) 1997
Fp = apCaIp (1 + 3hx/hr) Wp
Rp
![Page 12: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/12.jpg)
The Form is the Same
IBC0.4 apSDS is a measure of acceleration
Rp/Ip
UBCapCaIp is a measure of acceleration
Rp
![Page 13: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/13.jpg)
Simplifying
IBC
Fp = CsWp (1 +2Z/h)
UBC
Fp = Cs(1 + 3hx/hr)Wp
![Page 14: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/14.jpg)
The Components
IBC (1 + 2Z/h)and
UBC (1 + 3hx/hr)
Are Adjustments for the Anticipated Force Levels Depending on Location in the Building
![Page 15: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/15.jpg)
Basic Equation
Fp = CsWp
Where Cs includes the Location Adjustment Factors
![Page 16: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/16.jpg)
Rearranging the Equation
=Wp
Cs
Fp
![Page 17: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/17.jpg)
The SMACNA Seismic Restraint Manual has Tables for Four Values
of Cs
These Tables are Identified as Seismic Hazard Level (SHL)
![Page 18: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/18.jpg)
SMACNA SHL Values
SHL C = Cs = .21
SHL B = Cs = .42
SHL A = Cs = .67
SHL AA = Cs = 1.0
![Page 19: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/19.jpg)
The Design Professional Should
1. Calculate Cs from the Information in the Applicable Local Building Code
2. Calculate the Values of Cs at the Various Attachment Locations in the Building
3. Indicate the Required SMACNA SHL Tables to be Used at the Different Attachment Locations
![Page 20: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/20.jpg)
General Requirements
1. Details provide lateral bracing system. Typical vertical supports per local building code must be used.
2. Thermal expansion not given but must be considered.
3. Duct construction to conform to the appropriate SMACNA publications.
![Page 21: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/21.jpg)
General Requirements
4. Pipes will conform to ANSI/ASME B 31.9 Building Services Piping Code.
5. Brace in-line equipment independently of ducts and pipes.
6. Cold formed angles to conform to the requirements of the latest "Specifications for the Design of Cold-Formed Steel Structural Members" (AISI) (FY = 33 KSI)
![Page 22: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/22.jpg)
General Requirements
7. Hot rolled shapes and plates to conform to ASTM A36. Pipes used as braces to conform to ASTM A120 or A53.
8. Cables to have minimum breaking strength. Per Table 3-2.
FS = 2.0FS = 5.0
![Page 23: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/23.jpg)
General Requirements9. Bolts to conform to ASTM A307.10. Expansion anchors per Table 3.3.
Proprietary connectors may be used where values are greater.
11. Welding to conform to AWS D1.1 using shielded or submerged ARC method.
12. Brace conduit same as equivalent weight of pipe.
![Page 24: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/24.jpg)
General Requirements
13. Do not mix solid and cable bracing. 14. Bracing for equipment NOT included.15. All runs will have a minimum of two
transverse and one longitudinal braces. 16. A run is defined as any change in
direction except as allowed by offsets.
![Page 25: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/25.jpg)
Bracing of Ducts1. Brace all ducts with a cross sectional area
of 6 square feet or larger. Brace flat oval ducts the same as rectangular ducts.
2. Exception - Hangars 12" in length or less as measured from the top of the duct to the supporting structure. Hangars must be positively attached to the duct within two inches of the top with a minimum of two No. 10 sheet metal screws.
![Page 26: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/26.jpg)
Bracing of Ducts
3. Transverse and longitudinal bracing per tables (Chapters 5, 6 and 7).
4. Ducts may be grouped. Select bracing requirements based on combined weight. Minimum of two sides to be attached to horizontal or vertical angles.
![Page 27: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/27.jpg)
Bracing of Ducts
5. Wall penetrations may replace transverse brace. Solid blocking required.
![Page 28: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/28.jpg)
Bracing of Pipes - Conduit
1. Brace fuel oil, gas (such as, fuel gas) medical gas and compressed air as per local codes.
2. Brace piping in boiler, mechanical equipment and refrigeration mechanical rooms 1 ¼" inch or larger.
![Page 29: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/29.jpg)
Bracing of Pipes - Conduit3. Brace all pipes 2 ½ inch nominal diameter or
larger.4. Exception - Pipes suspended from individual
hangers 12" or less as measured from the top of the pipe to the supporting structure. For pipes on a trapeze, the 12" exception is measured from the upper face of the horizontal trapeze member or the bottom of the pipe.
![Page 30: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/30.jpg)
Bracing of Pipes - Conduit
5. Transverse and longitudinal bracing as per tables (Chapters 5, 6 and 7).
6. Provide joints/connections capable of accommodating seismic displacements where pipes pass through building seismic or expansion joints or where pipes connect to equipment with vibration isolators.
![Page 31: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/31.jpg)
Bracing of Pipes - Conduit
7. Branch lines may not be used to brace main lines.
![Page 32: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/32.jpg)
Vertical risers not specifically
engineered will be laterally
supported with a riser clamp at each
floor.
![Page 33: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/33.jpg)
DEFINITIONS
TRANSVERSE BRACE - those designed and installed to restrain movement in the direction perpendicular to the piping or duct run
![Page 34: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/34.jpg)
DEFINITIONS
LONGITUDINAL BRACE - those designed and installed to restrain movement in the direction parallel to the piping or duct run
RUN (Piping or Duct) - a straight length with no changes in direction except as allowed by offsets
![Page 35: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/35.jpg)
Elements of a Seismic Restraint
Brace
Attachment to the Component
Attachment to the Structure
![Page 36: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/36.jpg)
Bracing Members
RIGIDAnglesPipesStrut Channels
NON-RIGIDCables
![Page 37: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/37.jpg)
Connection to the Element
Ducts
Pipes
![Page 38: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/38.jpg)
FIGURE 4-2 SIDE BRACING FOR RECTANGULAR DUCTS
![Page 39: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/39.jpg)
FIGURE 4-3 SIDE BRACING FOR RECTANGULAR DUCTS
![Page 40: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/40.jpg)
FIGURE 4-4 CABLE SIDE BRACING FOR RECTANGULAR DUCTS
![Page 41: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/41.jpg)
FIGURE 4-5 SIDE BRACING FOR RECTANGULAR DUCTS
![Page 42: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/42.jpg)
FIGURE 4-6 CENTER BRACING FOR RECTANGULAR DUCTS
![Page 43: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/43.jpg)
FIGURE 4-7 CABLE CENTER BRACING FOR RECTANGULAR DUCTS
![Page 44: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/44.jpg)
FIGURE 4-8 FLOOR SUPPORTED DUCT
![Page 45: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/45.jpg)
FIGURE 4-9 SINGLE HANGER SPACING FOR ROUND DUCTS33-36 INCHES (838-900 MM)
![Page 46: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/46.jpg)
FIGURE 4-10 SINGLE HANGER CABLE BRACING FOR ROUND DUCTS33-36 INCHES (838-900 MM)
![Page 47: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/47.jpg)
FIGURE 4-13 TRANSVERSE BRACING FOR PIPES
![Page 48: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/48.jpg)
FIGURE 4-14 STRUT BRACING FOR PIPES
![Page 49: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/49.jpg)
FIGURE 4-16 LONGITUDINAL BRACING FOR PIPES
![Page 50: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/50.jpg)
FIGURE 4-18 CABLE BRACING FOR PIPES
![Page 51: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/51.jpg)
FIGURE 4-20 STRUT BRACING FOR PIPE TRAPEZE
![Page 52: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/52.jpg)
FIGURE 4-21 CABLE BRACING FOR PIPE TRAPEZE
![Page 53: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/53.jpg)
FIGURE 4-22 FLOOR SUPPORTED PIPES
![Page 54: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/54.jpg)
Tables
![Page 55: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/55.jpg)
TABLE 5-1 SIDE BRACING FOR RECTANGULAR DUCTS, SHL A, L=2' 8" (MAX.)
![Page 56: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/56.jpg)
TABLE 5-2 SIDE BRACING FOR RECTANGULAR DUCTS WITH ROD HANGERS, SHL A
![Page 57: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/57.jpg)
TABLE 5-6 BRACING FOR ROUND DUCTS, SHL A
![Page 58: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/58.jpg)
TABLE 5-7 SCHEDULE FOR BRACING PIPES AND CONDUIT, SHL A
![Page 59: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/59.jpg)
TABLE 5-8 SCHEDULE FOR BRACING PIPES ON TRAPEZE, SHL A
![Page 60: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/60.jpg)
Connection to the Structure
![Page 61: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/61.jpg)
FIGURE 8-1 CONNECTIONS TO CONCRETE
![Page 62: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/62.jpg)
TABLE 8-1 SCHEDULE FOR TYPICAL CONNECTIONS TO STRUCTURAL SUPPORTING MEMBERS
![Page 63: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/63.jpg)
Miscellaneous Connections
![Page 64: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/64.jpg)
FIGURE 8-2 ADJUSTABLE CONNECTIONS TO CONCRETE
![Page 65: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/65.jpg)
FIGURE 8-4 ALTERNATE CONNECTIONS TO CONCRETE
![Page 66: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/66.jpg)
FIGURE 8-6 CONNECTIONS TO CONCRETE FILL ON STEEL DECK
![Page 67: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/67.jpg)
FIGURE 8-12 CONNECTIONS TO STEEL
![Page 68: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/68.jpg)
FIGURE 9-5 CABLE END CONNECTION
![Page 69: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/69.jpg)
FIGURE 9-10 RISER BRACING FOR HUBLESS PIPES
![Page 70: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/70.jpg)
FIGURE 9-17 WELDED TABS
![Page 71: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/71.jpg)
FIGURE 9-20 288-POUND (MAX.) VARIABLE AIR VOLUME TERMINAL
![Page 72: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/72.jpg)
SMACNA Guidelines/ConsultantSEISMIC SOURCES:
Contractor/ConsultantSEISMIC DESIGN (Mechanical):
10.0 Richter EarthquakeSEISMIC REQUIREMENTS:
3 MillionSEISMIC RESTRAINT COST:
30 Million (No Equipment)PIPING/SHEET METAL:
4350 Tons Cooling - Central PlantMECHANICAL:
Start 1989, (1992), Complete 1997TIME:
1 BillionCOST:
6 Buildings, 110 Acres, 100 Year Life, 945,000 SFSIZE:
Getty Center - Brentwood, CaliforniaPROJECT:
![Page 73: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/73.jpg)
![Page 74: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/74.jpg)
![Page 75: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/75.jpg)
![Page 76: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/76.jpg)
![Page 77: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/77.jpg)
![Page 78: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/78.jpg)
![Page 79: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/79.jpg)
![Page 80: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/80.jpg)
![Page 81: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/81.jpg)
![Page 82: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/82.jpg)
![Page 83: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/83.jpg)
![Page 84: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/84.jpg)
![Page 85: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/85.jpg)
![Page 86: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/86.jpg)
![Page 87: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/87.jpg)
![Page 88: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/88.jpg)
Other Resources
ASHRAE –
A Practical Guide to Seismic Restraint
![Page 89: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/89.jpg)
Other Resources
FEMA1. 2000 Provisions (FEMA 368)2. 2000 Commentary (FEMA 369)3. Installing Seismic Restraints For
Mechanical Equipment (FEMA 412)4. Installing Seismic Restraints For Duct &
Pipe (FEMA 414)
FEMA Distribution Center 1-800-480-2520
![Page 90: SMACNA Seismic Restraint Manual](https://reader034.vdocument.in/reader034/viewer/2022050619/563e0a115503464e708b495b/html5/thumbnails/90.jpg)