Page 1: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

1

Floor Mounted Air Conditioners

®Engineering Manual

Perimeter

EM

Indoor Cooling

STULZ CyberAiR® Floor Mounted Systems60 - 730 kW Chilled Water SystemsPrecision Air Handlers Utilizing EC Fan Technology(60Hz Data)

Page 2: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

2

CyberAiR CFD/CFU-COur Mission: Driving innovation in our industry, providing highest quality environmental control products, superior technology, customer solutions and exceptional customer service while being a socially and environmentally responsible and ethical company.

STULZ is dedicated to providing innovative solutions for critical temperature and humidity control needs. STULZ designs and manufactures specialized, energy efficient, environmental control equipment. STULZ serves a diverse marketplace; our customers represent a variety of industries including telecommunications, information technology, medical, financial, educational, industrial process and government. Our world-class “island” manufacturing processes takes place in a

modern, 218,000 ft2 facility located in Frederick, MD USA. STULZ combines a global network of sales and service companies with an extensive factory engineering staff and highly flexible manufacturing resources dedicated to providing world-class quality, innovation and customer service.

This commitment to excellence, along with a standard two year warranty, fast lead times, and outstanding customer service, make STULZ the perfect choice for all your environmental control needs.

Solutions that help you reach your goals.Ultrasonic Humidifiers

• Duct, AHU, Wall Mounted & Stand-alone• Clean, Energy Efficient• Adiabatic Cooling

Precision Air Conditioning• Ceiling, Row & Floor Mounted from 1-200 tons• Air, Water, Glycol, Chilled Water• Free Cooling• Alternate Water Source

ISO-9001 Quality RegisteredSTULZ is committed to satisfying customer expectations by meeting and exceeding requirements. Our Quality Policy ensures that every Employee is committed to Customer Satisfaction, Teamwork and utilizing Continuous Process Improvement methods in order to deliver an exceptional product. We will continually measure our performance to improve the effectiveness of our quality management system.

STULZ CyberAiR® “CFD/CFU” vertical, floor mounted air conditioning units provide precision temperature and humidity control for computer rooms and other critical areas where continuous 24 hours per day, 365 days per year operation is required.

Designed for front only access, CyberAiR “CFD/CFU” systems require minimal floor space. The units are designed with a wide range of options to handle both precision and comfort cooling applications.

Typical applications include:

INDUSTRIES: Internet / Web Hosting

Telecommunications

Financial / Banking

Insurance

Airlines / Mass Transit

Legal Services

Entertainment

Government

Colleges / Universities

APPLICATIONS: Data Centers

Computer / LAN Rooms

Telecommunications Rooms

Co-location Centers

ISP (Internet Service Providers)

ASP (Applications Service Providers)

STULZ

Page 3: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

i

Floor Mounted Air Conditioners

Table of Contents Introduction to STULZ .......................................................................... 2 Table of Contents/Model Nomenclature ............................................... 3

CyberAiR CFD/CFU-C Systems Product Advantages/Features ............................................................... 4 Product Features Index .....................................................................5-6

Performance Data Technical Specifications ....................................................................7-9 Performance/Capacity Data - Down-flow Units @45°F EWT ..........10-11 Performance/Capacity Data - Up-flow Units @45°F EWT .................... 12 Performance/Capacity Data - Down-flow Units @50°F EWT ..........13-14 Performance/Capacity Data - Up-flow Units @50°F EWT .................... 15

Electrical Data Electrical Data (FLA/MCA/MFS) .....................................................16-17

Dimensional Data / Installation Drawings 60 - 730 kW Downflow Systems ..................................................18-24 60 - 280 kW Upflow Systems .......................................................25-28 Plenums / Seismic Floor Stands .......................................................... 29

Guide Specifications Product Guide Specifications ........................................................30-35

Table o

f Co

nten

ts / Mo

del N

om

enclatu

reCyberAiR CFD/CFU-C

Page 4: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

ii

CyberAiR CFD/CFU-C

Page 5: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

1

Floor Mounted Air Conditioners

Model Nomenclature

CFX-XXX-XXX-X-XX

CF Air Pattern Capacity (kW)Cooling Method

Number of CW Circuits

Piping Connections

Secondary Cooling Options

Fan Location

Additional Special Options

CyberAiR Floor

Mounted System

D = DownflowU = UpflowR = Rear ReturnF = Front Discharge

060, 090, 120, 150, 180, 190, 230, 280, 310, 360, 510, 630, 730

C = CW 1 2*

R = Right Hand Piping

L = Left Hand Piping*

0 = NoneF = Water Side

Economizer

I = In Unit 0 = StandardS = Special*

CF D 230 C 1 R 0 I 0

* Please consult factory for additional information.

Example:230 kW Capacity, Single Circuit, Chilled Water, Downflow, Floor Mounted System; with Right Hand Piping, Internal EC Fans, and No Additional Options : CFD-230-C1R-0-I0

STULZ CyberAiR “CFD/CFU” floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements. CW Systems are available in sizes from 60 to 730 kW in a variety of space saving cabinet foot prints.

Efficiently designed for 100% front service access, STULZ CyberAiR units can easily be tucked into a corner or placed side-by-side. STULZ CyberAiR units are especially adaptable to raised floors and are available in both down-flow and up-flow air pattern configurations.

STULZ CyberAiR® Floor Mounted CW Systems

Page 6: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

2

CyberAiR CFD/CFU-CPr

od

uct

Ad

van

tag

es /

Fea

ture

s

CyberAiR Systems Offer Outstanding Advantages

Versatility• Down-Flow and Up-Flow Air Patterns• Ducted Systems• Raised Floor Mounting with Floor Stands

100% Front Service AccessFrom 60 to 730 kW, STULZ CyberAiR systems are designed for 100% Front Only Access. The compact foot-print requires minimal floor space.

Non-Proprietary PartsSTULZ CyberAiR systems incorporate non-proprietary components where possible. Most major HVAC, refrigeration and electrical distributors stock an exact model cross reference or an alternate to most factory provided components.

Microprocessor ControlPrecision temperature and/or humidity control with highly versatile and flexible E2 series controls. Designed primarily for STULZ precision air conditioners, E2 controllers offer a wide range of expanded control functions and alarms.

The E2 controller features a “menu-driven” operating environment to allow system setup and operation via an easy to read user interface display panel which is typically mounted on the front door of the STULZ CyberAiR system.

Electronically Commutated (EC) FanMaintenance free, highly reliable EC (Electronically Commutated) Fans offer considerable cost savings and long life. EC Fans do not use drive belts so belt abrasion dust is eliminated as is routine belt maintenance.Fan speed is continuously adjustable via a signal from the system controller without the use of VFD’s. EC fans offer clean, energy efficient, quiet and low vibration operation.

Complete Temperature & Humidity Control • Electrode Canister Steam Humidification

• Dehumidification Mode with - Staged Electric Reheat/Heat - Optional Hot Water Reheat/Heat

24/7 Year Round OperationOption offerings available with CyberAiR systems allow for year-round, 24 hrs-a-day A/C operation in any environment in the world.

Modular Motor ControllersCyberAiR systems incorporate modular motor controllers with motor circuit breakers in lieu of inconvenient replaceable fuses, eliminating the need for ANY motor fusing.

Quiet OperationEC Fans, and acoustically lined cabinets provide quiet operation.

Warranty - 2 Year Parts Standard

Code (UL / CSA) Conformance

- NYC MEA Approved (MEA-433-00-E)- ETL LIsted, Conforms to UL STD 1995- CAN/CSA C22.2 No. 236

Selected Standard Features:• Compact Foot Print• Microprocessor Control• High Efficiency EC Fans• MERV 8 Filtration• Main Power Non-Fused Disconnect Switch• Modular Motor Controllers (w/ motor circuit breakers)• Acoustical/Thermal Insulation• Aluminum Finned / Copper Tube Coils• Modulating Chilled Water Control Valves• Entering/Leaving CW Temperature Sensors• Front Filter Access

Other Available Options:• Automatic Switchover to Back-Up Power• Floor Stands • Condensate Pumps• Firestats• Smoke Detectors• Water Leak Detectors• MERV 11 Filtration• High Short Circuit Current Rating (KAIC)• 2 & 3-way Grilled Plenum Boxes• Seismic Rated Floor Stands

• Many more options available!

CyberAiR CFD/CFU(Model CFD-230-C shown)

Space Saving Configuration

With 100% Front Access, the

CyberAiR CFD/CFU is Suitable for

Standalone, Side-By-Side

or Corner Installations

Page 7: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

3

Floor Mounted Air ConditionersPro

du

ct Features In

dex

CFD/CFU-CW MODELS 060 090 120 150 180 190 230 280SELECTED FEATURES:TEMPERATURE CONTROL2-Way Modulating Chilled Water Control Valve Standard Standard Standard Standard Standard Standard Standard Standard

3-Way Modulating Chilled Water Control Valve Optional Optional Optional Optional Optional Optional Optional Optional

Differential Temperature Flow Standard Standard Standard Standard Standard Standard Standard Standard

2-Stage Electric Reheating/Heating Standard Standard Standard N/A N/A N/A N/A N/A

3-Stage Electric Reheating/Heating N/A N/A N/A Standard Standard Standard Standard Standard

Hot Water Reheat Optional Optional Optional Optional Optional Optional Optional Optional

High Efficiency, Aluminum Fin/Copper Tube Coils Standard Standard Standard Standard Standard Standard Standard Standard

HUMIDITY CONTROLElectrode Canister Steam Humidifier Standard Standard Standard Standard Standard Standard Standard Standard

Dehumidification Mode - Electric Reheat Standard Standard Standard Standard Standard Standard Standard Standard

CONTROLSE² Color Touchscreen Graphic Microprocessor w/ Alarms Standard Standard Standard Standard Standard Standard Standard Standard

MIB - Multi-Interface BMS/LAN Communication Optional Optional Optional Optional Optional Optional Optional Optional

CABINETGalvannealed Steel, Powder Coated Finish Standard Standard Standard Standard Standard Standard Standard Standard

Stainless Steel Condensate Drain Pan Standard Standard Standard Standard Standard Standard Standard Standard

1/2" Thick, 2 lb/ft² Density Thermal & Sound Insulation Standard Standard Standard Standard Standard Standard Standard Standard

Floor Stand (Adjustable) Optional Optional Optional Optional Optional Optional Optional Optional

FILTERS / PLENUMS2 or 3-Way Plenum Box (Up-Flow Units) Optional Optional Optional Optional Optional Optional Optional Optional

Return Air Plenum Extension Box (Down-Flow Units) Optional Optional Optional Optional Optional Optional Optional Optional

Internal / Exterternal Filters Internal Internal Internal Internal Internal Internal Internal Internal

4", MERV8 Rated Pleated Filters Standard Standard Standard Standard Standard Standard Standard Standard

4", MERV11 Rated Pleated Filters Optional Optional Optional Optional Optional Optional Optional Optional

BLOWERS / MOTORSBackward Inclined, Plenum Style Fan, With an EC Motor Standard Standard Standard Standard Standard Standard Standard Standard

ELECTRICAL3-Phase Power Supply -- See Electrical Table --

Multi-Voltage Control Transformer (24V Class 2) Standard Standard Standard Standard Standard Standard Standard Standard

Motor Starter Protectors and Integral Circuit Breakers Standard Standard Standard Standard Standard Standard Standard Standard

SAFETY FEATURESAudible/ Visual Local & Remote Alarms Standard Standard Standard Standard Standard Standard Standard Standard

Main Power Circuit Breaker, Unit Mounted Standard Standard Standard Standard Standard Standard Standard Standard

Motor Overload Protection Standard Standard Standard Standard Standard Standard Standard Standard

CODE CONFORMANCENRTL Conformance Compliance to UL 1995 Standard Standard Standard Standard Standard Standard Standard Standard Standard

CSA/ NYC MEA-433-00-E Standard Standard Standard Standard Standard Standard Standard Standard

Upflow/Downflow Models 060-C thru 280-C

Page 8: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

4

CyberAiR CFD/CFU-C

CFD-CW MODELS 310 360 510 630 730SELECTED FEATURES:TEMPERATURE CONTROL2-Way Modulating Chilled Water Control Valve Standard Standard Standard Standard Standard

3-Way Modulating Chilled Water Control Valve Optional N/A N/A N/A N/A

Entering/Leaving CW Temperature Sensors Standard Standard Standard Standard Standard

2-Stage Electric Reheating/Heating N/A N/A N/A N/A N/A

3-Stage Electric Reheating/Heating Standard Standard N/A N/A N/A

Hot Water Reheat Optional Optional N/A N/A N/A

High Efficiency, Aluminum Fin/Copper Tube Coils Standard Standard Standard Standard Standard

HUMIDITY CONTROLElectrode Canister Steam Humidifier Standard Standard N/A N/A N/A

Dehumidification Mode - Electric Reheat Standard Standard N/A N/A N/A

CONTROLSE² Color Touchscreen Graphic Microprocessor w/ Alarms Standard Standard Standard Standard Standard

MIB - Multi-Interface BMS/LAN Communication Optional Optional Optional Optional Optional

CABINETGalvannealed Steel, Powder Coated Finish Standard Standard Standard Standard Standard

Stainless Steel Condensate Drain Pan Standard Standard Standard Standard Standard

1/2" Thick, 2 lb/ft² Density Thermal & Sound Insulation Standard Standard Standard Standard Standard

Floor Stand (Adjustable) Optional Optional Optional Optional Optional

FILTERS / PLENUMS2 or 3-Way Plenum Box (Up-Flow Units) N/A N/A N/A N/A N/A

Return Air Plenum Extension Box (Down-Flow Units) Optional Optional Optional Optional Optional

Internal / External Filters External External External External External

4", MERV8 Rated Pleated Filters (Down-Flow Units) Standard Standard Standard Standard Standard

4", MERV11 Rated Pleated Filters (Down-Flow Units) Optional Optional Optional Optional Optional

6", MERV8 Rated Pleated Filters (Up-Flow Units) N/A N/A N/A N/A N/A

6", MERV11 Rated Pleated Filters (Up-Flow Units) N/A N/A N/A N/A N/A

BLOWERS / MOTORSBackward Inclined, Plenum Style Fan, With an EC Motor Standard Standard Standard Standard Standard

ELECTRICAL3-Phase Power Supply -- See Electrical Table --

Multi-Voltage Control Transformer (24V Class 2) Standard Standard Standard Standard Standard

Motor Starter Protectors and Integral Circuit Breakers Standard Standard Standard Standard Standard

SAFETY FEATURESAudible/ Visual Local & Remote Alarms Standard Standard Standard Standard Standard

Main Power Circuit Breaker, Unit Mounted Standard Standard Standard Standard Standard

Motor Overload Protection Standard Standard Standard Standard Standard

CODE CONFORMANCENRTL Conformance Compliance to UL 1995 Standard Standard Standard Standard Standard Standard

CSA/ NYC MEA-433-00-E Standard Standard Standard Standard Standard

Pro

du

ct F

eatu

res

Ind

ex

Downflow Models 310-C thru 730-C

Page 9: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

5

Floor Mounted Air Conditioners

Model CFD-060-C1 CFU-060-C1 CFD-090-C1 CFU-090-C1 CFD-120-C1 CFU-120-C1

Chilled Water Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions

2-way Modulating (standard)

Size" / (Cv) 2 / (20) 2 / (20) 2 / (28) 2 / (28) 2 / (30) 2 / (30)

Valve Pressure Rating - psi 600 600 600 600 600 600

Close-off Pressure Rating - psi 200 200 200 200 200 200

3-way Modulating (optional)

Size" / (Cv) 2 / (20) 2 / (20) 2 / (28) 2 / (28) 2 / (30) 2 / (30)

Valve Pressure Rating - psi 400 400 400 400 400 400

Close-off Pressure Rating - psi 200 200 200 200 200 200

Chilled Water Coil - Aluminum Fin, Copper Tube

Rows/Face Area (ft2) 4 / (31.3) 4 / (31.3) 5 / (31.3) 5 / (31.3) 6 / (37.2) 6 / (37.2)

Face Velocity, fpm 368 352 368 352 333 269

Evaporator Blower / Motor - Backward Inclined Direct Driven EC

Nominal Horsepower Each 3.9 3.9 3.9 3.9 3.9 3.9

Rated Air Flow, CFM @ .3” H2O ESP 11,500 11,000 11,500 11,000 12,400 10,000

Quantity of Blowers 2 2 2 2 2 2

Reheat / Heat - Performance Capacities Include Evaporator Blower Motor Heat @ Rated CFM & ESP

Electric Reheat / Heat - Finned Tubular Heaters, (Standard)

Number of Stages 2 2 2 2 2 2

Heater Rating, kW 18.0 18.0 18.0 18.0 18.0 18.0

Total Capacity, MBH 81.2 81.2 81.2 81.2 81.2 81.2

Hot Water Reheat / Heat - Rated at 180°F EWT / 160°F LWT & 75°FDB/61.1°FWB EAT (Optional)

Total Capacity, MBH 84.9 96.9 84.9 96.9 94.1 104.2

GPM / (Pressure Drop, ft H2O) 7 / (4) 8 / (5) 7 / (4) 8 / (5) 8 / (4) 9 / (6)

Control Valve ON/OFF, 2-WAY, 1”, 300PSI, CV=8.0

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Standard)

Lbs/Hr, (kW Power Input) 15 / (5.1) 15 / (5.1) 15 / (5.1) 15 / (5.1) 15 / (5.1) 15 / (5.1)

Std Control Proportional Proportional Proportional Proportional Proportional Proportional

Filters - MERV 8 Average Dust Spot Efficiency, Throwaway (Standard), MERV 11 Average Dust Spot Efficiency (Optional)

Actual Size, H" x W" x D" (QTY)

37 x 23 x 3 3/4 (3)

35 7/8 x 24 3/4 x 3 3/4 (1)

35 7/8 x 18 7/8 x 3 3/4 (2)

21 x 18 7/8 x 3 3/4 (1)

37 x 23 x 3 3/4 (3)

35 7/8 x 24 3/4 x 3 3/4 (1)

35 7/8 x 18 7/8 x 3 3/4 (2)

21 x 18 7/8 x 3 3/4 (1)

37 x 29 x 3 3/4 (3)35 7/8 x 24 3/4 x 3

3/4 (3) 24 3/4 x 21 x 3 3/4 (1)

Filter Face Area, ft2 17.7 18.3 17.7 18.3 22.4 22.1

Connection Sizes - Copper, (Water In/Out connections are sized for flow rates at 75°FDB/62.5°FWB EAT conditions.)

Water In/Out, OD"(see drawing for quantity)

2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8

Condensate Drain w/o Pump, OD" 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8

Condensate Drain w/ Pump, OD" 1/2 1/2 1/2 1/2 1/2 1/2

Humidifier Inlet, OD" 1/4 1/4 1/4 1/4 1/4 1/4

HW Reheat / Heat In/Out, OD" 7/8 7/8 7/8 7/8 7/8 7/8

Physical Data

Approximate Unit Weight 1,500 lbs 1,700 lbs 1,600 lbs 1,800 lbs 1,900 lbs 2,000 lbs

Approximate Shipping Weight 1,600 lbs 1,800 lbs 1,700 lbs 1,900 lbs 2,100 lbs 2,200 lbs

Unit Dimensions: H”x W”xD”76.2 x 77.4 x 40.3

88.1 x 77.4 x 40.376.2 x 77.4 x 40.3

88.1 x 77.4 x 40.376.2 x 89.1 x 40.3

88.1 x 89.1 x 40.3

(w/ Hot Water Reheat) (91.1 x 77.4 x 40.3) (91.1 x 77.4 x 40.3) (91.1 x 89.1 x 40.3)

Unit Shipping Dimensions: H”xW”xD” 83 x 80 x 46

95 x 80 x 46

83 x 80 x 46

95 x 80 x 46

83 x 95 x 46

95 x 95 x 46

(98 x 80 x 46) (98 x 80 x 46) (98 x 95 x 46)(w/ Hot Water Reheat)

Techn

ical Specifi

cation

s

Page 10: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

6

CyberAiR CFD/CFU-CTe

chn

ical

Sp

ecifi

cati

on

s

Model CFD-150-C1 CFU-150-C1 CFD-180-C1 CFU-180-C1 CFD-190-C1 CFU-190-C1 CFD-230-C1 CFU-230-C1

Chilled Water Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions

2-way Modulating (standard)

Size" / (Cv) 2 / (40) 2 / (40) 2 / (60) 2 / (60) 2 / (60) 2 / (60) 2 / (60) 2 / (60)

Valve Pressure Rating - psi 600 600 600 600 600 600 600 600

Close-off Pressure Rating - psi 200 200 200 200 200 200 200 200

3-way Modulating (optional)

Size" / (Cv) 2 / (40) 2 / (40) 2 / (60) 2 / (60) 2 / (60) 2 / (60) 2 / (60) 2 / (60)

Valve Pressure Rating - psi 400 400 400 400 400 400 400 400

Close-off Pressure Rating - psi 200 200 200 200 200 200 200 200

Chilled Water Coil - Aluminum Fin, Copper Tube

Rows/Face Area (ft2) 3 / (52.6) 3 / (52.6) 4 / (52.6) 4 / (52.6) 5 / (52.6) 5 / (52.6) 6 / (52.6) 6 / (52.6)

Face Velocity, fpm 314 314 342 319 342 319 361 312

Evaporator Blower / Motor - Backward Inclined Direct Driven EC

Nominal Horsepower Each 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

Rated Air Flow, CFM @ .3” H2O ESP 16,500 16,500 18,000 16,800 18,000 16,800 19,000 16,400

Quantity of Blowers 3 3 3 3 3 3 3 3

Reheat / Heat - Performance Capacities Include Evaporator Blower Motor Heat @ Rated CFM & ESP

Electric Reheat / Heat - Finned Tubular Heaters, (Standard)

Number of Stages 3 3 3 3 3 3 3 3

Heater Rating, kW 27.0 27.0 27.0 27.0 27.0 27.0 27.0 27.0

Total Capacity, MBH 121.8 121.8 121.8 121.8 121.8 121.8 121.8 121.8

Hot Water Reheat / Heat - Rated at 180°F EWT / 160°F LWT & 75°FDB/61.1°FWB EAT (Optional)

Total Capacity, MBH 157.9 191.9 162.9 192.9 162.9 192.9 165.9 191.4

GPM / (Pressure Drop, ft H2O) 13 / (13) 17 / (20) 14 / (13) 17 / (20) 14 / (13) 17 / (20) 14 / (14) 17 / (19)

Control Valve ON/OFF, 2-WAY, 1”, 300PSI, CV=8.0

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Standard)

Lbs/Hr, (kW Power Input) 20 / (6.8) 20 / (6.8) 20 / (6.8) 20 / (6.8) 20 / (6.8) 20 / (6.8) 20 / (6.8) 20 / (6.8)

Std Control Proportional Proportional Proportional Proportional Proportional Proportional Proportional Proportional

Filters - MERV 8 Average Dust Spot Efficiency, Throwaway (Standard), MERV 11 Average Dust Spot Efficiency (Optional)

Actual Size, H"xW"xD" (Qty)35 7/8 x 24 3/4 x 3

3/4 (4) 24 3/4 x 21 x 3

3/4 (2)

37 x 18 1/2 x 3 3/4 (6)

35 7/8 x 24 3/4 x 3 3/4 (4)

24 3/4 x 21 x 3 3/4 (2)

37 x 18 1/2 x 3 3/4 (6)

35 7/8 x 24 3/4 x 3 3/4 (4)

24 3/4 x 21 x 3 3/4 (2)

37 x 18 1/2 x 3 3/4 (6)

35 7/8 x 24 3/4 x 3 3/4 (4)

24 3/4 x 21 x 3 3/4 (2)

36 1/2 x 25 3/8 x 6 (3)

25 3/8 x 17 3/8 x 6 (1)

Filter Face Area, ft2 28.5 31.9 28.5 31.9 28.5 31.9 28.5 31.9

Connection Sizes - Copper, (Water In/Out connections are sized for flow rates at 75°FDB/62.5°FWB EAT conditions.)

Water In/Out, OD"(see drawing for quantity)

2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8

Condensate Drain w/o Pump, OD" 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8

Condensate Drain w/ Pump, OD" 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Humidifier Inlet, OD" 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4

HW Reheat / Heat In/Out, OD" 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8

Physical Data

Approximate Unit Weight 2,000 lbs 2,200 lbs 2,100 lbs 2,300 lbs 2,200 lbs 2,400 lbs 2,300 lbs 2,500 lbs

Approximate Shipping Weight 2,200 lbs 2,400 lbs 2,800 lbs 2,500 lbs 2,400 lbs 2,600 lbs 2,500 lbs 2,700 lbs

Unit Dimensions: H”xW”xD”76.2 x 118.4

x 40.3

88.1 x 118.4 x 40.376.2 x 118.4

x 40.3

88.1 x 118.4 x 40.3 76.2 x 118.4

x 40.3

88.1 x 118.4 x 40.3 76.2 x 118.4

x 40.3

88.1 x 118.4 x 40.3

(w/ Hot Water Reheat) (91.1 x 118.4 x 40.3)

(91.1 x 118.4 x 40.3)

(91.1 x 118.4 x 40.3)

(91.1 x 118.4 x 40.3)

Unit Shipping Dimensions: H”xW”xD” 83 x 124 x 46

95 x 124 x 4683 x 124 x 46

95 x 124 x 4683 x 124 x 46

95 x 124 x 4683 x 124 x 46

95 x 124 x 46

(w/ Hot Water Reheat) (98 x 124 x 46) (98 x 124 x 46) (98 x 124 x 46) (98 x 124 x 46)

Page 11: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

7

Floor Mounted Air ConditionersTech

nical Sp

ecificatio

ns

Model CFD-280-C1 CFU-280-C1 CFD-310-C1 CFD-360-C1 CFD-510-C1 CFD-630-C1 CFD-730-C1

Chilled Water Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions

2-way Modulating (standard)

Size" / (Cv) 2 / (60) 2 / (60) 2 / (60) 3 / (124)3 / (124)

Qty 23 / (124)

Qty 23 / (124)

Qty 2

Valve Pressure Rating - psi 600 600 600 600 600 600 600

Close-off Pressure Rating - psi 200 200 200 200 200 200 200

3-way Modulating (optional)

Size" / (Cv) 2 / (60) 2 / (60) 2 / (60) N/A N/A N/A N/A

Valve Pressure Rating - psi 400 400 400 N/A N/A N/A N/A

Close-off Pressure Rating - psi 200 200 200 N/A N/A N/A N/A

Chilled Water Coil - Aluminum Fin, Copper Tube

Rows/Face Area (ft2) 6 / (70.2) 6 / (70.2) 6 / (70.2) 6 / (82.8) 8 / (123.8) 8 / (123.8) 8 / (123.8)

Face Velocity, fpm 342 294 413 386 291 388 485

Evaporator Blower / Motor - Backward Inclined Direct Driven EC

Nominal Horsepower Each 5.3 5.3 5.3 5.3 4.2 4.2 4.2

Rated Air Flow, CFM @ .3” H2O ESP 24,000 20,600 29,000 32,000 36,000 48,000 60,000

Quantity of Blowers 3 3 4 4 6 8 10

Reheat / Heat - Performance Capacities Include Evaporator Blower Motor Heat @ Rated CFM & ESP

Electric Reheat / Heat - Finned Tubular Heaters, (Standard)

Number of Stages 3 3 3 3 N/A N/A N/A

Heater Rating, kW 27.0 27.0 27.0 27.0 N/A N/A N/A

Total Capacity, MBH 121.8 121.8 131.7 131.7 N/A N/A N/A

Hot Water Reheat / Heat - Rated at 180°F EWT / 160°F LWT & 75°FDB/61.1°FWB EAT (Optional)

Total Capacity, MBH 162.6 192.4 183.2 179.4 N/A N/A N/A

GPM / (Pressure Drop, ft H2O) 14 / (16) 17 / (22) 15 / (18) 14 / (17) N/A N/A N/A

Control Valve ON/OFF, 2-WAY, 1”, 300PSI, CV=8.0

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Standard)

lbs/hr (kW Power Input) 20 / (6.8) 20 / (6.8) 20 / (6.8) 30 / (10.2) N/A N/A N/A

Std Control Proportional Proportional Proportional Proportional N/A N/A N/A

Filters - MERV 8 Average Dust Spot Efficiency, Throwaway (Standard), MERV 11 Average Dust Spot Efficiency (Optional)

Actual Size, H"x W"x D" (Qty) 46 1/2 x 18 1/2 x 3 3/4 (6)

35 7/8 x 24 3/4 x 3 3/4 (1)

24 3/4 x 21 x 3 3/4 (2)45 x 24 3/4 x 3 3/4(3)

37 x 29 x 3 3/4 (8) External Filter Plenum

37 x 25 x 3 3/4 (10) External Filter Plenum

37 x 20 1/2 x 3 3/4 (24)

External Filter Plenum

37 x 20 1/2 x 3 3/4 (24)

External Filter Plenum

37 x 20 1/2 x 3 3/4 (24)

External Filter Plenum

Filter Face Area, ft2 35.8 36.6 59.6 64.2 126.4 126.4 126.4

Connection Sizes - Copper, (Water In/Out connections are sized for flow rates at 75°FDB/62.5°FWB EAT conditions.)

Water In/Out, OD" (see drawing for quantity)

2 5/8 2 5/8 2 5/8 3 1/8 2 5/8 2 5/8 3 1/8

Condensate Drain w/o Pump, OD" 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8

Condensate Drain w/ Pump, OD'' 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Humidifier Inlet, OD" 1/4 1/4 1/4 1/4 N/A N/A N/A

HW Reheat / Heat In/Out, OD" 7/8 7/8 7/8 7/8 N/A N/A N/A

Physical Data

Approximate Unit Weight 2,900 lbs 3,000 lbs 3,200 lbs 3,400 lbs 4,100 lbs 4,300 lbs 4,500 lbs

Approximate Shipping Weight 3,100 lbs 3,200 lbs 3,400 lbs 3,600 lbs 4,500 lbs 4,700 lbs 4,900 lbs

Unit Dimensions: H”x W”x D”88.1 x 118.4

x 50.2

96.0 x 118.4 x 50.2 88.1 x 118.4

x 50.288.1 x 127.9

x 50.2

96.0 x 154.0 x 65.7

96.0 x 154.0 x 65.7

96.0 x 154.0 x 65.7

(w/ Hot Water Reheat) (99.0 x 118.4 x 50.2)

(N/A) (N/A) (N/A)

Unit Dimensions w/ Filter Plenum: H”x W”x D”

N/A N/A124.1 x 118.4

x 50.2124.1 x 127.9

x 50.2132.0 x 154.0

x 65.7132.0 x 154.0

x 65.7132.0 x 154.0

x 65.7

Unit Shipping Dimensions: H”xW”xD” 95 x 125 x 57

103 x 125 x 57 95 x 125 x 57 95 x 135 x 57

102 x 160 x 72 102 x 160 x 72 102 x 160 x 72

(w/ Hot Water Reheat) (106 x 125 x 57) (N/A) (N/A) (N/A)

Filter Plenum Shipping Dimensions: H”xW”xD”

N/A N/A 43 x 125 x 57 43 x 135 x 57 43 x 160 x 72 43 x 160 x 72 43 x 160 x 72

Page 12: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

8

CyberAiR CFD/CFU-CModel CFD- 060-C1 090-C1 120-C1 150-C1 180-C1 190-C1 230-C1

NET COOLING CAPACITY - MBH @ 45°F EWT, 0% Glycol Solution (Includes motor heat @ rated CFM & ESP)

85°FDB/65.9°FWB, 36% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 349 399 496 454 582 675 772

Sensible, MBH 329 358 422 436 536 588 652

Flow Rate, GPM / (Pressure Drop, ft H2O) 74 / (49) 84 / (38) 104 / (39) 97 / (42) 123 / (38) 141 / (63) 161 / (42)

Med. Flow(12°F ∆Tw)

Total, MBH 338 389 481 438 566 660 758

Sensible, MBH 321 352 415 423 525 579 645

Flow Rate, GPM / (Pressure Drop, ft H2O) 60 / (34) 69 / (27) 84 / (27) 78 / (30) 100 / (27) 116 / (45) 132 / (30)

Low Flow(14°F ∆Tw)

Total, MBH 326 377 468 422 550 645 747

Sensible, MBH 311 343 409 408 512 569 639

Flow Rate, GPM / (Pressure Drop, ft H2O) 50 / (25) 57 / (20) 70 / (21) 65 / (22) 83 / (20) 97 / (33) 111 / (23)

80°FDB/64.2°FWB, 42% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 300 347 432 388 504 594 680

Sensible, MBH 277 304 360 366 454 503 559

Flow Rate, GPM / (Pressure Drop, ft H2O) 65 / (38) 74 / (30) 91 / (31) 84 / (33) 107 / (30) 125 / (51) 143 / (34)

Med. Flow(12°F ∆Tw)

Total, MBH 288 333 416 371 487 574 666

Sensible, MBH 268 295 352 352 442 491 552

Flow Rate, GPM / (Pressure Drop, ft H2O) 52 / (26) 59 / (21) 73 / (22) 67 / (23) 87 / (22) 101 / (35) 116 / (25)

Low Flow(14°F ∆Tw)

Total, MBH 273 320 402 354 468 559 647

Sensible, MBH 257 286 345 337 428 482 541

Flow Rate, GPM / (Pressure Drop, ft H2O) 42 / (19) 49 / (16) 61 / (17) 55 / (17) 72 / (16) 85 / (27) 97 / (19)

75°FDB/62.5°FWB, 50% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 250 292 367 322 426 509 588

Sensible, MBH 223 247 295 295 369 414 463

Flow Rate, GPM / (Pressure Drop, ft H2O) 54 / (29) 63 / (23) 78 / (24) 71 / (25) 92 / (24) 108 / (40) 124 / (27)

Med. Flow(12°F ∆Tw)

Total, MBH 234 276 350 302 404 491 567

Sensible, MBH 213 237 286 279 355 404 452

Flow Rate, GPM / (Pressure Drop, ft H2O) 43 / (20) 50 / (16) 62 / (17) 56 / (18) 73 / (17) 87 / (28) 100 / (19)

Low Flow(14°F ∆Tw)

Total, MBH 218 260 333 279 379 474 545

Sensible, MBH 200 227 278 261 337 393 441

Flow Rate, GPM / (Pressure Drop, ft H2O) 34 / (14) 41 / (12) 51 / (13) 45 / (13) 59 / (13) 72 / (21) 83 / (15)

85°FDB/64.5°FWB, 32% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 325 390 477 433 540 653 743

Sensible, MBH 325 372 438 433 540 608 677

Flow Rate, GPM / (Pressure Drop, ft H2O) 69 / (44) 83 / (36) 100 / (37) 93 / (39) 115 / (34) 137 / (59) 155 / (39)

Med. Flow(12°F ∆Tw)

Total, MBH 311 382 469 415 520 643 736

Sensible, MBH 311 366 434 415 520 600 672

Flow Rate, GPM / (Pressure Drop, ft H2O) 56 / (30) 68 / (26) 82 / (26) 75 / (28) 92 / (24) 113 / (43) 128 / (28)

Low Flow(14°F ∆Tw)

Total, MBH 294 326 398 395 500 633 729

Sensible, MBH 294 326 398 395 500 592 667

Flow Rate, GPM / (Pressure Drop, ft H2O) 45 / (21) 50 / (16) 60 / (16) 61 / (20) 76 / (18) 95 / (32) 109 / (22)

80°FDB/62.9°FWB, 38% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 275 338 416 366 492 570 653

Sensible, MBH 275 317 374 366 472 520 581

Flow Rate, GPM / (Pressure Drop, ft H2O) 59 / (33) 72 / (29) 88 / (29) 80 / (31) 105 / (29) 120 / (48) 137 / (32)

Med. Flow(12°F ∆Tw)

Total, MBH 258 327 405 347 439 558 644

Sensible, MBH 258 308 369 347 439 511 575

Flow Rate, GPM / (Pressure Drop, ft H2O) 47 / (22) 58 / (21) 71 / (21) 63 / (21) 79 / (19) 99 / (34) 113 / (23)

Low Flow(14°F ∆Tw)

Total, MBH 239 267 395 325 412 547 631

Sensible, MBH 239 267 363 325 412 502 568

Flow Rate, GPM / (Pressure Drop, ft H2O) 37 / (16) 41 / (13) 60 / (16) 51 / (16) 64 / (14) 83 / (26) 95 / (18)

75°FDB/61.1°FWB, 45% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 244 282 351 316 412 483 558

Sensible, MBH 235 260 311 308 388 431 485

Flow Rate, GPM / (Pressure Drop, ft H2O) 53 / (28) 61 / (22) 75 / (23) 70 / (25) 89 / (22) 103 / (37) 118 / (25)

Med. Flow(12°F ∆Tw)

Total, MBH 202 270 339 275 395 470 544

Sensible, MBH 202 251 304 275 374 422 477

Flow Rate, GPM / (Pressure Drop, ft H2O) 37 / (16) 49 / (16) 60 / (16) 51 / (16) 71 / (16) 84 / (26) 96 / (18)

Low Flow(14°F ∆Tw)

Total, MBH 181 204 247 248 318 457 529

Sensible, MBH 181 204 247 248 318 411 468

Flow Rate, GPM / (Pressure Drop, ft H2O) 29 / (12) 32 / (10) 39 / (9) 40 / (12) 50 / (11) 70 / (20) 80 / (14)

Perf

orm

ance

/Cap

acit

y D

ata

- D

ow

nfl

ow

/ 4

5° E

WT

/ 0%

Gly

col

Page 13: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

9

Floor Mounted Air ConditionersPerfo

rman

ce/Cap

acity Data - D

ow

nfl

ow

/ 45° EWT / 0%

Glyco

l

Model CFD- 280-C1 310-C1 360-C1 510-C1 630-C1 730-C1

NET COOLING CAPACITY - MBH @ 45°F EWT, 0% Glycol Solution (Includes motor heat @ rated CFM & ESP)

85°FDB/65.9°FWB, 36% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 986 1,122 1,274 1,738 2,177 2,570

Sensible, MBH 828 965 1,084 1,362 1,751 2,120

Flow Rate, GPM / (Pressure Drop, ft H2O) 206 / (55) 236 / (71) 266 / (42) 362 / (57) 454 / (84) 536 / (113)

Med. Flow(12°F ∆Tw)

Total, MBH 969 1,104 1,254 1,714 2,147 2,537

Sensible, MBH 820 955 1,074 1,352 1,737 2,103

Flow Rate, GPM / (Pressure Drop, ft H2O) 169 / (39) 193 / (50) 218 / (31) 298 / (41) 372 / (60) 442 / (80)

Low Flow(14°F ∆Tw)

Total, MBH 953 1,087 1,235 1,692 2,121 2,508

Sensible, MBH 811 945 1,062 1,340 1,724 2,087

Flow Rate, GPM / (Pressure Drop, ft H2O) 142 / (30) 163 / (37) 185 / (24) 252 / (32) 316 / (46) 374 / (61)

80°FDB/64.2°FWB, 42% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 870 986 1,122 1,548 1,934 2,276

Sensible, MBH 710 824 929 1,179 1,511 1,824

Flow Rate, GPM / (Pressure Drop, ft H2O) 182 / (45) 208 / (57) 235 / (35) 324 / (47) 404 / (69) 478 / (92)

Med. Flow(12°F ∆Tw)

Total, MBH 851 966 1,099 1,522 1,901 2,240

Sensible, MBH 700 813 916 1,167 1,495 1,804

Flow Rate, GPM / (Pressure Drop, ft H2O) 149 / (32) 170 / (40) 193 / (25) 266 / (34) 332 / (50) 392 / (66)

Low Flow(14°F ∆Tw)

Total, MBH 826 946 1,077 1,497 1,871 2,207

Sensible, MBH 687 801 903 1,154 1,480 1,787

Flow Rate, GPM / (Pressure Drop, ft H2O) 124 / (24) 143 / (30) 162 / (19) 224 / (26) 280 / (37) 332 / (49)

75°FDB/62.5°FWB, 50% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 753 849 969 1,360 1,691 1,983

Sensible, MBH 589 680 769 990 1,264 1,519

Flow Rate, GPM / (Pressure Drop, ft H2O) 159 / (35) 181 / (44) 205 / (28) 286 / (39) 356 / (56) 418 / (74)

Med. Flow(12°F ∆Tw)

Total, MBH 724 825 943 1,329 1,652 1,940

Sensible, MBH 574 666 754 976 1,245 1,497

Flow Rate, GPM / (Pressure Drop, ft H2O) 128 / (25) 147 / (31) 166 / (20) 234 / (28) 290 / (40) 342 / (52)

Low Flow(14°F ∆Tw)

Total, MBH 696 794 908 1,299 1,618 1,901

Sensible, MBH 560 649 734 962 1,228 1,476

Flow Rate, GPM / (Pressure Drop, ft H2O) 106 / (19) 122 / (23) 138 / (15) 196 / (21) 244 / (30) 288 / (39)

85°FDB/64.5°FWB, 32% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 947 1,085 1,229 1,633 2,064 2,457

Sensible, MBH 858 1,005 1,127 1,389 1,798 2,190

Flow Rate, GPM / (Pressure Drop, ft H2O) 198 / (52) 228 / (67) 257 / (40) 340 / (52) 430 / (77) 514 / (105)

Med. Flow(12°F ∆Tw)

Total, MBH 938 1,076 1,218 1,620 2,050 2,443

Sensible, MBH 852 998 1,120 1,383 1,791 2,180

Flow Rate, GPM / (Pressure Drop, ft H2O) 163 / (37) 189 / (48) 212 / (29) 282 / (38) 356 / (56) 426 / (75)

Low Flow(14°F ∆Tw)

Total, MBH 928 1,067 1,209 1,611 2,039 2,432

Sensible, MBH 846 991 1,113 1,378 1,784 2,173

Flow Rate, GPM / (Pressure Drop, ft H2O) 139 / (28) 161 / (36) 181 / (23) 240 / (29) 304 / (43) 364 / (58)

80°FDB/62.9°FWB, 38% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 832 951 1,079 1,453 1,830 2,171

Sensible, MBH 737 859 966 1,204 1,553 1,885

Flow Rate, GPM / (Pressure Drop, ft H2O) 175 / (42) 201 / (53) 227 / (33) 304 / (43) 384 / (63) 456 / (85)

Med. Flow(12°F ∆Tw)

Total, MBH 820 939 1,066 1,438 1,812 2,152

Sensible, MBH 729 851 958 1,196 1,543 1,874

Flow Rate, GPM / (Pressure Drop, ft H2O) 144 / (30) 166 / (38) 187 / (24) 252 / (32) 318 / (46) 378 / (61)

Low Flow(14°F ∆Tw)

Total, MBH 805 926 1,052 1,425 1,798 2,137

Sensible, MBH 720 842 947 1,189 1,535 1,864

Flow Rate, GPM / (Pressure Drop, ft H2O) 121 / (23) 140 / (29) 158 / (19) 214 / (24) 270 / (35) 322 / (47)

75°FDB/61.1°FWB, 45% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 712 811 922 1,260 1,581 1,871

Sensible, MBH 616 716 807 1,016 1,307 1,583

Flow Rate, GPM / (Pressure Drop, ft H2O) 151 / (32) 173 / (41) 196 / (26) 266 / (34) 334 / (50) 396 / (67)

Med. Flow(12°F ∆Tw)

Total, MBH 694 795 906 1,242 1,561 1,848

Sensible, MBH 605 705 795 1,007 1,297 1,569

Flow Rate, GPM / (Pressure Drop, ft H2O) 123 / (23) 142 / (29) 160 / (19) 218 / (25) 276 / (37) 326 / (48)

Low Flow(14°F ∆Tw)

Total, MBH 675 774 882 1,224 1,543 1,828

Sensible, MBH 593 691 780 998 1,286 1,556

Flow Rate, GPM / (Pressure Drop, ft H2O) 103 / (18) 119 / (22) 134 / (15) 184 / (20) 234 / (28) 278 / (37)

Page 14: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

10

CyberAiR CFD/CFU-CPe

rfo

rman

ce/C

apac

ity

Dat

a -

Up

flo

w /

45°

EW

T /

0% G

lyco

l

Model CFU- 060-C1 090-C1 120-C1 150-C1 180-C1 190-C1 230-C1 280-C1

NET COOLING CAPACITY - MBH @ 45°F EWT, 0% Glycol Solution (Includes motor heat @ rated CFM & ESP)

85°FDB/65.9°FWB, 36% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 339 387 416 454 556 646 690 876

Sensible, MBH 317 345 346 436 507 556 572 722

Flow Rate, GPM / (Pressure Drop, ft H2O) 72 / (47) 82 / (36) 88 / (29) 97 / (42) 118 / (35) 136 / (58) 144 / (35) 184 / (45)

Med. Flow(12°F ∆Tw)

Total, MBH 328 376 403 438 540 628 678 861

Sensible, MBH 310 338 340 423 496 546 566 715

Flow Rate, GPM / (Pressure Drop, ft H2O) 58 / (32) 67 / (25) 71 / (21) 78 / (30) 95 / (25) 110 / (41) 118 / (25) 151 / (32)

Low Flow(14°F ∆Tw)

Total, MBH 316 365 391 422 524 614 663 841

Sensible, MBH 300 331 334 408 484 537 558 705

Flow Rate, GPM / (Pressure Drop, ft H2O) 48 / (24) 55 / (19) 59 / (16) 65 / (22) 80 / (19) 93 / (31) 99 / (19) 126 / (24)

80°FDB/64.2°FWB, 42% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 291 336 363 388 481 566 609 773

Sensible, MBH 268 293 295 366 429 475 491 620

Flow Rate, GPM / (Pressure Drop, ft H2O) 63 / (37) 72 / (29) 77 / (24) 84 / (33) 103 / (28) 120 / (47) 128 / (28) 163 / (37)

Med. Flow(12°F ∆Tw)

Total, MBH 278 323 348 371 464 550 592 752

Sensible, MBH 258 285 288 352 417 466 483 609

Flow Rate, GPM / (Pressure Drop, ft H2O) 50 / (25) 58 / (20) 62 / (17) 67 / (23) 83 / (20) 97 / (33) 104 / (21) 132 / (26)

Low Flow(14°F ∆Tw)

Total, MBH 265 309 336 354 445 532 574 730

Sensible, MBH 248 276 282 337 404 455 474 598

Flow Rate, GPM / (Pressure Drop, ft H2O) 41 / (18) 48 / (15) 51 / (13) 55 / (17) 68 / (15) 81 / (25) 87 / (16) 110 / (20)

75°FDB/62.5°FWB, 50% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 243 283 308 322 406 485 526 667

Sensible, MBH 216 238 242 295 349 391 406 513

Flow Rate, GPM / (Pressure Drop, ft H2O) 53 / (28) 61 / (22) 66 / (19) 71 / (25) 88 / (22) 104 / (37) 112 / (23) 142 / (29)

Med. Flow(12°F ∆Tw)

Total, MBH 227 267 293 302 385 468 504 640

Sensible, MBH 205 229 234 279 335 381 396 499

Flow Rate, GPM / (Pressure Drop, ft H2O) 42 / (19) 48 / (16) 53 / (14) 56 / (18) 70 / (16) 83 / (26) 89 / (17) 114 / (21)

Low Flow(14°F ∆Tw)

Total, MBH 211 252 278 279 360 451 483 614

Sensible, MBH 193 219 227 261 318 371 385 486

Flow Rate, GPM / (Pressure Drop, ft H2O) 33 / (14) 39 / (12) 43 / (11) 45 / (13) 56 / (12) 69 / (20) 74 / (13) 94 / (16)

85°FDB/64.5°FWB, 32% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 315 378 398 433 543 620 660 836

Sensible, MBH 315 358 358 433 526 573 591 745

Flow Rate, GPM / (Pressure Drop, ft H2O) 67 / (41) 80 / (34) 84 / (27) 93 / (39) 115 / (34) 131 / (55) 138 / (32) 176 / (42)

Med. Flow(12°F ∆Tw)

Total, MBH 301 370 389 415 495 610 652 827

Sensible, MBH 301 352 354 415 495 565 587 740

Flow Rate, GPM / (Pressure Drop, ft H2O) 54 / (28) 65 / (25) 69 / (20) 75 / (28) 88 / (22) 107 / (39) 114 / (24) 145 / (30)

Low Flow(14°F ∆Tw)

Total, MBH 284 315 382 395 475 601 644 815

Sensible, MBH 284 315 350 395 475 558 582 734

Flow Rate, GPM / (Pressure Drop, ft H2O) 44 / (20) 48 / (16) 58 / (15) 61 / (20) 73 / (17) 91 / (30) 97 / (18) 123 / (23)

80°FDB/62.9°FWB, 38% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 286 327 346 366 468 541 581 736

Sensible, MBH 279 305 306 366 446 490 508 640

Flow Rate, GPM / (Pressure Drop, ft H2O) 62 / (36) 70 / (27) 74 / (22) 80 / (31) 100 / (27) 115 / (44) 123 / (27) 156 / (34)

Med. Flow(12°F ∆Tw)

Total, MBH 249 316 337 347 455 530 570 721

Sensible, MBH 249 297 301 347 434 482 502 632

Flow Rate, GPM / (Pressure Drop, ft H2O) 45 / (21) 57 / (20) 60 / (16) 63 / (21) 81 / (20) 94 / (32) 100 / (20) 127 / (25)

Low Flow(14°F ∆Tw)

Total, MBH 231 258 272 325 390 519 558 708

Sensible, MBH 231 258 272 325 390 473 495 624

Flow Rate, GPM / (Pressure Drop, ft H2O) 36 / (15) 40 / (12) 42 / (10) 51 / (16) 61 / (13) 79 / (24) 85 / (15) 107 / (19)

75°FDB/61.1°FWB, 45% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 237 273 292 316 392 459 494 627

Sensible, MBH 227 250 253 308 367 407 423 534

Flow Rate, GPM / (Pressure Drop, ft H2O) 52 / (27) 59 / (21) 63 / (17) 70 / (25) 85 / (21) 98 / (34) 105 / (21) 134 / (27)

Med. Flow(12°F ∆Tw)

Total, MBH 195 261 282 275 375 447 481 610

Sensible, MBH 195 242 248 275 353 398 416 524

Flow Rate, GPM / (Pressure Drop, ft H2O) 36 / (15) 47 / (15) 51 / (13) 51 / (16) 68 / (15) 80 / (24) 86 / (16) 109 / (19)

Low Flow(14°F ∆Tw)

Total, MBH 175 197 271 248 300 434 468 593

Sensible, MBH 175 197 242 248 300 388 408 515

Flow Rate, GPM / (Pressure Drop, ft H2O) 28 / (11) 31 / (9) 42 / (10) 40 / (12) 48 / (10) 67 / (19) 72 / (12) 91 / (15)

Page 15: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

11

Floor Mounted Air ConditionersPerfo

rman

ce/Cap

acity Data - D

ow

nfl

ow

/ 50° EWT / 0%

Glyco

l

Model CFD- 060-C1 090-C1 120-C1 150-C1 180-C1 190-C1 230-C1

NET COOLING CAPACITY - MBH @ 50°F EWT, 0% Glycol Solution (Includes motor heat @ rated CFM & ESP)

85°FDB/65.9°FWB, 36% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 275 304 412 365 459 561 640

Sensible, MBH 275 304 386 365 459 532 596

Flow Rate, GPM / (Pressure Drop, ft H2O) 59 / (33) 65 / (25) 87 / (29) 80 / (30) 98 / (26) 119 / (46) 134 / (31)

Med. Flow(12°F ∆Tw)

Total, MBH 260 289 354 346 438 551 635

Sensible, MBH 260 289 354 346 438 523 592

Flow Rate, GPM / (Pressure Drop, ft H2O) 47 / (23) 52 / (17) 63 / (17) 63 / (21) 78 / (19) 97 / (33) 111 / (23)

Low Flow(14°F ∆Tw)

Total, MBH 242 270 332 327 416 476 545

Sensible, MBH 242 270 332 327 416 476 545

Flow Rate, GPM / (Pressure Drop, ft H2O) 38 / (16) 42 / (13) 51 / (13) 51 / (16) 64 / (14) 73 / (21) 83 / (15)

80°FDB/64.2°FWB, 42% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 223 248 347 297 376 474 546

Sensible, MBH 223 248 324 297 376 444 501

Flow Rate, GPM / (Pressure Drop, ft H2O) 49 / (24) 54 / (18) 74 / (22) 66 / (22) 82 / (20) 101 / (35) 116 / (24)

Med. Flow(12°F ∆Tw)

Total, MBH 205 229 282 277 354 464 540

Sensible, MBH 205 229 282 277 354 435 496

Flow Rate, GPM / (Pressure Drop, ft H2O) 38 / (16) 42 / (13) 51 / (13) 52 / (16) 64 / (14) 83 / (26) 95 / (18)

Low Flow(14°F ∆Tw)

Total, MBH 185 208 254 251 324 384 432

Sensible, MBH 185 208 254 251 324 384 432

Flow Rate, GPM / (Pressure Drop, ft H2O) 30 / (12) 33 / (10) 40 / (10) 41 / (12) 51 / (11) 60 / (16) 67 / (11)

75°FDB/62.5°FWB, 50% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 168 188 281 227 291 386 450

Sensible, MBH 168 188 258 227 291 354 403

Flow Rate, GPM / (Pressure Drop, ft H2O) 38 / (16) 42 / (13) 61 / (17) 52 / (16) 65 / (14) 84 / (26) 96 / (18)

Med. Flow(12°F ∆Tw)

Total, MBH 147 166 203 201 259 373 437

Sensible, MBH 147 166 203 201 259 343 394

Flow Rate, GPM / (Pressure Drop, ft H2O) 28 / (11) 31 / (9) 38 / (9) 39 / (11) 49 / (10) 68 / (19) 78 / (14)

Low Flow(14°F ∆Tw)

Total, MBH 124 141 167 171 223 280 307

Sensible, MBH 124 141 167 171 223 280 307

Flow Rate, GPM / (Pressure Drop, ft H2O) 21 / (8) 23 / (7) 27 / (7) 29 / (8) 37 / (8) 45 / (11) 49 / (8)

85°FDB/64.5°FWB, 32% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 274 304 373 365 458 513 587

Sensible, MBH 274 304 373 365 458 513 587

Flow Rate, GPM / (Pressure Drop, ft H2O) 59 / (33) 65 / (25) 79 / (25) 79 / (30) 98 / (26) 109 / (40) 124 / (27)

Med. Flow(12°F ∆Tw)

Total, MBH 260 289 354 346 438 495 570

Sensible, MBH 260 289 354 346 438 495 570

Flow Rate, GPM / (Pressure Drop, ft H2O) 47 / (23) 52 / (17) 63 / (17) 63 / (21) 78 / (19) 88 / (28) 100 / (19)

Low Flow(14°F ∆Tw)

Total, MBH 242 270 331 327 416 476 544

Sensible, MBH 242 270 331 327 416 476 544

Flow Rate, GPM / (Pressure Drop, ft H2O) 38 / (16) 42 / (13) 51 / (13) 51 / (16) 64 / (14) 73 / (21) 82 / (15)

80°FDB/62.9°FWB, 38% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 223 248 305 296 376 426 490

Sensible, MBH 223 248 305 296 376 426 490

Flow Rate, GPM / (Pressure Drop, ft H2O) 49 / (24) 54 / (18) 65 / (18) 66 / (22) 82 / (20) 92 / (30) 104 / (21)

Med. Flow(12°F ∆Tw)

Total, MBH 205 229 282 277 354 406 464

Sensible, MBH 205 229 282 277 354 406 464

Flow Rate, GPM / (Pressure Drop, ft H2O) 38 / (16) 42 / (13) 51 / (13) 52 / (16) 64 / (14) 73 / (21) 83 / (15)

Low Flow(14°F ∆Tw)

Total, MBH 184 208 254 251 324 384 432

Sensible, MBH 184 208 254 251 324 384 432

Flow Rate, GPM / (Pressure Drop, ft H2O) 30 / (12) 33 / (10) 40 / (10) 41 / (12) 51 / (11) 60 / (16) 66 / (11)

75°FDB/61.1°FWB, 45% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 168 188 232 226 291 336 383

Sensible, MBH 168 188 232 226 291 336 383

Flow Rate, GPM / (Pressure Drop, ft H2O) 38 / (16) 42 / (13) 51 / (13) 52 / (16) 65 / (14) 74 / (22) 83 / (15)

Med. Flow(12°F ∆Tw)

Total, MBH 147 166 203 200 259 313 349

Sensible, MBH 147 166 203 200 259 313 349

Flow Rate, GPM / (Pressure Drop, ft H2O) 28 / (11) 31 / (9) 38 / (9) 39 / (11) 49 / (10) 58 / (15) 64 / (11)

Low Flow(14°F ∆Tw)

Total, MBH 124 140 167 170 223 279 307

Sensible, MBH 124 140 167 170 223 279 307

Flow Rate, GPM / (Pressure Drop, ft H2O) 21 / (8) 23 / (7) 27 / (7) 29 / (8) 37 / (8) 45 / (11) 49 / (8)

Page 16: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

12

CyberAiR CFD/CFU-CPe

rfo

rman

ce/C

apac

ity

Dat

a -

Do

wn

flo

w /

50°

EW

T /

0% G

lyco

l

Model CFD- 280-C1 310-C1 360-C1 510-C1 630-C1 730-C1

NET COOLING CAPACITY - MBH @ 50°F EWT, 0% Glycol Solution (Includes motor heat @ rated CFM & ESP)

85°FDB/65.9°FWB, 36% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 815 936 1,059 1,395 1,769 2,113

Sensible, MBH 754 886 993 1,211 1,574 1,923

Flow Rate, GPM / (Pressure Drop, ft H2O) 171 / (40) 198 / (52) 223 / (32) 292 / (40) 372 / (59) 444 / (81)

Med. Flow(12°F ∆Tw)

Total, MBH 809 827 942 1,389 1,764 2,108

Sensible, MBH 750 827 942 1,208 1,570 1,917

Flow Rate, GPM / (Pressure Drop, ft H2O) 142 / (29) 147 / (31) 166 / (20) 244 / (30) 310 / (44) 370 / (59)

Low Flow(14°F ∆Tw)

Total, MBH 695 795 908 1,385 1,760 2,102

Sensible, MBH 695 795 908 1,205 1,567 1,911

Flow Rate, GPM / (Pressure Drop, ft H2O) 106 / (18) 122 / (23) 138 / (15) 208 / (23) 264 / (34) 316 / (45)

80°FDB/64.2°FWB, 42% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 696 797 904 1,204 1,522 1,815

Sensible, MBH 635 742 835 1,027 1,332 1,623

Flow Rate, GPM / (Pressure Drop, ft H2O) 148 / (31) 170 / (40) 192 / (25) 254 / (32) 322 / (47) 386 / (63)

Med. Flow(12°F ∆Tw)

Total, MBH 687 678 894 1,197 1,515 1,806

Sensible, MBH 629 678 827 1,023 1,326 1,615

Flow Rate, GPM / (Pressure Drop, ft H2O) 122 / (23) 122 / (23) 158 / (19) 212 / (24) 268 / (34) 320 / (46)

Low Flow(14°F ∆Tw)

Total, MBH 553 629 724 1,191 1,508 1,796

Sensible, MBH 553 629 724 1,019 1,321 1,607

Flow Rate, GPM / (Pressure Drop, ft H2O) 85 / (14) 98 / (16) 111 / (12) 180 / (19) 228 / (27) 272 / (36)

75°FDB/62.5°FWB, 50% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 572 654 745 1,009 1,271 1,510

Sensible, MBH 510 594 670 836 1,080 1,312

Flow Rate, GPM / (Pressure Drop, ft H2O) 123 / (23) 142 / (29) 160 / (19) 216 / (25) 272 / (35) 324 / (47)

Med. Flow(12°F ∆Tw)

Total, MBH 556 509 585 1,000 1,260 1,495

Sensible, MBH 500 509 585 830 1,073 1,301

Flow Rate, GPM / (Pressure Drop, ft H2O) 100 / (17) 94 / (16) 107 / (11) 178 / (19) 226 / (26) 268 / (34)

Low Flow(14°F ∆Tw)

Total, MBH 394 445 520 986 1,247 1,477

Sensible, MBH 394 445 520 823 1,063 1,287

Flow Rate, GPM / (Pressure Drop, ft H2O) 62 / (10) 72 / (11) 82 / (9) 150 / (15) 192 / (21) 228 / (27)

85°FDB/64.5°FWB, 32% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 748 855 970 1,349 1,632 1,945

Sensible, MBH 748 855 970 1,261 1,613 1,945

Flow Rate, GPM / (Pressure Drop, ft H2O) 158 / (35) 182 / (45) 205 / (28) 284 / (38) 344 / (52) 412 / (70)

Med. Flow(12°F ∆Tw)

Total, MBH 727 826 941 1,355 1,604 1,905

Sensible, MBH 727 826 941 1,264 1,601 1,905

Flow Rate, GPM / (Pressure Drop, ft H2O) 128 / (25) 147 / (31) 166 / (20) 238 / (29) 282 / (37) 336 / (50)

Low Flow(14°F ∆Tw)

Total, MBH 695 795 907 1,360 1,570 1,856

Sensible, MBH 695 795 907 1,265 1,570 1,856

Flow Rate, GPM / (Pressure Drop, ft H2O) 105 / (18) 122 / (23) 138 / (15) 204 / (23) 238 / (28) 282 / (37)

80°FDB/62.9°FWB, 38% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 624 709 808 1,165 1,490 1,635

Sensible, MBH 624 709 808 1,073 1,402 1,635

Flow Rate, GPM / (Pressure Drop, ft H2O) 133 / (26) 153 / (33) 173 / (21) 246 / (30) 316 / (45) 350 / (53)

Med. Flow(12°F ∆Tw)

Total, MBH 592 677 774 1,168 1,343 1,587

Sensible, MBH 592 677 774 1,074 1,343 1,587

Flow Rate, GPM / (Pressure Drop, ft H2O) 106 / (18) 122 / (23) 138 / (16) 206 / (23) 238 / (29) 284 / (38)

Low Flow(14°F ∆Tw)

Total, MBH 551 628 723 1,036 1,300 1,526

Sensible, MBH 551 628 723 1,020 1,300 1,526

Flow Rate, GPM / (Pressure Drop, ft H2O) 85 / (14) 98 / (16) 111 / (12) 158 / (16) 198 / (22) 234 / (28)

75°FDB/61.1°FWB, 45% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 489 557 638 973 1,112 1,312

Sensible, MBH 489 557 638 887 1,107 1,312

Flow Rate, GPM / (Pressure Drop, ft H2O) 106 / (19) 123 / (23) 139 / (16) 208 / (23) 240 / (29) 284 / (38)

Med. Flow(12°F ∆Tw)

Total, MBH 447 507 584 973 1,068 1,252

Sensible, MBH 447 507 584 886 1,068 1,252

Flow Rate, GPM / (Pressure Drop, ft H2O) 82 / (13) 94 / (16) 107 / (11) 174 / (18) 194 / (21) 228 / (27)

Low Flow(14°F ∆Tw)

Total, MBH 393 445 516 798 1,005 1,174

Sensible, MBH 393 445 516 798 1,005 1,174

Flow Rate, GPM / (Pressure Drop, ft H2O) 62 / (10) 72 / (11) 82 / (9) 124 / (12) 156 / (16) 184 / (19)

Page 17: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

13

Floor Mounted Air ConditionersPerfo

rman

ce/Cap

acity Data - U

pfl

ow

/ 50° EWT / 0%

Glyco

l

Model CFU- 060-C1 090-C1 120-C1 150-C1 180-C1 190-C1 230-C1 280-C1

NET COOLING CAPACITY - MBH @ 50°F EWT, 0% Glycol Solution (Includes motor heat @ rated CFM & ESP)

85°FDB/65.9°FWB, 36% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 266 294 341 365 436 531 566 717

Sensible, MBH 266 294 314 365 436 500 519 653

Flow Rate, GPM / (Pressure Drop, ft H2O) 58 / (32) 63 / (23) 73 / (22) 80 / (30) 94 / (24) 113 / (42) 120 / (25) 152 / (33)

Med. Flow(12°F ∆Tw)

Total, MBH 252 279 295 346 416 523 562 712

Sensible, MBH 252 279 295 346 416 493 516 650

Flow Rate, GPM / (Pressure Drop, ft H2O) 46 / (22) 50 / (17) 53 / (14) 63 / (21) 75 / (17) 93 / (31) 99 / (19) 126 / (24)

Low Flow(14°F ∆Tw)

Total, MBH 234 261 276 327 394 453 482 612

Sensible, MBH 234 261 276 327 394 453 482 612

Flow Rate, GPM / (Pressure Drop, ft H2O) 37 / (16) 41 / (12) 43 / (10) 51 / (16) 61 / (13) 69 / (20) 74 / (13) 94 / (16)

80°FDB/64.2°FWB, 42% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 216 240 288 297 357 450 484 613

Sensible, MBH 216 240 263 297 357 418 437 550

Flow Rate, GPM / (Pressure Drop, ft H2O) 48 / (23) 52 / (18) 62 / (17) 66 / (22) 78 / (18) 96 / (33) 103 / (20) 131 / (26)

Med. Flow(12°F ∆Tw)

Total, MBH 198 222 235 277 336 440 476 602

Sensible, MBH 198 222 235 277 336 410 432 544

Flow Rate, GPM / (Pressure Drop, ft H2O) 37 / (16) 41 / (12) 43 / (10) 52 / (16) 61 / (13) 79 / (24) 85 / (15) 107 / (19)

Low Flow(14°F ∆Tw)

Total, MBH 178 201 211 251 306 365 383 485

Sensible, MBH 178 201 211 251 306 365 383 485

Flow Rate, GPM / (Pressure Drop, ft H2O) 29 / (11) 32 / (9) 33 / (8) 41 / (12) 49 / (10) 57 / (15) 59 / (10) 76 / (12)

75°FDB/62.5°FWB, 50% RH, 55°FDP

High Flow(10°F ∆Tw)

Total, MBH 162 216 233 227 276 366 396 502

Sensible, MBH 162 204 209 227 276 333 350 440

Flow Rate, GPM / (Pressure Drop, ft H2O) 37 / (16) 48 / (15) 51 / (13) 52 / (16) 62 / (13) 80 / (24) 86 / (16) 109 / (19)

Med. Flow(12°F ∆Tw)

Total, MBH 142 161 168 201 246 355 385 488

Sensible, MBH 142 161 168 201 246 323 343 432

Flow Rate, GPM / (Pressure Drop, ft H2O) 27 / (11) 31 / (9) 32 / (8) 39 / (11) 46 / (10) 65 / (18) 70 / (12) 88 / (14)

Low Flow(14°F ∆Tw)

Total, MBH 119 136 130 171 209 265 271 344

Sensible, MBH 119 136 130 171 209 265 271 344

Flow Rate, GPM / (Pressure Drop, ft H2O) 20 / (8) 23 / (7) 22 / (6) 29 / (8) 35 / (7) 43 / (11) 43 / (7) 55 / (8)

85°FDB/64.5°FWB, 32% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 266 294 310 365 435 486 521 660

Sensible, MBH 266 294 310 365 435 486 521 660

Flow Rate, GPM / (Pressure Drop, ft H2O) 58 / (32) 63 / (23) 67 / (19) 79 / (30) 94 / (24) 104 / (37) 111 / (22) 140 / (29)

Med. Flow(12°F ∆Tw)

Total, MBH 251 279 295 346 416 470 504 639

Sensible, MBH 251 279 295 346 416 470 504 639

Flow Rate, GPM / (Pressure Drop, ft H2O) 46 / (22) 50 / (17) 53 / (14) 63 / (21) 75 / (17) 84 / (26) 89 / (16) 114 / (21)

Low Flow(14°F ∆Tw)

Total, MBH 234 261 276 327 394 452 482 611

Sensible, MBH 234 261 276 327 394 452 482 611

Flow Rate, GPM / (Pressure Drop, ft H2O) 37 / (16) 41 / (12) 43 / (10) 51 / (16) 61 / (13) 69 / (20) 74 / (13) 94 / (16)

80°FDB/62.9°FWB, 38% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 216 240 254 296 357 404 433 549

Sensible, MBH 216 240 254 296 357 404 433 549

Flow Rate, GPM / (Pressure Drop, ft H2O) 48 / (23) 52 / (18) 55 / (14) 66 / (22) 78 / (18) 87 / (28) 93 / (17) 118 / (22)

Med. Flow(12°F ∆Tw)

Total, MBH 198 221 234 277 336 385 410 520

Sensible, MBH 198 221 234 277 336 385 410 520

Flow Rate, GPM / (Pressure Drop, ft H2O) 37 / (16) 41 / (12) 43 / (10) 52 / (16) 61 / (13) 70 / (20) 74 / (13) 94 / (16)

Low Flow(14°F ∆Tw)

Total, MBH 178 201 211 251 306 364 382 485

Sensible, MBH 178 201 211 251 306 364 382 485

Flow Rate, GPM / (Pressure Drop, ft H2O) 29 / (11) 32 / (9) 33 / (8) 41 / (12) 48 / (10) 57 / (15) 59 / (10) 76 / (12)

75°FDB/61.1°FWB, 45% RH, 52°FDP

High Flow(10°F ∆Tw)

Total, MBH 162 182 192 226 275 318 339 429

Sensible, MBH 162 182 192 226 275 318 339 429

Flow Rate, GPM / (Pressure Drop, ft H2O) 37 / (16) 41 / (12) 43 / (11) 52 / (16) 62 / (13) 70 / (20) 74 / (13) 94 / (16)

Med. Flow(12°F ∆Tw)

Total, MBH 142 160 168 200 246 295 308 392

Sensible, MBH 142 160 168 200 246 295 308 392

Flow Rate, GPM / (Pressure Drop, ft H2O) 27 / (11) 30 / (9) 32 / (8) 39 / (11) 46 / (10) 55 / (14) 57 / (9) 72 / (11)

Low Flow(14°F ∆Tw)

Total, MBH 119 136 130 170 209 265 269 343

Sensible, MBH 119 136 130 170 209 265 269 343

Flow Rate, GPM / (Pressure Drop, ft H2O) 20 / (8) 23 / (7) 22 / (6) 29 / (8) 35 / (7) 43 / (11) 43 / (7) 55 / (8)

Page 18: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

14

CyberAiR CFD/CFU-C

Note 1: Standard 1 KAIC rating, optional KAIC ratings available.

Note 2: For voltages not shown, please consult factory.

Voltage

Model

With Condensate

Pump

CFU/D-060-C1 CFU/D-090-C1 CFU/D-120-C1 CFU/D-150-C1 CFU/D-180-C1

FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS

Cooling w/ Electric Reheat & Humidification460/3/60 No 36.9 46.1 50 36.9 46.1 50 36.9 46.1 50 54.0 67.5 70 54.0 67.5 70460/3/60 Yes 38.1 47.6 50 38.1 47.6 50 38.1 47.6 50 55.2 69.0 70 55.2 69.0 70

575/3/60 No 29.5 36.9 40 29.5 36.9 40 29.5 36.9 40 43.2 54.0 60 43.2 54.0 60

575/3/60 Yes 30.5 38.1 40 30.5 38.1 40 30.5 38.1 40 44.1 55.2 60 44.1 55.2 60

Cooling w/ Electric Reheat 460/3/60 No 30.5 38.1 40 30.5 38.1 40 30.5 38.1 40 45.5 56.9 60 45.5 56.9 60460/3/60 Yes 31.7 39.6 40 31.7 39.6 40 31.7 39.6 40 46.7 58.4 60 46.7 58.4 60575/3/60 No 24.4 30.5 35 24.4 30.5 35 24.4 30.5 35 36.4 45.5 50 36.4 45.5 50575/3/60 Yes 25.4 31.7 35 25.4 31.7 35 25.4 31.7 35 37.3 46.7 50 37.3 46.7 50

Cooling w/ Humidification460/3/60 No 14.3 17.9 20 14.3 17.9 20 14.3 17.9 20 20.1 25.1 30 20.1 25.1 30460/3/60 Yes 15.5 19.4 20 15.5 19.4 20 15.5 19.4 20 21.3 26.6 30 21.3 26.6 30575/3/60 No 11.5 14.4 15 11.5 14.4 15 11.5 14.4 15 16.2 20.2 25 16.2 20.2 25575/3/60 Yes 12.5 15.6 20 12.5 15.6 20 12.5 15.6 20 17.1 21.4 25 17.1 21.4 25

Cooling Only460/3/60 No 7.9 9.9 15 7.9 9.9 15 7.9 9.9 15 11.6 14.5 15 11.6 14.5 15460/3/60 Yes 9.1 11.4 15 9.1 11.4 15 9.1 11.4 15 12.8 16.0 20 12.8 16.0 20575/3/60 No 6.4 8.0 15 6.4 8.0 15 6.4 8.0 15 9.4 11.7 15 9.4 11.7 15575/3/60 Yes 7.4 9.2 15 7.4 9.2 15 7.4 9.2 15 10.3 12.9 15 10.3 12.9 15

Voltage

Model

With Condensate

Pump

CFU/D-190-C1 CFU/D-230-C1 CFU/D-280-C1 CFD-310-C1 CFD-360-C1

FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFSCooling w/ Electric Reheat & Humidification

460/3/60 No 54.0 67.5 70 54.0 67.5 70 57.9 72.4 80 67.2 84.0 90 67.2 84.0 90

460/3/60 Yes 55.2 69.0 70 55.2 69.0 70 59.1 73.9 80 68.4 85.5 90 68.4 85.5 90

575/3/60 No 43.2 54.0 60 43.2 54.0 60 46.3 57.9 60 53.7 67.1 70 53.7 67.1 70

575/3/60 Yes 44.1 55.2 60 44.1 55.2 60 47.3 59.1 60 54.7 68.3 70 54.7 68.3 70

Cooling w/ Electric Reheat 460/3/60 No 45.5 56.9 60 45.5 56.9 60 49.4 61.8 70 54.4 68.0 70 54.4 68.0 70460/3/60 Yes 46.7 58.4 60 46.7 58.4 60 50.6 63.3 70 55.6 69.5 70 55.6 69.5 70575/3/60 No 36.4 45.5 50 36.4 45.5 50 39.5 49.4 50 43.5 54.4 60 43.5 54.4 60575/3/60 Yes 37.3 46.7 50 37.3 46.7 50 40.5 50.6 60 44.5 55.6 60 44.5 55.6 60

Cooling w/ Humidification460/3/60 No 20.1 25.1 30 20.1 25.1 30 24.0 30.0 30 33.3 41.6 45 33.3 41.6 45460/3/60 Yes 21.3 26.6 30 21.3 26.6 30 25.2 31.5 35 34.5 43.1 45 34.5 43.1 45575/3/60 No 16.2 20.2 25 16.2 20.2 25 19.3 24.1 25 26.7 33.4 35 26.7 33.4 35575/3/60 Yes 17.1 21.4 25 17.1 21.4 25 20.3 25.3 30 27.7 34.6 35 27.7 34.6 35

Cooling Only460/3/60 No 11.6 14.5 15 11.6 14.5 15 15.5 19.4 20 20.5 25.6 30 20.5 25.6 30460/3/60 Yes 12.8 16.0 20 12.8 16.0 20 16.7 20.9 25 21.7 27.1 30 21.7 27.1 30575/3/60 No 9.4 11.7 15 9.4 11.7 15 12.5 15.6 20 16.5 20.6 25 16.5 20.6 25575/3/60 Yes 10.3 12.9 15 10.3 12.9 15 13.5 16.8 20 17.5 21.8 25 17.5 21.8 25

Elec

tric

al D

ata

Page 19: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

15

Floor Mounted Air ConditionersElectrical D

ata

Note 1: Standard 1 KAIC rating, optional KAIC ratings available.

Note 2: For voltages not shown, please consult factory.

Voltage

Model

With Condensate

Pump

CFD-510-C1 CFD-630-C1 CFD-730-C1

FLA MCA MFS FLA MCA MFS FLA MCA MFS

Cooling w/ Electric Reheat & Humidification460/3/60 No N/A N/A N/A460/3/60 Yes N/A N/A N/A

575/3/60 No N/A N/A N/A

575/3/60 Yes N/A N/A N/A

Cooling w/ Electric Reheat 460/3/60 No N/A N/A N/A460/3/60 Yes N/A N/A N/A575/3/60 No N/A N/A N/A575/3/60 Yes N/A N/A N/A

Cooling w/ Humidification460/3/60 No N/A N/A N/A460/3/60 Yes N/A N/A N/A575/3/60 No N/A N/A N/A575/3/60 Yes N/A N/A N/A

Cooling Only460/3/60 No 25.7 32.1 35 34.1 42.6 45 42.5 53.1 60460/3/60 Yes 26.9 33.6 35 35.3 44.1 45 43.3 54.1 60575/3/60 No 20.7 25.8 30 27.4 34.2 35 34.1 42.6 45

575/3/60 Yes 21.6 27.0 30 28.3 35.4 40 34.7 43.4 45

Page 20: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

16

CyberAiR CFD/CFU-CD

imen

sio

nal

Dat

a -

CFD

-060

/090

-C

CFD-060/090-CDownflow Vertical Air Conditioner“Free Return” or with optional “Ducted Return”

Note: Standard piping connections terminate inside the cabinet at the bottom, right hand side. Top right hand side and bottom left hand side piping are available as an option.

CFD-060-090-C

A

76.2”(OVERALL)

75.6”

38.4”

40.3”(OVERALL)

77.4”(OVERALL)

38.4”(BASE)

75.6”(BASE)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

Adjustable Floor Stand Height Dimensions (inches)

Nominal Height

Dim A Minimum

Dim A Maximum

15.0 14.0 18.0

18.0 17.0 21.0

24.0 23.0 26.0

36.0 35.0 38.0

48.0 47.0 50.0

Other Floor Stand Heights Optionally Available.

Adjustable Floor Stand, Non-Seismic(Seismic Rated Floor Stand is Available)

CFD-060-090-C

A

76.2”(OVERALL)

75.6”

38.4”

40.3”(OVERALL)

77.4”(OVERALL)

38.4”(BASE)

75.6”(BASE)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

Page 21: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

17

Floor Mounted Air ConditionersD

imen

sion

al Data - C

FD-120-C

CFD-120-CDownflow Vertical Air Conditioner“Free Return” or with optional “Ducted Return”

Note: Standard piping connections terminate inside the cabinet at the bottom, right hand side. Top right hand side and bottom left hand side piping are available as an option.

CFD-120-C

A

76.2”(OVERALL)

87.3”

38.4”

89.1”(OVERALL)

40.3”(OVERALL)

38.4”(BASE)

87.3”(BASE)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

Adjustable Floor Stand Height Dimensions (inches)

Nominal Height

Dim A Minimum

Dim A Maximum

15.0 14.0 18.0

18.0 17.0 21.0

24.0 23.0 26.0

36.0 35.0 38.0

48.0 47.0 50.0

Other Floor Stand Heights Optionally Available.

Adjustable Floor Stand, Non-Seismic(Seismic Rated Floor Stand is Available)

CFD-120-C

A

76.2”(OVERALL)

87.3”

38.4”

89.1”(OVERALL)

40.3”(OVERALL)

38.4”(BASE)

87.3”(BASE)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

Page 22: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

18

CyberAiR CFD/CFU-CD

imen

sio

nal

Dat

a -

CFD

-150

/180

/190

/230

-C

CFD-150/180/190/230-CDownflow Vertical Air Conditioner“Free Return” or with optional “Ducted Return”

Adjustable Floor Stand Height Dimensions (inches)

Nominal Height

Dim A Minimum

Dim A Maximum

15.0 14.0 18.0

18.0 17.0 21.0

24.0 23.0 26.0

36.0 35.0 38.0

48.0 47.0 50.0

Adjustable Floor Stand, Non-Seismic(Seismic Rated Floor Stand is Available)

Other Floor Stand Heights Optionally Available.

CFD-150-180-190-230-C

A

76.2”(OVERALL)

116.6”

38.4”

118.4”(OVERALL)

40.3”(OVERALL)

38.4”(BASE)

116.6”(BASE)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

CFD-150-180-190-230-C

A

76.2”(OVERALL)

116.6”

38.4”

118.4”(OVERALL)

40.3”(OVERALL)

38.4”(BASE)

116.6”(BASE)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

Note: Standard piping connections terminate inside the cabinet at the bottom, right hand side. Top right hand side and bottom left hand side piping are available as an option.

Page 23: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

19

Floor Mounted Air ConditionersCFD-280-CDownflow Vertical Air Conditioner“Free Return” or with optional “Ducted Return”

Note: Piping connections terminate inside the cabinet at the bottom, right hand side (standard). As an option, piping connections may be furnished inside the cabinet at the bottom left hand side.

Adjustable Floor Stand Height Dimensions (inches)

Nominal Height

Dim A Minimum

Dim A Maximum

18.0 17.0 21.0

24.0 23.0 26.0

36.0 35.0 38.0

42.0 41.0 44.0

48.0 47.0 50.0

Adjustable Floor Stand, Non-Seismic(Seismic Rated Floor Stand is Available)

CFD-280-C

A

88.1”(OVERALL)

116.6”

48.0”

118.4”(OVERALL)

48.0”(BASE)

116.6”(BASE)

50.2”(OVERALL)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

CFD-280-C

A

88.1”(OVERALL)

116.6”

48.0”

118.4”(OVERALL)

48.0”(BASE)

116.6”(BASE)

50.2”(OVERALL)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

Dim

ensio

nal D

ata - CFD

-280-C

Other Floor Stand Heights Optionally Available.

Page 24: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

20

CyberAiR CFD/CFU-C

CFD-310-CDownflow Vertical Air Conditioner“Free Return” or with optional “Ducted Return”

Note: Piping connections terminate inside the cabinet at the bottom, right hand side (standard). As an option, piping connections may be furnished inside the cabinet at the bottom left hand side.

Other Floor Stand Heights Optionally Available.

Adjustable Floor Stand Height Dimensions (inches)

Nominal Height

Dim A Minimum

Dim A Maximum

24.0 23.0 26.0

36.0 35.0 38.0

42.0 41.0 44.0

48.0 47.0 50.0

Adjustable Floor Stand, Non-Seismic(Seismic Rated Floor Stand is Available)

Dim

ensi

on

al D

ata

- C

FD-3

10-C

CFD-310-C

A 116.6”

48.0”

118.4”(OVERALL)

50.2”(OVERALL)

88.1”(OVERALL)

116.6”(BASE)

48.0”(BASE)

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

36.0”

AIR IN

CFD-310-C

A 116.6”

48.0”

118.4”(OVERALL)

50.2”(OVERALL)

88.1”(OVERALL)

116.6”(BASE)

48.0”(BASE)

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

36.0”

AIR IN

CFD-310-C

A 116.6”

48.0”

118.4”(OVERALL)

50.2”(OVERALL)

88.1”(OVERALL)

116.6”(BASE)

48.0”(BASE)

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

36.0”

AIR IN

Page 25: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

21

Floor Mounted Air Conditioners

Note: Piping connections terminate inside the cabinet at the bottom, right hand side (standard). As an option, piping connections may be furnished inside the cabinet at the bottom left hand side.

CFD-360-CDownflow Vertical Air Conditioner“Free Return” or with optional “Ducted Return”

Adjustable Floor Stand Height Dimensions (inches)

Nominal Height

Dim A Minimum

Dim A Maximum

24.0 23.0 26.0

36.0 35.0 38.0

42.0 41.0 44.0

48.0 47.0 50.0

Other Floor Stand Heights Optionally Available.

Adjustable Floor Stand, Non-Seismic(Seismic Rated Floor Stand is Available)

Dim

ensio

nal D

ata - CFD

-360-C

CFD-360-C

A 126.0”

48.0”

127.9”(OVERALL)

50.2”(OVERALL)

88.1”(OVERALL)

126.0”(BASE)

48.0”(BASE) AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

36.0”

AIR IN

CFD-360-C

A 126.0”

48.0”

127.9”(OVERALL)

50.2”(OVERALL)

88.1”(OVERALL)

126.0”(BASE)

48.0”(BASE) AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

36.0”

AIR IN

CFD-360-C

A 126.0”

48.0”

127.9”(OVERALL)

50.2”(OVERALL)

88.1”(OVERALL)

126.0”(BASE)

48.0”(BASE) AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

36.0”

AIR IN

Page 26: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

22

CyberAiR CFD/CFU-C

Note 1: Piping connections terminate inside the cabinet at the bottom, right hand side (standard). As an option, piping connections may be furnished inside the cabinet at the bottom left hand side.

CFD-510/630/730-CDownflow Vertical Air Conditioner“Free Return” or with optional “Ducted Return”

Adjustable Floor Stand Height Dimensions (inches)

Nominal Height

Dim A Minimum

Dim A Maximum

36.0 35.0 38.0

42.0 41.0 44.0

48.0 47.0 50.0

Other Floor Stand Heights Optionally Available.

Adjustable Floor Stand, Non-Seismic(Seismic Rated Floor Stand is Available)D

imen

sio

nal

Dat

a -

CFD

-510

/630

/730

-C

(Model CFD-630-D Fans Shown For Reference)

CFD-510-630-730-C

A

154.0”(OVERALL)

65.7”(OVERALL)

63.8”(BASE)

152.1”(BASE)

96.0”(OVERALL)

63.8”

152.1”

36.0”

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPING CONNECTIONS(2) INLET, (2) OUTLET

CFD-510-630-730-C

A

154.0”(OVERALL)

65.7”(OVERALL)

63.8”(BASE)

152.1”(BASE)

96.0”(OVERALL)

63.8”

152.1”

36.0”

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPING CONNECTIONS(2) INLET, (2) OUTLET

CFD-510-630-730-C

A

154.0”(OVERALL)

65.7”(OVERALL)

63.8”(BASE)

152.1”(BASE)

96.0”(OVERALL)

63.8”

152.1”

36.0”

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPING CONNECTIONS(2) INLET, (2) OUTLET

Page 27: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

23

Floor Mounted Air ConditionersD

imen

sion

al Data - C

FU-060/090-C

CFU-060/090-CUpflow Vertical Air Conditioner “Ducted” or provided with optional “2 or 3-way Plenum Box”

Note: Standard piping connections terminate outside the cabinet at the top, right hand side. Top, left hand piping is available as an option.

CFU-060-090-C

88.1”

3.0”

40.3”(OVERALL)

77.4”(OVERALL)

38.4”(BASE)

75.6”(BASE)

AIR IN

PIPINGCONNECTIONS

OPTIONAL HOT WATER REHEAT

PLENUM

AIR OUT

POWERCONNECTIONS

OPTIONAL HOTWATER REHEATPLENUM

Adjustable Floor Stand Height Dimensions (inches)

Nominal Height

Dim A Minimum

Dim A Maximum

15.0 14.0 18.0

18.0 17.0 21.0

24.0 23.0 26.0

36.0 35.0 38.0

48.0 47.0 50.0

Other Floor Stand Heights Optionally Available.

Adjustable Floor Stand, Non-Seismic(Seismic Rated Floor Stand is Available)

CFD-060-090-C

A

76.2”(OVERALL)

75.6”

38.4”

40.3”(OVERALL)

77.4”(OVERALL)

38.4”(BASE)

75.6”(BASE)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

Page 28: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

24

CyberAiR CFD/CFU-CD

imen

sio

nal

Dat

a -

CFU

-120

-C

CFU-120-CUpflow Vertical Air Conditioner “Ducted” or provided with optional “2 or 3-way Plenum Box”

Note: Standard piping connections terminate outside the cabinet at the top, right hand side. Top, left hand piping is available as an option.

CFU-120-C

88.1”

3.0”

89.1”(OVERALL)

40.3”(OVERALL)

38.4”(BASE)

87.3”(BASE)

AIR IN

AIR OUTPIPINGCONNECTIONS

OPTIONAL HOTWATER REHEATPLENUM

POWERCONNECTIONS

OPTIONAL HOTWATER REHEATPLENUM

Adjustable Floor Stand Height Dimensions (inches)

Nominal Height

Dim A Minimum

Dim A Maximum

15.0 14.0 18.0

18.0 17.0 21.0

24.0 23.0 26.0

36.0 35.0 38.0

48.0 47.0 50.0

Other Floor Stand Heights Optionally Available.

Adjustable Floor Stand, Non-Seismic(Seismic Rated Floor Stand is Available)

CFD-120-C

A

76.2”(OVERALL)

87.3”

38.4”

89.1”(OVERALL)

40.3”(OVERALL)

38.4”(BASE)

87.3”(BASE)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

Page 29: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

25

Floor Mounted Air ConditionersD

imen

sion

al Data - C

FU-150/180/190/230-C

CFU-150/180/190/230-CUpflow Vertical Air Conditioner “Ducted” or provided with optional “2 or 3-way Plenum Box”

Note: Standard piping connections terminate outside the cabinet at the top, right hand side. Top, left hand piping is available as an option.

CFU-150-180-190-230-C

88.1”

3.0”

118.4”(OVERALL)

40.3”(OVERALL)

38.4”(BASE)

116.6”(BASE)

AIR IN

AIR OUT

PIPINGCONNECTIONS

POWERCONNECTIONSOPTIONAL HOT WATER

REHEAT PLENUM

OPTIONAL HOTWATER REHEATPLENUM

Adjustable Floor Stand Height Dimensions (inches)

Nominal Height

Dim A Minimum

Dim A Maximum

15.0 14.0 18.0

18.0 17.0 21.0

24.0 23.0 26.0

36.0 35.0 38.0

48.0 47.0 50.0

Adjustable Floor Stand, Non-Seismic(Seismic Rated Floor Stand is Available)

CFD-150-180-190-230-C

A

76.2”(OVERALL)

116.6”

38.4”

118.4”(OVERALL)

40.3”(OVERALL)

38.4”(BASE)

116.6”(BASE)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

Other Floor Stand Heights Optionally Available.

Page 30: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

26

CyberAiR CFD/CFU-CD

imen

sio

nal

Dat

a -

CFU

-280

-C

CFU-280-CUpflow Vertical Air Conditioner “Ducted” or provided with optional “2 or 3-way Plenum Box”

Note: Standard piping connections terminate outside the cabinet at the top, right hand side. Top, left hand piping is available as an option.

Adjustable Floor Stand Height Dimensions (inches)

Nominal Height

Dim A Minimum

Dim A Maximum

15.0 14.0 18.0

18.0 17.0 21.0

24.0 23.0 26.0

36.0 35.0 38.0

48.0 47.0 50.0

Other Floor Stand Heights Optionally Available.

Adjustable Floor Stand, Non-Seismic(Seismic Rated Floor Stand is Available)

CFU-280-C

116.6”(BASE)

48.0”(BASE)

49.9”(OVERALL)

118.4”(OVERALL)

96.0”(OVERALL

3.0”

AIR IN

AIR OUT

PIPINGCONNECTIONS

POWERCONNECTIONS

OPTIONAL HOT WATERREHEAT PLENUM

OPTIONAL HOTWATER REHEATPLENUM

CFD-280-C

A

88.1”(OVERALL)

116.6”

48.0”

118.4”(OVERALL)

48.0”(BASE)

116.6”(BASE)

50.2”(OVERALL)

AIR IN

AIR OUT

AIR IN

AIR OUT

POWERCONNECTIONS

PIPINGCONNECTIONS

Page 31: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

27

Floor Mounted Air ConditionersPlen

um

s/Seismic Flo

or Stan

ds

Plenum Extension Box

Plenum Box

Seismic Rated Floor Stands (Available For Any Size Cabinet)

Note: Taller plenum boxes are optionally available.

(Plenum extension boxes may be stacked)

(Enclosed, non-seismic rated Floor stands also available)

Typical Seismic Rated Floor Stand Typical Enclosed, Seismic Rated Floor Stand

PlenumBoxes

(Upflow Units)

Dim ANominal(inches)

Dim B Minimum(inches)

Dim C Maximum

(inches)

CFU-060 18.5 77.4 38.7

CFU-090 18.5 77.4 38.7

CFU-120 18.5 89.1 38.7

CFU-150 24 118.4 38.7

CFU-180 24 118.4 38.7

CFU-190 24 118.4 38.7

CFU-230 24 118.4 38.7

CFU-280 24 118.4 48.1

PlenumExtension Boxes

(Downflow Units)

Dim ANominal(inches)

Dim B Minimum(inches)

Dim C Maximum

(inches)

CFD-060 24, 36 or 48 77.4 38.8

CFD-090 24, 36 or 48 77.4 38.8

CFD-120 24, 36 or 48 89.1 38.8

CFD-150 24, 36 or 48 118.4 38.8

CFD-180 24, 36 or 48 118.4 38.8

CFD-190 24, 36 or 48 118.4 38.8

CFD-230 24, 36 or 48 118.4 38.8

CFD-280 24, 36 or 48 118.4 48.1

CFD-310 24, 36 or 48 118.4 48.1

CFD-360 24, 36 or 48 127.9 48.1

CFD-510 24, 36 or 48 154.0 63.9

CFD-630 24, 36 or 48 154.0 63.9

CFD-730 24, 36 or 48 154.0 63.9

Page 32: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

28

CyberAiR CFD/CFU-C

STULZ CyberAiR® Series60 - 730 kW CW “CFD/CFU”

Floor Mounted Precision Air Conditioners

SUMMARY

This specification describes requirements for a precision environmental control system. The STULZ CyberAiR floor-mounted air conditioning system shall provide precision temperature and/or humidity control for computer rooms or rooms containing telecommunications or other highly-sensitive heat load equipment where continuous 24 hour a day, 365 days a year air conditioning is required. Designed for front access, CyberAiR systems require minimum floor space. The units are designed with a wide range of options to handle both precision and comfort cooling applications.

DESIGN REQUIREMENTS

The environmental control system shall be a STULZ CyberAiR factory-assembled unit. The unit shall be designed for corner installation, requiring front access through hinged and removable front access panels. No allowance for side service access shall be required.

CyberAiR units are especially adapted for both raised and non-raised floors. The air handling system shall be specifically designed for high sensible heat ratio. Each system shall be capable of handling ___CFM. The unit shall have a total cooling capacity of ___BTU/H, and a sensible cooling capacity of ___BTU/H based on entering air conditions of ___°F dry bulb and ___°F wet bulb. The main fan motors shall be ___HP. The unit shall have a power supply of ___volts___/phase/___frequency.

QUALITY ASSURANCE

The manufacturer shall maintain a set of international standards of quality management to insure product quality. Each system shall be subjected to a complete operational and functional test procedure at the factory prior to shipment.

CABINET

Down-Flow:Access panels shall be fabricated from 18 gauge galvannealed steel. Door jambs and top cabinet frame shall be fabricated from 16 gauge galvannealed steel. Bottom cabinet frame shall be fabricated from 10 gauge galvannealed steel.

Up-Flow:Access panels shall be fabricated from 18 gauge galvannealed steel. Door jambs shall be fabricated from 16 gauge galvannealed steel. Top and bottom cabinet frame shall be fabricated from 10 gauge galvannealed steel.

The panels shall be lined with 1/2” (13 mm), 2 lb (.90 kg), high-density sound and thermal insulation and sealed with a self-extinguishing gasket conforming to NFPA 90A and 90B. The main unit color shall be black, extra fine texture.

AIR FLOW PATTERNSDown-Flow:The air conditioner shall be configured for a down-flow air pattern with free return air to the top and conditioned supply air discharge through bottom of the system into the raised floor.

Up-Flow:The air conditioner shall be configured for an up-flow air pattern with free return air through front filtered grille and conditioned supply air through the top of the unit.

Air FiltrationAll units shall be supplied with disposable air filters classified as UL 900 or UL 586. Filters shall be 4” deep (nominal). Filters shall be pleated with a Minimum Efficiency Reporting Value (MERV) of 8. Filters shall be installed in a front accessible, steel holding frame, and accessible through the front of the unit.

Optional: Filters rated up to MERV 11, shall be available.

MECHANICAL COMPONENTS

Backward Inclined, Plenum Style Fan, With an EC MotorThe blower(s) shall be direct driven, single inlet, backward curved centrifugal fan with an electronically commutated motor for maintenance free operation. The motor shall include: integrated electronic control board and direct microprocessor control signaling for fan speed control, soft-

Pro

du

ct G

uid

e Sp

ecifi

cati

on

s

Page 33: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

29

Floor Mounted Air ConditionersPro

du

ct Gu

ide Sp

ecificatio

ns

starting capabilities, RS-485 BUS connection, and integrated current limitations. Each fan shall be low noise, low vibration manufactured with an anti-corrosive aluminum impeller. Each fan impeller shall be dynamically and statically balanced in two planes to minimize vibration during operation.

Chilled Water Cooling CoilThe coil shall be constructed of seamless drawn copper tubes, mechanically bonded to tempered aluminum fins with enhanced fin design for maximum heat transfer, and mounted in a stainless steel condensate drain pan. The coil shall be designed for a maximum of 500 ft./min. face velocity. The water circuit shall be designed to distribute water into the entire coil face area.

MODULATING CW CONTROL VALVES

2-Way Chilled Water Control Valve (Standard)A two-way fully modulating control valve shall be factory installed and wired. The two-way chilled water modulating valve shall automatically meter the flow of chilled water to the cooling coil in response to a proportional signal (0-10 VDC) provided to the valve by the microprocessor controller. The pressure rating of the valve shall be maximum of 600 psig w.w.p. Manual override capabilities shall be included on the actuator drive.

3-Way Chilled Water Control Valve (Optional)A 3-way modulating valve shall be factory piped and wired. The three-way modulating valve shall automatically meter the flow of chilled water to the cooling coil as needed for cooling load control, the remaining flow shall bypass the chilled water coil. A proportional control signal ( 0-10 VDC ) is provided to the valve by the unit’s controller. The pressure rating of the valve shall be maximum of 400 psig w.w.p. Manual override capabilities shall be included on the actuator drive.

Differential Temperature Flow (Standard)Factory mounted and wired NTC temperature sensors for inlet and outlet chilled water temperatures shall be provided. The sensors shall supply input signals to the system controller for the purpose of indicating the entering and leaving CW temperature in a status display screen.

The controller shall provide a loss of flow alarm in the event the inlet/outlet temperature difference is within 3° F (adjustable) during chilled water valve operation.

Steam Generating Humidifier (Standard)The humidifier shall be a self-contained atmospheric steam generator. The humidifier assembly shall include an integral fill cup, fill and drain valves, disposable steam cylinder and associated piping. The humidifier shall be equipped with an auto adaptive control system to optimize water conductivity, control automatic drain/flush cycles, minimize energy waste and maximize cylinder life. Drain water tempered fill water shall insure drains do not exceed 140°F during operation. The humidifier shall have modulating output between 20% and 100% of rated capacity.

Dehumidification Cycle (Standard)The system shall be provided with a dehumidification control mode. The chilled water valve shall be opened to allow chilled water flow when a dehumidification demand exists. Moisture is condensed on the cooling coil and discharged through the condensate drain. Reheat (electric) shall be provided to offset sensible cooling during the dehumidification cycle.

Electric Heat/ Reheat (Standard)A factory mounted and wired low-watt density, plated fin-tubular design electric resistance heater shall be included to provide automatic sensible re-heating as required during the dehumidification cycle and automatic heating mode. Electric heaters shall be provided with miniature thermal/magnetic circuit breakers, which shall protect each ungrounded conductor. Also included will be one automatic reset and one manual reset over-temperature safety device (pilot duty).

Hot Water Reheat/Heat (Optional)A factory-installed, copper tube, aluminum fin heat/reheat coil and 2-way control valve shall be provided to control the flow of hot water for automatic sensible reheating mode during the dehumidification cycle and automatic heating mode as required.

SCR Fired Reheat/Heat (Optional)The electric heat/reheat shall be controlled through a “Zero Firing” Silicon Controlled Rectifier (SCR) with an extruded aluminum heat sink and solid state logic system to provide close dry bulb temperature control of the leaving conditioned air temperature.

Proportional (0-10 VDC) microprocessor controls shall be provided with the SCR Fired Electric Reheat option.

Page 34: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

30

CyberAiR CFD/CFU-CPr

od

uct

Gu

ide

Spec

ifica

tio

ns

ELECTRICAL SYSTEM

The electrical system shall conform to National Electrical Code requirements. The control circuit shall be 24 volts AC, wire in accordance with NEC Class II requirements. The control circuit wire shall not be smaller than 18 AWG. All wiring shall be neatly wrapped and routed in bundles. Each wire shall end with a service loop and be securely fastened by an approved method. Each wire in the unit shall be numbered for ease of service tracing.

All electrically actuated components shall be easily accessible from the front of the unit without reaching over exposed high voltage components or rotating parts. Each high voltage circuit shall be individually protected by circuit breakers or manual motor starters on all three phases. The blower motor shall have thermal and short circuit protection. Line voltage and 24 volt control circuit wiring shall be routed in separate bundles.

The electric box shall be positioned for service convenience and shall include all the contactors, starters, fuses, circuit breakers, terminal boards and control transformer required for operation of the STULZ unit and shall allow for full service access.

Main Power Service SwitchThe indoor CyberAiR Chilled Water model shall be provided with a unit mounted main power service switch.

Remote Stop/Start ContactsIncluded in the system’s electrical control circuit shall be a 2-pin terminal connection for remote stop/start of the CyberAiR CW air conditioner by remote source.

Manual Control Override Switch (Optional) A front panel mounted keyed override switch shall allow full fan operation and 100 % chilled water valve position once engaged in the unlikely event of a controller failure.

Automatic Dual Power Transfer Switch (Optional) Two individual main power input disconnect switches shall be provided, one for each incoming power source. In the event the primary power fails or a phase loss/imbalance occurs, the automatic transfer switch immediately transfers power to the secondary power source. Once the primary power has been restored, the transfer switch automatically shifts the power load back to the primary power. The transfer time from one source to the other is user adjustable to allow staging or sequence restart of load.

In addition to the automatic transfer switch function, the local controller display shall indicate which power source has

failed. This indication is a visual depiction that allows the user to determine the status of the input source. This status shall be conveyed thru the BMS serial communications link.

A thru-the-door indicator light shall be included for a fast and local notification of available power sources.

AIR CONTROL

EC Fan Speed Control The system shall include a variable fan speed control package. The unit’s controller shall permit control of the fan speed from 100% rated air volumetric flow rate to a user define minimum fan speed setting. Minimum and maximum fan speed settings shall be user adjustable. User configured control sequences shall be available for fan speed energy savings control.

Fail Safe ModeIn the event of a fan failure, the controller shall automatically enable all remaining EC fans to increase to the maximum fan speed setting.

E² SERIES CONTROLLER DESCRIPTION

GeneralThe advanced microprocessor based E² Series controller shall be equipped with flexible software capable of meeting the specific needs of the application. The setpoints shall be default and their ranges shall be easily viewed and adjusted from the user interface display. The program and operating parameters shall be permanently stored on a non-volatile system in the event of power failure.

The controller shall be designed to manage temperature and relative humidity (RH) levels to a user defined setpoint via control output signals to the CW system. Control parameters have variable outputs from 0 to 100% of the full rated capacity.

The controller shall receive inputs for measurable control conditions (temperature, relative humidity, and dew point) via return air or room mounted sensors. The internal logic will then determine if the conditions require cooling, humidification or dehumidification. Control setpoints shall be established to maintain design conditions of the installation. The controller will respond accordingly to changes in these conditions and control the output/demand for the appropriate mode of operation until user defined conditions are achieved.

Page 35: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

31

Floor Mounted Air ConditionersPro

du

ct Gu

ide Sp

ecificatio

ns

Field ConfigurableThe program for the E² Series controller shall be field configurable, allowing the operator the capability of selecting control setpoints specific to the application. Operator interface for the E² controller is provided via a door mounted user interface display panel. The display panel shall have a backlit LCD graphical display and function keys giving the user complete control and monitoring capability of the precision cooling system. The menu driven interface shall provide users the ability to scroll through and enter various menu screens.

Password ProtectionAccess to the Info Menu, Alarms Log, and the ability to monitor room conditions shall be allowed without the use of a password. Modifications to the control setpoints shall require the use of a password. The controller shall be programmed to recognize predetermined security levels before allowing access to display screens containing critical variables. Three secured menu levels (Control, Service and Factory) will support unique passwords that must be entered to access the menu screens so only authorized personnel may perform modifications to the settings.

Restorable Parameters/Factory DefaultsUpon initial start-up the CW system shall operate using the setpoints programmed by the factory. The customer may enter new operating parameters in the Control menu and the system will then operate accordingly. The new setpoints may be stored as, “Customer Default Setpoints”. The primary setpoints entered by the factory still remain stored in the controllers’ memory as, “Factory Setpoints”. The setpoints for the system may be re-adjusted in the Control menu at any time. If it becomes necessary, the customer may restore the setpoints back to the Customer Default setpoint values or to the original Factory (primary) setpoint values.

Timer FeatureThe timer shall allow the user to set up an operating schedule to automatically scale back or shut down the air conditioner during low demand or unoccupied periods. This is an energy saving feature offering the user the ability to create an operating schedule tailored to the needs of the building. An evening (night-setback) schedule may also be created, allowing the CW system to operate at night with relaxed temperature/humidity setpoints and offsets.

A/C Grouping pLAN OperationMultiple STULZ CyberAiR system controllers shall be able to be connected (grouped) to a pLAN local network, allowing

the communication of data and information from each controller to a central control terminal or Lead controller. The Lead controller display screens can be used to monitor and adjust group control variables for the individual system controllers. Each E² controller connected to the pLAN network shall be identified with its own unique address.

Multiple STULZ CyberAiR systems consisting of up to eight STULZ precision air conditioners equipped with like controllers may be controlled and monitored via the E² series controller. With multiple STULZ CyberAiR systems each unit can selectively be configured as “Active” to operate as a primary A/C, “Capacity Assist” for staged operation, or as “Standby” to come online in case of a failed air conditioning unit to ensure continuous availability. The controller may also be configured to rotate units with timed duty cycling to promote equal run-time and assure that each STULZ CyberAiR system within the rotating group is operationally exercised on a periodic timed basis.

BMS Interface (Optional)The E² series controller shall incorporate a 10 Mbps communication interface port that can be field connected through a serial interface to a Building Management System via Modbus, BACnet, SNMP, or HTTP as configured by the factory. A controller interfaced to a network must be configured for BMS communication.

AlarmsAlarm conditions shall activate a red LED indicator that backlights the alarm function key. As an option, an alarm condition may also be enunciated by an audible alarm signal. An alarm is acknowledged by pressing the alarm key. This calls up alarm display screens that provide a text message detailing the alarm conditions. After an alarm condition is corrected, the alarm can be cleared by pressing the alarm key.

Large Bezel Display Panel- Touch ScreenThe large bezel touch screen user interface display panel features a high resolution backlit liquid-crystal graphical display equipped with contrast adjustment and LED illuminated function keys. The screens that appear on the user interface display panel present data that originates from the controller I/O module. The controller is operated via a round membrane type keypad and offers an alarm log plus four different interface menu levels to the operator: Information, Control, Service, and Factory. These menus permit the user to easily view, control, and configure operating parameters for the STULZ CyberAiR system.

Page 36: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

32

CyberAiR CFD/CFU-CPr

od

uct

Gu

ide

Spec

ifica

tio

ns

E² Constant Contact (Optional)The control package shall include a STULZ Constant Contact short term power supply for the E² Series Controller to allow the controller to manage the power transfer switch from one primary power source to another while maintaining communications with an active monitoring system. The E² Constant Contact shall permit a minimum of one minute ride thru period. The Constant Contact shall include LED indications for presence of power, low charge indication, and minimum backup time.

OPTIONAL FEATURES

STULZ CyberAiR floor-mounted air conditioning system standard features can be deleted and/or substituted with optional features to allow you the flexibility to select the configuration best suited for your application.

Adjustable Floor StandAn adjustable floor stand shall be provided to allow for ease of installation of the STULZ CyberAiR floor-mounted air conditioning system onto a raised floor environment. Floor stand height shall be adjustable. The floor stand shall ship separately for field installation.

Enclosed Floor StandA factory provided enclosed floor stand shall be factory constructed full cabinet length and pre-fabricated within the support structure for one-way front air discharge.

Seismic Rated Floor Stand The unit floor stand shall be constructed and rated for use to the install site seismic performance requirements.

Condensate PumpA condensate pump shall be factory installed within the STULZ CyberAiR floor-mounted air conditioning system for automatic removal of condensate and humidifier flush water (if applicable). The condensate pump shall include an internal overflow safety float which, when wired to the STULZ CyberAiR unit’s remote stop/start terminals, shall open the unit’s control circuit, thereby shutting the unit down in the event of a condensate overflow. The condensate pump shall be specifically designed to operate with the higher condensate temperatures caused by the flush and drain cycle of the electrode canister humidifiers.

Smoke Detection A photo-electric smoke detector shall be factory installed and wired in the return air section of the STULZ CyberAiR floor-mounted air conditioning system. The photo-electric detector shall include built-in circuitry that performs a functional test of all detection circuits at least once every 40 seconds without the need for generating smoke. The UL listed velocity range shall be 0-3000 fm. The air conditioner will shut down upon sensing smoke in the return air stream.

FirestatThe STULZ CyberAiR floor-mounted air conditioning system shall be provided with a factory wired and mounted firestat. The firestat will shut down the air conditioner upon sensing a high return air temperature.

Supply Air ControlThe STULZ CyberAiR floor-mounted air conditioning system controller shall be provided with a temperature and humidity sensor factory unit mounted in the return air stream and a field installed supply air temperature and humidity sensor for supply air control capabilities. The controller shall provide the user an adjustable supply air control setpoint.

Under Floor Pressure ControlThe STULZ CyberAiR floor-mounted air conditioning system shall permit variable fan speed control to a user defined external static pressure setting. A remote differential pressure transducer shall be provided to determine the static pressure, the system controller shall modulate fan speed to maintain an external static pressure setpoint.

Remote Water Detector- Spot TypeA remote single point water/leak detector shall be factory supplied and shall ship separately for field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the STULZ CyberAiR floor-mounted air conditioning unit’s water produc-ing components.

Remote Water Detector- Dual Spot TypeA dual remote single point water/leak detector shall be factory supplied and shall ship separately for field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the STULZ CyberAiR floor-mounted air conditioning unit’s water producing components.

Page 37: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

33

Floor Mounted Air ConditionersPro

du

ct Gu

ide Sp

ecificatio

ns

Remote Water Detector- Strip TypeA 20 ft. in length remote strip/cable type water/leak detector shall be provided for remote field installation. In addition to the 20 ft. sensing cable, a 24 volt water detector power module shall require field mounting and wiring to the factory provided terminal connection. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the STULZ CyberAiR floor-mounted air conditioning unit’s water producing components.

Top Discharge Plenum Box (Upflow Units Only)A 2 or 3-way plenum discharge box shall be provided. The plenum box shall include double-deflecting, adjustable grilles.

High Short Circuit Current RatingThe STULZ CyberAiR floor-mounted air conditioning system shall be rated for a short circuit current rating for a minimum of _____. The higher short circuit current rating shall include safe touch fusing upstream of the unit’s main power disconnect switch.

Air-Side Economizer ControlsThe STULZ CyberAiR floor-mounted air conditioning system controller shall be equipped with a unique air-side economizer mode for applications utilizing outdoor air-side economizing. The STULZ Air-Side economizer control package shall include an outdoor temperature and humidity sensor, remote space return air sensor, and supply air sensor for proper control during economizer operation. Individual discrete analog output signals (0-10 VDC) are available to allow control of the external outdoor air intake damper and exhaust relief provisions. Control settings shall be included for both temperature and humidity properties of the outdoor air. A damper signal lockout shall be included if the outdoor air conditions reaches user adjustable limits.

The economizing damper signal shall allow a minimum output setting for minimum outside air control to meet ventilation requirements.

CODE CONFORMANCE

The supplied system shall be provided with the following compliance approvals:ETL/CETLUL Listed to UL 1995 and CSA C22.2 No.236MEA # 433-00-E

Page 38: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

34

CyberAiR CFD/CFU-C

Page 39: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

35

Floor Mounted Air Conditioners

Page 40: STULZ CyberAiR Floor Mounted Systems · STULZ CyberAiR “CFD/CFU”floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements

36

CyberAiR CFD/CFU-C

STULZ mission is to be the premier provider of energy efficient temperature and humidity control solutions for mission critical applications.

Production Facilities: U.S.A. • Germany • Italy • China • India

ISO-9001 Quality Management System - RequirementsISO9001Registered

Quality System

STULZ Air Technology Systems, Inc.1572 Tilco Drive, Frederick, Maryland 21704Phone: 301.620.2033 • Fax: 301.662.5487

E-mail: [email protected]

www.STULZ.com

May, 2015QECS009D

Specifications subject to change without notice.

®