  • 7/29/2019 Supervision Relay

    1/3

    Highlighting featuresIntroduction

    E-Labs trip circuit supervision relay type TS101 isdesigned for supervision & monitoring of trip coils andtrip circuits of power circuit breakers. It guarantees anefficient control system for power plants andsubstations.

    The health of the circuit breaker and associated cablingof the trip circuit (trip cables and inter panel wiring) is avital element for proper and efficient operation of thetrip scheme. It is an important consideration for apower plant or substation design to monitor thehealthiness of the trip circuit.A faulty trip circuit wouldcompletely jeopardize an efficiently and perfectlydesigned protection system. In case of faulty trip circuitthe breaker shall refuse to open under fault conditionand heavy currents will continue to flow through thepower system. This would cause heavy losses andf ai lu re o f t he p ow er s ys te m b y g en er at in g

    indiscriminate tripping and probable loss of numerouspower system components would be experienced. Thefault may spread to a wide area and numerous upstreambackup protections shall be tripped.

    Relay TS101 is specially designed to serve thesupervision function of trip circuits and used for in timedetection of such trip circuit /trip coil faults.

    Applicable for single pole and three pole

    breakers

    Complete supervision during CB close and

    open conditions

    Time delayed alarm signals to prevent false

    operation of the relay during CB opening

    to closing or closing to opening

    transition

    Operation is based on the current injection

    into the trip circuit and confirms the

    continuity of the circuit

    Covers all open circuit conditions of the trip

    coil or trip circuit

    Internal watch dog supervision for power

    supply unit and micro-controller along

    with associated LED and contact for

    alarm

    A PRODUCT OF

    E-LABS

    TS101TS101SUPERVISION RELAYSUPERVISION RELAY

    Contact us:

    TEL : +92 42 588 4232 Fax : +92 42 586 8

    Email : [email protected] URL : www.epesol

    EP SOL (Pvt) LtdELECTRICAL POWERENGINEERING SOLUTIONS

  • 7/29/2019 Supervision Relay

    2/3

    TS10TS10Application

    Operating Principle

    TS101 is the best selection to ensure the availability of

    the trip circuit and the trip coil. It detects the validity

    and integrity of the trip coil and trip circuit of the circuit

    breaker. The relay detects faulty or disconnected trip

    circuit or faulty trip coil condition and generates alarm

    on non availibilty of trip circuit coil In this way it

    ensures availability of trip circuit and trip coil,

    confirming healthy trip operations It facilitates timely

    maintenance (if required) before occurrence of a real

    fault with faulty trip circuit. The relay performs its job

    for both circuit breaker conditions (open & close) and

    can also be used for the supervision of closing coil

    The relay monitors the continuity of the tripping circuit

    by acting as a current generator. The circuit arrangement

    is such that this current generator injects the current

    (=2mA @ normal voltage) into tripping loop and then

    through the circuit breaker trip coil. The magnitude ofthis supervising current is kept very low so that the coil is

    neither heated up nor it is actuated. When the trip coil or

    the trip loop is open, this continuity is lost and the relay

    detects this open circuit and the alarms general alarm

    and trip circuit faulty are initiated. The initiation of this

    alarm is time delayed by 400ms. In addition, the relay

    continuously monitors the circuit breaker control

    voltage for under voltage conditions and activates an

    output contact in case the DC falls below a settable

    value for a settable time In either of the faults a general

    alarm is activatedon therelay.

    / .

    .

    .

    .

    Technical Specifications

    POWER SUPPLYSRT-XA 24 / 28 VDC, 20%

    SRT-XB 48 / 56 VDC, 20%SRT-XC 110 / 125 VDC, 20%SRT-XD 220 / 250 VDC, 20%

    APPROVALSIEC Compliance 60255-5

    ENVIRONMENTAL

    Temperature Range:Operation: -25 oC to +55 oCStorage: -40 oC to +70 oC

    According to IEC 60255-6

    Humidity: Max 95% without condensation

    SETTING ACCURACYVoltage: 5%

    Time: 5%

    INPUTSBurdens:

    DC Power Supply Burden:

  • 7/29/2019 Supervision Relay

    3/3

    71-B Garden Block New Garden Town Lahore

    TEL: +92 42 588 4232 FAX: +92 42 586 8145

    Email: URL: [email protected]

    TS10TS10

    EP SOL (Pvt) LtdELECTRICALPOWERENGINEERING SOLUTIONS

    TS101 x 0 0 x 0 0

    TS101 TC Supervision Relay

    1 1 Coil, 3 Pole CB

    A 24 VDC Aux Volt.

    B 48 VDC Aux Volt.

    C 110 VDC Aux Volt.

    D 220 VDC Aux Volt.

    Ordering Code