specifications - s & c electric · s&c specification bulletin 1072-31 3 speenet™ aio...
TRANSCRIPT
SpeedNet™ Radio
September 16, 2019
© S&C Electric Company 2013-2019, all rights reserved Specification Bulletin 1072-31
Conditions of SaleSTANDARD: The seller’s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under “SPECIAL WARRANTY PROVISIONS” on page 2.
SPECIAL TO THIS PRODUCT:
INCLUSIONS: S&C SpeedNet Radios provide high-speed, long-range, peer-to-peer data communication for fixed point-to-point nodes up to 25 miles apart. They feature:
• Unlicensed 902- to 928-MHz IMS band with regional support for North America, Brazil, and New Zealand
• 51 channels with 500-kHz bandwidth in North America
• Frequency Hopping Spread Spectrum (FHSS)
• 4-Gaussian Frequency-Shift Keying (4-GFSK) Modula-tion
• Fast data transmission rates—up to 650 kbps
• Message latency is 10.5 ms/per link, for a 300 byte DNP packet payload
• Frequency hop time, averaging 10 ms
• User-selectable transmit power: +30, +25, +20, or +10 dBm, default is +30 dBm
• -100 dBm sensitivity (at 10-5 Bit Error Rate)
• Use of 16-bit Cyclic Redundancy Check, Automatic Repeat request, and Reed-Solomon Forward Error Correction for error detection and correction
• Serial and Ethernet data input supporting: IPv4, TCP, UDP, ICMP, SNMPv3
• Use of the Enhanced Ad-hoc On-demand Distance Vector (AODV) network protocol
• Secure 128-bit AES data encryption with user-defined keysets created using the supplied Keygen tool
• MAC address filtering
• Star network or Mesh network using IP addresses
• Use of the Carrier Sense Multiple Access (CSMA) wireless protocol
• Assignable message priority—for example, configuring S&C IntelliRupter® PulseCloser® Fault Interrupter operation messages to transmit first
• Simple Network Management Protocol version 3 (SNMPv3) and a supplied Microsoft® Windows-based SpeedNet Client tool to set parameters, monitor status, and automate data collection
• Multi-level administrative passwords
• Over-the-air configuration and software updates
• Single network gateway
• Availability of received signal strength indication statistics in real time and from data logs
• Battery back-up with remote battery testing on repeater and gateway models
A highly adaptive IP-addressable mesh network of SpeedNet Radios is easy to set up and maintain. SpeedNet Radios can communicate through each other to establish new message paths when a node is lost, providing excellent signal-loss tolerance and network reliability.
SpeedNet Radios provide highly secure transmissions, too. Their frequency-hopping spread-spectrum signals are inherently difficult to intercept and jam. IP/MAC address filtering prevents unauthorized users from accessing the network. And 128-bit AES encryption ensures that critical data are not compromised.
SpeedNet Radios are offered in five versions:
• SpeedNet Radio for installation in a user-furnished enclosure
• SpeedNet Streetlight-Mounted Repeater Radio in a cast-aluminum weatherproof enclosure that mounts on a streetlight arm (Extends communication range and expands network area.)
• SpeedNet Extension Arm-Mounted Repeater Radio in a cast-aluminum weatherproof enclosure with an extension arm that mounts on a utility pole (Extends communication range and expands network area.)
• SpeedNet Utility-Pole-Mounted Repeater Radio in a padlockable plastic weatherproof enclosure that mounts directly on a utility pole (Extends communica-tion range and expands network area.)
• SpeedGate™ Radio Interface System in a pad-lockable plastic weatherproof enclosure that mounts directly on a utility pole (Includes provision for a gateway communication device, permitting data exchange with a different communication system.)
Specifications
2 S&C Specification Bulletin 1072-31
SpeedNet™ Radio
Conditions of Sale—Continued
Device CompatibilitySpeedNet Radios cannot communicate directly with other types of radios because of differences in frequency selection, spread-spectrum frequency-hopping patterns, channel use, and network management algorithms. A SpeedGate Repeater Radio, with an appropriate gateway communication device, is required in such instances.
AntennasSpeedNet Radios are FCC approved for use only with the antenna/cable combinations offered in this specification bulletin.
EXCLUSIONS: If the user’s communication system also requires licensed radios, frequency selection and FCC license application are to be provided by others.
SPECIAL WARRANTY PROVISIONS: The standard warranty contained in the seller’s standard conditions of sale, as set forth in Price Sheet 150, applies to S&C SpeedNet Radios, except that the first paragraph of the said warranty is replaced by the following:
(1) General: The seller warrants to the purchaser for a period of two years from the date of shipment that the equipment delivered will be of the kind and
quality specified in the contract description and will be free of defects of workmanship and mate-rial. Should any failure to conform to this warranty appear under proper and normal use within two years after the date of shipment, the seller agrees, upon prompt notification thereof and confirma-tion that the equipment has been stored, installed, operated, inspected, and maintained in accordance with the recommendations of the seller and stan-dard industry practice, to correct the nonconformity either by repairing any damaged or defective parts of the equipment or (at the seller’s option) by shipment of necessary replacement parts.
The above special warranty does not apply to gateway communication devices applied with SpeedNet Radios.
END USER LICENSE AGREEMENT: The end user is granted a nontransferable, non-sublicensable, nonexclusive license to use the software furnished with SpeedNet Radios only upon acceptance of all the terms and conditions of the seller’s end user license agreement set forth in Price Sheet 155.
How To OrderSelect catalog numbers for the radios and accessories, and catalog number suffixes for the desired options.
S&C Specification Bulletin 1072-31 3
SpeedNet™ Radio
Table 1. SpeedNet Radios and SpeedGate Radio Interface SystemItem Catalog Number
SpeedNet Radio①—for mounting in user-furnished enclosure. Includes a 4-foot (121.9-cm) power cord for connection to user-furnished 12-Vdc power source 110-000555-02
SpeedNet Streetlight-Mounted Repeater Radio②—in a cast-aluminum weatherproof enclosure. Includes an adjustable galvanized-steel mounting bracket for attachment to a streetlight arm or other circular cross-section, a battery charger, a battery providing 8-hour minimum backup on loss of ac control power③, a 3-foot (91.4-cm) streetlight photocell adapter power cable, and an omnidirectional 5-dBd whip antenna on bottom of enclosure
908-000958-01
With a 900-MHz band-pass filter 908-000959-01
With a 10-foot (304.8-cm) unterminated cable for connection to a user-furnished 110-240 Vac, 50/60-Hz power source⑥, instead of a streetlight photocell adapter power cable 908-000956-01
With a 10-foot (304.8-cm) unterminated cable for connection to a user-furnished 110-240 Vac, 50/60-Hz power source⑥, instead of a streetlight photocell adapter power cable, and a 900-MHz band-pass filter 908-000957-01
SpeedNet Extension Arm-Mounted Repeater Radio②—in a cast-aluminum weatherproof enclosure. Includes a galvanized steel extension arm for attachment to a utility pole, a battery charger, a battery providing 8-hour minimum backup on loss of ac control power③, a 10-foot (304.8-cm) unterminated cable for connection to a user-furnished 110-240 Vac, 50/60-Hz power source⑥, and an omnidirectional 5-dBd whip antenna on bottom of enclosure
908-000963-01
With 900-MHz band-pass filter 908-000963-02
SpeedNet Utility-Pole-Mounted Repeater Radio③—in a padlockable plastic weatherproof enclosure. Includes an aluminum bracket for direct attachment to utility pole, a battery charger, a battery providing 8-hour minimum backup on loss of ac control power③, a connector for a user-furnished 110-240 Vac, 50/60-Hz power source⑥, and an omnidirectional 5-dBd whip antenna on top of door
908-000953-01
With a 900-MHz band-pass filter 908-000953-04
With a PolyPhaser® surge suppressor on bottom of enclosure, for a remote antenna 908-000953-03
With a PolyPhaser surge suppressor on bottom of enclosure for a remote antenna and a 900-MHz band-pass filter 908-000953-02
SpeedGate Radio Interface System④—in a padlockable weatherproof plastic enclosure. Includes an aluminum bracket for direct attachment to a utility pole, a battery charger, a battery providing 8-hour minimum backup on loss of ac control power③, a connector for a user-furnished 110-240 Vac, 50/60-Hz power source⑤⑦
908-000954-01
① Select accessories from Table 3 on page 5.
② Select accessories from Table 4 on page 6.
③ Assuming typical IntelliTeam® II Automatic Restoration System communications traffic and an enclosure temperature of 77°F (25°C).
④ Select accessories from Table 5 on page 6.
⑤ Select gateway communication device from the Table 2 on page 4.
⑥ Power cable must be ordered separately from Table 4 on page 6
⑦ Power cable must be ordered separately from Table 5 on page 6.
4 S&C Specification Bulletin 1072-31
SpeedNet™ Radio
Table 2. SpeedGate Options List
Item①
Approximate Battery Carryover
Time, Hours②
Suffix to Be Added to SpeedGate Radio Catalog Number
Gateway Communication Devices for SpeedGate Radio Interface System (furnished by S&C)
UtiliNet® Series IV Radio 9 -XR67
MDS Transnet 900 Transceiver with Diagnostics 8 -XR19
Single-Mode Dymec 5843SHRT Fiber-Optic Modem 13 -XR44
Multi-Mode Dymec 5843HRT Fiber-Optic Modem 18 -XR45
Telemetric™ DNP-RTMII-GSM Transceiver 9 -XR161
SpeedNet™ Cell Edge Gateway 4G LTE cellular modem for AT&T Cellular Network (With Embedded AT&T SIM)④ -XR322
SpeedNet™ Cell Edge Gateway 4G LTE cellular modem with removeable SIM card for USA and Canada④ -XR324
MDS SD9 Remote Radio ●
Ready for Gateway Communication Devices for SpeedGate Radio Interface System (furnished by customer)
SpeedNet Radio — -R88
UtiliNet® Series 3000 or Series IV Radio 9 -XR66
MDS 9810 Radio 9 -XR02
MDS 9710A Radio 8 -XR03
MDS Transnet 900 Transceiver 8 -XR07
Single-Mode Dymec 5843SHRT Fiber-Optic Modem 13 -XR42
Multi-Mode Dymec 5843HRT Fiber-Optic Modem 18 -XR43
Telemetric™ DNP-RTMII-GSM Transceiver 9 -XR160
MDS SD9 Remote Radio -XR217
SpeedNet Radio Antenna Connector
N-Type Connector, Top Mounted, for Local Antenna -S1
N-Type Connector, Bottom Mounted, for Local Antenna -S2
Poly-Phaser® Surge Suppressor, N-Type Connector, Bottom Mounted, for Remote Antenna Installation③ -S3
Gateway Radio Antenna Connector
Poly-Phaser® Surge Suppressor, N-Type Connector, Bottom Mounted, for Remote Antenna Installation③ -XS3
TABLE CONTINUED ▶
① Contact your local S&C Sales Office regarding other communication devices.
② Battery carryover time is dependent on transmission polling rate, ambient temperature, and radio power consumption. Time indicated assumes typical IntelliTeam II Automatic Restoration System commu-nications traffic and an enclosure temperature of 77°F (25°C).
③ Select Remote Antenna Kit from Table 5 on page 6. Two Remote Antenna Kits are required if two remote antennas are specified.
④ Please see Specification Bulletin 1076-31 for SpeedNet Cell Edge Gateway antenna options.
● Specify the appropriate catalog number suffix based on the fre-quency band range and application for the radio, from the following table. For example, for a 928- to 960-MHz MDS SD9 Radio for Ethernet and serial application, specify catalog number suffix “-XR216CL.”
Frequency Band Range, MHz ApplicationSuffix to be
Added to Catalog Number
820 to 870
Serial
-XR216AK
928 to 960 -XR216CK
928 to 960, 50-kHz Channel -XR216DK
880 to 915 -XR216EK
880 to 915, 50-kHz Channel -XR216FK850 to 860 / 926 to 936,
Transmit Low -XR216GK
850 to 860 / 926 to 936, Transmit High -XR216HK
820 to 870
Ethernet and Serial
-XR216AL
928 to 960 -XR216CL
928 to 960, 50-kHz Channel -XR216DL
880 to 915 -XR216EL
880 to 915, 50-kHz Channel -XR216FL850 to 860 / 926 to 936,
Transmit Low -XR216GL
850 to 860 / 926 to 936, Transmit High -XR216HL
Frequency Band Range, MHz ApplicationSuffix to be
Added to Catalog Number
820 to 870
9710 Emulation
-XR216AM
928 to 960 -XR216CM
928 to 960, 50-kHz Channel -XR216DM
880 to 915 -XR216EM
880 to 915, 50-kHz Channel -XR216FM
850 to 860 / 926 to 936, Transmit Low -XR216GM
850 to 860 / 926 to 936, Transmit High -XR216HM
S&C Specification Bulletin 1072-31 5
SpeedNet™ Radio
Table 3. SpeedNet Radio Accessories
Item Catalog Number
12-Vdc Power Cord—4-foot (121-92 cm), with connector on one end and bare wires on the other end 007-001496-01
120-Vac Power Adapter—supplies 12 Vdc to radio 904-001171-01
Antenna Cable—22 inch (55.9 cm), with SMA male to N-Type male connectors and bulkhead connector 903-002320-01
External 900-MHz Band-Pass Filter Field Retrofit Kit 903-001174-01
Omnidirectional 5-dBd Whip Antenna—mounts on bulkhead connector 904-000071-00
Remote Antenna Kit—includes omnidirectional fiberglass antenna, pole-mounted single-antenna arm
With 30-foot (76.2-cm) coaxial cable with N-Type male connectors on both ends 903-002132-02
With 50-foot (127-cm) coaxial cable with N-Type male connectors on both ends 903-002132-03
Remote Antenna Kit—includes unidirectional Yagi antenna, pole-mounted single-antenna arm
With 30-foot (76.2-cm) coaxial cable with N-Type male connectors on both ends (Customer to provide 1.375-inch (34.9 mm) OD pipe for antenna)
903-002321-01
With 50-foot (127-cm) coaxial cable with N-Type male connectors on both ends (Customer to provide 1.375-inch (34.9 mm) OD pipe for antenna)
903-002321-02
½-inch (12.7-mm)Wave Dipole Antenna, Rubber Duck Style, 90 Degree Adjustable Knuckle, SMA Male, 870-960 MHz, 2.3 dBi Max Gain
904-002141-01
2-Way 900 MHz Signal Splitter, N-Female Connector 904-002182-01
3-Way 900 MHz Signal Splitter, N-Female Connector 904-002183-01
Flat-Panel Directional Antenna, 902-928 MHz, Dimensions 15.4 inches (391.2 mm) × 15.4 inches (391.2 mm) × 1.7 inches (43.2 mm) 904-002184-01
Type-400 ⅜-inch (9.5-mm) Coaxial Cable, sold by the foot 904-002185-01
Retrofit Kit for Replacing a UtiliNet Series II or Series 3000 Radio with a SpeedNet Radio. Includes mounting bracket, power- and antenna-adapter cables 904-001172-01
Retrofit Kit for Replacing a UtiliNet Series 3000 Radio with a SpeedNet Radio. No adapter cables included, connectors are the same for both radios 904-001172-02
Programming Cable—7-foot (213.4 cm), for Ethernet connection 904-001184-01
Table 2. SpeedGate Options List—Continued
Item①
Suffix to Be Added to SpeedGate Radio Catalog Number
SpeedNet Local Antenna
900-MHz 5-dB Gain Antenna, N-Type Male Connector 904-000071-00 -T2
900-MHz Mobile Mark Antenna RM3-900/1900 Dual-Band Cellular Antenna 007-001427-01 -T7
Band-Pass Filters
900-MHz Band-Pass Filter for SpeedNet Radio 904-001157-01 -F1
900-MHz Band-Pass Filter for UtiliNet Radio 904-001145-01 -XF2
6 S&C Specification Bulletin 1072-31
SpeedNet™ Radio
Table 6. Substation Communication PackageItem Catalog Number
Substation Communication Package. Includes a SpeedNet Radio, 110-Vac power supply, PolyPhasor® Surge Suppressor, 6-dB substation antenna with integrated mounting bracket, 80-foot (2438.2 cm) antenna cable, and other associated cabling
903-002325-01
① Other cord lengths are available.
Table 4. SpeedNet Repeater Radio AccessoriesItem Catalog Number
Ac Power Cable for Streetlight-Mounted and Extension- Arm-Mounted Repeater Radios
With 10-foot (304.8 cm) unterminated #10 wire 007-001468-01
With 6-foot (182.9 cm) with plug for ac outlet 007-001495-01
Ac Power Cable for Utility-Pole-Mounted Repeater RadioWith 10-foot (304.8 cm)unterminated #10 wire 007-001511-01
With 6-foot (182.9 cm) cable with plug for ac outlet 007-001530-01
Streetlight Photocell Adapter—includes 3-foot (91.44 cm) cord① 007-001467-01
External 900-MHz Band-Pass Filter Kit 903-001174-01
Replacement Battery, 4.5 Ampere-Hour, 12 Vdc 591-000860-01
Replacement Omnidirectional 5-dBd Whip Antenna 904-000071-00
Remote Antenna Kit for SpeedNet Utility-Pole-Mounted Repeater Radio—Includes omnidirectional fiberglass antenna, pole-mounted single-antenna arm
With 30-foot (914.4 cm) coaxial cable with N-Type male connectors on both ends 903-002132-02
With 50-foot (1524 cm) coaxial cable with N-Type male connectors on both ends 903-002132-03
SpeedNet Repeater Battery and External Hardware Replacement Kit—Includes Gasket 903-002436-01
SpeedNet External Hardware Replacement Kit—Includes Gasket 903-002436-02
Programming Cable—7-foot (213.4 cm) for Ethernet connection 904-001184-01
Table 5. SpeedGate Radio Interface System AccessoriesItem Catalog Number
Ac Power Cable—10-foot (304.8 cm) unterminated #10 wire 007-001511-01
Streetlight Photocell Adapter—includes 12-foot (365.8 cm) cord① 007-001515-01
900-MHz Band-Pass Filter Field-Retrofit Kit for SpeedNet Radio 903-001175-01
Replacement Battery, 4.5 Ampere-Hour, 12 Vdc 591-000860-01
Replacement Omnidirectional 5-dBd Whip Antenna 904-000071-00
Remote Antenna Kit—includes omnidirectional fiberglass antenna, pole-mounted single-antenna arm
With 30-foot (914.4 cm) coaxial cable with N-Type male connectors on both ends 903-002132-02
With 50-foot (1524 cm) coaxial cable with N-Type male connectors on both ends 903-002132-03
Remote Antenna Kit—includes unidirectional Yagi antenna, pole-mounted single-antenna arm
With 30-foot (914.4 cm) coaxial cable with N-Type male connectors on both ends (Customer to provide 1.375-inch (34.9 mm) OD pipe for antenna)
903-002321-01
With 50-foot (1524 cm)coaxial cable with N-Type male connectors on both ends (Customer to provide 1.375-inch (34.9 mm) OD pipe for antenna)
903-002321-02
Remote Dual-Antenna Kit—includes omnidirectional fiberglass SpeedNet antenna, cellular antenna, pole-mounted dual-antenna arm
With two 30-foot (914.4 cm) coaxial cables with N-Type male connectors on both ends 903-002172-02
With two 50-foot (1524 cm) coaxial cables with N-Type male connectors on both ends 903-002172-03
Programming Cable—7 foot (213.4 cm), for Ethernet connection 904-001175-01
① Other cord lengths are available.
S&C Specification Bulletin 1072-31 7
SpeedNet™ Radio
SpeedNet Radio
Dimensions in inches (mm)
4.25 (108)
4.75 (121)
4.75 (121)
0.25 (6)
6.30 (160)
1.29 (33)
5.25 (127)
8 S&C Specification Bulletin 1072-31
SpeedNet™ Radio
SpeedNet Streetlight-Mounted Repeater Radio
12.87 (327)
13.01 (330)
10.78 (274)
9.57 (243)
4.75 (121)
11.19 (284)
Dimensions in inches (mm)
S&C Specification Bulletin 1072-31 9
SpeedNet™ Radio
SpeedNet Extension Arm-Mounted Repeater Radio
8.00 (203)
36.00 (914)
Dimensions in inches (mm)
10 S&C Specification Bulletin 1072-31
SpeedNet™ Radio
SpeedNet Utility-Pole-Mounted Repeater Radio
0.840 (21)
0.250 (6)
0.560 (14) 0.750
(19)
11.35 (288)
5.00 (127)
10.25 (260)
14.79 (376)
18.00 (457)
20.00 (508)
1.50 (38)
13.00 (330)
2.50 (64)
9.85 (250)
Dimensions in inches (mm)
S&C Specification Bulletin 1072-31 11
SpeedNet™ Radio
SpeedGate Radio Interface System
0.83 (21)
5.00 (127)
16.69 (424)
1.50 (38)
18.50 (470)
1.81 (46)
0.250 (6)
0.750 (19)
24.00 (610)
22.00 (559)
9.85 (250)
16.26 (413)
Dimensions in inches (mm)
0.560 (14)
12 S&C Specification Bulletin 1072-31
SpeedNet™ Radio
Power Connector on the SpeedNet Repeater Radios and SpeedGate Radio Interface System
AB
E
CD
Connector on SpeedGate Radio.
A BECD
Connector on SpeedNet Repeater Radios.
The power cable connector has a jumper between pins D and E. When D and E are shorted the battery is connected, and the battery charger monitors and charges the battery. When the power cable is removed (D and E are open), the battery is disconnected so the radio will not discharge the battery before ac power is connected. A repeater radio or SpeedGate system is always operated with ac power connected, and battery backup is only used during a power outage.
Pin Connection
A Ac Hot
B Ac Neutral
C Not used
D Disconnect Logic +
E Disconnect Logic –