summary of revision, ieee c37.119-2016, guide for breaker...
TRANSCRIPT
![Page 1: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/1.jpg)
Summary of Revision, IEEE C37.119-2016, Guide for
Breaker Failure Protection of Power Circuit Breakers
Kevin Donahoe – GE Grid Solutions
2018 Texas A&M Protective Relaying Conference
![Page 2: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/2.jpg)
• Introduction
• Breaker Failure Minimal Current Scheme
• Current Differential Breaker Failure Protection
• Column Ground Protection
• Breaker Failure Protection for Generator Applications
• Redundant Control Circuits
• Conclusions
• Questions
Agenda
![Page 3: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/3.jpg)
Introduction • Replaced C37.119-2005 • PSRC Working Group followed up with the paper “Summary
of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection of Power Circuit Breakers
• Definition of breaker failure protection (BFP) • 2005: This protection is specifically relied upon to take
appropriate action to clear a fault when the breaker that is normally expected to clear the fault fails to do so for any reason.
• 2016: A form of protection that is designed to detect the failure of a circuit breaker to operate or to interrupt a fault. Upon detection of a breaker failure during a fault condition the scheme is designed to take appropriate action to clear the fault. Upon detection of a breaker failure during a non-fault condition, the scheme may take other appropriate action.
![Page 4: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/4.jpg)
Introduction
• Covered in C37.102, IEEE Guide for AC Generator Protection • BFP can fall in overlap between generation and transmission • Added clause increase familiarity with the unique
requirements for generator BFP • IEEE-Standards Association asked to expand the scope of
the C37-119 • Now includes performance failures of breakers other than
fault clearing failures • Failure to close during synchronizing is now covered
![Page 5: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/5.jpg)
BF Minimal Current Scheme
• Breaker failure applications associated with high-impedance power system apparatus, such as generators, transformers, static var compensators (SVC), and harmonic filters, may have such low currents associated with internal faults that current detectors are not reliable.
• BF logic can also be achieved using breaker auxiliary switches
![Page 6: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/6.jpg)
BF Minimal Current Scheme
Considerations
![Page 7: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/7.jpg)
BF Minimal Current Scheme
![Page 8: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/8.jpg)
BF Minimal Current Scheme
![Page 9: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/9.jpg)
BF Minimal Current Scheme
• False BFI – one cause, accidental battery ground • Measures to reduce possibility of false BFI
• BFI input that responds only above half of the maximum battery voltage
• Binary inputs are compliant with IEC 60255-26, Measuring relays and protection equipment – Electromagnetic compatibility requirements with specific reference to Clause 7.2.7, Power frequency immunity on DC binary inputs
• Minimize cable run length and capacitance • Data communication-based means for conveying the BFI
between buildings
![Page 10: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/10.jpg)
Current Differential BFP
• Accurate fault diagnosis • Extra installation and maintenance cost • Logical condition of adjacent operation of protection zones
![Page 11: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/11.jpg)
Column Ground Protection
• CT column changes BFP
• No overlap • Most likely:
column to ground flashover
• CTs around the base of each column
• Direct trip of 86 • IEEE Std.
C37.234: Buses
![Page 12: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/12.jpg)
BFP for Generator Applications
• Mechanical Indication of Breaker Status • CT Locations • Open Generator Breaker Flashover Protection • Breaker Arrangement: High-Side Breakers • Breaker Arrangement: Low-Side Breaker • Generator Breaker Failure to Close Protection
![Page 13: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/13.jpg)
Mechanical Indication of Breaker Status
• Consider, in a motoring event, failure to separate from the power system can damage the prime mover
• A steam turbine has a typical motoring power range .5-3% • CTs sized for 5A at generator rating – current in milliamps • CTs on dual breakers, CTR may be based on bus rating • Current measurement is not reliable for all conditions
requiring BFP
![Page 14: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/14.jpg)
CT Locations
• Even after the breakers open, the generator will feed a in-zone fault until stored energy in the field dissapates
• Never use generator neutral CTs • For low-side breaker location, not appropriate to use
generator terminals • CTs that measure the current flowing directly into the
breaker
![Page 15: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/15.jpg)
Open Generator Breaker Flashover Protection
• Flashover most likely to occur just prior to synchronizing or just after the generator separates
![Page 16: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/16.jpg)
Open Generator Breaker Flashover Protection
![Page 17: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/17.jpg)
Breaker Arrangement: High-Side Breakers
![Page 18: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/18.jpg)
Breaker Arrangement: High-Side Breakers
![Page 19: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/19.jpg)
Breaker Arrangement: High-Side Breakers
![Page 20: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/20.jpg)
Breaker Arrangement: Low-Side Breaker
• For Faults • Trip the generator CB G • Open the generator field breaker • Isolate the energy source that drives the prime mover
![Page 21: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/21.jpg)
Generator BF to Close Protection
• Synchronizing systems minimize: • Speed difference or slip rate • Voltage difference • Angle difference
• Main contacts make at the instant when the angle difference is as near to zero as possible
• If breaker mechanism is slow then the generator rotor angle will pass zero and start increasing
• BFP could isolate the synchronizing breaker so that the generator closes into a dead bus
![Page 22: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/22.jpg)
Generator BF to Close Protection
![Page 23: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/23.jpg)
BFP on Redundant Control Circuits
![Page 24: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/24.jpg)
Conclusions
• “Summary of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection of Power Circuit Breakers” is available at http://www.pes-psrc.org/kb/published/reports/Paper_SummaryofRevC37-119.pdf
• Go to pes-psrc.org • Go to Knowledge Base • Go to Reports • D subcommittee or search for 119
![Page 25: Summary of Revision, IEEE C37.119-2016, Guide for Breaker ...prorelay.tamu.edu/wp-content/uploads/sites/3/2018/... · of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection](https://reader035.vdocument.in/reader035/viewer/2022062417/6125d3e59fbba970c53e5430/html5/thumbnails/25.jpg)
Thank You
Questions?