Edition: May 1998 Addendum to T 963 EN EB 963 EN Mounting and Operating Instructions Solenoid Valves Type 3963 Fig. 1 General Assembly, commissioning and oper- ation of these devices may only be performed by experienced person- nel. Proper shipping and appropriate storage are assumed. The air supply may not exceed the maximum permissible pressure and, if necessary, it must be limited by a pressure reducer. The devices can be mounted in any desired position. The filter in the enclosure cover and the cable gland Pg 13.5 must be installed hanging downwards, or if this is not possible, horizontally. On mounting, it is important that a clearance of 300 mm above the enclosure cover is kept. If the device is mounted to a rotary actuator or linear actuator with positioner, it is necessary to change over the air supply to an external supply at connection 9 (see page 7 ff.). The minimum permissible ambient temperature is 25 °C (for Type 3963- .... 0/- .... 2 and 3756-1203/-6203) and 40 °C (for Type 3963- .... 1/- .... 3 and 3756-1213/-6213/ -3…/-8…). The maximum permissible ambient temperature of 80 °C is lowered for intrinsically safe devices in accordance with the Certificate of Conformity PTB No. Ex-90.C.2100 (see page 10). Technical data, ordering data, spare parts and accessories see Data Sheet T 963 EN. Contents General Page 1 Mounting Page 2 Air connection Page 6 Electrical connection Page 9 Certificate of Conformity Page10 PTB No. Ex-90.C.2100 (Extract) Installation directions for devices Page12 for use in hazardous locations in compliance with CSA approval Installation directions for devices Page13 for use in hazardous locations in compliance with FM approval

Upload: others

Post on 20-Jan-2022

13 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Solenoid Valves Type 3963 - Samson AG

Edition: May 1998 Addendum to T 963 EN EB 963 EN

Mounting and Operating Instructions

Solenoid Valves Type 3963

Fig. 1

General

Assembly, commissioning and oper-ation of these devices may only beperformed by experienced person-

nel. Proper shipping and appropriate storageare assumed.The air supply may not exceed the maximumpermissible pressure and, if necessary, it mustbe limited by a pressure reducer.

The devices can be mounted in any desiredposition. The filter in the enclosure cover andthe cable gland Pg 13.5 must be installedhanging downwards, or if this is not possible,horizontally.On mounting, it is important that a clearanceof ≥ 300 mm above the enclosure cover is kept.If the device is mounted to a rotary actuator orlinear actuator with positioner, it is necessaryto change over the air supply to an externalsupply at connection 9 (see page 7 ff.).The minimum permissible ambient temperatureis 25 °C (for Type 3963-....0/-....2 and3756-1203/-6203) and 40 °C (for Type3963-....1/-....3 and 3756-1213/-6213/-3…/-8…).

The maximum permissible ambient temperatureof 80 °C is lowered for intrinsically safedevices in accordance with the Certificate ofConformity PTB No. Ex-90.C.2100 (seepage 10).Technical data, ordering data, spare parts andaccessories see Data Sheet T 963 EN.

Contents

General Page 1Mounting Page 2Air connection Page 6Electrical connection Page 9Certificate of Conformity Page 10PTB No. Ex-90.C.2100 (Extract)Installation directions for devices Page 12for use in hazardous locations incompliance with CSA approvalInstallation directions for devices Page 13for use in hazardous locations incompliance with FM approval

Page 2: Solenoid Valves Type 3963 - Samson AG

EB 963 EN – 2 –

Mounting

Mounting rails

Type 3963-..14/-..27/-..28/-..54/-..64These devices can be attached with two mount-ing bases for G-profile 32 according toEN 50 035 or top hat rail 35 according toEN 50 022 (Fig. 2).

Wall mounting

Type 3963-..14/-..27/-..28/-..54/-..64These devices can be attached to a wall mount-ing plate (Fig. 2).

Type 3963-..25, combined withType 3756-1203/-6203/-1213/-6213

Type 3963-..76, combined withType 3756-3205/-8205/-3206/-8206/

-3325/-8325/-3335/-8335/-3345/-8345/-3355/-8355

These devices can be attached with screwsthrough bore holes (Fig. 3).

Fig. 2 · Dimensions in mm

Wall mounting plate(Order No. 1400-6726)

Mounting base for G-profile 32(Order No. 1400-5930)

Mounting base for top hat rail 35(Order No. 1400-5931)

Fig. 3 · Dimensions in mm

Type 3963-..25, combined withType 3756-1203/-6203/-1213/-6213

Type 3963-..76, combined withType 3756-3205/-8205/-3206/-8206/

-3325/-8325/-3335/-8335/-3345/-8345/-3355/-8355

M 3 x 8 DIN 84

38

63

M 3 x 8 DIN 84

38

63

M 3 x 8 DIN 912

38 ø6

25

63

82

94

63 29

1

89

7

21 2132 52

61

3052

3 45

29 63

1

69

4.35

41

32

22

3250.8

29 63

4.3

3250.8

22

2

44

5

13

4

2

Page 3: Solenoid Valves Type 3963 - Samson AG

Mounting to rotary actuators with NAMURinterface according to VDI/VDE 3845

Type 3963-..11/-..12/-..21/-..22/-..23/-..52/-..62

Type 3963-..76, combined withType 3756-3207/-8207/-3208/-8208/

-3327/-3827/-3337/-3837/-3347/-3847/-3357/-3857

These devices can be directly attached to rotaryactuators with NAMUR interface (Fig. 4).Before mounting, check that the two O ringsare positioned correctly. The operation direc-tion is determined by a threaded coding pinM 5 10 DIN 916 on the mounting flange ofthe rotary actuator. The device is attached withtwo screws M 5 35 DIN 912. The mounting ac-cessories are delivered together with the device.

Mounting to restrictor blockfor rotary actuators with NAMUR interfaceaccording to VDI/VDE 3845

Type 3963-..76, combined withType 3756-3207/-8207/-3208/-8208

These devices can be attached to a restrictorblock for rotary actuators with NAMUR inter-face (Fig. 5). The restricting function can beidentified from the symbol indicated on thedevice. Different closing and opening times canbe adjusted in a ratio of 1:15 by turning therestricting screws to the left or to the rightrespectively with a screw driver.

24

32

12

8 M 5

G 1/4

2

Threaded coding pin

NAMUR interfaceaccording to VDI/VDE 3845

Fig. 4 · Dimensions in mm

– 3 – EB 963 EN

Fig. 5 · Dimensions in mm

Mounting to restrictor blockfor single-acting rotary actuators(Order No. 1400-6763)

Mounting to restrictor blockfor double-acting rotary actuators(Order No. 1400-6764)

29 63

55 25.4

5

1

3

4

2

96

75

122

47

9

5

1

29 63

55 25.4

5

1

3

4

2

72

40

122

47

9

5

1

Page 4: Solenoid Valves Type 3963 - Samson AG

EB 963 EN – 4 –

Mounting with adapter plateto linear actuators with NAMUR ribaccording to DIN IEC 534

Type 3963-..11/-..12/-..21/-..22/-..23/-..52/-..62

Type 3963-..76, combined withType 3756-3207/-3208

These devices can be mounted with an adapterplate (Fig. 6) to linear actuators with NAMURrib. When positioners or limit switches withlong lever are to be mounted on linear actu-ators ≤ DN 50 at the same time a bracket(Order No. 0320-1416) is required.

Mounting with screwed pipe connection ofCrNiMo to linear actuators

Type 3963-..27/-..28/-..54 Type 3963-..25, combined with

Type 3756-1203/-1213 Type 3963-..76, combined with

Type 3756-3205/-3206These devices can be mounted with a screwedpipe connection to linear actuators, e. g.SAMSON Type 271 or 3277 (Fig. 7).Mounting instructions for SAMSON devices seeMounting and Operating InstructionsEB 8310 EN and EB 8311 EN.

Fig. 7 · Dimensions in mm

6015 30

G1/2

1.3 2.3

92

10

30

25 12 1225

3214M 51.3

2.3

ø8M 8 x 35 DIN 912

Adapter plateNAMUR rib/NAMUR interface(Order No. 1400-6751)

Fig. 6 · Dimensions in mm

Actuator size Connection A Order No.80/240 cm2 G 1/4 / 1/4 64 1400-6759350/700 cm2 G 3/8 / 1/4 75 1400-6761

G 3/8 / 1/2 64 1400-6735

Actuator size Connection Order No.1400 cm2 G 3/4 / 1/2 1400-67362100 cm2 G 1 / 1/2 1400-67372800 cm2

A

97

45

Mounting with screwed pipe connection of CrNiMo to linear actuators

Page 5: Solenoid Valves Type 3963 - Samson AG

– 5 – EB 963 EN

A B

Type 3963-..29/-..55 Connection block foractuator "stem extends"(Order No. 1400-6943/-6944),actuator "stem retracts"(Order No. 1400-6945/-6946),with piping kit(Order No. 1400-6444/-6445/-6446/-6447)A-B

Mounting flange

*Clearance for mounting of enclosure cover≥

390*

190

9029

Mounting to connection block for Linear Actuator SAMSON Type 3277

Fig. 8 · Dimensions in mm

Mounting to connection blockfor Linear Actuator SAMSON Type 3277

Type 3963-..29/-..55These devices can be mounted to connectionblock for Linear Actuator SAMSON Type 3277with Positioner SAMSON Type 3766, 3767 or3780 (Fig. 8). Before mounting, check that thefour O-rings are positioned correctly on themounting flange. The device is attached withtwo screws M 5 60 DIN 912. The mountingaccessories are delivered together with the de-vice. Mounting instructions for SAMSON de-vices see Mounting and Operating InstructionsEB 8311 EN, EB 8355 EN and EB 8380 EN.

Mounting to linear actuators with NAMUR ribaccording to DIN IEC 534

Type 3963-..53These device can be directly mounted to a lin-ear actuator with NAMUR rib. The device isattached with one screw M 8 45 DIN 912which is delivered with the device.

Page 6: Solenoid Valves Type 3963 - Samson AG

EB 963 EN – 6 –

Air connection

The air supply pipes and screwjoints may only be laid and as-sembled by experienced personnel.

They must be regularly checked for leaks anddamage, and if necessary, repaired. Beforestarting any repair work, all supply pipeswhich are to be opened must be depress-urized.

The air connections are G (NPT) 1/4 orG (NPT) 1/2 tapped holes depending on theversion.Note: The Kvs value of a pressure reducerconnected upstream must be at least 1.6 timeslarger than the Kvs value of the device.

Supply pipe

Note: For supply pipes length ≥ 2 m largernominal sizes must be provided.

Type 3963-..25, combined withType 3756-1203/-6203/-1213/-6213

With the above listed devices, it is possible tocheck whether the nominal size of the supplypipe is sufficient as follows:1. Unscrew the screw plug covering con-

nection 9 and connect a pressure gauge.2. The nominal size of the supply pipe proves

to be sufficient when there is a pressure of≥ 1.3 bar during the switching process.

Nominal size (Supply pipe length ≤ 2 m)Press- Kvs valueure 0.16 1.4 4.3 –

0.32Connection

(bar) 4 1 and 3 4 9≥ 1.4 ≥ DN 6 ≥ DN 8 ≥ DN 10 ≥ DN 4≥ 2.5 ≥ DN 4 ≥ DN 6 ≥ DN 8≥ 6 ≥ DN 4 ≥ DN 6

Working medium

Instrument air 1.4 … 6 bar for internal airsupply (as-delivered condition).

Instrument air, oil-containing air or non-aggressive gases of 0 … 6 bar (10 bar withType 3756) for external air supply across con-nection 9 (see page 7 ff.).

Exhaust air restrictors

Type 3963-..12/-..22/-..23/-..28/-..29These devices have one or two exhaust air re-strictors. The restricting function can be ident-ified from the symbol indicated on the device.Different closing and opening times can be ad-justed in a ratio of 1:15 by turning restrictingscrews to the right or to the left respectivelywith a screw driver. The restricting screws canbe found underneath the enclosure cover or atthe adapter plate (Fig. 9).

1.3

2.3

+_

Manual operation(optionally)

Setting of the exhaust air restrictors

Fig. 9

Air supply instrument air 1.4 … 6 barAmbient Particle Dew Oilytemperature size point residues(°C) (µm) (°C) (mg/m3)15 … 35 ≤ 5 10 ≤ 0.115 2032 4060 70

4

1.3

Type 3963-..12/-..22/-..28/-..29

Type 3963-..23

Page 7: Solenoid Valves Type 3963 - Samson AG

– 7 – EB 963 EN

Conversion to external air supplyacross connection 9

Type 3963-..25, combined withType 3756-1203/-6203/-1213/-6213

To these devices air supply in the as-deliveredcondition is to be connected internal viaconnection 4. Conversion to external air supplyvia connection 9 is effected as follows:1. Remove pilot valve enclosure cover after re-

moval of four filister head screws.2. Remove pilot valve from booster valve after

removal of three hexagon socket headscrews.

3. Remove plate with flat gasket [1] after re-moval of a filister head screw (Fig. 10).

4. Turn flat gasket [1] by 90°. After assembly,the tab of the gasket [1] is not visible fromthe outside.

5. Conversion to external air supply isdetermined only by turning the flat gasket[1]. Prior to assembly, install flat gasket [3]between pilot valve and booster valve asfollows (Fig. 12):Type 3963 with index -01, -02, -04 and -06The white mark in the slots of the flatgasket [3] is not visible.Type 3963 with index -03, -05 and -10The tab of the flat gasket [3] is placed incutout “Int“ of the enclosure.

Type 3963-..76, combined withType 3756-3205/-8205/-3206/-8206/

-3207/-8207/-3208/-8208/-3325/-8325/-3327/-8327/-3335/-8335/-3337/-8337/-3345/-8345/-3347/-8347/-3355/-8355/-3357/-8357

To these devices air supply in the as-deliveredcondition is to be connected internal viaconnection 1 or 3. Conversion to external airsupply via connection 9 is effected as follows:1. Remove plate with flat gasket [2] from the

connecting plate after removal of a filisterhead screw.

2. Turn flat gasket [2] by 180°. The tab of flatgasket [2] is then placed in cutout “9“ ofthe connecting plate (Fig. 11).

Note: In the case of bilaterally actuatedbooster valves, both pilot valves must beconverted.

Installation of flat gasket [1]

Fig. 10

Fig. 11

Installation of flat gasket [2]

[1]

[2]

Page 8: Solenoid Valves Type 3963 - Samson AG

EB 963 EN – 8 –

Type 3963-..14/-..52/-..53/-..54To these devices air supply in the as-deliveredcondition is to be connected internal viaconnection 4. Conversion to external air supplyvia connection 9 is effected as follows:1. Remove enclosure cover after removal of

four filister head screws.2. Remove solenoid valve from adapter plate

after removal of three hexagon socket headscrews.Type 3963 with index -01, -02, -04 and -06

3. Turn flat gasket [3] by 180°. The whitemark is then visible in the slots (Fig. 12).Type 3963 with index -03, -05 and -10Turn flat gasket [3] by 180°. The tab of theflat gasket [3] is then placed in cutout “9“of the enclosure (Fig. 12).

Type 3963-..11/-..12/-..21/-..22/-..27/-..28/-..29/-..55/-..62

To these devices the air supply cannot bechanged. The flat gasket [3], if provided, mustbe installed in accordance with the as-delivered condition (Fig. 12).

Exhaust air return

Type 3963-..76, combined withType 3756-3206/-8206

To these devices, in the as-delivered conditionconnection 4 is closed with a threaded plug. Ifthe exhaust air return is used for spring-loadedactuators, the threaded plug must be removedand connection 4 must be connected to thespring chamber of the actuator by a hose withnominal size DN 4 to 10 (depending on theactuator size).

Fig. 12

Installation of flat gasket [3]

[3] [3]

[3]

Int

[3]

9

Internal air supplyvia connection 4(as-delivered condition)

External air supplyvia connection 9

Internal air supplyvia connection 4(as-delivered condition)

External air supplyvia connection 9

Type 3963 with index -03, -05 and -10

Type 3963 with index -01, -02, -04 and -06

Page 9: Solenoid Valves Type 3963 - Samson AG

– 9 – EB 963 EN

Electrical connection

As far as the electrical installationof the device is concerned, the rel-evant VDE regulations and the acci-

dent prevention regulations of the employers´liability insurance association must be ob-served.For installation in hazardous areas, therespective national regulations of the countryin which the device is to be used must beobserved. In Germany this is VDE 0165.When connected to DC voltage signals, cor-rect polarity must be ensured.For connection of intrinsically safe circuits, the Certificate of Conformity PTB No.Ex-90.C.2100 applies (see page 10).The coated screws in the enclosure may not betampered with.

The power supply is connected, depending onversion, either through a cable gland Pg 13.5to the terminals in the enclosure, with a Hartingconnector, a socket in accordance to DIN43 650 or a cable socket M 12 1 (Fig. 13).

Cable

It is recommended that connecting cables witha conductor cross-section of ≥ 0.5 mm2 areused. Connecting cables with an external diameter of 6 … 12 mm are suitable for thecable gland Pg 13.5.

Degree of protection

The devices can be changed from degree ofprotection IP 54 (Order No. 8504-0066) todegree of protection IP 65 (Order No. 1099-1103) by exchanging the filter in the enclosurecover.

Manual operation

The devices have a manual operation as analternative to allow the device to be manuallyoperated when a nominal signal is not available:– Switch outside of the enclosure– Push button outside of the enclosure– Switch in the enclosure cover– Pushbutton underneath enclosure cover

(see page 6, fig. 9)Note: For safety circuits, only devices withoutmanual operation should be used.

81 82

+ _

+_

blue

bro

wn

2 13

_ +

blue

bro

wn

2 1

3 4

_ +

blue

bro

wn

3 4

5678

2

Fig. 13

Terminals in the enclosure

Cable socket M 12 1

Socket in accordance to DIN 43 650

Connection diagrams

Harting connector

Page 10: Solenoid Valves Type 3963 - Samson AG

EB 963 EN – 10 –

Certificate of Conformity PTB No. Ex-90.C.2100 (Extract)

for the electric apparatus Solenoid Valve Type 3963-1... index -02 and -03

Class EEx ia IIC T6

dated 06.09.19901. Addendum dated 28.06.19912. Addendum dated 11.04.19943. Addendum dated 10.10.1995

The following table shows the maximum permissible ambient temperature within the temperatureclasses:

Note: Minimum permissible ambient temperature 45 °C. This is limited to 25 °C (for Type 3963-1...0/-1…2) and 40 °C (for Type 3963-1...1/-1…3) due to the materials used.

To connect to a certified intrinsically safe electric circuit, refer to the maximum permissible valuesfor voltage U0, current Ik and power P in the following table:

*) No power limit

Note: Internal capacitance and internal inductance are negligible.

Nominal signal Type Permissible maximum ambient temperatureT 6 T 5 T 4

6 V 3963-11 60 °C 70 °C 80 °C12 V 3963-1224 V 3963-1322 mA 3963-14

7.5 V 3963-17 65 °C 80 °C

Type 3963-11 3963-12 3963-13 3963-14 3963-17U0 (V) 13 27 25 28 32 32 28 8 15 28 32Ik (mA) 150 125 150 115 70 90 115 150 200 115 90P (mW) *) 400 *) 400 *) 250 *) *) 400 *) 350

Page 11: Solenoid Valves Type 3963 - Samson AG

– 11 – EB 963 EN

Certificate of Conformity PTB No. Ex-90.C.2100 (Extract)

for the electric apparatus Solenoid Valve Type 3963-1... index -04 and up

Class EEx ia IIC

4. Addendum dated 11.07.1997

The following table shows the maximum permissible ambient temperature within the temperatureclasses:

*) Limited to 25 °C (for Type 3963-1...0/-1…2) and 40 °C (for Type 3963-1...1/-1…3) due tothe materials used.

To connect to a certified intrinsically safe circuit, refer to the maximum permissible values forvoltage U0, current I0 and power P in the following table:

Note: Internal capacitance and internal inductance are negligible.

Temperature class T6 T5 T4Ambient temperature maximum 60 °C 70 °C 80 °C

minimum 45 °C *)

U0 (V) 25 V 27 V 28 V 30 V 32 VI0 (mA) 150 mA 125 mA 115 mA 100 mA 90 mAP no power limit

Page 12: Solenoid Valves Type 3963 - Samson AG

Installation Directions for Devicesfor Use in Hazardous Locations inCompliance with CSA Approval

The devices may be installed in intrinsicallysafe circuits when connected with CSAapproved intrinsically safe barriers (Fig. 14).In case of doubt as regards barrier selection,contact the manufacturer. For maximum valuesof Vmax, Rmin and Imax of the various devicessee the following table:

Type Vmax Rmin Imax[V DC] [Ω] [mA]

3963-31 13 94 1503963-32 25 168 1503963-33 28 256 1103963-34 9 60 1503963-37 28 256 110

Connection diagrams

CSA certified for Hazardous Locations: Class I; Division 1; Groups A, B, C, D

CSA certified for Hazardous Locations: Class I; Division 2; Groups A, B, C, D

Fig. 14

Hazardous Location Safe Location

I.S. circuit

I.S. barrier

SolenoidValveType3963-3...

+

_

*)

+

_

Supply barrier

to instrument

Return barrier

Ground

Hazardous Location Safe Location

+

_

_

+

*)

Ground

SolenoidValveType3963-3...

Unspecifiedapparatus,e.g. transistorrelay,with outputparametersper table

*) Only for metal enclosure

Cable entry Pg 13,5 or metal conduitaccording to assembly drawing No. 3963-3...and drawing No. 1150-6016 T-3

*) Only for metal enclosure

Cable entry only rigid metal conduitaccording to drawing No. 1150-6016 T-3

EB 963 E – 12 –

Page 13: Solenoid Valves Type 3963 - Samson AG

Hazardous Location Safe Location

I.S. circuit

I.S. barrier

SolenoidValveType3963-3...

+

_

*)

to instrument

Ground

– 13 – EB 963 EN

Installation Directions for Devicesfor Use in Hazardous Locations inCompliance with FM Approval

The devices may be installed in intrinsicallysafe circuits when connected with FM approvedintrinsically safe barriers (Fig. 15). In case ofdoubt as regards barrier selection, contact themanufacturer. For maximum values of Vmaxand Imax of the various devices see the follow-ing table:

Type Vmax Imax[V DC] [mA]

3963-31 13 1503963-32 25 1503963-33 28 1103963-34 9 1503963-37 28 110

Connection diagrams

FM certified for Hazardous Locations: Class I, II, III; Division 2; Groups A, B, C, D, E, F, G

FM certified for Hazardous Locations: Class I, II, III; Division 1; Groups A, B, C, D, E, F, G

Fig. 15

Hazardous Location Safe Location

+

_

_

+

*)

Ground

SolenoidValveType3963-3...

Unspecifiedapparatus,e.g. transistorrelay,with outputparametersper table

*) Only for metal enclosure

*) Only for metal enclosure

Page 14: Solenoid Valves Type 3963 - Samson AG

SAMSOMATICAUTOMATIONSSYSTEMEGMBH

– A subsidiary of SAMSON AG

(Specifications subject to change without notice)