technical guide mlc

Upload: craciun-daniel

Post on 31-Oct-2015

79 views

Category:

Documents


1 download

TRANSCRIPT

  • INSTALLATION SYSTEMS

    T E C H N I C A LI N F O R M A T I O N

    MLCP system fortap water installation and radiator connection

  • T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 72

    Uponor offers solutions based on well thought out products - which is probably the reason why today we rank among the most signi cant suppliers world-wide in the areas of house, environment and municipal technology. With the consolidation into a strong global market we streamline our work processes, operate even more ef ciently and simplify our proposals. That means: Only rst-rate products leave our house. Products, which today meet the requirements of tomorrow, combined with outstand-ing service for our customers coming from the operating elds of Heating/Cooling, Plumbing and Infrastructure systems.

    A trade name a promise

    We feel committed to our customers and partners. With a sense of responsibility, dependability and transparency we keep each and every promise. Together with market specialists we create wellness worlds in which to live, this translates into an advantage for our partners. Today and for the future.

    We reserve the right to effect modi cations in content and in the scope of technical engineering.

    More information under www.uponor.de and www.uponor.com

    Uponor stands for quality and know-how, for a wide range of individual solutions combined with rst-class service.

    In the future we will bundle our competence in the three operating elds, Heating/Cooling,Plumbing Systems and Infrastructure.

    An individual approach is required for the problems of each of the application areas. We can supply them!

    Two or more components combine into a system. We provide perfected, practice tested solutions for our customers and partners.

    Individual, coordinated components form the basis of our systems. You can easily nd these components in our price lists.

    The di erence lies with Uponor

    Components

    Company

    Operating elds

    Field of application

    Systems

    Uponor the intelligent choice

  • T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Contents:

    All legal and technical information in this publication was compiled carefully to the best of our knowledge. Nevertheless errors can not be ruled out completely and we accept no liability for same. The original German version represents the sole legal basis of this manual.

    All parts of this manual are protected by copyright. Any use beyond the exceptions permitted by copyright law is prohibited without the express permission of Uponor GmbH. In particular, we reserve the rights to all duplications, re-printing, adaptation, electronic data processing and storage, translation and micro lming.Subject to technical modi cations.

    The Uponor MLCP system 5

    The Uponor Unipipe MLC pipe 6 5 layers built for the future 6 Technical data and delivery dimensions 7 Zeta values and equivalent pipe lengths 9

    Fast, simple, safe: The connection technology for Uponor Unipipe MLC pipes 10 Test reliability is built-in at the factory: The Uponor MLC press ttings 11

    The Uponor MLP system used in tap water installation 13

    Installation friendly system components 14 Individual installations with the Uponor 2 m mounting track 15

    Planning basis for tap water installation 16 Installation variations 17 Protection of tap water 18 Uponor Aquastrom T plus circulation systems 18 Use of trace heating 20 Connection to ow heater Hot water tank and ttings 20 Humidity protection 21 Pressure test/pipe ushing/test reports 22 Ordinances and regulations, DIN standards (German Institute for Standardisation) 27

    Calculations basis for tap water installation 28 Pipe friction tables 30 Pressure-loss grap 33

    Radiator connection with the Uponor MLCP system 34

    Planning basis for radiator connection 36 Fields of application 36 Installation possibilities Single-pipe heating system 36 Installation possibilities Double-pipe heating system 37 Connection variations with the Uponor MLCP system 38 Pressure test/Pressure test report 41 Ordinances and regulations, DIN standards (German Institute for Standardisation) 43 Calculation basis for radiator connection 44 Pressure-loss graph 44 Pipe friction tables 46 Calculation example 50

    Planning software Uponor HSE 51

    3

  • T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Contents:

    4

    Calculations for the Uponor MLCP system 52

    Technical notes on the Uponor MLCP system 54 Fire protection 54 Sound protection 55 Thermal protection 57 Equipotential bonding 66 Mixed installations 66 Repair or renovation work 66 Outer corrosion protection of Uponor ttings 67 Threaded connection handling instructions 67

    Assembly and installation guidelines 68 Overview Uponor pressing tools 68 Compatibility list Uponor pressing jaws/external pressing tools 69 Installation dimensions 70 Installation method by Z-dimension 71 Bending the Uponor Unipipe MLC pipes 72 Consideration of thermal length variation 73 Pipe installation onto the raw oor 75 Installation under mastic asphalt 78

    Transportation, storage and working conditions 79

  • The complete system from one source

    Whether it is tap water, radia tor connection or compressed air applications the Uponor MLCP system is the perfect solution. The comprehensive program permits the complete installation from the house connection line to the consumer. The installation is simple and economical: The core of the system, i.e. the Uponor Unipipe MLC pipe and the relevant ttings, are manufactured in house and therefore perfectly coordinated. Through the inherent stability of the pipe and the low linear expan-sion, only a few mounting points are necessary the practical advantage for a safe and fast installation. The Uponor MLCP system is rounded off by a well thought out Tool program: from pipe cutting tool over bevel-ling tool up to pressing tools.

    Basis for your professional installation

    Permanently watertight, together with a long service life, are the most important requirements that are demanded today from a reliable and high-quality installation. Uponor as a leading manufacturer of plastic pipes for house construction and municipal technology ful ls these requirements without reservation with its Uponor MLCP system. With this system we offer you the security that is so impor tant for your installation.

    The Uponor MLCP system

    Tested Quality

    With the Uponor MLCP system you install tested and certi ed quality. Thus you observe all required building regulations, including re protection, sound protection and thermal insulation regulations. The system technology is also here particularly long-lived and safe, certi ed by numerous tests and licences.

  • T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 76

    With our 5 layer composite pipe we developed a product with a future, which combines the bene ts of both metal and plastic pipes. Product bene ts are obtained that cannot be surpassed: The inner aluminium pipe is absolutely safe against oxygen penetration. It compen-sates for the snap-back forces and the linear expansion caused by temperature changes. The basis of the system is simple, safe and fast pipe installation: simply bend by hand, cut to length, bevelling, join together, press done!

    The Uponor Unipipe MLC pipe a well thought out development

    Your plus

    Absolutely oxygen diffusion tight multi-layer composite pipe

    Available in dimensions 14-110 mm

    Easy handling

    Low weight

    High inherent stability and bend exibility

    Low linear expansion

    Excellent hydrostatic stress performance

    Corrosion resistance

    The Uponor Unipipe MLC pipe con-sists of a long itudinal safety welded aluminium pipe, to which an inner and outer layer of high temperature resistant polyethylene is applied (in accordance with DIN 16833). All layers are permanently bounded to-gether by means of an intermediate adhesive layer. A special welding technique guarantees a maximum of safety. The thickness of the alu-minium selected for the Uponor Unipipe MLC pipe is exactly adapt-ed to the compressive strength re-quirements as well as the bending capability.

    The Uponor Unipipe MLC pipe has a comparatively low linear expansion due to the plastic lms rm bond to the aluminium

    Construction of the Uponor Unipipe MLC pipe

    5 layers built for the future

    The best insulation

    The Uponor Unipipe MLC pipe for tap water installation and radiator connection can also be ordered pre-insulated. You have an assortment available in sizes from 16-25 mm that ful ls all insulation require-ments of DIN 1988-2 and the German Energy Saving Directive (EnEV). The pre-insulated pipes save installation time because the time intensive insulation of the mounted pipes and the resulting gluing of joints are eliminated.

    PE-RT Adhesive Adhesive PE-RT

    Longitudinal safety weldedaluminium pipe

    PP

    PB

    PVC

    Unipipe

    Copper

    Galvanized steel

    Stainless steel

    50 m t 50 k

  • T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7 7

    The resilience of the multi-layer composite pipe is checked regularly by tensile testing. Along with the continuous laboratory testing of the pipe, each Uponor Unipipe MLC pipe is checked during production for accuracy of size and water tight-ness.

    Technical data and delivery dimensions

    * Please contact the manufacturer if you require additional explanation of the parameters

    Dimensions OD x s [mm] 14 x 2 16 x 2 18 x 2 20 x 2,25 25 x 2,5 32 x 3

    Inner diameter ID [mm] 10 12 14 15.5 20 26Length coil [m] 200 100/200/500 200 100/200 50/100 50Length straight length [m] - 5 5 5 5 5Outer diameter coil [cm] 80 80 80 100 120 120Weight coil/straight length [g/m] 91/- 105/118 123/135 148/160 211/240 323/323Weight coil/straight length with water 10 C [g/m] 170/- 218/231 277/289 337/349 525/554 854/854Weight per coil [kg] 18.2 21.0/52.5 24.6 14.8/29.6 10.6/21.1 16.2Weight per straight length [kg] - 0.59 0.68 0.80 1.20 1.6Water volume [l/m] 0.079 0.113 0.154 0.189 0.314 0.531Pipe roughness k [mm] 0.0004 0.0004 0.0004 0.0004 0.0004 0.0004Thermal conductivity (W/m x K) 0.40 0.40 0.40 0.40 0.40 0.40Coef cient of expansion (m/m x K) 25 x 10 -6 25 x 10 -6 25 x 10 -6 25 x 10 -6 25 x 10 -6 25 x 10 -6

    Maximal temperature: 95 C*

    Maximum continuous operating pressure 10 bar at 70 C continuous operation temperature, Tested hydrostatic stress performance 50 years, safety factor 1.5*

    Min. bending radius by hand:5 x OD [mm] 70 80 90 100 125 160Min. bending radius withinner blending spring 4 x OD [mm] 56 64 72 80 100 128Min. bending radius with outer blending spring 4 x OD [mm] 56 64 72 80 100 -Min. bending radius with bending tool [mm] 43 49 49 78 80 128

  • 8 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Dimensions OD x s [mm] 40 x 4 50 x 4.5 63 x 6 75 x 7.5 90 x 8.5 110 x 10

    Inner diameter ID [mm] 32 41 51 60 73 90Length coil [m] - - - - - -Length straight length [m] 5 5 5 5 5 5Outer diameter coil [cm] - - - - - -Weight coil/straight length [g/m] -/508 -/745 -/1224 -/1788 -/2545 -/3597Weight coil/straight length with water 10 C [g/m] -/1310 -/2065 -/3267 -/4615 -/6730 -/9959Weight per coil [kg] - - - - - -Weight per straight length [kg] 2.54 3.73 6.12 8.94 12.73 17.99Water volume [l/m] 0.800 1.320 2.040 2.827 4.185 6.362Pipe roughness k [mm] 0.0004 0.0004 0.0004 0.0004 0.0004 0.0004Thermal conductivity (W/m x K) 0.40 0.40 0.40 0.40 0.40 0.40Coef cient of expansion (m/m x K) 25 x 10 -6 25 x 10 -6 25 x 10 -6 25 x 10 -6 25 x 10 -6 25 x 10 -6

    Maximal temperature: 95 C*

    Maximum continuous operating pressure 10 bar at 70 C continuous operation temperature, Tested hydrostatic stress performance 50 years, safety factor 1.5*

    Min. bending radius by hand:5 x OD [mm] - - - - - -Min. bending radius withinner blending spring 4 x OD [mm] - - - - - -Min. bending radius with outer blending spring 4 x OD [mm] - - - - - -Min. bending radius with bending tool [mm] - - - - - -

    Technical data and delivery dimensions (continued)

    * Please contact the manufacturer if you require additional explanation of the parameters

  • 9T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Zeta values and equivalent pipe lengths

    A ow rate of 2 m/s has been used for the calculation of equivalent pipe lengths:

    Dim

    ensi

    ons

    OD

    x s

    [m

    m]

    14 x

    2

    16 x

    2

    18 x

    2

    20 x

    2.2

    5 25

    x 2

    .5

    32 x

    3

    40 x

    4

    50 x

    4.5

    63

    x 6

    75

    x 7

    .5

    90 x

    8.5

    11

    0 x

    10In

    ner

    diam

    eter

    ID

    [m

    m]

    10

    12

    14

    15

    .5

    20

    26

    32

    41

    51

    60

    73

    90

    Zet

    a va

    lues

    (-

    )/eq

    uiva

    lent

    P

    ipe

    leng

    th e

    L [m

    ]

    eL

    eL

    eL

    eL

    eL

    eL

    eL

    eL

    eL

    eL

    eL

    eL

    Pres

    s el

    bow

    90

    7.

    0 2.

    5 4.

    4 2.

    0 3.

    6 2.

    0 3.

    0 1.

    9 2.

    8 2.

    4 2.

    3 2.

    7 2.

    0 3.

    1 1.

    6 3.

    3 1.

    4 3.

    8 1.

    4 4.

    6 3.

    7 15

    .4

    2.9

    15.5

    Pres

    s el

    bow

    45

    -

    - -

    - -

    - -

    - 1.

    5 1.

    3 1.

    2 1.

    4 1.

    2 1.

    8 0.

    8 1.

    7 0.

    8 2.

    2 0.

    8 2.

    6 0.

    7 2.

    9 0.

    6 3.

    2

    Red

    ucin

    g

    2.

    8 1.

    0 1.

    7 0.

    8 1.

    4 0.

    8 1.

    2 0.

    8 1.

    0 0.

    9 0.

    9 1.

    1 0.

    8 1.

    2 0.

    6 1.

    2 0.

    6 1.

    6 0.

    5 1.

    6 0.

    5 2.

    1 0.

    7 3.

    7

    Bra

    nch

    at

    ow

    spl

    it

    8

    .3

    3.0

    5.2

    2.4

    4.2

    2.3

    3.6

    2.3

    3.2

    2.7

    2.6

    3.1

    2.4

    3.7

    1.9

    3.9

    1.7

    4.6

    1.7

    5.6

    3.7

    15.4

    2.

    9 15

    .5

    Bra

    nch

    run

    at

    ow s

    plit

    2.0

    0.

    7 1.

    2 0.

    6 1.

    0 0.

    6 0.

    8 0.

    5 0.

    8 0.

    7 0.

    7 0.

    8 0.

    5 0.

    8 0.

    4 0.

    8 0.

    4 1.

    1 0.

    4 1.

    3 0.

    5 2.

    1 0.

    4 2.

    1

    Bra

    nch

    reve

    rse

    run

    at

    ow s

    plit

    7.3

    2.

    7 4.

    6 2.

    1 3.

    7 2.

    0 3.

    2 2.

    0 2.

    9 2.

    5 2.

    3 2.

    7 2.

    1 3.

    2 1.

    7 3.

    5 1.

    5 4.

    1 1.

    5 4.

    9 2.

    2 9.

    1 1.

    7 9.

    1

  • 10 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Fast, simple, safe: The connection technology for Uponor Unipipe MLC pipes

    Extensive program from a single source

    Uponor shows its strength in the development and manufacturing of a tting concept precisely coordi-nated to the pipe being used. The pipe tting program with its cou-plings, elbows, T-pieces and large number of practical system compo-nents satis es your every need: Pressed or compression both methods can be used and ensure durable watertight connections.

    The exibility of the Uponor Unipipe MLC pipes can often re-duce the number of elbows needed for the installation. This substan-tially lowers material costs as well as reducing installation time. Further bene ts are shorter tted length and an increased installation safety.

    Even with complicated applications you nd the right connection in Uponors extensive tting program whether press or compression.

    Overview of composite pipe and connection technology

    Pipe Metal MLC Metal MLC Composite Metal MLC MLCdimension press tting, press tting MLC PPSU clamp tting compression reliable testing press tting tting, with coloured reliable stop rings testing

    14 x 2 16 x 2 18 x 2 20 x 2 25 x 2,5 32 x 3 40 x 4 50 x 4,5 63 x 6 75 x 7,5 90 x 8,5 110 x 10

    Uponor MLC press ttings

    Connections can be made within seconds with the patented Uponor press system. Complicated connec-tion techniques such as a welding or soldering are not necessary.The connection technique produces permanent watertight press, clamp and compression connections, as is con rmed by the SKZ test reports and DVGW certi cates.

    Auditable metal press ttings Composite tting made from PPSU

  • 11T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Metal MLC press tting with coloured stop rings

    The Uponor press tting 14-32 mm is a new generation metal press tting. Because here reliable testing is standard. The tting is manufac-tured with optimized support sleeve geometry; a stop ring and press jaw guide ensures simple, skew free pressing. O-rings ensure an abso-lute watertight connection between the support sleeve and inner pipe wall. The system is certi ed by DVGW.

    The installation friendly metal press tting is designed in such a way that, during the prescribed pressure test, water leaks from the un-pressed connections or the tting separates from the pipe. That means, simply press and a durable and watertight connection is guar-anteed.

    Coloured stop rings on the practice proven installation friendly Uponor press ttings are the sign of the new Uponor tting generation. Each nominal size from 14 to 32 mm has its own colour this brings clarity to the building site, the warehouse as well as to the wholesaler.

    Test reliability is built-in at the factory: The Uponor MLC press ttings 14 32 mm

    1. ApplicationThe press jaw is placed onto the press guide of the press sleeve.

    2. PressingDuring the pressing procedure the stop ring breaks into pieces and falls off of the press sleeve.

    3. TestingThe missing stop rings reliably mark a success-ful connection. This can be recognized at a distance of many metres.

    4. InsulationContinuous pipe insulation such as Tubolit can be easily pushed over the obstacle-free connexion.

    If a connection is still not pressed, this is shows up doubly when pressing. The coloured stop rings are still attached. Additionally tting is designed in such a way that during the pressure test water leaks out. Now simply press and the connection is permanently tight.

    Dimension 32 Dimension 25 Dimension 20 Dimension 18 Dimension 16 Dimension 14

  • 12 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Uponor MLC press ttings

    40 75 mm Description/characteristics Material

    Firmly xed press sleeve, permanently connected with the tting

    body protects against mechanical damage to the O-ring

    Press sleeves with inspection windows, the penetration depth of the

    pipe into the tting can be checked before pressing

    After installation the form-stable press sleeve allows the connection

    to absorb bending forces without developing leaks. This allows a

    pipe that has already been installed to be realigned after installation

    (up until the pressure test)

    Brass, tin plated

    Stainless steel press sleeve

    Uponor MLC composite press ttings

    16 32 mm Description/characteristics Material

    During installation the Uponor Unipipe MLC pipe it is pushed

    between the supporting sleeve and stainless steel press sleeve and

    a force-closed connection is made with the Uponor composite

    tting. Pressed into the inner plastic layer of the pipe, the special

    pro le of the PPSU insert produces a reliable connection. A high-

    temperature and age resistant O-ring tted into a groove provides

    sealing between the insert part and inner wall of the pipe.

    After installation the form-stable press sleeve allows the connection

    to absorb bending forces without developing leaks. This allows a

    pipe that has already been installed to be realigned after installation

    (up until the pressure test)

    High performance synthetic PPSU

    stainless steel press sleeve

    Uponor MLC metal clamp tting

    90 110 mm Description/characteristics Material

    Clamp connection whereby the pipe is permanently pressed between

    insert part and locking ring. The tting insertion depth is rst marked

    on the pipe end. Subsequently the pipe is inserted into the tting

    and the clamping ring is tightened with conventional tools.

    A pressing tool is not required for this connection technique.

    Gunmetal

    Uponor MLC compression ttings

    14 25 mm Description/characteristics Material

    The Uponor MLC compression tting can be used for the direct

    connection of the Uponor Unipipe MLC pipes to Uponor ttings,

    manifolds, and plumbing press ttings. The variation permits the

    connection to Eurokonus ttings.

    Coated brass union nut

    insert part PPSU

    polyamide (PA) press ring

    Uponor MLC press tting with coloured stop rings

    14 32 mm Description/characteristics Material

    Firmly xed press sleeve, permanently connected with the tting

    body protects against mechanical damage to the O-ring

    Press sleeves with inspection windows, the penetration depth of the

    pipe into the tting can be checked before pressing

    Coloured stop rings that break off during pressing

    After installation the form-stable press sleeve allows the connection

    to absorb bending forces without developing leaks. This allows a

    pipe that has already been installed to be realigned after installation

    (up until the pressure test)

    Brass, tin plated

    Aluminium formed press sleeve

    Coloured plastic stop rings

    Dimension colour codes

    14 20

    16 25

    18 32

  • 13T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    The Uponor MLCP system used in tap water installations

    Extensive assortment for com-plete installations

    Everything thats required from one system: The Uponor MLCP tap water program permits complete tap water installations from the service connection to the nal usage point. You select the installa-tion variation, its your decision: Single connections via a manifold, T-piece or a loop system.

    The comfortable system technology insures you of a simple and ex-tremely fast installation. And you only use certi ed and tested quali-ty. Longevity and security have been con rmed by numerous tests. The Uponor MLCP system has DVGW and SKZ approval and is applicable for tap water installations of all sizes.

    With our large selection of special solutions we cover all individual requirements in existing as well as new construction. An extensive assortment of couplings permits the connection of the system to all cur-rent front wall installation systems and ttings.

    The Uponor Unipipe MLC pipe is certi ed on the basis of the DVGW W 542 worksheet. This certi cation takes into consideration the exami-nation and evaluation of micro-organism growth on basis of the DVGW W 270 worksheet as well as numerous mechanical performance requirements. This also includes regular testing of the hygiene re-quirements in accordance with KTW recommendations (Plastic for tap water recommendations of the Tap water interests working group of the plastics commission of the German Federal Health Of ce).

    The press and clamp connectors used in the Uponor MLCP system are fully tin plated. The brass mate-rials used ful ls all requirements of the new German tap water directive. In accordance with DIN 50930-6 they can be used without restriction with all water qualities that correspond to the German tap water directive.

    Summary: The Uponor MLCP system is the trend-setting system for tap water installation and it can be used without reservation for all types of tap water that correspond to the German tap water directive! An investment in the future.

    Your plus

    Complies with the strict guidelines of the German tap water directive

    5 layer composite pipe made from foodstuff safe polyethylene

    Manufactured under comprehensive quality control for the safety of the tap water installation

    High quality surface nish inhibits deposits

    Simple and secure mounting

    Practice oriented product range

    Ideally suited for both surface mounted and concealed installation

  • 14 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Uponor mounting plate, 50 mm

    Uponor mounting plate, 75/150 mm

    Uponor mounting unit MLC with sound protection set

    Installation friendly system components

    Uponor press tap connection elbow MLC with round ange

    Uponor UPS press connection elbow, MLC

    Uponor press wall penetration MLC, elbow

    Practical as well as functional

    We designed the Uponor tap water connection system to be even more user friendly. The new Uponor MLCP system tap water compo-nents are a result of the continued development of our innovative products. The coordinated product range provides you with an eco-nomical and simple installation for all sectors.

    For all installation situations Preformed mounting brackets and mounting plates, press tap elbows and wall plates for different instal-lation situations facilitate the work on the building site. Simple align-ment and mounting on the sub-strate is made possible by the elongated and round holes of the mounting brackets and plates.

    Practice oriented product range

    You can select from our proven press and compression connection technologies for press tap elbows and wall plates. For the installation of loop systems, along with single connections, we also stock double press tap elbows and double wall plates in 90 and 160 models. Along with this, alter-natives are available for the installa-tion through dry walls. We also of-fer optimum solutions for universal ushing tank connections.

    The new concept: plug in, clamp, secure!

    1. Push in and lock the Uponor press tap elbow

    2. Attach the Uponor xing element

    3. Clamp - the Uponor press tap elbow is installed rmly on the Uponor mounting bracket and is twist proof

  • 15T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Individual installations with the Uponor 2 m mounting track

    A rail for all installation situations - variable and an exact match

    Sound protection in accordance with DIN 4109 tested by the Fraunhofer Institute for building physics (IBP), Test report P-BA 242/2004

    Meets all building site requirements

    The new Uponor 2 m mounting track substantially reduces your work on the building site: They can be simply formed with the Uponor bending tool to meet all installation requirements.

    User friendly features

    Convincing dimensions: 2 m long, 50 mm thick, with 8 mm elongated holes and 6 mm round holes for the simple positioning and wall mount-ing. Made from galvanized steel.

    Extended application areas

    For fast and uncomplicated mount-ing of Uponor wall brackets and wall panels (also with sound protec-tion set).

    Easily bent

    The Uponor 2 m mounting track is easily bent with the Uponor bend-ing tool. This makes it ideal for all possible requirements.

    Simple installation

    The Uponor MLC press tap elbow is quickly attached to the rail using various methods: Plug in, clamp,

    secure. The Uponor press MLC wall plate and the sound protection set are screwed onto the front of the rail with the system screws (acces-sories, article no. 97 00 95).

  • 16 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Planning basis for tap water installation using the Uponor MLCP system

    Fields of application

    The Uponor MLCP system is applicable for all sanitary facilities, e.g. for commercial and public buildings, house construction, series cleaning plants and barrier-free construction.

    The large selection of Uponor Unipipe MLC pipes and ttings in the dimensions 14 to 110 mm permits safe and fast tap water installation from a one-family house up to special usage buildings.

    The Uponor MLCP system offers a large selection of special solutions, whereby all individual requirements in existing as well as new construc-tion can be covered. All currently available sanitary equipment and ttings can be connected to the system. This is ensured by the assortment of tting and equip-ment connections. When installing the pipe systems you must ensure a perfect isolation of all components from the structure. For this purpose Uponor offers the sound protection set for wall plates.

    Certi cates

    According to DVGW worksheet W 542 a minimum useful life of 50 years must be proven for multi-layer composite pipes used in tap water distribution systems. For this purpose an independent testing institute runs a series of tests in order to produce an internal pres-sure creep rupture diagram. For Uponor this report was produced by the South German Plastics Centre in Wurzburg (SKZ). Along with other tests, the internal pressure creep rupture diagram forms the basis for DVGW issuing a mark of approval for Uponor with all associated connectors. Together with the test institute and DVGW, Uponor works continuously on the testing of the pipe system in accordance with all relevant DVGW worksheets.

    DVGW certi cation permits the use of the Uponor MLP systems in tap water installations in accordance with the requirements of DIN 1988 TRWI (Technical regulations for drinking-water installations) All components coming into contact with tap water are materials and articles in the sense of the German Foodstuff and Consumer Goods Act. The Uponor MLCP system corresponds to the recommenda-tions of the German Federal Board of Health (KTW recommendation), and through the DVGW mark of approval is also accordingly reviewed and recognized.

    The brass alloy used for the Uponor MLC ttings corresponds to DIN 50930-6 and ful ls the require-ments of the German tap water directive (TrinkwV).

    For use world-wide, Uponor has more than 60 international certi -cates (e.g. VGW, SVGW, KIWA, CSTB, etc.).

  • 17T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Installation variations

    The Uponor MLCP system offers the possibility of a complete sanitary installation from the service connection to the nal usage point. For example, the following installation variations are possible:

    Shower

    xxxxx

    3

    HW CWC

    Wash-basin

    flush-water tankSingle inlet system over tap water

    distributor and single connection

    Equipment connection over double connection

    Loop system with tap water distributor and double connection

    Classical equipment connection over T-pieces and a single connection

    Single connection an a single storey pipe out of the false ceiling with a single shut-off

    Single inlet system from the false ceiling over a tap water distributor

    Basement distributor

  • 18 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Measures for inhibiting the growth of legionella

    Conditions must be established that inhibit an unhealthy concentration of legionella in hot water tank systems and their attached warm water distribution systems.

    Legionella is rod-shaped bacteria, which naturally occur at low con-centrations in fresh water e.g. lakes, rivers and occasionally also in tap water. Approximately 40 forms of the legionella bacteria are known. Some legionella forms can cause infections through the inhalation of contaminated aerosols ( ne water

    droplets) e.g. while showering or through moisturizers in air-condi-tioners. For people with health problems e.g. weakened immune system, chronic bronchitis etc. this can lead to pneumonia (legionella pneumonia or legionnaires disease) or to Pontiac fever.

    According to DVGW worksheet W 551 the infection risk is a direct function of the temperature of the water from the tap water installa-tion. The temperature range in which increased the legionella growth appears is appropriate between 30 C and 45 C.

    Based on the present level of know-ledge, the workpaper describes the necessary technical measures for the reduction of legionella growth in tap water installations. Additional measures are described for the rehabilitation of contaminated tap water systems.

    Circulation systems

    Warm water distribution systems in which warm tap water is constantly available at the taps must main-tained permanent hot water circula-tion. For the operation of circula-tion systems, the conditions as stipulated in DVGW worksheets W 551 and W 553 must be maintained in order to avoided the above mentioned health risks.

    Requirements

    The complete warm water distribu-tion system is to be operated in such a way that on the one hand the warm water leaves the tap water heater with at least 60 C and returns to the heater with a tem-perature loss of no more than 5 K. On the other hand a suf cient warm water volume ow must be present in all circulation lines. The DVGW worksheet recommends the operation of a circulation system with a water temperature of at least 57 C at the end of each return line. The required ow rates are calculated in accordance with DVGW worksheet W 553.

    This worksheet contains three calculation procedures:

    A short procedure for small systems (e.g. one and two family houses), with which no calcula-tions must be made.

    A simpli ed procedure for all system sizes with the goal of supplying a calculation method which supplies suf ciently accurate results for the draft and the implementation without excessive effort.

    A differentiated procedure for all system sizes with the goal of achieving a better approximation of the real operational condi-tions, particularly for large systems.

    The mentioned calculation methods should be taken from the DVGW worksheet W 553. The Uponor HSE calculation software is available for these calculations.

    Protection of tap water

  • 19T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Uponor Aquastrom T plus

    Thermostat preset for circulation conduit

    Uponor Aquastrom T plus is a preset thermostat for circulation conduit that conforms to DVGW worksheets W551 and W553. It regulates the circulation water temperature in the recommended range of 55 C to 60 C (max. control range 40 C to 65 C; accuracy +/- 1 C). The valve automatically supports thermal disinfection. The volume ow rises approximately 6K above the set temperature and reduces itself, inde-pendent of the temperature set, starting from approxi-mately 73 C on the remaining volume ow. The valve thereby optimally supports the thermal disinfection of the circulation system. The maximum volume ow can be preset and locked, independent of the temperature set. The valve is made from red brass and is equipped with a drain valve with a hose mounting that allows the circulation branch line to be emptied for maintenance purposes. Temperature monitoring is possible with thermometers or temperature sensors. The temperature setting is protected against change by a seal cover. The temperature value set can still be read.

    Max. operating temperature: 90 CNominal pressure: 16 barFactory settings: Temperature: 57 C Volume ow setting: DN 15: 2.0

    DVGW certi ed

    Bene ts

    Automatic thermal regulation of the volume ow Supports thermal disinfection Volume ow rises approx. 6 K above the temper-

    ature set, thus quickly reaching the disinfection temperature in the branch line

    Restricted above 73 C, the volume ow is again normalized in order to ensure disinfection of additional components

    High corrosion resistance Temperature setting can also be read with a seal

    cover installed Later sealing is possible Temperature monitoring with thermometer or

    temperature sensor (accessories) is possible for the incorporation in building control technology

    The maximum volume ow can be preset and locked independent of the set temperature and can be shut off for maintenance.

    Integrated drain valve with hose connection

  • 20 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    The Uponor Unipipe MLC pipe is suitable for use with trace heating. The inner aluminium pipe ensures uniform heat distribution around the pipe, the customary temperature limitation of 60 C by the manufac-turer is to be respected. The xing of the heating band is to be done according to the manufacturers instructions, whereby the Uponor Unipipe MLC pipe is to be classi ed as a plastic pipe.

    You must make sure that the water can expand correspondingly if Uponor Unipipe MLC pipes with a self-regulating heating band are permitted. If this is not the case,

    e.g. as with tank outlets to the warm water distributor, short lines to the usage points or with house connection lines that only bypass one story, damage of the Uponor of pipe due to the high increase in pressure cannot be ruled out.

    For these cases suitable safeguards are to be taken, e.g. the installation of a suitable safety valve or expan-sion vessel.

    Note:The pressure increase of the components due to the use of heat-ing tape is to be closely watched. Suitable safety precautions are to be planned that ensure pressure equalization. The manufacturers assembly guidelines and installation notes for the self-regulating heating band must be observed.

    Use of trace heating

    Connection to a instantaneous water heater

    Due to their construction, hydrauli-cally controlled, electrical and gas red ow heaters can build up high temperatures and pressures, both in normal operation and as a result of a failure, which can cause damage to the pipe system. The Uponor MLCP system may only be directly connected to electronically control-led equipment. The manufacturers instructions must be observed when using electronically controlled equipment to heat tap water.

    Connection to a hot water tank

    Generally it must be ensured when connecting hot water tanks (par-ticularly with direct red hot water tanks, solar storage tanks and special constructions) that in normal operation as well as in the case of a failure, the operation limits of the Uponor Unipipe MLC pipe are not exceeded. This applies in particular to the maximum warm water outlet temperature, which is to be checked at start-up or be obtained from the manufacturer. In the case of doubt, suitable safety precautions are to be taken (e.g. installation of an industrial water mixing valve).

    Mixer connections

    Fitting connection installation must be torsion-proof (e.g. by xing the press tap elbow on mounting brackets or mounting plates).

    Connection to instantaneous water heaters, hot water tanks and mixer

  • 21T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Humidity protection

    The humidity protection required in sanitary facilities is regulated by DIN 18195-5 Water-proo ng against non-pressing water. The following implementations are limited to humidity protection within the area of sanitary ttings and wall bushings, e.g. within the area of dry lining panelling.

    Each sanitary facility can be divided in two humidity classes:

    Humidity protection in the area of sanitary ttings and wall penetration

    With concealed ttings, a seal must be made to the brick-work or the

    opposite dry lining panelling with a suitable humidity seal. The tiler integrates these in accordance with the generally accepted rules of technology into a surface seal. The same applies to wall bushings for

    equipment connections with surface mounted ttings, e.g. showers and bath tubs.

    Dry area

    Wet area

    Wall bushing seal with exible silicone

    Wall bushing seal with station-ary seal ring and integration into the surface seal

    2

    1

    12

    2

    Concealed ttings with integration into the surface seal

    Dry lining boards/plaster

    UP tting

    Surface sealing, e.g. by the tiler

    Sealing sleeve, e.g. by an installation specialist

    Thin bed mortar

    Tiles

    1

    5

    4

    3

    2

    6

    1

    5

    4

    3

    2

    6

    Wet area2

    Due to moisture build-up (conden-sation), particular at the cut-out sites in dry lining panelling, e.g. for urinal controls, a seal against

    moisture penetration must be applied to building material sur-faces. All other wall penetrations within the dry area (e.g. against the

    ceramic facings/tiles) can be sealed with neutrally hardening sanitary silicone.

  • 22 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    As for all tap water installations, a pressure test in accordance with DIN 1988-2 is also to be run for the Uponor MLCP system. Before the pressure test, all components of the installation must be freely accessi-ble and visible in order to be able to locate unpressed or incorrectly pressed ttings. All open pipes are to be closed with metal screw plugs, caps, blanking plates or blind anges. Equipment, pressurized tanks or tap water heaters are to be separated from the pipes. It is recommended to perform the pressure test with compressed air or an inert gas if the pipe system is to remain un lled after the test. At the nal inspection the pressure test and ushing must be done with water in accordance with DIN 1988-2.

    Pressure test with compressed air or inert gas

    The pressure test with compressed air or inert gas is to be run in accordance with the generally accepted rules of technology in two steps, the leak test and the strength test. With both tests, before start-ing the test period, you must wait for temperature equalisation and steady-state condition after pres-sure build-up.

    Leak testA visual inspection of all pipe con-nections is to be made before the leak test. The pressure gauge used for the test must have an accuracy of 0.1 bar in the display range for the pressure being measured. The system is pressurised with a test pressure of 110 mbar. For a system volume of up to 100 litres the test period must be at least 30 minutes.

    The required time is extended by a further 10 minutes for every addi-tional 100 litres. During the test no leakage may appear at the connec-tors.

    Strength testThe strength test is to be run fol-lowing the leak test. Here the pres-sure is raised to a maximum of 3 bar (pipe dimension 63 x 6 mm) or a maximum of 1 bar (pipe dimensions 63 x 6 mm). For a system volume of up to 100 litres the test period must be at least 30 minutes. The required time is extended by a fur-ther 10 minutes for every additional 100 litres.

    Pressure testing the tap water installation

    Wall penetration with integration into the surface seal

    Dry lining boards/plaster

    Press wall duct

    Seal sleeve made from elastomer

    Surface sealing, e.g. by the tiler

    Thin bed mortar

    Tiles

    1

    5

    4

    3

    2

    6

    wet areas2

    15

    4

    3

    2

    6

  • 23T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Pressure testing with water

    A visual inspection of all pipe connections is to be made before pressure testing with water. The pressure gauge must be connected at the lowest point of the installa-tion being tested. Only measuring instruments may be used where a pressure difference of 0.1 bar can be read. The installation must be lled with ltered tap water (pro-tect against frost!) and vented. Shut-off valves before and after boilers and tanks are to be closed so that the test pressure is kept away from the rest of the system. The system is to be pressurized with the maximum permissible operating pressure (10 bar) plus 5 bar (in relation to the lowest point of the system). Check the maximum operating pressure with pressure boosting systems! A suitable time must elapse to allow for the tem-perature equalisation between the ambient temperature and the temperature of the ll water. If necessary, the test pressure must be re-established after the waiting period.

    Preliminary testRe-establish the test pressure two times within 30 minutes at intervals of 10 minutes. After a further 30 minutes the test pressure must not have dropped by more than 0.6 bar.

    Main testThe main test is to be run directly following the preliminary test. The pressure test is considered to have been passed successfully if the test pressure has not dropped by more than 0.2 bar after a further two hours.

    After completion of the pressure test all ttings are to be checked for possible leakage. The results of the pressure test must be recorded in a report as a record for the plumber and customer. The forms at the end of this chapter can be used for this report.

    Pressure pump

  • 24 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Pipe line ushing

    The total system is to be ushed thoroughly as soon as possible after installation of the pipes and follow-ing the pressure test. Filtered tap water ( lter in accordance with DIN EN 13443-1) is to be used as ushing liquid. In order to ensure an unlimited operational reliability, ushing must remove all contami-nation and installation residue from the interior surfaces of the pipes and system components, estab-lished the quality of the tap water as well as inhibit corrosion damage and malfunctions of the ttings and components. In general two ush-ing methods can be used:

    Flushing with an air water mixture in accordance with DIN 1988-2

    This procedure be based on a pul-sating ow of water and air and is described in detail in the Tap water supply systems; materials, compo-nents, appliances, design and instal-lation (DVGW code of practice) DIN 1988-2 section 11.2. Suitable ushing equipment is to be used. This ushing procedure should be used if ushing with water is not expected to produce a suf cient ushing effect.

    Flushing with water

    If no other ushing method is con-tractually agreed upon or emanded, the Uponor tap water pipelines are to be ushed using the water

    method and local supply pressure. The procedure for the pipe line ushing is described in the ZVSHK brochure Notes on ushing meth-ods for tap water installations in accordance with TRWI 1988. This brochure can be obtained from the German Central Association of Plumbing, Heating and Climate-Control System Engineers (ZVSHK), Rathausstrasse 6, 53757 St. Augus-tin. Details and general information on ushing with water can be taken from the brochure. Under point 4.1 the brochure states:The pipes must be ushed as soon as possible after installation. The tap water used for the ushing must be ltered ( lter in accordance with DIN EN 13443-1). In order to pro-tect sensitive ttings (e.g. solenoid valves, ushing valve, thermostats etc.) and equipment (e.g. tap water heater) against damage from ushed foreign matter adaptors should be initially installed in place of such components. Such compo-nents should only be installed after the system has been ushed. Built in ne-meshed sieves installed in front of ttings that cannot be removed or bypassed are to be cleaned after ushing. Aerators, nozzles, ow limiters, shower heads or shower handsets must be removed from the remaining installed ttings during ushing. The manufacturers installation instructions are to be followed for concealed thermostats and other sensitive ttings that cannot be

    removed during ushing. All main-tenance ttings, oor shut-off valves and pre-shut-off valves (e.g. angle valves) must be fully opened. Possibly built-in pressure reducers must be fully opened and only be adjusted after ushing.

    Depending on the size of the sys-tem and the pipe routing, the installation can be ushed in sec-tions. In this case the ushing direc-tion and sequence should be from the main isolation valve in sections and branches (actual ush section) from the nearest to the furthest branch. One oor after the other is to be ush beginning at the ascend-ing pipe end. Within the story and single supply lines at least as many usage points speci ed as a guideline in the following table for a section being ushed are to be fully opened one after the other for at least 5 minutes. This is to be repeated for each story. Within the story the usage points, beginning with the usage point furthest away from the ascending pipe are to be fully opened. After a ushing period of 5 minutes at the ushing point last opened the usage points are closed one after the other in reverse order.

    For the Uponor Unipipe MLC pipe the following guidelines for the minimum number of usage points which are to be opened in relation to the largest inside diameter of the distribution conduit must be observed:

    Pipe dimensions OD x s [mm]of the distribution conduit in the actual section being ushed

    32 x 3 40 x 4 50 x 4.5 63 x 6 75 x 7.5 90 x 8.5 110 x 10

    Minimum number of usage points to be opened DN 15

    2 4 6 8 12 18 28

  • 25T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    MASTER

    Pressure test with water for tap water pipes

    Note: The chapter Pressure test of tap water installations in the actual technical manual MLCP system for tap water installation and radiator connection is to be followed.

    Construction project:

    Stage:

    Person carrying out the test:

    Test pressure = max. permissible operating pressure + 5 bar 15 bar(related to the lowest point of the system)

    All tanks, equipment and ttings, e.g. safety valve and expansion tanks, which are not suitable for the pressure test, must be removed from the system during the test period. The system is lled with ltered water and completely vented. A visual inspection of the pipe joints must be made during the test. After the test pressure has been reached a suitable time must elapse to allow for temperature equalisation between the ambient temperature and the temperature of the ll water. If necessary, the test pressure must be re-established after the waiting period.

    Preliminary test

    Begin: Test pressure:oclock,Date Time

    Re-establish the test pressure two times within 30 minutes at intervals of 10 minutes then wait 30 minutes and read the test pressure (max. pressure loss 0.6 bar).

    End: Test pressure:oclock,Date Time

    bar

    bar

    (max. pressure loss 0.6 bar!)

    Certi cation

    Test pressure:oclock,Date Time

    bar

    End: Test pressure:oclock,Date Time

    bar

    (max. pressure loss 0.2 bar!)

    No leakage was found in the above speci ed system during the preliminary or during the main test.

    Locality, date Signature/contractors stamp

    Locality, date Signature/contractors stamp

    Main test

    Begin:

  • 26 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Pressure test with compressed air or inert gas for tap water pipes

    Note: The chapter Pressure test of tap water installations in the actual technical manual MLCP system for tap water installation and radiator connection has to be followed.

    Construction project:

    Client represented by:

    Contractor/person responsibleSpecialist represented by:

    Connection type:

    Testing method for partial acceptance, for the nal inspection the pressure test in accordance with DIN 1988-2 must be run with water. Following the ZVSHK instruction lea et Leak testing of tap water installations with compressed air, inert gas or water.

    Locality, date Signature/contractors stamp

    Locality, date Signature/contractors stamp

    System pressure: bar

    Ambient temperature: C

    Test medium temperature: C

    All pipes are to be closed with metal screw plugs, caps, blanking plates or blind anges. Equipment, pressurized tanks or tap water heaters are to be separated from the pipes. A visual inspection of all pipe connections has been made in accordance with to good professional practice.

    Leak test

    Test pressure 110 mbarAt least 30 a minutes test period for pipe capacities up to 100 Litre For each additional 100 litres the test period is to be increased by 10 minutes

    Pipe capacity: Litre

    Test period: Minutes

    The test period was started after the temperature and steady-state condition was established.

    During the test period no pressure drop was found.

    Strength test with increased pressure

    Test pressure: Uponor pipe 63 x 6 mm max. 3 bar Uponor pipe > 63 x 6 mm max. 1 barAt least 30 a minutes test period for pipe capacities up to 100 Litre For each additional 100 litres the test period is to be increased by 10 minutes

    The test period was started after the temperature and steady-state condition was established.

    During the test period no pressure drop was found.

    The pipe system has no leaks.

    MASTER

    Test medium:

    Oil-free compressed air Nitrogen Carbon dioxide

    the tap water system was tested as

    complete system in stages

  • 27T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Ordinances and regulations, DIN standards

    The valid standards and regulations for sanitary facilities and installations are presented in the following table. Due to the number the applicable DIN standards, ordinances and regulations only the most important are listed.

    Standards and regulations Meaning

    a.R.d.T. In accordance with the generally accepted rules of technology

    ArbStattV/ASR Work place regulations and pertinent working place guidelines

    BGB 633 Liability for guaranteed quality

    DVGW German Technical and Scienti c Association on Gas and Water

    EnEV German Energy Saving Directive

    ETB Established technical building regulations

    HeimMindBauV Minimum building regulations for nursing homes

    HeizkostenV Regulation for heating expenses settlement

    II WoBauG Second National Housing Act

    LBO German state building regulations

    MBO Model building code

    MLAR Model pipe-conduit guidelines

    SBO Special building codes for special buildings and usage

    VOB/B and C General contract conditions for carrying out construction works, DIN 1961

    ZVSHK Central association of plumbing, heating and climatisation

    DIN 1053 Masonry design and construction

    DIN 1986-100 Drainage facilities for buildings and properties

    DIN 1988 Technical regulations for drinking-water installations (TWRI)

    DIN 2000 Guidelines for the central supply of tap water

    DIN 2001 Individual tap water supply

    DIN 4102 Fire protection in above-ground construction, re behaviour of building materials and building and components

    DIN 4109/A1 Sound protection in above ground construction

    DIN 4708 Central heating water installations

    DIN 4753 Water heaters and water heating installations for tap water and service water

    DIN 18022 Kitchens, baths and toilets in house construction

    DIN 18024 Barrier-free built environment

    DIN 18025 Barrier-free dwelling

    DIN 18180 Gypsum plasterboards - Types and requirements

    DIN 18181 Gypsum plasterboards in above-ground construction

    DIN 18183 Prefabricated gypsum plasterboard; metal stud partitions

    DIN 18195 Water-proo ng of buildings

    DIN 18202 Tolerances in building construction

    DIN 18381 VOB, part of C (ATV); Gas, water and sewage plumbing works inside of buildings

    DIN 18560 Floor screeds in building construction

    DIN EN 806 Speci cations for tap water installation (valid parallel to DIN 1988)

    DIN EN 832 Thermal performance of buildings - Calculation of energy use for heating

  • 28 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Calculations basis for tap water installations

    The planning of tap water installations is carried out in accordance with the calculation basis of DIN 1988 part 3: Technical regulations for tap-water installations (TRWI) pipe sizing (DVGW code of practice). Take product speci c data from the following diagrams and tables. Please also observe DVGW Worksheet W553: Dimensioning of circulation-systems in central tap water heating systems as well as the chapter on Circulation systems in this technical manual.

    Planning software Uponor HSE

    The Uponor Software HSE permits the comfortable graphic design of tap water pipelines pursuant to DIN 1988. No additional CAD program is required for working with HSE. You will nd further details about the software on page 52 in the chapter Planning software Uponor HSE in this technical manual.

    Standards and regulations Meaning

    DIN EN 1717 Protection against pollution of potable water installations and general require-ments of devices to prevent pollution by back ow

    DIN EN 12056 Gravity drainage systems inside buildings

    DIN V 4108-6 Thermal protection and energy economy in buildings application oriented requirements of heat-insulating materials

    DIN V 4108-10 Thermal protection and energy conservation in buildings - Factory made products

    DIN V 4701-10 Energy ef ciency of heating and ventilation systems in buildings - Heating, domestic hot water supply, ventilation

    VDI 6023 Hygiene for tap water supply systems - Requirements for planning, design, operation, and maintenance

    VDI 4100 Sound control in housing - Criteria for planning and assessment

  • 29T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Minimum ow pressures and ow velocity calculation of usage point ttings pursuant to DIN 1988-3P

    eak

    flow

    Total flow with flow calculation valid with flush valves

    with flow calculation valid with flushing tankR

    Type of the tap water usage point

    DN Minimum ow pressure

    With mixed water discharge in each case

    With discharge of cold or warm water

    PminFL [bar] Cold V.

    R [l/s] Warm V.

    R [l/s] V.

    R [l/s]

    Kitchen ttingsWash basin mixing tap DN 15 1 0.07 0.07 Household washing machine DN 15 1 0.25Household dishwasher DN 10 1 0.15Outlet valve with aerator DN 15 1 0.15

    Bath ttingsBath tub mixing tap DN 15 1 0.15 0.15 Shower mixing tap DN 15 1 0.15 0.15 Shower head DN 15 1 0.1 0.1 0.2Washbasin mixing tap DN 15 1 0.07 0.07 Bidet mixing tap DN 15 1 0.07 0.07

    WC ttingsFlushing cistern (according to DIN 19542) DN 15 0.5 0.13Flushing valve (according to DIN 3265) DN 15 1.2 0.7Flushing valve (according to DIN 3265) DN 20 0.4 1Flushing valve (according to DIN 3265) DN 25 1 1Flushing urinal DN 15 1 0.3

    Individual hot water tankElectrical boiler DN 15 1 0.1

    Special ttingsOutlet valve without aerator DN 15 0.5 0.3Outlet valve without aerator DN 20 0.5 0.5Outlet valve without aerator DN 25 0.5 1 Mixing tap DN 20 1 0.3 0.3

    If ttings are not listed follow the manufacturers speci cations!

    Characteristic Table

    For the calculation of the peak ow (V.s) from the total ow V

    .R for residential, of ce and administration buildings

    up to a total ow V.R 20 l/s.

  • 30 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Pipe friction tables

    Dimensioning of the stages (design tables)

    The selection of the pipe dimension for a stage can be determined using the following table or from the pressure drop diagram The required formulae for the dimensioning of the pipes, required minimum ow pressure and ow velocity calculation are to be taken from DIN 1988-3.

    However, in both cases the maximum ow rate and the available pipe friction resistance are to be observed. The following tables represent the pipe friction resistance and the ow rate as a function of the peak ow for chilled water (10 C).

    OD x s 14 x 2 mm 16 x 2 mm 18 x 2 mm 20 x 2.25 mm ID 10 mm 12 mm 14 mm 15.5 mm V/l 0.078 l/m 0.11 l/m 0.15 l/m 0.19 l/m V.s v R v R v R v R

    l/s m/s hPa/m m/s hPa/m m/s hPa/m m/s hPa/m

    0.01 0.13 0.51 0.09 0.22 0.06 0.11 0.05 0.07 0.02 0.25 1.61 0.18 0.69 0.13 0.34 0.11 0.21 0.03 0.38 3.19 0.27 1.36 0.19 0.66 0.16 0.41 0.04 0.51 5.21 0.35 2.21 0.26 1.07 0.21 0.66 0.05 0.64 7.62 0.44 3.23 0.32 1.56 0.26 0.97 0.06 0.76 10.43 0.53 4.41 0.39 2.13 0.32 1.32 0.07 0.89 13.59 0.62 5.75 0.45 2.78 0.37 1.72 0.08 1.02 17.12 0.71 7.23 0.52 3.49 0.42 2.16 0.09 1.15 20.99 0.80 8.86 0.58 4.28 0.48 1.91 0.10 1.27 25.20 0.88 10.63 0.65 5.13 0.53 3.17 0.15 1.91 51.07 1.33 21.49 0.97 10.35 0.79 6.39 0.20 2.55 84.56 1.77 35.52 1.30 17.08 1.06 10.54 0.25 3.18 125.23 2.21 52.55 1.62 25.24 1.32 15.56 0.30 3.82 172.79 2.65 72.43 1.95 34.76 1.59 21.41 0.35 4.46 227.01 3.09 95.07 2.27 45.59 1.85 28.07 0.40 5.09 287.69 3.54 120.39 2.60 57.70 2.12 35.52 0.45 5.73 354.68 3.98 148.33 2.92 71.05 2.38 43.72 0.50 6.37 427.86 4.42 178.83 3.25 85.62 2.65 52.67 0.55 7.00 507.11 4.86 211.85 3.57 101.38 2.91 62.35 0.60 5.31 247.33 3.90 118.31 3.18 72.74 0.65 5.75 285.24 4.22 136.40 3.44 83.84 0.70 6.19 325.56 4.55 155.63 3.71 95.64 0.75 6.63 368.25 4.87 175.98 3.97 108.13 0.80 7.07 413.27 5.20 197.44 4.24 121.29 0.85 5.52 219.99 4.50 135.12 0.90 5.85 243.63 4.77 149.62 0.95 6.17 268.35 5.03 164.77 1.00 6.50 294.13 5.30 180.57 1.05 6.82 320.97 5.56 197.02 1.10 7.15 348.86 5.83 214.11 1.15 6.09 231.84 1.20 6.36 250.19 1.25 6.62 269.17 1.30 6.89 288.77 1.35 7.15 308.99

    V.s = peak ow in litres/second in accordance with DIN 1988-3

    v = ow rate in meters/secondR = pipe friction resistance in hectopascal/meter (1 hPa = 1 mbar = 100 Pa, 1 hPa 10 mm wc)

  • 31T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    OD x s 25 x 2.5 mm 32 x 2 mm 40 x 4 mm 50 x 4.5 mm ID 20 mm 25 mm 32 mm 40 mm V/l 0.31 l/m 0.53 l/m 0.80 l/m 1.32 l/m V.s v R v R v R v R

    l/s m/s hPa/m m/s hPa/m m/s hPa/m m/s hPa/m

    0.10 0.32 0.95 0.19 0.28 0.12 0.10 0.08 0.03 0.20 0.64 3.15 0.38 0.91 0.25 0.34 0.15 0.11 0.30 0.95 6.38 0.57 1.84 0.37 0.69 0.23 0.21 0.40 1.27 10.55 0.75 3.03 0.50 1.13 0.30 0.35 0.50 1.59 15.62 0.94 4.48 0.62 1.67 0.38 0.52 0.60 1.91 21.55 1.13 6.17 0.75 2.30 0.45 0.71 0.70 2.23 28.30 1.32 8.10 0.87 3.01 0.53 0.93 0.80 2.55 35.86 1.51 10.25 0.99 3.81 0.61 1.17 0.90 2.86 44.20 1.70 12.63 1.12 4.69 0.68 1.44 1.00 3.18 53.30 1.88 15.22 1.24 5.65 0.76 1.73 1.10 3.50 63.16 2.07 18.02 1.37 6.69 0.83 2.05 1.20 3.82 73.76 2.26 21.03 1.49 7.80 0.91 2.39 1.30 4.14 85.08 2.45 24.24 1.62 8.99 0.98 2.76 1.40 4.46 97.12 2.64 27.66 1.74 10.25 1.06 3.14 1.50 4.77 109.88 2.83 31.28 1.87 11.59 1.14 3.55 1.60 5.09 123.33 3.01 35.09 1.99 13.00 1.21 3.98 1.70 3.20 39.10 2.11 14.48 1.29 4.43 1.80 3.39 43.30 2.24 16.03 1.36 4.90 1.90 3.58 47.69 2.36 17.65 1.44 5.40 2.00 3.77 52.27 2.49 19.34 1.51 5.91 2.10 3.96 57.04 2.61 21.10 1.59 6.45 2.20 4.14 61.99 2.74 22.92 1.67 7.00 2.30 4.33 67.13 2.86 24.82 1.74 7.58 2.40 4.52 72.45 2.98 26.78 1.82 8.18 2.50 4.71 77.96 3.11 28.81 1.89 8.79 2.60 4.90 83.64 3.23 30.90 1.97 9.43 2.70 5.09 89.50 3.36 33.06 2.05 10.09 2.80 3.48 35.28 2.12 10.76 2.90 3.61 37.57 2.20 11.46 3.00 3.73 39.93 2.27 12.17 3.50 4.35 52.65 2.65 16.04 4.00 4.97 66.93 3.03 20.37 4.50 5.60 82.73 3.41 25.17 5.00 3.79 30.41 5.50 4.17 36.09 6.00 4.54 42.22 6.50 4.92 48.77 7.00 5.30 55.74 7.50 5.68 63.13 8.00 6.06 70.94 8.50 6.44 79.16 9.00 6.82 87.78

    V.s = peak ow in litres/second according to DIN 1988-3

    v = ow rate in meters/secondR = pipe friction resistance in hectopascal/meter (1 hPa = 1 mbar = 100 Pa, 1 hPa 10 mm WS)

  • 32 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    OD x s 63 x 6 mm 75 x 7.5 mm 90 x 8.5 mm 110 x 10 mm ID 51 mm 60 mm 73 mm 90 mm V/l 2.04 l/m 2.83 l/m 4.18 l/m 6.36 l/m V.s v R v R v R v R

    l/s m/s hPa/m m/s hPa/m m/s hPa/m m/s hPa/m

    1.00 0.49 0.61 0.35 0.28 0.24 0.11 0.16 0.04 1.25 0.61 0.91 0.44 0.42 0.30 0.17 0.20 0.06 1.50 0.73 1.25 0.53 0.58 0.36 0.23 0.24 0.08 1.75 0.86 1.65 0.62 0.76 0.42 0.30 0.28 0.11 2.00 0.98 2.08 0.71 0.96 0.48 0.38 0.31 0.14 2.25 1.10 2.57 0.80 1.18 0.54 0.46 0.35 0.17 2.50 1.22 3.10 0.88 1.43 0.60 0.56 0.39 0.21 2.75 1.35 3.67 0.97 1.69 0.66 0.66 0.43 0.24 3.00 1.47 4.28 1.06 1.97 0.72 0.77 0.47 0.28 3.25 1.59 4.94 1.15 2.27 0.78 0.89 0.51 0.33 3.50 1.71 5.64 1.24 2.59 0.84 1.01 0.55 0.37 3.75 1.84 6.38 1.33 2.93 0.90 1.15 0.59 0.42 4.00 1.96 7.16 1.41 3.29 0.96 1.29 0.63 0.47 4.25 2.08 7.98 1.50 3.66 1.02 1.43 0.67 0.53 4.50 2.20 8.84 1.59 4.06 1.08 1.59 0.71 0.58 4.75 2.33 9.73 1.68 4.47 1.13 1.75 0.75 0.64 5.00 2.45 10.67 1.77 4.90 1.19 1.92 0.79 0.70 6.00 2.94 14.80 2.12 6.79 1.43 2.65 0.94 0.97 7.00 3.43 19.53 2.48 8.95 1.67 3.49 1.10 1.28 8.00 3.92 24.84 2.83 11.38 1.91 4.44 1.26 1.63 9.00 4.41 30.71 3.18 14.07 2.15 5.49 1.41 2.01 10.00 4.90 37.15 3.54 17.01 2.39 6.63 1.57 2.43 11.00 5.38 44.13 3.89 20.20 2.63 7.87 1.73 2.88 12.00 4.24 23.63 2.87 9.21 1.89 3.37 13.00 4.60 27.31 3.11 10.63 2.04 3.89 14.00 4.95 31.23 3.34 12.16 2.20 4.45 15.00 5.31 35.38 3.58 13.77 2.36 5.03 16.00 5.66 39.77 3.82 15.47 2.52 5.65 17.00 6.01 44.39 4.06 17.27 2.67 6.31 18.00 4.30 19.15 2.83 6.99 19.00 4.54 21.12 2.99 7.71 20.00 4.78 23.17 3.14 8.46 21.00 5.02 25.31 3.30 9.24 22.00 5.26 27.54 3.46 10.05 23.00 5.50 29.86 3.62 10.89 24.00 5.73 32.25 3.77 11.77 25.00 3.93 12.67 26.00 4.09 13.60 27.00 4.24 14.57 28.00 4.40 15.56 29.00 4.56 16.58 30.00 4.72 17.63

    V.s = peak ow in litres/second in accordance with DIN 1988-3

    v = ow rate in meters/secondR = pipe friction resistance in hectopascal/meter (1 hPa = 1 mbar = 100 Pa, 1 hPa 10 mm WS)

  • 33T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Pressure-loss graph

    The pressure pressure-loss graph contains the pipe characteristics for the various dimensions of Uponor Unipipe MLC pipes as well as the ow rate limits.

    The friction head per meter in relation to the pipe dimension and the ow rate can be simply read from the diagram given the volume ow or discharge.

    Pipe friction resistance - Uponor Unipipe MLC pipeWater, mean temperature 10 C

    v = 0,1 m/s

    Peak flow Vs [l/s]

    Pip

    e fr

    icti

    on r

    esis

    tanc

    e R

    [hP

    a/m

    ]

    1.000,0

    100,0

    10,0

    1,0

    0,10,01 0,1 1,0 10,0 100,0

  • 34 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    One system for all radiators

    The Uponor MLCP radiator con-nection system allows you to install complete heating systems from the heat generator to the furthest radiator fast and economically. The program can be combined without problems with all boilers and radiators offered on the market.

    Convince yourself of the variety of the Uponor MLCP system with its components for house or story orientated distribution, control and temperature measurement. Exten-sive accessories round off the assortment.

    Radiator connection with the Uponor MLCP system

    Variety of connections

    The system for connecting radiators is a complete system containing many components. This opens up various connection possibilities. They are suitable for single or double pipe connections and can be quickly and securely connected to all common radiators, whether directly out of the oor or wall. The plus of exibility: You can use any pipe installation method.

  • 35T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Radiator connection set

    The Uponor radiator connection set not only facilitates the installation for you. It also protects the pipe against damage in the screed as well as providing for a visually clean spacing guide.

    Radiator connection unit

    Pressure testing of the system is possible before installing the radia-tors. The preformed Uponor Uni-pipe MLC pipe in the insulation box is simply inserted into the wall and connected with the radiator or the distribution conduits. The radiator can simply be mounted at a later time. The installation of the con-nection is made in the wall. Your bene t: a visually clean connection and installation of the radiator.

    Press connection T-piece

    With the press connection T-piece you can connect the radiator using coated copper pipes. This ensures a stable construction for everyday use. This variation is used if no wall connection is possible.

    Your plus

    Practical radiator connection variations for new construction as well as renovation

    Absolutely oxygen diffusion tight multi-layer composite pipe

    Pre-insulated multi-layer composite pipes and components

    Extensive assortment of ttings

    Extensive accessory program

  • 36 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    The high resilience of Uponor Unipipe MLCP makes it especially suitable for heating installations:

    Maximal temperature: 95 C* Maximum continuous operating

    pressure: 10 bar at a continuous operation temperature of 70 C, tested hydrostatic stress per-formance of 50 years, safety factor 1.5*

    * Please contact the manufacturer if you require additional explanation of the installation parameters.

    Fields of application

    All heating system components can be connected using the high-quality Uponor Unipipe MLC pipes with an outside diameter of 14-32 mm in coils and 16-110 mm in straight lenghts together with suitable system components such as press and screw ttings. The possibility of supplying over-sized pipe dimensions of up to OD = 110 mm permits their use as cellar distribution and house connection lines in larger heating systems. The Uponor MLCP system can be used from the heat generator over the distribution conduits and house connection lines up to the connec-tion to the heat consumer.

    Planning basis for radiator connection

    Caution:Uponor Unipipe MLC pipes may not be directly connected to systems with operating temperatures 95 C, such as solar or district heating systems. It must be ensured that the operational limits of the Uponor pipe are not exceeded under any conditions.

    With the following methods you can realize trouble-free heating water distribution using the Uponor MLCP system:

    Single-pipe heating system Double-pipe heating system Tichelmann system

    With a single-pipe heating system all radiators of a heating circuit are connected to a closed ring loop.

    In this case ring loops are con-nected directly by a T-piece to the house connection lines of the heat generator. If there are several ring loops, these can be connected to the Uponor heater distributor. The distributor is in turn connected to the house connection line of the heat generator.

    As a rule, the adjustment of single-pipe heating systems is usually complex. With a single-pipe heating system the temperature gradient between the radiators, i.e. the decreasing supply temperature from radiator to radiator, must be considered when dimensioning the heating element in the form of an area surcharge.

    Bene ts are a result of lower material and assembly costs.

    Installation possibilities Single-pipe heating system

  • 37T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    The double-pipe heating system with its variations for the single and multi-family dwelling sectors is particularly suitable for low-tem-perature heaters. With this installa-

    tion variation the radiators are connected to the supply and return. All radiators have approxi-mately the same supply tempera-ture. A bene t is the fast and easy

    adjustment of the double-pipe heating system.

    Double-pipe heating system with manifold

    With this installation variation the heating water distribution is con-nected to the radiators by means of single inlets from a central mani-fold. The Uponor manifold is in turn connected to the house connection line of the heat generator.

    Double-pipe heating system with tee connection and cross tting

    Beginning from the house connec-tion line, the heating water distri-bution is made by a common ring loop. If the ring loop runs directly by the radiator, the radiator con-nection can be made with a press connection tee. The last radiator of the ring loop is connected by an Uponor press angle bracket. If the radiator is connected over a single inlet to the ring loop, the use of a cross tting is recommended.

    Tichelmann system

    In the Tichelmann system the pipes are arranged in such a way that the sum of the length of supply and

    return for each radiator is approxi-mate equal. That means that the radiator with the longest supply has

    the shortest return. Thus a more uniform pressure drop in the individual stages is achieved.

    Installation possibilities Double-pipe heating system

  • 38 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Connection variations with the Uponor MLCP system

    All descriptions are without insulation; insulation must be installed in accordance with the German Energy Saving Directive (see section Thermal protection starting from page 57).

    Connection possibilities of the double-pipe heating system with distribution systemRadiator connections from bottom and side.

    Bene ts: Simple planning Simple pressure drop determination and dimensioning Lower pressure-loss No connection points required in the oor Only a few mouldings are required Large number of possible connection variations

    Connection of a radiator by means of a con-nection tting or with a wall mounted press connection.

    Connection of a radiator with a wall mounted Uponor MLC press connection elbow.

    Connection of a thermostat controlled radia-tor with a wall mounted Uponor MLC press angle bracket.

    Connection of a thermostat controlled radia-tor by means of a wall mounted Uponor MLC compression adapter.

    Connection of a thermostat controlled radia-tor by means of a 35/50 mm mounting brack-et, Uponor MLC press tap elbow and a con-nection pipe coming from the wall.

    Connection of a thermostat-controlled radia-tor with a wall mounted Uponor MLC radiator connection unit.

  • 39T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Connection of a radiator with a oor mounted Uponor press connection elbow.

    Connection of a thermostat-controlled radiator by means of an Uponor MLC com-pression adapter and an Uponor radiator connection set.

    Connection of a thermostat-controlled radia-tor with a oor mounted Uponor MLC press connection elbow.

    Connection possibilities of the double-pipe heating system over a T-piece distributionRadiator connections from below.

    Bene ts: Simple planning Crossing-free radiator connections through use of cross ttings Large number of possible radiator connection variations All radiators with the same supply temperature

    Connection of a thermostat-controlled radia-tor with oor mounted Uponor MLC press connection tee.

    Connection of a radiator with oor mounted Uponor MLC press connection tee.

    Connection of a thermostat-controlled radia-tor with a wall mounted Uponor MLC radiator connection unit. Connection of the connect-ing pipe to the distribution conduit by means of Uponor MLC cross tting.

  • 40 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Connection possibilities of the double-pipe heating system from the baseboardRadiator connections from below.

    Bene ts: Ideal for modernization and restoration Little dirt, as very little cutting work is necessary Short installation time No re risk from welding and soldering when modernizing existing buildings Simple planning All radiators with the same supply temperature

    Connection of a thermostat-controlled radia-tor with the Uponor MLC press SL connection set and an Uponor SL angle.

    Connection of a thermostat-controlled radia-tor with the Uponor MLC press SL connection set and an Uponor SL bend.

    Connection possibilities of the single-pipe heating system with ring loopRadiator connections from below.

    Bene ts: Short pipe length Few ttings

    Connection of a radiator and a single-pipe valve set by means of a Uponor MLC com-pression adapter coming from the oor.

    Connection of a thermostat-controlled radia-tor and a single-pipe connection block with a oor mounted Uponor MLC press connection elbow.

  • 41T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Pressure testing for the radiator installation

    Pressure test for radiator installation in accordance with DIN 18380

    The following procedure describes the pressure test for the Uponor MLCP system with screw or press connections.

    The heating engineer/plumber has to perform a leak test on the heater pipes after installation and before closing wall slits, wall and oor breakthroughs as well as, if neces-sary, before the screed or other covering is laid.

    The heating system is to be lled slowly and completely vented (protect against frost!). This can be done quickly and with little effort with the Uponor pressure test plug. Water heaters are to be checked with a pressure of 1.3 x the total

    pressure (static pressure) of the system; however, at least 1 bar excess pressure must be reached throughout the system. Only pressure meters may be used that permit the accurate reading of a 0.1 bar pressure change. The pressure meter is to be connected, if possible, to the lowest point of the system.

    After the test pressure has been reached a suitable time must elapse to allow for temperature equalisa-tion between the ambient tempera-ture and the temperature of the ll water. If necessary, the test pres-sure must be re-established after the waiting period.

    The test pressure must be main-tained for 2 hours and may not drop by more than 0.2 bar. No leakages may appear during this time. As soon as possible after the cold water pressure test the system is heated to the highest calculated heating water temperature to check whether the system also remains leak-free at high temperature. After the system cools down the heating pipes and connections are to be checked for leaks.

  • 42 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    MASTER

    Pressure test report for the radiator installation

    Note: The chapter Pressure test of radiator installations in the actual technical manual MLCP system for tap water installation and radiator connection is to be followed

    Construction project:

    Stage:

    Person carrying out the test:

    maximum permissible operating pressure (in relation to the lowest point of the system). bar

    System altitude: m

    Design parameter Supply temperature: C Return temperature: C

    After the test pressure has been reached, a suitable time must elapse to allow for temperature equalisation between the ambient temperature and the temperature of the ll water. If necessary, the test pressure must be re-established after the waiting period.

    All tanks, equipment and ttings, e.g. safety valve and expansion tanks, which are not suitable for the pressure test, must be removed from the system during the test period. The system is lled with ltered water and completely vented. During the test a visual inspection of the pipe connections must be made.

    Begin: , oclock Test pressure: bar Date Time

    End: , oclock Pressure loss: bar Date Time (max. 0,2 bar!)

    The system speci ed above was heated to the design temperatures on and no leakage was found There was also no leakage found after the cooling. With frost danger suitable measures are to be taken (e.g. use of antifreeze, heating of the building). If no freeze protection is required for the intended system use, the antifreeze is to be removed by emptying and ushing the system with at least 3 water changes.

    Antifreeze was added to the water: Yes No

    Drainage as stated above: Yes No

    Certi cation

    Owner - date/signature Owner - date/signature

    Plumber - date/signature

  • 43T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Ordinances and regulations, DIN standards

    The valid standards and regulations for the installation of heating systems are presented the following table. Due to the number the applicable DIN standards, ordinances and regulations only the most important are listed, particularly in the area of pipe installation.

    Standards and regulations Meaning

    a.R.d.T. In accordance with the generally accepted rules of technology

    EnEV German Energy Saving Directive 2002

    ETB Established technical building regulations

    HeizkostenV Regulation for heating expenses settlement

    LBO State building regulations

    MBO Model building code

    MLAR Model pipe-conduit guidelines

    VOB/B and C General contract conditions for carrying out construction works, DIN 1961

    ISO 10508 Plastics piping systems for hot and cold water installations

    DIN 1053 Masonry

    DIN 4102 Fire protection in above ground construction

    DIN 4108 Thermal insulation in above ground construction

    DIN 4109 Sound protection in above ground construction

    DIN 4751 hot-water space heating system

    DIN 18380 VOB-C (ATV); Heating systems and central water heating installations

    DIN 18560 Floor screeds in building construction

    DIN EN 832 Thermal performance of buildings - Calculation of energy use for heating

    DIN EN 12828 Heating systems in buildings - Design of water-based heating systems

    DIN EN 12831 Heating systems in buildings - Method for calculation of the design heat load

    DIN EN 12831 Heating systems in buildings - Method for calculation of the design heat load

    Supplement 1 National appendix NA

    DIN EN 14336 Heating systems in buildings - Installation and commissioning of water based heating systems

    DIN V 4108-10 Thermal protection and energy conservation in buildings - Application-related requirements for thermal insulation materials

    DIN V 4108-6 Thermal protection and energy conservation in buildings - Calculation of annual heat and energy use

    DIN V 4701-10 Energy ef ciency of heating and ventilation systems in buildings - Heating, domestic hot water supply, ventilation

    VDI 4100 Sound control in housing - Criteria for planning and assessment

  • 44 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Calculation basis for radiator connection

    Pressure-loss graph

    The pressure drop diagram contains the pipe characteristics for the Up-onor Unipipe MLC pipe in the vari-ous dimensions as well as the ow rate limits.

    Out

    put

    Q in

    kW

    at

    T =

    5 K

    T =

    10

    K

    T =

    15

    K

    T =

    20

    KM

    ass

    flow

    rat

    em

    in k

    g/h

    Pip

    e fr

    icti

    on r

    esis

    tanc

    e R

    in P

    a/m

    Pipe friction resistance as a function of the mass ow rate at a mean water temperature of 60 C

  • 45T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    Pipe friction resistance as a function of the mass ow rate at a mean water temperature of 60 C

    Out

    put

    Q in

    kW

    at

    T =

    5 K

    T =

    10

    K

    T =

    15

    K

    T =

    20

    KM

    ass

    flow

    rat

    em

    in k

    g/h

    Pip

    e fr

    icti

    on r

    esis

    tanc

    e R

    in P

    a/m

  • 46 T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    OD x s 14 x 2 mm 16 x 2 mm 18 x 2 mmID 10 mm 12 mm 14 mmV/l 0.08 l/m 0.11 l/m 0.15 l/mQ m v R v R v RW kg/h m/s Pa/m m/s Pa/m m/s Pa/m

    200 9 0.03 3 0.02 1 0.02 1400 17 0.06 11 0.04 5 0.03 2600 26 0.09 21 0.06 9 0.05 4800 34 0.12 34 0.09 15 0.06 71000 43 0.15 50 0.11 21 0.08 101200 52 0.19 68 0.13 29 0.09 141400 60 0.22 89 0.15 38 0.11 181600 69 0.25 112 0.17 47 0.13 231800 78 0.28 137 0.19 58 0.14 282000 86 0.31 164 0.22 69 0.16 342200 95 0.34 194 0.24 82 0.17 402400 103 0.37 225 0.26 95 0.19 462600 112 0.40 258 0.28 109 0.21 532800 121 0.43 294 0.30 124 0.22 603000 129 0.46 331 0.32 140 0.24 673200 138 0.50 370 0.34 156 0.25 753400 146 0.53 411 0.37 173 0.27 843600 155 0.56 454 0.39 192 0.28 923800 164 0.59 499 0.41 210 0.30 1014000 172 0.62 546 0.43 230 0.32 1114200 181 0.65 595 0.45 250 0.33 1214400 189 0.68 645 0.47 271 0.35 1314600 198 0.71 697 0.50 293 0.36 1414800 207 0.74 751 0.52 316 0.38 1525000 215 0.77 807 0.54 339 0.40 1635200 224 0.81 864 0.56 363 0.41 1755400 233 0.84 923 0.58 388 0.43 1875600 241 0.87 984 0.60 414 0.44 1995800 250 0.90 1046 0.62 440 0.46 2116000 258 0.93 1111 0.65 467 0.47 2246200 267 0.96 1177 0.67 494 0.49 2386400 276 0.99 1244 0.69 522 0.51 2516600 284 1.02 1313 0.71 551 0.52 2656800 293 0.73 581 0.54 2797000 301 0.75 611 0.55 2947500 323 0.81 690 0.59 3318000 344 0.86 773 0.63 3718500 366 0.91 860 0.67 4139000 388 0.97 951 0.71 4569500 409 1.02 1046 0.75 50210000 431 0.79 54910500 452 0.83 59911000 474 0.87 65011500 495 0.91 70312000 517 0.95 75812500 538 0.99 81413000 560 1.03 87313500 581 1.07 93314000 603 1.11 99514500 624 1.15 1059

    Q = power in Watt v = ow rate in meters/second R = pipe friction resistance in pascal/meter (100 Pa = 1 hPa = 1 mbar, 1 hPa ~ 10 mm wc)

    Pipe friction tables

    Pipe friction table, heating T = 20 K (70 C/50 C)

    Pipe friction resistance for water as a function of warming or mass ow rate at a mean water temperature of 60 C and a spread of T = 20 K (70 C/50 C)

    Note: You can nd additional pipe friction tables for other operating temperatures available for download under www.uponor.de

  • 47T E C H N I C A L I N F O R M A T I O N M L C P S Y S T E M 0 8 / 2 0 0 7

    OD x s 20 x 2.25 mm 25 x 2.5 mm 32 x 3 mmID 15.5 mm 20 mm 26 mmV/l 0.19 l/m 0.31 l/m 0.53 l/mQ m v R v R v RW kg/h m/s Pa/m m/s Pa/m m/s Pa/m

    1000 43 0.06 6 0.04 2 0.02 12000 86 0.13 21 0.08 6 0.05 23000 129 0.19 42 0.12 13 0.07 44000 172 0.26 68 0.15 21 0.09 65000 215 0.32 101 0.19 30 0.11 96000 258 0.39 138 0.23 41 0.14 127000 301 0.45 181 0.27 54 0.16 168000 344 0.52 229 0.31 68 0.18 209000 388 0.58 281 0.35 84 0.21 2410000 431 0.64 338 0.39 101 0.23 2911000 474 0.71 400 0.43 119 0.25 3412000 517 0.77 466 0.46 139 0.28 4013000 560 0.84 537 0.50 160 0.30 4614000 603 0.90 612 0.54 182 0.32 521