2/14/2012 1 1 Streetlight Contact Voltage Testing ITE/IMSA Joint Conference February 13, 2012 2 Presentation Outline SCL Streetlight History Streetlight Engineering Vision, Mission & Goals System Condition & Inventory Contact Voltage History Contact Voltage Discovery Testing Methodology Lessons Learned

Upload: trinhkhue

Post on 07-Feb-2018

216 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

1

1

Streetlight Contact Voltage Testing

ITE/IMSA Joint Conference

February 13, 2012

2

Presentation Outline

SCL Streetlight History

Streetlight Engineering Vision, Mission & Goals

System Condition & Inventory

Contact Voltage History

Contact Voltage Discovery

Testing Methodology

Lessons Learned

Page 2: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

2

3

SCL Streetlight History

1869 - City of Seattle Charter granted the Seattle City Council the power to provide street lighting

1885 - the Seattle Light Department, now Seattle City Light (SCL), maintained streetlights and managed power accounts for independent power suppliers throughout the central business district

1905 - City’s first power plant became operational making SCL responsible for both streetlights and power generation

1999 - Jurisdiction of arterial streetlights from Seattle Department of Transportation to SCL made SCL responsible for operations and maintenance of residential and arterial street lighting

4

SCL Streetlight History (cont.)

Lights designed to simulate a clear full moon lit night

Page 3: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

3

5

SCL Streetlight History (cont.)

LED Conversion

6

Cities ServedCities Served

Seattle Burien Lake Forest

Park Normandy Park

(portion) Renton (portion) Seatac (portion) Shoreline Tukwila (most) Unincorporated King County

Seattle Burien Lake Forest

Park Normandy Park

(portion) Renton (portion) Seatac (portion) Shoreline Tukwila (most) Unincorporated King County

Page 4: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

4

7

Streetlight Engineering Vision/Mission/Goals

8

System Condition

Majority of the streetlight system is aging

Portions no longer meet current electrical code due to changes over the years

Failures and outages continue to increase

Contact voltage caused by aging infrastructure, weather, workmanship, rodent activity, copper wire theft, and corrosion

Current luminaires 25+/- years old

Page 5: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

5

9

System Condition (Cont.)

Life cycle estimates for system components

HPS Lamps – 4 to 5 years

Standard Cobra Head Luminaire – 20 to 25 years

LED Luminaires – 15 to 20 years

Electrical Wiring and Conduits – 20 to 75 years depending on material quality and type

Poles – 30 to 85+ years

10

System Inventory

~85,000 Streetlights

131 sq. mile service territory

Primarily HPS Luminaires, residential LED conversion program in process

Annual revenue recovery: ~$13 million

Page 6: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

6

11

1B,1C,1D,1E,1F 3A,3B,3C,3E,3D 3D ARCH CLEV

ENT1 & ENT2 2PR 2F 2G

2JJ, 2KK 2BB 2H, 2L, 2J 2R 2O

2Z, 2HH 2N, 2M 2Y, 2PP 2W 1SP

12

Contact Voltage History

19 deaths in 13 states have been reported in the media since the early 1990s

2004: grad student Jodie Lane was electrocuted in New York while walking her dogs - stepped on a slush-covered utility box with bad wiring

2005: Institute of Electrical and Electronics Engineers (IEEE) convened a Working Group to define and develop guidelines for mitigating contact voltage

Page 7: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

7

13

Contact Voltage Definitions

Results from abnormal power system conditions present between 2 conductive surfaces the general public and/or animals can come in contact with

Caused by power system fault current flowing through an impedance of available fault current pathways

Conductive surfaces include the earth and/or extensions of the earth such as concrete sidewalks and metal floor drains

Leaking of voltage is lost power not billable by utilities

14

Contact Voltage Definitions (cont.)

Assets susceptible to contact voltage in an urban street-level environment

Metal poles

Handholes

Fiberglass poles with metal components

Concrete rebar-reinforced poles

Electrified signs

Traffic signals and traffic count meters

Street and pedestrian lights

Page 8: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

8

15

Contact Voltage Discovery

Thanksgiving Day 2010, dog was electrocuted when it touched an energized streetlight handhole cover

Combination of factors contributed to the incident Weather – there was melting snow on the

ground

Pinched wire in the luminaire

Improper grounding of the streetlight from installation

16

Contact Voltage Discovery (Cont.)

As a result of media reports, 6 other pet owners notified SCL of similar reactions

Voltage detected either from a metal streetlight pole or metal equipment servicing the pole

SCL took immediate action to test all metal streetlight poles and equipment within its service territory

Implemented an annual contact voltage testing program

Page 9: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

9

17

Testing Methodology

Initially used 2 methods with 2 different contractors:

1. Manual testing

2. Mobile detection

Executed a 5-year contract for annual contact voltage detection program using mobile detection capability

18

Testing Methodology (Cont.)

Decided to use SVD2000 mobile contact voltage detection system for annual testing because:

More efficient, 2011 scan performed in 31 days

Accuracy / sensitivity of objects less than 1 volt

Specialized equipment sends out a signal and detects elevated voltage in its monitoring area

Page 10: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

10

19

Testing Methodology (Cont.)

Manual investigations with Fluke 345 PQ-capable voltmeter, switchable 3000 Ω shunt resistor and handheld electric field detector, were performed where indicated

Covered 1,721 linear miles Tested 37,500 pieces of electrical equipment

associated with metal streetlight fixtures OSHA considers any current at or above 30 volts a

potentially dangerous level of electricity for heart fibrillation, and is the threshold to determine risk to the public

Used GPS maps to audit contractor’s data

20

Testing Methodology (Cont.)

If elevated voltage detected, voltage is recorded and source located

Information is reported to SCL for further investigation and resolution

Voltage detected at or above 30 volts, requires securing the equipment from public contact and until SCL crews arrive to perform repairs or de-energize the equipment

Testing equipment does not distinguish between SCL assets and other touch potential assets in the right-of-way

Page 11: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

11

21

Testing Methodology (Cont.)

5 events detected at 30 volts or more, but only 2 of the detected events involved SCL equipment

3 remaining events involved private or by other organization ownership

Result comparisons from 2010, show a significant decrease in contact voltage events

2010: 158 events of electrified assets detected, 56 of which were discovered > 30 volts

2011: 61 events detected, 2 events > 30 volts

22

Testing Methodology (Cont.)Annual Contact Voltage Event Results for SCL Assets - Years 2010 and 2011

56

102

2

59

0

20

40

60

80

100

120

Voltage 30 or above Voltage below 30

Events

2010

2011

Page 12: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

12

23

Lessons Learned

City Light is taking the following proactive approaches to protect the public: Touch potential testing instituted for

both SCL crews and contractors, testing is performed prior to beginning work and after the work is finished

10-year Horizon Plan being implemented that prioritizes infrastructure replacement and refurbishment

24

Lessons Learned (Cont.)

SCL has taken responsibility for testing and inspecting all streetlight equipment before it is energized Departmental Policy and Procedure (DPP)

being drafted to formalize responsibilities and processes for inspecting, commissioning and testing street lighting systems

Finally, SCL will continue to test its streetlight system annually and report the findings to the public

Page 13: Streetlight Contact Voltage Testing - WesternITE · PDF fileElectrical Wiring and Conduits – 20 to 75 years ... streetlight pole or metal equipment servicing the pole SCL took immediate

2/14/2012

13

25

Conclusion

Streetlights are an important part of a safe community

SCL is committed to maintaining the streetlight system and to do so safely

26

More Information

To report malfunctioning streetlight or if an energized structure is suspected, contact the Streetlight Hotline at: (206) 684-7056 [email protected] www.seattle.gov/light/streetlight

SCL Contact Voltage Reports: www.seattle.gov/light/streetlight/streetlightsandcontactvoltage.htm

Toronto Hydro Contact Voltage Information:www.torontohydro.com/sites/electricsystem/residential/electricalsafety/Pages/contactvoltage.aspx