Suitable for Emergency, Peak and PrimePower System Applications
TTHHEE PPOOWWEERR AAUUTTHHOORRIITTYY
Low Voltage Automatic Transfer Switch Systems
THE POWER AUTHORITYASCO’s experience and commitment to excellence indesigning and building Emergency Power ControlSystems for any application has made us the premiermanufacturing and service organization in the world.
For over 100 years we have built upon a tradition ofproviding our customers a full range of high perfor-mance and quality products. ASCO’s experiencespans the history of the power control industry andsince 1888 we have set the standard for the entireindustry. Our reputation as the leader in emergencypower control equipment speaks to the quality of ourproducts and the dedication of our people.
ASCO operates two modern facilities dedicated tomanufacturing low and medium voltage power controlsystems. Located in Parsippany, New Jersey andStockton, California, these manufacturing plantsproduce state-of-the-art power control systems foremergency or standby power generation, peak loadshaving, prime power, parallel with utility, co-generation, emergency load management and powerdistribution. These products are designed andmanufactured to meet and exceed the demands of agrowing global market.
Our ongoing dedication to research & developmentand extensive testing have confirmed ASCO productsas the industry standard. Since our beginnings thissame dedication has established ASCO as thepioneering innovator in the emergency power controlindustry. This commitment continues to set ASCOapart as the company that stands at the threshold ofnew technologies and has resulted in a long list ofindustry firsts throughout the years.
ASCO has always been committed to providing afull range of products with only one thing inmind... transferring power from an available source toa critical load. Telecommunications systems, datanetworks, industrial processes and critical installationsdemand proven emergency and standby power transfersolutions. As the worlds leader in emergency andstandby power, ASCO products and systems safeguardyour business... because we keep your power on.
Page 2
Fig. 1 Parsippany, New Jersey, USA
Fig. 2 Stockton, California, USA
Automatic Transfer Systems Product Overview
Content Page
Service Entrance Rated Transfer System ............................................. 4
ATS Switchboard .................................................................................. 5
Two Source Automatic Transfer System .............................................. 6
Three Source ATS System .................................................................... 7
Three Source Priority System .............................................................. 8
Soft Load Transfer System ................................................................... 9
Custom Applications ....................................................................... 10-11
Page 3
For more information on ASCO Automatic Transfer Systems contact yournearest ASCO source at 800-937-ASCO or visit our website at www.asco.com.
Service Entrance Rated Transfer System
ASCO service entrance rated transfer systems are designedfor automatic switching of loads between the utility sourceand an alternate source of power. The transfer system alsocontains a disconnect device on the normal source, plus adisconnect link on the utility neutral, and a disconnect linkbetween neutral and ground. If the utility source is Yconnected, the voltage is greater than 250 volts phase toneutral and the system continuous current is greater than1000 amperes, the utility disconnect device will be equippedwith ground fault trip.
Figure 3 shows a typical service entrance rated transfersystem with a 1200 ampere automatic transfer switch and a1200 ampere utility circuit breaker.
Product Features
• The utility disconnect device will be equipped withground fault trip if the voltage between neutral andground is greater than 250 volts, and the continuouscurrent is greater than 1000 amperes.
• Disconnect link for the utility neutral bus.
• Disconnect link between the neutral bus and theground bus.
• Meets all NEC requirements for service entrancerating, and is labeled to UL 891 standards.
• Available up through 4000 amperes using ASCO940, 962, 434, 436 and ASCO's new 7000 seriesautomatic transfer switches.
Page 4
NeutralDisconnect
Link
GroundDisconnect
Link
GFCT
Utility
UtilityCB
ATS
Emergency
LoadN
Ø
N Ø
Fig. 4 One line diagram of the service entrance rated transfer system shown in figure 3.
GFCT - Ground FaultCurrent Transformer
ATS - AutomaticTransfer Switch
Acc. 28
Fig. 3 Service entrance rated transfer system.
ATS Switchboards
An automatic transfer switchboard is a switch-board containing two or more automatic transferswitches in a common line-up. The switchboardshown in figure 5 contains two ASCO 962, 2000ampere, automatic transfer bypass-isolationswitches with circuit breakers on the normal andload side of each switch. An ammeter and volt-meter are also located on the load side of eachswitch.
Product Features
• Connects multiple automatic transfer switches together in a common switchboard.
• Optional normal and/or emergency circuit breakers for overcurrent protection.
• Optional distribution circuit breakers of the size andtype to meet customer load requirements.
• Optional instrument meters for normal,emergency, or load for local monitoring.
• Designs can be provided with a UL 891 Label containing up through a 10,000 ampere main bus.
• Utilizes ASCO 940, 962, 434, 436 and ASCO's new 7000 series automatic transfer switches.
Page 5
Source #1
ATS/BP #1ATS/BP #2
Source #2
Load Load
CircuitBreaker
CircuitBreaker
CircuitBreaker
CircuitBreaker
43A
43V
43 A
43 V
Fig. 5 Automatic transfer switchboard.
Fig. 6 One line diagram of the automatic transfer switchboard shown in figure 5.
V - VoltmeterA - Ammeter43 - Selector SwitchATS/BP - Automatic Transfer and
Bypass-Isolation Switch
Two Source Automatic Transfer System
ASCO two-source systems are designed for automatic switching ofloads between the utility source and an alternate source of power.Upon the loss of the utility power source, the system provides anautomatic start signal to the alternate source of power. Once thealternate source has reached proper voltage and frequency, thesystem transfers the critical load from the utility source to thealternate power source. When normal power is restored the controlswill retransfer the load to the utility and signal shutdown of thealternate power source after allowing a cooldown period.
ASCO two-source systems include an automatic transfer switch,plus any or all of the following options; automatic engine startingcontrols, overcurrent protection for both emergency and normalsources, instrument meters, status annunciation, and audible alarm.The systems are designed to NEMA switchboard construction andare labeled to UL 891 standards.
These systems can be designed for top cable entrance, bottom cableentrance or bus duct connections.
The system shown in figure 7 contains a 1200 ampere closedtransition automatic transfer switch with a 1200 ampere utilitycircuit breaker, multi-purpose meter, reverse power relay, and analarm horn.
Product Features
• Normal, emergency, and/or load circuit breakers.
• Protective relaying (as required).
• Optional instrument meters for normal, emergency,or load for local monitoring.
• Designs are based on NEMA and UL 891 standards.
• Optional engine start control logic and/or loadcontrol logic.
• Designs available up to 4000 amperes utilizingASCO 940, 962, 434, 436 and ASCO's new 7000series automatic transfer switches.
Page 6
Fig. 8 One line diagram of the two source automatic transfer system shown in figure 7.
Engine
MM
ATSLOAD
Normal Source
32
MM = Multi-Purpose Meter
32 = Reverse Power Relay
ATS = Automatic Transfer Switch
Fig. 7 Two source system with main circuit breaker,protective relaying and and automatic transfer switch rated 1200 amperes.
Three Source Automatic Transfer System
ASCO three-source systems are similar to ASCO two-source systems except that a second alternate powersource is added to back up the first if that power sourcefails. Upon the loss of the utility power source, thesystem provides all necessary controls to start bothalternate power sources. The critical loads areautomatically transferred to the first alternate powersource that achieves acceptable voltage and frequency.The second alternate power source is then automatical-ly shutdown after a time delay and cooldown period. Ifthe first alternate power source fails, the secondalternative power source will be automaticallyre-started and the load will be transferred from the firstalternative power source to the second alternative powersource. When the normal power is restored, thecontrols automatically retransfer the load to the utilitypower source.
Figure 9 shows a three source automatic transfer systemwith two 940 automatic transfer switches and threedistribution circuit breakers for feeding critical loads.
Product Features
• Control logic for selecting between the alternativepower sources.
• Normal, emergency, and/or load circuit breakers.
• Protective relaying (as required).
• Optional instrument meters for normal, emergency, orload for local monitoring.
• Designs are based on NEMA and UL 891 standards.
• Optional engine start control logic and/or load controllogic.
• Designs available up to 4000 amperes utilizing ASCO940, 962, 434, 436 and ASCO's new 7000 seriesautomatic transfer switches.
Page 7
ATS = Automatic Transfer Switch
Fig. 10 One line diagram of the three source automatic transfer system shown in figure 9.
Engine 1 Engine 2
ATS1
ATS2
NORMALSOURCE
LoadCircuit
Breakers
Fig. 9 Three source automatic transfer system.
Three Source Priority System
ASCO three-source priority systems are similar to the ASCO three-source systems except they protect two criticalloads rather than one critical load. Upon the loss of the utility power source, the system provides all necessarycontrols to start both alternative power sources. The most critical load is transferred to the first alternate powersource that achieves acceptable voltage and frequency. The second most critical load is then transferred to thesecond alternate power source when it achieves acceptable voltage and frequency. If the alternate power sourcefeeding the most critical load should fail, the most critical load would be transferred to the second alternate powersource and the second most critical load would be shed. When the utility power source is restored, the systemcontrols automatically retransfer the loads to the utility and both alternate power sources are run for a cooldownperiod and then shutdown.
Figure 11 shows a three source priority system containing a priority selector transfer switch (ATS-2) and sevendistribution circuit breakers. ATS-1 and ATS-2 are wall mounted automatic transfer switches and are not shown inthis line-up.
Product Features
• Priority selector transfer switch.
• Control logic for selecting between alternate power sources
• Normal, emergency, and/or load circuit breakers.
• Protective relaying (as required).
• Optional instrument meters for normal, emergency, or load for localmonitoring.
• Designs are based on NEMA and UL 891 standards.
• Optional engine start control logic and/or load control logic.
• Designs available up through 4000 amperes utilizing ASCO 940, 962,434, 436 and ASCO's new 7000 series automatic transfer switches.
Page 8
Fig. 12 One line diagram of the three source priority system shown in figure 11.
Engine 1 Engine 2
NORMALSOURCE
No.1CriticalLoad
No. 2CriticalLoad
ATS - 1 ATS - 3
ATS - 2
ATS = Automatic Transfer Switch
Fig. 11 Three source priority system.
Product Features• Open or closed transition transfer between normal and emergency.
• Emergency or peak shave mode of operation.
• Engine start control logic and load control logic.
• Available configurations include either an ASCO 434, 436 or ASCO’s new7000 Series closed transition transfer switches through 4000 amperes. Thetransfer system configuration can also accommodate power circuit breakers.
• Normal and emergency circuit breakers can be provided when using a transfer switch for overcurrent protection.
• Full manual paralleling operation (standard).
• Protective relaying (as required).
• Optional instrument meters for normal, emergency, or load for local monitoring.
• Designs are based on NEMA and UL 891 standards.
Page 9
Soft Load Transfer SystemASCO soft load closed transition transfer switches provide a make-before-break transfer of a building load from a utility power source to an alternatepower source. This system automatically brings the engine generator intosynchronism with the utility source, then gradually shifts the load from theutility to the engine generator with virtually no voltage or frequencyfluctuations.
Figure 13 shows a typical soft load transfer system containing an ASCO closedtransition transfer switch.
Fig. 14 One line diagram of the soft load transfer system shown in figure 13.
CTTS
KW
V
A
F
KW
32R86
25C
90*65*
43V
47N
2759
81O/U
43
43
ASCO Control Panel
Load
Alternate PowerSource
UtilityPowerSource
WattXDCR
To 52GShunt TripSY
Ground 400A
Neutral 2000A
Phase 2000A
STB
STB
STB V - VoltmeterA - AmmeterF - Frequency MeterKW - WattmeterWatt XDCR - Watt TransducerSTB - Shorting Terminal Block25C - Synch Check Relay27/59 - Under/Over Voltage Relay32R - Reverse Power Relay47N - Phase Sequence Under
Voltage Relay65 - Governor (*)81O/U - Over/Under
Frequency Relay90 - Voltage Regulator (*)CTTS - Closed Transition
Transfer SwitchSY - Synchroscope43 - Phase Selector Switch86 - Lockout Relay
Note:* Furnished by alternate power source supplier
Fig. 13 Soft load transfer system.
Page 10
Custom Applications
Selective load systems allow one load at a time to be operatedwhen normal power fails. The system uses the minimum amountof auxiliary power for operation so the alternate power source canbe sized for only one load at a time. The selective load system canbe designed to handle any number of loads in any combination ofsizes to suit the customers needs.
The only interfacing between the ASCO selective load system andthe load controls are power cables.
The system can be used with any electrical load application whereonly one load out of a number of loads are to be operated from thealternate power source at one time. A typical application is withmultiple banks of elevators when you want to enable only oneelevator at a time to operate under emergency conditions.
The system can be supplied with a separate control panel, whichallows loads to be selected from a remote location.
Figure 15 shows a typical selective load system with transferswitches for five loads. The control panel has a selector switchand position indication of each load.
Selective Load System
Transfer Switch with Distribution System
Transfer switches can be provided with normal andemergency circuit breakers for overcurrentprotection, plus any combination of distributioncircuit breakers, bolted pressure switches, orfusible disconnect switches.
Figure 16 shows a switchboard containing a circuitbreaker on the normal source of the automatictransfer switch plus a distribution panelboard ofmolded case circuit breakers to protect criticaldownstream loads. The cubicle on the left end ofthe system provides monitoring and control of thedistribution system.
Fig. 16 Transfer switch with distribution.
Fig. 15 Selective load system.
Custom Applications
Page 11
Figure 17 shows a 4000 ampere transfer switchwith bus risers for bottom entry bus duct on boththe normal source and load connections. Theemergency side of the transfer switch has lugs forcable connections from the top of the enclosure.This demonstrates our capability to meet customservice entry requirements.
Transfer Switch with Bottom Bus Risers
Figure 18 shows a transfer switch with afuse disconnect switch on the normal side.The switch is in a non-walk-in NEMA 3Routdoor enclosure. The outdoor enclosureis designed for front and rear entry onlywith three point catches on the doors aswell as provisions for padlocking.
Outdoor enclosures are available for allASCO transfer switch products.
Transfer Switch in an Outdoor Enclosure
Fig. 17 Transfer switch with bottom bus riser.
Fig. 18 Transfer switch in an outdoor enclosure.
Publication 3049
ASIA • AUSTRALIA • BRAZIL • CANADA • GERMANY • JAPAN • MEXICO • SOUTH AFRICA • UNITED ARAB EMIRATES • UNITED KINGDOM • UNITED STATES
Florham Park, New Jersey 07932 USA© Automatic Switch Co. 1998 Printed in the U.S.A.
800-937-ASCOwww.asco.com
Power Solutions — North AmericaFully Integrated, Reliable, Efficient
CNA100235_Full Line Brochure 2 12/28/10 7:59 PM
With more than 90 years of experience in power generation and an extensive global distributor network across 190 countries, Cummins Power Generation is ready to match the right generating, transfer and control technologies with your power needs — whether you require continuous, prime, peaking or standby power; cogeneration; or a complete turnkey power plant.
Contents
Diesel generator sets ..........................................4
Diesel generator sets: 10 kW to 300 kW .............5
Diesel generator sets: 350 kW to 2750 kW .........6
Low-emissions technologies ...............................7
Lean-burn gas generator sets .............................8
Spark-ignited generator sets ...............................9
Enclosures .................................................. 10–11
Generator set controls ................................ 12–13
Power transfer equipment .......................... 14–15
Paralleling systems ...........................................16
Rental power ....................................................17
Software and networking ............................ 18–19
Global Power Leader
Our global operations:
79Factories 19TechnicalCenters 20PartsDistributionCenters 550Distributors 5,200SalesandServiceCenters 190Countries40,000Employees
2 www.cumminspower.com
CNA100235_Full Line Brochure 3 12/28/10 7:59 PM
Global Strength, Local Partnership
Cummins Power Generation is committed to
understanding and meeting our customers’ needs
worldwide — through trusted local relationships,
innovative solutions and dedicated customer
service. This promise enables us to deliver power
wherever, whenever and however it is needed.
Our worldwide distribution network includes 550
distributors and 5,200 sales and service locations
and 20 parts distribution centers. That means you
can expect a face-to-face, trustworthy relationship
and fast access to reliable service, engineering
expertise and parts support. Our service centers,
located strategically throughout the world, are
staffed with technicians trained to the highest
Cummins Power Generation standards.
Wherever you need fully integrated, reliable
and efficient power, your local Cummins Power
Generation distributor is available. Visit
www.cumminspower.com/local to find the
distributor nearest you.
Fullyintegrated,reliable,efficient
For more than a decade, Cummins Power
Generation has been the industry leader in power
system integrated designs. All major components
of our systems — the engine, alternator,
generator sets, transfer switches and paralleling
controls — are manufactured by Cummins.
Because they are designed by one manufacturer,
all of the elements of our power generation
systems work in harmony from the start. This
integral approach — what we call the Power of
One™ — gives you the peace of mind that comes
from premium customer support and reliable,
trouble-free operation.
Cummins Power Generation PowerCommand®
diesel-powered generator sets are available in
sizes ranging from 10 to 2750 kW. Our spark-
ignited generator sets are available from 20 to
150 kW. A complete range of transfer switches
and paralleling controls supports our generator
sets. As a result, you can expect an industry-
leading power solution with unrivaled reliability.
www.cumminspower.com 3
CNA100235_Full Line Brochure 4 12/28/10 7:59 PM
PowerCommand® Diesel Generator Sets
Integrated design and manufacturing combine to give you unequaled reliability, power quality, rated performance and efficient operation. PowerCommand diesel-powered generator sets
remain the best-value choice for standby and
emergency power systems worldwide. Known for
their rugged dependability and reliable mechanical
and electrical performance, our diesel generators
are also well suited to utility peaking plants,
distributed generation facilities, peak shaving (or
peak lopping), and power management at large
commercial or industrial sites.
Powered by Cummins engines, PowerCommand
diesel generator sets are available in sizes ranging
from 10 to 2750 kW. Heavy-duty Cummins
engines are known for their fuel efficiency,
responsive transient performance and rugged
reliability. Cooling systems are prototype-tested to
provide guaranteed performance in high ambient
applications, so you get all the power you pay for
every day.
High-performance, low-reactance Cummins-
manufactured alternators provide good voltage
waveform and exceptional motor starting in
demanding applications such as data centers,
hospitals and industrial facilities.
PowerCommand generator sets are controlled
by the world’s first and most fully integrated
microprocessor-based control system. The
system seamlessly integrates governing,
voltage regulation, generator set control and
protection functions.
You can rely on PowerCommand diesel-powered
generator sets to provide these benefits:
n International Building Code (IBC) seismic
certification on all emissions-regulated products
(up to 2500 kW)
n Proven reliability and low life-cycle costs
n High efficiency and operational flexibility
n High-quality electrical performance
n Well-established service and fuel supply
infrastructure
n Optional factory-integrated exhaust after-
treatments to reduce emissions for high-hour
use in environmentally sensitive locations
Reliability and redundancy meet hospital requirements AlbertaChildren’sHospital,Calgary
Three 2 MW diesel generators provide
emergency standby power for the
133-bed hospital. The PowerCommand
paralleling system features complete
integration and interoperability between
the generator sets and controls.
4 www.cumminspower.com
CNA100235_Full Line Brochure 5 12/28/10 7:59 PM
For additional technical specifications, visit: http://www.cumminspower.com/na/products/generators/diesel
Model
StandbykW PrimekW StandbykVA PrimekVA Engine
60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz type
DSKAA* 10 – 9.1 – 12.5 – 11.4 – Kubota D1703-M
DSKAB* 15 – 13.6 – 18.8 – 17 – Kubota D1703-M
DSKBA* 20 – 18.2 – 25 – 22.7 – Kubota V2203-M
DSKCA* 25 – 22.7 – 31.3 – 28.4 – Kubota V3300
DGHCA* 30 – 27 – 38 – 34 – 4BT3.3G5 NR4i
DGHCB* 35 – 32 – 44 – 40 – 4BT3.3G5 NR4i
DSFAA* 35 – 32 – 44 – 40 – QSB5-G3 NR3
DGHCC* 40 – 36 – 50 – 45 – 4BT3.3G5 NR4i
DSFAB* 40 – 35 – 50 – 44 – QSB5-G3 NR3
DGCA 50 40 45 36 63 50 56 45 4BT3.9-G4
DSFAC* 50 – 45 – 63 – 56 – QSB5-G3 NR3
DGCB 60 50 55 45 75 63 69 56 4BT3.9-G4
DSFAD* 60 – 55 – 75 – 69 – QSB5-G3 NR3
DGCG 80 65 72 60 100 81 90 75 4BTA3.9-G3
DSFAE* 80 – 72 – 100 – 90 – QSB5-G3 NR3
DGDB 100 85 90 80 125 106 113 100 4BT3.9-G4
DSGAA** 100 – 90 – 125 – 113 – QSB7-G3 NR3
DGDK 125 100 113 90 156 125 141 113 6BTA5.9-G3
DSGAB** 125 – 113 – 156 – 141 – QSB7-G3 NR3
DGFA 150 140 135 125 188 175 169 156 6CTA8.3-G2
DSGAC** 150 – 135 – 188 – 169 – QSB7-G3 NR3
DGFB 175 150 160 135 219 188 200 169 6CTA8.3-G2
DSHAB** 175 – 160 – 219 – 200 – QSL9-G2 NR3
DGFC 200 178 180 180 250 220 225 200 6CTAA8.3-G2
DSHAC** 200 – 180 – 250 – 225 – QSL9-G2 NR3
DGFS 230 – – – 288 – – – 6CTAA8.3-G2
DSHAD 230 – 209 – 288 – 261 – QSL9-G2 NR3
DQDAA** 250 220 225 200 313 275 281 250 QSL9-G3 NR3QSL9-G5
DQDAB 275 250 250 227 344 313 313 284 QSL9-G5
DQHAA** 275 – 250 – 344 – 313 – QSM11-G4 NR3
DQDAC 300 265 270 240 375 331 338 300 QSL9-G5
DQHAB** 300 – 270 – 375 – 338 – QSM11-G4 NR3
Poweroutput
DSHAC
DSGAB
DSFAE
* Available with EPA Nonroad Emissions Certification
** Available with EPA Stationary Emergency CertificationMost models UL 2200-listed. See your distributor for specific details.
Diesel 10 kW to 300 kW
www.cumminspower.com 5
CNA100235_Full Line Brochure 6 12/28/10 7:59 PM
For additional technical specifications, visit: http://www.cumminspower.com/na/products/generators/diesel
Poweroutput
DQKAA
DFEK
DQDAA
DFHC
** Available with EPA Stationary Emergency Certification
Most models UL 2200-listed. See your distributor for specific details.
Diesel 350 kW to 2750 kW
Model
StandbykW PrimekW StandbykVA PrimekVA Engine
60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz type
DFEG** 350 – 320 – 438 – 400 – QSX15-G9 NR2
DFEH** 400 352 350 320 500 440 438 400 QSX15-G9 NR2 (60 Hz) QSX15-G8 (50 Hz)
DFEJ** 450 400 410 364 563 500 513 455 QSX15-G9 NR2 (60 Hz) QSX15-G8 (50 Hz)
DFEK** 500 440 455 400 625 550 569 500 QSX15-G9 NR2 (60 Hz) QSX15-G8 (50 Hz)
DFGB 600 550 545 500 750 688 681 625 VTA28-G5
DQCA** 600 545 545 500 750 681 681 625 QSK23-G7 (60 Hz) QSK23-G3 (50 Hz)
DFGE 750 – – – 938 – – – VTA28-G7
DFHA 750 620 680 560 938 775 850 700 QST30-G1
DQCB** 750 660 680 600 938 825 850 750 QSK23-G7 (60 Hz) QSK23-G3 (50 Hz)
DQFAA** 750 – 680 – 1000 – 850 – QST30-G5 NR2
DFHB 800 700 725 640 1000 875 906 800 QST30-G2
DQCC** 800 720 725 656 1000 900 906 820 QSK23-G7 (60 Hz) QSK23-G3 (50 Hz)
DQFAB** 800 – 725 – 1125 – 907 – QST30-G5 NR2
DFHC 900 800 818 725 1125 1000 1023 906 QST30-G3
DQFAC** 900 – 818 – 1250 – 1023 – QST30-G5 NR2
DFHD 1000 880 900 800 1250 1100 1125 1000 QST30-G5 (60 Hz) QST30-G4 (50 Hz)
DQFAD** 1000 – 900 – 1563 – 1125 – QST30-G5 NR2
DFLC 1250 1120 1100 1000 1563 1400 1375 1250 KTA50-G3
DQGAA** 1250 – 1100 – 1563 – 1375 – QSK50-G4 NR2
DQGAE** 1250 – 1135 – 1563 – 1419 – QSK50-G5
DFLE 1500 1290 1250 1100 1875 1613 1563 1375 KTA50-G9 (60 Hz) KTA50-G8 (50 Hz)
DQGAB** 1500 – 1350 – 1875 – 1688 – QSK50-G4 NR2
DQGAF** 1500 – 1365 – 1875 – 1706 – QSK50-G5
DQKB 1750 1500 1600 1350 2188 1875 2000 1688 QSK60-G6 (60 Hz) QSK60-G3 (50 Hz)
DQKAA** 1750 – 1600 – 2188 – 2000 – QSK60-G6 NR2
DQKAD** 1750 – 1600 – 2188 – 2000 – QSK60-G6
DQKC 2000 1650 1825 1500 2500 2063 2281 1875 QSK60-G6 (60 Hz) QSK60-G3 (50 Hz)
DQKAB** 2000 – 1825 – 2500 – 2281 – QSK60-G6 NR2
DQKAE** 2000 – 1825 – 2500 – 2281 – QSK60-G6
DQKD – 1800 – 1600 – 2250 – 2000 QSK60-G4
DQKH 2250 2000 – – 2813 2500 – – QSK60-G9 (60 Hz) QSK60-G8 (50 Hz)
DQKAF** 2250 – 1825 – 2813 – 2281 – QSK60-G14
DQLC 2500 – 2335 – 3125 – 2920 – QSK78-G6
DQLE** 2500 – – – – – – – QSK78-G10
DQLD 2750 – 2500 – – – – – QSK78-G8
6 www.cumminspower.com
CNA100235_Full Line Brochure 7 12/28/10 7:59 PM
Sound-attenuated and weather-protective enclosures > For generator sets from 10 to 1000 kW
Sound-attenuated and weather-protective enclosures from Cummins Power Generation Inc. meet even the strictest sound requirements and provide optimum protection from inclement weather.
Cummins Power Generation diesel and spark-ignited generator sets are available with sound-attenuated and weather-protective enclosures. Pre-assembled, pre-integrated and delivered as part of the entire power system, these enclosures are designed to speed installation time and reduce costs. Choose from three levels of sound-attenuation, depending on model size, to comply with even the strictest noise requirements. Enclosures are constructed of steel or aluminum, which is preferred in coastal regions or other environments where corrosion is a concern.
> Diesel generator set enclosures 10 to 1000 kW Weather-protective Level I, Level II, Level III
> Spark-ignited generator set enclosures 20 to 150 kW Weather-protective Level I, Level II
www.cumminspower.com
Features:
■Fixed air inlet and outlet louvers
■Stainless steel hardware Resists rust
■Recessed, lockable doors Provides easy service access and protects internal equipment
■Enclosed exhaust system Ensures safety
■Cambered roof Prevents water accumulation
■12 and 14 gauge steel construction
■Ships assembled on fuel tank or lifting base
■Choice of vertical or horizontal discharge
■Emergency stop button (standard on 600-1000 kW)
■Non-hydroscopic sound insulation
■Rodent barriers on inlet and outlet
■Flexible oil and coolant drain lines with interior valves
> Three levels of sound attenuation
Level I: 70 to 89 d(B)A*
Level II: 63 to 78 d(B)A*
Level III: 68 to 70 d(B)A*
> Compact footprint, low profile design
> Easy access to all major generator and engine control components for servicing
> Fully-house, enclosed exhaust silencer ensures safety and protects against rust
> Enclosure, generator set, exhaust system and tank are pre-assembled, pre-integrated and shipped as one package, saving time and labor costs
> All-steel construction with stainless steel hardware offers durability
> Upgrade kits
> Enclosures mounted directly to a sub-base fuel tank or lifting base
> UL2200-listed
> Customer options available to meet your application needs
Enclosure options
> Aluminum enclosure is wind-rated to 150 mph (per ASCE 7-05 exposure D, category 1 importance factor)
> Kits available to up-fit existing generator sets or to upgrade existing enclosures with additional sound attenuation
> Exterior oil and coolant drains with interior valves for ease of service
> Overhead 2-point lifting brackets (some models)
* Full load at 7 meters, steel enclosures
www.cumminspower.com
Choose from weather protective enclosure or three levels of sound attenuation:
Sound levels (dB(A))*
kW Model Weather- protective Level I Level II
Diesel
10 DSKAA 78 68 65
15 DSKAB 81 69 66
20 DSKBA 80 70 67
25 DSKFA 82 72 69
35 DGBB 82 71 63
35 DGGD 81 72 66
40 DGBC 82 72 63
40 DGHD 79 71 64
50 DGCA 83 72 66
50 DGHE 79 70 65
60 DGCB 84 73 67
60 DSFAD 87 79 71
80 DGCG 84 76 67
80 DSFAE 87 82 72
100 DGDB 86 77 70
100 DSGAA 87 - 73
100 DSHAF 95 88 78
125 DGDK 86 80 71
125 DSGAB 87 - 74
125 DSHAE 95 88 78
150 DGFA 89 77 72
150 DSGAC 88 - 75
150 DSHAA 95 88 78
175 DGFB 90 78 72
175 DSHAB 95 88 78
200 DGFC 91 80 74
200 DSHAC 95 88 78
230 DGFS 91 81 75
230 DSHAD 96 89 78
250 DQDAA 90 86 71
275 DQDAB 89 86 71
275 DQHAA 86 85 74
300 DFCB 86 84 71
300 DQDAC 89 86 71
300 DQHAB 89 88 76
350 DFCC 87 85 72
350 DFEG 85 83 72
400 DFCE 89 85 73
400 DFEG 89 85 73
450 DFEJ 87 84 73
500 DFEK 88 85 76
600 DFGB 85 78 74
600 DQCA 87 79 74
750 DFGE 87 80 75
750 DFHA 91 81 77
750 DQCB 87 79 74
750 DQFAA 89 79 75
800 DFHB 91 81 77
800 DQCC 87 79 74
800 DQFAB 89 79 75
900 DFHC 93 83 78
900 DQFAC 88 80 76
1000 DFHD 90 80 76
1000 DQFAD 90 80 76
Sound levels (dB(A))*
kW Model Weather- protective Level I Level II
Spark-ignited
20 GGMA 77 N/A 66
25 GGMB 78 N/A 66
30 GGMC 79 N/A 67
35 GGFD 80 73 65
42/47 GGFE 83 73 66
60 GGHE 86 77 68
70/75 GGHF 87 77 69
85 GGHG 85 79 75
100 GGHH 86 80 76
125 GGLA 85 79 75
150 GGLB 85 79 75
Diesel generator sets from 100 to 150 kW (models DSGAA, DSGAB, DSGAC) are available in Level III sound attenuation.
Shown: 100 kW Tier 3 diesel generator set (model DSGAA).
www.cumminspower.com* Full load at 7 meters, steel enclosures
*
*
*
Also available Level III
100 kW DSGAA 68 dB(A) 125 kW DSGAB 69 dB(A) 150 kW DSGAC 70 dB(A)
*
Package listed to UL2200Cummins Power Generation1400 73rd Avenue N.E. Minneapolis, MN 55432 Phone: 763 574 5000 Fax: 763 574 5298
Latin America3350 Southwest 148th Ave., Suite 205Miramar, FL 33027USAPhone 1 954 431 5511Fax 1 954 433 5797
Our energy working for you.™
www.cumminspower.com© 2008 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. (3/08) CPG-623 F-1493
Diesel package dimensions (in.)
Tank capacity
(gal.)
Weather- protective
Length Width Height
Level I
Length Width Height
Level II, III
Length Width Height
35-80 kW
70 83 40 63 83 40 81 102 40 81
140 83 40 71 83 40 89 102 40 89
100-230 kW
109 105 40 67 108 40 85 142 40 87
173 105 40 72 108 40 90 142 40 92
309 105 44 87 N/A N/A N/A 145 43 97
336 105 40 86 108 40 104 142 40 106
230-500 kW
Lifting base 188 82 100 188 82 100 222 82 100
300 188 82 104 188 82 104 222 82 104
400 188 82 106 188 82 106 222 82 106
500 188 82 108 188 82 108 222 82 108
600 188 82 111 188 82 111 222 82 111
660 188 82 113 188 82 113 222 82 113
720 188 82 114 188 82 114 222 82 114
850 188 82 118 188 82 118 222 82 118
1470 200 82 128 200 82 128 200 82 128
1700 234 82 128 234 82 128 234 82 128
600-1000 kW
200 260 98 133 303 98 133 315 98 133
660 260 98 133 303 98 133 315 98 133
1000 260 98 137 303 98 137 315 98 137
1500 260 98 142 303 98 142 315 98 142
2000 280 98 142 320 98 142 320 98 142
2400 332 98 142 330 98 142 332 98 142
Spark-ignited package dimensions (in.)
Modelnumber
Weather- protective
Length Width Height
Level I
Length Width Height
Level II
Length Width Height
20 kW
GGMA 65 30 46 N/A N/A N/A 85 30 47
25 kW
GGMB 65 30 46 N/A N/A N/A 85 30 47
30 kW
GGMC 65 30 46 N/A N/A N/A 85 30 47
35 kW
GGFD 83 40 54 83 40 72 83 40 72
45 kW
GGFE 83 40 54 83 40 72 83 40 72
60 kW
GGHE 83 40 54 83 40 72 83 40 72
70 kW
GGHF 83 40 54 83 40 72 83 40 72
85 kW
GGHG 105 40 70 105 60 70 142 60 70
100 kW
GGHH 105 40 70 105 60 70 142 60 70
125 kW
GGLA 105 40 70 105 60 70 142 60 70
150 kW
GGLB 105 40 70 105 60 70 142 60 70
Our energy working for you.™
Final standards for stationary and nonroaddiesel generator sets
On July 11, 2006, the US EPA fi nalized its proposalto regulate emissions from stationary dieselcompression-ignition engines. Called the “NewSource Performance Standards,” the EPA rulerequires emissions from stationary diesel-poweredgenerator sets to be harmonized with nonroad(mobile) applications starting from January 1, 2007.
As a result of the rule:
> Generators with engine ratings of 10-99 hp must comply with Tier 2 regulations;
> Generators with engine ratings of 100-751 hp must comply with Tier 3 regulations;
> Generators with engine ratings of 752-3000 hp must comply with Tier 2 regulations;
> Engines that are not certifi ed to 2007 nonroad standards must be installed by the end-user by January 1, 2009.
Key exceptions are:
> Stationary engines over 3000 hp will remain at Tier 1 until their Tier 4 requirements become effective in 2011.
> Beginning in 2011 at Tier 4, emergency stationary diesel generators will not have to advance to standards that require aftertreatment.
U.S. EPA emissions regulations for on-site power generation
Proposed regulations for spark-ignited gasengines
On June 12, 2006, the EPA proposed new rules toregulate emissions from stationary spark-ignited gasengines. The fi rst regulation will become effectiveJuly 1, 2007, when emissions levels for stationarynon-emergency engines (typically used in peaking and landfi ll gas) and engines below 25 hp will be regulated. Spark-ignited gas engines above 25 hp used in stationary emergency applications will require EPA certifi cation effective January 1, 2009.
Cummins Power Generation intends to offer EPA-certifi ed gas products to meet the EPA stationaryemergency requirements for spark-ignited gas. Please consult your Cummins Power Generation dealer or visit www.cumminspower.com for a list of our EPA-compliant gas generator sets.
Award-winning diesel technology
Frost & Sullivan named Cummins Power Generation the recipient of the 2006 North American Diesel Engine Technology Leadership of the Year Award. The award recognizes Cummins Power Generation’s advancements and market leadership in emissions technology.
Our energy working for you.™
www.cumminspower.com
Cummins Power Generation1400 73rd Avenue N.E.Minneapolis, MN 55432Phone: 763 574 5000Fax: 763 574 5298
Our energy working for you.™
www.cumminspower.com© 2006 | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” and PowerCommand are trademarks of Cummins Power Generation. F-1689 (11/06) CPG473
Cummins Power Generation Tier-certifi edproducts by application
Cummins Power Generation offers a full rangeof diesel generator sets that meet or exceed
EPA requirements. Below are the U.S. EPA Tierlevels for stationary and nonroad applications andcorresponding Cummins Power Generation Tier-certifi ed models:
Stationary* NonroadStationary and
NonroadStationary and
NonroadStationary and
Nonroad
kWe 2006 2006 2007 2008 200915 / 20 / 25 DK Series DK Series DK Series DSBAB, DSCAA, DSCAB DSBAB, DSCAA, DSCAB
30 DSCAC DSCAC
35 DGGD, DGBB** DGBB** DGBB**, DGGD** DSDAA DSDAA
40 DGHD, DGBC** DGBC** DGBC**, DGHD** DSDAB DSDAB
50 DGHE, DGCA** DGCA** DGCA**, DGHE** DSDAC DSDAC
60 DGCB** DGCB** DGCB** DSFAA DSFAA
80 DGCG, DGDA DGDA DSFAE DSFAE DSFAE
100 DGDB DGDB DSHAF, DSGAA DSGAA DSGAA
125 DGDK, DSGAB DSHAE DSHAE, DSGAB DSGAB DSGAB
150 DGFA, DSHAA DSHAA DSHAA, DSGAC DSGAC DSGAC
175 DGFB, DSHAB DSHAB DSHAB DSHAB DSHAB
200 DGFC, DSHAC DSHAC DSHAC DSHAC DSHAC
230 DGFS, DSHAD DSHAD DSHAD DSHAD DSHAD
250 DQDAA DQDAA*** DQDAA*** DQDAA*** DQDAA***
275 DQDAB DQHAA DQHAA DQHAA DQHAA
300 DQDAC DQHAB DQHAB DQHAB DQHAB
350 DFEG DFEG DFEG DFEG DFEG
400 DFEH DFEH DFEH DFEH DFEH
450 DFEJ DFEJ DFEJ DFEJ DFEJ
500 DFEK DFEK DFEK DFEK DFEK
600 DFHA, DQCA, DQMAA DQMAA, DQCA DQMAA, DQCA DQMAA, DQCA DQMAA, DQCA
750 DFHA, DQCB, DQFAA DQFAA, DQCB DQFAA, DQCB DQFAA, DQCB DQFAA, DQCB
800 DFHB, DQCC, DQFAB DQFAB, DQCC DQFAB, DQCC DQFAB, DQCC DQFAB, DQCC
900 DFHD, DQFAC DQFAC DQFAC DQFAC DQFAC
1000 DFHD, DQFAD DQFAD DQFAD DQFAD DQFAD
1250 DFLE, DQGAA DQGAA DQGAA DQGAA DQGAA
1500 DFLE, DQGAB DQGAB DQGAB DQGAB DQGAB
1750 DQKB, DQKAA DQKAA DQKAA DQKAA DQKAA
2000 DQKC, DQKAB DQKAB DQKAB DQKAB DQKAB
2250* DQKH DQKH DQKH DQKH DQKH
2500* DQLC DQLC DQLC DQLC
* Tier 1 or greater required for stationary from 4/1/2006.** Tier 1 and Tier 2 models available.*** Tier 1 and Tier 3 models available.
Note: Our interpretation of the NSPS as it applies to stationary diesel generators is believed to be accurate. However, do not rely solely on this document for compliance information.
Cummins Power Generation Tier-certifi ed diesel generator sets
Tier 2
Tier 3
Tier 4
Tier 1Stationary only (cannot use for nonroad)
EPA Certifi cation Levels:
“As a recognized industry leader, Cummins Power Generation hasbeen working closely with the EPA and supports their efforts tostrengthen emissions regulations for nonroad and stationary dieselengines. Cummins Pow er Generation was the fi rst manufacturer tooffer EPA-certifi ed Tier 3 generator sets.
“Cummins Power Generation’s design strategy for meetingnew emissions standards has been to focus on our existingelectronic-controlled engine platforms and new in-cylinder design
enhancements. We believe this has been the best approach tohigher performance, better fuel effi ciency and high reliability thandesigns that rely on costly exhaust aftertreatments. This designstrategy has helped us become one of the few manufacturers whocan offer the marketplace a full line of EPA-certifi ed products.”
Tom LinebargerPresident, Cummins Power Generation
SD SERIES - SPECIFICATION DATA SHEET 1.1
Kirk Key Interlock Company211 Wetmore Ave. S.E., Massillon, OH 44646
Phone: 330.833.8223 • Fax: 330.833.1528 • Toll Free: 800.438.2442Email: [email protected]
www.kirkkey.com Type F - Flat Mounted
The Type F interlock is generally flat or face mounted with bolts through the front of the housing. The body of thelock is brass and the locking bolt is made of 5/8” diameter stainless steel. The throw, or travel, of the locking bolt is3/4".
OPTIONS• Locking Bolt Length - when ordering, specify the length of the locking bolt in the withdrawn position. Standardlengths are 1/4", 3/8", 1/2", 3/4”, 1", 2", and 3". Non-standard lengths are also available. (1” Lock Bolt shown ondrawing)
• Key Removable - the key(s) is removable when the locking bolt is either in the extended (E) or withdrawn (W)position. Please choose E or W when ordering an interlock. Key removable extended is the most common becausethe locking bolt is typically extended to block/engage something.
• Multi-Cylinder - up to 15 cylinders available. Housings with 5 cylinders or more come with mounting holes at eachend of the housing. Designate "E" or "W" key removable position for each cylinder.
• Stamp Key Interchange - specify an alphanumeric code to be stamped on the cylinder face and the key (e.g. A1,A2, B1, etc. - up to 5 characters). See SD Series Data Sheet for Keys (3.4) and Terminology (4.1) for details.
• Auxiliary Switches - see SD Series Data Sheets for Type Thermoplastic (2.3), Type S (2.4) and Type K (2.5) fordetails.
• Dust Covers - see SD Series Data Sheet for Dust Covers (3.1) for details.
• Mounting Bolts - see SD Series Data Sheet for Mounting Bolts (3.2) for details.
• "Opposite Hand" - see SD Series Data Sheet for Terminology (4.1) for details.
SD SERIES - SPECIFICATION DATA SHEET 1.1
Kirk Key Interlock Company211 Wetmore Ave. S.E., Massillon, OH 44646
Phone: 330.833.8223 • Fax: 330.833.1528 • Toll Free: 800.438.2442Email: [email protected]
www.kirkkey.com Type F - Flat Mounted
NOTES:1) 0.4062” (10.32mm) holes for mounting bolts (2 holes).2) Mounting holes for locks with 5 or more cylinders. Type F interlocks with five or more cylinders will havemounting holes at each end of the interlock. The rear mounting holes are 7/8” (22.23mm) from the end. The totallength of the five cylinder Type F interlock is 9 1/2” (24.13cm) . Add 1 1/2” (38.1mm) for every additional cylinder.
80TG3 S u r g e P r O T e C T I O N
TransGuard®
kA Rating (Must Choose One)Available TG3TM kA Ratings: 050, 080, 100, 125, 150, 200,
250, 300
Voltage* (Must Choose One)208 120/208240 120/240380 220/380480 277/480600 347/600
Configuration* (Must Choose One)1G 1-Phase, Grounded2G 2-Phase, Grounded, Split-Phase3Y 3-Phase, Grounded, Wye3R 3-Phase, Grounded, High-Resistance3H 3-Phase, Grounded, High-Leg Delta3D 3-Phase, Grounded, Delta
Enclosure (Must Choose One)MN Metal Without DisconnectMD Metal With DisconnectSN Stainless Steel Without DisconnectSD Stainless Steel With DisconnectPN Fiberglass Reinforced Polyester
Without Disconnect
Cable Entry (Must Choose One)T Top FeedB Bottom Feed
Monitoring (Must Choose One)M0 No local monitoring
(see remote MxX stand-alone option)M1 LED/Phase + Audible Alarm,
Dry Relay ContactsM2 M1 + Surge CounterM3 Advanced Monitoring,
Character Display, Modbus RTUM4E M3 + Ethernet, Modbus TCPM5 Advanced Monitoring,
Graphics Display, Modbus RTUM6E M5 + Ethernet, Modbus TCP
Filter (Must Choose One)F FilterN No Filter
Optional Feature (May Choose One)2 Test Port
Stand-Alone Options (To Be Ordered As Separate Items)DTS DTS-2 Diagnostic Test SetMxX Remote Monitor Extension
M1X through M6EXHPI HPI Cable
T G 3 — 0 8 0 — 2 0 8 — 3 Y — P N T — M 6 E — F 2
Mod
el
kA R
atin
g
Volta
ge
Conf
igur
atio
n
Cabl
e En
try
Mon
itorin
g
Filte
r Op
tion
Optio
nal F
eatu
re
Encl
osur
e
E.g.: TG3-080-208-3Y-PNT-M6E-F2 (as shown in above photo)
Model NuMber ScheMe (TG3TM)
*See table on back for more Voltage/Configuration Options.
TM
TransGuard® TG3TM suppression filter systems feature a powerful failure-free ISMTM (Integrated Suppression Module). The ISMTM contains individual thermally fused and protected MOVs, surge-rated copper busing, robust filtering and advanced remote communications capabilities. The TG3TM protects today’s facilities from costly downtime and equipment damage caused by routine or catastrophic electrical disturbances.
ProducT SPecificaTioNS
General SpecificationsMaximum Surge Current Rating 80kA Per Mode, 160kA Per PhaseNominal Discharge Surge Current I-n = 20kASafety Listings Listed by UL to UL 1449 3rd Edition
(2009 Revision) for Type 1 and Type 2 SPD applications, cUL, and UL 1283 / Meets Requirements for UL 96A / Compliant to IEEE C62.41.1-2002, C62.41.2-2002 and C62.45-2002 / NFPA 70 [NEC], Article 285 / RoHS Compliant / CE, IEC 61643-11-2011 / FCC Part B Class B / EMC Directive 2004/108/EC / Low Voltage Directive 2006/95/EC
Protection Method Thermally protected MOVs, Capacitive FilterProduct Design Individual thermally fused and protected MOVs,
and All Copper, Tin-plated BusDimensions Metal/Stainless Steel: 16”H x 16”W x 9.2”D Fiberglass Reinforced Polyester: 14"H x 12.75"W x 6.6"DWeight. Metal/Stainless Steel: 40 lbs. Fiberglass Reinforced Polyester: 17 lbsEnclosure Type NEMA 4/12 Standard (NEMA 4X Option)Installation Location Outdoor or IndoorOperating Environment -25°C to +60°C
5% – 95% Non-Condensing HumidityFault Current (SCCR) 200kAICConnection Method ParallelProtection Modes All Modes (L-N, L-G, N-G, L-L)Response Time < 0.5 NanosecondsOperating Frequency 47 – 63 HzWarranty 15 Years
Filtering Attenuation Frequencies (Per Mil-Std-220B January 2000)** 10 KHz 100 KHz 1 MHz 10 MHz Max at 142 KHz 18.1 dB 44 dB 22.8 dB 15.3 dB 54.6 dB
Single/Repetitive Surge Current Capacities (Tested)**Protection Mode Single Pulse Surge Repetitive Surge Current Capacity/Mode Current Capacity/ModeLine-to-Neutral 80,000A 6,000 ImpulsesLine-to-Ground 80,000A 6,000 ImpulsesNeutral-to-Ground 80,000A 6,000 ImpulsesLine-to-Line 160,000A 12,000 ImpulsesPer Phase 160,000A 12,000 Impulses
Maximum Continuous Operating Voltage (MCOV)Voltage L-N MCOV Voltage L-L MCOV120V 150V 240V 300V277V 320V 480V 552V347V 420V 600V 690V
** Data based on actual tests. Contact factory for test reports
System Voltage120/240V
or 120/208V
277/480V 347/600V 480V Delta
Protection Mode L-N L-G N-G L-L L-N L-G N-G L-L L-N L-G N-G L-L L-G L-L
MCOV 150 150 150 300 320 320 320 552 420 420 420 690 552 552
B3 Ring Wave 6kV, 500A 490 570 640 500 450 540 570 530 490 520 600 550 1450 530
B3/C1 Combo Wave 6kV, 3kA 614 629 634 1011 1013 1031 950 1857 1197 1219 1175 2369 1542 1857
C3 Combo Wave 20kV, 10kA 980 980 1170 1600 1420 1540 1600 2600 1670 1670 1730 2980 2270 2600
UL 1449 3rd Edition VPR 6kV, 3kA 700 700 700 1200 1200 1200 1000 2000 1200 1500 1200 2500 1800 2000
060314
Metal/Stainless Steel TG3TM/80 Inches (mm)H1 16.00 (406.4)H2 17.25 (438.2)H3 18.50 (469.9)W1 16.00 (406.4)W2 10.00 (254.0)D 9.20 (233.7)
Fiberglass Reinforced Polyester TG3TM/80 Inches (mm)H1 14.00 (355.6)H2 14.75 (374.7)H3 15.50 (393.7)W1 12.75 (323.9)W2 10.00 (254.0)D 6.60 (167.6)
TG3 TM/80 PerforMaNce daTa
All TG3 TM systems voltage protection ratings (VPR) are peak values (±10%) measured from the 90° reference point and are in compliance with test and evaluation procedures outlined in ANSI/IEEE C62.41
diMeNSioNal SPecificaTioNS VolTaGe/coNfiGuraTioN oPTioNS
1-Ph
ase,
Gro
unde
d
2-Ph
ase,
Gro
unde
d, S
plit-
Phas
e
3-Ph
ase,
Gro
unde
d, W
ye
3-Ph
ase,
Gro
unde
d, H
igh-
Resis
tanc
e
3-Ph
ase,
Gro
unde
d, H
igh-
Leg
Delta
3-Ph
ase,
Gro
unde
d, D
elta
1G 2G 3Y 3R 3H 3D
Voltage Configuration
120 X
208 X X X X
220 X X X X
230 X X
240 X X X X
380 X X X X
415 X X X X
480 X X X X
600 X X X X
Not all voltage configurations are displayed, contact Thomas & Betts Power Solutions for additional configurations.
(W1)
(W2)
(H1)(H2)
(H3)
(D)
ø 0.38
(H3)(H2)
(W1)(W2)
(D)
(H1)
ø 0.38
(W1)(W2)
(H3)(H2)
(H1)
(D)
ø 0.38
© 2014, Thomas & Betts Power Solutions, LLC. • Thomas & Betts Power Solutions, LLC., is a wholly owned subsidiary of Thomas & Betts Corporation. Current Technology® and TransGuard® are registered trademarks of Thomas & Betts International, Inc. • Specifications are subject to change without notice. • Visit our website for latest revisions.
Thomas & Betts Power Solutions5900 Eastport Blvd. • Richmond, VA 23231-4453 USA
Tel: (804) 236-3300 • Toll free: (800) 238-5000 • Fax: (804) 236-4841tnbpowersolutions.com/current_technology
Ge
ne
ra
to
r
Do
CK
InG
Sta
tIo
nS
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
3507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com
TRYSTAR® PORTAbLE POwER CAbLECam to cam cable extensions
Striped Cable Distribution equipment Cable with integrity
DESCRIPTION
• 2000V, 100A-400A rated to NEC table 400.5 (B)
• All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
• MSHA Listed
• Dual layer jacket with inner safety liner of contrasting color
• Available in any color, including 208V & 480V phases
• Your custom print on every foot of the cable
• All cables are factory tested
Trystar® Generator Docking Stations provide reliable, affordable
assurance that your business stays up and running in any power outage.
Custom-mounted to your structure, each station allows for quick
and easy connection of external generator power. And our unique
design helps prevent theft and hazardous disconnects.
• Up To 4000A
• THEfT AND TAMpER RESiSTANT
• CAM Lok READY
• CUSToM CABLiNG AND powDER CoATiNG
• BREAkER pANELS AND MoRE
TRYSTAR® gENERATOR DOCKINg STATIONS
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER. CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
4507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com 5507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com
Compression lug pin lug Bare end
TRYSTAR® PORTAbLE POwER CAbLE pig tails, male or female, any length
DESCRIPTION
• 2000V, 100A-400A rated to NEC table 400.5 (B)
• All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
• MSHA Listed
• Dual layer jacket with inner safety liner of contrasting color
• Available in any color, including 208V & 480V phases
• Cam style to bare end with pin lugs or compression lugs available
gDS-044w-SM(pictured)
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
pad lockableDocking station 400A phase colored cable
TRYSTAR® COMMERCIAL gRADE gENERATOR DOCKINg STATION
DESCRIPTION
• Available for 100A to 400A service
• powder coated aluminum or stainless steel construction
• Lockable rake system reduces cable theft
• Non-angled vertical Cam style inputs
• UL and C-UL 50 listed enclosure, NEMA 3R
• options are not available with this unit
• provides safe and easy cam connections to existing transfer switches
• for use in residential and light duty environments
• Your custom print on every foot of the cable
• All cables are factory tested
2917 Industrial DriveFaribault, Minnesota 55021
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
6507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com 7507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
Part #gDS-205w-LM(pictured)
optional leg kit 1200A output panel 400A docking station
TRYSTAR® gENERATOR DOCKINg STATIONUp To 4000A
DESCRIPTION
• Available for 100A to 4000A service
• powder coated aluminum or stainless steel construction
• Docking stations accommodate any style inlet or receptacle
• Lockable rake system reduces cable theft & cable disconnection
• Cam style inputs and/or outputs or other
• UL and C-UL 50 listed enclosure, NEMA 3R
• provides safe and easy cam connections to transfer switches
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
TRYSTAR® gENERATOR DOCKINg STATION wITh LOCKINg bLOCK Up to 4000A
4000A Closed 400A Closed 400A open with rake system
Part #gDS-405w-LM-K2(pictured lower left)
Part #gDS-045w-SM-K1(pictured center and lower right)
DESCRIPTION
• Available for 100A to 4000A service
• patented locking block incorporated into a standard Trystar GDS
• kirk key can be installed into a facility’s new or existing main breaker
• only the provided key will open Trystar’s GDS with locking block
• The key is captive and is only released by disconnecting the main breaker
• key releases only when doors of GDS are closed and locked
• Both doors will close only if the cable is not connected to the GDS
• The facility’s main breaker is used to lock out and transfer power from utility to generator
• UL and C-UL 50 listed enclosure, NEMA 3R
8507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com 9507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
Part #gDR-125w-LM(pictured)
TRYSTAR® ROTARY gENERATOR DOCKINg STATIONUp to 1200A
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
Part #gDS-POSITRYSTAR® POSI-LOK gENERATOR DOCKINg STATION
DESCRIPTION
• integrated rotary transfer switch (oN - off - oN)
• Available for 100A to 1200A service
• powder coated aluminum or stainless steel construction
• Available with non-service entrance or service entrance rating
• Lockable rake system reduces cable theft & cable disconnection
• Cam style inputs and/or outputs
• inside mount handle for added security
• UL and C-UL 50 listed enclosure, NEMA 3R
DESCRIPTION
• powder coated aluminum or stainless steel construction
• Mounts to switches, buildings and generators
• posi-Lok® is designed for sequential, fool-proof hook up
• Lockable rake system reduces cable theft & cable disconnection
• UL and C-UL 50 listed enclosure, NEMA 3R
portable option Utility - off - Generator switch pad lockable Lockable posi-Loks connectedposi-Lok cable
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
10507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com 11507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
Part #gDS-326P-LL(pictured)
phase colored cableSecondary door closed Hard wire connection
TRYSTAR® hARD-wIRE DOCKINg STATIONGenerator Roll-Up Box
DESCRIPTION
• includes mechanical lugs suitable for up to 500MCM THHN cable
• Trap door access for easy hard wire connection
• Secondary door offers additional protection between generator and electrical load
• UL and C-UL 50 listed enclosure, NEMA 3R
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
TRYSTAR® RENTAL TRANSfER SwITChES wITh bUILT IN DOCKINg STATIONS
integral docking station Two full door access fully wired
DESCRIPTION
• optional stainless steel or powder coated aluminum
• Double throw, manual (non-automatic) or automatic
• Docking Station integral to the switch
• Heavy duty reinforced frame with 2 door support & access
• Add gland plates for any inlet or receptacle
• Non service and service entrance rated
• UL and C-UL 50 Listed enclosure
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
12507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com 13507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
Part #DbDS(pictured)
TRYSTAR® DUAL KIRK KEY bREAKER DOCKINg STATIONS
DESCRIPTION
• Standby power breaker cannot be energized unless the utility breaker is locked in the off position
• Breaker A is for loadbanking a permanent generator
• Breaker B is for a temporary generator
• Ability to have a temporary generator connected during a load bank test
• Allows for quick, easy hook up of a portable generator if permanent generator goes down
• Up to 4000A per breaker
• phase rotation monitor included
• full CAD drawings available upon request
• Cam style connection or hard wire option available for input
• UL and C-UL 50 listed enclosure, NEMA 3R
Closed view open view
Part #SbDS(pictured)
TRYSTAR® SINgLE OR DUAL bREAKER DOCKINg STATIONS
DESCRIPTION
• Single breaker docking station with kirk key provision
• kirk key is provided for main breaker on building
• The key is captive in the building’s main breaker until it is shut off
• when the main breaker is off, use the same key to turn on the GDS breaker
• The key is captive in the GDS breaker until it is shut off
• Up to 4000A
• kirk-key adaptable
• phase rotation monitor included
• full CAD drawings available upon request
• Cam style connection or hard wire option available for input
• UL and C-UL 50 listed enclosure, NEMA 3R
Closed view open view
2917 Industrial DriveFaribault, Minnesota 55021
2917 Industrial DriveFaribault, Minnesota 55021
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER. CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
PRODUCT NAME
14507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com 15507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com
Part #UOPTRYSTAR® UTILITY bREAKERED OUTPUT PANELPart #DPgLbDSTRYSTAR® DUAL PURPOSE gENERATOR/LOAD bANK DOCKINg STATION
open view open viewClosed viewClosed view
DESCRIPTION
• Quick and easier access to permanent generator for load banking
• kirk key access to lock out permanent generator, giving access for roll up rental generator
• Does not include any breakers
• Cam style or hard-wire inputs and/or outputs
• phase rotation monitor included
• Up to 4000A
• UL 50 and C(UL) 50 Listed enclosure, NEMA 3R
DESCRIPTION
• Available for 100A to 4000A service
• powder coated aluminum or stainless steel construction
• output panels accommodate any style outlet
• Breakers included to match specification
• Cam style or hard-wire outputs, or other
• Lockable rake system reduces cable theft and cable disconnection
• UL 50 and C(UL) 50 Listed enclosure, NEMA 3R
16507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com 17507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
Part #gDS-MgTRYSTAR® DOCKINg STATION fOR MObILE gENERATORS
Closed view Back view
DESCRIPTION
• Single or dual kirk key systems
• inserts into a mobile generator which provides flexibility for long or short-term projects
• Breaker A is generator’s main, breaker B is the building’s main
• phase rotation monitor included
• Up to 4000A per breaker
• full CAD drawings available upon request
• Cam style connection or hard wire option available for input
• UL and C-UL 50 listed enclosure, NEMA 3R
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
inside wiring of an ATS
Docking station
TRYSTAR® gENERATOR DOCKINg STATIONS MOUNTED TO ATS
inside wiring of an ATS
18507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com 19507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
Mounted to transfer switch Three phase 208V with pigtails Shown with lockable cover
TRYSTAR® INLET gENERATOR CONNECTION PANEL100A to 400A
DESCRIPTION
• powder coated aluminum or stainless steel construction
• Converts a panel from a mechanical lug connection to a quick connect panel
• Mounts to switches, buildings and/or generators
• Complete with 30” tails sized to your requirement
• option for lockable front cover
• UL and C-UL 50 listed enclosure, NEMA 3R
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
Part #TSSV
plastic collapsible bins plastic non collapsible bins
TRYSTAR® POwERTrystar Steel Storage Vault
DESCRIPTION
• Lockable
• Capable of holding up to 3000 lbs.
• Nearly impenetrable
• Custom colors available
CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER. CALL 1-866-TRYSTAR (879-7827) TO PLACE YOUR ORDER.
20507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com 21507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com
TEMpERATURE CoRRECTioN fACToRS **
Ambient Temp °C
fACToR Ambient Temp °f
Number ofConductors
TemperatureAdjustment
21-25 1.04 70-77 4-6 80%
26-30 1.00 78-86 7-9 70%
31-35 0.96 87-95 10-20 50%
36-40 0.91 96-104 21-30 45%
41-45 0.87 105-113 41-40 40%
46-50 0.82 114-122 41+ 35%
51-55 0.76 123-131D RATiNG foR CoNDUiT oR TRAY AppLiCATioN56-60 0.71 132-140
61-70 0.58 141-158
71-80 0.41 159-176 28%
Adjustment factor for more than three current carrying conductors
* for ambient temperatures other than 30 C (86 f) multiply the allowable ampacities stated above by the appropriate conversion factor.
** indented into sheath: (UL) TYpE ppE 90°C DRY 75°C wET SUN RES 2000V E204219 p-07-kA070022-MSHA AwG 4/0 C(UL) ppC/TpE fT5 90°C SUN RES 600V
*** Values Listed are for single conductors, where the individual conductor is not installed in raceways or physical contact with each other except in the lengths not exceeding 24.0 inches.
Size Stranding Strand Nominal oD
finished Nominal oD
weight lbs. / MfT
Ampacity*
8 168 x 30 0.150 0.485 162 80
6 266 x 30 0.192 0.525 197 105
4 420 x 30 0.252 0.582 204 125
2 665 x 30 0.320 0.650 315 190
1 833 x 30 0.354 0.725 376 220
1/0 1064 x 30 0.397 0.775 480 260
2/0 1330 x 30 0.450 0.820 603 300
3/0 1691 x 30 0.510 0.880 716 350
4/0 2109 x 30 0.580 0.965 895 405
AVAILAbLE SIZES, SPECIfICATIONS & AMPACITY CORRECTION fACTORS
fEATURES
• Available colors: Black, blue, red, green, white, yellow, orange, brown or custom
• - 45°C to 105°C, 2000 Volt Rating, flame retardant
• Resistant to oil, water, acid, gas, ozone, cuts, tears and abrasion
• (UL) 2000 volt rating, C(UL) 600 volts continuous use
• Manufactured to UL & C(UL) standard 1650, & MSHA
• Surpasses NEC 400 requirements and may be used in any application where ppE, Type w, G or G-GC cable is used.
APPLICATIONS
Designed for use with industrial equipment, including portable generators, chillers, air conditioning, motor and welding leads, submersible wells, grounding, heavy tools, power extensions, marine dockside, mining and oil drilling applications, where long term, quality performance at all operating temperatures is desired.
CONSTRUCTION
Conductor• Bare, annealed electrolytic copper• 30 AwG Class k rope lay stranding
DUAL INSULATED JACKETINg TEChNOLOgY
inner Jacket- Added for Your SafetyA separator of high contrast color is applied between the conductor and outer sheath for your added safety.This provides: increased insulation, added flexibility, and allows you to easily identify damage or wear.
outer JacketTYpE ppE (fT5) provides: oil, water, acid, gas, ozone, resistance, flame retardant, durability and extreme flexibility at all operating temperatures.
indented into outer jacket: (UL) TYpE ppE 90°C DRY 75°C
wET SUN RES 2000V E204219 p-07-kA070022-MSHA AwG
4/0 C(UL) ppC/TpE fT5 90°C SUN RES 600V
TRYSTAR® PORTAbLE POwER CAbLE (UL) C(UL)AVAILAbLE IN: CUSTOM COLOR, ANY LENgTh, CUT, COILED, COMPLETE wITh CONNECTOR ASSEMbLY
TRYSTAR® gENERATOR DOCKINg STATION SPECIfICATION
AMPERAgE VOLTAgE MOUNT STYLE PERMANENT bUS CONNECTION
02 - 200A 1 - 120/240 (2H + N + G) w - wall hanging L - Mechanical Lugs (std)
04 - 400A 3 - 208/120V (3H + N + G) p - pad (free standing) Qty and size per phase
08 - 800A 4 - 480V (3H + G) f - flush (front flange) 200 - 400A — 2 x 600 MCM
12 - 1200A 5 - 480/277 (3H + N + G) 800A — 3 x 500 MCM
16 - 1600A 6 - 600V (3H + N + G) 1200A — 4 x 500 MCMSample Construction:
1600A, 208/120V, wall Mount S
Mechanical Lug permanent busbar connection
Male cam style receptacle generator connection
phase Rotation Monitor, 2x Duplex GfCi, Generator Signal Terminal Block
gDS-163w-LM-AC2h
20 - 2000A 1600A — 6 x 500 MCM
24 - 2400A 2000A — 8 x 500 MCM
28 - 2800AVoltage Colors for Cam Style Receptacles
1 - Black, Red, white & Green3 - Black, Red, Blue, white and Green4 - Brown, orange, Yellow and Green5 - Brown, orange, Yellow, white and Green6 - Black, Black, Black, white and Green
2400A — 10 x 500 MCM
32 - 3200A 3200A — 14 x 500 MCM
40 - 4000A 4000A — 16 x 500 MCM
C - Long Barrel Compression
S - 1/2” x 13 Threaded Stud (400A and below)
o - other (Specify)
gENERATOR CONNECTION (OPTIONAL LOADbANK CONNECTION) (OThER OPTIONS - LIST ALL AfTER DASh)
M - Male Cam Style Receptacles (std) Lf - female Cam Style Receptacles A - phase rotation monitor
L - Mechanical Lugs LL - Mechanical Lug B - 1Ø 120V 20A Duplex outlet
o - other (Specify) C - 1Ø 120V 20A Duplex GfCi outlet
D - 1Ø 120V 30A NEMA L5‐30 outlet
E - 1Ø 120V 50A Twist‐Lock outlet
f - 1Ø 125/250V 50A Twist‐Lock outlet (Add number after letter if requesting more than one)
H - Generator Signal Terminal wiring Block
i - Stainless Steel construction
J - Bottom conduit access (increased panel depth - contact factory for details)
k# - kirk‐key door interlock (# - number of key cylinders)
L - Custom lug size or compression type
p - Custom powder coat color (Specify - ANSi grey standard)
S - Special (explain)
NOTES:
for 400-800A choose up to 2 from B-E
for 1200-4000A choose up to 3 from B-E
Make selections from the listed options.
ExAMpLE SHowN: gDS-325P-LM(-LfA)
gDS AMPERAgE VOLTAgE MOUNT STYLE PERMANENT bUS CONNECTION
gENERATOR CONNECTION ( - (OPTIONAL LOADbANK
CONNECTION)(OThER OPTIONS -
LIST ALL AfTER DASh) )
gDS - 32 5 P - L M ( - Lf A )
2917 Industrial DriveFaribault, Minnesota 5502122507.333.3990 • 866.TRYSTAR • fax 507.334.1683 • trystar.com
NOTESMANUfACTURINg
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________