Stulz Stulz CyberAir CyberAir II II Whats New at Stulz By Lewis Marton

Upload: vu-minh-tuan

Post on 28-Nov-2014

160 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

StulzStulz CyberAirCyberAir IIII

Whats New at Stulz

By Lewis Marton

Page 2: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

2

Starts of with their usual stuff Starts of with their usual stuff Starts of with their usual stuff

7

Global Precision Cooling MeetingTognana, Italy May 15-17, 2007

Confidential

• CyberAir units offer the highest cooling capacities with the lowest footprint

• Latest EC fan technology

• Infinitely variable air volume

• Standby- Management

• Freecooling

• High optionality

CyberAir 2: established improved

9

Global Precision Cooling MeetingTognana, Italy May 15-17, 2007

Confidential

• Stand alone intelligence per unit by C7000.

• Connection to BMS systems of well-established manufacturers

• Communication via internet protocols SNMP and HTTP

• SMS or email alarm messages via GSM modem

CyberAir 2: established improved

10

Global Precision Cooling MeetingTognana, Italy May 15-17, 2007

Confidential

A-System G-System

ACW-System GCW-System

GE1-System GE2-System

CW-System CW2-System

CyberAir

10

Global Precision Cooling MeetingTognana, Italy May 15-17, 2007

Confidential

A-System G-System

ACW-System GCW-System

GE-System

CW-System CW2-System

CyberAir 2

Page 3: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

3

8

Global Precision Cooling MeetingTognana, Italy May 15-17, 2007

Confidential

Refrigerant R410ARefrigerant R410ARefrigerant R410A

State-of-the-art refrigerantR410A

50% R32

50% R125

Advantages• Highest system performance• Refillable and service friendly two-component

refrigerant • Worldwide high availability

Disadvantage•High system pressure level

XXXX

RefrigerantsRefrigerantsRefrigerants

8

Global Precision Cooling MeetingTognana, Italy May 15-17, 2007

Confidential

RefrigerantsRefrigerantsRefrigerants

For high temperature areas is only on choice: R134a

EU regulations are requiring replacement of R22The choice of replacement is R407C, R410A, or R134a

Stulz is using R407C as standard refrigerant since 2000

Extensive tests have shown that there are significant benefits with air conditioning systems using R410A

Stulz offers them all

Except when you order product they deliver units with R22

As an option or as an SFA

8

Global Precision Cooling MeetingTognana, Italy May 15-17, 2007

Confidential

Refrigerant R407CRefrigerant R407CRefrigerant R407C

standard refrigerant since 2000

AdvantagesThe vapour pressure curve and the volumetricenthalpy of R407C are similar to those of R-22.-> R407C can be used in many instances with equipment originally designed for R-22.

R407C

52% R134a

25% R125

23% R32

Disadvantages• Any refrigerant loss will make it necessary to empty the installation and make a

complete refill -> capacity reduction up to 17%• Temperature glide

8

Global Precision Cooling MeetingTognana, Italy May 15-17, 2007

Confidential

Refrigerant R134aRefrigerant R134aRefrigerant R134a

Refrigerant for extreme ambient temperatures

Advantages• No mixture of components• No Temperatureglide• Servicefriendly

DisadvantageReduction of cooling capacity has to be compensated by using bigger compressors

R134a

100% R134a

Also EER reduction

8

Global Precision Cooling MeetingTognana, Italy May 15-17, 2007

Confidential

Refrigerant: Properties and System EffectsRefrigerant: Properties and System EffectsRefrigerant: Properties and System Effects

*Reference R22

System Performance*

95-100% 95-100% 98-106%

R407C R134a R410AGlide (K)

GWP

Pressure at 50°C

Heat Transfer*

Compressor COP*

6 0 < 0.5

1610 1300 1090

19.6 13.2 30.8

95-101% 101% 92-100%

Same Slightly less Higher

Stulz offer R22, R407C, R410a, R134a

All without significant derating ???

Page 4: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

4

Electronic Expansion ValveElectronicElectronic Expansion ValveExpansion Valve• Fast reaction time 1.5 second

• Fully true hermetic design, body from stainless steel

• No additional solenoid valve necessary

• Continuous modulation of mass flow, no stress in the refrigeration circuit

• Ceramic slide and port parts for highly accurate flow and minimal wear

Note brand of EEV - Alco

Page 5: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

5

Controlled dehumidification at constant airflow

Electronic Expansion Valve: Benefit

No risk of hot spots

->Means safe conditions for computer equipment

Extended dehumidification (selectable)if the preseted humidity is not reached after 30 minutes the airflow will be reduced in addition

Sounds like they are not sure of how well it will work

The EEV valve opens for dehum operation ?

It seems like they have had some issues with hot spots in the room by varying the air flow

• Increased capacity and COP by precise control with short response time and point-precise setting of superheating

• optimized saturation of the evaporator

• Low pressure can be controlled independent of high pressureTherewith is cold water usable to increase capacity in water-cooled DX systems

Page 6: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

6

Regular Operation „Cold-water“ Operation

CondensingTemperature: 45°C

=>

Capacity: 41,0 kWPower Input: 8,8 kWCOP: 4,67

Calculation for Copeland scroll compressor ZR144

CondensingTemperature: 35°C

=>

Capacity: 48,0 kWPower Input: 7,45 kWCOP: 6,41

Capacity: + 17%Power Input: -15%COP: +37%

Increased efficiency for water-cooled DX

Works at low ambient conditions. Requires cold water supply at 20C. OK for cold winter climates.

Page 7: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

7

• Only two EEVs covers the whole capacity range ( from 10 up to 60 kW)

• The same valve can be used for all refrigerants

Electronic Expansion Valve: Benefit

Besides Uniflair and Citec, Stulz will be the only major manufacturer who includes the EEV as standard

R407C R134aR410A

This will be an option on DS and Himod.

Expect another Energy Efficiency play here.

Page 8: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

8

New Compressors series

• Extension of Copeland series “Summit“• Reduced dimensions and weight• One bottom plate for all • One height• Always same connection points• World wide available• Advanced Scroll Temperature Protection

(ASTP)Selling the benefits of Copeland Scroll compressors!

Page 9: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

9

Advanced Scroll Temperature Protection (ASTP)Advanced Scroll Temperature Protection (ASTP)Advanced Scroll Temperature Protection (ASTP)

• ASTP protects your compressor from excessively high discharge temperatures

• The compressor is protected, but the motor runs further.

• Internal balance between high pressure and suction side

One of the many features of Copeland Scroll compressors

Page 10: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

10

This is where it gets interesting: The slides below are from our Beat Stulz Silver Bullets PresentationThis is where it gets interesting: The slides below are This is where it gets interesting: The slides below are from our Beat from our Beat StulzStulz Silver Bullets PresentationSilver Bullets Presentation

EC Evaporator FansEC Evaporator FansEC Evaporator Fans“These fans look great, but how do I get them out ?”

EC Evaporator FansEC Evaporator FansEC Evaporator FansCyberAir Operating Instruction manual recognises the removal challenge !

High MTTR (Mean-Time-To-Repair) !!!

Electric HeatersElectric HeatersElectric HeatersHeater elements envelop the EC fan

Retaining clamps are riveted to each element

Removal would require rear access and/or fan removal

High MTTR !!

NC#3 – Humidifier Steam NozzleNC#3 NC#3 –– Humidifier Steam NozzleHumidifier Steam NozzleHumidifier steam nozzle accessible from REAR of unit only

Australian Standard AS3666.2 requires access for inspection and cleaning

NC#2 – Evaporator Drain Tray AccessNC#2 NC#2 –– Evaporator Drain Tray AccessEvaporator Drain Tray AccessEvaporator drain tray accessible from REAR of unit only

Australian Standard AS3666.1 requires access for inspection and cleaning

Based on the Beat Stulz program and Silver Bullets presentations & critique it appears that the changes have been now made to the CyberAir 2 to counter our criticism

Page 11: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

11

CyberAir 2 - Outstanding accessibilityCyberAir 2 CyberAir 2 -- Outstanding Outstanding accessibilityaccessibilityfront access to all maintenance relevant components

EC-Fan

steam humidifier

compressor

filter dryer

liquid receiver /safety valve

They have come up with the answers to the criticisms

Page 12: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

12

Outstanding accessibilityOutstanding Outstanding accessibilityaccessibility

Front access to all maintenance relevant components

EC-Fan

steam humidifier

compressor

filter dryer

liquid receiver /safety valve

Himod and PEX always had it

Even though it looks like the EC fan plate is hinged for service, for access need to it lift out

Note top and bottom handles

The humidifier has to be removed on the LH side

Pipe connections obstruct on the LH side

The middle fan should be OK to remove

In all cases the mullions maybe in the way

Note - This shows a 3 fan unit, a single fan unit will have both the fans and pipework in front of the fan

The lifting in and out of replacement compressors at least 600 mm above floor level will be interesting

Page 13: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

13

Accessibility: Electrical reheat/ humidifierAccessibilityAccessibility: Electrical reheat/ humidifier: Electrical reheat/ humidifierCyberAir 2CyberAir

Fan encircled heaterflat profile heaterone humidifier

position

It was nearly impossible to replace heater elements

Pipework in front of compressors

Access more difficult on Water cooled units

Fan access from rear, with some models also requiring side access

Uneven reheat only on one side of unit

Once field piping connected how will the heater element be removed

Receiver mounted on inner skin

Page 14: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

14

Reliability: refrigerant circuitReliability: refrigerant circuitReliability: refrigerant circuitCyberAir 2CyberAir

Solder Fittings were replaced with Pipe Elbows

The pipework still looks rough

EEV location

No Valve or spud connection on compressor Hot works still required in room.

Now flare connection on the drier

Compressor support beams

Page 15: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

)Accessibility : Pipe ducting

CyberAir 2Only one standardized duct area for all unit sizes

condensate drain

New bottom plate

insertion for power cable

pipe duct areahumidifier inlet

Yes all the possibilities was a nightmare for the contractor

Pipe duct area leads contractor to run pipework in front of and across fan outlet

Concentration of re heat at one end / side of unit

Overlapping elements. Multiple W shape elements

Once field piping connected how will the heater element be removed

Water cooled units not shown where the pipework and WRV will take up more access space

Page 16: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

16

Behind the service flapsBehind the service flapsBehind the service flaps

steam-pipe distributionUnit size

size 1

size2

size 3-5

Service flaps

1

2

3

OK Why do they need service flaps ?

Page 17: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

17

Behind the service flaps Behind the service flaps Behind the service flaps

Unit size

size 1

size2

size 3-5

Service flaps

1

2

3

Why do they need service flaps ?

To clean out the condensate tray

To access the humidifier distribution pipes

Page 18: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

18

A Cross SectionA Cross SectionA Cross SectionBased on a width of 890mm this CAD dwg shows the unit to be over 2000mm high

Distance between Fan inlet and back panel is approx 200mm

Condensate and Humidifier distributor daintray app 200 mm below the bottom of the evap. coil

Filter overlaps coil to allow for smooth air flow

No condensate trap provided in the unit

Looks like a 560mm dia EC fan

Page 19: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

19

Behind the service flaps Behind the service flaps Behind the service flaps

steam-pipe distribution

OK Why do they need service flaps = Service flaps can be seen just in front of the distributor nozzle pipe

Good steam distribution compared to the previous single outlet on CyberAir 1

Still no by pass air which could be a problem with water in the base of unit and and floor

Stainless Steel tray

Page 20: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

20

New Condenser - TargetNew Condenser New Condenser -- TargetTarget

• Higher availability

• Cost Reduction

• Clear product line

• Cancellation of former temperature classification

• Reduction of sound pressure groups (only two are requested from the market)

• Epoxy coating for all sizes (continuously available as option)

• Free choice of casing material (Aluminium or galvanised steel)

Looks like at least 6 rows deep. Condenser Fan Power consumption not considered in Calculations!?!?

Cabling and piping loose

Will follow existing philosophy e.g. Pressure actuated Fan cycling control fitted as an option or Fan speed control supplied loose for the contractor to fit as options when requested

No isolating switch fitted as standard or as an option

Page 21: Stulz Cyber Air 2 - Whats New V1 (2) LEWIS

21

CondenserCondenserCondenserFormer condenser product family:

• 57 different condensers types

• 3 sound groups A, B and C

• 3 temperature classes X,Y and Z

• after all only 37 different condensers, because some Z condensers are same to construction like the X condenser of smaller achievement and some C condensers are also used in sound group A

The new series consists of:• 27 types• 2 sound groups (There will be

13 standards and 14 LowNoisetypes)

• All Types in 50Hz and 60Hz available

Sounds simple but probably lost in the translation

Presuming that the new series will also be outsourced