supergrid update epri superconductivity working group 3 april 2003 milwaukee, wi
DESCRIPTION
SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI. Paul M. Grant Science Fellow SS&T [email protected] Electric Power Research Institute Palo Alto, California USA. 1967 SC Cable !. 100 GW dc, 1000 km !. Garwin-Matisoo. - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/1.jpg)
SuperGrid Update (Milwaukee, 3 April 2003) .1
![Page 2: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/2.jpg)
SuperGrid Update (Milwaukee, 3 April 2003) .2
SuperGrid Update
EPRI Superconductivity Working Group3 April 2003
Milwaukee, WI
Paul M. GrantScience Fellow
SS&T
[email protected] Power Research Institute
Palo Alto, California USA
![Page 3: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/3.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .3
1967 SC Cable !
100 GW dc, 1000 km !
![Page 4: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/4.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .4
Garwin-Matisoo
Superconducting Lines for the Transmission of Large Amounts of Electric Power over Great Distances,R. L. Garwin and J. Matisoo, Proceedings of the IEEE 55, 538 (1967)
![Page 5: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/5.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .5
Garwin-Matisoo
• Nb3Sn Wire• TC = 9 K• LHe liquid-vapor
cooled• LN2 heat shield
![Page 6: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/6.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .6
Electricity Pipe
P.M. Grant, S. Schoenung, W. Hassenzahl, EPRI Report 8065-12, 1997
Initial EPRIstudy on longdistance (1000 km)HTSC dc cablecooled by liquidnitrogen -- 1997 --
![Page 7: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/7.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .7
P.M. Grant, The Industrial Physicist, Feb/March Issue, 2002
http://www.aip.org/tip/INPHFA/vol-8/iss-1/p22.pdf
SupermarketSchool Home
Family Car
DNA-to-order.com
Nuclearplant
H2
H2
MgB2
SuperCity
![Page 8: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/8.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .8
“Continential SuperGrid Workshop,” UIUC/Rockefeller U., Palo Alto, Nov. 2002
http://www.epri.com/journal/details.asp?doctype=features&id=511
SuperGrid
![Page 9: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/9.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .9
Chicago!
PowerPlants
SuperCitySuperGr
id
![Page 10: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/10.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .10
2 April 2003: abcNEWS.com
They are proposing something they call a SuperGrid.”
![Page 11: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/11.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .11
SuperCables
H2 H2
Circuit #1 +v I-v
I
H2 H2
Circuit #2
Multiple circuitscan be laid in single tunnel
+v-v
II
![Page 12: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/12.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .12
SuperCable
HV Insulation
“Super-Insulation”
DO
Hydrogen
DH2
Superconductor
tsc
![Page 13: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/13.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .14
Power Flows
PH2 = 2(QρvA)H2, where PH2 = Chemical power flow Q = Gibbs H2 oxidation energy (2.46 eV per mol H2)ρ = H2 Density v = H2 Flow Rate A = Cross-sectional area of H2 cryotube PSC = 2|V|IASC, where PSC = Electric power flowV = Voltage to neutral (ground)I = SupercurrentASC = Cross-sectional area of superconducting annulus
Hydrogen
Electricity
![Page 14: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/14.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .15
3183.8110500
“Equivalent” Current
Density (A/cm2)
H2 Flow Rate (m/sec)
Inner Pipe Diameter, DH2
(cm)
Power (MW)
Hydrogen (LH2, 20 K)
Electric & H2 Power
0.12525,000100,000+/- 50001000
Annular Wall
Thickness (cm)
Critical Current Density (A/cm2)
Current (A)Voltage (V)Power (MW)
Electricity
![Page 15: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/15.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .16
Thermal Losses
WR = 0.5εσ (T4amb – T
4SC), where
WR = Power radiated in as watts/unit areaσ = 5.67×10-12 W/cm2K4
Tamb = 300 KTSC = 20 Kε = 0.05 per inner and outer tube surfaceDSC = 10 cm WR = 3.6 W/m Superinsulation: WR
f = WR/(n-1), where n = number of layers Target: WR
f = 0.5 W/m requires ~10 layers Other addenda (convection, conduction): WA = 0.5 W/m WT = WR
f + WA = 1.0 W/m
RadiationLosses
![Page 16: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/16.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .17
Heat Removal
dT/dx = WT/(ρvCPA)H2, where dT/dx = Temp rise along cable, K/mWT = Thermal in-leak per unit Lengthρ = H2 Density v = H2 Flow RateCP = H2 Heat Capacity A = Cross-sectional area of H2 cryotube
Take WT = 1.0 W/m, then dT/dx = 1.8910-5 K/m, Or, 0.2 K over a 10 km distance
![Page 17: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/17.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .18
Remaining Issues
• Current stabilization via voltage control• Magnetic forces• Hydrogen gas cooling and transport• Pumping losses• Hydrogen storage• Costs !!
![Page 18: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/18.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .19
Hindenburg Hysteria
The Hindenburg did not crashBecause of a hydrogen leak!
![Page 19: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/19.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .20
Tunnels
Yamanashi MagLev Test Line
![Page 20: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/20.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .21
Tunnels for the SuperGrid
• Joint efforts with research groups, engineering firms, contractors, and machine manufactures to develop and demonstrate appropriate excavation and tunneling systems
• Link directional drilling, micro-tunneling and larger tunnel boring machine technologies
• Support demonstration projects using advanced technologies for driving tunnels (e.g., VLHC @ Fermilab)
What’s Needed:
![Page 21: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/21.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .22
Rock Group
![Page 22: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/22.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .23
Transformer Form Factors
Waukasha Transformer Sizes
Weight Width Length
300 MVA
lbs, in 500,000 80 200
tons, ft 250 6.67 16.67
30 MVA Conventional
lbs, in 96,000 108 108
tons, ft 48 9.00 9.00
30 MVA Superconducting
lbs, in 32,000 36 72
tons, ft 16 3 6
![Page 23: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/23.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .24
“Heavy Movers”
CalTrans/CHP
"18" Wheelers: 20,000 lbs/axle
= 80,000 lbs gross
= 40 tons
![Page 24: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/24.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .25
“Heavy Lifters”
Helicopters
Boeing Chinook CH-47F
Max Gross Weight: 50,000 lbs = 25 tons
Empty: 23,401 lbs = 11.70 tons
"Freight" 26,599 lbs = 13.30 tons
Planes
Lockheed C-5A Galaxy
4000 Mile Range: 250,000 lbs = 125 tons
8000 Mile Range: 125,000 lbs = 63 tons
![Page 25: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/25.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .26
A Moveable Substation
![Page 26: SuperGrid Update EPRI Superconductivity Working Group 3 April 2003 Milwaukee, WI](https://reader035.vdocument.in/reader035/viewer/2022081520/56814ae4550346895db7f54c/html5/thumbnails/26.jpg)
SuperGrid Update: PMG PDASWG Talk (Milwaukee, 3 April 2003) .27
Supergrid Opportunities• Long-term project• Large capital costs for installation• Special requirements for installing the grid: tunnel size, lengths of
runs, ranges of ground conditions to be encountered. • Trend with time: less space and more difficult access for installing
utlities. Less public tolerance for disturbance• Increasing use of tunneling and trenchless technologies rather
than trenching and open excavation. • Focus for improving tunneling technology for supergrid:
– Contracting practices: mitigation and assignment of risk– Joint efforts with research groups, engineering firms, contractors, and
machine manufactures to develop and demonstrate excavation and tunneling systems that will fit the requirements of the project
– Link directional drilling, micro-tunneling and larger tunnel boring machine technologies.
– Support demonstration projects using advanced technologies for driving tunnels.