storage s v s v building s v s v s v sub 87.6 concrete ...€¦ · hv connecivity has been amended...

5
UNIVERSITY PL UNIVERSITY AVE CONCRETE FOOTPATH CONCRETE FOOTPATH HV LV 1400mm CENTER TO CENTER PL 0.0 PL 0.0 250 SON T2049 250 SON T1503 400 MBF T2050 400 MBF T2051 250 SON T1482 400 MBF T1484 400 MBF T952 250 SON T1485 400 MBF T2055 250 SON T1486 250 SON T2056 250 SON 487 0 MBF T2057 250 SON AR 06 95AL ABC 95AL ABC 3x22 & 1x15 LE LE-4300 LE-4501 LE-281 LE-4538 LE-4216 LE-10166 LE-10167 LE-4 LE-4215 LE-10168 LE-4213 LE-4214 LE-10169 LE-4212 LE-10171 LE-4211 LE-10172 4210 LE-10173 WARNING NOTE - AT JOINT BAY HV CONNECIVITY HAS BEEN AMENDED TO REFLECT SYSTEM DIAGRAM DUE TO CABLE DETAILS NOT BEING VERIFIED IN THE FIELD. 95AL ABC 25 AL2 ABC A,B,C 7 TW2 95AL ABC 3x22 & 1x15 7 TW2 7 TW2 25AL ABC A,B,C 1x7 7 TW4 7 TW4 7 TW4 1x7 7 TW2 2x7 2x7 7 TW4 4x15 A,B,C 1x7 1x7 4x15 A,B,C 1x7 2x7 A 2x7 4x15 A,B,C 4x15 A,B,C 1x7 4x15 A,B,C x7 X X X X STORAGE BUILDING BAXTERS LODGE ARUNDEL ST PARRAMATTA RD UNIVERSITY PL D UNIVERSITY AVE UNIVERSITY PL H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V LE-10170 T2054 400 MBF T2053 400 MBF NR 250 SON S V S V S V S V S V S V S V S V S V S V S V S V CONCRETE FOOTPATH 3m 6m 10m CONCRETE FOOTPATH HV LV 1 PROTECTION BOLLARDS 1400mm CENTER TO CENTER H V H V H V H V H V PL 0.0 PL 0.0 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X U H V H V H V H V H V H V H V H V H V H V H V H V H V H V H H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V H V A1 20160817 CONSULTING ENGINEERS NORTH SYDNEY, NSW 2060 AUSTRALIA 60 MILLER STREET LEVEL 1 NAME: ALISON (YIQING) KONG ABN 29 003 234 571 T +61 2 9928 6800 F +61 2 9955 6900 www.ndy.com AUC: NDY MANAGEMENT PTY LTD - 2349 AUP No.2349/05 ID#: H60122769 APPROVED : BY V. D. 18/09/2017 CHECKED : BY V. D. 18/09/2017 DRAWN : BY A. K. 18/09/2017 REV 0 - ORIGINAL ISSUE APPROVED : BY V. D. 01/11/2017 CHECKED : BY V. D. 01/11/2017 DRAWN : BY A. K. 01/11/2017 REV 1 -1000A FUSE UPDATED TO 1200A s21586-279 A.KONG 2349/05 SUBMITTED 01/11/2017 CITY OF SYDNEY P14, K01 LE62 XCZ20224 SC09773 1 5 1 ESTABLISH L TYPE KIOSK SUB S78214 UNIVERSITY BARFF CCW MUSEUM UNIVERSITY OF SYDNEY CAMPERDOWN PROJECT LOCATION PLAN : SYDNEY UNI, CAMPERDOWN SYD UBD , P14 G01 SCALE N.T.S. THIS INFORMATION INCLUDES DATA FROM THE NSW DIGITAL CADASTRAL DATABASE BY /$1' $1' 3523(57< ,1)250$7,21 86(' 81'(5 &5($7,9( &200216 /,&(1&( VERSION 4.0. "FOR IDENTIFICATION AND JOINTING PURPOSES, ALL CABLE ENDS SHALL BE LABELLED AT THE TERMINATION LOCATIONS AND IN JOINT BAYS DURING CABLE INSTALLATION. THE CABLES MUST BE LABELLED AS PER CERTIFIED DESIGN DRAWING ." WARNING x THIS DESIGN CANNOT BE USED FOR CONSTRUCTION PURPOSES UNTIL THE LOCATION OF ALL EXISTING SERVICES IS VERIFIED. x THE INFORMATION PROVIDED IN THIS DESIGN MUST BE CHECKED ON SITE AND THE MOST CURRENT INFORMATION ON THE CONFIGERATION OF ALL SERVICES, INCLUDING AUSGRID'S NETWORK, MUST BE VERIFIED IMMEDIATLEY BEFORE CONSTRUCTION COMMENCES BY CONTACTING DIAL-BEFORE-YOU-DIG BY TELEPHONE ON 1100 OR AT www.1100.com.au. x DIAL-BEFORE-YOU-DIG INFORMATION MUST NOT BE OLDER THAN 20 BUSINESS DAYS AT THE TIME OF CONSTRUCTION. ASP LEVEL 2 WORK ALL LEVEL 2 ASP WORK DEPICTED ON THIS DRAWING IS SHOWN FOR INFORMATION PURPOSES ONLY AND DOES NOT FORM PART OF THE CERTIFIED DESIGN. NOTES x CLAIMS FOR VARIATIONS TO THE COST OF NON-CONTESTABLE WORKS, INCLUDING ROCK EXCAVATION, WILL NOT BE ACCEPTED UNLESS VERIFIED ON SITE BY AUSGRID WHILE THE WORKS ARE IN PROGRESS. x THE ASP1 IS RESPONSIBLE FOR UNDERTAKING SATISFACTORY CONSULTATION WITH ALL LOCAL CUSTOMERS WHO MAY POTENTIALLY BE AFFECTED BY THE CONSTRUCTION WORKS INCLUDING ALL ALTERATIONS TO SERVICE MAINS. x THE ASP/1 MUST MINIMISE THE IMPACT OF THE WORKS ON THE ELECTRICITY SUPPLY TO CUSTOMERS AND INTERRUPTIONS TO SUPPLY MUST BE AVOIDED WHEREVER POSSIBLE. AT LEAST FOUR (4) CLEAR BUSINESS DAYS NOTICE MUST BE PROVIDED TO ALL AFFECTED CUSTOMERS PRIOR TO ANY PLANNED INTERRUPTIONS TO THE ELECTRICITY SUPPLY. NOTICE MUST BE IN WRITING IN ACCORDANCE WITH CLAUSE 90 OF THE NATIONAL ENERGY RETAIL RULES. x SPECIFIC PRIOR APPROVAL MUST BE SOUGHT FROM AUSGRID FOR ANY PLANNED ELECTRICITY SUPPLY INTERRUPTIONS WHERE THE PLANNED INTERRUPTION WILL EXCEED ONE (1) HOUR IN DURATION OR THE DURATION WILL BE LESS THAN ONE HOUR, BUT A SUITABLE TIME FOR THE INTERRUPTION CANNOT BE MUTUALLY AGREED TO WITH THE AFFECTED CUSTOMER(S). x THE ASP/1 IS TO MAINTAIN ADEQUATE PUBLIC LIGHTING LEVELS FOR THE DURATION OF THE WORKS. IF NECESSARY, THE ASP/1 IS TO ARRANGE FOR SUITABLE TEMPORARY STREET LIGHTING TO BE PROVIDED UNTIL PERMANENT LIGHTING IS RE-ESTABLISHED. x FOR KIOSK AND CHAMBER TYPE SUBSTATIONS IN THE HUNTER AREAS, ARRANGE PHASING OF 11KV AND LOW VOLTAGE TRANSFORMER TERMINATIONS TO ACHIEVE DYN 11 INTERCONNECTION CAPABILITIES. x THE ASP/1 IS TO CO-ORDINATE THE MODIFICATION AND TESTING OF ANY REQUIRED PROTECTION RELAY WITH THE AUSGRID TECHNICAL SERVICES GROUP x THE ASP1 IS REQUIRED TO COMPLY WITH THE CORRECT PROCEDURE(S) FOR WORKING WITH AND/OR NEAR ASBESTOS MATERIAL (REFER TO AUSGRID NUS 211 - WORKING WITH ASBESTOS PRODUCTS). THE FOLLOWING AUSGRID ASSETS ARE REGISTERED AS CONTAINING ASBESTOS. x VEHICLE PROTECTION TO BE PROVIDED AS PER NS141. ALLOW FOR 4 X SHALLOW SURFACE MOUNT BOLLARDS. INSTALLED OUTSIDE OF SUBSTATION EASEMENT. INSTALLED OUTSIDE OF SUBSTATION EASEMENT. CENTURIAN C90SM OR EQUIVALENT APPROVED, POWDER-COATED SAFETY YELLOW. BOLLARDS TO BE REMOVABLE AND LOCKABLE x HANDRAIL IN ACCORDANCE WITH CURRENT NATIONAL CONSTRUCTION CODE/BUILDING CODE AUSTRALIA (NCC/BCA) & AUSROAD GUIDE TO ROAD DESIGN, TO BE PROVIDED IMMEDIATELY OUTSIDE OF PROPOSED SUBSTATION EASEMENT ON THE RETAINING WALL TO PREVENT FALLS DOWN BATTER. x VEHICLE PARKING TO BE PROVIDED FOR ALL AUSGRID STAFF TO CARRY OUT ALL WORKS. x FINISH SUBSTATION SITE AS PER NS141 CLAUSE 7.7. LEGEND POLE PRIVATE POLE STREET LIGHT POLE KIOSK SUB CHAMBER HV SUB BASE DUCT AUX UG LV UG LV JOINT LV UGOH LV POT END LV OH LV SWITCH LINK HV UG HV CABLE JOINT HV UGOH HV POT END HV SEALED END HV OH HV SWITCH LINK SL UG SL OH SV UG SV OH LV PILLAR LV SWITCHGEAR STREET LIGHT STREET LIGHT PEC EARTHING UG CABLE UG CABLE ABANDONED PROPOSED EXISTING REMOVE H V LEGEND L V S L S L A u x L V S V S V S V S V H V X X X P CONSTRUCTION PLAN C C B B A A D D E E AREA OF WORKS AREA OF WORKS PROPOSED CHAU CHAK WING MUSEUM NOTE: PROJECT SC08470, INSTALLATION OF S.77836 IS UNDER CONSTRUCTION. DESIGN IS BASED ON THAT PROJECT SC07013 IS 100% COMPLETE PL 0.0 PL 0.0 INSET A INSET B INSET A INSET B HV JOINT 24.0 EOP 29.5 HV JOINT 41.0 THREE TO ONE JOINT 67.2 THREE TO ONE JOINT 65.5 EOP 64.4 EOP 69.4 SUB 87.6 SUB 87.1 THREE TO ONE JOINT 65.5 EOP 69.4 THREE TO ONE JOINT 67.2 EOP 64.4 HV JOINT 24.0 EOP 29.5 HV JOINT 41.0 E E D D

Upload: others

Post on 10-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

U

N

IV

E

R

S

IT

Y

P

L

U

N

IV

E

R

S

IT

Y

A

V

E

CONCRETE FOOTPATH

C

O

N

C

R

E

T

E

F

O

O

T

P

A

T

H

H

V

L

V

1400mm CENTER TO CENTER

P

L

0

.0

P

L 0.0

T1504

250 SO

N

T2049

250 SO

N

T1503

400 MB

F

T2050

400 MB

F

T2051

250 SO

N

T1482

400 MB

F

T1484

400 MB

F

T952

250 SO

N

T1485

400 MB

F

T2055

250 SO

N

T1486

250 SO

N

T2056

250 SO

N

T1487

400 MB

F

T2057

250 SO

N A

R

13006

95AL A

BC

9

5

A

L

A

B

C

9

5

A

L

A

B

C

3x22 & 1x15

LE

-4299

LE

-4300

LE

-4501

LE

-281

LE

-4538

LE

-4216

LE

-10166

LE

-10167

LE

-4204

LE

-4203

LE

-4215

LE

-10168

LE

-4213

LE

-4214

LE

-10169

LE

-4212

LE

-10171

LE

-4211

LE

-10172

LE

-4210

LE

-10173

W

AR

NIN

G N

OTE

- A

T JO

INT B

AY

HV

CO

NN

EC

IVIT

Y H

AS

BE

EN

AM

EN

DE

D T

O R

EFLE

CT S

YS

TEM

DIA

GR

AM

DU

E T

O C

AB

LE D

ETA

ILS

NO

T BE

ING

VE

RIF

IED

IN T

HE

FIE

LD.

9

5

A

L

A

B

C

2

5

A

L

2

A

B

C

A

,B

,C

7 TW2

95AL A

BC

3x22 & 1x15

7

T

W

2

7 T

W2

25AL ABC A,B,C

1x7

7 TW4

7 T

W4

7

T

W

4

1x7

7 T

W2

2x7

2x7

7

T

W

4

4x15 A,B

,C

1x7

1x7

4x15 A,B,C

1x7

2x7 A

2x7

4x15 A,B,C

4x15 A,B,C

1

x

7

4x15 A,B,C

1

x

7

X

X

X

X

ST

OR

AG

E

BU

ILD

ING

BAXTERS

LODGE

ARUNDEL ST

PARRAMATTA RD

U

N

IV

E

R

S

IT

Y

P

L

S

C

IE

N

C

E

R

D

U

N

IV

E

R

S

IT

Y

A

V

E

U

N

IV

E

R

S

IT

Y

P

L

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

LE

-10170

T2054

400 MB

F

T2053

400 MB

F

NR

250 SO

N

S V

S V

S V

S V

S V

S V

S V

S V

S

V

S

V

S

V

S

V

CO

NC

RE

TE F

OO

TPA

TH

3m

6m

10m

C

O

N

C

R

E

T

E

F

O

O

T

P

A

T

H

H

V

L

V

1

PROTECTION BOLLARDS

1400mm CENTER TO CENTER

H

V

H

V

H

V

H

V

H

V

P

L

0

.0

PL 0.0

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

U

N

IV

E

R

S

IT

Y

A

V

E

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H V

H

V

H

V

H

V

H

V

H

V

A1

20160817

CONSULTING ENGINEERS

NORTH SYDNEY, NSW 2060

AUSTRALIA

60 MILLER STREET LEVEL 1

NAME: ALISON (YIQING) KONG

ABN 29 003 234 571

T +61 2 9928 6800

F +61 2 9955 6900

www.ndy.com

AUC: NDY MANAGEMENT PTY LTD - 2349

AUP No.2349/05

ID#: H60122769

AP

PR

OV

ED

: B

Y V

. D

. 18/09/2017

CH

EC

KE

D : B

Y V

. D

. 18/09/2017

DR

AW

N : B

Y A

. K

. 18/09/2017

RE

V 0 - O

RIG

IN

AL IS

SU

E

AP

PR

OV

ED

: B

Y V

. D

. 01/11/2017

CH

EC

KE

D : B

Y V

. D

. 01/11/2017

DR

AW

N : B

Y A

. K

. 01/11/2017

RE

V 1 -1000A

F

US

E U

PD

AT

ED

T

O

1200A

s21586-279

A.KONG

2349/05

SUBMITTED 01/11/2017

CITY OF SYDNEY

P14, K01

LE62

XCZ20224

SC097731 5 1

ESTABLISH L TYPE KIOSK SUB

S78214 UNIVERSITY BARFF

CCW MUSEUM

UNIVERSITY OF SYDNEY

CAMPERDOWN

PROJECT LOCATION PLAN : SYDNEY UNI, CAMPERDOWN SYD UBD , P14 G01

SCALE N.T.S.

THIS INFORMATION INCLUDES DATA FROM THE NSW DIGITAL CADASTRAL DATABASE BY

LAND AND PROPERTY INFORMATION © 2016, USED UNDER CREATIVE COMMONS LICENCE

VERSION 4.0.

"FOR IDENTIFICATION AND JOINTING PURPOSES, ALL CABLE ENDS SHALL BE LABELLED

AT THE TERMINATION LOCATIONS AND IN JOINT BAYS DURING CABLE INSTALLATION. THE

CABLES MUST BE LABELLED AS PER CERTIFIED DESIGN DRAWING ."

WARNING

THIS DESIGN CANNOT BE USED FOR CONSTRUCTION PURPOSES UNTIL THE LOCATION OF ALL EXISTING

SERVICES IS VERIFIED.

THE INFORMATION PROVIDED IN THIS DESIGN MUST BE CHECKED ON SITE AND THE MOST CURRENT

INFORMATION ON THE CONFIGERATION OF ALL SERVICES, INCLUDING AUSGRID'S NETWORK, MUST BE

VERIFIED IMMEDIATLEY BEFORE CONSTRUCTION COMMENCES BY CONTACTING DIAL-BEFORE-YOU-DIG

BY TELEPHONE ON 1100 OR AT www.1100.com.au.

DIAL-BEFORE-YOU-DIG INFORMATION MUST NOT BE OLDER THAN 20 BUSINESS DAYS AT THE TIME OF

CONSTRUCTION.

ASP LEVEL 2 WORK

ALL LEVEL 2 ASP WORK DEPICTED ON THIS DRAWING IS SHOWN FOR INFORMATION PURPOSES ONLY

AND DOES NOT FORM PART OF THE CERTIFIED DESIGN.

NOTES

CLAIMS FOR VARIATIONS TO THE COST OF NON-CONTESTABLE WORKS, INCLUDING ROCK EXCAVATION, WILL

NOT BE ACCEPTED UNLESS VERIFIED ON SITE BY AUSGRID WHILE THE WORKS ARE IN PROGRESS.

THE ASP1 IS RESPONSIBLE FOR UNDERTAKING SATISFACTORY CONSULTATION WITH ALL LOCAL CUSTOMERS

WHO MAY POTENTIALLY BE AFFECTED BY THE CONSTRUCTION WORKS INCLUDING ALL ALTERATIONS TO

SERVICE MAINS.

THE ASP/1 MUST MINIMISE THE IMPACT OF THE WORKS ON THE ELECTRICITY SUPPLY TO CUSTOMERS AND

INTERRUPTIONS TO SUPPLY MUST BE AVOIDED WHEREVER POSSIBLE. AT LEAST FOUR (4) CLEAR BUSINESS

DAYS NOTICE MUST BE PROVIDED TO ALL AFFECTED CUSTOMERS PRIOR TO ANY PLANNED INTERRUPTIONS TO

THE ELECTRICITY SUPPLY. NOTICE MUST BE IN WRITING IN ACCORDANCE WITH CLAUSE 90 OF THE NATIONAL

ENERGY RETAIL RULES.

SPECIFIC PRIOR APPROVAL MUST BE SOUGHT FROM AUSGRID FOR ANY PLANNED ELECTRICITY SUPPLY

INTERRUPTIONS WHERE THE PLANNED INTERRUPTION WILL EXCEED ONE (1) HOUR IN DURATION OR THE

DURATION WILL BE LESS THAN ONE HOUR, BUT A SUITABLE TIME FOR THE INTERRUPTION CANNOT BE

MUTUALLY AGREED TO WITH THE AFFECTED CUSTOMER(S).

THE ASP/1 IS TO MAINTAIN ADEQUATE PUBLIC LIGHTING LEVELS FOR THE DURATION OF THE WORKS. IF

NECESSARY, THE ASP/1 IS TO ARRANGE FOR SUITABLE TEMPORARY STREET LIGHTING TO BE PROVIDED UNTIL

PERMANENT LIGHTING IS RE-ESTABLISHED.

FOR KIOSK AND CHAMBER TYPE SUBSTATIONS IN THE HUNTER AREAS, ARRANGE PHASING OF 11KV AND LOW

VOLTAGE TRANSFORMER TERMINATIONS TO ACHIEVE DYN 11 INTERCONNECTION CAPABILITIES.

THE ASP/1 IS TO CO-ORDINATE THE MODIFICATION AND TESTING OF ANY REQUIRED PROTECTION RELAY WITH

THE AUSGRID TECHNICAL SERVICES GROUP

THE ASP1 IS REQUIRED TO COMPLY WITH THE CORRECT PROCEDURE(S) FOR WORKING WITH AND/OR NEAR

ASBESTOS MATERIAL (REFER TO AUSGRID NUS 211 - WORKING WITH ASBESTOS PRODUCTS). THE FOLLOWING

AUSGRID ASSETS ARE REGISTERED AS CONTAINING ASBESTOS.

VEHICLE PROTECTION TO BE PROVIDED AS PER NS141. ALLOW FOR 4 X SHALLOW SURFACE MOUNT BOLLARDS.

INSTALLED OUTSIDE OF SUBSTATION EASEMENT. INSTALLED OUTSIDE OF SUBSTATION EASEMENT. CENTURIAN

C90SM OR EQUIVALENT APPROVED, POWDER-COATED SAFETY YELLOW. BOLLARDS TO BE REMOVABLE AND

LOCKABLE

HANDRAIL IN ACCORDANCE WITH CURRENT NATIONAL CONSTRUCTION CODE/BUILDING CODE AUSTRALIA

(NCC/BCA) & AUSROAD GUIDE TO ROAD DESIGN, TO BE PROVIDED IMMEDIATELY OUTSIDE OF PROPOSED

SUBSTATION EASEMENT ON THE RETAINING WALL TO PREVENT FALLS DOWN BATTER.

VEHICLE PARKING TO BE PROVIDED FOR ALL AUSGRID STAFF TO CARRY OUT ALL WORKS.

FINISH SUBSTATION SITE AS PER NS141 CLAUSE 7.7.

LEGEND

POLE

PRIVATE POLE

STREET LIGHT POLE

KIOSK SUB

CHAMBER HV SUB

BASE DUCT

AUX UG

LV UG

LV JOINT

LV UGOH

LV POT END

LV OH

LV SWITCH LINK

HV UG

HV CABLE JOINT

HV UGOH

HV POT END

HV SEALED END

HV OH

HV SWITCH LINK

SL UG

SL OH

SV UG

SV OH

LV PILLAR

LV SWITCHGEAR

STREET LIGHT

STREET LIGHT PEC

EARTHING UG CABLE

UG CABLE ABANDONED

PROPOSED EXISTING REMOVE

H V

LEGEND

L V

S L

S L

A u x

L V

S V S V

S V S V

H V

X X X

P

CONSTRUCTION PLAN

C

C

B

B

A

A

D

D

E

E

A

R

E

A

O

F

W

O

R

K

S

A

R

E

A

O

F W

O

R

K

S

P

R

O

P

O

S

E

D

C

H

A

U

C

H

A

K

W

IN

G

M

U

S

E

U

M

NOTE: PROJECT SC08470, INSTALLATION

OF S.77836 IS UNDER CONSTRUCTION.

DESIGN IS BASED ON THAT PROJECT

SC07013 IS 100% COMPLETE

P

L

0

.0

PL 0.0

INSET A

INSET B

INSET A

INSET B

H

V

JO

IN

T 24.0

E

O

P

29.5

H

V

JO

IN

T 41.0

THREE TO ONE

JOINT 67.2

THREE TO ONE

JOINT 65.5

EOP 64.4

EOP 69.4

SUB 87.6

SUB 87.1

THREE TO

ONE

JOINT 65.5

EOP 69.4

THREE TO

ONE

JOINT 67.2

EOP 64.4

H

V

JO

IN

T

24.0

E

O

P

29.5

H

V

JO

IN

T

41.0

E

E

D

D

A1

20160817

CONSULTING ENGINEERS

NORTH SYDNEY, NSW 2060

AUSTRALIA

60 MILLER STREET LEVEL 1

NAME: ALISON (YIQING) KONG

ABN 29 003 234 571

T +61 2 9928 6800

F +61 2 9955 6900

www.ndy.com

AUC: NDY MANAGEMENT PTY LTD - 2349

AUP No.2349/05

ID#: H60122769

AP

PR

OV

ED

: B

Y V

. D

. 18/09/2017

CH

EC

KE

D : B

Y V

. D

. 18/09/2017

DR

AW

N : B

Y A

. K

. 18/09/2017

RE

V 0 - O

RIG

IN

AL IS

SU

E

AP

PR

OV

ED

: B

Y V

. D

. 01/11/2017

CH

EC

KE

D : B

Y V

. D

. 01/11/2017

DR

AW

N : B

Y A

. K

. 01/11/2017

RE

V 1 -1000A

F

US

E U

PD

AT

ED

T

O

1200A

s21586-279

A.KONG

2349/05

SUBMITTED 01/11/2017

CITY OF SYDNEY

P14, K01

LE62

XCZ020224

SC097732 5 1

ESTABLISH L TYPE KIOSK SUB

S78214 UNIVERSITY BARFF

CCW MUSEUM

UNIVERSITY OF SYDNEY

CAMPERDOWN

UNDERGROUND CONSTRUCTION WORKS SCHEDULE (DUCTPULL V1.1)

REF.

IDENTIFIER

ROUTE

DISTANCE

(m)

CIRCUIT

VOLTAGE

CONDUCTOR OR ASSET DETAIL

CONDUCTOR

CODE /

STOCK CODE

MIN. INTERNAL

BENDING

RADIUS (mm)

DURING

INSTALLATION

MIN. INTERNAL BENDING

RADIUS (mm)

AFTER INSTALLATION

CALCULATED MAX.

PULLING TENSION (kN)

DURING INSTALLATION

CONSTRUCTION DETAIL

A N/A N/A

KL TYPE KIOSK SUBSTATION (S.78214)

N/A N/A N/A N/A

INSTALL NEW 1000 kVA KL-TYPE SUBSTATION 78214 " UNIVERSITY BARFF" IN

ACCORDANCE WITH AUSGRID REQUIREMENTS AND DRAWING 151572.

A-B 24m 11KV

2 x 11 KV 300 CU 1 EPR 70 CU(WS) Z

YQ/TX/EA1400/10A

6 x 150mm CONDUIT BANK (4 SPARES)

1 x 63mm CONDUIT FOR FUTRE OPTIC FIBRE

PILOT CABLE USE (SPARE)

391 1335 890 3.63

INSTALL NEW 11KV300 CU 1 EPR 70 CU(WS) Z YQ / TX / EA1400/10A IN NEW 150mm

CONDUIT BANKS AS PER TRENCHING SECTIONS AND INSTALL NEW 63mm CONDUIT

FOR FUTURE OPTIC FIBRE PILOT CABLE USE

C N/A 11KV

HV THREE-TO-ONE JOINT POLYMERIC TO

POLYMERIC (HV 2-23)

177811 N/A N/A N/A

INSTALL THREE TO ONE JOINT BETWEEN POLYMERIC CABLES 11 KV 300 CU1 EPR 70

CU(WS) Z YQ/TX/EA1400/10A AND 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ

AT REF 'C'. STOCK CODE - 177811

D N/A 11KV

HV THREE-TO-ONE JOINT POLYMERIC TO

POLYMERIC (HV2-23)

177811 N/A N/A N/A

INSTALL THREE TO ONE JOINT BETWEEN POLYMERIC CABLES 11 KV 300 CU1 EPR 70

CU(WS) Z YQ/TX/EA1400/10A AND 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ

AT REF 'D'. STOCK CODE - 177811

B-E 5m 11KV

2 x 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ

2 x 11 KV 300 CU 1 EPR 70 CU(WS) Z

436

391

2315

1335

1390

890

N/A

INSTALL NEW 2 x 11KV 500AL3 TRXQ 35 CU(WS) ZYQ AND 11 KV 300 CU1 EPR 70 CU(WS)

Z YQ/TX/EA1400/10A AND STJ

E 65m 11KV

2 x 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ

4 X150mm CONDUIT BANK (2 SPARE)

1 X 63mm CONDUIT FOR FUTURE OPTIC FIBRE

PILOT CABLE USE (SPARE)

436 2315 1390 6.58

INSTALL NEW 2 x 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ IN NEW 150mm CONDUIT BANKS

AS PER DESIGN AND ASSOCIATED CROSS SECTION DETAILS AND AS PER NS130

E1 29.6m 11KV

2 x 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ

4 X150mm CONDUIT BANK (2 SPARE)

1 X 63mm CONDUIT FOR FUTURE OPTIC FIBRE

PILOT CABLE USE (SPARE)

436 2315 1390 6.58

INSTALL NEW 2 x 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ IN NEW 150mm CONDUIT BANKS

AS PER DESIGN AND ASSOCIATED CROSS SECTION DETAILS AND AS PER NS130

E1-F 15.1m 11KV

1 x 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ

436 2315 1390 N/A

INSTALL NEW 1 x 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ DIRECTLY BURIED AND CONNECT

TO TRANSITION THROUGH JOINTS (POLYMERIC TO PILC)

F N/A 11KV

HV TRANSITION STRAIGHT THROUGH JOINTS

POLYMERIC TO PILC (HV2-25)

152603 N/A N/A N/A

EXPOSE CABLE AND INSTALL TRANSITION STRAIGHT THROUGH JOINTS (POLYMERIC

TO PILC) BETWEEN POLYMERIC 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ AND PILC CABLES

11KV 300 CU3 P H L YQAT REF 'F'. TRANSITION JOINT BASE KIT STOCK CODE - 177853;

CONNECTOR STOCKCODE - 152603.

E1-G 16m 11KV

1 x 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ

436 2315 1390 N/A

INSTALL NEW 1 x 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ DIRECTLY BURIED AND CONNECT

TO TRANSITION THROUGH JOINTS (POLYMERIC TO PILC)

G N/A 11KV

HV TRANSITION STRAIGHT THROUGH JOINTS

POLYMERIC TO PILC (HV2-25)

152603 N/A N/A N/A

EXPOSE CABLE AND INSTALL TRANSITION STRAIGHT THROUGH JOINTS (POLYMERIC

TO PILC) BETWEEN POLYMERIC 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ AND PILC CABLES

11KV 300 CU3 P H L YQAT REF 'G'. TRANSITION JOINT BASE KIT STOCK CODE - 177853;

CONNECTOR STOCKCODE - 152603.

EXISTING TRENCH SECTION

PROPOSED TRENCH SECTION

THE TRENCH SECTIONS MUST BE READ IN CONJUNCTION WITH THE LATEST CIVIL AND SURVEY DRAWINGS. ASP 1 TO COORDINATE FINISHED

SURFACE LEVELS WITH CIVIL CONTRACTOR.

NEW CABLE DUCTS AND CABLES SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF AUSGRID STANDARD NS130.

WARNING

THIS DESIGN CANNOT BE USED FOR CONSTRUCTION PURPOSES UNTIL THE LOCATION OF ALL EXISTING SERVICES IS VERIFIED.

THE INFORMATION PROVIDED IN THIS DESIGN MUST BE CHECKED ON SITE AND THE MOST CURRENT INFORMATION ON THE CONFIGERATION OF ALL SERVICES,

INCLUDING AUSGRID'S NETWORK, MUST BE VERIFIED IMMEDIATLEY BEFORE CONSTRUCTION COMMENCES BY CONTACTING DIAL-BEFORE-YOU-DIG BY TELEPHONE ON

1100 OR AT www.1100.com.au.

DIAL-BEFORE-YOU-DIG INFORMATION MUST NOT BE OLDER THAN 20 BUSINESS DAYS AT THE TIME OF CONSTRUCTION.

ASP LEVEL 2 WORK

ALL LEVEL 2 ASP WORK DEPICTED ON THIS DRAWING IS SHOWN FOR INFORMATION PURPOSES ONLY AND DOES NOT FORM PART OF THE CERTIFIED DESIGN.

NOTES

CLAIMS FOR VARIATIONS TO THE COST OF NON-CONTESTABLE WORKS, INCLUDING ROCK EXCAVATION, WILL NOT BE ACCEPTED UNLESS VERIFIED ON SITE BY AUSGRID

WHILE THE WORKS ARE IN PROGRESS.

THE ASP1 IS RESPONSIBLE FOR UNDERTAKING SATISFACTORY CONSULTATION WITH ALL LOCAL CUSTOMERS WHO MAY POTENTIALLY BE AFFECTED BY THE

CONSTRUCTION WORKS INCLUDING ALL ALTERATIONS TO SERVICE MAINS.

THE ASP/1 MUST MINIMISE THE IMPACT OF THE WORKS ON THE ELECTRICITY SUPPLY TO CUSTOMERS AND INTERRUPTIONS TO SUPPLY MUST BE AVOIDED WHEREVER

POSSIBLE. AT LEAST FOUR (4) CLEAR BUSINESS DAYS NOTICE MUST BE PROVIDED TO ALL AFFECTED CUSTOMERS PRIOR TO ANY PLANNED INTERRUPTIONS TO THE

ELECTRICITY SUPPLY. NOTICE MUST BE IN WRITING IN ACCORDANCE WITH CLAUSE 90 OF THE NATIONAL ENERGY RETAIL RULES.

SPECIFIC PRIOR APPROVAL MUST BE SOUGHT FROM AUSGRID FOR ANY PLANNED ELECTRICITY SUPPLY INTERRUPTIONS WHERE THE PLANNED INTERRUPTION WILL

EXCEED ONE (1) HOUR IN DURATION OR THE DURATION WILL BE LESS THAN ONE HOUR, BUT A SUITABLE TIME FOR THE INTERRUPTION CANNOT BE MUTUALLY AGREED TO

WITH THE AFFECTED CUSTOMER(S).

THE ASP/1 IS TO MAINTAIN ADEQUATE PUBLIC LIGHTING LEVELS FOR THE DURATION OF THE WORKS. IF NECESSARY, THE ASP/1 IS TO ARRANGE FOR SUITABLE

TEMPORARY STREET LIGHTING TO BE PROVIDED UNTIL PERMANENT LIGHTING IS RE-ESTABLISHED.

FOR KIOSK AND CHAMBER TYPE SUBSTATIONS IN THE HUNTER AREAS, ARRANGE PHASING OF 11KV AND LOW VOLTAGE TRANSFORMER TERMINATIONS TO ACHIEVE DYN

11 INTERCONNECTION CAPABILITIES.

THE ASP/1 IS TO CO-ORDINATE THE MODIFICATION AND TESTING OF ANY REQUIRED PROTECTION RELAY WITH THE AUSGRID TECHNICAL SERVICES GROUP

THE ASP1 IS REQUIRED TO COMPLY WITH THE CORRECT PROCEDURE(S) FOR WORKING WITH AND/OR NEAR ASBESTOS MATERIAL (REFER TO AUSGRID NUS 211 -

WORKING WITH ASBESTOS PRODUCTS). THE FOLLOWING AUSGRID ASSETS ARE REGISTERED AS CONTAINING ASBESTOS.

CHECK FOR OTHER SERVICES BEFORE BORING OR EXCAVATING

65

COVER

FINISHED SURFACE LEVEL

PLASTIC

TAPE

1 - PROPOSED 11kV 300 TRIPLEX (CABLE CODE: 391) IN 150mm CONDUIT

2 - PROPOSED 11kV 300 TRIPLEX (CABLE CODE: 391) IN 150mm CONDUIT

3 - SPARE 150mm CONDUIT

4 - SPARE 63mm CONDUIT FOR FUTURE OPTIC FIBRE PILOT CABLE USE

4 - SPARE 150mm CONDUIT

5 - SPARE 150mm CONDUIT

6 - SPARE 150mm CONDUIT

7 - SPARE 150mm CONDUIT

SECTION A- A

21

BACKFILL

1 - EXISTING 11KV 300 CU3 P H L YQ(CABLE CODE: 314) IN

125mm CONDUIT

2 - EXISTING 1.5 CU4 Q Q Z NY/TR(CABLE CODE:802) AND 11KV

300 CU3 P H L YQ(CABLE CODE:314) IN 125mm CONDUIT

3 - EXISTING 1.5 CU4 Q Q Z NY/TR(CABLE CODE:802) .CUT

EXISTING 125mm CONDUIT AND ABANDON EXISTING 11KV 300

CU3 P H L YQ(CABLE CODE:314) AND REPLACE WITH 11KV 500

AL3 TRXQ 35 CU(WS) ZYQ (CABLE CODE: 436)

4 - EXISTING 11KV 300 CU3 P H L YQ(CABLE CODE: 314) IN

125mm CONDUIT

5 - EXISTING 11KV 300 CU3 P H L YQ(CABLE CODE: 314) IN

125mm CONDUIT

6 - SPARE 125mm CONDUIT

7 - SPARE 125mm CONDUIT

8 - SPARE 125mm CONDUIT

9 - SPARE 125mm CONDUIT

SECTION D - D

530

750

COVER

4 5

87

6

9

1 2

3

3

7

4

SECTION E- E

530

75

0

COVER

FINISHED SURFACE LEVEL

5

1 2

3

1 - EXISTING 11KV 300 CU3 P H L YQ(CABLE CODE: 314)

DIRECTLY BURIED

2 - EXISTING 1.5 CU4 Q Q Z NY/TR(CABLE CODE:802) AND 11KV

300 CU3 P H L YQ(CABLE CODE:314) DIRECTLY BURIED

3 - EXISTING 1.5 CU4 Q Q Z NY/TR(CABLE CODE:802) AND 11KV

300 CU3 P H L YQ(CABLE CODE:314) DIRECTLY BURIED

4 - REMOVE EXISTING 11KV 300 CU3 P H L YQ(CABLE CODE:

314) AND INSTALL NEW 11KV 500 AL3 TRXQ 35 CU(WS) ZYQ

(CABLE CODE: 436) DIRECT BURIED

5 - EXISTING 11KV 300 CU3 P H L YQ(CABLE CODE: 314)

DIRECTLY BURIED

FINISHED SURFACE LEVEL

PR

OP

ER

TY

A

LIG

NM

EN

T

600-900

1500-1800

12

00

75

0

65

COVER

FINISHED UNIVERSITY PL ROADWAY SURFACE LEVEL

PLASTIC

TAPE

1 - PROPOSED 11kV 300 TRIPLEX (CABLE CODE: 391) IN 150mm CONDUIT

2 - PROPOSED 11kV 300 TRIPLEX (CABLE CODE: 391) IN 150mm CONDUIT

3 - SPARE 150mm CONDUIT

4 - SPARE 63mm CONDUIT FOR FUTURE OPTIC FIBRE PILOT CABLE USE

4 - SPARE 150mm CONDUIT

5 - SPARE 150mm CONDUIT

6 - SPARE 150mm CONDUIT

7 - SPARE 150mm CONDUIT

SECTION B- B

21

TSB

BACKFILL

3

7

4

RO

AD

A

LIG

NM

EN

T

0

600-900

1500-1800

RO

AD

A

LIG

NM

EN

T

0

TSB

65

COVER

FINISHED UNIVERSITY AVE SURFACE LEVEL

PLASTIC

TAPE

1 - PROPOSED 11kV 300 TRIPLEX (CABLE CODE: 391) IN 150mm CONDUIT

2 - PROPOSED 11kV 300 TRIPLEX (CABLE CODE: 391) IN 150mm CONDUIT

3 - SPARE 150mm CONDUIT

4 - SPARE 63mm CONDUIT FOR FUTURE OPTIC FIBRE PILOT CABLE USE

4 - SPARE 150mm CONDUIT

5 - SPARE 150mm CONDUIT

6 - SPARE 150mm CONDUIT

7 - SPARE 150mm CONDUIT

SECTION C- C

21

BACKFILL

3

7

4

1800

900

RO

AD

A

LIG

NM

EN

T

0

TSB

12

00

75

0

12

00

75

0

CUT CONDUIT

4

PARRAMATTA RD

U

N

IV

E

R

S

IT

Y

P

L

S

C

IE

N

C

E

R

D

U

N

IV

E

R

S

IT

Y

A

V

E

B

A

R

F

F

R

D

5912-3000

BA

R

FF

R

D

U

N

IV

E

R

S

IT

Y

P

L

U

N

IV

E

R

S

IT

Y

P

L

M

A

N

N

IN

G

R

D

CO

NC

RE

TE F

OO

TPA

TH

C

O

N

C

R

E

T

E

F

O

O

T

P

A

T

H

H

V

L

V

P

L

0

.0

PL 0.0

A1

20160817

CONSULTING ENGINEERS

NORTH SYDNEY, NSW 2060

AUSTRALIA

60 MILLER STREET LEVEL 1

NAME: ALISON (YIQING) KONG

ABN 29 003 234 571

T +61 2 9928 6800

F +61 2 9955 6900

www.ndy.com

AUC: NDY MANAGEMENT PTY LTD - 2349

AUP No.2349/05

ID#: H60122769

AP

PR

OV

ED

: B

Y V

. D

. 18/09/2017

CH

EC

KE

D : B

Y V

. D

. 18/09/2017

DR

AW

N : B

Y A

. K

. 18/09/2017

RE

V 0 - O

RIG

IN

AL IS

SU

E

AP

PR

OV

ED

: B

Y V

. D

. 01/11/2017

CH

EC

KE

D : B

Y V

. D

. 01/11/2017

DR

AW

N : B

Y A

. K

. 01/11/2017

RE

V 1 -1000A

F

US

E U

PD

AT

ED

T

O

1200A

s21586-279

A.KONG

2349/05

SUBMITTED 01/11/2017

CITY OF SYDNEY

P14, K01

LE62

XCZ020224

SC097733 5 1

ESTABLISH L TYPE KIOSK SUB

S78214 UNIVERSITY BARFF

CCW MUSEUM

UNIVERSITY OF SYDNEY

CAMPERDOWN

1600

1200

A B

TO:

S.35316

BARFF CITY

TO:

S. 77386

BARFF CITY NO.2

LV DISTRIBUTOR DETAILS

DIST DESTINATION

1 CHAU CHAK WING MUSEUM

2

WDNO(0/400)

3

WDNO(0/400)

1 2

S. 78214

UNIVERSITY BARFF

400

0

KIOSK SUBSTATION DETAILS

SUBSTATION NAME: UNIVERSITY BARFF

SUBSTATION NUMBER: 78214

ADDRESS:3000 PARRAMATTA ROAD, CAMPERDOWN

SUBSTATION TYPE: KL TYPE

SIZE (kVA):

1000 kVA

VECTOR GROUP:

Dyn 1

TAP SETTING: 11000/433

HV SWITCHGEAR: ABB SAFELINK RMI

HV FUSE DETAILS: 100A SIBA 30.020.93.100

LOAD CYCLE: A: COMMERCIAL/INDUSTRIAL

PHASING DETAIL: TO BE CONFIRMED ON SITE

LOW VOLTAGE BOARD: 1600/400/400

TRANSF. LV LINK RATING: 1600

CCT1 LV FUSE SIZE (Amps): 1200/1200 (1200A 165mm CENTRES ALSTOM)

CCT2 LV FUSE SIZE (Amps): 0/400 (400A 92mm CENTRES BELL/MEM "J")

CCT3 LV FUSE SIZE (Amps): 0/400 (400A 92mm CENTRES BELL/MEM "J")

CCT4 LV FUSE SIZE (Amps):

N/A

CONFIGURE AS Dyn11:

NO

EARTHING REQUIREMENTS:

AS PER NS116(SME) & SITE SPECIFIC EARTHING

DESIGN

SUBSTATION PIERING: AS PER DRAWING No. 151572

EASEMENT PLAN DETAIL: AS PER SHEET 3 OF 5

GROUP A - HV ELECTRODES

DESIGN AS BUILT

NUMBER OF ELECTRODES 2

DEPTH OF EACH ELECTRODE 5.4

SPACING BETWEEN ELECTRODES 2.3

MAX RESISTANCE - NORMAL 9.04 -

MAX RESISTANCE - DROUGHT 14.27 -

MEASURED -

SUBSTATION EARTHING AS BUILT TABLE(STANDARD MINIMUM EARTHING

(SME) APPLIES. REFER TO NS116 AND AUSGRID DWG 167433

A

3

400

0

ASP LEVEL 2 WORK

ALL LEVEL 2 ASP WORK DEPICTED ON THIS DRAWING IS SHOWN FOR INFORMATION PURPOSES ONLY AND DOES NOT FORM PART OF THE CERTIFIED DESIGN.

CHECK FOR OTHER SERVICES BEFORE BORING OR EXCAVATING

'A' - EASEMENT FOR ELECTRICITY & OTHER PURPOSES (5.5m x 3.3m MINIMUM)

'B' - EASEMENT FOR ELECTRICITY & OTHER PURPOSES (1m WIDE MINIMUM)

'C' - RIGHT OF WAY (4m WIDE MINIMUM & VARIABLE)

5300 3300

P

R

O

P

O

S

E

D

C

H

A

U

C

H

A

K

W

IN

G

M

U

S

E

U

M

RESISTANCE 8.22

MIN SEPARATION TO TELCO ASSETS 1.2

MIN SEPARATION TO BWTWEEN HV

AND LV AND / OR MEN ELECTRODES

4.3

GROUP B - LV ELECTRODES

DESIGN AS BUILT

NUMBER OF ELECTRODES 2

DEPTH OF EACH ELECTRODE 5.4

SPACING BETWEEN ELECTRODES 2.3

MAX RESISTANCE - NORMAL 9.04 -

MAX RESISTANCE - DROUGHT 14.27 -

MEASURED -

E

A

S

E

M

E

N

T

B

O

U

N

D

A

R

Y

G

R

O

U

P

A

5

3

0

0

5

0

0

5

0

0

500

500

G

R

O

U

P

B

3300

R

E

T

A

IN

IN

G

W

A

L

L

EARTHING PLAN

N.T.S

70mm2 CU

500

5

0

0

500

500

e

REFER TO NS116 AND EARTHING DESIGN SPECIFICATION & AS BUILT INSTALLATION REPORT XCZ020224

'C

'C

'B'

'B'

'A'

'C

'C

'C

'C

'C

'C

'C

'B'

'B'

'B''B''B''B'

'B'

'C

614

U

N

IV

E

R

S

IT

Y

P

L

U

N

IV

E

R

S

IT

Y

A

V

E

CO

NC

RE

TE F

OO

TPA

TH

C

O

N

C

R

E

T

E

F

O

O

T

P

A

T

H

614

613

U

N

IV

E

R

S

IT

Y

P

L

U

N

IV

E

R

S

IT

Y

A

V

E

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

CO

NC

RE

TE F

OO

TPA

TH

C

O

N

C

R

E

T

E

F

O

O

T

P

A

T

H

H

V

L

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

A1

20160817

CONSULTING ENGINEERS

NORTH SYDNEY, NSW 2060

AUSTRALIA

60 MILLER STREET LEVEL 1

NAME: ALISON (YIQING) KONG

ABN 29 003 234 571

T +61 2 9928 6800

F +61 2 9955 6900

www.ndy.com

AUC: NDY MANAGEMENT PTY LTD - 2349

AUP No.2349/05

ID#: H60122769

AP

PR

OV

ED

: B

Y V

. D

. 18/09/2017

CH

EC

KE

D : B

Y V

. D

. 18/09/2017

DR

AW

N : B

Y A

. K

. 18/09/2017

RE

V 0 - O

RIG

IN

AL IS

SU

E

AP

PR

OV

ED

: B

Y V

. D

. 01/11/2017

CH

EC

KE

D : B

Y V

. D

. 01/11/2017

DR

AW

N : B

Y A

. K

. 01/11/2017

RE

V 1 -1000A

F

US

E U

PD

AT

ED

T

O

1200A

s21586-279

A.KONG

2349/05

SUBMITTED 01/11/2017

CITY OF SYDNEY

P14, K01

LE62

XCZ020224

SC097734 5 1

ESTABLISH L TYPE KIOSK SUB

S78214 UNIVERSITY BARFF

CCW MUSEUM

UNIVERSITY OF SYDNEY

CAMPERDOWN

HV NETWORK - EXISTING

HV NETWORK - EXISTING

To S.35316

BARFF CITY

TO S.77836

BARFF CITY

NO.2

NOTE: PROJECT SC08470, INSTALLATION

OF S.77836 IS UNDER CONSTRUCTION.

DESIGN IS BASED ON THAT PROJECT

SC07013 IS 100% COMPLETE

300mm2 CU1

500mm2 AL3

500mm2 AL3

300mm2 CU1

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

S V

H

V

3m

6m

10m

C

O

N

C

R

E

T

E

F

O

O

T

P

A

T

H

H

V

L

V

1

H

V

H

V

H

V

H

V

H

V

H

V

H

V

H

V

PROTECTION BOLLARDS

1400mm CENTER TO CENTER

A1

20160817

CONSULTING ENGINEERS

NORTH SYDNEY, NSW 2060

AUSTRALIA

60 MILLER STREET LEVEL 1

NAME: ALISON (YIQING) KONG

ABN 29 003 234 571

T +61 2 9928 6800

F +61 2 9955 6900

www.ndy.com

AUC: NDY MANAGEMENT PTY LTD - 2349

AUP No.2349/05

ID#: H60122769

AP

PR

OV

ED

: B

Y V

. D

. 18/09/2017

CH

EC

KE

D : B

Y V

. D

. 18/09/2017

DR

AW

N : B

Y A

. K

. 18/09/2017

RE

V 0 - O

RIG

IN

AL IS

SU

E

AP

PR

OV

ED

: B

Y V

. D

. 01/11/2017

CH

EC

KE

D : B

Y V

. D

. 01/11/2017

DR

AW

N : B

Y A

. K

. 01/11/2017

RE

V 1 -1000A

F

US

E U

PD

AT

ED

T

O

1200A

s21586-279

A.KONG

2349/05

SUBMITTED 01/11/2017

CITY OF SYDNEY

P14, K01

LE62

XCZ020224

SC097735 5 1

ESTABLISH L TYPE KIOSK SUBSTATION

S78214 UNIVERSITY BARFF

CCW MUSEUM

UNIVERSITY OF SYDNEY

CAMPERDOWN

SUBSTATION LAYOUT

CHECK FOR OTHER SERVICES BEFORE BORING OR EXCAVATING

300d

400

400

180

130

185d

350

325

65L

PROPOSED

HV SYSTEM DIAGRAM

(11 kV)

EXISTING

HV SYSTEM DIAGRAM

(11 kV)

65L

66

66

180

130

A

2

B

A

2

B

A

1

B

C

2

D

E

3

F

G1

2

1

L

L

L

1

2

3

400

385

194

1+2+3

BARFF

CITY

35316

GEOLOGY

BUILDING

7299

400

385

194

A

1

B

C

2

D

E

3

F

1

2

3

1+2+3

L

L

L

300d

400

400

60

55

CT

400

400

300AI

185d

350

325

CT

G1

C

1

D

C

1

D

2

1

GEOLOGY

BUILDING

7299

BARFF

CITY

35316

60

55

400

400

300AI

L

V

NOTES:

· THERE ARE NO COMBUSTIBLE MATERIALS WITHIN A 3m RADIUS OF

THE KIOSK HOUSING.

· STRUCTURES WITHIN A 3m RADIUS OF THE KIOSK HOUSING SHALL

HAVE A 120/120/120 FRL, UNLESS A SUITABLE BLAST PROOF BARRIER

IS INSTALLED.

· WINDOWS SHALL NOT BE LOCATED WITHIN A 3m RADIUS OF THE

KIOSK HOUSING.

· THERE IS NO BUILDING VENTILATION WITHIN A 6m RADIUS OF THE

KIOSK HOUSING.

· THERE ARE NO FIRE HYDRANTS WITHIN A 10m RADIUS OF THE KIOSK

HOUSING.

· THE KIOSK IS NOT SITED IN AN AREA PRONE TO STORM WATER

RUN-OFF.

· THE KIOSK IS NOT SITED IN A 1 IN 100 YEAR FLOOD AREA.

CAMPERDOWN ZS (19)

CAMPERDOWN ZS (19)

SECTION A-Z

PIERS AS PER AUSGRID DRAWING No. 151572

SECTION A-Y

EA

SE

ME

NT

B

OU

ND

AR

Y

PIERS AS PER AUSGRID

DRAWING No. 151572

5300

RL 36.89 FINISHED / EXISTING

GROUND LEVEL

EA

SE

ME

NT

B

OU

ND

AR

Y

RETAINING WALL BEHIND

3300

EA

SE

ME

NT

B

OU

ND

AR

Y

EA

SE

ME

NT

B

OU

ND

AR

Y

RL 36.89 FINISHED GROUND LEVEL

1

4

0

0

5

3

0

0

3

3

0

0

5

0

0

AS

300 Cu 1 Tails

500 AL3

HANDRAIL BEHINDHANDRAIL

56

5

RL 36.325 EXISTING LEVEL

e