Job Name HOTEL SECRETS AKUMAL
UMA J01-J02Mark for
Date July 10, 2014
Unit Parameters
Unit Size: 15
Insulation: 1" 1.5# Tuf-Skin II Double Wall
Hand: Right
No Export Crate
Controls: No Product Integrated Controls
ANG Angle Filter Section
2in Pleated MERV8 Filters - kit
(9) 16in. x 20in.
LA Horizontal Cooling (LFA) Coil/Fan Section
Fan RPM: 716
Drive
Motor HP: 3
Voltage: 230/460 3 Phase 60Hz
Efficiency: Premium
Enclosure: ODP
RPM: 1800
Manufacturer - Generic
Frame Size - 182T
Motor Shaft Diameter (in.) - 1.125
Full Load Amps - 7.8/3.9
MCA - 9.7/4.9
MOCP - 15/6
Efficiency - 89.5%
Discharge: Top Horiz. Front
CW 14.9 sq.ft. 6 Rows 11 FPI Full Circuit
0.016 in. Tube Wall Thickness
Weights and Dimensions
(LxWxH in ft in) 7' 9" x 5' 5" x 3' 4" **
Dry 1096 LB ** Wet 1180 LB **
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
Job Name HOTEL SECRETS AKUMAL
UMA J01-J02Mark for
Date July 10, 2014
Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and
fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are
provided primarily for shipping purposes. Shipping skids are not included.
All filter media efficiency ratings are for the filter media only.
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
v6.34 02/11/14 www.carrier.com
Cooling Application's Balance Criteria: Fluid Flow
Coil Model Carrier 28NARow / FPI / Circ 6 / 11 / FL
Face Area Type LargeCoil Face Area 14.90 sqftFace Velocity 436.2 fpmTube Material Al / CuTube Diameter 0.5 inTube spacing: Stf x Str 1.25 x 0.781 inTube Wall Thickness 0.016 in
Actual Airflow 6500 CFMSite Altitude 0 ft
Total Cooling Capacity 293.41 MBHSensible Cooling Capacity 156.81 MBHFluid Flow Rate 41.9 gpmFluid Pressure Drop 3.4 ft wg
Fluid Velocity 2.2 ft/sEntering Fluid Temperature 42.00 FLeaving Fluid Temperature 56.00 FFluid Temperature Rise 14.0 FEntering Air Dry Bulb 77.00 FEntering Air Wet Bulb 68.90 FEntering Air Enthalpy 33.01 BTU/lbLeaving Air Dry Bulb 54.94 FLeaving Air Wet Bulb 54.69 FLeaving Air Enthalpy 23.0 BTU/lb
Air Friction 0.76 in wg
Brine FWBrine Concentration 0 %Fouling Factor 0.0 (hr-sqft-F)/BTU
NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org).
HOTEL SECRETS AKUMALUMA J01-J02
Project:Tag:
Chilled Water Coil Performance Summary
v6.34 02/11/14 www.carrier.com
Fan Model 39L
Unit Size 15
Fan Type LA (For LFA Clg. Coils)
Inlet Guide Vanes No
Actual Airflow, CFM 6500
Site Altitude, ft 0
Upstream Ext. Static, in wg 0.00
Downstream Ext. Static, in wg 0.45
Cooling Coil Static, in wg 0.76
Heating Coil Static, in wg 0.00
Other Losses, in wg 0.00
Total Accessory Static, in wg 0.11
Total Static Pressure, in wg 1.32
Fan RPM 701
Fan BHP 2.4
Acoustic Data:
CasingInletDischarge
807886 63 Hz
746886 125 Hz
656382 250 Hz
636383 500 Hz
585774 1000 Hz
565869 2000 Hz
505063 4000 Hz
453955 8000 Hz
Accessories:
(1) ANG Pleated 2 inch MERV 8 [0.11]
HOTEL SECRETS AKUMALUMA J01-J02
Project:Tag:
Supply Fan Performance Summary
Job Name HOTEL SECRETS AKUMAL
UMA J03Mark for
Date July 10, 2014
Unit Parameters
Unit Size: 15
Insulation: 1" 1.5# Tuf-Skin II Double Wall
Hand: Right
No Export Crate
Controls: No Product Integrated Controls
ANG Angle Filter Section
2in Pleated MERV8 Filters - kit
(9) 16in. x 20in.
LA Horizontal Cooling (LFA) Coil/Fan Section
Fan RPM: 716
Drive
Motor HP: 5
Voltage: 230/460 3 Phase 60Hz
Efficiency: Premium
Enclosure: ODP
RPM: 1800
Manufacturer - Generic
Frame Size - 184T
Motor Shaft Diameter (in.) - 1.125
Full Load Amps - 13/6.5
MCA - 16.2/8.1
MOCP - 25/10
Efficiency - 89.5%
Discharge: Top Horiz. Front
CW 14.9 sq.ft. 4 Rows 14 FPI Half Circuit
0.016 in. Tube Wall Thickness
Weights and Dimensions
(LxWxH in ft in) 7' 9" x 5' 5" x 3' 4" **
Dry 1040 LB ** Wet 1101 LB **
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
Job Name HOTEL SECRETS AKUMAL
UMA J03Mark for
Date July 10, 2014
Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and
fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are
provided primarily for shipping purposes. Shipping skids are not included.
All filter media efficiency ratings are for the filter media only.
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
v6.34 02/11/14 www.carrier.com
Cooling Application's Balance Criteria: Fluid Flow
Coil Model Carrier 28NARow / FPI / Circ 4 / 14 / HF
Face Area Type LargeCoil Face Area 14.90 sqftFace Velocity 436.2 fpmTube Material Al / CuTube Diameter 0.5 inTube spacing: Stf x Str 1.25 x 0.781 inTube Wall Thickness 0.016 in
Actual Airflow 6500 CFMSite Altitude 0 ft
Total Cooling Capacity 298.83 MBHSensible Cooling Capacity 153.39 MBHFluid Flow Rate 42.7 gpmFluid Pressure Drop 16.9 ft wg
Fluid Velocity 4.5 ft/sEntering Fluid Temperature 42.00 FLeaving Fluid Temperature 56.00 FFluid Temperature Rise 14.0 FEntering Air Dry Bulb 77.90 FEntering Air Wet Bulb 70.00 FEntering Air Enthalpy 33.93 BTU/lbLeaving Air Dry Bulb 56.32 FLeaving Air Wet Bulb 55.89 FLeaving Air Enthalpy 23.7 BTU/lb
Air Friction 0.54 in wg
Brine FWBrine Concentration 0 %Fouling Factor 0.0 (hr-sqft-F)/BTU
NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org).
HOTEL SECRETS AKUMALUMA J03
Project:Tag:
Chilled Water Coil Performance Summary
v6.34 02/11/14 www.carrier.com
Fan Model 39L
Unit Size 15
Fan Type LA (For LFA Clg. Coils)
Inlet Guide Vanes No
Actual Airflow, CFM 6500
Site Altitude, ft 0
Upstream Ext. Static, in wg 0.00
Downstream Ext. Static, in wg 0.67
Cooling Coil Static, in wg 0.54
Heating Coil Static, in wg 0.00
Other Losses, in wg 0.00
Total Accessory Static, in wg 0.11
Total Static Pressure, in wg 1.32
Fan RPM 701
Fan BHP 2.4
Acoustic Data:
CasingInletDischarge
807886 63 Hz
746886 125 Hz
656382 250 Hz
636383 500 Hz
585774 1000 Hz
565869 2000 Hz
505063 4000 Hz
453955 8000 Hz
Accessories:
(1) ANG Pleated 2 inch MERV 8 [0.11]
HOTEL SECRETS AKUMALUMA J03
Project:Tag:
Supply Fan Performance Summary
Job Name HOTEL SECRETS AKUMAL
UMA J04-J05Mark for
Date July 10, 2014
Unit Parameters
Unit Size: 10
Insulation: 1" 1.5# Tuf-Skin II Double Wall
Hand: Right
No Export Crate
Controls: No Product Integrated Controls
ANG Angle Filter Section
2in Pleated MERV8 Filters - kit
(4) 16in. x 25in.
LA Horizontal Cooling (LFA) Coil/Fan Section
Fan RPM: 863
Drive
Motor HP: 2
Voltage: 230/460 3 Phase 60Hz
Efficiency: Premium
Enclosure: ODP
RPM: 1800
Manufacturer - Generic
Frame Size - 145T
Motor Shaft Diameter (in.) - 0.875
Full Load Amps - 5.6/2.8
MCA - 6.9/3.5
MOCP - 10/6
Efficiency - 86.5%
Discharge: Top Horiz. Front
CW 9.5 sq.ft. 6 Rows 14 FPI Double Circuit
0.016 in. Tube Wall Thickness
Weights and Dimensions
(LxWxH in ft in) 6' 4" x 4' 10" x 2' 8" **
Dry 783 LB ** Wet 840 LB **
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
Job Name HOTEL SECRETS AKUMAL
UMA J04-J05Mark for
Date July 10, 2014
Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and
fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are
provided primarily for shipping purposes. Shipping skids are not included.
All filter media efficiency ratings are for the filter media only.
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
v6.34 02/11/14 www.carrier.com
Cooling Application's Balance Criteria: Fluid Flow
Coil Model Carrier 28NARow / FPI / Circ 6 / 14 / DB
Face Area Type LargeCoil Face Area 9.54 sqftFace Velocity 419.3 fpmTube Material Al / CuTube Diameter 0.5 inTube spacing: Stf x Str 1.25 x 0.781 inTube Wall Thickness 0.016 in
Actual Airflow 4000 CFMSite Altitude 0 ft
Total Cooling Capacity 179.53 MBHSensible Cooling Capacity 94.07 MBHFluid Flow Rate 25.6 gpmFluid Pressure Drop 0.8 ft wg
Fluid Velocity 1.2 ft/sEntering Fluid Temperature 42.00 FLeaving Fluid Temperature 56.00 FFluid Temperature Rise 14.0 FEntering Air Dry Bulb 77.90 FEntering Air Wet Bulb 70.00 FEntering Air Enthalpy 33.93 BTU/lbLeaving Air Dry Bulb 56.39 FLeaving Air Wet Bulb 56.28 FLeaving Air Enthalpy 24.0 BTU/lb
Air Friction 0.76 in wg
Brine FWBrine Concentration 0 %Fouling Factor 0.0 (hr-sqft-F)/BTU
NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org).
HOTEL SECRETS AKUMALUMA J04-J05
Project:Tag:
Chilled Water Coil Performance Summary
v6.34 02/11/14 www.carrier.com
Fan Model 39L
Unit Size 10
Fan Type LA (For LFA Clg. Coils)
Inlet Guide Vanes No
Actual Airflow, CFM 4000
Site Altitude, ft 0
Upstream Ext. Static, in wg 0.00
Downstream Ext. Static, in wg 0.48
Cooling Coil Static, in wg 0.76
Heating Coil Static, in wg 0.00
Other Losses, in wg 0.00
Total Accessory Static, in wg 0.11
Total Static Pressure, in wg 1.35
Fan RPM 826
Fan BHP 1.7
Acoustic Data:
CasingInletDischarge
807886 63 Hz
746886 125 Hz
656382 250 Hz
636383 500 Hz
595875 1000 Hz
586071 2000 Hz
535366 4000 Hz
504460 8000 Hz
Accessories:
(1) ANG Pleated 2 inch MERV 8 [0.11]
HOTEL SECRETS AKUMALUMA J04-J05
Project:Tag:
Supply Fan Performance Summary
Job Name HOTEL SECRETS AKUMAL
UMA J06Mark for
Date July 10, 2014
Unit Parameters
Unit Size: 18
Insulation: 1" 1.5# Tuf-Skin II Double Wall
Hand: Right
No Export Crate
Controls: No Product Integrated Controls
FMB1 Combo Filter Mixing Box Sect. (Top & Rear Inlet)
2in Pleated MERV8 Filters - kit
(9) 16in. x 20in.
LA Horizontal Cooling (LFA) Coil/Fan Section
Fan RPM: 666
Drive
Motor HP: 5
Voltage: 230/460 3 Phase 60Hz
Efficiency: Premium
Enclosure: ODP
RPM: 1800
Manufacturer - Generic
Frame Size - 184T
Motor Shaft Diameter (in.) - 1.125
Full Load Amps - 13/6.5
MCA - 16.2/8.1
MOCP - 25/10
Efficiency - 89.5%
Discharge: Top Horiz. Front
CW 17.7 sq.ft. 4 Rows 14 FPI Half Circuit
0.016 in. Tube Wall Thickness
Weights and Dimensions
(LxWxH in ft in) 9' 8" x 5' 5" x 3' 8" **
Dry 1330 LB ** Wet 1401 LB **
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
Job Name HOTEL SECRETS AKUMAL
UMA J06Mark for
Date July 10, 2014
Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and
fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are
provided primarily for shipping purposes. Shipping skids are not included.
All filter media efficiency ratings are for the filter media only.
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
v6.34 02/11/14 www.carrier.com
Cooling Application's Balance Criteria: Fluid Flow
Coil Model Carrier 28NARow / FPI / Circ 4 / 14 / HF
Face Area Type LargeCoil Face Area 17.70 sqftFace Velocity 536.7 fpmTube Material Al / CuTube Diameter 0.5 inTube spacing: Stf x Str 1.25 x 0.781 inTube Wall Thickness 0.016 in
Actual Airflow 9500 CFMSite Altitude 0 ft
Total Cooling Capacity 460.76 MBHSensible Cooling Capacity 292.62 MBHFluid Flow Rate 65.8 gpmFluid Pressure Drop 29.6 ft wg
Fluid Velocity 5.9 ft/sEntering Fluid Temperature 42.00 FLeaving Fluid Temperature 56.00 FFluid Temperature Rise 14.0 FEntering Air Dry Bulb 87.00 FEntering Air Wet Bulb 72.00 FEntering Air Enthalpy 35.60 BTU/lbLeaving Air Dry Bulb 58.83 FLeaving Air Wet Bulb 57.64 FLeaving Air Enthalpy 24.8 BTU/lb
Air Friction 0.73 in wg
Brine FWBrine Concentration 0 %Fouling Factor 0.0 (hr-sqft-F)/BTU
NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org).
HOTEL SECRETS AKUMALUMA J06
Project:Tag:
Chilled Water Coil Performance Summary
v6.34 02/11/14 www.carrier.com
Fan Model 39L
Unit Size 18
Fan Type LA (For LFA Clg. Coils)
Inlet Guide Vanes No
Actual Airflow, CFM 9500
Site Altitude, ft 0
Upstream Ext. Static, in wg 0.00
Downstream Ext. Static, in wg 0.50
Cooling Coil Static, in wg 0.73
Heating Coil Static, in wg 0.00
Other Losses, in wg 0.00
Total Accessory Static, in wg 0.11
Total Static Pressure, in wg 1.34
Fan RPM 648
Fan BHP 4.7
Acoustic Data:
CasingInletDischarge
848290 63 Hz
797391 125 Hz
696786 250 Hz
676787 500 Hz
626178 1000 Hz
596172 2000 Hz
535366 4000 Hz
484258 8000 Hz
Accessories:
(1) Filter/Mixing Box Pleated 2 inch MERV 8 [0.11]
HOTEL SECRETS AKUMALUMA J06
Project:Tag:
Supply Fan Performance Summary
Job Name HOTEL SECRETS AKUMAL
UMA J07Mark for
Date July 10, 2014
Unit Parameters
Unit Size: 8
Insulation: 1" 1.5# Tuf-Skin II Double Wall
Hand: Right
No Export Crate
Controls: No Product Integrated Controls
ANG Angle Filter Section
2in Pleated MERV8 Filters - kit
(2) 16in. x 20in.
(2) 16in. x 25in.
LA Horizontal Cooling (LFA) Coil/Fan Section
Fan RPM: 1026
Drive
Motor HP: 3
Voltage: 230/460 3 Phase 60Hz
Efficiency: Premium
Enclosure: ODP
RPM: 1800
Manufacturer - Generic
Frame Size - 182T
Motor Shaft Diameter (in.) - 1.125
Full Load Amps - 7.8/3.9
MCA - 9.7/4.9
MOCP - 15/6
Efficiency - 89.5%
Discharge: Top Horiz. Front
CW 7.9 sq.ft. 6 Rows 14 FPI Half Circuit
0.016 in. Tube Wall Thickness
Weights and Dimensions
(LxWxH in ft in) 6' 4" x 4' 2" x 2' 8" **
Dry 729 LB ** Wet 779 LB **
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
Job Name HOTEL SECRETS AKUMAL
UMA J07Mark for
Date July 10, 2014
Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and
fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are
provided primarily for shipping purposes. Shipping skids are not included.
All filter media efficiency ratings are for the filter media only.
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
v6.34 02/11/14 www.carrier.com
Cooling Application's Balance Criteria: Fluid Flow
Coil Model Carrier 28NARow / FPI / Circ 6 / 14 / HF
Face Area Type LargeCoil Face Area 7.90 sqftFace Velocity 506.3 fpmTube Material Al / CuTube Diameter 0.5 inTube spacing: Stf x Str 1.25 x 0.781 inTube Wall Thickness 0.016 in
Actual Airflow 4000 CFMSite Altitude 0 ft
Total Cooling Capacity 165.90 MBHSensible Cooling Capacity 118.52 MBHFluid Flow Rate 23.7 gpmFluid Pressure Drop 9.4 ft wg
Fluid Velocity 3.4 ft/sEntering Fluid Temperature 42.00 FLeaving Fluid Temperature 56.00 FFluid Temperature Rise 14.0 FEntering Air Dry Bulb 79.50 FEntering Air Wet Bulb 66.00 FEntering Air Enthalpy 30.65 BTU/lbLeaving Air Dry Bulb 52.40 FLeaving Air Wet Bulb 52.09 FLeaving Air Enthalpy 21.4 BTU/lb
Air Friction 0.96 in wg
Brine FWBrine Concentration 0 %Fouling Factor 0.0 (hr-sqft-F)/BTU
NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org).
HOTEL SECRETS AKUMALUMA J07
Project:Tag:
Chilled Water Coil Performance Summary
v6.34 02/11/14 www.carrier.com
Fan Model 39L
Unit Size 8
Fan Type LA (For LFA Clg. Coils)
Inlet Guide Vanes No
Actual Airflow, CFM 4000
Site Altitude, ft 0
Upstream Ext. Static, in wg 0.00
Downstream Ext. Static, in wg 0.30
Cooling Coil Static, in wg 0.96
Heating Coil Static, in wg 0.00
Other Losses, in wg 0.00
Total Accessory Static, in wg 0.13
Total Static Pressure, in wg 1.39
Fan RPM 1010
Fan BHP 2.0
Acoustic Data:
CasingInletDischarge
838189 63 Hz
777189 125 Hz
686685 250 Hz
646484 500 Hz
666582 1000 Hz
636576 2000 Hz
595972 4000 Hz
575167 8000 Hz
Accessories:
(1) ANG Pleated 2 inch MERV 8 [0.13]
HOTEL SECRETS AKUMALUMA J07
Project:Tag:
Supply Fan Performance Summary
Job Name HOTEL SECRETS AKUMAL
UMA J08Mark for
Date July 10, 2014
Unit Parameters
Unit Size: 6
Insulation: 1" 1.5# Tuf-Skin II Double Wall
Hand: Right
No Export Crate
Controls: No Product Integrated Controls
FLT Flat Filter Section
2in Pleated MERV8 Filters - kit
(2) 20in. x 20in.
LA Horizontal Cooling (LFA) Coil/Fan Section
Fan RPM: 926
Drive
Motor HP: 1
Voltage: 230/460 3 Phase 60Hz
Efficiency: Premium
Enclosure: ODP
RPM: 1800
Manufacturer - Generic
Frame Size - 143T
Motor Shaft Diameter (in.) - 0.875
Full Load Amps - 2.8/1.4
MCA - 3.6/1.8
MOCP - 6/3
Efficiency - 85.5%
Discharge: Top Horiz. Front
CW 5.9 sq.ft. 6 Rows 14 FPI Half Circuit
0.016 in. Tube Wall Thickness
Weights and Dimensions
(LxWxH in ft in) 4' 9" x 3' 10" x 2' 4" **
Dry 467 LB ** Wet 506 LB **
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
Job Name HOTEL SECRETS AKUMAL
UMA J08Mark for
Date July 10, 2014
Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and
fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are
provided primarily for shipping purposes. Shipping skids are not included.
All filter media efficiency ratings are for the filter media only.
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
v6.34 02/11/14 www.carrier.com
Cooling Application's Balance Criteria: Fluid Flow
Coil Model Carrier 28NARow / FPI / Circ 6 / 14 / HF
Face Area Type LargeCoil Face Area 5.90 sqftFace Velocity 406.8 fpmTube Material Al / CuTube Diameter 0.5 inTube spacing: Stf x Str 1.25 x 0.781 inTube Wall Thickness 0.016 in
Actual Airflow 2400 CFMSite Altitude 0 ft
Total Cooling Capacity 90.52 MBHSensible Cooling Capacity 70.47 MBHFluid Flow Rate 12.9 gpmFluid Pressure Drop 3.9 ft wg
Fluid Velocity 2.2 ft/sEntering Fluid Temperature 42.00 FLeaving Fluid Temperature 56.00 FFluid Temperature Rise 14.0 FEntering Air Dry Bulb 78.00 FEntering Air Wet Bulb 64.00 FEntering Air Enthalpy 29.14 BTU/lbLeaving Air Dry Bulb 51.15 FLeaving Air Wet Bulb 50.90 FLeaving Air Enthalpy 20.8 BTU/lb
Air Friction 0.67 in wg
Brine FWBrine Concentration 0 %Fouling Factor 0.0 (hr-sqft-F)/BTU
NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org).
HOTEL SECRETS AKUMALUMA J08
Project:Tag:
Chilled Water Coil Performance Summary
v6.34 02/11/14 www.carrier.com
Fan Model 39L
Unit Size 6
Fan Type LA (For LFA Clg. Coils)
Inlet Guide Vanes No
Actual Airflow, CFM 2400
Site Altitude, ft 0
Upstream Ext. Static, in wg 0.00
Downstream Ext. Static, in wg 0.30
Cooling Coil Static, in wg 0.67
Heating Coil Static, in wg 0.00
Other Losses, in wg 0.00
Total Accessory Static, in wg 0.15
Total Static Pressure, in wg 1.12
Fan RPM 897
Fan BHP 0.9
Acoustic Data:
CasingInletDischarge
787684 63 Hz
726684 125 Hz
636180 250 Hz
626282 500 Hz
585774 1000 Hz
586071 2000 Hz
545467 4000 Hz
524662 8000 Hz
Accessories:
(1) Flat pleated 2 inch MERV 8 [0.15]
HOTEL SECRETS AKUMALUMA J08
Project:Tag:
Supply Fan Performance Summary
Job Name HOTEL SECRETS AKUMAL
UMA J09Mark for
Date July 10, 2014
Unit Parameters
Unit Size: 8
Insulation: 1" 1.5# Tuf-Skin II Double Wall
Hand: Right
No Export Crate
Controls: No Product Integrated Controls
ANG Angle Filter Section
2in Pleated MERV8 Filters - kit
(2) 16in. x 20in.
(2) 16in. x 25in.
LA Horizontal Cooling (LFA) Coil/Fan Section
Fan RPM: 1080
Drive
Motor HP: 3
Voltage: 230/460 3 Phase 60Hz
Efficiency: Premium
Enclosure: ODP
RPM: 1800
Manufacturer - Generic
Frame Size - 182T
Motor Shaft Diameter (in.) - 1.125
Full Load Amps - 7.8/3.9
MCA - 9.7/4.9
MOCP - 15/6
Efficiency - 89.5%
Discharge: Top Horiz. Front
CW 7.9 sq.ft. 6 Rows 14 FPI Half Circuit
0.016 in. Tube Wall Thickness
Weights and Dimensions
(LxWxH in ft in) 6' 4" x 4' 2" x 2' 8" **
Dry 729 LB ** Wet 779 LB **
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
Job Name HOTEL SECRETS AKUMAL
UMA J09Mark for
Date July 10, 2014
Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and
fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are
provided primarily for shipping purposes. Shipping skids are not included.
All filter media efficiency ratings are for the filter media only.
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
v6.34 02/11/14 www.carrier.com
Cooling Application's Balance Criteria: Fluid Flow
Coil Model Carrier 28NARow / FPI / Circ 6 / 14 / HF
Face Area Type LargeCoil Face Area 7.90 sqftFace Velocity 506.3 fpmTube Material Al / CuTube Diameter 0.5 inTube spacing: Stf x Str 1.25 x 0.781 inTube Wall Thickness 0.016 in
Actual Airflow 4000 CFMSite Altitude 0 ft
Total Cooling Capacity 169.06 MBHSensible Cooling Capacity 103.17 MBHFluid Flow Rate 24.1 gpmFluid Pressure Drop 9.7 ft wg
Fluid Velocity 3.4 ft/sEntering Fluid Temperature 42.00 FLeaving Fluid Temperature 56.00 FFluid Temperature Rise 14.0 FEntering Air Dry Bulb 76.30 FEntering Air Wet Bulb 66.50 FEntering Air Enthalpy 31.07 BTU/lbLeaving Air Dry Bulb 52.71 FLeaving Air Wet Bulb 52.50 FLeaving Air Enthalpy 21.7 BTU/lb
Air Friction 1.00 in wg
Brine FWBrine Concentration 0 %Fouling Factor 0.0 (hr-sqft-F)/BTU
NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org).
HOTEL SECRETS AKUMALUMA J09
Project:Tag:
Chilled Water Coil Performance Summary
v6.34 02/11/14 www.carrier.com
Fan Model 39L
Unit Size 8
Fan Type LA (For LFA Clg. Coils)
Inlet Guide Vanes No
Actual Airflow, CFM 4000
Site Altitude, ft 0
Upstream Ext. Static, in wg 0.00
Downstream Ext. Static, in wg 0.42
Cooling Coil Static, in wg 1.00
Heating Coil Static, in wg 0.00
Other Losses, in wg 0.00
Total Accessory Static, in wg 0.13
Total Static Pressure, in wg 1.55
Fan RPM 1053
Fan BHP 2.2
Acoustic Data:
CasingInletDischarge
838189 63 Hz
787290 125 Hz
696786 250 Hz
646484 500 Hz
676683 1000 Hz
636576 2000 Hz
606073 4000 Hz
585268 8000 Hz
Accessories:
(1) ANG Pleated 2 inch MERV 8 [0.13]
HOTEL SECRETS AKUMALUMA J09
Project:Tag:
Supply Fan Performance Summary