steam systems basics, challenges and troubleshooting john cilyo senior account executive spirax...
TRANSCRIPT
![Page 1: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/1.jpg)
Steam Systems Basics, Challenges and
Troubleshooting
John Cilyo
Senior Account Executive Spirax Sarco Inc.
For Steve Jalowiec, PE, CHFM
![Page 2: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/2.jpg)
Steam Systems & Chaos Theory
In mathematics, chaos theory describes the behavior of certain dynamic systems – that is, systems whose states evolve with time – that may exhibit dynamics that are highly sensitive to initial conditions (popularly referred to as the butterfly effect). As a result of this sensitivity, which manifests itself as an exponential growth of perturbations in the initial conditions, the behavior of chaotic systems appears to be random. This happens even though these systems are deterministic, meaning that their future dynamics are fully defined by their initial conditions with no random elements involved. This behavior is known as deterministic chaos, or simply chaos.
![Page 3: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/3.jpg)
Steam Systems & the 2nd Law
Second Law of Thermodynamics• The entropy of an isolated system not in equilibrium
will tend to increase over time, approaching a maximum value at equilibrium.
• In a simple manner, the second law states "energy systems have a tendency to increase their entropy rather than decrease it." This can also be stated as "heat can spontaneously flow from a higher-temperature region to a lower-temperature region, but not the other way around." (Heat can flow from cold to hot, but not spontaneously—- for example, when a refrigerator expends electrical power.)
• A way of thinking about the second law for non-scientists is to consider entropy as a measure of disorder. So, for example, a broken cup has less order (more entropy) than an intact one, and it is more difficult to repair a broken cup (reducing its entropy) than to break an intact one (increasing its entropy). Likewise, solid crystals, the most organized form of matter, have very low entropy values; and gases, which are very disorganized, have high entropy values.
![Page 4: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/4.jpg)
Basic Steam System
![Page 5: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/5.jpg)
Another view of a Steam System
BOILER
Steam Header
Condensate ReturnPiping
LoadsRadiators, SterilizersHeat Exchangers, etc
Condensate Return Tank
Deaerator
(Treated) Make up water
Steam Traps
![Page 6: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/6.jpg)
Steam System Basics• Boiler Design
• Water Tube, smaller steam space, need to be run closer to design pressure
• Fire Tube, large steam chest, can be run a lower than design pressure.
• Definitions• "Carryover" means that you have a problem with the TDS (total
dissolved solids). You need to properly define the PPM values needed. Fire tube boilers have a normal TDS of 3000 ppm, while water tube designs need 2000 ppm. Everyone uses the 3000 ppm value regardless of boiler type and that is their first mistake.
• "Priming" is a mechanical condition caused by too great of a takeoff velocity (50 to 100fpm).This is corrected mechanically.
• Testing• With the boiler running, take a condensate sample from a drip pocket on
the main header. If you see a high TDS value (say 2000 PPM), you have a carryover issue. If your value is 5 ppm or is immeasurable, you have priming. Remember, steam has no TDS!
![Page 7: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/7.jpg)
Steam systems have many end uses in hospitals; radiators, heat exchangers,
humidification but probably none as critical as Steam Sterilizers
![Page 8: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/8.jpg)
Your Objectives(Challenges)
•Deliver good quality steam to heating, humidification and process equipment.
•Operate the system safely.
•Get maximum efficiency from heating equipment - energy $$$
•Maintain the system at a reasonable cost.
![Page 9: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/9.jpg)
Steam Has Another Objective In Mind!
(Challenges)•Condenses anywhere and everywhere
it can.
•Happily fills the system with air, in the worst possible locations.
•Carries entrained water, gases, chemicals and dirt into every nook and cranny.
•Will slow down and stop flowing as soon as differential pressure is lost.
![Page 10: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/10.jpg)
Your Mission Is To Stay Ahead of Potential Problems
(Challenges)
• Test/maintain steam traps routinely.• Clean strainers!• Clean and maintain regulators/control valves• Routine maintenance of condensate pumps.• Keep an ear open for excess pipe-line water-
hammer & correct the root-cause.• Watch for repeat instances of valve wire-draw
& correct root-cause (wet steam, valve sizing)• Recognize that water hammer in heat
exchangers and heating coils is correctable.
![Page 11: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/11.jpg)
No problem – right?All it takes is money and
manpower!Anyone here have enough of both?
But there is help:•Boiler Water Treatment Company
•Steam Specialty Companies
•Steam Consultants
•Some of these can help for free, some will cost.
Challenges
![Page 12: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/12.jpg)
Steam System Challenges• Remember Steam Systems are dynamic systems
• Never Steady State• Loads coming on and off
• Sterilizers
• Heating coils
• Steam Absorption Chillers
• Manual Building Heat (Old fashion radiators)
• System Sizing• Sized for steady state or instantaneous loads
(sterilizers)
![Page 13: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/13.jpg)
Steam System Troubleshooting
Myths• My boilers never carry over, prime, etc.• The water level is always steady in the gauge
glass.• I don’t need trap maintenance, failed traps
will become apparent on their own. (The water hammer will tell me about a bad trap.)
• Boiler water treatment is a scam.• Boiler blow-down wastes energy and water.
![Page 14: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/14.jpg)
Steam System TroubleshootingSteam System Chemistry
• Feed Water Quality•Softener•Deaerator
– Dissolved O2 and non-condensable gases
•Chemical Treatment• Totaled Dissolved Solids (TDS)
•Blow down• Continuous Surface• Bottom Blow Down
![Page 15: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/15.jpg)
Test TypicalLimitsLow/Hi
Softener Feedwater Boiler Condensate Return
Deaerator
pH See chart > 8.5 8.3 – 9.4
Sulfite % So2(Higher in lay-up)
30/60 XX XX
Alkalinity P 200/400 XX
Alkalinity M 250/500
Silica Monitor trends
< 150 mg/L
XX XX
Conductivity 3000/3500 XX XX XX
Calcium < 0.3/FW XX XX XX
Iron < 0.1/FW XX XX
Copper < 0.05/FW XX XX
PrimaryTreatment Chem.
Permfg
XX
Dissolved O2 7 ppb XX
Typical Steam System Chemistry
(May vary with chemical supplier and boiler manufacturer)
![Page 16: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/16.jpg)
Status Polytreat
TL-200
Sulfite
as SO3
Alkalinity
P M
pH
Silica Conductivity Calcium Iron Copper
Boiler 2 Lead 18.5 110 370 510 - 77.6 2886(N) -
Boiler 3 Open - - - - - - - -
Softener 2 6.0 129 0.17
Pwr. Plnt. cond. 8.60 45 0.05 0.03 0.03
MR1 cond. - - - - -
Kitchen Dish.
condensate
- - -
Sub base. large - - -
Feedwater 3.6 8.35 2.2 72 0.26 0.10 0.03
Recommended Low/ High Limits
__10__
20
_30_
60
_200
_ 400
_250
_ 500
_8.0_
8.5
Record
__3000__
3500
_< .3_
FW
_< .1_
FW
_< .05_
FW
Courtesy of Barclay Water Management, Inc.
Typical Boiler Water Treatment Test Report (partial)
![Page 17: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/17.jpg)
Steam System Troubleshooting• Water Level Control
• Sight glass levels are not reliable• Variable feed versus on/off
• Steam Flow Metering & Data• Data is invaluable for system troubleshooting
“
You cannot manage what you cannot measure”
Lord Kelvin
![Page 18: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/18.jpg)
Why is proper condensate drainage important?
![Page 19: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/19.jpg)
Water hammer!
Result of a drip trap being removed, that was draining a 100 psig line, before a valve
![Page 20: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/20.jpg)
Steam System Troubleshooting•Steam Traps
•Properly located
•Drip Legs properly sized
•Trap Selection and sizing
•Steam Trap Testing & Maintenance
![Page 21: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/21.jpg)
Steam System Troubleshooting• Steam Traps
• Main Header Main header drip legs are full size
• Other drip legs are properly sized• Drips located 300’ or less and any change of
elevation• Drip stations located ahead of automatic
valves• Steam traps are properly sized• Steam traps are working and maintained• Missing insulation
• heat goes to cold• another consequence of the 2nd law thermodynamics!
![Page 22: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/22.jpg)
![Page 23: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/23.jpg)
Ineffective vs Proper Drain Ineffective vs Proper Drain PointsPoints
Condensate
Steam Trap SetFull
Diameter Pocket
Cross Section
Cross Section
Steam Trap Set
Steam Flow
Steam Flow
CorrectCorrect
IncorrectIncorrect
![Page 24: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/24.jpg)
Steam System Troubleshooting
Steam Trap Testing• Visual *
• Temperature **
• Ultrasonic ***
• Continuous monitoring systems ****• conductivity
![Page 25: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/25.jpg)
Steam System Troubleshooting•Belts & suspenders
• Steam separators & filters
Wet Steam
Dry Steam
Condensate Outlet
![Page 26: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/26.jpg)
Example: Process requires 4,645,000 Btu’s / hr
Available: 30 psig steam @ 274oF
@ 100% Dry (saturated) steam supplies 929 Btu / lb. process requires 5,000 lb/hr.
@ 90% Dryness Fraction, steam supplies 836 Btu/lb. process now requires 5556 lb /hr. A 11% Increase
@ 80% Dryness Fraction, steam supplies 743 Btu/lb process now requires 6251 lb /hr. A 25% increase
Steam Conditioning Dry Steam saves energy
![Page 27: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/27.jpg)
Steam System Troubleshooting
•Condensate equipment operating properly• Pumps• Flash tanks
•Loads• Varying loads• Instantaneous loads - Sterilizers
![Page 28: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/28.jpg)
Steam System Troubleshooting Now what do I do
If you suddenly have problems• What has changed?• Go back to basics
•Start at the boiler plant and work your way out into the system
•Left Hand Analysis
![Page 29: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/29.jpg)
Courtesy of Walt Graham Thermo Diagnostics, Co, LLC
![Page 30: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/30.jpg)
Now what do I do
• Steam Trap Repairs• Steam Trap Survey & Assessment• Steam Trap Maintenance Program• Boiler Water Treatment Modification• Steam Conditioning Equipment
• Separators• Filters
• Repair damaged insulation• Steam Metering (for troubleshooting)
![Page 31: Steam Systems Basics, Challenges and Troubleshooting John Cilyo Senior Account Executive Spirax Sarco Inc. For Steve Jalowiec, PE, CHFM](https://reader035.vdocument.in/reader035/viewer/2022062223/55156cf455034685568b5f91/html5/thumbnails/31.jpg)
Thank you!• Questions or Comments
• Special Thanks to – John Cilyo, Spirax Sarco– William Wethey, Barclay Water Management
• Contact Information– Steve Jalowiec, PE, CHFM– Waterbury Hospital, 64 Robbins Street,
Waterbury CT– Work 203-573-7197– Cell 203-228-3480