technical guide description r-410a zh/zj/zr series 3 - 12 ... · the non-corrosive drain pan slides...

208
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 5167795-YTG-O-0120 TECHNICAL GUIDE Description ASHRAE 90.1 COMPLIANT YORK® Sun™ Pro units are convertible single packages with a common footprint cabinet and common roof curb for all 3 through 12.5 ton models. All 6.5 through 12.5 ton units have two compressors with independent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame. All Sun™ Pro units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation. Sun™ Pro units in all tonnage sizes are convertible between side airflow and down airflow, with corresponding economizer if economizer option is desired. Sun™ Pro units are available in the following configurations: cooling only, cooling with electric heat, cooling with gas heat, reheat only, reheat with electric heat and reheat with gas heat. Electric heaters are available as factory-installed options or field-installed accessories. All units provide constant supply air volume. A variable air volume (VAV) option, which features a variable frequency drive (VFD), is available on 6.5 through 12.5 ton ZH/ZJ models only. Tested in accordance with: R-410A ZH/ZJ/ZR SERIES 3 - 12.5 TON 60 Hertz ZH/ZJ/ZR 3 THROUGH 10 TON ZH/ZJ/ZR 12.5 TON

Upload: others

Post on 31-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

5167795-YTG-O-0120

TECHNICAL GUIDE Description

ASHRAE 90.1 COMPLIANT

YORK® Sun™ Pro units are convertible single packages with a common footprint cabinet and common roof curb for all 3 through 12.5 ton models. All 6.5 through 12.5 ton units have two compressors with independent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame.

All Sun™ Pro units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation.

Sun™ Pro units in all tonnage sizes are convertible between side airflow and down airflow, with corresponding economizer if economizer option is desired.

Sun™ Pro units are available in the following configurations: cooling only, cooling with electric heat, cooling with gas heat, reheat only, reheat with electric heat and reheat with gas heat. Electric heaters are available as factory-installed options or field-installed accessories.

All units provide constant supply air volume. A variable air volume (VAV) option, which features a variable frequency drive (VFD), is available on 6.5 through 12.5 ton ZH/ZJ models only.

Tested in accordance with:

R-410AZH/ZJ/ZR SERIES3 - 12.5 TON60 Hertz

ZH/ZJ/ZR 3 THROUGH 10 TON

ZH/ZJ/ZR 12.5 TON

Page 2: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

2 Johnson Controls Ducted Systems

Table of Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138

Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174

Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196

Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207

Component Location

Cooling With Gas Heat (6 Through 10 Ton)

Intelligent control board for safe and efficient

operation

Smart Equipment™ Control board w/screw connectors for T-stat

wiring and Network Connections

Disconnect location (optional disconnect switch)

Filter access (2" or 4”

filter options)

Filter drier (solid core)3-5 Ton Cooling

Slide out motor and blower assembly for

easy adjustment and service

Base rails w/forklift slots

(three sides) and lifting

holes

Toolless door latch

Side entry power and control wiring

knockouts

Belt-drive blower motor

Power ventor motor

20-gauge aluminized steel tubular heat

exchanger for long life (stainless steel option)

One or Two stage gas heating to maintain warm, comfortable

temperatureSlide-out drain pan with 1" NPT connection

Compressor access

Second model nameplate inside hinged access

panel

Roof curbs in eight-andfourteen-inch heights.

Roof curbs for transitioningfrom York Sunline™ footprint

to the ZH/ZJ/ZR Series footprintare available

(field-installed accessory)

Micro-Channel AluminumTube/Aluminum Fin

Condenser(Single Orifice System shown.See Actual Model Physical Data for details)

Filter drier (solid core)3-5 Ton Reheat

Roof curbs in eight- and fourteen-inch heights. Roof curbs for transitioning from York Sunline™ footprint to the ZH/ZJ/ZR Series footprints are also available (field installed accessory)

Base rails w/forklift slots (three sides) and lifting holes

Compressor #2 access

Dual stage cooling for maximum comfort

Second model nameplate inside hinged access panel

Terminal block for hi-voltage connection

Smart Equipment™ control board w/screw connector for T-stat wiring and network connections

Disconnect location (optional disconnect switch)

Filter access (2” or 4” filter options)

Filter drier (solid core)

Slide-out motor andblower assembly for easy adjustmentand service

Belt-driveblower motor

Power ventor motor

20-gauge aluminizedsteel tubular heatexchanger for long life(stainless steel option)

Two-stage gas heating to maintain warm, comfortable temperature

Intelligent control board for safe and efficient operation

Compressor #1 access Toolless door latch

Side entry power and control wiring knockouts

VFD location (optional)

Slide-out drain panwith 1” NPT,female connection

Micro-Channel AluminumTube/Aluminum FinCondenser

Page 3: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 3

Nomenclature

Z H 090 C A 2 A 1 A 1A A 2

Product Category

Z = A/C, Single Pkg., R-410A

B = Standard StaticD = High StaticE = VFD/VAV Std StaticG = VFD/VAV High StaticH = VFD/VAV w/Bypass Std StaticK = VFD/VAV w/Bypass High StaticL = VFD/VAV Customer Std StaticN = VFD/VAV Customer High StaticP = VFD IntelliSpeed Std StaticR = VFD IntelliSpeed High StaticS = VFD w/Byp IntelliSp Std StaticU = VFD w/Byp IntelliSp Hi StaticV = VFD Cust IntelliSp Std StaticX = VFD Cust IntelliSp Hi Static

Blower Option

Product Generation

1 = First Generation2 = Second Generation

C = Cooling OnlyE = Electric Heat

Heat Type

H = 1 Stage Gas Aluminized SteelJ = 1 Stage Gas Stainless SteelK = 1 Stage Low Nox Gas Aluminized SteelL = 1 Stage Low Nox Gas Stainless Steel

03 = 3 KW (037)06 = 6 KW (037,049,061)09 = 9 KW (037,049,061,078,090,102)15 = 15KW (037,049,061)18 = 18 KW (078,090,102,120,150)20 = 20 KW (049,061)24 = 24 KW (061, 078,090,102,120,150)36 = 36 KW (078,090,102,120,150)54 = 54 KW (120,150)

06 = 60 MBH Input (037, 049)08 = 80 MBH Input (037, 049, 061)12 = 120 MBH Input (037, 049, 061, 078, 090, 102)16 = 160 MBH Input (061)18 = 180 MBH Input (078,090,102,120,150)24 = 240 MBH Input (120,150)

Single Stage Natural Gas Heat Options

Heat Capacity

078 = 6.5 Ton

Nominal Cooling Capacity

090 = 7.5 Ton102 = 8.5 Ton

037 = 3 Ton049 = 4 Ton061 = 5 Ton

120 = 10.0 Ton150 = 12.5 Ton

Product Identifier

H = Standard(3-5)/High(6-12) EffJ = Pkg AC High EffR = Standard Eff Reheat

Voltage

2 = 208/230-3-604 = 460-3-605 = 575-3-60

Additional Options

1 = STD Throwaway Filter2 = 2" Pleated Filters (Merv 8)3 = 4" Pleated Filters (Merv 13)4 = Coil Guard (CG), STD Filter5 = 2" Pleated Filter,CG6 = 4" Pleated Filter,CG

A = Std CabinetE = SSD (SST Drain Pan)R = Reverse Drain Pan

A = No EconomizerB = Economizer w/Barometric RLFD = Economizer w/Power EXHH = Motorized Damper

Outdoor Air Option

1 = No Service Options2 = DSC (Disconnect Switch)3 = NCO (Non-PWR Conv. Outlet)4 = PCO (Powered Conv. Outlet)5 = DSC,NCO6 = DSC,PCO

A = No SensorsB = PHM (Phase Monitor)C = DFS (Dirty Filter Switch)D = SSD (Supply Air Smoke DET)E = RSD (Return Air Smoke DET)F = PHM,DFSG = PHM,SSDH = PHM,RSDJ = DFS,SSDK = DFS,RSDL = SSD,RSDM = PHM,DFS,SSDN = PHM,DFS,RSDP = PHM,SSD,RSDQ = DFS,SSD,RSDR = PHM,DFS,SSD,RSD

Refrigeration

A = Standard RefrigerationB = ECC (E-Coat Cond Coil)C = EEC (E-Coat Evap Coil)D = HGBP (Hot Gas Bypass)F = ECC,EECG = ECC,EEC,HGBPJ = ECC,HGBPM = EEC,HGBP

Service Options

A = Stand Alone Smart Equipment™C = BACnet MSTP,Mdbs,N2 COM CardD = CPC Control, DFS, APSG = Novar UCM Ctrl, DFS, APSH = Hnywll Excel 10 CTRL,DFS,APSM = Verasys Single ZoneN = Verasys Change Over BypassP = Verasys VAV

Controls Option

3-12.5 Ton York® Model Number Nomenclature

Two Stage Natural Gas Heat Options

N = 2 Stage Gas Aluminized SteelS = 2 Stage Gas Stainless SteelP = 2 Stage Low Nox Gas Aluminized SteelQ = 2 Stage Low Nox Gas Stainless Steel

00

00 = Cooling Only

Gas MBH Input (Unit Size Allowed)

Electric Heat (Unit Size Allowed)

Sensors

A

Cabinet Options

Page 4: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

4 Johnson Controls Ducted Systems

Features and Benefits

Standard Features

• Service Friendly - The Sun™ Pro incorporates a number of key features for ease of serviceability.

The motor and blower slide out of the unit as a common assembly. This facilitates greater access to all the indoor airflow components, thus simplifying maintenance and adjustment.

Service time is reduced through the use of hinged, toolless panels. Such panels provide access to frequently inspected components and areas, including the control box, compressors, filters, indoor motor & blower, and the heating section. The panels are screwed in place at the factory to prevent access by children or other unauthorized persons. It is recommended that the panels be secured with screws once service is complete.

Service windows have been placed in both condenser section walls. Rotation of the cover allows easy access to the condenser coils for cleaning or inspection.

The Smart Equipment™ control board provides alarm messages to help quickly identify any faults.

All units use four filters of the same standard size. This standardization simplifies selections for filter replacement.

The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing the drain pan cover plate on the rear of the unit. Once the plate is removed, the drain pan slides out through the rear of the unit.

All Sun™ Pro units have a second model nameplate located inside the control access door. This is to prevent deterioration of the nameplate through weathering.

• Coil Technology – All ZH/ZJ condensers utilize Micro-Channel “all-aluminum” condensers which provide improved heat transfer capabilities and reduced charge volumes. All evaporators utilize a conventional copper tube/aluminum fin design for proven reliability and performance. ZR037 thru 061 models utilize Micro- Channel condenser coils, ZR078 thru 150 models utilize copper tube/aluminum fin or Micro-Channel condenser coils. For specific unit model information see Physical Data Tables.

• Environmentally Aware - For improved Indoor Air Quality, a combination of aluminum foil faced and

elastometric rubber insulations are used exclusively throughout the units.

• Balanced Heating - The Sun™ Pro two stage gas heating offers "Ultimate Heating Comfort" with a balance between 1st and 2nd stage gas heating to provide a well maintained desired temperature.

• Convertible Airflow Design – The side duct openings are covered when they leave the factory. If a side supply/return is desired, the installer simply removes the two side duct covers from the outside of the unit and installs them over the down shot openings. No panel cutting is required. Convertible airflow design allows maximum field flexibility and minimum inventory.

• System Protection - Suction line freezestats are supplied on all units to protect against loss of charge and coil frosting when the economizer operates at low outdoor air temperatures while the compressors are running. Every unit has solid-core liquid line filter-driers and high and low-pressure switches. Internal compressor protection is standard on all compressors. Phase Monitors are standard on units with Scroll compressors. This accessory monitors the incoming power to the unit and protects the unit from phase loss and reversed phase rotation.

• Advanced Controls - Smart Equipment™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.

Unit Tonnage 1st. Stage 2nd. Stage

3-5 Ton70 to 75% of Heating

Capacity100% of Heating

Capacity

6.5 - 12.5 Ton60% of Heating

Capacity100% of Heating

Capacity

The Smart Equipment™ control board used in this product will effectively operate the cooling system down to 0°F when this product is applied in a comfort cooling application for people. An economizer is typically included in this type of application. When applying this product for process cooling applications (computer rooms, switchgear, etc.), please call the applications department for Ducted Systems @ 1-877-874-SERV for guidance. Additional accessories may be needed for stable operation at temperatures below 30°F.

Page 5: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 5

• Units will come with the new state of the art Smart Equipment™ control system. The new unit control incorporates the best of the already proven controls and creates a more robust, intelligent control. The goal of this control is to utilize cutting edge technology making the equipment easier to install, operate, and service. All units are Factory commissioned, configured, and run tested.

• Versatile - The Smart Equipment™ control can be configured to use with a standard thermostat (easy to connect screw terminals), A zone sensor, or can be setup to communicate with multiple BAS communication protocols to integrate with building automation systems.

• Reduce field installed complexity - Each unit will comes equipped with factory installed supply air, return air, and outdoor air temperature sensors providing key temperature readings thus reduce field installed complexity.

• On-board USB Port - The new control comes with a long list of features including data logging, current and previous system faults and software update capabilities using the on board USB port and common flash drive. Energy use monitoring capabilities allow custom tailoring to allow a system to work more efficiently at all times and occupancy levels. Self test and start-up reports also available from the board VIA the USB port.

• Embedded LCD Display - The board has a easy to read, built-in LCD display and easy to use navigation joystick and buttons allowing the user to quickly navigate the menus displaying unit status, options, current function, supply, return and outdoor temperatures, fault codes and other information.

• Safety Monitoring - The control monitors the outdoor, supply, and return air temperatures and the high and low pressure switch status on the independent refrigerant circuits. On units with heating the gas valve and high temperature limit switches are monitored on gas and electric heating units. The control also monitors the voltage supplied to the unit and will protect the unit if low

voltage due to a brown out, or other electrical issue occurs.

• Low Ambient - An integrated low-ambient control allows units to operate in the cooling mode down to 0°F outdoor ambient without additional components or intervention. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

• Anti-Short Cycle Protection - To aid compressor life, an anti- short cycle delay is incorporated into the standard control. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti-short cycle delay can be temporarily overridden with the push of a button.

• Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and/or heating capacity.

• Nuisance Trip Protection and Three Strikes - To prevent nuisance calls, the control board uses a three times, you're out philosophy. The high, low-pressure switch, anti-freeze protection, low voltage or heating high limit must trip three times within two hours before the unit control board will lock out the associated compressor.An alarm message will be displayed on the LCD screen.

• Lead-Lag - An integrated Lead-Lag option allows equal run time hours on all compressors, thereby extending the life of all compressors. This option is selectable on the unit control board.

• Low Limit Control (LLC) - To prevent the supply air from dropping below a specified set point, when there is a demand for cooling during cold outside conditions. (Programmable Set point)

• Reliable - From the beginning - All units undergo computer automated testing before they leave the factory. Units are tested for refrigerant charge and pressure, unit amperage, and 100% functionality. For the long term - All units are painted with a long lasting, powder paint that stands up over the life of the unit. The paint used has been proven by a 750-hour salt spray test.

• Full Perimeter Base Rails - The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails offer rigging holes so that an overhead crane can be used to place the units on a roof.

• Easy Installation - Gas and electric utility knockouts are supplied in the unit underside as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. All units are shipped with 2" throw-away filters installed.

• Wide Range of Indoor Airflows - All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/or static pressure requirement.

Page 6: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

6 Johnson Controls Ducted Systems

• Warranty - All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements each carry a 5-year warranty. Aluminized steel (10 yr.) and stainless steel tubular heat exchangers carry a 15- year warranty.

Factory Installed Options

YORK® offers several equipment options factory installed, for the Sun™ Proline.

• Optional Factory Installed Economizers - Sun™ Pro units offer a variety of optional factory installed economizers with low leak dampers. The outdoor air dry bulb sensor enables economizer operation if the outdoor air temperature is less than the set point of the economizer logic module. See economizer options section to determine the correct economizer for your application.

• Down flow / End Return Economizers (with barometric relief and fresh air hood) - All units offer a variety of optional factory installed down flow economizers that are shipped, installed and wired with low leak dampers designed to meet ASHRAE 90.1, AMCA 511 Class 1A damper, and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 CFM/sq. ft. at 1" of static pressure. Each economizer goes through a rigorous 60,000 cycle test. Dry bulb, single enthalpy, and dual enthalpy (with field installed kit) can be selected. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the outdoor air dry bulb temperature or the outdoor air enthalpy input. The optional (field installed) single or dual enthalpy kits provide additional inputs to monitor outdoor air/ or return air humidity and temperature for true enthalpy control. The installer needs only to assemble the outdoor air hood, attach the enthalpy control the hood and mount the hood to the unit (Hood and control are provided).

• Power Exhaust - This factory option allows down flow or horizontal end return economizer operation. The power exhaust must be removed from the unit and mounted in the horizontal end return duct work when applying the product in the horizontal, end return configuration.

• Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry.

• Alternate Indoor Blower Motor - For applications with high static restrictions, units are offered with optional indoor motors that provide higher static output and/or higher airflow, depending upon the installer’s needs.

• Variable Air Volume (VAV; 6.5 through 12.5 ton, only) - A factory-installed variable frequency drive (VFD), mounted in the Blower Access compartment, is used to

control the speed of the indoor blower motor in order to maintain a constant static pressure in the supply duct. A duct pressure transducer is provided with the unit. The drive comes completely wired and pre-programmed from the factory.

An optional, factory-installed manual bypass switch available with factory-installed VFD can be found in the Blower Motor Access compartment. The switch can be used to either route power to the VFD for modulating control of the blower motor, to bypass the drive and operate the motor at full speed, or to power the drive (and not the motor) for diagnostic purposes.

VAV is not available with the factory-installed 3rd. party BAS controllers. VAV is only factory installed with the Smart Equipment™ Controller.

A 'VFD-ready' option provides the provisions for a customer-installed drive. The unit comes with a mounting bracket installed in the Blower Access compartment which may accommodate other vendor's drives depending on their size. In order to utilize the unit's mounting bracket, the maximum recommended drive dimensions are limited to approximately 9" H x 5" W x 7.5" D.

If the drive will not fit in the allotted space, then it will have to be mounted elsewhere; either within the building on a perpendicular wall which is not subjected to excessive temperature, vibration, humidity, dust, corrosive gas, explosive gas, etc., or within an appropriate enclosure rated for outside installation to safeguard against moisture, dust and excessive heat. A terminal block located in the control box is provided for field connection of the VFD controls.

• IntelliSpeed™ Supply Fan Control Option (ASHRAE 90.1 compliant) - Units configured with the IntelliSpeed™ Supply Fan Option will contain a VFD for multi-speed supply fan operation. This option allows the supply fan RPM to vary based on the number of compressors or heating stages energized. The economizer's minimum position will also be configurable to vary based on the supply fan VFD frequency output.

• Aluminized Steel Gas Heat Exchanger - For applications in non-corrosive environments.

• Stainless Steel Gas Heat Exchanger - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.

• Low NOx Option - For units with gas furnaces in locations where codes require that the Oxides of Nitrogen emissions from the furnace be below 40 Nano grams per joule.

• Stainless Steel Drain Pan - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.

• Electric Heaters - The electric heaters range from 3kW to 54kW and are available in all the voltage options of the base units. All heaters are intended for single point power supply.

• Disconnect Switch - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the

Page 7: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 7

largest electric heat available for the particular unit is provided. Factory installed option only.

• Convenience Outlet - (Non-Powered/Powered) - This option locates a 120V single-phase GFCI outlet with cover, on the corner of the unit housing adjacent to the compressors. The “Non-powered” option requires the installer to provide the 120V single-phase power source and wiring. The “Powered” option is powered by a stepdown transformer in the unit. Factory installed option only.

• Smoke Detectors - The smoke detectors stop operation of the unit and provide a fault message to the control board. Smoke detectors are available for both the supply and/or return air configurations.

• Filters - 2” Pleated MERV 8 or 4” Pleated MERV 13 are available to meet LEED requirements. A 2” Throwaway is shipped as standard.

• Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition. (Standard on units with Scroll Compressors.)

• Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. Additionally, this kit stops animals and foreign objects from entering the space between the inner condenser coil and the main cabinet. This is not a hail guard kit.

• Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

• E-Coat Condenser Coils - The condenser coils are coated with an epoxy polymer coating to protect against corrosion.

• E-Coat Evaporator Coils - The evaporator coils are coated with an epoxy polymer coating to protect against corrosion.

• Hot Gas Bypass - Allows operation during low load conditions while avoiding coil frosting and damage to compressor. When suction pressure falls below valve setpoint, the valve modulates hot gas to the inlet of the evaporator. HGBP is standard on all units with VAV and optional with constant-volume units.

Control Options

• Smart Equipment™ with Communication Option Control - The York® Smart Equipment™ with Communication Option Control is factory installed. It includes all the features of the Smart Equipment™ control

with an additional gateway to BACnet MS/TP (programmable to Modbus or N2 protocols).

• FDD (Fault Detection and Diagnostics) - Refrigerant side (Modification Center Option Only)A factory installed control system option on the commercial equipment that constantly monitors refrigerant circuit pressures, refrigerant circuit temperatures, as well as the environmental temperatures and humidity via multiple sensor inputs.

• Provides a building owner, technician or contractor with the operational characteristics of the RTUs entire refrigerant circuit to ensure the unit is functioning at its specified performance level.

• Provides alarms if the unit is not functioning optimally.

• Remotely accessible via the Mobile Access Portal (MAP) gateway as well as scrolled on the UCB LCD screen.

• Novar® BAS Control - The Novar® building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

• CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, with optional dirty filter indicator switch and air proving switch.

• Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, with optional dirty filter indicator switch, and air proving switch.

• Verasys - Verasys provides a simple user experience with configurable self-recognizing controllers without the need for any additional tools. Verasys creates enhanced integration of HVACR equipment, zoning, and controls. Contractors are able to offer a complete bundled solution of equipment and controls to serve the light commercial market.

Field Installed Accessories

YORK® offers several equipment accessories for field installation, for the Sun™ Pro line.

• Down flow and End Return Economizers (with fresh air hood and barometric relief) - All units offer a variety of optional factory installed down flow economizers that are shipped, installed and wired with low leak dampers designed to meet ASHRAE 90.1, AMCA 511 Class 1A damper, and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 CFM/sq. ft. at 1" of static pressure. Each economizer goes through a rigorous 60,000 cycle test. Dry bulb, single enthalpy, and dual enthalpy (with field installed kit) can be selected. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the outdoor air dry bulb temperature or the outdoor air enthalpy input. The dual enthalpy kit provides a second input used to

Factory-installed smoke detectors may be subjected to extreme temperatures during "off" times due to outside air infiltration. These smoke detectors have an operational limit of -4°F to 158°F. Smoke detectors installed in areas that could be outside this range will have to be relocated to prevent false alarms.

Page 8: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

8 Johnson Controls Ducted Systems

monitor the return air (field installed). The installer needs only to assemble the outdoor air hood, attach the enthalpy control the hood and mount the hood to the unit (Hood and control are provided).

• Single or Dual Enthalpy Control, Accessories - These kits contain the required components to convert a dry bulb economizer to a single enthalpy and/or dual enthalpy economizer.

• Barometric Relief Damper - Zero to 100% capacity barometric relief dampers for use with horizontal flow, or field installed economizers.

• Power Exhaust - This accessory installs in the unit with a down flow or horizontal end return economizer. Power exhaust plugs into the connector in the unit bulkhead. User must purchase the 1EH0408 barometric relief and hood kit when applying the product in a horizontal flow application. The power exhaust must be mounted in the horizontal end return ductwork.

• Manual Outdoor Air Damper - Like the motorized outdoor air damper, each manual outdoor air damper includes a slide-in damper assembly with an outdoor air hood and filters. Customers have a choice of dampers with ranges of 0% to 100% or 0% to 35% outdoor air entry.

• Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.

• Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

• CO2 Sensor - Senses CO2 levels and automatically overrides the economizer when levels rise above the preset limits.

• Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters.

• Coil Guard - Field installed decorative wire coil guard.

• Hail Guard - This kit includes a sloped hood which installs over the outside condenser coil and prevents damage to the coil fins from hail strikes. Field installed accessory only.

• Flue Exhaust Extension Kit - In locations with wind or weather conditions which may interfere with proper

exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.

• Gas Heat High Altitude Kit - This kit converts a gas heat unit to operate at high altitudes, 2,000 to 6,000 feet. Conversion kits are available for natural gas and propane.

• Low NOx Kit - For units with gas furnaces in locations where codes require that the Oxides of Nitrogen emissions from the furnace be below 40 Nano grams per joule.

• Gas Heat Propane Conversion Kit - This kit converts a gas-fired heater from natural gas to propane. It contains the main burner orifices and gas valve replacement springs.

• Gas Piping Kit - Contains pipe nipples, fittings and gas cock required for gas supply connection with external shut off.

• Electric Heaters - The electric heaters range from 3kW to 54kW and are available in all the voltage options of the base units. The 54kW/208-240 volt, field-installed heater kit is not available with VAV units due to a lack of space to accommodate the heater’s fuse block accessory.

All heaters are dual staged. Cooling units include an adapter panel for easy installation of the electric heaters. Necessary hardware and connectors are included with the heaters. All heaters are intended for single point power supply.

• Metal Frame Filter Kit - Metal frame with polyester filter medium.

• Permanent Filters - Permanent filters are available.

• Roof Curbs - The roof curbs have insulated decks and are shipped disassembled The roof curbs are available in 8” and 14” heights. For applications with security concerns, burglar bars are available for the duct openings of the roof curbs.

• Roof Curb Transition - Single Piece Adapter (10” High) - Roof curbs for transitioning from Sunline™ units to Sun™ Pro units. Fits 7.5 to 12.5 Sunline™ roof curbs only.

• Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.

• Thermostat - The units are designed to operate with 24- volt electronic and electro-mechanical thermostats. All 6.5 thru 12.5 ton ZH,ZJ units and all 3 thru 12.5 ton ZR units (with or without an economizer) operate with two-stage heat/two-stage cool or two-stage cooling only thermostats, depending upon unit configuration.

Page 9: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 9

Accessories Field Installed Accessories - Non-Electrical

MODEL VOLTAGE DESCRIPTION WHERE USED1BD0408 All Burglar Bars, Downflow All Cabinets

1CG0419 All Coil Guard(Electric / Electric Models), 50” Tall Standard Cabinets

1CG0420 All Coil Guard (Gas / Electric Models), 50" Tall Standard Cabinets1CG0427 All Coil Guard (Electric / Electric Models), 42” Tall Cabinets1CG0428 All Coil Guard (Gas / Electric Models), 42" Tall Cabinets

1HG0411 All Hail Guard KitAll Tall (50") Standard Cabinets, (Excludes 12.5T "V" cabinets)

1HG0415 All Hail Guard Kit All Short (42") Standard Cabinets

1HG0425 All Hail Guard KitDiamond Pattern "W" Style Cabinet: ZH/ZR/ZJ/XP 150

1HG0431 All Hail Guard Kit Provent Style 42" Std Short Cabinets

1HG0432 All Hail Guard KitProvent Style 50" Std Tall Cabinets (Excludes 12.5T "V" cabinets)

1FE0412 All Flue Exhaust Extension Kit All Cabinets1FF0414 All 2" only Metal Filter Frame Kit All Tall 50" Cabinets1FF0415 All 2" only Metal Filter Frame Kit All Tall 42" Cabinets1FL0402 All Permanent 2" only Filter Kit Includes (4) Four Filters) All Tall 50" Cabinets1FL0423 All Permanent 2" only Filter Kit (Includes (4) four Filters) All Tall 42" Cabinets1GP0405 All Gas Piping Kit All Cabinets1HA0442 All High Altitude Kit for Natural Gas All 6 - 12T Cabinets1HA0450 All High Altitude Kit for Natural Gas 3 - 5T (80, 120 & 160 MBH Input)1HA0451 All High Altitude Kit for Natural Gas 3 - 4T (60 MBH Input)1HA0443 All High Altitude Kit for Propane All 6 - 12T Cabinets1HA0452 All High Altitude Kit for Propane 3 - 5T (80, 120 & 160 MBH Input)1HA0453 All High Altitude Kit for Propane 3 - 4T (60 MBH Input)1NP0442 All Propane Conversion Kit All 6 - 12T Cabinets1NP0454 All Propane Conversion Kit 3 - 5T (80, 120 & 160 MBH Input)1NP0455 All Propane Conversion Kit 3 - 4T (60 MBH Input)1RC0470 All Roof Curb, 8" Height All Cabinets1RC0471 All Roof Curb, 14" Height All Cabinets

1RC0472 AllRoof Curb, Transition (7.5 T thru 12.5T Sunline to Sun™ Pro 3- 12T)

All Cabinets

1WC0412 AllWooden Crate for extra protection during shipping and handling

Standard Cabinets Only (not applicable to units 119" in length)

1LN0407 All Low NOx Kit 3 - 5T (80, 120 & 160 MBH Input)1LN0408 All Low NOx Kit 3 - 5T (60 MBH Input)

Page 10: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

10 Johnson Controls Ducted Systems

Field Installed Accessories - Electric HeatMODEL VOLTAGE DESCRIPTION WHERE USED

2TP04520925 2309kW Electric Heat All 50" Cabinet 6.5 and 8.5 Ton Models2TP04520946 460

2TP04520958 5752TP04531825 230

18kW Electric Heat All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models2TP04531846 4602TP04521858 5752TP04532425 230

24kW Electric Heat All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models2TP04532446 4602TP04522458 5752TP04533625 230

36kW Electric Heat All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models2TP04533646 4602TP04523658 5752TP04525425 230

54kW Electric Heat All 50" 10 and 12.5 Ton Models2TP04525446 4602TP04525458 5752TP04540925 230

9kW Electric Heat All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models2TP04540946 4602TP04540958 5752TP04541825 230

18kW Electric Heat All 42" 6.5, 7.5 and 8.5 Ton Models2TP04541846 4602TP04541858 5752TP04542425 230

24kW Electric Heat All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models2TP04542446 4602TP04542458 5752TP04543625 230

36kW Electric Heat All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models2TP04543646 4602TP04543658 5752TP04510325 230

3kW Electric Heat All 42" Cabinet 3 Ton Models2TP04510346 4602TP04510625 230

6kW Electric Heat All 42" Cabinet 3, 4 and 5 Ton Models2TP04510646 4602TP04510825 230

9kW Electric Heat All 42" Cabinet 3, 4 and 5 Ton Models2TP04510846 4602TP04510858 5752TP04511525 230

15kW Electric Heat All 42" Cabinet 3, 4 and 5 Ton Models2TP04511546 4602TP04511558 5752TP04512025 230

20kW Electric Heat All 42" 4 and 5 Ton Models2TP04512046 4602TP04512058 5752TP04512325 230

24kW Electric Heat All 42" Cabinet 5 Ton Models2TP04512346 4602TP04512358 575

Accessories (Continued)

Page 11: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 11

Guide Specifications

GENERAL

YORK® Sun™ Pro units are convertible single packages with a common footprint cabinet and common roof curb for all 3 through 12.5 ton models. All 6.5 through 12.5 ton units have two compressors with independent R-410A refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame. All Sun™ Pro units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged with R-410A, wired, piped, and tested at the factory to provide a quick and easy field installation. All units are convertible between side and down airflow. Independent economizer designs are used on side and down discharge applications, as well as all tonnage sizes. Sun™ Pro units are available in the following configurations: cooling only, cooling with electric heat, cooling with gas heat, reheat only, reheat with electric heat and reheat with gas heat.

Electric heaters are available as factory-installed options or field-installed accessories.

DESCRIPTION

Units shall be factory assembled, single package, (Elec/Elec, Gas/Elec), designed for outdoor installation. They shall have built in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return and be available with factory installed options or field installed accessories. The units shall be factory wired, piped and charged with R-410A refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. The cooling performance shall be rated in accordance with DOE and AHRI test procedures. Units shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236-M90 standards.

UNIT CABINET

Unit cabinet shall be constructed of galvanized steel with exterior surfaces coated with a non-chalking, powder paint finish, certified at a 750-hour salt spray test per ASTM-B117

Field Installed Accessories - Fresh AirMODEL VOLTAGE DESCRIPTION WHERE USED

1FA0413 All Manual Outside Air Damper 0-35%, Downflow All Cabinets1FA0414 All Manual Outside Air Damper 0-100%, Downflow All Cabinets1EH0408 All Barometric Relief Kit for Power Exhaust, Horizontal Application All Cabinets2EC0401 All Single Enthalpy Control All Cabinets2EC0402 All Dual Enthalpy Control (Includes 2 Sensors) All Cabinets

2EE04717424 AllEconomizer for Downflow, End Return Horizontal, or ERV Applications. Includes FA Hood, Exhaust Hood w/Baro Relief

All 50" Cabinets

2EE04717624 AllEconomizer for Downflow, End Return Horizontal, or ERV Applications. Includes FA Hood, Exhaust Hood w/Baro Relief

All 42" Cabinets

2EE04706924 All Horizontal Economizer without Barometric Relief All Cabinets2MD04703824 All Motorized Damper, Downflow without Barometric Relief All Cabinets2MD04703924 All Motorized Damper, Horizontal without Barometric Relief All Cabinets2PE04704706 230 Power Exhaust 230V Downflow or Horizontal All Cabinets2PE04704746 460 Power Exhaust 460V Downflow or Horizontal All Cabinets2PE04704758 575 Power Exhaust 575V Downflow or Horizontal All Cabinets

Field Installed Accessories - ControlsMODEL VOLTAGE DESCRIPTION WHERE USED

2AP0401 All Air Proving Switch All Units2AQ04700524 All CO² Space Accessory All Units2AQ04700624 All CO² Unit Accessory All Units2DF0402 All Dirty Air Switch All Units2SD04700824 All Smoke Detector for Supply All Gen 5 units and greater with 2" & 4" Filters2SD04700924 All Smoke Detector for Return All Gen 5 units and greater with 2" & 4" Filters2SD04701024 All Smoke Detector for Supply and Return All Gen 5 units and greater with 2" & 4" FiltersS1-YK-MAP1810-0P

AllMAP (Mobile Access Portal) Gateway- For use with Smart Equipment™ Control.

All Units

S1-MP-PRTKIT-0P

AllMAP (Mobile Access Portal) Gateway Kit- Replacement MAP gateway protective case, lanyard and communication cable. Use only to replace worn or damaged components.

All Units

Field Installed Accessories - ElectricalMODEL VOLTAGE DESCRIPTION WHERE USED

2LA04702412 All Low Ambient Kit All 3 - 10T units (excludes ZT and 3-5T ZR units)2LA04702424 All Low Ambient Kit All 12.5T cabinets

Accessories (Continued)

Page 12: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

12 Johnson Controls Ducted Systems

standards. Indoor blower sections shall be insulated with up to 1” thick insulation coated on the airside. Either aluminum foil faced or elastometric rubber insulation shall be used in the unit’s compartments and be fastened to prevent insulation from entering the air stream. Cabinet doors shall be hinged with toolless access for easy servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing on roof curb applications. Disposable 2” filters shall be furnished as standard and be accessible through hinged access door. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating bypass of the coils. Condensate pan shall be slide out design, constructed of a non corrosive material, internally sloped and conforming to ASHRAE 62-B9 standards. Condensate connection shall be a minimum of ¾” I.D. female and be rigid mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

Fan shall be a belt drive assembly and include an adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors nameplate horsepower rating plus the ser-vice factor. Units shall be designed to operate within the service factor. Fan wheel shall be double inlet type with forward curve blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. Entire blower assembly and motor shall be slide out design.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for smooth operation. The outdoor fan motors shall have permanently lubricated bearings internally protected against overload conditions and staged independently. A cleaning window shall be provided on two sides of the units for coil cleaning.

REFRIGERANT COMPONENTS

Compressors:

a. Shall be fully hermetic type, direct drive, internallyprotected with internal high-pressure relief and overtemperature protection. The hermetic motor shall besuction gas cooled and have a voltage range of + or –10% of the unit nameplate voltage.

b. Shall have internal spring isolation and sound muffling tominimize vibration and noise, and be externally isolatedon a dedicated, independent mounting.

Coils:

a. Evaporator coils shall have aluminum plate finsmechanically bonded to seamless internally enhancedcopper tubes with all joints brazed. Special Phenoliccoating shall be available as a factory option.

b. Evaporator coils shall be of the direct expansion, draw-thru design.

c. Condenser coils shall have aluminum plate finsmechanically bonded to seamless internally enhancedcopper tubes with all joints brazed or Micro-Channelaluminum tube, aluminum fins.

d. Condenser coils shall be of the draw-thru design.

Refrigerant Circuit and Refrigerant Safety Components shall include:

a. Independent fixed-orifice or thermally operatedexpansion devices.

b. Solid core filter drier/strainer to eliminate any moisture orforeign matter.

c. Accessible service gage connections on both suctionand discharge lines to charge, evacuate, and measurerefrigerant pressure during any necessary servicing ortroubleshooting, without losing charge.

d. The 6.5 through 12.5 ton unit shall have two independentrefrigerant circuits, equally split in 50% capacityincrements.

Unit Controls:

a. Unit shall be complete with self-contained low-voltagecontrol circuit protected by a resettable circuit breaker onthe 24-volt transformer side.

b. Unit shall incorporate a lockout circuit which providesreset capability at the space thermostat or base unit,should any of the following standard safety devices tripand shut off compressor.

1. Loss-of-charge/Low-pressure switch.

2. High-pressure switch.

3. Freeze condition sensor on evaporator coil. If any of these safety devices trip, the LCD screen will display the alarm message.

c. Unit shall incorporate "AUTO RESET" compressor overtemperature, over current protection.

d. Unit shall operate with conventional thermostat designsand have a low voltage terminal strip for easy hook-up.

e. Unit control board shall have on-board diagnostics andfault message display.

f. Standard controls shall include anti-short cycle and lowvoltage protection, and permit cooling operation down toa selectable value as low as 0 °F.

g. Control board shall monitor each refrigerant safety switchindependently.

GAS HEATING SECTION (IF EQUIPPED)

Heat exchanger and exhaust system shall be constructed of aluminized steel, and be designed with induced draft combus-tion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for cor-rosion resistance and allowing minimum mixed air entering tem-perature of 40 ºF. Burners shall be of the in-shot type, constructed of aluminum-coated steel. All gas piping shall enter the unit cabinet at a single location, through either the side or

Page 13: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 13

bottom, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the following minimum protection:

a. Primary and auxiliary high-temperature limit switches.

b. Induced draft pressure sensor.

c. Flame roll out switch (manual reset).

d. Flame proving controls.

e. All two stage gas units shall have two independentstages of capacity as shown on Page 5.

ELECTRIC HEATING SECTION (IF EQUIPPED)

An electric heating section, with nickel chromium elements, shall be provided in a range of 3 thru 54KW. The heating sec-tion shall have a primary limit control(s) (automatic reset) to pre-vent the heating element system from operating at an excessive temperature. The Heating Section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125 ºF outdoor temperature, exceeding maximum load criteria of AHRI Stan-dard 340/360. The compressor, with standard controls, shall be capable of operation down to 0 ºF outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up. (Gas heat only)

ELECTRICAL REQUIREMENTS - All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES - Compressor – 5 Years, Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years,Parts – 1 Year

OPTIONAL OUTDOOR AIR (Shall be made available by either/or):

• DRY BULB AUTOMATIC ECONOMIZER - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall be designed to meet ASHRAE 90.1, AMCA 511 Class 1A damper, and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 CFM/sq. ft. at 1" of static pressure. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided.

Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Available with barometric relief and power exhaust.

• MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and return air dampers that are interlocked and positioned by a 2- position, spring-return damper actuator. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

ADDITIONAL FACTORY INSTALLED OPTIONS

• ALTERNATE INDOOR BLOWER MOTOR – For applications with high restrictions, units are available with optional indoor blower motors that provide higher static output and/or higher airflow.

• VARIABLE AIR VOLUME (VAV) - The VAV option using a variable frequency drive (VFD) shall be available on6.5 through 12.5 ton models for applications requiring a constant supply-duct static pressure. Units equipped for VAV shall be controlled by a duct pressure transducer with a 0 - 5" WC pressure range. The pressure transducer shall provide a 0 - 5 VDC output signal to a VAV control board which, in turn shall provide a 2 - 10 VDC speed reference signal to the VFD. The control board shall operate using factory-installed Supply Air, Return Air and Outside Air Temperature Sensors with a nominal resistance of 10,000 Ohms. Units equipped with VFD's shall have factory-installed manual bypass as an option.

• CONVENIENCE OUTLET (POWERED/NON-POWERED)– Unit can be provided with an optional 120VAC GFCI outlet with cover on the corner of the unit housing the compressors.

• ELECTRIC HEAT - Electric Heaters range from 3kW to 54kW and are available in all the voltage options of the base unit.

• PHASE MONITOR - Designed to prevent damage in out-of-phase condition.

• COIL GUARD - Designed to prevent condenser coil damage.

• BAS CONTROLS HARDWARE - Include supply air sensor, return air sensor, dirty filter indicator and air proving switch.

• DIRTY FILTER SWITCH – This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high-pressure drop across the filters.

• BREAKER – An HACR breaker can be factory installed on gas heat units or cooling units with electric heat.

• DISCONNECT SWITCH - A disconnect can be factory installed on a cooling only units sized for the largest electric heat available.

Page 14: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

14 Johnson Controls Ducted Systems

• STAINLESS STEEL HEAT EXCHANGER – For applications in a corrosive environment, this option provides a full stainless steel heat exchanger assembly.

• SMOKE DETECTOR – A smoke detector can be factory mounted and wired in the supply and/or return air compartments.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

• ROOF CURB - 14” and 8” high, full perimeter knockdown curb, with hinged design for quick assembly.

• BAROMETRIC RELIEF DAMPER – (Unit mounted – Downflow, Duct Mounted – Horizontal) – Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit during economizer operation.

• PROPANE CONVERSION KIT – Contains new orifices and gas valve springs to convert from natural to L.P. gas.

• ECONOMIZER (Downflow and Horizontal flow)

• POWER EXHAUST – (Unit mount – Downflow, Duct mount – Horizontal flow)

• DUAL ENTHALPY KIT - Provides a second input to economizer to monitor return air.

Page 15: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 15

Physical Data

ZH037-061 Single Stage Gas Physical Data

ComponentModels

ZH037 ZH049 ZH061

Nominal Tonnage 3.0 4.0 5.0

AHRI COOLING PERFORMANCE

Gross Capacity @ AHRI A point (MBh) 36700 48500 60000

AHRI net capacity (MBh) 35600 47000 58000

EER 12.0 12.0 12.0

SEER 14 14 14

CFM 1200 1600 2000

System power (KW) 2.97 3.92 4.83

Refrigerant type R-410A R-410A R-410A

Refrigerant charge (lb-oz)

System 1 6-2 6-10 8-2

System 2 - - -

AHRI HEATING PERFORMANCE

Heating model H06 H08 H12 H06 H08 H12 H08 H12 H16

Heat input (K Btu) 60 80 120 60 80 120 80 120 160

Heat output (K Btu) 49 65 97 49 65 97 65 97 129

AFUE % - - - - - -

Steady state efficiency (%) 81.5 81 81 81.5 81 81 81 81 80.5

No. burners 4 4 6 4 4 6 4 6 8

No. stages 1 1 1 1 1 1 1 1 1

Temperature Rise Range (ºF) 20-50°F 25-65°F 50-80°F 20-50°F 25-65°F 40-70°F 25-65°F 35-65°F 45-75°F

Gas Limit Setting (ºF) 235°F 200°F 255°F 235°F 200°F 255°F 200°F 245°F 240°F

Gas piping connection (in.) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

DIMENSIONS (inches)

Length 89 89 89

Width 59 59 59

Height 42 42 42

OPERATING WT. (lbs.) 701 748 855

COMPRESSORS1

Type Scroll Scroll Scroll

Quantity 1 1 1

Unit Capacity Steps (%) 100 100 100

CONDENSER COIL DATA

Face area (Sq. Ft.) 11.9 18.5 21.1

Rows 1 1 1

Fins per inch 23 23 23

Tube diameter (in./MM) 1/25 .71/18 .71/18

Circuitry Type 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel

EVAPORATOR COIL DATA

Face area (Sq. Ft.) 8 8 10.6

Rows 3 3 3

Fins per inch 15 15 15

Tube diameter 0.375 0.375 0.375

Refrigerant control TXV TXV TXV

Page 16: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

16 Johnson Controls Ducted Systems

CONDENSER FAN DATA

Quantity of fans 1 1 2

Fan diameter (Inch) 24 24 24

Type Prop Prop Prop

Drive type Direct Direct Direct

Quantity of motors 1 1 2

Motor HP each 1/3 1/3 1/3

No. speeds 1 1 1

RPM 850 850 850

Total CFM 3300 3700 6700

BELT DRIVE EVAP FAN DATA

Quantity 1 1 1

Fan Size (Inch) 12 x 9 12 x 9 12 x 9

Type Centrifugal Centrifugal Centrifugal

Motor Sheave 1VM34 1VL44 1VM34 1VL44 1VL40 1VP56

Blower Sheave AK69 AK69 AK56 AK56 AK61 AK74

Belt A47 A47 A47 A47 A47 A51

Motor HP each 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2

RPM 1725 1725 1725 1725 1725 1725

Frame size 56 56 56 56 56 56

FILTERS

Quantity - Size4 - (24 x 16 x 2)2,3 4 - (24 x 16 x 2)2,3 4 - (24 x 16 x 2)2,3

4 - (24 x 16 x 4)4 4 - (24 x 16 x 4)4 4 - (24 x 16 x 4)4

1. ZH037, ZH049, ZH061 have crankcase heaters standard.2. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value).3. 2 In. Pleated, Optional, MERV 8.4. 4 In. Pleated, Optional, MERV 13.

ZH037-061 Single Stage Gas Physical Data (Continued)

ComponentModels

ZH037 ZH049 ZH061

Nominal Tonnage 3.0 4.0 5.0

Page 17: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 17

ZH037-061 Two Stage Gas Physical Data

ComponentModels

ZH037 ZH049 ZH061

Nominal Tonnage 3.0 4.0 5.0

AHRI COOLING PERFORMANCE

Gross Capacity @ AHRI A point (MBh) 36700 48500 60000

AHRI net capacity (MBh) 35600 47000 58000

EER 12.0 12.0 12.0

SEER 14 14 14

CFM 1200 1600 2000

System power (KW) 2.97 3.92 4.83

Refrigerant type R-410A R-410A R-410A

Refrigerant charge (lb-oz)

System 1 6-2 6-10 8-2

System 2 - - -

AHRI HEATING PERFORMANCE

Heating model N06 N08 N12 N06 N08 N12 N08 N12 N16

Heat input (K Btu) 60 80 120 60 80 120 80 120 160

Heat output (K Btu) 49 65 97 49 65 97 65 97 129

AFUE % - - - - - -

Steady state efficiency (%) 81.5 81 81 81.5 81 81 81 81 80.5

No. burners 4 4 6 4 4 6 4 6 8

No. stages 21 22 22 21 22 22 22 22 22

Temperature Rise Range (ºF) 20-50°F 25-65°F 50-80°F 20-50°F 25-65°F 40-70°F 25-65°F 35-65°F 45-75°F

Gas Limit Setting (ºF) 235°F 200°F 255°F 235°F 200°F 255°F 200°F 245°F 240°F

Gas piping connection (in.) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

DIMENSIONS (inches)

Length 89 89 89

Width 59 59 59

Height 42 42 42

OPERATING WT. (lbs.) 701 748 855

COMPRESSORS3

Type Scroll Scroll Scroll

Quantity 1 1 1

Unit Capacity Steps (%) 100 100 100

CONDENSER COIL DATA

Face area (Sq. Ft.) 11.9 18.5 21.1

Rows 1 1 1

Fins per inch 23 23 23

Tube diameter (in./MM) 1/25 .71/18 .71/18

Circuitry Type 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel

EVAPORATOR COIL DATA

Face area (Sq. Ft.) 8 8 10.6

Rows 3 3 3

Fins per inch 15 15 15

Tube diameter 0.375 0.375 0.375

Refrigerant control TXV TXV TXV

Page 18: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

18 Johnson Controls Ducted Systems

CONDENSER FAN DATA

Quantity of fans 1 1 2

Fan diameter (Inch) 24 24 24

Type Prop Prop Prop

Drive type Direct Direct Direct

Quantity of motors 1 1 2

Motor HP each 1/3 1/3 1/3

No. speeds 1 1 1

RPM 850 850 850

Total CFM 3300 3700 6700

BELT DRIVE EVAP FAN DATA

Quantity 1 1 1

Fan Size (Inch) 12 x 9 12 x 9 12 x 9

Type Centrifugal Centrifugal Centrifugal

Motor Sheave 1VM34 1VL44 1VM34 1VL44 1VL40 1VP56

Blower Sheave AK69 AK69 AK56 AK56 AK61 AK74

Belt A47 A47 A47 A47 A47 A51

Motor HP each 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2

RPM 1725 1725 1725 1725 1725 1725

Frame size 56 56 56 56 56 56

FILTERS

Quantity - Size4 - (24 x 16 x 2)4,5 4 - (24 x 16 x 2)4,5 4 - (24 x 16 x 2)4,5

4 - (24 x 16 x 4)6 4 - (24 x 16 x 4)6 4 - (24 x 16 x 4)6

1. 1st Stage Capacity is 75% of Full Capacity.2. 1st Stage Capacity is 70% of Full Capacity.3. ZH037, ZH049, ZH061 have crankcase heaters standard.4. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value)5. 2 In. Pleated, Optional, MERV 8.6. 4 In. Pleated, Optional, MERV 13.

ZH037-061 Two Stage Gas Physical Data (Continued)

ComponentModels

ZH037 ZH049 ZH061

Nominal Tonnage 3.0 4.0 5.0

Page 19: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 19

ZH078-150 Physical Data

ComponentModels

ZH078 ZH090 ZH102 ZH120 ZH150

Nominal Tonnage 6.5 7.5 8.5 10 12.5

AHRI COOLING PERFORMANCE

Gross Capacity @ AHRI A point (Btu) 80500 87500 102800 125000 156000

AHRI net capacity (Btu) 77000 85000 99000 118000 150000

EER 11.71/11.52 11.5 11.71/11.52 11.71/11.52 11.71/11.52

IEER with Constant Volume 12.03 12.23 12.03 12.03 12.81/12.62

IEER with Intellispeed 14.81/14.62 13.5 14.01/13.82 14.81/14.62 14.41/14.22

IEER with VAV 13.91/13.72 13.21/13.02 13.01/12.82 13.51/13.32 13.41/13.22

CFM 2700 2500 3400 4000 3750

System power (KW) 6.70 7.40 9.0 10.40 12.80

Refrigerant type R-410A R-410A R-410A R-410A R-410A

Refrigerant charge (lb-oz)

System 1 5-6 6-0 7-2 8-6 8-2

System 2 5-14 5-10 6-14 7-7 8-2

AHRI HEATING PERFORMANCE

Heating model N12 N18 N12 N18 N12 N18 N18 N24 N18 N24

Heat input (K Btu) 120 180 120 180 120 180 180 240 180 240

Heat output (K Btu) 96 144 96 144 96 144 144 192 144 192

AFUE % - - - - - - - - - -

Steady state efficiency (%) 80 80 80 80 80 80 80 80 80 80

No. burners 4 6 4 6 4 6 6 8 6 8

No. stages 24 24 24 24 24 24 24 24 24 24

Temperature Rise Range (ºF) 20-50 35-65 15-45 30-60 10-40 25-55 20-50 35-65 10-40 25-55

Gas Limit Setting (ºF) 165 165 165 165 215 195 195 160 195 160

Gas piping connection (in.) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

DIMENSIONS (inches)

Length 89 89 89 89 119-1/2

Width 59 59 59 59 59

Height 42 42 50-3/4 50-3/4 50-3/4

OPERATING WT. (lbs.) 911 895 1032 1090 1280

COMPRESSORS5

Type Scroll Scroll Scroll Scroll Scroll

Quantity 2 2 2 2 2

Unit Capacity Steps (%) 50 / 100 50 / 100 50 / 100 50 / 100 50 / 100

CONDENSER COIL DATA

Face area (Sq. Ft.) 23.8 23.8 29.0 29.0 47.5

Rows 1 1 1 1 1

Fins per inch 23 23 23 23 23

Tube diameter (in./MM) 1/25 1/25 1/25 1/25 .71/18

Circuitry Type 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel

EVAPORATOR COIL DATA

Face area (Sq. Ft.) 10.6 10.6 13.2 13.2 13.2

Rows 3 3 3 4 4

Fins per inch 15 15 15 15 15

Tube diameter 0.375 0.375 0.375 0.375 0.375

Circuitry Type Intertwined Intertwined Intertwined Intertwined Intertwined

Refrigerant control TXV TXV TXV TXV TXV

Page 20: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

20 Johnson Controls Ducted Systems

CONDENSER FAN DATA

Quantity of fans 2 2 2 2 4

Fan diameter (Inch) 24 24 24 24 24

Type Prop Prop Prop Prop Prop

Drive type Direct Direct Direct Direct Direct

Quantity of motors 2 2 2 2 4

Motor HP each 1/3 3/4 3/4 3/4 1/3

No. speeds 1 1 1 1 1

RPM 850 1110 1110 1110 850

Total CFM 6700 8600 9400 9400 14000

BELT DRIVE EVAP FAN DATA

Quantity 1 1 1 1 1

Fan Size (Inch) 12 x 12 12 x 12 15 x 15 15 x 15 15 x 15

Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal

Motor Sheave 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VP56

Blower Sheave AK74 AK64 AK74 AK61 AK94 AK74 AK84 AK74 AK74 BK77

Belt A49 A49 A49 A49 A56 A54 A56 A54 A54 BX55

Motor HP each 1-1/2 2 1-1/2 3 2 3 2 3 3 5

RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725

Frame size 56 56 56 56 56 56 56 56 56 184T

FILTERS

Quantity - Size4 - (24 x 16 x 2)6,7 4 - (24 x 16 x 2)6,7 4 - (24 x 20 x 2)6,7 4 - (24 x 20 x 2)6,7 4 - (24 x 20 x 2)6,7

4 - (24 x 16 x 4)8 4 - (24 x 16 x 4)8 4 - (24 x 20 x 4)8 4 - (24 x 20 x 4)8 4 - (24 x 20 x 4)8

1. Cooling Only Unit or Cooling Unit with Electric Heat2. Cooling Unit with Gas Heat3. Does not meet DOE 2018 minimum efficiency requirements.4. 1st Stage 60% of Full Capacity.5. All ZH units have crankcase heaters standard.6. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.7. 2 In. Pleated, Optional, MERV 8.8. 4 In. Pleated, Optional, MERV 13.

ZH078-150 Physical Data (Continued)

ComponentModels

ZH078 ZH090 ZH102 ZH120 ZH150

Nominal Tonnage 6.5 7.5 8.5 10 12.5

Page 21: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 21

ZJ037-061 Single Stage Gas Heat Physical Data

ComponentModels

ZJ037 ZJ049 ZJ061

Nominal Tonnage 3.0 4.0 5.0

AHRI COOLING PERFORMANCE

Gross Capacity @ AHRI A point (MBh) 36000 48500 59000

AHRI net capacity (MBh) 35000 47000 57000

EER 12.2 12.2 12.2

SEER 14.5 15 14.5

CFM 1200 1600 2000

System power (KW) 2.87 3.85 4.67

Refrigerant type R-410A R-410A R-410A

Refrigerant charge (lb-oz)

System 1 6-12 8-6 7-8

System 2 - - -

AHRI HEATING PERFORMANCE

Heating model H06 H08 H12 H06 H08 H12 H08 H12 H16

Heat input (K Btu) 60 80 120 60 80 120 80 120 160

Heat output (K Btu) 49 65 97 49 65 97 65 97 129

AFUE % - - - - - -

Steady state efficiency (%) 81.5 81 81 81.5 81 81 81 81 80.5

No. burners 4 4 6 4 4 6 4 6 8

No. stages 1 1 1 1 1 1 1 1 1

Temperature Rise Range (ºF) 20-50°F 25-65°F 50-80°F 20-50°F 25-65°F 40-70°F 25-65°F 35-65°F 45-75°F

Gas Limit Setting (ºF) 235°F 200°F 255°F 235°F 200°F 255°F 200°F 245°F 240°F

Gas piping connection (in.) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

DIMENSIONS (inches)

Length 89 89 89

Width 59 59 59

Height 42 42 42

OPERATING WT. (lbs.) 719 748 765

COMPRESSORS1

Type Scroll Scroll Scroll

Quantity 1 1 1

Unit Capacity Steps (%) 100 100 100

CONDENSER COIL DATA

Face area (Sq. Ft.) 18.5 23.8 23.8

Rows 1 1 1

Fins per inch 23 23 23

Tube diameter (in./MM) .71/18 .71/18 .71/18

Circuitry Type 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel

EVAPORATOR COIL DATA

Face area (Sq. Ft.) 7.9 10.5 10.5

Rows 3 3 3

Fins per inch 15 15 15

Tube diameter 0.375 0.375 0.375

Refrigerant control TXV TXV TXV

Page 22: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

22 Johnson Controls Ducted Systems

CONDENSER FAN DATA

Quantity of fans 1 1 2

Fan diameter (Inch) 24 24 24

Type Prop Prop Prop

Drive type Direct Direct Direct

Quantity of motors 1 1 2

Motor HP each 1/3 1/3 1/3

No. speeds 1 1 1

RPM 850 850 850

Total CFM 3300 3700 6300

BELT DRIVE EVAP FAN DATA

Quantity 1 1 1

Fan Size (Inch) 12 x 9 12 x 9 12 x 9

Type Centrifugal Centrifugal Centrifugal

Motor Sheave 1VM34 1VL44 1VM34 1VL44 1VL40 1VP56

Blower Sheave AK69 AK69 AK56 AK56 AK61 AK74

Belt A47 A47 A47 A47 A47 A51

Motor HP each 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2

RPM 1725 1725 1725 1725 1725 1725

Frame size 56 56 56 56 56 56

FILTERS

Quantity - Size4 - (24 x 16 x 2)2,3 4 - (24 x 16 x 2)2,3 4 - (24 x 16 x 2)2,3

4 - (24 x 16 x 4)4 4 - (24 x 16 x 4)4 4 - (24 x 16 x 4)4

1. ZJ037, ZJ049 and ZJ061 have crankcase heaters standard.2. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3. 2 In. Pleated, Optional, MERV 8.4. 4 In. Pleated, Optional, MERV 13.

ZJ037-061 Single Stage Gas Heat Physical Data (Continued)

ComponentModels

ZJ037 ZJ049 ZJ061

Nominal Tonnage 3.0 4.0 5.0

Page 23: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 23

ZJ037-061 Two Stage Gas Heat Physical Data

ComponentModels

ZJ037 ZJ049 ZJ061

Nominal Tonnage 3.0 4.0 5.0

AHRI COOLING PERFORMANCE

Gross Capacity @ AHRI A point (MBh) 36000 48500 59000

AHRI net capacity (MBh) 35000 47000 57000

EER 12.2 12.2 12.2

SEER 14.5 15 14.5

CFM 1200 1600 2000

System power (KW) 2.87 3.85 4.67

Refrigerant type R-410A R-410A R-410A

Refrigerant charge (lb-oz)

System 1 6-12 8-6 7-8

System 2 - - -

AHRI HEATING PERFORMANCE

Heating model N06 N08 N12 N06 N08 N12 N08 N12 N16

Heat input (K Btu) 60 80 120 60 80 120 80 120 160

Heat output (K Btu) 49 65 97 49 65 97 65 97 129

AFUE % - - - - - -

Steady state efficiency (%) 81.5 81 81 81.5 81 81 81 81 80.5

No. burners 4 4 6 4 4 6 4 6 8

No. stages 21 22 22 21 22 22 22 22 22

Temperature Rise Range (ºF) 20-50°F 25-65°F 50-80°F 20-50°F 25-65°F 40-70°F 25-65°F 35-65°F 45-75°F

Gas Limit Setting (ºF) 235°F 200°F 255°F 235°F 200°F 255°F 200°F 245°F 240°F

Gas piping connection (in.) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

DIMENSIONS (inches)

Length 89 89 89

Width 59 59 59

Height 42 42 42

OPERATING WT. (lbs.) 719 748 765

COMPRESSORS3

Type Scroll Scroll Scroll

Quantity 1 1 1

Unit Capacity Steps (%) 100 100 100

CONDENSER COIL DATA

Face area (Sq. Ft.) 18.5 23.8 23.8

Rows 1 1 1

Fins per inch 23 23 23

Tube diameter (in./MM) .71/18 .71/18 .71/18

Circuitry Type 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel

EVAPORATOR COIL DATA

Face area (Sq. Ft.) 7.9 23.8 10.5

Rows 3 3 3

Fins per inch 15 15 15

Tube diameter 0.375 0.375 0.375

Refrigerant control TXV TXV TXV

Page 24: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

24 Johnson Controls Ducted Systems

CONDENSER FAN DATA

Quantity of fans 1 1 2

Fan diameter (Inch) 24 24 24

Type Prop Prop Prop

Drive type Direct Direct Direct

Quantity of motors 1 1 2

Motor HP each 1/3 1/3 1/3

No. speeds 1 1 1

RPM 850 850 850

Total CFM 3300 3700 6300

BELT DRIVE EVAP FAN DATA

Quantity 1 1 1

Fan Size (Inch) 12 x 9 12 x 9 12 x 9

Type Centrifugal Centrifugal Centrifugal

Motor Sheave 1VM34 1VL44 1VM34 1VL44 1VL40 1VP56

Blower Sheave AK69 AK69 AK56 AK56 AK61 AK74

Belt A47 A47 A47 A47 A47 A51

Motor HP each 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2

RPM 1725 1725 1725 1725 1725 1725

Frame size 56 56 56 56 56 56

FILTERS

Quantity - Size4 - (24 x 16 x 2)4,5 4 - (24 x 16 x 2)4,5 4 - (24 x 16 x 2)4,5

4 - (24 x 16 x 4)6 4 - (24 x 16 x 4)6 4 - (24 x 16 x 4)6

1. 1st Stage Capacity is 75% of Full Capacity.2. 1st Stage Capacity is 70% of Full Capacity.3. ZJ037, ZJ049 and ZJ061 have crankcase heaters standard.4. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value)5. 2 In. Pleated, Optional, MERV 8.6. 4 In. Pleated, Optional, MERV 13.

ZJ037-061 Two Stage Gas Heat Physical Data (Continued)

ComponentModels

ZJ037 ZJ049 ZJ061

Nominal Tonnage 3.0 4.0 5.0

Page 25: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 25

ZJ078-150 Physical Data

ComponentModels

ZJ078 ZJ090 ZJ102 ZJ120 ZJ150

Nominal Tonnage 6.5 7.5 8.5 10 12.5

AHRI COOLING PERFORMANCE

Gross Capacity @ AHRI A point (Btu) 76000 88000 99700 124000 154000

AHRI net capacity (Btu) 74000 86000 96000 120000 150000

EER 11.8 12.21/12.02 12.21/12.02 12.0 12.11/122

IEER with Constant Volume 13.20 13.21/13.02 13.0 12.91/12.82 13.71/13.52

IEER with Intellispeed 14.81/14.62 14.81/14.62 14.01/13.82 14.81/14.62 15.21/15.02

IEER with VAV 14.11/13.92 13.21/13.02 13.451/13.252 13.851/13.652 13.81/13.62

CFM 2500 2500 3300 3400 3500

System power (KW) 6.40 7.17 8.00 9.80 12.50

Refrigerant type R-410A R-410A R-410A R-410A R-410A

Refrigerant charge (lb-oz)

System 1 5-12 7-12 8-2 7-14 10-8

System 2 5-12 7-5 7-14 7-14 9-12

AHRI HEATING PERFORMANCE

Heating model N12 N18 N12 N18 N12 N18 N18 N24 N18 N24

Heat input (K Btu) 120 180 120 180 120 180 180 240 180 240

Heat output (K Btu) 96 144 96 144 96 144 144 192 144 192

AFUE % - - - - - - - - - -

Steady state efficiency (%) 80 80 80 80 80 80 80 80 80 80

No. burners 4 6 4 6 4 6 6 8 6 8

No. stages 23 23 23 23 23 23 23 23 23 23

Temperature Rise Range (ºF) 20-50 35-65 15-45 30-60 10-40 25-55 20-50 35-65 10-40 25-55

Gas Limit Setting (ºF) 165 165 165 165 215 195 195 160 195 160

Gas piping connection (in.) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

DIMENSIONS (inches)

Length 89 89 89 89 119-1/2

Width 59 59 59 59 59

Height 50-3/4 50-3/4 50-3/4 50-3/4 50-3/4

OPERATING WT. (lbs.) 1033 1035 1044 1070 1280

COMPRESSORS4

Type Scroll Scroll Scroll Scroll Scroll

Quantity 2 2 2 2 2

Unit Capacity Steps (%) 50 / 100 50 / 100 50 / 100 50 / 100 50 / 100

CONDENSER COIL DATA

Face area (Sq. Ft.) 29.0 23.8 29.0 29.0 47.5

Rows 1 1 1 1 1

Fins per inch 23 23 23 23 23

Tube diameter (in./MM) .71/18 1/25 1/25 1/25 .71/18

Circuitry Type 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel

EVAPORATOR COIL DATA

Face area (Sq. Ft.) 13.2 13.2 13.2 13.2 13.2

Rows 3 4 4 4 4

Fins per inch 15 15 15 15 15

Tube diameter 0.375 0.375 0.375 0.375 0.375

Circuitry Type Intertwined Intertwined Intertwined Intertwined Intertwined

Refrigerant control TXV TXV TXV TXV TXV

Page 26: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

26 Johnson Controls Ducted Systems

CONDENSER FAN DATA

Quantity of fans 2 2 2 2 4

Fan diameter (Inch) 24 24 24 24 24

Type Prop Prop Prop Prop Prop

Drive type Direct Direct Direct Direct Direct

Quantity of motors 2 2 2 2 4

Motor HP each 1/3 3/4 3/4 3/4 1/3

No. speeds 1 1 1 1 1

RPM 850 1110 1110 1110 850

Total CFM 7400 8000 9000 9400 14000

BELT DRIVE EVAP FAN DATA

Quantity 1 1 1 1 1

Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15

Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal

Motor Sheave 1VL40 1VM50 1VL40 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VP56

Blower Sheave AK74 AK74 AK69 AK69 AK89 AK74 AK84 AK74 AK74 BK77

Belt A53 A54 A52 A54 A56 A54 A56 A54 A54 BX56

Motor HP each 1-1/2 2 1-1/2 3 2 3 2 3 3 5

RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725

Frame size 56 56 56 56 56 56 56 56 56 184T

FILTERS

Quantity - Size4 - (24 x 20 x 2)5,6 4 - (24 x 20 x 2)5,6 4 - (24 x 20 x 2)5,6 4 - (24 x 20 x 2)5,6 4 - (24 x 20 x 2)5,6

4 - (24 x 20 x 4)7 4 - (24 x 20 x 4)7 4 - (24 x 20 x 4)7 4 - (24 x 20 x 4)7 4 - (24 x 20 x 4)7

1. Cooling Only Unit or Cooling Unit with Electric Heat2. Cooling Unit with Gas Heat3. 1st Stage 50% of Full Capacity.4. ZJ078 through ZJ150 have crankcase heaters standard.5. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.6. 2 In. Pleated, Optional, MERV 8.7. 4 In. Pleated, Optional, MERV 13.

ZJ078-150 Physical Data (Continued)

ComponentModels

ZJ078 ZJ090 ZJ102 ZJ120 ZJ150

Nominal Tonnage 6.5 7.5 8.5 10 12.5

Page 27: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 27

ZR037-061 Single Stage Gas Heat Physical Data

ComponentModels

ZR037 ZR049 ZR061

Nominal Tonnage 3 4 5

AHRI COOLING PERFORMANCE

Gross Capacity @ AHRI A point (Btu) 37600 48500 60200

AHRI net capacity (Btu) 35600 47000 58000

EER 12.2 12.1 12.1

SEER 14.5 14.5 14.3

CFM 1200 1600 2000

System power (KW) 2.92 3.88 4.80

Refrigerant type R-410A R-410A R-410A

Refrigerant charge (lb-oz)

System 1 11-8 11-0 11-10

System 2 - - -

AHRI HEATING PERFORMANCE

Heating model H06 H08 H12 H06 H08 H12 H08 H12 H16

Heat input (K Btu) 60 80 120 60 80 120 80 120 160

Heat output (K Btu) 49 65 97 49 65 97 65 97 129

AFUE % - - - - - -

Steady state efficiency (%) 81.5 81 81 81.5 81 81 81 81 80.5

No. burners 4 4 6 4 4 6 4 6 8

No. stages 1 1 1 1 1 1 1 1 1

Temperature Rise Range (ºF) 20-50°F 25-65°F 50-80°F 20-50°F 25-65°F 40-70°F 25-65°F 35-65°F 45-75°F

Gas Limit Setting (ºF) 235°F 200°F 255°F 235°F 200°F 255°F 200°F 245°F 240°F

Gas piping connection (in.) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

DIMENSIONS (inches)

Length 89 89 89

Width 59 59 59

Height 42 42 42

OPERATING WT. (lbs.) 846 865 858

COMPRESSORS1

Type Scroll Scroll Scroll

Quantity 1 1 1

Unit Capacity Steps (%) 100 100 100

CONDENSER COIL DATA

Face area (Sq. Ft.) 11.9 11.9 11.9

Rows 1 1 1

Fins per inch 23 23 23

Tube diameter (in./MM) .98/25 .98/25 .71/18 -.98/25

Circuitry Type 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel

EVAPORATOR COIL DATA

Face area (Sq. Ft.) 10.56 10.56 10.56

Rows 3 3 4

Fins per inch 15 15 12

Tube diameter 0.375 0.375 0.375

Refrigerant control TXV TXV TXV

REHEAT COIL DATA

Face area (Sq. Ft.) 8.9 8.9 8.9

Rows 2 2 2

Fins per inch 15 15 15

Tube diameter 0.375 0.375 0.375

Refrigerant control Solenoid Solenoid Solenoid

Page 28: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

28 Johnson Controls Ducted Systems

ComponentModels

ZR037 ZR049 ZR061

Nominal Tonnage 3 4 5

CONDENSER FAN DATA

Quantity of fans 1 2 2

Fan diameter (Inch) 24 24 24

Type Prop Prop Prop

Drive type Direct Direct Direct

Quantity of motors 1 2 2

Motor HP each 1/3 1/3 1/3

No. speeds Var. Var. Var.

RPM (max.) 850 850 850

Total CFM 3500 7000 7000

BELT DRIVE EVAP FAN DATA

Quantity 1 1 1

Fan Size (Inch) 12 x 9 12 x 9 12 x 9

Type Centrifugal Centrifugal Centrifugal

Motor Sheave 1VP34 1VL44 1VP34 1VL44 1VP34 1VL44

Blower Sheave AK61 AK59 AK61 AK59 AK61 AK59

Belt A47 A47 A47 A47 A47 A47

Motor HP each 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2

RPM 1725 1725 1725 1725 1725 1725

Frame size 56 56 56 56 56 56

FILTERS

Quantity - Size4 - (24 x 16 x 2)2, 3 4 - (24 x 16 x 2) 2,3 4 - (24 x 16 x 2) 2,3

4 - (24 x 16 x 4) 4 4 - (24 x 16 x 4) 4 4 - (24 x 16 x 4) 4

1. ZR037, ZR049 and ZR061 have crankcase heaters standard.2. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value).3. 2 In. Pleated, Optional, MERV 8.4. 4 In. Pleated, Optional, MERV 13.

ZR037-061 Single Stage Gas Heat Physical Data (Continued)

Page 29: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 29

ZR037-061 Two Stage Gas Heat Physical Data

ComponentModels

ZR037 ZR049 ZR061

Nominal Tonnage 3 4 5

AHRI COOLING PERFORMANCE

Gross Capacity @ AHRI A point (Btu) 37600 48500 60200

AHRI net capacity (Btu) 35600 47000 58000

EER 12.2 12.1 12.1

SEER 14.5 14.5 14.30

CFM 1200 1600 2000

System power (KW) 2.92 3.88 4.80

Refrigerant type R-410A R-410A R-410A

Refrigerant charge (lb-oz)

System 1 11-8 11-0 11-10

System 2 - - -

AHRI HEATING PERFORMANCE

Heating model N06 N08 N12 N06 N08 N12 N08 N12 N16

Heat input (K Btu) 60 80 120 60 80 120 80 120 160

Heat output (K Btu) 49 65 97 49 65 97 65 97 129

AFUE % - - - - - -

Steady state efficiency (%) 81.5 81 81 81.5 81 81 81 81 80.5

No. burners 4 4 6 4 4 6 4 6 8

No. stages 21 22 22 21 22 22 22 22 22

Temperature Rise Range (ºF) 20-50°F 25-65°F 35-80°F 20-50°F 25-65°F 35-80°F 25-65°F 35-80°F 45-75°F

Gas Limit Setting (ºF) 200°F 235°F 290°F 200°F 235°F 290°F 235°F 290°F 240°F

Gas piping connection (in.) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

DIMENSIONS (inches)

Length 89 89 89

Width 59 59 59

Height 42 42 42

OPERATING WT. (lbs.) 846 865 858

COMPRESSORS3

Type Scroll Scroll Scroll

Quantity 1 1 1

Unit Capacity Steps (%) 100 100 100

CONDENSER COIL DATA

Face area (Sq. Ft.) 11.9 11.9 11.9

Rows 1 1 1

Fins per inch 23 23 23

Tube diameter (in./MM) .98/25 .98/25 .71/18 -.98/25

Circuitry Type 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel

EVAPORATOR COIL DATA

Face area (Sq. Ft.) 10.56 10.56 10.56

Rows 3 3 4

Fins per inch 15 15 12

Tube diameter 0.375 0.375 0.375

Refrigerant control TXV TXV TXV

REHEAT COIL DATA

Face area (Sq. Ft.) 8.9 8.9 8.9

Rows 2 2 2

Fins per inch 15 15 15

Tube diameter 0.375 0.375 0.375

Refrigerant control Solenoid Solenoid Solenoid

Page 30: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

30 Johnson Controls Ducted Systems

ComponentModels

ZR037 ZR049 ZR061

Nominal Tonnage 3 4 5

CONDENSER FAN DATA

Quantity of fans 1 2 2

Fan diameter (Inch) 24 24 24

Type Prop Prop Prop

Drive type Direct Direct Direct

Quantity of motors 1 2 2

Motor HP each 1/3 1/3 1/3

No. speeds Var. Var. Var.

RPM 850 850 850

Total CFM 3500 7000 7000

BELT DRIVE EVAP FAN DATA

Quantity 1 1 1

Fan Size (Inch) 12 x 9 12 x 9 12 x 9

Type Centrifugal Centrifugal Centrifugal

Motor Sheave 1VP34 1VL44 1VP34 1VL44 1VP34 1VL44

Blower Sheave AK61 AK59 AK61 AK59 AK61 AK59

Belt A47 A47 A47 A47 A47 A47

Motor HP each 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2

RPM 1725 1725 1725 1725 1725 1725

Frame size 56 56 56 56 56 56

FILTERS

Quantity - Size4 - (24 x 16 x 2)4,5 4 - (24 x 16 x 2)4,5 4 - (24 x 16 x 2)4,5

4 - (24 x 16 x 4)6 4 - (24 x 16 x 4)6 4 - (24 x 16 x 4)6

1. 1st Stage Capacity is 75% of Full Capacity.2. 1st Stage Capacity is 70% of Full Capacity.3. ZR037, ZR049 and ZR061 have crankcase heaters standard.4. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value).5. 2 In. Pleated, Optional, MERV 8.6. 4 In. Pleated, Optional, MERV 13.

ZR037-061 Two Stage Gas Heat Physical Data (Continued)

Page 31: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 31

ZR078-150 Physical Data

ComponentModels

ZR078 ZR090 ZR102 ZR120 ZR150

Nominal Tonnage 6.5 7.5 8.5 10 12.5

AHRI COOLING PERFORMANCE

Gross Capacity @ AHRI A point (Mbh) 80000 90000 105000 124000 157000

AHRI net capacity (Mbh) 78000 88000 1020001/1000002 118000 150000

EER 11.2 11.2 11.2 11.2 11.0

IEER with Constant Volume3 12.5 12.5 12.41/12.22 11.4 11.4

IEER with Intellispeed 13 14.01/13.82 13.21/13.02 12.91/12.72 13.21/13.02

CFM 2200 2775 3350 3750 4450

System power (KW) 6.96 7.77 9.11 10.71 13.39

Refrigerant type R-410A R-410A R-410A R-410A R-410A

Refrigerant charge (lb-oz)

System 1 9-0 6-12 11-10 8-11 20-0

System 2 5-8 6-0 10-3 7-8 19-0

AHRI HEATING PERFORMANCE

Heating model N12 N18 N12 N18 N12 N18 N18 N24 N18 N24

Heat input (K Btu) 120 180 120 180 120 180 180 240 180 240

Heat output (K Btu) 96 144 96 144 96 144 144 192 144 192

AFUE % - - - - - - - - - -

Steady state efficiency (%) 80 80 80 80 80 80 80 80 80 80

No. burners 4 6 4 6 4 6 6 8 6 8

No. stages 24 24 24 24 24 24 24 24 24 24

Temperature Rise Range (ºF) 20-50 35-65 15-45 30-60 10-40 25-55 20-50 35-65 10-40 25-55

Gas Limit Setting (ºF) 165 165 165 165 215 195 195 160 195 160

Gas piping connection (in.) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

DIMENSIONS (inches)

Length 89 89 89 89 119-7/16

Width 59 59 59 59 59

Height 42 42 50-3/4 50-3/4 50-3/4

OPERATING WT. (lbs.) 957 965 1200 1200 1465

COMPRESSORS5

Type Scroll Scroll Scroll Scroll Scroll

Quantity 2 2 2 2 2

Unit Capacity Steps (%) 50 / 100 50 / 100 50 / 100 50 / 100 50 / 100

CONDENSER COIL DATA

Face area (Sq. Ft.) 23.8 23.8 29.0 29.0 47.5

Rows 2 / 1 1 2 1 2

Fins per inch 20 23 20 23 15

Tube diameter (in.) 3/8 - 3/8 - 3/8

Tube diameter (in.)/MM - 1/25 - 1/25 -

Circuitry Type Split-face2-pass

MicrochannelSplit-face

2-passMicrochannel

Split-face

EVAPORATOR COIL DATA

Face area (Sq. Ft.) 10.6 10.6 13.2 13.2 13.2

Rows 3 3 4 4 4

Fins per inch 15 15 15 15 15

Tube diameter 3/8 3/8 3/8 3/8 3/8

Circuitry Type Split-face Split-face Split-face Split-face Split-face

Refrigerant control TXV TXV TXV TXV TXV

Page 32: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

32 Johnson Controls Ducted Systems

REHEAT COIL DATA

Face area (Sq. Ft.) 6.66 6.66 10 10 10

Rows 2 2 2 2 2

Fins per inch 13 13 13 13 13

Tube diameter (in.) 3/8 3/8 3/8 3/8 3/8

CONDENSER FAN DATA

Quantity of Fans 2 2 2 2 4

Fan diameter (Inch) 24 24 24 24 24

Type Prop Prop Prop Prop Prop

Drive type Direct Direct Direct Direct Direct

Quantity of motors 2 2 2 2 4

Motor HP each 1/3 1/3 1/3 3/4 1/3

No. speeds 1 1 1 1 1

RPM 850 850 850 1110 850

Total CFM 6800 6800 6800 9500 14000

BELT DRIVE EVAP FAN DATA

Quantity 1 1 1 1 1

Fan Size (Inch) 12 x 12 12 x 12 15 x 15 15 x 15 15 x 15

Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal

Motor Sheave 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VP56

Blower Sheave AK74 AK64 AK74 AK61 AK89 AK74 AK84 AK74 AK74 BK77

Belt A49 A49 A49 A49 A56 A54 A56 A54 A54 BX55

Motor HP each 1-1/2 2 1-1/2 3 2 3 2 3 3 5

RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725

Frame size 56 56 56 56 56 56 56 56 56 184T

FILTERS

Quantity - Size4 - (24 x 16 x 2)6,7 4 - (24 x 16 x 2)6,7 4 - (24 x 20 x 2)6,7 4 - (24 x 20 x 2)6,7 4 - (24 x 20 x 2)6,7

4 - (24 x 16 x 4)8 4 - (24 x 16 x 4)8 4 - (24 x 20 x 4)8 4 - (24 x 20 x 4)8 4 - (24 x 20 x 4)8

1. Cooling Only Unit or Cooling Unit with Electric Heat2. Cooling Unit with Gas Heat3. Does not meet DOE 2018 minimum efficiency requirements.4. 1st Stage 60% of 2nd Stage5. ZR90, ZR102, ZR120, ZR150, have crankcase heaters standard.6. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.7. 2 In. Pleated, Optional, MERV 8.8. 4 In. Pleated, Optional, MERV 13.

ZR078-150 Physical Data (Continued)

ComponentModels

ZR078 ZR090 ZR102 ZR120 ZR150

Nominal Tonnage 6.5 7.5 8.5 10 12.5

Page 33: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 33

ZH/ZJ/ZR078-150 Unit Limitations

Size(Tons)

Model Unit Voltage SCCR (kVA)

Unit Limitations

Applied Voltage Outdoor DB Temp

Min Max Max (°F)

037(3)

ZH/ZJ/ZR

208/230-3-60 5 187 252 125

460-3-60 5 432 504 125

575-3-60 5 540 630 125

049(4)

ZH/ZJ/ZR

208/230-3-60 5 187 252 125

460-3-60 5 432 504 125

575-3-60 5 540 630 125

061(5)

ZH/ZJ/ZR

208/230-3-60 5 187 252 125

460-3-60 5 432 504 125

575-3-60 5 540 630 125

078(6.5)

ZH/ZJ/ZR

208/230-3-60 5 187 252 125

460-3-60 5 432 504 125

575-3-60 5 540 630 125

090(7.5)

ZH/ZJ/ZR

208/230-3-60 5 187 252 125

460-3-60 5 432 504 125

575-3-60 5 540 630 125

102(8.5)

ZH/ZJ/ZR

208/230-3-60 5 187 252 125

460-3-60 5 432 504 125

575-3-60 5 540 630 125

120(10)

ZH/ZJ/ZR

208/230-3-60 5 187 252 125

460-3-60 5 432 504 125

575-3-60 5 540 630 125

150(12.5)

ZH/ZJ/ZR

208/230-3-60 5 187 252 125

460-3-60 5 432 504 125

575-3-60 5 540 630 125

Page 34: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

34 Johnson Controls Ducted Systems

Capacity Performance

ZH037-150 Cooling Capacities

ZH037 (3.0 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

750

77 46.5 2.2 23.8 20.5 17.2 - - - 44.7 2.4 22.3 19.1 15.9 - - -

72 42.2 2.1 29.1 25.2 21.2 17.2 - - 40.4 2.4 28.2 24.2 20.2 16.2 - -

67 37.9 2.1 34.5 29.8 25.2 21.1 17.2 - 36.1 2.4 34.1 29.3 24.6 20.4 16.4 -

62 36.5 2.1 36.5 32.9 29.2 24.1 21.1 17.1 35.3 2.4 35.3 32.1 28.9 24.2 20.5 16.3

900

77 46.6 2.2 27.0 22.3 17.6 - - - 44.7 2.4 26.0 21.3 16.5 - - -

72 43.0 2.1 31.8 27.1 22.4 17.7 - - 41.1 2.4 31.0 26.3 21.5 16.8 - -

67 39.3 2.1 36.6 31.9 27.2 22.4 17.7 - 37.5 2.4 36.0 31.3 26.6 21.7 16.9 -

62 38.2 2.1 38.2 35.1 32.1 26.4 22.5 17.6 36.9 2.4 36.9 34.2 31.6 26.3 21.8 16.9

57 37.1 2.1 37.1 37.1 36.9 32.0 27.2 22.3 36.3 2.4 36.3 36.3 36.3 31.6 26.6 21.6

1050

77 46.8 2.2 30.2 24.1 17.9 - - - 44.6 2.4 29.7 23.4 17.1 - - -

72 43.8 2.1 34.5 29.0 23.6 18.2 - - 41.8 2.4 33.8 28.3 22.8 17.4 - -

67 40.8 2.1 38.7 34.0 29.3 23.7 18.3 - 39.0 2.4 37.8 33.2 28.6 23.0 17.5 -

62 39.9 2.1 39.9 37.4 34.9 28.7 23.8 18.2 38.5 2.4 38.5 36.4 34.3 28.4 23.1 17.4

57 39.1 2.1 39.1 39.1 39.0 35.0 29.3 23.7 38.0 2.4 38.0 38.0 38.0 34.3 28.6 22.9

1200

77 46.9 2.2 33.4 25.9 18.3 - - - 44.5 2.4 33.4 25.5 17.7 - - -

72 44.5 2.2 37.1 31.0 24.8 18.7 - - 42.5 2.4 36.5 30.3 24.2 18.0 - -

67 42.2 2.1 40.8 36.1 31.3 25.0 18.8 - 40.4 2.4 39.7 35.1 30.6 24.3 18.1 -

62 41.6 2.1 41.6 39.7 37.8 31.0 25.1 18.8 40.1 2.4 40.1 38.6 37.0 30.5 24.3 18.0

57 41.1 2.1 41.1 41.1 41.1 37.9 31.5 25.1 39.8 2.4 39.8 39.8 39.8 37.0 30.6 24.1

1350

72 45.3 2.2 39.8 32.9 26.0 19.1 - - 43.2 2.4 39.3 32.4 25.5 18.6 - -

67 43.6 2.1 42.9 38.1 33.3 26.3 19.4 - 41.9 2.4 41.5 37.1 32.6 25.6 18.6 -

62 43.3 2.1 43.3 42.0 40.6 33.3 26.5 19.4 41.7 2.4 41.7 40.7 39.8 32.6 25.6 18.5

57 43.0 2.1 43.0 43.0 43.0 40.8 33.6 26.4 41.5 2.4 41.5 41.5 41.5 39.7 32.6 25.4

1500

72 46.1 2.2 42.4 34.8 27.2 19.6 - - 43.9 2.4 42.0 34.4 26.8 19.1 - -

67 45.1 2.2 45.1 40.2 35.4 27.6 19.9 - 43.3 2.4 43.3 39.0 34.6 26.9 19.2 -

62 45.0 2.2 45.0 44.3 43.5 35.7 27.8 20.0 43.3 2.4 43.3 42.9 42.5 34.7 26.9 19.1

57 45.0 2.2 45.0 45.0 45.0 43.7 35.7 27.8 43.3 2.4 43.3 43.3 43.3 42.4 34.5 26.7

95°F 105°F

750

77 43.0 2.7 20.9 17.8 14.7 - - - 39.9 3.1 21.6 18.0 14.3 - - -

72 38.6 2.7 27.3 23.3 19.3 15.3 - - 36.3 3.0 27.0 22.9 18.7 14.5 - -

67 34.3 2.6 33.8 28.9 23.9 19.7 15.6 - 32.7 3.0 32.4 27.7 23.1 18.9 14.8 -

62 34.1 2.6 34.1 31.3 28.5 24.2 19.9 15.6 32.6 3.0 32.6 30.0 27.5 23.3 19.1 15.0

900

77 42.7 2.7 25.0 20.3 15.5 - - - 39.8 3.1 25.2 20.0 14.7 - - -

72 39.2 2.7 30.2 25.4 20.7 15.9 - - 36.9 3.1 29.5 24.7 19.9 15.1 - -

67 35.7 2.6 35.4 30.6 25.9 21.0 16.2 - 34.1 3.0 33.8 29.5 25.1 20.2 15.3 -

62 35.6 2.6 35.6 33.4 31.1 26.1 21.1 16.1 34.0 3.0 34.0 32.1 30.3 25.3 20.3 15.4

57 35.5 2.6 35.5 35.5 35.5 31.2 26.1 21.0 33.9 3.0 33.9 33.9 33.9 30.4 25.3 20.3

1050

77 42.5 2.7 29.2 22.7 16.3 - - - 39.8 3.1 28.8 22.0 15.2 - - -

72 39.8 2.7 33.1 27.6 22.1 16.6 - - 37.6 3.1 32.0 26.6 21.1 15.7 - -

67 37.2 2.7 36.9 32.4 27.9 22.3 16.7 - 35.5 3.0 35.3 31.2 27.1 21.5 15.9 -

62 37.1 2.7 37.1 35.4 33.7 28.0 22.3 16.6 35.4 3.0 35.4 34.2 33.0 27.3 21.5 15.8

57 37.0 2.7 37.0 37.0 37.0 33.7 27.9 22.1 35.3 3.0 35.3 35.3 35.3 33.1 27.2 21.3

1200

77 42.2 2.7 33.4 25.2 17.1 - - - 39.7 3.1 32.4 24.0 15.6 - - -

72 40.4 2.7 35.9 29.7 23.5 17.3 - - 38.3 3.1 34.6 28.5 22.4 16.3 - -

67 38.7 2.7 38.5 34.2 29.9 23.6 17.3 - 36.8 3.1 36.7 32.9 29.1 22.8 16.4 -

62 38.6 2.7 38.6 37.4 36.3 29.9 23.5 17.1 36.8 3.1 36.8 36.3 35.8 29.3 22.7 16.2

57 38.5 2.7 38.5 38.5 38.5 36.2 29.7 23.2 36.7 3.1 36.7 36.7 36.7 35.8 29.0 22.2

1350

72 41.0 2.7 38.8 31.8 24.9 18.0 - - 38.9 3.1 37.1 30.3 23.6 16.8 - -

67 40.1 2.7 40.1 36.0 31.9 24.9 17.9 - 38.2 3.1 38.1 34.6 31.1 24.0 17.0 -

62 40.1 2.7 40.1 39.5 38.9 31.8 24.7 17.6 38.2 3.1 38.2 38.2 38.2 31.2 23.9 16.6

57 40.0 2.7 40.0 40.0 40.0 38.7 31.5 24.4 38.1 3.1 38.1 38.1 38.1 38.1 30.8 23.2

1500

72 41.6 2.7 41.6 34.0 26.315 18.6 - - 39.6 3.1 39.6 32.2 24.8 17.4 - -

67 41.6 2.7 41.6 37.7 33.9 26.2 18.4 - 39.6 3.1 39.6 36.3 33.1 25.3 17.5 -

62 41.6 2.7 41.6 41.5 41.4 33.7 25.9 18.1 39.6 3.1 39.6 39.6 39.6 33.2 25.1 17.0

57 41.6 2.7 41.6 41.6 41.6 41.2 33.4 25.5 39.5 3.1 39.5 39.5 39.5 39.5 32.6 24.1

Page 35: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 35

115°F 125°F

750

77 36.8 3.5 22.4 18.2 13.9 - - - 33.7 3.8 23.1 18.4 13.6 - - -

72 34.0 3.4 26.7 22.4 18.1 13.8 - - 31.6 3.8 26.4 21.9 17.5 13.1 - -

67 31.1 3.4 31.0 26.6 22.3 18.1 14.0 - 29.6 3.8 29.6 25.5 21.5 17.3 13.2 -

62 31.1 3.4 31.1 28.8 26.5 22.4 18.4 14.3 29.6 3.8 29.6 27.5 25.4 21.5 17.6 13.7

900

77 36.9 3.5 25.4 19.7 14.0 - - - 34.0 3.8 25.6 19.4 13.3 - - -

72 34.7 3.4 28.9 24.0 19.2 14.3 - - 32.4 3.8 28.2 23.3 18.4 13.5 - -

67 32.4 3.4 32.3 28.3 24.3 19.4 14.5 - 30.8 3.8 30.8 27.1 23.5 18.6 13.7 -

62 32.4 3.4 32.4 30.9 29.4 24.5 19.6 14.6 30.8 3.8 30.8 29.7 28.6 23.7 18.8 13.9

57 32.3 3.4 32.3 32.3 32.3 29.6 24.6 19.6 30.8 3.8 30.8 30.8 30.8 28.8 23.9 19.0

1050

77 37.1 3.5 28.5 21.3 14.1 - - - 34.4 3.8 28.1 20.5 13.0 - - -

72 35.4 3.4 31.0 25.6 20.2 14.8 - - 33.2 3.8 30.0 24.6 19.2 13.8 - -

67 33.7 3.4 33.6 30.0 26.3 20.7 15.0 - 32.0 3.8 32.0 28.7 25.5 19.8 14.2 -

62 33.7 3.4 33.7 33.0 32.4 26.6 20.7 14.9 31.9 3.8 31.9 31.8 31.7 25.8 20.0 14.1

57 33.6 3.4 33.6 33.6 33.6 32.5 26.4 20.4 31.9 3.8 31.9 31.9 31.9 31.9 25.7 19.6

1200

77 37.2 3.5 31.5 22.8 14.2 - - - 34.8 3.8 30.6 21.6 12.7 - - -

72 36.1 3.4 33.2 27.2 21.2 15.2 - - 34.0 3.8 31.9 26.0 20.1 14.2 - -

67 35.0 3.4 34.9 31.6 28.3 21.9 15.6 - 33.1 3.8 33.1 30.3 27.5 21.1 14.7 -

62 34.9 3.4 34.9 34.9 34.9 28.6 21.9 15.2 33.1 3.8 33.1 33.1 33.1 28.0 21.1 14.2

57 34.9 3.4 34.9 34.9 34.9 34.9 28.3 21.2 33.1 3.8 33.1 33.1 33.1 33.1 27.5 20.2

1350

72 36.8 3.5 35.4 28.8 22.2 15.7 - - 34.7 3.8 33.7 27.3 20.9 14.5 - -

67 36.3 3.4 36.2 33.3 30.3 23.2 16.1 - 34.3 3.8 34.3 31.9 29.5 22.3 15.2 -

62 36.2 3.5 36.2 36.2 36.2 30.7 23.1 15.5 34.3 3.8 34.3 34.3 34.3 30.2 22.3 14.4

57 36.2 3.5 36.2 36.2 36.2 36.2 30.1 22.0 34.3 3.8 34.3 34.3 34.3 34.3 29.4 20.7

1500

72 37.6 3.5 37.6 30.4 23.3 16.1 - - 35.5 3.9 35.5 28.6 21.8 14.9 - -

67 37.6 3.5 37.6 34.9 32.3 24.5 16.6 - 35.5 3.8 35.5 33.5 31.5 23.6 15.7 -

62 37.5 3.5 37.5 37.5 37.5 32.8 24.3 15.8 35.5 3.9 35.5 35.5 35.5 32.3 23.5 14.6

57 37.5 3.5 37.5 37.5 37.5 37.5 31.9 22.7 35.4 3.9 35.4 35.4 35.4 35.4 31.2 21.3

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZH037 (3.0 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 36: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

36 Johnson Controls Ducted Systems

ZH049 (4.0 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1000

77 60.6 2.7 32.1 27.3 22.5 - - - 58.2 3.0 30.6 26.4 22.2 - - -

72 55.4 2.6 38.5 33.2 27.8 22.5 - - 53.0 3.0 37.5 32.1 26.7 21.3 - -

67 50.1 2.6 45.0 39.1 33.2 27.7 22.5 - 47.8 2.9 44.3 37.7 31.1 26.2 21.4 -

62 48.1 2.6 54.6 41.8 38.6 38.0 27.8 22.4 46.4 2.9 44.9 40.3 35.6 30.2 26.9 22.6

1200

77 61.0 2.7 35.8 29.4 23.0 - - - 58.4 3.0 34.7 28.6 22.6 - - -

72 56.4 2.6 41.8 35.6 29.3 23.1 - - 53.9 3.0 40.7 34.5 28.2 22.0 - -

67 51.9 2.6 47.7 41.7 35.7 29.3 23.2 - 49.5 2.9 46.7 40.3 33.8 27.9 22.1 -

62 50.2 2.6 47.7 44.9 42.0 41.0 29.4 23.1 48.4 2.9 47.2 43.3 39.4 33.1 28.5 23.1

57 48.5 2.6 47.7 47.7 47.7 42.0 35.6 29.2 47.4 2.9 47.4 46.3 45.0 40.0 34.9 29.8

1400

77 61.4 2.7 39.5 31.5 23.5 - - - 58.5 3.0 38.7 30.8 23.0 - - -

72 57.5 2.6 45.0 37.9 30.8 23.8 - - 54.9 3.0 43.9 36.8 29.7 22.6 - -

67 53.6 2.6 50.5 44.3 38.2 30.9 23.8 - 51.2 2.9 49.2 42.8 36.5 29.6 22.8 -

62 52.3 2.6 50.5 48.0 45.5 36.9 31.0 23.7 50.4 2.9 49.5 46.4 43.2 36.0 30.1 23.5

57 51.1 2.6 50.4 50.4 50.4 45.5 38.1 30.8 49.6 2.9 49.6 49.5 49.0 43.6 37.3 31.0

1600

77 61.9 2.7 43.2 33.6 24.1 - - - 58.7 3.0 42.7 33.0 23.4 - - -

72 58.6 2.7 48.2 40.3 32.3 24.4 - - 55.8 3.0 47.1 39.2 31.3 23.3 - -

67 55.3 2.6 53.2 46.9 40.6 32.5 24.5 - 53.0 3.0 51.6 45.4 39.1 31.3 23.5 -

62 54.4 2.6 53.2 51.1 48.9 39.9 32.6 24.4 52.4 3.0 51.8 49.4 47.0 38.9 31.6 24.0

57 53.6 2.6 53.2 53.2 53.2 48.9 40.6 32.4 51.9 3.0 51.9 51.9 51.9 47.3 39.8 32.2

1800

72 59.7 2.7 51.4 42.6 33.8 25.0 - - 56.8 3.0 50.4 41.6 32.8 24.0 - -

67 57.0 2.6 56.0 49.5 43.1 34.1 25.2 - 54.7 3.0 54.0 47.9 41.8 33.0 24.2 -

62 56.6 2.6 56.0 54.1 52.3 42.8 34.2 25.1 54.4 3.0 54.1 52.5 50.8 41.8 33.2 24.4

57 56.1 2.6 55.9 55.9 55.9 52.4 43.2 33.9 54.2 3.0 54.2 54.2 54.2 51.0 42.2 33.4

2000

72 60.7 2.7 54.7 45.0 35.3 25.7 - - 57.7 3.0 53.6 44.0 34.3 24.7 - -

67 58.7 2.7 58.7 52.1 45.6 35.7 25.9 - 56.5 3.0 56.5 50.5 44.5 34.7 24.9 -

62 58.7 2.7 69.7 57.2 55.8 45.8 35.8 25.8 56.4 3.0 56.4 55.5 54.6 44.7 34.8 24.9

57 58.7 2.7 69.9 62.3 66.0 55.8 45.7 35.5 56.4 3.0 68.4 60.6 64.7 54.7 44.6 34.6

95°F 105°F

1000

77 55.9 3.3 29.2 25.6 22.0 - - - 52.2 3.8 29.1 24.9 20.7 - - -

72 50.6 3.3 36.4 31.0 25.5 20.1 - - 47.8 3.8 35.6 30.1 24.7 19.2 - -

67 45.4 3.2 43.6 36.4 29.1 24.7 20.4 - 43.3 3.7 42.1 35.4 28.7 24.0 19.3 -

62 44.8 3.2 44.8 38.7 32.6 29.4 26.1 22.8 42.9 3.7 42.9 37.8 32.7 28.8 24.9 21.0

1200

77 55.8 3.3 33.5 27.9 22.2 - - - 52.2 3.8 33.1 27.0 20.8 - - -

72 51.5 3.3 39.6 33.4 27.1 20.8 - - 48.6 3.8 38.6 32.3 26.1 19.8 - -

67 47.2 3.3 45.7 38.8 31.9 26.5 21.1 - 44.9 3.7 44.0 37.7 31.4 25.7 20.0 -

62 46.7 3.3 46.7 41.7 36.8 32.2 27.6 23.1 44.6 3.7 44.6 40.6 36.6 31.5 26.4 21.3

57 46.2 3.3 46.2 44.6 41.6 37.9 34.2 30.4 44.3 3.7 44.3 43.6 41.9 37.4 32.8 28.3

1400

77 55.6 3.3 37.8 30.2 22.5 - - - 52.3 3.8 37.2 29.1 20.9 - - -

72 52.3 3.3 42.9 35.7 28.6 21.5 - - 49.4 3.8 41.5 34.5 27.5 20.5 - -

67 48.9 3.3 47.9 41.3 34.8 28.3 21.8 - 46.6 3.7 45.9 40.0 34.1 27.4 20.7 -

62 48.6 3.3 48.6 44.8 40.9 35.1 29.2 23.3 46.4 3.7 46.4 43.5 40.6 34.3 27.9 21.6

57 48.2 3.3 48.2 48.2 47.1 41.8 36.5 31.3 46.1 3.7 46.1 46.1 46.1 41.2 35.2 29.2

1600

77 55.5 3.3 42.2 32.5 22.7 - - - 52.3 3.8 41.3 31.2 21.1 - - -

72 53.1 3.3 46.1 38.1 30.2 22.3 - - 50.3 3.8 44.5 36.7 28.9 21.1 - -

67 50.7 3.3 50.0 43.8 37.6 30.1 22.5 - 48.3 3.8 47.8 42.3 36.8 29.1 21.4 -

62 50.4 3.3 50.4 47.8 45.1 37.9 30.7 23.5 48.1 3.8 48.1 46.4 44.6 37.0 29.5 21.9

57 50.2 3.3 50.2 50.2 50.2 45.7 38.9 32.1 47.9 3.8 47.9 47.9 47.9 45.0 37.5 30.1

1800

72 53.9 3.3 49.3 40.5 31.8 23.0 - - 51.1 3.8 47.5 38.9 30.3 21.8 - -

67 52.4 3.3 52.1 46.3 40.5 31.9 23.2 - 49.9 3.8 49.7 44.6 39.5 30.8 22.1 -

62 52.3 3.3 52.3 50.8 49.3 40.7 32.2 23.7 49.8 3.8 49.8 49.2 48.6 39.8 31.0 22.2

57 52.2 3.3 52.2 52.2 52.2 49.6 41.3 32.9 49.7 3.8 49.7 49.7 49.7 48.8 39.9 31.0

2000

72 54.7 3.3 52.5 42.9 33.311 23.7 - - 51.9 3.8 50.5 41.1 31.8 22.4 - -

67 54.2 3.3 54.2 48.8 43.4 33.6 23.9 - 51.6 3.8 51.6 46.9 42.2 32.5 22.8 -

62 54.2 3.3 54.2 53.8 53.4 43.6 33.8 24.0 51.6 3.8 51.6 51.6 51.6 42.5 32.5 22.5

57 54.2 3.3 54.2 54.2 54.2 53.5 43.6 33.7 51.6 3.8 51.6 51.6 51.6 51.6 42.2 31.9

Page 37: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 37

115°F 125°F

1000

77 48.6 4.3 28.9 24.2 19.4 - - - 44.9 4.7 28.8 23.5 18.1 - - -

72 44.9 4.2 34.8 29.3 23.8 18.3 - - 42.0 4.7 34.0 28.5 23.0 17.5 - -

67 41.2 4.2 40.6 34.4 28.2 23.3 18.3 - 39.1 4.7 44.0 33.5 27.8 22.5 17.2 -

62 41.0 4.2 41.0 36.8 32.7 28.2 23.7 19.2 39.0 4.7 39.0 35.9 32.7 27.6 22.5 17.4

1200

77 48.7 4.3 32.7 26.1 19.4 - - - 45.2 4.7 32.3 25.2 18.0 - - -

72 45.7 4.2 37.5 31.3 25.1 18.9 - - 42.9 4.7 36.4 30.3 24.1 17.9 - -

67 42.7 4.2 42.3 36.5 30.8 24.9 18.9 - 40.5 4.7 46.2 35.4 30.2 24.1 17.9 -

62 42.6 4.2 42.6 39.5 36.5 30.8 25.2 19.6 40.5 4.7 40.5 38.4 36.3 30.2 24.0 17.8

57 42.4 4.2 42.4 42.4 42.2 36.8 31.5 26.1 40.4 4.7 46.4 41.5 42.5 36.3 30.1 23.9

1400

77 48.9 4.3 36.5 28.0 19.4 - - - 45.5 4.7 35.9 26.9 17.9 - - -

72 46.6 4.2 40.2 33.3 26.4 19.4 - - 43.7 4.7 38.9 32.1 25.2 18.4 - -

67 44.3 4.2 43.9 38.6 33.3 26.5 19.6 - 42.0 4.7 48.2 37.3 32.6 25.6 18.5 -

62 44.2 4.2 44.2 42.2 40.3 33.5 26.7 19.9 41.9 4.7 41.9 41.0 40.0 32.7 25.5 18.2

57 44.0 4.2 44.0 44.0 44.0 40.5 33.8 27.1 41.9 4.7 48.4 44.6 47.4 39.9 32.5 25.0

1600

77 49.0 4.3 40.3 29.9 19.4 - - - 45.8 4.7 39.4 28.6 17.8 - - -

72 47.4 4.2 43.0 35.3 27.6 20.0 - - 44.6 4.7 41.4 33.9 26.4 18.9 - -

67 45.8 4.2 45.6 40.7 35.9 28.1 20.3 - 43.4 4.7 50.2 39.2 35.0 27.1 19.2 -

62 45.7 4.2 45.7 44.9 44.1 36.2 28.2 20.3 43.4 4.7 43.4 43.4 43.4 35.3 27.0 18.7

57 45.7 4.2 45.7 45.7 45.7 44.3 36.2 28.1 43.4 4.7 50.4 47.8 50.4 43.5 34.8 26.1

1800

72 48.3 4.3 45.7 37.3 28.9 20.5 - - 45.5 4.7 43.9 35.7 27.5 19.3 - -

67 47.4 4.2 47.3 42.8 38.4 29.7 21.0 - 44.8 4.7 52.3 41.1 37.4 28.6 19.8 -

62 47.3 4.2 47.3 47.3 47.3 38.8 29.7 20.6 44.9 4.7 44.9 44.9 44.9 37.9 28.5 19.1

57 47.3 4.2 47.3 47.3 47.3 47.3 38.5 29.1 44.9 4.7 52.5 51.0 52.5 47.1 37.2 27.2

2000

72 49.1 4.3 48.4 39.3 30.2 21.1 - - 46.4 4.7 46.4 37.5 28.6 19.8 - -

67 48.9 4.3 48.9 44.9 41.0 31.3 21.6 - 46.3 4.7 46.3 43.0 39.8 30.1 20.5 -

62 48.9 4.3 48.9 48.9 48.9 41.5 31.2 21.0 46.3 4.7 46.3 46.3 46.3 40.4 30.0 19.5

57 48.9 4.3 48.9 48.9 48.9 48.9 40.9 30.1 46.3 4.7 46.3 46.3 46.3 46.3 39.5 28.2

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZH049 (4.0 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 38: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

38 Johnson Controls Ducted Systems

ZH061 (5.0 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1250

77 76.9 3.6 39.7 34.1 28.4 - - - 74.0 4.1 37.8 32.3 26.8 - - -

72 69.9 3.6 48.5 41.8 35.1 28.5 - - 67.0 4.0 47.1 40.4 33.7 27.0 - -

67 63.0 3.5 57.3 49.6 41.9 35.1 28.4 - 60.0 4.0 56.4 48.5 40.5 33.8 27.1 -

62 60.4 3.5 54.6 52.9 48.6 38.0 35.0 28.2 58.4 4.0 56.8 52.1 47.4 39.4 34.0 27.3

1500

77 77.2 3.7 44.7 37.0 29.2 - - - 74.0 4.1 43.4 35.6 27.8 - - -

72 71.2 3.6 52.7 44.9 37.1 29.3 - - 68.2 4.0 51.4 43.6 35.7 27.9 - -

67 65.3 3.6 60.7 52.9 45.1 37.2 29.3 - 62.3 4.0 59.4 51.6 43.7 35.9 28.1 -

62 63.2 3.6 60.7 56.8 53.0 41.0 37.1 29.1 61.0 4.0 59.8 55.7 51.7 42.8 36.0 28.2

57 61.1 3.5 60.7 60.7 60.7 52.9 44.9 36.8 59.8 4.0 59.8 59.8 59.6 51.8 44.0 36.2

1750

77 77.6 3.7 49.8 39.9 30.0 - - - 74.0 4.1 49.0 38.9 28.7 - - -

72 72.6 3.6 56.9 48.0 39.1 30.2 - - 69.3 4.0 55.7 46.8 37.8 28.9 - -

67 67.5 3.6 64.1 56.2 48.2 39.2 30.2 - 64.6 4.0 62.5 54.7 46.9 37.9 29.0 -

62 66.0 3.6 64.1 60.7 57.3 46.7 39.2 30.1 63.7 4.0 62.7 59.3 56.0 46.2 38.1 29.1

57 64.4 3.6 64.1 64.1 64.1 57.3 48.1 38.9 62.7 4.0 62.7 62.7 62.7 56.1 47.2 38.2

2000

77 77.9 3.7 54.8 42.8 30.8 - - - 74.1 4.1 54.6 42.2 29.7 - - -

72 73.9 3.6 61.2 51.1 41.1 31.1 - - 70.5 4.1 60.1 50.0 39.9 29.8 - -

67 69.8 3.6 67.5 59.5 51.4 41.3 31.1 - 67.0 4.0 65.5 57.8 50.1 40.0 29.9 -

62 68.8 3.6 67.5 64.6 61.7 50.5 41.2 31.0 66.3 4.0 65.7 63.0 60.2 49.7 40.1 30.0

57 67.7 3.6 67.5 67.5 67.5 61.7 51.3 41.0 65.6 4.0 65.6 65.6 65.6 60.4 50.3 40.2

2250

72 75.2 3.6 65.4 54.3 43.1 32.0 - - 71.7 4.1 64.4 53.2 42.0 30.7 - -

67 72.1 3.6 71.0 62.8 54.6 43.3 32.1 - 69.3 4.0 68.6 60.9 53.2 42.0 30.8 -

62 71.6 3.6 70.9 68.5 66.1 54.2 43.3 31.9 68.9 4.0 68.6 66.6 64.5 53.1 42.1 30.9

57 71.0 3.6 70.9 70.9 70.9 66.1 54.6 43.1 68.6 4.0 68.6 68.6 68.6 64.6 53.4 42.2

2500

72 76.5 3.6 69.6 57.4 45.1 32.8 - - 72.8 4.1 68.7 56.4 44.0 31.7 - -

67 74.4 3.6 74.4 66.1 57.8 45.4 33.0 - 71.6 4.1 71.6 64.0 56.4 44.1 31.8 -

62 74.3 3.6 69.7 69.7 69.7 57.9 45.4 32.8 71.6 4.1 71.6 70.2 68.8 56.5 44.2 31.8

57 74.3 3.6 69.9 69.9 69.9 69.9 57.8 45.1 71.5 4.1 68.4 68.4 68.4 68.4 56.6 44.2

95°F 105°F

1250

77 71.2 4.5 35.9 30.6 25.2 - - - 66.4 5.1 36.1 30.3 24.4 - - -

72 64.1 4.5 45.7 39.0 32.2 25.5 - - 60.4 5.0 44.8 38.0 31.2 24.4 - -

67 57.0 4.4 55.6 47.4 39.2 32.5 25.8 - 54.5 5.0 53.5 45.7 38.0 31.3 24.6 -

62 56.4 4.4 56.4 51.3 46.1 39.6 33.0 26.4 54.0 5.0 54.0 49.4 44.7 38.2 31.6 25.1

1500

77 70.8 4.5 42.1 34.2 26.4 - - - 66.3 5.1 41.7 33.3 24.9 - - -

72 65.1 4.5 50.1 42.2 34.4 26.5 - - 61.5 5.0 48.8 40.9 33.1 25.2 - -

67 59.4 4.4 58.2 50.3 42.4 34.6 26.8 - 56.7 5.0 55.9 48.6 41.2 33.3 25.5 -

62 58.9 4.4 58.9 54.6 50.4 42.7 35.0 27.3 56.3 5.0 56.3 52.8 49.3 41.5 33.7 25.8

57 58.4 4.4 58.4 58.4 58.3 50.8 43.2 35.6 56.0 5.0 56.0 56.0 56.0 49.6 41.8 34.0

1750

77 70.5 4.5 48.2 37.9 27.5 - - - 66.3 5.1 47.3 36.4 25.5 - - -

72 66.1 4.5 54.5 45.5 36.5 27.5 - - 62.6 5.0 52.8 43.9 34.9 26.0 - -

67 61.7 4.4 60.9 53.2 45.5 36.6 27.7 - 58.9 5.0 58.3 51.4 44.4 35.4 26.4 -

62 61.4 4.4 61.4 58.0 54.6 45.8 37.0 28.2 58.6 5.0 58.6 56.3 53.9 44.8 35.7 26.6

57 61.0 4.4 61.0 61.0 61.0 54.9 46.2 37.6 58.4 5.0 58.4 58.4 58.4 54.2 45.0 35.8

2000

77 70.2 4.5 54.4 41.5 28.6 - - - 66.2 5.1 53.0 39.5 26.0 - - -

72 67.1 4.5 59.0 48.8 38.7 28.5 - - 63.7 5.1 56.8 46.8 36.8 26.8 - -

67 64.1 4.5 63.5 56.1 48.7 38.7 28.7 - 61.1 5.0 60.7 54.2 47.6 37.4 27.2 -

62 63.8 4.4 63.8 61.3 58.8 48.9 39.0 29.1 60.9 5.0 60.9 59.7 58.5 48.1 37.7 27.3

57 63.6 4.4 63.6 63.6 63.6 59.1 49.3 39.5 60.7 5.0 60.7 60.7 60.7 58.7 48.2 37.6

2250

72 68.1 4.5 63.4 52.1 40.8 29.5 - - 64.7 5.1 60.9 49.8 38.7 27.6 - -

67 66.5 4.5 66.2 59.0 51.9 40.7 29.6 - 63.4 5.1 63.2 57.0 50.9 39.5 28.1 -

62 66.3 4.5 66.3 64.6 63.0 52.0 41.0 29.9 63.2 5.1 63.2 63.1 63.1 51.4 39.7 28.0

57 66.2 4.5 66.2 66.2 66.2 63.2 52.3 41.4 63.1 5.1 63.1 63.1 63.1 63.1 51.3 39.4

2500

72 69.2 4.5 67.8 55.4 42.95 30.5 - - 65.8 5.1 64.9 52.7 40.5 28.4 - -

67 68.8 4.5 68.8 61.9 55.1 42.8 30.5 - 65.6 5.1 65.6 59.8 54.1 41.5 29.0 -

62 68.8 4.5 68.8 68.0 67.2 55.1 42.9 30.8 65.5 5.1 65.5 65.5 65.5 54.7 41.7 28.8

57 68.7 4.5 68.7 68.7 68.7 67.3 55.4 43.4 65.5 5.1 65.5 65.5 65.5 65.5 54.5 41.1

Page 39: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 39

115°F 125°F

1250

77 61.6 5.6 36.3 30.0 23.6 - - - 56.9 6.2 36.5 29.6 22.8 - - -

72 56.8 5.6 43.9 37.0 30.2 23.3 - - 53.1 6.2 42.9 36.1 29.2 22.3 - -

67 51.9 5.6 51.4 44.1 36.8 30.1 23.4 - 49.4 6.1 44.0 42.5 35.6 28.9 22.2 -

62 51.7 5.6 51.7 47.5 43.3 36.8 30.3 23.8 49.3 6.2 49.3 45.6 41.9 35.4 28.9 22.4

1500

77 61.8 5.6 41.4 32.4 23.5 - - - 57.3 6.2 41.0 31.6 22.1 - - -

72 57.9 5.6 47.5 39.6 31.8 23.9 - - 54.3 6.2 46.2 38.3 30.5 22.6 - -

67 54.0 5.6 53.6 46.8 40.0 32.1 24.2 - 51.3 6.2 46.2 45.1 38.9 30.9 22.9 -

62 53.8 5.6 53.8 51.0 48.3 40.3 32.3 24.4 51.3 6.2 51.3 49.3 47.2 39.1 31.0 22.9

57 53.6 5.6 53.6 53.6 53.6 48.5 40.5 32.4 51.2 6.2 46.4 46.4 46.4 46.4 39.1 30.9

1750

77 62.0 5.6 46.4 34.9 23.4 - - - 57.8 6.2 45.5 33.5 21.4 - - -

72 59.1 5.6 51.1 42.2 33.4 24.5 - - 55.5 6.2 49.4 40.6 31.8 23.0 - -

67 56.1 5.6 55.8 49.5 43.3 34.1 25.0 - 53.3 6.2 48.2 47.7 42.2 32.9 23.6 -

62 55.9 5.6 55.9 54.6 53.2 43.8 34.4 25.0 53.2 6.2 53.2 52.9 52.6 42.8 33.1 23.3

57 55.7 5.6 55.7 55.7 55.7 53.5 43.8 34.1 53.1 6.2 48.4 48.4 48.4 48.4 42.5 32.3

2000

77 62.2 5.6 51.5 37.4 23.3 - - - 58.2 6.2 50.1 35.4 20.7 - - -

72 60.2 5.6 54.7 44.8 34.9 25.0 - - 56.7 6.2 52.6 42.9 33.1 23.3 - -

67 58.2 5.6 58.0 52.3 46.6 36.2 25.8 - 55.2 6.2 50.2 50.2 45.5 34.9 24.4 -

62 58.0 5.6 58.0 58.0 58.0 47.3 36.4 25.5 55.1 6.2 55.1 55.1 55.1 46.5 35.2 23.8

57 57.9 5.6 57.9 57.9 57.9 57.9 47.1 35.7 55.1 6.2 50.4 50.4 50.4 50.4 46.0 33.8

2250

72 61.3 5.6 58.4 47.5 36.5 25.6 - - 57.9 6.2 55.9 45.1 34.4 23.7 - -

67 60.2 5.6 60.1 55.0 49.8 38.2 26.6 - 57.1 6.2 52.3 52.3 48.8 36.9 25.1 -

62 60.2 5.6 60.2 60.2 60.2 50.8 38.5 26.1 57.1 6.2 57.1 57.1 57.1 50.2 37.2 24.2

57 60.1 5.6 60.1 60.1 60.1 60.1 50.4 37.3 57.0 6.2 52.5 52.5 52.5 52.5 49.4 35.3

2500

72 62.5 5.7 62.0 50.1 38.1 26.2 - - 59.1 6.2 59.1 47.4 35.7 24.0 - -

67 62.3 5.7 62.3 57.7 53.1 40.2 27.4 - 59.1 6.2 59.1 55.6 52.1 39.0 25.8 -

62 62.3 5.7 62.3 62.3 62.3 54.3 40.5 26.7 59.0 6.2 59.0 59.0 59.0 53.9 39.3 24.7

57 62.3 5.7 62.3 62.3 62.3 62.3 53.6 38.9 59.0 6.2 59.0 59.0 59.0 59.0 52.8 36.7

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZH061 (5.0 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 40: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

40 Johnson Controls Ducted Systems

ZH078 (6.5 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1625

77 100.9 5.1 53.4 46.0 38.5 - - - 93.6 5.8 50.8 43.4 36.0 - - -

72 92.5 5.1 62.8 54.6 46.4 38.1 - - 86.6 5.7 60.5 52.2 44.0 35.7 - -

67 84.1 5.1 72.2 63.2 54.2 46.1 37.9 - 79.5 5.7 70.2 61.0 51.9 43.9 35.8 -

62 78.8 5.1 78.8 70.5 62.1 52.8 45.9 37.8 75.4 5.7 75.4 67.6 59.9 51.4 44.1 36.2

1950

77 102.0 5.1 58.7 49.0 39.2 - - - 96.4 5.8 56.4 46.7 36.9 - - -

72 94.3 5.1 67.9 58.3 48.629 39.0 - - 89.3 5.8 65.5 55.9 46.3 36.6 - -

67 86.7 5.1 77.1 67.6 58.0 48.5 38.9 - 82.1 5.7 74.6 65.1 55.7 46.2 36.8 -

62 82.4 5.1 82.4 74.9 67.4 57.0 48.5 39.0 78.8 5.7 78.8 71.9 65.1 55.3 46.6 37.3

57 78.2 5.1 78.2 78.2 76.8 67.4 58.0 48.6 75.5 5.7 75.5 75.5 74.5 65.4 56.4 47.3

2275

77 103.1 5.1 64.0 52.0 40.0 - - - 99.3 5.8 62.1 49.9 37.7 - - -

72 96.2 5.1 73.0 62.0 50.9 39.8 - - 92.0 5.8 70.5 59.6 48.6 37.6 - -

67 89.2 5.1 82.1 71.9 61.8 50.8 39.9 - 84.6 5.7 79.0 69.2 59.4 48.6 37.8 -

62 86.0 5.1 86.0 79.4 72.7 61.1 51.0 40.2 82.2 5.7 82.2 76.2 70.3 59.3 49.1 38.5

57 82.8 5.1 82.8 82.8 82.2 72.9 62.2 51.4 79.7 5.7 79.7 79.7 79.7 70.7 60.3 49.9

2600

77 104.1 5.1 69.3 55.0 40.8 - - - 102.1 5.8 67.7 53.1 38.5 - - -

72 98.0 5.1 78.2 65.7 53.2 40.7 - - 94.7 5.8 75.6 63.2 50.8 38.5 - -

67 91.8 5.1 87.0 76.3 65.6 53.2 40.9 - 87.2 5.7 83.5 73.3 63.2 51.0 38.8 -

62 89.7 5.1 89.7 83.8 78.0 65.3 53.6 41.4 85.5 5.7 85.5 80.5 75.5 63.3 51.5 39.6

57 87.5 5.1 87.5 87.5 87.5 78.3 66.3 54.2 83.9 5.7 83.9 83.9 83.9 76.0 64.3 52.5

2925

72 99.8 5.1 83.3 69.4 55.4 41.5 - - 97.4 5.8 80.6 66.9 53.1 39.4 - -

67 94.4 5.1 92.0 80.7 69.4 55.6 41.9 - 89.8 5.8 87.9 77.4 66.9 53.4 39.8 -

62 93.3 5.1 93.3 88.3 83.3 69.5 56.1 42.6 88.9 5.8 88.9 84.8 80.7 67.2 54.0 40.7

57 92.2 5.1 92.2 92.2 92.2 83.8 70.4 57.0 88.0 5.7 88.0 88.0 88.0 81.3 68.2 55.1

3250

72 101.6 5.1 88.4 73.1 57.72 42.4 - - 100.1 5.8 85.6 70.5 55.4 40.3 - -

67 97.0 5.1 97.0 85.1 73.2 58.0 42.9 - 92.3 5.8 92.3 81.5 70.6 55.7 40.8 -

62 96.9 5.1 96.9 92.7 88.6 73.6 58.7 43.7 92.3 5.8 92.3 89.1 85.9 71.2 56.5 41.8

57 96.9 5.1 96.9 96.9 96.9 89.3 74.5 59.8 92.2 5.8 92.2 92.2 92.2 86.7 72.2 57.7

95°F 105°F

1625

77 86.2 6.4 48.2 40.9 33.6 - - - 82.4 7.2 46.5 39.2 31.9 - - -

72 80.6 6.4 58.2 49.9 41.6 33.3 - - 76.3 7.2 56.2 48.0 39.8 31.6 - -

67 74.9 6.4 68.2 58.9 49.6 41.6 33.7 - 70.5 7.2 66.0 56.9 47.7 39.8 31.8 -

62 72.0 6.3 72.0 64.8 57.6 49.9 42.3 34.6 68.5 7.2 68.5 62.1 55.6 47.9 40.2 32.5

1950

77 90.8 6.4 54.2 44.3 34.5 - - - 85.2 7.2 52.5 42.5 32.6 - - -

72 84.2 6.4 63.1 53.5 43.909 34.3 - - 79.1 7.2 61.0 51.5 42.0 32.5 - -

67 77.5 6.4 72.1 62.7 53.3 44.0 34.7 - 73.0 7.2 69.4 60.4 51.4 42.1 32.8 -

62 75.1 6.3 75.1 68.9 62.7 53.7 44.7 35.7 71.4 7.2 71.4 66.1 60.8 51.7 42.6 33.5

57 72.8 6.3 72.8 72.8 72.1 63.4 54.7 46.0 69.8 7.2 69.8 69.8 69.8 61.3 52.3 43.4

2275

77 95.5 6.4 60.1 47.8 35.4 - - - 88.1 7.2 58.5 45.9 33.3 - - -

72 87.7 6.4 68.1 57.1 46.2 35.3 - - 81.9 7.2 65.7 54.9 44.2 33.4 - -

67 80.0 6.4 76.0 66.5 57.0 46.4 35.7 - 75.5 7.2 72.8 63.9 55.1 44.4 33.8 -

62 78.3 6.4 78.3 73.1 67.8 57.5 47.1 36.7 74.3 7.2 74.3 70.1 65.9 55.4 44.9 34.4

57 76.5 6.4 76.5 76.5 76.5 68.6 58.5 48.4 73.1 7.2 73.1 73.1 73.1 66.4 56.0 45.6

2600

77 100.1 6.4 66.1 51.2 36.3 - - - 90.9 7.2 64.6 49.3 34.0 - - -

72 91.3 6.4 73.0 60.7 48.5 36.3 - - 84.7 7.2 70.4 58.4 46.4 34.4 - -

67 82.6 6.4 79.9 70.3 60.7 48.7 36.8 - 78.1 7.2 76.3 67.5 58.7 46.8 34.8 -

62 81.4 6.4 81.4 77.2 73.0 61.2 49.5 37.8 77.2 7.2 77.2 74.2 71.1 59.2 47.2 35.3

57 80.2 6.4 80.2 80.2 80.2 73.7 62.2 50.8 76.4 7.2 76.4 76.4 76.4 71.5 59.7 47.8

2925

72 94.9 6.4 77.9 64.4 50.8 37.2 - - 87.5 7.2 75.1 61.9 48.6 35.3 - -

67 85.2 6.4 83.8 74.1 64.4 51.1 37.8 - 80.6 7.2 79.7 71.0 62.4 49.1 35.8 -

62 84.5 6.4 84.5 81.3 78.1 65.0 51.9 38.8 80.1 7.2 80.1 78.2 76.2 62.9 49.6 36.2

57 83.9 6.4 83.9 83.9 83.9 78.9 66.0 53.2 79.7 7.2 79.7 79.7 79.7 76.7 63.3 50.0

3250

72 98.5 6.4 82.9 68.0 53.095 38.2 - - 90.3 7.2 79.9 65.3 50.8 36.2 - -

67 87.7 6.4 87.7 77.9 68.1 53.5 38.8 - 83.1 7.2 83.1 74.6 66.1 51.4 36.8 -

62 87.6 6.4 87.6 85.4 83.2 68.8 54.3 39.9 83.0 7.2 83.0 82.2 81.4 66.6 51.9 37.2

57 87.6 6.4 87.6 87.6 87.6 84.0 69.8 55.6 83.0 7.2 83.0 83.0 83.0 81.8 67.0 52.2

Page 41: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 41

115°F 125°F

1625

77 78.5 8.1 44.7 37.4 30.1 - - - 74.6 8.9 42.9 35.7 28.4 - - -

72 72.1 8.1 54.3 46.1 38.0 29.8 - - 67.8 8.9 52.3 44.2 36.2 28.1 - -

67 66.1 8.1 63.8 54.8 45.8 37.9 29.9 - 61.7 8.9 61.7 52.8 43.9 36.0 28.1 -

62 65.1 8.1 65.1 59.4 53.7 45.9 38.2 30.4 61.6 8.9 61.6 56.6 51.7 43.9 36.1 28.4

1950

77 79.6 8.1 50.8 40.8 30.7 - - - 74.0 8.9 49.1 39.0 28.8 - - -

72 74.1 8.1 58.8 49.4 40.1 30.7 - - 69.0 8.9 56.6 47.4 38.2 28.9 - -

67 68.6 8.1 66.8 58.1 49.5 40.2 30.9 - 64.1 8.9 64.1 55.8 47.5 38.3 29.0 -

62 67.7 8.1 67.7 63.3 58.8 49.6 40.4 31.2 64.0 8.9 64.0 60.5 56.9 47.6 38.3 29.0

57 66.9 8.1 66.9 66.9 66.9 59.1 50.0 40.9 63.9 8.9 63.9 63.9 63.9 56.9 47.6 38.3

2275

77 80.7 8.1 56.9 44.1 31.3 - - - 73.3 8.9 55.3 42.3 29.2 - - -

72 76.1 8.1 63.3 52.7 42.2 31.6 - - 70.3 8.9 60.9 50.6 40.2 29.8 - -

67 71.0 8.1 69.7 61.4 53.1 42.5 31.9 - 66.6 8.9 66.6 58.8 51.1 40.5 29.9 -

62 70.4 8.1 70.4 67.2 64.0 53.4 42.7 32.0 66.5 8.9 66.5 64.3 62.1 51.3 40.5 29.7

57 69.8 8.1 69.8 69.8 69.8 64.2 53.5 42.8 66.4 8.9 66.4 66.4 66.4 62.1 51.1 40.1

2600

77 81.8 8.1 63.1 47.4 31.8 - - - 72.6 8.9 61.5 45.6 29.6 - - -

72 78.1 8.1 67.8 56.1 44.3 32.5 - - 71.5 8.9 65.3 53.7 42.2 30.6 - -

67 73.5 8.1 72.6 64.7 56.7 44.8 32.8 - 69.0 8.9 69.0 61.9 54.7 42.8 30.9 -

62 73.1 8.1 73.1 71.1 69.2 57.1 45.0 32.8 68.9 8.9 68.9 68.1 67.3 55.0 42.7 30.4

57 72.6 8.1 72.6 72.6 72.6 69.4 57.1 44.8 68.9 8.9 68.9 68.9 68.9 67.2 54.5 41.8

2925

72 80.1 8.1 72.4 59.4 46.4 33.4 - - 72.7 8.9 69.6 56.9 44.2 31.4 - -

67 76.0 8.1 75.5 68.0 60.4 47.1 33.8 - 71.4 8.9 71.4 64.9 58.4 45.1 31.8 -

62 75.8 8.1 75.8 75.1 74.4 60.8 47.2 33.6 71.4 8.9 71.4 71.4 71.4 58.7 44.9 31.0

57 75.5 8.1 75.5 75.5 75.5 74.5 60.6 46.8 71.3 8.9 71.3 71.3 71.3 71.3 58.0 43.6

3250

72 82.1 8.1 76.9 62.7 48.5 34.3 - - 73.9 8.9 73.9 60.0 46.2 32.3 - -

67 78.5 8.1 78.5 71.2 64.0 49.4 34.8 - 73.8 8.9 73.8 67.9 62.0 47.3 32.7 -

62 78.4 8.1 78.4 78.4 78.4 64.5 49.5 34.4 73.8 8.9 73.8 73.8 73.8 62.4 47.1 31.7

57 78.4 8.1 78.4 78.4 78.4 78.4 64.2 48.7 73.8 8.9 73.8 73.8 73.8 73.8 61.4 45.3

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZH078 (6.5 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 42: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

42 Johnson Controls Ducted Systems

ZH090 (7.5 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1875

77 110.9 5.6 59.4 50.1 40.9 - - - 105.8 6.2 56.3 47.7 39.1 - - -

72 102.1 5.5 70.4 60.6 50.9 41.2 - - 97.2 6.2 68.1 58.5 48.9 39.3 - -

67 93.4 5.5 81.4 71.2 61.0 51.0 41.6 - 88.5 6.1 79.8 69.2 58.7 49.0 39.5 -

62 88.2 5.4 88.2 79.6 71.0 59.3 51.6 41.9 84.8 6.1 84.8 76.6 68.4 57.9 49.4 39.8

2250

77 112.0 5.6 65.4 53.8 42.2 - - - 106.5 6.2 62.8 51.5 40.2 - - -

72 104.1 5.5 76.0 64.8 53.642 42.5 - - 98.9 6.2 73.6 62.6 51.5 40.4 - -

67 96.2 5.5 86.6 75.8 65.0 53.8 42.8 - 91.4 6.1 84.4 73.6 62.7 51.6 40.7 -

62 92.1 5.4 92.1 84.3 76.5 63.8 54.4 43.3 88.4 6.1 88.4 81.2 73.9 62.2 52.0 41.1

57 87.9 5.4 87.9 87.9 87.9 76.9 65.9 54.9 85.4 6.1 85.4 85.4 85.2 74.3 63.4 52.5

2625

77 113.1 5.6 71.4 57.5 43.6 - - - 107.2 6.2 69.3 55.4 41.4 - - -

72 106.1 5.5 81.6 69.0 56.4 43.7 - - 100.7 6.2 79.2 66.6 54.1 41.6 - -

67 99.0 5.5 91.8 80.5 69.1 56.5 44.1 - 94.2 6.1 89.0 77.9 66.8 54.2 41.9 -

62 95.9 5.5 95.9 88.9 81.9 68.3 57.1 44.7 92.0 6.1 92.0 85.7 79.4 66.5 54.7 42.3

57 92.8 5.4 92.8 92.8 92.8 82.4 70.1 57.8 89.7 6.1 89.7 89.7 89.7 79.8 67.5 55.3

3000

77 114.2 5.6 77.5 61.2 44.9 - - - 107.9 6.2 75.8 59.2 42.6 - - -

72 108.0 5.5 87.2 73.2 59.1 45.0 - - 102.5 6.2 84.7 70.7 56.7 42.7 - -

67 101.8 5.5 97.0 85.1 73.2 59.2 45.4 - 97.1 6.2 93.6 82.2 70.8 56.9 43.0 -

62 99.7 5.5 99.7 93.5 87.4 72.8 59.8 46.0 95.6 6.1 95.6 90.3 85.0 70.8 57.4 43.6

57 97.7 5.5 97.7 97.7 97.7 87.9 74.2 60.6 94.1 6.1 94.1 94.1 94.1 85.4 71.7 58.0

3375

72 110.0 5.6 92.9 77.3 61.8 46.3 - - 104.2 6.2 90.3 74.8 59.3 43.9 - -

67 104.7 5.5 102.2 89.8 77.3 61.9 46.6 - 99.9 6.2 98.2 86.5 74.9 59.5 44.2 -

62 103.6 5.5 103.6 98.2 92.8 77.3 62.5 47.4 99.1 6.2 99.1 94.8 90.5 75.0 60.0 44.8

57 102.5 5.5 102.5 102.5 102.5 93.4 78.4 63.5 98.4 6.2 98.4 98.4 98.4 90.9 75.9 60.8

3750

72 111.9 5.6 98.5 81.5 64.521 47.5 - - 106.0 6.2 95.8 78.9 61.9 45.0 - -

67 107.5 5.5 107.5 94.4 81.4 64.6 47.9 - 102.8 6.2 102.8 90.8 78.9 62.2 45.4 -

62 107.4 5.5 107.4 102.8 98.3 81.8 65.3 48.8 102.7 6.2 102.7 99.3 96.0 79.3 62.7 46.1

57 107.4 5.5 107.4 107.4 107.4 98.9 82.6 66.4 102.7 6.2 102.7 102.7 102.7 96.5 80.0 63.5

95°F 105°F

1875

77 100.7 6.9 53.3 45.3 37.3 - - - 94.0 7.8 51.5 43.3 35.0 - - -

72 92.2 6.8 65.8 56.3 46.8 37.3 - - 86.2 7.7 63.3 53.9 44.4 35.0 - -

67 83.7 6.7 78.3 67.3 56.3 46.9 37.5 - 78.6 7.6 75.0 64.4 53.9 44.5 35.2 -

62 81.4 6.7 81.4 73.6 65.9 56.5 47.1 37.8 77.1 7.6 77.1 70.2 63.3 54.0 44.7 35.5

2250

77 101.0 6.9 60.3 49.3 38.3 - - - 94.1 7.8 58.4 47.1 35.8 - - -

72 93.8 6.8 71.3 60.3 49.314 38.3 - - 87.7 7.7 68.4 57.6 46.8 36.0 - -

67 86.6 6.7 82.2 71.3 60.4 49.5 38.5 - 81.4 7.7 78.5 68.1 57.8 47.0 36.2 -

62 84.7 6.7 84.7 78.1 71.4 60.6 49.7 38.9 80.1 7.7 80.1 74.5 68.8 58.0 47.3 36.5

57 82.9 6.7 82.9 82.9 82.5 71.7 60.9 50.1 78.9 7.6 78.9 78.9 78.9 69.0 58.3 47.5

2625

77 101.3 6.9 67.3 53.2 39.2 - - - 94.1 7.8 65.3 50.9 36.6 - - -

72 95.4 6.8 76.7 64.3 51.8 39.4 - - 89.2 7.7 73.6 61.4 49.2 37.0 - -

67 89.4 6.8 86.2 75.3 64.4 52.0 39.6 - 84.1 7.7 81.9 71.9 61.8 49.5 37.3 -

62 88.1 6.8 88.1 82.5 77.0 64.7 52.3 40.0 83.2 7.7 83.2 78.8 74.3 62.1 49.8 37.5

57 86.7 6.7 86.7 86.7 86.7 77.3 65.0 52.8 82.3 7.7 82.3 82.3 82.3 74.6 62.3 50.0

3000

77 101.6 6.9 74.2 57.2 40.2 - - - 94.2 7.8 72.1 54.8 37.4 - - -

72 96.9 6.8 82.2 68.3 54.3 40.4 - - 90.8 7.7 78.8 65.2 51.6 37.9 - -

67 92.3 6.8 90.1 79.3 68.4 54.6 40.7 - 86.9 7.7 85.4 75.6 65.7 52.0 38.3 -

62 91.4 6.8 91.4 87.0 82.5 68.7 54.9 41.1 86.3 7.7 86.3 83.0 79.8 66.1 52.3 38.5

57 90.5 6.8 90.5 90.5 90.5 82.9 69.2 55.4 85.6 7.7 85.6 85.6 85.6 80.1 66.3 52.4

3375

72 98.5 6.8 87.7 72.2 56.8 41.4 - - 92.3 7.8 83.9 68.9 53.9 38.9 - -

67 95.2 6.8 94.1 83.3 72.5 57.1 41.8 - 89.6 7.7 88.9 79.3 69.6 54.5 39.4 -

62 94.7 6.8 94.7 91.4 88.1 72.8 57.5 42.2 89.3 7.7 89.3 87.3 85.4 70.1 54.8 39.5

57 94.3 6.8 94.3 94.3 94.3 88.5 73.3 58.0 89.0 7.7 89.0 89.0 89.0 85.7 70.3 54.9

3750

72 100.1 6.9 93.1 76.2 59.348 42.5 - - 93.8 7.8 89.1 72.7 56.3 39.9 - -

67 98.0 6.8 98.0 87.3 76.5 59.7 42.9 - 92.4 7.8 92.4 83.0 73.6 57.0 40.4 -

62 98.0 6.8 98.0 95.8 93.7 76.9 60.1 43.4 92.4 7.8 92.4 91.6 90.9 74.1 57.3 40.5

57 98.0 6.8 98.0 98.0 98.0 94.1 77.4 60.7 92.4 7.8 92.4 92.4 92.4 91.2 74.3 57.3

Page 43: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 43

115°F 125°F

1875

77 87.4 8.7 49.7 41.3 32.8 - - - 80.8 9.5 48.0 39.2 30.5 - - -

72 80.2 8.6 60.7 51.4 42.1 32.7 - - 74.3 9.5 58.2 49.0 39.7 30.5 - -

67 73.5 8.6 71.7 61.6 51.4 42.1 32.9 - 68.4 9.5 68.4 58.7 48.9 39.7 30.6 -

62 72.7 8.6 72.7 66.7 60.7 51.5 42.3 33.2 68.4 9.5 68.4 63.2 58.1 49.0 39.9 30.9

2250

77 87.2 8.7 56.5 44.9 33.4 - - - 80.3 9.6 54.6 42.8 30.9 - - -

72 81.7 8.6 65.6 55.0 44.3 33.7 - - 75.6 9.5 62.8 52.3 41.8 31.3 - -

67 76.2 8.6 74.7 65.0 55.2 44.6 33.9 - 70.9 9.5 70.9 61.8 52.7 42.1 31.6 -

62 75.5 8.6 75.5 70.8 66.2 55.5 44.8 34.1 70.9 9.5 70.9 67.2 63.6 52.9 42.3 31.7

57 74.9 8.6 74.9 74.9 74.9 66.4 55.7 44.9 70.9 9.5 70.9 70.9 70.9 63.7 53.0 42.3

2625

77 87.0 8.7 63.3 48.6 34.0 - - - 79.9 9.6 61.3 46.3 31.3 - - -

72 83.1 8.6 70.5 58.5 46.5 34.6 - - 77.0 9.5 67.4 55.6 43.9 32.2 - -

67 78.8 8.6 77.7 68.4 59.1 47.0 34.9 - 73.5 9.5 73.5 65.0 56.5 44.5 32.5 -

62 78.3 8.6 78.3 75.0 71.7 59.4 47.2 35.0 73.4 9.5 73.4 71.2 69.0 56.8 44.7 32.5

57 77.8 8.6 77.8 77.8 77.8 71.9 59.5 47.2 73.4 9.5 73.4 73.4 73.4 69.2 56.8 44.4

3000

77 86.8 8.7 70.0 52.3 34.6 - - - 79.4 9.6 67.9 49.8 31.8 - - -

72 84.6 8.6 75.4 62.1 48.8 35.5 - - 78.4 9.6 71.9 59.0 46.0 33.0 - -

67 81.4 8.6 80.7 71.8 63.0 49.4 35.9 - 76.0 9.5 76.0 68.1 60.2 46.9 33.5 -

62 81.1 8.6 81.1 79.1 77.1 63.4 49.7 35.9 76.0 9.5 76.0 75.2 74.4 60.7 47.0 33.3

57 80.8 8.6 80.8 80.8 80.8 77.4 63.4 49.4 76.0 9.5 76.0 76.0 76.0 74.6 60.5 46.4

3375

72 86.0 8.7 80.2 65.6 51.0 36.4 - - 79.7 9.6 76.5 62.3 48.1 33.9 - -

67 84.1 8.6 83.7 75.3 66.8 51.9 36.9 - 78.5 9.6 78.5 71.2 64.0 49.2 34.5 -

62 83.9 8.6 83.9 83.3 82.6 67.4 52.1 36.8 78.5 9.6 78.5 78.5 78.5 64.6 49.4 34.1

57 83.8 8.6 83.8 83.8 83.8 82.8 67.3 51.7 78.5 9.6 78.5 78.5 78.5 78.5 64.2 48.5

3750

72 87.5 8.7 85.1 69.2 53.2 37.3 - - 81.1 9.6 81.1 65.6 50.2 34.7 - -

67 86.7 8.7 86.7 78.7 70.7 54.3 37.9 - 81.0 9.6 81.0 74.4 67.8 51.6 35.5 -

62 86.7 8.7 86.7 86.7 86.7 71.3 54.5 37.7 81.1 9.6 81.1 81.1 81.1 68.5 51.7 34.9

57 86.7 8.7 86.7 86.7 86.7 86.7 71.1 53.9 81.1 9.6 81.1 81.1 81.1 81.1 68.0 50.5

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZH090 (7.5 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 44: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

44 Johnson Controls Ducted Systems

ZH102 (8.5 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

2125

77 128.6 6.1 68.9 58.4 47.9 - - - 122.6 6.9 65.1 55.3 45.5 - - -

72 118.1 6.1 81.3 70.2 59.0 47.9 - - 112.6 6.9 78.5 67.5 56.6 45.6 - -

67 107.6 6.1 93.7 81.9 70.2 58.9 48.0 - 102.5 6.9 91.8 79.7 67.7 56.6 45.7 -

62 101.8 6.1 54.6 54.6 54.6 38.0 54.6 48.3 97.9 6.9 93.9 86.3 78.8 65.8 56.8 45.8

2550

77 129.9 6.1 75.9 62.7 49.5 - - - 123.7 6.9 72.5 59.7 46.8 - - -

72 120.4 6.1 87.9 75.1 62.2 49.4 - - 114.8 6.9 84.9 72.3 59.6 47.0 - -

67 111.0 6.1 99.9 87.4 74.9 62.1 49.5 - 105.9 6.9 97.3 84.9 72.4 59.7 47.1 -

62 106.4 6.1 99.9 93.7 87.6 41.0 62.4 49.9 102.2 6.9 99.0 92.1 85.2 70.9 59.9 47.2

57 101.8 6.1 99.9 99.9 99.9 87.9 75.4 62.9 98.5 6.9 98.5 98.5 98.0 85.4 72.7 60.0

2975

77 131.2 6.1 83.0 67.1 51.2 - - - 124.8 6.9 79.9 64.0 48.2 - - -

72 122.8 6.1 94.5 80.0 65.4 50.9 - - 117.0 6.9 91.3 77.0 62.7 48.3 - -

67 114.4 6.1 106.0 92.8 79.7 65.2 50.9 - 109.3 6.9 102.8 90.0 77.2 62.8 48.5 -

62 110.9 6.1 106.0 100.0 93.9 77.3 65.6 51.4 106.5 6.9 104.1 97.9 91.7 76.1 63.0 48.6

57 107.4 6.1 106.0 106.0 106.0 94.2 80.2 66.2 103.7 6.9 103.7 103.7 103.7 91.8 77.5 63.1

3400

77 132.5 6.1 90.0 71.4 52.8 - - - 125.9 6.9 87.2 68.4 49.5 - - -

72 125.1 6.1 101.1 84.9 68.6 52.4 - - 119.3 6.9 97.8 81.8 65.7 49.7 - -

67 117.8 6.1 112.2 98.3 84.4 68.3 52.4 - 112.6 6.9 108.3 95.1 81.9 65.9 49.9 -

62 115.4 6.1 112.2 106.2 100.2 82.8 68.7 52.9 110.8 6.9 109.1 103.6 98.1 81.3 66.1 50.0

57 113.1 6.1 112.1 112.1 112.1 100.5 85.0 69.5 108.9 6.9 108.9 108.9 108.9 98.3 82.3 66.2

3825

72 127.5 6.1 107.7 89.7 71.8 53.9 - - 121.5 6.9 104.2 86.5 68.8 51.1 - -

67 121.1 6.1 118.4 103.8 89.1 71.5 53.9 - 116.0 6.9 113.9 100.3 86.7 69.0 51.2 -

62 120.0 6.1 118.3 112.4 106.4 88.3 71.8 54.5 115.0 6.9 114.2 109.4 104.6 86.5 69.1 51.4

57 118.8 6.1 118.3 118.3 118.3 106.8 89.7 72.7 114.1 6.9 114.1 114.1 114.1 104.8 87.0 69.3

4250

72 129.9 6.1 114.3 94.6 75.0 55.4 - - 123.7 6.9 110.7 91.2 71.8 52.4 - -

67 124.5 6.1 124.5 109.2 93.9 74.6 55.3 - 119.4 6.9 119.4 105.4 91.4 72.0 52.6 -

62 124.5 6.1 69.7 69.7 69.7 69.7 69.7 56.0 119.3 6.9 119.3 115.2 111.1 91.6 72.2 52.8

57 124.4 6.1 69.9 69.9 69.9 69.9 69.9 69.9 119.2 6.9 68.4 68.4 68.4 68.4 68.4 68.4

95°F 105°F

2125

77 116.7 7.7 61.3 52.2 43.1 - - - 110.3 8.7 59.1 50.0 41.0 - - -

72 107.1 7.7 75.6 64.9 54.1 43.3 - - 101.2 8.7 73.1 62.4 51.8 41.2 - -

67 97.4 7.6 89.9 77.5 65.1 54.3 43.4 - 92.1 8.7 87.0 74.9 62.7 51.9 41.2 -

62 94.0 7.6 94.0 85.1 76.2 65.2 54.3 43.4 89.8 8.7 89.8 81.7 73.6 62.7 51.8 40.9

2550

77 117.6 7.7 69.0 56.6 44.1 - - - 111.0 8.7 67.1 54.5 42.0 - - -

72 109.2 7.7 81.9 69.5 57.0 44.6 - - 103.2 8.7 79.2 66.9 54.7 42.4 - -

67 100.8 7.6 94.7 82.3 69.9 57.3 44.7 - 95.4 8.7 91.4 79.4 67.3 54.9 42.5 -

62 98.1 7.6 98.1 90.4 82.8 70.1 57.3 44.6 93.6 8.7 93.6 86.8 80.0 67.4 54.8 42.2

57 95.3 7.6 95.3 95.3 95.3 82.8 70.0 57.1 91.7 8.7 91.7 91.7 91.7 79.9 67.1 54.4

2975

77 118.5 7.7 76.8 61.0 45.2 - - - 111.7 8.7 75.0 59.0 43.1 - - -

72 111.3 7.7 88.2 74.1 59.9 45.8 - - 105.2 8.7 85.4 71.4 57.5 43.6 - -

67 104.1 7.7 99.6 87.2 74.7 60.4 46.0 - 98.7 8.7 95.7 83.9 72.0 57.9 43.7 -

62 102.1 7.7 102.1 95.8 89.5 74.9 60.4 45.8 97.4 8.7 97.4 91.9 86.4 72.1 57.8 43.4

57 100.0 7.7 100.0 100.0 100.0 89.5 74.7 60.0 96.0 8.7 96.0 96.0 96.0 86.4 71.8 57.3

3400

77 119.3 7.7 84.5 65.3 46.2 - - - 112.3 8.7 83.0 63.5 44.1 - - -

72 113.4 7.7 94.5 78.7 62.8 47.0 - - 107.2 8.7 91.5 75.9 60.4 44.8 - -

67 107.5 7.7 104.5 92.0 79.5 63.4 47.3 - 102.1 8.7 100.1 88.3 76.6 60.8 45.0 -

62 106.1 7.7 106.1 101.1 96.1 79.8 63.4 47.1 101.1 8.7 101.1 97.0 92.9 76.8 60.8 44.7

57 104.7 7.7 104.7 104.7 104.7 96.1 79.5 62.9 100.2 8.7 100.2 100.2 100.2 92.8 76.5 60.2

3825

72 115.5 7.7 100.8 83.3 65.8 48.3 - - 109.2 8.7 97.7 80.4 63.2 46.0 - -

67 110.8 7.7 109.3 96.8 84.2 66.4 48.6 - 105.4 8.7 104.4 92.8 81.3 63.8 46.3 -

62 110.1 7.7 110.1 106.4 102.7 84.6 66.5 48.3 104.9 8.7 104.9 102.1 99.3 81.5 63.7 45.9

57 109.4 7.7 109.4 109.4 109.4 102.8 84.3 65.9 104.4 8.7 104.4 104.4 104.4 99.3 81.2 63.1

4250

72 117.6 7.7 107.0 87.8 68.662 49.5 - - 111.2 8.7 103.8 84.9 66.1 47.2 - -

67 114.2 7.7 114.2 101.6 89.0 69.5 49.9 - 108.8 8.7 108.8 97.3 85.9 66.7 47.5 -

62 114.1 7.7 114.1 111.8 109.4 89.5 69.5 49.6 108.7 8.7 108.7 107.2 105.8 86.2 66.7 47.2

57 114.0 7.7 114.0 114.0 114.0 109.4 89.1 68.8 108.7 8.7 108.7 108.7 108.7 105.7 85.9 66.0

Page 45: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 45

115°F 125°F

2125

77 104.0 9.8 56.9 47.9 38.9 - - - 97.6 10.9 54.7 45.7 36.8 - - -

72 95.3 9.8 70.5 60.0 49.5 39.0 - - 89.4 10.9 68.0 57.6 47.3 36.9 - -

67 86.7 9.8 84.2 72.2 60.2 49.6 38.9 - 81.3 10.9 44.0 44.0 44.0 44.0 36.7 -

62 85.5 9.8 85.5 78.2 70.9 60.1 49.3 38.5 81.2 10.9 81.2 74.7 68.3 57.6 46.8 36.1

2550

77 104.4 9.8 65.1 52.5 39.9 - - - 97.8 10.9 63.2 50.5 37.8 - - -

72 97.2 9.8 76.6 64.4 52.3 40.2 - - 91.2 10.9 73.9 61.9 50.0 38.0 - -

67 90.0 9.8 88.0 76.4 64.7 52.5 40.2 - 84.6 10.9 46.2 46.2 46.2 46.2 37.9 -

62 89.1 9.8 89.1 83.1 77.2 64.7 52.2 39.8 84.6 10.9 84.6 79.4 74.3 62.0 49.7 37.4

57 88.1 9.8 88.1 88.1 88.1 76.9 64.3 51.7 84.5 10.9 46.4 46.4 46.4 46.4 46.4 46.4

2975

77 104.9 9.8 73.3 57.1 41.0 - - - 98.1 10.8 71.6 55.2 38.9 - - -

72 99.1 9.8 82.6 68.8 55.1 41.4 - - 93.0 10.8 79.8 66.2 52.7 39.2 - -

67 93.4 9.8 91.8 80.6 69.3 55.3 41.4 - 88.0 10.8 48.2 48.2 48.2 48.2 39.1 -

62 92.6 9.8 92.6 88.0 83.4 69.3 55.2 41.0 87.9 10.8 87.9 84.1 80.4 66.4 52.5 38.6

57 91.9 9.8 91.9 91.9 91.9 83.2 68.9 54.6 87.9 10.8 48.4 48.4 48.4 48.4 48.4 48.4

3400

77 105.3 9.8 81.5 61.8 42.0 - - - 98.3 10.8 80.0 60.0 40.0 - - -

72 101.0 9.8 88.6 73.2 57.9 42.6 - - 94.8 10.8 85.6 70.5 55.4 40.4 - -

67 96.7 9.8 95.7 84.7 73.8 58.2 42.7 - 91.3 10.8 50.2 50.2 50.2 50.2 40.3 -

62 96.2 9.8 96.2 92.9 89.6 73.9 58.1 42.3 91.3 10.8 91.3 88.8 86.4 70.9 55.4 39.9

57 95.7 9.8 95.7 95.7 95.7 89.5 73.5 57.5 91.2 10.8 50.4 50.4 50.4 50.4 50.4 50.4

3825

72 102.9 9.8 94.6 77.6 60.7 43.8 - - 96.6 10.8 91.5 74.8 58.2 41.5 - -

67 100.0 9.8 99.5 88.9 78.3 61.1 43.9 - 94.6 10.8 52.3 52.3 52.3 52.3 41.5 -

62 99.8 9.8 99.8 97.8 95.9 78.4 61.0 43.5 94.6 10.8 94.6 93.5 92.5 75.3 58.2 41.1

57 99.5 9.8 99.5 99.5 99.5 95.8 78.1 60.4 94.6 10.8 52.5 52.5 52.5 52.5 52.5 52.5

4250

72 104.8 9.8 100.6 82.0 63.5 44.9 - - 98.4 10.8 97.4 79.1 60.9 42.7 - -

67 103.4 9.8 103.4 93.1 82.8 64.0 45.1 - 98.0 10.8 98.0 88.8 79.7 61.2 42.7 -

62 103.3 9.8 103.3 102.7 102.1 83.0 63.9 44.8 98.0 10.8 98.0 98.0 98.0 79.8 61.1 42.4

57 103.3 9.8 103.3 103.3 103.3 102.0 82.6 63.2 98.0 10.8 98.0 98.0 98.0 98.0 79.4 60.5

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZH102 (8.5 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 46: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

46 Johnson Controls Ducted Systems

ZH120 (10 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

2500

77 148.4 7.2 37.9 39.0 40.1 - - - 145.3 7.9 35.2 36.6 38.0 - - -

72 138.6 7.0 56.2 57.2 58.3 59.4 - - 134.2 7.7 53.1 54.5 55.9 57.3 - -

67 128.8 6.7 74.4 75.5 76.5 77.6 78.7 - 123.2 7.6 70.9 72.3 73.7 75.1 76.5 -

62 119.6 6.7 103.4 95.5 94.1 95.2 96.2 97.3 115.1 7.6 100.5 93.0 90.7 92.1 93.5 94.9

3000

77 155.1 7.2 54.6 49.4 44.1 - - - 150.7 7.9 51.9 46.8 41.8 - - -

72 144.8 7.0 74.7 69.4 64.2 59.0 - - 139.3 7.8 71.5 66.5 61.4 56.4 - -

67 134.6 6.7 94.8 89.5 84.3 79.0 73.8 - 127.8 7.6 91.1 86.1 81.0 76.0 71.0 -

62 124.9 6.7 114.1 108.9 103.6 98.4 93.2 87.9 119.5 7.6 109.7 104.7 99.7 94.6 89.6 84.5

57 122.1 6.7 116.9 111.7 106.4 101.2 95.9 90.7 116.7 7.6 111.4 106.3 101.3 96.3 91.2 86.2

3500

77 161.8 7.2 71.2 59.7 48.2 - - - 156.2 7.9 68.5 57.1 45.6 - - -

72 151.1 6.9 93.2 81.6 70.1 58.6 - - 144.3 7.8 89.9 78.5 67.0 55.5 - -

67 140.3 6.7 115.1 103.6 92.0 80.5 68.9 - 132.5 7.6 111.3 99.8 88.4 76.9 65.4 -

62 130.3 6.7 124.9 122.3 113.2 101.6 90.1 78.6 123.8 7.6 118.9 116.4 108.7 97.2 85.7 74.2

57 127.3 6.7 124.7 122.1 116.2 104.7 93.1 81.6 121.0 7.6 118.3 115.8 110.4 99.0 87.5 76.0

4000

77 168.5 7.2 87.9 70.1 52.2 - - - 161.7 7.9 85.2 67.3 49.4 - - -

72 157.3 6.9 111.7 93.8 76.0 58.2 - - 149.4 7.8 108.4 90.4 72.5 54.6 - -

67 146.1 6.7 135.4 117.6 99.8 81.9 64.1 - 137.1 7.7 131.5 113.6 95.7 77.8 59.9 -

62 135.7 6.6 135.7 135.7 122.7 104.9 87.0 69.2 128.2 7.6 128.2 128.2 117.7 99.8 81.8 63.9

57 132.6 6.6 132.6 132.6 126.0 108.1 90.3 72.5 125.2 7.6 125.2 125.2 119.6 101.7 83.8 65.8

4500

72 157.8 7.0 102.0 89.8 77.6 65.4 - - 150.2 7.8 98.7 86.5 74.4 62.3 - -

67 146.6 6.8 126.3 114.1 101.9 89.7 77.5 - 137.9 7.7 122.4 110.3 98.2 86.0 73.9 -

62 136.1 6.8 136.1 136.1 125.3 113.1 100.9 88.7 128.9 7.6 128.9 128.9 120.7 108.6 96.5 84.3

57 133.0 6.8 133.0 133.0 128.9 116.7 104.5 92.3 125.9 7.6 125.9 125.9 122.7 110.6 98.4 86.3

5000

72 158.3 7.2 92.4 85.8 79.3 72.7 - - 151.1 7.9 89.0 82.6 76.3 69.9 - -

67 147.1 6.9 117.2 110.6 104.1 97.5 91.0 - 138.6 7.8 113.3 107.0 100.6 94.3 87.9 -

62 136.6 6.9 136.6 136.6 128.0 121.4 114.9 108.3 129.6 7.7 129.6 129.6 123.8 117.4 111.1 104.7

57 133.4 6.9 133.4 133.4 131.8 125.2 118.6 112.1 126.6 7.7 126.6 126.6 125.8 119.4 113.1 106.7

95°F 105°F

2500

77 142.1 8.5 32.5 34.3 36.0 - - - 130.2 9.7 26.3 30.7 32.7 - - -

72 129.8 8.5 50.0 51.7 53.4 55.2 - - 120.3 9.7 46.3 48.4 50.4 52.5 - -

67 117.5 8.5 67.4 69.2 70.9 72.6 74.4 - 110.4 9.7 66.3 66.1 68.2 70.2 72.3 -

62 110.7 8.4 97.7 90.5 87.2 88.9 90.7 92.4 104.5 9.6 92.5 85.6 82.2 84.3 86.3 88.4

3000

77 146.4 8.5 49.2 44.3 39.5 - - - 133.8 9.8 45.2 40.5 35.9 - - -

72 133.7 8.5 68.3 63.5 58.7 53.8 - - 123.6 9.7 64.6 59.9 55.3 50.6 - -

67 121.1 8.6 87.5 82.7 77.8 73.0 68.1 - 113.4 9.7 84.0 79.3 74.7 70.0 65.4 -

62 114.0 8.5 105.4 100.5 95.7 90.8 86.0 81.2 107.3 9.6 99.4 94.7 90.1 85.4 80.8 76.1

57 111.4 8.5 105.8 101.0 96.2 91.3 86.5 81.6 104.7 9.6 99.7 95.1 90.4 85.8 81.1 76.5

3500

77 150.6 8.5 65.8 54.4 43.0 - - - 137.3 9.8 64.0 50.3 39.0 - - -

72 137.6 8.6 86.7 75.3 63.9 52.4 - - 126.9 9.8 82.8 71.4 60.1 48.7 - -

67 124.6 8.6 107.6 96.1 84.7 73.3 61.9 - 116.5 9.7 101.6 92.5 81.2 69.8 58.5 -

62 117.3 8.5 113.0 110.6 104.2 92.8 81.3 69.9 110.2 9.7 106.2 103.9 97.9 86.6 75.2 63.9

57 114.6 8.5 111.9 109.4 104.7 93.3 81.9 70.4 107.4 9.6 105.0 102.6 98.3 87.0 75.6 64.3

4000

77 154.9 8.6 82.5 64.5 46.5 - - - 140.9 9.8 82.8 60.2 42.1 - - -

72 141.5 8.6 105.1 87.1 69.1 51.1 - - 130.2 9.8 101.0 83.0 64.9 46.8 - -

67 128.1 8.6 127.6 109.6 91.6 73.6 55.6 - 119.5 9.8 119.2 105.7 87.7 69.6 51.6 -

62 120.7 8.5 120.7 120.7 112.7 94.7 76.7 58.7 113.0 9.7 113.0 113.0 105.8 87.7 69.7 51.6

57 117.9 8.5 117.9 117.9 113.2 95.2 77.2 59.2 110.2 9.6 110.2 110.2 106.2 88.1 70.1 52.0

4500

72 142.7 8.6 95.3 83.2 71.2 59.1 - - 131.2 9.8 91.1 79.1 67.1 55.1 - -

67 129.1 8.6 118.5 106.5 94.4 82.3 70.3 - 120.4 9.8 112.4 102.7 90.7 78.7 66.7 -

62 121.6 8.5 121.6 121.6 116.1 104.0 92.0 79.9 113.9 9.7 113.9 113.9 109.4 97.4 85.4 73.5

57 118.8 8.5 118.8 118.8 116.5 104.5 92.4 80.3 111.0 9.6 111.0 111.0 109.0 97.1 85.1 73.1

5000

72 143.8 8.6 85.5 79.4 73.3 67.1 - - 132.2 9.8 81.2 75.3 69.4 63.4 - -

67 130.2 8.6 109.4 103.3 97.2 91.1 84.9 - 121.3 9.8 105.5 99.6 93.7 87.8 81.9 -

62 122.6 8.5 122.6 122.6 119.5 113.4 107.3 101.1 114.8 9.7 114.8 114.8 113.0 107.1 101.2 95.3

57 119.8 8.5 119.8 119.8 119.8 113.7 107.5 101.4 111.9 9.6 111.9 111.9 111.9 106.0 100.1 94.2

Page 47: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 47

115°F 125°F

2500

77 118.3 11.0 20.1 27.1 29.5 - - - 106.4 12.3 13.8 23.5 26.2 - - -

72 110.8 10.9 42.7 45.0 47.4 49.8 - - 101.3 12.2 39.0 41.7 44.4 47.1 - -

67 103.3 10.9 65.2 63.0 65.4 67.8 70.2 - 96.2 12.0 64.1 59.9 62.6 65.4 68.1 -

62 98.3 10.8 87.3 80.7 77.2 79.6 82.0 84.4 92.1 12.0 82.1 75.7 72.3 75.0 77.7 80.4

3000

77 121.2 11.0 41.1 36.7 32.2 - - - 108.6 12.3 37.1 32.8 28.6 - - -

72 113.5 10.9 60.8 56.3 51.9 47.4 - - 103.4 12.1 57.0 52.7 48.5 44.2 - -

67 105.8 10.9 80.4 76.0 71.5 67.1 62.6 - 98.2 12.0 76.9 72.6 68.4 64.1 59.8 -

62 100.7 10.8 93.4 88.9 84.5 80.0 75.6 71.1 94.0 12.0 87.3 83.1 78.8 74.6 70.3 66.1

57 97.9 10.7 93.6 89.1 84.7 80.2 75.8 71.3 91.2 11.8 87.5 83.2 79.0 74.7 70.4 66.2

3500

77 124.0 11.0 62.1 46.3 35.0 - - - 110.7 12.3 60.4 42.2 31.0 - - -

72 116.2 10.9 78.9 67.6 56.3 45.0 - - 105.5 12.1 75.0 63.7 52.5 41.3 - -

67 108.3 10.9 95.6 88.9 77.6 66.3 55.0 - 100.2 12.0 89.7 85.3 74.1 62.8 51.6 -

62 103.0 10.8 99.4 97.2 91.7 80.4 69.1 57.8 95.9 12.0 92.6 90.4 85.4 74.2 63.0 51.8

57 100.2 10.7 98.1 95.8 91.9 80.6 69.4 58.1 93.0 11.8 91.2 89.1 85.5 74.3 63.1 51.9

4000

77 126.9 11.0 83.1 55.8 37.7 - - - 112.9 12.3 83.6 51.5 33.3 - - -

72 118.9 11.0 97.0 78.8 60.7 42.6 - - 107.5 12.1 92.9 74.7 56.6 38.4 - -

67 110.8 10.9 110.8 101.8 83.7 65.6 47.5 - 102.2 12.0 102.2 98.0 79.8 61.6 43.4 -

62 105.4 10.8 105.4 105.4 98.9 80.8 62.6 44.5 97.8 12.0 97.8 97.8 92.0 73.8 55.6 37.4

57 102.5 10.7 102.5 102.5 99.2 81.0 62.9 44.8 94.9 11.8 94.9 94.9 92.1 73.9 55.8 37.6

4500

72 119.7 10.9 86.9 75.0 63.1 51.2 - - 108.2 12.1 82.7 70.9 59.1 47.2 - -

67 111.6 10.9 106.2 98.9 87.0 75.1 63.2 - 102.8 12.0 100.1 95.1 83.3 71.4 59.6 -

62 106.2 10.8 106.2 106.2 102.7 90.8 78.9 67.0 98.4 12.0 98.4 98.4 96.0 84.2 72.4 60.6

57 103.3 10.7 103.3 103.3 101.6 89.7 77.8 65.9 95.5 11.8 95.5 95.5 94.1 82.3 70.5 58.6

5000

72 120.5 10.9 76.8 71.1 65.5 59.8 - - 108.9 12.1 72.5 67.0 61.5 56.1 - -

67 112.4 10.9 101.6 95.9 90.2 84.6 78.9 - 103.5 12.0 97.7 92.2 86.8 81.3 75.8 -

62 106.9 10.8 106.9 106.9 106.6 100.9 95.2 89.5 99.0 12.0 99.0 99.0 99.0 94.6 89.2 83.7

57 104.0 10.7 104.0 104.0 104.0 98.3 92.6 86.9 96.1 11.8 96.1 96.1 96.1 90.6 85.2 79.7

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZH120 (10 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 48: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

48 Johnson Controls Ducted Systems

ZH150 (12.5 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

3125

77 204.4 9.6 82.4 68.5 54.6 - - - 192.2 10.6 77.2 63.6 50.0 - - -

72 186.6 9.3 106.6 92.6 78.7 64.8 - - 176.1 10.4 100.7 87.2 73.6 60.0 - -

67 168.8 9.1 130.7 116.8 102.9 88.9 75.0 - 159.9 10.2 124.3 110.7 97.1 83.6 70.0 -

62 153.0 9.0 153.0 143.5 127.2 113.3 99.4 85.5 144.9 10.0 144.9 138.4 120.1 106.6 93.0 79.4

3750

77 210.2 9.7 89.0 73.6 58.1 - - - 197.5 10.7 84.3 69.1 53.9 - - -

72 191.8 9.4 114.7 99.3 83.9 68.4 - - 180.9 10.5 109.7 94.4 79.2 64.0 - -

67 173.5 9.1 140.4 125.0 109.6 94.2 78.7 - 164.3 10.2 135.0 119.8 104.6 89.4 74.2 -

62 157.2 9.0 157.2 150.9 135.5 120.1 104.7 89.3 148.9 10.1 148.9 144.5 129.3 114.1 98.9 83.7

57 152.9 8.9 152.9 152.9 144.1 128.7 113.3 97.8 146.9 10.0 146.9 146.9 135.2 120.0 104.8 89.6

4375

77 215.9 9.7 95.5 78.6 61.7 - - - 202.8 10.8 91.4 74.5 57.7 - - -

72 197.1 9.4 122.8 105.9 89.0 72.1 - - 185.7 10.5 118.6 101.7 84.9 68.0 - -

67 178.3 9.2 150.1 133.2 116.3 99.4 82.5 - 168.6 10.3 145.8 128.9 112.0 95.2 78.3 -

62 161.5 9.1 161.5 158.4 143.8 126.9 110.0 93.1 152.8 10.1 152.8 150.7 138.5 121.7 104.8 88.0

57 157.1 9.0 157.1 157.1 152.9 136.0 119.1 102.2 150.8 10.1 150.8 150.8 144.8 128.0 111.1 94.3

5000

77 221.6 9.8 102.1 83.7 65.3 - - - 208.0 10.8 98.5 80.0 61.5 - - -

72 202.3 9.5 130.9 112.6 94.2 75.8 - - 190.5 10.6 127.5 109.0 90.5 72.0 - -

67 183.0 9.2 159.8 141.4 123.0 104.6 86.2 - 173.0 10.4 156.5 138.0 119.5 101.0 82.5 -

62 165.8 9.1 165.8 165.8 152.1 133.7 115.3 96.9 156.8 10.2 156.8 156.8 147.8 129.3 110.8 92.3

57 161.2 9.0 161.2 161.2 161.8 143.4 125.0 106.6 154.8 10.1 154.8 154.8 154.5 136.0 117.5 99.0

5625

72 206.6 9.5 140.7 121.0 101.3 81.6 - - 193.5 10.6 136.3 116.5 96.7 76.9 - -

67 186.9 9.2 174.9 152.0 132.3 112.6 92.9 - 175.7 10.4 167.3 147.5 127.7 107.9 88.1 -

62 169.3 9.2 169.3 169.3 162.5 142.8 123.1 103.4 159.3 10.2 159.3 159.3 154.7 135.0 115.2 95.4

57 164.7 9.0 164.7 164.7 165.0 145.3 125.6 105.8 157.2 10.1 157.2 157.2 157.0 137.2 117.5 97.7

6250

72 210.9 9.5 150.5 129.4 108.4 87.4 - - 196.5 10.6 145.1 124.0 102.9 81.8 - -

67 190.8 9.3 190.0 162.7 141.6 120.6 99.6 - 178.4 10.4 178.0 157.0 135.9 114.8 93.7 -

62 172.9 9.2 172.9 172.9 172.9 151.8 130.8 109.8 161.7 10.2 161.7 161.7 161.7 140.6 119.6 98.5

57 168.1 9.0 168.1 168.1 168.1 147.1 126.1 105.0 159.6 10.2 159.6 159.6 159.6 138.5 117.4 96.4

95°F 105°F

3125

77 180.0 11.6 71.9 58.7 45.5 - - - 169.2 13.1 68.8 56.1 43.0 - - -

72 165.5 11.4 94.9 81.7 68.5 55.2 - - 155.1 13.0 91.6 78.5 65.5 52.4 - -

67 151.0 11.3 117.8 104.6 91.4 78.2 65.0 - 140.9 12.8 114.3 100.9 87.9 74.9 61.8 -

62 136.9 11.0 136.9 133.3 113.0 99.8 86.6 73.4 128.7 12.5 128.7 126.9 108.9 95.8 82.8 69.8

3750

77 184.8 11.7 79.6 64.6 49.6 - - - 173.5 13.2 76.3 61.6 46.8 - - -

72 169.9 11.5 104.6 89.6 74.6 59.6 - - 159.0 13.0 100.7 86.0 71.2 56.5 - -

67 155.0 11.4 129.6 114.6 99.6 84.6 69.6 - 144.5 12.8 125.1 110.4 95.6 80.9 66.1 -

62 140.5 11.1 140.5 138.1 123.1 108.1 93.1 78.1 131.9 12.6 131.9 130.7 118.4 103.7 88.9 74.1

57 141.0 11.0 141.0 141.0 126.3 111.3 96.3 81.3 131.4 12.6 131.4 131.4 118.3 103.5 88.8 74.0

4375

77 189.6 11.8 87.3 70.5 53.7 - - - 177.8 13.2 83.9 67.1 50.6 - - -

72 174.3 11.6 114.3 97.5 80.7 63.9 - - 162.9 13.1 109.9 93.4 77.0 60.5 - -

67 159.0 11.5 141.4 124.6 107.8 91.0 74.2 - 148.1 12.9 135.9 119.8 103.3 86.9 70.4 -

62 144.2 11.2 144.2 143.0 133.3 116.5 99.7 82.9 135.2 12.6 135.2 134.6 128.0 111.5 95.0 78.5

57 144.6 11.1 144.6 144.6 136.7 119.9 103.1 86.3 134.6 12.6 134.6 134.6 127.8 111.4 94.9 78.4

5000

77 194.4 11.9 94.9 76.3 57.7 - - - 182.0 13.3 91.5 72.6 54.4 - - -

72 178.7 11.7 124.1 105.5 86.9 68.3 - - 166.8 13.1 119.1 100.9 82.7 64.5 - -

67 163.0 11.6 153.2 134.6 116.0 97.4 78.8 - 151.6 12.9 146.7 129.2 111.0 92.9 74.7 -

62 147.8 11.3 147.8 147.8 143.4 124.8 106.2 87.6 138.4 12.7 138.4 138.4 137.5 119.3 101.1 82.9

57 148.3 11.2 148.3 148.3 147.1 128.5 109.9 91.3 137.8 12.7 137.8 137.8 137.4 119.2 101.0 82.8

5625

72 180.4 11.7 131.9 112.0 92.2 72.3 - - 168.0 13.2 127.6 107.9 88.2 68.6 - -

67 164.5 11.6 159.6 142.9 123.1 103.2 83.3 - 152.7 13.0 150.2 137.8 118.5 98.8 79.1 -

62 149.2 11.3 149.2 149.2 147.0 127.1 107.3 87.4 139.4 12.7 139.4 139.4 138.9 119.3 99.6 80.0

57 149.7 11.2 149.7 149.7 149.1 129.2 109.4 89.5 138.8 12.7 138.8 138.8 138.6 118.9 99.3 79.6

6250

72 182.1 11.8 139.7 118.6 97.4 76.3 - - 169.2 13.2 136.0 114.9 93.8 72.6 - -

67 166.1 11.6 166.1 151.3 130.1 109.0 87.9 - 153.7 13.0 153.7 146.3 125.9 104.8 83.6 -

62 150.6 11.3 150.6 150.6 150.6 129.5 108.3 87.2 140.4 12.7 140.4 140.4 140.4 119.2 98.1 77.0

57 151.1 11.3 151.1 151.1 151.1 130.0 108.8 87.7 139.8 12.7 139.8 139.8 139.8 118.6 97.5 76.4

Page 49: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 49

115°F 125°F

3125

77 158.4 14.6 65.6 53.5 40.6 - - - 147.6 16.1 60.0 50.8 38.1 - - -

72 144.6 14.5 88.2 75.4 62.5 49.6 - - 134.2 16.0 84.9 72.2 59.5 46.8 - -

67 130.9 14.3 110.9 97.3 84.4 71.5 58.7 - 120.9 15.8 107.4 93.6 80.9 68.2 55.5 -

62 120.5 14.0 120.5 120.5 104.7 91.9 79.0 66.1 112.3 15.6 112.3 112.3 100.7 87.9 75.2 62.5

3750

77 162.2 14.7 73.1 58.6 44.1 - - - 150.8 16.1 69.9 55.6 41.3 - - -

72 148.1 14.5 96.9 82.4 67.9 53.3 - - 137.2 16.0 93.0 78.7 64.5 50.2 - -

67 134.0 14.3 120.6 106.1 91.6 77.1 62.6 - 123.5 15.8 116.2 101.9 87.6 73.4 59.1 -

62 123.3 14.1 123.3 123.3 113.7 99.2 84.7 70.2 114.8 15.6 114.8 114.8 109.0 94.7 80.5 66.2

57 121.8 14.1 121.8 121.8 110.3 95.8 81.2 66.7 112.1 15.6 112.1 112.1 102.2 88.0 73.7 59.4

4375

77 165.9 14.7 80.6 63.7 47.6 - - - 154.1 16.1 79.7 60.3 44.5 - - -

72 151.5 14.5 105.5 89.4 73.2 57.1 - - 140.1 15.9 101.1 85.3 69.5 53.6 - -

67 137.1 14.3 130.4 115.0 98.9 82.7 66.6 - 126.2 15.8 125.0 110.2 94.4 78.6 62.7 -

62 126.2 14.1 126.2 126.2 122.7 106.5 90.4 74.2 117.2 15.5 117.2 117.2 117.2 101.6 85.7 69.9

57 124.6 14.1 124.6 124.6 119.0 102.8 86.7 70.5 114.6 15.6 114.6 114.6 110.1 94.3 78.4 62.6

5000

77 169.7 14.7 88.1 68.8 51.0 - - - 157.3 16.1 89.6 65.1 47.7 - - -

72 155.0 14.5 114.2 96.4 78.6 60.8 - - 143.1 15.9 109.2 91.8 74.4 57.0 - -

67 140.2 14.3 140.2 123.9 106.1 88.3 70.5 - 128.9 15.7 128.9 118.6 101.1 83.7 66.3 -

62 129.1 14.1 129.1 129.1 131.7 113.9 96.1 78.3 119.7 15.5 119.7 119.7 119.7 108.4 91.0 73.6

57 127.4 14.2 127.4 127.4 127.7 109.9 92.1 74.3 117.0 15.6 117.0 117.0 117.0 100.6 83.2 65.7

5625

72 155.6 14.6 123.2 103.8 84.3 64.9 - - 143.2 16.0 118.9 99.7 80.4 61.2 - -

67 140.8 14.4 140.8 132.6 113.9 94.4 74.9 - 128.9 15.8 128.9 127.5 109.3 90.0 70.8 -

62 129.6 14.1 129.6 129.6 130.9 111.4 92.0 72.5 119.8 15.6 119.8 119.8 119.8 103.6 84.3 65.1

57 127.9 14.2 127.9 127.9 128.1 108.6 89.1 69.7 117.0 15.6 117.0 117.0 117.0 98.3 79.0 59.8

6250

72 156.2 14.6 132.3 111.2 90.1 69.0 - - 143.3 16.0 128.6 107.5 86.4 65.3 - -

67 141.4 14.4 141.4 141.4 121.6 100.5 79.4 - 129.0 15.8 129.0 129.0 117.4 96.3 75.2 -

62 130.1 14.2 130.1 130.1 130.1 109.0 87.9 66.8 119.9 15.6 119.9 119.9 119.9 98.8 77.7 56.5

57 128.4 14.2 128.4 128.4 128.4 107.3 86.2 65.1 117.1 15.7 117.1 117.1 117.1 96.0 74.9 53.8

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZH150 (12.5 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 50: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

50 Johnson Controls Ducted Systems

ZJ037-150 Cooling Capacities

ZJ037 (3.0 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

750

77 48.1 1.8 23.3 19.3 15.3 - - - 45.0 2.1 21.6 17.8 14.1 - - -

72 43.0 1.8 27.6 23.5 19.3 15.2 - - 40.3 2.1 26.4 22.2 18.1 14.0 - -

67 37.8 1.8 32.0 27.7 23.4 19.0 14.9 - 35.7 2.1 31.1 26.6 22.1 17.8 13.7 -

62 35.9 1.8 35.6 31.5 27.4 22.2 18.8 14.5 34.1 2.1 34.1 30.1 26.1 21.5 17.7 13.4

900

77 48.6 1.9 25.8 20.7 15.6 - - - 45.3 2.1 24.4 19.4 14.4 - - -

72 44.0 1.8 30.3 25.4 20.5 15.6 - - 41.2 2.1 29.0 24.1 19.2 14.3 - -

67 39.4 1.8 34.8 30.1 25.4 20.3 15.4 - 37.2 2.1 33.6 28.8 24.1 19.1 14.2 -

62 37.8 1.8 37.6 33.9 30.3 24.5 20.2 15.1 35.9 2.1 35.9 32.4 28.9 23.6 18.9 14.0

57 36.2 1.8 36.2 36.2 35.2 30.0 24.9 19.8 34.6 2.1 34.6 34.6 33.8 28.7 23.7 18.7

1050

77 49.1 1.9 28.4 22.1 15.9 - - - 45.6 2.1 27.2 20.9 14.7 - - -

72 45.1 1.8 33.0 27.3 21.6 16.0 - - 42.1 2.1 31.7 26.0 20.3 14.7 - -

67 41.1 1.8 37.6 32.5 27.4 21.6 15.9 - 38.6 2.1 36.1 31.1 26.0 20.3 14.6 -

62 39.7 1.8 39.6 36.4 33.2 26.8 21.5 15.7 37.7 2.1 37.7 34.7 31.7 25.7 20.2 14.5

57 38.4 1.8 38.4 38.4 37.9 33.0 27.1 21.2 36.7 2.1 36.7 36.7 36.7 31.6 25.8 20.0

1200

77 49.7 1.9 31.0 23.6 16.2 - - - 45.9 2.1 30.0 22.5 14.9 - - -

72 46.2 1.9 35.7 29.2 22.8 16.3 - - 43.0 2.1 34.3 27.9 21.5 15.1 - -

67 42.7 1.8 40.4 34.9 29.4 22.8 16.4 - 40.1 2.1 38.6 33.3 28.0 21.5 15.1 -

62 41.6 1.8 41.6 38.9 36.1 29.1 22.9 16.3 39.5 2.1 39.5 37.1 34.5 27.8 21.5 15.0

57 40.6 1.8 40.6 40.6 40.6 36.0 29.4 22.7 38.8 2.1 38.8 38.8 38.8 34.5 27.9 21.4

1350

72 47.2 1.9 38.4 31.2 24.0 16.7 - - 43.9 2.1 36.9 29.8 22.6 15.4 - -

67 44.3 1.8 43.2 37.3 31.5 24.1 16.9 - 41.6 2.1 41.0 35.5 30.0 22.7 15.5 -

62 43.5 1.9 43.5 41.3 39.0 31.4 24.2 16.9 41.3 2.1 41.3 39.4 37.3 30.0 22.8 15.5

57 42.8 1.9 42.8 42.8 42.8 39.0 31.6 24.2 41.0 2.1 41.0 41.0 41.0 37.4 30.1 22.7

1500

72 48.3 1.9 41.1 33.1 25.1 17.1 - - 44.8 2.1 39.6 31.7 23.7 15.8 - -

67 45.9 1.9 45.9 39.7 33.5 25.4 17.4 - 43.1 2.1 43.1 37.7 31.9 23.9 16.0 -

62 45.5 1.9 45.5 43.8 41.8 33.7 25.6 17.5 43.1 2.1 43.1 41.7 40.1 32.1 24.1 16.0

57 45.0 1.9 45.0 45.0 45.0 42.0 33.8 25.6 43.1 2.1 43.1 43.1 43.1 40.3 32.2 24.1

95°F 105°F

750

77 41.9 2.4 20.0 16.4 12.9 - - - 38.8 2.8 19.1 15.4 11.7 - - -

72 37.7 2.3 25.1 21.0 16.9 12.7 - - 34.8 2.7 23.8 19.7 15.6 11.5 - -

67 33.6 2.3 30.2 25.5 20.9 16.7 12.6 - 30.8 2.7 28.4 23.9 19.4 15.3 11.2 -

62 32.2 2.3 32.2 28.7 24.9 20.7 16.5 12.4 30.1 2.7 30.1 26.7 23.3 19.1 15.0 10.9

900

77 42.0 2.4 23.0 18.1 13.1 - - - 38.8 2.8 22.1 16.9 11.8 - - -

72 38.4 2.3 27.7 22.8 18.0 13.1 - - 35.4 2.7 26.2 21.4 16.5 11.7 - -

67 34.9 2.3 32.3 27.6 22.8 17.9 13.0 - 32.1 2.7 30.4 25.8 21.3 16.4 11.5 -

62 33.9 2.3 33.9 30.9 27.6 22.7 17.7 12.8 31.6 2.7 31.6 28.9 26.0 21.1 16.2 11.2

57 32.9 2.3 32.9 32.9 32.4 27.4 22.5 17.5 31.1 2.7 31.1 31.1 30.7 25.8 20.8 15.9

1050

77 42.1 2.4 26.1 19.7 13.4 - - - 38.8 2.8 25.1 18.5 11.9 - - -

72 39.1 2.4 30.3 24.7 19.1 13.4 - - 36.1 2.8 28.7 23.1 17.5 11.9 - -

67 36.2 2.3 34.5 29.6 24.7 19.0 13.4 - 33.4 2.7 32.3 27.7 23.1 17.5 11.8 -

62 35.6 2.3 35.6 33.1 30.3 24.6 18.9 13.3 33.1 2.7 33.1 31.1 28.7 23.0 17.3 11.6

57 35.0 2.3 35.0 35.0 35.0 30.2 24.5 18.8 32.8 2.7 32.8 32.8 32.8 28.6 22.8 17.1

1200

77 42.1 2.4 29.1 21.4 13.7 - - - 38.8 2.8 28.1 20.0 11.9 - - -

72 39.8 2.4 32.9 26.5 20.2 13.8 - - 36.8 2.8 31.2 24.8 18.4 12.1 - -

67 37.6 2.3 36.7 31.6 26.6 20.2 13.8 - 34.7 2.7 34.2 29.6 25.0 18.5 12.1 -

62 37.3 2.3 37.3 35.3 33.0 26.6 20.1 13.7 34.6 2.7 34.6 33.2 31.5 25.0 18.5 12.0

57 37.1 2.3 37.1 37.1 37.1 33.0 26.5 20.0 34.5 2.7 34.5 34.5 34.5 31.4 24.8 18.3

1350

72 40.6 2.4 35.5 28.4 21.3 14.1 - - 37.4 2.8 33.6 26.5 19.4 12.3 - -

67 38.9 2.4 38.9 33.7 28.5 21.3 14.2 - 36.0 2.8 36.0 31.4 26.8 19.6 12.4 -

62 39.0 2.3 39.0 37.5 35.7 28.5 21.3 14.1 36.0 2.8 36.0 35.4 34.2 26.9 19.6 12.3

57 39.1 2.3 39.1 39.1 39.1 35.7 28.5 21.3 36.1 2.8 36.1 36.1 36.1 34.2 26.8 19.5

1500

72 41.3 2.4 38.1 30.2 22.352 14.5 - - 38.1 2.8 36.1 28.2 20.3 12.5 - -

67 40.2 2.4 40.2 35.7 30.4 22.5 14.6 - 37.3 2.8 37.3 33.3 28.6 20.7 12.7 -

62 40.7 2.4 40.7 39.7 38.4 30.5 22.5 14.6 37.5 2.8 37.5 37.5 36.9 28.8 20.8 12.7

57 41.2 2.4 41.0 41.0 41.0 38.5 30.5 22.5 37.8 2.8 37.8 37.8 37.8 37.0 28.8 20.7

Page 51: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 51

115°F 125°F

750

77 35.7 3.2 18.2 14.4 10.6 - - - 32.6 3.6 17.3 13.4 9.5 - - -

72 31.8 3.1 22.5 18.4 14.3 10.3 - - 28.9 3.5 21.1 17.1 13.1 9.0 - -

67 28.0 3.0 26.7 22.4 18.0 13.9 9.8 - 25.2 3.4 25.0 20.8 16.6 12.5 8.5 -

62 28.0 3.1 27.7 24.7 21.7 17.6 13.5 9.4 25.9 3.4 25.3 22.7 20.1 16.1 12.0 7.9

900

77 35.7 3.2 21.2 15.8 10.5 - - - 32.5 3.6 20.3 14.7 9.1 - - -

72 32.4 3.1 24.8 19.9 15.1 10.3 - - 29.4 3.5 23.3 18.5 13.7 8.9 - -

67 29.2 3.1 28.4 24.1 19.8 14.9 10.0 - 26.4 3.5 26.4 22.3 18.3 13.4 8.6 -

62 29.3 3.1 29.3 26.9 24.4 19.5 14.6 9.7 27.0 3.5 26.8 24.8 22.9 18.0 13.0 8.1

57 29.4 3.1 29.4 29.4 29.1 24.1 19.2 14.2 27.6 3.5 27.2 27.2 27.2 22.5 17.5 12.5

1050

77 35.6 3.2 24.2 17.2 10.3 - - - 32.4 3.6 23.2 16.0 8.7 - - -

72 33.0 3.2 27.1 21.5 15.9 10.3 - - 30.0 3.6 25.5 19.9 14.4 8.8 - -

67 30.5 3.1 30.0 25.8 21.6 15.9 10.2 - 27.6 3.5 27.6 23.9 20.0 14.3 8.7 -

62 30.6 3.1 30.6 29.0 27.2 21.4 15.7 9.9 28.0 3.5 28.0 27.0 25.6 19.9 14.1 8.3

57 30.6 3.1 30.6 30.6 30.6 27.0 21.2 15.3 28.4 3.5 28.4 28.4 28.4 25.4 19.5 13.6

1200

77 35.6 3.2 27.1 18.6 10.1 - - - 32.3 3.6 26.1 17.2 8.3 - - -

72 33.7 3.2 29.4 23.1 16.7 10.4 - - 30.6 3.6 27.7 21.3 15.0 8.7 - -

67 31.7 3.2 31.7 27.5 23.3 16.9 10.4 - 28.8 3.6 28.8 25.4 21.7 15.2 8.7 -

62 31.8 3.2 31.8 31.2 29.9 23.4 16.8 10.2 29.1 3.6 29.1 29.1 28.4 21.8 15.1 8.5

57 31.9 3.2 31.9 31.9 31.9 29.9 23.2 16.5 29.3 3.6 29.3 29.3 29.3 28.3 21.5 14.7

1350

72 34.3 3.2 31.7 24.6 17.5 10.4 - - 31.1 3.6 29.8 22.7 15.7 8.6 - -

67 33.0 3.2 33.0 29.2 25.1 17.9 10.6 - 30.1 3.6 30.1 27.0 23.4 16.1 8.8 -

62 33.1 3.2 33.1 33.1 32.7 25.3 17.9 10.5 30.1 3.6 30.1 30.1 30.1 23.7 16.2 8.7

57 33.1 3.2 33.1 33.1 33.1 32.7 25.2 17.6 30.1 3.6 30.1 30.1 30.1 30.1 23.5 15.8

1500

72 34.9 3.2 34.0 26.2 18.3 10.5 - - 31.7 3.7 31.7 24.2 16.3 8.5 - -

67 34.3 3.2 34.3 30.9 26.9 18.8 10.8 - 31.3 3.7 31.3 28.5 25.1 17.0 8.9 -

62 34.3 3.2 34.3 34.3 34.3 27.2 19.0 10.8 31.1 3.6 31.1 31.1 31.1 25.6 17.2 8.9

57 34.4 3.2 34.4 34.4 34.4 34.4 27.2 18.8 31.0 3.6 31.0 31.0 31.0 31.0 25.5 16.9

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZJ037 (3.0 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 52: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

52 Johnson Controls Ducted Systems

ZJ049 (4.0 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1000

77 64.5 2.6 31.6 26.5 21.4 - - - 60.3 2.9 28.9 24.1 19.4 - - -

72 58.2 2.5 37.2 31.8 26.4 21.1 - - 54.5 2.9 35.4 30.1 24.7 19.4 - -

67 51.9 2.5 42.8 37.1 31.5 26.0 20.7 - 48.6 2.8 41.9 36.0 30.0 24.5 19.0 -

62 47.1 2.5 54.6 39.8 36.5 38.0 25.7 20.2 45.4 2.8 43.7 39.5 35.4 28.7 24.1 18.4

1200

77 66.1 2.6 34.9 28.4 21.9 - - - 61.3 2.9 32.9 26.4 19.9 - - -

72 60.2 2.5 40.8 34.5 28.1 21.7 - - 56.1 2.9 39.1 32.7 26.3 19.9 - -

67 54.2 2.5 46.8 40.5 34.3 27.8 21.4 - 50.8 2.8 45.3 39.0 32.7 26.1 19.6 -

62 50.4 2.5 46.8 43.6 40.4 41.0 27.4 20.9 48.3 2.9 46.6 42.9 39.1 31.6 25.8 19.1

57 46.6 2.5 46.6 46.6 46.6 40.0 33.5 26.9 45.7 2.9 45.7 45.7 45.5 38.7 31.9 25.1

1400

77 67.8 2.6 38.2 30.3 22.5 - - - 62.3 2.9 36.9 28.6 20.4 - - -

72 62.1 2.6 44.5 37.1 29.8 22.4 - - 57.7 2.9 42.8 35.3 27.9 20.4 - -

67 56.4 2.5 50.9 44.0 37.1 29.5 22.1 - 53.1 2.8 48.7 42.0 35.3 27.7 20.2 -

62 53.6 2.5 50.5 47.4 44.3 35.5 29.2 21.7 51.2 2.9 49.5 46.2 42.8 34.5 27.5 19.8

57 50.8 2.5 50.2 50.2 50.2 44.0 36.3 28.7 49.2 2.9 49.2 49.2 49.2 42.5 34.7 26.9

1600

77 69.5 2.6 41.5 32.2 23.0 - - - 63.4 2.9 40.9 30.9 20.9 - - -

72 64.1 2.6 48.2 39.8 31.4 23.1 - - 59.3 2.9 46.5 38.0 29.4 20.9 - -

67 58.7 2.5 54.9 47.4 39.8 31.3 22.8 - 55.3 2.9 52.1 45.0 38.0 29.4 20.8 -

62 56.8 2.5 54.2 51.2 48.2 38.8 31.0 22.4 54.0 2.9 52.4 49.5 46.5 37.4 29.2 20.5

57 55.0 2.5 53.5 53.5 53.5 47.9 39.2 30.4 52.8 2.9 52.8 52.8 52.8 46.3 37.5 28.8

1800

72 66.0 2.6 51.9 42.5 33.1 23.7 - - 60.9 2.9 50.2 40.6 31.0 21.4 - -

67 60.9 2.5 59.0 50.8 42.6 33.1 23.6 - 57.5 2.9 55.5 48.0 40.6 31.0 21.4 -

62 60.1 2.5 57.9 55.0 52.1 42.0 32.8 23.1 56.9 2.9 55.3 52.8 50.3 40.3 30.9 21.1

57 59.3 2.6 56.9 56.9 56.9 51.8 42.0 32.2 56.3 2.9 55.2 55.2 55.2 50.1 40.3 30.6

2000

72 68.0 2.6 55.5 45.1 34.8 24.4 - - 62.5 2.9 53.8 43.2 32.6 22.0 - -

67 63.2 2.6 63.0 54.2 45.4 34.8 24.3 - 59.7 2.9 58.8 51.1 43.3 32.6 21.9 -

62 63.3 2.6 69.7 58.8 56.0 45.3 34.6 23.8 59.8 2.9 58.2 56.1 54.0 43.3 32.5 21.8

57 63.5 2.6 69.9 63.4 66.7 55.8 44.9 34.0 59.8 2.9 68.4 61.1 64.7 53.9 43.2 32.495°F 105°F

1000

77 56.2 3.2 26.2 21.8 17.4 - - - 51.6 3.8 25.3 20.7 16.1 - - -

72 50.8 3.2 33.7 28.3 23.0 17.6 - - 47.1 3.7 32.4 26.9 21.5 16.0 - -

67 45.3 3.2 41.1 34.9 28.6 23.0 17.4 - 42.6 3.7 39.4 33.1 26.8 21.2 15.6 -

62 43.7 3.2 43.7 39.3 34.2 28.4 22.5 16.6 41.5 3.7 41.2 36.7 32.2 26.4 20.7 14.9

1200

77 56.6 3.2 30.9 24.4 17.8 - - - 52.0 3.8 29.7 22.9 16.1 - - -

72 52.0 3.2 37.4 30.9 24.5 18.0 - - 48.3 3.7 35.7 29.2 22.7 16.2 - -

67 47.5 3.2 43.8 37.5 31.1 24.5 17.8 - 44.6 3.7 41.7 35.5 29.3 22.6 15.9 -

62 46.2 3.2 46.2 42.1 37.8 30.9 24.1 17.3 43.6 3.7 43.1 39.5 35.9 29.1 22.2 15.4

57 44.9 3.2 44.9 44.9 44.4 37.4 30.4 23.3 42.7 3.6 42.7 42.7 42.5 35.5 28.5 21.5

1400

77 56.9 3.2 35.6 26.9 18.3 - - - 52.3 3.8 34.1 25.1 16.1 - - -

72 53.3 3.2 41.1 33.5 26.0 18.4 - - 49.4 3.7 39.0 31.5 23.9 16.4 - -

67 49.7 3.2 46.5 40.1 33.6 26.0 18.3 - 46.5 3.7 43.9 37.9 31.8 24.0 16.3 -

62 48.7 3.2 48.5 44.9 41.3 33.5 25.7 17.9 45.8 3.7 45.0 42.3 39.6 31.7 23.8 15.8

57 47.7 3.2 47.7 47.7 47.7 41.1 33.1 25.2 45.1 3.7 45.1 45.1 45.1 39.3 31.2 23.1

1600

77 57.2 3.2 40.3 29.5 18.7 - - - 52.7 3.7 38.5 27.3 16.1 - - -

72 54.6 3.2 44.8 36.1 27.4 18.8 - - 50.5 3.7 42.4 33.8 25.2 16.6 - -

67 51.9 3.2 49.2 42.7 36.1 27.4 18.7 - 48.4 3.7 46.2 40.2 34.3 25.5 16.7 -

62 51.2 3.2 50.6 47.7 44.8 36.1 27.3 18.5 47.9 3.7 47.0 45.1 43.3 34.3 25.3 16.3

57 50.5 3.2 50.5 50.5 50.5 44.7 35.9 27.1 47.5 3.7 47.5 47.5 47.5 43.2 34.0 24.7

1800

72 55.8 3.2 48.4 38.7 28.9 19.2 - - 51.7 3.7 45.7 36.1 26.4 16.8 - -

67 54.1 3.2 51.9 45.3 38.7 28.9 19.2 - 50.3 3.7 48.4 42.6 36.7 26.9 17.0 -

62 53.7 3.2 52.7 50.6 48.4 38.6 28.9 19.2 50.1 3.7 48.9 47.9 47.0 36.9 26.9 16.8

57 53.4 3.2 53.4 53.4 53.4 48.4 38.7 28.9 49.8 3.7 49.3 49.3 49.3 47.0 36.7 26.4

2000

72 57.1 3.2 52.1 41.3 30.405 19.5 - - 52.8 3.7 49.0 38.3 27.7 17.0 - -

67 56.3 3.2 54.6 47.9 41.2 30.4 19.6 - 52.3 3.7 50.7 45.0 39.2 28.3 17.4 -

62 56.2 3.2 54.8 53.4 51.9 41.2 30.5 19.8 52.2 3.7 50.8 50.8 50.7 39.6 28.4 17.2

57 56.2 3.2 55.0 55.0 55.0 52.1 41.4 30.8 52.2 3.7 50.9 50.9 50.9 50.9 39.4 28.0

Page 53: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 53

115°F 125°F

1000

77 47.0 4.4 24.4 19.6 14.8 - - - 42.5 4.9 23.5 18.5 13.5 - - -

72 43.5 4.3 31.1 25.5 19.9 14.3 - - 39.9 4.8 29.8 24.1 18.4 12.7 - -

67 39.9 4.2 37.8 31.4 25.0 19.4 13.8 - 37.2 4.7 44.0 29.7 23.3 17.6 12.0 -

62 39.3 4.1 38.1 34.1 30.2 24.5 18.8 13.2 37.1 4.6 35.0 31.5 28.1 22.5 17.0 11.4

1200

77 47.4 4.3 28.5 21.5 14.4 - - - 42.8 4.9 27.3 20.0 12.6 - - -

72 44.5 4.3 34.1 27.5 20.9 14.4 - - 40.7 4.8 32.4 25.8 19.2 12.5 - -

67 41.6 4.2 39.6 33.5 27.5 20.8 14.1 - 38.6 4.7 46.2 31.6 25.7 18.9 12.2 -

62 41.1 4.1 39.8 36.9 34.0 27.2 20.3 13.5 38.5 4.6 36.5 34.3 32.2 25.3 18.4 11.5

57 40.6 4.1 40.1 40.1 40.1 33.6 26.6 19.6 38.4 4.5 46.4 37.1 38.7 31.7 24.7 17.7

1400

77 47.7 4.3 32.7 23.3 13.9 - - - 43.1 4.8 31.2 21.5 11.8 - - -

72 45.5 4.2 37.0 29.5 21.9 14.4 - - 41.6 4.8 35.0 27.5 19.9 12.4 - -

67 43.3 4.2 41.4 35.6 29.9 22.1 14.3 - 40.0 4.7 48.2 33.4 28.1 20.2 12.4 -

62 42.9 4.1 41.5 39.7 37.9 29.9 21.8 13.8 39.9 4.6 38.1 37.1 36.2 28.0 19.9 11.7

57 42.5 4.1 41.7 41.7 41.7 37.6 29.3 21.0 39.9 4.5 48.4 40.8 44.4 35.9 27.4 18.9

1600

77 48.1 4.2 36.8 25.1 13.5 - - - 43.5 4.7 35.0 23.0 10.9 - - -

72 46.5 4.2 40.0 31.5 22.9 14.4 - - 42.4 4.7 37.6 29.1 20.7 12.2 - -

67 44.9 4.2 43.2 37.8 32.4 23.5 14.6 - 41.4 4.7 50.2 35.3 30.5 21.5 12.6 -

62 44.6 4.2 43.3 42.5 41.8 32.6 23.3 14.1 41.4 4.6 39.6 39.6 39.6 30.8 21.3 11.8

57 44.4 4.1 43.4 43.4 43.4 41.6 32.0 22.4 41.3 4.6 50.4 44.6 50.1 40.1 30.1 20.1

1800

72 47.5 4.2 42.9 33.4 23.9 14.5 - - 43.3 4.7 40.2 30.8 21.5 12.1 - -

67 46.6 4.2 45.0 39.9 34.8 24.8 14.9 - 42.8 4.7 52.3 37.2 32.9 22.8 12.7 -

62 46.4 4.2 45.0 45.0 45.0 35.2 24.8 14.4 42.8 4.6 41.1 41.1 41.1 33.5 22.7 12.0

57 46.3 4.2 45.1 45.1 45.1 45.1 34.7 23.8 42.7 4.6 52.5 48.3 52.5 44.2 32.7 21.3

2000

72 48.5 4.2 45.9 35.4 25.0 14.5 - - 44.2 4.6 42.8 32.5 22.2 12.0 - -

67 48.2 4.2 46.7 42.0 37.3 26.2 15.2 - 44.2 4.7 42.8 39.0 35.3 24.1 12.9 -

62 48.2 4.2 46.7 46.7 46.7 37.9 26.3 14.7 44.2 4.7 42.7 42.7 42.7 36.3 24.2 12.1

57 48.2 4.2 46.7 46.7 46.7 46.7 37.4 25.2 44.2 4.7 42.6 42.6 42.6 42.6 35.4 22.4

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZJ049 (4.0 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 54: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

54 Johnson Controls Ducted Systems

ZJ061 (5.0 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1250

77 80.3 3.2 40.2 34.0 27.8 - - - 76.4 3.6 37.4 31.5 25.6 - - -

72 72.1 3.2 46.8 40.1 33.4 26.6 - - 69.0 3.6 44.9 38.1 31.4 24.7 - -

67 63.9 3.2 53.4 46.2 38.9 32.4 25.7 - 61.7 3.6 52.3 44.7 37.2 30.5 23.8 -

62 58.2 3.1 54.6 49.3 44.4 38.0 31.4 25.0 56.3 3.6 55.3 49.1 43.0 35.2 29.7 23.1

1500

77 81.3 3.3 43.6 35.8 28.0 - - - 77.2 3.6 41.5 33.7 26.0 - - -

72 73.7 3.2 51.1 43.1 35.1 27.2 - - 70.3 3.6 49.2 41.2 33.2 25.3 - -

67 66.1 3.2 58.5 50.4 42.3 34.4 26.4 - 63.4 3.6 56.9 48.7 40.5 32.5 24.5 -

62 61.7 3.2 58.5 54.0 49.5 41.0 33.6 25.6 59.4 3.6 58.7 53.2 47.8 38.9 31.7 23.6

57 57.3 3.1 57.3 57.3 56.7 48.7 40.8 32.8 55.4 3.6 55.4 55.4 55.1 47.0 38.9 30.8

1750

77 82.3 3.3 47.0 37.5 28.1 - - - 77.9 3.6 45.6 35.9 26.3 - - -

72 75.3 3.2 55.3 46.1 36.9 27.7 - - 71.5 3.6 53.5 44.3 35.1 25.8 - -

67 68.2 3.2 63.6 54.7 45.8 36.5 27.1 - 65.1 3.6 61.4 52.6 43.8 34.5 25.1 -

62 65.2 3.2 62.9 58.8 54.6 43.9 35.7 26.3 62.5 3.6 62.1 57.4 52.6 42.5 33.6 24.1

57 62.1 3.2 62.1 62.1 61.8 53.9 44.3 34.7 60.0 3.6 60.0 60.0 60.0 51.8 42.2 32.5

2000

77 83.3 3.3 50.3 39.3 28.2 - - - 78.6 3.7 49.7 38.1 26.6 - - -

72 76.9 3.3 59.5 49.1 38.7 28.3 - - 72.7 3.6 57.8 47.4 36.9 26.4 - -

67 70.4 3.2 68.7 58.9 49.2 38.6 27.9 - 66.8 3.6 66.0 56.6 47.2 36.5 25.8 -

62 68.7 3.2 67.3 63.5 59.7 47.9 37.9 26.9 65.6 3.6 65.5 61.5 57.5 46.1 35.6 24.7

57 67.0 3.2 66.0 66.0 66.0 59.0 47.8 36.7 64.5 3.6 64.5 64.5 64.5 56.6 45.5 34.3

2250

72 78.4 3.3 63.7 52.1 40.5 28.9 - - 73.9 3.6 62.2 50.4 38.7 27.0 - -

67 72.6 3.2 72.6 63.2 52.7 40.7 28.6 - 68.5 3.6 68.5 60.5 50.5 38.5 26.4 -

62 72.2 3.2 71.7 68.3 64.8 52.0 40.0 27.6 68.7 3.6 68.7 65.6 62.3 49.7 37.6 25.2

57 71.8 3.2 69.7 69.7 69.7 64.2 51.4 38.6 69.0 3.6 67.2 67.2 67.2 61.5 48.8 36.1

2500

72 80.0 3.3 67.9 55.1 42.3 29.4 - - 75.1 3.7 66.5 53.5 40.5 27.5 - -

67 74.8 3.2 74.8 67.5 56.1 42.7 29.4 - 70.2 3.6 70.2 64.5 53.8 40.5 27.1 -

62 75.7 3.3 69.7 69.7 69.7 56.0 42.1 28.3 71.9 3.6 71.9 69.7 67.2 53.4 39.6 25.8

57 76.7 3.3 69.9 69.9 69.9 69.3 54.9 40.5 73.5 3.6 68.4 68.4 68.4 66.3 52.1 37.9

95°F 105°F

1250

77 72.6 4.0 34.6 29.0 23.4 - - - 65.5 4.6 30.7 26.1 21.4 - - -

72 66.0 4.0 42.9 36.2 29.5 22.7 - - 61.0 4.6 40.8 34.8 28.7 22.7 - -

67 59.4 4.0 51.2 43.3 35.5 28.7 22.0 - 56.5 4.6 50.9 43.5 36.0 29.4 22.8 -

62 54.4 4.1 54.4 49.0 41.5 34.7 27.9 21.2 53.2 4.6 53.2 48.9 43.4 36.2 29.0 21.8

1500

77 73.0 4.0 39.4 31.7 23.9 - - - 66.4 4.6 36.2 28.9 21.6 - - -

72 66.8 4.0 47.3 39.3 31.3 23.3 - - 62.0 4.6 45.1 37.6 30.1 22.7 - -

67 60.7 4.0 55.2 47.0 38.7 30.6 22.5 - 57.5 4.6 53.9 46.3 38.7 30.7 22.7 -

62 57.1 4.0 57.1 52.5 46.1 37.9 29.8 21.6 55.2 4.6 55.2 51.8 47.3 38.7 30.1 21.5

57 53.6 4.1 53.6 53.6 53.5 45.2 37.0 28.7 52.8 4.6 52.8 52.8 52.8 46.7 37.5 28.4

1750

77 73.5 4.0 44.2 34.3 24.4 - - - 67.2 4.6 41.8 31.8 21.8 - - -

72 67.7 4.0 51.8 42.5 33.2 23.9 - - 62.9 4.6 49.3 40.4 31.6 22.7 - -

67 61.9 4.0 59.3 50.6 41.9 32.5 23.1 - 58.6 4.6 56.8 49.1 41.4 31.9 22.5 -

62 59.8 4.0 59.8 56.0 50.7 41.1 31.6 22.0 57.2 4.6 57.2 54.6 51.2 41.2 31.2 21.2

57 57.8 4.1 57.8 57.8 57.8 49.7 40.0 30.3 55.7 4.6 55.7 55.7 55.7 50.4 39.9 29.4

2000

77 73.9 4.0 49.1 37.0 24.9 - - - 68.1 4.6 47.3 34.6 22.0 - - -

72 68.5 4.0 56.2 45.6 35.0 24.5 - - 63.9 4.6 53.6 43.3 33.0 22.7 - -

67 63.2 4.0 63.2 54.2 45.2 34.4 23.6 - 59.7 4.6 59.7 51.9 44.0 33.2 22.4 -

62 62.6 4.0 62.6 59.5 55.3 44.3 33.4 22.4 59.1 4.6 59.1 57.5 55.1 43.7 32.3 20.9

57 62.0 4.0 62.0 62.0 62.0 54.2 43.1 32.0 58.6 4.6 58.6 58.6 58.6 54.2 42.3 30.3

2250

72 69.4 4.0 60.6 48.8 36.9 25.1 - - 64.8 4.6 57.8 46.1 34.4 22.7 - -

67 64.4 4.0 64.4 57.9 48.4 36.3 24.2 - 60.7 4.6 60.7 54.7 46.7 34.5 22.2 -

62 65.3 4.0 65.3 62.9 59.8 47.5 35.2 22.8 61.1 4.6 61.1 60.4 59.0 46.2 33.4 20.7

57 66.1 4.0 64.7 64.7 64.7 58.7 46.2 33.6 61.5 4.5 60.8 60.8 60.8 57.9 44.6 31.3

2500

72 70.3 4.0 65.1 51.9 38.778 25.6 - - 65.8 4.6 62.0 48.9 35.8 22.7 - -

67 65.6 4.0 65.6 61.5 51.6 38.2 24.7 - 61.8 4.6 61.8 57.5 49.4 35.7 22.1 -

62 68.0 4.0 68.0 66.4 64.4 50.7 37.0 23.3 63.1 4.5 63.1 63.1 62.9 48.7 34.6 20.4

57 70.3 4.0 65.5 65.5 65.5 63.2 49.2 35.2 64.5 4.5 61.5 61.5 61.5 61.5 47.0 32.3

Page 55: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 55

115°F 125°F

1250

77 58.5 5.1 26.8 23.1 19.3 - - - 51.5 5.7 22.9 20.1 17.3 - - -

72 56.0 5.1 38.8 33.4 28.0 22.6 - - 51.0 5.7 36.7 32.0 27.2 22.5 - -

67 53.5 5.2 50.7 43.7 36.6 30.1 23.6 - 50.5 5.7 44.0 43.8 37.2 30.8 24.4 -

62 51.9 5.2 51.9 48.9 45.2 37.6 30.0 22.4 50.6 5.7 50.5 48.8 47.1 39.1 31.0 23.0

1500

77 59.8 5.1 33.0 26.1 19.2 - - - 53.1 5.7 29.9 23.4 16.9 - - -

72 57.1 5.1 42.8 35.9 29.0 22.0 - - 52.2 5.7 40.6 34.2 27.8 21.4 - -

67 54.4 5.1 52.6 45.6 38.7 30.7 22.8 - 51.2 5.7 46.2 45.0 38.7 30.8 22.9 -

62 53.2 5.2 53.2 51.1 48.5 39.4 30.4 21.4 51.2 5.7 51.2 50.4 49.6 40.2 30.8 21.3

57 52.0 5.2 52.0 52.0 52.0 48.1 38.1 28.0 51.2 5.7 46.4 46.4 46.4 46.4 38.6 27.7

1750

77 61.0 5.2 39.3 29.2 19.1 - - - 54.7 5.7 36.8 26.6 16.4 - - -

72 58.1 5.1 46.9 38.4 29.9 21.5 - - 53.4 5.7 44.4 36.4 28.3 20.3 - -

67 55.3 5.1 54.4 47.6 40.8 31.4 21.9 - 52.0 5.7 48.2 46.1 40.3 30.8 21.4 -

62 54.5 5.1 54.5 53.3 51.7 41.3 30.9 20.4 51.8 5.7 51.8 51.8 51.8 41.3 30.5 19.7

57 53.6 5.1 53.6 53.6 53.6 51.2 39.8 28.4 51.6 5.7 48.4 48.4 48.4 48.4 39.6 27.4

2000

77 62.2 5.2 45.6 32.3 19.0 - - - 56.3 5.7 43.8 29.9 16.0 - - -

72 59.2 5.1 50.9 40.9 30.9 20.9 - - 54.5 5.7 48.3 38.6 28.9 19.2 - -

67 56.2 5.1 56.2 49.6 42.9 32.0 21.1 - 52.7 5.7 50.2 47.3 41.8 30.8 19.9 -

62 55.7 5.1 55.7 55.6 54.9 43.1 31.3 19.5 52.3 5.7 52.3 52.3 52.3 42.5 30.2 18.0

57 55.3 5.1 55.3 55.3 55.3 54.2 41.4 28.7 52.0 5.7 50.4 50.4 50.4 50.4 40.6 27.1

2250

72 60.3 5.1 55.0 43.4 31.9 20.4 - - 55.7 5.7 52.1 40.8 29.4 18.1 - -

67 57.1 5.1 57.1 51.6 45.0 32.6 20.3 - 53.4 5.6 52.3 48.4 43.3 30.8 18.3 -

62 57.0 5.1 57.0 57.0 57.0 44.9 31.7 18.5 52.9 5.6 52.9 52.9 52.9 43.6 30.0 16.3

57 56.9 5.1 56.9 56.9 56.9 56.9 43.1 29.1 52.4 5.6 52.5 52.5 52.5 52.5 41.6 26.8

2500

72 61.3 5.1 59.0 46.0 32.9 19.8 - - 56.9 5.7 56.0 43.0 30.0 16.9 - -

67 58.0 5.1 58.0 53.5 47.1 33.3 19.5 - 54.2 5.6 54.2 49.5 44.9 30.8 16.8 -

62 58.3 5.1 58.3 58.3 58.3 46.7 32.1 17.5 53.5 5.6 53.5 53.5 53.5 44.7 29.7 14.7

57 58.6 5.1 57.6 57.6 57.6 57.6 44.8 29.4 52.7 5.6 52.7 52.7 52.7 52.7 42.6 26.5

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZJ061 (5.0 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 56: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

56 Johnson Controls Ducted Systems

ZJ078 (6.5 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1625

77 109.0 5.3 61.1 51.7 42.4 - - - 98.6 5.5 51.7 43.3 35.0 - - -

72 94.4 4.9 64.2 53.6 43.1 32.5 - - 86.7 5.2 58.8 49.1 39.5 29.8 - -

67 79.8 4.4 67.2 55.5 43.8 36.8 30.7 - 74.8 5.0 66.0 55.0 44.0 36.0 28.5 -

62 72.8 4.4 72.8 62.9 49.3 41.7 39.4 36.8 70.0 4.9 70.0 61.8 50.8 42.5 36.8 31.0

1950

77 107.9 5.2 64.3 50.9 37.6 - - - 98.7 5.5 57.1 45.4 33.7 - - -

72 95.7 4.8 68.9 57.4 45.819 34.3 - - 88.6 5.3 64.3 53.4 42.6 31.8 - -

67 83.6 4.5 73.6 63.8 54.1 43.2 33.0 - 78.5 5.1 71.4 61.5 51.5 41.1 31.0 -

62 78.0 4.5 78.0 71.4 62.3 52.7 43.4 33.9 74.6 5.0 74.6 68.5 60.4 50.6 40.9 31.2

57 72.5 4.4 72.5 72.5 70.5 62.1 53.7 45.3 70.7 5.0 70.7 70.7 69.3 60.1 50.9 41.6

2275

77 106.8 5.1 67.5 50.2 32.8 - - - 98.9 5.5 62.6 47.5 32.5 - - -

72 97.1 4.8 73.7 61.1 48.6 36.0 - - 90.5 5.3 69.7 57.7 45.8 33.8 - -

67 87.4 4.5 79.9 72.1 64.3 49.6 35.4 - 82.2 5.2 76.8 68.0 59.1 46.1 33.4 -

62 83.2 4.5 83.2 79.9 75.3 63.6 47.4 31.1 79.2 5.2 79.2 75.3 70.1 58.6 45.0 31.3

57 79.0 4.5 79.0 79.0 78.1 73.9 59.4 41.2 76.3 5.1 76.3 76.3 76.3 69.3 56.5 41.9

2600

77 105.7 5.0 70.7 49.4 28.0 - - - 99.0 5.4 68.0 49.6 31.2 - - -

72 98.4 4.8 78.5 64.9 51.3 37.7 - - 92.4 5.4 75.1 62.0 48.9 35.9 - -

67 91.2 4.6 86.2 80.4 74.6 56.0 37.8 - 85.8 5.3 82.3 74.5 66.7 51.2 35.9 -

62 88.4 4.6 88.4 88.4 88.4 74.5 51.4 28.2 83.8 5.3 83.8 82.0 79.7 66.7 49.1 31.4

57 85.6 4.6 85.6 85.6 85.6 85.6 65.1 37.0 81.9 5.3 81.9 81.9 81.9 78.4 62.2 42.2

2925

72 99.8 4.8 83.2 68.6 54.0 39.4 - - 94.3 5.4 80.6 66.3 52.1 37.9 - -

67 95.0 4.7 92.5 88.6 84.8 62.4 40.1 - 89.5 5.4 87.7 81.0 74.2 56.3 38.4 -

62 93.6 4.7 93.6 93.6 93.6 85.5 55.4 25.3 88.5 5.4 88.5 88.5 88.5 74.7 53.1 31.5

57 92.2 4.7 92.2 92.2 92.2 92.2 70.7 32.9 87.5 5.4 87.5 87.5 87.5 87.5 67.9 42.5

3250

72 101.1 4.8 88.0 72.4 56.767 41.2 - - 96.2 5.4 86.0 70.6 55.3 39.9 - -

67 98.8 4.8 98.8 96.9 95.1 68.8 42.5 - 93.1 5.5 93.1 87.5 81.8 61.3 40.9 -

62 98.8 4.8 98.8 98.8 98.8 96.4 59.4 22.5 93.1 5.5 93.1 93.1 93.1 82.8 57.2 31.6

57 98.8 4.8 98.8 98.8 98.8 98.8 76.4 28.8 93.1 5.5 93.1 93.1 93.1 93.1 73.5 42.8

95°F 105°F

1625

77 88.2 5.7 42.3 34.9 27.6 - - - 81.7 6.6 39.5 32.4 25.4 - - -

72 79.0 5.6 53.5 44.7 35.9 27.1 - - 72.4 6.5 50.9 42.2 33.5 24.8 - -

67 69.9 5.5 64.7 54.4 44.1 35.2 26.3 - 63.6 6.4 62.3 51.9 41.5 32.7 23.9 -

62 67.1 5.5 67.1 60.7 52.4 43.3 34.3 25.3 62.3 6.4 62.3 56.9 49.6 40.6 31.6 22.7

1950

77 89.6 5.8 49.9 39.9 29.9 - - - 82.8 6.6 47.4 37.5 27.6 - - -

72 81.5 5.7 59.6 49.5 39.434 29.4 - - 75.2 6.6 57.0 47.1 37.1 27.1 - -

67 73.4 5.7 69.2 59.1 49.0 38.9 28.9 - 67.6 6.5 66.6 56.6 46.6 36.6 26.6 -

62 71.2 5.6 71.2 65.7 58.6 48.5 38.4 28.4 66.6 6.5 66.6 62.2 56.2 46.0 35.9 25.8

57 68.9 5.6 68.9 68.9 68.1 58.1 48.0 38.0 65.6 6.5 65.6 65.6 65.6 55.5 45.3 35.1

2275

77 91.0 5.8 57.6 44.9 32.1 - - - 84.0 6.7 55.4 42.6 29.7 - - -

72 84.0 5.8 65.7 54.4 43.0 31.7 - - 78.0 6.7 63.1 51.9 40.7 29.5 - -

67 76.9 5.8 73.8 63.8 53.9 42.7 31.5 - 71.7 6.6 70.9 61.3 51.7 40.5 29.3 -

62 75.2 5.8 75.2 70.6 64.8 53.7 42.6 31.5 70.9 6.6 70.9 67.4 62.8 51.5 40.2 28.9

57 73.5 5.8 73.5 73.5 73.5 64.7 53.7 42.7 70.1 6.6 70.1 70.1 70.1 62.4 51.1 39.8

2600

77 92.4 5.9 65.2 49.8 34.4 - - - 85.2 6.7 63.4 47.6 31.9 - - -

72 86.4 5.9 71.8 59.2 46.6 34.0 - - 80.8 6.8 69.3 56.8 44.4 31.9 - -

67 80.4 5.9 78.4 68.6 58.8 46.4 34.0 - 75.7 6.8 75.2 66.0 56.8 44.4 32.0 -

62 79.3 5.9 79.3 75.5 71.0 58.8 46.7 34.6 75.2 6.8 75.2 72.7 69.3 56.9 44.5 32.0

57 78.2 5.9 78.2 78.2 78.2 71.3 59.3 47.4 74.7 6.8 74.7 74.7 74.7 69.4 57.0 44.6

2925

72 88.9 6.0 77.9 64.0 50.2 36.3 - - 83.6 6.9 75.4 61.7 48.0 34.3 - -

67 84.0 6.1 82.9 73.3 63.7 50.2 36.6 - 79.8 6.9 79.5 70.7 62.0 48.3 34.7 -

62 83.4 6.1 83.4 80.5 77.2 64.0 50.8 37.6 79.5 6.9 79.5 77.9 75.9 62.3 48.7 35.2

57 82.8 6.0 82.8 82.8 82.8 77.8 65.0 52.2 79.2 6.9 79.2 79.2 79.2 76.3 62.8 49.3

3250

72 91.3 6.1 84.0 68.9 53.757 38.6 - - 86.4 6.9 81.5 66.6 51.6 36.7 - -

67 87.5 6.2 87.5 78.0 68.6 53.9 39.2 - 83.8 7.0 83.8 75.4 67.1 52.2 37.4 -

62 87.4 6.2 87.4 85.4 83.4 69.2 54.9 40.7 83.8 7.0 83.8 83.1 82.5 67.8 53.0 38.3

57 87.4 6.2 87.4 87.4 87.4 84.4 70.7 56.9 83.8 7.0 83.8 83.8 83.8 83.3 68.7 54.1

Page 57: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 57

115°F 125°F

1625

77 75.1 7.4 36.7 30.0 23.2 - - - 68.6 8.2 34.0 27.5 21.0 - - -

72 65.8 7.3 48.3 39.7 31.1 22.5 - - 59.2 8.1 45.7 37.2 28.7 20.2 - -

67 57.2 7.2 57.2 49.4 39.0 30.2 21.4 - 50.9 8.0 50.9 46.9 36.4 27.7 19.0 -

62 57.5 7.2 57.5 53.1 46.8 37.9 29.0 20.0 52.7 8.1 52.7 49.3 44.1 35.2 26.3 17.4

1950

77 76.1 7.5 45.0 35.1 25.3 - - - 69.3 8.3 42.5 32.7 23.0 - - -

72 68.9 7.4 54.4 44.6 34.8 24.9 - - 62.7 8.2 51.9 42.2 32.4 22.7 - -

67 61.8 7.3 61.8 54.1 44.3 34.3 24.2 - 56.0 8.2 56.0 51.6 41.9 31.9 21.9 -

62 62.0 7.3 62.0 58.7 53.8 43.6 33.4 23.2 57.5 8.2 57.5 55.2 51.4 41.1 30.9 20.6

57 62.3 7.4 62.3 62.3 62.3 52.9 42.5 32.2 58.9 8.2 56.7 56.7 56.7 50.3 39.8 29.3

2275

77 77.0 7.5 53.2 40.3 27.3 - - - 70.0 8.4 51.0 38.0 24.9 - - -

72 72.1 7.5 60.6 49.5 38.5 27.4 - - 66.1 8.4 58.1 47.1 36.2 25.2 - -

67 66.4 7.5 66.4 58.8 49.6 38.3 27.1 - 61.1 8.3 61.1 56.3 47.4 36.2 24.9 -

62 66.6 7.5 66.6 64.2 60.7 49.3 37.8 26.4 62.2 8.3 62.2 61.0 58.7 47.1 35.4 23.8

57 66.7 7.5 66.7 66.7 66.7 60.2 48.6 36.9 63.3 8.3 61.6 61.6 61.6 58.0 46.0 34.1

2600

77 77.9 7.6 61.5 45.4 29.4 - - - 70.7 8.4 59.6 43.2 26.8 - - -

72 75.2 7.6 66.8 54.4 42.1 29.8 - - 69.6 8.5 64.2 52.1 39.9 27.7 - -

67 71.0 7.6 71.0 63.5 54.9 42.4 29.9 - 66.3 8.4 66.3 60.9 53.0 40.4 27.8 -

62 71.1 7.6 71.1 69.8 67.7 55.0 42.2 29.5 67.0 8.4 67.0 66.9 66.0 53.0 40.0 27.0

57 71.2 7.6 71.2 71.2 71.2 67.5 54.6 41.7 67.7 8.5 66.6 66.6 66.6 65.7 52.2 38.8

2925

72 78.4 7.7 72.9 59.4 45.8 32.3 - - 73.1 8.6 70.4 57.0 43.6 30.3 - -

67 75.6 7.7 75.6 68.2 60.2 46.5 32.7 - 71.4 8.6 71.4 65.6 58.5 44.6 30.7 -

62 75.6 7.7 75.6 75.3 74.6 60.7 46.7 32.7 71.8 8.6 71.8 71.8 71.8 59.0 44.6 30.2

57 75.7 7.7 75.7 75.7 75.7 74.8 60.6 46.5 72.1 8.6 71.5 71.5 71.5 71.5 58.5 43.6

3250

72 81.5 7.8 79.1 64.3 49.5 34.7 - - 76.6 8.7 76.6 62.0 47.4 32.8 - -

67 80.2 7.9 80.2 72.9 65.5 50.5 35.5 - 76.6 8.7 76.6 70.3 64.0 48.8 33.7 -

62 80.2 7.9 80.2 80.2 80.2 66.3 51.1 35.9 76.5 8.7 76.5 76.5 76.5 64.9 49.2 33.4

57 80.1 7.9 80.1 80.1 80.1 80.1 66.7 51.2 76.5 8.7 76.5 76.5 76.5 76.5 64.7 48.4

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZJ078 (6.5 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 58: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

58 Johnson Controls Ducted Systems

ZJ090 (7.5 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1875

77 117.2 4.8 57.7 49.7 41.7 - - - 113.7 5.4 56.6 48.5 40.4 - - -

72 106.9 4.7 71.6 62.0 52.4 42.7 - - 102.5 5.3 69.8 60.1 50.4 40.7 - -

67 96.6 4.7 85.4 74.2 63.0 53.2 43.3 - 91.3 5.3 83.0 71.7 60.4 50.7 41.0 -

62 91.7 4.7 91.7 82.7 73.6 61.2 53.5 43.4 87.9 5.3 87.9 79.1 70.3 59.5 50.9 41.2

2250

77 117.1 4.9 65.4 54.2 43.1 - - - 113.2 5.5 64.8 53.3 41.7 - - -

72 108.2 4.8 77.9 66.6 55.203 43.8 - - 103.7 5.4 76.1 64.7 53.2 41.8 - -

67 99.3 4.8 90.4 78.9 67.4 55.9 44.3 - 94.1 5.4 87.4 76.1 64.7 53.4 42.0 -

62 95.4 4.8 95.4 87.5 79.5 66.0 56.2 44.6 91.3 5.4 91.3 83.8 76.3 64.0 53.6 42.3

57 91.5 4.7 91.5 91.5 91.5 79.9 68.1 56.3 88.5 5.4 88.5 88.5 87.8 76.5 65.3 54.1

2625

77 117.0 5.0 73.1 58.8 44.4 - - - 112.7 5.6 73.1 58.1 43.0 - - -

72 109.6 4.9 84.3 71.2 58.1 44.9 - - 104.8 5.6 82.5 69.3 56.1 42.9 - -

67 102.1 4.9 95.4 83.6 71.7 58.6 45.4 - 96.8 5.5 91.8 80.5 69.1 56.1 43.0 -

62 99.1 4.9 99.1 92.3 85.4 70.8 59.0 45.8 94.7 5.5 94.7 88.5 82.2 68.6 56.4 43.5

57 96.2 4.9 96.2 96.2 96.2 85.8 72.5 59.3 92.6 5.5 92.6 92.6 92.6 82.5 69.8 57.0

3000

77 116.9 5.1 80.9 63.3 45.7 - - - 112.2 5.7 81.4 62.8 44.3 - - -

72 110.9 5.0 90.6 75.8 60.9 46.0 - - 105.9 5.7 88.8 73.9 58.9 44.0 - -

67 104.9 5.0 100.4 88.2 76.1 61.3 46.4 - 99.6 5.6 96.2 84.9 73.5 58.8 44.1 -

62 102.9 5.0 102.9 97.0 91.2 75.5 61.7 47.0 98.2 5.6 98.2 93.1 88.1 73.2 59.2 44.7

57 100.9 5.0 100.9 100.9 100.9 91.7 77.0 62.3 96.7 5.6 96.7 96.7 96.7 88.5 74.2 60.0

3375

72 112.2 5.1 97.0 80.4 63.7 47.1 - - 107.0 5.8 95.2 78.5 61.8 45.1 - -

67 107.7 5.1 105.4 92.9 80.4 64.0 47.5 - 102.3 5.8 100.7 89.3 77.9 61.5 45.1 -

62 106.6 5.1 106.6 101.8 97.1 80.3 64.5 48.2 101.6 5.8 101.6 97.8 94.0 77.7 61.9 45.9

57 105.5 5.1 105.5 105.5 105.5 97.6 81.5 65.3 100.8 5.8 100.8 100.8 100.8 94.4 78.7 63.0

3750

72 113.6 5.2 103.3 85.0 66.596 48.2 - - 108.1 5.9 101.5 83.0 64.6 46.1 - -

67 110.4 5.2 110.4 97.6 84.8 66.7 48.5 - 105.1 5.9 105.1 93.7 82.3 64.2 46.2 -

62 110.3 5.2 110.3 106.6 102.9 85.1 67.2 49.4 105.0 5.9 105.0 102.5 99.9 82.3 64.7 47.0

57 110.2 5.2 110.2 110.2 110.2 103.5 85.9 68.3 104.9 5.9 104.9 104.9 104.9 100.4 83.2 65.9

95°F 105°F

1875

77 110.3 6.0 55.4 47.3 39.2 - - - 102.6 6.9 53.7 45.8 37.8 - - -

72 98.2 5.9 68.0 58.2 48.4 38.7 - - 92.0 6.8 65.8 56.2 46.6 37.0 - -

67 86.1 5.9 80.6 69.1 57.7 48.2 38.6 - 81.6 6.8 77.9 66.7 55.4 46.0 36.7 -

62 84.0 5.9 84.0 75.5 67.0 57.7 48.3 39.0 80.3 6.7 80.3 72.2 64.1 55.1 46.0 36.9

2250

77 109.3 6.1 64.2 52.3 40.4 - - - 101.7 7.0 61.9 50.1 38.4 - - -

72 99.1 6.1 74.3 62.8 51.272 39.7 - - 93.0 6.9 71.6 60.3 49.1 37.8 - -

67 88.8 6.0 84.4 73.3 62.1 50.9 39.6 - 84.3 6.9 81.3 70.5 59.8 48.7 37.6 -

62 87.2 6.0 87.2 80.1 73.0 62.0 51.1 40.1 83.1 6.9 83.1 76.8 70.5 59.6 48.7 37.8

57 85.5 6.0 85.5 85.5 83.9 73.2 62.5 51.8 82.0 6.9 82.0 82.0 81.2 70.5 59.8 49.1

2625

77 108.4 6.2 73.1 57.4 41.7 - - - 100.7 7.1 70.1 54.5 38.9 - - -

72 100.0 6.2 80.7 67.4 54.1 40.8 - - 93.9 7.1 77.4 64.5 51.5 38.6 - -

67 91.6 6.2 88.2 77.4 66.5 53.6 40.7 - 86.9 7.1 84.7 74.4 64.2 51.4 38.6 -

62 90.3 6.1 90.3 84.7 79.0 66.4 53.8 41.3 86.0 7.0 86.0 81.4 76.9 64.2 51.5 38.8

57 89.1 6.1 89.1 89.1 89.1 79.2 67.0 54.7 85.2 7.0 85.2 85.2 85.2 76.9 64.3 51.8

3000

77 107.5 6.3 81.9 62.4 42.9 - - - 99.8 7.2 78.3 58.8 39.4 - - -

72 100.9 6.3 87.0 72.0 56.9 41.9 - - 94.8 7.2 83.1 68.6 54.0 39.4 - -

67 94.3 6.3 92.1 81.5 71.0 56.3 41.7 - 89.5 7.2 88.0 78.3 68.6 54.1 39.5 -

62 93.5 6.3 93.5 89.2 85.0 70.8 56.6 42.4 88.9 7.2 88.9 86.1 83.2 68.7 54.2 39.7

57 92.6 6.3 92.6 92.6 92.6 85.2 71.4 57.7 88.3 7.2 88.3 88.3 88.3 83.3 68.9 54.4

3375

72 101.8 6.4 93.3 76.5 59.8 43.0 - - 95.8 7.4 88.9 72.7 56.5 40.2 - -

67 97.0 6.4 95.9 85.6 75.4 59.1 42.8 - 92.1 7.3 91.4 82.2 73.0 56.7 40.5 -

62 96.6 6.4 96.6 93.8 91.0 75.2 59.3 43.5 91.8 7.3 91.8 90.7 89.6 73.2 56.9 40.6

57 96.1 6.4 96.1 96.1 96.1 91.3 75.9 60.6 91.5 7.3 91.5 91.5 91.5 89.8 73.4 57.0

3750

72 102.7 6.6 99.7 81.1 62.587 44.1 - - 96.7 7.5 94.7 76.8 58.9 41.1 - -

67 99.8 6.6 99.8 89.8 79.8 61.8 43.8 - 94.7 7.5 94.7 86.1 77.4 59.4 41.4 -

62 99.7 6.6 99.7 98.3 97.0 79.5 62.1 44.7 94.7 7.5 94.7 94.7 94.7 77.8 59.7 41.5

57 99.7 6.6 99.7 99.7 99.7 97.3 80.4 63.5 94.6 7.5 94.6 94.6 94.6 94.6 77.9 59.6

Page 59: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 59

115°F 125°F

1875

77 95.0 7.7 52.0 44.3 36.5 - - - 87.3 8.6 50.4 42.8 35.2 - - -

72 85.9 7.7 63.7 54.2 44.8 35.3 - - 79.7 8.5 61.5 52.2 42.9 33.6 - -

67 77.2 7.6 75.3 64.2 53.0 43.9 34.8 - 72.7 8.5 72.7 61.7 50.7 41.8 32.8 -

62 76.5 7.6 76.5 68.9 61.3 52.5 43.7 34.9 72.7 8.5 72.7 65.5 58.4 49.9 41.4 32.8

2250

77 94.0 7.9 59.6 47.9 36.3 - - - 86.3 8.7 57.2 45.7 34.3 - - -

72 86.8 7.8 68.9 57.9 46.9 35.9 - - 80.7 8.7 66.2 55.4 44.7 33.9 - -

67 79.7 7.8 78.2 67.8 57.4 46.5 35.6 - 75.1 8.7 75.1 65.1 55.1 44.3 33.6 -

62 79.1 7.8 79.1 73.5 68.0 57.2 46.4 35.6 75.1 8.7 75.1 70.3 65.5 54.8 44.0 33.3

57 78.5 7.8 78.5 78.5 78.5 67.9 57.2 46.5 75.0 8.7 75.0 75.0 75.0 65.2 54.5 43.8

2625

77 93.0 8.0 67.1 51.6 36.1 - - - 85.2 8.8 64.1 48.7 33.3 - - -

72 87.8 8.0 74.1 61.5 49.0 36.4 - - 81.7 8.9 70.8 58.6 46.4 34.2 - -

67 82.2 7.9 81.1 71.5 61.8 49.2 36.5 - 77.5 8.8 77.5 68.5 59.5 46.9 34.4 -

62 81.7 7.9 81.7 78.2 74.7 61.9 49.1 36.3 77.4 8.8 77.4 75.0 72.6 59.7 46.7 33.8

57 81.3 7.9 81.3 81.3 81.3 74.7 61.7 48.8 77.4 8.8 77.4 77.4 77.4 72.4 59.1 45.8

3000

77 92.0 8.1 74.6 55.2 35.9 - - - 84.2 9.0 71.0 51.7 32.4 - - -

72 88.8 8.1 79.3 65.2 51.1 37.0 - - 82.7 9.0 75.4 61.8 48.1 34.5 - -

67 84.7 8.1 83.9 75.1 66.3 51.8 37.3 - 79.9 9.0 79.9 71.9 63.9 49.5 35.1 -

62 84.4 8.1 84.4 82.9 81.4 66.6 51.8 37.0 79.8 9.0 79.8 79.8 79.7 64.5 49.4 34.3

57 84.0 8.1 84.0 84.0 84.0 81.5 66.3 51.1 79.8 9.0 79.8 79.8 79.8 79.6 63.7 47.8

3375

72 89.7 8.3 84.5 68.8 53.2 37.5 - - 83.7 9.2 80.1 65.0 49.9 34.8 - -

67 87.2 8.3 86.8 78.7 70.7 54.4 38.2 - 82.3 9.2 82.3 75.3 68.3 52.1 35.9 -

62 87.0 8.3 87.0 87.0 87.0 71.3 54.5 37.7 82.2 9.2 82.2 82.2 82.2 69.4 52.1 34.7

57 86.8 8.3 86.8 86.8 86.8 86.8 70.8 53.4 82.2 9.2 82.2 82.2 82.2 82.2 68.3 49.8

3750

72 90.7 8.4 89.7 72.5 55.3 38.1 - - 84.7 9.4 84.7 68.1 51.6 35.1 - -

67 89.7 8.4 89.7 82.4 75.1 57.1 39.0 - 84.7 9.4 84.7 78.7 72.7 54.7 36.6 -

62 89.6 8.4 89.6 89.6 89.6 76.1 57.2 38.4 84.6 9.4 84.6 84.6 84.6 74.3 54.8 35.2

57 89.6 8.4 89.6 89.6 89.6 89.6 75.4 55.7 84.5 9.4 84.5 84.5 84.5 84.5 72.9 51.8

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZJ090 (7.5 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 60: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

60 Johnson Controls Ducted Systems

ZJ102 (8.5 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

2125

77 134.2 5.5 62.8 53.2 43.5 - - - 124.2 6.3 59.9 50.8 41.7 - - -

72 120.4 5.5 78.0 66.5 54.9 43.4 - - 112.4 6.2 74.8 63.6 52.3 41.1 - -

67 106.7 5.4 93.2 79.8 66.3 55.6 44.5 - 100.6 6.1 89.8 76.4 63.0 52.1 41.2 -

62 102.7 5.4 54.6 54.6 54.6 38.0 54.6 47.0 98.1 6.0 91.5 82.6 73.7 61.1 52.5 41.9

2550

77 135.5 5.5 72.3 59.3 46.3 - - - 125.0 6.2 69.7 56.3 42.9 - - -

72 123.2 5.5 85.8 72.5 59.2 45.9 - - 114.9 6.2 82.6 69.2 55.7 42.3 - -

67 110.9 5.4 99.2 85.6 72.1 58.9 45.4 - 104.9 6.1 95.4 82.0 68.6 55.2 41.7 -

62 107.5 5.4 99.2 92.1 85.0 41.0 58.2 44.9 102.7 6.0 96.6 89.0 81.4 66.4 54.5 41.0

57 104.0 5.4 99.2 98.5 97.9 84.5 71.1 57.7 100.5 6.0 97.8 96.0 94.2 80.7 67.2 53.7

2975

77 136.8 5.5 81.8 65.4 49.1 - - - 125.8 6.2 79.6 61.9 44.2 - - -

72 126.0 5.5 93.5 78.5 63.4 48.4 - - 117.5 6.2 90.3 74.7 59.2 43.6 - -

67 115.2 5.4 105.2 91.5 77.8 62.2 46.3 - 109.1 6.1 101.0 87.6 74.2 58.2 42.2 -

62 112.2 5.4 105.1 98.6 92.2 73.4 59.3 42.8 107.2 6.1 101.7 95.4 89.2 71.6 56.4 40.0

57 109.2 5.4 105.0 105.0 105.0 89.4 72.2 55.0 105.3 6.1 102.5 102.5 102.5 87.4 70.6 53.8

3400

77 138.0 5.5 91.3 71.6 51.9 - - - 126.6 6.2 89.4 67.4 45.4 - - -

72 128.8 5.5 101.3 84.5 67.7 50.9 - - 120.0 6.2 98.0 80.3 62.6 44.9 - -

67 119.5 5.4 111.2 97.4 83.6 65.4 47.2 - 113.4 6.1 106.6 93.2 79.7 61.3 42.8 -

62 117.0 5.4 111.0 105.2 99.4 78.3 60.3 40.7 111.7 6.1 106.8 101.9 96.9 76.9 58.4 39.1

57 114.5 5.4 110.8 110.8 110.8 94.3 73.3 52.3 110.0 6.1 107.1 107.1 107.1 94.0 74.0 53.9

3825

72 131.6 5.5 109.0 90.5 72.0 53.4 - - 122.5 6.2 105.7 85.9 66.0 46.1 - -

67 123.8 5.5 117.2 103.3 89.3 68.7 48.1 - 117.6 6.1 112.1 98.7 85.3 64.3 43.3 -

62 121.8 5.5 116.9 111.8 106.6 83.2 61.3 38.6 116.2 6.1 111.9 108.3 104.7 82.1 60.3 38.1

57 119.7 5.5 116.6 116.6 116.6 99.2 74.4 49.7 114.8 6.1 111.7 111.7 111.7 100.7 77.3 54.0

4250

72 134.4 5.5 116.8 96.5 76.2 56.0 - - 125.0 6.1 113.4 91.4 69.4 47.4 - -

67 128.1 5.5 123.2 109.1 95.0 72.0 49.0 - 121.9 6.1 117.7 104.3 90.9 67.4 43.8 -

62 126.5 5.5 69.7 69.7 69.7 69.7 62.3 36.5 120.8 6.1 117.0 114.7 112.4 87.3 62.3 37.2

57 124.9 5.5 69.9 69.9 69.9 69.9 69.9 47.0 119.6 6.1 68.4 68.4 68.4 68.4 68.4 54.1

95°F 105°F

2125

77 114.3 7.0 57.0 48.4 39.8 - - - 104.2 7.9 54.9 46.0 37.1 - - -

72 104.4 6.8 71.7 60.7 49.7 38.8 - - 97.1 7.8 69.2 57.9 46.6 35.3 - -

67 94.6 6.7 86.4 73.0 59.7 48.7 37.8 - 90.1 7.7 83.5 69.8 56.1 45.1 34.2 -

62 93.6 6.7 89.8 79.7 69.6 58.7 47.8 36.9 88.3 7.6 84.8 75.2 65.6 55.0 44.4 33.8

2550

77 114.6 6.9 67.2 53.3 39.5 - - - 106.0 7.9 64.9 50.5 36.0 - - -

72 106.7 6.8 79.4 65.8 52.3 38.8 - - 99.5 7.8 75.9 62.3 48.8 35.2 - -

67 98.8 6.7 91.6 78.3 65.1 51.5 38.0 - 92.9 7.7 86.9 74.2 61.6 48.0 34.4 -

62 97.9 6.7 94.0 85.9 77.8 64.3 50.7 37.1 92.1 7.7 88.5 81.4 74.4 60.7 47.1 33.5

57 96.9 6.7 96.5 93.6 90.6 77.0 63.4 49.8 91.4 7.6 90.2 88.7 87.1 73.5 59.8 46.2

2975

77 114.8 6.9 77.4 58.3 39.3 - - - 107.9 7.8 74.9 54.9 34.9 - - -

72 108.9 6.8 87.0 71.0 54.9 38.8 - - 101.8 7.8 82.6 66.8 51.0 35.2 - -

67 103.0 6.7 96.7 83.6 70.5 54.3 38.2 - 95.7 7.7 90.3 78.7 67.1 50.8 34.6 -

62 102.1 6.7 98.3 92.2 86.1 69.9 53.6 37.3 96.0 7.7 92.3 87.7 83.1 66.5 49.8 33.2

57 101.3 6.7 99.9 99.9 99.9 85.4 69.0 52.6 96.2 7.7 94.2 94.2 94.2 82.1 65.1 48.0

3400

77 115.1 6.9 87.5 63.3 39.0 - - - 109.8 7.8 84.9 59.4 33.9 - - -

72 111.2 6.8 94.7 76.1 57.5 38.8 - - 104.2 7.8 89.4 71.3 53.2 35.1 - -

67 107.2 6.8 101.9 88.9 75.9 57.1 38.3 - 98.5 7.7 93.8 83.2 72.6 53.7 34.8 -

62 106.4 6.7 102.6 98.5 94.4 75.4 56.5 37.5 99.8 7.7 96.0 93.9 91.9 72.2 52.6 32.9

57 105.6 6.7 103.3 103.3 103.3 93.8 74.6 55.5 101.1 7.7 98.2 98.2 98.2 90.8 70.3 49.9

3825

72 113.4 6.8 102.4 81.2 60.0 38.9 - - 106.5 7.7 96.1 75.8 55.4 35.1 - -

67 111.5 6.8 107.1 94.2 81.4 59.9 38.5 - 101.3 7.7 97.2 87.6 78.1 56.5 35.0 -

62 110.7 6.8 106.9 104.8 102.7 81.0 59.4 37.7 103.7 7.7 99.7 99.7 99.7 78.0 55.3 32.6

57 110.0 6.8 106.8 106.8 106.8 102.1 80.2 58.3 106.0 7.7 102.2 102.2 102.2 99.4 75.6 51.7

4250

72 115.6 6.8 110.1 86.3 62.614 38.9 - - 108.8 7.7 102.8 80.2 57.6 35.1 - -

67 115.7 6.8 112.2 99.5 86.8 62.7 38.7 - 104.2 7.7 100.7 92.1 83.5 59.4 35.3 -

62 115.0 6.8 111.2 111.1 111.0 86.6 62.3 37.9 107.5 7.7 103.5 103.5 103.5 83.8 58.1 32.4

57 114.3 6.8 110.2 110.2 110.2 110.2 85.8 61.2 110.9 7.8 106.3 106.3 106.3 106.3 80.8 53.6

Page 61: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 61

115°F 125°F

2125

77 94.1 8.9 52.8 43.6 34.3 - - - 83.9 9.8 50.8 41.2 31.6 - - -

72 89.8 8.7 66.7 55.0 43.4 31.8 - - 82.5 9.7 64.2 52.2 40.3 28.3 - -

67 85.6 8.6 80.5 66.5 52.5 41.5 30.6 - 81.1 9.5 44.0 44.0 44.0 37.9 27.0 -

62 83.0 8.6 79.8 70.7 61.6 51.3 40.9 30.6 77.7 9.5 74.9 66.2 57.6 47.6 37.5 27.5

2550

77 97.5 8.8 62.7 47.6 32.5 - - - 89.0 9.8 60.4 44.7 29.0 - - -

72 92.3 8.7 72.4 58.9 45.3 31.7 - - 85.1 9.7 69.0 55.4 41.8 28.1 - -

67 87.0 8.6 82.2 70.1 58.1 44.4 30.8 - 81.1 9.5 46.2 46.2 46.2 40.9 27.2 -

62 86.4 8.6 83.0 76.9 70.9 57.2 43.5 29.9 80.6 9.6 77.5 72.4 67.4 53.7 39.9 26.2

57 85.8 8.6 83.8 83.7 83.7 69.9 56.2 42.5 80.2 9.6 46.4 46.4 46.4 46.4 46.4 38.9

2975

77 101.0 8.8 72.5 51.6 30.6 - - - 94.1 9.8 70.1 48.2 26.3 - - -

72 94.7 8.7 78.2 62.7 47.1 31.6 - - 87.6 9.7 73.8 58.5 43.2 28.0 - -

67 88.4 8.6 83.9 73.8 63.6 47.3 31.1 - 81.1 9.5 48.2 48.2 48.2 43.9 27.5 -

62 89.8 8.6 86.2 83.2 80.1 63.1 46.1 29.1 83.6 9.6 80.1 78.6 77.1 59.7 42.4 25.0

57 91.2 8.6 88.4 88.4 88.4 78.9 61.1 43.4 86.2 9.6 48.4 48.4 48.4 48.4 48.4 38.8

3400

77 104.5 8.8 82.3 55.6 28.8 - - - 99.2 9.7 79.7 51.7 23.6 - - -

72 97.1 8.7 84.0 66.5 49.0 31.5 - - 90.1 9.6 78.6 61.7 44.7 27.8 - -

67 89.8 8.6 85.6 77.4 69.2 50.2 31.3 - 81.1 9.5 50.2 50.2 50.2 46.8 27.8 -

62 93.2 8.7 89.4 89.4 89.4 69.0 48.7 28.3 86.6 9.6 82.7 82.7 82.7 65.8 44.8 23.7

57 96.6 8.7 93.1 93.1 93.1 87.8 66.1 44.3 92.1 9.7 50.4 50.4 50.4 50.4 50.4 38.7

3825

72 99.6 8.7 89.8 70.3 50.8 31.3 - - 92.7 9.6 83.5 64.8 46.2 27.6 - -

67 91.2 8.6 87.4 81.1 74.7 53.2 31.6 - 81.1 9.5 52.3 52.3 52.3 49.8 28.1 -

62 96.6 8.7 92.5 92.5 92.5 75.0 51.3 27.6 89.6 9.6 85.3 85.3 85.3 71.9 47.2 22.5

57 102.1 8.7 97.7 97.7 97.7 96.8 71.0 45.1 98.1 9.7 52.5 52.5 52.5 52.5 52.5 38.6

4250

72 102.0 8.7 95.5 74.1 52.7 31.2 - - 95.2 9.6 88.3 68.0 47.7 27.4 - -

67 92.6 8.6 89.1 84.7 80.3 56.1 31.8 - 81.1 9.5 77.5 77.3 77.1 52.7 28.4 -

62 100.1 8.7 95.7 95.7 95.7 80.9 53.8 26.8 92.6 9.7 88.0 88.0 88.0 78.0 49.6 21.2

57 107.5 8.8 102.3 102.3 102.3 102.3 75.9 46.0 104.1 9.8 98.4 98.4 98.4 98.4 70.9 38.4

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZJ102 (8.5 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 62: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

62 Johnson Controls Ducted Systems

ZJ120 (10 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

2500

77 159.5 7.3 63.5 52.6 41.7 - - - 148.2 8.2 61.1 50.3 39.4 - - -

72 145.9 7.2 83.1 72.2 61.3 50.4 - - 136.1 8.1 80.2 69.3 58.4 47.6 - -

67 132.2 7.1 102.7 91.8 80.9 70.0 59.1 - 124.0 8.0 99.3 88.4 77.5 66.6 55.8 -

62 123.1 7.0 123.1 118.4 99.0 88.1 77.2 66.3 114.8 7.9 114.8 112.5 95.6 84.8 73.9 63.0

3000

77 164.8 7.4 71.2 58.4 45.5 - - - 153.7 8.2 68.6 55.9 43.1 - - -

72 150.7 7.2 92.6 79.8 67.0 54.2 - - 141.1 8.1 89.5 76.7 64.0 51.3 - -

67 136.6 7.1 114.0 101.2 88.4 75.6 62.8 - 128.6 8.0 110.4 97.6 84.9 72.2 59.5 -

62 127.2 7.0 127.2 124.1 108.2 95.4 82.6 69.8 119.0 7.9 119.0 117.5 104.8 92.1 79.3 66.6

57 125.9 7.0 125.9 125.9 113.4 100.6 87.8 75.0 118.5 7.9 118.5 118.5 107.1 94.4 81.7 69.0

3500

77 170.1 7.4 78.9 64.2 49.4 - - - 159.1 8.2 76.0 61.5 46.9 - - -

72 155.5 7.3 102.1 87.4 72.7 57.9 - - 146.1 8.1 98.7 84.2 69.6 55.0 - -

67 140.9 7.1 125.4 110.6 95.9 81.2 66.5 - 133.1 8.1 121.5 106.9 92.3 77.7 63.2 -

62 131.2 7.1 131.2 129.7 117.5 102.7 88.0 73.3 123.3 8.0 123.3 122.5 113.9 99.3 84.8 70.2

57 129.9 7.0 129.9 129.9 123.1 108.3 93.6 78.9 122.7 7.9 122.7 122.7 116.5 101.9 87.3 72.8

4000

77 175.4 7.4 86.6 70.0 53.3 - - - 164.5 8.3 83.5 67.1 50.7 - - -

72 160.3 7.3 111.7 95.0 78.4 61.7 - - 151.1 8.2 108.0 91.6 75.2 58.8 - -

67 145.3 7.2 136.7 120.1 103.4 86.8 70.1 - 137.6 8.1 132.5 116.1 99.7 83.3 66.9 -

62 135.3 7.1 135.3 135.3 126.7 110.0 93.4 76.7 127.5 8.0 127.5 127.5 123.0 106.6 90.2 73.8

57 133.9 7.1 133.9 133.9 132.7 116.1 99.4 82.8 126.9 8.0 126.9 126.9 125.8 109.4 93.0 76.6

4500

72 164.1 7.4 118.0 100.1 82.2 64.4 - - 154.0 8.2 115.6 97.7 79.8 61.9 - -

67 148.7 7.2 144.4 126.4 108.5 90.7 72.8 - 140.3 8.1 137.7 123.7 105.8 87.9 70.1 -

62 138.4 7.1 138.4 138.4 134.1 116.3 98.4 80.5 129.9 8.0 129.9 129.9 127.7 109.8 91.9 74.0

57 137.0 7.1 137.0 137.0 136.4 118.6 100.7 82.8 129.3 8.0 129.3 129.3 128.8 110.9 93.0 75.1

5000

72 167.8 7.4 124.3 105.2 86.1 67.0 - - 156.8 8.2 123.1 103.7 84.4 65.0 - -

67 152.0 7.3 152.0 132.7 113.6 94.5 75.5 - 142.9 8.1 142.9 131.3 111.9 92.6 73.2 -

62 141.6 7.2 141.6 141.6 141.6 122.5 103.4 84.3 132.3 8.0 132.3 132.3 132.3 112.9 93.6 74.2

57 140.1 7.2 140.1 140.1 140.1 121.0 101.9 82.9 131.7 8.0 131.7 131.7 131.7 112.4 93.0 73.7

95°F 105°F

2500

77 136.9 9.0 58.8 47.9 37.1 - - - 125.0 10.0 52.9 44.3 33.5 - - -

72 126.4 8.9 77.3 66.5 55.6 44.8 - - 115.5 10.0 73.3 62.5 51.7 40.9 - -

67 115.8 8.9 95.9 85.0 74.1 63.3 52.4 - 105.9 10.0 93.6 80.7 69.9 59.1 48.3 -

62 106.6 8.8 106.6 106.6 92.2 81.4 70.5 59.7 98.2 9.9 98.2 98.2 86.0 75.2 64.5 53.7

3000

77 142.5 9.0 66.0 53.4 40.7 - - - 131.1 10.1 62.3 49.7 37.2 - - -

72 131.5 9.0 86.3 73.7 61.1 48.5 - - 121.1 10.0 82.5 69.9 57.3 44.7 - -

67 120.5 8.9 106.7 94.1 81.4 68.8 56.2 - 111.1 10.0 102.6 90.0 77.5 64.9 52.3 -

62 110.9 8.8 110.9 110.9 101.3 88.7 76.0 63.4 102.9 9.9 102.9 102.9 95.3 82.7 70.2 57.6

57 111.2 8.8 111.2 111.2 100.9 88.2 75.6 63.0 103.1 9.9 103.1 103.1 93.2 80.6 68.0 55.5

3500

77 148.1 9.1 73.2 58.8 44.4 - - - 137.1 10.1 71.7 55.1 40.8 - - -

72 136.7 9.0 95.4 80.9 66.5 52.1 - - 126.7 10.1 91.6 77.3 62.9 48.5 - -

67 125.3 9.0 117.5 103.1 88.7 74.3 59.9 - 116.2 10.1 111.6 99.4 85.0 70.7 56.3 -

62 115.3 8.9 115.3 115.3 110.4 96.0 81.6 67.2 107.7 10.0 107.7 107.7 104.6 90.3 75.9 61.5

57 115.6 8.9 115.6 115.6 109.9 95.5 81.1 66.7 107.9 9.9 107.9 107.9 102.3 87.9 73.5 59.2

4000

77 153.7 9.1 80.4 64.2 48.0 - - - 143.2 10.2 81.1 60.5 44.4 - - -

72 141.9 9.0 104.4 88.2 72.0 55.8 - - 132.3 10.2 100.8 84.7 68.5 52.3 - -

67 130.0 9.0 128.3 112.2 96.0 79.8 63.7 - 121.4 10.1 120.5 108.8 92.6 76.4 60.3 -

62 119.6 8.9 119.6 119.6 119.4 103.3 87.1 70.9 112.5 10.0 112.5 112.5 113.9 97.8 81.6 65.4

57 120.0 8.9 120.0 120.0 118.9 102.7 86.6 70.4 112.6 10.0 112.6 112.6 111.3 95.2 79.0 62.8

4500

72 143.9 9.1 113.1 95.2 77.3 59.4 - - 133.6 10.1 109.0 91.2 73.5 55.7 - -

67 131.8 9.0 131.0 121.0 103.1 85.2 67.3 - 122.6 10.1 122.2 115.3 99.4 81.6 63.8 -

62 121.3 8.9 121.3 121.3 121.2 103.3 85.4 67.5 113.6 10.0 113.6 113.6 114.3 96.6 78.8 61.1

57 121.7 8.9 121.7 121.7 121.1 103.2 85.3 67.5 113.8 10.0 113.8 113.8 113.1 95.4 77.6 59.8

5000

72 145.9 9.1 121.9 102.3 82.7 63.1 - - 134.9 10.1 117.2 97.8 78.5 59.1 - -

67 133.7 9.0 133.7 129.8 110.2 90.6 71.0 - 123.8 10.1 123.8 121.9 106.1 86.8 67.4 -

62 123.0 8.9 123.0 123.0 123.0 103.4 83.8 64.2 114.7 10.0 114.7 114.7 114.7 95.4 76.1 56.7

57 123.4 8.9 123.4 123.4 123.4 103.7 84.1 64.5 114.9 10.0 114.9 114.9 114.9 95.5 76.2 56.8

Page 63: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 63

115°F 125°F

2500

77 113.0 11.0 47.0 40.7 30.0 - - - 101.1 12.1 44.1 37.0 26.4 - - -

72 104.5 11.0 69.2 58.5 47.8 37.1 - - 93.6 12.1 65.1 54.5 43.9 33.3 - -

67 96.0 11.0 91.4 76.3 65.6 55.0 44.3 - 86.1 12.1 86.1 72.0 61.4 50.8 40.2 -

62 89.7 11.0 89.7 89.7 79.8 69.1 58.4 47.7 81.3 12.1 81.3 81.3 74.1 63.0 52.3 41.7

3000

77 119.6 11.1 58.6 46.1 33.6 - - - 108.1 12.1 57.2 42.5 30.0 - - -

72 110.6 11.1 78.6 66.1 53.5 41.0 - - 100.1 12.2 74.7 62.2 49.8 37.3 - -

67 101.6 11.1 98.5 86.0 73.5 61.0 48.5 - 92.1 12.2 92.1 82.0 69.5 57.1 44.6 -

62 94.9 11.0 94.9 94.9 89.3 76.8 64.3 51.8 87.0 12.2 87.0 87.0 83.3 70.9 58.4 46.0

57 94.9 11.0 94.9 94.9 85.5 73.0 60.5 47.9 86.7 12.0 86.7 86.7 77.8 65.3 52.9 40.4

3500

77 126.1 11.2 70.2 51.5 37.2 - - - 115.1 12.2 70.3 47.9 33.6 - - -

72 116.6 11.2 87.9 73.6 59.3 44.9 - - 106.6 12.3 84.2 69.9 55.6 41.3 - -

67 107.2 11.2 105.6 95.7 81.4 67.0 52.7 - 98.1 12.3 98.1 92.0 77.7 63.4 49.1 -

62 100.1 11.1 100.1 100.1 98.9 84.6 70.2 55.9 92.6 12.3 92.6 92.6 92.6 78.8 64.6 50.3

57 100.1 11.0 100.1 100.1 94.6 80.3 66.0 51.6 92.3 12.1 92.3 92.3 87.0 72.7 58.4 44.1

4000

77 132.7 11.3 81.8 56.9 40.8 - - - 122.2 12.3 83.4 53.3 37.1 - - -

72 122.7 11.3 97.3 81.1 65.0 48.8 - - 113.1 12.4 93.7 77.6 61.5 45.3 - -

67 112.7 11.3 112.7 105.4 89.2 73.1 56.9 - 104.1 12.4 104.1 102.0 85.8 69.7 53.6 -

62 105.3 11.2 105.3 105.3 108.4 92.3 76.1 60.0 98.2 12.4 98.2 98.2 98.2 86.8 70.7 54.5

57 105.3 11.1 105.3 105.3 103.7 87.6 71.5 55.3 98.0 12.2 98.0 98.0 96.2 80.0 63.9 47.8

4500

72 123.4 11.2 104.9 87.3 69.6 52.0 - - 113.1 12.3 100.8 83.3 65.8 48.3 - -

67 113.3 11.2 113.3 109.7 95.6 78.0 60.4 - 104.1 12.3 104.1 104.0 91.9 74.4 56.9 -

62 105.9 11.2 105.9 105.9 107.5 89.8 72.2 54.6 98.2 12.3 98.2 98.2 98.2 83.1 65.6 48.1

57 105.9 11.1 105.9 105.9 105.1 87.5 69.9 52.2 98.0 12.2 98.0 98.0 97.1 79.6 62.1 44.6

5000

72 124.0 11.2 112.5 93.4 74.3 55.2 - - 113.1 12.3 107.8 89.0 70.1 51.3 - -

67 113.9 11.2 113.9 113.9 102.0 82.9 63.8 - 104.1 12.3 104.1 104.1 97.9 79.1 60.3 -

62 106.5 11.2 106.5 106.5 106.5 87.4 68.3 49.2 98.2 12.3 98.2 98.2 98.2 79.4 60.6 41.7

57 106.4 11.1 106.4 106.4 106.4 87.3 68.3 49.2 98.0 12.1 98.0 98.0 98.0 79.1 60.3 41.5

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZJ120 (10 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 64: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

64 Johnson Controls Ducted Systems

ZJ150 (12.5 Ton)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

3125

77 191.5 9.8 80.3 66.9 53.5 - - - 184.5 10.7 76.0 62.6 49.3 - - -

72 178.7 9.5 103.3 89.9 76.4 63.0 - - 171.3 10.5 99.0 85.7 72.3 59.0 - -

67 165.9 9.2 126.3 112.8 99.4 86.0 72.6 - 158.1 10.2 122.1 108.8 95.4 82.1 68.7 -

62 149.9 9.1 149.9 139.5 122.9 109.5 96.1 82.7 143.1 10.1 143.1 135.8 117.5 104.2 90.8 77.5

3750

77 201.3 9.8 89.4 74.2 58.9 - - - 193.5 10.7 85.1 69.8 54.5 - - -

72 187.9 9.5 114.7 99.5 84.2 69.0 - - 179.6 10.5 110.6 95.3 80.0 64.6 - -

67 174.5 9.3 140.0 124.8 109.5 94.3 79.1 - 165.8 10.3 136.1 120.8 105.5 90.1 74.8 -

62 157.6 9.1 157.6 150.7 135.4 120.2 105.0 89.7 150.1 10.1 150.1 145.2 129.9 114.6 99.3 83.9

57 152.3 9.1 152.3 152.3 140.7 125.5 110.2 95.0 145.8 10.1 145.8 145.8 134.0 118.7 103.3 88.0

4375

77 211.1 9.8 98.5 81.5 64.4 - - - 202.4 10.8 94.2 76.9 59.6 - - -

72 197.0 9.6 126.2 109.1 92.0 75.0 - - 187.9 10.6 122.1 104.9 87.6 70.3 - -

67 183.0 9.3 153.8 136.7 119.7 102.6 85.5 - 173.5 10.3 150.1 132.8 115.5 98.2 80.9 -

62 165.3 9.1 165.3 161.8 148.0 130.9 113.8 96.8 157.0 10.1 157.0 154.6 142.3 125.0 107.7 90.4

57 159.7 9.1 159.7 159.7 153.7 136.6 119.6 102.5 152.6 10.2 152.6 152.6 146.7 129.4 112.2 94.9

5000

77 221.0 9.9 107.6 88.8 69.9 - - - 211.4 10.9 103.3 84.1 64.8 - - -

72 206.2 9.6 137.6 118.7 99.8 80.9 - - 196.3 10.6 133.7 114.4 95.2 75.9 - -

67 191.5 9.3 167.5 148.7 129.8 110.9 92.0 - 181.2 10.4 164.1 144.8 125.5 106.3 87.0 -

62 173.0 9.1 173.0 173.0 160.5 141.6 122.7 103.8 164.0 10.2 164.0 164.0 154.6 135.4 116.1 96.9

57 167.2 9.1 167.2 167.2 166.7 147.8 129.0 110.1 159.3 10.2 159.3 159.3 159.5 140.2 121.0 101.7

5625

72 215.4 9.6 150.0 129.1 108.3 87.5 - - 204.6 10.7 146.0 124.7 103.5 82.2 - -

67 200.0 9.3 185.5 161.6 140.8 119.9 99.1 - 188.8 10.4 179.0 157.7 136.5 115.2 93.9 -

62 180.7 9.2 180.7 180.7 174.4 153.6 132.8 111.9 170.9 10.2 170.9 170.9 166.3 145.0 123.7 102.4

57 174.6 9.1 174.6 174.6 174.4 153.5 132.7 111.9 166.1 10.3 166.1 166.1 166.2 144.9 123.6 102.3

6250

72 224.6 9.6 162.3 139.5 116.7 94.0 - - 212.9 10.7 158.4 135.1 111.7 88.4 - -

67 208.5 9.3 203.5 174.5 151.8 129.0 106.2 - 196.5 10.5 194.0 170.7 147.4 124.1 100.8 -

62 188.4 9.2 188.4 188.4 188.4 165.6 142.8 120.0 177.9 10.3 177.9 177.9 177.9 154.6 131.3 108.0

57 182.0 9.2 182.0 182.0 182.0 159.2 136.5 113.7 172.8 10.3 172.8 172.8 172.8 149.5 126.2 102.9

95°F 105°F

3125

77 177.5 11.6 71.6 58.3 45.1 - - - 168.0 12.8 67.5 55.1 42.0 - - -

72 163.9 11.4 94.8 81.5 68.2 55.0 - - 154.2 12.7 90.8 77.7 64.5 51.4 - -

67 150.3 11.2 118.0 104.7 91.4 78.1 64.9 - 140.3 12.6 114.2 100.2 87.1 73.9 60.8 -

62 136.4 11.0 136.4 132.1 112.1 98.9 85.6 72.3 128.6 12.4 128.6 126.4 106.8 93.6 80.5 67.3

3750

77 185.6 11.7 80.8 65.4 50.0 - - - 175.2 12.9 77.1 61.9 46.7 - - -

72 171.4 11.5 106.5 91.1 75.7 60.3 - - 160.8 12.8 102.2 86.9 71.7 56.5 - -

67 157.2 11.3 132.2 116.8 101.4 86.0 70.6 - 146.4 12.7 127.2 112.0 96.8 81.6 66.4 -

62 142.6 11.1 142.6 139.7 124.3 109.0 93.6 78.2 134.1 12.5 134.1 132.7 118.7 103.5 88.2 73.0

57 139.4 11.1 139.4 139.4 127.2 111.8 96.5 81.1 131.5 12.5 131.5 131.5 118.9 103.7 88.5 73.3

4375

77 193.7 11.8 89.9 72.4 54.9 - - - 182.4 13.0 86.7 68.6 51.3 - - -

72 178.9 11.6 118.1 100.6 83.1 65.6 - - 167.4 12.9 113.5 96.2 78.9 61.6 - -

67 164.0 11.4 146.4 128.8 111.3 93.8 76.3 - 152.4 12.8 140.3 123.8 106.5 89.2 71.9 -

62 148.8 11.2 148.8 147.4 136.6 119.1 101.5 84.0 139.6 12.6 139.6 138.9 130.6 113.3 96.0 78.7

57 145.4 11.2 145.4 145.4 139.7 122.2 104.7 87.2 136.9 12.6 136.9 136.9 130.9 113.6 96.3 79.0

5000

77 201.8 11.9 99.1 79.4 59.8 - - - 189.6 13.1 96.3 75.4 56.0 - - -

72 186.3 11.7 129.8 110.2 90.5 70.9 - - 174.0 13.0 124.8 105.5 86.1 66.8 - -

67 170.8 11.5 160.6 140.9 121.3 101.7 82.0 - 158.5 12.9 153.3 135.6 116.2 96.9 77.5 -

62 155.0 11.3 155.0 155.0 148.8 129.2 109.5 89.9 145.1 12.7 145.1 145.1 142.5 123.2 103.8 84.5

57 151.5 11.3 151.5 151.5 152.2 132.6 113.0 93.4 142.3 12.7 142.3 142.3 142.8 123.4 104.1 84.7

5625

72 193.8 11.8 142.1 120.4 98.6 76.9 - - 180.7 13.1 136.9 115.4 94.0 72.5 - -

67 177.7 11.6 172.5 153.9 132.1 110.4 88.7 - 164.5 13.0 161.9 148.3 126.8 105.3 83.9 -

62 161.2 11.3 161.2 161.2 158.1 136.4 114.6 92.9 150.7 12.8 150.7 150.7 149.3 127.9 106.4 84.9

57 157.6 11.4 157.6 157.6 157.9 136.2 114.5 92.7 147.8 12.8 147.8 147.8 148.0 126.5 105.0 83.6

6250

72 201.2 11.9 154.4 130.6 106.7 82.9 - - 187.3 13.2 149.0 125.4 101.8 78.2 - -

67 184.5 11.7 184.5 166.8 143.0 119.2 95.3 - 170.5 13.1 170.5 161.0 137.4 113.8 90.2 -

62 167.4 11.4 167.4 167.4 167.4 143.6 119.7 95.9 156.2 12.9 156.2 156.2 156.2 132.6 109.0 85.4

57 163.6 11.5 163.6 163.6 163.6 139.8 116.0 92.1 153.2 12.9 153.2 153.2 153.2 129.6 106.0 82.4

Page 65: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 65

115°F 125°F

3125

77 158.4 14.0 63.3 51.9 38.9 - - - 148.8 15.3 56.6 48.7 35.8 - - -

72 144.4 14.0 86.9 73.8 60.8 47.8 - - 134.6 15.3 82.9 70.0 57.1 44.2 - -

67 130.4 14.0 110.4 95.8 82.7 69.7 56.7 - 120.4 15.4 106.6 91.3 78.4 65.5 52.6 -

62 120.7 13.8 120.7 120.7 101.4 88.4 75.3 62.3 112.9 15.2 112.9 112.9 96.0 83.1 70.2 57.3

3750

77 164.8 14.1 73.4 58.4 43.3 - - - 154.3 15.4 69.8 54.9 40.0 - - -

72 150.2 14.1 97.9 82.8 67.8 52.7 - - 139.6 15.4 93.6 78.7 63.8 48.9 - -

67 135.6 14.1 122.3 107.3 92.2 77.2 62.1 - 124.8 15.5 117.4 102.5 87.6 72.7 57.9 -

62 125.6 13.9 125.6 125.6 113.0 98.0 82.9 67.9 117.1 15.3 117.1 117.1 107.3 92.5 77.6 62.7

57 123.7 13.9 123.7 123.7 110.6 95.6 80.5 65.5 115.8 15.3 115.8 115.8 102.3 87.4 72.5 57.7

4375

77 171.1 14.2 83.5 64.8 47.8 - - - 159.8 15.5 82.9 61.1 44.2 - - -

72 156.0 14.2 108.8 91.8 74.7 57.7 - - 144.5 15.5 104.2 87.4 70.5 53.7 - -

67 140.8 14.2 134.2 118.7 101.7 84.6 67.6 - 129.2 15.6 128.1 113.7 96.9 80.0 63.2 -

62 130.4 14.0 130.4 130.4 124.6 107.6 90.5 73.4 121.2 15.4 121.2 121.2 118.6 101.8 85.0 68.1

57 128.4 14.0 128.4 128.4 122.0 104.9 87.9 70.8 119.9 15.5 119.9 119.9 113.1 96.3 79.4 62.6

5000

77 177.5 14.4 93.6 71.3 52.2 - - - 165.3 15.6 96.0 67.2 48.5 - - -

72 161.8 14.3 119.8 100.8 81.7 62.6 - - 149.5 15.7 114.8 96.1 77.3 58.5 - -

67 146.1 14.3 146.1 130.2 111.2 92.1 73.0 - 133.7 15.7 133.7 124.9 106.1 87.3 68.5 -

62 135.3 14.1 135.3 135.3 136.2 117.2 98.1 79.0 125.4 15.5 125.4 125.4 125.4 111.1 92.4 73.6

57 133.2 14.1 133.2 133.2 133.3 114.3 95.2 76.1 124.1 15.6 124.1 124.1 123.9 105.1 86.3 67.5

5625

72 167.6 14.4 131.7 110.5 89.3 68.1 - - 154.5 15.8 126.5 105.6 84.6 63.6 - -

67 151.3 14.4 151.3 142.7 121.5 100.3 79.0 - 138.1 15.8 138.1 137.1 116.1 95.2 74.2 -

62 140.1 14.2 140.1 140.1 140.6 119.4 98.1 76.9 129.6 15.6 129.6 129.6 129.6 110.9 89.9 68.9

57 138.0 14.2 138.0 138.0 138.0 116.8 95.6 74.4 128.2 15.7 128.2 128.2 128.1 107.1 86.1 65.2

6250

72 173.4 14.5 143.6 120.2 96.9 73.5 - - 159.4 15.9 138.2 115.1 91.9 68.8 - -

67 156.5 14.5 156.5 155.2 131.8 108.4 85.0 - 142.5 15.9 142.5 142.5 126.2 103.0 79.9 -

62 145.0 14.3 145.0 145.0 145.0 121.6 98.2 74.8 133.7 15.7 133.7 133.7 133.7 110.6 87.4 64.3

57 142.7 14.3 142.7 142.7 142.7 119.4 96.0 72.6 132.3 15.8 132.3 132.3 132.3 109.1 86.0 62.8

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZJ150 (12.5 Ton) (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 66: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

66 Johnson Controls Ducted Systems

ZR037-150 Cooling and Reheat Capacities

ZR037 (3.0 Ton) Cooling

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

750

77 45.1 2.0 23.9 20.6 17.3 - - - 43.0 2.2 22.3 19.3 16.3 - - -

72 41.0 1.9 28.7 24.9 21.1 17.3 - - 38.8 2.2 27.6 23.8 20.0 16.3 - -

67 36.8 1.9 33.5 29.2 24.9 20.9 17.2 - 34.7 2.1 32.8 28.3 23.8 19.9 16.2 -

62 35.4 1.9 33.5 31.1 28.8 23.2 20.8 16.8 33.9 2.1 32.9 30.3 27.6 23.0 20.0 16.1

900

77 45.3 2.0 27.1 22.4 17.7 - - - 43.0 2.2 25.8 21.2 16.6 - - -

72 41.8 1.9 31.3 26.8 22.262 17.7 - - 39.6 2.2 30.2 25.7 21.2 16.7 - -

67 38.3 1.9 35.6 31.2 26.9 22.1 17.7 - 36.2 2.2 34.6 30.2 25.8 21.2 16.7 -

62 37.2 1.9 35.6 33.5 31.5 25.5 22.1 17.5 35.5 2.2 34.7 32.6 30.4 25.2 21.3 16.7

57 36.0 1.9 35.6 35.6 35.6 31.3 26.6 21.9 34.9 2.1 34.9 34.9 34.9 30.4 25.8 21.3

1050

77 45.5 2.0 30.3 24.2 18.0 - - - 43.0 2.2 29.4 23.2 17.0 - - -

72 42.6 1.9 34.0 28.7 23.4 18.1 - - 40.3 2.2 32.9 27.7 22.4 17.1 - -

67 39.7 1.9 37.7 33.3 28.8 23.4 18.1 - 37.6 2.2 36.5 32.1 27.7 22.4 17.2 -

62 38.9 1.9 37.7 35.9 34.2 27.9 23.5 18.2 37.1 2.2 36.6 34.8 33.1 27.4 22.6 17.3

57 38.0 1.9 37.7 37.7 37.7 34.2 28.8 23.5 36.7 2.2 36.6 36.6 36.6 33.2 27.9 22.7

1200

77 45.8 2.0 33.5 25.9 18.4 - - - 43.0 2.2 32.9 25.1 17.4 - - -

72 43.5 2.0 36.7 30.6 24.5 18.5 - - 41.1 2.2 35.6 29.6 23.5 17.5 - -

67 41.2 1.9 39.9 35.3 30.7 24.6 18.6 - 39.1 2.2 38.3 34.0 29.7 23.7 17.7 -

62 40.6 1.9 39.9 38.4 36.9 30.2 24.8 18.8 38.8 2.2 38.4 37.1 35.9 29.6 23.9 17.9

57 40.1 1.9 39.8 39.8 39.8 37.0 31.1 25.1 38.4 2.2 38.4 38.4 38.4 36.1 30.1 24.1

1350

72 44.3 2.0 39.3 32.5 25.7 18.8 - - 41.8 2.2 38.3 31.5 24.7 17.9 - -

67 42.7 1.9 42.0 37.3 32.6 25.8 19.1 - 40.6 2.2 40.2 35.9 31.7 24.9 18.2 -

62 42.4 1.9 42.0 40.8 39.6 32.6 26.2 19.5 40.4 2.2 40.2 39.4 38.7 31.8 25.2 18.4

57 42.1 1.9 42.0 42.0 42.0 39.9 33.3 26.7 40.2 2.2 40.2 40.2 40.2 38.9 32.2 25.5

1500

72 45.2 2.0 42.0 34.4 26.82 19.2 - - 42.6 2.2 41.0 33.4 25.9 18.4 - -

67 44.1 2.0 44.1 39.3 34.5 27.1 19.6 - 42.0 2.2 42.0 37.8 33.7 26.2 18.7 -

62 44.1 2.0 44.1 43.2 42.3 34.9 27.6 20.2 42.0 2.2 42.0 41.7 41.4 34.0 26.5 19.0

57 44.1 2.0 44.1 44.1 44.1 42.8 35.5 28.3 42.0 2.2 42.0 42.0 42.0 41.8 34.3 26.9

95°F 105°F

750

77 40.9 2.5 20.8 18.0 15.2 - - - 37.7 2.8 21.0 17.8 14.7 - - -

72 36.7 2.4 26.4 22.7 18.9 15.2 - - 34.3 2.8 25.8 22.0 18.2 14.4 - -

67 32.5 2.4 32.1 27.4 22.7 19.0 15.3 - 30.9 2.8 30.6 26.2 21.7 18.0 14.4 -

62 32.4 2.4 32.4 29.4 26.4 22.8 19.1 15.5 30.8 2.8 30.8 28.0 25.2 21.7 18.2 14.7

900

77 40.7 2.5 24.6 20.1 15.6 - - - 37.7 2.8 24.4 19.6 14.8 - - -

72 37.4 2.4 29.1 24.6 20.145 15.6 - - 35.0 2.8 28.2 23.7 19.3 14.8 - -

67 34.0 2.4 33.7 29.2 24.7 20.2 15.8 - 32.3 2.8 32.0 27.9 23.7 19.3 14.9 -

62 33.9 2.4 33.9 31.6 29.2 24.8 20.4 16.0 32.2 2.8 32.2 30.2 28.1 23.8 19.4 15.1

57 33.8 2.4 33.8 33.8 33.8 29.4 25.0 20.6 32.1 2.8 32.1 32.1 32.1 28.3 24.0 19.7

1050

77 40.5 2.5 28.4 22.2 16.0 - - - 37.7 2.8 27.7 21.3 14.9 - - -

72 38.0 2.4 31.8 26.6 21.4 16.1 - - 35.7 2.8 30.6 25.5 20.3 15.2 - -

67 35.5 2.4 35.2 31.0 26.7 21.5 16.3 - 33.6 2.8 33.5 29.6 25.7 20.5 15.4 -

62 35.4 2.4 35.4 33.7 32.1 26.9 21.6 16.4 33.6 2.8 33.6 32.3 31.1 25.9 20.7 15.5

57 35.3 2.4 35.3 35.3 35.3 32.2 27.0 21.8 33.5 2.8 33.5 33.5 33.5 31.2 26.0 20.8

1200

77 40.3 2.5 32.3 24.3 16.4 - - - 37.8 2.8 31.1 23.1 15.1 - - -

72 38.7 2.5 34.5 28.6 22.6 16.6 - - 36.4 2.8 33.0 27.2 21.4 15.6 - -

67 37.0 2.4 36.8 32.8 28.7 22.7 16.7 - 35.0 2.8 34.9 31.3 27.7 21.8 15.9 -

62 36.9 2.4 36.9 35.9 34.9 28.9 22.9 16.9 34.9 2.8 34.9 34.5 34.0 28.0 21.9 15.9

57 36.8 2.4 36.8 36.8 36.8 35.1 29.1 23.1 34.9 2.8 34.9 34.9 34.9 34.2 28.0 21.9

1350

72 39.3 2.5 37.2 30.5 23.8 17.0 - - 37.1 2.8 35.4 28.9 22.4 16.0 - -

67 38.4 2.5 38.4 34.6 30.8 24.0 17.2 - 36.4 2.8 36.3 33.0 29.7 23.0 16.3 -

62 38.4 2.5 38.4 38.1 37.7 31.0 24.2 17.4 36.3 2.8 36.3 36.3 36.3 30.1 23.2 16.3

57 38.3 2.5 38.3 38.3 38.3 37.9 31.1 24.3 36.3 2.8 36.3 36.3 36.3 36.3 30.1 23.0

1500

72 39.9 2.5 39.9 32.5 24.971 17.5 - - 37.8 2.8 37.8 30.6 23.5 16.4 - -

67 39.9 2.5 39.9 36.3 32.8 25.2 17.7 - 37.7 2.8 37.7 34.7 31.7 24.3 16.8 -

62 39.9 2.5 39.9 39.9 39.9 33.0 25.4 17.8 37.7 2.8 37.7 37.7 37.7 32.2 24.5 16.7

57 39.9 2.5 39.9 39.9 39.9 39.9 33.1 25.5 37.7 2.8 37.7 37.7 37.7 37.7 32.1 24.0

Page 67: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 67

115°F 125°F

750

77 34.5 3.2 21.2 17.7 14.2 - - - 31.3 3.5 21.5 17.6 13.7 - - -

72 31.9 3.2 25.2 21.3 17.4 13.6 - - 29.5 3.5 24.5 20.6 16.7 12.8 - -

67 29.2 3.1 29.1 24.9 20.7 17.1 13.5 - 27.6 3.5 27.6 23.7 19.7 16.2 12.6 -

62 29.2 3.1 29.2 26.6 24.0 20.6 17.2 13.9 27.5 3.5 27.5 25.2 22.8 19.5 16.3 13.0

900

77 34.7 3.2 24.1 19.1 14.0 - - - 31.7 3.5 23.9 18.6 13.2 - - -

72 32.6 3.2 27.3 22.8 18.4 13.9 - - 30.2 3.5 26.3 21.9 17.5 13.0 - -

67 30.5 3.1 30.4 26.5 22.7 18.3 14.0 - 28.8 3.5 28.8 25.2 21.7 17.4 13.1 -

62 30.4 3.1 30.4 28.7 27.0 22.8 18.5 14.2 28.7 3.5 28.7 27.3 25.9 21.7 17.5 13.3

57 30.4 3.1 30.4 30.4 30.4 27.2 23.0 18.8 28.7 3.5 28.7 28.7 28.7 26.1 22.0 17.9

1050

77 34.9 3.2 27.0 20.4 13.9 - - - 32.2 3.5 26.3 19.5 12.8 - - -

72 33.4 3.2 29.3 24.3 19.3 14.2 - - 31.0 3.5 28.1 23.2 18.2 13.3 - -

67 31.8 3.1 31.7 28.2 24.7 19.6 14.5 - 29.9 3.5 29.9 26.8 23.7 18.6 13.6 -

62 31.7 3.1 31.7 30.9 30.1 24.9 19.7 14.6 29.9 3.5 29.9 29.5 29.1 23.9 18.8 13.6

57 31.7 3.1 31.7 31.7 31.7 30.2 25.0 19.8 29.8 3.5 29.8 29.8 29.8 29.2 24.0 18.7

1200

77 35.2 3.2 29.9 21.8 13.7 - - - 32.6 3.5 28.7 20.5 12.4 - - -

72 34.1 3.2 31.4 25.8 20.2 14.6 - - 31.8 3.5 29.9 24.4 19.0 13.6 - -

67 33.0 3.2 33.0 29.8 26.7 20.8 15.0 - 31.1 3.5 31.1 28.4 25.6 19.9 14.1 -

62 33.0 3.2 33.0 33.0 33.0 27.1 21.0 14.9 31.1 3.5 31.1 31.1 31.1 26.1 20.0 13.9

57 33.0 3.2 33.0 33.0 33.0 33.0 27.0 20.7 31.0 3.5 31.0 31.0 31.0 31.0 26.0 19.5

1350

72 34.9 3.2 33.5 27.3 21.1 14.9 - - 32.6 3.5 31.6 25.7 19.8 13.9 - -

67 34.3 3.2 34.3 31.5 28.6 22.1 15.5 - 32.2 3.5 32.2 29.9 27.6 21.1 14.6 -

62 34.3 3.2 34.3 34.3 34.3 29.2 22.2 15.3 32.2 3.5 32.2 32.2 32.2 28.3 21.3 14.2

57 34.2 3.2 34.2 34.2 34.2 34.2 29.0 21.6 32.2 3.5 32.2 32.2 32.2 32.2 28.0 20.3

1500

72 35.6 3.2 35.6 28.8 22.0 15.2 - - 33.4 3.6 33.4 27.0 20.6 14.1 - -

67 35.6 3.2 35.6 33.1 30.6 23.3 16.0 - 33.4 3.6 33.4 31.5 29.6 22.3 15.1 -

62 35.6 3.2 35.6 35.6 35.6 31.4 23.5 15.6 33.4 3.6 33.4 33.4 33.4 30.5 22.5 14.5

57 35.5 3.2 35.5 35.5 35.5 35.5 31.0 22.6 33.4 3.6 33.4 33.4 33.4 33.4 29.9 21.1

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR037 (3.0 Ton) Cooling (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 68: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

68 Johnson Controls Ducted Systems

ZR037 (3.0 Ton) Reheat

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

35°F 45°F

750

72 21.8 1.8 6.3 5.2 4.0 - - 24.7 1.8 6.3 5.2 4.1 - -

67 22.5 1.8 10.8 9.7 8.6 7.5 - 22.5 1.8 10.3 9.2 8.1 7.0 -

62 21.1 1.7 14.7 13.6 12.5 11.4 10.3 19.5 1.8 13.2 12.1 11.0 9.9 8.8

900

72 21.9 1.8 6.7 5.5 4.3 - - 24.8 1.8 6.9 5.7 4.5 - -

67 22.6 1.8 11.6 10.4 9.2 8.1 - 22.5 1.8 11.2 10.0 8.8 7.6 -

62 21.2 1.7 15.8 14.6 13.4 12.2 11.0 19.6 1.8 14.4 13.2 12.0 10.7 9.5

57 17.9 1.7 16.6 15.4 14.3 13.1 11.9 16.9 1.8 15.5 14.3 13.1 11.9 10.7

1050

72 21.9 1.8 7.1 5.9 4.6 - - 24.9 1.8 7.5 6.1 4.8 - -

67 22.7 1.8 12.4 11.1 9.9 8.6 - 22.6 1.8 12.2 10.8 9.5 8.2 -

62 21.2 1.8 16.9 15.6 14.3 13.1 11.8 19.7 1.8 15.6 14.2 12.9 11.6 10.3

57 18.0 1.7 17.4 16.5 15.2 14.0 12.7 17.0 1.8 16.3 15.5 14.2 12.9 11.6

1200

72 22.0 1.8 7.6 6.2 4.9 - - 25.0 1.8 8.0 6.6 5.2 - -

67 22.8 1.8 13.2 11.8 10.5 9.2 - 22.7 1.8 13.1 11.7 10.2 8.8 -

62 21.3 1.8 17.9 16.6 15.3 13.9 12.6 19.7 1.8 16.7 15.3 13.9 12.5 11.1

57 18.1 1.7 18.1 17.6 16.2 14.9 13.5 17.1 1.8 17.1 16.6 15.2 13.8 12.4

1350

72 23.0 1.8 8.3 6.8 5.3 - - 25.4 1.8 8.5 7.0 5.5 - -

67 23.6 1.8 14.4 12.9 11.4 9.8 - 23.1 1.8 13.9 12.4 10.9 9.3 -

62 22.1 1.7 19.5 18.0 16.5 15.0 13.5 20.1 1.8 17.7 16.2 14.7 13.2 11.7

57 18.7 1.7 18.7 18.5 16.9 15.4 13.9 17.3 1.8 17.3 17.1 15.6 14.1 12.6

1500

72 23.9 1.8 9.1 7.4 5.7 - - 25.8 1.8 9.0 7.4 5.8 - -

67 24.5 1.8 15.6 13.9 12.2 10.5 - 23.5 1.8 14.7 13.1 11.5 9.9 -

62 22.8 1.7 21.1 19.4 17.7 16.0 14.3 20.4 1.8 18.8 17.2 15.5 13.9 12.3

57 19.4 1.7 19.4 19.4 17.7 16.0 14.3 17.6 1.8 17.6 17.6 16.0 14.4 12.8

55°F 65°F

750

72 27.7 1.9 6.4 5.3 4.2 - - 26.8 1.9 5.9 4.8 3.7 - -

67 22.4 1.8 9.8 8.7 7.6 6.5 - 21.7 1.9 9.4 8.3 7.2 6.1 -

62 18.0 1.8 11.8 10.6 9.5 8.4 7.3 17.4 1.9 11.6 10.5 9.4 8.4 7.3

900

72 27.8 1.8 7.1 5.8 4.6 - - 26.6 1.9 6.4 5.2 4.0 - -

67 22.5 1.8 10.9 9.6 8.4 7.1 - 21.5 1.9 10.2 9.0 7.8 6.6 -

62 18.0 1.8 13.0 11.8 10.5 9.3 8.0 17.3 1.9 12.6 11.4 10.2 9.1 7.9

57 15.9 1.8 14.5 13.2 12.0 10.7 9.5 15.3 1.9 14.2 13.0 11.8 10.6 9.5

1050

72 27.9 1.8 7.8 6.4 5.0 - - 26.5 1.9 6.9 5.6 4.3 - -

67 22.6 1.8 11.9 10.6 9.2 7.8 - 21.4 1.9 10.9 9.7 8.4 7.1 -

62 18.1 1.8 14.2 12.9 11.5 10.2 8.8 17.2 1.9 13.5 12.3 11.0 9.7 8.5

57 16.0 1.8 15.2 14.5 13.1 11.7 10.4 15.2 1.9 14.6 14.0 12.7 11.4 10.2

1200

72 28.0 1.8 8.4 7.0 5.5 - - 26.3 1.9 7.4 6.0 4.6 - -

67 22.7 1.8 13.0 11.5 10.0 8.5 - 21.2 1.9 11.7 10.4 9.0 7.7 -

62 18.2 1.8 15.5 14.0 12.5 11.0 9.6 17.1 1.9 14.5 13.1 11.8 10.4 9.1

57 16.0 1.8 16.0 15.7 14.3 12.8 11.3 15.1 1.9 15.1 15.0 13.6 12.3 10.9

1350

72 27.8 1.8 8.7 7.2 5.7 - - 26.2 1.9 7.6 6.2 4.9 - -

67 22.6 1.8 13.4 11.9 10.4 8.9 - 21.2 1.9 12.2 10.8 9.4 8.0 -

62 18.1 1.8 16.0 14.5 13.0 11.5 10.0 17.0 1.9 15.0 13.7 12.3 10.9 9.5

57 15.9 1.8 15.9 15.8 14.3 12.8 11.3 15.1 1.9 15.1 15.0 13.6 12.2 10.9

1500

72 27.7 1.8 8.9 7.4 5.9 - - 26.1 1.9 7.9 6.5 5.1 - -

67 22.4 1.8 13.8 12.2 10.7 9.2 - 21.1 1.9 12.6 11.2 9.8 8.4 -

62 18.0 1.8 16.4 14.9 13.4 11.9 10.4 16.9 1.9 15.6 14.2 12.8 11.4 10.0

57 15.9 1.8 15.9 15.9 14.3 12.8 11.3 15.0 1.9 15.0 15.0 13.6 12.2 10.9

Page 69: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 69

75°F 85°F

750

72 26.0 1.9 5.3 4.3 3.2 - - 25.2 1.9 4.8 3.8 2.8 - -

67 20.9 1.9 8.9 7.9 6.8 5.8 - 20.2 1.9 8.5 7.5 6.5 5.5 -

62 16.9 1.9 11.5 10.4 9.4 8.3 7.3 16.3 1.9 11.3 10.3 9.3 8.3 7.3

900

72 25.5 1.9 5.6 4.5 3.4 - - 24.4 1.9 4.9 3.9 2.8 - -

67 20.5 1.9 9.4 8.3 7.2 6.1 - 19.6 1.9 8.7 7.7 6.7 5.6 -

62 16.6 1.9 12.1 11.0 9.9 8.8 7.7 15.8 1.9 11.7 10.7 9.6 8.6 7.6

57 14.8 1.9 13.9 12.8 11.7 10.6 9.5 14.2 2.0 13.6 12.5 11.5 10.5 9.4

1050

72 25.0 1.9 6.0 4.8 3.6 - - 23.6 1.9 5.0 4.0 2.9 - -

67 20.2 1.9 10.0 8.8 7.6 6.5 - 18.9 1.9 9.0 7.9 6.9 5.8 -

62 16.2 1.9 12.8 11.7 10.5 9.3 8.2 15.3 2.0 12.1 11.0 10.0 8.9 7.8

57 14.5 1.9 14.0 13.5 12.3 11.1 10.0 13.7 2.0 13.4 13.0 11.9 10.9 9.8

1200

72 24.6 1.9 6.3 5.0 3.8 - - 22.9 1.9 5.2 4.1 3.0 - -

67 19.8 1.9 10.5 9.3 8.0 6.8 - 18.3 1.9 9.3 8.2 7.1 6.0 -

62 15.9 1.9 13.5 12.3 11.0 9.8 8.6 14.8 2.0 12.5 11.4 10.3 9.2 8.1

57 14.2 1.9 14.2 14.2 13.0 11.7 10.5 13.3 2.0 13.3 13.3 12.3 11.2 10.1

1350

72 24.5 1.9 6.5 5.3 4.0 - - 22.9 1.9 5.4 4.3 3.2 - -

67 19.8 1.9 10.9 9.7 8.5 7.2 - 18.3 1.9 9.7 8.6 7.5 6.4 -

62 15.9 1.9 14.1 12.8 11.6 10.4 9.1 14.8 2.0 13.1 12.0 10.9 9.8 8.7

57 14.2 1.9 14.2 14.2 12.9 11.7 10.5 13.3 2.0 13.3 13.3 12.3 11.2 10.0

1500

72 24.5 1.9 6.8 5.5 4.3 - - 22.9 1.9 5.7 4.5 3.4 - -

67 19.7 1.9 11.4 10.1 8.9 7.6 - 18.4 1.9 10.2 9.1 8.0 6.9 -

62 15.9 1.9 14.7 13.4 12.2 10.9 9.7 14.9 2.0 13.8 12.7 11.6 10.4 9.3

57 14.2 1.9 14.2 14.2 12.9 11.7 10.4 13.3 2.0 13.3 13.3 12.2 11.1 10.0

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR037 (3.0 Ton) Reheat (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

Page 70: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

70 Johnson Controls Ducted Systems

ZR049 (4.0 Ton) Cooling

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1000

77 60.5 2.6 30.6 26.7 22.9 - - - 57.9 2.9 29.6 25.4 21.2 - - -

72 55.0 2.6 38.5 33.2 27.8 22.5 - - 52.5 2.9 37.5 32.1 26.7 21.2 - -

67 49.5 2.5 46.3 39.6 32.8 27.9 22.5 - 47.1 2.8 45.5 38.8 32.1 26.9 21.4 -

62 48.1 2.5 46.3 42.1 37.8 31.1 27.7 22.6 46.3 2.8 45.5 41.5 37.6 31.5 27.0 21.6

1200

77 60.5 2.6 35.1 29.2 23.3 - - - 57.7 2.9 34.3 28.0 21.7 - - -

72 55.8 2.6 41.9 35.6 29.379 23.1 - - 53.2 2.9 40.9 34.6 28.2 21.8 - -

67 51.2 2.6 48.7 42.1 35.5 29.5 23.1 - 48.8 2.9 47.5 41.1 34.7 28.5 22.0 -

62 50.1 2.5 48.7 45.1 41.6 34.1 29.3 23.2 48.2 2.8 47.5 44.4 41.3 34.3 28.6 22.2

57 48.9 2.5 48.7 48.2 47.7 41.6 35.5 29.4 47.6 2.8 47.5 47.5 47.5 41.4 35.1 28.8

1400

77 60.4 2.6 39.6 31.7 23.7 - - - 57.4 2.9 39.1 30.6 22.2 - - -

72 56.7 2.6 45.3 38.1 30.9 23.7 - - 54.0 2.9 44.3 37.0 29.7 22.5 - -

67 52.9 2.6 51.0 44.6 38.1 31.1 23.7 - 50.5 2.9 49.6 43.5 37.3 30.1 22.7 -

62 52.0 2.6 51.0 48.2 45.3 37.2 30.9 23.7 50.1 2.9 49.6 47.2 44.9 37.1 30.2 22.8

57 51.2 2.6 51.0 50.8 50.6 45.3 38.1 31.0 49.6 2.9 49.6 49.6 49.6 45.1 37.7 30.2

1600

77 60.3 2.6 44.1 34.1 24.1 - - - 57.2 2.9 43.8 33.2 22.6 - - -

72 57.5 2.6 48.7 40.6 32.4 24.3 - - 54.8 2.9 47.7 39.5 31.3 23.1 - -

67 54.6 2.6 53.3 47.0 40.8 32.7 24.4 - 52.3 2.9 51.6 45.8 39.9 31.7 23.3 -

62 54.0 2.6 53.3 51.2 49.1 40.2 32.6 24.3 52.0 2.9 51.6 50.1 48.6 39.8 31.8 23.3

57 53.5 2.6 53.3 53.3 53.3 49.1 40.8 32.5 51.7 2.9 51.6 51.6 51.6 48.7 40.2 31.7

1800

72 58.3 2.6 52.1 43.1 34.0 24.9 - - 55.5 2.9 51.1 42.0 32.8 23.7 - -

67 56.3 2.6 55.7 49.5 43.4 34.2 25.0 - 54.0 2.9 53.7 48.1 42.5 33.3 24.0 -

62 56.0 2.6 55.7 54.3 52.8 43.2 34.2 24.9 53.8 2.9 53.7 53.0 52.2 42.6 33.4 23.9

57 55.7 2.6 55.7 55.7 55.7 52.8 43.4 34.0 53.7 2.9 53.7 53.7 53.7 52.4 42.8 33.2

2000

72 59.1 2.6 55.6 45.5 35.498 25.5 - - 56.3 2.9 54.5 44.4 34.4 24.3 - -

67 58.0 2.6 58.0 52.0 46.0 35.8 25.6 - 55.7 2.9 55.7 50.4 45.1 34.9 24.6 -

62 58.0 2.6 58.0 57.3 56.6 46.2 35.8 25.4 55.7 2.9 55.7 55.7 55.7 45.4 35.0 24.5

57 58.0 2.6 58.0 58.0 58.0 56.6 46.0 35.5 55.7 2.9 55.7 55.7 55.7 55.7 45.3 34.6

95°F 105°F

1000

77 55.2 3.2 28.6 24.1 19.5 - - - 51.2 3.6 29.3 24.1 19.0 - - -

72 49.9 3.2 36.6 31.1 25.5 19.9 - - 47.0 3.6 36.0 30.3 24.7 19.0 - -

67 44.6 3.1 44.6 38.0 31.4 25.9 20.3 - 42.7 3.5 42.7 36.5 30.4 24.8 19.2 -

62 44.6 3.1 44.6 41.0 37.4 31.8 26.2 20.7 42.7 3.5 42.7 39.4 36.1 30.6 25.1 19.6

1200

77 54.8 3.2 33.6 26.8 20.1 - - - 51.1 3.6 33.6 26.4 19.1 - - -

72 50.6 3.2 40.0 33.5 27.033 20.6 - - 47.7 3.6 39.0 32.5 26.0 19.5 - -

67 46.4 3.1 46.4 40.2 34.0 27.5 20.9 - 44.3 3.6 44.3 38.6 32.9 26.4 19.9 -

62 46.4 3.1 46.4 43.7 41.0 34.4 27.8 21.2 44.3 3.6 44.3 42.1 39.8 33.2 26.7 20.1

57 46.3 3.1 46.3 46.3 46.3 41.3 34.7 28.1 44.2 3.6 44.2 44.2 44.2 40.1 33.5 26.8

1400

77 54.5 3.2 38.6 29.6 20.6 - - - 51.1 3.6 37.9 28.6 19.3 - - -

72 51.3 3.2 43.4 36.0 28.6 21.2 - - 48.5 3.6 41.9 34.6 27.3 20.1 - -

67 48.2 3.2 48.2 42.4 36.6 29.1 21.6 - 45.9 3.6 45.9 40.7 35.4 28.0 20.5 -

62 48.1 3.2 48.1 46.3 44.5 37.0 29.4 21.8 45.9 3.6 45.9 44.7 43.5 35.9 28.3 20.6

57 48.1 3.2 48.1 48.1 48.1 44.8 37.2 29.5 45.9 3.6 45.9 45.9 45.9 43.8 36.0 28.2

1600

77 54.2 3.2 43.5 32.3 21.2 - - - 51.0 3.6 42.2 30.8 19.4 - - -

72 52.0 3.2 46.7 38.4 30.1 21.8 - - 49.3 3.6 44.9 36.8 28.7 20.6 - -

67 49.9 3.2 49.9 44.5 39.1 30.7 22.3 - 47.5 3.6 47.5 42.7 38.0 29.6 21.2 -

62 49.9 3.2 49.9 49.0 48.1 39.5 31.0 22.4 47.5 3.6 47.5 47.4 47.2 38.5 29.8 21.1

57 49.9 3.2 49.9 49.9 49.9 48.4 39.7 30.9 47.5 3.6 47.5 47.5 47.5 47.5 38.5 29.5

1800

72 52.7 3.2 50.1 40.9 31.7 22.5 - - 50.0 3.6 47.8 38.9 30.0 21.1 - -

67 51.7 3.2 51.7 46.7 41.7 32.3 22.9 - 49.2 3.6 49.2 44.8 40.5 31.1 21.8 -

62 51.6 3.2 51.6 51.6 51.6 42.1 32.5 23.0 49.1 3.6 49.1 49.1 49.1 41.2 31.4 21.7

57 51.6 3.2 51.6 51.6 51.6 51.6 42.1 32.4 49.1 3.6 49.1 49.1 49.1 49.1 41.1 30.9

2000

72 53.4 3.2 53.4 43.3 33.246 23.1 - - 50.8 3.6 50.8 41.1 31.3 21.6 - -

67 53.4 3.2 53.4 48.8 44.2 33.9 23.6 - 50.8 3.6 50.8 46.9 43.0 32.7 22.4 -

62 53.4 3.2 53.4 53.4 53.4 44.7 34.1 23.5 50.8 3.6 50.8 50.8 50.8 43.8 33.0 22.2

57 53.4 3.2 53.4 53.4 53.4 53.4 44.6 33.8 50.7 3.6 50.7 50.7 50.7 50.7 43.6 32.2

Page 71: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 71

115°F 125°F

1000

77 47.3 4.0 30.0 24.2 18.4 - - - 43.3 4.4 30.7 24.3 17.9 - - -

72 44.0 4.0 35.4 29.6 23.9 18.2 - - 41.0 4.4 34.8 28.9 23.1 17.3 - -

67 40.7 4.0 40.7 35.1 29.4 23.8 18.2 - 38.8 4.4 38.8 33.6 28.3 22.7 17.1 -

62 40.7 4.0 40.7 37.8 34.8 29.4 23.9 18.5 38.7 4.4 38.7 36.2 33.6 28.2 22.8 17.4

1200

77 47.5 4.0 33.7 25.9 18.2 - - - 43.8 4.4 33.7 25.5 17.2 - - -

72 44.8 4.0 37.9 31.5 25.0 18.5 - - 41.9 4.4 36.9 30.4 24.0 17.5 - -

67 42.2 4.0 42.2 37.0 31.8 25.3 18.8 - 40.1 4.4 40.1 35.4 30.8 24.3 17.7 -

62 42.2 4.0 42.2 40.4 38.7 32.1 25.5 18.9 40.1 4.4 40.1 38.8 37.6 31.0 24.4 17.8

57 42.1 4.0 42.1 42.1 42.1 38.9 32.2 25.6 40.0 4.4 40.0 40.0 40.0 37.7 31.0 24.4

1400

77 47.6 4.0 37.3 27.6 17.9 - - - 44.2 4.4 36.6 26.6 16.5 - - -

72 45.7 4.0 40.5 33.3 26.1 18.9 - - 42.8 4.4 39.1 32.0 24.9 17.8 - -

67 43.7 4.0 43.7 39.0 34.3 26.9 19.4 - 41.5 4.4 41.5 37.3 33.2 25.8 18.3 -

62 43.7 4.0 43.7 43.1 42.5 34.8 27.1 19.4 41.4 4.4 41.4 41.4 41.4 33.8 26.0 18.2

57 43.6 4.0 43.6 43.6 43.6 42.8 34.8 26.9 41.4 4.4 41.4 41.4 41.4 41.4 33.6 25.5

1600

77 47.8 4.0 40.9 29.3 17.6 - - - 44.6 4.4 39.6 27.7 15.9 - - -

72 46.5 4.0 43.0 35.1 27.2 19.3 - - 43.7 4.4 41.2 33.5 25.7 18.0 - -

67 45.2 4.0 45.2 41.0 36.8 28.4 20.1 - 42.8 4.4 42.8 39.2 35.6 27.3 18.9 -

62 45.1 4.0 45.1 45.1 45.1 37.6 28.7 19.9 42.8 4.4 42.8 42.8 42.8 36.6 27.6 18.6

57 45.1 4.0 45.1 45.1 45.1 45.1 37.4 28.1 42.7 4.4 42.7 42.7 42.7 42.7 36.3 26.7

1800

72 47.3 4.0 45.6 37.0 28.3 19.7 - - 44.6 4.4 43.3 35.0 26.6 18.3 - -

67 46.6 4.0 46.6 43.0 39.3 30.0 20.7 - 44.1 4.4 44.1 41.1 38.1 28.8 19.6 -

62 46.6 4.0 46.6 46.6 46.6 40.3 30.3 20.4 44.1 4.4 44.1 44.1 44.1 39.4 29.2 19.1

57 46.6 4.0 46.6 46.6 46.6 46.6 40.0 29.3 44.1 4.4 44.1 44.1 44.1 44.1 38.9 27.8

2000

72 48.1 4.0 48.1 38.8 29.4 20.0 - - 45.5 4.5 45.5 36.5 27.5 18.5 - -

67 48.1 4.0 48.1 44.9 41.7 31.5 21.3 - 45.5 4.5 45.5 43.0 40.5 30.3 20.2 -

62 48.1 4.0 48.1 48.1 48.1 43.0 31.9 20.8 45.5 4.5 45.5 45.5 45.5 42.2 30.8 19.5

57 48.1 4.0 48.1 48.1 48.1 48.1 42.5 30.6 45.4 4.5 45.4 45.4 45.4 45.4 41.5 29.0

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR049 (4.0 Ton) Cooling (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 72: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

72 Johnson Controls Ducted Systems

ZR49 (4.0 Ton) Reheat

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

35°F 45°F

1000

72 34.9 2.4 11.4 9.8 8.2 - - 35.9 2.5 10.3 8.7 7.2 - -

67 30.2 2.4 15.8 14.2 12.6 11.0 - 29.5 2.5 14.7 13.2 11.7 10.1 -

62 25.4 2.4 18.7 17.1 15.5 13.9 12.2 25.1 2.4 17.5 16.0 14.5 13.0 11.4

1200

72 34.8 2.4 12.0 10.3 8.6 - - 35.2 2.5 10.8 9.2 7.7 - -

67 30.1 2.4 16.6 14.9 13.2 11.5 - 29.0 2.5 15.5 13.9 12.4 10.8 -

62 25.3 2.4 19.6 17.9 16.2 14.5 12.8 24.6 2.4 18.5 16.9 15.4 13.8 12.2

57 23.8 2.4 21.3 19.6 17.9 16.2 14.5 22.6 2.4 19.7 18.1 16.5 14.9 13.4

1400

72 34.7 2.4 12.5 10.7 9.0 - - 34.5 2.5 11.4 9.7 8.1 - -

67 30.0 2.4 17.4 15.6 13.8 12.0 - 28.4 2.5 16.3 14.7 13.0 11.4 -

62 25.2 2.4 20.5 18.7 16.9 15.2 13.4 24.2 2.4 19.5 17.9 16.2 14.6 12.9

57 23.7 2.4 22.4 20.5 18.7 17.0 15.2 22.2 2.4 20.7 19.1 17.4 15.8 14.1

1600

72 34.7 2.4 13.1 11.2 9.4 - - 33.8 2.5 12.0 10.2 8.5 - -

67 29.9 2.4 18.1 16.3 14.4 12.5 - 27.8 2.5 17.2 15.5 13.7 12.0 -

62 25.2 2.4 21.4 19.6 17.7 15.8 14.0 23.7 2.4 20.5 18.8 17.1 15.4 13.6

57 23.6 2.4 23.6 21.4 19.6 17.7 15.8 21.7 2.4 21.7 20.1 18.4 16.7 14.9

1800

72 34.3 2.4 13.4 11.6 9.8 - - 33.6 2.5 12.1 10.5 8.8 - -

67 29.6 2.4 18.6 16.8 15.0 13.2 - 27.7 2.5 17.4 15.8 14.1 12.5 -

62 24.9 2.4 22.0 20.2 18.4 16.6 14.8 23.5 2.4 20.8 19.2 17.5 15.9 14.2

57 23.4 2.4 23.4 22.1 20.3 18.5 16.7 21.6 2.4 21.6 20.5 18.9 17.2 15.5

2000

72 34.0 2.4 13.7 12.0 10.2 - - 33.4 2.5 12.3 10.7 9.1 - -

67 29.3 2.4 19.1 17.3 15.6 13.9 - 27.5 2.4 17.7 16.1 14.5 12.9 -

62 24.7 2.4 22.6 20.9 19.1 17.4 15.7 23.4 2.4 21.2 19.6 18.0 16.4 14.8

57 23.1 2.4 23.1 22.8 21.1 19.4 17.7 21.4 2.4 21.4 20.9 19.3 17.8 16.2

55°F 65°F

1000

72 36.9 2.6 9.1 7.7 6.3 - - 34.2 2.7 8.3 7.0 5.7 - -

67 28.9 2.5 13.6 12.2 10.7 9.3 - 26.5 2.6 12.5 11.2 9.9 8.6 -

62 24.9 2.5 16.4 15.0 13.5 12.1 10.7 22.4 2.6 15.4 14.1 12.7 11.4 10.1

1200

72 35.6 2.6 9.7 8.2 6.7 - - 33.1 2.7 8.7 7.4 6.0 - -

67 27.9 2.5 14.5 13.0 11.5 10.0 - 25.7 2.6 13.2 11.9 10.5 9.2 -

62 24.0 2.5 17.5 16.0 14.5 13.0 11.5 21.7 2.6 16.2 14.9 13.5 12.2 10.8

57 21.4 2.5 18.1 16.6 15.1 13.7 12.2 19.6 2.6 17.2 15.8 14.5 13.2 11.8

1400

72 34.3 2.6 10.3 8.7 7.2 - - 31.9 2.7 9.2 7.8 6.4 - -

67 26.9 2.5 15.3 13.8 12.3 10.8 - 24.8 2.6 13.9 12.5 11.2 9.8 -

62 23.1 2.5 18.5 17.0 15.5 13.9 12.4 20.9 2.6 17.0 15.7 14.3 12.9 11.6

57 20.6 2.5 19.0 17.7 16.2 14.6 13.1 18.9 2.6 17.7 16.7 15.3 13.9 12.6

1600

72 33.0 2.5 10.8 9.3 7.7 - - 30.8 2.6 9.6 8.2 6.8 - -

67 25.8 2.5 16.2 14.6 13.1 11.5 - 23.9 2.6 14.6 13.2 11.8 10.4 -

62 22.2 2.5 19.6 18.0 16.4 14.9 13.3 20.2 2.6 17.9 16.5 15.1 13.7 12.3

57 19.8 2.5 19.8 18.7 17.2 15.6 14.0 18.2 2.6 18.2 17.5 16.1 14.7 13.3

1800

72 32.9 2.5 10.9 9.3 7.8 - - 30.4 2.6 9.5 8.2 6.8 - -

67 25.8 2.5 16.3 14.8 13.2 11.7 - 23.6 2.6 14.5 13.2 11.8 10.5 -

62 22.2 2.5 19.7 18.2 16.6 15.1 13.6 19.9 2.6 17.8 16.5 15.1 13.8 12.4

57 19.8 2.5 19.8 18.9 17.4 15.9 14.3 18.0 2.6 18.0 17.4 16.1 14.8 13.4

2000

72 32.8 2.5 10.9 9.4 8.0 - - 29.9 2.7 9.5 8.2 6.9 - -

67 25.7 2.5 16.4 14.9 13.4 11.9 - 23.2 2.6 14.5 13.2 11.9 10.6 -

62 22.1 2.5 19.8 18.3 16.8 15.4 13.9 19.6 2.6 17.8 16.5 15.2 13.9 12.6

57 19.7 2.5 19.7 19.1 17.6 16.1 14.6 17.7 2.6 17.7 17.4 16.1 14.8 13.5

Page 73: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 73

75°F 85°F

1000

72 31.5 2.8 7.4 6.3 5.1 - - 28.8 2.9 6.6 5.5 4.5 - -

67 24.2 2.7 11.5 10.3 9.1 7.9 - 21.8 2.9 10.4 9.4 8.3 7.3 -

62 20.0 2.7 14.3 13.1 12.0 10.8 9.6 17.6 2.8 13.3 12.2 11.2 10.1 9.1

1200

72 30.5 2.8 7.7 6.5 5.3 - - 28.0 2.9 6.7 5.7 4.6 - -

67 23.5 2.7 12.0 10.8 9.6 8.4 - 21.2 2.8 10.7 9.7 8.6 7.5 -

62 19.4 2.7 14.9 13.7 12.5 11.3 10.1 17.1 2.8 13.7 12.6 11.6 10.5 9.5

57 17.7 2.7 16.2 15.0 13.8 12.6 11.5 15.9 2.8 15.3 14.2 13.2 12.1 11.1

1400

72 29.6 2.8 8.0 6.8 5.6 - - 27.2 2.9 6.9 5.8 4.8 - -

67 22.7 2.7 12.4 11.2 10.0 8.8 - 20.6 2.8 11.0 9.9 8.9 7.8 -

62 18.8 2.7 15.5 14.3 13.1 11.9 10.7 16.7 2.8 14.1 13.0 11.9 10.9 9.8

57 17.2 2.7 16.4 15.7 14.5 13.3 12.0 15.4 2.8 15.1 14.7 13.6 12.6 11.5

1600

72 28.6 2.7 8.3 7.1 5.9 - - 26.4 2.8 7.1 6.0 4.9 - -

67 22.0 2.7 12.9 11.7 10.5 9.2 - 20.0 2.8 11.3 10.2 9.1 8.1 -

62 18.2 2.7 16.1 14.9 13.7 12.5 11.2 16.2 2.8 14.4 13.4 12.3 11.2 10.2

57 16.6 2.7 16.6 16.3 15.1 13.9 12.6 15.0 2.8 15.0 15.0 14.1 13.0 11.9

1800

72 27.8 2.8 8.2 7.0 5.9 - - 25.2 2.9 6.9 5.9 4.9 - -

67 21.3 2.7 12.7 11.6 10.4 9.3 - 19.1 2.8 11.0 10.0 9.0 8.0 -

62 17.7 2.7 15.9 14.8 13.6 12.5 11.3 15.4 2.8 14.1 13.1 12.1 11.1 10.1

57 16.1 2.7 16.1 16.0 14.8 13.7 12.5 14.3 2.8 14.3 14.3 13.6 12.6 11.6

2000

72 27.0 2.8 8.1 7.0 5.9 - - 24.0 2.9 6.6 5.7 4.8 - -

67 20.7 2.7 12.6 11.5 10.4 9.3 - 18.2 2.8 10.7 9.8 8.9 8.0 -

62 17.1 2.7 15.7 14.6 13.6 12.5 11.4 14.7 2.8 13.7 12.8 11.9 11.0 10.1

57 15.7 2.7 15.7 15.7 14.6 13.5 12.4 13.6 2.8 13.6 13.6 13.1 12.2 11.3

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR49 (4.0 Ton) Reheat (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

Page 74: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

74 Johnson Controls Ducted Systems

ZR061 (5.0 Ton) Cooling

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1250

77 72.9 3.5 38.6 33.2 27.8 - - - 68.8 3.9 38.0 32.3 26.6 - - -

72 66.2 3.4 47.9 41.2 34.5 27.8 - - 62.9 3.8 46.9 40.1 33.2 26.4 - -

67 59.4 3.4 57.1 49.1 41.1 34.2 27.7 - 57.0 3.7 55.8 47.8 39.9 33.0 26.3 -

62 58.6 3.3 57.1 52.4 47.8 38.2 34.2 27.4 56.5 3.7 55.8 51.1 46.5 38.4 33.1 26.3

1500

77 72.7 3.5 45.0 36.6 28.3 - - - 68.8 3.9 44.0 35.4 26.8 - - -

72 67.3 3.5 52.5 44.5 36.459 28.5 - - 64.0 3.8 51.1 43.1 35.1 27.0 - -

67 61.8 3.4 60.0 52.3 44.6 36.4 28.5 - 59.2 3.8 58.3 50.8 43.4 35.2 27.2 -

62 61.2 3.4 60.0 56.4 52.8 42.4 36.6 28.5 58.9 3.8 58.3 55.0 51.7 42.4 35.4 27.2

57 60.6 3.4 60.0 60.0 60.0 52.8 44.7 36.5 58.6 3.8 58.3 58.3 58.3 51.8 43.6 35.4

1750

77 72.5 3.5 51.3 40.1 28.8 - - - 68.7 3.9 50.0 38.5 27.0 - - -

72 68.3 3.5 57.1 47.8 38.5 29.1 - - 65.1 3.9 55.4 46.2 36.9 27.7 - -

67 64.2 3.4 62.8 55.5 48.1 38.6 29.4 - 61.5 3.8 60.8 53.9 46.9 37.4 28.1 -

62 63.7 3.4 62.8 60.3 57.7 46.7 39.0 29.6 61.3 3.8 60.8 58.8 56.8 46.4 37.7 28.1

57 63.3 3.4 62.8 62.8 62.8 57.9 48.5 39.1 61.0 3.8 60.8 60.8 60.8 57.0 47.3 37.6

2000

77 72.2 3.5 57.6 43.5 29.3 - - - 68.7 3.9 55.9 41.6 27.2 - - -

72 69.4 3.5 61.7 51.1 40.4 29.8 - - 66.3 3.9 59.7 49.2 38.8 28.3 - -

67 66.6 3.5 65.7 58.6 51.6 40.8 30.3 - 63.8 3.8 63.4 56.9 50.3 39.6 28.9 -

62 66.3 3.5 65.7 64.2 62.7 50.9 41.3 30.7 63.6 3.8 63.3 62.6 61.9 50.4 40.0 29.0

57 66.0 3.4 65.7 65.7 65.7 63.1 52.4 41.7 63.4 3.8 63.3 63.3 63.3 62.3 51.1 39.9

2250

72 70.5 3.5 66.3 54.4 42.4 30.5 - - 67.4 3.9 63.9 52.3 40.6 28.9 - -

67 69.0 3.5 68.6 61.8 55.1 43.1 31.1 - 66.1 3.9 65.9 59.9 53.8 41.8 29.8 -

62 68.9 3.5 68.5 68.1 67.7 55.1 43.7 31.7 66.0 3.9 65.8 65.8 65.8 54.4 42.3 29.9

57 68.7 3.5 68.5 68.5 68.5 68.3 56.3 44.2 65.9 3.9 65.8 65.8 65.8 65.8 54.8 42.1

2500

72 71.6 3.5 70.9 57.7 44.434 31.2 - - 68.5 3.9 68.2 55.3 42.4 29.6 - -

67 71.5 3.5 71.5 65.0 58.5 45.3 32.0 - 68.4 3.9 68.4 62.9 57.3 44.0 30.7 -

62 71.4 3.5 71.4 71.4 71.4 59.4 46.1 32.8 68.4 3.9 68.4 68.4 68.4 58.4 44.6 30.8

57 71.4 3.5 71.4 71.4 71.4 71.4 60.1 46.8 68.3 3.9 68.3 68.3 68.3 68.3 58.6 44.3

95°F 105°F

1250

77 64.7 4.3 37.4 31.4 25.4 - - - 60.1 4.8 38.1 31.2 24.4 - - -

72 59.6 4.2 45.9 39.0 32.0 25.0 - - 56.0 4.7 45.0 38.0 30.9 23.9 - -

67 54.5 4.1 54.5 46.6 38.6 31.8 25.0 - 52.0 4.6 52.0 44.8 37.5 30.6 23.7 -

62 54.5 4.1 54.5 49.9 45.3 38.6 31.9 25.2 51.9 4.6 51.9 48.0 44.1 37.4 30.7 24.0

1500

77 64.9 4.3 43.0 34.1 25.2 - - - 60.5 4.8 42.9 33.5 24.1 - - -

72 60.8 4.2 49.8 41.8 33.682 25.6 - - 57.2 4.7 48.4 40.4 32.4 24.4 - -

67 56.7 4.1 56.7 49.4 42.1 34.0 25.8 - 54.0 4.6 54.0 47.4 40.8 32.7 24.7 -

62 56.6 4.1 56.6 53.6 50.6 42.4 34.2 26.0 53.9 4.6 53.9 51.5 49.1 41.0 32.9 24.8

57 56.6 4.1 56.6 56.6 56.6 50.7 42.5 34.2 53.8 4.6 53.8 53.8 53.8 49.3 41.2 33.0

1750

77 65.0 4.3 48.6 36.9 25.1 - - - 60.9 4.8 47.7 35.7 23.8 - - -

72 61.9 4.2 53.7 44.6 35.4 26.2 - - 58.4 4.7 51.8 42.9 33.9 25.0 - -

67 58.9 4.2 58.9 52.2 45.6 36.2 26.7 - 56.0 4.7 56.0 50.0 44.1 34.8 25.6 -

62 58.8 4.2 58.8 57.3 55.9 46.1 36.4 26.7 55.9 4.7 55.9 55.1 54.2 44.7 35.2 25.6

57 58.8 4.2 58.8 58.8 58.8 56.1 46.1 36.1 55.8 4.7 55.8 55.8 55.8 54.6 44.7 34.9

2000

77 65.2 4.3 54.2 39.6 25.0 - - - 61.3 4.8 52.5 38.0 23.5 - - -

72 63.1 4.3 57.6 47.4 37.1 26.8 - - 59.6 4.8 55.2 45.3 35.4 25.5 - -

67 61.0 4.2 61.0 55.1 49.1 38.4 27.6 - 58.0 4.7 58.0 52.7 47.4 36.9 26.5 -

62 61.0 4.2 61.0 61.0 61.0 49.9 38.7 27.4 57.9 4.7 57.9 57.9 57.9 48.4 37.4 26.5

57 60.9 4.2 60.9 60.9 60.9 60.9 49.8 38.0 57.9 4.7 57.9 57.9 57.9 57.9 48.3 36.9

2250

72 64.3 4.3 61.5 50.2 38.8 27.4 - - 60.8 4.8 58.6 47.8 36.9 26.1 - -

67 63.2 4.3 63.2 57.9 52.6 40.5 28.5 - 60.0 4.8 60.0 55.3 50.6 39.0 27.4 -

62 63.2 4.3 63.2 63.2 63.2 53.7 40.9 28.2 59.9 4.8 59.9 59.9 59.9 52.0 39.7 27.3

57 63.1 4.3 63.1 63.1 63.1 63.1 53.4 39.9 59.9 4.8 59.9 59.9 59.9 59.9 51.9 38.8

2500

72 65.4 4.3 65.4 53.0 40.46 28.0 - - 62.0 4.8 62.0 50.2 38.4 26.6 - -

67 65.4 4.3 65.4 60.8 56.1 42.7 29.3 - 62.0 4.8 62.0 58.0 53.9 41.1 28.3 -

62 65.3 4.3 65.3 65.3 65.3 57.5 43.2 28.9 61.9 4.8 61.9 61.9 61.9 55.7 41.9 28.1

57 65.3 4.3 65.3 65.3 65.3 65.3 57.1 41.9 61.9 4.8 61.9 61.9 61.9 61.9 55.5 40.7

Page 75: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 75

115°F 125°F

1250

77 55.4 5.2 38.8 31.1 23.4 - - - 50.8 5.7 39.5 30.9 22.4 - - -

72 52.5 5.2 44.2 37.0 29.9 22.7 - - 48.9 5.6 43.3 36.0 28.8 21.6 - -

67 49.5 5.1 49.5 42.9 36.4 29.4 22.5 - 47.0 5.6 47.0 41.1 35.2 28.3 21.3 -

62 49.3 5.1 49.3 46.1 42.9 36.1 29.4 22.7 46.8 5.6 46.8 44.2 41.7 34.9 28.2 21.5

1500

77 56.1 5.2 42.8 32.8 22.9 - - - 51.7 5.7 42.7 32.2 21.7 - - -

72 53.7 5.2 47.1 39.1 31.2 23.2 - - 50.2 5.7 45.7 37.8 29.9 22.0 - -

67 51.3 5.1 51.3 45.4 39.4 31.5 23.5 - 48.7 5.6 48.7 43.4 38.1 30.2 22.3 -

62 51.2 5.1 51.2 49.4 47.7 39.7 31.7 23.7 48.5 5.6 48.5 47.4 46.3 38.4 30.4 22.5

57 51.0 5.1 51.0 51.0 51.0 47.9 39.9 31.8 48.2 5.6 48.2 48.2 48.2 46.5 38.6 30.6

1750

77 56.7 5.3 46.8 34.6 22.4 - - - 52.6 5.7 45.8 33.5 21.1 - - -

72 54.9 5.2 50.0 41.2 32.5 23.7 - - 51.4 5.7 48.1 39.5 31.0 22.5 - -

67 53.1 5.2 53.1 47.8 42.5 33.5 24.4 - 50.3 5.7 50.3 45.6 41.0 32.1 23.3 -

62 53.0 5.2 53.0 52.8 52.6 43.2 33.9 24.6 50.1 5.7 50.1 50.1 50.1 41.8 32.7 23.5

57 52.9 5.2 52.9 52.9 52.9 52.9 43.4 33.8 50.0 5.7 50.0 50.0 50.0 50.0 42.0 32.6

2000

77 57.4 5.3 50.8 36.3 21.9 - - - 53.5 5.8 49.0 34.7 20.4 - - -

72 56.2 5.3 52.9 43.3 33.8 24.2 - - 52.7 5.7 50.5 41.3 32.1 22.9 - -

67 54.9 5.2 54.9 50.3 45.6 35.5 25.4 - 51.9 5.7 51.9 47.9 43.8 34.1 24.3 -

62 54.9 5.2 54.9 54.9 54.9 46.8 36.1 25.5 51.8 5.7 51.8 51.8 51.8 45.2 34.9 24.5

57 54.8 5.2 54.8 54.8 54.8 54.8 46.9 35.7 51.7 5.7 51.7 51.7 51.7 51.7 45.4 34.5

2250

72 57.4 5.3 55.8 45.4 35.1 24.7 - - 54.0 5.8 52.9 43.0 33.2 23.4 - -

67 56.8 5.3 56.8 52.7 48.7 37.5 26.4 - 53.5 5.8 53.5 50.1 46.7 36.0 25.3 -

62 56.7 5.3 56.7 56.7 56.7 50.3 38.4 26.4 53.5 5.8 53.5 53.5 53.5 48.6 37.1 25.6

57 56.7 5.3 56.7 56.7 56.7 56.7 50.4 37.6 53.5 5.8 53.5 53.5 53.5 53.5 48.9 36.5

2500

72 58.7 5.3 58.7 47.5 36.4 25.2 - - 55.3 5.8 55.3 44.8 34.3 23.8 - -

67 58.6 5.3 58.6 55.2 51.7 39.5 27.3 - 55.1 5.8 55.1 52.3 49.5 37.9 26.3 -

62 58.6 5.3 58.6 58.6 58.6 53.9 40.6 27.4 55.2 5.8 55.2 55.2 55.2 52.0 39.3 26.6

57 58.6 5.3 58.6 58.6 58.6 58.6 53.9 39.6 55.3 5.8 55.3 55.3 55.3 55.3 52.3 38.4

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR061 (5.0 Ton) Cooling (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 76: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

76 Johnson Controls Ducted Systems

ZR061 (5.0 Ton) Reheat

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

35°F 45°F

1250

72 29.0 2.8 - - - - - 32.7 3.0 0.9 0.3 - - -

67 28.0 2.8 6.7 6.0 5.3 4.6 - 28.9 2.9 6.3 5.7 5.0 4.3 -

62 26.9 2.8 14.2 13.5 12.7 12.0 11.3 24.3 2.9 12.3 11.7 11.0 10.3 9.6

1500

72 28.6 2.8 - - - - - 32.9 3.0 1.2 0.3 - - -

67 27.6 2.8 7.5 6.8 6.0 5.3 - 29.1 2.9 7.8 6.9 6.1 5.3 -

62 26.7 2.8 16.0 15.3 14.6 13.8 13.1 24.5 2.9 15.1 14.3 13.4 12.6 11.8

57 25.5 2.9 19.2 18.5 17.8 17.1 16.3 23.4 2.9 17.4 16.5 15.7 14.9 14.0

1750

72 28.1 2.8 - - - - - 33.2 3.0 1.4 0.4 - - -

67 27.3 2.8 8.2 7.5 6.7 6.0 - 29.4 2.9 9.2 8.2 7.2 6.2 -

62 26.5 2.8 17.9 17.1 16.4 15.7 14.9 24.7 2.9 17.9 16.9 15.9 14.9 13.9

57 25.4 2.9 22.2 20.8 20.1 19.4 18.6 23.6 2.9 20.6 19.6 18.6 17.6 16.6

2000

72 27.7 2.8 - - - - - 33.5 3.0 1.6 0.4 - - -

67 27.0 2.8 9.0 8.2 7.5 6.7 - 29.6 2.9 10.6 9.5 8.3 7.2 -

62 26.3 2.8 19.7 19.0 18.2 17.5 16.7 24.9 2.9 20.7 19.5 18.4 17.2 16.0

57 25.2 2.9 25.1 23.2 22.4 21.7 20.9 23.8 2.9 23.8 22.6 21.4 20.3 19.1

2250

72 27.8 2.8 - - - - - 33.5 2.9 1.7 0.5 - - -

67 27.0 2.8 9.4 8.6 7.9 7.1 - 29.6 2.9 11.6 10.4 9.1 7.9 -

62 26.4 2.8 22.8 21.1 20.3 19.6 18.8 24.9 2.9 22.6 21.4 20.1 18.9 17.6

57 25.2 2.8 25.2 24.2 23.5 22.7 22.0 23.8 2.9 23.7 23.2 21.9 20.7 19.4

2500

72 27.9 2.8 - - - - - 33.4 2.9 1.9 0.5 - - -

67 27.1 2.8 9.8 9.1 8.3 7.5 - 29.5 2.9 12.6 11.3 9.9 8.6 -

62 26.4 2.8 25.9 23.2 22.4 21.7 20.9 24.9 2.9 24.6 23.2 21.9 20.6 19.2

57 25.3 2.8 25.3 25.3 24.5 23.8 23.0 23.7 2.9 23.7 23.7 22.4 21.1 19.7

55°F 65°F

1250

72 36.3 3.1 2.7 2.0 1.4 - - 35.8 3.2 1.7 1.3 0.8 - -

67 29.8 3.0 5.9 5.3 4.7 4.0 - 28.5 3.1 4.4 3.9 3.5 3.1 -

62 21.7 3.0 10.5 9.9 9.2 8.6 8.0 20.7 3.1 8.2 7.8 7.3 6.9 6.5

1500

72 37.3 3.1 3.7 2.8 1.8 - - 36.4 3.2 2.5 1.8 1.0 - -

67 30.6 3.0 8.0 7.1 6.2 5.2 - 28.9 3.1 6.5 5.8 5.0 4.3 -

62 22.3 3.0 14.2 13.3 12.3 11.4 10.4 21.1 3.1 12.2 11.5 10.7 10.0 9.2

57 21.3 2.9 15.5 14.5 13.6 12.7 11.7 19.9 3.1 13.3 12.5 11.8 11.0 10.3

1750

72 38.3 3.1 4.7 3.5 2.2 - - 37.0 3.2 3.4 2.3 1.3 - -

67 31.5 3.0 10.2 8.9 7.7 6.4 - 29.4 3.1 8.7 7.6 6.5 5.5 -

62 22.9 3.0 17.9 16.7 15.4 14.1 12.9 21.4 3.1 16.3 15.2 14.2 13.1 12.0

57 21.9 2.9 19.0 18.3 17.0 15.8 14.5 20.2 3.1 16.9 16.6 15.5 14.5 13.4

2000

72 39.3 3.1 5.7 4.2 2.6 - - 37.5 3.2 4.2 2.8 1.5 - -

67 32.3 3.0 12.3 10.8 9.2 7.6 - 29.9 3.1 10.8 9.4 8.1 6.7 -

62 23.5 3.0 21.6 20.1 18.5 16.9 15.4 21.7 3.1 20.3 18.9 17.6 16.2 14.8

57 22.4 2.9 22.4 22.0 20.4 18.9 17.3 20.5 3.1 20.5 20.6 19.3 17.9 16.5

2250

72 39.1 3.1 6.5 4.7 3.0 - - 37.7 3.2 4.8 3.2 1.7 - -

67 32.1 3.0 13.9 12.1 10.4 8.6 - 30.0 3.1 12.4 10.8 9.3 7.7 -

62 23.4 2.9 22.5 21.7 19.9 18.2 16.4 21.8 3.1 21.1 20.4 18.9 17.3 15.7

57 22.3 2.9 22.3 22.1 20.4 18.6 16.9 20.6 3.1 20.6 20.7 19.1 17.5 16.0

2500

72 38.9 3.1 7.2 5.2 3.3 - - 37.9 3.2 5.4 3.6 1.9 - -

67 32.0 3.0 15.4 13.5 11.6 9.7 - 30.1 3.1 14.0 12.2 10.5 8.7 -

62 23.3 2.9 23.3 23.3 21.4 19.4 17.5 21.9 3.1 21.9 21.9 20.2 18.4 16.7

57 22.2 2.9 22.2 22.2 20.3 18.3 16.4 20.7 3.1 20.7 20.7 18.9 17.2 15.4

Page 77: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 77

75°F 85°F

1250

72 35.3 3.3 0.7 0.5 0.2 - - 34.9 3.3 - - - - -

67 27.2 3.2 2.8 2.6 2.4 2.1 - 25.8 3.3 1.3 1.3 1.2 1.1 -

62 19.7 3.2 5.9 5.7 5.4 5.2 5.0 18.7 3.3 3.7 3.6 3.6 3.5 3.4

1500

72 35.5 3.3 1.4 0.8 0.3 - - 34.5 3.3 0.2 - - - -

67 27.2 3.2 5.0 4.4 3.9 3.3 - 25.5 3.3 3.5 3.1 2.7 2.4 -

62 19.8 3.2 10.3 9.7 9.2 8.6 8.1 18.5 3.3 8.3 8.0 7.6 7.2 6.9

57 18.5 3.2 11.1 10.5 10.0 9.4 8.9 17.1 3.3 8.9 8.5 8.2 7.8 7.4

1750

72 35.6 3.3 2.0 1.2 0.3 - - 34.2 3.3 0.7 0.0 - - -

67 27.3 3.2 7.1 6.3 5.4 4.6 - 25.3 3.3 5.6 5.0 4.3 3.6 -

62 19.9 3.2 14.6 13.8 12.9 12.0 11.2 18.3 3.3 13.0 12.3 11.6 11.0 10.3

57 18.6 3.2 14.9 14.9 14.0 13.2 12.3 16.9 3.3 12.8 13.2 12.6 11.9 11.2

2000

72 35.7 3.3 2.7 1.5 0.3 - - 33.9 3.3 1.1 0.2 - - -

67 27.4 3.2 9.3 8.1 7.0 5.8 - 25.0 3.3 7.8 6.8 5.8 4.9 -

62 19.9 3.2 19.0 17.8 16.6 15.5 14.3 18.1 3.3 17.6 16.7 15.7 14.7 13.7

57 18.6 3.2 18.6 19.3 18.1 16.9 15.8 16.7 3.3 16.7 16.7 16.7 16.0 15.0

2250

72 36.3 3.3 3.1 1.8 0.4 - - 34.9 3.3 1.5 0.3 - - -

67 27.9 3.2 10.9 9.5 8.1 6.8 - 25.7 3.4 9.4 8.2 7.0 5.8 -

62 20.2 3.2 19.8 19.2 17.8 16.4 15.0 18.6 3.3 18.4 17.9 16.7 15.5 14.3

57 18.9 3.2 18.9 19.2 17.9 16.5 15.1 17.2 3.3 17.2 17.2 16.6 15.4 14.2

2500

72 36.9 3.3 3.6 2.0 0.4 - - 35.8 3.3 1.8 0.4 - - -

67 28.3 3.2 12.5 10.9 9.3 7.7 - 26.5 3.4 11.0 9.6 8.2 6.7 -

62 20.6 3.2 20.6 20.6 19.0 17.4 15.8 19.2 3.3 19.2 19.2 17.8 16.3 14.9

57 19.2 3.2 19.2 19.2 17.6 16.0 14.4 17.7 3.3 17.7 17.7 16.3 14.9 13.5

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR061 (5.0 Ton) Reheat (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

Page 78: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

78 Johnson Controls Ducted Systems

ZR078 (6.5 Ton) Cooling

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1625

77 99.9 5.1 39.3 33.2 27.1 - - - 90.5 5.8 36.9 30.8 24.7 - - -

72 91.5 5.0 50.3 44.2 38.1 32.1 - - 83.7 5.7 48.0 41.8 35.7 29.6 - -

67 83.0 5.0 61.3 55.2 49.2 43.1 37.0 - 76.9 5.7 59.0 52.9 46.8 40.7 34.5 -

62 72.4 4.9 72.4 70.1 60.9 54.9 48.8 42.7 68.7 5.7 68.7 66.7 57.6 51.5 45.4 39.3

1950

77 106.5 5.1 45.5 37.9 30.3 - - - 96.8 5.9 42.8 35.2 27.7 - - -

72 97.5 5.1 57.8 50.2 42.6 35.1 - - 89.5 5.8 55.1 47.6 40.0 32.5 - -

67 88.5 5.1 70.1 62.5 54.9 47.4 39.8 - 82.2 5.8 67.5 60.0 52.4 44.9 37.3 -

62 77.2 5.0 77.2 75.6 68.1 60.5 52.9 45.4 73.4 5.7 73.4 72.1 64.6 57.0 49.5 41.9

57 78.2 5.0 78.2 78.2 72.6 65.0 57.5 49.9 70.6 5.7 70.6 70.6 65.6 58.0 50.5 43.0

2275

77 113.1 5.2 51.6 42.6 33.5 - - - 103.0 5.9 48.6 39.6 30.7 - - -

72 103.5 5.2 65.2 56.2 47.1 38.0 - - 95.2 5.9 62.3 53.3 44.4 35.4 - -

67 93.9 5.1 78.8 69.8 60.7 51.6 42.6 - 87.5 5.8 76.0 67.0 58.1 49.1 40.1 -

62 81.9 5.1 81.9 81.2 75.2 66.2 57.1 48.0 78.1 5.8 78.1 77.5 71.5 62.6 53.6 44.6

57 83.1 5.1 83.1 83.1 80.3 71.2 62.1 53.1 75.2 5.8 75.2 75.2 72.7 63.7 54.7 45.8

2600

77 119.7 5.3 57.8 47.3 36.7 - - - 109.3 6.0 54.4 44.0 33.6 - - -

72 109.5 5.2 72.7 62.2 51.6 41.0 - - 101.0 6.0 69.5 59.1 48.7 38.3 - -

67 99.4 5.2 87.6 77.0 66.5 55.9 45.3 - 92.8 5.9 84.5 74.1 63.7 53.3 42.9 -

62 86.7 5.1 86.7 86.7 82.4 71.8 61.3 50.7 82.9 5.9 82.9 82.9 78.5 68.1 57.7 47.3

57 87.9 5.2 87.9 87.9 87.9 77.4 66.8 56.2 79.7 5.9 79.7 79.7 79.7 69.3 59.0 48.6

2925

72 109.6 5.2 74.8 64.0 53.1 42.2 - - 100.2 5.9 71.6 60.8 50.0 39.3 - -

67 99.5 5.1 91.9 79.3 68.4 57.5 46.7 - 92.0 5.9 87.0 76.3 65.5 54.7 44.0 -

62 86.8 5.1 86.8 86.8 84.6 73.8 62.9 52.0 82.2 5.8 82.2 82.2 80.0 69.3 58.5 47.7

57 88.0 5.1 88.0 88.0 88.0 77.1 66.2 55.3 79.1 5.8 79.1 79.1 79.1 68.3 57.6 46.8

3250

72 109.7 5.1 76.9 65.7 54.6 43.4 - - 99.4 5.8 73.7 62.5 51.4 40.3 - -

67 99.6 5.1 96.1 81.5 70.3 59.1 48.0 - 91.3 5.8 89.5 78.4 67.3 56.1 45.0 -

62 86.9 5.0 86.9 86.9 86.9 75.7 64.5 53.4 81.5 5.8 81.5 81.5 81.5 70.4 59.3 48.1

57 88.0 5.0 88.0 88.0 88.0 76.8 65.6 54.4 78.5 5.8 78.5 78.5 78.5 67.3 56.2 45.1

95°F 105°F

1625

77 81.2 6.5 34.6 28.4 22.3 - - - 76.9 7.3 31.0 26.2 20.1 - - -

72 75.9 6.5 45.6 39.5 33.3 27.2 - - 70.8 7.3 43.2 37.1 31.0 24.8 - -

67 70.7 6.4 56.7 50.5 44.4 38.2 32.1 - 64.7 7.2 55.3 47.9 41.8 35.7 29.6 -

62 64.9 6.4 64.9 63.3 54.3 48.1 42.0 35.8 59.4 7.2 59.4 58.5 49.9 43.8 37.7 31.6

1950

77 87.0 6.6 40.1 32.5 25.0 - - - 81.8 7.4 37.4 30.0 22.6 - - -

72 81.4 6.5 52.5 45.0 37.5 30.0 - - 75.3 7.4 49.6 42.2 34.8 27.4 - -

67 75.8 6.5 64.9 57.4 49.9 42.4 34.9 - 68.8 7.3 61.8 54.4 47.0 39.6 32.1 -

62 69.7 6.4 69.7 68.6 61.0 53.5 46.0 38.5 63.2 7.3 63.2 62.6 56.1 48.7 41.3 33.9

57 63.0 6.5 63.0 63.0 58.6 51.1 43.5 36.0 61.6 7.3 61.6 61.4 55.5 48.1 40.6 33.2

2275

77 92.9 6.7 45.5 36.7 27.8 - - - 86.7 7.5 43.8 33.8 25.1 - - -

72 87.0 6.6 59.3 50.5 41.6 32.8 - - 79.8 7.5 56.0 47.3 38.6 29.9 - -

67 81.0 6.6 73.2 64.3 55.4 46.6 37.7 - 73.0 7.4 68.3 60.9 52.2 43.5 34.7 -

62 74.4 6.5 74.4 73.8 67.8 59.0 50.1 41.2 67.0 7.3 67.0 66.7 62.3 53.6 44.9 36.2

57 67.3 6.5 67.3 67.3 65.1 56.2 47.3 38.5 65.2 7.4 65.2 65.1 61.6 52.9 44.2 35.5

2600

77 98.8 6.7 51.0 40.8 30.6 - - - 91.6 7.6 50.2 37.6 27.6 - - -

72 92.5 6.7 66.2 56.0 45.8 35.6 - - 84.3 7.6 62.5 52.5 42.5 32.5 - -

67 86.1 6.6 81.4 71.2 61.0 50.8 40.5 - 77.1 7.5 74.7 67.3 57.3 47.3 37.3 -

62 79.1 6.6 79.1 79.1 74.6 64.4 54.2 43.9 70.8 7.4 70.8 70.8 68.5 58.5 48.5 38.5

57 71.5 6.6 71.5 71.5 71.5 61.3 51.1 40.9 68.9 7.4 68.9 68.9 67.7 57.7 47.7 37.7

2925

72 90.8 6.6 68.3 57.6 47.0 36.3 - - 83.1 7.5 64.7 54.2 43.8 33.3 - -

67 84.5 6.6 82.2 73.2 62.6 51.9 41.3 - 75.9 7.4 74.8 69.1 59.1 48.7 38.2 -

62 77.6 6.5 77.6 77.6 75.4 64.7 54.1 43.4 69.7 7.4 69.7 69.7 68.6 58.1 47.7 37.2

57 70.2 6.6 70.2 70.2 70.2 59.6 48.9 38.3 67.9 7.4 67.9 67.9 67.3 56.8 46.4 35.9

3250

72 89.1 6.6 70.4 59.3 48.2 37.1 - - 81.8 7.4 66.9 56.0 45.1 34.2 - -

67 83.0 6.5 83.0 75.3 64.2 53.1 42.0 - 74.8 7.4 74.8 70.9 60.9 50.0 39.1 -

62 76.2 6.5 76.2 76.2 76.2 65.1 54.0 42.9 68.6 7.3 68.6 68.6 68.6 57.7 46.8 35.9

57 68.9 6.5 68.9 68.9 68.9 57.8 46.8 35.7 66.9 7.3 66.9 66.9 66.9 56.0 45.1 34.2

Page 79: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 79

115°F 125°F

1625

77 72.6 8.1 27.5 24.0 18.0 - - - 68.3 9.0 24.0 21.5 15.8 - - -

72 65.6 8.1 40.7 34.7 28.6 22.5 - - 60.4 8.9 38.3 32.2 26.2 20.2 - -

67 58.6 8.1 54.0 45.3 39.2 33.1 27.1 - 52.6 8.9 52.6 42.6 36.6 30.6 24.6 -

62 53.8 8.0 53.8 53.8 45.6 39.5 33.4 27.4 48.2 8.8 48.2 48.2 41.2 35.2 29.2 23.1

1950

77 76.5 8.2 34.8 27.5 20.2 - - - 71.2 9.1 33.0 25.0 17.8 - - -

72 69.1 8.2 46.7 39.4 32.1 24.8 - - 63.0 9.0 43.9 36.6 29.4 22.2 - -

67 61.8 8.2 58.7 51.4 44.0 36.7 29.4 - 54.7 9.0 54.7 48.3 41.1 33.9 26.7 -

62 56.7 8.1 56.7 56.7 51.2 43.9 36.6 29.3 50.2 8.9 50.2 50.2 46.3 39.1 31.9 24.7

57 60.1 8.1 60.1 59.7 52.4 45.1 37.7 30.4 58.7 8.9 58.7 58.0 49.3 42.1 34.8 27.6

2275

77 80.4 8.4 42.1 31.0 22.4 - - - 74.1 9.2 42.0 28.4 19.7 - - -

72 72.7 8.3 52.7 44.2 35.6 27.1 - - 65.5 9.2 49.4 41.0 32.6 24.2 - -

67 64.9 8.3 63.4 57.4 48.9 40.3 31.8 - 56.9 9.1 56.9 54.0 45.6 37.2 28.8 -

62 59.6 8.2 59.6 59.6 56.8 48.3 39.7 31.2 52.2 9.0 52.2 52.2 51.4 43.0 34.6 26.2

57 63.2 8.2 63.2 63.0 58.1 49.6 41.0 32.5 61.2 9.0 61.2 60.8 54.7 46.3 37.9 29.5

2600

77 84.3 8.5 49.4 34.4 24.6 - - - 77.1 9.3 51.0 31.8 21.6 - - -

72 76.2 8.4 58.8 49.0 39.2 29.4 - - 68.1 9.3 55.0 45.4 35.9 26.3 - -

67 68.1 8.4 68.1 63.5 53.7 43.9 34.1 - 59.1 9.2 59.1 59.1 50.1 40.5 30.9 -

62 62.5 8.3 62.5 62.5 62.5 52.7 42.9 33.1 54.2 9.1 54.2 54.2 54.2 46.8 37.2 27.7

57 66.3 8.3 66.3 66.3 63.9 54.1 44.3 34.5 63.6 9.1 63.6 63.6 60.0 50.5 40.9 31.3

2925

72 75.4 8.3 61.1 50.8 40.6 30.3 - - 67.6 9.2 57.5 47.4 37.4 27.3 - -

67 67.3 8.3 67.3 65.0 55.7 45.4 35.1 - 58.7 9.2 58.7 58.7 52.2 42.1 32.1 -

62 61.8 8.2 61.8 61.8 61.8 51.5 41.3 31.0 53.8 9.0 53.8 53.8 53.8 44.9 34.9 24.8

57 65.5 8.2 65.5 65.5 64.3 54.1 43.8 33.6 63.2 9.0 63.2 63.2 61.4 51.3 41.3 31.2

3250

72 74.5 8.3 63.4 52.7 42.0 31.3 - - 67.2 9.1 59.9 49.4 38.9 28.3 - -

67 66.6 8.2 66.6 66.6 57.6 46.9 36.2 - 58.4 9.1 58.4 58.4 54.3 43.7 33.2 -

62 61.1 8.1 61.1 61.1 61.1 50.4 39.7 28.9 53.5 8.9 53.5 53.5 53.5 43.0 32.5 22.0

57 64.8 8.1 64.8 64.8 64.8 54.1 43.4 32.7 62.7 9.0 62.7 62.7 62.7 52.2 41.7 31.2

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR078 (6.5 Ton) Cooling (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 80: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

80 Johnson Controls Ducted Systems

ZR078 (6.5 Ton) Reheat

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

35°F 45°F

1625

72 31.6 4.5 1.6 1.5 1.5 - - 34.9 5.1 - - - - -

67 32.2 4.6 1.5 1.5 1.4 1.4 - 35.2 4.9 2.5 2.2 1.9 1.7 -

62 28.5 4.4 1.6 1.6 1.5 1.5 1.4 32.0 4.9 5.2 4.9 4.6 4.4 4.1

1950

72 36.1 4.3 2.2 1.6 0.9 - - 37.2 4.9 - - - - -

67 36.7 4.5 6.6 5.9 5.3 4.6 - 37.6 4.7 6.2 5.6 4.9 4.2 -

62 32.6 4.3 10.8 10.1 9.4 8.8 8.1 34.2 4.7 13.0 12.4 11.7 11.1 10.4

57 34.2 4.4 17.1 16.4 15.8 15.1 14.5 34.5 4.7 18.2 17.6 16.9 16.3 15.6

2275

72 40.5 4.2 2.9 1.7 0.4 - - 39.6 4.7 - - - - -

67 41.2 4.3 11.6 10.4 9.1 7.8 - 39.9 4.5 9.9 8.9 7.9 6.8 -

62 36.7 4.2 19.9 18.6 17.4 16.1 14.8 36.3 4.5 20.9 19.8 18.8 17.8 16.7

57 38.3 4.2 29.8 29.5 28.2 26.9 25.7 36.6 4.5 28.5 28.2 27.2 26.1 25.1

2600

72 45.0 4.1 3.6 1.7 -0.1 - - 41.9 4.5 - - - - -

67 45.7 4.2 16.7 14.8 12.9 11.1 - 42.3 4.3 13.7 12.3 10.8 9.4 -

62 40.8 4.0 29.0 27.1 25.3 23.4 21.6 38.4 4.3 28.7 27.3 25.9 24.5 23.1

57 42.5 4.1 42.5 42.5 40.6 38.7 36.9 38.8 4.4 38.8 38.8 37.4 36.0 34.5

2925

72 42.5 4.0 4.6 2.8 1.0 - - 40.8 4.6 - - - - -

67 43.2 4.1 17.5 15.7 13.9 12.1 - 41.1 4.4 15.2 13.7 12.2 10.8 -

62 38.5 4.0 31.6 29.1 27.3 25.5 23.7 37.4 4.4 32.0 30.5 29.1 27.6 26.1

57 40.2 4.0 40.2 40.2 38.3 36.5 34.7 37.7 4.4 37.7 37.7 36.2 34.8 33.3

3250

72 40.0 3.9 5.7 3.9 2.1 - - 39.6 4.6 - - - - -

67 40.6 4.0 18.4 16.6 14.8 13.0 - 40.0 4.4 16.7 15.2 13.6 12.1 -

62 36.2 3.9 34.2 31.1 29.3 27.5 25.8 36.3 4.4 35.3 33.8 32.3 30.7 29.2

57 37.9 4.0 37.9 37.9 36.1 34.3 32.5 36.7 4.5 36.7 36.7 35.1 33.6 32.0

55°F 65°F

1625

72 38.2 5.7 - - - - - 36.3 5.7 - - - - -

67 38.2 5.1 3.4 2.9 2.4 1.9 - 36.2 5.3 2.4 2.1 1.8 1.5 -

62 35.5 5.3 8.8 8.3 7.8 7.3 6.7 33.1 5.2 6.5 6.2 5.9 5.6 5.3

1950

72 38.4 5.5 - - - - - 36.8 5.6 - - - - -

67 38.4 4.9 5.8 5.2 4.5 3.9 - 36.7 5.2 4.9 4.3 3.8 3.2 -

62 35.7 5.1 15.3 14.7 14.0 13.3 12.7 33.5 5.0 13.9 13.3 12.7 12.2 11.6

57 34.7 5.1 19.4 18.7 18.1 17.4 16.8 32.9 5.0 17.0 16.5 15.9 15.3 14.8

2275

72 38.6 5.2 - - - - - 37.3 5.4 - - - - -

67 38.6 4.7 8.3 7.5 6.6 5.8 - 37.2 5.0 7.4 6.6 5.8 5.0 -

62 35.9 4.9 21.9 21.0 20.2 19.4 18.6 34.0 4.9 21.2 20.4 19.6 18.8 18.0

57 34.9 4.8 27.2 26.9 26.1 25.3 24.5 33.4 4.9 25.4 25.2 24.3 23.5 22.7

2600

72 38.8 5.0 - - - - - 37.8 5.3 - - - - -

67 38.9 4.4 10.7 9.7 8.8 7.8 - 37.7 4.9 9.9 8.9 7.8 6.8 -

62 36.1 4.6 28.4 27.4 26.5 25.5 24.6 34.4 4.8 28.5 27.5 26.4 25.3 24.3

57 35.1 4.6 35.1 35.1 34.1 33.2 32.2 33.8 4.8 33.8 33.8 32.8 31.7 30.7

2925

72 39.0 5.2 - - - - - 38.0 5.4 - - - - -

67 39.1 4.6 12.9 11.7 10.6 9.5 - 38.0 5.0 12.2 10.9 9.7 8.4 -

62 36.3 4.8 32.4 32.0 30.8 29.7 28.6 34.6 4.9 31.7 31.2 29.9 28.7 27.4

57 35.3 4.8 35.3 35.3 34.2 33.0 31.9 34.1 4.9 34.1 34.1 32.8 31.6 30.3

3250

72 39.2 5.3 - - - - - 38.2 5.5 - - - - -

67 39.3 4.8 15.0 13.7 12.5 11.2 - 38.2 5.0 14.4 13.0 11.6 10.1 -

62 36.5 5.0 36.5 36.5 35.2 33.9 32.6 34.8 4.9 34.8 34.8 33.4 32.0 30.5

57 35.5 5.0 35.5 35.5 34.2 32.9 31.6 34.3 4.9 34.3 34.3 32.8 31.4 29.9

Page 81: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 81

75°F 85°F

1625

72 34.3 5.7 - - - - - 32.4 5.6 - - - - -

67 34.2 5.4 1.3 1.2 1.1 1.0 - 32.2 5.6 0.3 0.4 0.5 0.6 -

62 30.6 5.0 4.3 4.2 4.1 4.0 3.9 28.2 4.8 2.1 2.2 2.2 2.3 2.4

1950

72 35.1 5.7 - - - - - 33.5 5.8 - - - - -

67 35.0 5.4 4.0 3.5 3.0 2.6 - 33.3 5.7 3.0 2.7 2.3 1.9 -

62 31.3 5.0 12.4 12.0 11.5 11.0 10.6 29.1 4.9 11.0 10.6 10.3 9.9 9.5

57 31.2 5.0 14.6 14.2 13.7 13.3 12.8 29.4 4.9 12.2 11.9 11.5 11.2 10.8

2275

72 35.9 5.7 - - - - - 34.5 5.9 - - - - -

67 35.8 5.4 6.6 5.8 5.0 4.2 - 34.4 5.8 5.7 4.9 4.1 3.3 -

62 32.0 5.0 20.5 19.7 18.9 18.1 17.3 30.1 5.1 19.9 19.1 18.3 17.4 16.6

57 31.9 5.0 23.6 23.4 22.6 21.8 21.0 30.4 5.0 21.8 21.6 20.8 20.0 19.2

2600

72 36.7 5.7 - - - - - 35.6 6.0 - - - - -

67 36.6 5.4 9.2 8.1 6.9 5.7 - 35.5 5.9 8.5 7.2 6.0 4.7 -

62 32.7 5.0 28.7 27.5 26.3 25.2 24.0 31.0 5.2 28.8 27.5 26.3 25.0 23.8

57 32.6 5.0 32.6 32.6 31.4 30.3 29.1 31.3 5.2 31.3 31.3 30.1 28.8 27.6

2925

72 37.0 5.6 - - - - - 35.9 5.8 - - - - -

67 36.9 5.4 11.5 10.2 8.8 7.4 - 35.8 5.8 10.9 9.4 7.9 6.4 -

62 33.0 4.9 30.9 30.4 29.0 27.6 26.2 31.3 5.0 30.2 29.6 28.0 26.5 25.0

57 32.8 4.9 32.8 32.8 31.5 30.1 28.7 31.6 5.0 31.6 31.6 30.1 28.6 27.1

3250

72 37.2 5.6 - - - - - 36.2 5.7 - - - - -

67 37.1 5.3 13.9 12.3 10.7 9.1 - 36.1 5.6 13.3 11.5 9.8 8.0 -

62 33.2 4.9 33.2 33.2 31.6 30.0 28.4 31.6 4.9 31.6 31.6 29.8 28.1 26.3

57 33.1 4.9 33.1 33.1 31.5 29.9 28.3 31.9 4.9 31.9 31.9 30.1 28.4 26.6

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR078 (6.5 Ton) Reheat (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

Page 82: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

82 Johnson Controls Ducted Systems

ZR090 (7.5 Ton) Cooling

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

1875

77 95.3 5.1 41.7 33.4 25.0 - - - 98.4 5.8 42.5 34.5 26.4 - - -

72 88.9 5.0 49.7 41.3 33.0 24.6 - - 91.0 5.8 52.7 44.7 36.7 28.6 - -

67 82.4 4.9 57.7 49.3 41.0 32.6 24.2 - 83.6 5.7 63.0 54.9 46.9 38.9 30.8 -

62 72.3 4.9 72.3 63.4 49.7 41.3 32.9 24.6 74.5 5.7 74.5 70.1 57.5 49.5 41.5 33.4

2250

77 104.3 5.1 50.1 40.6 31.2 - - - 104.3 5.9 49.0 39.9 30.7 - - -

72 97.2 5.0 60.3 50.9 41.4 32.0 - - 96.4 5.8 60.9 51.8 42.6 33.5 - -

67 90.1 5.0 70.6 61.1 51.7 42.2 32.8 - 88.5 5.8 72.8 63.7 54.5 45.4 36.3 -

62 79.1 4.9 79.1 73.2 62.8 53.3 43.9 34.4 79.0 5.7 79.0 76.0 66.9 57.8 48.6 39.5

57 76.9 4.9 76.9 74.8 63.8 54.3 44.9 35.4 77.6 5.7 77.6 76.5 67.4 58.3 49.1 40.0

2625

77 113.3 5.2 58.4 47.9 37.4 - - - 110.2 5.9 55.5 45.3 35.0 - - -

72 105.5 5.1 70.9 60.4 49.9 39.4 - - 101.9 5.8 69.1 58.9 48.6 38.4 - -

67 97.8 5.0 83.4 72.9 62.4 51.9 41.3 - 93.5 5.8 82.7 72.4 62.2 52.0 41.7 -

62 85.9 5.0 85.9 82.9 75.8 65.3 54.8 44.3 83.4 5.7 83.4 82.0 76.3 66.1 55.8 45.6

57 83.6 5.0 83.6 82.5 77.0 66.5 55.9 45.4 82.0 5.7 82.0 81.4 76.9 66.6 56.4 46.2

3000

77 122.2 5.2 66.8 55.2 43.6 - - - 116.0 5.9 62.0 50.7 39.4 - - -

72 113.8 5.1 81.6 69.9 58.3 46.7 - - 107.3 5.9 77.3 65.9 54.6 43.3 - -

67 105.4 5.1 96.3 84.7 73.1 61.5 49.9 - 98.5 5.8 92.5 81.2 69.9 58.5 47.2 -

62 92.7 5.0 92.7 92.7 88.9 77.3 65.7 54.1 87.9 5.8 87.9 87.9 85.7 74.3 63.0 51.7

57 90.2 5.0 90.2 90.2 90.2 78.6 67.0 55.4 86.3 5.8 86.3 86.3 86.3 75.0 63.7 52.3

3375

72 116.9 5.2 86.8 74.3 61.8 49.4 - - 109.2 5.9 82.5 70.2 58.0 45.8 - -

67 108.2 5.1 103.7 89.9 77.5 65.0 52.5 - 100.3 5.8 97.3 86.4 74.2 62.0 49.7 -

62 95.1 5.1 95.1 95.1 93.3 80.8 68.4 55.9 89.4 5.8 89.4 89.4 88.3 76.1 63.9 51.6

57 92.7 5.1 92.7 92.7 92.7 80.2 67.7 55.3 87.9 5.8 87.9 87.9 87.9 75.6 63.4 51.2

3750

72 119.9 5.2 92.0 78.7 65.3 52.0 - - 111.1 5.9 87.7 74.5 61.4 48.3 - -

67 111.0 5.1 111.0 95.2 81.9 68.5 55.2 - 102.0 5.8 102.0 91.7 78.5 65.4 52.3 -

62 97.6 5.1 97.6 97.6 97.6 84.3 71.0 57.7 91.0 5.8 91.0 91.0 91.0 77.9 64.7 51.6

57 95.1 5.1 95.1 95.1 95.1 81.8 68.4 55.1 89.4 5.8 89.4 89.4 89.4 76.3 63.1 50.0

95°F 105°F

1875

77 101.5 6.6 43.2 35.6 27.9 - - - 94.5 7.5 39.4 33.0 25.5 - - -

72 93.1 6.6 55.7 48.0 40.3 32.7 - - 86.4 7.5 52.8 45.3 37.7 30.2 - -

67 84.7 6.5 68.2 60.5 52.8 45.1 37.4 - 78.3 7.5 66.2 57.5 50.0 42.5 34.9 -

62 76.8 6.5 76.8 76.8 65.4 57.7 50.0 42.3 71.2 7.4 71.2 71.2 60.6 53.1 45.5 38.0

2250

77 104.3 6.6 47.9 39.1 30.3 - - - 96.9 7.5 45.1 36.4 27.7 - - -

72 95.7 6.6 61.5 52.7 43.9 35.0 - - 88.5 7.5 58.4 49.7 41.0 32.3 - -

67 87.0 6.5 75.0 66.2 57.4 48.6 39.8 - 80.2 7.4 71.7 63.0 54.3 45.6 36.9 -

62 78.9 6.5 78.9 78.9 71.0 62.2 53.4 44.6 73.0 7.4 73.0 73.0 65.8 57.1 48.4 39.7

57 78.3 6.5 78.3 78.3 71.1 62.2 53.4 44.6 73.0 7.4 73.0 73.0 66.1 57.4 48.7 40.0

2625

77 107.1 6.6 52.6 42.6 32.7 - - - 99.2 7.5 50.7 39.7 29.8 - - -

72 98.2 6.6 67.2 57.3 47.4 37.4 - - 90.6 7.5 63.9 54.1 44.2 34.3 - -

67 89.3 6.5 81.9 72.0 62.0 52.1 42.1 - 82.1 7.4 77.1 68.4 58.6 48.7 38.8 -

62 81.0 6.5 81.0 81.0 76.7 66.8 56.9 46.9 74.7 7.4 74.7 74.7 70.9 61.1 51.2 41.4

57 80.4 6.5 80.4 80.4 76.7 66.8 56.9 46.9 74.8 7.4 74.8 74.8 71.3 61.4 51.6 41.7

3000

77 109.9 6.6 57.3 46.2 35.1 - - - 101.5 7.5 56.4 43.0 32.0 - - -

72 100.7 6.6 73.0 61.9 50.9 39.8 - - 92.7 7.5 69.5 58.5 47.4 36.4 - -

67 91.6 6.5 88.7 77.7 66.6 55.6 44.5 - 84.0 7.4 82.6 73.9 62.8 51.8 40.8 -

62 83.1 6.5 83.1 83.1 82.4 71.4 60.3 49.2 76.5 7.4 76.5 76.5 76.1 65.1 54.1 43.0

57 82.4 6.5 82.4 82.4 82.4 71.4 60.3 49.3 76.5 7.4 76.5 76.5 76.5 65.5 54.4 43.4

3375

72 101.5 6.6 78.2 66.2 54.2 42.2 - - 93.0 7.4 74.7 62.7 50.8 38.8 - -

67 92.3 6.5 90.9 82.9 70.9 58.9 46.9 - 84.3 7.4 83.5 78.0 67.3 55.3 43.4 -

62 83.7 6.5 83.7 83.7 83.4 71.4 59.4 47.4 76.7 7.4 76.7 76.7 76.5 64.6 52.6 40.6

57 83.1 6.5 83.1 83.1 83.1 71.1 59.1 47.1 76.7 7.4 76.7 76.7 76.7 64.8 52.8 40.8

3750

72 102.3 6.6 83.3 70.4 57.5 44.5 - - 93.3 7.4 79.9 67.0 54.1 41.2 - -

67 93.0 6.6 93.0 88.2 75.2 62.3 49.4 - 84.5 7.4 84.5 82.1 71.7 58.8 46.0 -

62 84.3 6.5 84.3 84.3 84.3 71.4 58.5 45.5 76.9 7.4 76.9 76.9 76.9 64.0 51.1 38.2

57 83.7 6.5 83.7 83.7 83.7 70.7 57.8 44.9 76.9 7.4 76.9 76.9 76.9 64.0 51.1 38.3

Page 83: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 83

115°F 125°F

1875

77 87.6 8.4 35.5 30.5 23.1 - - - 80.6 9.2 30.9 27.9 20.7 - - -

72 79.7 8.4 49.9 42.5 35.1 27.8 - - 73.0 9.2 47.0 39.8 32.5 25.3 - -

67 71.9 8.4 64.3 54.6 47.2 39.8 32.4 - 65.5 9.3 62.3 51.6 44.4 37.2 29.9 -

62 65.7 8.3 65.7 65.7 55.8 48.4 41.1 33.7 60.2 9.3 60.2 60.2 51.0 43.8 36.6 29.4

2250

77 89.4 8.3 42.2 33.6 25.0 - - - 82.0 9.2 39.3 30.9 22.4 - - -

72 81.4 8.3 55.2 46.7 38.1 29.5 - - 74.3 9.2 52.1 43.7 35.2 26.7 - -

67 73.4 8.4 68.3 59.7 51.1 42.6 34.0 - 66.6 9.3 64.9 56.5 48.0 39.5 31.1 -

62 67.1 8.3 67.1 67.1 60.5 51.9 43.3 34.7 61.2 9.2 61.2 61.2 55.2 46.7 38.3 29.8

57 67.8 8.3 67.8 67.8 61.1 52.5 43.9 35.4 62.5 9.2 62.5 62.5 56.1 47.7 39.2 30.7

2625

77 91.2 8.3 48.9 36.8 27.0 - - - 83.3 9.2 47.7 33.8 24.1 - - -

72 83.1 8.3 60.6 50.8 41.0 31.2 - - 75.5 9.2 57.3 47.6 37.9 28.2 - -

67 74.9 8.3 72.3 64.9 55.1 45.3 35.5 - 67.7 9.2 67.6 61.3 51.6 41.9 32.2 -

62 68.5 8.3 68.5 68.5 65.2 55.4 45.6 35.8 62.2 9.2 62.2 62.2 59.4 49.7 40.0 30.2

57 69.2 8.3 69.2 69.2 65.8 56.0 46.3 36.5 63.6 9.2 63.6 63.6 60.4 50.7 40.9 31.2

3000

77 93.1 8.3 55.5 39.9 28.9 - - - 84.7 9.2 56.1 36.7 25.8 - - -

72 84.7 8.3 66.0 55.0 44.0 33.0 - - 76.7 9.2 62.4 51.5 40.5 29.6 - -

67 76.4 8.3 76.4 70.0 59.1 48.1 37.1 - 68.8 9.2 68.8 66.2 55.3 44.3 33.4 -

62 69.8 8.3 69.8 69.8 69.8 58.8 47.9 36.9 63.2 9.2 63.2 63.2 63.2 52.6 41.6 30.7

57 70.6 8.3 70.6 70.6 70.6 59.6 48.6 37.6 64.6 9.2 64.6 64.6 64.6 53.6 42.7 31.7

3375

72 84.5 8.3 71.2 59.3 47.4 35.5 - - 76.0 9.2 67.8 55.9 44.0 32.1 - -

67 76.2 8.3 76.2 73.0 63.6 51.7 39.8 - 68.1 9.2 68.1 68.1 60.0 48.1 36.2 -

62 69.6 8.3 69.6 69.6 69.6 57.7 45.8 33.9 62.6 9.2 62.6 62.6 62.6 50.9 39.0 27.1

57 70.4 8.3 70.4 70.4 70.4 58.4 46.5 34.6 64.0 9.1 64.0 64.0 64.0 52.1 40.3 28.4

3750

72 84.3 8.3 76.5 63.7 50.8 38.0 - - 75.3 9.1 73.1 60.3 47.5 34.7 - -

67 76.0 8.3 76.0 76.0 68.2 55.4 42.5 - 67.5 9.2 67.5 67.5 64.7 51.9 39.1 -

62 69.5 8.3 69.5 69.5 69.5 56.6 43.8 30.9 62.0 9.2 62.0 62.0 62.0 49.2 36.4 23.6

57 70.2 8.2 70.2 70.2 70.2 57.3 44.5 31.6 63.4 9.1 63.4 63.4 63.4 50.6 37.8 25.0

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR090 (7.5 Ton) Cooling (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 84: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

84 Johnson Controls Ducted Systems

ZR090 (7.5 Ton) Reheat

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

35°F 45°F

1875

77 57.4 4.6 - - - - - - 58.7 4.9 - - - - - -

72 54.9 4.4 7.7 6.3 4.9 3.5 - - 54.6 4.7 5.8 4.5 3.2 1.9 - -

67 52.4 4.3 14.9 13.5 12.1 10.7 9.3 - 50.5 4.5 13.7 12.4 11.1 9.9 8.6 -

62 48.7 4.1 21.7 20.3 18.9 17.5 16.1 14.7 46.6 4.3 21.9 20.7 19.4 18.1 16.8 15.5

2250

77 62.8 4.5 - - - - - - 62.7 4.8 - - - - - -

72 60.0 4.4 11.2 9.1 7.0 4.9 - - 58.3 4.6 8.3 6.4 4.6 2.7 - -

67 57.2 4.2 22.2 20.1 18.0 15.9 13.8 - 53.9 4.4 19.6 17.7 15.9 14.0 12.1 -

62 53.0 4.0 32.6 30.5 28.4 26.3 24.2 22.1 49.8 4.2 31.3 29.4 27.6 25.7 23.8 22.0

57 49.6 4.0 37.1 35.0 32.9 30.8 28.7 26.6 47.9 4.2 36.2 34.3 32.5 30.6 28.8 26.9

2625

77 68.1 4.5 - - - - - - 66.6 4.8 - - - - - -

72 65.0 4.3 14.8 12.0 9.2 6.4 - - 62.0 4.6 10.8 8.4 5.9 3.5 - -

67 61.9 4.2 29.5 26.7 23.9 21.1 18.3 - 57.3 4.4 25.4 23.0 20.6 18.1 15.7 -

62 57.4 4.0 43.6 40.8 38.0 35.2 32.4 29.6 53.0 4.2 40.6 38.2 35.8 33.3 30.9 28.5

57 53.7 3.9 47.5 46.4 44.0 41.2 38.4 35.6 50.9 4.1 45.1 44.1 42.1 39.7 37.3 34.8

3000

77 73.4 4.5 - - - - - - 70.6 4.8 - - - - - -

72 70.0 4.3 18.4 14.9 11.4 7.9 - - 65.7 4.6 13.3 10.3 7.3 4.3 - -

67 66.6 4.2 36.8 33.3 29.8 26.3 22.8 - 60.8 4.4 31.3 28.3 25.3 22.3 19.3 -

62 61.8 4.0 54.5 51.0 47.5 44.0 40.5 37.0 56.1 4.2 50.0 47.0 44.0 40.9 37.9 34.9

57 57.8 3.9 57.8 57.8 55.1 51.6 48.1 44.6 54.0 4.1 54.0 54.0 51.8 48.8 45.8 42.8

3375

72 71.8 4.3 18.9 15.5 12.1 8.6 - - 67.4 4.6 14.3 11.1 7.9 4.7 - -

67 68.3 4.2 37.5 34.0 30.6 27.2 23.8 - 62.3 4.4 33.7 30.5 27.3 24.1 20.9 -

62 63.3 4.0 58.3 53.2 48.3 44.9 41.4 38.0 57.6 4.2 53.8 50.6 47.4 44.2 41.0 37.8

57 59.3 3.9 59.3 59.3 57.9 54.5 51.1 47.6 55.3 4.1 55.3 55.3 54.3 51.1 47.9 44.7

3750

72 73.5 4.3 19.4 16.1 12.7 9.4 - - 69.1 4.6 15.2 11.8 8.4 5.1 - -

67 69.9 4.2 38.2 34.8 31.4 28.1 24.7 - 63.9 4.4 36.0 32.6 29.3 25.9 22.5 -

62 64.9 4.0 62.1 55.3 49.1 45.7 42.4 39.0 59.0 4.2 57.6 54.3 50.9 47.5 44.1 40.7

57 60.7 3.9 60.7 60.7 60.7 57.4 54.0 50.6 56.7 4.1 56.7 56.7 56.7 53.3 50.0 46.6

55°F 65°F

1875

77 59.9 5.1 - - - - - - 57.9 5.4 - - - - - -

72 54.2 4.9 3.9 2.7 1.6 - - - 51.6 5.2 1.5 - - - - -

67 48.5 4.7 12.6 11.4 10.2 9.0 7.9 - 45.3 5.0 11.0 10.0 9.0 7.9 6.9 -

62 44.6 4.5 22.2 21.0 19.9 18.7 17.5 16.4 42.1 4.8 22.4 21.4 20.4 19.3 18.3 17.3

2250

77 62.6 5.1 - - - - - - 59.7 5.4 - - - - - -

72 56.6 4.9 5.4 3.7 2.1 - - - 53.2 5.2 2.2 - - - - -

67 50.7 4.7 17.0 15.4 13.7 12.1 10.5 - 46.6 4.9 14.3 12.9 11.6 10.2 8.9 -

62 46.6 4.5 29.9 28.3 26.7 25.1 23.5 21.8 43.4 4.7 28.8 27.5 26.1 24.7 23.4 22.0

57 46.2 4.4 35.3 33.7 32.1 30.4 28.8 27.2 42.7 4.7 33.5 32.2 30.8 29.4 28.1 26.7

2625

77 65.2 5.1 - - - - - - 61.4 5.4 - - - - - -

72 59.0 4.9 6.8 4.7 2.7 - - - 54.7 5.1 2.9 1.2 - - - -

67 52.8 4.6 21.4 19.3 17.3 15.2 13.1 - 48.0 4.9 17.6 15.9 14.2 12.5 10.8 -

62 48.5 4.4 37.7 35.6 33.6 31.5 29.4 27.3 44.7 4.7 35.2 33.5 31.8 30.1 28.4 26.7

57 48.1 4.4 42.7 41.9 40.3 38.2 36.1 34.1 43.9 4.6 39.3 38.7 37.6 35.9 34.2 32.5

3000

77 67.8 5.1 - - - - - - 63.1 5.3 - - - - - -

72 61.4 4.8 8.2 5.7 3.2 - - - 56.2 5.1 3.6 1.5 - - - -

67 54.9 4.6 25.8 23.3 20.8 18.3 15.7 - 49.4 4.9 20.9 18.9 16.8 14.7 12.7 -

62 50.5 4.4 45.4 42.9 40.4 37.9 35.4 32.8 45.9 4.7 41.7 39.6 37.6 35.5 33.5 31.4

57 50.1 4.3 50.1 50.1 48.5 46.0 43.4 40.9 45.2 4.6 45.2 45.2 44.4 42.3 40.3 38.2

3375

72 63.0 4.8 9.6 6.6 3.7 - - - 57.9 5.1 4.1 1.5 - - - -

67 56.4 4.6 29.8 26.9 23.9 21.0 18.0 - 50.8 4.9 25.7 23.2 20.6 18.0 15.5 -

62 51.8 4.4 49.3 48.0 46.5 43.6 40.6 37.6 47.3 4.7 45.2 44.1 43.0 40.4 37.9 35.3

57 51.4 4.3 51.4 51.4 50.6 47.6 44.7 41.7 46.5 4.6 46.5 46.5 46.1 43.6 41.0 38.4

3750

72 64.6 4.8 11.0 7.6 4.2 - - - 59.6 5.1 4.6 1.5 - - - -

67 57.9 4.6 33.9 30.5 27.1 23.7 20.3 - 52.3 4.9 30.5 27.5 24.4 21.3 18.2 -

62 53.2 4.4 53.2 53.2 52.7 49.3 45.9 42.5 48.7 4.7 48.7 48.7 48.4 45.3 42.2 39.2

57 52.7 4.3 52.7 52.7 52.7 49.3 45.9 42.5 47.9 4.6 47.9 47.9 47.9 44.8 41.7 38.6

Page 85: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 85

75°F 85°F

1875

77 56.0 5.7 - - - - - - 54.0 6.0 - - - - - -

72 49.0 5.5 - - - - - - 46.3 5.8 - - - - - -

67 42.0 5.2 9.4 8.6 7.7 6.8 6.0 - 38.7 5.5 7.8 7.1 6.4 5.8 5.1 -

62 39.6 5.0 22.6 21.7 20.9 20.0 19.1 18.3 37.2 5.3 22.7 22.0 21.3 20.7 20.0 19.3

2250

77 56.8 5.7 - - - - - - 53.9 6.0 - - - - - -

72 49.7 5.5 - - - - - - 46.2 5.7 - - - - - -

67 42.6 5.2 11.6 10.5 9.4 8.3 7.2 - 38.6 5.5 8.9 8.1 7.3 6.4 5.6 -

62 40.2 5.0 27.7 26.6 25.5 24.4 23.3 22.2 37.0 5.3 26.5 25.7 24.9 24.0 23.2 22.4

57 39.2 4.9 31.7 30.6 29.5 28.4 27.3 26.2 35.6 5.2 30.0 29.1 28.3 27.4 26.6 25.8

2625

77 57.6 5.7 - - - - - - 53.8 5.9 - - - - - -

72 50.4 5.4 - - - - - - 46.1 5.7 - - - - - -

67 43.2 5.2 13.8 12.5 11.1 9.8 8.4 - 38.4 5.5 10.0 9.0 8.1 7.1 6.1 -

62 40.8 5.0 32.8 31.5 30.1 28.8 27.4 26.1 36.9 5.3 30.4 29.4 28.4 27.4 26.4 25.5

57 39.7 4.9 36.0 35.5 34.9 33.6 32.2 30.9 35.5 5.2 32.7 32.2 32.2 31.2 30.3 29.3

3000

77 58.4 5.6 - - - - - - 53.6 5.9 - - - - - -

72 51.1 5.4 - - - - - - 45.9 5.7 - - - - - -

67 43.8 5.2 16.0 14.4 12.8 11.2 9.7 - 38.2 5.4 11.1 10.0 8.9 7.7 6.6 -

62 41.4 5.0 37.9 36.3 34.7 33.2 31.6 30.0 36.8 5.3 34.2 33.0 31.9 30.8 29.7 28.5

57 40.3 4.9 40.3 40.3 40.3 38.7 37.1 35.5 35.4 5.2 35.4 35.4 35.4 35.0 33.9 32.8

3375

72 52.8 5.4 - - - - - - 47.7 5.7 - - - - - -

67 45.3 5.2 21.6 19.4 17.3 15.1 12.9 - 39.7 5.4 17.5 15.7 13.9 12.2 10.4 -

62 42.8 5.0 41.0 40.2 39.4 37.3 35.1 32.9 38.2 5.2 36.9 36.3 35.9 34.1 32.4 30.6

57 41.6 4.9 41.6 41.6 41.6 39.5 37.3 35.1 36.7 5.2 36.7 36.7 36.7 35.4 33.6 31.8

3750

72 54.5 5.4 - - - - - - 49.5 5.6 - - - - - -

67 46.8 5.1 27.2 24.4 21.7 18.9 16.2 - 41.2 5.4 23.9 21.4 19.0 16.6 14.1 -

62 44.1 4.9 44.1 44.1 44.1 41.4 38.6 35.9 39.6 5.2 39.6 39.6 39.6 37.5 35.0 32.6

57 43.0 4.9 43.0 43.0 43.0 40.2 37.5 34.7 38.1 5.1 38.1 38.1 38.1 35.7 33.3 30.8

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR090 (7.5 Ton) Reheat (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 86: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

86 Johnson Controls Ducted Systems

ZR102 (8.5 Ton) Cooling

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

2125

77 121.9 6.4 54.3 43.2 32.9 - - - 118.7 7.4 52.3 42.1 32.0 - - -

72 118.1 6.4 71.1 60.8 50.5 40.2 - - 112.8 7.3 69.0 58.8 48.6 38.5 - -

67 114.3 6.3 87.8 78.4 68.1 57.8 47.5 - 106.9 7.2 85.6 75.4 65.3 55.1 45.0 -

62 105.8 6.2 105.8 98.7 83.7 73.4 63.1 52.8 98.9 7.0 98.9 95.3 80.2 70.1 59.9 49.8

2550

77 126.3 6.5 59.7 47.9 36.1 - - - 122.9 7.4 58.7 46.9 35.2 - - -

72 122.4 6.4 79.1 67.3 55.5 43.7 - - 116.8 7.3 77.0 65.3 53.5 41.8 - -

67 118.4 6.4 98.4 86.6 74.8 63.0 51.2 - 110.7 7.2 95.3 83.6 71.9 60.1 48.4 -

62 109.7 6.2 109.7 104.9 92.0 80.2 68.4 56.6 102.4 7.1 102.4 100.1 88.3 76.6 64.9 53.1

57 107.0 6.3 107.0 107.0 97.1 85.3 73.5 61.7 99.6 7.1 99.6 99.6 90.0 78.3 66.5 54.8

2975

77 130.7 6.5 65.1 52.7 39.4 - - - 127.2 7.4 65.0 51.7 38.4 - - -

72 126.6 6.4 87.0 73.7 60.5 47.2 - - 120.9 7.3 85.0 71.7 58.4 45.1 - -

67 122.6 6.4 108.9 94.8 81.5 68.2 54.9 - 114.6 7.2 105.1 91.7 78.4 65.1 51.8 -

62 113.5 6.3 113.5 111.1 100.2 86.9 73.6 60.3 106.0 7.1 106.0 104.8 96.4 83.1 69.8 56.5

57 110.8 6.3 110.8 110.8 105.8 92.5 79.2 65.9 103.0 7.2 103.0 103.0 98.2 84.9 71.6 58.3

3400

77 135.1 6.5 70.6 57.4 42.6 - - - 131.4 7.4 71.4 56.5 41.7 - - -

72 130.9 6.5 95.0 80.2 65.4 50.6 - - 124.9 7.3 93.1 78.2 63.3 48.4 - -

67 126.7 6.4 119.5 103.0 88.2 73.4 58.6 - 118.4 7.2 114.8 99.9 85.0 70.1 55.2 -

62 117.3 6.3 117.3 117.3 108.5 93.7 78.9 64.1 109.5 7.1 109.5 109.5 104.5 89.6 74.7 59.8

57 114.5 6.4 114.5 114.5 114.5 99.7 84.9 70.1 106.5 7.2 106.5 106.5 106.5 91.6 76.7 61.8

3825

72 130.9 6.5 99.4 84.1 68.8 53.5 - - 125.4 7.4 98.3 82.6 66.9 51.2 - -

67 126.8 6.4 123.1 108.1 92.8 77.5 62.2 - 118.8 7.3 117.0 105.4 89.7 74.0 58.4 -

62 117.4 6.3 117.4 117.4 112.9 97.6 82.3 67.0 109.9 7.1 109.9 109.9 107.4 91.7 76.0 60.3

57 114.5 6.4 114.5 114.5 114.5 99.2 83.9 68.6 106.9 7.2 106.9 106.9 106.9 91.2 75.5 59.8

4250

72 131.0 6.5 103.7 87.9 72.1 56.3 - - 125.9 7.4 103.4 86.9 70.4 53.9 - -

67 126.8 6.5 126.8 113.1 97.3 81.5 65.7 - 119.3 7.3 119.3 111.0 94.5 78.0 61.5 -

62 117.4 6.3 117.4 117.4 117.4 101.6 85.8 70.0 110.4 7.2 110.4 110.4 110.4 93.8 77.3 60.8

57 114.6 6.4 114.6 114.6 114.6 98.8 83.0 67.2 107.3 7.2 107.3 107.3 107.3 90.7 74.2 57.7

95°F 105°F

2125

77 115.5 8.3 50.3 41.1 31.1 - - - 108.8 9.3 44.7 38.2 28.2 - - -

72 107.5 8.1 66.9 56.8 46.8 36.8 - - 100.5 9.1 63.5 53.6 43.7 33.8 - -

67 99.5 8.0 83.4 72.5 62.5 52.5 42.4 - 92.1 9.0 82.4 69.0 59.1 49.2 39.3 -

62 91.9 7.9 91.9 91.9 76.8 66.8 56.7 46.7 85.2 8.9 85.2 85.2 70.3 60.4 50.5 40.6

2550

77 119.5 8.3 57.6 46.0 34.3 - - - 112.4 9.3 54.4 42.9 31.3 - - -

72 111.3 8.2 75.0 63.3 51.6 39.9 - - 103.8 9.2 71.5 60.0 48.4 36.8 - -

67 103.0 8.0 92.3 80.6 68.9 57.2 45.6 - 95.1 9.0 88.6 77.1 65.5 53.9 42.3 -

62 95.2 7.9 95.2 95.2 84.7 73.0 61.3 49.7 88.0 8.9 88.0 88.0 77.9 66.3 54.7 43.1

57 92.1 7.9 92.1 92.1 82.9 71.2 59.6 47.9 85.8 9.0 85.8 85.8 76.4 64.9 53.3 41.7

2975

77 123.6 8.3 64.9 50.8 37.5 - - - 115.9 9.4 64.2 47.5 34.3 - - -

72 115.1 8.2 83.1 69.7 56.4 43.1 - - 107.0 9.2 79.5 66.3 53.1 39.8 - -

67 106.5 8.0 101.2 88.7 75.3 62.0 48.7 - 98.1 9.0 94.9 85.1 71.8 58.6 45.4 -

62 98.5 7.9 98.5 98.5 92.6 79.3 65.9 52.6 90.8 8.9 90.8 90.8 85.4 72.2 58.9 45.7

57 95.2 8.0 95.2 95.2 90.7 77.3 64.0 50.7 88.5 9.0 88.5 88.5 83.8 70.6 57.4 44.1

3400

77 127.7 8.4 72.3 55.6 40.7 - - - 119.5 9.4 74.0 52.2 37.3 - - -

72 118.9 8.2 91.2 76.2 61.2 46.3 - - 110.3 9.2 87.6 72.7 57.8 42.9 - -

67 110.1 8.1 110.1 96.7 81.8 66.8 51.8 - 101.2 9.1 101.2 93.1 78.2 63.3 48.4 -

62 101.7 8.0 101.7 101.7 100.5 85.5 70.6 55.6 93.6 8.9 93.6 93.6 93.0 78.1 63.2 48.3

57 98.4 8.0 98.4 98.4 98.4 83.4 68.5 53.5 91.2 9.0 91.2 91.2 91.2 76.4 61.5 46.6

3825

72 119.8 8.3 97.1 81.0 64.9 48.8 - - 111.2 9.3 93.4 77.4 61.3 45.3 - -

67 110.9 8.1 110.9 102.8 86.7 70.6 54.5 - 102.0 9.1 102.0 97.2 83.0 67.0 51.0 -

62 102.5 8.0 102.5 102.5 101.9 85.8 69.7 53.6 94.3 9.0 94.3 94.3 94.0 78.0 61.9 45.9

57 99.2 8.0 99.2 99.2 99.2 83.1 67.0 50.9 92.0 9.1 92.0 92.0 92.0 75.9 59.9 43.9

4250

72 120.8 8.3 103.1 85.9 68.6 51.4 - - 112.1 9.3 99.2 82.1 64.9 47.7 - -

67 111.8 8.1 111.8 108.9 91.7 74.4 57.2 - 102.8 9.1 102.8 101.3 87.8 70.7 53.5 -

62 103.3 8.0 103.3 103.3 103.3 86.1 68.9 51.6 95.1 9.0 95.1 95.1 95.1 77.9 60.7 43.5

57 99.9 8.1 99.9 99.9 99.9 82.7 65.5 48.3 92.7 9.1 92.7 92.7 92.7 75.5 58.4 41.2

Page 87: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 87

115°F 125°F

2125

77 102.2 10.3 39.0 35.2 25.4 - - - 95.6 11.4 36.2 31.0 22.6 - - -

72 93.5 10.1 60.2 50.4 40.6 30.8 - - 86.5 11.1 56.8 47.1 37.5 27.8 - -

67 84.8 10.0 81.3 65.5 55.8 46.0 36.2 - 77.4 10.9 77.4 62.1 52.4 42.7 33.1 -

62 78.5 9.9 78.5 78.5 63.8 54.0 44.2 34.4 71.8 10.8 71.8 71.8 57.3 47.7 38.0 28.3

2550

77 105.2 10.4 51.2 39.7 28.3 - - - 98.0 11.4 49.9 36.6 25.3 - - -

72 96.2 10.2 68.1 56.6 45.2 33.7 - - 88.7 11.2 64.7 53.3 41.9 30.6 - -

67 87.3 10.0 85.0 73.5 62.0 50.6 39.1 - 79.4 11.0 79.4 70.0 58.6 47.3 35.9 -

62 80.8 9.9 80.8 80.8 71.0 59.6 48.1 36.6 73.6 10.9 73.6 73.6 64.2 52.8 41.5 30.1

57 79.6 10.0 79.6 79.6 69.9 58.5 47.0 35.5 73.3 11.0 73.3 73.3 63.4 52.1 40.7 29.3

2975

77 108.2 10.4 63.4 44.3 31.1 - - - 100.5 11.4 63.7 42.3 28.0 - - -

72 99.0 10.2 76.0 62.9 49.7 36.6 - - 90.9 11.2 72.5 59.5 46.4 33.4 - -

67 89.8 10.0 88.6 81.5 68.3 55.2 42.1 - 81.4 11.0 81.4 77.9 64.8 51.8 38.7 -

62 83.1 9.9 83.1 83.1 78.2 65.1 51.9 38.8 75.4 10.9 75.4 75.4 71.0 58.0 44.9 31.9

57 81.8 10.0 81.8 81.8 77.0 63.9 50.7 37.6 75.1 11.0 75.1 75.1 70.2 57.1 44.1 31.0

3400

77 111.2 10.4 75.7 48.8 34.0 - - - 102.9 11.4 77.4 47.9 30.7 - - -

72 101.7 10.2 84.0 69.1 54.3 39.5 - - 93.1 11.2 80.4 65.6 50.9 36.1 - -

67 92.3 10.0 92.3 89.5 74.6 59.8 45.0 - 83.3 11.0 83.3 83.3 71.1 56.3 41.6 -

62 85.4 9.9 85.4 85.4 85.4 70.6 55.8 41.0 77.3 10.9 77.3 77.3 77.3 63.1 48.4 33.6

57 84.1 10.0 84.1 84.1 84.1 69.3 54.5 39.6 77.0 11.0 77.0 77.0 77.0 62.2 47.5 32.7

3825

72 102.6 10.3 89.7 73.7 57.7 41.8 - - 93.9 11.3 86.0 70.1 54.1 38.2 - -

67 93.0 10.1 93.0 91.6 79.3 63.3 47.4 - 84.0 11.1 84.0 84.0 75.6 59.7 43.8 -

62 86.1 10.0 86.1 86.1 86.1 70.1 54.2 38.2 77.9 11.0 77.9 77.9 77.9 62.3 46.4 30.5

57 84.8 10.1 84.8 84.8 84.8 68.8 52.8 36.9 77.6 11.1 77.6 77.6 77.6 61.7 45.8 29.8

4250

72 103.4 10.3 95.4 78.3 61.1 44.0 - - 94.7 11.4 91.6 74.5 57.4 40.3 - -

67 93.8 10.1 93.8 93.8 84.0 66.9 49.7 - 84.7 11.1 84.7 84.7 80.2 63.1 46.0 -

62 86.8 10.0 86.8 86.8 86.8 69.7 52.6 35.4 78.6 11.1 78.6 78.6 78.6 61.5 44.4 27.3

57 85.5 10.1 85.5 85.5 85.5 68.3 51.2 34.1 78.2 11.2 78.2 78.2 78.2 61.2 44.1 27.0

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR102 (8.5 Ton) Cooling (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 88: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

88 Johnson Controls Ducted Systems

ZR102 (8.5 Ton) Reheat

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

35°F 45°F

2125

72 72.0 5.0 8.5 7.1 5.7 - - 62.7 5.5 3.5 2.4 1.3 - -

67 74.0 4.9 11.6 10.2 8.8 7.3 - 61.5 5.3 9.5 8.4 7.2 6.1 -

62 61.6 5.1 21.8 20.4 18.9 17.5 16.1 53.9 5.3 18.2 17.1 16.0 14.9 13.8

2550

72 73.3 4.9 13.4 11.3 9.2 - - 64.8 5.5 5.6 3.8 2.1 - -

67 75.3 4.8 17.9 15.8 13.7 11.6 - 63.6 5.3 14.9 13.2 11.4 9.7 -

62 62.6 5.0 33.6 31.5 29.4 27.3 25.2 55.8 5.2 28.7 26.9 25.2 23.4 21.7

57 58.2 4.7 37.4 35.3 33.2 31.2 29.1 50.7 5.0 33.0 31.2 29.5 27.7 26.0

2975

72 74.5 4.8 18.2 15.5 12.7 - - 66.9 5.4 7.6 5.2 2.8 - -

67 76.7 4.7 24.1 21.4 18.7 15.9 - 65.7 5.2 20.4 18.0 15.6 13.2 -

62 63.6 5.0 45.3 42.6 39.9 37.1 34.4 57.6 5.2 39.2 36.8 34.4 32.0 29.6

57 59.2 4.7 48.8 47.8 45.0 42.3 39.6 52.4 5.0 43.5 42.6 40.2 37.8 35.4

3400

72 75.7 4.7 23.0 19.6 16.2 - - 69.1 5.3 9.7 6.6 3.6 - -

67 78.1 4.6 30.4 27.0 23.6 20.2 - 67.8 5.1 25.8 22.8 19.7 16.7 -

62 64.7 4.9 57.1 53.7 50.4 47.0 43.6 59.5 5.1 49.7 46.6 43.6 40.5 37.5

57 60.2 4.6 60.2 60.2 56.8 53.5 50.1 54.0 4.9 54.0 54.0 51.0 47.9 44.9

3825

72 73.9 4.7 25.8 22.4 18.9 - - 70.1 5.3 10.9 7.5 4.2 - -

67 76.5 4.6 33.7 30.2 26.8 23.3 - 68.7 5.1 29.2 25.8 22.5 19.1 -

62 63.0 4.9 62.0 60.1 56.7 53.2 49.8 60.3 5.1 55.4 52.9 49.5 46.1 42.8

57 58.8 4.6 58.8 58.8 55.4 51.9 48.4 54.8 4.9 54.8 54.8 51.4 48.1 44.7

4250

72 72.0 4.7 28.7 25.1 21.6 - - 71.0 5.3 12.1 8.4 4.7 - -

67 75.0 4.6 37.0 33.5 29.9 26.4 - 69.7 5.1 32.5 28.9 25.2 21.5 -

62 61.4 4.9 61.4 61.4 61.4 59.5 55.9 61.2 5.1 61.2 59.1 55.4 51.7 48.0

57 57.4 4.6 57.4 57.4 53.9 50.4 46.8 55.6 4.9 55.6 55.6 51.9 48.2 44.5

55°F 65°F

2125

72 53.3 6.1 - - - - - 48.0 6.2 - - - - -

67 49.0 5.8 7.3 6.5 5.7 4.9 - 42.2 6.1 4.4 4.0 3.5 3.1 -

62 46.3 5.4 14.6 13.9 13.1 12.3 11.5 39.1 5.8 9.5 9.1 8.6 8.2 7.7

2550

72 56.3 6.0 - - - - - 53.6 6.1 - - - - -

67 51.8 5.7 11.9 10.5 9.1 7.7 - 47.0 6.1 9.1 8.0 6.9 5.8 -

62 49.0 5.4 23.8 22.4 21.0 19.6 18.1 43.5 5.7 20.2 19.1 18.0 16.9 15.8

57 43.2 5.3 28.6 27.1 25.7 24.3 22.9 36.3 5.7 22.6 21.5 20.4 19.3 18.2

2975

72 59.4 6.0 - - - - - 59.2 6.1 - - - - -

67 54.6 5.7 16.6 14.5 12.5 10.4 - 51.7 6.0 13.7 12.0 10.2 8.5 -

62 51.6 5.4 33.0 31.0 28.9 26.8 24.8 47.8 5.7 30.9 29.1 27.4 25.7 23.9

57 45.5 5.3 38.2 37.5 35.4 33.4 31.3 39.8 5.6 33.0 32.4 30.7 28.9 27.2

3400

72 62.4 6.0 - - - - - 64.8 6.1 - - - - -

67 57.4 5.7 21.3 18.5 15.8 13.1 - 56.5 6.0 18.3 15.9 13.6 11.2 -

62 54.3 5.3 42.2 39.5 36.8 34.1 31.4 52.2 5.7 41.6 39.2 36.8 34.4 32.0

57 47.9 5.2 47.9 47.9 45.2 42.4 39.7 43.3 5.6 43.3 43.3 41.0 38.6 36.2

3825

72 66.2 5.9 - - - - - 67.4 6.0 - - - - -

67 60.9 5.6 24.7 21.4 18.1 14.9 - 58.8 6.0 22.2 19.2 16.3 13.3 -

62 57.6 5.3 48.8 45.6 42.3 39.0 35.8 54.4 5.6 47.7 45.5 42.6 39.6 36.6

57 50.8 5.2 50.8 50.8 47.5 44.3 41.0 45.2 5.6 45.2 45.2 42.2 39.3 36.3

4250

72 70.1 5.9 - - - - - 70.0 6.0 - - - - -

67 64.5 5.6 28.1 24.2 20.4 16.6 - 61.1 5.9 26.0 22.5 19.0 15.4 -

62 60.9 5.3 55.5 51.6 47.8 44.0 40.2 56.5 5.6 53.8 51.9 48.3 44.8 41.2

57 53.7 5.2 53.7 53.7 49.9 46.1 42.3 47.1 5.5 47.1 47.1 43.5 40.0 36.4

Page 89: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 89

75°F 85°F

2125

72 42.8 6.3 - - - - - 37.6 6.4 - - - - -

67 35.4 6.5 1.6 1.5 1.4 1.2 - 28.6 6.8 - - - - -

62 31.9 6.2 4.4 4.3 4.2 4.1 4.0 24.7 6.5 - - - - -

2550

72 50.9 6.2 - - - - - 48.3 6.4 - - - - -

67 42.1 6.4 6.2 5.4 4.7 3.9 - 37.3 6.8 3.3 2.9 2.5 2.0 -

62 38.0 6.1 16.6 15.8 15.0 14.3 13.5 32.5 6.5 13.0 12.5 12.1 11.6 11.2

57 29.4 6.1 16.6 15.8 15.0 14.3 13.5 22.5 6.4 10.6 10.1 9.7 9.3 8.8

2975

72 59.1 6.2 - - - - - 58.9 6.3 - - - - -

67 48.9 6.4 10.8 9.4 8.0 6.6 - 46.0 6.7 7.9 6.8 5.7 4.6 -

62 44.0 6.1 28.7 27.3 25.9 24.5 23.1 40.2 6.4 26.6 25.5 24.4 23.3 22.2

57 34.1 6.0 27.7 27.3 25.9 24.5 23.1 28.4 6.4 22.4 22.2 21.1 20.0 19.0

3400

72 67.2 6.2 - - - - - 69.6 6.3 - - - - -

67 55.6 6.3 15.4 13.3 11.3 9.2 - 54.7 6.7 12.5 10.7 9.0 7.3 -

62 50.1 6.0 40.9 38.8 36.8 34.7 32.6 48.0 6.4 40.2 38.5 36.7 35.0 33.3

57 38.8 6.0 38.8 38.8 36.8 34.7 32.6 34.3 6.3 34.3 34.3 32.6 30.8 29.1

3825

72 68.6 6.1 - - - - - 69.7 6.2 - - - - -

67 56.7 6.3 19.7 17.0 14.4 11.7 - 54.6 6.6 17.2 14.9 12.5 10.2 -

62 51.1 6.0 46.5 45.5 42.8 40.1 37.5 47.9 6.3 45.3 45.4 43.1 40.7 38.3

57 39.6 5.9 39.6 39.6 36.9 34.3 31.6 34.0 6.3 34.0 34.0 31.6 29.3 26.9

4250

72 69.9 6.1 - - - - - 69.8 6.2 - - - - -

67 57.8 6.3 24.0 20.8 17.5 14.2 - 54.5 6.6 22.0 19.0 16.0 13.1 -

62 52.1 5.9 52.1 52.1 48.8 45.6 42.3 47.7 6.3 47.7 47.7 47.7 46.4 43.4

57 40.4 5.9 40.4 40.4 37.1 33.9 30.6 33.7 6.2 33.7 33.7 30.7 27.8 24.8

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR102 (8.5 Ton) Reheat (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

Page 90: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

90 Johnson Controls Ducted Systems

ZR120 (10 Ton) Cooling

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

2500

77 137.8 7.3 67.5 55.5 43.9 - - - 132.5 8.2 62.6 51.3 40.0 - - -

72 131.8 7.1 85.5 73.9 62.3 50.6 - - 125.8 8.1 80.7 69.5 58.2 46.9 - -

67 125.8 7.0 103.5 92.3 80.6 69.0 57.4 - 119.1 8.0 98.9 87.6 76.4 65.1 53.9 -

62 113.9 6.9 113.9 112.8 97.5 85.8 74.2 62.6 108.5 7.9 108.5 107.0 91.1 79.8 68.6 57.3

3000

77 143.9 7.4 73.5 60.4 47.3 - - - 138.1 8.3 69.4 56.5 43.6 - - -

72 137.6 7.2 93.3 80.2 67.1 54.0 - - 131.1 8.2 89.1 76.3 63.4 50.5 - -

67 131.3 7.0 113.1 100.0 86.9 73.8 60.7 - 124.1 8.0 108.9 96.0 83.1 70.2 57.4 -

62 118.9 6.9 118.9 118.2 105.1 92.0 78.9 65.8 113.1 8.0 113.1 112.1 99.2 86.3 73.4 60.5

57 114.8 6.9 114.8 114.8 108.3 95.2 82.2 69.1 110.6 7.9 110.6 110.6 102.2 89.3 76.4 63.5

3500

77 150.0 7.4 79.5 65.3 50.8 - - - 143.7 8.3 76.2 61.7 47.1 - - -

72 143.4 7.2 101.1 86.5 72.0 57.4 - - 136.4 8.2 97.6 83.0 68.5 54.0 - -

67 136.9 7.1 122.7 107.7 93.2 78.6 64.0 - 129.1 8.1 119.0 104.4 89.9 75.4 60.9 -

62 123.9 7.0 123.9 123.6 112.7 98.1 83.5 69.0 117.7 8.0 117.7 117.1 107.2 92.7 78.2 63.7

57 119.6 7.0 119.6 119.6 116.2 101.6 87.0 72.5 115.1 8.0 115.1 115.1 110.5 96.0 81.5 67.0

4000

77 156.1 7.4 85.5 70.2 54.2 - - - 149.3 8.4 83.0 66.8 50.7 - - -

72 149.3 7.3 108.9 92.8 76.8 60.8 - - 141.7 8.2 106.0 89.8 73.7 57.5 - -

67 142.5 7.1 132.2 115.4 99.4 83.4 67.4 - 134.1 8.1 129.0 112.8 96.7 80.5 64.4 -

62 129.0 7.0 129.0 129.0 120.2 104.2 88.2 72.2 122.2 8.0 122.2 122.2 115.3 99.2 83.0 66.8

57 124.5 7.0 124.5 124.5 124.0 108.0 91.9 75.9 119.6 8.0 119.6 119.6 118.9 102.7 86.5 70.4

4500

72 151.7 7.3 116.7 99.1 81.6 64.0 - - 143.8 8.2 113.4 95.8 78.1 60.5 - -

67 144.8 7.1 139.7 123.1 105.6 88.0 70.5 - 136.2 8.1 133.6 120.2 102.5 84.9 67.2 -

62 131.1 7.0 131.1 131.1 126.7 109.2 91.6 74.1 124.1 8.0 124.1 124.1 120.6 103.0 85.3 67.6

57 126.6 7.0 126.6 126.6 126.3 108.8 91.2 73.7 121.4 8.0 121.4 121.4 121.0 103.4 85.7 68.1

5000

72 154.2 7.3 124.5 105.4 86.4 67.3 - - 146.0 8.3 120.9 101.7 82.6 63.4 - -

67 147.2 7.2 147.2 130.9 111.8 92.7 73.6 - 138.2 8.1 138.2 127.5 108.3 89.2 70.0 -

62 133.3 7.1 133.3 133.3 133.3 114.2 95.1 76.0 125.9 8.1 125.9 125.9 125.9 106.8 87.6 68.5

57 128.6 7.1 128.6 128.6 128.6 109.6 90.5 71.4 123.2 8.0 123.2 123.2 123.2 104.1 84.9 65.7

95°F 105°F

2500

77 127.3 9.2 57.6 47.1 36.2 - - - 117.5 10.5 52.8 44.2 33.5 - - -

72 119.8 9.1 75.9 65.0 54.1 43.3 - - 110.8 10.4 72.3 61.6 50.9 40.3 - -

67 112.4 9.0 94.3 83.0 72.1 61.2 50.3 - 104.0 10.3 91.8 79.1 68.4 57.7 47.0 -

62 103.2 9.0 103.2 101.2 84.7 73.8 62.9 52.0 96.1 10.2 96.1 95.1 80.3 69.6 58.9 48.2

3000

77 132.4 9.2 65.2 52.5 39.8 - - - 122.4 10.5 61.8 49.3 36.9 - - -

72 124.6 9.1 85.0 72.3 59.6 46.9 - - 115.4 10.4 81.0 68.5 56.1 43.7 - -

67 116.9 9.0 104.8 92.1 79.4 66.7 54.0 - 108.3 10.3 100.2 87.8 75.3 62.9 50.5 -

62 107.3 9.0 107.3 106.0 93.3 80.6 67.9 55.2 100.1 10.2 100.1 99.4 88.5 76.0 63.6 51.2

57 106.5 8.9 106.5 106.5 96.1 83.4 70.7 58.0 99.2 10.2 99.2 99.2 89.5 77.0 64.6 52.2

3500

77 137.4 9.2 72.9 58.0 43.5 - - - 127.3 10.5 70.7 54.5 40.3 - - -

72 129.4 9.2 94.1 79.6 65.1 50.6 - - 120.0 10.4 89.6 75.5 61.3 47.2 - -

67 121.3 9.1 115.3 101.2 86.7 72.2 57.7 - 112.6 10.3 108.6 96.5 82.3 68.1 54.0 -

62 111.4 9.0 111.4 110.7 101.8 87.3 72.8 58.3 104.0 10.2 104.0 103.7 96.6 82.5 68.3 54.2

57 110.6 9.0 110.6 110.6 104.9 90.4 75.9 61.4 103.2 10.2 103.2 103.2 97.7 83.6 69.4 55.3

4000

77 142.5 9.3 80.5 63.5 47.2 - - - 132.1 10.5 79.6 59.6 43.7 - - -

72 134.1 9.2 103.1 86.8 70.5 54.3 - - 124.6 10.4 98.3 82.4 66.5 50.6 - -

67 125.8 9.1 125.8 110.2 93.9 77.6 61.3 - 117.0 10.3 117.0 105.2 89.3 73.4 57.5 -

62 115.5 9.0 115.5 115.5 110.4 94.1 77.8 61.5 108.0 10.2 108.0 108.0 104.8 88.9 73.0 57.1

57 114.7 9.0 114.7 114.7 113.7 97.4 81.1 64.8 107.1 10.2 107.1 107.1 106.0 90.1 74.2 58.3

4500

72 136.0 9.2 110.2 92.4 74.7 56.9 - - 126.1 10.4 105.2 87.8 70.5 53.1 - -

67 127.5 9.1 127.5 117.2 99.4 81.7 63.9 - 118.4 10.3 118.4 111.2 94.6 77.2 59.9 -

62 117.1 9.0 117.1 117.1 114.5 96.7 79.0 61.2 109.4 10.2 109.4 109.4 107.8 90.4 73.1 55.7

57 116.2 9.0 116.2 116.2 115.8 98.0 80.2 62.5 108.4 10.2 108.4 108.4 107.9 90.5 73.2 55.8

5000

72 137.8 9.2 117.3 98.0 78.8 59.5 - - 127.6 10.4 112.0 93.2 74.4 55.6 - -

67 129.2 9.1 129.2 124.2 104.9 85.7 66.4 - 119.8 10.3 119.8 117.3 99.9 81.1 62.2 -

62 118.6 9.0 118.6 118.6 118.6 99.4 80.2 60.9 110.7 10.2 110.7 110.7 110.7 91.9 73.1 54.3

57 117.8 9.0 117.8 117.8 117.8 98.6 79.3 60.1 109.8 10.2 109.8 109.8 109.8 91.0 72.1 53.3

Page 91: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 91

115°F 125°F

2500

77 107.7 11.9 48.1 41.3 30.8 - - - 98.0 13.2 43.3 38.4 28.1 - - -

72 101.7 11.7 68.7 58.2 47.7 37.3 - - 92.6 13.0 65.1 54.8 44.5 34.3 - -

67 95.6 11.6 89.3 75.1 64.6 54.2 43.7 - 87.3 12.8 86.8 71.2 60.9 50.6 40.4 -

62 89.0 11.4 89.0 89.0 75.9 65.4 54.9 44.4 81.8 12.6 81.8 81.8 71.4 61.2 50.9 40.6

3000

77 112.4 11.8 58.3 46.1 34.0 - - - 102.5 13.1 54.8 42.9 31.1 - - -

72 106.1 11.7 76.9 64.8 52.6 40.5 - - 96.9 13.0 72.9 61.0 49.2 37.3 - -

67 99.8 11.5 95.6 83.4 71.3 59.1 47.0 - 91.3 12.8 91.0 79.1 67.2 55.4 43.5 -

62 92.8 11.3 92.8 92.8 83.7 71.5 59.4 47.2 85.6 12.5 85.6 85.6 78.9 67.0 55.1 43.2

57 91.9 11.4 91.9 91.9 82.8 70.7 58.5 46.4 84.6 12.7 84.6 84.6 76.2 64.3 52.4 40.5

3500

77 117.1 11.8 68.5 51.0 37.2 - - - 107.0 13.1 66.3 47.5 34.0 - - -

72 110.6 11.7 85.2 71.4 57.5 43.7 - - 101.2 12.9 80.8 67.3 53.8 40.3 - -

67 104.0 11.5 101.9 91.8 77.9 64.1 50.3 - 95.3 12.7 95.2 87.1 73.6 60.1 46.6 -

62 96.7 11.3 96.7 96.7 91.5 77.6 63.8 50.0 89.4 12.5 89.4 89.4 86.3 72.8 59.3 45.8

57 95.7 11.4 95.7 95.7 90.5 76.7 62.9 49.1 88.3 12.6 88.3 88.3 83.4 69.9 56.4 42.9

4000

77 121.8 11.8 78.7 55.8 40.3 - - - 111.5 13.0 77.8 52.0 36.9 - - -

72 115.0 11.6 93.4 77.9 62.5 47.0 - - 105.4 12.8 88.6 73.5 58.4 43.3 - -

67 108.2 11.5 108.2 100.1 84.6 69.1 53.6 - 99.3 12.7 99.3 95.0 79.9 64.8 49.7 -

62 100.6 11.3 100.6 100.6 99.3 83.8 68.3 52.8 93.1 12.4 93.1 93.1 93.1 78.6 63.5 48.4

57 99.6 11.4 99.6 99.6 98.3 82.8 67.3 51.8 92.0 12.6 92.0 92.0 90.5 75.4 60.3 45.3

4500

72 116.2 11.6 100.1 83.2 66.2 49.3 - - 106.4 12.9 95.1 78.5 62.0 45.5 - -

67 109.3 11.5 109.3 105.3 89.7 72.8 55.8 - 100.2 12.7 100.2 99.3 84.8 68.3 51.8 -

62 101.7 11.3 101.7 101.7 101.0 84.1 67.1 50.2 94.0 12.4 94.0 94.0 94.0 77.7 61.2 44.7

57 100.6 11.4 100.6 100.6 100.0 83.1 66.1 49.2 92.9 12.6 92.9 92.9 92.1 75.6 59.1 42.5

5000

72 117.5 11.7 106.8 88.4 70.0 51.6 - - 107.3 12.9 101.5 83.6 65.6 47.7 - -

67 110.5 11.5 110.5 110.5 94.8 76.4 58.1 - 101.1 12.7 101.1 101.1 89.8 71.8 53.9 -

62 102.7 11.3 102.7 102.7 102.7 84.4 66.0 47.6 94.8 12.5 94.8 94.8 94.8 76.8 58.9 40.9

57 101.7 11.4 101.7 101.7 101.7 83.3 65.0 46.6 93.7 12.7 93.7 93.7 93.7 75.7 57.8 39.8

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR120 (10 Ton) Cooling (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 92: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

92 Johnson Controls Ducted Systems

ZR120 (10 Ton) Reheat

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

35°F 45°F

2500

77 81.3 6.2 - - - - - - 66.7 6.8 - - - - - -

72 75.9 6.1 12.0 9.6 7.1 4.7 - - 65.6 6.5 6.6 4.6 2.7 - - -

67 70.6 6.0 26.3 23.9 21.5 19.1 16.6 - 64.5 6.2 21.3 19.3 17.3 15.4 13.4 -

62 72.8 5.8 42.2 39.7 37.3 34.9 32.5 30.0 62.5 6.0 35.2 33.2 31.3 29.3 27.4 25.4

3000

77 82.4 6.2 - - - - - - 69.4 6.8 - - - - - -

72 76.7 6.0 15.1 12.1 9.2 6.2 - - 68.3 6.5 8.5 6.0 3.4 - - -

67 71.0 5.9 31.5 28.6 25.6 22.7 19.7 - 67.1 6.2 27.0 24.4 21.8 19.3 16.7 -

62 73.6 5.7 50.1 47.2 44.2 41.3 38.3 35.4 65.0 6.0 44.6 42.0 39.4 36.8 34.2 31.6

57 65.6 5.7 56.8 53.9 50.9 48.0 45.0 42.1 60.6 5.9 51.5 48.9 46.3 43.7 41.1 38.6

3500

77 83.5 6.1 - - - - - - 72.1 6.7 - - - - - -

72 77.5 6.0 18.1 14.7 11.2 7.8 - - 70.9 6.5 10.5 7.3 4.1 - - -

67 71.5 5.9 36.6 33.2 29.7 26.3 22.8 - 69.7 6.2 32.8 29.6 26.3 23.1 19.9 -

62 74.3 5.7 58.0 54.6 51.1 47.7 44.2 40.8 67.6 6.0 53.9 50.7 47.5 44.3 41.1 37.8

57 66.1 5.6 61.7 60.2 58.7 55.3 51.8 48.4 63.0 5.9 58.4 57.1 55.9 52.6 49.4 46.2

4000

77 84.7 6.1 - - - - - - 74.9 6.7 - - - - - -

72 78.3 6.0 21.2 17.2 13.3 9.3 - - 73.6 6.4 12.5 8.6 4.8 - - -

67 71.9 5.9 41.8 37.8 33.9 29.9 25.9 - 72.4 6.2 38.5 34.7 30.8 27.0 23.1 -

62 75.1 5.7 66.0 62.0 58.0 54.1 50.1 46.1 70.1 5.9 63.3 59.4 55.6 51.7 47.9 44.1

57 66.6 5.6 66.6 66.6 66.6 62.6 58.6 54.7 65.4 5.9 65.4 65.4 65.4 61.5 57.7 53.8

4500

72 79.5 6.0 22.5 18.3 14.1 9.9 - - 73.1 6.5 13.3 9.2 5.1 - - -

67 73.3 5.9 44.3 40.1 35.9 31.7 27.5 - 71.9 6.2 41.1 36.9 32.8 28.7 24.6 -

62 76.3 5.7 71.7 67.7 61.5 57.3 53.1 49.0 69.7 6.0 66.2 63.3 59.2 55.1 50.9 46.8

57 67.8 5.6 67.8 67.8 67.8 63.6 59.4 55.2 64.9 5.9 64.9 64.9 64.9 60.8 56.7 52.6

5000

72 80.8 6.0 23.8 19.4 15.0 10.6 - - 72.6 6.5 14.1 9.8 5.4 - - -

67 74.7 5.9 46.7 42.3 38.0 33.6 29.2 - 71.4 6.2 43.6 39.2 34.8 30.4 26.0 -

62 77.5 5.7 77.5 73.5 65.0 60.6 56.2 51.8 69.2 6.0 69.2 67.2 62.8 58.4 54.0 49.6

57 69.0 5.6 69.0 69.0 69.0 64.6 60.2 55.8 64.5 5.9 64.5 64.5 64.5 60.1 55.7 51.3

55°F 65°F

2500

77 52.1 7.4 - - - - - - 46.4 7.7 - - - - - -

72 55.3 6.9 1.2 - - - - - 49.0 7.3 - - - - - -

67 58.4 6.5 16.2 14.7 13.2 11.7 10.2 - 51.6 6.9 13.0 11.8 10.6 9.4 8.2 -

62 52.2 6.2 28.2 26.7 25.2 23.7 22.3 20.8 46.1 6.5 23.7 22.5 21.3 20.0 18.8 17.6

3000

77 56.5 7.4 - - - - - - 51.3 7.7 - - - - - -

72 59.8 6.9 2.0 - - - - - 54.1 7.3 - - - - - -

67 63.2 6.5 22.5 20.3 18.1 15.8 13.6 - 57.0 6.8 19.4 17.4 15.4 13.5 11.5 -

62 56.5 6.2 39.0 36.8 34.5 32.3 30.1 27.8 50.8 6.5 34.9 33.0 31.0 29.0 27.1 25.1

57 55.7 6.1 46.2 44.0 41.7 39.5 37.3 35.0 50.2 6.5 40.6 38.6 36.6 34.7 32.7 30.7

3500

77 60.8 7.3 - - - - - - 56.1 7.7 - - - - - -

72 64.4 6.9 2.9 - - - - - 59.2 7.3 - - - - - -

67 68.0 6.5 28.9 25.9 22.9 20.0 17.0 - 62.3 6.8 25.7 23.0 20.2 17.5 14.8 -

62 60.8 6.2 49.8 46.8 43.9 40.9 37.9 34.9 55.6 6.5 46.2 43.5 40.7 38.0 35.3 32.5

57 60.0 6.1 55.2 54.1 53.0 50.0 47.0 44.0 54.9 6.5 50.1 49.1 48.1 45.4 42.6 39.9

4000

77 65.1 7.3 - - - - - - 60.9 7.7 - - - - - -

72 69.0 6.9 3.7 - - - - - 64.3 7.2 - - - - - -

67 72.8 6.5 35.3 31.5 27.8 24.1 20.4 - 67.6 6.8 32.0 28.5 25.1 21.6 18.1 -

62 65.2 6.2 60.6 56.9 53.2 49.4 45.7 42.0 60.4 6.5 57.5 54.0 50.5 47.0 43.5 40.0

57 64.2 6.1 64.2 64.2 64.2 60.5 56.8 53.0 59.6 6.5 59.6 59.6 59.6 56.1 52.6 49.1

4500

72 66.7 7.0 4.1 - - - - - 63.3 7.3 - - - - - -

67 70.4 6.6 37.8 33.8 29.7 25.7 21.6 - 66.7 6.9 36.0 32.0 28.0 24.0 20.0 -

62 63.0 6.3 60.7 58.9 56.8 52.8 48.7 44.7 59.5 6.6 58.0 56.3 54.5 50.5 46.5 42.5

57 62.1 6.2 62.1 62.1 62.1 58.0 54.0 49.9 58.8 6.5 58.8 58.8 58.7 54.7 50.7 46.7

5000

72 64.4 7.0 4.5 - - - - - 62.4 7.3 - - - - - -

67 68.0 6.6 40.4 36.0 31.7 27.3 22.9 - 65.7 6.9 40.0 35.5 31.0 26.5 22.0 -

62 60.9 6.3 60.9 60.9 60.5 56.2 51.8 47.4 58.6 6.6 58.6 58.6 58.5 53.9 49.4 44.9

57 60.0 6.2 60.0 60.0 60.0 55.6 51.2 46.8 57.9 6.5 57.9 57.9 57.9 53.4 48.9 44.4

Page 93: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 93

75°F 85°F

2500

77 40.8 8.0 - - - - - - 35.1 8.4 - - - - - -

72 42.8 7.6 - - - - - - 36.6 8.0 - - - - - -

67 44.9 7.2 9.9 9.0 8.1 7.1 6.2 - 38.1 7.5 6.8 6.1 5.5 4.8 4.2 -

62 39.9 6.9 19.1 18.2 17.3 16.3 15.4 14.5 33.8 7.2 14.6 13.9 13.3 12.6 12.0 11.3

3000

77 46.1 8.0 - - - - - - 40.9 8.4 - - - - - -

72 48.4 7.6 - - - - - - 42.7 7.9 - - - - - -

67 50.7 7.2 16.2 14.5 12.8 11.1 9.4 - 44.5 7.5 13.0 11.6 10.2 8.7 7.3 -

62 45.2 6.8 30.9 29.2 27.5 25.7 24.0 22.3 39.5 7.2 26.8 25.3 23.9 22.5 21.0 19.6

57 44.8 6.8 34.9 33.2 31.5 29.8 28.1 26.4 39.3 7.1 29.3 27.9 26.4 25.0 23.6 22.1

3500

77 51.4 8.0 - - - - - - 46.7 8.3 - - - - - -

72 54.0 7.6 - - - - - - 48.8 7.9 - - - - - -

67 56.6 7.1 22.5 20.0 17.5 15.1 12.6 - 50.9 7.5 19.3 17.1 14.8 12.6 10.4 -

62 50.4 6.8 42.6 40.1 37.6 35.1 32.7 30.2 45.1 7.1 39.0 36.8 34.5 32.3 30.0 27.8

57 49.9 6.8 45.0 44.2 43.2 40.7 38.3 35.8 44.9 7.1 39.9 39.2 38.4 36.1 33.9 31.6

4000

77 56.7 8.0 - - - - - - 52.5 8.3 - - - - - -

72 59.6 7.6 - - - - - - 54.9 7.9 - - - - - -

67 62.4 7.1 28.8 25.6 22.3 19.0 15.8 - 57.3 7.4 25.6 22.6 19.5 16.5 13.4 -

62 55.6 6.8 54.3 51.1 47.8 44.6 41.3 38.0 50.8 7.1 50.8 48.2 45.1 42.1 39.1 36.0

57 55.1 6.8 55.1 55.1 54.9 51.7 48.4 45.1 50.5 7.1 50.5 50.5 50.3 47.2 44.2 41.2

4500

72 60.0 7.6 - - - - - - 56.7 7.9 - - - - - -

67 62.9 7.2 34.2 30.3 26.3 22.4 18.4 - 59.2 7.5 32.4 28.5 24.6 20.7 16.8 -

62 56.0 6.9 55.4 53.7 52.1 48.1 44.2 40.2 52.5 7.2 52.5 51.2 49.7 45.8 41.9 38.0

57 55.5 6.8 55.5 55.5 55.4 51.4 47.5 43.5 52.2 7.1 52.2 52.2 52.1 48.2 44.2 40.3

5000

72 60.5 7.7 - - - - - - 58.5 8.0 - - - - - -

67 63.4 7.2 39.7 35.0 30.4 25.7 21.0 - 61.0 7.5 39.3 34.5 29.7 24.9 20.1 -

62 56.4 6.9 56.4 56.4 56.4 51.7 47.1 42.4 54.2 7.2 54.2 54.2 54.2 49.5 44.7 39.9

57 55.9 6.9 55.9 55.9 55.9 51.2 46.6 41.9 53.9 7.2 53.9 53.9 53.9 49.1 44.3 39.5

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR120 (10 Ton) Reheat (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 94: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

94 Johnson Controls Ducted Systems

ZR150 (12.5 Ton) Cooling

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

75°F 85°F

3125

77 190.5 9.0 87.6 73.4 59.1 - - - 185.2 10.5 81.6 67.3 53.0 - - -

72 180.7 9.2 111.5 97.2 83.0 68.8 - - 172.9 10.5 105.4 91.1 76.8 62.5 - -

67 171.0 9.3 135.4 121.1 106.9 92.7 78.4 - 160.6 10.5 129.2 114.9 100.6 86.3 72.0 -

62 158.6 9.1 158.6 158.6 158.6 150.5 136.2 122.0 148.0 10.3 148.0 148.0 139.6 125.3 111.1 96.8

3750

77 199.8 9.2 94.7 78.6 62.4 - - - 194.0 10.6 89.0 72.9 56.8 - - -

72 189.6 9.3 119.8 103.7 87.5 71.3 - - 181.1 10.6 114.4 98.3 82.2 66.1 - -

67 179.4 9.4 145.0 128.8 112.6 96.4 80.3 - 168.3 10.6 139.9 123.8 107.7 91.6 75.5 -

62 166.3 9.2 166.3 166.3 166.3 157.9 141.8 125.6 155.1 10.4 155.1 155.1 149.5 133.4 117.3 101.2

57 154.4 9.2 154.4 154.4 148.9 132.7 116.6 100.4 146.9 10.4 146.9 146.9 137.3 121.2 105.2 89.1

4375

77 209.1 9.3 101.9 83.8 65.7 - - - 202.8 10.7 96.3 78.4 60.5 - - -

72 198.4 9.4 128.2 110.1 92.0 73.9 - - 189.3 10.7 123.4 105.5 87.6 69.7 - -

67 187.7 9.6 154.5 136.4 118.3 100.2 82.1 - 175.9 10.7 150.6 132.7 114.8 96.9 79.0 -

62 174.1 9.4 174.1 174.1 174.1 165.4 147.3 129.2 162.1 10.5 162.1 162.1 159.3 141.4 123.5 105.6

57 161.6 9.3 161.6 161.6 156.6 138.5 120.4 102.3 153.5 10.5 153.5 153.5 146.4 128.5 110.6 92.7

5000

77 218.4 9.4 109.0 89.0 68.9 - - - 211.6 10.8 103.6 83.9 64.2 - - -

72 207.3 9.6 136.6 116.5 96.5 76.5 - - 197.5 10.8 132.4 112.7 93.0 73.3 - -

67 196.1 9.7 164.1 144.1 124.1 104.0 84.0 - 183.5 10.8 161.2 141.5 121.8 102.1 82.4 -

62 181.8 9.5 181.8 181.8 181.8 172.9 152.9 132.8 169.1 10.6 169.1 169.1 169.1 149.4 129.7 110.0

57 168.8 9.5 168.8 168.8 164.4 144.3 124.3 104.2 160.2 10.6 160.2 160.2 155.4 135.7 116.0 96.3

5625

72 211.2 9.6 148.0 126.6 105.3 83.9 - - 202.2 10.8 143.3 122.0 100.8 79.5 - -

67 199.9 9.7 179.4 156.7 135.4 114.0 92.7 - 187.8 10.8 174.5 153.2 131.9 110.7 89.4 -

62 185.3 9.5 185.3 185.3 185.3 169.5 148.2 126.8 173.1 10.6 173.1 173.1 173.1 151.9 130.6 109.3

57 172.0 9.5 172.0 172.0 169.8 148.5 127.1 105.8 164.0 10.6 164.0 164.0 161.6 140.3 119.1 97.8

6250

72 215.2 9.5 159.4 136.7 114.0 91.4 - - 206.9 10.8 154.1 131.3 108.5 85.6 - -

67 203.6 9.7 194.6 169.4 146.7 124.0 101.4 - 192.2 10.8 187.7 164.9 142.0 119.2 96.4 -

62 188.8 9.5 188.8 188.8 188.8 166.2 143.5 120.9 177.1 10.6 177.1 177.1 177.1 154.3 131.5 108.6

57 175.3 9.4 175.3 175.3 175.3 152.6 130.0 107.3 167.8 10.6 167.8 167.8 167.8 145.0 122.1 99.3

95°F 105°F

3125

77 180.0 11.9 75.6 61.3 46.9 - - - 168.2 13.3 71.8 58.0 43.9 - - -

72 165.1 11.8 99.3 85.0 70.6 56.3 - - 153.8 13.2 95.1 81.0 66.9 52.8 - -

67 150.2 11.7 123.0 108.6 94.3 80.0 65.6 - 139.5 13.0 118.4 103.9 89.8 75.7 61.6 -

62 137.5 11.5 137.5 133.0 114.6 100.2 85.9 71.5 127.9 12.9 127.9 125.7 110.1 96.0 81.9 67.8

3750

77 188.2 12.0 83.2 67.2 51.2 - - - 175.5 13.3 79.5 63.7 47.8 - - -

72 172.7 11.9 109.0 93.0 77.0 60.9 - - 160.6 13.2 104.5 88.6 72.8 56.9 - -

67 157.1 11.7 134.8 118.8 102.8 86.7 70.7 - 145.6 13.1 129.4 113.6 97.7 81.9 66.0 -

62 143.8 11.6 143.8 140.8 124.8 108.8 92.8 76.8 133.5 12.9 133.5 132.1 119.8 104.0 88.1 72.2

57 139.4 11.6 139.4 139.4 125.8 109.8 93.8 77.7 130.3 13.0 130.3 130.3 117.1 101.2 85.4 69.5

4375

77 196.5 12.0 90.7 73.0 55.4 - - - 182.9 13.4 87.3 69.3 51.7 - - -

72 180.3 11.9 118.6 101.0 83.3 65.6 - - 167.3 13.3 113.9 96.3 78.7 61.0 - -

67 164.0 11.8 146.6 128.9 111.2 93.5 75.8 - 151.8 13.1 140.5 123.3 105.6 88.0 70.4 -

62 150.1 11.6 150.1 148.6 135.1 117.4 99.7 82.0 139.2 13.0 139.2 138.4 129.5 111.9 94.3 76.6

57 145.5 11.7 145.5 145.5 136.1 118.4 100.7 83.1 135.7 13.0 135.7 135.7 126.6 109.0 91.3 73.7

5000

77 204.8 12.1 98.3 78.9 59.6 - - - 190.3 13.4 95.1 75.0 55.6 - - -

72 187.8 12.0 128.3 109.0 89.6 70.2 - - 174.1 13.3 123.3 104.0 84.6 65.2 - -

67 170.9 11.9 158.4 139.0 119.6 100.3 80.9 - 157.9 13.2 151.6 132.9 113.6 94.2 74.8 -

62 156.4 11.7 156.4 156.4 145.3 126.0 106.6 87.2 144.8 13.0 144.8 144.8 139.2 119.8 100.4 81.1

57 151.6 11.7 151.6 151.6 146.4 127.1 107.7 88.4 141.2 13.1 141.2 141.2 136.1 116.7 97.3 77.9

5625

72 193.2 12.0 138.6 117.4 96.2 75.1 - - 178.5 13.3 133.3 112.3 91.2 70.2 - -

67 175.8 11.9 169.6 149.7 128.5 107.3 86.1 - 161.8 13.2 158.7 143.5 122.5 101.5 80.4 -

62 160.9 11.7 160.9 160.9 155.4 134.2 113.0 91.8 148.4 13.0 148.4 148.4 145.6 124.6 103.5 82.5

57 156.0 11.7 156.0 156.0 153.4 132.2 111.0 89.8 144.7 13.1 144.7 144.7 142.2 121.1 100.1 79.1

6250

72 198.6 12.0 148.9 125.9 102.9 79.9 - - 182.8 13.3 143.3 120.6 97.9 75.2 - -

67 180.7 11.9 180.7 160.4 137.4 114.4 91.4 - 165.8 13.2 165.8 154.1 131.4 108.7 86.1 -

62 165.4 11.7 165.4 165.4 165.4 142.4 119.4 96.4 152.0 13.0 152.0 152.0 152.0 129.3 106.6 84.0

57 160.3 11.8 160.3 160.3 160.3 137.3 114.3 91.3 148.3 13.1 148.3 148.3 148.3 125.6 102.9 80.2

Page 95: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 95

115°F 125°F

3125

77 156.3 14.6 67.9 54.8 40.9 - - - 144.5 16.0 60.9 51.5 37.9 - - -

72 142.6 14.5 90.8 77.0 63.1 49.3 - - 131.3 15.9 86.6 73.0 59.4 45.8 - -

67 128.8 14.4 113.7 99.1 85.3 71.5 57.6 - 118.1 15.7 110.3 94.4 80.8 67.2 53.6 -

62 118.4 14.2 118.4 118.4 105.7 91.8 78.0 64.1 108.8 15.6 108.8 108.8 102.4 87.6 74.0 60.4

3750

77 162.8 14.7 75.9 60.2 44.5 - - - 150.2 16.0 72.3 56.7 41.2 - - -

72 148.5 14.6 100.0 84.3 68.6 52.9 - - 136.4 15.9 95.5 80.0 64.4 48.9 - -

67 134.1 14.4 124.1 108.4 92.7 77.0 61.3 - 122.7 15.8 118.8 103.2 87.7 72.1 56.6 -

62 123.3 14.3 123.3 123.3 114.8 99.1 83.4 67.7 113.0 15.6 113.0 113.0 109.8 94.3 78.7 63.2

57 121.1 14.3 121.1 121.1 108.4 92.7 77.0 61.3 112.0 15.7 112.0 112.0 99.7 84.2 68.6 53.1

4375

77 169.3 14.7 83.9 65.6 48.0 - - - 155.8 16.1 83.6 61.9 44.4 - - -

72 154.4 14.6 109.2 91.6 74.1 56.5 - - 141.5 16.0 104.5 87.0 69.5 52.0 - -

67 139.5 14.5 134.5 117.6 100.1 82.5 65.0 - 127.2 15.8 127.2 112.0 94.5 77.0 59.5 -

62 128.2 14.3 128.2 128.2 124.0 106.4 88.8 71.3 117.3 15.7 117.3 117.3 117.3 100.9 83.4 65.9

57 126.0 14.4 126.0 126.0 117.1 99.5 81.9 64.4 116.2 15.7 116.2 116.2 107.5 90.0 72.6 55.1

5000

77 175.8 14.8 91.9 71.0 51.6 - - - 161.4 16.2 95.0 67.0 47.6 - - -

72 160.3 14.7 118.4 98.9 79.5 60.1 - - 146.6 16.0 113.4 93.9 74.5 55.1 - -

67 144.9 14.5 144.9 126.9 107.5 88.1 68.6 - 131.8 15.9 131.8 120.8 101.4 82.0 62.5 -

62 133.1 14.4 133.1 133.1 133.1 113.7 94.3 74.9 121.5 15.7 121.5 121.5 121.5 107.6 88.1 68.7

57 130.8 14.4 130.8 130.8 125.7 106.3 86.9 67.5 120.4 15.8 120.4 120.4 115.4 95.9 76.5 57.0

5625

72 163.7 14.7 128.0 107.1 86.2 65.3 - - 148.9 16.0 122.7 102.0 81.2 60.4 - -

67 147.9 14.5 147.9 137.4 116.5 95.6 74.7 - 133.9 15.9 133.9 131.3 110.5 89.7 69.0 -

62 135.9 14.4 135.9 135.9 135.9 115.0 94.1 73.2 123.4 15.7 123.4 123.4 123.4 105.4 84.6 63.9

57 133.5 14.4 133.5 133.5 131.0 110.1 89.2 68.3 122.3 15.8 122.3 122.3 119.8 99.0 78.3 57.5

6250

72 167.0 14.7 137.7 115.3 92.9 70.5 - - 151.2 16.0 132.0 110.0 87.9 65.8 - -

67 150.9 14.5 150.9 147.9 125.5 103.1 80.7 - 135.9 15.8 135.9 135.9 119.6 97.5 75.4 -

62 138.6 14.4 138.6 138.6 138.6 116.3 93.9 71.5 125.3 15.7 125.3 125.3 125.3 103.2 81.1 59.0

57 136.2 14.4 136.2 136.2 136.2 113.9 91.5 69.1 124.2 15.7 124.2 124.2 124.2 102.1 80.0 58.0

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR150 (12.5 Ton) Cooling (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

90 85 80 75 70 65 90 85 80 75 70 65

Page 96: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

96 Johnson Controls Ducted Systems

ZR150 (12.5 Ton) Reheat

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

35°F 45°F

3125

72 87.0 7.7 6.6 4.8 3.1 - - 85.9 8.3 5.6 3.9 2.2 - -

67 84.6 7.3 14.4 12.7 11.0 9.2 - 83.3 8.0 11.8 10.1 8.4 6.7 -

62 82.9 7.3 20.3 18.6 16.9 15.2 13.5 80.8 7.7 17.7 16.0 14.3 12.6 10.9

3750

72 89.0 7.4 11.5 9.2 6.9 - - 88.9 8.0 10.7 8.3 5.9 - -

67 86.5 7.1 26.3 24.0 21.7 19.5 - 86.2 7.7 24.1 21.7 19.3 17.0 -

62 84.8 7.1 36.7 34.4 32.1 29.8 27.5 83.6 7.4 36.6 34.2 31.9 29.5 27.1

57 82.2 7.7 43.1 40.9 38.6 36.3 34.0 79.1 8.2 40.8 38.4 36.0 33.7 31.3

4375

72 90.9 7.2 16.4 13.5 10.7 - - 91.8 7.7 15.8 12.7 9.7 - -

67 88.4 6.9 38.3 35.4 32.5 29.7 - 89.1 7.4 36.3 33.3 30.2 27.2 -

62 86.6 6.8 53.1 50.2 47.4 44.5 41.6 86.4 7.2 55.5 52.5 49.4 46.4 43.3

57 84.0 7.4 63.2 60.0 57.1 54.2 51.4 81.8 7.9 61.9 58.9 55.8 52.8 49.7

5000

72 92.8 6.9 21.3 17.9 14.4 - - 94.8 7.4 20.9 17.2 13.4 - -

67 90.3 6.6 50.2 46.8 43.3 39.9 - 91.9 7.1 48.6 44.9 41.1 37.4 -

62 88.5 6.6 69.5 66.0 62.6 59.1 55.7 89.2 6.9 74.5 70.7 67.0 63.3 59.5

57 85.9 7.1 83.2 79.1 75.6 72.2 68.7 84.4 7.6 83.1 79.4 75.6 71.9 68.2

5625

72 94.1 7.5 15.2 12.5 9.9 - - 96.7 7.8 16.3 13.1 9.9 - -

67 91.5 7.1 35.5 32.8 30.2 27.5 - 93.8 7.6 37.4 34.2 31.0 27.8 -

62 89.7 7.1 48.0 45.4 42.7 40.1 37.4 91.0 7.3 57.1 53.9 50.7 47.5 44.3

57 87.1 7.7 58.0 55.0 52.4 49.7 47.1 86.1 8.0 63.7 60.5 57.3 54.1 50.8

6250

72 95.4 8.0 9.1 7.2 5.4 - - 98.6 8.3 11.7 9.0 6.3 - -

67 92.8 7.7 20.7 18.9 17.0 15.2 - 95.6 8.0 26.2 23.5 20.8 18.1 -

62 91.0 7.6 26.6 24.7 22.9 21.0 19.2 92.8 7.8 39.8 37.1 34.4 31.7 29.0

57 88.3 8.3 32.9 31.0 29.2 27.3 25.5 87.8 8.5 44.3 41.6 38.9 36.2 33.5

55°F 65°F

3125

72 84.8 8.9 4.6 2.9 1.2 - - 84.2 9.3 - - - - -

67 81.9 8.7 9.3 7.6 5.9 4.2 - 79.1 8.9 10.4 8.9 7.3 5.8 -

62 78.7 8.2 15.1 13.4 11.7 10.0 8.3 74.6 8.4 24.9 23.4 21.8 20.3 18.7

3750

72 88.8 8.6 9.9 7.4 5.0 - - 87.3 9.2 - - - - -

67 85.8 8.3 21.9 19.4 16.9 14.5 - 82.0 8.8 18.2 16.0 13.9 11.8 -

62 82.5 7.8 36.5 34.1 31.6 29.1 26.7 77.4 8.3 40.0 37.9 35.8 33.7 31.5

57 76.1 8.7 38.4 36.0 33.5 31.0 28.6 72.6 9.0 44.1 42.0 39.9 37.8 35.6

4375

72 92.8 8.2 15.2 11.9 8.7 - - 90.4 9.1 - - - - -

67 89.7 8.0 34.4 31.2 27.9 24.7 - 85.0 8.7 25.9 23.2 20.5 17.8 -

62 86.2 7.5 58.0 54.7 51.5 48.3 45.0 80.2 8.2 55.1 52.4 49.8 47.1 44.4

57 79.5 8.3 60.7 57.8 54.6 51.3 48.1 75.2 8.9 60.3 57.7 55.1 52.4 49.7

5000

72 96.8 7.8 20.5 16.5 12.4 - - 93.5 9.0 1.1 - - - -

67 93.6 7.6 47.0 42.9 38.9 34.9 - 87.9 8.6 33.6 30.4 27.1 23.8 -

62 89.9 7.1 79.4 75.4 71.4 67.4 63.4 83.0 8.1 70.3 67.0 63.7 60.4 57.2

57 83.0 8.0 83.0 79.6 75.6 71.6 67.6 77.8 8.8 76.4 73.5 70.2 66.9 63.7

5625

72 99.3 8.2 17.4 13.6 9.8 - - 97.7 9.2 - - - - -

67 96.0 8.0 39.3 35.5 31.8 28.0 - 91.8 8.8 31.7 28.3 25.0 21.6 -

62 92.2 7.5 66.2 62.4 58.7 54.9 51.1 86.6 8.3 69.4 66.0 62.6 59.3 55.9

57 85.1 8.4 69.3 65.9 62.1 58.4 54.6 81.2 9.0 72.7 70.3 66.9 63.6 60.2

6250

72 101.8 8.6 14.3 10.8 7.3 - - 101.9 9.5 - - - - -

67 98.4 8.4 31.7 28.1 24.6 21.1 - 95.7 9.1 29.8 26.3 22.8 19.4 -

62 94.6 7.9 53.0 49.4 45.9 42.4 38.8 90.3 8.6 68.5 65.0 61.6 58.1 54.6

57 87.2 8.8 55.7 52.2 48.7 45.1 41.6 84.7 9.3 68.9 67.1 63.7 60.2 56.8

Page 97: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 97

75°F 85°F

3125

72 83.6 9.7 - - - - - 83.0 10.2 - - - - -

67 76.2 9.2 11.5 10.1 8.7 7.3 - 73.4 9.4 12.6 11.4 10.1 8.8 -

62 70.5 8.7 34.8 33.4 32.0 30.6 29.2 66.4 8.9 44.7 43.4 42.1 40.9 39.6

3750

72 85.8 9.9 - - - - - 84.3 10.5 - - - - -

67 78.2 9.3 14.5 12.7 10.9 9.1 - 74.4 9.7 10.8 9.3 7.9 6.4 -

62 72.3 8.8 43.6 41.8 40.0 38.2 36.4 67.3 9.3 47.1 45.6 44.2 42.7 41.3

57 69.0 9.3 49.8 48.1 46.3 44.5 42.7 65.5 9.7 55.5 54.1 52.7 51.2 49.8

4375

72 88.0 10.0 - - - - - 85.5 10.9 - - - - -

67 80.2 9.4 17.4 15.2 13.1 10.9 - 75.5 10.1 8.9 7.2 5.6 4.0 -

62 74.2 8.9 52.3 50.2 48.0 45.8 43.7 68.2 9.6 49.5 47.9 46.2 44.6 43.0

57 70.8 9.5 59.9 57.7 55.5 53.4 51.2 66.4 10.0 59.4 57.6 56.0 54.4 52.8

5000

72 90.1 10.1 - - - - - 86.8 11.3 - - - - -

67 82.2 9.5 20.3 17.8 15.2 12.7 - 76.5 10.5 7.0 5.2 3.4 1.6 -

62 76.0 9.0 61.1 58.5 56.0 53.5 50.9 69.1 10.0 51.9 50.1 48.3 46.5 44.7

57 72.6 9.6 69.9 67.3 64.8 62.3 59.7 67.4 10.4 63.3 61.2 59.4 57.6 55.8

5625

72 96.1 10.3 - - - - - 94.4 11.3 - - - - -

67 87.6 9.6 24.1 21.1 18.1 15.2 - 83.4 10.5 16.4 13.9 11.3 8.8 -

62 81.0 9.1 72.5 69.6 66.6 63.7 60.7 75.4 9.9 75.4 73.1 70.6 68.0 65.5

57 77.3 9.7 76.0 74.7 71.8 68.8 65.8 73.4 10.4 73.4 73.4 73.4 73.4 71.5

6250

72 102.0 10.4 - - - - - 102.0 11.3 - - - - -

67 93.0 9.8 27.8 24.5 21.1 17.7 - 90.3 10.4 25.9 22.6 19.3 16.0 -

62 86.0 9.2 84.0 80.6 77.2 73.8 70.5 81.7 9.9 81.7 81.7 81.7 81.7 81.7

57 82.1 9.8 82.1 82.1 78.7 75.3 71.9 79.5 10.3 79.5 79.5 79.5 79.5 79.5

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZR150 (12.5 Ton) Reheat (Continued)

Air onEvaporator Coil

Temperature of Air on Condenser Coil

TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh) TotalCapacity1

(MBh)

TotalInput(kW)2

Sensible Capacity (MBh)

CFMWB(°F)

Return Dry Bulb (°F) Return Dry Bulb (°F)

85 80 75 70 65 85 80 75 70 65

Page 98: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

98 Johnson Controls Ducted Systems

Drive Selection

1. Determine side or bottom supply duct Application.

2. Determine desired airflow.

3. Calculate or measure the amount of external static pressure.

• Add or deduct any additional static resistance from “Additional Static Resistance Table”.

4. Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table. (Linear interpolation may be necessary.)

5. Noting the RPM and BHP from step 4, locate the appropriate motor and, or drive on the RPM selection table.

6. Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.

7. Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the chosen motor.

8. Determine turns open to obtain the desired operation point.

Example

1. 2600 CFM

2. 1.6 iwg

3. Using the supply air blower performance table below, the following data point was located: 1268 RPM & 1.95 BHP.

4. Using the RPM selection table below, Size X and Model Y is found.

5. 1.95 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.

6. 1268 RPM is within the range of the 2 HP drives.

7. Using the 2 HP motor and drive, .5 turns open will achieve 1268 RPM.

Airflow Performance

Example Supply Air Blower Performance

Air Flow(CFM)

Available External Static Pressure - IWG0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP1.5 HP & Field Supplied Drive Standard 1.5 HP & Drive Alternate 2 HP & Drive

2200 804 0.50 866 0.71 925 0.90 982 1.06 1038 1.21 1092 1.35 1147 1.48 1203 1.61 1259 1.73 1317 1.87

2400 835 0.66 897 0.87 956 1.06 1013 1.22 1069 1.37 1124 1.51 1178 1.64 1234 1.77 1290 1.90 1348 2.03

2600 869 0.84 931 1.05 990 1.24 1047 1.40 1103 1.55 1158 1.69 1212 1.82 1268 1.95 1324 2.07 1382 2.21

2800 906 1.03 968 1.25 1027 1.43 1084 1.60 1139 1.75 1194 1.89 1249 2.02 1304 2.14 1361 2.27 - -

Example RPM Selection

Size(Tons)

ModelAirflow Option

HPMaxBHP

MotorSheave

BlowerSheave

6 TurnsOpen

5 TurnsOpen

4 TurnsOpen

3 TurnsOpen

2 TurnsOpen

1 TurnOpen

FullyClosed

X YStd. 1.5 1.73 1VM50 AK74 N/A 897 945 991 1035 1079 1126

H. Static 2 2.30 1VM50 AK64 N/A 1039 1094 1150 1207 1256 1308

Example Additional Static Resistance

Size(Tons)

Model CFM Cooling Only Economizer 4” Pleated FilterElectric Heat kW

3 6 9 15 20 24

X Y

900 0.05 -0.05 0.01 0.00 0.00 0.00 0.01 0.01 0.01

1000 0.05 -0.03 0.02 0.00 0.00 0.00 0.02 0.02 0.02

1100 0.04 -0.02 0.03 0.01 0.01 0.01 0.02 0.02 0.02

1200 0.04 0.00 0.04 0.01 0.01 0.01 0.02 0.02 0.02

1300 0.03 0.01 0.05 0.01 0.01 0.01 0.03 0.03 0.03

Page 99: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 99

Altitude and Temperature Correction for CFM, Static Pressure and Power.

The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level.

The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases. In order to

use the indoor blower tables for high altitude applications, certain corrections are necessary.

A centrifugal fan is a "constant volume" device. This means that, if the rpm remains constant, the CFM delivered is the same regardless of the density of the air. However, since the air at high altitude is less dense, less static pressure will be generated and less power will be required than a similar application at sea level. Air density correction factors are shown in Table Altitude/Temperature Correction Factors and following Figure.

The examples below will assist in determining the airflow performance of the product at altitude.

Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?

Solution: At an elevation of 5,000 ft. the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, Airflow Performance Table must be used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. Altitude/Temperature Correction Factors Table shows the correction factor to be 0.832.

Corrected static pressure = 1.5 x 0.832 = 1.248 IWCCorrected BHP = 4.0 x 0.832 = 3.328

Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit blower tables to select the blower speed and the BHP requirement.

Solution: As in the example above, no temperature information is given so 70°F is assumed.

The 1.5" static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions.

Sea level static pressure = 1.5 / .832 = 1.80"Enter the blower table at 6000 CFM and static pressure of 1.8". The rpm listed will be the same rpm needed at 5,000 ft.

Suppose that the corresponding BHP listed in the table is 3.2.This value must be corrected for elevation.

BHP at 5,000 ft. = 3.2 x .832 = 2.66

Altitude/Temperature Correction Factors

AirTemp.

Altitude (Ft.)0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000

40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.72950 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.71560 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.70170 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.68880 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.67690 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663

100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651

0.600

0.650

0.700

0.750

0.800

0.850

0.900

0.950

1.000

1.050

1.100

40 50 60 70 80 90 100Air Temperature (ºF)

Cor

rect

ion

Fact

or

Sea Level

1000 ft

2000 ft

3000 ft

4000 ft

6000 ft7000 ft8000 ft9000 ft10000 ft

5000 ft

Page 100: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

100 Johnson Controls Ducted Systems

Indoor Blower Specifications

Size(Tons)

ModelAirflowOption

Motor Motor Sheave Blower SheaveBelt

HP RPM Eff. SF FrameDatum Dia.

(in.)Bore (in.) Model

Datum Dia.(in.)

Bore (in.) Model

037(3)

ZHStd. 1-1/2 1725 0.8 1.15 56 2.0 - 3.0 7/8 1VM34 6.5 1 AK69 A47

H. Static 1-1/2 1725 0.8 1.15 56 3.0 - 4.0 7/8 1VL44 6.5 1 AK69 A47049(4)

ZHStd. 1-1/2 1725 0.8 1.15 56 2.0 - 3.0 7/8 1VM34 5.2 1 AK56 A47

H. Static 1-1/2 1725 0.8 1.15 56 3.0 - 4.0 7/8 1VL44 5.2 1 AK56 A47061(5)

ZHStd. 1-1/2 1725 0.8 1.15 56 2.6 - 3.6 7/8 1VL40 5.7 1 AK61 A47

H. Static 2 1725 0.8 1.15 56 4.2 - 5.2 7/8 1VP56 7.0 1 AK74 A51078(6.5)

ZHStd. 1-1/2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A49

H. Static 2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 6.0 1 AK64 A49090(7.5)

ZHStd. 1-1/2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A49

H. Static 3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 5.7 1 AK61 A49102(8.5)

ZHStd. 2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 9.0 1 AK94 A56

H. Static 3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54120(10)

ZHStd. 2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 8.0 1 AK84 A56

H. Static 3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54150

(12.5)ZH

Std. 3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54H. Static 5 1725 0.87 1.15 184T 4.3 - 5.3 1-1/8 1VP56 6.7 1 BK77 BX55

037(3)

ZJStd. 1-1/2 1725 0.8 1.15 56 2.0 - 3.0 7/8 1VM34 6.5 1 AK69 A47

H. Static 1-1/2 1725 0.8 1.15 56 3.0 - 4.0 7/8 1VL44 6.5 1 AK69 A47049(4)

ZJStd. 1-1/2 1725 0.8 1.15 56 2.0 - 3.0 7/8 1VM34 5.2 1 AK56 A47

H. Static 1-1/2 1725 0.8 1.15 56 3.0 - 4.0 7/8 1VL44 5.2 1 AK56 A47061(5)

ZJStd. 1-1/2 1725 0.8 1.15 56 2.6 - 3.6 7/8 1VL40 5.7 1 AK61 A47

H. Static 2 1725 0.8 1.15 56 4.2 - 5.2 7/8 1VP56 7.0 1 AK74 A51078(6.5)

ZJStd. 1-1/2 1725 0.8 1.15 56 2.6 - 3.6 7/8 1VL40 7.0 1 AK74 A53

H. Static 2 1725 0.8 1.15 56 3.6 - 4.6 7/8 1VM50 7.0 1 AK74 A54090(7.5)

ZJStd. 1-1/2 1725 0.8 1.15 56 2.6 - 3.6 7/8 1VL40 6.5 1 AK69 A52

H. Static 3 1725 0.8 1.15 56 3.6 - 4.6 7/8 1VM50 6.5 1 AK69 A54102(8.5)

ZJStd. 2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 8.5 1 AK89 A56

H. Static 3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54120(10)

ZJStd. 2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 8.0 1 AK84 A56

H. Static 3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54150

(12.5)ZJ

Std. 3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54H. Static 5 1725 0.87 1.15 184T 4.3 - 5.3 1-1/8 1VP56 6.7 1 BK77 BX55

037ZR

Std. 1-1/2 1725 0.8 1.15 56 1.2 - 2.9 7/8 1VP34 5.7 1 AK61 A47

(3) H. Static 1-1/2 1725 0.8 1.15 56 3.0 - 4.0 7/8 1VL44 5.5 1 AK59 A47

049ZR

Std. 1-1/2 1725 0.8 1.15 56 1.2 - 2.9 7/8 1VP34 5.7 1 AK61 A47

(4) H. Static 1-1/2 1725 0.8 1.15 56 3.0 - 4.0 7/8 1VL44 5.5 1 AK59 A47

061ZR

Std. 1-1/2 1725 0.8 1.15 56 1.2 - 2.9 7/8 1VP34 5.7 1 AK61 A47

(5) H. Static 2 1725 0.8 1.15 56 3.0 - 4.0 7/8 1VL44 5.5 1 AK59 A47

078(6.5)

ZRStd. 1-1/2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A49

H. Static 2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 6.0 1 AK64 A49090(7.5)

ZRStd. 1-1/2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A49

H. Static 3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 5.7 1 AK61 A49102(8.5)

ZRStd. 2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 8.5 1 AK89 A56

H. Static 3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54120(10)

ZRStd. 2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 8.0 1 AK84 A56

H. Static 3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54150

(12.5)ZR

Std. 3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54H. Static 5 1725 0.87 1.15 184T 4.3 - 5.3 1-1/8 1VP56 6.7 1 BK77 BX55

Power Exhaust Specifications

Model VoltageMotor Unit (Per Circuit)

Fuse SizeCFM @0.1 ESPHP RPM1

1. Motors are multi-tapped and factory wired for high speed.

QTY LRA FLA MCA2PE04704706 208/230-1-60 3/4 1075 1 24.9 5 6.3 10 48002PE04704746 460-1-60 3/4 1075 1 N/A 2.2 2.8 5 48002PE04704758 575-1-60 3/4 1050 1 N/A 1.5 1.9 4 4800

Page 101: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 101

RPM Selection

Size(Tons)

ModelAirflow Option

HPMaxBHP

MotorSheave

BlowerSheave

6 TurnsOpen

5 TurnsOpen

4 TurnsOpen

3 TurnsOpen

2 TurnsOpen

1 TurnOpen

FullyClosed

037(3)

ZHStd. 1.5 1.5 1VM34 AK69 N/A 531 584 637 690 743 796

H. Static 1.5 1.5 1VL44 AK69 N/A 796 849 902 955 1008 1062

049(4)

ZHStd. 1.5 1.5 1VM34 AK56 N/A 663 730 796 863 929 995

H. Static 1.5 1.5 1VL44 AK56 N/A 995 1062 1128 1194 1261 1327

061(5)

ZHStd. 1.5 1.5 1VL40 AK61 N/A 787 847 908 968 1029 1089

H. Static 2 2 1VP56 AK74 N/A 1035 1084 1134 1183 1232 1281

078(6.5)

ZHStd. 1.5 1.73 1VM50 AK74 N/A 887 936 986 1035 1084 1134

H. Static 2 2.30 1VM50 AK64 N/A 1039 1094 1150 1207 1256 1308

090(7.5)

ZHStd. 1.5 1.73 1VM50 AK74 N/A 887 936 986 1035 1084 1134

H. Static 3 3.45 1VM50 AK61 N/A 1088 1147 1205 1265 1312 1365

102(8.5)

ZHStd. 2 2.30 1VM50 AK94 N/A 690 728 767 805 843 882

H. Static 3 3.45 1VM50 AK74 N/A 887 936 986 1035 1084 1134

120(10)

ZHStd. 2 2.30 1VM50 AK84 N/A 776 819 863 906 949 992

H. Static 3 3.45 1VM50 AK74 N/A 887 936 986 1035 1084 1134

150(12.5)

ZHStd. 3 3.45 1VM50 AK74 N/A 887 936 986 1035 1084 1134

H. Static 5 5.75 1VP56 BK77 1052 1095 1136 1175 1216 1272 N/A

037(3)

ZJStd. 1.5 1.5 1VM34 AK69 N/A 531 584 637 690 743 796

H. Static 1.5 1.5 1VL44 AK69 N/A 796 849 902 955 1008 1062

049(4)

ZJStd. 1.5 1.5 1VM34 AK56 N/A 663 730 796 863 929 995

H. Static 1.5 1.5 1VL44 AK56 N/A 995 1062 1128 1194 1261 1327

061(5)

ZJStd. 1.5 1.5 1VL40 AK61 N/A 787 847 908 968 1029 1089

H. Static 2 2 1VP56 AK74 N/A 1035 1084 1134 1183 1232 1281

078(6.5)

ZJStd. 1.5 1.73 1VL40 AK74 N/A 641 690 739 789 838 887

H. Static 2 2.30 1VM50 AK74 N/A 887 936 986 1035 1084 1134

090(7.5)

ZJStd. 1.5 1.73 1VL40 AK69 N/A 690 743 796 849 902 955

H. Static 3 3.45 1VM50 AK69 N/A 955 1008 1062 1115 1168 1221

102(8.5)

ZJStd. 2 2.30 1VM50 AK89 N/A 731 771 812 852 893 934

H. Static 3 3.45 1VM50 AK74 N/A 887 936 986 1035 1084 1134

120(10)

ZJStd. 2 2.30 1VM50 AK84 N/A 776 819 863 906 949 992

H. Static 3 3.45 1VM50 AK74 N/A 887 936 986 1035 1084 1134

150(12.5)

ZJStd. 3 3.45 1VM50 AK74 N/A 887 936 986 1035 1084 1134

H. Static 5 5.75 1VP56 BK77 1052 1095 1136 1175 1216 1272 N/A

037(3.0)

ZRStd. 1.5 1.5 1VP34 AK61 N/A 575 636 696 757 817 878

H. Static 1.5 1.5 1VL44 AK59 N/A 878 941 1004 1066 1129 1192

049(4.0)

ZRStd. 1.5 1.5 1VP34 AK61 N/A 575 636 696 757 817 878

H. Static 1.5 1.5 1VL44 AK59 N/A 878 941 1004 1066 1129 1192

061(5.0)

ZRStd. 1.5 1.5 1VP34 AK61 N/A 575 636 696 757 817 878

H. Static 2 2 1VL44 AK59 N/A 878 941 1004 1066 1129 1192

078(6.5)

ZRStd. 1.5 1.73 1VM50 AK74 N/A 897 945 991 1035 1079 1126

H. Static 2 2.30 1VM50 AK64 N/A 1039 1094 1150 1207 1256 1308

090(7.5)

ZRStd. 1.5 1.73 1VM50 AK74 N/A 897 945 991 1035 1079 1126

H. Static 3 3.45 1VM50 AK61 N/A 1088 1147 1205 1265 1312 1365

102(8.5)

ZRStd. 2 2.30 1VM50 AK89 N/A 735 775 815 851 889 930

H. Static 3 3.45 1VM50 AK74 N/A 880 928 972 1016 1067 1110

120(10)

ZRStd. 2 2.30 1VM50 AK84 N/A 785 821 858 901 940 980

H. Static 3 3.45 1VM50 AK74 N/A 880 928 972 1016 1067 1110

150(12.5)

ZRStd. 3 3.45 1VM50 AK74 N/A 880 928 972 1016 1067 1110

H. Static 5 5.75 1VP56 BK77 1052 1095 1136 1175 1216 1272 N/A

Page 102: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

102 Johnson Controls Ducted Systems

Additional Static Resistance - ZH037 thru 061

Size(Tons)

Model CFM Cooling Only1

1. Add these values to the available static resistance in the respective Blower Performance Tables.

Economizer2 3

2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct

is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

4” Pleated Filter2 Electric Heat kW2

3 6 9 15 20 24

037 (3)049 (4)

ZH

900 0.05 -0.05 0.01 0.00 0.00 0.00 0.01 0.01 0.01

1000 0.05 -0.03 0.02 0.00 0.00 0.00 0.02 0.02 0.02

1100 0.04 -0.02 0.03 0.01 0.01 0.01 0.02 0.02 0.02

1200 0.04 0.00 0.04 0.01 0.01 0.01 0.02 0.02 0.02

1300 0.03 0.01 0.05 0.01 0.01 0.01 0.03 0.03 0.03

1400 0.03 0.03 0.07 0.02 0.02 0.02 0.03 0.03 0.03

1500 0.03 0.04 0.08 0.02 0.02 0.02 0.04 0.04 0.04

1600 0.02 0.06 0.09 0.02 0.02 0.02 0.04 0.04 0.04

1700 0.02 0.07 0.10 0.03 0.03 0.03 0.05 0.05 0.05

1800 0.01 0.08 0.11 0.03 0.03 0.03 0.05 0.05 0.05

1900 0.01 0.10 0.13 0.04 0.04 0.04 0.06 0.06 0.06

2000 0.00 0.11 0.14 0.04 0.04 0.04 0.07 0.07 0.07

061 (5) ZH

1500 -0.01 0.13 0.07 0.02 0.02 0.02 0.04 0.04 0.04

1600 -0.01 0.14 0.08 0.02 0.02 0.02 0.04 0.04 0.04

1700 -0.01 0.15 0.08 0.03 0.03 0.03 0.05 0.05 0.05

1800 -0.02 0.16 0.09 0.03 0.03 0.03 0.05 0.05 0.05

1900 -0.02 0.17 0.10 0.04 0.04 0.04 0.06 0.06 0.06

2000 -0.02 0.18 0.10 0.04 0.04 0.04 0.07 0.07 0.07

2100 -0.03 0.19 0.11 0.05 0.05 0.05 0.07 0.07 0.07

2200 -0.03 0.20 0.12 0.06 0.06 0.06 0.08 0.08 0.08

2300 -0.04 0.21 0.12 0.06 0.06 0.06 0.09 0.09 0.09

2400 -0.04 0.22 0.13 0.07 0.07 0.07 0.10 0.10 0.10

2500 -0.05 0.23 0.14 0.08 0.08 0.08 0.11 0.11 0.11

Additional Static Resistance - ZJ/ZR037 thru 061

Size(Tons)

Model CFM Cooling Only1

1. Add these values to the available static resistance in the respective Blower Performance Tables.

Economizer2 3

2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct

is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

4” Pleated Filter2 Electric Heat kW2

3 6 9 15 20 24

037 (3) ZJ/ZR

900 0.05 -0.05 0.01 0.00 0.00 0.00 0.01 0.01 0.01

1000 0.05 -0.03 0.02 0.00 0.00 0.00 0.02 0.02 0.02

1100 0.04 -0.02 0.03 0.01 0.01 0.01 0.02 0.02 0.02

1200 0.04 0.00 0.04 0.01 0.01 0.01 0.02 0.02 0.02

1300 0.03 0.01 0.05 0.01 0.01 0.01 0.03 0.03 0.03

1400 0.03 0.03 0.07 0.02 0.02 0.02 0.03 0.03 0.03

1500 0.03 0.04 0.08 0.02 0.02 0.02 0.04 0.04 0.04

049 (4)061 (5)

ZJ/ZR

1200 -0.01 0.10 0.05 0.01 0.01 0.01 0.02 0.02 0.02

1300 -0.01 0.11 0.06 0.01 0.01 0.01 0.03 0.03 0.03

1400 -0.01 0.12 0.06 0.02 0.02 0.02 0.03 0.03 0.03

1500 -0.01 0.13 0.07 0.02 0.02 0.02 0.04 0.04 0.04

1600 -0.01 0.14 0.08 0.02 0.02 0.02 0.04 0.04 0.04

1700 -0.01 0.15 0.08 0.03 0.03 0.03 0.05 0.05 0.05

1800 -0.02 0.16 0.09 0.03 0.03 0.03 0.05 0.05 0.05

1900 -0.02 0.17 0.10 0.04 0.04 0.04 0.06 0.06 0.06

2000 -0.02 0.18 0.10 0.04 0.04 0.04 0.07 0.07 0.07

2100 -0.03 0.19 0.11 0.05 0.05 0.05 0.07 0.07 0.07

2200 -0.03 0.20 0.12 0.06 0.06 0.06 0.08 0.08 0.08

2300 -0.04 0.21 0.12 0.06 0.06 0.06 0.09 0.09 0.09

2400 -0.04 0.22 0.13 0.07 0.07 0.07 0.10 0.10 0.10

2500 -0.05 0.23 0.14 0.08 0.08 0.08 0.11 0.11 0.11

Page 103: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 103

Additional Static Resistance - ZH/ZR078 thru 150

Size(Tons)

Model CFM Cooling Only1

1. Add these values to the available static resistance in the respective Blower Performance Tables.

Economizer2 3

2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct

is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

4” Filter2 Electric Heat kW2

09 18 24 36 54

078 (6.5)090 (7.5)

ZHZR

1900 0.00 0.07 0.10 0.05 0.06 0.07 0.08 0.10

2100 -0.01 0.09 0.11 0.06 0.07 0.08 0.09 0.11

2300 -0.01 0.11 0.12 0.07 0.08 0.09 0.10 0.13

2500 -0.02 0.13 0.14 0.08 0.09 0.10 0.11 0.14

2700 -0.03 0.16 0.15 0.09 0.10 0.12 0.13 0.16

2900 -0.04 0.18 0.16 0.10 0.11 0.13 0.14 0.18

3100 -0.05 0.20 0.18 0.12 0.13 0.15 0.16 0.20

3300 -0.06 0.22 0.19 0.13 0.14 0.17 0.18 0.22

3500 -0.07 0.24 0.20 0.15 0.16 0.19 0.20 0.24

3700 -0.08 0.27 0.21 0.17 0.18 0.21 0.22 0.26

3900 -0.09 0.29 0.23 0.19 0.20 0.23 0.24 0.28

4100 -0.09 0.31 0.24 0.21 0.22 0.25 0.26 0.31

4300 -0.10 0.30 0.25 0.23 0.24 0.28 0.29 0.34

4500 -0.11 0.35 0.26 0.25 0.26 0.30 0.31 0.37

102 (8.5)120 (10)

150 (12.5)ZH/ZR

1900 0.06 0.02 0.12 0.05 0.06 0.07 0.08 0.10

2100 0.07 0.02 0.13 0.06 0.07 0.08 0.09 0.11

2300 0.08 0.04 0.14 0.07 0.08 0.09 0.10 0.13

2500 0.09 0.11 0.16 0.08 0.09 0.10 0.11 0.14

2700 0.11 0.18 0.17 0.09 0.10 0.12 0.13 0.16

2900 0.12 0.25 0.19 0.10 0.11 0.13 0.14 0.18

3100 0.14 0.31 0.20 0.12 0.13 0.15 0.16 0.20

3300 0.16 0.37 0.22 0.13 0.14 0.17 0.18 0.22

3500 0.18 0.43 0.25 0.15 0.16 0.19 0.20 0.24

3700 0.20 0.49 0.27 0.17 0.18 0.21 0.22 0.26

3900 0.23 0.54 0.29 0.19 0.20 0.23 0.24 0.28

4100 0.25 0.58 0.32 0.21 0.22 0.25 0.26 0.31

4300 0.28 0.65 0.35 0.23 0.24 0.28 0.29 0.34

4500 0.30 0.69 0.38 0.25 0.26 0.30 0.31 0.37

4700 0.33 0.74 0.41 0.28 0.29 0.33 0.34 0.40

4900 0.36 0.78 0.44 0.30 0.31 0.35 0.37 0.43

5100 0.39 0.82 0.47 0.33 0.34 0.38 0.40 0.46

5300 0.42 0.86 0.51 0.35 0.37 0.41 0.43 0.49

5500 0.45 0.89 0.56 0.38 0.40 0.44 0.46 0.53

5700 0.48 0.93 0.58 0.41 0.43 0.47 0.49 0.56

5900 0.52 0.96 0.62 0.44 0.46 0.50 0.53 0.59

6100 0.56 0.98 0.67 0.47 0.49 0.53 0.56 0.62

6300 0.60 1.01 0.71 0.50 0.53 0.56 0.59 0.65

Page 104: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

104 Johnson Controls Ducted Systems

Additional Static Resistance - ZJ078-150

Size(Tons)

Model CFM Cooling Only1

1. Add these values to the available static resistance in the respective Blower Performance Tables.

Economizer2,3

2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is

less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

4” Filter2 Electric Heat kW2

9 18 24 36 54

078 (6.5)090 (7.5)102 (8.5)120 (10)

150 (12.5)

ZJ

1900 0.06 0.02 0.12 0.05 0.06 0.07 0.08 0.10

2100 0.07 0.02 0.13 0.06 0.07 0.08 0.09 0.11

2300 0.08 0.04 0.14 0.07 0.08 0.09 0.10 0.13

2500 0.09 0.11 0.16 0.08 0.09 0.10 0.11 0.14

2700 0.11 0.18 0.17 0.09 0.10 0.12 0.13 0.16

2900 0.12 0.25 0.19 0.10 0.11 0.13 0.14 0.18

3100 0.14 0.31 0.20 0.12 0.13 0.15 0.16 0.20

3300 0.16 0.37 0.22 0.13 0.14 0.17 0.18 0.22

3500 0.18 0.43 0.26 0.15 0.16 0.19 0.20 0.24

3700 0.20 0.49 0.27 0.17 0.18 0.21 0.22 0.26

3900 0.23 0.54 0.29 0.19 0.20 0.23 0.24 0.28

4100 0.25 0.58 0.32 0.21 0.22 0.25 0.26 0.31

4300 0.28 0.65 0.35 0.23 0.24 0.28 0.29 0.34

4500 0.30 0.69 0.38 0.25 0.26 0.30 0.31 0.37

4700 0.33 0.74 0.41 0.28 0.29 0.33 0.34 0.40

4900 0.36 0.78 0.44 0.30 0.31 0.35 0.37 0.43

5100 0.39 0.82 0.47 0.33 0.34 0.38 0.40 0.46

5300 0.42 0.86 0.51 0.35 0.37 0.41 0.43 0.49

5500 0.45 0.89 0.55 0.38 0.40 0.44 0.46 0.53

5700 0.48 0.93 0.58 0.41 0.43 0.47 0.49 0.56

5900 0.52 0.96 0.62 0.44 0.46 0.50 0.53 0.59

6100 0.56 0.98 0.67 0.47 0.49 0.53 0.56 0.62

6300 0.60 1.01 0.71 0.50 0.53 0.56 0.59 0.65

Page 105: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 105

Gas Heat Minimum Supply Air

Size(Tons)

Model Heat SizeSupply Air (CFM)

HeatingMin Max

037(3)

ZH/ZJ/ZRH06 / N06 890 2220H08 / N08 915 2370H12 / N12 1130 1800

049(4)

ZH/ZJ/ZRH06 / N06 890 2220H08 / N08 915 2370H12 / N12 1290 2250

061(5)

ZH/ZJ/ZRH08 / N08 915 2370H12 / N12 1380 2570H16 / N16 1580 2630

078(6.5)

ZH/ZJ/ZRN12 1950 3250N18 1950 3250

090(7.5)

ZH/ZJ/ZRN12 2250 3750N18 2250 3750

102(8.5)

ZH/ZJ/ZRN12 2550 4250N18 2550 4250

120(10)

ZH/ZJ/ZRN18 3000 5000N24 3000 5000

150(12.5)

ZH/ZJ/ZRN18 3750 6250N24 3750 6250

Electric Heat Minimum Supply Air

3 thru 5 Tons

Size(Tons)

Model VoltageMinimum Supply Air (CFM)

Heater kW3 6 9 15 20 24

037(3)

ZH/ZJ/ZR208/230-3-60 960 960 1020 1020 - -

460-3-60 980 960 960 960 - -600-3-60 - - 960 960 - -

049(4)

ZH/ZJ/ZR208/230-3-60 - 1280 1420 1420 1420 -

460-3-60 - 1400 1400 1400 1400 -600-3-60 - - 1400 1400 1400 -

061(5)

ZH/ZJ/ZR208/230-3-60 - 1600 1600 1600 1600 1600

460-3-60 - 1600 1600 1600 1600 1600600-3-60 - - 1600 1600 1600 1600

6-1/2 thru 12-1/5 Tons

Size(Tons)

Model VoltageMinimum Supply Air (CFM)

Heater kW9 18 24 36 54

078(6.5)

ZH/ZJ/ZR208/230-3-60 1950 1950 1950 1950 -

460-3-60 1950 1950 1950 1950 -600-3-60 1950 1950 1950 1950 -

090(7.5)

ZH/ZJ/ZR208/230-3-60 2250 2250 2250 2250 -

460-3-60 2250 2250 2250 2250 -600-3-60 2250 2250 2250 2250 -

102(8.5)

ZH/ZJ/ZR208/230-3-60 2550 2550 2550 2550 -

460-3-60 2550 2550 2550 2550 -600-3-60 2550 2550 2550 2550 -

120(10)

ZH/ZJ/ZR208/230-3-60 - 3000 3000 3000 3500

460-3-60 - 3000 3000 3000 3000600-3-60 - 3000 3000 3000 3500

150(12.5)

ZH/ZJ/ZR208/230-3-60 - 3750 3750 3750 4000

460-3-60 - 3750 3750 3750 3750600-3-60 - 3750 3750 3750 3750

Page 106: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

106 Johnson Controls Ducted Systems

Airflow Performance

ZH037-150 Side Duct Application

ZH037 (3.0 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Standard 1.5 HP & Drive Hi Static 1.5 HP & Drive

900 560 0.29 628 0.35 695 0.42 760 0.51 823 0.61 886 0.72 949 0.82 1011 0.92 1073 1.01 1136 1.09

1000 582 0.29 650 0.34 716 0.42 781 0.51 845 0.61 908 0.71 970 0.82 1032 0.92 1095 1.01 1158 1.08

1100 601 0.30 670 0.35 736 0.43 801 0.52 864 0.62 927 0.72 990 0.83 1052 0.93 1114 1.02 1177 1.09

1200 620 0.32 688 0.37 754 0.45 819 0.54 883 0.64 946 0.74 1008 0.85 1070 0.95 1133 1.04 1196 1.11

1300 638 0.35 706 0.40 772 0.48 837 0.57 901 0.67 964 0.77 1026 0.88 1088 0.98 1151 1.06 1214 1.14

1400 655 0.39 724 0.44 790 0.51 855 0.60 918 0.70 981 0.81 1044 0.91 1106 1.01 1168 1.10 1231 1.18

1500 673 0.43 741 0.48 807 0.56 872 0.65 936 0.75 999 0.85 1061 0.96 1124 1.06 1186 1.15 1249 1.22

1.5 HP & Field Supplied Drive

ZH049 (4.0 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 1.5 HP & Drive Hi Static 1.5 HP & Drive

1200 620 0.32 688 0.37 754 0.45 819 0.54 883 0.64 946 0.74 1008 0.85 1070 0.95 1133 1.04 1196 1.11

1300 638 0.35 706 0.40 772 0.48 837 0.57 901 0.67 964 0.77 1026 0.88 1088 0.98 1151 1.06 1214 1.14

1400 655 0.39 724 0.44 790 0.51 855 0.60 918 0.70 981 0.81 1044 0.91 1106 1.01 1168 1.10 1231 1.18

1500 673 0.43 741 0.48 807 0.56 872 0.65 936 0.75 999 0.85 1061 0.96 1124 1.06 1186 1.15 1249 1.22

1600 691 0.48 759 0.54 825 0.61 890 0.70 954 0.80 1017 0.90 1079 1.01 1141 1.11 1204 1.20 1267 1.27

1700 709 0.54 777 0.59 843 0.67 908 0.76 972 0.86 1035 0.96 1097 1.07 1160 1.17 1222 1.26 1285 1.33

1800 728 0.60 796 0.66 862 0.73 927 0.82 991 0.92 1053 1.03 1116 1.13 1178 1.23 1241 1.32 1303 1.39

1900 747 0.67 815 0.73 881 0.80 946 0.89 1010 0.99 1073 1.09 1135 1.20 1197 1.30 1260 1.39 1323 1.46

2000 766 0.75 834 0.80 901 0.87 966 0.96 1029 1.06 1092 1.17 1155 1.27 1217 1.37 1279 1.46 - -

ZH061 (5.0 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1.5 HP & Field Supplied Drive Standard 1.5 HP & DriveHi Static 2 HP & Drive

1500 659 0.35 719 0.46 780 0.57 843 0.67 905 0.77 964 0.87 1020 0.97 1071 1.07 1116 1.17 1154 1.28

1600 675 0.38 735 0.50 796 0.60 859 0.71 920 0.81 980 0.91 1036 1.01 1087 1.11 1132 1.21 1170 1.32

1700 691 0.42 751 0.54 812 0.64 875 0.75 936 0.85 996 0.95 1052 1.05 1103 1.15 1148 1.25 1186 1.36

1800 707 0.47 767 0.58 829 0.69 891 0.79 953 0.90 1012 0.99 1069 1.09 1120 1.20 1165 1.30 1202 1.41

1900 724 0.53 784 0.64 846 0.75 908 0.85 970 0.95 1029 1.05 1085 1.15 1137 1.25 1182 1.35 1219 1.46

2000 741 0.59 801 0.70 863 0.81 925 0.91 987 1.01 1047 1.11 1103 1.21 1154 1.31 1199 1.41 1236 1.52

2100 759 0.65 819 0.77 881 0.87 943 0.98 1005 1.08 1065 1.18 1121 1.28 1172 1.38 1217 1.48 1254 1.59

2200 778 0.73 838 0.84 900 0.95 962 1.05 1024 1.15 1083 1.25 1139 1.35 1191 1.45 1236 1.56 1273 1.66

2300 797 0.81 857 0.92 919 1.03 981 1.13 1043 1.23 1103 1.33 1159 1.43 1210 1.53 1255 1.64 1292 1.74

2400 817 0.90 877 1.01 939 1.12 1002 1.22 1063 1.32 1123 1.42 1179 1.52 1230 1.62 1275 1.73 1312 1.83

2500 838 1.00 898 1.11 960 1.22 1022 1.32 1084 1.42 1144 1.52 1200 1.62 1251 1.72 1296 1.82 1333 1.93

FS4

Page 107: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 107

ZH078 (6.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 1.5 HP & Drive Hi Static 2 HP & Drive

1800 751 0.22 813 0.43 872 0.62 929 0.78 985 0.93 1040 1.07 1095 1.20 1150 1.33 1206 1.46 1265 1.59

2000 776 0.35 838 0.56 897 0.75 954 0.92 1010 1.07 1064 1.20 1119 1.33 1175 1.46 1231 1.59 1289 1.72

2200 804 0.50 866 0.71 925 0.90 982 1.06 1038 1.21 1092 1.35 1147 1.48 1203 1.61 1259 1.73 1317 1.87

2400 835 0.66 897 0.87 956 1.06 1013 1.22 1069 1.37 1124 1.51 1178 1.64 1234 1.77 1290 1.90 1348 2.03

2600 869 0.84 931 1.05 990 1.24 1047 1.40 1103 1.55 1158 1.69 1212 1.82 1268 1.95 1324 2.07 1382 2.21

2800 906 1.03 968 1.25 1027 1.43 1084 1.60 1139 1.75 1194 1.89 1249 2.02 1304 2.14 1361 2.27 - -

3000 945 1.25 1007 1.46 1066 1.65 1123 1.81 1179 1.96 1234 2.10 1288 2.23 - - - - - -

3200 987 1.48 1048 1.69 1107 1.88 1165 2.04 1220 2.19 - - - - - - - - - -

3400 1030 1.73 1092 1.94 1151 2.12 1208 2.29 - - - - - - - - - - - -

2 HP & Field Supplied Drive

ZH090 (7.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 1.5 HP & Drive Hi Static 3 HP & Drive

2000 776 0.35 838 0.56 897 0.75 954 0.92 1010 1.07 1064 1.20 1119 1.33 1175 1.46 1231 1.59 1289 1.72

2200 804 0.50 866 0.71 925 0.90 982 1.06 1038 1.21 1092 1.35 1147 1.48 1203 1.61 1259 1.73 1317 1.87

2400 835 0.66 897 0.87 956 1.06 1013 1.22 1069 1.37 1124 1.51 1178 1.64 1234 1.77 1290 1.90 1348 2.03

2600 869 0.84 931 1.05 990 1.24 1047 1.40 1103 1.55 1158 1.69 1212 1.82 1268 1.95 1324 2.07 1382 2.21

2800 906 1.03 968 1.25 1027 1.43 1084 1.60 1139 1.75 1194 1.89 1249 2.02 1304 2.14 1361 2.27 1419 2.40

3000 945 1.25 1007 1.46 1066 1.65 1123 1.81 1179 1.96 1234 2.10 1288 2.23 1344 2.36 1400 2.48 1458 2.62

3200 987 1.48 1048 1.69 1107 1.88 1165 2.04 1220 2.19 1275 2.33 1330 2.46 1385 2.59 1442 2.71 1500 2.85

3400 1030 1.73 1092 1.94 1151 2.12 1208 2.29 1264 2.44 1319 2.58 1374 2.71 1429 2.84 1485 2.96 1544 3.10

3600 1076 1.99 1138 2.20 1197 2.39 1254 2.56 1310 2.71 1364 2.84 1419 2.97 1475 3.10 1531 3.23 1589 3.36

3800 1124 2.27 1185 2.48 1245 2.67 1302 2.84 1357 2.99 1412 3.12 1467 3.25 1522 3.38 - - - -

3 HP & Field Supplied Drive

ZH102 (8.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 2 HP & Drive Hi Static 3 HP & Drive

2600 628 0.56 678 0.76 730 0.93 781 1.09 833 1.25 883 1.41 933 1.59 980 1.80 1025 2.05 1068 2.35

2800 648 0.67 698 0.87 750 1.04 801 1.20 853 1.36 903 1.52 953 1.70 1000 1.91 1046 2.16 1088 2.46

3000 666 0.80 717 1.00 768 1.17 820 1.33 871 1.49 922 1.65 971 1.83 1019 2.04 1064 2.29 1106 2.59

3200 684 0.95 735 1.15 786 1.32 838 1.48 889 1.63 940 1.80 989 1.98 1037 2.19 1082 2.44 1124 2.74

3400 702 1.11 753 1.31 804 1.48 856 1.64 907 1.79 958 1.96 1007 2.14 1055 2.35 1100 2.60 1142 2.90

3600 721 1.28 772 1.48 824 1.65 875 1.81 927 1.97 977 2.13 1027 2.31 1074 2.52 1119 2.77 - -

3800 742 1.47 793 1.67 844 1.84 896 2.00 947 2.15 998 2.32 1047 2.50 1095 2.71 1140 2.96 - -

4000 765 1.67 815 1.86 867 2.04 918 2.19 970 2.35 1020 2.51 1070 2.70 1117 2.91 - - - -

4200 789 1.87 840 2.07 891 2.24 943 2.40 995 2.56 1045 2.72 1094 2.90 - - - - - -

3 HP & Field Supplied Drive

Page 108: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

108 Johnson Controls Ducted Systems

ZH120 (10 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 2 HP & Drive Hi Static 3 HP & Drive

2600 675 0.53 726 0.74 776 0.94 824 1.12 870 1.30 914 1.48 957 1.65 1000 1.82 1041 1.99 1082 2.17

2800 686 0.63 738 0.84 787 1.04 835 1.23 881 1.41 925 1.58 969 1.76 1011 1.93 1052 2.10 1093 2.27

3000 699 0.75 750 0.96 800 1.16 847 1.34 893 1.52 938 1.70 981 1.87 1024 2.04 1065 2.21 1106 2.39

3200 713 0.88 764 1.09 814 1.28 861 1.47 907 1.65 952 1.83 995 2.00 1037 2.17 1079 2.34 1119 2.52

3400 728 1.02 779 1.23 829 1.43 877 1.61 923 1.79 967 1.97 1010 2.14 1053 2.31 1094 2.48 1135 2.66

3600 745 1.18 796 1.39 846 1.59 893 1.77 939 1.95 984 2.13 1027 2.30 1069 2.47 1111 2.64 1152 2.82

3800 763 1.36 815 1.57 864 1.76 912 1.95 958 2.13 1002 2.31 1046 2.48 1088 2.65 1129 2.82 1170 3.00

4000 783 1.55 835 1.76 884 1.96 932 2.15 978 2.33 1022 2.50 1066 2.67 1108 2.84 1149 3.02 1190 3.19

4200 805 1.77 856 1.98 906 2.17 953 2.36 999 2.54 1044 2.72 1087 2.89 1129 3.06 1171 3.23 1211 3.41

4400 828 2.00 879 2.21 929 2.41 976 2.59 1022 2.77 1067 2.95 1110 3.12 1152 3.29 - - - -

4600 852 2.25 904 2.46 953 2.66 1001 2.85 1047 3.03 1092 3.20 1135 3.37 - - - - - -

4800 879 2.52 930 2.73 980 2.93 1027 3.12 1073 3.30 - - - - - - - - - -

5000 906 2.81 958 3.02 1007 3.22 1055 3.41 - - - - - - - - - - - -

3 HP & Field Supplied Drive

ZH150 (12.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 3 HP & Drive

3200 713 0.88 764 1.09 814 1.28 861 1.47 907 1.65 952 1.83 995 2.00 1037 2.17 1079 2.34 1119 2.52

3400 728 1.02 779 1.23 829 1.43 877 1.61 923 1.79 967 1.97 1010 2.14 1053 2.31 1094 2.48 1135 2.66

3600 745 1.18 796 1.39 846 1.59 893 1.77 939 1.95 984 2.13 1027 2.30 1069 2.47 1111 2.64 1152 2.82

3800 763 1.36 815 1.57 864 1.76 912 1.95 958 2.13 1002 2.31 1046 2.48 1088 2.65 1129 2.82 1170 3.00

4000 783 1.55 835 1.76 884 1.96 932 2.15 978 2.33 1022 2.50 1066 2.67 1108 2.84 1149 3.02 1190 3.19

4200 805 1.77 856 1.98 906 2.17 953 2.36 999 2.54 1044 2.72 1087 2.89 1129 3.06 1171 3.23 1211 3.41

4400 828 2.00 879 2.21 929 2.41 976 2.59 1022 2.77 1067 2.95 1110 3.12 1152 3.29 1194 3.46 1235 3.64

4600 852 2.25 904 2.46 953 2.66 1001 2.85 1047 3.03 1092 3.20 1135 3.37 1177 3.54 1219 3.72 1259 3.89

4800 879 2.52 930 2.73 980 2.93 1027 3.12 1073 3.30 1118 3.47 1161 3.65 1203 3.82 1245 3.99 1285 4.16

5000 906 2.81 958 3.02 1007 3.22 1055 3.41 1101 3.59 1146 3.76 1189 3.94 1231 4.11 1273 4.28 1313 4.45

5200 936 3.12 987 3.33 1037 3.53 1084 3.72 1130 3.90 1175 4.07 1218 4.24 1260 4.42 1302 4.59 1343 4.76

5400 966 3.45 1018 3.66 1067 3.86 1115 4.05 1161 4.23 1206 4.40 1249 4.57 1291 4.74 1333 4.91 1373 5.09

5600 999 3.80 1050 4.01 1100 4.20 1147 4.39 1193 4.57 1238 4.75 1281 4.92 1323 5.09 1365 5.26 1405 5.44

5800 1032 4.16 1084 4.37 1133 4.57 1181 4.75 1227 4.93 1271 5.11 1315 5.28 1357 5.45 1398 5.62 - -

6000 1067 4.54 1119 4.75 1168 4.95 1216 5.13 1262 5.31 1306 5.49 1350 5.66 - - - - - -

6200 1103 4.94 1155 5.15 1204 5.34 1252 5.53 1298 5.71 - - - - - - - - - -

Hi Static 5 HP & Drive 5 HP & Field Supplied Drive

Page 109: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 109

ZH037-150 Bottom Duct Application

ZH037 (3.0 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Standard 1.5 HP & Drive Hi Static 1.5 HP & Drive

900 605 0.23 671 0.33 738 0.42 804 0.52 869 0.62 933 0.71 995 0.80 1054 0.89 1111 0.98 1164 1.07

1000 621 0.25 688 0.34 754 0.44 820 0.53 885 0.63 949 0.72 1011 0.82 1071 0.91 1127 1.00 1180 1.09

1100 637 0.27 703 0.36 769 0.46 835 0.56 900 0.65 964 0.74 1026 0.84 1086 0.93 1142 1.02 1195 1.11

1200 651 0.30 717 0.39 784 0.49 850 0.58 915 0.68 979 0.77 1041 0.87 1100 0.96 1157 1.05 1210 1.13

1300 666 0.33 732 0.43 799 0.52 865 0.62 930 0.71 994 0.81 1056 0.90 1115 0.99 1172 1.08 1225 1.17

1400 681 0.37 747 0.47 814 0.56 880 0.66 945 0.75 1009 0.85 1071 0.94 1130 1.03 1187 1.12 1240 1.21

1500 697 0.42 763 0.51 830 0.61 896 0.71 961 0.80 1025 0.90 1087 0.99 1146 1.08 1203 1.17 1256 1.26

1.5 HP & Field Supplied Drive

ZH049 (4.0 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 1.5 HP & Drive Hi Static 1.5 HP & Drive

1200 651 0.30 717 0.39 784 0.49 850 0.58 915 0.68 979 0.77 1041 0.87 1100 0.96 1157 1.05 1210 1.13

1300 666 0.33 732 0.43 799 0.52 865 0.62 930 0.71 994 0.81 1056 0.90 1115 0.99 1172 1.08 1225 1.17

1400 681 0.37 747 0.47 814 0.56 880 0.66 945 0.75 1009 0.85 1071 0.94 1130 1.03 1187 1.12 1240 1.21

1500 697 0.42 763 0.51 830 0.61 896 0.71 961 0.80 1025 0.90 1087 0.99 1146 1.08 1203 1.17 1256 1.26

1600 714 0.47 780 0.57 846 0.66 913 0.76 978 0.86 1042 0.95 1103 1.04 1163 1.14 1220 1.22 1273 1.31

1700 732 0.53 798 0.63 864 0.73 930 0.82 996 0.92 1059 1.01 1121 1.10 1181 1.20 1237 1.29 1291 1.37

1800 751 0.60 817 0.70 883 0.79 950 0.89 1015 0.98 1079 1.08 1140 1.17 1200 1.26 1257 1.35 1310 1.44

1900 771 0.68 837 0.77 904 0.87 970 0.96 1035 1.06 1099 1.15 1161 1.25 1220 1.34 1277 1.43 - -

2000 793 0.75 859 0.85 925 0.95 991 1.04 1056 1.14 1120 1.23 1182 1.32 1242 1.42 1298 1.51 - -

ZH061 (5.0 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP1.5 HP & Field Supplied Drive Standard 1.5 HP & Drive Hi Static 2 HP & Drive

1500 673 0.47 736 0.54 797 0.63 855 0.72 910 0.82 964 0.92 1016 1.03 1067 1.14 1117 1.25 1166 1.36

1600 693 0.49 756 0.57 817 0.65 874 0.75 930 0.85 984 0.95 1036 1.06 1087 1.17 1137 1.28 1186 1.39

1700 713 0.53 777 0.60 837 0.69 895 0.78 951 0.88 1004 0.98 1057 1.09 1107 1.20 1157 1.31 1207 1.42

1800 734 0.57 797 0.65 858 0.73 916 0.83 971 0.92 1025 1.03 1077 1.14 1128 1.25 1178 1.36 1228 1.47

1900 755 0.62 819 0.70 879 0.79 937 0.88 992 0.98 1046 1.08 1098 1.19 1149 1.30 1199 1.41 1249 1.52

2000 776 0.69 840 0.76 900 0.85 958 0.94 1014 1.04 1067 1.14 1120 1.25 1171 1.36 1221 1.47 1270 1.59

2100 798 0.76 861 0.84 921 0.92 979 1.02 1035 1.11 1089 1.22 1141 1.32 1192 1.44 1242 1.55 1291 1.66

2200 819 0.84 882 0.92 943 1.00 1001 1.10 1056 1.20 1110 1.30 1162 1.41 1213 1.52 1263 1.63 1312 1.74

2300 840 0.93 903 1.01 964 1.10 1022 1.19 1077 1.29 1131 1.39 1183 1.50 1234 1.61 1284 1.72 1334 1.83

2400 861 1.03 925 1.11 985 1.20 1043 1.29 1099 1.39 1152 1.49 1204 1.60 1255 1.71 1305 1.82 1355 1.93

2500 882 1.14 946 1.22 1006 1.30 1064 1.40 1120 1.50 1173 1.60 1226 1.71 1276 1.82 1326 1.93 1376 2.04

3 HP & Field Supplied Drive

Page 110: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

110 Johnson Controls Ducted Systems

ZH078 (6.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 1.5 HP & Drive Hi Static 2 HP & Drive

1800 775 0.31 850 0.53 924 0.72 998 0.89 1072 1.05 1147 1.20 1224 1.35 1303 1.51 1384 1.69 1469 1.89

2000 803 0.45 878 0.67 952 0.86 1026 1.03 1100 1.19 1175 1.34 1252 1.49 1331 1.65 1412 1.83 1497 2.03

2200 838 0.60 913 0.82 986 1.01 1060 1.19 1134 1.34 1210 1.49 1286 1.65 1365 1.81 1447 1.98 1532 2.18

2400 878 0.78 953 1.00 1027 1.19 1100 1.36 1174 1.52 1250 1.67 1327 1.82 1405 1.98 1487 2.16 - -

2600 923 0.98 997 1.20 1071 1.39 1145 1.56 1219 1.72 1294 1.87 1371 2.02 1450 2.18 - - - -

2800 971 1.20 1046 1.42 1119 1.61 1193 1.78 1267 1.94 1343 2.09 1419 2.24 - - - - - -

3000 1023 1.44 1097 1.66 1171 1.85 1245 2.03 1319 2.18 - - - - - - - - - -

3200 1077 1.71 1151 1.93 1225 2.12 1299 2.29 - - - - - - - - - - - -

3400 1133 1.99 1208 2.21 - - - - - - - - - - - - - - - -

2 HP & Field Supplied Drive

ZH090 (7.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 1.5 HP & Drive Hi Static 3 HP & Drive

2000 803 0.45 878 0.67 952 0.86 1026 1.03 1100 1.19 1175 1.34 1252 1.49 1331 1.65 1412 1.83 1497 2.03

2200 838 0.60 913 0.82 986 1.01 1060 1.19 1134 1.34 1210 1.49 1286 1.65 1365 1.81 1447 1.98 1532 2.18

2400 878 0.78 953 1.00 1027 1.19 1100 1.36 1174 1.52 1250 1.67 1327 1.82 1405 1.98 1487 2.16 1572 2.36

2600 923 0.98 997 1.20 1071 1.39 1145 1.56 1219 1.72 1294 1.87 1371 2.02 1450 2.18 1532 2.36 1617 2.56

2800 971 1.20 1046 1.42 1119 1.61 1193 1.78 1267 1.94 1343 2.09 1419 2.24 1498 2.40 1580 2.58 1665 2.78

3000 1023 1.44 1097 1.66 1171 1.85 1245 2.03 1319 2.18 1394 2.33 1471 2.49 1550 2.65 1632 2.82 1717 3.02

3200 1077 1.71 1151 1.93 1225 2.12 1299 2.29 1373 2.45 1448 2.60 1525 2.75 1604 2.91 1686 3.09 1771 3.29

3400 1133 1.99 1208 2.21 1282 2.41 1356 2.58 1430 2.73 1505 2.88 1582 3.04 1661 3.20 1742 3.37 - -

3600 1192 2.30 1267 2.52 1341 2.71 1414 2.88 1489 3.04 1564 3.19 1641 3.34 - - - - - -

3800 1253 2.63 1327 2.85 1401 3.04 1475 3.21 1549 3.37 - - - - - - - - - -

3 HP & Field Supplied Drive

ZH102 (8.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 2 HP & Drive Hi Static 3 HP & Drive

2600 674 0.71 731 0.88 786 1.05 838 1.24 887 1.42 933 1.59 974 1.74 1010 1.87 1040 1.97 1064 2.03

2800 689 0.86 746 1.02 801 1.20 854 1.38 903 1.56 948 1.73 989 1.88 1025 2.01 1056 2.11 1080 2.17

3000 707 1.01 764 1.17 819 1.35 872 1.53 921 1.71 966 1.88 1007 2.03 1043 2.16 1074 2.26 1098 2.32

3200 728 1.17 785 1.33 840 1.51 892 1.69 941 1.87 987 2.04 1028 2.20 1064 2.33 1094 2.42 1118 2.48

3400 751 1.34 808 1.51 863 1.68 915 1.87 964 2.05 1010 2.22 1051 2.37 1087 2.50 1117 2.60 1141 2.66

3600 776 1.53 833 1.70 888 1.87 941 2.06 990 2.24 1035 2.41 1076 2.56 1112 2.69 1142 2.79 1167 2.85

3800 804 1.74 861 1.90 916 2.08 969 2.26 1018 2.44 1063 2.61 1104 2.77 1140 2.90 1170 2.99 - -

4000 835 1.97 892 2.13 947 2.31 999 2.49 1048 2.67 1094 2.84 1135 2.99 - - - - - -

4200 867 2.21 924 2.37 979 2.55 1032 2.73 1081 2.91 1127 3.08 - - - - - - - -

3 HP & Field Supplied Drive

Page 111: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 111

ZH120 (10 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPField Supplied

DriveStandard 2 HP & Drive Hi Static 3 HP & Drive

2600 722 0.83 776 0.97 828 1.11 878 1.25 926 1.37 973 1.50 1018 1.62 1063 1.74 1106 1.86 1149 1.99

2800 744 0.97 798 1.12 850 1.26 900 1.39 949 1.52 995 1.64 1041 1.76 1085 1.88 1128 2.00 1171 2.13

3000 769 1.13 823 1.28 875 1.42 925 1.55 974 1.68 1020 1.80 1066 1.92 1110 2.05 1153 2.17 1196 2.29

3200 797 1.32 851 1.46 903 1.60 953 1.74 1001 1.86 1048 1.99 1093 2.11 1138 2.23 1181 2.35 1224 2.48

3400 828 1.52 882 1.67 934 1.81 983 1.94 1032 2.07 1078 2.19 1124 2.32 1168 2.44 1212 2.56 1254 2.68

3600 861 1.75 915 1.90 967 2.04 1017 2.17 1065 2.30 1112 2.42 1157 2.54 1201 2.67 1245 2.79 1287 2.91

3800 897 2.00 951 2.15 1002 2.29 1052 2.42 1101 2.55 1147 2.67 1193 2.80 1237 2.92 1280 3.04 1323 3.16

4000 935 2.27 989 2.42 1041 2.56 1091 2.69 1139 2.82 1186 2.95 1231 3.07 1275 3.19 1319 3.31 1362 3.43

4200 976 2.57 1030 2.72 1082 2.86 1132 2.99 1180 3.12 1227 3.24 1272 3.36 - - - - - -

4400 1019 2.88 1073 3.03 1125 3.17 1175 3.30 1223 3.43 - - - - - - - - - -

4600 1065 3.22 1119 3.36 - - - - - - - - - - - - - - - -

3 HP & Field Supplied Drive

ZH150 (12.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 3 HP & Drive Hi Static 5 HP & Drive

3200 797 1.32 851 1.46 903 1.60 953 1.74 1001 1.86 1048 1.99 1093 2.11 1138 2.23 1181 2.35 1224 2.48

3400 828 1.52 882 1.67 934 1.81 983 1.94 1032 2.07 1078 2.19 1124 2.32 1168 2.44 1212 2.56 1254 2.68

3600 861 1.75 915 1.90 967 2.04 1017 2.17 1065 2.30 1112 2.42 1157 2.54 1201 2.67 1245 2.79 1287 2.91

3800 897 2.00 951 2.15 1002 2.29 1052 2.42 1101 2.55 1147 2.67 1193 2.80 1237 2.92 1280 3.04 1323 3.16

4000 935 2.27 989 2.42 1041 2.56 1091 2.69 1139 2.82 1186 2.95 1231 3.07 1275 3.19 1319 3.31 1362 3.43

4200 976 2.57 1030 2.72 1082 2.86 1132 2.99 1180 3.12 1227 3.24 1272 3.36 1316 3.48 1360 3.60 1402 3.73

4400 1019 2.88 1073 3.03 1125 3.17 1175 3.30 1223 3.43 1270 3.55 1315 3.67 1360 3.80 1403 3.92 1446 4.04

4600 1065 3.22 1119 3.36 1171 3.50 1221 3.64 1269 3.76 1316 3.89 1361 4.01 1405 4.13 1449 4.25 1491 4.38

4800 1113 3.57 1167 3.72 1219 3.86 1269 3.99 1317 4.12 1364 4.24 1409 4.36 1453 4.48 1497 4.61 1540 4.73

5000 1163 3.94 1217 4.09 1269 4.23 1319 4.36 1367 4.49 1414 4.62 1459 4.74 1504 4.86 1547 4.98 1590 5.10

5200 1216 4.34 1270 4.48 1321 4.62 1371 4.76 1420 4.88 1466 5.01 1512 5.13 1556 5.25 1600 5.37 1642 5.50

5400 1270 4.75 1324 4.89 1376 5.03 1426 5.17 1474 5.29 1521 5.42 1566 5.54 1611 5.66 - - - -

5600 1327 5.17 1381 5.32 1433 5.46 1483 5.59 1531 5.72 - - - - - - - - - -

5800 1385 5.62 - - - - - - - - - - - - - - - - - -

5 HP & Field Supplied Drive

Page 112: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

112 Johnson Controls Ducted Systems

ZJ037-150 Side Duct Application

ZJ037 (3.0 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Standard 1.5 HP & Drive Hi Static 1.5 HP & Drive

900 560 0.29 628 0.35 695 0.42 760 0.51 823 0.61 886 0.72 949 0.82 1011 0.92 1073 1.01 1136 1.09

1000 582 0.29 650 0.34 716 0.42 781 0.51 845 0.61 908 0.71 970 0.82 1032 0.92 1095 1.01 1158 1.08

1100 601 0.30 670 0.35 736 0.43 801 0.52 864 0.62 927 0.72 990 0.83 1052 0.93 1114 1.02 1177 1.09

1200 620 0.32 688 0.37 754 0.45 819 0.54 883 0.64 946 0.74 1008 0.85 1070 0.95 1133 1.04 1196 1.11

1300 638 0.35 706 0.40 772 0.48 837 0.57 901 0.67 964 0.77 1026 0.88 1088 0.98 1151 1.06 1214 1.14

1400 655 0.39 724 0.44 790 0.51 855 0.60 918 0.70 981 0.81 1044 0.91 1106 1.01 1168 1.10 1231 1.18

1500 673 0.43 741 0.48 807 0.56 872 0.65 936 0.75 999 0.85 1061 0.96 1124 1.06 1186 1.15 1249 1.22

1.5 HP & Field Supplied Drive

ZJ049 (4.0 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 1.5 HP & Drive Hi Static 1.5 HP & Drive

1200 608 0.25 677 0.34 744 0.44 807 0.54 868 0.64 927 0.74 986 0.84 1043 0.93 1101 1.02 1160 1.10

1300 623 0.28 692 0.37 758 0.47 822 0.57 883 0.67 942 0.77 1001 0.86 1058 0.96 1116 1.04 1175 1.13

1400 637 0.31 706 0.40 772 0.50 836 0.60 897 0.70 956 0.80 1015 0.90 1072 0.99 1130 1.08 1189 1.16

1500 650 0.35 720 0.44 786 0.54 849 0.64 911 0.74 970 0.84 1028 0.93 1086 1.03 1144 1.12 1202 1.20

1600 664 0.39 734 0.49 800 0.58 863 0.68 924 0.78 984 0.88 1042 0.98 1100 1.07 1158 1.16 1216 1.24

1700 678 0.44 748 0.54 814 0.63 877 0.73 938 0.83 998 0.93 1056 1.03 1114 1.12 1172 1.21 1230 1.29

1800 693 0.50 763 0.59 829 0.69 892 0.79 953 0.89 1013 0.99 1071 1.08 1129 1.18 1186 1.26 1245 1.35

1900 708 0.56 778 0.65 844 0.75 907 0.85 968 0.95 1028 1.05 1086 1.15 1144 1.24 1202 1.33 1260 1.41

2000 725 0.62 794 0.72 860 0.82 924 0.92 985 1.02 1044 1.12 1102 1.21 1160 1.30 1218 1.39 1277 1.47

ZJ061 (5.0 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1.5 HP & Field Suplied Drive Standard 1.5 HP & Drive Hi Static 2 HP & Drive

1500 659 0.35 719 0.46 780 0.57 843 0.67 905 0.77 964 0.87 1020 0.97 1071 1.07 1116 1.17 1154 1.28

1600 675 0.38 735 0.50 796 0.60 859 0.71 920 0.81 980 0.91 1036 1.01 1087 1.11 1132 1.21 1170 1.32

1700 691 0.42 751 0.54 812 0.64 875 0.75 936 0.85 996 0.95 1052 1.05 1103 1.15 1148 1.25 1186 1.36

1800 707 0.47 767 0.58 829 0.69 891 0.79 953 0.90 1012 0.99 1069 1.09 1120 1.20 1165 1.30 1202 1.41

1900 724 0.53 784 0.64 846 0.75 908 0.85 970 0.95 1029 1.05 1085 1.15 1137 1.25 1182 1.35 1219 1.46

2000 741 0.59 801 0.70 863 0.81 925 0.91 987 1.01 1047 1.11 1103 1.21 1154 1.31 1199 1.41 1236 1.52

2100 759 0.65 819 0.77 881 0.87 943 0.98 1005 1.08 1065 1.18 1121 1.28 1172 1.38 1217 1.48 1254 1.59

2200 778 0.73 838 0.84 900 0.95 962 1.05 1024 1.15 1083 1.25 1139 1.35 1191 1.45 1236 1.56 1273 1.66

2300 797 0.81 857 0.92 919 1.03 981 1.13 1043 1.23 1103 1.33 1159 1.43 1210 1.53 1255 1.64 1292 1.74

2400 817 0.90 877 1.01 939 1.12 1002 1.22 1063 1.32 1123 1.42 1179 1.52 1230 1.62 1275 1.73 1312 1.83

2500 838 1.00 898 1.11 960 1.22 1022 1.32 1084 1.42 1144 1.52 1200 1.62 1251 1.72 1296 1.82 1333 1.93

FS4

Page 113: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 113

ZJ078 (6.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 1.5 HP & Drive Hi Static 2 HP & Drive

1800 514 0.15 586 0.33 657 0.52 727 0.71 794 0.89 857 1.07 917 1.23 972 1.38 1021 1.50 1064 1.59

2000 529 0.23 601 0.41 672 0.60 741 0.79 808 0.97 872 1.15 931 1.31 986 1.46 1036 1.58 1079 1.67

2200 544 0.33 616 0.51 687 0.69 756 0.88 823 1.07 886 1.24 946 1.41 1001 1.55 1051 1.67 1094 1.77

2400 559 0.43 631 0.61 702 0.80 771 0.98 838 1.17 902 1.35 961 1.51 1016 1.65 1066 1.78 1109 1.87

2600 574 0.54 646 0.72 717 0.91 787 1.10 853 1.28 917 1.46 977 1.62 1032 1.77 1081 1.89 1124 1.98

2800 590 0.67 662 0.85 733 1.03 802 1.22 869 1.41 933 1.59 993 1.75 1047 1.89 1097 2.02 1140 2.11

3000 607 0.80 679 0.98 750 1.17 819 1.36 886 1.54 949 1.72 1009 1.88 1064 2.03 1113 2.15 1157 2.24

3200 624 0.95 695 1.13 766 1.31 836 1.50 903 1.69 966 1.86 1026 2.03 1081 2.17 1130 2.29 - -

3400 641 1.10 713 1.28 784 1.47 853 1.66 920 1.84 984 2.02 1043 2.18 1098 2.33 - - - -

FS4

ZJ090 (7.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 1.5 HP & Drive Hi Static 3 HP & Drive

2000 - - 656 0.24 711 0.48 768 0.73 826 0.96 886 1.19 945 1.41 1003 1.61 1058 1.79 1110 1.95

2200 619 0.07 670 0.32 724 0.57 781 0.81 840 1.04 899 1.27 959 1.49 1016 1.69 1072 1.87 1124 2.04

2400 631 0.16 682 0.41 736 0.66 793 0.90 852 1.14 911 1.36 970 1.58 1028 1.78 1084 1.97 1136 2.13

2600 642 0.27 692 0.52 747 0.76 804 1.01 862 1.24 922 1.47 981 1.69 1039 1.89 1094 2.07 1146 2.24

2800 652 0.39 703 0.64 757 0.88 814 1.13 873 1.36 932 1.59 992 1.81 1049 2.01 1105 2.19 1157 2.36

3000 663 0.53 714 0.77 768 1.02 825 1.26 884 1.50 943 1.73 1003 1.94 1060 2.14 1116 2.33 1168 2.49

3200 675 0.68 726 0.92 780 1.17 837 1.41 896 1.65 955 1.88 1014 2.09 1072 2.29 1128 2.48 1180 2.64

3400 688 0.84 739 1.09 793 1.34 850 1.58 909 1.82 968 2.04 1027 2.26 1085 2.46 1141 2.65 1193 2.81

3600 703 1.03 753 1.28 807 1.52 864 1.76 923 2.00 983 2.23 1042 2.44 1100 2.64 1155 2.83 - -

3800 718 1.23 769 1.47 823 1.72 880 1.96 939 2.20 998 2.43 1058 2.64 1115 2.84 1171 3.03 - -

ZJ102 (8.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 2 HP & Drive Hi Static 3 HP & Drive

2200 654 0.32 706 0.53 755 0.73 803 0.92 849 1.10 893 1.27 937 1.44 979 1.62 1020 1.79 1061 1.96

2400 664 0.43 716 0.64 765 0.83 813 1.02 859 1.20 904 1.38 947 1.55 989 1.72 1030 1.89 1071 2.07

2600 675 0.53 726 0.74 776 0.94 824 1.12 870 1.30 914 1.48 957 1.65 1000 1.82 1041 1.99 1082 2.17

2800 686 0.63 738 0.84 787 1.04 835 1.23 881 1.41 925 1.58 969 1.76 1011 1.93 1052 2.10 1093 2.27

3000 699 0.75 750 0.96 800 1.16 847 1.34 893 1.52 938 1.70 981 1.87 1024 2.04 1065 2.21 1106 2.39

3200 713 0.88 764 1.09 814 1.28 861 1.47 907 1.65 952 1.83 995 2.00 1037 2.17 1079 2.34 1119 2.52

3400 728 1.02 779 1.23 829 1.43 877 1.61 923 1.79 967 1.97 1010 2.14 1053 2.31 1094 2.48 1135 2.66

3600 745 1.18 796 1.39 846 1.59 893 1.77 939 1.95 984 2.13 1027 2.30 1069 2.47 1111 2.64 1152 2.82

3800 763 1.36 815 1.57 864 1.76 912 1.95 958 2.13 1002 2.31 1046 2.48 1088 2.65 1129 2.82 1170 3.00

4000 783 1.55 835 1.76 884 1.96 932 2.15 978 2.33 1022 2.50 1066 2.67 1108 2.84 1149 3.02 1190 3.19

4200 805 1.77 856 1.98 906 2.17 953 2.36 999 2.54 1044 2.72 1087 2.89 1129 3.06 1171 3.23 1211 3.41

3 HP & Field Supplied Drive

Page 114: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

114 Johnson Controls Ducted Systems

ZJ120 (10 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 2 HP & Drive Hi Static 3 HP & Drive

2600 675 0.53 726 0.74 776 0.94 824 1.12 870 1.30 914 1.48 957 1.65 1000 1.82 1041 1.99 1082 2.17

2800 686 0.63 738 0.84 787 1.04 835 1.23 881 1.41 925 1.58 969 1.76 1011 1.93 1052 2.10 1093 2.27

3000 699 0.75 750 0.96 800 1.16 847 1.34 893 1.52 938 1.70 981 1.87 1024 2.04 1065 2.21 1106 2.39

3200 713 0.88 764 1.09 814 1.28 861 1.47 907 1.65 952 1.83 995 2.00 1037 2.17 1079 2.34 1119 2.52

3400 728 1.02 779 1.23 829 1.43 877 1.61 923 1.79 967 1.97 1010 2.14 1053 2.31 1094 2.48 1135 2.66

3600 745 1.18 796 1.39 846 1.59 893 1.77 939 1.95 984 2.13 1027 2.30 1069 2.47 1111 2.64 1152 2.82

3800 763 1.36 815 1.57 864 1.76 912 1.95 958 2.13 1002 2.31 1046 2.48 1088 2.65 1129 2.82 1170 3.00

4000 783 1.55 835 1.76 884 1.96 932 2.15 978 2.33 1022 2.50 1066 2.67 1108 2.84 1149 3.02 1190 3.19

4200 805 1.77 856 1.98 906 2.17 953 2.36 999 2.54 1044 2.72 1087 2.89 1129 3.06 1171 3.23 1211 3.41

4400 828 2.00 879 2.21 929 2.41 976 2.59 1022 2.77 1067 2.95 1110 3.12 1152 3.29 - - - -

4600 852 2.25 904 2.46 953 2.66 1001 2.85 1047 3.03 1092 3.20 1135 3.37 - - - - - -

4800 879 2.52 930 2.73 980 2.93 1027 3.12 1073 3.30 - - - - - - - - - -

5000 906 2.81 958 3.02 1007 3.22 1055 3.41 - - - - - - - - - - - -

3 HP & Field Supplied Drive

ZJ150 (12.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 3 HP & Drive

3200 713 0.88 764 1.09 814 1.28 861 1.47 907 1.65 952 1.83 995 2.00 1037 2.17 1079 2.34 1119 2.52

3400 728 1.02 779 1.23 829 1.43 877 1.61 923 1.79 967 1.97 1010 2.14 1053 2.31 1094 2.48 1135 2.66

3600 745 1.18 796 1.39 846 1.59 893 1.77 939 1.95 984 2.13 1027 2.30 1069 2.47 1111 2.64 1152 2.82

3800 763 1.36 815 1.57 864 1.76 912 1.95 958 2.13 1002 2.31 1046 2.48 1088 2.65 1129 2.82 1170 3.00

4000 783 1.55 835 1.76 884 1.96 932 2.15 978 2.33 1022 2.50 1066 2.67 1108 2.84 1149 3.02 1190 3.19

4200 805 1.77 856 1.98 906 2.17 953 2.36 999 2.54 1044 2.72 1087 2.89 1129 3.06 1171 3.23 1211 3.41

4400 828 2.00 879 2.21 929 2.41 976 2.59 1022 2.77 1067 2.95 1110 3.12 1152 3.29 1194 3.46 1235 3.64

4600 852 2.25 904 2.46 953 2.66 1001 2.85 1047 3.03 1092 3.20 1135 3.37 1177 3.54 1219 3.72 1259 3.89

4800 879 2.52 930 2.73 980 2.93 1027 3.12 1073 3.30 1118 3.47 1161 3.65 1203 3.82 1245 3.99 1285 4.16

5000 906 2.81 958 3.02 1007 3.22 1055 3.41 1101 3.59 1146 3.76 1189 3.94 1231 4.11 1273 4.28 1313 4.45

5200 936 3.12 987 3.33 1037 3.53 1084 3.72 1130 3.90 1175 4.07 1218 4.24 1260 4.42 1302 4.59 1343 4.76

5400 966 3.45 1018 3.66 1067 3.86 1115 4.05 1161 4.23 1206 4.40 1249 4.57 1291 4.74 1333 4.91 1373 5.09

5600 999 3.80 1050 4.01 1100 4.20 1147 4.39 1193 4.57 1238 4.75 1281 4.92 1323 5.09 1365 5.26 1405 5.44

5800 1032 4.16 1084 4.37 1133 4.57 1181 4.75 1227 4.93 1271 5.11 1315 5.28 1357 5.45 1398 5.62 - -

6000 1067 4.54 1119 4.75 1168 4.95 1216 5.13 1262 5.31 1306 5.49 1350 5.66 - - - - - -

6200 1103 4.94 1155 5.15 1204 5.34 1252 5.53 1298 5.71 - - - - - - - - - -

Hi Static 5 HP & Drive 5 HP & Field Supplied Drive

Page 115: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 115

ZJ037-150 Bottom Duct Application

ZJ037 (3.0 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Standard 1.5 HP & Drive Hi Static 1.5 HP & Drive

900 605 0.23 671 0.33 738 0.42 804 0.52 869 0.62 933 0.71 995 0.80 1054 0.89 1111 0.98 1164 1.07

1000 621 0.25 688 0.34 754 0.44 820 0.53 885 0.63 949 0.72 1011 0.82 1071 0.91 1127 1.00 1180 1.09

1100 637 0.27 703 0.36 769 0.46 835 0.56 900 0.65 964 0.74 1026 0.84 1086 0.93 1142 1.02 1195 1.11

1200 651 0.30 717 0.39 784 0.49 850 0.58 915 0.68 979 0.77 1041 0.87 1100 0.96 1157 1.05 1210 1.13

1300 666 0.33 732 0.43 799 0.52 865 0.62 930 0.71 994 0.81 1056 0.90 1115 0.99 1172 1.08 1225 1.17

1400 681 0.37 747 0.47 814 0.56 880 0.66 945 0.75 1009 0.85 1071 0.94 1130 1.03 1187 1.12 1240 1.21

1500 697 0.42 763 0.51 830 0.61 896 0.71 961 0.80 1025 0.90 1087 0.99 1146 1.08 1203 1.17 1256 1.26

1.5 HP & Field Supplied Drive

ZJ049 (4.0 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 1.5 HP & Drive Hi Static 1.5 HP & Drive

1200 635 0.25 704 0.34 770 0.44 832 0.54 893 0.65 953 0.75 1013 0.85 1073 0.94 1134 1.02 1197 1.08

1300 648 0.28 717 0.38 782 0.47 845 0.58 906 0.68 966 0.78 1025 0.88 1085 0.97 1147 1.05 1210 1.12

1400 661 0.32 730 0.42 796 0.51 858 0.62 919 0.72 979 0.82 1039 0.92 1099 1.01 1160 1.09 1223 1.16

1500 675 0.37 744 0.46 810 0.56 872 0.66 933 0.77 993 0.87 1053 0.96 1113 1.05 1174 1.14 1237 1.20

1600 690 0.42 759 0.51 825 0.61 887 0.72 948 0.82 1008 0.92 1068 1.02 1128 1.11 1189 1.19 1252 1.26

1700 706 0.48 775 0.57 841 0.67 903 0.77 964 0.88 1024 0.98 1084 1.08 1144 1.17 1205 1.25 1268 1.31

1800 723 0.55 792 0.64 857 0.74 920 0.84 981 0.94 1041 1.04 1101 1.14 1161 1.23 1222 1.31 1285 1.38

1900 741 0.62 810 0.71 875 0.81 938 0.91 999 1.01 1059 1.11 1118 1.21 1178 1.30 1240 1.38 1303 1.45

2000 760 0.69 829 0.79 894 0.88 957 0.99 1018 1.09 1078 1.19 1137 1.29 1197 1.38 1258 1.46 1322 1.53

ZJ061 (5.0 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP1.5 HP & Field Supplied Drive Standard 1.5 HP & Drive Hi Static 2 HP & Drive

1500 673 0.47 736 0.54 797 0.63 855 0.72 910 0.82 964 0.92 1016 1.03 1067 1.14 1117 1.25 1166 1.36

1600 693 0.49 756 0.57 817 0.65 874 0.75 930 0.85 984 0.95 1036 1.06 1087 1.17 1137 1.28 1186 1.39

1700 713 0.53 777 0.60 837 0.69 895 0.78 951 0.88 1004 0.98 1057 1.09 1107 1.20 1157 1.31 1207 1.42

1800 734 0.57 797 0.65 858 0.73 916 0.83 971 0.92 1025 1.03 1077 1.14 1128 1.25 1178 1.36 1228 1.47

1900 755 0.62 819 0.70 879 0.79 937 0.88 992 0.98 1046 1.08 1098 1.19 1149 1.30 1199 1.41 1249 1.52

2000 776 0.69 840 0.76 900 0.85 958 0.94 1014 1.04 1067 1.14 1120 1.25 1171 1.36 1221 1.47 1270 1.59

2100 798 0.76 861 0.84 921 0.92 979 1.02 1035 1.11 1089 1.22 1141 1.32 1192 1.44 1242 1.55 1291 1.66

2200 819 0.84 882 0.92 943 1.00 1001 1.10 1056 1.20 1110 1.30 1162 1.41 1213 1.52 1263 1.63 1312 1.74

2300 840 0.93 903 1.01 964 1.10 1022 1.19 1077 1.29 1131 1.39 1183 1.50 1234 1.61 1284 1.72 1334 1.83

2400 861 1.03 925 1.11 985 1.20 1043 1.29 1099 1.39 1152 1.49 1204 1.60 1255 1.71 1305 1.82 1355 1.93

2500 882 1.14 946 1.22 1006 1.30 1064 1.40 1120 1.50 1173 1.60 1226 1.71 1276 1.82 1326 1.93 1376 2.04

2 HP & Field Supplied Drive

Page 116: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

116 Johnson Controls Ducted Systems

ZJ078 (6.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 1.5 HP & Drive Hi Static 2 HP & Drive

1800 603 0.13 656 0.36 718 0.58 784 0.79 851 0.98 914 1.16 968 1.31 1010 1.43 1035 1.53 1039 1.59

2000 627 0.26 680 0.49 742 0.71 808 0.92 875 1.12 937 1.29 992 1.44 1034 1.57 1059 1.66 1063 1.72

2200 650 0.40 703 0.63 765 0.85 831 1.06 898 1.25 961 1.43 1015 1.58 1057 1.71 1082 1.80 1086 1.86

2400 673 0.55 726 0.78 788 1.00 854 1.21 921 1.40 984 1.58 1038 1.73 1080 1.85 1105 1.95 1109 2.01

2600 696 0.71 749 0.94 811 1.16 878 1.37 944 1.56 1007 1.73 1061 1.89 1103 2.01 1128 2.10 1133 2.16

2800 720 0.87 773 1.10 835 1.32 902 1.53 968 1.73 1031 1.90 1085 2.05 1127 2.18 1152 2.27 1157 2.33

3000 745 1.05 798 1.28 860 1.50 926 1.71 993 1.91 1056 2.08 1110 2.23 1152 2.36 1177 2.45 1181 2.51

3200 771 1.24 824 1.47 886 1.69 952 1.90 1019 2.09 1081 2.27 1136 2.42 1178 2.54 1203 2.64 1207 2.70

3400 797 1.44 850 1.67 912 1.89 979 2.10 1045 2.29 1108 2.47 1162 2.62 1204 2.74 1229 2.84 1234 2.90

3 HP & Field Supplied Drive

ZJ090 (7.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 1.5 HP & Drive Hi Static 3 HP & Drive

2000 644 0.11 698 0.38 755 0.62 814 0.85 874 1.06 933 1.26 990 1.46 1043 1.66 1090 1.87 1131 2.09

2200 666 0.26 720 0.53 777 0.77 836 1.00 896 1.21 956 1.41 1012 1.61 1065 1.81 1113 2.02 1153 2.24

2400 689 0.42 743 0.69 800 0.93 859 1.16 919 1.37 978 1.57 1035 1.77 1088 1.97 1135 2.18 1176 2.40

2600 712 0.60 766 0.87 823 1.11 882 1.34 942 1.55 1002 1.75 1058 1.95 1111 2.15 1159 2.36 1199 2.58

2800 736 0.80 790 1.06 847 1.31 906 1.53 967 1.74 1026 1.94 1082 2.14 1135 2.34 1183 2.55 1223 2.78

3000 761 1.00 815 1.27 872 1.52 931 1.74 991 1.95 1051 2.15 1107 2.35 1160 2.55 1208 2.76 1248 2.98

3200 787 1.22 840 1.49 898 1.74 957 1.96 1017 2.17 1076 2.37 1133 2.57 1186 2.77 1233 2.98 1274 3.20

3400 813 1.46 867 1.73 924 1.97 984 2.19 1044 2.40 1103 2.61 1160 2.80 1212 3.01 1260 3.21 - -

3600 841 1.70 894 1.97 952 2.21 1011 2.44 1071 2.65 1130 2.85 1187 3.05 - - - - - -

3800 869 1.96 923 2.22 980 2.47 1039 2.69 1099 2.90 1158 3.10 1215 3.30 - - - - - -

3 HP & Field Supplied Drive

ZJ102 (8.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 2 HP & Drive Hi Static 3 HP & Drive

2200 685 0.59 739 0.74 791 0.88 841 1.01 889 1.14 936 1.27 981 1.39 1025 1.51 1069 1.63 1111 1.75

2400 702 0.70 756 0.85 808 0.99 858 1.12 906 1.25 953 1.37 999 1.49 1043 1.62 1086 1.74 1129 1.86

2600 722 0.83 776 0.97 828 1.11 878 1.25 926 1.37 973 1.50 1018 1.62 1063 1.74 1106 1.86 1149 1.99

2800 744 0.97 798 1.12 850 1.26 900 1.39 949 1.52 995 1.64 1041 1.76 1085 1.88 1128 2.00 1171 2.13

3000 769 1.13 823 1.28 875 1.42 925 1.55 974 1.68 1020 1.80 1066 1.92 1110 2.05 1153 2.17 1196 2.29

3200 797 1.32 851 1.46 903 1.60 953 1.74 1001 1.86 1048 1.99 1093 2.11 1138 2.23 1181 2.35 1224 2.48

3400 828 1.52 882 1.67 934 1.81 983 1.94 1032 2.07 1078 2.19 1124 2.32 1168 2.44 1212 2.56 1254 2.68

3600 861 1.75 915 1.90 967 2.04 1017 2.17 1065 2.30 1112 2.42 1157 2.54 1201 2.67 1245 2.79 1287 2.91

3800 897 2.00 951 2.15 1002 2.29 1052 2.42 1101 2.55 1147 2.67 1193 2.80 1237 2.92 1280 3.04 1323 3.16

4000 935 2.27 989 2.42 1041 2.56 1091 2.69 1139 2.82 1186 2.95 1231 3.07 1275 3.19 1319 3.31 1362 3.43

4200 976 2.57 1030 2.72 1082 2.86 1132 2.99 1180 3.12 1227 3.24 1272 3.36 - - - - - -

3 HP & Field Supplied Drive

Page 117: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 117

ZJ120 (10 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPField Supplied

DriveStandard 2 HP & Drive Hi Static 3 HP & Drive

2600 722 0.83 776 0.97 828 1.11 878 1.25 926 1.37 973 1.50 1018 1.62 1063 1.74 1106 1.86 1149 1.99

2800 744 0.97 798 1.12 850 1.26 900 1.39 949 1.52 995 1.64 1041 1.76 1085 1.88 1128 2.00 1171 2.13

3000 769 1.13 823 1.28 875 1.42 925 1.55 974 1.68 1020 1.80 1066 1.92 1110 2.05 1153 2.17 1196 2.29

3200 797 1.32 851 1.46 903 1.60 953 1.74 1001 1.86 1048 1.99 1093 2.11 1138 2.23 1181 2.35 1224 2.48

3400 828 1.52 882 1.67 934 1.81 983 1.94 1032 2.07 1078 2.19 1124 2.32 1168 2.44 1212 2.56 1254 2.68

3600 861 1.75 915 1.90 967 2.04 1017 2.17 1065 2.30 1112 2.42 1157 2.54 1201 2.67 1245 2.79 1287 2.91

3800 897 2.00 951 2.15 1002 2.29 1052 2.42 1101 2.55 1147 2.67 1193 2.80 1237 2.92 1280 3.04 1323 3.16

4000 935 2.27 989 2.42 1041 2.56 1091 2.69 1139 2.82 1186 2.95 1231 3.07 1275 3.19 1319 3.31 1362 3.43

4200 976 2.57 1030 2.72 1082 2.86 1132 2.99 1180 3.12 1227 3.24 1272 3.36 - - - - - -

4400 1019 2.88 1073 3.03 1125 3.17 1175 3.30 1223 3.43 - - - - - - - - - -

4600 1065 3.22 1119 3.36 - - - - - - - - - - - - - - - -

3 HP & Field Supplied Drive

ZJ150 (12.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard 3 HP & Drive Hi Static 5 HP & Drive

3200 797 1.32 851 1.46 903 1.60 953 1.74 1001 1.86 1048 1.99 1093 2.11 1138 2.23 1181 2.35 1224 2.48

3400 828 1.52 882 1.67 934 1.81 983 1.94 1032 2.07 1078 2.19 1124 2.32 1168 2.44 1212 2.56 1254 2.68

3600 861 1.75 915 1.90 967 2.04 1017 2.17 1065 2.30 1112 2.42 1157 2.54 1201 2.67 1245 2.79 1287 2.91

3800 897 2.00 951 2.15 1002 2.29 1052 2.42 1101 2.55 1147 2.67 1193 2.80 1237 2.92 1280 3.04 1323 3.16

4000 935 2.27 989 2.42 1041 2.56 1091 2.69 1139 2.82 1186 2.95 1231 3.07 1275 3.19 1319 3.31 1362 3.43

4200 976 2.57 1030 2.72 1082 2.86 1132 2.99 1180 3.12 1227 3.24 1272 3.36 1316 3.48 1360 3.60 1402 3.73

4400 1019 2.88 1073 3.03 1125 3.17 1175 3.30 1223 3.43 1270 3.55 1315 3.67 1360 3.80 1403 3.92 1446 4.04

4600 1065 3.22 1119 3.36 1171 3.50 1221 3.64 1269 3.76 1316 3.89 1361 4.01 1405 4.13 1449 4.25 1491 4.38

4800 1113 3.57 1167 3.72 1219 3.86 1269 3.99 1317 4.12 1364 4.24 1409 4.36 1453 4.48 1497 4.61 1540 4.73

5000 1163 3.94 1217 4.09 1269 4.23 1319 4.36 1367 4.49 1414 4.62 1459 4.74 1504 4.86 1547 4.98 1590 5.10

5200 1216 4.34 1270 4.48 1321 4.62 1371 4.76 1420 4.88 1466 5.01 1512 5.13 1556 5.25 1600 5.37 1642 5.50

5400 1270 4.75 1324 4.89 1376 5.03 1426 5.17 1474 5.29 1521 5.42 1566 5.54 1611 5.66 - - - -

5600 1327 5.17 1381 5.32 1433 5.46 1483 5.59 1531 5.72 - - - - - - - - - -

5800 1385 5.62 - - - - - - - - - - - - - - - - - -

5 HP & Field Supplied Drive

Page 118: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

118 Johnson Controls Ducted Systems

ZR037-150 Side Duct Application

ZR037 (3.0 Ton) Side Duct

ZR049 (4.0 Ton) Side Duct

ZR061 (5.0 Ton) Side Duct

Air Flow

(CFM)

Available External Static Pressure - IWG1

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 1.5 HP & Drive Hi Static 1.5 HP & Drive

900 480 0.4 582 0.4 673 0.5 756 0.5 830 0.6 898 0.7 960 0.8 1018 0.9 1072 1.0 1124 1.1

1000 489 0.4 591 0.4 682 0.5 764 0.6 839 0.6 907 0.7 969 0.8 1026 0.9 1080 1.0 1132 1.1

1100 500 0.4 602 0.4 693 0.5 776 0.6 850 0.6 918 0.7 980 0.8 1038 0.9 1092 1.0 1144 1.1

1200 513 0.4 614 0.5 706 0.5 788 0.6 863 0.7 931 0.8 993 0.8 1050 0.9 1104 1.0 1156 1.1

1300 525 0.4 627 0.5 719 0.6 801 0.6 876 0.7 943 0.8 1005 0.9 1063 1.0 1117 1.1 1169 1.2

1400 537 0.5 639 0.5 731 0.6 813 0.7 888 0.7 955 0.8 1017 0.9 1075 1.0 1129 1.1 1181 1.2

1500 549 0.5 650 0.6 742 0.6 824 0.7 899 0.8 966 0.9 1028 0.9 1086 1.0 1140 1.1 1192 1.2

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

Air Flow(CFM

Available External Static Pressure - IWG1

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1.5 HP & Field Supplied Drive

Standard 1.5 HP & Drive Hi Static 1.5 HP & Drive

1200 513 0.4 614 0.5 706 0.5 788 0.6 863 0.7 931 0.8 993 0.8 1050 0.9 1104 1.0 1156 1.1

1300 525 0.4 627 0.5 719 0.6 801 0.6 876 0.7 943 0.8 1005 0.9 1063 1.0 1117 1.1 1169 1.2

1400 537 0.5 639 0.5 731 0.6 813 0.7 888 0.7 955 0.8 1017 0.9 1075 1.0 1129 1.1 1181 1.2

1500 549 0.5 650 0.6 742 0.6 824 0.7 899 0.8 966 0.9 1028 0.9 1086 1.0 1140 1.1 1192 1.2

1600 558 0.6 660 0.6 752 0.7 834 0.8 909 0.8 976 0.9 1038 1.0 1096 1.1 1150 1.2 1202 1.3

1700 566 0.6 668 0.7 760 0.7 842 0.8 917 0.9 984 1.0 1046 1.1 1104 1.1 1158 1.2 1210 1.4

1800 573 0.7 675 0.7 766 0.8 849 0.9 923 1.0 991 1.0 1053 1.1 1110 1.2 1164 1.3 1216 1.4

1900 577 0.8 679 0.8 771 0.9 853 1.0 928 1.0 995 1.1 1057 1.2 1115 1.3 1169 1.4 1221 1.5

2000 580 0.8 682 0.9 773 1.0 856 1.0 930 1.1 998 1.2 1060 1.3 1117 1.4 1172 1.5 1224 1.6

FS4

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

Air Flow

(CFM)

Available External Static Pressure - IWG1

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPStandard 1.5 HP & Drive Hi Static 2 HP & Drive

1500 616 0.5 685 0.6 766 0.7 833 0.8 905 0.9 975 1.0 1035 1.0 1101 1.1 1163 1.2 1229 1.3

1600 638 0.6 707 0.7 781 0.7 848 0.8 920 0.9 990 1.0 1050 1.1 1104 1.1 1166 1.2 1232 1.3

1700 655 0.6 724 0.7 796 0.8 863 0.9 935 1.0 1005 1.1 1064 1.1 1109 1.2 1172 1.3 1238 1.4

1800 670 0.7 739 0.8 810 0.8 877 0.9 949 1.0 1018 1.1 1078 1.2 1117 1.2 1179 1.3 1245 1.5

1900 686 0.7 755 0.8 823 0.9 890 1.0 962 1.1 1032 1.2 1091 1.2 1125 1.3 1187 1.4 1253 1.5

2000 702 0.8 772 0.9 836 1.0 903 1.1 975 1.2 1045 1.3 1078 1.3 1135 1.4 1197 1.5 1263 1.6

2100 722 0.9 791 1.0 849 1.0 916 1.1 988 1.2 1058 1.3 1089 1.4 1147 1.5 1209 1.6 1275 1.7

2200 745 0.9 814 1.0 861 1.1 928 1.2 1000 1.3 1050 1.4 1102 1.5 1159 1.6 1221 1.7 1287 1.8

2300 772 1.0 841 1.1 874 1.2 941 1.3 1013 1.4 1064 1.5 1115 1.6 1173 1.7 1235 1.8 - -

2400 804 1.1 832 1.2 886 1.3 953 1.4 1033 1.4 1078 1.6 1130 1.7 1188 1.8 - - - -

2500 841 1.2 844 1.3 898 1.4 965 1.5 1049 1.5 1094 1.7 - - - - 2 HP & Field Supplied Drive

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

Page 119: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 119

ZR078-150 Side Duct Application

ZR078 (6.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1.5 HP & Field Supplied Drive Standard 1.5 HP & Drive Hi Static 2 HP & Drive

1800 778 0.37 838 0.56 895 0.73 951 0.88 1005 1.01 1059 1.13 1112 1.25 1166 1.36 1221 1.47 1278 1.59

2000 803 0.50 864 0.69 921 0.85 977 1.00 1031 1.14 1085 1.26 1138 1.37 1192 1.49 1247 1.60 1304 1.72

2200 833 0.64 893 0.83 951 1.00 1006 1.14 1061 1.28 1114 1.40 1168 1.51 1221 1.63 1276 1.74 1333 1.86

2400 866 0.80 926 0.99 984 1.15 1039 1.30 1094 1.43 1147 1.56 1201 1.67 1254 1.78 1309 1.90 1366 2.02

2600 902 0.97 962 1.16 1020 1.33 1076 1.47 1130 1.61 1183 1.73 1237 1.85 1291 1.96 1346 2.07 1402 2.19

2800 941 1.16 1002 1.35 1059 1.52 1115 1.67 1169 1.80 1222 1.92 1276 2.04 1330 2.15 1385 2.26 - -

3000 983 1.37 1043 1.56 1101 1.73 1157 1.88 1211 2.01 1264 2.13 1318 2.25 - - - - - -

3200 1028 1.60 1088 1.79 1145 1.95 1201 2.10 1255 2.24 - - - - - - - - - -

3400 1074 1.84 1134 2.03 1192 2.20 - - - - - - - - - - - - - -

2 HP & Field Supplied Drive

ZR090 (7.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP1.5 HP & Field Supplied Drive Standard 1.5 HP & Drive Hi Static 3 HP & Drive

2000 803 0.50 864 0.69 921 0.85 977 1.00 1031 1.14 1085 1.26 1138 1.37 1192 1.49 1247 1.60 1304 1.72

2200 833 0.64 893 0.83 951 1.00 1006 1.14 1061 1.28 1114 1.40 1168 1.51 1221 1.63 1276 1.74 1333 1.86

2400 866 0.80 926 0.99 984 1.15 1039 1.30 1094 1.43 1147 1.56 1201 1.67 1254 1.78 1309 1.90 1366 2.02

2600 902 0.97 962 1.16 1020 1.33 1076 1.47 1130 1.61 1183 1.73 1237 1.85 1291 1.96 1346 2.07 1402 2.19

2800 941 1.16 1002 1.35 1059 1.52 1115 1.67 1169 1.80 1222 1.92 1276 2.04 1330 2.15 1385 2.26 1442 2.38

3000 983 1.37 1043 1.56 1101 1.73 1157 1.88 1211 2.01 1264 2.13 1318 2.25 1372 2.36 1427 2.47 1483 2.59

3200 1028 1.60 1088 1.79 1145 1.95 1201 2.10 1255 2.24 1309 2.36 1362 2.47 1416 2.59 1471 2.70 1528 2.82

3400 1074 1.84 1134 2.03 1192 2.20 1248 2.35 1302 2.48 1355 2.60 1409 2.72 1463 2.83 1518 2.94 1574 3.06

3600 1123 2.10 1183 2.29 1241 2.46 1297 2.61 1351 2.74 1404 2.86 1458 2.98 1512 3.09 1567 3.21 1623 3.32

3800 1174 2.38 1234 2.57 1292 2.74 1348 2.88 1402 3.02 1455 3.14 1509 3.26 1562 3.37 - - - -

3 HP & Field Supplied Drive

ZR102 (8.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2 HP & Field

Supplied DriveStandard 2 HP & Drive Hi Static 3 HP & Drive

2200 684 0.48 735 0.67 783 0.84 829 1.01 874 1.17 918 1.32 960 1.48 1001 1.63 1041 1.78 1081 1.94

2400 695 0.58 745 0.76 793 0.94 840 1.11 885 1.27 928 1.42 970 1.57 1011 1.73 1052 1.88 1091 2.04

2600 706 0.67 756 0.86 805 1.04 851 1.20 896 1.36 939 1.52 981 1.67 1023 1.82 1063 1.98 1103 2.13

2800 719 0.78 769 0.96 817 1.14 863 1.31 908 1.47 952 1.62 994 1.78 1035 1.93 1075 2.08 1115 2.24

3000 732 0.89 782 1.08 831 1.25 877 1.42 922 1.58 965 1.74 1007 1.89 1049 2.04 1089 2.19 1128 2.35

3200 747 1.02 797 1.21 846 1.38 892 1.55 937 1.71 980 1.86 1023 2.02 1064 2.17 1104 2.32 1144 2.48

3400 764 1.16 814 1.35 862 1.53 909 1.69 954 1.85 997 2.01 1039 2.16 1080 2.31 1121 2.47 1160 2.62

3600 783 1.33 833 1.51 881 1.69 927 1.86 972 2.02 1016 2.17 1058 2.32 1099 2.48 1139 2.63 1179 2.79

3800 803 1.51 853 1.69 901 1.87 948 2.04 992 2.20 1036 2.35 1078 2.50 1119 2.66 1159 2.81 1199 2.97

4000 825 1.71 875 1.89 923 2.07 970 2.23 1014 2.39 1058 2.55 1100 2.70 1141 2.86 1181 3.01 1221 3.16

4200 849 1.92 899 2.11 947 2.29 993 2.45 1038 2.61 1082 2.77 1124 2.92 1165 3.07 1205 3.23 1245 3.38

3 HP & Field Supplied Drive

Page 120: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

120 Johnson Controls Ducted Systems

ZR120 (10 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2 HP & Field Supplied Drive Standard 2 HP & Drive Hi Static 3 HP & Drive

2600 706 0.67 756 0.86 805 1.04 851 1.20 896 1.36 939 1.52 981 1.67 1023 1.82 1063 1.98 1103 2.13

2800 719 0.78 769 0.96 817 1.14 863 1.31 908 1.47 952 1.62 994 1.78 1035 1.93 1075 2.08 1115 2.24

3000 732 0.89 782 1.08 831 1.25 877 1.42 922 1.58 965 1.74 1007 1.89 1049 2.04 1089 2.19 1128 2.35

3200 747 1.02 797 1.21 846 1.38 892 1.55 937 1.71 980 1.86 1023 2.02 1064 2.17 1104 2.32 1144 2.48

3400 764 1.16 814 1.35 862 1.53 909 1.69 954 1.85 997 2.01 1039 2.16 1080 2.31 1121 2.47 1160 2.62

3600 783 1.33 833 1.51 881 1.69 927 1.86 972 2.02 1016 2.17 1058 2.32 1099 2.48 1139 2.63 1179 2.79

3800 803 1.51 853 1.69 901 1.87 948 2.04 992 2.20 1036 2.35 1078 2.50 1119 2.66 1159 2.81 1199 2.97

4000 825 1.71 875 1.89 923 2.07 970 2.23 1014 2.39 1058 2.55 1100 2.70 1141 2.86 1181 3.01 1221 3.16

4200 849 1.92 899 2.11 947 2.29 993 2.45 1038 2.61 1082 2.77 1124 2.92 1165 3.07 1205 3.23 1245 3.38

4400 874 2.16 924 2.35 972 2.52 1019 2.69 1064 2.85 1107 3.01 1149 3.16 1190 3.31 - - - -

4600 901 2.42 952 2.61 1000 2.78 1046 2.95 1091 3.11 1134 3.26 1177 3.42 - - - - - -

4800 930 2.70 981 2.88 1029 3.06 1075 3.23 1120 3.39 - - - - - - - - - -

5000 961 2.99 1011 3.18 1059 3.35 - - - - - - - - - - - - - -

3 HP & Field Supplied Drive

ZR150 (12.5 Ton) Side Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3 HP & Field Supplied Drive Standard 3 HP & Drive

3200 747 1.02 797 1.21 846 1.38 892 1.55 937 1.71 980 1.86 1023 2.02 1064 2.17 1104 2.32 1144 2.48

3400 764 1.16 814 1.35 862 1.53 909 1.69 954 1.85 997 2.01 1039 2.16 1080 2.31 1121 2.47 1160 2.62

3600 783 1.33 833 1.51 881 1.69 927 1.86 972 2.02 1016 2.17 1058 2.32 1099 2.48 1139 2.63 1179 2.79

3800 803 1.51 853 1.69 901 1.87 948 2.04 992 2.20 1036 2.35 1078 2.50 1119 2.66 1159 2.81 1199 2.97

4000 825 1.71 875 1.89 923 2.07 970 2.23 1014 2.39 1058 2.55 1100 2.70 1141 2.86 1181 3.01 1221 3.16

4200 849 1.92 899 2.11 947 2.29 993 2.45 1038 2.61 1082 2.77 1124 2.92 1165 3.07 1205 3.23 1245 3.38

4400 874 2.16 924 2.35 972 2.52 1019 2.69 1064 2.85 1107 3.01 1149 3.16 1190 3.31 1231 3.47 1270 3.62

4600 901 2.42 952 2.61 1000 2.78 1046 2.95 1091 3.11 1134 3.26 1177 3.42 1218 3.57 1258 3.72 1298 3.88

4800 930 2.70 981 2.88 1029 3.06 1075 3.23 1120 3.39 1163 3.54 1206 3.69 1247 3.85 1287 4.00 1327 4.16

5000 961 2.99 1011 3.18 1059 3.35 1106 3.52 1151 3.68 1194 3.84 1236 3.99 1277 4.14 1318 4.29 1357 4.45

5200 993 3.31 1043 3.49 1092 3.67 1138 3.84 1183 4.00 1226 4.15 1269 4.30 1310 4.46 1350 4.61 1390 4.77

5400 1027 3.64 1077 3.83 1126 4.00 1172 4.17 1217 4.33 1260 4.48 1302 4.64 1344 4.79 1384 4.94 1424 5.10

5600 1063 3.99 1113 4.18 1161 4.35 1207 4.52 1252 4.68 1296 4.84 1338 4.99 1379 5.14 1419 5.29 1459 5.45

5800 1100 4.36 1150 4.55 1198 4.72 1244 4.89 1289 5.05 1333 5.20 1375 5.36 1416 5.51 1456 5.66 - -

6000 1138 4.75 1188 4.93 1237 5.11 1283 5.28 1328 5.44 1371 5.59 1413 5.74 - - - - - -

6200 1178 5.15 1228 5.34 1277 5.51 1323 5.68 - - - - - - - - - - - -

Hi Static 5 HP & Drive 5 HP & Field Supplied Drive

Page 121: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 121

ZR037-150 Bottom Duct Application

ZR037 (3.0 Ton) Bottom Duct

ZR049 (4.0 Ton) Bottom Duct

ZR061 (5.0 Ton) Bottom Duct

Air Flow

(CFM)

Available External Static Pressure - IWG1

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS4 Standard 1.5 HP & Drive Hi Static 1.5 HP & Drive

900 544 0.4 632 0.5 708 0.5 774 0.6 834 0.7 889 0.8 941 0.9 993 1.0 1047 1.1 1104 1.2

1000 549 0.4 637 0.5 713 0.5 779 0.6 839 0.7 894 0.8 946 0.9 998 1.0 1052 1.1 1109 1.2

1100 562 0.4 649 0.5 725 0.6 792 0.6 852 0.7 906 0.8 959 0.9 1010 1.0 1064 1.1 1121 1.2

1200 579 0.5 666 0.5 742 0.6 809 0.6 868 0.7 923 0.8 975 0.9 1027 1.0 1081 1.1 1138 1.2

1300 598 0.5 685 0.5 761 0.6 828 0.7 887 0.8 942 0.8 994 0.9 1046 1.0 1100 1.2 1157 1.3

1400 617 0.5 705 0.6 781 0.6 847 0.7 907 0.8 962 0.9 1014 1.0 1066 1.1 1119 1.2 1177 1.3

1500 637 0.6 724 0.6 800 0.7 867 0.8 927 0.8 981 0.9 1034 1.0 1085 1.1 1139 1.2 1196 1.4

FS4

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

Air Flow

(CFM)

Available External Static Pressure - IWG1

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPStandard 1.5 HP & Drive Hi Static 1.5 HP & Drive

1200 579 0.5 666 0.5 742 0.6 809 0.6 868 0.7 923 0.8 975 0.9 1027 1.0 1081 1.1 1138 1.2

1300 598 0.5 685 0.5 761 0.6 828 0.7 887 0.8 942 0.8 994 0.9 1046 1.0 1100 1.2 1157 1.3

1400 617 0.5 705 0.6 781 0.6 847 0.7 907 0.8 962 0.9 1014 1.0 1066 1.1 1119 1.2 1177 1.3

1500 637 0.6 724 0.6 800 0.7 867 0.8 927 0.8 981 0.9 1034 1.0 1085 1.1 1139 1.2 1196 1.4

1600 655 0.6 743 0.7 819 0.7 885 0.8 945 0.9 1000 1.0 1052 1.1 1104 1.2 1158 1.3 1215 1.4

1700 672 0.7 760 0.7 836 0.8 902 0.9 962 1.0 1017 1.0 1069 1.1 1121 1.2 1175 1.3 1232 1.5

1800 687 0.7 775 0.8 851 0.9 918 0.9 977 1.0 1032 1.1 1084 1.2 1136 1.3 1190 1.4 1247 1.5

1900 700 0.8 788 0.9 864 0.9 930 1.0 990 1.1 1045 1.2 1097 1.3 1149 1.4 1202 1.5 1260 1.6

2000 711 0.9 798 0.9 874 1.0 941 1.1 1000 1.2 1055 1.2 1107 1.3 1159 1.4 1213 1.6 1270 1.7

FS4

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

Air Flow

(CFM)

Available External Static Pressure - IWG1

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPStandard 1.5 HP & Drive Hi Static 2 HP & Drive

1500 613 0.5 684 0.6 759 0.7 831 0.7 928 0.8 984 0.9 1042 1.0 1093 1.1 1149 1.2 1201 1.3

1600 629 0.6 700 0.6 775 0.7 847 0.8 929 0.8 985 0.9 1043 1.0 1098 1.1 1154 1.2 1206 1.3

1700 646 0.6 717 0.7 793 0.8 864 0.8 934 0.9 990 1.0 1048 1.1 1106 1.2 1161 1.3 1214 1.4

1800 666 0.7 737 0.7 812 0.8 884 0.9 943 1.0 999 1.1 1057 1.2 1116 1.3 1172 1.4 1224 1.5

1900 687 0.7 758 0.8 833 0.9 905 0.9 954 1.0 1010 1.1 1068 1.2 1128 1.3 1184 1.4 1236 1.5

2000 710 0.8 781 0.9 856 0.9 927 1.0 968 1.1 1024 1.2 1082 1.3 1142 1.4 1198 1.5 1250 1.6

2100 733 0.8 804 0.9 879 1.0 951 1.1 983 1.2 1039 1.3 1097 1.4 1157 1.5 1213 1.6 1265 1.7

2200 758 0.9 828 1.0 904 1.1 947 1.2 1000 1.3 1056 1.4 1116 1.5 1174 1.6 1229 1.7 1281 1.8

2300 783 1.0 854 1.1 929 1.1 964 1.3 1018 1.4 1075 1.5 1133 1.6 1191 1.7 1246 1.8 - -

2400 809 1.1 879 1.2 932 1.3 983 1.4 1037 1.5 1094 1.6 1152 1.7 1209 1.8 - - - -

2500 835 1.1 906 1.2 951 1.4 1001 1.5 1055 1.6 1112 1.7 1170 1.8 2 HP & Field Supplied Drive

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

Page 122: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

122 Johnson Controls Ducted Systems

ZR078-150 Bottom Duct Application

ZR078 (6.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP1.5 HP & Field Supplied Drive Standard 1.5 HP & Drive Hi Static 2 HP & Drive

1800 801 0.45 874 0.65 946 0.82 1018 0.97 1090 1.11 1163 1.25 1238 1.38 1315 1.52 1395 1.68 1477 1.86

2000 831 0.59 903 0.78 975 0.95 1047 1.10 1119 1.24 1193 1.38 1267 1.51 1344 1.66 1424 1.81 1507 1.99

2200 867 0.74 940 0.93 1012 1.10 1084 1.25 1156 1.39 1229 1.53 1304 1.66 1381 1.81 1461 1.96 1543 2.14

2400 910 0.91 983 1.10 1055 1.27 1126 1.43 1199 1.57 1272 1.70 1347 1.84 1424 1.98 1503 2.14 - -

2600 957 1.10 1030 1.30 1102 1.47 1174 1.62 1246 1.76 1320 1.89 1394 2.03 1471 2.17 - - - -

2800 1009 1.32 1082 1.51 1154 1.69 1225 1.84 1298 1.98 1371 2.11 1446 2.25 - - - - - -

3000 1064 1.56 1137 1.75 1208 1.92 1280 2.08 1353 2.22 - - - - - - - - - -

3200 1122 1.82 1194 2.02 1266 2.19 - - - - - - - - - - - - - -

3400 1182 2.10 1254 2.30 - - - - - - - - - - - - - - - -

2 HP & Field Supplied Drive

ZR090 (7.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP1.5 HP & FieldSupplied Drive

Standard 1.5 HP & Drive Hi Static 3 HP & Drive

2000 831 0.59 903 0.78 975 0.95 1047 1.10 1119 1.24 1193 1.38 1267 1.51 1344 1.66 1424 1.81 1507 1.99

2200 867 0.74 940 0.93 1012 1.10 1084 1.25 1156 1.39 1229 1.53 1304 1.66 1381 1.81 1461 1.96 1543 2.14

2400 910 0.91 983 1.10 1055 1.27 1126 1.43 1199 1.57 1272 1.70 1347 1.84 1424 1.98 1503 2.14 1586 2.31

2600 957 1.10 1030 1.30 1102 1.47 1174 1.62 1246 1.76 1320 1.89 1394 2.03 1471 2.17 1551 2.33 1634 2.51

2800 1009 1.32 1082 1.51 1154 1.69 1225 1.84 1298 1.98 1371 2.11 1446 2.25 1523 2.39 1602 2.55 1685 2.73

3000 1064 1.56 1137 1.75 1208 1.92 1280 2.08 1353 2.22 1426 2.35 1501 2.49 1578 2.63 1657 2.79 1740 2.96

3200 1122 1.82 1194 2.02 1266 2.19 1338 2.34 1410 2.48 1484 2.61 1559 2.75 1636 2.89 1715 3.05 1798 3.23

3400 1182 2.10 1254 2.30 1326 2.47 1398 2.62 1471 2.76 1544 2.90 1619 3.03 1696 3.17 1775 3.33 - -

3600 1244 2.41 1317 2.60 1389 2.77 1461 2.93 1533 3.07 1606 3.20 1681 3.33 - - - - - -

3800 1308 2.73 1381 2.93 1453 3.10 1525 3.25 1597 3.39 - - - - - - - - - -

3 HP & Field Supplied Drive

ZR102 (8.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2 HP & Field

Supplied DriveStandard 2 HP & Drive Hi Static 3 HP & Drive

2200 715 0.72 768 0.85 818 0.98 867 1.09 914 1.21 960 1.32 1004 1.43 1047 1.53 1089 1.64 1131 1.75

2400 734 0.83 786 0.96 837 1.08 886 1.20 933 1.31 978 1.42 1022 1.53 1066 1.64 1108 1.75 1150 1.86

2600 755 0.95 808 1.08 858 1.20 907 1.32 954 1.44 1000 1.55 1044 1.65 1087 1.76 1129 1.87 1171 1.98

2800 779 1.09 832 1.22 882 1.35 931 1.46 978 1.58 1024 1.69 1068 1.80 1111 1.90 1153 2.01 1195 2.12

3000 806 1.25 859 1.38 910 1.51 958 1.63 1005 1.74 1051 1.85 1095 1.96 1138 2.07 1181 2.17 1222 2.28

3200 837 1.44 889 1.57 940 1.69 989 1.81 1036 1.93 1081 2.04 1125 2.14 1168 2.25 1211 2.36 1252 2.47

3400 870 1.65 922 1.78 973 1.90 1022 2.02 1069 2.13 1114 2.24 1158 2.35 1202 2.46 1244 2.57 1286 2.68

3600 906 1.88 959 2.01 1009 2.13 1058 2.25 1105 2.36 1150 2.47 1195 2.58 1238 2.69 1280 2.80 1322 2.91

3800 945 2.13 998 2.26 1048 2.38 1097 2.50 1144 2.61 1190 2.72 1234 2.83 1277 2.94 1319 3.05 1361 3.16

4000 987 2.40 1040 2.53 1090 2.66 1139 2.78 1186 2.89 1231 3.00 1276 3.11 1319 3.21 1361 3.32 1403 3.43

4200 1032 2.70 1084 2.83 1135 2.95 1184 3.07 1231 3.18 1276 3.29 1320 3.40 - - - - - -

3 HP & Field Supplied Drive

Page 123: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 123

ZR120 (10 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2 HP & Field

Supplied DriveStandard 2 HP & Drive Hi Static 3 HP & Drive

2600 755 0.95 808 1.08 858 1.20 907 1.32 954 1.44 1000 1.55 1044 1.65 1087 1.76 1129 1.87 1171 1.98

2800 779 1.09 832 1.22 882 1.35 931 1.46 978 1.58 1024 1.69 1068 1.80 1111 1.90 1153 2.01 1195 2.12

3000 806 1.25 859 1.38 910 1.51 958 1.63 1005 1.74 1051 1.85 1095 1.96 1138 2.07 1181 2.17 1222 2.28

3200 837 1.44 889 1.57 940 1.69 989 1.81 1036 1.93 1081 2.04 1125 2.14 1168 2.25 1211 2.36 1252 2.47

3400 870 1.65 922 1.78 973 1.90 1022 2.02 1069 2.13 1114 2.24 1158 2.35 1202 2.46 1244 2.57 1286 2.68

3600 906 1.88 959 2.01 1009 2.13 1058 2.25 1105 2.36 1150 2.47 1195 2.58 1238 2.69 1280 2.80 1322 2.91

3800 945 2.13 998 2.26 1048 2.38 1097 2.50 1144 2.61 1190 2.72 1234 2.83 1277 2.94 1319 3.05 1361 3.16

4000 987 2.40 1040 2.53 1090 2.66 1139 2.78 1186 2.89 1231 3.00 1276 3.11 1319 3.21 1361 3.32 1403 3.43

4200 1032 2.70 1084 2.83 1135 2.95 1184 3.07 1231 3.18 1276 3.29 1320 3.40 - - - - - -

4400 1079 3.01 1132 3.15 1182 3.27 1231 3.39 - - - - - - - - - - - -

4600 1129 3.35 - - - - - - - - - - - - - - - - - -

3 HP & Field Supplied Drive

ZR150 (12.5 Ton) Bottom Duct

Air Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP3 HP & Field

Supplied DriveStandard 3 HP & Drive Hi Static 5 HP & Drive

3200 837 1.44 889 1.57 940 1.69 989 1.81 1036 1.93 1081 2.04 1125 2.14 1168 2.25 1211 2.36 1252 2.47

3400 870 1.65 922 1.78 973 1.90 1022 2.02 1069 2.13 1114 2.24 1158 2.35 1202 2.46 1244 2.57 1286 2.68

3600 906 1.88 959 2.01 1009 2.13 1058 2.25 1105 2.36 1150 2.47 1195 2.58 1238 2.69 1280 2.80 1322 2.91

3800 945 2.13 998 2.26 1048 2.38 1097 2.50 1144 2.61 1190 2.72 1234 2.83 1277 2.94 1319 3.05 1361 3.16

4000 987 2.40 1040 2.53 1090 2.66 1139 2.78 1186 2.89 1231 3.00 1276 3.11 1319 3.21 1361 3.32 1403 3.43

4200 1032 2.70 1084 2.83 1135 2.95 1184 3.07 1231 3.18 1276 3.29 1320 3.40 1364 3.51 1406 3.62 1447 3.73

4400 1079 3.01 1132 3.15 1182 3.27 1231 3.39 1278 3.50 1324 3.61 1368 3.72 1411 3.83 1453 3.93 1495 4.05

4600 1129 3.35 1182 3.48 1232 3.61 1281 3.72 1328 3.84 1374 3.95 1418 4.06 1461 4.16 1503 4.27 1545 4.38

4800 1182 3.71 1235 3.84 1285 3.96 1334 4.08 1381 4.20 1426 4.31 1471 4.41 1514 4.52 1556 4.63 1598 4.74

5000 1237 4.08 1290 4.22 1340 4.34 1389 4.46 1436 4.57 1481 4.68 1526 4.79 1569 4.90 1611 5.01 1653 5.12

5200 1294 4.48 1347 4.61 1398 4.74 1446 4.85 1493 4.97 1539 5.08 1583 5.19 1626 5.29 1669 5.40 1710 5.51

5400 1354 4.89 1407 5.03 1457 5.15 1506 5.27 1553 5.38 1599 5.49 1643 5.60 1686 5.71 - - - -

5600 1416 5.33 1469 5.46 1519 5.58 1568 5.70 - - - - - - - - - - - -

5800 - - - - - - - - - - - - - - - - - - - -

5 HP & Field Supplied Drive

Page 124: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

124 Johnson Controls Ducted Systems

Sound PerformanceIndoor Sound Power Levels (3 thru 5 Ton)Indoor Sound Power Levels (Horizontal Ducted Inlet, Standard Static Belt Drive)

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR037 / 3 Ton / Standard Static Belt Drive

TEST CONFIGURATION Horizontal (Side Return) Ducted Inlet

Indoor Blower Speed (RPM) 612 - 3 Turns Open Equivalent 709 - 1 Turn Open Equivalent

External Static Pressure (IWG) 0.5 0.4

Airflow (CFM) 850 1300

Blower Motor BHP 0.37 0.40

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB) ID Blower Only (dB) Cooling Operation1 (dB)

63 73 77 73 77

125 61 70 66 71

250 56 63 60 64

500 51 56 55 57

1000 44 48 51 52

2000 41 44 48 49

4000 44 47 47 48

8000 42 44 43 44

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / Standard Static Belt Drive

TEST CONFIGURATION Horizontal (Side Return) Ducted Inlet

Indoor Blower Speed (RPM) 612 - 3 Turns Open Equivalent 709 - 1 Turn Open Equivalent

External Static Pressure (IWG) 0.5 0.4

Airflow (CFM) 850 1300

Blower Motor BHP 0.37 0.40

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB)

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

ID Blower Only (dB) Cooling Operation1 (dB)

63 73 77 73 77

125 61 70 66 71

250 56 63 60 64

500 51 56 55 57

1000 44 48 51 52

2000 41 44 48 49

4000 44 47 47 48

8000 42 44 43 44

Page 125: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 125

Indoor Sound Power Levels (Horizontal Ducted Discharge, Standard Static Belt Drive)

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / Standard Static Belt Drive

TEST CONFIGURATION Horizontal (Side Return) Ducted Inlet

Indoor Blower Speed (RPM) 814 - 3 Turns Open Equivalent 918 - 1 Turn Open Equivalent

External Static Pressure (IWG) 0.6 0.8

Airflow (CFM) 1700 1950

Blower Motor BHP 0.42 0.88

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB) ID Blower Only (dB) Cooling Operation1 (dB)

63 77 81 85 82

125 71 80 68 81

250 63 67 64 68

500 58 60 60 61

1000 56 57 58 59

2000 52 53 55 55

4000 51 51 54 54

8000 47 47 48 48

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR037 / 3 Ton / Standard Static Belt Drive

TEST CONFIGURATION Horizontal (Side Supply) Ducted Discharge

Indoor Blower Speed (RPM) 610 - 3 Turns Open Equivalent 710 - 1 Turn Open Equivalent

External Static Pressure (IWG) 0.5 0.6

Airflow (CFM) 850 950

Blower Motor BHP 0.37 0.42

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB) ID Blower Only (dB) Cooling Operation1 (dB)

63 77 78 79 79

125 74 75 75 76

250 66 68 70 70

500 61 61 65 64

1000 60 62 65 66

2000 52 52 58 58

4000 52 52 59 60

8000 44 44 50 50

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Page 126: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

126 Johnson Controls Ducted Systems

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / Standard Static Belt Drive

TEST CONFIGURATION Horizontal (Side Supply) Ducted Discharge

Indoor Blower Speed (RPM) 610 - 3 Turns Open Equivalent 710 - 1 Turn Open Equivalent

External Static Pressure (IWG) 0.5 0.6

Airflow (CFM) 850 950

Blower Motor BHP 0.37 0.42

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB) ID Blower Only (dB) Cooling Operation1 (dB)

63 77 78 79 79

125 74 75 75 76

250 66 68 70 70

500 61 61 65 64

1000 60 62 65 66

2000 52 52 58 58

4000 52 52 59 60

8000 44 44 50 50

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / Standard Static Belt Drive

TEST CONFIGURATION Horizontal (Side Supply) Ducted Discharge

Indoor Blower Speed (RPM) 810 - 3 Turns Open Equivalent 918 - 1 Turn Open Equivalent

External Static Pressure (IWG) 0.4 0.8

Airflow (CFM) 2050 1950

Blower Motor BHP 0.73 0.88

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB) ID Blower Only (dB) Cooling Operation1 (dB)

63 85 83 83 83

125 78 79 76 79

250 69 70 69 70

500 68 68 68 68

1000 64 64 65 65

2000 63 63 64 64

4000 64 64 64 64

8000 59 59 59 60

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Page 127: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 127

Indoor Sound Power Levels (Vertical Ducted Inlet, Standard Static Belt Drive)

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR037 / 3 Ton / Standard Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Return) Ducted Inlet

Indoor Blower Speed (RPM) 609 - 3 Turns Open Equivalent 708 - 1 Turn Open Equivalent

External Static Pressure (IWG) 0.4 0.4

Airflow (CFM) 850 1150

Blower Motor BHP 0.32 0.38

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB)

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

ID Blower Only (dB) Cooling Operation1 (dB)

63 76 76 74 76

125 63 70 66 70

250 55 62 59 62

500 54 55 58 59

1000 48 48 53 53

2000 44 44 48 48

4000 41 44 45 46

8000 42 43 43 44

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / Standard Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Return) Ducted Inlet

Indoor Blower Speed (RPM) 609 - 3 Turns Open Equivalent 708 - 1 Turn Open Equivalent

External Static Pressure (IWG) 0.4 0.4

Airflow (CFM) 850 1150

Blower Motor BHP 0.32 0.38

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB) ID Blower Only (dB) Cooling Operation1 (dB)

63 76 76 74 76

125 63 70 66 70

250 55 62 59 62

500 54 55 58 59

1000 48 48 53 53

2000 44 44 48 48

4000 41 44 45 46

8000 42 43 43 44

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Page 128: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

128 Johnson Controls Ducted Systems

Indoor Sound Power Levels (Vertical Ducted Discharge, Standard Static Belt Drive)

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / Standard Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Return) Ducted Inlet

Indoor Blower Speed (RPM) 812 - 3 Turns Open Equivalent 915- 1 Turn Open Equivalent

External Static Pressure (IWG) 0.6 0.8

Airflow (CFM) 1575 1800

Blower Motor BHP 0.64 0.83

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB) ID Blower Only (dB) Cooling Operation1 (dB)

63 75 78 80 80

125 66 80 69 81

250 59 66 62 65

500 60 60 63 63

1000 57 57 60 60

2000 52 53 55 55

4000 49 50 53 53

8000 44 45 47 47

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR037 / 3 Ton / Standard Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Supply) Ducted Discharge

Indoor Blower Speed (RPM) 609 - 3 Turns Open Equivalent 712 - 1 Turn Open Equivalent

External Static Pressure (IWG) 0.4 0.6

Airflow (CFM) 850 950

Blower Motor BHP 0.32 0.42

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB) ID Blower Only (dB) Cooling Operation1 (dB)

63 76 77 81 81

125 68 68 72 72

250 55 65 57 57

500 56 57 57 57

1000 51 57 52 56

2000 49 49 50 50

4000 48 48 49 51

8000 46 46 47 48

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Page 129: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 129

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / Standard Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Supply) Ducted Discharge

Indoor Blower Speed (RPM) 609 - 3 Turns Open Equivalent 712 - 1 Turn Open Equivalent

External Static Pressure (IWG) 0.4 0.6

Airflow (CFM) 850 950

Blower Motor BHP 0.32 0.42

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB) ID Blower Only (dB) Cooling Operation1 (dB)

63 76 77 81 81

125 68 68 72 72

250 55 65 57 57

500 56 57 57 57

1000 51 57 52 56

2000 49 49 50 50

4000 48 48 49 51

8000 46 46 47 48

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / Standard Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Supply) Ducted Discharge

Indoor Blower Speed (RPM) 809 - 3 Turns Open Equivalent 914 - 1 Turn Open Equivalent

External Static Pressure (IWG) 0.5 0.8

Airflow (CFM) 1700 1800

Blower Motor BHP 0.64 0.83

Octave Center Freq. Hz ID Blower Only (dB) Cooling Operation1 (dB) ID Blower Only (dB) Cooling Operation1 (dB)

63 81 81 79 79

125 75 75 75 76

250 65 65 63 63

500 67 67 67 67

1000 63 63 63 63

2000 61 62 61 61

4000 62 62 61 61

8000 57 57 56 56

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Page 130: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

130 Johnson Controls Ducted Systems

Indoor Sound Power Levels (Horizontal Ducted Inlet, High Static Belt Drive)

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR037 / 3 Ton / High Static Belt Drive

TEST CONFIGURATION Horizontal (Side Return) Ducted Inlet

Indoor Blower Speed (RPM) 876 - 4 Turns Open Equivalent 1,064 - 1/2 Turn Open Equivalent 1,190 - 2.5 Turns Open Equivalent1

External Static Pressure (IWG) 1.0 1.6 2.0 1

Nominal Airflow (CFM) 1,200 1,100 1,000

Blower Motor BHP 0.64 0.93 1.08

Octave Center Freq. HzID BlowerOnly (dB)

CoolingOperation2 (dB)

ID BlowerOnly (dB)

CoolingOperation2 (dB)

ID BlowerOnly (dB)

CoolingOperation2 (dB)

63 75 80 81 81 81 83

125 69 71 71 73 73 75

250 62 68 66 71 68 70

500 54 56 57 59 59 60

1000 52 56 56 58 58 60

2000 47 49 52 52 54 56

4000 43 45 48 49 51 53

8000 43 45 45 46 47 48

1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.2. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / High Static Belt Drive

TEST CONFIGURATION Horizontal (Side Return) Ducted Inlet

Indoor Blower Speed (RPM) 965 - 5.5 Turns Open Equivalent 1,088 - 4 Turns Open Equivalent 1,186 - 2.5 Turns Open Equivalent

External Static Pressure (IWG) 1.0 1.6 2.0

Nominal Airflow (CFM) 1,600 1,400 1,200

Blower Motor BHP 0.86 1.03 1.13

Octave Center Freq. HzID BlowerOnly (dB)

Cooling Operation1 (dB)

ID BlowerOnly (dB)

Cooling Operation1 (dB)

ID BlowerOnly (dB)

Cooling Operation1 (dB)

63 74 80 77 80 81 81

125 69 74 72 75 75 76

250 68 68 68 69 70 71

500 62 62 60 61 61 63

1000 60 61 58 58 59 60

2000 57 57 53 54 55 56

4000 56 56 49 50 51 52

8000 54 54 45 47 47 48

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Page 131: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 131

Indoor Sound Power Levels (Horizontal Ducted Discharge, High Static Belt Drive)

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / High Static Belt Drive

TEST CONFIGURATION Horizontal (Side Return) Ducted Inlet

Indoor Blower Speed (RPM) 1,012- 5.5 Turns Open Equivalent 1,134 - 3 Turns Open Equivalent 1,174 - 2 Turns Open Equivalent

External Static Pressure (IWG) 1.0 1.6 2.0

Nominal Airflow (CFM) 2,000 1,800 1,600

Blower Motor BHP 1.04 1.25 1.39

Octave Center Freq. HzID BlowerOnly (dB)

Cooling Operation1 (dB)

ID BlowerOnly (dB)

Cooling Operation1 (dB)

ID BlowerOnly (dB)

CoolingOperation1 (dB)

63 76 78 78 79 79 81

125 70 73 73 76 74 77

250 68 70 68 69 69 70

500 61 62 61 62 60 62

1000 61 62 61 62 58 60

2000 57 58 57 58 54 56

4000 56 56 55 56 52 53

8000 50 50 50 50 47 48

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR037 / 3 Ton / High Static Belt DriveTEST CONFIGURATION Horizontal (Side Supply) Ducted Discharge

Indoor Blower Speed (RPM) 896 - 3.5 Turns Open Equivalent 1,072 - Fully Closed Equivalent 1,170 - 2.5 Turns Open Equivalent1

1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.

External Static Pressure (IWG) 1.0 1.6 2.0 1

Nominal Airflow (CFM) 1,200 1,100 1,000

Blower Motor BHP 0.64 0.93 1.08

Octave Center Freq. HzID BlowerOnly (dB)

CoolingOperation2 (dB)

2. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

ID BlowerOnly (dB)

CoolingOperation2 (dB)

ID BlowerOnly (dB)

CoolingOperation2 (dB)

63 77 81 83 84 83 84

125 74 76 76 77 80 80

250 67 68 70 70 72 73

500 65 66 67 67 67 68

1000 61 62 67 67 66 69

2000 58 60 63 63 63 64

4000 57 59 62 62 62 63

8000 51 53 56 57 56 58

Page 132: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

132 Johnson Controls Ducted Systems

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / High Static Belt Drive

TEST CONFIGURATION Horizontal (Side Supply) Ducted Discharge

Indoor Blower Speed (RPM) 922 - 6 Turns Open Equivalent 1,069 - 4 Turns Open Equivalent 1,165 - 2.5 Turns Open Equivalent

External Static Pressure (IWG) 1.0 1.6 2.0

Nominal Airflow (CFM) 1,600 1,400 1,200

Blower Motor BHP 0.86 1.03 1.13

Octave Center Freq. HzID BlowerOnly (dB)

Cooling Operation1 (dB)

ID BlowerOnly (dB)

Cooling Operation1 (dB)

ID BlowerOnly (dB)

Cooling Operation1 (dB)

63 80 82 82 83 84 84

125 76 77 76 77 78 79

250 71 72 72 72 74 74

500 69 69 69 69 70 70

1000 65 65 69 69 70 70

2000 64 64 64 64 65 65

4000 63 63 63 63 64 64

8000 58 58 58 58 59 59

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / High Static Belt Drive

TEST CONFIGURATION Horizontal (Side Supply) Ducted Discharge

Indoor Blower Speed (RPM) 1,009- 5.5 Turns Open Equivalent 1,131 - 3 Turns Open Equivalent 1,184 - 2 Turns Open Equivalent

External Static Pressure (IWG) 1.0 1.6 2.0

Nominal Airflow (CFM) 2,000 1,800 1,600

Blower Motor BHP 1.04 1.25 1.39

Octave Center Freq. HzID BlowerOnly (dB)

Cooling Operation1 (dB)

ID BlowerOnly (dB)

Cooling Operation1 (dB)

ID BlowerOnly (dB)

CoolingOperation1 (dB)

63 84 85 82 83 82 83

125 78 79 79 79 78 79

250 75 75 74 75 73 73

500 71 71 70 71 69 69

1000 69 69 71 71 71 72

2000 66 67 67 67 66 66

4000 66 66 66 67 66 66

8000 61 62 61 62 60 60

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Page 133: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 133

Indoor Sound Power Levels (Vertical Ducted Inlet, High Static Belt Drive)

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR037 / 3 Ton / High Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Return) Ducted Inlet

Indoor Blower Speed (RPM) 927 - 3 Turns Open Equivalent 1,085 - 1/2 Turn Open Equivalent 1,190 - 2.5 Turns Open Equivalent1

1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.

External Static Pressure (IWG) 1.0 1.6 2.01

Nominal Airflow (CFM) 1,200 1,100 1,000

Blower Motor BHP 0.68 0.93 1.09

Octave Center Freq. HzID BlowerOnly (dB)

CoolingOperation2 (dB)

2. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

ID BlowerOnly (dB)

CoolingOperation2 (dB)

ID BlowerOnly (dB)

CoolingOperation2 (dB)

63 77 79 82 83 79 81

125 68 69 70 71 72 73

250 60 67 62 69 64 67

500 58 58 63 63 62 63

1000 54 55 60 60 60 60

2000 48 49 56 56 55 55

4000 43 44 48 49 51 51

8000 44 44 45 46 47 47

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / High Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Return) Ducted Inlet

Indoor Blower Speed (RPM) 968 - 5.5 Turns Open Equivalent 1,120 - 3.5 Turns Open Equivalent 1,218 - 2.0 Turns Open Equivalent

External Static Pressure (IWG) 1.0 1.6 2.0

Nominal Airflow (CFM) 1,600 1,400 1,200

Blower Motor BHP 0.86 1.03 1.13

Octave Center Freq. HzID BlowerOnly (dB)

CoolingOperation1 (dB)

ID BlowerOnly (dB)

CoolingOperation1 (dB)

ID BlowerOnly (dB)

CoolingOperation1 (dB)

63 77 79 78 78 81 81

125 69 73 71 73 73 74

250 63 63 63 64 66 66

500 63 64 62 63 64 64

1000 59 59 59 59 61 61

2000 54 54 53 54 56 56

4000 49 49 48 48 50 51

8000 45 46 45 46 47 47

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Page 134: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

134 Johnson Controls Ducted Systems

Indoor Sound Power Levels (Vertical Ducted Discharge, High Static Belt Drive)

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / High Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Return) Ducted Inlet

Indoor Blower Speed (RPM) 1,039 - 5 Turns Open Equivalent 1,143 - 3 Turns Open Equivalent 1,201 - 2 Turns Open Equivalent

External Static Pressure (IWG) 1.0 1.6 2.0

Nominal Airflow (CFM) 2,000 1,800 1,600

Blower Motor BHP 1.11 1.25 1.39

Octave Center Freq. HzID BlowerOnly (dB)

Cooling Operation1 (dB)

ID BlowerOnly (dB)

Cooling Operation1 (dB)

ID BlowerOnly (dB)

Cooling Operation1 (dB)

63 79 80 77 77 81 81

125 74 75 71 73 73 74

250 63 65 63 64 63 65

500 62 63 64 64 62 62

1000 61 61 61 61 59 59

2000 55 56 55 56 54 55

4000 52 52 50 51 50 50

8000 47 47 46 46 46 46

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR037 / 3 Ton / High Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Supply) Ducted Discharge

Indoor Blower Speed (RPM) 920 - 3.0 Turns Open Equivalent 1,074 - Fully Closed Equivalent 1,189 - 2.0 Turns Open Equivalent1

1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.

External Static Pressure (IWG) 1.0 1.6 2.01

Nominal Airflow (CFM) 1,200 1,100 1,000

Blower Motor BHP 0.68 0.93 1.09

Octave Center Freq. HzID BlowerOnly (dB)

CoolingOperation2 (dB)

2. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

ID BlowerOnly (dB)

CoolingOperation2 (dB)

ID BlowerOnly (dB)

CoolingOperation2 (dB)

63 81 82 81 81 82 82

125 78 78 78 78 81 81

250 69 70 70 71 74 74

500 67 68 68 69 71 71

1000 62 63 67 68 70 71

2000 60 61 62 63 65 66

4000 61 61 63 63 66 66

8000 54 55 57 57 60 61

Page 135: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 135

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / High Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Supply) Ducted Discharge

Indoor Blower Speed (RPM) 962 - 5.5 Turns Open Equivalent 1,092 - 3.5 Turns Open Equivalent 1,190 - 2.0 Turns Open Equivalent

External Static Pressure (IWG) 1.0 1.6 2.0

Nominal Airflow (CFM) 1,600 1,400 1,200

Blower Motor BHP 0.86 1.03 1.13

Octave Center Freq. HzID BlowerOnly (dB)

CoolingOperation1 (dB)

ID BlowerOnly (dB)

CoolingOperation1 (dB)

ID BlowerOnly (dB)

CoolingOperation1 (dB)

63 83 84 82 82 83 83

125 80 81 79 80 80 81

250 75 75 74 75 75 75

500 71 72 70 71 71 72

1000 66 67 70 71 72 72

2000 63 64 64 64 65 65

4000 64 64 64 64 65 66

8000 58 59 59 59 60 60

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / High Static Belt Drive

TEST CONFIGURATION Vertical (Bottom Supply) Ducted Discharge

Indoor Blower Speed (RPM) 1,033 - 5.5 Turns Open Equivalent 1,135 - 3 turns Open Equivalent 1,175 - 2.5 Turns Open Equivalent

External Static Pressure (IWG) 1.0 1.6 2.0

Nominal Airflow (CFM) 2,000 1,135 1,175

Blower Motor BHP 1.11 1.25 1.39

Octave Center Freq. HzID BlowerOnly (dB)

CoolingOperation1 (dB)

ID BlowerOnly (dB)

CoolingOperation1 (dB)

ID BlowerOnly (dB)

CoolingOperation1 (dB)

63 83 83 83 83 85 86

125 84 84 82 82 79 81

250 79 80 77 78 66 66

500 73 73 70 71 65 66

1000 69 70 69 70 61 65

2000 67 67 65 66 60 61

4000 67 68 66 67 61 62

8000 62 63 60 61 54 54

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning

Equipment.• Testing datum includes effect of standard inlet air filters.• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.• Test duct termination is flush with reverberant room wall.• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Page 136: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

136 Johnson Controls Ducted Systems

Indoor Sound Power Levels (6.5 thru 12.5 Ton)

Size(Tons)

Model CFMESP

(IWG)Blower

Sound Power, dB (10-12) Watts

Sound Rating1

dB (A)Octave Band Centerline Frequency (Hz)

RPM BHP 63 125 250 500 1000 2000 4000 8000

078(6.5)

ZH/ZJ/ZR 2600 0.6 812 1.14 74 71 73 73 71 69 65 65 60

090(7.5)

ZH/ZJ/ZR 3000 0.6 854 1.47 77 74 76 76 74 72 68 68 63

102(8.5)

ZH/ZJ/ZR 3400 0.6 872 1.65 80 77 79 79 77 75 71 71 66

120(10)

ZH/ZJ/ZR 4000 0.6 959 2.29 83 80 82 82 80 78 74 74 69

150(12.5)

ZH/ZJ/ZR 5000 0.6 1132 3.74 87 84 86 86 84 82 78 78 73

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data in any other form than sound power level ratings.

Page 137: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 137

Outdoor Sound Power LevelsZH/ZJ/ZR037-150

Size(Tons)

ModelSound Rating1

dB (A)Octave Band Centerline Frequency (Hz)

63 125 250 500 1000 2000 4000 8000

037(3)

ZH 78 79.0 83.0 76.0 75.0 73.0 68.0 63.0 59.0

049(4)

ZH 78 82.0 86.0 78.5 75.5 73.0 68.0 63.0 56.0

061(5)

ZH 84 81.0 91.0 82.5 80.5 79.0 73.5 69.5 64.5

078(6.5)

ZH 87 89.0 88.5 84.5 84.5 82.0 76.5 72.0 66.5

090(7.5)

ZH 89 87.0 91.0 88.0 87.0 84.0 78.0 73.0 66.0

102(8.5)

ZH 92 97.0 94.0 93.5 90.5 87.0 81.5 76.0 69.0

120(10)

ZH 91 99.5 91.5 91.5 89.0 86.0 80.5 76.5 71.0

150(12.5)

ZH 86 89.5 91.0 85.5 84.0 81.0 76.5 71.0 62.5

037(3)

ZJ 72 80.0 83.0 72.0 69.0 66.0 61.0 55.0 50.0

049(4)

ZJ 76 80.0 81.0 75.0 73.0 71.0 67.0 61.0 55.0

061(5)

ZJ 78 81.0 86.0 80.0 74.0 71.0 67.0 63.0 59.0

078(6.5)

ZJ 83 77.0 85.0 82.0 81.0 79.0 73.0 67.0 60.0

090(7.5)

ZJ 86 86.0 91.0 87.0 84.0 80.0 76.0 71.0 65.0

102(8.5)

ZJ 88 89.0 91.0 89.0 86.0 83.0 78.0 74.0 67.0

120(10)

ZJ 91 99.5 91.5 91.5 89.0 86.0 80.5 76.5 71.0

150(12.5)

ZJ 85 89.0 88.0 83.5 83.5 78.5 74.0 69.5 64.5

037(3)

ZR 77 82.0 83.5 80.0 73.0 70.0 65.5 60.5 55.5

049(4)

ZR 81 87.5 88.5 83.0 77.5 73.5 70.5 67.0 62.0

61(5)

ZR 76 82.0 84.0 77.0 74.0 70.0 64.0 59.0 51.0

078(6.5)

ZR 83 ~ 88.0 82.5 81.5 78.0 73.0 69.0 62.0

090(7.5)

ZR 83 ~ 89.5 83.5 82.0 78.0 72.5 68.0 60.5

102(8.5)

ZR 83 ~ 89.0 84.5 81.5 78.0 72.5 68.5 70.5

120(10)

ZR 83 ~ 89.5 83.5 81.0 78.0 72.0 68.5 70.5

150(12.5)

ZR 84 ~ 90.0 84.5 81.5 77.5 72.0 68.5 61.5

1. Rated in accordance with AHRI 270 standard.

Page 138: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

138 Johnson Controls Ducted Systems

Electrical Data

ZH037-061 Standard Indoor Blower - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

1. Minimum Circuit Ampacity.

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 2.3 1 6.4 18.6 24.1 25 30E06 4.5 1 12.5 22.1 29 25 30E08 6.8 1 18.9 30.1 37 35 40E15 11.3 2 31.4 45.8 52.6 50 60

230 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 3 1 7.2 18.6 24.1 25 30E06 6 1 14.4 24.5 31.4 25 35E08 9 1 21.7 33.6 40.5 35 45E15 15 2 36.1 51.6 58.5 60 60

460 5.8 38 9 1.26 2.6 2.2

None - - - 11.2 13.4 15 15E03 3 1 3.6 11.2 13.4 15 15E06 6 1 7.2 12.3 15 15 15E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30

575 3.8 36.5 6 0.66 2 1.8None - - - 7.5 9.3 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25

049(4)

208 13.8 83.1 22 2.1 5.2 5.5

None - - - 24.6 30.1 35 40E06 4.5 1 12.5 24.6 30.1 35 40E08 6.8 1 18.9 30.1 37 35 40E15 11.3 2 31.4 45.8 52.6 50 60E20 15 2 41.6 58.5 65.4 60 70

230 13.8 83.1 22 2.1 5.2 5.5

None - - - 24.6 30.1 35 40E06 6 1 14.4 24.6 31.4 35 40E08 9 1 21.7 33.6 40.5 35 45E15 15 2 36.1 51.6 58.5 60 60E20 20 2 48.1 66.6 73.5 70 80

460 6.2 41 10 1.26 2.6 2.2

None - - - 11.7 13.9 15 20E06 6 1 7.2 12.3 15 15 20E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30E20 20 2 24.1 33.4 36.1 35 40

575 4.9 33 8 0.66 2 1.8

None - - - 8.8 10.6 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25E20 20 2 19.2 26.5 28.8 30 30

061(5)

208 15.9 110 25 2.1 5.2 5.5

None - - - 29.3 34.8 40 45E06 4.5 1 12.5 29.3 34.8 40 45E08 6.8 1 18.9 30.1 37 40 50E15 11.3 2 31.4 45.8 52.6 50 60E20 15 2 41.6 58.5 65.4 60 70E23 18 2 50 69 75.9 70 80

230 15.9 110 25 2.1 5.2 5.5

None - - - 29.3 34.8 40 45E06 6 1 14.4 29.3 34.8 40 45E08 9 1 21.7 33.6 40.5 45 50E15 15 2 36.1 51.6 58.5 60 60E20 20 2 48.1 66.6 73.5 70 80E23 24 2 57.7 78.6 85.5 80 90

460 7.1 52 11 1.26 2.6 2.2

None - - - 14 16.2 20 20E06 6 1 7.2 14 16.2 20 20E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30E20 20 2 24.1 33.4 36.1 35 40E23 24 2 28.9 39.4 42.1 40 45

575 5.1 39.5 8 0.66 2 1.8

None - - - 9.7 11.5 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25E20 20 2 19.2 26.5 28.8 30 30E23 24 2 23.1 31.4 33.6 35 35

Page 139: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 139

ZH078-150 Standard Motor - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 11.2 84 18 2.1 5.2 5.5

None - - - 34.6 40.1 45 50E09 6.8 1 18.9 34.6 40.1 45 50E18 13.5 2 37.5 53.4 60.3 60 70E24 18 2 50 69 75.9 70 80E36 25.5 2 70.8 95 101.9 100 110

230 11.2 84 18 2.1 5.2 5.5

None - - - 34.6 40.1 45 50E09 9 1 21.7 34.6 40.5 45 50E18 18 2 43.3 60.6 67.5 70 70E24 24 2 57.7 78.6 85.5 80 90E36 34 2 81.8 108.8 115.6 110 125

460 5.6 44 9 1.26 2.6 2.2

None - - - 17.7 19.9 20 25E09 9 1 10.8 17.7 19.9 20 25E18 18 2 21.7 30.4 33.1 35 35E24 24 2 28.9 39.4 42.1 40 45E36 34 2 40.9 54.4 57.1 60 60

575 3.8 34 6 0.66 2 1.8

None - - - 11.9 13.7 15 15E09 9 1 8.7 13.4 15.6 15 20E18 18 2 17.3 24.1 26.4 25 30E24 24 2 23.1 31.4 33.6 35 35E36 34 2 32.7 43.4 45.6 45 50

090(7.5)

208 13.8 83.1 22 3.03 5.2 5.5

None - - - 42.4 47.9 50 60E09 6.8 1 18.9 42.4 47.9 50 60E18 13.5 2 37.5 53.4 60.3 60 70E24 18 2 50 69 75.9 70 80E36 25.5 2 70.8 95 101.9 100 110

230 13.8 83.1 22 3.03 5.2 5.5

None - - - 42.4 47.9 50 60E09 9 1 21.7 42.4 47.9 50 60E18 18 2 43.3 60.6 67.5 70 70E24 24 2 57.7 78.6 85.5 80 90E36 34 2 81.8 108.8 115.6 110 125

460 6.2 41 10 1.6 2.6 2.2

None - - - 19.8 22 25 25E09 9 1 10.8 19.8 22 25 25E18 18 2 21.7 30.4 33.1 35 35E24 24 2 28.9 39.4 42.1 40 45E36 34 2 40.9 54.4 57.1 60 60

575 4.9 33 8 1.35 2 1.8

None - - - 15.7 17.5 20 20E09 9 1 8.7 15.7 17.5 20 20E18 18 2 17.3 24.1 26.4 25 30E24 24 2 23.1 31.4 33.6 35 35E36 34 2 32.7 43.4 45.6 45 50

102(8.5)

208 14.5 98 23 3.03 6.8 5.5

None - - - 45.5 51 60 60E09 6.8 1 18.9 45.5 51 60 60E18 13.5 2 37.5 55.4 62.3 60 70E24 18 2 50 71 77.9 80 80E36 25.5 2 70.8 97 103.9 100 110

230 14.5 98 23 3.03 6.8 5.5

None - - - 45.5 51 60 60E09 9 1 21.7 45.5 51 60 60E18 18 2 43.3 62.6 69.5 70 70E24 24 2 57.7 80.6 87.5 90 90E36 34 2 81.8 110.8 117.6 125 125

460 6.3 55 10 1.6 3.4 2.2

None - - - 20.8 23 25 25E09 9 1 10.8 20.8 23 25 25E18 18 2 21.7 31.4 34.1 35 35E24 24 2 28.9 40.4 43.1 45 45E36 34 2 40.9 55.4 58.1 60 60

575 6 41 9 1.35 2.4 1.8

None - - - 18.6 20.4 20 25E09 9 1 8.7 18.6 20.4 20 25E18 18 2 17.3 24.6 26.9 25 30E24 24 2 23.1 31.9 34.1 35 35E36 34 2 32.7 43.9 46.1 45 50

Page 140: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

140 Johnson Controls Ducted Systems

120(10)

208 16 110 25 3.03 6.8 5.5

None - - - 48.9 54.4 60 70E18 13.5 2 37.5 55.4 62.3 60 70E24 18 2 50 71 77.9 80 80E36 25.5 2 70.8 97 103.9 100 110E54 40.6 2 112.7 149.4 156.3 150 175

230 16 110 25 3.03 6.8 5.5

None - - - 48.9 54.4 60 70E18 18 2 43.3 62.6 69.5 70 70E24 24 2 57.7 80.6 87.5 90 90E36 34 2 81.8 110.8 117.6 125 125E54 54 2 129.9 138.4 145.3 150 175

460 7.8 52 12 1.6 3.4 2.2

None - - - 24.2 26.4 30 30E18 18 2 21.7 31.4 34.1 35 35E24 24 2 28.9 40.4 43.1 45 45E36 34 2 40.9 55.4 58.1 60 60E54 54 2 65 69.3 72 80 80

575 5.7 38.9 9 1.35 2.4 1.8

None - - - 17.9 19.7 20 25E18 18 2 17.3 24.6 26.9 25 30E24 24 2 23.1 31.9 34.1 35 35E36 34 2 32.7 43.9 46.1 45 50E54 54 2 52 55 57.3 60 60

150(12.5)

208 23.1 160 36 2.1 9.6 5.5

None - - - 70 75.5 90 90E18 13.5 2 37.5 70 75.5 90 90E24 18 2 50 74.5 81.4 90 90E36 25.5 2 70.8 100.5 107.4 110 110E54 40.6 2 112.7 152.9 159.8 175 175

230 23.1 160 36 2.1 9.6 5.5

None - - - 70 75.5 90 90E18 18 2 43.3 70 75.5 90 90E24 24 2 57.7 84.1 91 90 100E36 34 2 81.8 114.3 121.1 125 125E54 54 2 129.9 141.9 148.8 175 175

460 12.2 87 19 1.26 4.7 2.2

None - - - 37.2 39.4 45 50E18 18 2 21.7 37.2 39.4 45 50E24 24 2 28.9 42 44.8 45 50E36 34 2 40.9 57 59.8 60 60E54 54 2 65 70.9 73.6 80 80

575 8.7 62 14 0.66 3.6 1.8

None - - - 25.8 27.6 30 35E18 18 2 17.3 26.1 28.4 30 35E24 24 2 23.1 33.4 35.6 35 40E36 34 2 32.7 45.4 47.6 50 50E54 54 2 52 56.5 58.8 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

ZH078-150 Standard Motor - Without Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 141: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 141

ZH037-061 Hi Static Indoor Blower - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

1. Minimum Circuit Ampacity.

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 2.3 1 6.4 18.6 24.1 25 30E06 4.5 1 12.5 22.1 29 25 30E08 6.8 1 18.9 30.1 37 35 40E15 11.3 2 31.4 45.8 52.6 50 60

230 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 3 1 7.2 18.6 24.1 25 30E06 6 1 14.4 24.5 31.4 25 35E08 9 1 21.7 33.6 40.5 35 45E15 15 2 36.1 51.6 58.5 60 60

460 5.8 38 9 1.26 2.6 2.2

None - - - 11.2 13.4 15 15E03 3 1 3.6 11.2 13.4 15 15E06 6 1 7.2 12.3 15 15 15E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30

575 3.8 36.5 6 0.66 2 1.8None - - - 7.5 9.3 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25

049(4)

208 13.8 83.1 22 2.1 5.2 5.5

None - - - 24.6 30.1 35 40E06 4.5 1 12.5 24.6 30.1 35 40E08 6.8 1 18.9 30.1 37 35 40E15 11.3 2 31.4 45.8 52.6 50 60E20 15 2 41.6 58.5 65.4 60 70

230 13.8 83.1 22 2.1 5.2 5.5

None - - - 24.6 30.1 35 40E06 6 1 14.4 24.6 31.4 35 40E08 9 1 21.7 33.6 40.5 35 45E15 15 2 36.1 51.6 58.5 60 60E20 20 2 48.1 66.6 73.5 70 80

460 6.2 41 10 1.26 2.6 2.2

None - - - 11.7 13.9 15 20E06 6 1 7.2 12.3 15 15 20E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30E20 20 2 24.1 33.4 36.1 35 40

575 4.9 33 8 0.66 2 1.8

None - - - 8.8 10.6 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25E20 20 2 19.2 26.5 28.8 30 30

061(5)

208 15.9 110 25 2.1 6.8 5.5

None - - - 30.9 36.4 40 50E06 4.5 1 12.5 30.9 36.4 40 50E08 6.8 1 18.9 32.1 39 45 50E15 11.3 2 31.4 47.8 54.6 50 60E20 15 2 41.6 60.5 67.4 70 70E23 18 2 50 71 77.9 80 80

230 15.9 110 25 2.1 6.8 5.5

None - - - 30.9 36.4 40 50E06 6 1 14.4 30.9 36.4 40 50E08 9 1 21.7 35.6 42.5 45 50E15 15 2 36.1 53.6 60.5 60 70E20 20 2 48.1 68.6 75.5 70 80E23 24 2 57.7 80.6 87.5 90 90

460 7.1 52 11 1.26 3.4 2.2

None - - - 14.8 17 20 20E06 6 1 7.2 14.8 17 20 20E08 9 1 10.8 17.8 20.5 20 25E15 15 2 18 26.8 29.5 30 30E20 20 2 24.1 34.4 37.1 35 40E23 24 2 28.9 40.4 43.1 45 45

575 5.1 39.5 8 0.66 2.4 1.8

None - - - 10.1 11.9 15 15E08 9 1 8.7 13.9 16.1 15 20E15 15 2 14.4 21 23.3 25 25E20 20 2 19.2 27 29.3 30 30E23 24 2 23.1 31.9 34.1 35 35

Page 142: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

142 Johnson Controls Ducted Systems

ZH078-150 Hi Static Motor - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 11.2 84 18 2.1 6.8 5.5

None - - - 36.2 41.7 45 50E09 6.8 1 18.9 36.2 41.7 45 50E18 13.5 2 37.5 55.4 62.3 60 70E24 18 2 50 71 77.9 80 80E36 25.5 2 70.8 97 103.9 100 110

230 11.2 84 18 2.1 6.8 5.5

None - - - 36.2 41.7 45 50E09 9 1 21.7 36.2 42.5 45 50E18 18 2 43.3 62.6 69.5 70 70E24 24 2 57.7 80.6 87.5 90 90E36 34 2 81.8 110.8 117.6 125 125

460 5.6 44 9 1.26 3.4 2.2

None - - - 18.5 20.7 20 25E09 9 1 10.8 18.5 20.7 20 25E18 18 2 21.7 31.4 34.1 35 35E24 24 2 28.9 40.4 43.1 45 45E36 34 2 40.9 55.4 58.1 60 60

575 3.8 34 6 0.66 2.4 1.8

None - - - 12.3 14.1 15 15E09 9 1 8.7 13.9 16.1 15 20E18 18 2 17.3 24.6 26.9 25 30E24 24 2 23.1 31.9 34.1 35 35E36 34 2 32.7 43.9 46.1 45 50

090(7.5)

208 13.8 83.1 22 3.03 9.6 5.5

None - - - 46.8 52.3 60 60E09 6.8 1 18.9 46.8 52.3 60 60E18 13.5 2 37.5 58.9 65.8 60 70E24 18 2 50 74.5 81.4 80 90E36 25.5 2 70.8 100.5 107.4 110 110

230 13.8 83.1 22 3.03 9.6 5.5

None - - - 46.8 52.3 60 60E09 9 1 21.7 46.8 52.3 60 60E18 18 2 43.3 66.1 73 70 80E24 24 2 57.7 84.1 91 90 100E36 34 2 81.8 114.3 121.1 125 125

460 6.2 41 10 1.6 4.7 2.2

None - - - 21.9 24.1 25 30E09 9 1 10.8 21.9 24.1 25 30E18 18 2 21.7 33 35.8 35 40E24 24 2 28.9 42 44.8 45 45E36 34 2 40.9 57 59.8 60 60

575 4.9 33 8 1.35 3.6 1.8

None - - - 17.3 19.1 20 20E09 9 1 8.7 17.3 19.1 20 20E18 18 2 17.3 26.1 28.4 30 30E24 24 2 23.1 33.4 35.6 35 40E36 34 2 32.7 45.4 47.6 50 50

102(8.5)

208 14.5 98 23 3.03 9.6 5.5

None - - - 48.3 53.8 60 60E09 6.8 1 18.9 48.3 53.8 60 60E18 13.5 2 37.5 58.9 65.8 60 70E24 18 2 50 74.5 81.4 80 90E36 25.5 2 70.8 100.5 107.4 110 110

230 14.5 98 23 3.03 9.6 5.5

None - - - 48.3 53.8 60 60E09 9 1 21.7 48.3 53.8 60 60E18 18 2 43.3 66.1 73 70 80E24 24 2 57.7 84.1 91 90 100E36 34 2 81.8 114.3 121.1 125 125

460 6.3 55 10 1.6 4.7 2.2

None - - - 22.1 24.3 25 30E09 9 1 10.8 22.1 24.3 25 30E18 18 2 21.7 33 35.8 35 40E24 24 2 28.9 42 44.8 45 45E36 34 2 40.9 57 59.8 60 60

575 6 41 9 1.35 3.6 1.8

None - - - 19.8 21.6 25 25E09 9 1 8.7 19.8 21.6 25 25E18 18 2 17.3 26.1 28.4 30 30E24 24 2 23.1 33.4 35.6 35 40E36 34 2 32.7 45.4 47.6 50 50

Page 143: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 143

120(10)

208 16 110 25 3.03 9.6 5.5

None - - - 51.7 57.2 60 70E18 13.5 2 37.5 58.9 65.8 60 70E24 18 2 50 74.5 81.4 80 90E36 25.5 2 70.8 100.5 107.4 110 110E54 40.6 2 112.7 152.9 159.8 175 175

230 16 110 25 3.03 9.6 5.5

None - - - 51.7 57.2 60 70E18 18 2 43.3 66.1 73 70 80E24 24 2 57.7 84.1 91 90 100E36 34 2 81.8 114.3 121.1 125 125E54 54 2 129.9 141.9 148.8 175 175

460 7.8 52 12 1.6 4.7 2.2

None - - - 25.5 27.7 30 35E18 18 2 21.7 33 35.8 35 40E24 24 2 28.9 42 44.8 45 45E36 34 2 40.9 57 59.8 60 60E54 54 2 65 70.9 73.6 80 80

575 5.7 38.9 9 1.35 3.6 1.8

None - - - 19.1 20.9 20 25E18 18 2 17.3 26.1 28.4 30 30E24 24 2 23.1 33.4 35.6 35 40E36 34 2 32.7 45.4 47.6 50 50E54 54 2 52 56.5 58.8 70 70

150(12.5)

208 23.1 160 36 2.1 14 5.5

None - - - 74.4 79.9 90 100E18 13.5 2 37.5 74.4 79.9 90 100E24 18 2 50 80 86.9 90 100E36 25.5 2 70.8 106 112.9 110 125E54 40.6 2 112.7 158.4 165.3 175 175

230 23.1 160 36 2.1 14 5.5

None - - - 74.4 79.9 90 100E18 18 2 43.3 74.4 79.9 90 100E24 24 2 57.7 89.6 96.5 90 100E36 34 2 81.8 119.8 126.6 125 150E54 54 2 129.9 147.4 154.3 175 175

460 12.2 87 19 1.26 6.6 2.2

None - - - 39.1 41.3 50 50E18 18 2 21.7 39.1 41.3 50 50E24 24 2 28.9 44.4 47.1 50 50E36 34 2 40.9 59.4 62.1 60 70E54 54 2 65 73.3 76 80 90

575 8.7 62 14 0.66 5.2 1.8

None - - - 27.4 29.2 35 35E18 18 2 17.3 28.1 30.4 35 35E24 24 2 23.1 35.4 37.6 40 40E36 34 2 32.7 47.4 49.6 50 50E54 54 2 52 58.5 60.8 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

ZH078-150 Hi Static Motor - Without Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 144: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

144 Johnson Controls Ducted Systems

ZH037-061 Standard Indoor Blower - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

1. Minimum Circuit Ampacity.

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 2.3 1 6.4 28.8 34.3 35 40E06 4.5 1 12.5 34.6 41.5 40 45E08 6.8 1 18.9 42.6 49.5 45 50E15 11.3 2 31.4 58.3 65.1 60 70

230 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 3 1 7.2 28.8 34.9 35 40E06 6 1 14.4 37 43.9 40 45E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80

460 5.8 38 9 1.26 2.6 2.2 20

None - - - 16.2 18.4 20 20E03 3 1 3.6 16.2 18.4 20 20E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35

575 3.8 36.5 6 0.66 2 1.8 20None - - - 11.5 13.3 15 15E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30

049(4)

208 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 34.6 40.1 45 50E06 4.5 1 12.5 34.6 41.5 45 50E08 6.8 1 18.9 42.6 49.5 45 50E15 11.3 2 31.4 58.3 65.1 60 70E20 15 2 41.6 71 77.9 80 80

230 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 34.6 40.1 45 50E06 6 1 14.4 37 43.9 45 50E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80E20 20 2 48.1 79.1 86 80 90

460 6.2 41 10 1.26 2.6 2.2 20

None - - - 16.7 18.9 20 25E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35E20 20 2 24.1 39.6 42.4 40 45

575 4.9 33 8 0.66 2 1.8 20

None - - - 12.8 14.6 15 15E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30E20 20 2 19.2 31.5 33.8 35 35

061(5)

208 15.9 110 25 2.1 5.2 5.5 20

None - - - 39.3 44.8 50 60E06 4.5 1 12.5 39.3 44.8 50 60E08 6.8 1 18.9 42.6 49.5 50 60E15 11.3 2 31.4 58.3 65.1 60 70E20 15 2 41.6 71 77.9 80 80E23 18 2 50 81.5 88.4 90 90

230 15.9 110 25 2.1 5.2 5.5 20

None - - - 39.3 44.8 50 60E06 6 1 14.4 39.3 44.8 50 60E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80E20 20 2 48.1 79.1 86 80 90E23 24 2 57.7 91.1 98 100 100

460 7.1 52 11 1.26 2.6 2.2 20

None - - - 19 21.2 25 25E06 6 1 7.2 19 21.3 25 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35E20 20 2 24.1 39.6 42.4 40 45E23 24 2 28.9 45.6 48.4 50 50

575 5.1 39.5 8 0.66 2 1.8 20

None - - - 13.7 15.5 15 20E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30E20 20 2 19.2 31.5 33.8 35 35E23 24 2 23.1 36.4 38.6 40 40

Page 145: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 145

ZH078-150 Standard Motor - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 11.2 84 18 2.1 5.2 5.5 20

None - - - 44.6 50.1 50 60E09 6.8 1 18.9 44.6 50.1 50 60E18 13.5 2 37.5 65.9 72.8 70 80E24 18 2 50 81.5 88.4 90 90E36 25.5 2 70.8 107.5 114.4 110 125

230 11.2 84 18 2.1 5.2 5.5 20

None - - - 44.6 50.1 50 60E09 9 1 21.7 46.1 53 50 60E18 18 2 43.3 73.1 80 80 80E24 24 2 57.7 91.1 98 100 100E36 34 2 81.8 121.3 128.1 125 150

460 5.6 44 9 1.26 2.6 2.2 20

None - - - 22.7 24.9 25 30E09 9 1 10.8 23 25.8 25 30E18 18 2 21.7 36.6 39.4 40 40E24 24 2 28.9 45.6 48.4 50 50E36 34 2 40.9 60.6 63.4 70 70

575 3.8 34 6 0.66 2 1.8 20

None - - - 15.9 17.7 20 20E09 9 1 8.7 18.4 20.6 20 25E18 18 2 17.3 29.1 31.4 30 35E24 24 2 23.1 36.4 38.6 40 40E36 34 2 32.7 48.4 50.6 50 60

090(7.5)

208 13.8 83.1 22 3.03 5.2 5.5 20

None - - - 52.4 57.9 60 70E09 6.8 1 18.9 52.4 57.9 60 70E18 13.5 2 37.5 65.9 72.8 70 80E24 18 2 50 81.5 88.4 90 90E36 25.5 2 70.8 107.5 114.4 110 125

230 13.8 83.1 22 3.03 5.2 5.5 20

None - - - 52.4 57.9 60 70E09 9 1 21.7 52.4 57.9 60 70E18 18 2 43.3 73.1 80 80 80E24 24 2 57.7 91.1 98 100 100E36 34 2 81.8 121.3 128.1 125 150

460 6.2 41 10 1.6 2.6 2.2 20

None - - - 24.8 27 30 30E09 9 1 10.8 24.8 27 30 30E18 18 2 21.7 36.6 39.4 40 40E24 24 2 28.9 45.6 48.4 50 50E36 34 2 40.9 60.6 63.4 70 70

575 4.9 33 8 1.35 2 1.8 20

None - - - 19.7 21.5 20 25E09 9 1 8.7 19.7 21.5 20 25E18 18 2 17.3 29.1 31.4 30 35E24 24 2 23.1 36.4 38.6 40 40E36 34 2 32.7 48.4 50.6 50 60

102(8.5)

208 14.5 98 23 3.03 6.8 5.5 20

None - - - 55.5 61 70 70E09 6.8 1 18.9 55.5 61 70 70E18 13.5 2 37.5 67.9 74.8 70 80E24 18 2 50 83.5 90.4 90 100E36 25.5 2 70.8 109.5 116.4 110 125

230 14.5 98 23 3.03 6.8 5.5 20

None - - - 55.5 61 70 70E09 9 1 21.7 55.5 61 70 70E18 18 2 43.3 75.1 82 80 90E24 24 2 57.7 93.1 100 100 100E36 34 2 81.8 123.3 130.1 125 150

460 6.3 55 10 1.6 3.4 2.2 20

None - - - 25.8 28 30 30E09 9 1 10.8 25.8 28 30 30E18 18 2 21.7 37.6 40.4 40 45E24 24 2 28.9 46.6 49.4 50 50E36 34 2 40.9 61.6 64.4 70 70

575 6 41 9 1.35 2.4 1.8 20

None - - - 22.6 24.4 25 30E09 9 1 8.7 22.6 24.4 25 30E18 18 2 17.3 29.6 31.9 30 35E24 24 2 23.1 36.9 39.1 40 40E36 34 2 32.7 48.9 51.1 50 60

Page 146: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

146 Johnson Controls Ducted Systems

120(10)

208 16 110 25 3.03 6.8 5.5 20

None - - - 58.9 64.4 70 80E18 13.5 2 37.5 67.9 74.8 70 80E24 18 2 50 83.5 90.4 90 100E36 25.5 2 70.8 109.5 116.4 110 125E54 40.6 2 112.7 161.9 168.8 175 175

230 16 110 25 3.03 6.8 5.5 20

None - - - 58.9 64.4 70 80E18 18 2 43.3 75.1 82 80 90E24 24 2 57.7 93.1 100 100 100E36 34 2 81.8 123.3 130.1 125 150E54 54 2 129.9 150.9 157.8 175 175

460 7.8 52 12 1.6 3.4 2.2 20

None - - - 29.2 31.4 35 35E18 18 2 21.7 37.6 40.4 40 45E24 24 2 28.9 46.6 49.4 50 50E36 34 2 40.9 61.6 64.4 70 70E54 54 2 65 75.5 78.3 80 90

575 5.7 38.9 9 1.35 2.4 1.8 20

None - - - 21.9 23.7 25 25E18 18 2 17.3 29.6 31.9 30 35E24 24 2 23.1 36.9 39.1 40 40E36 34 2 32.7 48.9 51.1 50 60E54 54 2 52 60 62.3 70 70

150(12.5)

208 23.1 160 36 2.1 9.6 5.5 20

None - - - 80 85.5 100 100E18 13.5 2 37.5 80 85.5 100 100E24 18 2 50 87 93.9 100 100E36 25.5 2 70.8 113 119.9 125 125E54 40.6 2 112.7 165.4 172.3 175 175

230 23.1 160 36 2.1 9.6 5.5 20

None - - - 80 85.5 100 100E18 18 2 43.3 80 85.5 100 100E24 24 2 57.7 96.6 103.5 100 110E36 34 2 81.8 126.8 133.6 150 150E54 54 2 129.9 154.4 161.3 175 175

460 12.2 87 19 1.26 4.7 2.2 20

None - - - 42.2 44.4 50 50E18 18 2 21.7 42.2 44.4 50 50E24 24 2 28.9 48.3 51 50 60E36 34 2 40.9 63.3 66 70 70E54 54 2 65 77.1 79.9 90 90

575 8.7 62 14 0.66 3.6 1.8 20

None - - - 29.8 31.6 35 40E18 18 2 17.3 31.1 33.4 35 40E24 24 2 23.1 38.4 40.6 40 45E36 34 2 32.7 50.4 52.6 60 60E54 54 2 52 61.5 63.8 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

ZH078-150 Standard Motor - With Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 147: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 147

ZH037-061 Hi Static Indoor Blower - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

1. Minimum Circuit Ampacity.

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 2.3 1 6.4 28.8 34.3 35 40E06 4.5 1 12.5 34.6 41.5 40 45E08 6.8 1 18.9 42.6 49.5 45 50E15 11.3 2 31.4 58.3 65.1 60 70

230 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 3 1 7.2 28.8 34.9 35 40E06 6 1 14.4 37 43.9 40 45E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80

460 5.8 38 9 1.26 2.6 2.2 20

None - - - 16.2 18.4 20 20E03 3 1 3.6 16.2 18.4 20 20E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35

575 3.8 36.5 6 0.66 2 1.8 20None - - - 11.5 13.3 15 15E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30

049(4)

208 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 34.6 40.1 45 50E06 4.5 1 12.5 34.6 41.5 45 50E08 6.8 1 18.9 42.6 49.5 45 50E15 11.3 2 31.4 58.3 65.1 60 70E20 15 2 41.6 71 77.9 80 80

230 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 34.6 40.1 45 50E06 6 1 14.4 37 43.9 45 50E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80E20 20 2 48.1 79.1 86 80 90

460 6.2 41 10 1.26 2.6 2.2 20

None - - - 16.7 18.9 20 25E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35E20 20 2 24.1 39.6 42.4 40 45

575 4.9 33 8 0.66 2 1.8 20

None - - - 12.8 14.6 15 15E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30E20 20 2 19.2 31.5 33.8 35 35

061(5)

208 15.9 110 25 2.1 6.8 5.5 20

None - - - 40.9 46.4 50 60E06 4.5 1 12.5 40.9 46.4 50 60E08 6.8 1 18.9 44.6 51.5 50 60E15 11.3 2 31.4 60.3 67.1 70 70E20 15 2 41.6 73 79.9 80 80E23 18 2 50 83.5 90.4 90 100

230 15.9 110 25 2.1 6.8 5.5 20

None - - - 40.9 46.4 50 60E06 6 1 14.4 40.9 46.4 50 60E08 9 1 21.7 48.1 55 50 60E15 15 2 36.1 66.1 73 70 80E20 20 2 48.1 81.1 88 90 90E23 24 2 57.7 93.1 100 100 100

460 7.1 52 11 1.26 3.4 2.2 20

None - - - 19.8 22 25 25E06 6 1 7.2 19.8 22.3 25 25E08 9 1 10.8 24 26.8 25 30E15 15 2 18 33 35.8 35 40E20 20 2 24.1 40.6 43.4 45 45E23 24 2 28.9 46.6 49.4 50 50

575 5.1 39.5 8 0.66 2.4 1.8 20

None - - - 14.1 15.9 15 20E08 9 1 8.7 18.9 21.1 20 25E15 15 2 14.4 26 28.3 30 30E20 20 2 19.2 32 34.3 35 35E23 24 2 23.1 36.9 39.1 40 40

Page 148: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

148 Johnson Controls Ducted Systems

ZH078-150 Hi Static Motor - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 11.2 84 18 2.1 6.8 5.5 20

None - - - 46.2 51.7 50 60E09 6.8 1 18.9 46.2 51.7 50 60E18 13.5 2 37.5 67.9 74.8 70 80E24 18 2 50 83.5 90.4 90 100E36 25.5 2 70.8 109.5 116.4 110 125

230 11.2 84 18 2.1 6.8 5.5 20

None - - - 46.2 51.7 50 60E09 9 1 21.7 48.1 55 50 60E18 18 2 43.3 75.1 82 80 90E24 24 2 57.7 93.1 100 100 100E36 34 2 81.8 123.3 130.1 125 150

460 5.6 44 9 1.26 3.4 2.2 20

None - - - 23.5 25.7 25 30E09 9 1 10.8 24 26.8 25 30E18 18 2 21.7 37.6 40.4 40 45E24 24 2 28.9 46.6 49.4 50 50E36 34 2 40.9 61.6 64.4 70 70

575 3.8 34 6 0.66 2.4 1.8 20

None - - - 16.3 18.1 20 20E09 9 1 8.7 18.9 21.1 20 25E18 18 2 17.3 29.6 31.9 30 35E24 24 2 23.1 36.9 39.1 40 40E36 34 2 32.7 48.9 51.1 50 60

090(7.5)

208 13.8 83.1 22 3.03 9.6 5.5 20

None - - - 56.8 62.3 70 70E09 6.8 1 18.9 56.8 62.3 70 70E18 13.5 2 37.5 71.4 78.3 80 80E24 18 2 50 87 93.9 90 100E36 25.5 2 70.8 113 119.9 125 125

230 13.8 83.1 22 3.03 9.6 5.5 20

None - - - 56.8 62.3 70 70E09 9 1 21.7 56.8 62.3 70 70E18 18 2 43.3 78.6 85.5 80 90E24 24 2 57.7 96.6 103.5 100 110E36 34 2 81.8 126.8 133.6 150 150

460 6.2 41 10 1.6 4.7 2.2 20

None - - - 26.9 29.1 30 35E09 9 1 10.8 26.9 29.1 30 35E18 18 2 21.7 39.3 42 40 45E24 24 2 28.9 48.3 51 50 60E36 34 2 40.9 63.3 66 70 70

575 4.9 33 8 1.35 3.6 1.8 20

None - - - 21.3 23.1 25 25E09 9 1 8.7 21.3 23.1 25 25E18 18 2 17.3 31.1 33.4 35 35E24 24 2 23.1 38.4 40.6 40 45E36 34 2 32.7 50.4 52.6 60 60

102(8.5)

208 14.5 98 23 3.03 9.6 5.5 20

None - - - 58.3 63.8 70 70E09 6.8 1 18.9 58.3 63.8 70 70E18 13.5 2 37.5 71.4 78.3 80 80E24 18 2 50 87 93.9 90 100E36 25.5 2 70.8 113 119.9 125 125

230 14.5 98 23 3.03 9.6 5.5 20

None - - - 58.3 63.8 70 70E09 9 1 21.7 58.3 63.8 70 70E18 18 2 43.3 78.6 85.5 80 90E24 24 2 57.7 96.6 103.5 100 110E36 34 2 81.8 126.8 133.6 150 150

460 6.3 55 10 1.6 4.7 2.2 20

None - - - 27.1 29.3 30 35E09 9 1 10.8 27.1 29.3 30 35E18 18 2 21.7 39.3 42 40 45E24 24 2 28.9 48.3 51 50 60E36 34 2 40.9 63.3 66 70 70

575 6 41 9 1.35 3.6 1.8 20

None - - - 23.8 25.6 25 30E09 9 1 8.7 23.8 25.6 25 30E18 18 2 17.3 31.1 33.4 35 35E24 24 2 23.1 38.4 40.6 40 45E36 34 2 32.7 50.4 52.6 60 60

Page 149: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 149

120(10)

208 16 110 25 3.03 9.6 5.5 20

None - - - 61.7 67.2 70 80E18 13.5 2 37.5 71.4 78.3 80 80E24 18 2 50 87 93.9 90 100E36 25.5 2 70.8 113 119.9 125 125E54 40.6 2 112.7 165.4 172.3 175 175

230 16 110 25 3.03 9.6 5.5 20

None - - - 61.7 67.2 70 80E18 18 2 43.3 78.6 85.5 80 90E24 24 2 57.7 96.6 103.5 100 110E36 34 2 81.8 126.8 133.6 150 150E54 54 2 129.9 154.4 161.3 175 175

460 7.8 52 12 1.6 4.7 2.2 20

None - - - 30.5 32.7 35 40E18 18 2 21.7 39.3 42 40 45E24 24 2 28.9 48.3 51 50 60E36 34 2 40.9 63.3 66 70 70E54 54 2 65 77.1 79.9 90 90

575 5.7 38.9 9 1.35 3.6 1.8 20

None - - - 23.1 24.9 25 30E18 18 2 17.3 31.1 33.4 35 35E24 24 2 23.1 38.4 40.6 40 45E36 34 2 32.7 50.4 52.6 60 60E54 54 2 52 61.5 63.8 70 70

150(12.5)

208 23.1 160 36 2.1 14 5.5 20

None - - - 84.4 89.9 100 110E18 13.5 2 37.5 84.4 89.9 100 110E24 18 2 50 92.5 99.4 100 110E36 25.5 2 70.8 118.5 125.4 125 150E54 40.6 2 112.7 170.9 177.8 175 200

230 23.1 160 36 2.1 14 5.5 20

None - - - 84.4 89.9 100 110E18 18 2 43.3 84.4 91 100 110E24 24 2 57.7 102.1 109 110 110E36 34 2 81.8 132.3 139.1 150 150E54 54 2 129.9 159.9 166.8 175 175

460 12.2 87 19 1.26 6.6 2.2 20

None - - - 44.1 46.3 50 50E18 18 2 21.7 44.1 46.3 50 50E24 24 2 28.9 50.6 53.4 60 60E36 34 2 40.9 65.6 68.4 70 70E54 54 2 65 79.5 82.3 90 90

575 8.7 62 14 0.66 5.2 1.8 20

None - - - 31.4 33.2 40 40E18 18 2 17.3 33.1 35.4 40 40E24 24 2 23.1 40.4 42.6 45 45E36 34 2 32.7 52.4 54.6 60 60E54 54 2 52 63.5 65.8 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

ZH078-150 Hi Static Motor - With Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 150: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

150 Johnson Controls Ducted Systems

ZJ037-061 Standard Indoor Blower - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

1. Minimum Circuit Ampacity.

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 2.3 1 6.4 18.6 24.1 25 30E06 4.5 1 12.5 22.1 29 25 30E08 6.8 1 18.9 30.1 37 35 40E15 11.3 2 31.4 45.8 52.6 50 60

230 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 3 1 7.2 18.6 24.1 25 30E06 6 1 14.4 24.5 31.4 25 35E08 9 1 21.7 33.6 40.5 35 45E15 15 2 36.1 51.6 58.5 60 60

460 5.8 38 9 1.26 2.6 2.2

None - - - 11.2 13.4 15 15E03 3 1 3.6 11.2 13.4 15 15E06 6 1 7.2 12.3 15 15 15E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30

575 3.8 36.5 6 0.66 2 1.8None - - - 7.5 9.3 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25

049(4)

208 13.8 83.1 22 2.1 5.2 5.5

None - - - 24.6 30.1 35 40E06 4.5 1 12.5 24.6 30.1 35 40E08 6.8 1 18.9 30.1 37 35 40E15 11.3 2 31.4 45.8 52.6 50 60E20 15 2 41.6 58.5 65.4 60 70

230 13.8 83.1 22 2.1 5.2 5.5

None - - - 24.6 30.1 35 40E06 6 1 14.4 24.6 31.4 35 40E08 9 1 21.7 33.6 40.5 35 45E15 15 2 36.1 51.6 58.5 60 60E20 20 2 48.1 66.6 73.5 70 80

460 6.2 41 10 1.26 2.6 2.2

None - - - 11.7 13.9 15 20E06 6 1 7.2 12.3 15 15 20E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30E20 20 2 24.1 33.4 36.1 35 40

575 4.9 33 8 0.66 2 1.8

None - - - 8.8 10.6 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25E20 20 2 19.2 26.5 28.8 30 30

061(5)

208 15.9 110 25 2.1 5.2 5.5

None - - - 29.3 34.8 40 45E06 4.5 1 12.5 29.3 34.8 40 45E08 6.8 1 18.9 30.1 37 40 50E15 11.3 2 31.4 45.8 52.6 50 60E20 15 2 41.6 58.5 65.4 60 70E23 18 2 50 69 75.9 70 80

230 15.9 110 25 2.1 5.2 5.5

None - - - 29.3 34.8 40 45E06 6 1 14.4 29.3 34.8 40 45E08 9 1 21.7 33.6 40.5 45 50E15 15 2 36.1 51.6 58.5 60 60E20 20 2 48.1 66.6 73.5 70 80E23 24 2 57.7 78.6 85.5 80 90

460 7.1 52 11 1.26 2.6 2.2

None - - - 14 16.2 20 20E06 6 1 7.2 14 16.2 20 20E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30E20 20 2 24.1 33.4 36.1 35 40E23 24 2 28.9 39.4 42.1 40 45

575 5.1 39.5 8 0.66 2 1.8

None - - - 9.7 11.5 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25E20 20 2 19.2 26.5 28.8 30 30E23 24 2 23.1 31.4 33.6 35 35

Page 151: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 151

ZJ078-150 Standard Motor - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 11.2 84 18 2.1 5.2 5.5

None - - - 34.6 40.1 45 50

E09 6.8 1 18.9 34.6 40.1 45 50

E18 13.5 2 37.5 53.4 60.3 60 70

E24 18 2 50 69 75.9 70 80

E36 25.5 2 70.8 95 101.9 100 110

230 11.2 84 18 2.1 5.2 5.5

None - - - 34.6 40.1 45 50

E09 9 1 21.7 34.6 40.5 45 50

E18 18 2 43.3 60.6 67.5 70 70

E24 24 2 57.7 78.6 85.5 80 90

E36 34 2 81.8 108.8 115.6 110 125

460 5.6 44 9 1.26 2.6 2.2

None - - - 17.7 19.9 20 25

E09 9 1 10.8 17.7 19.9 20 25

E18 18 2 21.7 30.4 33.1 35 35

E24 24 2 28.9 39.4 42.1 40 45

E36 34 2 40.9 54.4 57.1 60 60

575 3.8 34 6 0.66 2 1.8

None - - - 11.9 13.7 15 15

E09 9 1 8.7 13.4 15.6 15 20

E18 18 2 17.3 24.1 26.4 25 30

E24 24 2 23.1 31.4 33.6 35 35

E36 34 2 32.7 43.4 45.6 45 50

090(7.5)

208 13.6 83.1 21 3.03 5.2 5.5

None - - - 41.9 47.4 50 60

E09 6.8 1 18.9 41.9 47.4 50 60

E18 13.5 2 37.5 53.4 60.3 60 70

E24 18 2 50 69 75.9 70 80

E36 25.5 2 70.8 95 101.9 100 110

230 13.6 83.1 21 3.03 5.2 5.5

None - - - 41.9 47.4 50 60

E09 9 1 21.7 41.9 47.4 50 60

E18 18 2 43.3 60.6 67.5 70 70

E24 24 2 57.7 78.6 85.5 80 90

E36 34 2 81.8 108.8 115.6 110 125

460 6.1 41 10 1.6 2.6 2.2

None - - - 19.5 21.7 25 25

E09 9 1 10.8 19.5 21.7 25 25

E18 18 2 21.7 30.4 33.1 35 35

E24 24 2 28.9 39.4 42.1 40 45

E36 34 2 40.9 54.4 57.1 60 60

575 4.2 33 7 1.35 2 1.8

None - - - 14.2 16 15 20

E09 9 1 8.7 14.2 16 15 20

E18 18 2 17.3 24.1 26.4 25 30

E24 24 2 23.1 31.4 33.6 35 35

E36 34 2 32.7 43.4 45.6 45 50

102(8.5)

208 14.5 98 23 3.03 6.8 5.5

None - - - 45.5 51 60 60

E09 6.8 1 18.9 45.5 51 60 60

E18 13.5 2 37.5 55.4 62.3 60 70

E24 18 2 50 71 77.9 80 80

E36 25.5 2 70.8 97 103.9 100 110

230 14.5 98 23 3.03 6.8 5.5

None - - - 45.5 51 60 60

E09 9 1 21.7 45.5 51 60 60

E18 18 2 43.3 62.6 69.5 70 70

E24 24 2 57.7 80.6 87.5 90 90

E36 34 2 81.8 110.8 117.6 125 125

460 6.3 55 10 1.6 3.4 2.2

None - - - 20.8 23 25 25

E09 9 1 10.8 20.8 23 25 25

E18 18 2 21.7 31.4 34.1 35 35

E24 24 2 28.9 40.4 43.1 45 45

E36 34 2 40.9 55.4 58.1 60 60

575 6 41 9 1.35 2.4 1.8

None - - - 18.6 20.4 20 25

E09 9 1 8.7 18.6 20.4 20 25

E18 18 2 17.3 24.6 26.9 25 30

E24 24 2 23.1 31.9 34.1 35 35

E36 34 2 32.7 43.9 46.1 45 50

Page 152: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

152 Johnson Controls Ducted Systems

120(10)

208 16.0 110.0 24.9 3.0 6.8 5.5 0.0

None - - - 48.9 54.4 60 70E18 13.5 2 37.5 55.3 62.2 60 70E24 18.0 2 50.0 71.0 77.8 80 80E36 25.5 2 70.8 97.0 103.9 100 110E54 40.6 2 112.7 149.4 156.2 150 175

230 16.0 110.0 24.9 3.0 6.8 5.5 0.0

None - - - 48.9 54.4 60 70E18 18.0 2 43.3 62.6 69.5 70 70E24 24.0 2 57.7 80.7 87.5 90 90E36 34.0 2 81.8 110.7 117.6 125 125E54 54.0 2 129.9 138.4 145.3 150 175

460 7.8 52.0 12.1 1.6 3.4 2.2 0.0

None - - - 24.2 26.4 30 30E18 18.0 2 21.7 31.3 34.1 35 35E24 24.0 2 28.9 40.3 43.1 45 45E36 34.0 2 40.9 55.4 58.1 60 60E54 54.0 2 65.0 69.2 72.0 80 80

575 5.7 38.9 8.9 1.4 2.4 1.8 0.0

None - - - 17.9 19.7 20 25E18 18.0 2 17.3 24.7 26.9 25 30E24 24.0 2 23.1 31.9 34.1 35 35E36 34.0 2 32.7 43.9 46.1 45 50E54 54.0 2 52.0 55.0 57.2 60 60

150(12.5)

208 23.1 160.0 36.0 2.1 9.6 5.5 0.0

None - - - 70.0 75.5 90 90E18 13.5 2 37.5 70.0 75.5 90 90E24 18.0 2 50.0 74.5 81.3 90 90E36 25.5 2 70.8 100.5 107.4 110 110E54 40.6 2 112.7 152.9 159.7 175 175

230 23.1 160.0 36.0 2.1 9.6 5.5 0.0

None - - - 70.0 75.5 90 90E18 18.0 2 43.3 70.0 75.5 90 90E24 24.0 2 57.7 84.2 91.0 90 100E36 34.0 2 81.8 114.2 121.1 125 125E54 54.0 2 129.9 141.9 148.8 175 175

460 12.2 87.0 19.0 1.3 4.7 2.2 0.0

None - - - 37.2 39.4 45 50E18 18.0 2 21.7 37.2 39.4 45 50E24 24.0 2 28.9 42.0 44.7 45 50E36 34.0 2 40.9 57.0 59.7 60 60E54 54.0 2 65.0 70.8 73.6 80 80

575 8.7 62.0 13.5 0.7 3.6 1.8 0.0

None - - - 25.8 27.6 30 35E18 18.0 2 17.3 26.2 28.4 30 35E24 24.0 2 23.1 33.4 35.6 35 40E36 34.0 2 32.7 45.4 47.6 50 50E54 54.0 2 52.0 56.5 58.7 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

ZJ078-150 Standard Motor - Without Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 153: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 153

ZJ037-061 Hi Static Indoor Blower - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

1. Minimum Circuit Ampacity.

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 2.3 1 6.4 18.6 24.1 25 30E06 4.5 1 12.5 22.1 29 25 30E08 6.8 1 18.9 30.1 37 35 40E15 11.3 2 31.4 45.8 52.6 50 60

230 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 3 1 7.2 18.6 24.1 25 30E06 6 1 14.4 24.5 31.4 25 35E08 9 1 21.7 33.6 40.5 35 45E15 15 2 36.1 51.6 58.5 60 60

460 5.8 38 9 1.26 2.6 2.2

None - - - 11.2 13.4 15 15E03 3 1 3.6 11.2 13.4 15 15E06 6 1 7.2 12.3 15 15 15E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30

575 3.8 36.5 6 0.66 2 1.8None - - - 7.5 9.3 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25

049(4)

208 13.8 83.1 22 2.1 5.2 5.5

None - - - 24.6 30.1 35 40E06 4.5 1 12.5 24.6 30.1 35 40E08 6.8 1 18.9 30.1 37 35 40E15 11.3 2 31.4 45.8 52.6 50 60E20 15 2 41.6 58.5 65.4 60 70

230 13.8 83.1 22 2.1 5.2 5.5

None - - - 24.6 30.1 35 40E06 6 1 14.4 24.6 31.4 35 40E08 9 1 21.7 33.6 40.5 35 45E15 15 2 36.1 51.6 58.5 60 60E20 20 2 48.1 66.6 73.5 70 80

460 6.2 41 10 1.26 2.6 2.2

None - - - 11.7 13.9 15 20E06 6 1 7.2 12.3 15 15 20E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30E20 20 2 24.1 33.4 36.1 35 40

575 4.9 33 8 0.66 2 1.8

None - - - 8.8 10.6 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25E20 20 2 19.2 26.5 28.8 30 30

061(5)

208 15.9 110 25 2.1 6.8 5.5

None - - - 30.9 36.4 40 50E06 4.5 1 12.5 30.9 36.4 40 50E08 6.8 1 18.9 32.1 39 45 50E15 11.3 2 31.4 47.8 54.6 50 60E20 15 2 41.6 60.5 67.4 70 70E23 18 2 50 71 77.9 80 80

230 15.9 110 25 2.1 6.8 5.5

None - - - 30.9 36.4 40 50E06 6 1 14.4 30.9 36.4 40 50E08 9 1 21.7 35.6 42.5 45 50E15 15 2 36.1 53.6 60.5 60 70E20 20 2 48.1 68.6 75.5 70 80E23 24 2 57.7 80.6 87.5 90 90

460 7.1 52 11 1.26 3.4 2.2

None - - - 14.8 17 20 20E06 6 1 7.2 14.8 17 20 20E08 9 1 10.8 17.8 20.5 20 25E15 15 2 18 26.8 29.5 30 30E20 20 2 24.1 34.4 37.1 35 40E23 24 2 28.9 40.4 43.1 45 45

575 5.1 39.5 8 0.66 2.4 1.8

None - - - 10.1 11.9 15 15E08 9 1 8.7 13.9 16.1 15 20E15 15 2 14.4 21 23.3 25 25E20 20 2 19.2 27 29.3 30 30E23 24 2 23.1 31.9 34.1 35 35

Page 154: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

154 Johnson Controls Ducted Systems

ZJ078-150 Hi Static Motor - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 11.2 84 18 2.1 6.8 5.5

None - - - 36.2 41.7 45 50E09 6.8 1 18.9 36.2 41.7 45 50E18 13.5 2 37.5 55.4 62.3 60 70E24 18 2 50 71 77.9 80 80E36 25.5 2 70.8 97 103.9 100 110

230 11.2 84 18 2.1 6.8 5.5

None - - - 36.2 41.7 45 50E09 9 1 21.7 36.2 42.5 45 50E18 18 2 43.3 62.6 69.5 70 70E24 24 2 57.7 80.6 87.5 90 90E36 34 2 81.8 110.8 117.6 125 125

460 5.6 44 9 1.26 3.4 2.2

None - - - 18.5 20.7 20 25E09 9 1 10.8 18.5 20.7 20 25E18 18 2 21.7 31.4 34.1 35 35E24 24 2 28.9 40.4 43.1 45 45E36 34 2 40.9 55.4 58.1 60 60

575 3.8 34 6 0.66 2.4 1.8

None - - - 12.3 14.1 15 15E09 9 1 8.7 13.9 16.1 15 20E18 18 2 17.3 24.6 26.9 25 30E24 24 2 23.1 31.9 34.1 35 35E36 34 2 32.7 43.9 46.1 45 50

090(7.5)

208 13.6 83.1 21 3.03 9.6 5.5

None - - - 46.3 51.8 50 60E09 6.8 1 18.9 46.3 51.8 50 60E18 13.5 2 37.5 58.9 65.8 60 70E24 18 2 50 74.5 81.4 80 90E36 25.5 2 70.8 100.5 107.4 110 110

230 13.6 83.1 21 3.03 9.6 5.5

None - - - 46.3 51.8 50 60E09 9 1 21.7 46.3 51.8 50 60E18 18 2 43.3 66.1 73 70 80E24 24 2 57.7 84.1 91 90 100E36 34 2 81.8 114.3 121.1 125 125

460 6.1 41 10 1.6 4.7 2.2

None - - - 21.6 23.8 25 25E09 9 1 10.8 21.6 23.8 25 25E18 18 2 21.7 33 35.8 35 40E24 24 2 28.9 42 44.8 45 45E36 34 2 40.9 57 59.8 60 60

575 4.2 33 7 1.35 3.6 1.8

None - - - 15.8 17.6 20 20E09 9 1 8.7 15.8 17.6 20 20E18 18 2 17.3 26.1 28.4 30 30E24 24 2 23.1 33.4 35.6 35 40E36 34 2 32.7 45.4 47.6 50 50

102(8.5)

208 14.5 98 23 3.03 9.6 5.5

None - - - 48.3 53.8 60 60E09 6.8 1 18.9 48.3 53.8 60 60E18 13.5 2 37.5 58.9 65.8 60 70E24 18 2 50 74.5 81.4 80 90E36 25.5 2 70.8 100.5 107.4 110 110

230 14.5 98 23 3.03 9.6 5.5

None - - - 48.3 53.8 60 60E09 9 1 21.7 48.3 53.8 60 60E18 18 2 43.3 66.1 73 70 80E24 24 2 57.7 84.1 91 90 100E36 34 2 81.8 114.3 121.1 125 125

460 6.3 55 10 1.6 4.7 2.2

None - - - 22.1 24.3 25 30E09 9 1 10.8 22.1 24.3 25 30E18 18 2 21.7 33 35.8 35 40E24 24 2 28.9 42 44.8 45 45E36 34 2 40.9 57 59.8 60 60

575 6 41 9 1.35 3.6 1.8

None - - - 19.8 21.6 25 25E09 9 1 8.7 19.8 21.6 25 25E18 18 2 17.3 26.1 28.4 30 30E24 24 2 23.1 33.4 35.6 35 40E36 34 2 32.7 45.4 47.6 50 50

Page 155: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 155

120(10)

208 16.0 110.0 24.9 3.0 9.6 5.5 0.0

None - - - 51.7 57.2 60 70E18 13.5 2 37.5 58.8 65.7 60 70E24 18.0 2 50.0 74.5 81.3 80 90E36 25.5 2 70.8 100.5 107.4 110 110E54 40.6 2 112.7 152.9 159.7 175 175

230 16.0 110.0 24.9 3.0 9.6 5.5 0.0

None - - - 51.7 57.2 60 70E18 18.0 2 43.3 66.1 73.0 70 80E24 24.0 2 57.7 84.2 91.0 90 100E36 34.0 2 81.8 114.2 121.1 125 125E54 54.0 2 129.9 141.9 148.8 175 175

460 7.8 52.0 12.1 1.6 4.7 2.2 0.0

None - - - 25.5 27.7 30 35E18 18.0 2 21.7 32.9 35.7 35 40E24 24.0 2 28.9 42.0 44.7 45 45E36 34.0 2 40.9 57.0 59.7 60 60E54 54.0 2 65.0 70.8 73.6 80 80

575 5.7 38.9 8.9 1.4 3.6 1.8 0.0

None - - - 19.1 20.9 20 25E18 18.0 2 17.3 26.2 28.4 30 30E24 24.0 2 23.1 33.4 35.6 35 40E36 34.0 2 32.7 45.4 47.6 50 50E54 54.0 2 52.0 56.5 58.7 70 70

150(12.5)

208 23.1 160.0 36.0 2.1 14.0 5.5 0.0

None - - - 74.4 79.9 90 100E18 13.5 2 37.5 74.4 79.9 90 100E24 18.0 2 50.0 80.0 86.8 90 100E36 25.5 2 70.8 106.0 112.9 110 125E54 40.6 2 112.7 158.4 165.2 175 175

230 23.1 160.0 36.0 2.1 14.0 5.5 0.0

None - - - 74.4 79.9 90 100E18 18.0 2 43.3 74.4 79.9 90 100E24 24.0 2 57.7 89.7 96.5 90 100E36 34.0 2 81.8 119.7 126.6 125 150E54 54.0 2 129.9 147.4 154.3 175 175

460 12.2 87.0 19.0 1.3 6.6 2.2 0.0

None - - - 39.1 41.3 50 50E18 18.0 2 21.7 39.1 41.3 50 50E24 24.0 2 28.9 44.3 47.1 50 50E36 34.0 2 40.9 59.4 62.1 60 70E54 54.0 2 65.0 73.2 76.0 80 90

575 8.7 62.0 13.5 0.7 5.2 1.8 0.0

None - - - 27.4 29.2 35 35E18 18.0 2 17.3 28.2 30.4 35 35E24 24.0 2 23.1 35.4 37.6 40 40E36 34.0 2 32.7 47.4 49.6 50 50E54 54.0 2 52.0 58.5 60.7 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

ZJ078-150 Hi Static Motor - Without Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 156: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

156 Johnson Controls Ducted Systems

ZJ037-061 Standard Indoor Blower - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

1. Minimum Circuit Ampacity.

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 2.3 1 6.4 28.8 34.3 35 40E06 4.5 1 12.5 34.6 41.5 40 45E08 6.8 1 18.9 42.6 49.5 45 50E15 11.3 2 31.4 58.3 65.1 60 70

230 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 3 1 7.2 28.8 34.9 35 40E06 6 1 14.4 37 43.9 40 45E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80

460 5.8 38 9 1.26 2.6 2.2 20

None - - - 16.2 18.4 20 20E03 3 1 3.6 16.2 18.4 20 20E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35

575 3.8 36.5 6 0.66 2 1.8 20None - - - 11.5 13.3 15 15E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30

049(4)

208 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 34.6 40.1 45 50E06 4.5 1 12.5 34.6 41.5 45 50E08 6.8 1 18.9 42.6 49.5 45 50E15 11.3 2 31.4 58.3 65.1 60 70E20 15 2 41.6 71 77.9 80 80

230 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 34.6 40.1 45 50E06 6 1 14.4 37 43.9 45 50E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80E20 20 2 48.1 79.1 86 80 90

460 6.2 41 10 1.26 2.6 2.2 20

None - - - 16.7 18.9 20 25E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35E20 20 2 24.1 39.6 42.4 40 45

575 4.9 33 8 0.66 2 1.8 20

None - - - 12.8 14.6 15 15E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30E20 20 2 19.2 31.5 33.8 35 35

061(5)

208 15.9 110 25 2.1 5.2 5.5 20

None - - - 39.3 44.8 50 60E06 4.5 1 12.5 39.3 44.8 50 60E08 6.8 1 18.9 42.6 49.5 50 60E15 11.3 2 31.4 58.3 65.1 60 70E20 15 2 41.6 71 77.9 80 80E23 18 2 50 81.5 88.4 90 90

230 15.9 110 25 2.1 5.2 5.5 20

None - - - 39.3 44.8 50 60E06 6 1 14.4 39.3 44.8 50 60E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80E20 20 2 48.1 79.1 86 80 90E23 24 2 57.7 91.1 98 100 100

460 7.1 52 11 1.26 2.6 2.2 20

None - - - 19 21.2 25 25E06 6 1 7.2 19 21.3 25 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35E20 20 2 24.1 39.6 42.4 40 45E23 24 2 28.9 45.6 48.4 50 50

575 5.1 39.5 8 0.66 2 1.8 20

None - - - 13.7 15.5 15 20E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30E20 20 2 19.2 31.5 33.8 35 35E23 24 2 23.1 36.4 38.6 40 40

Page 157: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 157

ZJ078-150 Standard Motor - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 11.2 84 18 2.1 5.2 5.5 20

None - - - 44.6 50.1 50 60E09 6.8 1 18.9 44.6 50.1 50 60E18 13.5 2 37.5 65.9 72.8 70 80E24 18 2 50 81.5 88.4 90 90E36 25.5 2 70.8 107.5 114.4 110 125

230 11.2 84 18 2.1 5.2 5.5 20

None - - - 44.6 50.1 50 60E09 9 1 21.7 46.1 53 50 60E18 18 2 43.3 73.1 80 80 80E24 24 2 57.7 91.1 98 100 100E36 34 2 81.8 121.3 128.1 125 150

460 5.6 44 9 1.26 2.6 2.2 20

None - - - 22.7 24.9 25 30E09 9 1 10.8 23 25.8 25 30E18 18 2 21.7 36.6 39.4 40 40E24 24 2 28.9 45.6 48.4 50 50E36 34 2 40.9 60.6 63.4 70 70

575 3.8 34 6 0.66 2 1.8 20

None - - - 15.9 17.7 20 20E09 9 1 8.7 18.4 20.6 20 25E18 18 2 17.3 29.1 31.4 30 35E24 24 2 23.1 36.4 38.6 40 40E36 34 2 32.7 48.4 50.6 50 60

090(7.5)

208 13.6 83.1 21 3.03 5.2 5.5 20

None - - - 51.9 57.4 60 70E09 6.8 1 18.9 51.9 57.4 60 70E18 13.5 2 37.5 65.9 72.8 70 80E24 18 2 50 81.5 88.4 90 90E36 25.5 2 70.8 107.5 114.4 110 125

230 13.6 83.1 21 3.03 5.2 5.5 20

None - - - 51.9 57.4 60 70E09 9 1 21.7 51.9 57.4 60 70E18 18 2 43.3 73.1 80 80 80E24 24 2 57.7 91.1 98 100 100E36 34 2 81.8 121.3 128.1 125 150

460- 6.1 41 10 1.6 2.6 2.2 20

None - - - 24.5 26.7 30 30E09 9 1 10.8 24.5 26.7 30 30E18 18 2 21.7 36.6 39.4 40 40E24 24 2 28.9 45.6 48.4 50 50E36 34 2 40.9 60.6 63.4 70 70

575 4.2 33 7 1.35 2 1.8 20

None - - - 18.2 20 20 20E09 9 1 8.7 18.4 20.6 20 25E18 18 2 17.3 29.1 31.4 30 35E24 24 2 23.1 36.4 38.6 40 40E36 34 2 32.7 48.4 50.6 50 60

102(8.5)

208 14.5 98 23 3.03 6.8 5.5 20

None - - - 55.5 61 70 70E09 6.8 1 18.9 55.5 61 70 70E18 13.5 2 37.5 67.9 74.8 70 80E24 18 2 50 83.5 90.4 90 100E36 25.5 2 70.8 109.5 116.4 110 125

230 14.5 98 23 3.03 6.8 5.5 20

None - - - 55.5 61 70 70E09 9 1 21.7 55.5 61 70 70E18 18 2 43.3 75.1 82 80 90E24 24 2 57.7 93.1 100 100 100E36 34 2 81.8 123.3 130.1 125 150

460 6.3 55 10 1.6 3.4 2.2 20

None - - - 25.8 28 30 30E09 9 1 10.8 25.8 28 30 30E18 18 2 21.7 37.6 40.4 40 45E24 24 2 28.9 46.6 49.4 50 50E36 34 2 40.9 61.6 64.4 70 70

575 6 41 9 1.35 2.4 1.8 20

None - - - 22.6 24.4 25 30E09 9 1 8.7 22.6 24.4 25 30E18 18 2 17.3 29.6 31.9 30 35E24 24 2 23.1 36.9 39.1 40 40E36 34 2 32.7 48.9 51.1 50 60

Page 158: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

158 Johnson Controls Ducted Systems

120(10)

208 16.0 110.0 24.9 3.0 6.8 5.5 10.0

None - - - 58.9 64.4 70 80E18 13.5 2 37.5 67.8 74.7 70 80E24 18.0 2 50.0 83.5 90.3 90 100E36 25.5 2 70.8 109.5 116.4 110 125E54 40.6 2 112.7 161.9 168.7 175 175

230 16.0 110.0 24.9 3.0 6.8 5.5 10.0

None - - - 58.9 64.4 70 80E18 18.0 2 43.3 75.1 82.0 80 90E24 24.0 2 57.7 93.2 100.0 100 100E36 34.0 2 81.8 123.2 130.1 125 150E54 54.0 2 129.9 150.9 157.8 175 175

460 7.8 52.0 12.1 1.6 3.4 2.2 5.0

None - - - 29.2 31.4 35 35E18 18.0 2 21.7 37.6 40.3 40 45E24 24.0 2 28.9 46.6 49.3 50 50E36 34.0 2 40.9 61.6 64.4 70 70E54 54.0 2 65.0 75.5 78.2 80 90

575 5.7 38.9 8.9 1.4 2.4 1.8 4.0

None - - - 21.9 23.7 25 25E18 18.0 2 17.3 29.7 31.9 30 35E24 24.0 2 23.1 36.9 39.1 40 40E36 34.0 2 32.7 48.9 51.1 50 60E54 54.0 2 52.0 60.0 62.2 70 70

150(12.5)

208 23.1 160.0 36.0 2.1 9.6 5.5 10.0

None - - - 80.0 85.5 100 100E18 13.5 2 37.5 80.0 85.5 100 100E24 18.0 2 50.0 87.0 93.8 100 100E36 25.5 2 70.8 113.0 119.9 125 125E54 40.6 2 112.7 165.4 172.2 175 175

230 23.1 160.0 36.0 2.1 9.6 5.5 10.0

None - - - 80.0 85.5 100 100E18 18.0 2 43.3 80.0 85.5 100 100E24 24.0 2 57.7 96.7 103.5 100 110E36 34.0 2 81.8 126.7 133.6 150 150E54 54.0 2 129.9 154.4 161.3 175 175

460 12.2 87.0 19.0 1.3 4.7 2.2 5.0

None - - - 42.2 44.4 50 50E18 18.0 2 21.7 42.2 44.4 50 50E24 24.0 2 28.9 48.2 51.0 50 60E36 34.0 2 40.9 63.2 66.0 70 70E54 54.0 2 65.0 77.1 79.8 90 90

575 8.7 62.0 13.5 0.7 3.6 1.8 4.0

None - - - 29.8 31.6 35 40E18 18.0 2 17.3 31.2 33.4 35 40E24 24.0 2 23.1 38.4 40.6 40 45E36 34.0 2 32.7 50.4 52.6 60 60E54 54.0 2 52.0 61.5 63.7 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

ZJ078-150 Standard Motor - With Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 159: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 159

ZJ037-061 Hi Static Blower - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

1. Minimum Circuit Ampacity.

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 2.3 1 6.4 28.8 34.3 35 40E06 4.5 1 12.5 34.6 41.5 40 45E08 6.8 1 18.9 42.6 49.5 45 50E15 11.3 2 31.4 58.3 65.1 60 70

230 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 3 1 7.2 28.8 34.9 35 40E06 6 1 14.4 37 43.9 40 45E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80

460 5.8 38 9 1.26 2.6 2.2 20

None - - - 16.2 18.4 20 20E03 3 1 3.6 16.2 18.4 20 20E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35

575 3.8 36.5 6 0.66 2 1.8 20None - - - 11.5 13.3 15 15E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30

049(4)

208 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 34.6 40.1 45 50E06 4.5 1 12.5 34.6 41.5 45 50E08 6.8 1 18.9 42.6 49.5 45 50E15 11.3 2 31.4 58.3 65.1 60 70E20 15 2 41.6 71 77.9 80 80

230 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 34.6 40.1 45 50E06 6 1 14.4 37 43.9 45 50E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80E20 20 2 48.1 79.1 86 80 90

460 6.2 41 10 1.26 2.6 2.2 20

None - - - 16.7 18.9 20 25E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35E20 20 2 24.1 39.6 42.4 40 45

575 4.9 33 8 0.66 2 1.8 20

None - - - 12.8 14.6 15 15E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30E20 20 2 19.2 31.5 33.8 35 35

061(5)

208 15.9 110 25 2.1 6.8 5.5 20

None - - - 40.9 46.4 50 60E06 4.5 1 12.5 40.9 46.4 50 60E08 6.8 1 18.9 44.6 51.5 50 60E15 11.3 2 31.4 60.3 67.1 70 70E20 15 2 41.6 73 79.9 80 80E23 18 2 50 83.5 90.4 90 100

230 15.9 110 25 2.1 6.8 5.5 20

None - - - 40.9 46.4 50 60E06 6 1 14.4 40.9 46.4 50 60E08 9 1 21.7 48.1 55 50 60E15 15 2 36.1 66.1 73 70 80E20 20 2 48.1 81.1 88 90 90E23 24 2 57.7 93.1 100 100 100

460 7.1 52 11 1.26 3.4 2.2 20

None - - - 19.8 22 25 25E06 6 1 7.2 19.8 22.3 25 25E08 9 1 10.8 24 26.8 25 30E15 15 2 18 33 35.8 35 40E20 20 2 24.1 40.6 43.4 45 45E23 24 2 28.9 46.6 49.4 50 50

575 5.1 39.5 8 0.66 2.4 1.8 20

None - - - 14.1 15.9 15 20E08 9 1 8.7 18.9 21.1 20 25E15 15 2 14.4 26 28.3 30 30E20 20 2 19.2 32 34.3 35 35E23 24 2 23.1 36.9 39.1 40 40

Page 160: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

160 Johnson Controls Ducted Systems

ZJ078-150 Hi Static Motor - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 11.2 84 18 2.1 6.8 5.5 20

None - - - 46.2 51.7 50 60E09 6.8 1 18.9 46.2 51.7 50 60E18 13.5 2 37.5 67.9 74.8 70 80E24 18 2 50 83.5 90.4 90 100E36 25.5 2 70.8 109.5 116.4 110 125

230 11.2 84 18 2.1 6.8 5.5 20

None - - - 46.2 51.7 50 60E09 9 1 21.7 48.1 55 50 60E18 18 2 43.3 75.1 82 80 90E24 24 2 57.7 93.1 100 100 100E36 34 2 81.8 123.3 130.1 125 150

460 5.6 44 9 1.26 3.4 2.2 20

None - - - 23.5 25.7 25 30E09 9 1 10.8 24 26.8 25 30E18 18 2 21.7 37.6 40.4 40 45E24 24 2 28.9 46.6 49.4 50 50E36 34 2 40.9 61.6 64.4 70 70

575 3.8 34 6 0.66 2.4 1.8 20

None - - - 16.3 18.1 20 20E09 9 1 8.7 18.9 21.1 20 25E18 18 2 17.3 29.6 31.9 30 35E24 24 2 23.1 36.9 39.1 40 40E36 34 2 32.7 48.9 51.1 50 60

090(7.5)

208 13.6 83.1 21 3.03 9.6 5.5 20

None - - - 56.3 61.8 60 70E09 6.8 1 18.9 56.3 61.8 60 70E18 13.5 2 37.5 71.4 78.3 80 80E24 18 2 50 87 93.9 90 100E36 25.5 2 70.8 113 119.9 125 125

230 13.6 83.1 21 3.03 9.6 5.5 20

None - - - 56.3 61.8 60 70E09 9 1 21.7 56.3 61.8 60 70E18 18 2 43.3 78.6 85.5 80 90E24 24 2 57.7 96.6 103.5 100 110E36 34 2 81.8 126.8 133.6 150 150

460 6.1 41 10 1.6 4.7 2.2 20

None - - - 26.6 28.8 30 30E09 9 1 10.8 26.6 28.8 30 30E18 18 2 21.7 39.3 42 40 45E24 24 2 28.9 48.3 51 50 60E36 34 2 40.9 63.3 66 70 70

575 4.2 33 7 1.35 3.6 1.8 20

None - - - 19.8 21.6 20 25E09 9 1 8.7 20.4 22.6 25 25E18 18 2 17.3 31.1 33.4 35 35E24 24 2 23.1 38.4 40.6 40 45E36 34 2 32.7 50.4 52.6 60 60

102(8.5)

208 14.5 98 23 3.03 9.6 5.5 20

None - - - 58.3 63.8 70 70E09 6.8 1 18.9 58.3 63.8 70 70E18 13.5 2 37.5 71.4 78.3 80 80E24 18 2 50 87 93.9 90 100E36 25.5 2 70.8 113 119.9 125 125

230 14.5 98 23 3.03 9.6 5.5 20

None - - - 58.3 63.8 70 70E09 9 1 21.7 58.3 63.8 70 70E18 18 2 43.3 78.6 85.5 80 90E24 24 2 57.7 96.6 103.5 100 110E36 34 2 81.8 126.8 133.6 150 150

460 6.3 55 10 1.6 4.7 2.2 20

None - - - 27.1 29.3 30 35E09 9 1 10.8 27.1 29.3 30 35E18 18 2 21.7 39.3 42 40 45E24 24 2 28.9 48.3 51 50 60E36 34 2 40.9 63.3 66 70 70

575 6 41 9 1.35 3.6 1.8 20

None - - - 23.8 25.6 25 30E09 9 1 8.7 23.8 25.6 25 30E18 18 2 17.3 31.1 33.4 35 35E24 24 2 23.1 38.4 40.6 40 45E36 34 2 32.7 50.4 52.6 60 60

Page 161: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 161

120(10)

208 16.0 110.0 24.9 3.0 9.6 5.5 10.0

None - - - 61.7 67.2 70 80E18 13.5 2 37.5 71.3 78.2 80 80E24 18.0 2 50.0 87.0 93.8 90 100E36 25.5 2 70.8 113.0 119.9 125 125E54 40.6 2 112.7 165.4 172.2 175 175

230 16.0 110.0 24.9 3.0 9.6 5.5 10.0

None - - - 61.7 67.2 70 80E18 18.0 2 43.3 78.6 85.5 80 90E24 24.0 2 57.7 96.7 103.5 100 110E36 34.0 2 81.8 126.7 133.6 150 150E54 54.0 2 129.9 154.4 161.3 175 175

460 7.8 52.0 12.1 1.6 4.7 2.2 5.0

None - - - 30.5 32.7 35 40E18 18.0 2 21.7 39.2 41.9 40 45E24 24.0 2 28.9 48.2 51.0 50 60E36 34.0 2 40.9 63.2 66.0 70 70E54 54.0 2 65.0 77.1 79.8 90 90

575 5.7 38.9 8.9 1.4 3.6 1.8 4.0

None - - - 23.1 24.9 25 30E18 18.0 2 17.3 31.2 33.4 35 35E24 24.0 2 23.1 38.4 40.6 40 45E36 34.0 2 32.7 50.4 52.6 60 60E54 54.0 2 52.0 61.5 63.7 70 70

150(12.5)

208 23.1 160.0 36.0 2.1 14.0 5.5 10.0

None - - - 84.4 89.9 100 110E18 13.5 2 37.5 84.4 89.9 100 110E24 18.0 2 50.0 92.5 99.3 100 110E36 25.5 2 70.8 118.5 125.4 125 150E54 40.6 2 112.7 170.9 177.7 175 200

230 23.1 160.0 36.0 2.1 14.0 5.5 10.0

None - - - 84.4 89.9 100 110E18 18.0 2 43.3 84.4 91.0 100 110E24 24.0 2 57.7 102.2 109.0 110 110E36 34.0 2 81.8 132.2 139.1 150 150E54 54.0 2 129.9 159.9 166.8 175 175

460 12.2 87.0 19.0 1.3 6.6 2.2 5.0

None - - - 44.1 46.3 50 50E18 18.0 2 21.7 44.1 46.3 50 50E24 24.0 2 28.9 50.6 53.3 60 60E36 34.0 2 40.9 65.6 68.4 70 70E54 54.0 2 65.0 79.5 82.2 90 90

575 8.7 62.0 13.5 0.7 5.2 1.8 4.0

None - - - 31.4 33.2 40 40E18 18.0 2 17.3 33.2 35.4 40 40E24 24.0 2 23.1 40.4 42.6 45 45E36 34.0 2 32.7 52.4 54.6 60 60E54 54.0 2 52.0 63.5 65.7 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

ZJ078-150 Hi Static Motor - With Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 162: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

162 Johnson Controls Ducted Systems

ZR037-061 Standard Indoor Blower - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 2.3 1 6.4 18.6 24.1 25 30E06 4.5 1 12.5 22.1 29 25 30E08 6.8 1 18.9 30.1 37 35 40E15 11.3 2 31.4 45.8 52.6 50 60

230 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 3 1 7.2 18.6 24.1 25 30E06 6 1 14.4 24.5 31.4 25 35E08 9 1 21.7 33.6 40.5 35 45E15 15 2 36.1 51.6 58.5 60 60

460 5.8 38 9 1.26 2.6 2.2

None - - - 11.2 13.4 15 15E03 3 1 3.6 11.2 13.4 15 15E06 6 1 7.2 12.3 15 15 15E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30

575 3.8 36.5 6 0.66 2 1.8None - - - 7.5 9.3 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25

049(4)

208 13.8 83.1 22 2.1 5.2 5.5

None - - - 26.7 32.2 35 45E06 4.5 1 12.5 26.7 32.2 35 45E08 6.8 1 18.9 30.1 37 40 45E15 11.3 2 31.4 45.8 52.6 50 60E20 15 2 41.6 58.5 65.4 60 70

230 13.8 83.1 22 2.1 5.2 5.5

None - - - 26.7 32.2 35 45E06 6 1 14.4 26.7 32.2 35 45E08 9 1 21.7 33.6 40.5 40 45E15 15 2 36.1 51.6 58.5 60 60E20 20 2 48.1 66.6 73.5 70 80

460 6.2 41 10 1.26 2.6 2.2

None - - - 12.9 15.1 15 20E06 6 1 7.2 12.9 15.1 15 20E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30E20 20 2 24.1 33.4 36.1 35 40

575 4.9 33 8 0.66 2 1.8

None - - - 9.4 11.2 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25E20 20 2 19.2 26.5 28.8 30 30

061(5)

208 15.9 110 25 2.1 5.2 5.5

None - - - 29.3 34.8 40 45E06 4.5 1 12.5 29.3 34.8 40 45E08 6.8 1 18.9 30.1 37 40 50E15 11.3 2 31.4 45.8 52.6 50 60E20 15 2 41.6 58.5 65.4 60 70E23 18 2 50 69 75.9 70 80

230 15.9 110 25 2.1 5.2 5.5

None - - - 29.3 34.8 40 45E06 6 1 14.4 29.3 34.8 40 45E08 9 1 21.7 33.6 40.5 45 50E15 15 2 36.1 51.6 58.5 60 60E20 20 2 48.1 66.6 73.5 70 80E23 24 2 57.7 78.6 85.5 80 90

460 7.1 52 11 1.26 2.6 2.2

None - - - 14 16.2 20 20E06 6 1 7.2 14 16.2 20 20E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30E20 20 2 24.1 33.4 36.1 35 40E23 24 2 28.9 39.4 42.1 40 45

575 5.1 39.5 8 0.66 2 1.8

None - - - 9.7 11.5 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25E20 20 2 19.2 26.5 28.8 30 30E23 24 2 23.1 31.4 33.6 35 35

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

Page 163: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 163

ZR078-150 Standard Motor - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 13.5 88 21 2.1 5.2 5.5

None - - - 39.8 45.3 50 50E09 6.8 1 18.9 39.8 45.3 50 50E18 13.5 2 37.5 53.4 60.3 60 70E24 18 2 50 69 75.9 70 80E36 25.5 2 70.8 95 101.9 100 110

230 13.5 88 21 2.1 5.2 5.5

None - - - 39.8 45.3 50 50E09 9 1 21.7 39.8 45.3 50 50E18 18 2 43.3 60.6 67.5 70 70E24 24 2 57.7 78.6 85.5 80 90E36 34 2 81.8 108.8 115.6 110 125

460 6 44 9 1.26 2.6 2.2

None - - - 18.6 20.8 20 25E09 9 1 10.8 18.6 20.8 20 25E18 18 2 21.7 30.4 33.1 35 35E24 24 2 28.9 39.4 42.1 40 45E36 34 2 40.9 54.4 57.1 60 60

575 4.9 34 8 0.66 2 1.8

None - - - 14.3 16.1 15 20E09 9 1 8.7 14.3 16.1 15 20E18 18 2 17.3 24.1 26.4 25 30E24 24 2 23.1 31.4 33.6 35 35E36 34 2 32.7 43.4 45.6 45 50

090(7.5)

208 13.1 83.1 21 2.1 5.2 5.5

None - - - 38.9 44.4 50 50E09 6.8 1 18.9 38.9 44.4 50 50E18 13.5 2 37.5 53.4 60.3 60 70E24 18 2 50 69 75.9 70 80E36 25.5 2 70.8 95 101.9 100 110

230 13.1 83.1 21 2.1 5.2 5.5

None - - - 38.9 44.4 50 50E09 9 1 21.7 38.9 44.4 50 50E18 18 2 43.3 60.6 67.5 70 70E24 24 2 57.7 78.6 85.5 80 90E36 34 2 81.8 108.8 115.6 110 125

460 6.1 41 10 1.26 2.6 2.2

None - - - 18.8 21 20 25E09 9 1 10.8 18.8 21 20 25E18 18 2 21.7 30.4 33.1 35 35E24 24 2 28.9 39.4 42.1 40 45E36 34 2 40.9 54.4 57.1 60 60

575 4.4 33 7 0.66 2 1.8

None - - - 13.2 15 15 15E09 9 1 8.7 13.4 15.6 15 20E18 18 2 17.3 24.1 26.4 25 30E24 24 2 23.1 31.4 33.6 35 35E36 34 2 32.7 43.4 45.6 45 50

102(8.5)

208 14.5 98 23 2.1 6.8 5.5

None - - - 43.6 49.1 50 60E09 6.8 1 18.9 43.6 49.1 50 60E18 13.5 2 37.5 55.4 62.3 60 70E24 18 2 50 71 77.9 80 80E36 25.5 2 70.8 97 103.9 100 110

230 14.5 98 23 2.1 6.8 5.5

None - - - 43.6 49.1 50 60E09 9 1 21.7 43.6 49.1 50 60E18 18 2 43.3 62.6 69.5 70 70E24 24 2 57.7 80.6 87.5 90 90E36 34 2 81.8 110.8 117.6 125 125

460 6.3 55 10 1.26 3.4 2.2

None - - - 20.1 22.3 25 25E09 9 1 10.8 20.1 22.3 25 25E18 18 2 21.7 31.4 34.1 35 35E24 24 2 28.9 40.4 43.1 45 45E36 34 2 40.9 55.4 58.1 60 60

575 6 41 9 0.66 2.4 1.8

None - - - 17.2 19 20 25E09 9 1 8.7 17.2 19 20 25E18 18 2 17.3 24.6 26.9 25 30E24 24 2 23.1 31.9 34.1 35 35E36 34 2 32.7 43.9 46.1 45 50

Page 164: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

164 Johnson Controls Ducted Systems

120(10)

208 16 110 25 3.03 6.8 5.5

None - - - 48.9 54.4 60 70E18 13.5 2 37.5 55.4 62.3 60 70E24 18 2 50 71 77.9 80 80E36 25.5 2 70.8 97 103.9 100 110E54 40.6 2 112.7 149.4 156.3 150 175

230 16 110 25 3.03 6.8 5.5

None - - - 48.9 54.4 60 70E18 18 2 43.3 62.6 69.5 70 70E24 24 2 57.7 80.6 87.5 90 90E36 34 2 81.8 110.8 117.6 125 125E54 54 2 129.9 138.4 145.3 150 175

460 7.8 52 12 1.6 3.4 2.2

None - - - 24.2 26.4 30 30E18 18 2 21.7 31.4 34.1 35 35E24 24 2 28.9 40.4 43.1 45 45E36 34 2 40.9 55.4 58.1 60 60E54 54 2 65 69.3 72 80 80

575 5.7 38.9 9 1.35 2.4 1.8

None - - - 17.9 19.7 20 25E18 18 2 17.3 24.6 26.9 25 30E24 24 2 23.1 31.9 34.1 35 35E36 34 2 32.7 43.9 46.1 45 50E54 54 2 52 55 57.3 60 60

150(12.5)

208 22.4 149 35 2.1 9.6 5.5

None - - - 68.4 73.9 90 90E18 13.5 2 37.5 68.4 73.9 90 90E24 18 2 50 74.5 81.4 90 90E36 25.5 2 70.8 100.5 107.4 110 110E54 40.6 2 112.7 152.9 159.8 175 175

230 22.4 149 35 2.1 9.6 5.5

None - - - 68.4 73.9 90 90E18 18 2 43.3 68.4 73.9 90 90E24 24 2 57.7 84.1 91 90 100E36 34 2 81.8 114.3 121.1 125 125E54 54 2 129.9 141.9 148.8 175 175

460 10.6 75 17 1.26 4.7 2.2

None - - - 33.6 35.8 40 45E18 18 2 21.7 33.6 35.8 40 45E24 24 2 28.9 42 44.8 45 45E36 34 2 40.9 57 59.8 60 60E54 54 2 65 70.9 73.6 80 80

575 7.7 54 12 0.66 3.6 1.8

None - - - 23.5 25.3 30 30E18 18 2 17.3 26.1 28.4 30 30E24 24 2 23.1 33.4 35.6 35 40E36 34 2 32.7 45.4 47.6 50 50E54 54 2 52 56.5 58.8 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

ZR078-150 Standard Motor - Without Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 165: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 165

ZR037-061 Hi Static Indoor Blower - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 2.3 1 6.4 18.6 24.1 25 30E06 4.5 1 12.5 22.1 29 25 30E08 6.8 1 18.9 30.1 37 35 40E15 11.3 2 31.4 45.8 52.6 50 60

230 9 71 14 2.1 5.2 5.5

None - - - 18.6 24.1 25 30E03 3 1 7.2 18.6 24.1 25 30E06 6 1 14.4 24.5 31.4 25 35E08 9 1 21.7 33.6 40.5 35 45E15 15 2 36.1 51.6 58.5 60 60

460 5.8 38 9 1.26 2.6 2.2

None - - - 11.2 13.4 15 15E03 3 1 3.6 11.2 13.4 15 15E06 6 1 7.2 12.3 15 15 15E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30

575 3.8 36.5 6 0.66 2 1.8None - - - 7.5 9.3 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25

049(4)

208 13.8 83.1 22 2.1 5.2 5.5

None - - - 26.7 32.2 35 45E06 4.5 1 12.5 26.7 32.2 35 45E08 6.8 1 18.9 30.1 37 40 45E15 11.3 2 31.4 45.8 52.6 50 60E20 15 2 41.6 58.5 65.4 60 70

230 13.8 83.1 22 2.1 5.2 5.5

None - - - 26.7 32.2 35 45E06 6 1 14.4 26.7 32.2 35 45E08 9 1 21.7 33.6 40.5 40 45E15 15 2 36.1 51.6 58.5 60 60E20 20 2 48.1 66.6 73.5 70 80

460 6.2 41 10 1.26 2.6 2.2

None - - - 12.9 15.1 15 20E06 6 1 7.2 12.9 15.1 15 20E08 9 1 10.8 16.8 19.5 20 20E15 15 2 18 25.8 28.5 30 30E20 20 2 24.1 33.4 36.1 35 40

575 4.9 33 8 0.66 2 1.8

None - - - 9.4 11.2 15 15E08 9 1 8.7 13.4 15.6 15 20E15 15 2 14.4 20.5 22.8 25 25E20 20 2 19.2 26.5 28.8 30 30

061(5)

208 15.9 110 25 2.1 6.8 5.5

None - - - 30.9 36.4 40 50E06 4.5 1 12.5 30.9 36.4 40 50E08 6.8 1 18.9 32.1 39 45 50E15 11.3 2 31.4 47.8 54.6 50 60E20 15 2 41.6 60.5 67.4 70 70E23 18 2 50 71 77.9 80 80

230 15.9 110 25 2.1 6.8 5.5

None - - - 30.9 36.4 40 50E06 6 1 14.4 30.9 36.4 40 50E08 9 1 21.7 35.6 42.5 45 50E15 15 2 36.1 53.6 60.5 60 70E20 20 2 48.1 68.6 75.5 70 80E23 24 2 57.7 80.6 87.5 90 90

460 7.1 52 11 1.26 3.4 2.2

None - - - 14.8 17 20 20E06 6 1 7.2 14.8 17 20 20E08 9 1 10.8 17.8 20.5 20 25E15 15 2 18 26.8 29.5 30 30E20 20 2 24.1 34.4 37.1 35 40E23 24 2 28.9 40.4 43.1 45 45

575 5.1 39.5 8 0.66 2.4 1.8

None - - - 10.1 11.9 15 15E08 9 1 8.7 13.9 16.1 15 20E15 15 2 14.4 21 23.3 25 25E20 20 2 19.2 27 29.3 30 30E23 24 2 23.1 31.9 34.1 35 35

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

Page 166: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

166 Johnson Controls Ducted Systems

ZR078-150 Hi Static Motor - Without Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 13.5 88 21 2.1 6.8 5.5

None - - - 41.4 46.9 50 60E09 6.8 1 18.9 41.4 46.9 50 60E18 13.5 2 37.5 55.4 62.3 60 70E24 18 2 50 71 77.9 80 80E36 25.5 2 70.8 97 103.9 100 110

230 13.5 88 21 2.1 6.8 5.5

None - - - 41.4 46.9 50 60E09 9 1 21.7 41.4 46.9 50 60E18 18 2 43.3 62.6 69.5 70 70E24 24 2 57.7 80.6 87.5 90 90E36 34 2 81.8 110.8 117.6 125 125

460 6 44 9 1.26 3.4 2.2

None - - - 19.4 21.6 25 25E09 9 1 10.8 19.4 21.6 25 25E18 18 2 21.7 31.4 34.1 35 35E24 24 2 28.9 40.4 43.1 45 45E36 34 2 40.9 55.4 58.1 60 60

575 4.9 34 8 0.66 2.4 1.8

None - - - 14.7 16.5 15 20E09 9 1 8.7 14.7 16.5 15 20E18 18 2 17.3 24.6 26.9 25 30E24 24 2 23.1 31.9 34.1 35 35E36 34 2 32.7 43.9 46.1 45 50

090(7.5)

208 13.1 83.1 21 2.1 9.6 5.5

None - - - 43.3 48.8 50 60E09 6.8 1 18.9 43.3 48.8 50 60E18 13.5 2 37.5 58.9 65.8 60 70E24 18 2 50 74.5 81.4 80 90E36 25.5 2 70.8 100.5 107.4 110 110

230 13.1 83.1 21 2.1 9.6 5.5

None - - - 43.3 48.8 50 60E09 9 1 21.7 43.3 48.8 50 60E18 18 2 43.3 66.1 73 70 80E24 24 2 57.7 84.1 91 90 100E36 34 2 81.8 114.3 121.1 125 125

460 6.1 41 10 1.26 4.7 2.2

None - - - 20.9 23.1 25 25E09 9 1 10.8 20.9 23.1 25 25E18 18 2 21.7 33 35.8 35 40E24 24 2 28.9 42 44.8 45 45E36 34 2 40.9 57 59.8 60 60

575 4.4 33 7 0.66 3.6 1.8

None - - - 14.8 16.6 15 20E09 9 1 8.7 15.4 17.6 20 20E18 18 2 17.3 26.1 28.4 30 30E24 24 2 23.1 33.4 35.6 35 40E36 34 2 32.7 45.4 47.6 50 50

102(8.5)

208 14.5 98 23 2.1 9.6 5.5

None - - - 46.4 51.9 60 60E09 6.8 1 18.9 46.4 51.9 60 60E18 13.5 2 37.5 58.9 65.8 60 70E24 18 2 50 74.5 81.4 80 90E36 25.5 2 70.8 100.5 107.4 110 110

230 14.5 98 23 2.1 9.6 5.5

None - - - 46.4 51.9 60 60E09 9 1 21.7 46.4 51.9 60 60E18 18 2 43.3 66.1 73 70 80E24 24 2 57.7 84.1 91 90 100E36 34 2 81.8 114.3 121.1 125 125

460 6.3 55 10 1.26 4.7 2.2

None - - - 21.4 23.6 25 25E09 9 1 10.8 21.4 23.6 25 25E18 18 2 21.7 33 35.8 35 40E24 24 2 28.9 42 44.8 45 45E36 34 2 40.9 57 59.8 60 60

575 6 41 9 0.66 3.6 1.8

None - - - 18.4 20.2 20 25E09 9 1 8.7 18.4 20.2 20 25E18 18 2 17.3 26.1 28.4 30 30E24 24 2 23.1 33.4 35.6 35 40E36 34 2 32.7 45.4 47.6 50 50

Page 167: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 167

120(10)

208 16 110 25 3.03 9.6 5.5

None - - - 51.7 57.2 60 70E18 13.5 2 37.5 58.9 65.8 60 70E24 18 2 50 74.5 81.4 80 90E36 25.5 2 70.8 100.5 107.4 110 110E54 40.6 2 112.7 152.9 159.8 175 175

230 16 110 25 3.03 9.6 5.5

None - - - 51.7 57.2 60 70E18 18 2 43.3 66.1 73 70 80E24 24 2 57.7 84.1 91 90 100E36 34 2 81.8 114.3 121.1 125 125E54 54 2 129.9 141.9 148.8 175 175

460 7.8 52 12 1.6 4.7 2.2

None - - - 25.5 27.7 30 35E18 18 2 21.7 33 35.8 35 40E24 24 2 28.9 42 44.8 45 45E36 34 2 40.9 57 59.8 60 60E54 54 2 65 70.9 73.6 80 80

575 5.7 38.9 9 1.35 3.6 1.8

None - - - 19.1 20.9 20 25E18 18 2 17.3 26.1 28.4 30 30E24 24 2 23.1 33.4 35.6 35 40E36 34 2 32.7 45.4 47.6 50 50E54 54 2 52 56.5 58.8 70 70

150(12.5)

208 22.4 149 35 2.1 14 5.5

None - - - 72.8 78.3 90 100E18 13.5 2 37.5 72.8 78.3 90 100E24 18 2 50 80 86.9 90 100E36 25.5 2 70.8 106 112.9 110 125E54 40.6 2 112.7 158.4 165.3 175 175

230 22.4 149 35 2.1 14 5.5

None - - - 72.8 78.3 90 100E18 18 2 43.3 72.8 78.5 90 100E24 24 2 57.7 89.6 96.5 90 100E36 34 2 81.8 119.8 126.6 125 150E54 54 2 129.9 147.4 154.3 175 175

460 10.6 75 17 1.26 6.6 2.2

None - - - 35.5 37.7 45 45E18 18 2 21.7 35.5 38.1 45 45E24 24 2 28.9 44.4 47.1 45 50E36 34 2 40.9 59.4 62.1 60 70E54 54 2 65 73.3 76 80 90

575 7.7 54 12 0.66 5.2 1.8

None - - - 25.1 26.9 30 30E18 18 2 17.3 28.1 30.4 30 35E24 24 2 23.1 35.4 37.6 40 40E36 34 2 32.7 47.4 49.6 50 50E54 54 2 52 58.5 60.8 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

ZR078-150 Hi Static Motor - Without Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 168: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

168 Johnson Controls Ducted Systems

ZR037-061 Standard Indoor Blower - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 2.3 1 6.4 28.8 34.3 35 40E06 4.5 1 12.5 34.6 41.5 40 45E08 6.8 1 18.9 42.6 49.5 45 50E15 11.3 2 31.4 58.3 65.1 60 70

230 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 3 1 7.2 28.8 34.9 35 40E06 6 1 14.4 37 43.9 40 45E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80

460 5.8 38 9 1.26 2.6 2.2 20

None - - - 16.2 18.4 20 20E03 3 1 3.6 16.2 18.4 20 20E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35

575 3.8 36.5 6 0.66 2 1.8 20None - - - 11.5 13.3 15 15E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30

049(4)

208 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 36.7 42.2 50 50E06 4.5 1 12.5 36.7 42.2 50 50E08 6.8 1 18.9 42.6 49.5 50 50E15 11.3 2 31.4 58.3 65.1 60 70E20 15 2 41.6 71 77.9 80 80

230 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 36.7 42.2 50 50E06 6 1 14.4 37 43.9 50 50E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80E20 20 2 48.1 79.1 86 80 90

460 6.2 41 10 1.26 2.6 2.2 20

None - - - 17.9 20.1 20 25E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35E20 20 2 24.1 39.6 42.4 40 45

575 4.9 33 8 0.66 2 1.8 20

None - - - 13.4 15.2 15 20E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30E20 20 2 19.2 31.5 33.8 35 35

061(5)

208 15.9 110 25 2.1 5.2 5.5 20

None - - - 39.3 44.8 50 60E06 4.5 1 12.5 39.3 44.8 50 60E08 6.8 1 18.9 42.6 49.5 50 60E15 11.3 2 31.4 58.3 65.1 60 70E20 15 2 41.6 71 77.9 80 80E23 18 2 50 81.5 88.4 90 90

230 15.9 110 25 2.1 5.2 5.5 20

None - - - 39.3 44.8 50 60E06 6 1 14.4 39.3 44.8 50 60E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80E20 20 2 48.1 79.1 86 80 90E23 24 2 57.7 91.1 98 100 100

460 7.1 52 11 1.26 2.6 2.2 20

None - - - 19 21.2 25 25E06 6 1 7.2 19 21.3 25 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35E20 20 2 24.1 39.6 42.4 40 45E23 24 2 28.9 45.6 48.4 50 50

575 5.1 39.5 8 0.66 2 1.8 20

None - - - 13.7 15.5 15 20E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30E20 20 2 19.2 31.5 33.8 35 35E23 24 2 23.1 36.4 38.6 40 40

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

Page 169: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 169

ZR078-150 Standard Motor - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 13.5 88 21 2.1 5.2 5.5 20

None - - - 49.8 55.3 60 60E09 6.8 1 18.9 49.8 55.3 60 60E18 13.5 2 37.5 65.9 72.8 70 80E24 18 2 50 81.5 88.4 90 90E36 25.5 2 70.8 107.5 114.4 110 125

230 13.5 88 21 2.1 5.2 5.5 20

None - - - 49.8 55.3 60 60E09 9 1 21.7 49.8 55.3 60 60E18 18 2 43.3 73.1 80 80 80E24 24 2 57.7 91.1 98 100 100E36 34 2 81.8 121.3 128.1 125 150

460 6 44 9 1.26 2.6 2.2 20

None - - - 23.6 25.8 25 30E09 9 1 10.8 23.6 25.8 25 30E18 18 2 21.7 36.6 39.4 40 40E24 24 2 28.9 45.6 48.4 50 50E36 34 2 40.9 60.6 63.4 70 70

575 4.9 34 8 0.66 2 1.8 20

None - - - 18.3 20.1 20 25E09 9 1 8.7 18.4 20.6 20 25E18 18 2 17.3 29.1 31.4 30 35E24 24 2 23.1 36.4 38.6 40 40E36 34 2 32.7 48.4 50.6 50 60

090(7.5)

208 13.1 83.1 21 2.1 5.2 5.5 20

None - - - 48.9 54.4 60 60E09 6.8 1 18.9 48.9 54.4 60 60E18 13.5 2 37.5 65.9 72.8 70 80E24 18 2 50 81.5 88.4 90 90E36 25.5 2 70.8 107.5 114.4 110 125

230 13.1 83.1 21 2.1 5.2 5.5 20

None - - - 48.9 54.4 60 60E09 9 1 21.7 48.9 54.4 60 60E18 18 2 43.3 73.1 80 80 80E24 24 2 57.7 91.1 98 100 100E36 34 2 81.8 121.3 128.1 125 150

460 6.1 41 10 1.26 2.6 2.2 20

None - - - 23.8 26 25 30E09 9 1 10.8 23.8 26 25 30E18 18 2 21.7 36.6 39.4 40 40E24 24 2 28.9 45.6 48.4 50 50E36 34 2 40.9 60.6 63.4 70 70

575 4.4 33 7 0.66 2 1.8 20

None - - - 17.2 19 20 20E09 9 1 8.7 18.4 20.6 20 25E18 18 2 17.3 29.1 31.4 30 35E24 24 2 23.1 36.4 38.6 40 40E36 34 2 32.7 48.4 50.6 50 60

102(8.5)

208 14.5 98 23 2.1 6.8 5.5 20

None - - - 53.6 59.1 60 70E09 6.8 1 18.9 53.6 59.1 60 70E18 13.5 2 37.5 67.9 74.8 70 80E24 18 2 50 83.5 90.4 90 100E36 25.5 2 70.8 109.5 116.4 110 125

230 14.5 98 23 2.1 6.8 5.5 20

None - - - 53.6 59.1 60 70E09 9 1 21.7 53.6 59.1 60 70E18 18 2 43.3 75.1 82 80 90E24 24 2 57.7 93.1 100 100 100E36 34 2 81.8 123.3 130.1 125 150

460 6.3 55 10 1.26 3.4 2.2 20

None - - - 25.1 27.3 30 30E09 9 1 10.8 25.1 27.3 30 30E18 18 2 21.7 37.6 40.4 40 45E24 24 2 28.9 46.6 49.4 50 50E36 34 2 40.9 61.6 64.4 70 70

575 6 41 9 0.66 2.4 1.8 20

None - - - 21.2 23 25 25E09 9 1 8.7 21.2 23 25 25E18 18 2 17.3 29.6 31.9 30 35E24 24 2 23.1 36.9 39.1 40 40E36 34 2 32.7 48.9 51.1 50 60

Page 170: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

170 Johnson Controls Ducted Systems

120(10)

208 16 110 25 3.03 6.8 5.5 20

None - - - 58.9 64.4 70 80E18 13.5 2 37.5 67.9 74.8 70 80E24 18 2 50 83.5 90.4 90 100E36 25.5 2 70.8 109.5 116.4 110 125E54 40.6 2 112.7 161.9 168.8 175 175

230 16 110 25 3.03 6.8 5.5 20

None - - - 58.9 64.4 70 80E18 18 2 43.3 75.1 82 80 90E24 24 2 57.7 93.1 100 100 100E36 34 2 81.8 123.3 130.1 125 150E54 54 2 129.9 150.9 157.8 175 175

460 7.8 52 12 1.6 3.4 2.2 20

None - - - 29.2 31.4 35 35E18 18 2 21.7 37.6 40.4 40 45E24 24 2 28.9 46.6 49.4 50 50E36 34 2 40.9 61.6 64.4 70 70E54 54 2 65 75.5 78.3 80 90

575 5.7 38.9 9 1.35 2.4 1.8 20

None - - - 21.9 23.7 25 25E18 18 2 17.3 29.6 31.9 30 35E24 24 2 23.1 36.9 39.1 40 40E36 34 2 32.7 48.9 51.1 50 60E54 54 2 52 60 62.3 70 70

150(12.5)

208 22.4 149 35 2.1 9.6 5.5 20

None - - - 78.4 83.9 100 100E18 13.5 2 37.5 78.4 83.9 100 100E24 18 2 50 87 93.9 100 100E36 25.5 2 70.8 113 119.9 125 125E54 40.6 2 112.7 165.4 172.3 175 175

230 22.4 149 35 2.1 9.6 5.5 20

None - - - 78.4 83.9 100 100E18 18 2 43.3 78.6 85.5 100 100E24 24 2 57.7 96.6 103.5 100 110E36 34 2 81.8 126.8 133.6 150 150E54 54 2 129.9 154.4 161.3 175 175

460 10.6 75 17 1.26 4.7 2.2 20

None - - - 38.6 40.8 45 50E18 18 2 21.7 39.3 42 45 50E24 24 2 28.9 48.3 51 50 60E36 34 2 40.9 63.3 66 70 70E54 54 2 65 77.1 79.9 90 90

575 7.7 54 12 0.66 3.6 1.8 20

None - - - 27.5 29.3 35 35E18 18 2 17.3 31.1 33.4 35 35E24 24 2 23.1 38.4 40.6 40 45E36 34 2 32.7 50.4 52.6 60 60E54 54 2 52 61.5 63.8 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

ZR078-150 Standard Motor - With Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 171: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 171

ZR037-061 Hi Static Indoor Blower - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3 Size w/

Pwr Exh(Amps)

RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

037(3)

208 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 2.3 1 6.4 28.8 34.3 35 40E06 4.5 1 12.5 34.6 41.5 40 45E08 6.8 1 18.9 42.6 49.5 45 50E15 11.3 2 31.4 58.3 65.1 60 70

230 9 71 14 2.1 5.2 5.5 20

None - - - 28.8 34.3 35 40E03 3 1 7.2 28.8 34.9 35 40E06 6 1 14.4 37 43.9 40 45E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80

460 5.8 38 9 1.26 2.6 2.2 20

None - - - 16.2 18.4 20 20E03 3 1 3.6 16.2 18.4 20 20E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35

575 3.8 36.5 6 0.66 2 1.8 20None - - - 11.5 13.3 15 15E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30

049(4)

208 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 36.7 42.2 50 50E06 4.5 1 12.5 36.7 42.2 50 50E08 6.8 1 18.9 42.6 49.5 50 50E15 11.3 2 31.4 58.3 65.1 60 70E20 15 2 41.6 71 77.9 80 80

230 13.8 83.1 22 2.1 5.2 5.5 20

None - - - 36.7 42.2 50 50E06 6 1 14.4 37 43.9 50 50E08 9 1 21.7 46.1 53 50 60E15 15 2 36.1 64.1 71 70 80E20 20 2 48.1 79.1 86 80 90

460 6.2 41 10 1.26 2.6 2.2 20

None - - - 17.9 20.1 20 25E06 6 1 7.2 18.5 21.3 20 25E08 9 1 10.8 23 25.8 25 30E15 15 2 18 32 34.8 35 35E20 20 2 24.1 39.6 42.4 40 45

575 4.9 33 8 0.66 2 1.8 20

None - - - 13.4 15.2 15 20E08 9 1 8.7 18.4 20.6 20 25E15 15 2 14.4 25.5 27.8 30 30E20 20 2 19.2 31.5 33.8 35 35

061(5)

208 15.9 110 25 2.1 6.8 5.5 20

None - - - 40.9 46.4 50 60E06 4.5 1 12.5 40.9 46.4 50 60E08 6.8 1 18.9 44.6 51.5 50 60E15 11.3 2 31.4 60.3 67.1 70 70E20 15 2 41.6 73 79.9 80 80E23 18 2 50 83.5 90.4 90 100

230 15.9 110 25 2.1 6.8 5.5 20

None - - - 40.9 46.4 50 60E06 6 1 14.4 40.9 46.4 50 60E08 9 1 21.7 48.1 55 50 60E15 15 2 36.1 66.1 73 70 80E20 20 2 48.1 81.1 88 90 90E23 24 2 57.7 93.1 100 100 100

460 7.1 52 11 1.26 3.4 2.2 20

None - - - 19.8 22 25 25E06 6 1 7.2 19.8 22.3 25 25E08 9 1 10.8 24 26.8 25 30E15 15 2 18 33 35.8 35 40E20 20 2 24.1 40.6 43.4 45 45E23 24 2 28.9 46.6 49.4 50 50

575 5.1 39.5 8 0.66 2.4 1.8 20

None - - - 14.1 15.9 15 20E08 9 1 8.7 18.9 21.1 20 25E15 15 2 14.4 26 28.3 30 30E20 20 2 19.2 32 34.3 35 35E23 24 2 23.1 36.9 39.1 40 40

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

Page 172: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

172 Johnson Controls Ducted Systems

ZR078-150 Hi Static Motor - With Powered Convenience Outlet

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

078(6.5)

208 13.5 88 21 2.1 6.8 5.5 20

None - - - 51.4 56.9 60 70E09 6.8 1 18.9 51.4 56.9 60 70E18 13.5 2 37.5 67.9 74.8 70 80E24 18 2 50 83.5 90.4 90 100E36 25.5 2 70.8 109.5 116.4 110 125

230 13.5 88 21 2.1 6.8 5.5 20

None - - - 51.4 56.9 60 70E09 9 1 21.7 51.4 56.9 60 70E18 18 2 43.3 75.1 82 80 90E24 24 2 57.7 93.1 100 100 100E36 34 2 81.8 123.3 130.1 125 150

460 6 44 9 1.26 3.4 2.2 20

None - - - 24.4 26.6 30 30E09 9 1 10.8 24.4 26.8 30 30E18 18 2 21.7 37.6 40.4 40 45E24 24 2 28.9 46.6 49.4 50 50E36 34 2 40.9 61.6 64.4 70 70

575 4.9 34 8 0.66 2.4 1.8 20

None - - - 18.7 20.5 20 25E09 9 1 8.7 18.9 21.1 20 25E18 18 2 17.3 29.6 31.9 30 35E24 24 2 23.1 36.9 39.1 40 40E36 34 2 32.7 48.9 51.1 50 60

090(7.5)

208 13.1 83.1 21 2.1 9.6 5.5 20

None - - - 53.3 58.8 60 70E09 6.8 1 18.9 53.3 58.8 60 70E18 13.5 2 37.5 71.4 78.3 80 80E24 18 2 50 87 93.9 90 100E36 25.5 2 70.8 113 119.9 125 125

230 13.1 83.1 21 2.1 9.6 5.5 20

None - - - 53.3 58.8 60 70E09 9 1 21.7 53.3 58.8 60 70E18 18 2 43.3 78.6 85.5 80 90E24 24 2 57.7 96.6 103.5 100 110E36 34 2 81.8 126.8 133.6 150 150

460 6.1 41 10 1.26 4.7 2.2 20

None - - - 25.9 28.1 30 30E09 9 1 10.8 25.9 28.4 30 30E18 18 2 21.7 39.3 42 40 45E24 24 2 28.9 48.3 51 50 60E36 34 2 40.9 63.3 66 70 70

575 4.4 33 7 0.66 3.6 1.8 20

None - - - 18.8 20.6 20 25E09 9 1 8.7 20.4 22.6 25 25E18 18 2 17.3 31.1 33.4 35 35E24 24 2 23.1 38.4 40.6 40 45E36 34 2 32.7 50.4 52.6 60 60

102(8.5)

208 14.5 98 23 2.1 9.6 5.5 20

None - - - 56.4 61.9 70 70E09 6.8 1 18.9 56.4 61.9 70 70E18 13.5 2 37.5 71.4 78.3 80 80E24 18 2 50 87 93.9 90 100E36 25.5 2 70.8 113 119.9 125 125

230 14.5 98 23 2.1 9.6 5.5 20

None - - - 56.4 61.9 70 70E09 9 1 21.7 56.4 61.9 70 70E18 18 2 43.3 78.6 85.5 80 90E24 24 2 57.7 96.6 103.5 100 110E36 34 2 81.8 126.8 133.6 150 150

460 6.3 55 10 1.26 4.7 2.2 20

None - - - 26.4 28.6 30 30E09 9 1 10.8 26.4 28.6 30 30E18 18 2 21.7 39.3 42 40 45E24 24 2 28.9 48.3 51 50 60E36 34 2 40.9 63.3 66 70 70

575 6 41 9 0.66 3.6 1.8 20

None - - - 22.4 24.2 25 30E09 9 1 8.7 22.4 24.2 25 30E18 18 2 17.3 31.1 33.4 35 35E24 24 2 23.1 38.4 40.6 40 45E36 34 2 32.7 50.4 52.6 60 60

Page 173: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 173

120(10)

208 16 110 25 3.03 9.6 5.5 20

None - - - 61.7 67.2 70 80E18 13.5 2 37.5 71.4 78.3 80 80E24 18 2 50 87 93.9 90 100E36 25.5 2 70.8 113 119.9 125 125E54 40.6 2 112.7 165.4 172.3 175 175

230 16 110 25 3.03 9.6 5.5 20

None - - - 61.7 67.2 70 80E18 18 2 43.3 78.6 85.5 80 90E24 24 2 57.7 96.6 103.5 100 110E36 34 2 81.8 126.8 133.6 150 150E54 54 2 129.9 154.4 161.3 175 175

460 7.8 52 12 1.6 4.7 2.2 20

None - - - 30.5 32.7 35 40E18 18 2 21.7 39.3 42 40 45E24 24 2 28.9 48.3 51 50 60E36 34 2 40.9 63.3 66 70 70E54 54 2 65 77.1 79.9 90 90

575 5.7 38.9 9 1.35 3.6 1.8 20

None - - - 23.1 24.9 25 30E18 18 2 17.3 31.1 33.4 35 35E24 24 2 23.1 38.4 40.6 40 45E36 34 2 32.7 50.4 52.6 60 60E54 54 2 52 61.5 63.8 70 70

150(12.5)

208 22.4 149 35 2.1 14 5.5 20

None - - - 82.8 88.3 100 110E18 13.5 2 37.5 82.8 88.3 100 110E24 18 2 50 92.5 99.4 100 110E36 25.5 2 70.8 118.5 125.4 125 150E54 40.6 2 112.7 170.9 177.8 175 200

230 22.4 149 35 2.1 14 5.5 20

None - - - 82.8 88.3 100 110E18 18 2 43.3 84.1 91 100 110E24 24 2 57.7 102.1 109 110 110E36 34 2 81.8 132.3 139.1 150 150E54 54 2 129.9 159.9 166.8 175 175

460 10.6 75 17 1.26 6.6 2.2 20

None - - - 40.5 42.7 50 50E18 18 2 21.7 41.6 44.4 50 50E24 24 2 28.9 50.6 53.4 60 60E36 34 2 40.9 65.6 68.4 70 70E54 54 2 65 79.5 82.3 90 90

575 7.7 54 12 0.66 5.2 1.8 20

None - - - 29.1 30.9 35 35E18 18 2 17.3 33.1 35.4 35 40E24 24 2 23.1 40.4 42.6 45 45E36 34 2 32.7 52.4 54.6 60 60E54 54 2 52 63.5 65.8 70 70

1. Minimum Circuit Ampacity.2. Dual Element, Time Delay Type.3. HACR type per NEC.

Electric Heat Multipliers

VoltagekW Capacity Multipliers1

1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages.

Nominal Applied

240208 0.75

230 0.92

480 460 0.92

600 575 0.92

ZR078-150 Hi Static Motor - With Powered Convenience Outlet (Continued)

Size(Tons)

Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrExh

Motor

PwrConvOutlet

Electric Heat OptionMCA1

(Amps)

MCA1

w/PwrExh

(Amps)

Max Fuse2/Breaker3

Size(Amps)

Max Fuse2/Breaker3

Size w/ Pwr Exh

(Amps)RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps

Page 174: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

174 Johnson Controls Ducted Systems

Typical Wiring Diagrams

ZH/ZJ037-150 Typical Wiring Diagrams

Typical ZH/ZJ/ZR037-061 Cooling Unit with Gas Heat 208/230 Volt Wiring Diagram

Page 175: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 175

Typical ZH/ZJ/ZR037-061 Cooling Unit with Gas Heat 208/230 Volt Unit (Options)

Page 176: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

176 Johnson Controls Ducted Systems

Typical ZH/ZJ/ZR037-061 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram

Page 177: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 177

Typical ZH/ZJ/ZR037-061 Cooling Unit with Gas Heat 460/575 Volt Unit (Options)

Page 178: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

178 Johnson Controls Ducted Systems

Typical ZH/ZJ/ZR037-061 Cooling Unit with/without Electric Heat Wiring Diagram

Page 179: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 179

Typical ZH/ZJ/ZR037-061 Cooling Unit with/without Electric Heat Unit (Options)

Page 180: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

180 Johnson Controls Ducted Systems

Typical ZH/ZJ/ZR078-120 Cooling Unit with Gas Heat 208/230 Volt Wiring Diagram

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

���

��

Page 181: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 181

Typical ZH/ZJ/ZR078-120 Cooling Unit with Gas Heat 208/230 Volt Unit (Options)

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

���

!�

Page 182: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

182 Johnson Controls Ducted Systems

Typical ZH/ZJ/ZR078-120 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

!��

��

Page 183: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 183

Typical ZH/ZJ/ZR078-120 Cooling Unit with Gas Heat 460/575 Volt Unit (Options)

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

!��

!�

Page 184: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

184 Johnson Controls Ducted Systems

Typical ZH/ZJ/ZR078-120 Cooling Unit with/without Electric Heat Wiring Diagram

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

���

��

Page 185: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 185

Typical ZH/ZJ/ZR078-120 Cooling Unit with/without Electric Heat Unit (Options)

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

���

!�

Page 186: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

186 Johnson Controls Ducted Systems

Typical ZH/ZJ/ZR150 Cooling Unit with Gas Heat 208/230 Volt Wiring Diagram

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

���

��

Page 187: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 187

Typical ZH/ZJ/ZR150 Cooling Unit with Gas Heat 208/230 Volt Unit (Options)

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

���

!�

Page 188: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

188 Johnson Controls Ducted Systems

Typical ZH/ZJ/ZR150 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

���

��

Page 189: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 189

Typical ZH/ZJ/ZR150 Cooling Unit with Gas Heat 460/575 Volt Unit (Options)

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

���

!�

Page 190: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

190 Johnson Controls Ducted Systems

Typical ZH/ZJ/ZR150 Cooling Unit with/without Electric Heat Wiring Diagram

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

$��

��

Page 191: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 191

Typical ZH/ZJ/ZR150 Cooling Unit with/without Electric Heat Unit (Options)

��

��

��

���

����

���

���

��

���

���

����

���

���

����

���

��

���

����

���

����

���

���

���

��

���

���

���

��

��

���

����

$��

!�

Page 192: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

192 Johnson Controls Ducted Systems

BAS Controls Typical Wiring Diagrams

Typical SURVEYOR BAS Control Wiring Diagram

Page 193: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 193

Typical CPC BAS Control Wiring Diagram

Page 194: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

194 Johnson Controls Ducted Systems

Typical HONEYWELL BAS Control Wiring Diagram

Page 195: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 195

Typical NOVAR BAS Control Wiring Diagram

Page 196: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

196 Johnson Controls Ducted Systems

Weights and Dimensions

ZH/ZJ037-150 Unit WeightsUnit 4 Point Load Weight Unit 6 Point Load Weight

D

A

CBLEFTFRONT

D

A

C

BE

F

LEFTFRONT

Size(Tons)

ModelWeight (lbs.) Center of Gravity 4 Point Load Location (lbs.) 6 Point Load Location (lbs.)

Shipping Operating X Y A B C D A B C D E F037(3)

ZH 706 701 47.25 24.00 134 151 221 195 87 95 103 150 138 127

049(4)

ZH 753 748 48.25 25.34 147 174 231 195 95 106 119 159 141 127

061(5)

ZH 860 855 47.25 24.75 168 190 264 233 110 119 130 179 165 152

078(6.5)

ZH 916 911 47.25 24.00 174 197 287 254 114 123 134 195 180 166

090(7.5)

ZH 900 895 48.25 25.34 176 208 277 234 114 127 143 190 169 152

102(8.5)

ZH 1037 1032 47.25 24.75 203 230 318 281 133 144 156 216 199 184

120(10)

ZH 1095 1090 45.00 25.50 233 238 313 306 155 157 159 209 206 203

150(12.5)

ZH 1285 1280 49.75 24.50 234 297 418 330 150 175 206 290 246 212

037(3)

ZJ 724 719 47.25 24.00 137 155 226 200 90 97 106 154 142 131

049(4)

ZJ 753 748 48.25 25.34 147 174 231 195 95 106 119 159 141 127

061(5)

ZJ 770 765 47.25 24.75 151 170 236 208 98 107 116 160 148 136

078(6.5)

ZJ 1038 1033 47.25 24.00 197 223 325 287 129 140 152 221 204 188

090(7.5)

ZJ 1040 1035 48.25 25.34 204 241 320 270 132 147 165 220 196 175

102(8.5)

ZJ 1049 1044 47.25 24.75 205 233 322 284 134 145 158 219 201 186

120(10)

ZJ 1075 1070 45.00 25.50 229 234 307 300 152 154 156 206 202 199

150(12.5)

ZJ 1285 1280 49.75 24.50 234 297 418 330 150 175 206 290 246 212

X Y

LEFTFRONT

Page 197: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 197

ZR037-150 Unit WeightsUnit 4 Point Load Weight Unit 6 Point Load Weight

D

A

CBLEFTFRONT

D

A

C

BE

F

LEFTFRONT

Size(Tons)

ModelWeight (lbs.) Center of Gravity 4 Point Load Location (lbs.) 6 Point Load Location (lbs.)

Shipping Operating X Y A B C D A B C D E F

037(3)

ZR 851 846 47.25 24.00 161 183 266 235 105 114 124 181 167 154

049(4)

ZR 870 865 48.25 25.34 170 201 268 226 110 123 138 184 163 147

061(5)

ZR 863 858 47.25 24.75 169 191 264 234 110 120 130 180 165 153

078(6.5)

ZR 962 957 38 23 214 159 249 335 150 122 101 159 191 234

090(7.5)

ZR 970 965 38 23 216 161 251 337 151 123 102 160 193 236

102(8.5)

ZR 1205 1200 38 25.5 297 221 291 390 208 170 141 185 223 274

120(10)

ZR 1205 1200 38 25.5 297 221 291 390 208 170 141 185 223 274

150(12.5)

ZR 1470 1465 51 25.5 270 363 477 355 172 207 254 334 272 226

X Y

LEFTFRONT

Page 198: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

198 Johnson Controls Ducted Systems

ZH/ZJ/ZR037-150 Unit Dimensions

ZH/ZJ037-049 and ZR037

ZH/ZJ/ZR037-150 Unit Accessory Weights

Unit AccessoryWeight (lbs.)

Shipping OperatingEconomizer 90 85

Power Exhaust 40 35Electric Heat1

1. Weight given is for the maximum heater size available (54KW).

49 49Gas Heat2

2. Weight given is for the maximum number of tube heat exchangers available (8 tube).

110 110Variable Frequency Drive3

3. Weight includes mounting hardware, controls and manual bypass option (6-1/2 to 12-1/2 ton only).

30 30

Ø 25.31

59.00

15.51

29.75

59

LEFT

11 3/8

21 3/16

89

27 5/16

4 3/16FRONT

See detail A for gas inlet

A

See detail B for drain location

B

C D EF

29.52

Page 199: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 199

ZH/ZJ 061, ZR049 - 061 and ZH/ZJ/ZR078 thru 120

LEFT

A

59.00

CD

E

F

4.19

27.31

89.00

21.19

11.38

15.38

59.00

15.38

29.69

15.25

FRONT

SEE DETAIL BFOR DRAIN LOCATION

SEE DETAIL A FOR GAS INLET

B

2X Ø 24.38

Page 200: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

200 Johnson Controls Ducted Systems

ZH/ZJ/ZR150

15.23

29.03

14.85

29.03

14.85

15.23

28.86 29.66

44.09

Ø 24.58 TYP. 4 PL.

FRONT

See detail B for drain location

See detail A for gas inlet

CD

E

F

B

4 3/16

27 5/16

89

21 3/16

11 3/8

A

LEFT

59

ZH/ZJ/ZR037-150 Unit Physical Dimensions

Unit Model NumberDimension (in.)

A B C D E FZH037, 049, 061, 078, 090 42 89 22 1/8 18 3/16 15 3/16 6 3/16

ZH102, 120 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16ZH150 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16

ZJ037, 049, 061 42 89 22 1/8 18 3/16 15 3/16 6 3/16ZJ078, 090, 102, 120 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16

ZJ150 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16ZR037, 049, 061 42 89 22 1/8 18 3/16 15 3/16 6 3/16

ZR078, 090 42 89 22 1/8 18 3/16 15 3/16 6 3/16ZR102, 120 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16

ZR150 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16

Page 201: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 201

Detail A

Detail B42” CABINET

Ø 3.126

Ø 2.000

3.184

4.727

7.705

14.594

Gas Pipe Inlet

Gas Exhaust Vent

50 3/4” CABINET

Ø 3.126

Ø 2.000

3.184

4.737

7.715

17.541

Gas Pipe Inlet

Gas Exhaust Vent

5-3/8

1” FPT

ZH/ZJ/ZR037-150 Unit Clearances

Direction Distance (in.) Direction Distance (in.)Top1

1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.

72 Right 12Front 36 Left 36Rear 36 Bottom2

2. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.

0

Page 202: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

202 Johnson Controls Ducted Systems

ZH/ZJ/ZR037-150 Unit Bottom Duct Openings

TOP VIEW

Bottom condensate drain

Bottom gassupply entry

FRONT

RETURNAIR

SUPPLYAIR

RIGHTLEFT

20 1/8 19 1/8 17 1/8

6 13/16

6 13/16

32 11/16

14 1/2

16 3/8

18 1/16

25 9/16

12 5/16

27 1/224

2118

89

Ø 2.469

3X Ø 0.875

Bottom power, controland convenience outlet

wiring entry

Page 203: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 203

ZH/ZJ/ZR037-150 Unit Electrical Entry

ZH/ZJ/ZR037-120 Unit Side Duct Openings

Disconnect Swith Cover

Power Entry Ø 2-1/2

Control Entry Ø 7/8

Power Entry Ø 2-1/2

Convenience Outlet Cover

Convenience OutletPower Entry Ø 7/8 FRONT

D o t P l u g s

5 - 5 /3 2

3 1 - 1 1 /1 6

2 - 3 1 /3 2

1 8 - 1 /4

ReturnAir

Supply Air

A

B

C

D

Page 204: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

204 Johnson Controls Ducted Systems

ZH/ZJ/ZR150 Unit Side Duct Openings

ZH/ZJ/ZR037-150 Side Duct Dimensions

Unit Model NumberDimension (in.)

A B C D

ZH037, 049, 061, 078, 090 27 3/4 12 1/16 27 1/2 16

ZH102, 120 28 1/4 18 1/16 28 1/4 18 1/4

ZH150 28 1/4 18 1/16 28 1/4 18 1/4

ZJ037, 049, 061 27 3/4 12 1/16 27 1/2 16

ZJ078, 090, 102, 120 28 1/4 18 1/16 28 1/4 18 1/4

ZJ150 28 1/4 18 1/16 28 1/4 18 1/4

ZR037, 049, 061 27 3/4 12 1/16 27 1/2 16

ZR078, 090 27 3/4 12 1/16 27 1/2 16

ZR102, 120 28 1/4 18 1/16 28 1/4 18 1/4

ZR150 28 1/4 18 1/16 28 1/4 18 1/4

Dot Plugs

2-7/8

5-5/32

D

C 31-5/8

18-1/4

B

A

Page 205: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 205

ZH/ZJ/ZR037-150 Unit Left/End Duct Opening

4-5/16

A

C

B

ZH/ZJ/ZR037-150 Left/End Duct Dimensions

Unit Model NumberDimension (in.)

A B C

ZH037, 049, 061, 078, 090 30.357 13.365 22.516

ZH102, 120 30.358 22.580 22.330

ZH150 30.358 22.580 22.330

ZJ037, 049, 061 30.357 13.365 22.516

ZJ078, 090, 102, 120 30.358 22.580 22.330

ZJ150 30.358 22.580 22.330

ZR037, 049, 061 30.357 13.365 22.516

ZR078, 090 30.357 13.365 22.516

ZR102, 120 30.358 22.580 22.330

ZR150 30.358 22.580 22.330

Page 206: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

206 Johnson Controls Ducted Systems

ZH/ZJ/ZR037-150 Unit Accessory Dimensions

ZH/ZJ/ZR037-150 Roof Curb

ZH/ZJ/ZR037-150 Transition Roof Curb

8 or 14

50-1/2

30

20

20

80-5/8

6

2 TYP.

INSULATED DECK UNDERCOMPRESSOR SECTION

INSULATED DECK UNDERCONDENSER SECTION

FRONT

RIGHT

SUPPLY

RETURN

76-5/8

94

50-1/2 30-1/2

64-1/4

59-1/4

10

23 4

26 80-5/8

2 TYP

FRONT RIGHT

SUPPLY

RETURN

Page 207: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

5167795-YTG-O-0120

Johnson Controls Ducted Systems 207

Economizer Options

Economizer Downflow W/Power Exhaust

Economizer Usage

Application Cabinet Height Description Model

Side Return All Horizontal economizer without barometric relief 2EE047069241

Downflow, End Return Horizontal or ERV

42" Economizer, 42” tall cabinet 2EE047174242

50" Economizer, 50” tall cabinet 2EE047176242

1. Barometric relief must be ordered separately and installed in duct work.2. Includes fresh air hood, exhaust hood and barometric relief.

Fresh Air Hood

Barometric ReliefHood

BarometricRelief Damper

Power Exhaust

Low Leak Economizer

Page 208: TECHNICAL GUIDE Description R-410A ZH/ZJ/ZR SERIES 3 - 12 ... · The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing

Subject to change without notice. Printed in U.S.A. 5167795-YTG-O-0120 Copyright © 2019 by Johnson Controls, Inc. All rights reserved. Supersedes: 5167795-YTG-N-1118

York International Corporation5005 York Drive

Norman, OK 73069

Economizer End Return W/Power Exhaust

Field Installed Horizontal Economizer W/Power Exhaust

Fresh Air Hood

Field InstalledDuct Work

Power ExhaustBarometric Relief Damper

Barometric Relief Hood

Low LeakEconomizer

BarometricRelief Hood

BarometricRelief Damper

Power Exhaust

Fresh Air Hood

Fresh Air Damper

Return Air Damper

Field Installed Duct Work