Technical Brochure
LTG Air Diffusers
The Innovation Company
LTG Aktiengesellschaft
Linear air diffusers LDB
Installation in ceilings, walls and sills
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 2 of 27
Technical brochure • Linear air diffusers LDB
LTG Comfort Air Technology
Air Distribution
Air-Water Systems
Air Diffusers
NotesDimensions stated in this brochure are in mm.
Dimensions stated in this brochure are subject to General Tolerances according to DIN ISO 2768-vL.
Length tolerance : ≤1.5 m ± 1.5 mm≥1.5 m ± 2.0 mm
For the outlet grille see the special tolerances specifiedin the drawing.
Straightness and twist tolerances for extruded aluminum profiles according to DIN EN 12020-2.
For punched profiles - LDB 12 and LDB 15 - twice thestraightness and torsion tolerances acc. toDIN EN 12020-2.
The surface finishes meet standard indoor use requirements, i.e. room climate requirements according to DINEN ISO 7730. Other finishesmeeting special use requirements are available on request.
The actual tender documentations are available in wordformat at your local dealership or at www.LTG-AG.com.
Please note!The profiles for our linear diffusers are exclusively de-signed for use asdecoration elements to cover the gapbetween the ceiling and the diffuser. They are not suitablefor use as supporting profiles or fasteners!
Content Page
Product overview 4
General description 5
Diagram for “air only” systems 6
Selection diagram 7
Selection LDB 12/8 and 12/M 8
Dimensions LDB 12/8 and 12/M 9
Border profiles / additional profilesfor LDB 12/8 and 12/M
10
Insertion loss LDB 12/8 and 12/M 11
Selection LDB 20/8 12
Dimensions LDB 20/8 13
Border profiles / additional profilesfor LDB 20/8
14
Insertion loss LDB 20/8 15
Selection LDB 12 and 15 16
Dimensions, border profiles for LDB 12 17
Dimensions, border profiles for LDB 15 18
Selection LDB 50 19
Dimensions, border profiles for LDB 50 20
Installation 21
Accessories 22
Nomenclature, ordering code 27
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 3 of 27
Technical brochure • Linear air diffusers LDB
Air Diffusers for Ceiling Installation
LDB
LDB linear air diffusers with variable settings ensure effective ventilation and opti-
mized air conditions.
Advantages
Comfortable:
High induction air diffusers ensure rapidmixing
of supply and room air to create comfortable
thermal environments
Uniform, optimal purging of the roomwith fresh
air
A pleasant indoor climate thanks to uniform tem-
perature distribution
Quiet: Low-noise air distribution,aerodynamically
optimized inner cylinder contours
Variable:Limitless options for design, colour and
surface appearance, can be perfectly integrated
in all ceilings
Profiles are available in all colour systems (e.g.
RAL , Pantone, …) and can be combined individually
LTG System clean® -unique and ingenious!
Contaminants within the room air like dust,
tobacco smoke, carpet abrasions, dust or oil
vapour deposit around the ceiling and diüfiuser
as a result of entrainment. The LTGSystem
clean®prevents surface staining almost com-
pletely by providing a screen of clean supply
air across the ceiling. Benefits: The costs of
renovation and maintenance are considerably
reduced.
Flexible: Can be adjustedto individual spatial condi-
tions without impeding operation
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 4 of 27
Technical brochure • Linear air diffusers LDBProduct overview
TypeLDB 12/MLTG System clean®
LDB 12/8LTG System clean®
LDB 20/8 LDB 12
Air diffusionIndividuallyadjustable air flow
Individually adjustable air flow, even after installation
Special features
Completely madefrom metal, non-flammable
For high comfort For high comfort For an inconspicuous installation inshaded joints andsuspended ceilingsLTG System clean® to reduce contamina
tion around the diffuser
Profile width [mm] 41…129 31...240 31...240 15 resp. 28
Cylinder Ø [mm] -- 12 20 12
Recommendedair flow rate
at LWA
[m³/hm]
[dB(A)]
1 slot: 702 slots: 1303 slots: 190
30
1 slot: 702 slots: 1303 slots: 1905 slots: 25030
1 slot: 1102slots: 1903 slots: 2504 slots: 30030
65
35
Slot rows 1…3 1...4 1...4 1
Recommendedinstallationheight
[m] from 2,4 from 2,4 from 2,6 from 2,4
Length [mm] up to 2500 up to 2000 up to 2000 up to 1500
Version
Profile surface: untreated aluminium, anodized, painted similar to RAL.The diffusers can alternatively be ordered without air distribution box.
Diffuser elements:natural anodized,painted similar toRAL
Diffuser elements:black, white or aluminium grey, on request in other colours similar to RAL
Accessories For integration in the ceiling, a variety of border and additional profiles is available.
Type LDB 15 LTG System clean® LDB 50
Air diffusion Individually adjustable air flow, even after installation
Special featuresLTG System clean® to reduce contaminationaround the diffuser
For high ceilings and large flow rates
Profile width [mm] 15 resp. 25 100, 200, 300
Cylinder Ø [mm] — 50
Recommendedair flow rate
at LWA
[m³/hm]
[dB(A)]
up to 60
25
1 slot: 3102 slots: 4303 slots: 51038
Slot rows 1 1...3
Recommendedinstallationheight
[m] from 2,4 from 3,5
Length [mm] up to 2000 up to 2100
VersionProfile surface: untreated aluminium, anodized, painted similar to RAL.Diffuser elements: white or aluminium grey, on request in other colours similar to RAL.The diffusers can alternatively be ordered without air distribution box.
Accessories For integration in the ceiling, a variety of border and additional profiles is available.
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 5 of 27
Technical brochure • Linear air diffusers LDBGeneral Description
Product viewsType LDB 12/8 LTG System clean®
Type LDB 12/M LTG System clean®
Type LDB 20/8
Type LDB 12
Type LDB 15 LTG System clean®
Type LDB 50
ApplicationLTG diffusers type LDB are suitable for all kinds of applications, e.g. rooms with:
- high comfort requirements such as offices
- increased heat loads and fresh air requirements suchas labs or conference rooms
- special requirements regarding acoustics such asbroadcasting studios
- constant temperature requirements such as production halls.
LTG diffusers type LDB are perfect for both supply airwith a constant or varying volume flowrateand returnairwith the same diffuser element adjustment.
Installation, positioningLTG diffusers type LDBmay be installed in ceilings, wallsor sills depending on the looks desired, the existing airconditioning system and the intended use. Also availableare diffusers for special requests.
Flexibility regarding the interior design, by ensuring boththe use for an inconspicuous installation and as an eye-catching decoration element.
FunctionThe LTG diffuser type LDB is an adjustable linear diffuserallowing treated air to be distributed precisely within theroom, thus ensuring both highest thermal and acousticcomfort.
The diffuser consists of diffuser elements with an optimized interior and profile contour, mounted in aerodynamically harmonized aluminium frames. Each of thediffuser elements can be adjusted individually, thus permitting a large number of different flowpatterns, varyingfrom a flat ceiling flow to a broad fan jetwith amaximumof 36 micro-jets per meter diffuser length (exc. LDB 15).
These features ensure low air speeds and a rapid reduction of temperature differences within the room, some ofthe basic requirements for agreeable conditions in theoccupied space.
The highly inductive effect produces a stable flowpatternand permits supply air temperatures up to 12 K lowerthan the ambient temperature.
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 6 of 27
Technical brochure • Linear air diffusers LDBSelection
Diagram for “air only” systems
5 6 7 8 9 10 12 14 16 18 20 25 30 50
10
20
30
40
50
60
70
8090100
150
200
4035
1.5 2 3 4 5 6 7 8 9 10 12 14 16
Specific volume flow rate [m3/(hm2)]
Ventilation rate [1/h] based on a room height of 2.75 m
Specificco
olingca
pacity
[W/m
2]
c max
=0.15m/s
c max
=0.18m/s
c max
=0.15m/s
c max
=0.205m/s
c max
=0.25m/s
Use of the diagramBased on the known value, i.e. the specific cooling load,the specific volume flow rate can be calculated by choosing the corresponding temperature and volume flow rateof the supply air dependingon thedesired roomtemperature of 22 or 26 _C respectively.
DIN limits should, however, be observed to avoid draftand other sources of discomfort.
If the ventilation rate is too high, additional means to reduce the cooling load should be considered already during planning (e.g. sun screens etc.).
Example:An office area of 30 m2 (room length 6 m, room width 5m) requires ventilation and cooling.
The desired room temperature is 26 _C.
With a specific cooling capacity of 40 W/m2 andΔt= -10 K, the specific volume flow rate is 12 m3/(hm2).
The supply air required is 360 m3/h.
5m
6 m
Floor area = 30 m2
Room temperature = 26 °CFlow rate = 360 m3/hΔt = -10K
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 7 of 27
Technical brochure • Linear air diffusers LDBSelection
Selection diagram
Flow rate per meter of diffuser [m3/(hm)]
Installationheight[m
m]
10 20 30 40 50 60 70 80 100 200 300 400 500
2
3
4
6
8
10
12
With the volume flow rate known and the installationheight taken into consideration, a quickdecision canbemade regarding the appropriate number of slot rowsand the diffuser type.
Since there usually is a choice of products, the diffusertype that suits the application best may be selected.
Example:Based on the example opposite, a volume flow rate of60 m3/(hm) is obtained. With a room height of 2.75 m,LDB 12/8/1 LTG System cleanR would be perfect, butLDB 20/8/1 might be installed just as well.
Diffuser Type LDB 12/8/1 LTG System cleanR
with a volume flowrate of 60m3/(hm)wasselected.
Example:
5m
6 m
Supply air through linear diffuserLDB 12/8/1 LTG System cleanR
Facade
Return air, e.g. through lamps
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 8 of 27
Technical brochure • Linear air diffusers LDBType LDB 12/8 and 12/M, LTG System cleanR - selection
Selection diagram
20 40 60 80 100
5
10
15
20
50
200
0,512
10
20
H = 2,8 m
h = 1,7 m
- 10
- 6
4030
20 30 40 50 60 80 100 200
15
20
25
30
35
-10∆t [K]
LDB 12/8/1, 12/M/1
- 6
10
20
H = 2,8 m
h = 1,7 m
- 10- 6
- 12LDB 12/8/2, 12/8/3, 12/M/2, 12/M/3
- 3
- 3
- 3
With undisturbed air diffusion
With undisturbed air diffusion
-12
a (cmax) [m]
V [m3/(hm)]
- 12
............... = dimensioning area beyond LTG System clean®
300
300
c max[cm/s] ∆t [K]
∆t [K]
∆p [Pa]
a(cmax) cmax
Legend
V = volume flow rate [m3/(hm)]tzu = supply air temperature [C]tRA = room air temperature [C]Δt = temperature difference
between tzu and tRA [K]Δp = pressure drop [Pa]LWA = sound power level [dB(A)]a(cmax)= extension of jet at which the
maximum speed of the ambientair was measured [m]
cmax = maximum speed of ambient airwith uniformly distributedthermal loads [cm/s]
H = room height [m]h = height of measuring point [m]
Note: The recommended min. distance between twoparallel diffusers should, in case of high temperaturedifferences t, not be less than the value of a (cmax).
The diagrams are based on measuring results with thestandard diffuser element adjustment and a roomheightof 2.8 m.
Example for diagram above
Volume flow rate per meter of diffuser:V = 60 m3/(hm)
Resulting data for type LDB 12/8/1:Δp = 7 PaLWA = 17 dB(A)Δt = -10 Ka(cmax)≈ 1 mcmax ≤ 5 cm/s
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 9 of 27
Technical brochure • Linear air diffusers LDBType LDB 12/8 and LDB 12/M, LTG System cleanR - dimensions
Air distribution boxes
61
d/2
+10
210 1
45 Ød
60
65 LDB 12/8/1
LDB 12/M/1
Profile detailssee next page
*
Ød
61
d/2
+10
265
60
LDB 12/8/2LDB 12/M/2
Profile detailssee next page
*
Ød
92
d/2
+10
250
60
LDB 12/8/3LDB 12/M/3
Profile detailssee next page
*
Air distribution boxes with insulation (double skin box)
91
d/2
+10
225
45
64
1515
Ød
15
LDB 12/8/1LDB 12/M/1
Profile detailssee next page
*
Ød
91
d/2
+10
280
45
67
15
15 15
LDB 12/8/2LDB 12/M/2
Profile detailssee next page
*
Ød
122
d/2
+10
265
45
67
15
15 15
LDB 12/8/3LDB 1/M/3
Profile detailssee next page
*
* Execution: integrated throttle damper DLU at spigot diameters 99...139The values given refer to standard versions.Reduced box sizes and spigot diameters are available on request, depending on volume flow rate and acoustic requirements.
Spigot dimensionsDiffuser length Lnom [mm] 500 750 1000 1250 1500 1750 2000
The given values LWA refer only to the execution without throttle damper resp. with throttle damper open.LDB 12/8/1, example: 70 m3/hm
LWA in dB(A) out of diagram p. 10 (ref. to Lnom) 19 21 22 23 24 24 25
Ø = 79 mm no. of spigots /[correction to diagram in (dB)]standard version highlighted
1 / [-2] 1 / [+3] 2 / [-2] 2 / [0] 2 / [+3] 2 / [+6] 3 / [+1]
Ø = 99 mm 1 / [-4] 1 / [0] 1 / [+5] 2 / [-2] 2 / [0] 2 / [+3] 2 / [+5]
Ø = 124 mm 1 / [-5] 1 / [-3] 1 / [+1] 1 / [+4] 1 / [+7] 2 / [0] 2 / [+1]
LDB 12/8/2, example: 130 m3/hm
LWA in dB(A) out of diagram p. 10 (ref. to Lnom) 24 26 27 28 29 29 30
Ø = 79 mmno. of spigots /[correction to diagram in (dB)]standard version highlighted
1 /[+1] 2 / [-3] 2 / [-1] 2 / [+2] 3 / [-2] 3 / [0] 3 / [+2]
Ø = 99 mm 1 /[-2] 1 / [+2] 2 / [-2] 2 / [-1] 2 / [0] 2 / [+3] 3 / [-1]
Ø = 124 mm 1 / [-3] 1 / [-2] 1 / [0] 2 / [-3] 2 / [-3] 2 / [-1] 2 / [-1]
Ø = 139 mm 1 / [-3] 1 / [-3] 1 / [-1] 1 / [+2] 2 / [-3] 2 / [-2] 2 / [-2]
LDB 12/8/3, example: 190 m3/hm
LWA in dB(A) out of diagram p. 10 (ref. to Lnom) 22 24 25 26 27 27 28
Ø = 99 mmno. of spigots /[correction to diagram in (dB)]standard version highlighted
1 / [+4] 2 / [0] 2 / [+4] 3 / [+2] 3 / [+4] 4 / [+3] 4 / [+4]
Ø = 124 mm 1 / [0] 1 / [+5] 2 / [0] 2 / [+2] 2 / [+5] 3 / [+2] 3 / [+3]
Ø = 139 mm 1 / [-1] 1 / [+2] 1 / [+6] 2 / [0] 2 / [+2] 2 / [+4] 3 / [+1]
Ø = 159 mm 1 / [-1] 1 / [0] 1 / [+1] 1 / [+3] 2 / [0] 2 / [+1] 2 / [+1]
Example: LWA = LWA (out of diagram in page 9) + [correction value],LDB 12/8/3, length 1500 mm, 2 x Ø 139, LWA = 27 dB(A) + 2 dB = 29 dB(A)
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 10 of 27
Technical brochure • Linear air diffusers LDBType LDB 12/8 and LDB 12/M, LTG System cleanR - accessories
Various border and additional profiles are available forLTG linear diffusers series LDB and LDB LTG SystemcleanR ensuring a perfect integration in and adaptationtoall kindsof ceiling systems. Thus, both an inconspicous
installation of the diffuser and its use as an interior design element are possible. Profiles may also be used incombination with each other.
Border profiles for type LDB 12/8 LTG System clean® (more border profiles see page 14)
Border profile for installation in ceiling joints (max. length 1250 mm)
LDB 12/8/1/55 LDB 12/8/2/55 LDB 12/8/3/55
Border profile for combination with additional profiles
LDB 12/8/1/00 LDB 12/8/2/00 LDB 12/8/3/00Border profile for covering ceiling joints
LDB 12/8/1/88 LDB 12/8/2/88 LDB 12/8/3/88Border profile for covering ceiling joints
LDB 12/8/1/11 LDB 12/8/2/11 LDB 12/8/3/11
Border profiles for type LDB 12/M LTG System cleanR
Border profile for combination with additional profiles
41
27
72 103
LDB 12/M/1/00 LDB 12/M/2/00 LDB 12/M/3/00Border profile for covering ceiling joints
48
271,5
79 110
LDB 12/M/1/88 LDB 12/M/2/88 LDB 12/M/3/88Border profile for covering ceiling joints
129
LDB 12/M/3/11
Additional profiles for type LDB 12/8 and 12/M, LTG System cleanR
Additional profile 2 Additional profile 7 (installation adjacent to lamps)
LDB 12/8/1/00/22 LDB 12/8/1/00/7-
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 11 of 27
Technical brochure • Linear air diffusers LDBType LDB 12/8 and 12/M, LTG System clean® - with sound absorber
Insertion loss / end reflection factorThe cross-talk sound transmission via air ducts betweenadjacent rooms is a sound flanking path which might reduce the sound insulation of partition walls or suspendedceilings.
DIN 4109 or customer agreements set minimum soundinsulation requirements for partition walls in terms of aweighted sound reduction index R'w.
Sound insulation indicesmay be calculated in terms of asound pressure level difference with known ceiling surface S and the equivalent absorption surface A of the receiving room:
L = R L- 10 lg (S/A)
When assessing the sound pressure level difference inthe air duct between the source and receiving room, calculation must be in the frequency bands (compareVDI 2081, Pages 1, 2, and LTG selection program). Therefore, for cross-talk sound absorbersmanufacturers' frequency-dependent insertion loss indices will have to beused. For air diffusers, the insertion loss/end reflectionof the air diffusers according to DIN EN ISO 7235 is decisive.
The following decision must be made:
1. no cross-talk sound absorber required
2. soundabsorber integrated in theair diffuser required
3. additional packaged attenuator of length x required
Through loss data of the air diffusers are determined asfollows:
Dt = Di + Dtd
Di air diffuser insertion loss index
Dtd theoretical end reflection at the open end of astraight, solid duct (duct end reflection) fromequation B3 in DIN EN ISO 7235
Insertion loss /end reflection factor Dt
Octave[Hz]
Dt without sound trap[dB]
LDB12/8/1
LDB12/8/2
LDB12/8/3
LDB12/8/4
63 25 22 19 21
125 16 17 14 15
250 8 6 7 5
500 12 8 8 8
1000 12 7 9 7
2000 9 5 5 4
4000 6 5 6 5
8000 6 5 4 4
Octave[Hz]
Dt with sound trap[dB]
LDB12/8/1
LDB12/8/2
LDB12/8/3
LDB12/8/4
63 25 22 19 21
125 16 17 14 15
250 18 12 11 9
500 22 18 16 15
1000 24 19 15 13
2000 19 15 12 10
4000 20 13 13 11
8000 18 11 11 9
Dimensions air distribution box with sound absorber (melamine resin foam)
LDB 12/8/1/00with air distribution boxand throttling device DLU
180
60
132 60
40.6
240
d/2+10
Ød
LDB 12/8/2/00with air distribution boxand throttling device DLU
60
Ød
240
d/2+10
71.6
132
60180
LDB 12/8/3/00with air distribution boxand throttling device DLU
60
Ød
240
d/2+10
102.6
162
180
60
LDB 12/8/4/00with air distribution boxand throttling device DLU
60
Ød
240
d/2+10
192
180
60
134
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 12 of 27
Technical brochure • Linear air diffusers LDBType LDB 20/8 - Selection
Selection diagram
20 40 60 80 100
5
10
15
20
50
200
0.512Δp
[Pa]
10
20
10
H = 2.8 m
h = 1.7 m
- 10
∆t [K]
- 6
4030
20 30 40 50 60 80 100 200
15
20
25
30
-10∆t [K]
LDB 20/8/1 ./8/2
- 6
10
20
H = 2.8 m
h = 1.7 m
∆t [K]
- 6
- 3
- 3
- 3
35
- 8
a (cmax) [m]
V [m3 /(hm)]
- 10
LDB 20/8/3 and ./8/4
300
300
with undisturbed air diffusion
with undisturbed air diffusion
c max[cm/s]
a(cmax) cmax
LegendV = volume flow rate [m3/(hm)]tzu = supply air temperature [C]tRA = room air temperature [C]Δt = temperature difference
between tzu and tRA [K]Δp = pressure drop [Pa]LWA = sound power level [dB(A)]a(cmax)= extension of jet at which the
maximum speed of the ambientair was measured [m]
cmax = maximum speed of ambient airwith uniformly distributedthermal loads [cm/s]
h = height of measuring point [m]H = room height [m]
The recommended min. distance between two paralleldiffusers should, in case of high temperature differencest, not be less than the value of a(cmax).The diagrams are based on measuring results with thestandard diffuser element adjustment and a roomheightof 2.8 m.
Example for diagram above
Volume flow rate per meter of diffuser:V = 90 m3/(hm)Resulting data for type LDB 20/8/1:Δp = 10 PaLWA = 28 dB(A)Δt = -10 Ka(cmax)≈ 1.4 mcmax ≤ 18 cm/s
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 13 of 27
Technical brochure • Linear air diffusers LDBType LDB 20/8 - dimensions
Air distribution boxesØd
61
d/2
+10
210
60
145
65 LDB
20/8/1/00
*
Ød
61
d/2
+10
265
60
LDB20/8/2/00
*
Ød
92
d/2
+10
250
60
LDB20/8/3/00
*
LDB20/8/4/00
Ød
123
d/2
+10
235
60
*
Air distribution boxes with insulation (double skin box)
91 45
Ød
d/2
+10
225
64
15 15
15
LDB20/8/1/00
*
Ød
91
280
4515
15 15
d/2
+10
67
LDB20/8/2/00
*
Ød
122265
45
15 15
d/2
+10
67
15
LDB20/8/3/00
*
Ød
153
250
45
15 15
d/2
+10
67D
15
LDB20/8/4/00
*
* Execution: integrated throttle damper DLU at spigot diameters 99 ... 139The values given refer to standard versions.Reduced box sizes and spigot diameters are available on request, depending on volume flow rate and acoustic requirements.D For the double skin box LDB 20/8/4 and a spigot diameter of 160, it is 52 mm instead of 67 mm
Spigot dimensions
Diffuser length Lnom [mm] 500 750 1000 1250 1500 1750 2000The given values LWA refer only to the execution without throttle damper resp. with throttle damper open.LDB 20/8/1, example: 90 m3/hm
LWA in dB(A) out of diagr. p. 15 (ref. to Lnom) 26 28 29 30 31 31 32
Ø = 79 mm no. of spigots /[correction to diagram in (dB)]standard version highlighted
1 / [+1] 2 / [0] 2 / [+1] 2 / [+2] 3 / [0] 3 / [+2] 4 / [+1]
Ø = 99 mm 1 / [0] 1 / [+2] 2 / [0] 2 / [+1] 2 / [+1] 2 / [+1] 3 / [+1]
Ø = 124 mm 1 / [0] 1 / [0] 1 / [+2] 2 / [0] 2 / [0] 2 / [+2] 2 / [+2]
LDB 20/8/2, example: 150 m3/hm
LWA in dB(A) out of diagr. p. 15 (ref. to Lnom) 27 29 30 31 32 32 33
Ø = 79 mmno. of spigots /[correction to diagram in (dB)]standard version highlighted
1 / [+1] 2 / [-2] 2 / [0] 3 / [-2] 3 / [-1] 3 / [+1] 4 / [-1]
Ø = 99 mm 1 / [-1] 2 / [-3] 2 / [-2] 2 / [-1] 3 / [-2] 3 / [-1] 3 / [-1]
Ø = 124 mm 1 / [-2] 1 / [-2] 1 / [+1] 2 / [-2] 2 / [-2] 2 / [-1] 2 / [0]
Ø = 139 mm 1 / [-2] 1 / [-2] 1 / [0] 2 / [-2] 2 / [-2] 2 / [-1] 2 / [-1]
LDB 20/8/3, example: 210 m3/hm
LWA in dB(A) out of diagr. p. 15 (ref. to Lnom) 27 29 30 31 32 32 33
Ø = 99 mmno. of spigots /[correction to diagram in (dB)]standard version highlighted
1 / [+1] 2 / [-4] 2 / [+1] 3 / [-2] 3 / [+1] 4 / [-1] 4 / [+1]
Ø = 124 mm 1 / [-5] 1 / [+2] 2 / [-5] 2 / [-2] 2 / [+2] 3 / [-2] 3 / [0]
Ø = 139 mm 1 / [-6] 1 / [-2] 1 / [+3] 2 / [-4] 2 / [-2] 2 / [+1] 3 / [-4]
Ø = 159 mm 1 / [-7] 1 / [-6] 1 / [-3] 1 / [0] 2 / [-6] 2 / [-4] 2 / [-3]
LDB 20/8/4, example: 260 m3/hm
LWA in dB(A) out of diagr. p. 15 (ref. to Lnom) 27 29 30 31 32 32 33
Ø = 124 mm no. of spigots /[correction to diagram in (dB)]standard version highlighted
1 / [+1] 2 / [-1] 2 / [+1] 3 / [0] 3 / [+1] 4 / [0] 4 / [+1]
Ø = 139 mm 1 / [0] 1 / [+3] 2 / [0] 2 / [+1] 3 / [-1] 3 / [+1] 4 / [0]
Ø = 159 mm 1 / [-1] 1 / [0] 1 / [+2] 2 / [-1] 2 / [0] 2 / [+1] 3 / [-1]
Example: LWA = LWA (out of diagram in page 15) + [correction value],LDB 20/8/2, length = 1000 mm, 2 x Ø 99, LWA = 30 dB(A) - 2 dB = 28 dB(A)
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 14 of 27
Technical brochure • Linear air diffusers LDBType LDB 20/8 - additional profiles, border profiles
Various border and additional profiles are available forLTG linear diffusers type LDB and LDB LTG SystemcleanR ensuring a perfect integration in and adaptation
to all kinds of ceiling systems. Thus, both an inconspicuous installation of the diffuser and its use as an interiordesign element are possible. Profilesmay alsobe used incombination with each other.
Additional profiles
Additional profile 2 Additional profile 7 (installation adjacent to lamps)
LDB 20/8/1/00/22 LDB 20/8/1/00/7-
Border profiles
Border profile for installation in ceiling joints
LDB 20/8/1/55 LDB 20/8/2/55 LDB 20/8/3/55 LDB 20/8/4/55
Border profile for combination with additional profiles
LDB 20/8/1/00 LDB 20/8/2/00 LDB 20/8/3/00 LDB 20/8/4/00
Border profile for covering ceiling joints
LDB 20/8/1/88 LDB 20/8/2/88 LDB 20/8/3/88 LDB 20/8/4/88
Border profile for covering ceiling joints
LDB 20/8/1/11 LDB 20/8/2/11 LDB 20/8/3/11 LDB 20/8/4/11
Border profile for ceiling panels and adjacent to lamps
LDB 20/8/1/44 LDB 20/8/2/44 LDB 20/8/3/44 LDB 20/8/4/44
Border profile for ceiling panels
LDB 20/8/1/22 LDB 20/8/2/22 LDB 20/8/3/22 LDB 20/8/4/22
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 15 of 27
Technical brochure • Linear air diffusers LDBType LDB 20/8 - with sound absorber
Insertion loss / end reflection factorThe cross-talk sound transmission via air ducts betweenadjacent rooms is a sound flanking path which might reduce the sound insulation of partition walls or suspendedceilings.
DIN 4109 or customer agreements set minimum soundinsulation requirements for partition walls in terms of aweighted sound reduction index R'w.
Sound insulation indicesmay be calculated in terms of asound pressure level difference with known ceiling surface S and the equivalent absorption surface A of the receiving room:
ΔL = RL- 10 lg (S/A)
When assessing the sound pressure level difference inthe air duct between the source and receiving room, calculation must be in the frequency bands (compareVDI 2081, pages 1, 2, and LTG selection program). Therefore, for cross-talk sound absorbersmanufacturers' frequency-dependent insertion loss indices will have to beused. For air diffusers, the insertion loss/end reflectionof the air diffusers according to DIN EN ISO 7235 is decisive.
The following decision must be made:
1. no cross-talk sound absorber required
2. soundabsorber integrated in theair diffuser required
3. additional packaged attenuator of length x required
Through loss data of the air diffusers are determined asfollows:
Dt = Di + Dtd
Di air diffuser insertion loss index
Dtd theoretical end reflection at the open end of astraight, solid duct (duct end reflection) fromequation B3 in DIN EN ISO 7235
Insertion loss / end reflection factor Dt
Octave[Hz]
dt without sound trap[dB]
LDB20/8/1
LDB20/8/2
LDB20/8/3
LDB20/8/4
63 25 22 19 21
125 16 17 14 15
250 8 6 7 5
500 12 8 8 8
1000 12 7 9 7
2000 9 5 5 4
4000 6 5 6 5
8000 6 5 4 4
Octave[Hz]
Dt with sound trap[dB]
LDB20/8/1
LDB20/8/2
LDB20/8/3
LDB20/8/4
63 25 22 19 21
125 16 17 14 15
250 18 12 11 9
500 22 18 16 15
1000 24 19 15 13
2000 19 15 12 10
4000 20 13 13 11
8000 18 11 11 9
Dimensions air distribution box with sound absorber (melamine resin foam)
LDB 20/8/1/00with air distribution boxand throttling device DLU
132 60
d/2+10
180
240
60
ød
LDB 20/8/2/00with air distribution boxand throttling device DLU
60
ød
240
d/2+10
180
60
132
LDB 20/8/3/00with air distribution boxand throttling device DLU
60
ød
240
d/2+10
60180
162
LDB 20/8/4/00with air distribution boxand throttling device DLU
60
ød
240
d/2+10
60180
192
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 16 of 27
Technical brochure • Linear air diffusers LDBType LDB 12 and LDB 15 LTG System clean® – selection
Selection diagram
20 40 60 80 100
5
10
15
20
50
200
0,512
10
20
H = 2,8 m
h = 1,7 m
- 10
- 6
4030
20 30 40 50 60 80 100 200
15
20
25
30
35
-10∆t [K]
LDB 12
- 6
- 3
- 3with undisturbed air diffusion
10
20
H = 2,8 m
h = 1,7 m
- 10
∆t [K]
LDB 15
- 6
with undisturbed air diffusion
-12
a (cmax) [m]
V [m3/(hm)]
- 3
- 12
- 12
............... = dimensioning area beyond LTG System clean®
300
300
c max[cm/s] ∆t [K]
∆p [Pa]
a(cmax) cmax
Legend
V = volume flow rate [m3/(hm)]tzu = supply air temperature [C]tRA = room air temperature [C]Δt = temperature difference
between tzu and tRA [K]Δp = pressure drop [Pa]LWA = sound power level [dB(A)]a(cmax)= extension of jet at which the
maximum speed of the ambientair was measured [m]
cmax = maximum speed of ambient airwith uniformly distributedthermal loads [cm/s]
H = room height [m]h = height of measuring point [m]
Note: The recommended min. distance between twoparallel diffusers should, in case of high temperaturedifferences Δt, not be less than the value of a (cmax).
The diagrams are based on measuring results with thestandard diffuser element adjustment and a roomheightof 2.8 m.
Example for diagram above
Volume flow rate per meter of diffuser:V = 60 m3/(hm)
Resulting data for type LDB 15/-/1:Δp = 10 PaLWA = 25 dB(A)Δt = -10 Ka(cmax)≈ 1 mcmax ≤ 15 cm/s
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 17 of 27
Technical brochure • Linear air diffusers LDBType LDB 12 - dimensions and accessories border profiles
Air distribution box without insulation Air distribution box with insulation (double skin box)
96
121
15
45126
151
LDB 12/-/1/00 LDB 12/-/1/00
The values given refer to standard versions. Reduced box sizes and spigot diameters are available on request, depending on volumeflow rate and acoustic requirements. *) Neck lengths 45 to 80 mmSpecial dimensions on request.
Spigot dimensions Diffuser length Lnom [mm]* 500 750 1000 1250
LDB 12 Ø d [mm] 1 x 99 1 x 99 1 x 99 2 x 99
Border profiles (length max. 1250 mm)
LDB 12/-/1/00
Profile for inconspicuous installation inshaded joints
Profile for covering ceiling joints
Profile for lamps, suitable for lampborders of 6...7 mm
LDB 12/-/1/11
LDB 12/-/1/20
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 18 of 27
Technical brochure • Linear air diffusers LDBType LDB 15 LTG System cleanR - dimensions, border profiles
Air distribution box without insulation Air distribution box with insulation (double skin box)
96
121
126
15
45
151
LDB 15/0/1/00 LDB 15/0/1/00
The values given refer to standard versions. Reduced box sizes and spigot diameters are available on request, depending on volumeflow rate and acoustic requirements. *) Neck lengths 45 ... 80 mm
Spigot dimensions Length of diffuser LNom [mm]* 500 750 1000 1250 1500 1750 2000
LDB 15 Ø d [mm] 1x99 1x99 1x99 2x99 2x99 2x99 2x99
Border profiles
LDB 15/0/1/00Profile for inconspicuous installation inshaded joints
LDB 15/1/1/11 Profile for covering ceiling joints
LDB 15/0/1/20Profile for lamps, suitable for lampborders of 6...7 mm
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 19 of 27
Technical brochure • Linear air diffusers LDBType LDB 50 - selection
Selection diagram
200 400
5
10
15
20
50
800
11.524
Δp
[Pa]
10
20
H = 5 m
h = 1.7 m
- 10∆t [K]
- 6
4030
20
25
30
-10∆t [K]
LDB 50/-/1
- 6
10
20 H = 5 m
h = 1.7 m
35
300100 600
200 400 800300 600100
40
45
5 3
11,5245 3
- 8- 6 LDB 50/-/2
amin [m]
V [m3 /(hm)]
∆t [K] LDB 50/-/3- 6
- 4
- 4
with undisturbed air diffusion
with undisturbed air diffusion
1200
1200
a (cmax) [m]
c max[cm/s]
a(cmax) cmax
Legend
V = volume flow rate [m3/(hm)]tzu = supply air temperature [C]tRA = room air temperature [C]Δt = temperature difference
between tzu and tRA [K]Δp = pressure drop [Pa]LWA = sound power level [dB(A)]a(cmax)= extension of jet at which the
maximum speed of the ambientair was measured [m]
cmax = maximum speed of ambient airwith uniformly distributedthermal loads [cm/s]
H = room height [m]h = height of measuring point [m]
Note: The recommendedmin. distance between two parallel diffusers should, in case of high temperature differences Δt, not be less than the value of a (cmax).
The diagrams are based on measuring results with thestandard diffuser element adjustment, a room height of5m and a uniform load distribution. For an optimized airflow, an adaptationmaybe requiredaccording toproject.
Example for diagram above
Volume flow rate per meter of diffuser:V = 360 m3/(hm)Resulting data for type LDB 50/-/1:Δp = 26 PaLWA = 41 dB(A)Δt = -10 Ka(cmax)≈ 4.4 mcmax ≤ 24 cm/s
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 20 of 27
Technical brochure • Linear air diffusers LDBType LDB 50 - dimensions, additional profile
Dimensions of air distribution boxes
201
241
201
241
321
241
LDB 50/–/1/00 LDB 50/–/2/00 LDB 50/–3/00
Dimensions of air distribution boxes with insulation (double skin box)
231
326
201
241
1545 231
326
201
241
1545 351
326
321241
1545
LDB 50/–/1/00 LDB 50/–/2/00 LDB 50/–/3/00
The values given refer to standard versions. Reduced box sizes and spigot diameters are available on request, depending on volumeflow rate and acoustic requirements. *) Neck length 70 ... 170 mm
Spigot dimensions Additional profile
Diffuser length Lnom[mm]*
300 600 900 1200 1500 1800 2100
LDB 50/-/1(1 slot row)
Ø d1x199
1x199
2x199
2x199
3x199
3x199
3x199
LDB 50/-/2(2 slot rows)
Ø d1x199
1x199
2x199
2x199
3x199
3x199
4x199
LDB 50/-/3(3 slot rows)
Ø d1x199
1x199
2x199
2x199
3x199
3x199
4x199
*) We recommend to choose large spigot and duct diameters to obtain thelowest possible duct speed as this will result in lower pressure losses and lessnoise caused by the flow. Due to an improved air distribution, the system can dowithout some of the additional units usually required such as throttle valves.
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 21 of 27
Technical brochure • Linear air diffusers LDBInstallation
Distance between parallel linear diffusers and to wallsAn unfavorable arrangement of linear diffusers in parallel lines or close to walls may result in air flow speedshigher than those given in the technical specifications.
In order to avoid this problem:
- ensure that the distance between parallel linear diff-users is sufficiently large to exclude any interaction,
- ensure that air jets are mixed above the occupied zone(e.g. at a height of 1.8 m).
Based on these requirements, the two areas marked inFigure 1 are obtained indicating the recommended distance b between parallel linear diffusers.
For an installation parallel to walls, at least half the distance (b/2) is required.
b/2 b
0 0.5 1 1.5 2 2.5 3 3.5 40
1
2
3
4
5
6
Jet penetration depth a(cmax) [m]
Distance
b[m
]
Figure 1:Distance between parallel diffusers with a symmetric air flowpattern
Example
From theselection diagram: a(cmax) = 1.1 m
Recommended distancebetw. parallel diffusers: 1.1 m < b < 1.9 m or b > 2.9 m
recommended distanceto the wall: b/2 > 0.55 m
All linear diffusers also allow an asymmetric splitting ofthe air volume in a 1/3 to 2/3 ratio.
The recommended distances b1/3 and b2/3 betweenparallel diffusers are illustrated in Figure 2. For the jetpenetration depth a(cmax) refer to the selection diagramsfor a symmetric distribution.
0 0.5 1 1.5 2 2.5 30
1
2
3
4
5
0
2
4
6
8
10
Distance
b1/3
[m]
Distance
b2/3
[m]
Jet penetration depth a(cmax) [m]
b1/3/2 b2/3 b1/3 b2/3/2
Figure 2:Distance between parallel diffusers with an asymmetric airflow pattern (1/3 to 2/3).
Example
From theselection diagram: a(cmax) = 1.1 m
Recommended distancebetween parallel diffusers:1/3-share: 0.8 m < b1/3 < 1.4 m or b1/3 > 2.4 m2/3-share: 1.6 m < b2/3 < 2.8 m or b2/3 > 4.8 m
Recommended distanceto the wall:1/3-share: b1/3/2 > 0.4 m2/3-share: b2/3/2 > 0.8 m
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 22 of 27
Technical brochure • Linear air diffusers LDBAccessories - throttling device type DLU
Pressure drop and acoustic level DLU Ø 99
Flow rate [m3/h]
Additionalstaticpress
ure
drop[Pa]
40 60 80 100 120 140 160 1802002
4
6810
20
40
6080100
200
20
25
30
40
35
90°
45°
60°
75°
Pressure drop and acoustic level DLU Ø 124
2
4
6810
20
40
6080100
200
Flow rate [m3/h]
60 80 100 120 140 160 180 200 220240
90°
45°
60°
75°
2025
30
40
35
Additionalstaticpress
ure
drop[Pa]
The throttle damper type DLU consistsof a damper blade out of galvanizessteel sheet, integrated in the air distribution box. It is adjustable through thediffuser.
For an acoustic dimensioning, thesound sources must be summedlogarithmically when using thrott-ling devices in combination withlinear diffusers.
Pressure drop and acoustic level DLU Ø 139
2
4
6810
20
40
6080100
200
Flow rate [m3/h]
80 100 120 140 160 180 220 240
90°
45°
60°
75°
20
25
30
40
35
200
Additionalstaticpress
ure
drop[Pa]
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 23 of 27
Technical brochure • Linear air diffusers LDBAccessories - throttling devices type KLA and KLU
* other dimensions on request
2 x d *
Ød
41
61
d/2
+10
210
2 x d *
Ød
41
61
d/2
+10
210
Type KLA, Type KLU,adjustable from outside the duct adjustable through the diffuser
The throttling damper typeKLAandKLUare manually adjustable devices forconnection to the air distribution box.The damper blades are made ofperforated plate available with variousfree areas to suit throttlingrequirements. Type KLA is adjustablefrom outside the duct on the pivotspindle. Type KLU is adjustable throughthe diffuser.
For an acoustic dimensioning, thesound sources must be summed logarithmically when using throttling devices in combination with linear diffusers.
Pressure drop and acoustic level KLA, KLU
0.3 0.5 1 1.5 2 3 4 52
5
10
20
50
100
200
10 20 30 40 50 60 70 80 100 120
Ø d 139
Ø d 199
20 30 40 50 60 70 80 100 120 160 200Ø d 124
30 40 50 60 80 100 125 150 200 300 350Ø d 159
20 30 40 50 60 80 100 120 160 200 250
40 60 80 100 125 150 200 250 300 400 550
Ø d 99
+ 2 dB
+ 3 dB
+ 6 dB
+ 4 dB
90°/55°
60°/40°
45°/30°
30°/20°
Air velocity within spigot [m/s]
Flow rate [ m3/h]
Sound power level +/- 3 dB
Additionalstaticpress
ure
drop[Pa]
15
35
30
25
20
40
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 24 of 27
Technical brochure • Linear air diffusers LDBAccessories for installation of lamps
LTG has developed special border profiles for theapplication of linear diffusers in combination with lamps.Awide variety of lampbrandsandstyles can beusedwiththe linear diffusers. The installation of the diffuser isperformed by screw connections. In order to make the
installation even easier, the components are standard,which means that no drilling or adjusting of the lineardiffusers will be required to fit the lamps.Alternatively, the lamps may be integrated in the airdistribution box by using a lamp rail.
LTG linear diffuserstype LDB 12/8/2/12 witha lamp rail integrated inthe air distribution box.
Example for lamp installation using LDB 12/–/1/20
Example for lamp installation using LDB 12/8/1/40/-7
Example for lamp installation, suitable for the followinglinear diffuser types:LDB 12/-/1/20LDB 15/0/1/20LDB 12/8/1/40/-7LDB 20/8/1/40/-7
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 25 of 27
Technical brochure • Linear air diffusers LDBAccessories for suspension
Ø 5
Example for installation of typeLDB 12/8/1/00 with air distribution boxand subsequently “second fix” installedslotted rail
Example for installation of typeLDB 20/8/1/00 with air distribution boxand continuously adjustable springhanger (adjusting range about 3/4 of thelength of the hooked wire)
Example for installation of typeLDB 20/8/2/00 with air distribution boxwithout insulation.The four suspension eyes are includedin the delivery of the narrow box.
11462
90111151
43 57
30
Ø 7
41
50
oblong holes 12.5 x 5
31
17
Example for installationof type LDB 20/8/3/11with fixing brackets for blind attachment
Example for installationof type LDB 20/8/1/00with suspension bracket for blindattachment
Example for installationof blind profiles type LDB 15
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 26 of 27
Technical brochure • Linear air diffusers LDB
Accessories for installation
End capsBy using end caps, a closed frame of linear diffusers is obtained.
25*
1.567
41
17
41
Example:LDB 20/8/1/11 with end cup
Example:LDB 20/8/1/00 with support bracket
Example:LDB 20/8/1/00 with end plate
LDB 20: 15 or 25 mm*LDB 50: 20 mm
LDB 12/8 and 20/8: 4.5 mmLDB 50: 6 mm
* 15mm for border profile 8.25mm for border profile 1
2
4
17
Adjustable
height
asrequired
3
Connecting pieceA flush mounting of the diffusers is achieved by usingconnecting pieces inserted in the guiding grooves of theprofiles.Several linear diffusers may thus be connected to forma continuous line.For linear diffusers with additional profiles, a flushmounting is achievedby using additional overlapprofilesor connecting pins.
Connecting pin when usingadditional profiles
Connecting piece (not possible whenusing additional profiles)
AngleAnglesoffer a perfect solution for the continuous installation of linear diffusers.
L ± 0,5
L±0,5
Angle, Lmin = 250 mm
Displacement in height ± 0.5 mm
The Innovation Company
LTG Aktiengesellschaft
© LTG Aktiengesellschaft • Grenzstraße 7 • 70435 Stuttgart • Germany LDB-eng-TP (10/14)Tel. +49 711 8201-0 • Fax +49 711 8201-720 • [email protected] • www.LTG-AG.comFormer editions are invalid · Subject to technical modifications page 27 of 27
Technical brochure • Linear air diffusers LDBNomenclature, ordering code
LDB 20/8 / 1 / 00 / 1 / E6 EV1 / 2000 / S20 / S / EWB / S / – / SDA / O / B / M(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (15) (16)
(1) Diffuser type LDB 12/ = LDB 12/LDB 12/8 = LDB 12/8LDB 12/M = LDB 12/MLDB 20/8 = LDB 20/8LDB 15 = LDB 15LDB 50 = LDB 50
(2) Number of slots 1...4 = 1…4 slotsLDB 12 / LDB 15 only 1 slot, LDB 12/M only 1…3 slots
(3) Design border profile 0...8 = Left - right(4) Design additional profile – = Without
1, 7 = Left - right(5) Surface additional profile E6 = Anodized, unbrushed
LG = Painted, glossyLM = Painted, matR = UnfinishedX = Special finishB = Coated
(6) Colour border profile .... = RAL-shade = painted... = Anodizing shade = anodized
(7) Diffuser length .... = Diffuser length in mm(8) Flow pattern S12 = 2R2L, ... (for LDB 12/, LDB 12/8, LDB 12/M)
S20 = 3R3L, ...S15 = 3R3L3R, 3L3R3L, ...S50 = 3R3L, ...SX = ... (special version)
(9) Diffuser element colour S = RAL 9011 graphite blackW = RAL 9010 pure whiteG = RAL 9007 grey aluminiumX = RAL .... (special colour, indicate RAL-shade)
(10) End caps – = WithoutEWB = End caps both sidesEWR = End caps right sideEWL = End caps left sideEPB = End plat both sidesEPR = End plate right sideEPL = End plate left side
(11) Plenum box type – = WithoutS = Standard plenum boxD = Double skin plenum boxX = Special plenum boxW = Angle
(12) Sound absorber – = Without sound absorber
S = With sound absorber(13) Connection type – = Without
SDA = Spigot onlyDLU = Throttling device DLUKLA = Throttling device KLAKLU = Throttling device KLU
(14) Diffuser element type O = OpenB = Blind
(15) Suspension for dummydiffuser installation
O = WithoutB = Suspension bracketsDB = Double dummy brackets
(16) Second fix O = Without Second Fix fixingM = With Second Fix fixing
Note: Not all combinations are practicable. In individual cases please contact LTG. 1.Dient zur Identifizierung der letzten Seite
The Innovation Company
LTG Aktiengesellschaft
Product OverviewLTG Air Diffusers
Custom diffusers
LDR and LDB 12M LTG System clean
Step diffuser BLQ
Displacement air diffuser DLD
Displacement air diffuser DLQ
LTG air diffusers for ceiling, wall or floor
Lineardiffuser
LDB LDK-B LDU
LDB LTG System clean LDK-B LTG System clean LDU-W
Swirl-diffuser
DLA
Transfer airdevice
LDO- T
Ceiling Wall Floor
Engineering Services
LTG Engineering Services Comfort Air Technology
The Innovation Company
LTG Aktiengesellschaft
LTG Aktiengesellschaft
Grenzstraße 7
70435 Stuttgart
Germany
Tel.: +49 (711) 8201-0
Fax: +49 (711) 8201-720
E-Mail: [email protected]
www.LTG-AG.com
LTG Incorporated
105 Corporate Drive, Suite E
Spartanburg, SC 29303
USA
Tel..: +1 (864) 599-6340
Fax: +1 (864) 599-6344
E-Mail: [email protected]
www.LTG-INC.net
LDB-eng-TP (10/14) 419-16E LTG Aktiengesellschaft • Former editions are invalid • Subject to technical modifications
Comfort Air Technology
Air-Water Systems
Air Diffusers
Air Distribution
Process Air Technology
Fans
Filtration technology
Humidification Technology
Engineering Services
Air flow tests
Thermodynamics
Acoustics / Comfort
Customised solutions