Eltech Industries has established themselves as a benchmark supplier of high quality, ‘balance-of-order’ photovoltaic products to Australia’s rapidly growing, environmentally friendly, solar energy industry. The SolarConnect brand offers a quality range of products, especially suited to withstand the harsh environments this country has to offer. At very competitive prices, SolarConnect’s product range forms cost effective solutions for all your photovoltaic installations, whilst still maintaining the highest quality & ease of workability. Covered by an Australia wide two year warranty against any manufacturing defects, these products will give the confidence and assurance needed for all your field installations regardless of the circumstances and will keep you coming back for more. SolarConnect’s range of connection systems are fully compatible with other existing brands and systems, the only difference you will notice is the price!

TRANSCRIPT

Page 1: SolarConnect - Solar Energy Connections

Suppliers of photovoltaic connection systems to Australia’s rapidly growing, environmentally friendly, solar energy industry.

2011/12 Trade Catalogue

Page 2: SolarConnect - Solar Energy Connections

© Copyright Eltech Industries - 2011

This publication is copyright. Other than for the purposes of and subject to the conditions prescribed under the copyright act, no part of it may in any form or by any means be reproduced, stored in a retrieval system or transmitted without prior written permission of Eltech Industries.

While every effort has been made to ensure the accuracy of the information herein, Eltech Industries accepts no liability for any loss or damage, either direct or consequential, arising out of, or in relation to, the use or application of the said information or products referred to herein.

All information, specifications and prices are subject to change without any prior notice. All prices quoted exclude GST and delivery.

Photographs and images are for illustrative purposes only and may vary from products depicted.

Information correct at time of publication.

Brand and product names are trademarks or registered trademarks of their respective holders.

The photovoltaic connectors and pre-assembled leads featured in this catalogue are compatible with MC3 & MC4 Photovoltaic Connectors.

Page 3: SolarConnect - Solar Energy Connections

Eltech Industries has established themselves as a benchmark supplier of high quality, ‘balance-of-order’ photovoltaic products to Australia’s rapidly growing, environmentally friendly, solar energy industry.

The SolarConnect brand offers a quality range of products, especially suited to withstand the harsh environments this country has to offer.

At very competitive prices, SolarConnect’s product range forms cost effective solutions for all your photovoltaic installations, whilst still maintaining the highest quality and ease of workability. Covered by an Australia wide two year warranty against any manufacturing defects, these products will give the confi dence and assurance needed for all your fi eld installations regardless of the circumstances and will keep you coming back for more.

SolarConnect’s range of connection systems are fully compatible with other existing brands and systems, the only difference you will notice is the price & our high level of service!

to SolarConnect, a leading brand name in the photovoltaic industry.

■ PV3 Connection Systems 4

■ PV4 Connection Systems 5

■ PV3 & PV4 Pre-assembled Connection Leads 6

■ DC Solar Cables 7

■ Flexible Nylon Conduits 9

■ Nylon Cable Glands 9

■ Galvanised Saddles 10

■ Solar Panel Bonding Lugs 10

■ Miniature Circuit Breakers AC & DC and Accessories 11-12

■ DC Weatherproof Isolators 12

■ ETI Fuse Holders 13

■ ETI Lightning & Surge Arrestors for Photovoltaic 13

■ Distribution Enclosures - Weatherproof & Non-weatherproof 15

■ Solar Safety Labels 15

■ Rennsteig Installation Tools & Tool Kits 18-19

Welcome

CO

NT

EN

TS

Page 4: SolarConnect - Solar Energy Connections

PV3 Connection Systems

Part No. Description Qty

CCM3-11 Male Connector 2.5-4.0mm2 - includes crimp pin 1

Part No. Description Qty

CCF3-11 Female Connector 2.5-4.0mm2 - includes crimp pin 1

Part No. Description Qty

BC3-FMM Branch Plug - PV3 1

Part No. Description Qty

BC3-MFF Branch Socket - PV3 1

Part No. Description Qty

CCM3-11-T1 Male Connector Pin 2.5-4.0mm2 - To suit female connector 1

FEATURESFEATURESFEATURES• UV Resistant• UV Resistant• UV Resistant• IP65 Rated• IP65 Rated• IP65 Rated• 1000V DC, 30 amp rating• 1000V DC, 30 amp rating• 1000V DC, 30 amp rating

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable Energy Initiatives

www.solarconnect.com.au4

0 42.5

0 42.5

0 42.5

0 42.5

0 42.5

0 42.5

0 42.5

55.5

13.5

28.5

55.5

13.5

28.5

0 42.5

55.5

13.5

28.5

55.5

13.5

28.5

Part No. Description Qty

CCF3-11-T1 Female Connector Pin 2.5-4.0mm2 - To suit male connector 1

Page 5: SolarConnect - Solar Energy Connections

PV4 Connection Systems

Part No. Description Qty

CCM4-12 Male Connector 4.0-6.0mm2 - includes crimp pin 1

Part No. Description Qty

CCF4-12 Female Connector 4.0-6.0mm2 - includes crimp pin 1

Part No. Description Qty

BC4-FMM Branch Plug - PV4 1

Part No. Description Qty

BC4-MFF Branch Socket - PV4 1

Part No. Description Qty

PV-STO1/M2 Male Connector Pin 4.0-6.0mm2 - To suit female connector 1

Part No. Description Qty

PV-STO1/F2 Female Connector Pin 4.0-6.0mm2 - To suit male connector 1

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable

Energy Initiatives

www.solarconnect.com.au5

FEATURESFEATURESFEATURES• UV Resistant• UV Resistant• UV Resistant• IP67 Rated• IP67 Rated• IP67 Rated• 1000V DC, 30 amp rating• 1000V DC, 30 amp rating• 1000V DC, 30 amp rating

Page 6: SolarConnect - Solar Energy Connections

Pre-assembled Connection Leads

Part No. Description Length Qty

PV4-CABASS/1M PV4 Male to Female Pre-assembled Lead 1 metre 1

PV4-CABASS/2M PV4 Male to Female Pre-assembled Lead 2 metre 1

PV4-CABASS/5M PV4 Male to Female Pre-assembled Lead 5 metre 1

PV4-CABASS/8M PV4 Male to Female Pre-assembled Lead 8 metre 1

PV4-CABASS/10M PV4 Male to Female Pre-assembled Lead 10 metre 1

PV4-CABASS/12M PV4 Male to Female Pre-assembled Lead 12 metre 1

Part No. Description Length Qty

PV-CABASS-MF4 PV3 Male to PV4 Female Adaptor Lead 300mm 1

Part No. Description Length Qty

PV-CABASS-FM4 PV3 Female to PV4 Male Adaptor Lead 300mm 1

Part No. Description Length Qty

PV3-CABASS/1M PV3 Male to Female Pre-assembled Lead 1 metre 1

PV3-CABASS/2M PV3 Male to Female Pre-assembled Lead 2 metre 1

PV3-CABASS/5M PV3 Male to Female Pre-assembled Lead 5 metre 1

PV3-CABASS/8M PV3 Male to Female Pre-assembled Lead 8 metre 1

PV3-CABASS/10M PV3 Male to Female Pre-assembled Lead 10 metre 1

PV3-CABASS/12M PV3 Male to Female Pre-assembled Lead 12 metre 1

FEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURES• UV Resistant - cables & connectors• UV Resistant - cables & connectors• UV Resistant - cables & connectors• IP67 Rated - connectors• IP67 Rated - connectors• IP67 Rated - connectors• 1000V DC, 30 amp rating• 1000V DC, 30 amp rating• 1000V DC, 30 amp rating

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable Energy Initiatives

www.solarconnect.com.au6

Page 7: SolarConnect - Solar Energy Connections

PV Solar Cables - UV ResistantFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURES• Manufactured from UV resistant NBR/NBR insulation• Manufactured from UV resistant NBR/NBR insulation• Manufactured from UV resistant NBR/NBR insulation sheath material sheath material sheath material• 1200V DC, 30 Amp Rating• 1200V DC, 30 Amp Rating• 1200V DC, 30 Amp Rating• 2 & 3 Core cables are designed to maintain double• 2 & 3 Core cables are designed to maintain double• 2 & 3 Core cables are designed to maintain double• 2 & 3 Core cables are designed to maintain double• 2 & 3 Core cables are designed to maintain double• 2 & 3 Core cables are designed to maintain double• 2 & 3 Core cables are designed to maintain double• 2 & 3 Core cables are designed to maintain double• 2 & 3 Core cables are designed to maintain double sheath insulation, even when cores are seperated sheath insulation, even when cores are seperated sheath insulation, even when cores are seperated• Fully marked and compliant with AS/NZS 5033 & • Fully marked and compliant with AS/NZS 5033 & • Fully marked and compliant with AS/NZS 5033 & TUV PV1-F TUV PV1-F TUV PV1-F• Highly fl exible• Highly fl exible• Highly fl exible• Available on 100M rolls• Available on 100M rolls• Available on 100M rolls

Part No. Description Length

SOL-SDI-UV4 SDI Solar Cable 4.0mm2 Mtr

SOL-SDI-UV6 SDI Solar Cable 6.0mm2 Mtr

Part No. Description Length

SOL-FIG8-SDI-UV4 Twin SDI Solar Cable 4.0mm2 - Red/Blk Inner Cores Mtr

SOL-FIG8-SDI-UV6 Twin SDI Solar Cable 6.0mm2 - Red/Blk Inner Cores Mtr

Part No. Description Length

SOL-TRIPLE-SDI-UV4 Triple Solar Cable 2 Core + Earth x 4.0mm2 Black Mtr

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable

Energy Initiatives

www.solarconnect.com.au7

Page 8: SolarConnect - Solar Energy Connections

FEATURES

• Fittings rated at IP66

• One piece fitting – ‘Fit & Forget’

• Manufactured from UV stabilized Nylon

• Available in both M20 & M25

• Comes in a ‘Contractor Kit’ which includes 10 metres of conduit, 10 conduit fittings & 10 locknuts to suit

The Ultimate Conduit Systemfor your PV Solar Installation

Call 1800 007 458

Page 9: SolarConnect - Solar Energy Connections

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable

Energy Initiatives

www.solarconnect.com.au9

Part No. Description Size Qty

PV-COND20 Nylon Conduit M20 M

PV-COND25 Nylon Conduit M25 M

PV-COND20 FIT Nylon Conduit Fitting + Locknut M20 EA

PV-COND25 FIT Nylon Conduit Fitting + Locknut M25 EA

Part No. Description Size Qty

PV-COND KIT 20 Nylon Conduit Contractors Kit 10M Conduit + 10 Fittings M20 EA

PV-COND KIT 25 Nylon Conduit Contractors Kit 10M Conduit + 10 Fittings M25 EA

Part No. Description Qty

CG 16 Nylon Cable Gland M16 50

CG 20 Nylon Cable Gland M20 40

CG 25 Nylon Cable Gland M25 20

CG 32 Nylon Cable Gland M32 15

Nylon Conduit Systems

Nylon Cable Glands - Metric

FEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURES• Manufactured from UV stabilized nylon • Manufactured from UV stabilized nylon • Manufactured from UV stabilized nylon • One piece fi tting - ‘Fit & Forget’• One piece fi tting - ‘Fit & Forget’• One piece fi tting - ‘Fit & Forget’• One piece fi tting - ‘Fit & Forget’• One piece fi tting - ‘Fit & Forget’• One piece fi tting - ‘Fit & Forget’• One piece fi tting - ‘Fit & Forget’• One piece fi tting - ‘Fit & Forget’• One piece fi tting - ‘Fit & Forget’• Fittings rated at IP66• Fittings rated at IP66• Fittings rated at IP66

FEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURES• UV Resistant• UV Resistant• UV Resistant• IP68 Rating• IP68 Rating• IP68 Rating• IP68 Rating• IP68 Rating• IP68 Rating• IP68 Rating• IP68 Rating• IP68 Rating

Nylon Conduit Systems - Contractors Kit

Page 10: SolarConnect - Solar Energy Connections

SBL-001SBW-001

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable Energy Initiatives

www.solarconnect.com.au10

Galvanised SaddlesFEATURESFEATURESFEATURESFEATURESFEATURESFEATURES• Zinc plated galvanised steel • Zinc plated galvanised steel • Zinc plated galvanised steel • 6.25mm fi xing hole• 6.25mm fi xing hole• 6.25mm fi xing hole• 6.25mm fi xing hole• 6.25mm fi xing hole• 6.25mm fi xing hole• 6.25mm fi xing hole• 6.25mm fi xing hole• 6.25mm fi xing hole

Part No. Description Qty

GSF20 Galvanised Saddle – Full 20mm 100

GSF25 Galvanised Saddle – Full 25mm 80

GSF32 Galvanised Saddle – Full 32mm 50

GSH16 Galvanised Saddle – Half 16mm 100

GSH20 Galvanised Saddle – Half 20mm 100

GSH25 Galvanised Saddle – Half 25mm 80

GSH32 Galvanised Saddle – Half 32mm 50

Solar Panel Bonding Lugs - Zinc Plated Galvanised Steel

Solar Panel Bonding Lugs - Stainless Steel/Aluminium

FEATURESFEATURESFEATURESFEATURESFEATURESFEATURES• Zinc plated galvanised steel • Zinc plated galvanised steel • Zinc plated galvanised steel • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic solar panels solar panels solar panels • Cable size range: 2.5 - 10.0mm• Cable size range: 2.5 - 10.0mm• Cable size range: 2.5 - 10.0mm222

FEATURESFEATURESFEATURES• Manufactured from stainless steel • Manufactured from stainless steel • Manufactured from stainless steel • Manufactured from stainless steel • Manufactured from stainless steel • Manufactured from stainless steel • Manufactured from stainless steel • Manufactured from stainless steel • Manufactured from stainless steel

& aluminium& aluminium& aluminium• Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic • Designed for earthing photovoltaic

solar panelssolar panelssolar panels• Cable size range 2.5-6.0mm• Cable size range 2.5-6.0mm• Cable size range 2.5-6.0mm222

Part No. Description Qty

SCBL2.5-10 Solar panel bonding lug suits 2.5mm2 - 10.0mm2 cable 1

Part No. Description Qty

SBW-001 Solar panel bonding washer 1

SBL-001 Solar panel bonding lug suits 2.5mm2 - 6.0mm2 cable 1

Page 11: SolarConnect - Solar Energy Connections

Part No. Description Amperage Qty

CB2P6KA10DC/500 Circuit Breaker 2 Pole DC 250-500V 10 1

CB2P6KA16DC/500 Circuit Breaker 2 Pole DC 250-500V 16 1

CB2P6KA20DC/500 Circuit Breaker 2 Pole DC 250-500V 20 1

CB2P6KA25DC/500 Circuit Breaker 2 Pole DC 250-500V 25 1

CB2P6KA32DC/500 Circuit Breaker 2 Pole DC 250-500V 32 1

CB2P6KA40DC/500 Circuit Breaker 2 Pole DC 250-500V 40 1

CB4P6KA10DC/1000 Circuit Breaker 4 Pole DC 250-1000V 10 1

CB4P6KA16DC/1000 Circuit Breaker 4 Pole DC 250-1000V 16 1

CB4P6KA20DC/1000 Circuit Breaker 4 Pole DC 250-1000V 20 1

*CB4P6KA25DC/1000 Circuit Breaker 4 Pole DC 250-1000V 25 1

CB4P6KA32DC/1000 Circuit Breaker 4 Pole DC 250-1000V 32 1

CB4P6KA40DC/1000 Circuit Breaker 4 Pole DC 250-1000V 40 1

Miniature Circuit Breakers DCFEATURESFEATURESFEATURES• DIN Mounting• DIN Mounting• DIN Mounting• 6kA DC 500 & 1000 volt rating• 6kA DC 500 & 1000 volt rating• 6kA DC 500 & 1000 volt rating• Compliant with IEC60898-2• Compliant with IEC60898-2• Compliant with IEC60898-2• Compliant with IEC60898-2• Compliant with IEC60898-2• Compliant with IEC60898-2• Certifi ed with SAA AS/NZ • Certifi ed with SAA AS/NZ • Certifi ed with SAA AS/NZ

approvalapprovalapproval

* Not currently in stock

CB1P6KA10AC CB4P6KA20DC/1000CB2P6KA10DC/500

Suits

4 Pole

Enclosures

Part No. Description Amperage Qty

CB1P6KA10AC Circuit Breaker 1 Pole AC 240-415V 10 1

CB1P6KA16AC Circuit Breaker 1 Pole AC 240-415V 16 1

CB1P6KA20AC Circuit Breaker 1 Pole AC 240-415V 20 1

CB1P6KA25AC Circuit Breaker 1 Pole AC 240-415V 25 1

CB1P6KA32AC Circuit Breaker 1 Pole AC 240-415V 32 1

Miniature Circuit Breakers AC

FEATURESFEATURESFEATURES• DIN Mounting • DIN Mounting • DIN Mounting • DIN Mounting • DIN Mounting • DIN Mounting • DIN Mounting • DIN Mounting • DIN Mounting • 6kA AC 240-415 Volt Rating • 6kA AC 240-415 Volt Rating • 6kA AC 240-415 Volt Rating • Compliant with IEC60898• Compliant with IEC60898• Compliant with IEC60898• Compliant with IEC60898• Compliant with IEC60898• Compliant with IEC60898• Compliant with IEC60898• Compliant with IEC60898• Compliant with IEC60898

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable

Energy Initiatives

www.solarconnect.com.au11

Page 12: SolarConnect - Solar Energy Connections

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable Energy Initiatives

www.solarconnect.com.au12

Part No. Description Qty

CBBL Copper Circuit Breaker Bridging Link 1

MCB-LBG 1 MCB Lock Dog - Plastic 1

IRPT DIN Mounting Isolation Plates 1

Part No. Description Amperage Qty

DC ISO 16 1000V DC Weatherproof Isolator - 1000V 4 Pole 16 1

DC ISO 25 1000V DC Weatherproof Isolator - 1000V 4 Pole 25 1

DC ISO 32 1000V DC Weatherproof Isolator - 1000V 4 Pole 32 1

Miniature Circuit Breaker Accessories

DC Weatherproof Isolators - 1000V 4 Pole

FEATURESFEATURESFEATURES••• ManufacturedManufacturedManufacturedManufacturedManufacturedManufacturedManufacturedManufacturedManufacturedManufacturedManufacturedManufacturedManufacturedManufacturedManufacturedManufacturedManufactured fromfromfromfromfromfromfromfromfrom UVUVUVUVUVUVUVUVUV stabilisedstabilisedstabilisedstabilisedstabilisedstabilisedstabilisedstabilisedstabilised

PolycarbonatePolycarbonatePolycarbonate materialmaterialmaterial••••••••• 44444444444 PolePolePolePolePolePolePolePolePole switchswitchswitchswitchswitchswitchswitchswitchswitch bodybodybodybodybodybodybodybodybody configurationconfigurationconfigurationconfigurationconfigurationconfigurationconfigurationconfigurationconfiguration•••IndividualIndividualIndividual polespolespoles ratedratedrated atatat 1000VDC1000VDC1000VDC••• IP66IP66IP66 RatedRatedRated••• ComesComesComes completecompletecomplete withwithwith 444 xxx M25M25M25 conduitconduitconduit

entryentryentry points points points ••• FullyFullyFullyFullyFullyFullyFullyFullyFullyFullyFully compliantcompliantcompliant withwithwith AS/NZSAS/NZSAS/NZS 503350335033 andandand

IECIECIEC 60947-360947-360947-3 requirementsrequirementsrequirements••• PadlockablePadlockablePadlockable rotaryrotaryrotary handlehandlehandle

CBBLMCB-LBG 1

CURRENTLY CURRENTLY CURRENTLY 32

CURRENTLY 32

CURRENTLY

UNAVAILABLEUNAVAILABLE

Page 13: SolarConnect - Solar Energy Connections

ETI Fuses & Fuse Holders - 1000V AC/DC

ETITEC C-PV Lightning & Surge Arrestors for Photovoltaic

Part No. Description Amperage Qty

002625105 Fuse Link AC/DC 1000V 10 1

002625106 Fuse Link AC/DC 1000V 12 1

002625107 Fuse Link AC/DC 1000V 16 1

002625108 Fuse Link AC/DC 1000V 20 1

002625109 Fuse Link AC/DC 900V 25* 1

002550201 DIN Mounting Fuse Holders - Pole 1 1000V 20 1

002550203 DIN Mounting Fuse Holders - Pole 2 1000V 20 1

002550301 DIN Mounting Fuse Holders - Pole 1 900V 25 1

002550303 DIN Mounting Fuse Holders - Pole 2 900V 25 1

Part No. Description Amperage Qty

002445206 Surge Protection Device 100V DC 20 1

002445207 Surge Protection Device 550V DC 20 1

002445208 Surge Protection Device 1000V DC 20 1

002445209 Surge Protection Device 100V DC - Remote Signalization 20 1

002445210 Surge Protection Device 550V DC - Remote Signalization 20 1

002445211 Surge Protection Device 1000V DC - Remote Signalization 20 1

~

+ L

N

PE

-

+PV

~

-

-

+ L

N

PE

-

+PV

2 X ETITEC C-PV 100V/550V

2 X ETITEC C-PV 1000V

ETITEC C-PV for photovoltaic system on a building without External Lightning Protection

ETITEC B-PV series of overvoltage surge protective devices has been developed to protect against direct and indirect lightning discharges and is intended to protect photovoltaic systems. The circuit topology consist of two varistor stages each protected by a thermal disconnection device

T connection ETITEC C-PV

V connection ETITEC C-PV

Note: If dis-tance between

string and inverter is less than 7m, then you need only one ETITEC

(B.C).

FEATURESFEATURESFEATURES• DIN mounting fuse holders • DIN mounting fuse holders • DIN mounting fuse holders • Fuse holders available in 1 & 2 pole• Fuse holders available in 1 & 2 pole• Fuse holders available in 1 & 2 pole• 1000V DC - 30kA DC• 1000V DC - 30kA DC• 1000V DC - 30kA DC

FEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURES• Designed to protect photovoltaic systems • Designed to protect photovoltaic systems • Designed to protect photovoltaic systems

against indirect dischargesagainst indirect dischargesagainst indirect discharges• Available with Remote Signalization contacts• Available with Remote Signalization contacts• Available with Remote Signalization contacts• Available in 100, 550, 1000 Volt DC• Available in 100, 550, 1000 Volt DC• Available in 100, 550, 1000 Volt DC• Available in 100, 550, 1000 Volt DC• Available in 100, 550, 1000 Volt DC• Available in 100, 550, 1000 Volt DC• Available in 100, 550, 1000 Volt DC• Available in 100, 550, 1000 Volt DC• Available in 100, 550, 1000 Volt DC

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable

Energy Initiatives

www.solarconnect.com.au13

Page 14: SolarConnect - Solar Energy Connections

Need to weatherproof your

Circuit Protection?

RCD/MCB Weatherproof Enclosures

• IP66 Rated• 2-4 & 4-8 Pole Confi gurations • Padlockable Front Cover

Toll Free 1800 007 458

www.solarconnect.com.au

Page 15: SolarConnect - Solar Energy Connections

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable

Energy Initiatives

www.solarconnect.com.au15

Distribution Enclosures

Weatherproof Distribution Enclosures - IP66

Engraved ABS Solar Safety Label Kits

Part No. Description Qty

ELT CB1N 1 Pole Distribution Enclosure 1

ELT CB2N 2 Pole Distribution Enclosure 1

Part No. Description Qty

ELT CB4N 2-4 Pole Weatherproof 1 Distribution Enclosure

ELT CB8N 4-8 Pole Weatherproof 1 Distribution Enclosure

Part No. Description Qty

SOL/LABELKIT-ENG Engraved ABS Solar Safety Label Kit 1

Part No. Description Qty

SOL/LABELKITV2-ENG Engraved ABS Solar Safety Label Kit Version 2 1

FEATURESFEATURESFEATURES• Suits DIN mounting circuit protection• Suits DIN mounting circuit protection• Suits DIN mounting circuit protection• Available in 1 & 2 Pole• Available in 1 & 2 Pole• Available in 1 & 2 Pole• Material: PVC• Material: PVC• Material: PVC

FEATURESFEATURESFEATURES• Suits DIN mounting circuit protection• Suits DIN mounting circuit protection• Suits DIN mounting circuit protection• Suits DIN mounting circuit protection• Suits DIN mounting circuit protection• Suits DIN mounting circuit protection• IP66 Rating• IP66 Rating• IP66 Rating• Material: PVC - UV Resistant• Material: PVC - UV Resistant• Material: PVC - UV Resistant• Material: PVC - UV Resistant• Material: PVC - UV Resistant• Material: PVC - UV Resistant• Material: PVC - UV Resistant• Material: PVC - UV Resistant• Material: PVC - UV Resistant• Padlockable• Padlockable• Padlockable

FEATURESFEATURESFEATURES• Complete label set covers one system installation• Complete label set covers one system installation• Complete label set covers one system installation• Complete label set covers one system installation• Complete label set covers one system installation• Complete label set covers one system installation• High quality engraved labels • High quality engraved labels • High quality engraved labels • Very strong adhesive backing • Very strong adhesive backing • Very strong adhesive backing • Very strong adhesive backing • Very strong adhesive backing • Very strong adhesive backing • Very strong adhesive backing • Very strong adhesive backing • Very strong adhesive backing • Comply with Australian Standards• Comply with Australian Standards• Comply with Australian Standards

SOLAR ARRAY DCISOLATOR

ACISOLATOR

NORMALSUPPLY

MAINSWITCH

SOLARSUPPLY

MAINSWITCH

SOLAR ARRAY DCISOLATOR

SHUTDOWN PROCEDURE

1. TURN OFF THE INVERTER A.C. MAIN ISOLATOR

2. TURN OFF THE PV ARRAY ISOLATOR LOCATED NEXT TO THE INPUT TERMINALS OF THE INVERTER

3. “WARNING” DO NOT OPEN PLUG AND SOCKET CONNECTORS OR PV STRING ISOLATOR UNDER LOAD.

WARNINGTHIS PREMISE CONTAINSAN ELECTRICITY GENERATION SYSTEMTHE SOLAR ISOLATION SWITCHIS LOCATED

SOLAR ARRAY LOCATED

OPEN CIRCUIT VOLTAGE VDC

SHORT CIRCUIT CURRENT DC AMPS

WARNING

WARNING

DUAL SUPPLYISOLATE BOTH NORMAL AND SOLAR

SUPPLIES BEFORE WORKING ONTHIS EQUIPMENT

DUAL SUPPLYISOLATE BOTH NORMAL AND SOLAR

SUPPLIES BEFORE WORKING ONTHIS EQUIPMENT

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

Page 16: SolarConnect - Solar Energy Connections

Try our NEW engraved

PVC labels!

• Complete label set covers one system installation

• Very strong adhesive backing

• Compliant Australia wide

• UV Resistant engraved ABS

SHUTDOWN PROCEDURE

1. TURN OFF THE INVERTER A.C. MAIN ISOLATOR

2. TURN OFF THE PV ARRAY ISOLATOR LOCATED NEXT TO THE INPUT TERMINALS OF THE INVERTER

3. “WARNING” DO NOT OPEN PLUG AND SOCKET CONNECTORS OR PV STRING ISOLATOR UNDER LOAD.

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

copies

WARNINGDUAL SUPPLY

ISOLATE BOTH NORMAL AND SOLARSUPPLIES BEFORE WORKING ON

THIS EQUIPMENT

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

SOLAR ARRAY DCISOLATOR

WARNINGTHIS PREMISE CONTAINSAN ELECTRICITY GENERATION SYSTEMTHE SOLAR ISOLATION SWITCHIS LOCATED

Call 1800 007 458for more information

Need warning labels

for your solar install?

MAIN SWITCH(INVERTER SUPPLY)

MAIN SWITCH(GRID SUPPLY)

SOLAR ARRAY ON ROOFHAZARDOUS D.C. VOLTAGE

PV ARRAYD.C. ISOLATOR

Locate next to the meter box (if one exists) and the building’s main switchboard and fire panel.

[AS/NZS 5033 clause 6.4]

Labels for domestic switchboards canbe handwritten3000 7.3.8.2

AS4777.1 5.5.2 (B) also 5.3.3AS/NZS 5033 6.3.2

a) Turn off the MAIN SWITCH (Inverter Supply)

b) Turn off the inverter isolation device located near the inverter

c) Turn off the PV D.C. Isolator located next to the input terminals of the inverter

ISOLATE BOTH NORMAL AND

Multiple SUPPLIES

ISOLATE INVERTER SUPPLY AT DISTRIBUTION BOARD

………………….

HAZARDOUS D.C. VOLTAGE

INVERTER LOCATION

…………………...

Attach to d.c. isolator adjacent to inverter.

UPS CONNECTED FOLLOW SHUTDOWN

PROCEDURE

Normal supply label located next to main switch on main switchboard AS4777.1 clause 5.5.2 (b)

Inverter supply label located on main switchboard – AS4777.1 Clause 5.5.2(b)

Locate on main switchboard. Some utilities require additional copies of this sign to be located at the point of attachment (FOLCB) and meter panel. [AS4777.1 Clause 5.5.2(a)]

If the inverter system is connected to a distribution board then the following sign is located on main switchboard and on all intermediate distribution boards. [AS4777.1 Clause 5.5.2(a)]

All LV DC wiring and marshalling boxes need to be labeled with “Warning d.c.” [AS/NZS 5033 3.5 and 6.2]

Where a UPS system is installed, warning label mustbe located on main switchboard. [AS4777.1 Clause5.6.5]

Locate on main switchboard (assumes inverter is not immediately adjacentto switchboard) [AS4777.1 Clause 5.5.1]

SHUTDOWN PROCEDURE

EXAMPLE of…Need to define where and call it up in 5033 and or 4777.1

Multiple SUPPLIES ISOLATE ALL SUPPLIES

BEFORE WORKING ON THIS SWITCHBOARD

Page 17: SolarConnect - Solar Energy Connections

PHOTOVOLTAICSOLAR SYSTEMINSTALLATION TOOLS

CUTTINGSTRIPPINGCRIMPING

NEW! RENNSTEIG

Call 1800 007 458

for more information

Made in Germany

Page 18: SolarConnect - Solar Energy Connections

Rennsteig PV Installation Tool Kit - Basic

Rennsteig PV Installation Tool Kit - MC3/4 Advanced

Part No. Description Qty

624 105-07 PV Installation Tool Kit 1

Part No. Description Qty

624 105-11 PV Installation Tool Kit - MC3/MC4 Advanced 1

FEATURESFEATURESFEATURES• Includes cutting, stripping & crimping tools• Includes cutting, stripping & crimping tools• Includes cutting, stripping & crimping tools• Suitable for MC3 & MC4 style connectors• Suitable for MC3 & MC4 style connectors• Suitable for MC3 & MC4 style connectors• Suitable for Huber Suhner style connectors• Suitable for Huber Suhner style connectors• Suitable for Huber Suhner style connectors

FEATURESFEATURESFEATURES• Includes cutting, stripping & crimping tools• Includes cutting, stripping & crimping tools• Includes cutting, stripping & crimping tools• Suitable for MC3 & MC4 style connectors• Suitable for MC3 & MC4 style connectors• Suitable for MC3 & MC4 style connectors• Includes MC3 & MC4 lead assembly tools• Includes MC3 & MC4 lead assembly tools• Includes MC3 & MC4 lead assembly tools

Made in Germany

Made in Germany

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable Energy Initiatives

www.solarconnect.com.au18

Page 19: SolarConnect - Solar Energy Connections

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable

Energy Initiatives

www.solarconnect.com.au19

Rennsteig PV Installation Tools - Individually

Part No. Description Qty

607 226 3 Insulation Stripper to suit 1 1.5-6.0mm2 Solar Cable

Part No. Description Qty

600 015 36 Cable Cutters to suit 1 50mm2 (15mm O.D.) Cables

Part No. Description Qty

725 000 MC3 Style Assembly Tool 1

Part No. Description Qty

690 001 MC4 Style Assembly Tool 1 x set

Part No. Description Qty

624 188 3 Crimping Tool - With Huber 1 & Suhner Dies 2.5-4.0mm2

624 194 3 1 Crimping Tool - With MC3 1 Dies 2.5-6.0mm2

624 570 3 1 Crimping Tool - With MC4 1 Dies 2.5-6.0mm2

PV-CC Crimping Tool MC4 - Budget 1

FEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURESFEATURES• High quality German made precision tooling• High quality German made precision tooling• High quality German made precision tooling• Designed specifi cally for PV solar installers • Designed specifi cally for PV solar installers • Designed specifi cally for PV solar installers • Designed to handle a wide range of different PV • Designed to handle a wide range of different PV • Designed to handle a wide range of different PV

connectors & cablesconnectors & cablesconnectors & cablesconnectors & cablesconnectors & cablesconnectors & cablesconnectors & cablesconnectors & cablesconnectors & cablesMade in Germany

Page 20: SolarConnect - Solar Energy Connections

• FREE CALL 1800 007 458 • FAX 1300 885 122Supporting Renewable Energy Initiatives

www.solarconnect.com.au

E-MC3 Connection System

Part No. Description Qty Price $

CCM3-11 Male Connector 2.5-4.0mm2 - includes crimp pin 1 $3.90

Part No. Description Qty Price $

CCF3-11 Female Connector 2.5-4.0mm2 - includes crimp pin 1 $3.90

Part No. Description Qty Price $

BC3-FMM Branch Plug - MC3 Style 1 $12.55

Part No. Description Qty Price $

BC3-MFF Branch Socket - MC3 Style 1 $13.35

Part No. Description Qty Price $

CCM3-11-T1 Male Connector Pin 2.5-4.0mm2 - Spare 1 $1.95

Part No. Description Qty Price $

CCM3-11-T1 Male Connector Pin 2.5-4.0mm2 - Spare 1 $1.95

Features• UV Resistant • IP65 Rated• 1000V DC, 30 Amp RatingDistributed by

Eltech Industries 8 Industry Court (P.O.Box 84)Lilydale, VIC, 3140, Australia