tceq - 40 cfr part 60, subpart db; flowchart; december 20 ... · subpart da? §60.40b(e) no...
TRANSCRIPT
§60.40b(a)
Is the unit an
industrial-commercial-
institutional steam generating
unit with a heat input > 100 MMBtu/hr
that was constructed, modified,
or reconstructed after
06/19/1984?
End
40 CFR Part 60,
Subpart Db
does not apply.
Start
1
Does the
affected facility meet
the applicability requirements
of 40 CFR Part 60,
Subpart Da?
§60.40b(e)
No
§60.40b(f)
No
Has there
been any changes at
the existing unit for the sole
purpose of combusting gases
containing TRS
(§60.281)?
No
Yes
Does the
affected facility meet
the applicability requirements
of and is subject to 40 CFR Part
60, Subparts Ea, Eb
or AAAA?
Yes
§60.40b(h)
Yes
No
Yes
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Below is a flowchart describing 40 CFR Part 60, Subpart Db. It will likely not be accessible using a screen reader. For the text of the statute/rule, please go to
40 CFR Part 60, Subpart Db
(1 of 67)
End
Is the unit a heat
recovery steam generator
subject to 40 CFR Part 60,
Subpart KKKK?
§60.40b(i)
Is the facility
covered by EPA approved
State or Federal section 111(d)/129
plan implementing 40 CFR Part 60,
Subpart Cb or Subpart
BBBB?
§60.40b(k)
Yes
Yes
Was
construction, modification,
or reconstruction on or before
6/19/86?
No
No
Yes
3
2
§60.40b(b)
1
No
40 CFR Part 60,
Subpart Db
does not apply.
40 CFR Part 60, Subpart Db(2 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Is the affected facility
a coal-fired unit with a heat input
capacity > 250 MMBtu/hour and meeting the
applicability requirements of 40 CFR
Part 60, Subpart D?
Yes
Comply with the PM,
Opacity, and NOx standards
of this Subpart. Comply with
the SO2 standards of 40 CFR
Part 60, Subpart D.
§60.40b(b)(2)
2
Comply with the NOx
standards of this Subpart.
§60.40b(b)(3)
Is the affected facility
an oil-fired unit with a heat input
capacity > 250 MMBtu/hour and meeting the
applicability requirements of 40 CFR
Part 60, Subpart D?
Comply with the NOx standards
of this Subpart. Comply with the
PM, Opacity, and SO2 standards
of 40 CFR Part 60, Subpart D.
§60.40b(b)(4)
Yes
No
Yes
34
No
18
Yes
Comply with the PM,
Opacity, and NOx standards
of this Subpart.
§60.40b(b)(1)
Is the
affected facility a
coal-fired unit with a heat input
capacity between 100 and
250 MMBtu/hour?
No
Is the
affected facility an
oil-fired unit with a heat input
capacity between 100 and
250 MMBtu/hour?
No
3
40 CFR Part 60, Subpart Db(3 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Does the affected
facility meet the applicability
requirements of 40 CFR Part
60, Subpart J?
Comply with the PM, Opacity, and
NOx standards of this Subpart.
Comply with the SO2 standards of
40 CFR Part 60, Subpart J.
§60.40b(c)
Yes
No
Does the affected
facility meet the applicability
requirements of 40 CFR Part
60, Subpart E?
Comply with the PM,
Opacity, and NOx standards
of this Subpart.
§60.40b(d)
Yes
3
4
No
18
40 CFR Part 60, Subpart Db(4 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
SO2
Is the
affected facility combusting
coal or oil, alone or in combination with
any other fuel, in a duct burner as part
of a combined cycle
system?
Does the
affected facility have a
federally enforceable requirement
limiting operation to an annual
capacity factor of < 30%
for coal and oil?
§60.42b(d)(1)
§60.42b(d)(3)
5
No
4
Yes
Is < 30%
of the heat input from
combustion of coal and oil
in the duct burner and > 70%
from the exhaust
gases?
§60.42b(d)(3)
No
No
Yes
Is
the affected
facility burning coke
oven gas alone or in combination
with natural gas or very low
sulfur distillate
oil?
§60.42b(d)(4)
6
Yes
No
7
Was
construction,
reconstruction or modification
on on or before
2/28/2005?
§60.42b(a)
No 10Yes
Yes
40 CFR Part 60, Subpart Db(5 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Comply with the following:
Standard
§60.42b(d)
§60.42b(e), (g)
§60.45b(a)
Monitoring/Testing
[T]§60.45b(b), (c), (c)(1), [T](e)
[T]§60.45b(f), (g), (h)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1)-(3), (b), (j)
§60.49b(k), (k)(1)-(3), (k)(5)-(6)
§60.49b(k)(11), (v), (w)
5 6
Comply with the following:
Standard
§60.42b(d)
§60.42b(e), (g)
§60.45b(a)
Monitoring/Testing
[T]§60.45b(b), (c), (c)(1), [T](f)
§60.45b(g), (h)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
§60.49b(j), (k), (k)(1)-(3), (k)(5)-(6)
§60.49b(k)(11), (v), (w)
Are SO2
emissions determined by
using as-fired fuel sampling
and analysis per
Method 19?§60.45b(c)(5)
Yes
No
12
Comply with the following:
Monitoring/Testing
[G]§60.45b(c)(4), (c)(5)
Comply with the following:
Monitoring/Testing
[G]§60.45b(c)(3), [G](c)(4)
Is the affected
facility combusting only
coal or only oil?
§60.45b(c)(2)
Yes
Comply with the following:
Monitoring/Testing
[G]§60.45b(c)(2)
No
40 CFR Part 60, Subpart Db(6 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
7
Does the
affected facility combust
coal or oil alone, or in combination
with any other fuel and use
emerging technology to
control SO2?
§60.42b(c)
No
Comply with the following:
Standard
§60.42b(c)
§60.42b(g), (i)
§60.45b(a)
Monitoring/Testing
§60.45b(i)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)-(4)
§60.49b(j), (v), (w)
Is the
affected facility
combusting only very
low sulfur oil, natural gas, or a
mixture of these fuels with
any other fuels per
§60.45b(j)?
§60.45b(j)
8
11
Is the
affected facility using
fuel pretreatment to reduce
potential SO2
emissions?
§60.42b(h)
Yes
Comply with the following:
Standard
§60.42b(e), [G](h)
Monitoring/Testing
[T]§60.45b(b), (c), (c)(1), [T](f)
§60.45b(g), (h)
Reporting
§60.49b(b), [G](n)
No
Yes
Yes
Comply with the following:
Standard
§60.42b(e)
Monitoring/Testing
[T]§60.45b(b), (c), (c)(1), [T](f)
§60.45b(g), (h)
Reporting
§60.49b(b)
16
No
40 CFR Part 60, Subpart Db(7 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
8
Does the
affected facility combust
coal refuse alone in a
fluidized bed?
§60.42b(b)
No
Comply with the following:
Standard
§60.42b(b)
§60.42b(e), (g), (i)
§60.45b(a)
Monitoring/Testing
[T]§60.45b(b), (c), (c)(1), [G](c)(2)
[T]§60.45b(f), (g)-(i)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b), (j)
§60.49b(k), (k)(1)-(3), (k)(5)-(6)
§60.49b(k)(11), [G](n), (v), (w)
9
Yes
12
40 CFR Part 60, Subpart Db(8 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(9 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
9
Does the
affected facility combust
coal or oil?
§60.42b(a)
Comply with the following:
Standard
§60.42b(a)
§60.42b(g), (i)
§60.45b(a)
Monitoring/Testing
§60.45b(i)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (j)
§60.49b(v), (w)
Yes
No
No
Comply with the following:
Standard
§60.40b(a)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
Yes
Comply with the following:
Standard
§60.42b(e)
Monitoring/Testing
[T]§60.45b(b), (c), (c)(1), [T](f)
§60.45b(g), (h)
Reporting
§60.49b(b), [G](n)
Is the
affected facility
combusting only very
low sulfur oil, natural gas, or a
mixture of these fuels with
any other fuels per
§60.45b(j)?
§60.45b(j)
18
11
16
40 CFR Part 60, Subpart Db(10 of 67)
Does the
affected facility combust
coal or oil alone, or in combination
with any other fuel and use
emerging technology to
control SO2?
§60.42b(c)
Comply with the following:
Standard
§60.42b(c)
§60.42b(g), (i)
§60.45b(a)
Monitoring/Testing
§60.45b(i)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)-(4)
§60.49b(j), (v), (w)
Is the
affected facility using
fuel pretreatment to reduce
potential SO2
emissions?
Yes
Comply with the following:
Standard
§60.42b(e), [G](h)
Monitoring/Testing
[T]§60.45b(b), (c), (c)(1), [T](f)
§60.45b(g), (h)
Reporting
§60.49b(b), [G](n)
No
Yes
Yes
Comply with the following:
Standard
§60.42b(e)
Monitoring/Testing
[T]§60.45b(b), (c), (c)(1), [T](f)
§60.45b(g), (h)
Reporting
§60.49b(b)
No
10
13No
Is the
affected facility
combusting only very
low sulfur oil, natural gas, or a
mixture of these fuels with
any other fuels per
§60.45b(j)?
§60.45b(j)
11
16
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Are fuel
receipts maintained per
§60.49b(r)(1)?
Comply with the following:
Standard
§60.42b(j)
Monitoring/Testing
§60.45b(j)
§60.47b(f)
Recordkeeping
§60.42b(j)(2)
Reporting
[G]§60.49b(m)
No
Comply with the following:
Standard
§60.42b(j)
Monitoring/Testing
§60.42b(j)(1)
Reporting
§60.49b(b)
15
11
Does the
affected facility have a
federally enforceable permit limiting
the annual capacity factor
to < 10%?
§60.42b(f)(1)
Comply with the following:
Standard
[G]§60.42b(f)
Monitoring/Testing
[G]§60.45b(d)
Reporting
§60.49b(a)(2), (l)
§60.49b(l)(1)-(2), (l)(4)-(5)
Comply with the following:
Standard
§60.42b(e)
Monitoring/Testing
§60.45b(c), (c)(1), [G](c)(2)
Reporting
§60.49b(k), (k)(1)-(3)
§60.49b(k)(5)-(6), (k)(11)
No
Is low sulfur
content demonstrated
by procedures in
§60.49b(r)?§60.42b(j)
Comply with the following:
Recordkeeping
§60.49b(r), [G](r)(2)
Reporting
§60.49b(r), [G](r)(2)
Comply with the following:
Recordkeeping
§60.49b(r), (r)(1)
Reporting
§60.49b(r), (r)(1)
Yes
Yes
§60.49b(r)(1)
Yes
No
18
12
40 CFR Part 60, Subpart Db(11 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Is the
affected facility operating
a continuous emission monitoring
system for measuring SO2
concentrations?
§60.47b(a)
Comply with the following:
Monitoring/Testing
[G]§60.47b(a), (c)-(d), [G](e)
Recordkeeping
[G]§60.47b(a)
Reporting
§60.49b(k)(4), (k)(8)-(10)
12
No
Yes
Comply with the following:
Monitoring/Testing
§60.47b(b), (b)(2)-(4)
Reporting
§60.49b(k)(7)
Are SO2
emissions determined by
using as-fired fuel sampling
and analysis per
Method 19?
No
Comply with the following:
Monitoring/Testing
§60.47b(b), (b)(1), (b)(3)-(4)
Reporting
§60.49b(k)(7)
Yes
§60.47b(b)(1)
18
40 CFR Part 60, Subpart Db(12 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
13
Does the
affected facility
combust coal, oil, gaseous
fuels, a mixture of these fuels, or
a mixture of these fuels
with any other
fuels?§60.42b(k)(1)
Yes
No
Comply with the following:
Standard
§60.40b(a)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
Yes
Comply with the following:
Standard
§60.42b(k)(2)
Monitoring/Testing
§60.47b(f)
Recordkeeping
§60.45b(k)
§60.49b(o)
Reporting
§60.49b(a), (a)(1)
§60.42b(k)(2)
No
Is the
affected facility
combusting very low sulfur
oil, gaseous fuel, a mixture of
these fuels, or a mixture of these fuels
with any other fuels of potential SO2
emission rate of 140 ng/J
(0.32lb/MMBtu)
or less?
Yes
No
Comply with the following:
Recordkeeping
§60.49b(r), (r)(1)
Reporting
§60.49b(r), (r)(1)
Comply with the following:
Recordkeeping
§60.49b(r), [G](r)(2)
Reporting
§60.49b(r), [G](r)(2)
14
Are fuel
receipts maintained per
§60.49b(r)(1)?
§60.42b(k)
§60.49b(r)(1)
18
40 CFR Part 60, Subpart Db(13 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(14 of 67)
No
Is the §60.42b(k)(4)
alternative to §60.42b(k)(1)
being chosen?
§60.42b(k)(4)
Yes
14
§60.42b(k)(4)
Is the
affected facility
combusting coal or a mixture
of coal with other
fuels?
Yes
No
Comply with the following:
Standard
§60.42b(k)(1)
§60.42b(e), [G](f), (g)
§60.45b(a)
Monitoring/Testing
[T]§60.45b(b), (c), (c)(1), [T](f)
§60.45b(g)-(h)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
§60.49b(j), [G](n), (v), (w)
Comply with the following:
Standard
§60.42b(k)(4)
§60.42b(e), [G](f), (g)
§60.45b(a)
Monitoring/Testing
[T]§60.45b(b), (c), (c)(1), [T](f)
§60.45b(g)-(h)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
§60.49b(j), [G](n), (v), (w)
16
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
15
Is the
affected facility operating
a continuous emission monitoring
system for measuring SO2
concentrations?
§60.47b(a)
Comply with the following:
Monitoring/Testing
[G]§60.47b(a), (c)-(d), [G](e)
Recordkeeping
[G]§60.47b(a)
Reporting
§60.49b(b), (l)(3), (l)(7)-(9)
No
Yes
Comply with the following:
Monitoring/Testing
§60.47b(b), (b)(2)-(4)
Reporting
§60.49b(l)(6)
Comply with the following:
Monitoring/Testing
§60.47b(b), (b)(1), (b)(3)-(4)
Reporting
§60.49b(l)(6)
Yes
No
Will
as-fired fuel sampling and
analysis per Method 19 be
used?
§60.47b(b)(1)
18
40 CFR Part 60, Subpart Db(15 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
16
Is the affected facility
operating a CEMS for measuring
SO2 concentrations?
§60.47b(a)
Comply with the following:
Monitoring/Testing
[G]§60.47b(a), (c)-(d), [G](e)
Recordkeeping
[G]§60.47b(a)
Reporting
§60.49b(k), (k)(1)-(6), (k)(8)-(11)
Yes
Is
the affected
facility combusting coal or oil
with other
fuel?
§60.45b(c)(3)
Comply with the following:
Monitoring/Testing
[G]§60.45b(c)(3), [G](c)(4)
Comply with the following:
Monitoring/Testing
[G]§60.45b(c)(2)
No
17 18
Is the affected
facility combusting only coal
and/or oil?
Yes
§60.45b(c)(2)
No
YesNo
40 CFR Part 60, Subpart Db(16 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Will Method
6B sampling and analysis
be used?
§60.47b(b)(2)
Yes
Comply with the following:
Monitoring/Testing
§60.47b(b), (b)(1), (b)(3)-(4)
Reporting
§60.49b(k), (k)(1)-(3)
§60.49b(k)(5)-(7), (k)(11)
Comply with the following:
Monitoring/Testing
§60.47b(b), (b)(2)-(4)
Reporting
§60.49b(k), (k)(1)-(3)
§60.49b(k)(5)-(7), (k)(11)
17
No
18
40 CFR Part 60, Subpart Db(17 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
PM18
Was the
affected facility constructed,
reconstructed, or modified after
2/28/2005?
Yes
Yes
Is the affected
facility combusting only oil
containing no more than 0.3 weight
percent sulfur or coke oven gas alone or in
combination with other fuels not
subject to a particulate
matter standard?
Comply with the following:
Standard
§60.43b(h)(5)
[G]§60.48b(j)
Recordkeeping
§60.46b(i)
[G]§60.48b(j)
§60.49b(o)
Reporting
§60.49b(a), (a)(1)
No
Did the
affected facility commence
modification after
2/28/2005?
21
§60.43b(h)(1)
§60.43b(h)(5)
§60.43b(h)(2)
22
19No
Yes
Comply with the following:
Recordkeeping
§60.49b(r), (r)(1)
Reporting
§60.49b(r), (r)(1)
Comply with the following:
Recordkeeping
§60.49b(r), [G](r)(2)
Reporting
§60.49b(r), [G](r)(2)
Are fuel
receipts maintained per
§60.49b(r)(1)?
§60.46b(i)
§60.49b(r)(1)
No
No
Yes
34
40 CFR Part 60, Subpart Db(18 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(19 of 67)
20
Is the facility
burning coke oven
gas alone or with fuels not
subject to PM, and not using
a post-combustion
technology?
Comply with the following:
Standard
§60.43b(a)(4)
Recordkeeping
§60.49b(o)
Reporting
§60.49b(a), (a)(1)§60.43b(a)(4)
19
Is the affected
facility combusting only coal or
coal with other fuels?
§60.43b(a)(3)
25
No
Yes
No
Yes 34
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
20
31
Is the
heat input capacity < 250
MMBtu/hr?
Does the
affected facility have a
federally enforceable requirement limiting
operation to an annual capacity factor of
< 30% for coal or coal and
other solid fuels?
Was
construction commenced
after 6/19/84 and before
11/25/86?
§60.43b(a)(3)(ii)
§60.43b(a)(3)(iii)
24
No
Is the
affected facility
combusting only coal or a
mixture of coal with other fuels, and has
an annual capacity factor for
the other fuels of 10%
or less? §60.43b(a)(1)
Comply with the following:
Standard
§60.43b(a)(1)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
32
No
Yes
Yes
§60.43b(a)(3)(iv)
Yes
Yes
No
No
40 CFR Part 60, Subpart Db(20 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(21 of 67)
21
Does the affected
facility combust coal, oil,
wood, a mixture of these fuels, or a
mixture of these fuels with any
other fuels?
Comply with the following:
Standard
§60.40b(a)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
33
Comply with the following:
Standard
§60.43b(h)(1)
§60.43b(h)(1)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
NoYes
32
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(22 of 67)
22
Does the
affected facility combust
over 30% wood by heat
input?
Yes
No 23
Comply with the following:
Standard
§60.43b(h)(4)
§60.43b(h)(4)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
Does the
affected facility have
a maximum heat input capacity
greater than 73 MW
(250 MMBtu/hr)?
§60.43b(h)(4)
Comply with the following:
Standard
§60.43b(h)(3)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
Yes No
32
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(23 of 67)
23
Does the affected
facility combust coal, oil,
wood, a mixture of these fuels, or a
mixture of these fuels with
any other fuels?
No
Comply with the following:
Standard
§60.40b(a)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
Comply with the following:
Standard
§60.43b(h)(1)
§60.43b(h)(2)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
Is the
facility electing to use the
alternative requirements of
§60.43b(h)(2)?
Comply with the following:
Standard
[G]§60.43b(h)(2)
§60.43b(h)(2)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
NoYes
Yes
32
33
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Is the
affected facility
combusting coal and
other fuels, and have a federally
enforceable annual capacity
factor for the other
fuels > 10%?
Yes
§60.43b(a)(2)
Comply with the following:
Standard
§60.43b(a)(2)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1)-(3)
24
No
Is the
affected facility
combusting oil or mixtures
of oil with other fuels and uses a
conventional or emerging
technology to reduce
SO2?
Comply with the following:
Standard
§60.43b(b)
§60.43b(g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
§60.43b(b) Reporting
§60.49b(a), (a)(1), (a)(3)
Yes
No
26
25
Is the affected
facility combusting wood
or wood with other fuels
(except coal)?
§60.43b(c)
Yes
27No
32
40 CFR Part 60, Subpart Db(24 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Comply with the following:
Standard
§60.43b(c)(1)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
26
Is the
heat input capacity < 250
MMBtu/hr?
Does the
affected facility have
a federally enforceable
requirement limiting operation
to an annual capacity
factor of < 30%
for wood?
§60.43b(c)(2)(ii)
§60.43b(c)(2)(iii)
Does the
affected facility
have an annual capacity
factor > 30% for
wood?
§60.43b(c)(1)
Yes
Comply with the following:
Standard
§60.43b(c)(2)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1)-(3)
No
No
Yes
No
Yes
32
27
40 CFR Part 60, Subpart Db(25 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Is the
affected facility
combusting municipal-type
solid waste alone or with
other fuels?
§60.43b(d)
27
Is the
heat input capacity < 250
MMBtu/hr?
Does the
affected facility have
a federally enforceable requirement
limiting fuel operation to an annual
capacity factor
of < 30%?
§60.43b(d)(2)(iii)
§60.43b(d)(2)(ii)
Yes
Yes
No
Was
construction commenced
after 6/19/84 and before
11/25/86?
§60.43b(d)(2)(iv)
Yes
No
No
28
28 29
Yes
No
Comply with the following:
Standard
§60.40b(a)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
33
40 CFR Part 60, Subpart Db(26 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Is the
affected facility combusting
only municipal-type solid
waste?
§60.43b(d)(1)(i)
Comply with the following:
Standard
§60.43b(d)(2)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1)-(3)
No
Does the
affected facility,
combusting mixtures of fuels,
have an annual capacity factor
of < 10% for the other
fuels?§60.43b(d)(1)(ii)
30Yes
28 29
Comply with the following:
Standard
§60.40b(a)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
No
Yes
32
33
40 CFR Part 60, Subpart Db(27 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
31
Comply with the following:
Standard
§60.43b(a)(3)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1)-(3)
Comply with the following:
Standard
§60.43b(d)(1)
§60.43b(e), (g)
§60.46b(a)
Monitoring/Testing
§60.46b(b)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
30
32
40 CFR Part 60, Subpart Db(28 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(29 of 67)
32
Is the facility electing
to install, calibrate, maintain,
and operate a continuous emission
monitoring system?
Yes
No
Comply with the following:
Monitoring/Testing
[T][G]§60.46b(j)
§60.48b(k)
Recordkeeping
[G]§60.46b(j)
§60.48b(k)
Comply with the following:
Monitoring/Testing
[T]§60.46b(d), [T](d)(1)
[T][G]§60.46b(d)(2)
[T]§60.46b(d)(3)-(5)
[T][G]§60.46b(d)(6)
§60.46b(j)
33
Does
the affected facility
use a CEMS for monitoring
particulate
matter?
§60.43b(f)
Yes
Yes
Is the
facility subject to a
federally enforceable PM limit
of 0.030 lb/MMBtu
or less
No
No
§60.43b(f)
33A
33A
34
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Comply with the following:
Standard
§60.43b(f)
§60.43b(g)
§60.46b(a)
Monitoring/Testing
[T]§60.46b(d), [T](d)(7)
Recordkeeping
[G]§60.49b(d), [G](f), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
§60.49b(h), (h)(3), (v), (w)
Comply with the following:
Standard
§60.40b(a)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
33A
Does
the affected facility
combust coal, oil, wood,
or mixtures of these fuels
with any other
fuels?
Yes
No
§60.43b(f)
PM(Opacity)
Does
the affected
facility meet any of the
conditions in §60.48b(j)(1)-(6)
and not use a
COMS?§60.48b(j)
No
Comply with the following:
Monitoring/Testing
§60.48b(a), (e)
Recordkeeping
§60.48b(a)
Does
the affected facility
combust coal, wood, or
municipal-type solid
waste?
§60.48b(e)(1)Comply with the following:
Monitoring/Testing
§60.48b(e)(1)
Yes
No
Comply with the following:
Standard
[G]§60.48b(j)
Monitoring/Testing
§60.48b(a), [G](a)(1)-(2)
§60.48b(a)(3)
Recordkeeping
§60.48b(a), [G](a)(1)-(2)
§60.48b(a)(3)
[G]§60.48b(j)
Yes
34
40 CFR Part 60, Subpart Db(30 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Does the
affected facility combust
alone or in combination only natural
gas, distillate oil or residual oil with
a nitrogen content of
0.30% w or less?
§60.44b(j)(1)
Does
the affected facility
have a federally enforceable
requirement limiting operation to
firing natural gas, distillate oil and/or residual
oil with a nitrogen content of 0.30%
weight or less and an annual
capacity factor of
10% or less?
§60.44b(j)(2)
§60.44b(j)(3)
Does the
affected facility
have a heat input capacity
of 250 MMBtu/hr
or less?§60.44b(k)
Comply with the following:
Standard
§60.40b(a)
Monitoring/Testing
[T]§60.46b(g)
Recordkeeping
[G]§60.49b(d), (o), [G](p)
Reporting
§60.49b(a), (a)(1)-(3), (q)
§60.49b(q)(1), (q)(3), (w)
36
42
No 68
34 NOx
No
Yes
Yes
Did the
affected facility
commence construction or
reconstruction after
7/9/97?§60.44b(l)
No
46
Yes
No
Yes
40 CFR Part 60, Subpart Db(31 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
36
Does the affected
facility combust only
oil or natural gas?
§60.44b(a)
Yes
37
No
Comply with the following:
Standard
§60.44b(b)
[G]§60.44b(j)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](g), [G](h)
Recordkeeping
[G]§60.49b(d), (o), [G](p)
Reporting
§60.49b(a), (a)(1)-(3), (b), (q)
§60.49b(q)(1), (q)(3), (w)
Yes
Did the
affected facility
commence construction or
reconstruction after
7/9/97?
§60.44b(l)
No
40
Is the
affected facility
a duct burner used in
combined cycle
system?
§60.46b(f)62
35
NoYes
68
40 CFR Part 60, Subpart Db(32 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(33 of 67)
Is the
affected facility a duct
burner?
§60.44b(a)(4)(i) Comply with the following:
Standard
§60.44b(a)(4)(ii)
[G]§60.44b(j)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](g), [G](h)
Recordkeeping
[G]§60.49b(d), (o), [G](p)
Reporting
§60.49b(a), (a)(1)-(3), (b), (q)
§60.49b(q)(1)-(3), (w)
No
Is the
residual oil sampled
and analyzed for nitrogen
content as specified in
§60.49b(e)?
Comply with the following:
Monitoring/Testing
§60.46b(e)(4)
§60.49b(e)
Recordkeeping
§60.49b(e)
Comply with the following:
Monitoring/Testing
§60.46b(e)(2)
§60.49b(e)
§60.46b(e)(5)
72
No
Yes
37
Yes
Does the
affected facility combust
residual oil?
§60.44b(a)(4)(i)
Yes
No
Comply with the following:
Standard
§60.44b(a)(4)(i)
[G]§60.44b(j)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](g), [G](h)
Recordkeeping
[G]§60.49b(d), (o), [G](p)
Reporting
§60.49b(a), (a)(1)-(3), (b), (q)
§60.49b(q)(1), (q)(3), (w)
38
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(34 of 67)
38
Does
the affected
facility combust natural
gas or distillate oil with a
low heat release
rate?
§60.44b(a)(1)(i)
Comply with the following:
Standard
§60.44b(a)(1)(i)
[G]§60.44b(j)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](g), [G](h)
Recordkeeping
[G]§60.49b(d), (o), [G](p)
Reporting
§60.49b(a), (a)(1)-(3), (b), (q)
§60.49b(q)(1), (q)(3), (w)
No
Yes
Does
the affected
facility combust natural
gas or distillate oil with a
high heat release
rate?
§60.44b(a)(1)(ii)
No
Yes
Comply with the following:
Standard
§60.44b(a)(1)(ii)
[G]§60.44b(j)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](g), [G](h)
Recordkeeping
[G]§60.49b(d), (o), [G](p)
Reporting
§60.49b(a), (a)(1)-(3), (b), (q)
§60.49b(q)(1), (q)(3), (w)
39
72
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Does
the affected
facility combust residual
oil with a low heat
release rate?
§60.44b(a)(2)(i)
39Comply with the following:
Standard
§60.44b(a)(2)(i)
[G]§60.44b(j)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](g), [G](h)
Recordkeeping
[G]§60.49b(d), (o), [G](p)
Reporting
§60.49b(a), (a)(1)-(3), (b)
§60.49b(q), (q)(1)-(3), (w)
Comply with the following:
Standard
§60.44b(a)(2)(ii)
[G]§60.44b(j)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](g), [G](h)
Recordkeeping
[G]§60.49b(d), (o), [G](p)
Reporting
§60.49b(a), (a)(1)-(3), (b)
§60.49b(q), (q)(1)-(3), (w)
Yes
No
Is the
residual oil sampled
and analyzed for nitrogen
content as specified in
§60.49b(e)?
Comply with the following:
Monitoring/Testing
§60.46b(e)(4)
§60.49b(e)
Recordkeeping
§60.49b(e)
Comply with the following: §60.49b(e)Monitoring/Testing §60.46b(e)(5)
§60.46b(e)(2)
No
Yes
72
40 CFR Part 60, Subpart Db(35 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(36 of 67)
40
§60.44b(l)(3)
Comply with the following:
Standard
§60.44b(l)(3)
§60.44b(h), (i), [G](j)
§60.46b(a)
Monitoring/Testing
§60.48Da(i)
Recordkeeping
[G]§60.49b(d), (o), [G](p)
Reporting
§60.49b(a), (a)(1), (a)(3), (b), (w)
Is the affected
facility choosing to comply
with the output based limit
in §60.44b(l)(3)?
Is more than
10% of the total annual
output electrical or
mechanical?
Yes
41
§60.49Da(c)(2)
Is the CEMS
complying with the requirements
of 40 CFR Part 75?
Yes
Comply with the following:
Monitoring/Testing
§60.49Da(c)(1)
Recordkeeping
[G]§60.49b(g)
Comply with the following:
Monitoring/Testing
§60.49Da(c)(2)
Reporting
§60.51Da(a), [G](b), (f), [G](h)
§60.51Da(j), (k)
43
§60.44b(l)(3)
No
No
NoYes
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(37 of 67)
§60.44b(l)(2)
No
Does the
affected facility have low heat
release rate and combust natural gas or
distillate oil in excess of 30% of the heat
input from the combustion
of all fuels?
Yes
41
Is the affected facility
a duct burner used in combined
cycle system?
§60.46b(f)
Yes 59
No
58
35
Comply with the following:
Standard
§60.44b(l)(2)
[G]§60.44b(j)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](g)
Recordkeeping
[G]§60.49b(d), (o), [G](p)
Reporting
§60.49b(a), (a)(1)-(3), (b), (q)
§60.49b(q)(1), (q)(3), (w)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(38 of 67)
42
§60.44b(l)(3)
Comply with the following:
Standard
§60.44b(l)(3)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.48Da(i)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b), (w)
Is the affected
facility choosing to comply
with the output based limit
in §60.44b(l)(3)?
Is more than
10% of the total annual
output electrical or
mechanical?
No
Yes
44
§60.44b(l)(3)
Is the CEMS
complying with the requirements of
40 CFR Part 75?
Yes
Comply with the following:
Monitoring/Testing
§60.49Da(c)(1)
Recordkeeping
[G]§60.49b(g)
Comply with the following:
Monitoring/Testing
§60.49Da(c)(2)
Reporting
§60.51Da(a), [G](b), (f), [G](h)
§60.51Da(j), (k)
43
No
No
§60.44b(l)(3)
Yes
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Comply with the following:
Monitoring/Testing
§60.49Da(k), (k)(2)
Is the
facility gas- or oil-fired
using §60.49Da(n)
alternative?
Comply with the following:
Monitoring/Testing
§60.49Da(n)
Yes
§60.49Da(n)
No
Is the
facility using §60.49Da(m)
alternative?
§60.49Da(m)
Comply with the following:
Monitoring/Testing
§60.49Da(m)
Yes
Comply with the following:
Monitoring/Testing
§60.49Da(l)
No
Does the
facility generate process
steam in combination with
electricity?
Comply with the following:
Monitoring/Testing
§60.49Da(k), (k)(3)
Yes
§60.49Da(k)(3)
Does the
affected facility generate
electricity only?
§60.49Da(k)(1)
Comply with the following:
Monitoring/Testing
§60.49Da(k), (k)(1)
Yes
No
No
72
43
40 CFR Part 60, Subpart Db(39 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(40 of 67)
Does the
facility have an ACF
of 10% for coal, oil or natural gas,
and is it subject to a federally enforceable
requirement limiting the ACF
to 10% or less for these
fuels?
Comply with the following:
Standard
§60.44b(l)(1)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
No
§60.44b(l)(1)
Yes
§60.44b(l)(2)
Comply with the following:
Standard
§60.44b(l)(2)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)No
Does the affected
facility have low heat release rate and
combust natural gas or distillate oil in excess
of 30% of the heat input from the
combustion of all fuels?
45
Yes
44
46
Does the
affected facility
combust coal, oil or
natural gas, or a mixture of these
fuels, or a mixture of these
fuels with other
fuels?
No
§60.44b(l)(1)
Yes
46
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
45
Does
the affected
facility combust natural
gas or distillate oil alone in combination
with fuels other than coal
or residual
oil?
60Yes
§60.46b(e)(4)
Does the
affected facility
simultaneously combust mixtures of
natural gas, oil,
or coal?
63
65
Yes
§60.46b(e)(4)
No
No
40 CFR Part 60, Subpart Db(41 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(42 of 67)
Does the
affected facility
simultaneously combust natural gas
with wood, municipal-type solid
waste, or other solid fuel,
except coal?
§60.44b(d)
Does the
affected facility
simultaneously combust coal, oil, or
natural gas with byproduct/
waste?
§60.44b(e)
49
48
50
Yes
Yes
No
Does the affected
facility combust only coal,
oil, or natural gas?
§60.44b(a)
No
47
Does
the affected
facility simultaneously
combust mixtures of
natural gas, oil, or
coal?
56
§60.44b(b)
No
Yes
Yes
No
46
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Yes
Is the facility
subject to a federally
enforceable requirement limiting
the annual capacity factor for
natural gas to 10%
or less?
§60.44b(d)
Comply with the following:
Standard
§60.40b(a)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1)-(3)
Is the
facility subject
to a federally enforceable
requirement limiting the annual
capacity for coal, oil, and
natural gas to 10% §60.44b(e)or less?
4948
55
54
Yes
Comply with the following:
Standard
§60.44b(b)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
64
47
No
No
72
40 CFR Part 60, Subpart Db(43 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
50
No
67
Is the
affected facility a duct
burner in a combined cycle
system combusting natural
gas or distillate
oil?
Comply with the following:
Standard
§60.44b(a)(4)(i)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](f)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
Yes
§60.44b(a)(1)(i)
Does
the affected
facility combust natural
gas or distillate oil with a
low heat release
rate?
61
Comply with the following:
Standard
§60.44b(a)(1)(i)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
Yes
No
Comply with the following:
Standard
§60.44b(a)(4)(ii)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](f)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
Is the
affected facility a duct
burner in a combined cycle
system combusting
residual oil?
§60.44b(a)(4)(ii)
51
Yes 69
§60.44b(a)(4)(i)
No
40 CFR Part 60, Subpart Db(44 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Does
the affected
facility combust residual
oil with a low heat
release rate?
§60.44b(a)(2)(i)
Comply with the following:
Standard
§60.44b(a)(2)(i)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
51
Does
the affected
facility combust residual
oil with a high heat
release rate?
§60.44b(a)(2)(ii)
Comply with the following:
Standard
§60.44b(a)(2)(ii)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
No
Yes
No
52
Yes
70
Does
the affected
facility combust natural
gas or distillate oil with a
high heat release
rate?
§60.44b(a)(1)(ii)
Comply with the following:
Standard
§60.44b(a)(1)(ii)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)No
Yes 61
40 CFR Part 60, Subpart Db(45 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
52
53
Does the
affected facility
combust coal in a spreader
stoker and fluidized
bed?§60.44b(a)(3)(ii)
Comply with the following:
Standard
§60.44b(a)(3)(ii)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](e), [T](e)(1)
§60.46b(e)(2)
[G]§60.48b(b), (c)-(e), [G](e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(d), [G](g), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
§60.49b(i), (v), (w)
Yes
Does the
affected facility combust
pulverized coal?
§60.44b(a)(3)(iii)
Comply with the following:
Standard
§60.44b(a)(3)(iii)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](e), [T](e)(1)
§60.46b(e)(2)
[G]§60.48b(b), (c)-(e), [G](e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(d), [G](g), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
§60.49b(i), (v), (w)
No
No
Does
the affected
facility combust coal and
have a mass-feed
stoker?§60.44b(a)(3)(i)
Comply with the following:
Standard
§60.44b(a)(3)(i)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](e), [T](e)(1), (e)(2)
[G]§60.48b(b), (c)-(e), [G](e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(d), [G](g), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
§60.49b(i), (v), (w)
Yes
No
Yes
72
40 CFR Part 60, Subpart Db(46 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
53
Does
the affected
facility combust
lignite?
§60.44b(a)(3)(iv)
Comply with the following:
Standard
§60.44b(a)(3)(iv)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](e), [T](e)(1), (e)(2)
[G]§60.48b(b), (c)-(e), [G](e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(d), [G](g), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
§60.49b(i), (v), (w)
Yes
Comply with the following:
Standard
§60.44b(a)(3)(vi)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](e), [T](e)(1), (e)(2)
[G]§60.48b(b), (c)-(e), [G](e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(d), [G](g), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
§60.49b(i), (v), (w)
Does
the affected
facility combust lignite
mined in ND, SD, or MT
in a slag tap
furnace?
§60.44b(a)(3)(v)
Comply with the following:
Standard
§60.44b(a)(3)(v)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](e), [T](e)(1), (e)(2)
[G]§60.48b(b), (c)-(e), [G](e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(d), [G](g), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
§60.49b(i), (v), (w)
No
Yes
These requirements are
for a facility that
combusts coal-derived
synthetic fuels.
No
72
40 CFR Part 60, Subpart Db(47 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
54
Comply with the following:
Standard
§60.44b(e)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](e), [T](e)(1)
[G]§60.48b(b), (c)-(e), [G](e)(2)
§60.48b(e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(d), [G](g), (o)
Reporting
§60.49b(a), (a)(1)-(3)
§60.49b(b), (i), (v), (w)
55Comply with the following:
Standard
§60.44b(d)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](e), [T](e)(1)
[G]§60.48b(b), (c)-(e), [G](e)(2)
§60.48b(e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(d), [G](g), (o)
Reporting
§60.49b(a), (a)(1)-(3)
§60.49b(b), (i), (v), (w)Does the
affected facility
combust byproduct/waste with
natural gas or oil and petitioning the
Administrator to establish
emission limits for the
facility?
Comply with the following:
Standard
§60.44b(f)
[G]§60.44b(f)(1), (f)(2), (h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](e), [T](e)(1)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(d), [G](g), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
§60.49b(b), (i), (v), (w)
§60.44b(e)
Yes
No
72
72
40 CFR Part 60, Subpart Db(48 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
56
Does the affected
facility combust hazardous waste
with natural gas or oil?
§60.44b(g)
Comply with the following:
Standard
§60.44b(g)
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c), [T](e), [T](e)(1)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(d), [G](g), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
§60.49b(b), (i), (v), (w)
Yes
No
Comply with the following:
Standard
§60.40b(a)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3)
Does the
affected facility
simultaneously combust coal or
oil, or a mixture of these fuels with natural
gas, and wood, municipal-type
solid waste, or any
other fuel?
§60.44b(c)
57
Yes
No
72
40 CFR Part 60, Subpart Db(49 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(50 of 67)
Comply with the following:
Standard
§60.44b(b)*
§60.44b(h), (i)
§60.46b(a)
Monitoring/Testing
§60.46b(c)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1), (a)(3), (b)
Is the
facility subject to a
federally enforceable requirement
limiting the annual capacity factor for
coal or oil, or mixture of these
fuels with natural gas to
10%or less?§60.44b(c)
57
Comply with the following:
Standard
§60.40b(a)
Recordkeeping
[G]§60.49b(d), (o)
Reporting
§60.49b(a), (a)(1)-(3)
YesNo
7264
* A facility that simultaneously combusts the fuels specified in §60.44b(c) has an option to use
the emission limitations of §60.44b(a) or (b). To simplify the flowchart only the emission
limitation of §60.44b(b) is used because when fuels are simultaneously combusted the emission
limits of paragraph (a) are used to calculate the limit in paragraph (b). Also the emission
limitations will be the same for either §60.44b(a) or §60.44b(b).
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(51 of 67)
Does
the affected facility
combust residual
oil?
§60.49b(e)
Comply with the following:
Monitoring/Testing
[G]§60.46b(h)
5958
Is the affected
facility electing to conduct
the performance test per
§60.46b(f)(1)?
§60.46b(f)(1)
Yes
Comply with the following:
Standard
§60.48b(h)
Monitoring/Testing
§60.46b(f), [T][G](f)(1)
Comply with the following:
Monitoring/Testing
§60.46b(f), (f)(2)
[G]§60.48b(b), (c)-(d), (e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
No
Comply with the following:
Monitoring/Testing
§60.49b(e)
Recordkeeping
§60.49b(e)
Reporting
§60.49b(q)(2)
Yes
No
72
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(52 of 67)
Is the affected
facility electing to conduct
the performance test per
§60.46b(f)(1)?§60.46b(f)(1)
Comply with the following:
Standard
§60.48b(h)
Monitoring/Testing
§60.46b(f), [T][G](f)(1)
Recordkeeping
[G]§60.49b(p)
Comply with the following:
Monitoring/Testing
§60.46b(f), (f)(2)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
No
Is the affected facility
a duct burner used in combined
cycle system?
§60.46b(f)
60
Yes
Yes
No
72
61
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
61
Does the
affected facility
have a heat input of 250
MMBtu/hr
or less?
§60.46b(e)(4)
Does the
affected facility use
a CEMS?
§60.46b(e)
Comply with the following:
Monitoring/Testing
[T]§60.46b(e), [T](e)(1), (e)(3)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
Reporting
§60.49b(h), (i), (v), (w)
No
Comply with the following:
Monitoring/Testing
[T]§60.46b(e), [T](e)(1), (e)(4)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3)
§60.48b(f), (g)(1)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
Reporting
§60.49b(h), (h)(4), (i), (v), (w)Comply with the following:
Monitoring/Testing
§60.48b(g)(2)
Recordkeeping
[G]§60.49b(c), [G](g)
Reporting
[G]§60.49b(c), (h), (v), (w)
Yes
No
Yes
72
40 CFR Part 60, Subpart Db(53 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
71
Is the affected
facility electing to conduct
the performance test per
§60.46b(f)(1)?§60.46b(f)(1)
Yes
Comply with the following:
Standard
§60.48b(h)
Monitoring/Testing
§60.46b(f), [T][G](f)(1)
Comply with the following:
Monitoring/Testing
§60.46b(f), (f)(2)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
Is the
affected facility
a duct burner used in
combined cycle
system? §60.46b(f)
No
62
Yes
63
Is the affected
facility electing to conduct
the performance test per
§60.46b(f)(1)?
§60.46b(f)(1)
Comply with the following:
Standard
§60.48b(h)
Monitoring/Testing
§60.46b(f), [T][G](f)(1)
Comply with the following:
Monitoring/Testing
§60.46b(f), (f)(2)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
No
Yes
No
68
64
40 CFR Part 60, Subpart Db(54 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Does the
affected facility
have a heat input of 250
MMBtu/hr or
less?
§60.46b(e)(4)
No
Comply with the following:
Monitoring/Testing
[T]§60.46b(e), [T](e)(1)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
Reporting
§60.49b(i), (v), (w)
Comply with the following:
Monitoring/Testing
§60.48b(g)(2)
Recordkeeping
[G]§60.49b(c), [G](g)
Reporting
[G]§60.49b(c), (h), (v), (w)
Does the
affected facility use a
CEMS?
§60.46b(e)
Comply with the following:
Monitoring/Testing
[T]§60.46b(e), [T](e)(1), (e)(4)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f), (g)(1)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
Reporting
§60.49b(h), (h)(4), (i), (v), (w)
Yes
Is the
residual oil sampled
and analyzed for nitrogen
content as specified in
§60.49b(e)?
Comply with the following:
Monitoring/Testing
§60.46b(e)(4)
§60.49b(e)
Recordkeeping
§60.49b(e) §60.49b(e)
§60.46b(e)(5)
Comply with the following:
Monitoring/Testing
§60.46b(e)(2)
Does the
affected facility combust
residual oil?
§60.49b(e)
Yes
Yes
No
No
Yes
No
72
72
64
71
40 CFR Part 60, Subpart Db(55 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Is the affected
facility electing to conduct
the performance test per
§60.46b(f)(1)?
§60.46b(f)(1)
Yes
Comply with the following:
Standard
§60.48b(h)
Monitoring/Testing
§60.46b(f), [T][G](f)(1)
Comply with the following:
Monitoring/Testing
§60.46b(f), (f)(2)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
65
Is the affected facility
a duct burner used in combined
cycle system?
§60.46b(f)
No 66
No
Yes
71
40 CFR Part 60, Subpart Db(56 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Does the
affected facility have a heat
input of 250MMBtu/hr or
less?
§60.46b(e)(4)
Does the
affected facility use a
CEMS?
§60.46b(e)Comply with the following:
Monitoring/Testing
[T]§60.46b(e), [T](e)(1), [T](e)(4)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3)
§60.48b(f), (g)(1)
§60.49b(e)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
Reporting
§60.49b(h), (h)(4), (i), (v), (w)
Comply with the following:
Monitoring/Testing
§60.48b(g)(2)
Recordkeeping
[G]§60.49b(c), [G](g)
Reporting
[G]§60.49b(c), (h), (v), (w)
Yes
Yes
66
Does the
affected facility combust
coal?
No
§60.46b(e)(2)
Comply with the following:
Monitoring/Testing
§60.46b(e)(2)
Yes
No
No
Comply with the following:
Monitoring/Testing
[T]§60.46b(e), [T](e)(1), (e)(3)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
Reporting
§60.49b(h), (i), (v), (w)
71
71
40 CFR Part 60, Subpart Db(57 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(58 of 67)
Is the affected
facility electing to conduct
the performance test per
§60.46b(f)(1)?
§60.46b(f)(1)
No
Comply with the following:
Standard
§60.48b(h)
Monitoring/Testing
[T][G]§60.46b(f)(1)
Comply with the following:
Monitoring/Testing
§60.46b(f)(2)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
67
Yes
No
Does the
affected facility
combust residual oil with a nitrogen
content < 0.30 weight
percent?
Comply with the following:
Monitoring/Testing
§60.49b(e)
Recordkeeping
§60.49b(e)
Reporting
§60.49b(q)(2)
68
§60.49b(e)
Yes
72
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(59 of 67)
Is the affected
facility electing to conduct
the performance test per
§60.46b(f)(1)?
§60.46b(f)(1)
Comply with the following:
Standard
§60.48b(h)
Monitoring/Testing
[T][G]§60.46b(f)(1)
Comply with the following:
Monitoring/Testing
§60.46b(f)(2)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
69
Is the
residual oil sampled
and analyzed for nitrogen
content as specified in
§60.49b(e)?
Comply with the following:
Monitoring/Testing
§60.46b(e)(4)
§60.49b(e)
Recordkeeping
§60.49b(e)
Comply with the following:
Monitoring/Testing
§60.46b(e)(2)
§60.49b(e)
§60.46b(e)(5)
No
Does the
residual oil have a nitrogen
content greater than 0.30 %
by weight?
§60.46b(e)(2)
No Yes
YesNo
Yes 72
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
70
Does
the affected facility
have a heat input of 250
MMBtu/hr or
less?§60.46b(e)(4)
Does the
affected facility use
a CEMS?
§60.46b(e)
Comply with the following:
Monitoring/Testing
[T]§60.46b(e), [T](e)(1), (e)(3)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f)
Recordkeeping
[G]§60.48b(b), (c)
[G]§60.49b(g)
Reporting
§60.49b(h), (i), (v), (w)
No
Comply with the following:
Monitoring/Testing
[T]§60.46b(e), [T](e)(1), (e)(4)
[G]§60.48b(b), (c)-(e)
[G]§60.48b(e)(2), (e)(3), (f), (g)(1)
§60.49b(e)
Recordkeeping
[G]§60.48b(b), (c)
§60.49b(e), [G](g)
Reporting
§60.49b(h), (h)(4), (i), (v), (w)
Comply with the following:
Monitoring/Testing
§60.48b(g)(2)
Recordkeeping
[G]§60.49b(c), [G](g)
Reporting
[G]§60.49b(c), (h), (v), (w)
Yes
No
Yes
72
40 CFR Part 60, Subpart Db(60 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Comply with the following:
Monitoring/Testing
§60.49b(e)
Recordkeeping
§60.49b(e)
Does the
affected facility combust
residual oil?
§60.49b(e)
No
Yes
71
72
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
40 CFR Part 60, Subpart Db(61 of 67)
Is the affected facility
a coal-fired unit with a heat input
capacity > 250 MMBtu/hour and meet the
applicability requirements of 40 CFR
Part 60, Subpart D?
Yes
§60.40b(b)(2)
No
72
Is the affected facility
an oil-fired unit with a heat input
capacity > 250 MMBtu/hour and meet the
applicability requirements of 40 CFR
Part 60, Subpart D?
§60.40b(b)(4)
Yes 73
No
Does the affected
facility meet the applicability
requirements of 40 CFR Part
60, Subpart J?
§60.40b(c)
Yes 76End No
74
40 CFR Part 60, Subpart Db(62 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Is the affected
facility the Southwestern
Public Service Company's
Harrington Station #1, in
Amarillo?
73
§60.42(b)(1)
Comply with the following:
Standard
§60.42(b)(1)
Monitoring/Testing
§60.45(g), (g)(1)(i)
[T]§60.46(a), [T](b)(3)
Reporting
§60.45(g)
74
Comply with the following:
Standard
§60.42(a)(1)
Monitoring/Testing
[T]§60.46(a), [T](b)(1), [T][G](b)(2)
[T][G]§60.46(d)(1), [T](d)(2)
[T][G]§60.46(d)(3), [T](d)(6)-(7)
Comply with the following:
Standard
§60.42(a)(2)
Monitoring/Testing
§60.45(g), (g)(1)
[T]§60.46(a), [T](b)(3)
Reporting
§60.45(g)
Comply with the following:
Monitoring/Testing
§60.45(a), (c), (c)(5)
Is the
affected facility
combusting fossil fuel
and nonfossil
fuel?§60.45(c)(5)
Comply with the following:
Monitoring/Testing
§60.45(a), (c), (c)(3)
Yes
PM(Opacity)
No
NoYes
All of the following
requirements have been
taken from 40 CFR Part
60, Subpart D
PM
40 CFR Part 60, Subpart Db(63 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
74
§60.45(b)(1)
Is
the affected
facility combusting only
gaseous fossil
fuel?
Is
the affected
facility combusting liquid
fossil fuel or liquid fossil fuel
and wood residue?
No
§60.43(a)(1)
Yes
75
Comply with the following:
Standard
§60.43(a)(1)
Monitoring/Testing
[T]§60.46(a), [T](b)(1)
[T][G]§60.46(b)(4), [T][G](d)(1)
[T][G]§60.46(d)(3), [T](d)(4)
[T]§60.46(d)(6)-(7)
Is the
affected facility
combusting solid fossil fuel or
solid fossil fuel and wood
residue?
§60.43(a)(2)
Comply with the following:
Standard
§60.43(a)(2)
Monitoring/Testing
[T]§60.46(a), [T](b)(1)
[T][G]§60.46(b)(4), [T][G](d)(1)
[T][G]§60.46(d)(3), [T](d)(4)
[T]§60.46(d)(6)-(7)
Yes
Yes
Comply with the following:
Standard
§60.43(b)
§60.43(c)
Monitoring/Testing
[T]§60.46(a), [T](b)(1)
[T][G]§60.46(b)(4), [T][G](c)
[T][G]§60.46(d)(1), [T][G](d)(3)
[T]§60.46(d)(4), [T](d)(6)-(7)
No
No
End
All of the following
requirements have been
taken from 40 CFR Part
60, Subpart D
SO2
40 CFR Part 60, Subpart Db(64 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Comply with the following:
Monitoring/Testing
§60.45(a), (c), (c)(1)-(2)
[G]§60.45(e), [G](f)
§60.45(g), (g)(2)(i)
Reporting
§60.45(g)
Yes
75
Does the
fossil fuel-fired steam
generator use a flue gas
desulfurization
device?
§60.45(b)(2)
No
Comply with the following:
Monitoring/Testing
§60.45(b)(2), (b)(4)
Comply with the following:
Monitoring/Testing
§60.45(c)(5)
Is the
affected facility
combusting fossil fuel
and nonfossil
fuel?
§60.45(c)(5)
Comply with the following:
Monitoring/Testing
§60.45(c)(3)-(4)
No
Yes
Is the
affected facility
combusting combinations
of fossil
fuels?§60.45(c)(4)
Comply with the following:
Monitoring/Testing
§60.45(c)(3)
Yes
60D.001
No
End
40 CFR Part 60, Subpart Db(65 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
Does
the facility
include a fuel gas
combustion
device?
76
§60.100(a)
Comply with the following:
Standard
§60.104(a)(1)
§60.104
Monitoring/Testing
§60.105(a), (e)
§60.106(a)
Reporting
§60.105(e)
§60.107(e), (f)
Is an
instrument for
continuous monitoring
and recording of H2S
concentration in
fuel gasses
used?
§60.105(a)(4)
77
78
SO2
All of the following
requirements have been
taken from 40 CFR Part
60, Subpart J.
EndYes
Yes
No
40 CFR Part 60, Subpart Db(66 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09
The flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change. ***
77 78
Comply with the following:
Monitoring/Testing
§60.105(a)(4), (4)(i), (4)(iii)
§60.105(e)(3)(ii)
[G]60.106(e)(1)
Recordkeeping
§60.105(a)(4)
Reporting
§60.105(e)(3)(ii)
Comply with the following:
Monitoring/Testing
§60.105(a)(3), (a)(3)(i)-(iii)
§60.105(e)(3)(i)
§60.106(e)(2)
Recordkeeping
§60.105(a)(3)
Reporting
§60.105(e)(3)(i)
Do the fuel
gas combustion devices
have a common source
of fuel gas?
Do the fuel
gas combustion devices
have a common source
of fuel gas?
Comply with the following:
Monitoring/Testing
§60.105(a)(4)(ii)
Comply with the following:
Monitoring/Testing
§60.105(a)(3)(iv)
Yes
§60.105(a)(4)(ii) §60.105(a)(3)(iv)
Yes
End
No No
40 CFR Part 60, Subpart Db(67 of 67)
12/20/2011 40 CFR Part 60, Subpart Db, Amended 01/28/09