spring return actuator product range multi-function technology · 2017-06-26 · spring return...

28
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA 4 Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power Supply Power Consumption Control Input Control Input Auxiliary Switches NEMA 4 10 ft (3m) cable / 16 ft (5m) cable Motor Drive, (Default) (Fully programmable by Belimo or in field) Spring Return 24 VAC +/- 20%, VDC +/- 10%, 50/60 HZ VA Rating, Transformer Sizing Wattage Running (Holding) 2-10 VDC (Default) 4-20 mA* (w/500 Ω Resistor) 6 - 9 VDC, 20 VDC Output Voltage Honeywell Series 90, 0-135 Ω On/Off Floating Point Start and Span adj., Start 0.5 to 30 VDC, Span 2.5 to 32 VDC PWM adj., 0.02 to 50.0 Seconds 2-10 VDC (Default) VDC Variable, Start 0 to 8, Span 2 to 10 VDC 1 SPDT, 3 A (0.5 A inductive) @ 250V 2 SPDT, 3 A (0.5 A inductive) @ 250V 2 SPDT, 7 A (2.5 A inductive) @ 250V Enclosure (Part Number + N4) New Generation AFX Series 180 in-lb [20 Nm] Approx. 45 sq. ft.* AFX24-MFT 70…220 (150) <2010 7.5 (3.0) AFX24-MFT-S 70…220 (150) <2010 7.5 (3.0) AFX24-MFT95 70…220 (150) <20 10 7.5 (3.0) Original AF Series 133 in-lb [15 Nm] Approx. 33 sq. ft.* AF24-MFT US 75…300 (150) <20 10 6.0 (2.5) AF24-MFT-S US 75…300 (150) <20 10 6.0 (2.5) AF24-MFT95 US 75…300 (150) <20 10 6.0 (2.5) New Generation NFX Series 90 in-lb [10 Nm] Approx. 22 sq. ft.* NFX24-MFT 40…220 (150) <20 9 6.5 (3.0) NFX24-MFT-S 40…220 (150) <209 6.5 (3.0) Original NF Series 60 in-lb [7 Nm] Approx. 15 sq. ft.* NF24-MFT US 75…300 (150) <60 6 3.0 (1.8) LF Series 35 in-lb [4 Nm] Approx. 8 sq. ft. LF24-MFT US 75…300 (150) <255 2.5 (1.0) LF24-MFT-S US 75…300 (150) <25 5 2.5 (1.0) LF24-MFT-20 US 150 <25 6 3.5 (1.5) LF24-MFT-S-20 US 150 <256 3.5 (1.5) TF Series 18 in-lb [2 Nm] Approx. 4.5 sq. ft.* TF24-MFT US 75…300 (150) <254 2.0 (1.0) <60 seconds @ -22°F [-30°C]. † Dual mounting on a single shaft-MFT wired master slave. Please refer to page XX or call Belimo customer service for details. * Parallel blade without edge seals and 1000 FPM face velocity. NOTE: Some spring and non-spring damper actuators are also used for water applications. A linkage connects the actuators to the valve. Some of the valves, such as the PICCV use a running time of 100 seconds. Some actuators end with an X1 such as AMX24-MFTX1. M40035 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc.

Upload: others

Post on 19-Apr-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

4

Spring Return Actuator Product RangeMulti-Function Technology

CableOptions

Running Rime PowerSupply

PowerConsumption

ControlInput

Control InputAuxiliarySwitches

NEMA 4

10 ft

(3m

) cab

le /

16 ft

(5m

) cab

le

Mot

or D

rive,

(Def

ault)

(Ful

ly

prog

ram

mab

le b

y Be

limo

or in

fiel

d)

Sprin

g Re

turn

24 V

AC +

/- 20

%, V

DC +

/- 10

%, 5

0/60

HZ

VA R

atin

g, T

rans

form

er S

izing

Wat

tage

Run

ning

(Hol

ding

)

2-10

VDC

(Def

ault)

4-20

mA*

(w/5

00 Ω

Res

isto

r)

6 - 9

VDC

, 20

VDC

Outp

ut V

olta

ge

Hone

ywel

l Ser

ies

90, 0

-135

Ω

On/O

ff

Floa

ting

Poin

t

Star

t and

Spa

n ad

j., S

tart

0.5

to

30 V

DC, S

pan

2.5

to 3

2 VD

C

PWM

adj

., 0.

02 to

50.

0 Se

cond

s

2-10

VDC

(Def

ault)

VDC

Varia

ble,

Sta

rt 0

to 8

,Sp

an 2

to 1

0 VD

C

1 SP

DT, 3

A (0

.5 A

indu

ctiv

e) @

250

V

2 SP

DT, 3

A (0

.5 A

indu

ctiv

e) @

250

V

2 SP

DT, 7

A (2

.5 A

indu

ctiv

e) @

250

V

Encl

osur

e (P

art N

umbe

r + N

4)

New Generation AFX Series

180 in-lb [20 Nm]Approx. 45 sq. ft.*

AFX24-MFT† ● 70…220 (150) <20♦ ● 10 7.5 (3.0) ● ● ● ● ● ● ● ●

AFX24-MFT-S† ● 70…220 (150) <20♦ ● 10 7.5 (3.0) ● ● ● ● ● ● ● ● ●

AFX24-MFT95† 70…220 (150) <20♦ ● 10 7.5 (3.0) ● ● ● ● ●

Original AF Series

133 in-lb [15 Nm]Approx. 33 sq. ft.*

AF24-MFT US† 75…300 (150) <20 ● 10 6.0 (2.5) ● ● ● ● ● ● ●

AF24-MFT-S US† 75…300 (150) <20 ● 10 6.0 (2.5) ● ● ● ● ● ● ● ●

AF24-MFT95 US† 75…300 (150) <20 ● 10 6.0 (2.5) ● ● ● ●

New Generation NFX Series

90 in-lb [10 Nm]Approx. 22 sq. ft.*

NFX24-MFT ● 40…220 (150) <20♦ ● 9 6.5 (3.0) ● ● ● ● ● ● ● ●

NFX24-MFT-S ● 40…220 (150) <20♦ ● 9 6.5 (3.0) ● ● ● ● ● ● ● ● ●

Original NF Series

60 in-lb [7 Nm]Approx. 15 sq. ft.*

NF24-MFT US 75…300 (150) <60♦ ● 6 3.0 (1.8) ● ● ● ● ● ● ●

LF Series

35 in-lb [4 Nm]Approx. 8 sq. ft.

LF24-MFT US 75…300 (150) <25♦ ● 5 2.5 (1.0) ● ● ● ● ● ● ●

LF24-MFT-S US 75…300 (150) <25♦ ● 5 2.5 (1.0) ● ● ● ● ● ● ● ●

LF24-MFT-20 US 150 <25♦ ● 6 3.5 (1.5) ● ● ● ● ● ● ●

LF24-MFT-S-20 US 150 <25♦ ● 6 3.5 (1.5) ● ● ● ● ● ● ● ●

TF Series

18 in-lb [2 Nm]Approx. 4.5 sq. ft.*

TF24-MFT US 75…300 (150) <25♦ ● 4 2.0 (1.0) ● ● ● ● ● ● ●

♦ <60 seconds @ -22°F [-30°C].

† Dual mounting on a single shaft-MFT wired master slave. Please refer to page XX or call Belimo customer service for details.

* Parallel blade without edge seals and 1000 FPM face velocity.

NOTE: Some spring and non-spring damper actuators are also used for water applications. A linkage connects the actuators to the valve. Some of the valves, such as the PICCV use a running time of 100 seconds. Some actuators end with an X1 such as AMX24-MFTX1.

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 2: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

5

Non-Spring Return Actuator Product RangeMulti-Function Technology

CustomOptions

RunningTime

PowerSupply

PowerConsumption

ControlInput

Control Input PositionFeedback

AuxiliarySwitches

NEMA4X

10 ft

(3m

) cab

le /

16 ft

(5m

) cab

le

Term

inal

stri

pNE

MA

1/IP

20 /

2/IP

54

Mot

or D

rive

Rang

e, (D

efau

lt)…

-MFT

Ful

ly P

rogr

amm

able

24 V

AC +

/- 20

%, V

DC +

/- 10

%

100

to 2

40 V

AC

VA R

atin

g

Wat

tage

Run

ning

(Hol

ding

)

2-10

VDC

(Def

ault)

4-20

mA

(w/5

00 Ω

Res

isto

r)

Hone

ywel

l Ser

ies

90, 0

-135

Ω

On/O

ff

Floa

ting

Poin

t

Star

t and

Spa

n ad

j., S

tart

0.5

to

30 V

DC, S

pan

2.5

to 3

2 VD

C

PWM

adj

., 0.

02 to

50.

0 Se

cond

s

2-10

VDC

(Def

ault)

VDC

Varia

ble,

Sta

rt 0

to 8

,Sp

an 2

to 1

0 VD

C

Add-

on

Encl

osur

e (P

art N

o. +

N4 o

r +N4

H)

GMX Series 360 in-lb [40 Nm]Approx. 90 sq. ft.**

GMX24-MFT† ● 75-300 (150) ● 7 4.0 (1.5) ● ● ● ● ● ● ● ●

GMX24-MFT95† ● 100-300 (150) ● 7 4.0 (1.5) ● ● ● ●

AMX Series 180 in-lb [20 Nm]Approx. 45 sq. ft.**

AMX24-MFT ● 90-300 (150) ● 6 3.5 (1.3) ● ● ● ● ● ● ● ● ●

AMCX24-MFT ● 35-120 (35) ● 6 3.5 (1.3) ● ● ● ● ● ● ● ●

AMX24-MFT95 ● 90-150 (150) ● 6 3.5 (1.3) ● ● ● ●

AMQ Series 140 in-lb [16Nm] AMQX24-MFT ● 7-15 (7) ● 18 12 (1.5) ● ● ● ● ● ● ● ●

NMX Series 70 in-lb [8 Nm]Approx. 22 sq. ft.**

NMX24-MFT ● 45-150 (150) ● 6 3.5 (1.3) ● ● ● ● ● ● ● ● ●

NMX24-MFT95 ● 45-150 (150) ● 6 3.5 (1.3) ● ● ● ●

NMCX24-MFT ● 20-75 (20) ● 5 3.0 (0.6) ● ● ● ●

NMQ Series 70 in-lb [8Nm] NMQX24-MFT ● 4-20 (4) ● 18 12 (1.5) ● ● ● ● ● ● ●

LMX Series 35 in-lb [4 Nm]Approx. 11 sq. ft.**

LMX24-MFT ● 35-200 (150) ● 5 2.5 (1.2) ● ● ● ● ● ● ● ●

LMX24-MFT95 ● 35-150 (150) ● 5 2.5 (1.2) ● ● ● ●

LMQ Series 35 in-lb [4Nm] LMQX24-MFT ● 2.5-10 (2.5) ● 18 12 (1.5) ● ● ● ● ● ● ●

AHX Series 101 lbf [450 N Force]4” or 8” stroke

AHX24-MFT* ● 150* ● 6 3.5 (1.3) ● ● ● ● ● ● ●

AHQ Series 44 lbf [200 N Force] AHQX24-MFT-100 ● 7-30 (7)* ● 18 12 (1.5) ● ● ● ● ● ● ●

LHX Series 34 lbf [150 N Force]4” or 8” stroke

LHX24-MFT* ● 75-150 (150)* ● 5 2.5 (1.2) ● ● ● ● ● ● ●

LHQ Series 22 lbf [100 N Force] LHQX24-MFT-100 ● 3.5-15 (3.5)* ● 18 12 (1.5) ● ● ● ● ● ●

LUX Series 27 in-lb [3 Nm] LUX24-MFT ● 75-150 (150) ● 5 2.5 (1.2) ● ● ● ● ● ● ●

* The LH and AH linear series actuators come in three different stroke lengths [4, 8 or 12 in]. The part number is followed by -100, -200, -300 respectively. The default running time is 150 seconds per 4 inches [100 mm]. Running time is adjustable depending on model:LH Series: 70-270, 140-540, 200-810, on the -100, -200, -300 models respectively.AH Series: 150-600, 300-1200, 450-1800, on the -100, -200, -300 models respectively.

LHQ and AHQ available in 4 inch version only.

† Dual mounting on a single shaft is possible for higher torque (-3 and -SR wired in parallel), (-MFT wired Master-Slave). Please call Belimo customer service for details.

** Parallel blade without edge seals and 1000 FPM face velocity.

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 3: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

6

Pre-Set MFT Confi gurations DC Voltage Control

ApplicationHow the MFT actuator performs is determined by the configuration (P-10001, A01). The old generation actuators used a P-code (P-10001). The new generation actuators use a shorter 3 digit code. This shorter code is displayed on the reorder number.

P-1000... configuration types are used for control voltage applications.

Additional pre-set configurations are listed which offer solutions for non-standard control application for:

• Adjustable Start and Stop points

• Sequencing actuators

• Combination for master slave (see page 19.)

Wiring Diagram

(1) Common

(2) + Hot

(3) Y Input

(5) U Output

Position Feedback

Control Signal

Line Volts

24 VAC/DC Transformer

CCW CW

(+)(–)

(+)(–)

…MFT

W04

0

VDC

Select Configuration

Configuration Code Input Range Position Feedback Running Time Torque % Adaptation

Volta

ge

P-10001* A01 2.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10002 A02 0.5 to 10.0 VDC 0.5 to 10.0 VDC 150 100 MANUAL

P-10003 A03 2.0 to 10.0 VDC 0.5 to 5.0 VDC 150 100 MANUAL

P-10004 A04 4.0 to 7.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10005 A05 6.0 to 9.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10006 A06 10.5 to 13.5 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10007 A07 0.5 to 5.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10008 A08 0.5 to 5.0 VDC 0.5 to 10.0 VDC 150 100 MANUAL

P-10009 A09 5.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10010 A10 5.0 to 10.0 VDC 0.5 to 10.0 VDC 150 100 MANUAL

P-10013 A13 0.5 to 10.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10015 A15 2.0 to 5.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10016 A16 2.0 to 6.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10017 A17 6.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10018 A18 14.0 to 17.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10020 A20 9.0 to 12.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10031 A31 0.5 to 4.0 VDC 2.0 to 10.0 VDC 150 100 MANUAL

P-10063 A63 0.5 to 4.5 VDC 0.5 to 4.5 VDC 150 100 MANUAL

P-10064 A64 5.5 to 10.0 VDC 5.5 to 10.0 VDC 150 100 MANUAL

P-10091 A91 2.0 to 10.0 VDC 2.0 to 10.0 VDC 95 100** MANUAL* P-10001 (A01) is the default configuration code.** Reduced torque in Spring Return (see page 19)

Spring Return Actuators

AFX24-MFT(-S) 180 in-lb AF24-MFT(-S) US 133 in-lbNFX24-MFT(-S) 90 in-lbNF24-MFT US 60 in-lbLF24-MFT(-S) US 35 in-lbLF24-MFT(-S)-20 US 35 in-lb TF24-MFT US 18 in-lb

Non-Spring Return Actuators

GMX24-MFT 360 in-lbAMX24-MFT 180 in-lb NMX24-MFT 90 in-lbLMX24-MFT 45 in-lbAMQX24-MFT 140 in-lbNMQX24-MFT 70 in-lbLMQX24-MFT 35 in-lbAHX24-MFT 101 lbfAHQX24-MFT-100 44 lbfLHX24-MFT 34 lbfLHQX24-MFT-100 22 lbfLUX24-MFT 27 in-lb

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 4: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

7

Pre-Set MFT Confi gurations Pulse Width Modulation Control

ApplicationHow the MFT actuator performs is determined by the configuration (P-10001, A01). The old generation actuators used a P-code (P-10001). The new generation actuators use a shorter 3 digit code. This shorter code is displayed on the reorder number.

P-2000… configuration types are used for Pulse Width Modulation control outputs. Most D.D.C. controllers have digital outputs which incorporate a default PWM range.

This enables a D.O. to be used as a proportional output when needed. Simply select the appropriate configuration code according to your application.

Wiring Diagram

W04

1MFT

PWM, Triac Source and Sink

Spring Return Actuators

AFX24-MFT(-S) 180 in-lb

AF24-MFT(-S) US 133 in-lb

NFX24-MFT(-S) 90 in-lb

NF24-MFT US 60 in-lb

LF24-MFT(-S) US 35 in-lb

LF24-MFT(-S)-20 US 35 in-lb

TF24-MFT US 18 in-lb

Non-Spring Return Actuators

GMX24-MFT 360 in-lb

AMX24-MFT 180 in-lb

NMX24-MFT 90 in-lb

LMX24-MFT 45 in-lb

AH24-MFT 101 lbf

LH24-MFT 44 lbf

LUX24-MFT 27 in-lb

Select Configuration

Configuration Code Input Range Position Feedback Running Time Torque % Adaptation

Puls

e W

idth

Mod

ulat

ion

P-20001 W01 0.59 to 2.93 sec 2.0 to 10.0 VDC 150 100 MANUAL

P-20002 W02 0.02 to 5.00 sec 2.0 to 10.0 VDC 150 100 MANUAL

P-20003 W03 0.10 to 25.50 sec 2.0 to 10.0 VDC 150 100 MANUAL

P-20004 W04 0.10 to 25.60 sec 2.0 to 10.0 VDC 150 100 MANUAL

P-20005 W05 0.10 to 5.20 sec 0.5 to 5.0 VDC 150 100 MANUAL

P-20012 W12 0.50 to 25.50 sec 0.5 to 10.0 VDC 150 100 MANUAL

P-20013 W13 0.50 to 2.93 sec 0.5 to 5.0 VDC 150 100 MANUAL

P-20014 W14 0.10 to 10.00 sec 2.0 to 10.0 VDC 150 100 MANUAL

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 5: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

8

Spring Return Actuators

AFX24-MFT(-S) 180 in-lb AF24-MFT(-S) US 133 in-lb NFX24-MFT(-S) 90 in-lbNF24-MFT US 60 in-lbLF24-MFT(-S) US 35 in-lbLF24-MFT(-S)-20 US 35 in-lb

TF24-MFT US 18 in-lb

Non-Spring Return Actuators

GMX24-MFT 360 in-lbAMX24-MFT 180 in-lb NMX24-MFT 90 in-lbLMX24-MFT 45 in-lbAHX24-MFT 101 lbfLHX24-MFT 34 lbf

LUX24-MFT 27 in-lb

Wiring Diagram

(1) Common

(2) + Hot

(3) Y Input

(5) U Output

Position Feedback

COMHot

Controller

Line Volts

24 VAC Transformer (AC only)

CCW CW

1

4

5

2

6

…MFT A

B

3

Diode may be placed at the control panel. Reduces field wiring

Triac Sink Wiring

W04

2A

NOTE: Diode is internal on new generation spring return and non-spring return type actuators, connect to controller using wires 3 & 4.

Pre-Set MFT Confi gurations Floating Point Control

ApplicationHow the MFT actuator performs is determined by the configuration (P-10001, A01). The old generation actuators used a P-code (P-10001). The new generation actuators use a shorter 3 digit code. This shorter code is displayed on the reorder number.

P-3000… configuration types are used for floating point control outputs. In this application MFT actuators offer constant running time and standard feedback options. A IN4004 or IN4007 diode is required for original spring return actuators only.

Wiring Diagram

W04

2_08

Floating PointNOTE: Diode is internal on new generation spring and non-spring return type actuators, connect to

controller using wires 3 & 4.

Select Configuration

Configuration Code Input Range Position Feedback Running Time Torque % Adaptation

Floa

ting

Poin

t Con

trol

P-30001 F01 Floating Point 2.0 to 10.0 VDC 150 100 MANUAL

P-30002 F02 Floating Point 0.5 to 10.0 VDC 150 100 MANUAL

P-30003 F03 Floating Point 2.0 to 10.0 VDC 100 100 MANUAL

P-30004 F04 Floating Point 0.5 to 5.0 VDC 100 100 MANUAL

P-30005 F05 Floating Point 0.5 to 10.0 VDC 100 100 MANUAL

P-30006 F06 Floating Point 0.5 to 5.0 VDC 150 100 MANUAL

P-30007 F07 Floating Point 2.0 to 10.0 VDC 300 100 MANUAL

P-30008 F08 Floating Point 2.0 to 10.0 VDC 75 100* MANUAL

P-30009 F09 Floating Point 2.0 to 10.0 VDC 85 100* MANUAL

P-30010 F10 Floating Point 0.5 to 2.5 VDC 150 100 MANUAL* Reduced torque in Spring Return (see page 19)

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 6: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

9

Pre-Set MFT Confi gurations On/Off Control, P-4000… (J…)

ApplicationHow the MFT actuator performs is determined by the configuration (P-10001, A01). The old generation actuators used a P-code (P-10001). The new generation actuators use a shorter 3 digit code. This shorter code is displayed on the reorder number.

P-4000… configuration types are used for on/off control outputs. The configuration allows for service replacement of on/off actuators when a true on/off actuator is not available.

In addition the MFT actuator offers additional functionality in the on/off mode, such as configuration P-40003 with minimum position and 2 to 10 VDC feedback.

Wiring Diagram

(1) Common

(2) Hot

(3) Y Input

(5) U Output

Line Volts

24 VAC/DC Transformer

CCW CW

…MFT

aPosition

Feedback VDC (+)

(–)

p j y

W04

3

On/Off

Spring Return Actuators

AFX24-MFT(-S) 180 in-lb AF24-MFT(-S) US 133 in-lb

NFX24-MFT(-S) 90 in-lb

NF24-MFT US 60 in-lb

LF24-MFT(-S) US 35 in-lb

TF24-MFT US 18 in-lb

Non-Spring Return Actuators

GMX24-MFT 360 in-lb

AMX24-MFT 180 in-lb

NMX24-MFT 90 in-lb

LMX24-MFT 45 in-lb

AMQX24-MFT 140 in-lb

NMQX24-MFT 70 in-lb

LMQX24-MFT 35 in-lb

AHX24-MFT 101 lbf

AHQX24-MFT-100 44 lbf

LHX24-MFT 34 lbf

LHQX24-MFT-100 22 lbf

LUX24-MFT 27 in-lb

Select Configuration

Configuration Code Input Range Position Feedback Running Time Torque % Adaptation

On/O

ff Co

ntro

l P-40001 J01 On/Off 2.0 to 10.0 VDC 75 100* MANUAL

P-40002 J02 On/Off 2.0 to 10.0 VDC 150 100 MANUAL

P-40003 J03 On/Off 2.0 to 10.0 VDC 75 100* MANUAL

P-40004 J04 On/Off 0.5 to 5.0 VDC 100 100 MANUAL

P-40005 J05 On/Off 0.5 to 10.0 VDC 100 100 MANUAL* Reduced torque in Spring Return (see page 19)

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 7: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

10

Multi-Function Technology®

Operation

Control Accuracy and Stability(GM / AM / NM / LM / AH / LH / LU / GR / AR / LR)

Belimo non-spring return actuators are designed with a unique non-symmetrical deadband. The actuator follows an increasing or decreasing control signal with a 75 mV resolution. If the signal changes in the opposite direction, the actuator will not respond until the control signal changes by 175 mV. This allows these actuators to track even the slightest deviation very accurately, yet allowing the actuator to “wait” for a much larger change in control signal due to control signal instability.

SatisfiedControl Position

MinimumControl Resolution

75 mV

Actuator responds to a 75 mV signal whennot changing direction from stop position.

SatisfiedControl Position

Minimum ReversedControl Deadband

Prior to Normal Control175 mV

Actuator responds to a 175 mV signal whenreversing direction from stop position.

Control Accuracy and Stability(AF / NF / LF / TF)

The …MFT US actuators are designed with a unique non-symmetrical deadband. The actuator follows an increasing or decreasing control signal with a 80 mV resolution. If the signal changes in the opposite direction, the actuator will not respond until the control signal changes by 200 mV. This allows these actuators to track even the slightest deviation very accurately, yet allowing the actuator to “wait” for a much larger change in control signal due to control signal instability.

All MFT actuators have built-inbrushless DC motors which provide better accuracy and longer service life.

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 8: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

11

Multi-Function Technology®

Operation

Control Accuracy and Stability(AMQ / NMQ / LMQ / AHQ / LHQ)

Belimo Quick Running non-spring return actuators are designed with a unique non-symmetrical deadband. The actuator follows an increasing or decreasing control signal with a 40 mV resolution. If the signal changes in the opposite direction, the actuator will not respond until the control signal changes by 100 mV. This allows these actuators to track even the slightest deviation very accurately, yet allowing the actuator to “wait” for a much larger change in control signal due to control signal instability.

SatisfiedControl Position

MinimumControl Resolution

40 mV

Actuator responds to a 40 mV signal whennot changing direction from stop position.

SatisfiedControl Position

Minimum ReversedControl Deadband

Prior to Normal Control100 mV

Actuator responds to a 100 mV signal whenreversing direction from stop position.

All Belimo actuators have built-inbrushless DC motors which provide better accuracy and longer service life.

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 9: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

12

Multi-Function Technology®

Operation

Motion Parameter Variables Description

New Generation AF 70 to 220 seconds Running time is selectable allowing for customizing the actuator for the application at hand. Adjustable running time allows for:• Matching HVAC system sequence of operation.• Improving control loop stability.• Reducing actuating noise (slower running).• Retrofit applications

The running time is constant and independent of load.

New Generation NF 40 to 220 seconds

Runn

ing

Tim

e

AF / NF / LF / TF 75 to 300 seconds

GM 75 to 300 seconds

AM* 90 to 350 seconds

NM* 45 to 150 seconds

AH* 75 to 150 seconds

LM* 35 to 150 seconds

LH* 75 to 150 seconds

LU 75 to 150 seconds

Rota

tion

Direction of Rotation Default or Reversed The direction of rotation can be "Direct" or "Reverse" acting of the control signal. The direction of rotation is selected from a CW and CCW switch located on the actuator.

An alternative method of changing the direction of rotation is to use the PC-Tool software. This option allows you to make remote set-up corrections without having the need to be at the actuator.

Selection of the direction of rotation is only possible via the PC-Tool software or manually with the switch on the actuator. Selection via a preset configuration is not an option.

IntermediatePosition Control(Override Control)

• Minimum Position (Default 0%)• Intermediate Position (Default 50%)• Maximum Position (Default 100%)

Intermediate Positions are achieved through ‘forced override’ positions.

SEE FIGURE A – FORCED OVERRIDES.

All intermediate settings are adjustable from 0 to 100%. Programmed as default, these control positions are possible by using the wiring diagram in FIGURE A. The override functions can be used as a means to test the actuator’s functionality during equipment servicing or troubleshooting.Intermediate positions can also be integrated into the control circuit as a part of the sequence of operation.

The Min, Mid, and Max positions can be used in any MFT control mode.

• VDC: For stand-alone controllers where a minimum position is needed.• PWM: Eliminate add-on accessories.• Floating Point: New functionality to a common application.• On/Off: New functionality to a common application.

– Satisfy combustion air requirements or boiler sequencing with O/A damper.– Eliminates secondary minimum position dampers.

* Quicker running actuators are available. Contact Belimo Customer Service for details.

FIGURE A – Forced Overrides

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 10: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

13

Multi-Function Technology®

Operation

Motion Parameter Variables Description

Adaptation OFF When the manual override button is depressed, and released, the actuator will perform synchronization. The actuator will simply drive to the mechanical zero position and return to its last control position.

ON – Manual The default setting for adaptation is “ON – Manual”.

When the ON-Manual setting is selected, adaptation is initiated by:

• Pressing the manual override button twice (GM / AM / NM / LM).• Clicking the CW/CCW switch twice (AF, NF, LF and TF).

When adaptation is selected, (On-Manual or Automatic) the actuator will drive one full cycle to its mechanical end stops OR the valves mechanical seats. Upon completion of this cycle the actuators working range (input, feedback and running time) will be adapted to the actual mechanical angle of rotation.

ON – Automatic When the ON-Automatic setting is selected at every power-up the actuator will automatically adapt to the mechanical angle of rotation. Also upon pressing the manual override button or CW/CCW switch, adaptation is initiated (See above).

Mec

hani

cal R

elat

ions

hip Sound and

Running TimeAll Actuators As the speed of the actuator increases, there is an increase in the sound

power level.

Torque and Running Time

Original Spring Return (AF / NF / LF) Though the running time remains constant, at approximately the 100-second range there is a loss in output torque. This is due to the association of runtime to torque. To gain a faster running time there is a loss in torque.SEE FIGURE B.

FIGURE B – Torque and Run Time

Torque and Run Time, LF24-MFT US

TORQUE [in-lb]

150

Running time [s]

26

35

75 100

100 % torque rr curve

NOTE: All new generation spring return and non-spring return actuators are torque independent of speed.

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 11: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

14

Specifi cations Parameter Variables Description

Alarms - Fault A fi xed voltage of 8.5 VDC is present when Alarm ‘sounds’.

Hunting Alarm criteria: Actuator is hunting due to unstable control loop.

This fault occurs when the ratio of Active time to Operating time exceeds 20%.

Operating time: Total number of hours connected to power supply Active time: Total number of hours the actuator is in mechanical motion.

Mechanical Overload Alarm criteria: Actuator is in a position and not responding to the control input. An alarm will ‘sound’ when an object or circumstance is preventing the motion of the actuator, damper or valve. The actuator has initiated its own overload protection after a period of 13 seconds.

Mechanical Travel Alarm criteria: Actuator is adapted to the working angle of a damper or to the stroke of a valve and is less than 95-degree actuator rotation (eg. 75° adapted angle). An alarm will ‘sound’ when the actuator detects a mechanical travel difference of 10% above the adapted angle (eg. 82.6°).

Alarm - Maintenance A fi xed voltage of 5.5 VDC is present when Alarm ‘sounds’.

Mechanical load limit(Non-Sprlng Return Only)

Alarm criteria: The torque load of the application has exceeded the actuator’s torque.

A typical scenario – the torque requirements has increased due to:

• Lack of lubrication • Increased fl ow• Improper installation• Damage• Dirt and debris build-up

The alarm ‘sounds’ when the specifi ed torque rating of the actuator has been exceeded for a period of 5 seconds.

Multi-Function Technology®

Specifi cations/Descriptions

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 12: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

15

Multi-Function Technology®

Specifi cations/Defi nitions

Service Parameter Variables DescriptionDi

spla

ys

Identifi cation Serial Number Displays the actuators internal serial number.

Actuator Type / Software Version Displays the actuator nomenclature (AFX24-MFT US) and MFT software version.

Assembly Location Displays the where the actuator was assembled.

Setpoint Displays the actual control input position as a percentage. As signal input changes you will see the setpoint percentage change accordingly.

Actual Values Actual Position Displays the actual position as a percentage. As the setpoint changes the actual position percentage will increase or decrease accordingly. If the actuator is capable of rotating the damper or valve, this can be of benefi t when troubleshooting an application.

Function Control Type & Setting Displays the actual control type and operating range.

Feedback Type & Setting Displays the actual feedback signal type and operating range.

Torque % Setting Displays the actual torque setting, as a percentage of minimum torque.

Running Time Displays the actual running time as programmed in seconds.

Direction of Rotation Displays the status of the direction of rotation option (Normal or Reversed).

Min, Mid, Max Position Displays the actual position setting of the Intermediate position control.

Adaptation Displays the actual setting of the adaptation function (OFF, ON-Manual, ON-Automatic).

Sensitivity / Hysteresis Displays the actual setting of the sensitivity (Normal or Reduced).

Synchronization Displays the actual setting of the synchronization function (Normal, Sync at 0%, Sync at 100%).

Data Log Total Time / Operating Time Total number of hours the actuator is connected to a power supply.

Active Time Total number of hours the actuator is in motion.

Stop / Go Ratio (Hunting %) Displays a percentage the total number of hours the actuator has spent in mechanical motion, comparing the total time to the active time.

Sensitivity Normal, Reduced Displays the setting of the sensitivity function.

Func

tions

Messages Displays all messages present. Messages can be deleted as well.

Function Test This function enables you to check for complete opening and closing of the actuator.

The test report contains:• Information on the Project• Identifi cation on the Actuator• A list of fault messages pending before the start of the test• The test steps and results• The current actuator settings

This is of benefi t when troubleshooting an application, as the actuator will drive the damper or valve. This gives an opportunity to observe the installation to identify any possible problems.

Adaptation See Adaptation on page 13. Initiates the adaptation feature of the MFT actuator. The actuators working range (input, feedback, and running time) will be adapted to the actual angle of rotation.

This is of benefi t when troubleshooting an application, as the actuator will drive the damper or valve. This gives you an opportunity to observe the installation to identify any possible problems.

Synchronization Normal At initial commissioning, when the manual override button is pressed, the actuator runs to a default position defi ned by the position of the CW/CCW direction of rotation switch.

Sync at 0% At each power-up (includes power failures), the actuator runs to a default position defi ned by the position of the CW/CCW direction of rotation switch.

Sync at 100% At each power-up (includes power failures), the actuator runs to a default position of the CW/CCW direction of rotation switch.

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 13: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

16

Multi-Function Technology®

Wiring

WARNING The wiring technician must be trained and experienced with electronic circuits. Disconnect power supply before attempting any wiring connections or changes. Make all connections in

accordance with wiring diagrams and follow all applicable local and national codes. Provide disconnect and overload protection as required. Use copper, twisted pair, conductors only. If using electrical conduit, the attachment to the actuator must be made with flexible conduit.

Always read the controller manufacturer's installation literature carefully before making any connections. Follow all instructions in this literature. If you have any questions, contact the controller manufacturer and/or Belimo.

Transformer(s)

Non-spring return actuators require a 24 VAC class 2 transformer and draws a maximum of 5 VA per actuator. The actuator enclosure cannot be opened in the field, there are no parts or components to be replaced or repaired.

– EMC directive: 89/336/EEC – Software class A: Mode of operation type 1 – Low voltage directive: 73/23/EEC

CAUTION: It is good practice to power electronic or digital controllers from a separate power transformer than that used for actuators or other end devices. The power supply design in our actuators and other end devices use half wave rectification. Some controllers use full wave rectification. When these two different types of power supplies are connected to the same power transformer and the DC commons are connected together, a short circuit is created across one of the diodes in the full wave power supply, damaging the controller. Only use a single power transformer to power the controller and actuator if you know the controller power supply uses half wave rectification.

Typical Transformer SizingActuator Series Voltage Required VA Per Actuator New Generation AF 24 10*Original AF 24 10New Generation NF 24 9**Original NF 24 6LF 24 6TF 24 4GMB/GRB 24 7 AMB/ARB 24 6 NMB 24 6 LMB/LRB 24 5 AHB 24 6LHB 24 5 LUB 24 5 AMQB 24 18 NMQB 24 18 LMQB 24 18 AHQB 24 18 LHQB 24 18 * @ 70 second run time** @ 40 second run time

Multiple Actuators, One Transformer

Multiple actuators may be powered from one transformer provided the following rules are followed:1. The TOTAL current draw of the actuators (VA rating) is less than or equal to

the rating of the transformer.2. Polarity on the secondary of the transformer is strictly followed. This means

that all No. 1 wires from all actuators are connected to the common leg on the transformer and all No. 2 wires from all actuators are connected to the hotleg. Switching wire No. 1 & 2 on one leg of the transformer will result in erratic operation or failure of the actuator and/or controls.

Multiple Actuators, Multiple Transformers

Multiple actuators positioned by the same control signal may be powered from multiple transformers provided the following rules are followed:1. The transformers are properly sized.2. All No. 1 wires from all actuators are tied together and tied to the negative leg

of the control signal. See wiring diagram on page 11.

Wire Lengths for Actuators

Keep power wire runs below the lengths listed in the Figure H. If more than one actuator is powered from the same wire run, divide the allowable wire length by the number of actuators to determine the maximum run to any single actuator.

Example: 3 actuators, 16 Ga wire 350 Ft ÷ 3 Actuators = 117 Ft. Maximum wire run

LH-24…/LU-24… LM-24.../CM24Wire Size Max. Feet. Wire Size Max. Feet16 Ga 1175 Ft. 16 Ga 1125 Ft.18 Ga 1075 Ft. 18 Ga 750 Ft. 20 Ga 575 Ft. 20 Ga 400 Ft.22 Ga 300 Ft. 22 Ga 200 Ft.

NM-24…/AH-24…/LMX120… AM-24...Wire Size Max. Feet. Wire Size Max. Feet12 Ga 1250 Ft. 12 Ga 1150 Ft.14 Ga 1130 Ft. 12 Ga 925 Ft. 16 Ga 900 Ft. 16 Ga 550 Ft.18 Ga 575 Ft. 18 Ga 375 Ft.20 Ga 300 Ft. 20 Ga 200 Ft.22 Ga 150 Ft. 22 Ga 100 Ft.

GM…/NMX120…/AMX120…Wire Size Max. Feet. Wire Size Max. Feet12 Ga 1125 Ft. 18 Ga 325 Ft.14 Ga 800 Ft. 20 Ga 175 Ft. 16 Ga 500 Ft. 22 Ga 90 Ft.

FIGURE H – Maximum Wire Lengths

Wire Type and Wire Installation Tips

For most installations, 18 or 16 Ga. cable works well with the non-spring return actuators. Use code-approved wire nuts, terminal strips or solderless connectors where wires are joined. It is good practice to run control wires unspliced from the actuator to the controller. If splices are unavoidable, make sure the splice can be reached for possible maintenance. Tape and/or wire-tie the splice to reduce the possibility of the splice being inadvertently pulled apart.

The non-spring return proportional actuators have a digital circuit that is designed to ignore most unwanted input signals (pickup). In some situations the pickup may be severe enough to cause erratic running of the actuator. For example, a large inductive load (high voltage AC wires, motors, etc.) running near the power or control wiring may cause excessive pickup. To solve this problem, make one or more of the following changes:1. Run the wire in metallic conduit.2. Re-route the wiring away from the source of pickup.3. Use shielded wire (Belden 8760 or equal). Ground the shield to an earth

ground. Do not connect it to the actuator common.

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 14: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

17

Multi-Function Technology®

Wiring

ATTENTION Master-Slave is the correct method for wiring multiple Belimo MFT actuators to a single load. For example, you can have up to three AFX24-MFT on a single damper jackshaft or two GMX24-MFT on a large butterfly valve.

The current Belimo solution is to mount multiple actuators onto the damper or valve. In the past this required the installer to wire the actuators in a “master-slave” arrangement. This was typical for the AF24-SR US actuator.

By adding more actuators you can effectively increase the torque proportional to the minimum specified torque times the number of actuators. This is normal as seen on the following installations.

• Large dampers or valves • Rack and Pinion style globe valves• Large multiple section dampers • Ball or Butterfly valves

Multiple actuators mounted to one control shaftModel Max. Qty Per Shaft Torque GeneratedAFX24-MFT(-S) 3 432 in-lbNFX24-MFT(-S) 1 90 in-lbLF24-MFT(-S) US 1 35 in-lbGMX24-MFT 2 640 in-lbAMX24-MFT 1 180 in-lbNMX24-MFT 1 90 in-lbLMX24-MFT 1 45 in-lbGKX24-MFT 2 720 in-lb

The wiring method for multiple actuators mounted to shafts which are not mechanically connecting other actuators is to wire the control signal in parallel with each actuator.

Multiple XM24-MFT95…

EXCEPTION No mechanical dual mounting of AFX24-MFT US is possible. Electrical parallel wiring of AFX24-MFT95 is possible only for mechanically separate applications.

SOLUTION For increased torque requirement use AFX24-MFT95 as a master and the slave must be an AFX24-MFT. The masters feedback must match the slaves input signal. (Both are default 2-10 VDC.)

Wiring Diagrams

1 Provide overload protection and disconnect as required.

2 CAUTION Equipment damage!Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed.

3 Actuators may also be powered by 24 VDC.

5Control signal may be pulsed from either the Hot (source)or the Common (sink) 24 VAC line.

The ZG-R01 500 Ω resistor may be used.

WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may

be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

#

W04

8_08

Wiring multiple …MFT actuators to one shaft.All MFT actuators are wired in master-slave confi guration.

Wiring of multiple …MFT actuators on valves must be master-slave (wires 3-5).

MFT actuator confi gurations should also co-ordinate with each other.Meaning the master input = controllers output. Master output = slave input. Slave output = controller input.

W21

4_08

Controller Output Master Feedback Slave Input Slave Feedback0.1 to 25.5 sec 2 to 10 VDC 2 to 10 VDC 0 to 5 VDC

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 15: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

18

Multi-Function Technology®

Wiring Diagrams

Spring Return Actuator with MFT

VDC / 4 to 20mA Two Position PWM

Original AF, NF, LF, TF

New Generation AF, NF

Floating Point Override control to min, mid, max positions W425_08

Non-Spring Return Actuator with MFT

VDC / 4 to 20mA Two Position PWM

Floating Point Override control to min, mid, max positions W426_08

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 16: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

19

0 to 135 Ω Control (MFT95)

Override

Wiring multiple actuators to a Series 90 controller

Typical wiring diagrams for multiple actuators used with the W973, W7100 and T775 controllers.

Wiring multiple actuators to a Series 90 controller using a minimum position potentiometer

Low Limit Control

High Limit Control

Multi-Function Technology®

Wiring Diagrams

AF24-MFT95 US Wire Colors

1=Black 3=White 5=White

2=Red 4=White 6=White

AFX24-MFT95 and Non-Spring Return Wire Colors

1=Black 3=White 5=Gray

2=Red 4=Pink 6=Orange

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 17: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

20

Programmable Code Running Time Control Range Feedback Feedback Range Obsolete Code MP Bus Logo AdaptionA01 150s 2...10V U5 U5 2...10V P-10001 NO manualA02 150s 0.5...10V U5 U5 0.5…10V P-10002 NO manualA03 150s 2...10V U5 U5 0.5…5V P-10003 NO manualA04 150s 4...7V U5 U5 2…10V P-10004 NO manualA05 150s 6...9V U5 U5 2…10V P-10005 NO manualA06 150s 10.5...13.5V U5 U5 2…10V P-10006 NO manualA07 150s 0.5...5V U5 U5 2…10V P-10007 NO manualA08 150s 0.5...5V U5 U5 0.5…10V P-10008 NO manualA09 150s 5...10V U5 U5 2…10V P-10009 NO manualA10 150s 5...10V U5 U5 0.5…10V P-10010 NO manualA11 150s 0.5...5V U5 U5 0.5…5V P-10011 NO manualA12 150s 0.5...5V U5 U5 0.5…2.5V P-10012 NO manualA13 150s 0.5...10V U5 U5 2…10V P-10013 NO manualA14 100s 0.5…10V U5 U5 0.5…2.5V P-10014 NO manualA15 150s 2…5V U5 U5 2…10V P-10015 NO manualA16 150s 2…6V U5 U5 2…10V P-10016 NO manualA17 150s 6…10V U5 U5 2…10V P-10017 NO manualA18 150s 14…17V U5 U5 2…10V P-10018 NO manualA19 100s 2...10V U5 U5 2...10V P-10019 NO manualA20 150s 9...12V U5 U5 2...10V P-10020 NO manualA21 150s 2…10V U5 U5 0.5…5V P-10021 NO manualA22 150s 0.5…4.9V U5 0.5…4.9V P-10022 NO manualA23 150s 5.1…10V U5 5.1…10V P-10023 NO manualA24 150s 0.5…24V U5 U5 2...10V P-10024 NO manualA25 76s 2...10V U5 U5 2...10V P-10025 NO manualA26 150s 2…9V U5 U5 2...10V P-10026 NO manualA27 150s 5…9V U5 U5 2...10V P-10027 NO manualA28 PICCV ONLY 100s 0.5...10V U5 U5 0.5…10V P-10028 NO manualA29 150s 1…3V U5 U5 2...10V P-10029 NO manualA30 150s 3…9V U5 U5 2...10V P-10030 NO manualA31 150s 0.5…4V U5 U5 2...10V P-10031 NO manualA32 150s 6…14V U5 U5 2...10V P-10032 NO manualA33 150s 4…14V U5 U5 2...10V P-10033 NO manualA34 120s 2...10V U5 U5 2...10V P-10034 NO manualA35 78s 2...10V U5 U5 2...10V P-10035 NO manualA37 120s 0.5...10V U5 U5 0.5…10V P-10037 NO manualA38 150s 6...13V U5 U5 2...10V P-10038 NO manualA39 150s 10...14V U5 U5 2...10V P-10039 NO manualA40 150s 1...16V U5 U5 2...10V P-10040 NO manualA41 150s 3...6V U5 U5 2...10V P-10041 NO manualA42 75s 0.5…10V U5 U5 2...10V P-10042 NO manualA43 150s 0.5…2.5V U5 U5 2...10V P-10043 NO manualA44 150s 7…10V U5 U5 2...10V P-10044 NO manualA45 150s 13...17V U5 U5 2...10V P-10045 NO manualA46 150s 2...10V U5 U5 2...10V P-10046 NO manualA47 150s 0.5…20V U5 U5 2...10V P-10047 NO manualA48 150s 1…5V U5 U5 1…5V P-10048 NO auto-adapt.A49 150s 1…5V U5 U5 1…5V P-10049 NO auto-adapt.A51 P-10051A52 150s 2...10V U5 U5 0.5…5V P-10052 NO manualA53 120s 0.5…10V U5 U5 2...10V P-10053 NO manualA54 150s 0.5…2.5V U5 U5 0.5…2.5V P-10054 NO manualA55 75s 2…5V U5 U5 2...10V P-10055 NO manualA56 75s 6…9V U5 U5 2...10V P-10056 NO manualA57 150s 2…5.5V U5 U5 2...10V P-10057 NO manualA58 150s 6.5…10V U5 U5 2...10V P-10058 NO manualA59 150s 0.5…6V U5 U5 2...10V P-10059 NO manualA60 300s 2…10V U5 U5 2...10V P-10060 NO manualA61 150s 10…20V U5 U5 2...10V P-10061 NO manualA62 90s 2…10V U5 U5 2...10V P-10062 NO manualA63 150s 0.5…4.5V U5 U5 0.5…4.5V P-10063 NO manualA64 150s 5.5…10V U5 U5 5.5…10V P-10064 NO manualA65 150s 1…5V U5 U5 1…5V P-10065 NO manual

Multi-Function Technology®

MFT VDC Proportional Control Program Codes

*Note: Not every code works with every acuator

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 18: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

21

A66 150s 2…10V U5 U5 1…5V P-10066 NO manualA67 150s 2…8V U5 U5 2…10V P-10067 NO manualA68 150s 2…13V U5 U5 2…10V P-10068 NO manualA69 150s 1..4V U5 U5 2…10V P-10069 NO manualA70 150s 3.5…10V U5 U5 2…10V P-10070 NO manualA71 150s 2…15V U5 U5 2…10V P-10071 NO manualA72 95s 2…10V U5 U5 2…10V P-10072 NO manualA73 150s 6…18V U5 U5 2…10V P-10073 NO manualA74 150s 2…10V U5 U5 2…10V P-10074 NO manualA76 150s 0.5…3V U5 U5 0.5…10V P-10076 NO manualA77 76s 0.5…10V U5 U5 0.5…10V P-10077 NO manualA78 150s 2…10V U5 U5 0.5…10V P-10078 NO manualA79 150s 0.5…10V U5 U5 0.5…5V P-10079 NO manualA80 150s 0.5…3.5 U5 U5 2…10V P-10080 NO manualA81 150s 4.5…10 U5 U5 2…10V P-10081 NO manualA82 150s 3…10V U5 U5 2…10V P-10082 NO manualA83 150s 5…15V U5 U5 2…10V P-10083 NO manualA84 150s 13…20V U5 U5 2…10V P-10084 NO manualA85 150s 2…10V U5 U5 2…10V P-10085 NO manualA86 150s 5…10.5 U5 2…10V P-10086 NO manualA88 150s 2…10V U5 U5 2…10V P-10088 NO manualA89 150s 12.5…22V U5 U5 2…10V P-10089 NO manualA90 150s 2…5V U5 U5 2…5V P-10090 NO manualA91 95s 2…10V U5 U5 2…10V P-10091 NO manualA92 150s 0.5…15V U5 U5 0.5…10V P-10092 NO manualA93 150s 2…10V U5 U5 2…10V P-10093 NO manualA94 85s 2…10V U5 U5 2…10V P-10094 NO manualA95 150s 0.5…5V U5 U5 0.5…5V P-10095 NO manualA96 150s 0.5…10V U5 U5 2…10V P-10096 NO manualA97 150s 5.25…7.25 U5 U5 2…10V P-10097 NO manualA98 150s 2…10V U5 U5 2…10V P-10098 NO auto-synch.A99 150s 2…10V U5 U5 2…10V P-10099 NO manualAA0 150s 0.5…12.85 U5 U5 2…10V P-10100 NO manualAA1 150s 3…15V U5 U5 2…10V P-10101 NO manualAA2 150s 0.5…14V U5 U5 2…10V P-10102 NO manualAA4 150s 0.5…22V U5 U5 2…10V P-10104 NO manualAA5 150s 0.5…4V U5 U5 0.5…5V P-10105 NO manualAA6 150s 6…10V U5 U5 0.5…5V P-10106 NO manualAA7 150s 2…7V U5 U5 2…10V P-10107 NO manualAA8 150s 4…10V U5 U5 2…10V P-10108 NO manualAA9 P-10109AAA 150s 2…22V U5 U5 2…10V P-10110 NO manualAAB 150s 0.5…20V U5 U5 0.5…10V P-10111 NO manualAAC 150s 0.5….29V U5 U5 2…10V P-10112 NO manualAAD 100s 0.5…4.5V U5 U5 0.5…4.5V P-10113 NO manualAAE 100s 5.5…10V U5 U5 5.5…10V P-10114 NO manualAAF 150s 0.5…28V U5 U5 2…10V P-10115 NO manualAAG 75s 0.5…10V U5 U5 2…10V P-10116 NO auto-adapt.AAH 150s 0.5…10V U5 U5 4…5V P-10117 NO auto-adapt.AAJ 100s 2…6V U5 U5 2…10V P-10118 NO auto-adapt.AAK 100s 6…10V U5 U5 2…10V P-10119 NO manualAAL 150s 8…20V U5 U5 2…10V P-10120 NO manualAAM 120s 0.5…10V U5 U5 2…10V P-10121 NO auto-synch.AAN 100s 0.5…10V U5 U5 2…10V P-10122 NO manualAAP 150s 2…10V U5 U5 2…10V P-10123 NO manualAAR 150s 2…10V U5 U5 2…10V P-10124 NO auto-adapt.AAS 150s 2…10V U5 U5 2…10V P-10125 NO manualAAT 20s 2…10V U5 U5 2…10V --- NO manualAAU 100s 6…9V U5 U5 2…10V --- NO manualAAV 150s 1.2…6V U5 U5 2…10V --- NO manualAAWAAX 35s 2…10V U5 U5 2...10V P-10130 NO manualAC0 45s 2…10V U5 U5 2...10V P-10131 NO manual

Programmable Code Running Time Control Range Feedback Feedback Range Obsolete Code MP Bus Logo Adaption

Multi-Function Technology®

MFT VDC Proportional Control Program CodesM

4003

5 - 0

5/10

- Su

bjec

t to

chan

ge. ©

Bel

imo

Airc

ontro

ls (U

SA),

Inc.

Page 19: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

22

AC1 90s 2…10V U5 U5 2...10V P-10132 NO manualAC2 150s 0.5…10V U5 U5 0.5…10V --- NO manual000 150s 2…10V U5 U5 2...10V --- YES manualAC4 150s 0.5…10V U5 U5 0.5…10V --- YES manualAC5 75s 2…10V U5 U5 2…10V P-10133 NO manualAC6 450s 2…10V U5 U5 2…10V P-10134 NO manualAC7 150s … U5 U5 2...10V --- NO manualAC8 35s 0.5…10V U5 U5 0.5...10V --- NO manualAC9 45s 0.5…10V U5 U5 0.5...10V --- NO manualACA 90s 0.5…10V U5 U5 0.5...10V --- NO manualACX 150s 2...10V U5 U5 0.5...10V NO manualAD0 100s 0.5...5V U5 U5 2...10V P-10135 NO manualAD1 100s 5…10V U5 U5 2...10V P-10136 NO manualAD2 90s 2…10V U5 U5 2...10V --- NO auto-adapt.AD3 35s 2…10V U5 U5 2...10V --- NO auto-adapt.AD4 150s 2…10V U5 U5 2...10V --- NO manualAD5 100s 2...5V U5 U5 2...10V P-10137 NO manualAD6AD7 100s 0.5...5V U5 U5 2...10V P-10140 NO manualAD8AD9ADA PICCV ONLY 100s 0.5...10V U5 U5 0.5…10V --- NO manualADCADD 150s 9…13V U5 U5 2...10V --- NO manualADEADFADGADHADJADKADLADMADNADPADRADSADTADUADVADW 70s 2...10V US US 2...10V --- NO manualADX 40s 2...10V US US 2...10V --- NO manualAE0AE1AE2AE3

Multi-Function Technology®

MFT VDC Proportional Control Program Codes

Programmable Code Running Time Control Range Feedback Feedback Range Obsolete Code MP Bus Logo Adaption

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 20: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

23

AE4AE5AE6AE7AE8AE9AEA 120s 0.5…10V U5 U5 0.5…10V --- NO manualAEC 75s 0.5…10V U5 U5 0.5…10V --- NO manualAED 300s 0.5…10V U5 U5 0.5…10V --- NO manualAEE 450s 0.5…10V U5 U5 0.5…10V --- NO manualAEFAEGAEHAEJAEKAELAEMAENAEPAERAESAETAEUAEVAEWAEXAF0

Multi-Function Technology®

MFT VDC Proportional Control Program Codes

Programmable Code Running Time Control Range Feedback Feedback Range Obsolete Code MP Bus Logo Adaption

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 21: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

24

Programmable Code Running Time Control Range Feedback Feedback Range Obsolete Code MP Bus Logo AdaptionR01 150s 0…135 Ohm U5 U5 2…10V P-16001 NO manualR02 150s 0…135 Ohm U5 U5 0.5…10V P-16002 NO manualR03 150s 0…135 Ohm U5 U5 0.5…5V P-16003 NO manualR04 75s 0…135 Ohm U5 U5 2…10V P-16004 NO manualR05 100s 0…135 Ohm U5 U5 0.5…10V P-16028 NO manualR06 P-16029R07 35s 0…135 Ohm U5 U5 2…10V NO manualR08 45s 0…135 Ohm U5 U5 2…10V NO manualR09 90s 0…135 Ohm U5 U5 2…10V NO manualR0A 37s 0…135 Ohm U5 U5 2…10V NO manualR0CR0DR0ER0FR0GR0HR0JR0KR0LR0MR0NR0PR0RR0SR0TR0UR0VR0WR0XR10R11

Multi-Function Technology®

MFT 95 (Honeywell Series 90, 0-135Ω) Program Codes

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 22: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

25

Multi-Function Technology®

MFT PWM (Pulse Width Modulation) Program Codes

Programmable Code Running Time Control Range Feedback Feedback Range Obsolete Code MP Bus Logo AdaptionW01 150s 0.59…2.93s U5 U5 2…10V P-20001 NO manualW02 150s 0.02…5s U5 U5 2…10V P-20002 NO manualW03 150s 0.1…25.5s U5 U5 2…10V P-20003 NO manualW04 150s 0.1…25.6s U5 U5 2…10V P-20004 NO manualW05 150s 0.1…5.2s U5 U5 0.5…5V P-20005 NO manualW06 150s 0.59…2.93s U5 U5 0.5…10V P-20006 NO manualW07 150s 0.02…5s U5 U5 0.5…5V P-20007 NO manualW08 150s 0.1…10s U5 U5 2…10V P-20008 NO manualW09 150s 1…11s U5 U5 2…10V P-20009 NO manualW10 150s 0.02…5s U5 U5 2…10V P-20010 NO manualW11 150s 0.02…5.6s U5 U5 2…10V P-20011 NO manualW12 150s 0.5…25.5s U5 U5 2…10V P-20012 NO manualW13 150s 0.5…2.93s U5 U5 2…10V P-20013 NO manualW14 150s 0.1…10s U5 U5 2…10V P-20014 NO manualW15 150s 1…11s U5 U5 2…10V P-20015 NO manualW16 150s 0.02…5s U5 U5 2…10V P-20016 NO auto-adapt.W17 150s 0.02…5.6s U5 U5 2…10V P-20017 NO auto-adapt.W18 150s 0.1…25.5s U5 U5 2…10V P-20018 NO auto-adapt.W19 150s 0.02…2.5s U5 U5 2…10V P-20019 NO manualW20 150s 2.7…5s U5 U5 2…10V P-20020 NO manualW21 150s 0.1…5.2s U5 U5 2…10V P-20021 NO manualW22 150s 0.1…12.85s U5 U5 2…10V P-20022 NO manualW23 150s 5.1…10.1s U5 U5 2…10V P-20023 NO manualW24 150s 0.59…1.76s U5 U5 2…10V P-20024 NO manualW25 150s 1.76…2.93s U5 U5 2…10V P-20025 NO manualW26 150s 0.02…12s U5 U5 2…10V P-20026 NO manualW27 150s 0.02…14s U5 U5 2…10V P-20027 NO manualW28 150s 12.5…22s U5 U5 2…10V P-20028 NO manualW29 150s 0.5…12.85s U5 U5 2…10V P-20029 NO manualW30 150s 0.1…24s U5 U5 2…10V P-20030 NO manualW31 100s 0.02…5s U5 U5 Ω2…10V P-20031 NO offW32 100s 0.1…25.5 U5 U5 2…10V P-20032 NO offW33 150s 0.2…25.5 U5 U5 2…10V P-20033 NO manualW34 100s 0.59…2.93s U5 U5 2…10V P-20034 NO offW35 150s 5.5…9.5s U5 U5 2…10V P-20035 NO manualW36 150s 0.5…4.5s U5 U5 2…10V P-20036 NO manualW37 150s 0.1…5.2s U5 U5 0.5…10V P-20037 NO manualW38 150s 0.02…6s U5 U5 2…10V P-20038 NO manualW39 150s 0.59…2.93s U5 U5 2…10V P-20039 NO auto-adapt.W3A 150s 0.5…5.0s U5 U5 2…10V P-20040 NO auto-adapt.W3C 150s 0.1...25.5s U5 U5 2...10V --- NO manualW3D 150s 0.2...5.2s U5 U5 2...10V P-20041 NO manualW3EW3FW3GW3HW3JW3KW3LW3MW3NW3PW3RW3SW3TW3UW3VW3WW3XW40W41

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 23: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

26

Programmable Code Running Time Control Range Feedback Feedback Range Obsolete Code MP Bus Logo AdaptionF01 150s --- U5 U5 2…10V P-30001 NO manualF02 150s --- U5 U5 0.5…10V P-30002 NO manualF03 100s --- U5 U5 2…10V P-30003 NO manualF04 100s --- U5 U5 0.5…5V P-30004 NO manualF05 100s --- U5 U5 0.5…10V P-30005 NO manualF06 150s --- U5 U5 0.5…5V P-30006 NO manualF07 300s --- U5 U5 2…10V P-30007 NO manualF08 75s --- U5 U5 2…10V P-30008 NO manualF09 85s --- U5 U5 2…10V P-30009 NO manualF10 150s --- U5 U5 0.5…6V P-30010 NO manualF11 75s --- U5 U5 0.5…5V P-30011 NO manualF13 120s --- U5 U5 0.5…10V P-30013 NO manualF14 90s --- U5 U5 2…10V P-30014 NO manualF15 150s --- U5 U5 0.5…4.5V P-30015 NO manualF16 150s --- U5 U5 1…5V P-30016 NO manualF17 90s --- U5 U5 1…10V P-30017 NO manualF18 60s --- U5 U5 2…10V --- NO manualF19 45s --- U5 U5 2…10V --- NO manualF1A 35s --- U5 U5 2…10V --- NO manualF1CF1DF1EF1FF1G 120s --- U5 U5 2...10V --- NO manualF1H 450s --- U5 U5 2…10V --- NO manualF1JF1KF1LF1MF1NF1PF1RF1SF1TF1UF1VF1WF1XF20F21

Multi-Function Technology®

MFT Floating Point Program Codes

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 24: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

27

Programmable Code Running Time Control Range Feedback Feedback Range Obsolete Code MP Bus Logo AdaptionJ01 75s --- U5 U5 2…10V P-40001 NO manualJ02 150s --- U5 U5 2…10V P-40002 NO manualJ03 75s --- U5 U5 2…10V P-40003 NO manualJ04 100s --- U5 U5 0.5…5V P-40004 NO manualJ05 100s --- U5 U5 0.5…10V P-40005 NO manualJ06 120s --- U5 U5 2…10V P-40006 NO manualJ07 45s --- U5 U5 2…10V P-40007 NO manualJ08 200s --- U5 U5 2…10V P-40008 NO manualJ09 120s --- U5 U5 0.5…10V P-40009 NO manualJ10 300s --- U5 U5 2…10V P-40010 NO manualJ11 150s --- U5 U5 0.5…10V P-40011 NO manualJ13 100s --- U5 U5 0.5…5V P-40012 NO manual (off)J14J15J16J17J18J19J1AJ1CJ1DJ1EJ1FJ1GJ1HJ1JJ1KJ1LJ1MJ1NJ1PJ1RJ1SJ1TJ1UJ1VJ1WJ1XJ20J21

Multi-Function Technology®

MFT On/Off Program CodesM

4003

5 - 0

5/10

- Su

bjec

t to

chan

ge. ©

Bel

imo

Airc

ontro

ls (U

SA),

Inc.

Page 25: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

28

Programmable Code Running Time Control Range Feedback Feedback Range Obsolete Code MP Bus Logo AdaptionT01 2.5s 2…10V U5 U5 2...10V --- NO manualT02 4s 2…10V U5 U5 2...10V --- NO manualT03 7s 2…10V U5 U5 2...10V --- NO manualT04 10s 2…10V U5 U5 2...10V --- NO manualT05 15s 2…10V U5 U5 2...10V --- NO manualT06 20s 2…10V U5 U5 2...10V --- NO manualT07 2.5s 0.5…10V U5 U5 0.5...10V --- NO manualT08 4s 0.5…10V U5 U5 0.5...10V --- NO manualT09 7s 0.5…10V U5 U5 0.5...10V --- NO manualT0A 10s 0.5…10V U5 U5 0.5...10V --- NO manualT0C 15s 0.5…10V U5 U5 0.5...10V --- NO manualT0D 20s 0.5…10V U5 U5 0.5...10V --- NO manualT0ET0FT0GT0HT0JT0KT0LT0MT0NT0PT0RT0ST0TT0UT0VT0WT0XT10T11

Multi-Function Technology®

MFT Quick Actuators Proportional Control Program Codes

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 26: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

29

Multi-Function Technology®

MFT Special Control (Non-Spring Return Only) Program Codes

Programmable Code Running Time Control Range Feedback Feedback Range Obsolete Code MP Bus Logo AdaptionS01 150s Phasecut U5 U5 2…10V NO manualS02 35s Phasecut U5 U5 2…10V NO manualS03 45s Phasecut U5 U5 2…10V NO manualS04 90s Phasecut U5 U5 2…10V NO manualS05S06 150s 4…20mA U5 U5 2…10V NO manualS07S08 45s 4…20mA U5 U5 2…10V NO manualS09 90s 4…20mA U5 U5 2…10V NO manualS0AS0C 75s 4…20mA U5 U5 2…10V NO manualS0D 75s Phasecut U5 U5 2…10V NO manualS0ES0FS0GS0HS0JS0KS0LS0MS0NS0PS0RS0SS0TS0US0VS0WS0XS10S11

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 27: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

30

Programmable Code Running Time Control Range Feedback Feedback Range Obsolete Code MP Bus Logo AdaptionN01 150s 2…10V U5 U5 2...10V V-10001 NO manualN02 150s 0.5…10V U5 U5 0.5…10V V-10002 NO manualN03 150s 2…10V U5 U5 0.5…5V V-10003 NO manualN04 150s 4…7V U5 U5 2...10V V-10004 NO manualN05 150s 6…9V U5 U5 2...10V V-10005 NO manualN06 150s 10.5…13.5V U5 U5 2...10V V-10006 NO manualN07 150s 0.5…5V U5 U5 2...10V V-10007 NO manualN08 150s 0.5…5V U5 U5 0.5…10V V-10008 NO manualN09 150s 5…10V U5 U5 2...10V V-10009 NO manualN10 150s 5…10V U5 U5 0.5…10V V-10010 NO manualN11 150s 0.5…5V U5 U5 0.5…5V V-10011 NO manualN12 150s 0.5…5V U5 U5 0.5…2.5V V-10012 NO manualN13 150s 0.5…10V U5 U5 2...10V V-10013 NO manualN14 150s 0.5…10V U5 U5 0.5…2.5V V-10014 NO manualN15 150s 2…5V U5 U5 2...10V V-10015 NO manualN16 150s 2…6V U5 U5 2...10V V-10016 NO manualN17 150s 6…10V U5 U5 2...10V V-10017 NO manualN18 150s 14…17V U5 U5 2...10V V-10018 NO manualN19 100s 2…10V U5 U5 2...10V V-10019 NO manualN1A 150s 5.1…10V U5 U5 5.1...10V V-10023 NO manualN1C 75s 2…10V U5 U5 2...10V V-10025 NO manualN1D 150s 5…9V U5 U5 2...10V V-10027 NO manualN1E 100s 0.5…10V U5 U5 0.5…10V V-10028 NO manualN1F 150s 3…6V U5 U5 2...10V V-10041 NO manualN1G 150s 0.5…2.5V U5 U5 2...10V V-10043 NO manualN1H 150s 7…10V U5 U5 2...10V V-10044 NO manualN1J 150s 0.5…20V U5 U5 2...10V V-10047 NO manualN1K 150s 0.5…4.5V U5 U5 0.5…4.5V V-10063 NO manualN1L 150s 5.5…10V U5 U5 5.5…10V V-10064 NO manualN1M 150s 2…15V U5 U5 2...10V V-10071 NO manualN1N 76s 0.5…10V U5 U5 0.5…10V V-10077 NO manualN1P 75s 2…6V U5 U5 2...10V V-10078 NO manualN1R 75s 6…10V U5 U5 2...10V V-10079 NO manualN1S 150s 3…7V U5 U5 2...10V V-10082 manualN1T 150s 0.59…2.93s U5 U5 2...10V V-20001 NO manualN1U 150s 0.02…5s U5 U5 2...10V V-20002 NO manualN1V 150s 0.1…25.5s U5 U5 2...10V V-20003 NO manualN1W 150s 0.1…25.6s U5 U5 2...10V V-20004 NO manualN1X 150s 0.1…5.2s U5 U5 0.5…5V V-20005 NO manualN20 150s 0.59…2.93s U5 U5 0.5…5V V-20006 NO manualN21 150s 0.02…5s U5 U5 2...10V V-20007 NO manualN22 150s 0.1…5.2s U5 U5 2...10V V-20021 NO manualN23 150s 0.5…4.5s U5 U5 2...10V V-20040 NO manualN24 150s --- U5 U5 2...10V V-30001 NO manualN25 150s --- U5 U5 0.5…10V V-30002 NO manualN26 150s --- U5 U5 0.5…5V V-30006 NO manualN27 75s --- U5 U5 2...10V V-30008 NO manualN28 75s --- U5 U5 2...10V V-40001 NO manualN29 150s --- U5 U5 2...10V V-40002 NO manualN30 100s --- U5 U5 0.5…5V V-40004 NO manualN3A 100s --- U5 U5 0.5…10V V-40005 NO manual

Multi-Function Technology®

MFT NV/NVF Proportional Control Program Codes

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.

Page 28: Spring Return Actuator Product Range Multi-Function Technology · 2017-06-26 · Spring Return Actuator Product Range Multi-Function Technology Cable Options Running Rime Power

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

31

Multi-Function Technology®

SY-MFT

Programmable Code Loss of Control Signal Input Signal Feedback Output SignalACE stop 2…10V U5 U5 2...10VACF stop 0.5…10V U5 U5 0.5...10VACG stop 4…20mA U5 U5 4…20mAACH stop 4…20mA U5 U5 2...10VACJ open 2…10V U5 U5 2...10VACK open 0.5…10V U5 U5 0.5...10VACL open 4…20mA U5 U5 4…20mAACM open 4…20mA U5 U5 2...10VACN close 2…10V U5 U5 2...10VACP close 0.5…10V U5 U5 0.5...10VACR close 4…20mA U5 U5 4…20mAACS close 4…20mA U5 U5 2...10VW3E** stop 0.02-5.00 seconds PWM U5 U5 2...10V

Note: Runtime is fixed based on actuator model.**Available only on -24MFT models.

M40

035

- 05/

10 -

Subj

ect t

o ch

ange

. © B

elim

o Ai

rcon

trols

(USA

), In

c.