SCHEDULE-A2

CEG/GP-2/5253B

TECHNICAL SPECIFICATION

OF CABLES

FOR POWER STATIONS

Installed

Page 2: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

I N D E X

CLAUSE NO. TITLE Special Instruction to Bidder Qualifying Requirement of Bidder SCHEDULE-B Technical specification for Control and

L.T./H.T. Power Cables 1.0 Scope 2.0 Standards 3.0 Climatic Conditions 4.0 General Technical/Principal Parameters 5.0 Physical Constants of Materials 6.0 Physical Constants for Galvanized Steel Wires 7.0 Freedom from Defects 8.0 Wire Sizes 9.0 Joints in Wires

10.0 Stranding 11.0 Standard Length 12.0 Operation 13.0 Tests 14.0 Type Tests 15.0 Acceptance Tests 16.0 Routine Tests 17.0 Test During Manufacture 18.0 Testing Charges 19.0 Additional Charges 20.0 Sample Batch for Type Testing 21.0 Test Reports 22.0 Test Facilities 23.0 Inspection 24.0 Quality Assurance Plan 25.0 Documentation 26.0 Packaging and Forwarding 27.0 Marking 28.0 Quantity and Delivery Requirement 29.0 Drawing 30.0 Deviations

ANNEXURE-I System Particulars

Page 3: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE-B1 GTP for Telephone Cable

SCHEDULE-B2(1) GTP for Trailing Cable (LT) SCHEDULE-B2(2) GTP for Trailing Cable (HT)

SCHEDULE-B3 GTP for Control Cable (1.5 mm2) SCHEDULE-B4 GTP for Flexible Cable SCHEDULE-B5 GTP for Flat and Flat/Flexible Cable SCHEDULE-B6 GTP for Other Types Cable

SCHEDULE-B8(1) GTP for LT Cable (3 Core)(PVC Insulation) SCHEDULE-B8(2) GTP for LT Cable (3 Core)(XLPE Insulation) SCHEDULE-B9(1) GTP for LT Cable (3½ Core)(PVC Insulation) SCHEDULE-B9(2) GTP for LT Cable (3½ Core)(XLPE Insulation) SCHEDULE-B10 GTP for Control Cable (2.5 mm2) SCHEDULE-B11 GTP for Heat Resistance Cable SCHEDULE-B12 GTP for Optic Fiber Cable SCHEDULE-B13 GTP for Power Cable for Excitation System SCHEDULE-B14 GTP for Instrument Cable SCHEDULE-C1 GTP for Telephone Cable - to be filled by bidder

SCHEDULE-C2(1) GTP for Trailing Cable(LT)- to be filled by bidder SCHEDULE-C2(2) GTP for Trailing Cable(HT) - to be filled by bidder

SCHEDULE-C3 GTP for Control Cable (1.5 mm2) - to be filled by bidder

SCHEDULE-C4 GTP for Flexible Cable - to be filled by bidder SCHEDULE-C5 GTP for Flat and Flat/Flexible Cable - to be filled by

bidder SCHEDULE-C6 GTP for Other Types Cable - to be filled by bidder

SCHEDULE-C8(1) GTP for LT Cable (3 Core)(PVC Insulation) - to be filled by bidder

SCHEDULE-C8(2) GTP for LT Cable (3 Core)(XLPE Insulation) - to be filled by bidder

SCHEDULE-C9(1) GTP for LT Cable (3½ Core )(PVC Insulation) - to be filled by bidder

SCHEDULE-C9(2) GTP for LT Cable (3½ Core )(XLPE Insulation) - to be filled by bidder

SCHEDULE-C10 GTP for Control Cable (2.5 mm2) - to be filled by bidder

SCHEDULE-C11 GTP for Heat Resistance Cable - to be filled by bidder SCHEDULE-C12 GTP for Optic Fiber Cable - to be filled by bidder SCHEDULE-C13 GTP for Power Cable for Excitation System - to be filled

by bidder SCHEDULE-C14 GTP for Instrument Cable - to be filled by bidder

(This document is meant for exclusive purpose of bidding against this

specification and shall not transfer, reproduced or otherwise used for purposes other than that for which it is specifically issued.)

Page 4: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before submitting your bid: 1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in

AutoCAD format and manuals in PDF format, for offered item shall be submitted. Also the hard copies as per specification shall be submitted.

2. The bidder shall submit Quality Assurance Plan with the technical bid. 3. The bidder shall have to submit all the required type test reports for the offered

item. Bid without type tests will not be considered for evaluation. 4. The bidder must fill up all the points of GTP for offered item/s. Instead of

indicating “refer drawing, or as per IS/IEC”, the exact value/s must be filled in. 5. All the points other than GTP, which are asked to confirm in technical

specifications must be submitted separately with the bid. 6. The bidder is required to impart training in view of manufacture, assembly,

erection, operation and maintenance for offered item, at his works, to the person/s identified by GSECL, in the event of an order, free of cost. The cost of logistics will be bear by GSECL.

7. Please note that the evaluation will be carried out on the strength of content of bid only. No further correspondence will be made.

8. The bidder shall bring out all the technical deviation/s only at the specified

annexure.

Page 5: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

QUALIFYING REQUIREMENT FOR BIDDER Bidder to satisfy all the following requirements- 1. The Bidders should be original manufacturer of the quoted size of the cables

and shall have all the facilities to manufacture these sizes and higher sizes of control and / or power cables as the case may be. Traders are not eligible for participating in this Tender.

2. The Bidders have to submit proof of the satisfactory completion of order for supply of quoted sizes of the cables for the quantity not less than 300 Kms during last five years of total of all the sizes of control cables from utilities like State Electricity Corporations, NTPC, PGCIL. Any Technical offer without this certificate will be out rightly rejected. The proof means the Purchaser’s certificate of completing the supply within the stipulated time limit for the ordered quantity. However the total quantity supplied shall not be less than the one stated above (i.e. 300 Kms).

The details are to be submitted in following format: Sr. No

ITEMS SUPP- LIED TO

ORDER REFEREN CE No. & DATE

ITEMS QTY ORDER FULLY EXECUTED. YES/NO

STATUS, IF ORDER UNDER EXECUTION

REMARK

3. The cables offered must bear ISI mark. The Bidder shall invariably submit the attested copy of ISI certificate. Any cables without this mark will be out rightly rejected. The cables will be accepted only from the works, name and address of which is indicated in the offer.

4. All the bids shall comprise the copy of type test reports, of any of the quoted size, which shall not be later than five years from the date of opening of the Tender. However GSECL reserves the right to ask any or all the suppliers to carry out the Type Test at the Government Approved Testing Laboratory on the ordered size/s. The GSECL reserves the right to indicate the name of the NABL accredited Testing Lab at his own discretion and the Supplier will have to carry out the Type Tests in the designated laboratory at his own cost.

5. The quantity of each size offered shall be indicated clearly in the Technical Bid. The Bid will be out rightly rejected if this clause is not found clear.

6. This Specification shall be signed page to page without any addition / alteration and shall be submitted with the Technical Bid. Any offer without this will be out rightly rejected.

Page 6: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – B

TECHNICAL SPECIFICATION FOR CONTROL AND L.T. /H.T. POWER CABLES 1.0 SCOPE:

1.1 This specification provides for design, manufacture, testing, inspection,

packing and dispatch to destination of Copper Cored Control Cables and Aluminium cored HT / LT Power Cables, specified herein for their satisfactory operation in various Power stations of the State. Preparation of Drum drawings and getting it approved from C.E.-GSECL, Corporate Office, Vadodara.

1.2 These cables are to be used as control signal carrying cables or power carrying cables, as the case may be, in various Power stations of the Gujarat State situated in various areas having varying atmospheric conditions, for voltage ratings up to 400KV, from various equipments situated in Plant area, Control rooms, switchyard etc.

1.3 These cables are generally used under ground either in the cable trenches with no. of layers as per requirement covered with the cement covers or in the pipes installed under ground and then pits filled with the soil.

2.0 STANDARDS: 2.1 The Control, Power, Telephone and Trailing cables shall conform to the

following Indian / International Standards, which shall mean latest revisions, amendments / changes adopted and / or published as on the date of opening of the Tender.

Sr. No. Indian Standards Title

1 IS : 1554 For Cables up to working voltage 1100 V 2 IS : 7098 For XLPE Cables 3 IS : 5831 For Insulation Sheath 4 IS : 8130 For Copper And Aluminium Conductor 5 IS : 10418 For Wooden Drums 6 IS : 3975 For Armouring 7 IS : 3961 For Current Rating 8 IS : 9968 For Trailing Cables 9 IEC :189 / BS : 5308 For Instrument Cables 9 ITD: GR/CUG-01/03,

Aug-2003. For Telephone Cable

10 IEC-754, 332, ASTM D-2863, 2543

For FRLS Properties

2.2 Over and above, any other standards which are relevant may be quoted

by the bidder. However, in an event where the supplier offers Control and / or power cables conforming to standards other than the above, then the salient points of comparison between the standards adopted and the standards quoted herein shall be detailed in relevant schedule with an authenticated English version of such standards referred to.

Page 7: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

GSECL also reserves right to ask any supplier to supply the control / power cables related to any other IS or International Standards which may be found to give better quality and performance of the cables.

3.0 CLIMATIC CONDITIONS: 3.1 The cables to be supplied under these Specifications are to be used in

various Power Stations of the Gujarat State, located at different locations having varying atmospheric and climatic conditions and are suppose to operate satisfactorily under any conditions.

3.2 However the General conditions are given as under:

1 Location In the State of Gujarat as per Annexure-I

2 Maximum Ambient Air Temperature -(C) 50 3 Minimum Ambient Air Temperature -(C) 0 4 Average daily ambient Air Temperature -(C) 35 5 Maximum relative humidity – (%) 95 6 Average rainfall per annum -(mm) 1150 7 Maximum altitude above mean sea level -

(mtr) 1000

8 Ceraunic level i.e. Average number of Thunder storm -(Days/annum)

15

9 Maximum wind pressure -(KG/m2) 200 10 Seismic level i.e. Earthquake Acceleration

a) Horizontal Seismic Co-efficient (acceleration) – g (Equivalent to zone – 5)

b) Vertical Seismic Co-efficient (acceleration) – g (Equivalent to zone – 5)

(a) 0.3 (b)0.34

11 Terrain Hot, Humid, Tropical, Highly Polluted, Conductive, Corrosive, Prone to Fungus Growth etc

4.0 GENERAL TECHNICAL / PRINCIPAL PARAMETERS:(SCHEDULE: B1-TO-B13): 4.1 CONTROL / LT CABLES: (1) The control cables shall be round copper conductor (of required size) with

PVC insulation, armouring and sheath, color coded as per relevant standards or as specified / instructed by the GSECL.

(2) The LT Power cables shall be of aluminium conductor (of required size) PVC insulated, armouring and PVC sheathed, colour coded as per relevant standards or as specified / instructed by the GSECL.

Page 8: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

(3) The control cables shall be rated for minimum 1100 V and LT Power cables for minimum 6600 V, however Bidder may quote for higher voltage ratings, which shall be clearly brought out in the Technical Bid.

(4) All the cables quoted / supplied shall bear ISI mark. (5) The insulation of each core and outer and inner sheath, shall comply with

the relevant IS / this Specification, whichever is stringent, for control and / or power cables.

(6) All the armouring shall be strip / round wire type, hot dip galvanized. The armouring and galvanizing shall comply with relevant standards and or this Specification shall also bear ISI mark.

(7) The copper conductor used shall be electrolytic grade annealed and shall be made of minimum 99.5% pure copper, thus the total impurities shall not exceed 0.5%. The Aluminium conductor shall be of EC Grade 99.5% pure aluminium and thus the total impurities in this case also shall not exceed 0.5%. Both the copper and aluminium shall possess ISI mark.

(8) If the conductor is a bought out item or manufactured by the supplier, the proof to satisfy the above conditions shall be produced.

(9) Current Rating: The indicative values of continuous current carrying capacities at Maximum conductor temperature of 70º C (for design purpose by field) of the various sizes of the cables are given in GTP. Short circuit ratings of various sizes cable calculated for duration of one second at maximum temperature of 160º C, are given in GTP.

(10) The cables shall be suitable for being installed directly in the ground, in the pipes or in the cable trays/trenches. The cables shall therefore be suitable for satisfactory operation under the tropical climatic conditions listed in the relevant clause. The applicable design particular of the cables to be used in the Power Stations is furnished in Annexure - I. "System Particulars".

4.2 HT CABLE: (1) 11 KV (E) Grade XLPE, 3-Core, power cable shall be of high conductivity,

stranded compacted, H.D. aluminum circular shaped conductor with XLPE (Cross Linked Poly Ethylene) Dry/Gas cured insulation provided with shielding of extruded semi-conducting materials over conductor and XLPE insulation. Each insulated core shall have copper tape screen, laid together and provided with common covering of PVC Inner Sheath (Extruded). Overall galvanized steel strip armour and PVC outer sheath shall be provided. The specification for manufacture of cable shall be conforming to IS: 7098 (Part-II) 1985 (latest edition) for 11KV (E), 3-phase, 50 Hz, Earthed systems.

(2) Outer sheath shall be designed to afford high degree of mechanical protection and shall also be heat, oil, chemical and weather resistant, Common acid, alkalis and sealing solution shall not have adverse effect on material of PVC sheath.

(3) The cable conductor shall be made from high conductivity stranded High Density aluminum to form compacted circular shaped conductor having resistance within limits specified in IS: 8130/1984 and any latest amendment to it.

Page 9: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

(4) The conductor having semi-conducing screen shall ensure perfectly smooth profile and avoid concentration of stress. The conductor screen shall be extruded in the same operation as the insulation. The semi-conducting polymer shall be cross linked.

(5) Cable Parameters:

1 Voltage grade (Uo / U)- KV 6.35 / 11 2 Cores (Nos) 3 3 Nominal system voltage -KV 11 4 Highest system voltage -KV 12 5 System frequency- Hz 50 6 Variation in frequency -% ± 3 7 Maximum allowable temp. of conductor during

continuous normal operation at rated full load current - ºC 90 º C

8 Maximum allowable temp. under short circuit condition-ºC 250 º C 9 1.2/50 microsecond lightning impulse withstands voltage

wave value - KVp 75

10 5 Min, Power frequency withstand voltage -KV rms 17 11 System earthling Effectively

earthed. (6) The XLPE insulation shall be suitable for 11 / 22 kV system voltage and

should be manufactured with Dry / Gas curing process. The bidder shall submit the description of dry / gas curing process, with the clear inclusion of equipments / parameters involved. The manufacturing process shall ensure that the insulation shall be free of voids. The insulation shall withstand mechanical and thermal stress under steady state and transient operating conditions. The extrusion method should give very smooth interface between semi-conducting screen and insulation. The insulation of the cable shall be of high standard quality generally conforming to IS: 7098 (Part – II) – 1985 and any latest amendment to it.

(7) Insulation shield: Non-metallic semi-conducting shield shall be provided over the insulation to confine electrical field to the insulation. The insulation shield shall be extruded in the same operation as the conductor shield and the insulation by suitable extrusion process. The XLPE insulation shield shall be of tended type. The copper metallic overlapped tape shield shall be provided.

(8) Filler and Inner-Sheath: The sheath shall be suitable to withstand the site conditions and the desired temperature. It shall be of adequate thickness, consistent quality and free from all defects. The PVC sheath shall be extruded. The material of fillers and inner-sheath shall be compatible with the temperature ratings of the cable and shall have no deterious effect on any other component of the cable. Central PVC filler shall also, be provided with other peripheral PVC fillers to have proper circular section.

(9) Outer-Sheath: Extruded type ST-2 PVC outer-sheath, conforming to IS: 5831- (1984) (latest edition) over armouring with suitable additives (to prevent attack by rodents and termites), shall be provided.

(10) Armour: Armoring of galvanized steel strip shall be provided. The dimensions of steel strips shall be as per latest edition of IS: 3975 – 1979.

Page 10: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

(11) Cable shall be suitable for lying in covered trenches and / or buried under-ground in outdoor.

(12) Current Rating: The indicative values of continuous current carrying capacities at Maximum conductor temperature of 90º C (for design purpose by field) of the various sizes of the cables are given in GTP. Short circuit ratings of various sizes cable calculated for duration of one second at maximum temperature of 250º C, are given in GTP.

(13) The cables shall be suitable for being installed directly in the ground, in the pipes or in the cable trays/trenches. The cables shall therefore be suitable for satisfactory operation under the tropical climatic conditions listed in the relevant clause. The applicable design particular of the cables to be used in the Power Stations is furnished in Annexure - II. "System Particulars".

4.3 TELEPHONE CABLE:

Telephone Cable with annealed Copper conductor polyethylene insulated core twisted into pair laid up jelly filled cores wrapped with poly Aluminum Laminated moisture berried polyphone sheathed double steel tape armored overall black polyphone jacketed cable confirm to ITD Specification NO. GR / CUG -01 / 03, Aug 2003.

5.0 PHYSICAL CONSTANTS OF MATERIALS: 5.1 PHYSICAL CONSTANTS FOR COPPER / ALUMINIUM CONDUCTORS: 5.1.1 Resistivity: The volume resistivity of copper / aluminium depends upon its purity and its

physical condition. However as per the specified value of purity in this specification, the maximum value permitted is 0.01724 Ω-mm2/meter for copper and 0.28264 Ω-mm2/meter at 20 Deg. C, for aluminium. These values shall be used for calculation of the maximum permissible value of resistance. This value may be checked from the measured value of the resistance.

5.1.2 Density: At a temperature of 20C the minimum density of electrolytic grade

annealed copper shall be 8.89 and that of hard drawn aluminum shall be 2.703 Gm/CuCm.

5.2 Constant-Mass Temperature Co-efficient of Resistance: 5.2.1 At a temperature of 20C the constant-mass temperature co-efficient of

resistance of copper and hard drawn aluminum measured between two potential points rigidly fixed to the wire, the metal being allowed to expand freely, has been taken as 0.0039 and 0.004 per degree Celsius respectively for copper and aluminum.

Page 11: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

5.3 Co-efficient of Linear Expansion: 5.3.1 The co-efficient of linear expansion of copper and hard-drawn aluminium

at OC has been taken as 17x10-6 and 23 x 10-6 per C respectively for copper and aluminium. This value holds good for all practical purposes over the range of temperature from 0C to highest safe operating temperature.

6.0 PHYSICAL CONSTANTS FOR GALVANIZED STEEL WIRES: 6.1 Density: 6.1.1 At a temperature of 20C, the density of galvanized steel wire is to be

taken as 7.78 Gm/CuCm. 6.2 Co-efficient of Linear Expansion: 6.2.1 In order to obtain uniformity in calculations a value of 11.5 x 10-6 Per C

may be taken as the value for the co-efficient of Linear Expansion of galvanized steel wires used for the cores of steel-armoured copper / aluminium conductors.

6.3 Materials: 6.3.1 The conductors shall be manufactured from Electrolytic annealed copper

/ EC grade aluminium rods suitably hard-drawn on wire drawing machines. The copper / aluminium rods used shall comply with all the relevant ISS, BSS, or other standards to be specified along with the due justifications and this Specification.

6.3.2 Galvanized steel wire shall be drawn from high carbon steel rods

produced by either acidic or basic open hearth process, electric furnace process or basic oxygen process. All the properties of the steel strips and wires shall conform to the relevant standards.

6.3.3 The zinc used for galvanizing shall be electrolytic high grade Zinc not less than 99.95 percent purity. It shall conform to and satisfy all the requirements of relevant ISS, BSS, the Specification or other Standards to be specified with the due justification. Galvanizing has to be done by hot dip galvanizing process. Neutral grease may be applied between the layers of wires; however the weight of the same shall be specified and added to the total weight of the conductor.

NOTE: Lithium soap grease corresponding to Grade II of IS: 7623-1974

(Specification for lithium soap greases) may be suitable for such application.

6.3.4 The bidder should specify the source of raw materials along with the proof

of last purchases made. The Purchaser may reject the tender of the Bidders whose raw material suppliers are found to be supplying any poor quality or non-standard materials, to the purchaser of this Specification or any other purchaser.

Page 12: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

7.0 FREEDOM FROM DEFECTS: 7.1 The wires shall be smooth and free from all imperfections such as

spills, splits, slag inclusion, die marks, scratches, fittings, blow-holes, projections, looseness, overlapping of strands, chipping of copper / aluminium layers etc. and all such other defects which may hamper the mechanical and electrical properties of the conductor as also the installation of the cable at the site etc. Special care should be taken to keep away dirt, grit etc. during stranding / applying PVC coating.

8.0 WIRE SIZES: 8.1 Nominal Size and Tolerances: 8.1.1 The copper, aluminium and galvanized steel wires for the cable covered

by this Specification / standard shall have diameters as specified in clause respective GTP and shall be within the tolerances indicated therein. The diameter of the steel wires shall be measured over the zinc coating.

9.0 JOINTS IN WIRES: 9.1 Copper / Aluminium Wires: 9.1.1 No joints shall be permitted in the copper / aluminum wires in any of the

cables and any of the cores. 9.2 Galvanized steel wires: 9.2.1 There shall be no joints except those in the base rod or wire before final

drawing, in steel wires and strips forming the armouring of the copper / aluminium cables.

10.0 STRANDING: 10.1 The wires used in the construction of galvanized steel armouring of copper

and aluminium cables before stranding and after stranding shall satisfy all the relevant requirements as per the standards indicated or any other standards with due justification and this Specification.

10.2 The zinc used for galvanizing shall be electrolytic high grade Zinc. It shall conform to and satisfy all the requirements of relevant standards indicated or any other standards with due justification and this Specification. Galvanizing shall be done by hot dip galvanizing process. Neutral grease may be applied between the layers of wires.

NOTE: Lithium soap grease corresponding to Grade II of IS: 7623-1974 (Specification for lithium soap greases) may be suitable for such application.

Page 13: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

11.0 STANDARD LENGTH: 11.1 The standard length of the conductor shall be as per GTP. A tolerance of

+/-5% on the standard length shall be permitted. All lengths outside this limit of tolerance shall be treated as random lengths. Over all tolerance in total quantity of ordered cables shall be + 2%.

11.2 Random lengths will be accepted provided no length is less than 95% of the standard length specified and the total quantity of such random lengths shall not be more than 5% of the total quantity ordered.

11.3 Bidder shall also indicate the maximum single length, above the standard length, he can manufacture in the guaranteed technical particulars. This is required for special connections like Control and Relay Panels etc. The purchaser reserves the right to place orders for the above length to the extent of 50% of the total ordered quantity on the same terms and conditions applicable for the standard lengths during the pendency of the contract.

11.4 All the cables shall be marked at every meter with- 1. Name of the manufacturer 2. Name of the purchaser 3. Rating 4. Size of the cable 5. Date of manufacture 6. Length 7. Electric/Telephone as per IS

11.5 Every core of the cable shall be marked with core no. at every meter,

serially. 12.0 OPERATION: 12.1 Cable shall be suitable for operation under frequency variation of 3% and

voltage variation of 10% -15% and combined frequency-voltage variation of 10% (absolute sum).

13. TESTS: 13.1 The type, acceptance, routine tests, any tests specifically demanded by

the Purchaser and tests during manufacture shall be carried out on the cables free of cost.

13.2 Type tests shall mean those tests, which are to be carried out to prove the process of manufacture and general conformity of the material to this Specification and relevant Standards. These tests shall be carried out on samples prior to commencement of commercial production against the order. The Bidder shall indicate his schedule for carrying out these tests in the activity schedule. These tests shall have to be carried out at the Government Approved Testing Laboratory only in presence of the Purchaser’s representative. Purchaser reserves the right to specify the name of the laboratory also, if so felt.

Page 14: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

13.3 Acceptance Tests shall mean those tests, which are to be carried out on samples taken from each lot offered for pre-dispatch inspection, for the purposes of acceptance of that lot. These tests shall be carried out at the manufacturer’s works in presence of Purchaser’s representative before the dispatch of the materials to the site.

13.4 Routine Tests shall mean those tests which are to be carried out on each strand / spool / length of the cable to check requirements which are likely to vary during production. These tests shall be carried out by the manufacturer on each drum and shall have to furnish these reports to the GSECL’s representative during his visit for acceptance tests.

13.5 Tests during manufacture shall mean those tests, which are to be carried out during the process of manufacture and end inspection by the supplier to ensure the desired quality of the end product to be supplied by him, including all Quality Control checks and Raw Materials testing.

13.6 Samples for individual wires for tests shall be taken before stranding from not less than ten percent of the spools in the case of copper and aluminium wires and ten percent of the coils in the case of steel wires. If samples are taken after stranding, they shall be obtained by cutting 1.2 meters from the outer end or inner end of the finished cable from at least ten percent of the finished reels.

13.7 The standards to which these tests will be carried out are listed against them. Where a particular test is a specific requirement of this specification, the norms and procedures of the test shall be as specified in this Specification or as mutually agreed to between the Bidder and the purchaser in the Quality Assurance Programme.

13.8 For all type and acceptance tests, the acceptance values shall be the values guaranteed by the Bidder in the "Guaranteed Technical Particulars” of his proposal or the acceptance value specified in this specification, whichever is more stringent for that particular test.

14.0 TYPE TESTS: 14.1 All the type tests as per relevant Standards (IS 1554-Part-I, IS 7098-Part-II and

IS 9968) and this Specification shall be conducted once on each sample / samples of cables for every 50 KMs or less of production from each manufacturing facility. However if the Supplier has carried out the Type Tests within 5 years of opening of this Tender, the same will be considered acceptable, subject to submission of the same in original. However GSECL may ask any of the suppliers to carry out the Type Test at its own discretion, even if the same are not older than 5 years, but the same will be subject to allotment of minimum 15% of the total quantity indicated in this Specification. Some tests are listed below AT Cl. No. 14.4.

14.2 All the Type Tests shall be carried out by the supplier at no extra cost to the

GSECL, (for any number of times, as may be required) at the Government Approved Laboratory or at the Laboratory specified by the GSECL, at its own discretion.

Page 15: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

14.3 All the new suppliers, for the size offered or full lot, shall have to compulsorily carry out the Type Tests i.e. if the supplier has supplied one size of cable to the Company in past and is having type test certificate but has been allotted some other size for the first time by the GSECL then even if he possess the Type test, he has to carry out the same in presence of the GSECL’s representative.

14.4 List of Type Tests: (A) As per IS 1554: (a)Tests on conductor:

(1)Annealing test (2)Tensile test (3)Wrapping test (4)Conductor Resistance test

(b)Tests for armoring strips / wires:

(c)Tests for thickness of insulation and sheath: (d)Physical tests for insulation and outer sheath:

(1)Tensile strength and elongation at break (2)Ageing in air oven (3)Shrinkage test (4)Hot deformation test (5)Thermal stability

(e) Insulation resistance test (g)High voltage test (water immersion)

(m)Flammability test (B) As per IS 7098-Part-II: (a) Tests on conductor:

(1)Annealing test (2)Tensile test (3)Wrapping test (4)Conductor Resistance test

(b) Tests for armoring strips / wires:

(c)Tests for thickness of insulation and sheath: (d)Physical tests for insulation:

(1)Tensile strength and elongation at break (2)Ageing in air oven (3)Hot set test (4)Shrinkage test (5)Water absorption (6) Degree of cross linking

Page 16: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

(e)Physical tests on outer sheath:

(1)Tensile strength and elongation at break (2)Ageing in air oven (3)Shrinkage test (4)Hot deformation (5)Thermal stability

(f)Partial discharge test (g)Bending test (h)Dielectric power factor test

(1) as a function of voltage (2) as a function of temperature

(i)Insulation resistance test (volume resistivity) (j)Heating cycle test (k)Impulse withstand test (l)High voltage test (m)Flammability test (n)Test on extruded semi conducting screens

(a) Test for strippability of semiconducting strippable insulation screen(when applicable)

(b) Volume resistivity (o) Test on extruded semi conducting screens

15.0 ACCEPTANCE TESTS: 15.1 All the cables ordered shall be accepted only after carrying out of all the

acceptance tests, as per the relevant IS or the Specification, in presence of the GSECL’s Representative. Some tests are listed at Cl. No. 15.3.

15.2 The supplier shall possess all the facilities to carry out all the Acceptance Tests. If it is found that the testing equipment/s are not performing to the Standard or they are not duly Calibrated the related test/s shall be carried out at the Government approved laboratory in presence of Purchaser’s Representative, at no extra cost to the GSECL. The GSECL may specify the name of the laboratory.

Page 17: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

15.3 List of Acceptance Tests:

(A) As per IS 1554: (a)Annealing test (b)Tensile test (c)Wrapping test (d)Conductor Resistance test (e)Tests for thickness of insulation and sheath: (f)Tensile strength and elongation at break of insulation and sheath (g)Insulation resistance test (volume resistivity) (h)High voltage test

(B) As per IS 7098-Part-II: (a)Annealing test (b)Tensile test (c)Wrapping test (d)Conductor Resistance test (e)Tests for thickness of insulation and sheath (f) Hot set test for insulation (g)Tensile strength and elongation at break of insulation and sheath (h) Insulation resistance test (i)High voltage test (k)Partial discharge test

16.0 ROUTINE TESTS: 16.1 All the routine tests shall be carried out by the supplier during the

production of the cable and a copy of the same shall be provided to the Inspecting Officer, during inspection. Some tests are listed below at Cl. No. 16.2.

16.2 List of T Routine Tests:

(A) As per IS 1554: (a)Conductor Resistance test (b) High voltage test (c) Armour resistance test

(B) As per IS 7098-Part-II: (a)Conductor Resistance test (b) High voltage test (c) Armour resistance test (d) Partial discharge test

Page 18: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

17.0 TEST DURING MANUFACTURE:

a Chemical analysis of zinc used for galvanizing

Relevant IS with latest Amendment and this Specification.

b Chemical analysis of copper and aluminium used for making copper / aluminium conductors.

Relevant IS with latest Amendment and this Specification

c Chemical analysis of steel used making steel armouring.

Relevant IS with latest Amendment and this Specification

18.0 TESTING CHARGES: 18.1 The testing charges for the type tests specified and as per relevant IS /

international standards, shall be borne by the Supplier. All the Suppliers irrespective of their registration etc. will have to carry out the Type Test, as per the terms of this Specification at their own cost and the Purchaser will not have any financial or technical implication on this account.

18.2 In case of failure in any of the type test/s, the supplier is either required to modify the design of the material or repeat the particular type test three times successfully at his own expenses. The decision of the purchaser in this regard shall be final and binding. The Purchaser at its own desecration may also cancel the order at the risk and cost of the contractor, if the material fails twice successively in the Type Test.

18.3 Bidder shall indicate the laboratories in which they propose to conduct the

type tests. They shall ensure that the tests can be completed in these laboratories within the time schedule guaranteed by them in the appropriate schedule. The Purchaser reserves the right to specify the name of the laboratory also, if so felt.

18.4 The entire cost of testing for the type, acceptance routine tests and tests during manufacture, special tests etc specified herein or in the relevant Standards shall be treated as included in the quoted unit price of cable.

19.0 ADDITIONAL TESTS:

19.1 The Purchaser reserves the right of getting done any other test(s) of

reasonable nature carried out at Purchaser's premises, at site, or in any other place in addition to the aforesaid type, acceptance and routine tests to satisfy himself that the material comply with the specifications. In such case all the implications (financial and / or Technical) will be to Suppliers account.

20.0 SAMPLE BATCH FOR TYPE TESTING:

20.1 The Bidder shall offer minimum five (5) drums or the full quantity, which ever is

less, for selection of samples required for conducting all the type tests.

Page 19: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

20.2 The Bidder is required to carry out all the acceptance tests successfully in the presence of Purchaser's representative before dispatch of the selected sample to the testing laboratory for type test.

20.3 However the new supplier will have to offer the first lot for selection of sample for type test, after successfully carrying out the acceptance tests on it, in presence of the GSECL’s Representative. The first lot shall be minimum of 5 drums or full allotted quantity.

21.0 TEST REPORTS:

21.1 Test reports shall be furnished in at least two (2) copies along with one

original. One copy shall be returned duly certified by the Purchaser only after which the material already inspected i.e. the materials manufactured for selection of sample for type test, shall be dispatched on receipt of Dispatch Instructions from the C.E.(Generation), Corporate Office, GSECL, Vadodara.

21.2 Record of routine test reports shall be maintained by the Bidder at his works for periodic inspection by the purchaser’s representative.

21.3 Test Certificates of test during manufacture shall be maintained by the Bidder. These shall be produced for verification as and when desired by the Purchaser.

22.0 TEST FACILITIES: 22.1 The following additional facilities shall be available at Supplier's works: (a) Calibration Reports from Government approved testing laboratory of

various testing and measuring equipment including tensile testing machine, resistance measurement facilities, burette, thermometer, barometer etc.

(b) Standard resistance for calibration of resistance bridges. (c) Finished cable shall be checked for length verification and surface finish

on separate rewinding machine at reduced speed (variable from 8 to 16 meters per minute). The rewinding facilities shall have appropriate clutch system and free of vibrations, jerks etc. with transverse layering facilities.

(d) The bidder should have all the routine and acceptance testing facilities, in house.

23.0 INSPECTION: 23.1 The Purchaser's representative shall at all times during the tendency of the

contract be entitled to have access to the works and all places of manufacture where conductor is being manufactured and the representative shall have full facilities for unrestricted inspection of the Supplier’s works, raw materials and process of manufacture and conducting necessary tests as may be deemed fit, for certifying the quality of product.

23.2 The Supplier shall keep the Purchaser informed in advance of the time of starting and of the progress of manufacture of cable in its various stages so that arrangements can be made for inspection.

Page 20: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

23.3 No material shall be dispatched from its point of manufacture before it has been satisfactorily inspected, tested, and necessary dispatch instructions are issued in writing, except for the cases where waiver of inspection is granted by competent authority of the Purchaser, and even in this case also written dispatch instructions will be issued. Any dispatches before the issue of Dispatch Instructions in writing will be liable for rejection and non acceptance of the materials by the consignee.

23.4 The acceptance of any quantity of material shall in no way relieve the Bidder of any of his responsibilities for meeting all requirements of the Standards / Specification, and shall not prevent subsequent rejection if such material is later found to be defective. The dispatch of the manufactured materials shall not be delayed beyond 10 days from the date of issue of the Dispatch Instruction. Any delay beyond this will be treated as late delivery and all deductions as per late delivery will be affected.

23.5 At least 5% of the total number of drums subject to minimum of two in any lot put up for inspection, shall be selected at random to ascertain the length of cable by following method:

"At the works of the manufacturer of the cable, the cable shall be transferred from one drum to another at the same time measuring its length with the help of a graduated pulley and Cyclometer. The difference in the length (higher of the total measured lengths) thus obtained and as declared by the Bidder in the packing list shall be applied to all the drums if the cable is found short during checking."

23.6 The sample cut off from any numbers of drums for carrying out any type of tests will be to the suppliers account.

24.0 QUALITY ASSURANCE PLAN: 24.1 The bidder shall invariably furnish following information along with his

offer, failing which his offer shall be rejected. (i) Statement giving list of important raw materials, proposed to be used in

the manufacture of the cable against this Specification, names of sub suppliers for the raw materials, list of standards according to which the raw materials are tested, list of tests normally carried out on raw materials in presence of Bidder's representative as routine and / or acceptance during production and on finished goods, copies of test certificates.

(ii) Information and copies of test certificates as in (i) above in respect of bought out accessories.

(iii) List of manufacturing facilities available. (iv) Level of automation achieved and list of areas where manual

processing exists. (v) List of areas in manufacturing process, where stage inspections are

normally carried out for quality control and details of such tests and inspections.

(vi) List of testing equipment available with the Bidder for final testing of Cable specified. In the case if the Bidder does not possess all the Routine and Acceptance testing facilities the tender will be rejected.

Page 21: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

(vii) The Purchaser reserves the right for factory inspection to verify the facts quoted in the offer. If any of the facts are found to be misleading or incorrect the offer of that Bidder will be out rightly rejected and he may be black listed.

(viii) Special features provided to make it maintenance free and also any marking for identification after installation.

24.2 The bidder shall also submit following information to the purchaser along

with the technical Bid. . (i) List of raw materials as well as bought out accessories, and the

name of suppliers of raw materials as well as bought out accessories. (ii) Type test certificates of the raw material bought out accessories and

finished cables, offered. The reports shall not be older than 5 years on the date of opening of the Tender.

(iii) Quality assurance plan (QAP) with hold points for purchaser's inspection.

24.3 The Bidders shall submit the routine test certificates of all the cables, bought out items, accessories etc.

25.0 DOCUMENTATION: 25.1 Two sets of type test reports, duly approved by the Purchaser shall be

submitted by the Bidder, before commencement of supply. A copy of acceptance and routine test certificates, duly approved by the purchaser shall accompany the dispatch consignment.

25.2 The manufacturing of the cables shall be strictly in accordance with the

approved drawings and no deviation shall be permitted without the written approval of the Purchaser. All manufacturing and fabrication work in connection with the cable prior to the approval of the drawing shall be at supplier's risk.

25.3 Approval of drawing etc. by the purchaser shall not relieve the Bidder of his responsibility and liability for ensuring correctness and correct interpretation of the latest revision of applicable standards, rules and codes of practices. The cables shall conform in all respects to high standards of engineering, design, workmanship and latest revisions of relevant standards in vogue on the day of opening of the Technical Bid and purchaser shall have the power to reject any work or material which in his judgement is not in full accordance therewith.

26.0 PACKING AND FORWARDING: 26.1 The cables shall be supplied in non-returnable strong wooden drums

provided with lagging of adequate strength, and displacement during transit, storage and subsequent handling and laying operations in the field. The drums shall generally conform to relevant IS except otherwise specified hereinafter.

Page 22: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

26.2 The drums shall be suitable for wheel mounting and for jetting off the cable under a minimum controlled stress of the order of 5 Kg/m2 for copper cables and 15 Kg/m2 for aluminium cables.

26.3 The bidder should submit the proposed drum drawings along with the bid. However, the same shall be in line with the requirements as stated herein. After placement of the Letter of Award, the Bidder shall submit two copies of fully dimensioned drawing of the drum, for Purchaser’s approval before taking up manufacturing of Cables and or drums. After getting approval from the Purchaser, Bidder shall submit 6 copies of the approved drawing to Purchaser for further distribution and field use at Purchaser’s end.

26.4 All wooden components shall be manufactured out of seasoned soft wood free from defects that may materially weaken the component parts of the drums. Preservative treatment for anti-termite/anti-fungus (Aldrime / Aldruse) etc. shall be applied to the entire drum with preservatives of a quality which is not harmful to the cable or to the persons using or storing the same.

26.5 The flanges shall be of minimum two ply or higher construction with each ply at right angles to the other and nailed together. The nails shall be driven from the inside face flange, punched and then clenched on the outer face. The tolerance in thickness of each ply shall be +3 mm only. There shall be at least 3 nails per plank of ply with maximum nail spacing of 75 mm. Where a slot is cut in the flange to receive the inner end of the cable, the entrance shall be in the line with the periphery of the barrel.

26.6 The wooden battens used for making the barrel of the cable shall be of segmental type. These shall be nailed to the barrel supports with at least two nails. The battens shall be closely butted and shall provide a round barrel with smooth external surface. The edges of the battens shall be rounded or chamfered to avoid damage to the cable.

26.7 Barrel studs shall be used for construction of drums. The flanges shall be holed and the barrel supports slotted to receive them. The barrel studs shall be threaded over a length on either end, sufficient to accommodate washers, spindle plates and nuts for fixing flanges at the required spacing. Barrel studs should be tack welded with the nuts after tightening.

26.8 Normally, the nuts on the studs shall stand stroud of the flanges. All the nails used on the inner surface of the flanges and the drum barrel shall be countersunk. The ends of barrel shall generally be flushed with the top of the nuts.

26.9 The complete drum including inner cheek of the flanges and drum barrel surface shall be painted with bitumen based paint.

26.10 Before reeling, card board or double corrugated or thick bituminized waterproof bamboo paper shall be secured to the drum barrel and inside of flanges or the drum by means of a suitable commercial adhesive material. The paper should be dried before use. After reeling the cable, the exposed surface of the outer layer of cable shall be wrapped with thin polyphone sheet across the flanges to preserve the cable from dirt, grit and damage during transportation and handling and also to prevent ingress of rain water during storage / transport.

Page 23: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

26.11 A minimum space of 125 mm shall be provided between the inner surface

of the external protective layer and outer layer of the power cables; however 75 mm shall be acceptable for all control cables.

26.12 Each batten shall be securely nailed across grains as far as possible to the flange edges with at least 2 nails per end. The length of the nails shall not be less than twice the thickness of the battens. The nail shall not protrude above the general surface and shall not have exposed sharp edges or allow the battens to be released due to corrosion.

26.13 Outside the protective layer, there shall be minimum of two binders consisting of hoop iron / galvanized steel wire. Each protective layer shall have two recesses to accommodate the binders.

26.14 The cable ends shall be properly sealed and secured with the help of U-nails on one side of the flanges. The cable shall be banded by use of galvanized steel wire / aluminium wire.

26.15 Wire shall be bound at least at three locations at the most 75 mm apart covered with PVC adhesive tape so as to avoid loosening of cable in transit and handling.

26.16 Only Single length of cable shall be wound on each non returnable drum as per IS 10418 (Latest).

26.17 If any bidder wishes to supply the cables in the non returnable steel drums the same will be acceptable, however they shall be without any additional cost to the GSECL.

27.0 MARKING 27.1 Each drum shall have the following information stenciled on it in indelible

ink along with other essential data:

1. Contract Award letter / order number 2. Name and address of consignee 3. Manufacturer’s name and address 4. Drum Number 5. Size of cable 6. Length of cables in meters 7. Gross weight of drum with cable 8. Weight of empty drum with lagging 9. Arrow marking for unwinding.

28.0 QUANTITY AND DELIVERY REQUIREMENT 28.1 Schedule of requirement and desired delivery is shown in attached

SCHEDULE-A.

Page 24: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

29.0 DRAWINGS 29.1 All the bidders have to submit the drawings for the cables and drums to be

utilized for packing of the control and power cables, for the lengths specified in this Tender Specification. The cable drawing shall be enclosed with the calculations of current rating, dimensions etc and drum drawings with calculations in support of the size of the drum to accommodate the required length of cable.

30.0 DEVIATIONS 30.1 Any deviation to this tender Specification will be out rightly rejected. All the

Bidders have to submit this specification duly authenticated without any alterations, additions etc. on each page along with the Technical Bid. Any offer without this will be out rightly rejected.

Page 25: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

ANNEXURE-I

SYSTEM PARTICULARS ELECTRICAL SYSTEM DATA:

1 System Voltage a) Control Cables (DC Volts) b) LT Power Cables (AC Volts)

110/220

440 2 Max. Voltage

a) Control Cables (DC Volts) b) LT Power Cables (AC Volts)

130/250

470 3 Short circuit level (KA) 40

4 Radio interference voltage at one MHz when subjected to 50Hz AC. Voltage 320KV (rms) Line to ground – Micro Volts.

1000

5 Corona Voltages in 50 Hz AC system – KV (rms) Inception

I) Dry II) Wet

Extinction I) Dry II) Wet

>320 >320

>320 >320

Page 26: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE - B1 GUARANTEED TECHNICAL PARAMETER

TELEPHONE CABLE 1 2 3 4 5 6 7 8

SR. NO DESCRIPTION 5 P X 0.5 mm

20 P X 0.5 mm

50 P X 0.5 mm

10 P X 0.63 mm

20 P X 0.63 mm

50 P X 0.63 mm

1 Voltage Grade(AC, VOLT)

650

2 Suitable for earthed or unearthed system

Both

CONDUCTOR- 3 Material Solid, Annealed, Tinned Copper Conductor as per IS

8130-Twisted into pairs, Tapped

4 No. of Pair 5 20 50 10 20 50 5 Diameter Of the

conductor-(mm)(min) 0.50 0.50 0.50 0.63 0.63 0.63

7 Resistance at 20 °C (Ω/KM)(Max)

92.20 92.20 92.20 58.0 58.0 58.0

8 Resistivity(Ω-mm2/meter) 0.01724 9 Density (Gm/Cu-Cm) 8.89

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

0.0039

Elongation in % , Minimum

15

11 Coefficient of Linear Expansion per °C

17 x 10-6

12 Modulus of Elasticity (Kg/cm2)

9 to 10.5 x 103

CORE INSULATION- 13 Material PVC, Type-A 14 Thickness of PVC Core

Insulation(mm)- (Minimum)

0.2

15 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1 X 1013

(2)1 X 1010

16 Tensile Strength (N/mm2)(Min)

12.5

17 Elongation in % 150 18 Color code for Core

Identification As per IS

INNER SHEATH- 19 Material PVC, Type-ST-1

Page 27: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

20 Thickness of PVC Inner Sheath(mm)- (Minimum)

0.65 0.75 1.10 0.75 0.75 1.10

21 Tensile Strength (N/mm2)(Min)

12.5

22 Elongation in % 150 23 Color code for Core

Identification As per IS

OUTER SHEATH- 24 Material PVC, Type-ST-1

25 Thickness of PVC Outer Sheath(mm)-(Minimum)

1.24 1.24 1.40 1.24 1.24 1.40

26 Tensile Strength (N/mm2)(Min)

12.5

27 Elongation in % 150 28 Color code for Core

Identification As per IS

29 Overall Diameter of cable-(mm)(min)

12 16 19 14 16 22

ARMOUR- 30 Material/Type Galvanized Steel Round Wire

Galvani-zed Steel Flat Strip

31 Diameter Of Armour Wire-(mm) (1)Nominal (2) Minimum

(1)1.40 (2)1.34

(1)1.40 (2)1.34

(1)1.40 (2)1.34

(1)1.40 (2)1.34

(1)1.40 (2)1.34

(1)0.85x 4 (2)0.8 x 4

32 Resistance at 20 °C (Ω/KM)(Max)

As per IS

33 Tensile Strength (N/mm2)(Min)

As per IS

34 Elongation in % As per IS 35 Density at 20 °C(Gm/Cu-

Cm) 7.78

36 Coefficient of Linear Expansion per °C

19.5 x 10-6

37 Modulus of Elasticity (Kg/sq.cm)

19.7 x 103

38 Overall Diameter of Armour-(mm)(min)

As per IS

GENERAL- 39 Mutual Capacitance-

(nF/KM)(Max) 50

40 Short Time Current Rating for 1 Sec. (KA)

As per IS

41 Insulation Resistance (MΩ/KM)-(min)

5000

Page 28: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

44 Safe Pulling Force - 5 Kg/mm2 OR 50 N/mm2

45 Minimum Radius of Insulation

12 x Outer Diameter of Cable

46 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

SCHEDULE - B2(1)

GUARANTEED TERCHNICAL PARAMETER TRAILING CABLE(LT)

1 2 3 SR. NO DESCRIPTION 12C X 2.5 mm2 + 12C X 2.5 mm2 (Screen)

1 Voltage Grade(VOLT) 1100 2 Suitable for earthed

or unearthed system Both

3 Applicable Standard IS 9968 - Part - I - 1988 CONDUCTOR-

4 Material Flexible Annealed Tinned Copper Conductor- Class - 5 as per IS 8130 - 1984

5 No. of strands per core/Dia(max)(mm)

50/0.26

6 Diameter Of the conductor-(mm)(min)

As per IS 8130

7 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1)2.5 (2)2.5

8 Resistance at 20 °C (Ω/KM)(Max)

8.21

9 Resistivity(Ω-mm2/meter)

0.01724

10 Density (Gm/Cu-Cm) 8.89 11 Constant Mass

Temperature Coefficient for resistance - For Copper-per °C

0.0039

12 Elongation in % , Minimum

18

13 Coefficient of Linear Expansion per °C

17 x 10-6

14 Modulus of Elasticity (Kg/cm2)

9 to 10.5 x 103

CORE INSULATION- 15 Material EPR As per IE - 2 of IS-6380 - 1984 16 Thickness of PVC

Core Insulation (mm)-(Nominal)

1.0

Page 29: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

17 Insulation Resistance(MΩ-cm)- (1)At 20 °C (2)At 90 °C

(1)3670

(2)3.67

18 Tensile Strength (N/mm2)(Min)

4.2

19 Elongation in % 200 20 Color code for Core

Identification White with number print from 1 to 24

CONDUCTOR SCREEN- 21 Material/Type As per IS

INSULATION SCREEN- 22 Material/Type As per IS

REINFORCEMENT- 23 Material/Type Nylon Yarn

SHEATH- 24 Material PCP, SE 4 of IS. 6380-1984 25 Thickness of PVC

Sheath(mm)- (1) Inner (2) Outer

(1) 2.0 (2) 3.0

26 Tensile Strength (N/mm2)(Min)

11.0

27 Elongation in %

250

28 Color code for Core Identification

Black

29 Overall Diameter -(mm)(min)

As per IS

GENERAL- 30 Continuous Current

Rating at 40 ºC(Amp)- 30

31 Short Time Current Rating for 1 Sec. (KA)

0.357

32 Safe Pulling Force - 5 Kg/mm2 OR

50 N/mm2 33 Minimum Radius of

Insulation 12 x Outer Diameter of Cable

34 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

Page 30: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE - B2(2) GUARANTEED TERCHNICAL PARAMETER

TRAILING CABLE(HT) 1 2 3 4

SR. NO DESCRIPTION 3C X 25 mm2 + 3C X 25/3(8.33) mm2

4C X 35 mm2

1 Voltage Grade(VOLT) 6600 6600 2 Suitable for earthed

or unearthed system Both

3 Applicable Standard IS 9968 - Part - II - 1988 CONDUCTOR-

4 Material Flexible Annealed Tinned Copper Conductor- Class - 5 as per IS 8130 - 1984

5 No. of strands per core/Dia(max)(mm)

196 / 0.40 66 / 0.40 276/0.40

6 Diameter Of the conductor-(mm)(min)

As per IS 8130

7 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1)25 (2)25

(1)8.33 (2)8.33

(1)35 (2)35

8 Resistance at 20 °C (Ω/KM)(Max)

0.795 2.38 0.565

9 Resistivity(Ω-mm2/meter)

0.01724

10 Density (Gm/Cu-Cm) 8.89 11 Constant Mass

Temperature Coefficient for resistance - For Copper-per °C

0.0039

12 Elongation in % , Minimum

18

13 Coefficient of Linear Expansion per °C

17 x 10-6

14 Modulus of Elasticity (Kg/cm2)

9 to 10.5 x 103

CORE INSULATION- 15 Material EPR As per IE - 3 of IS-6380 - 1984 16 Thickness of PVC

Core Insulation (mm)-(Nominal)

4.0 4.0 4.0

17 Insulation Resistance(MΩ-cm)- (1)At 20 °C (2)At 90 °C

(1)3670

(2)3.67

18 Tensile Strength (N/mm2)(Min)

4.2

Page 31: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

19 Elongation in % 200 20 Color code for Core

Identification Red/Yellow/Blue/Green

CONDUCTOR SCREEN- 21 Material/Type Semi Conducting Compound As per IS

INSULATION SCREEN- 22 Material/Type Semi Conducting Compound

REINFORCEMENT- 23 Material/Type Composite Braid of ATC, Nylon Yarn As per IS

SHEATH- 24 Material PCP, SE 4 of IS. 6380-1984 25 Thickness of PVC

Sheath(mm)- (1) Inner (2) Outer

(1) 3.0 (1) 4.0

(1) 2.0 (3) 3.5

26 Tensile Strength (N/mm2)(Min)

11.0

27 Elongation in %

250

28 Color code for Core Identification

Black

29 Overall Diameter -(mm)(min)

As per IS

GENERAL- 30 Continuous Current

Rating at 40 ºC(Amp)- 138 68 162

31 Short Time Current Rating for 1 Sec. (KA)

3.57 0.94 5.01

32 Safe Pulling Force - 5 Kg/mm2 OR

50 N/mm2 33 Minimum Radius of

Insulation 15 x Outer Diameter of Cable

34 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

SCHEDULE - B3

GUARANTEED TECHNICAL PARAMETER CONTROL CABLE (1.5 mm2)

1 2 3 4 5 6 SR. NO

DESCRIPTION 3C X 1.5 mm2

7C X 1.5 mm2

12C X 1.5 mm2

24C X 1.5 mm2

Page 32: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

1 Voltage Grade (VOLT) 1100 2 Suitable for earthed or

unearthed system Both

CONDUCTOR- 3 Material Stranded Annealed Tinned High Conductivity

Copper Conductor as per IS 8130 4 No. of strands per core 7 5 Diameter Of the

conductor-(mm)(min) As per IS

6

Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1)1.5 (2)1.5

7 Resistance at 20 °C (Ω/KM)(Max)

12.1

8 Resistivity(Ω-mm2/meter) 0.01724 9 Density (Gm/Cu-Cm) 8.89

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

0.0039

11 Elongation in % , Minimum

18

12 Coefficient of Linear Expansion per °C

17 x 10-6

13 Modulus of Elasticity (Kg/cm2)

9 to 10.5 x 103

CORE INSULATION- 14 Material PVC, Type-A 15 Thickness of PVC Core

Insulation (mm)- (1) Nominal (2) Minimum

(1)0.8 (2)0.7

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1 X 1013

(2)1 X 1010

17 Tensile Strength (N/mm2)(Min)

12.5

18 Elongation in % 150 19 Color code for Core

Identification As per IS 1554 Clause 10

INNER SHEATH- 20 Material PVC, Type-ST-1

Page 33: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

21 Thickness of PVC Inner Sheath(mm)- (1) Nominal (2) Minimum

(1) 0.35 (2) 0.3

22 Tensile Strength (N/mm2)(Min)

12.5

23 Elongation in % 150 24 Color code for Core

Identification As per IS

OUTER SHEATH- 25 Material PVC,

Type-ST-1 PVC, FRLS, Type-ST-1

PVC, Type-ST-1

PVC, FRLS, Type-ST-1

26 Thickness of PVC Outer Sheath(mm)-(Minimum)

1.24 1.24 1.4 1.4

27 Tensile Strength (N/mm2)(Min)

12.5

28 Elongation in % 150 29 Color code for Core

Identification As per IS

30 Overall Diameter of cable-(mm)(min)

14 16 19 25

ARMOUR- 31 Material/Type Galvanized

Steel Round Wire

Galvanize-d Steel Flat

Strip

Galvanize-d Steel Flat

Strip

Galvanize-d Steel Flat Strip

32 Diameter Of Armour Wire-(mm) (1)Nominal (2) Minimum

(1)1.5 (2)1.4

(1)0.85 x 4 (2)0.8 x 4

(1)0.85 x 4 (2)0.8 x 4

(1)0.85 x 4 (2)0.8 x 4

33 Resistance at 20 °C (Ω/KM)(Max)

As per IS

34 Tensile Strength (N/mm2)(Min)

As per IS

35 Elongation in % As per IS 36 Density at 20 °C (Gm/Cu-

Cm) 7.78

37 Coefficient of Linear Expansion per °C

11.5 x 10-6

38 Modulus of Elasticity (Kg/sq.cm)

19.7 x 103

GENERAL- 39 Overall Diameter of

Armour-(mm)(min) As per IS

40 Continuous Current Rating (A)- (1) In Ground (2) In Duct (3) In Air

(1)21 (2)17 (3)17

(1)14 (2)13 (3)13

(1)12 (2)10 (3)10

(1)9 (2)8 (3)8

Page 34: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

41 Short Time Current Rating for 1 Sec. (KA)

0.17

42 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

(1)1 X 1013

(2)1 X 1010

43 Approximate Reactance per 1000 m at 50 Hz (Ω)

0.112

44 Approximate Capacitance per 1000 m at 50 Hz (μF)

0.35

45 Safe Pulling Force - 5 Kg/mm2 OR

50 N/mm2 46 Minimum Radius of

Insulation 12 x Outer Diameter of Cable

47 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

SCHEDULE - B4 GUARANTEED TECHNICAL PARAMETER

FLEXIBLE CABLE 1 2 3 4 5 6 7

SR. NO

DESCRIPTION 1C X 50 mm2

1C X 70 mm2

1C X 16 mm2

4C X 6 mm2

3C X 2.5 mm2

1 Voltage Grade(VOLT) 1100 2 Suitable for earthed

or unearthed system Both

CONDUCTOR- 3 Material Stranded, Tinned Copper Conductor as per IS 8130-Class-5

4 No. of strand/wires per core

396 360 126 84 50

5 Diameter/Size Of the conductor-(mm)(min)

0.41 0.51 0.41 0.31 0.26

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1)50.0 (2)50.0

(1)70.0 (2)70.0

(1)16.0 (2)16.0

(1) 6.0 (2) 6.0

(1)2.5 (2)2.5

7 Resistance at 20 °C (Ω/KM)(Max)

0.393 0.277 1.24 3.39 8.21

8 Resistivity(Ω-mm2/meter)

0.01724

9 Density (Gm/Cu-Cm) 8.89

Page 35: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

0.0039

11 Elongation in % , Minimum

18

12 Coefficient of Linear Expansion per °C

17 x 10-6

13 Modulus of Elasticity (Kg/cm2)

9 to 10.5 x 103

CORE INSULATION- 14 Material PVC, Type-C 15 Thickness of PVC

Core Insulation (mm)-(Nominal)

1.4 1.4 1.0 0.8 0.9

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1 X 1013

(2)1 X 1010

17 Tensile Strength (N/mm2)(Min)

12.5

18 Elongation in % 150 19 Color code for Core

Identification As per IS

SHEATH- 20 Material

Unsheathed

PVC,Type-SE-3

PVC,Type-SE-3

21 Thickness of PVC Inner Sheath(mm)- Nominal

1.2 1.0

22 Tensile Strength (N/mm2)(Min)

12.5 12.5

23 Elongation in % 150 150 24 Color code for Core

Identification

As per IS As per IS 694-2010 Clause 12

GENERAL- 25 Overall Diameter of

cable-(mm)(min) 13 15.6 7.8 14.5 10

26 Continuous Current Rating (Amp)-

138 217 62 31 18

27 Short Time Current Rating for 1 Sec. (KA)

5.75 8.10 1.85 0.69 0.29

28 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

(1)1 X 1013

(2)1 X 1010

Page 36: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

29 Approximate Reactance per 1000 m at 50 Hz (Ω)

0.10 0.091 0.11 0.096 0.11

30 Approximate Capacitance per 1000 m at 50 Hz (μF)

1.32 1.12 1.0 0.28 0.41

31 Safe Pulling Force - 5 Kg/mm2 OR

50 N/mm2 32 Minimum Radius of

Insulation 15 x Outer Diameter of Cable 12 x Outer Diameter

of Cable 33 Length per

Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

SCHEDULE - B5

GUARANTEED TECHNICAL PARAMETER FLAT CABLE FLAT/FLEXIBLE

1 2 3 4 5 SR. NO

DESCRIPTION 3C X 4 mm2

(SUB-MERSIBLE) 3C X 2.5 mm2 3C X 6 mm2

1 Voltage Grade(VOLT) 1100 2 Suitable for earthed or

unearthed system Both

CONDUCTOR- 3 Material Tinned, Annealed copper as per IS 8130 4 No. of strands/Diameter

(mm) per core 56/0.3 36/0.3 84/0.3

5 Diameter Of the conductor-(mm)(min)

As per IS 8130

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1)4.0 (2)4.0

(1)2.5 (2)2.5

(1)6.0 (2)6.0

7 Resistance at 20 °C (Ω/KM)(Max)

3.39 5.09 8.21

8 Resistivity(Ω-mm2/meter) 0.01724 9 Density (Gm/Cu-Cm) 8.89

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

0.0039

11 Elongation in % , Minimum 18 12 Coefficient of Linear

Expansion per °C 17 x 10-6

13 Modulus of Elasticity (Kg/cm2)

9 to 10.5 x 103

Page 37: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

CORE INSULATION- 14 Material PVC, Type-A 15 Thickness of PVC Core

Insulation (mm)- (1) Nominal (2) Minimum

(1)0.8 (2)0.8

(1)0.7 (2)0.7

(1)0.8 (2)0.8

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1 X 1013

(2)1 X 1010

17 Tensile Strength (N/mm2)(Min)

12.5

18 Elongation in % 150 19 Color code for Core

Identification As per IS

INNER SHEATH- 20 Material PVC, Type-ST-1 21 Thickness of PVC Inner

Sheath(mm)- Nominal

0.9 0.9 1.10

22 Tensile Strength (N/mm2)(Min)

12.5

23 Elongation in % 150 24 Color code for Core

Identification As per IS

GENERAL- 25 Overall Dimension of

Cable-(mm)(max) 15.3 (W) x 7.1 (H) 13.0 (W) x 6.2 (H) 19.2 (W) x 3.4 (H)

26 Continuous Current Rating (Amp)-

24 18 31

27 Short Time Current Rating for 1 Sec. (KA)

0.572 0.29 0.858

28 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

(1)1 X 1013

(2)1 X 1010

29 Approximate Reactance per 1000 m at 50 Hz (Ω)

0.106 0.11 0.108

30 Approximate Capacitance per 1000 m at 50 Hz (μF)

0.44 0.41 0.51

31 Safe Pulling Force - 5 Kg/mm2 OR

50 N/mm2 32 Minimum Radius of

Insulation 12 x Outer Diameter of Cable

33 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

Page 38: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE - B6

GUARANTEED TECHNICAL PARAMETER OTHER TYPES

1 2 3 4 5 6 7 8 9 10 11 12 SR. NO

DESCRIPTION 2C X 4 mm2

4C X 4 mm2

2C X 4 mm3

4C X 6 mm2

4C X 16 mm2

4C X 16 mm2

4C X 10 mm2

4C X 4 mm2

4C X 10 mm2

4C X 25 mm2

1 Voltage Grade(VOLT)

1100

2 Suitable for earthed or unearthed system

Both

CONDUCTOR- 3 Material Copper As

per IS 8130/As

per IS 1885-Section:461

-01-05 : Metal Clad

Stranded,

Tinned, Anneale

d Copper as per IS

8130

Stranded Aluminium as per IS 8130

Strande Aluminiu-m as per IS 8130

Stranded

Aluminiu-m as per IS 8130

Stranded Aluminiu-m as per IS 8130

Stranded,

Tinned, Anneale

d Copper as per IS

8130

Stranded Aluminium as per IS 8130

Stranded Aluminium as per IS 8130

Stranded Aluminiu-m as per IS 8130

4 No. of strands per core

As per IS 7 3 3 7 7 7 3 7 7

5 Diameter Of the conductor-(mm)(min)

As per IS 8130

6

Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1)4.0 (2)4.0

(1)4.0 (2)4.0

(1)4.0 (2)4.0

(1)6.0 (2)6.0

(1)16.0 (2)16.0

(1)16.0 (2)16.0

(1)10.0 (2)10.0

(1)4.0 (2)4.0

(1)10.0 (2)10.0

(1)25.0 (2)25.0

7 Resistance at 20 °C (Ω/KM)(Max)

4.70 4.70 7.41 4.61 1.91 1.91 1.84 7.41 3.08 0.734

Page 39: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

8 Resistivity(Ω-mm2/meter)

0.01724 0.01724 0.28264 0.28264 0.28264 0.28264 0.01724 0.28264 0.28264 0.28264

9 Density (Gm/Cu-Cm)

8.89 8.89 2.703 2.703 2.703 2.703 8.89 2.703 2.703 2.703

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

0.0039 0.0039 0.004 0.004 0.004 0.004 0.0039 0.004 0.004 0.004

11 Elongation in % , Minimum

18 18 NA NA NA NA 18 NA NA NA

12 Coefficient of Linear Expansion per °C

17 x 10-6 17 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6 17 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6

13 Modulus of Elasticity (Kg/cm2)

9 to 10.5 x 103

9 to 10.5 x 103

6.96 x 103 6.96 x 103 6.96 x 103

6.96 x 103 9 to 10.5 x 103

6.96 x 103

6.96 x 103 6.96 x 103

CORE INSULATION- 14 Material PVC, Type-A PVC,FRLS

Type-A PVC, Type-A

15 Thickness of PVC Core Insulation (mm)- (1) Nominal (2) Minimum

As per IS (1)1.0 (2)0.9

(1)1.0 (2)0.9

(1)1.0 (2)0.9

(1)1.0 (2)0.9

(1)1.0 (2)0.9

(1)1.0 (2)0.9

(1)1.0 (2)0.9

(1)1.0 (2)0.9

(1)1.2 (2)1.1

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1 X 1013

(2)1 X 1010

17 Tensile Strength (N/mm2)(Min)

12.5

18 Elongation in % 150 19 Color code for

Core Identification

As per IS 1554 Clause 10

Page 40: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

INNER SHEATH- 20 Material PVC, Type-ST-1 PVC,FRLS

Type-ST-1 PVC, Type-ST-1 PVC,

FRLS, Type-ST-1

PVC, Type-ST-1

21 Thickness of PVC Inner Sheath(mm)- (1) Nominal (2) Minimum

(1)0.35 (2) 0.3

22 Tensile Strength (N/mm2)(Min)

12.5

23 Elongation in % 150 24 Color code for

Identification Black

OUTER SHEATH- 25 Material PVC,

Type-ST-1 PVC,

Type-ST-1 PVC,

Type-ST-1 PVC,

Type-ST-1 PVC,

Type-ST-1 PVC,

FRLS,Type-ST-1

PVC, Type-ST-1

PVC, Type-ST-1

PVC, FRLS,Type

-ST-1

PVC, FRLS,

Type-ST-1 26 Thickness of PVC

Outer Sheath (mm)-(Minimum)

1.24 1.24 1.24 1.24 1.24 1.24 1.4 1.8 1.24 1.4

27 Tensile Strength (N/mm2)(Min)

12.5

28 Elongation in % 150 29 Color code for

Identification Black

ARMOUR- 30 Material/Type Galvaniz-

ed Steel Round Wire

Galvaniz-ed Steel Round Wire

Galvaniz-ed Steel Round Wire

Galvaniz-ed Steel Round Wire

Galvaniz-ed Steel Flat Strip

Galvaniz-ed Steel Flat Strip

Galvaniz-ed Steel Flat Strip

Unarmo-ured

Galvaniz-ed Steel Flat Strip

Galvaniz-ed Steel Flat Strip

Page 41: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

31 Diameter Of Armour Wire-(mm) (1)Nominal (2) Minimum

(1)1.40 (2)1.34

(1)1.40 (2)1.34

(1)1.40 (2)1.34

(1)1.40 (2)1.34

(1)0.85x 4 (2)0.8 x 4

(1)0.85x 4 (2)0.8 x 4

(1)0.85x 4 (2)0.8

x 4

NA (1)0.85 4 (2)0.8 x 4

(1)0.85x 4 (2)0.8 x 4

32 Resistance at 20 °C (Ω/KM)(Max)

4.83 4.14 4.83 3.76 3.99 3.99 4.68 NA 4.68 3.53

33 Tensile Strength (N/mm2)(Min) As per IS

34 Elongation in % As per IS 35 Density at 20 °C

(Gm/Cu-Cm) 7.78

36 Coefficient of Linear Expansion per °C

11.5 x 10-6

37 Modulus of Elasticity (Kg/sq.cm)

19.7 x 103

38 Overall Diameter of Armour-(mm)(min)

As per IS

GENERAL- 39 Overall Diameter -

(mm)(min) 15 18 15 19 22 22 19 16 20 24

40 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

(1)41 (2)35 (3)35

(1)36 (2)30 (3)30

(1)32 (2)27 (3)27

(1)35 (2)30 (3)30

(1)60 (2)50 (3)51

(1)60 (2)50 (3)51

(1)60 (2)50 (3)52

(1)28 (2)23 (3)23

(1)46 (2)39 (3)40

(1)76 (2)63 (3)70

41 Short Time Current Rating for 1 Sec. (KA)

0.46 0.46 0.30 0.46 1.220 1.22 1.15 0.304 0.76 1.9

Page 42: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

42 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

(1)1 X 1013

(2)1 X 1010

43 Approximate Reactance per 1000 m at 50 Hz (Ω)

0.106 0.106 0.105 0.099 0.086 0.86 0.091 0.100 0.094 0.85

44 Approximate Capacitance per 1000 m at 50 Hz (μF)

0.44 0.44 0.45 0.52 0.80 0.80 0.67 0.23 0.60 0.84

45 Safe Pulling Force - 5 Kg/mm2

OR 50

N/mm2

5 Kg/mm2

OR 50

N/mm2

3 Kg/mm2

OR 30

N/mm2

3 Kg/mm2

OR 30

N/mm2

3 Kg/mm2

OR 30

N/mm2

3 Kg/mm2

OR 30

N/mm2

5 Kg/mm2

OR 50

N/mm2

3 Kg/mm2

OR 30

N/mm2

3 Kg/mm2 OR 30

N/mm2

3 Kg/mm2

OR 30

N/mm2 46 Minimum Radius of

Insulation 12 x Outer Diameter of Cable

47 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

SCHEDULE - B8(1)

GUARANTEED TECHNICAL PARAMETER LT CABLE (3 CORE)(PVC INSULATION)

1 2 3 4 5 6 7 8 9 10 11 12 13 SR. NO

DESCRIPTION 3C X 16 mm2

3C X 6 mm3

3C X 10 mm3

3C X 25 mm2

3C X 35 mm2

3C X 50 mm2

3C X 70 mm3

3C X 95 mm2

3C X150 mm2

3C X185 mm2

3C X300 mm2

Page 43: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

1 Voltage Grade(VOLT)

650/1100

2 Suitable for earthed or unearthed system

Both

CONDUCTOR- 3 Material Stranded,

Tinned, Annealed Copper as per IS

8130

Stranded Aluminium Conductor as per IS 8130

4 No. of strands per core

7 3 7 7 7 19 19 19 37 37 61

5 Diameter Of the conductor-(mm)(min)

As per IS

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1)16.0 (2)16.0

(1)6.0 (2)6.0

(1)10.0 (2)10.0

(1)25.0 (2)25.0

(1)35.0 (2)35.0

(1)50.0 (2)50.0

(1)70.0 (2)70.0

(1)95.0 (2)95.0

(1)150.0 (2)150.0

(1)185.0 (2)185.0

(1) 300.0 (2) 300.0

7 Resistance at 20 °C (Ω/KM)(Max)

1.16 4.61 3.08 1.20 0.868 0641 0.443 0.320 0.206 0.164 0.100

8 Resistivity(Ω-mm2/meter)

0.01724 0.28264 0.28264 0.28264 0.28264 0.28264 0.28264 0.28264 0.28264 0.28264 0.28264

9 Density (Gm/Cu-Cm)

8.89 2.703 2.703 2.703 2.703 2.703 2.703 2.703 2.703 2.703 2.703

10 Constant Mass Temperature Coefficient for resistance -per °C

0.0039 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004

11 Coefficient of Linear Expansion per °C

17 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6

Page 44: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

12 Modulus of Elasticity (Kg/cm2)

9 to 10.5 x 103

6.96 x103

6.96 x103 6.96 x103 6.96 x103 6.96 x103 6.96 x103 6.96 x103 6.96 x103 6.96 x103 6.96 x103

CORE INSULATION- 13 Material PVC, Type-A 14 Thickness of PVC

Core Insulation (mm) - (1) Nominal (2) Minimum

(1)1.0 (2)0.9

(1)1.0 (2)0.9

(1)1.0 (2)0.9

(1)1.2 (2)1.1

(1)1.2 (2)1.1

(1)1.4 (2)1.3

(1)1.4 (2)1.3

(1)1.6 (2)1.5

(1)1.8 (2)1.7

(1)2.0 (2)1.9

(1)2.4 (2)2.3

15 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1X 013

(2)1X 1010

16 Tensile Strength (N/mm2)(Min)

12.5

17 Elongation in % 150 18 Color code for

Core Identification

As per IS 1554 Clause 10

INNER SHEATH- 19 Material PVC,

Type-ST-1

PVC, Type-ST-

1

PVC, Type-ST-1

PVC, Type- ST-1

PVC, Type-ST-1

PVC, Type-ST-1

PVC, Type-ST-

1

PVC, Type-ST-1

PVC, Type-ST-

1

PVC, Type-ST-

1

PVC, Type-ST-

1 20 Thickness of PVC

Inner Sheath (mm)- (1) Nominal (2) Minimum

(1)0.35 (2)0.3

(1)0.35 (2)0.3

(1)0.35 (2)0.3

(1)0.35 (2)0.3

(1)0.35 (2)0.3

(1)0.35 (2)0.3

(1)0.45 (2)0.4

(1)0.45 (2)0.4

(1)0.55 (2)0.5

(1)0.55 (2)0.5

(1)0.65 (2)0.6

21 Tensile Strength (N/mm2)(Min)

12.5

22 Elongation in % 150

Page 45: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

23 Color code for Identification

Black

OUTER SHEATH- 24 Material PVC,

Type-ST-1

PVC, Type-ST-

1

PVC, Type-ST-

1

PVC, FRLS,

Type-ST-1

PVC, FRLS,

Type-ST-1

PVC, FRLS,

Type-ST-1

PVC, FRLS,

Type-ST-1

PVC, Type-ST-1

PVC, Type-ST-1

PVC, FRLS,

Type-ST-1

PVC, Type-ST-

1 25 Thickness of PVC

Outer Sheath (mm)-(Minimum)

1.4 1.24 1.4 1.4 1.4 1.56 1.56 1.56 1.72 1.88 2.04

26 Tensile Strength (N/mm2)(Min)

12.5

27 Elongation in % 150 28 Color code for

Identification Black

ARMOUR- 29 Material/Type Galvani-

zed Steel

Flat Strip

Galvani-zed

Steel Round Wire

Galvaniz-ed Steel Round Wire

Galva-nized Steel

Flat Strip

Galvani-zed

Steel Flat Strip

Galvani-zed

Steel Flat Strip

Galvani-zed

Steel Flat Strip

Galva-nized Steel Flat Strip

Galvan-ized Steel Flat Strip

Galvani-zed Steel Flat Strip

Galvani-zed

Steel Flat Strip

30 Diameter Of Armour Wire-(mm) (1)Nominal (2) Minimum

(1) 0.85 x 4

(2) 0.8 x 4

(1)1.40 (2)1.34

(1)1.40 (2)1.34

(1) 0.85 x 4 (2) 0.8 x 4

31 Resistance at 20 °C (Ω/KM)(Max)

4.4 4.14 3.62 4.11 3.88 3.35 2.96 2.54 2.09 1.93 1.54

32 Tensile Strength (N/mm2)(Min)

As per IS

33 Elongation in % As per IS 34 Density at 20 °C

(Gm/Cu-Cm) 7.78

Page 46: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

35 Coefficient of Linear Expansion per °C

11.5 x 10-6

36 Modulus of Elasticity (Kg/sq.cm)

19.7 x 103

37 Overall Diameter of Armour-(mm)(min)

As per IS

GENERAL- 38 Overall Diameter

of cable-(mm)(min)

20 17 19 22 25 27 31 34 41 46 56

39 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

(1)77 (2)64 (3)66

(1)35 (2)30 (3)30

(1)46 (2)39 (3)40

(1)76 (2)63 (3)70

(1)92 (2)77 (3)86

(1)110 (2)95 (3)105

(1)135 (2)115 (3)130

(1)165 (2)140 (3)155

(1)210 (2)175 (3)205

(1)235 (2)200 (3)240

(1)305 (2)260 (3)315

40 Short Time Current Rating for 1 Sec. (KA)

1.54 0.456 0.76 1.90 2.66 3.80 5.32 7.22 11.40 14.10 22.81

41 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

(1)1 X 1013

(2)1 X 1010

42 Approximate Reactance per 1000 m at 50 Hz (Ω)

0.086 0.098 0.093 0.085 0.083 0.082 0.077 0.076 0.0743 0.074 0.073

Page 47: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

43 Approximate Capacitance per 1000 m at 50 Hz (μF)

0.8 0.52 0.60 0.84 0.96 0.98 1.12 1.16 1.26 1.28 1.35

44 Safe Pulling Force 5 Kg/mm2

OR 50

N/mm2

3 Kg/mm2 OR

30 N/mm2

45 Minimum Radius of Insulation

12 x Outer Diameter of Cable

46 Length per Drum (meter)-

(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

SCHEDULE - B8(2) GUARANTEED TECHNICAL PARAMETER LT CABLE (3 CORE)(XLPE INSULATION)

1 2 3 4 5 6 SR. NO

DESCRIPTION 3C X 70 mm3 3C X120 mm2 3C X185 mm2 3C X300 mm2

1 Voltage Grade(VOLT)

650/1100

2 Suitable for earthed or unearthed system

Both

CONDUCTOR- 3 Material Stranded Aluminium Conductor as per IS 8130

Page 48: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

4 No. of strands per core

19 37 37 61

5 Diameter Of the conductor-(mm)(min)

As per IS

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1)70.0 (2)70.0

(1)120.0 (2)120.0

(1)185.0 (2)185.0

(1) 300.0 (2) 300.0

7 Resistance at 20 °C (Ω/KM)(Max)

0.443 0.253 0.164 0.100

8 Resistivity(Ω-mm2/meter)

0.28264 0.28264 0.28264 0.28264

9 Density (Gm/Cu-Cm)

2.703 2.703 2.703 2.703

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

0.004 0.004 0.004 0.004

11 Coefficient of Linear Expansion per °C

23 x 10-6 23 x 10-6 23 x 10-6 23 x 10-6

12 Modulus of Elasticity (Kg/cm2)

6.96 x103 6.96 x103 6.96 x103 6.96 x103

CORE INSULATION- 13 Material XLPE, IS 7098-Part-1 14 Thickness of PVC

Core Insulation (mm) - (1) Nominal (2) Minimum

(1)1.1 (2)1.0

(1)1.2 (2)1.1

(1)1.6 (2)1.5

(1)1.8 (2)1.7

Page 49: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

15 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1 X 1014

(2)1 X 1012

16 Tensile Strength (N/mm2)(Min)

12.5

17 Elongation in % 200 18 Color code for

Core Identification

As per IS 7098-Part-2-Clause 14

INNER SHEATH- 19 Material PVC, FRLS, Type-ST-2 PVC, FRLS, Type-ST-2 PVC, FRLS, Type-ST-2 PVC, FRLS, Type-ST-2

20 Thickness of PVC Inner Sheath (mm)- (1) Nominal (2) Minimum

(1)0.45 (2)0.4

(1)0.45 (2)0.4

(1)0.55 (2)0.5

(1)0.65 (2)0.6

21 Tensile Strength (N/mm2)(Min)

12.5

22 Elongation in % 150 23 Color code for

Identification Black

OUTER SHEATH- 24 Material PVC, FRLS, Type-ST-2 PVC, FRLS, Type-ST-2 PVC, FRLS, Type-ST-2 PVC, FRLS, Type-ST-2

25 Thickness of PVC Outer Sheath (mm)-(Minimum)

1.56 1.56 1.88 2.04

26 Tensile Strength (N/mm2)(Min)

12.5

Page 50: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

27 Elongation in % 150 28 Color code for

Identification Black

ARMOUR- 29 Material/Type Galvanized Steel Flat Strip Galvanized Steel Flat Strip Galvanized Steel Flat Strip Galvanized Steel Flat

Strip 30 Diameter Of

Armour Wire-(mm) (1)Nominal (2) Minimum

(1) 0.85 x 4 (2) 0.8 x 4

31 Resistance at 20 °C (Ω/KM)(Max)

3012 2045 2.03 1.63

32 Tensile Strength (N/mm2)(Min)

As per IS

33 Elongation in % As per IS 34 Density at 20 °C

(Gm/Cu-Cm) 7.78

35 Coefficient of Linear Expansion per °C

11.5 x 10-6

36 Modulus of Elasticity (Kg/sq.cm)

19.7 x 103

37 Overall Diameter of Armour-(mm)(min)

As per IS

GENERAL- 38 Overall Diameter

of cable-(mm)(min)

28 35 43 52

Page 51: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

39 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

(1)170 (2)140 (3)176

(1)225 (2)158 (3)258

(1)285 (2)235 (3)339

(1)370 (2)305 (3)460

40 Short Time Current Rating for 1 Sec. (KA)

6.60 11.30 17.50 28.30

41 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

(1)1 X 1013

(2)1 X 1010

42 Approximate Reactance per 1000 m at 50 Hz (Ω)

0.077 0.072 0.072 0.071

43 Approximate Capacitance per 1000 m at 50 Hz (μF)

0.26 0.29 0.29 0.33

44 Safe Pulling Force

3 Kg/mm2 OR 30 N/mm2

45 Minimum Radius of Insulation

12 x Outer Diameter of Cable

46 Length per Drum (meter)-

(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

Page 52: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE - B9(1) GUARANTEED TECHNICAL PARAMETER LT CABLE (3½ CORE)(PVC INSULATION)

1 2 3 4 5 6 7 8 9 10 11 12 SR. NO

DESCRIPTION 3½ C X 16 mm2

3½ C X 25 mm2

3½ C X 35 mm2

3½ C X 50 mm2

3½ C X 70 mm2

3½ C X 95 mm2

3½ C X 120 mm2

3½ C X 150

mm2

3½ C X 185 mm2

3½ C X 240

mm2 1 Voltage

Grade(VOLT) 1100

2 Suitable for earthed or unearthed system

Both

CONDUCTOR- 3 Material Stranded Aluminium Conductor as per IS 8130 4 No. of strands per

core- (1) Main Core (2) Neutral

(1) 6 (2) 6

(1) 6 (2) 6

(1) 6 (2) 6

(1) 6 (2) 6

(1) 12 (2) 6

(1) 15 (2) 6

(1) 15 (2) 12

(1) 15 (2) 12

(1) 30 (2) 15

(1) 30 (2) 15

5 Diameter Of the conductor-(mm)

As per IS 8130

6 Nominal Cross-sectional area(mm2)- (1)Main (2)Neutral

As per IS (1)25.0 (2)16.0

(1)35.0 (2)16.0

(1)50.0 (2)25.0

(1)70.0 (2)35.0

(1)95.0 (2)50.0

(1)120.0 (2)70.0

(1)150.0 (2)70.0

(1)185.0 (2)95.0

(1)240.0 (2)120.0

7 Resistance at 20 °C (Ω/KM)(Max) (1) Main (2) Neutral

(1) 1.91 (2) As per IS

(1) 1.20 (2) 1.91

(1) 0.868 (2) 1.91

(1) 0.641 (2) 1.20

(1) 0.443 (2) 0.868

(1) 0.32 (2) 0.641

(1) 0.253 (2) 0.443

(1) 0.206 (2) 0.443

(1) 0.164 (2) 0.320

(1) 0.125 (2) 0.253

8 Resistivity(Ω-mm2/meter)

0.28264

9 Density (Gm/Cu-Cm)

2.703

Page 53: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

0.004

11 Coefficient of Linear Expansion per °C

23 x 10-6

12 Modulus of Elasticity (Kg/cm2)

6.96 x 103

CORE INSULATION- 13 Material PVC, Type-A XLPE, IS

7098-Part-1

14 Thickness of PVC Core Insulation (mm)- (1) Nominal (2) Minimum (3) Neutral

(1)1.0 (2)0.9

(3) As per IS

((1)1.2 (2)1.1 (3)1.0

(1)1.2 (2)1.1 (3)1.0

(1)1.4 (2)1.3 (3) 1.2

(1)1.4 (2)1.3 (3) 1.2

(1)1.6 (2)1.5 (3)1.4

(1)1.6 (2)1.5 (3)1.4

(1)1.8 (2)1.7 (3)1.4

(1)2.0 (2)1.9 (3)1.6

(1)1.7 (2)1.6 (3)1.5

15 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1 X1013

(2)1 X1010 (1) 1 X

1014

(2) 1 X 1012

16 Tensile Strength (N/mm2)(Min)

12.5 12.5

17 Elongation in % 150 200 18 Color code for

Core Identification As per IS 1554 Clause 10 As per IS

INNER SHEATH- 19 Material PVC, Type-ST-2 PVC,

FRLS, Type-ST-

2

Page 54: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

20 Thickness of PVC Inner Sheath(mm)- (1) Nominal (2) Minimum

(1)0.35 (2)0.3

(1)0.35 (2)0.3

(1)0.35 (2)0.3

(1)0.35 (2)0.3

(1)0.45 (2)0.4

(1)0.45 (2)0.4

(1)0.55 (2)0.5

(1)0.55 (2)0.5

(1)0.55 (2)0.5

(1)0.65 (2)0.6

21 Tensile Strength (N/mm2)(Min)

12.5

22 Elongation in % 150 23 Color code for

Identification Black

OUTER SHEATH- 24 Material PVC, Type-ST-2 PVC,

FRLS, Type-ST-2

25 Thickness of PVC Outer Sheath(mm)-(Minimum)

1.24 1.4 1.4 1.56 1.56 1.72 1.88 1.88 2.04 2.20

26 Tensile Strength (N/mm2)(Min)

12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5

27 Elongation in % 150 150 150 150 150 150 150 150 150 150 28 Color code for

Identification Black Black Black Black Black Black Black Black Black Black

ARMOUR- 29 Material/Type Galvanized Steel Flat Strip 30 Diameter Of Armour

Wire-(mm) (1)Nominal (2) Minimum

(1)0.85x4 (2)0.8 x 4

31 Resistance at 20 °C (Ω/KM)(Max)

As per IS

32 Tensile Strength (N/mm2)(Min)

As per IS

33 Elongation in % As per IS

Page 55: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

34 Density at 20 °C (Gm/Cu-Cm)

7.78

35 Coefficient of Linear Expansion per °C

11.5 x 10-6

36 Modulus of Elasticity (Kg/sq.cm)

As per IS

37 Overall Diameter of Armour-(mm)(min)

As per IS

GENERAL- 38 Overall Diameter of

cable-(mm)(min) 22 23 26 30 32 36 40 44 49 55

39 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

As per IS (1)76 (2)63 (3)70

(1)92 (2)77 (3)86

(1)110 (2)95 (3)105

(1)135 (2)115 (3)130

(1)165 (2)140 (3)155

(1)185 (2)155 (3)180

(1)210 (2)175 (3)205

(1)235 (2)200 (3)240

(1)325 (2)270 (3)400

40 Short Time Current Rating for 1 Sec. (KA)

1.22 1.90 2.66 3.80 5.32 7.22 9.12 11.40 14.10 22.60

41 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

(1)1X1013

(2)1X1010

42 Approximate Reactance per 1000 m at 50 Hz (Ω)

0.086 0.085 0.0827 0.0825 0.077 0.076 0.074 0.073 0.072 0.072

43 Approximate Capacitance per 1000 m at 50 Hz (μF)

0.80 0.84 0.96 0.98 1.12 1.16 1.28 1.29 1.30 1.34

Page 56: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

44 Safe Pulling Force - 3 Kg/m2 OR

30 N/mm2 45 Minimum Radius of

Insulation 12 x Outer Diameter of Cable

46 Length per Drum(meter)-

(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

SCHEDULE – B9(2)

GUARANTEED TECHNICAL PARAMETER LT CABLE (3½ CORE)(XLPE INSULATION)

1 2 3 SR. NO

DESCRIPTION 3½ C X 240 mm2

1 Voltage Grade(VOLT)

1100

2 Suitable for earthed or unearthed system

Both

CONDUCTOR- 3 Material Stranded Aluminium Conductor as per IS 8130 4 No. of strands

per core- (1) Main Core (2) Neutral

(1) 30 (2) 15

Page 57: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

5 Diameter Of the conductor-(mm)(min)

As per IS

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1) 240.0 (2) 120.0

7 Resistance at 20 °C (Ω/KM)(Max)

(1) 0.125 (2) 0.253

8 Resistivity(Ω-mm2/meter)

0.28264

9 Density (Gm/Cu-Cm)

2.703

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

0.004

11 Coefficient of Linear Expansion per °C

23 x 10-6

12 Modulus of Elasticity (Kg/cm2)

6.96 x103

CORE INSULATION- 13 Material XLPE, IS 7098-Part-1 14 Thickness of PVC

Core Insulation (mm) - (1) Nominal (2) Minimum (3) Neutral

(1)1.7 (2)1.6 (3)1.5

Page 58: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

15 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1 X 1014

(2)1 X 1012

16 Tensile Strength (N/mm2)(Min)

12.5

17 Elongation in % 200 18 Color code for

Core Identification

As per IS 7098-Part-2-Clause 14

INNER SHEATH- 19 Material PVC, FRLS, Type-ST-2 20 Thickness of PVC

Inner Sheath (mm)- (1) Nominal (2) Minimum

(1)0.65 (2)0.6

21 Tensile Strength (N/mm2)(Min)

12.5

22 Elongation in % 150 23 Color code for

Identification Black

OUTER SHEATH- 24 Material PVC, FRLS, Type-ST-2 25 Thickness of PVC

Outer Sheath (mm)-(Minimum)

2.2

26 Tensile Strength (N/mm2)(Min)

12.5

27 Elongation in % 150 28 Color code for

Identification Black

Page 59: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

ARMOUR- 29 Material/Type Galvanized Steel Flat Strip 30 Diameter Of

Armour Wire-(mm) (1)Nominal (2) Minimum

(1) 0.85 x 4 (2) 0.8 x 4

31 Resistance at 20 °C (Ω/KM)(Max)

As per IS

32 Tensile Strength (N/mm2)(Min)

As per IS

33 Elongation in % As per IS 34 Density at 20 °C

(Gm/Cu-Cm) 7.78

35 Coefficient of Linear Expansion per °C

11.5 x 10-6

36 Modulus of Elasticity (Kg/sq.cm)

As per IS

37 Overall Diameter of Armour-(mm)(min)

As per IS

GENERAL- 38 Overall Diameter

of cable-(mm)(min)

55

39 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

(1)325 (2)270 (3)400

Page 60: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

40 Short Time Current Rating for 1 Sec. (KA)

22.6

41 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

(1)1 X 1013

(2)1 X 1010

42 Approximate Reactance per 1000 m at 50 Hz (Ω)

0.072

43 Approximate Capacitance per 1000 m at 50 Hz (μF)

0.31

44 Safe Pulling Force

3 Kg/mm2 OR 30 N/mm2

45 Minimum Radius of Insulation

12 x Outer Diameter of Cable

46 Length per Drum (meter)-

(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

SCHEDULE - B10

GUARANTEED TECHNICAL PARAMETER CONTROL CABLE (2.5 mm2)

1 2 3 4 5 6 7 8 9 10 11 12 13 SR. NO

DESCRIPTION 2C X 2.5 mm2

3C X 2.5 mm2

4C X 2.5 mm2

5C X 2.5 mm2

7C X 2.5 mm2

9C X 2.5 mm2

12C X 2.5 mm2

14C X 2.5 mm

19C X 2.5 mm2

24C X 2.5 mm2

2C X 2.5 mm2

Page 61: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

1 Voltage Grade(VOLT)

1100

2 Suitable for earthed or unearthed system

Both

CONDUCTOR- 3 Material Stranded, Tinned, Annealed copper as per IS 8130 Stranded

Aluminium

Conductor as per IS 8130

4 No. of strands per core

3

5 Diameter Of the conductor-(mm) (1)Nominal (2) Minimum

(1)1.03 (2)1.03

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1)2.50 (2)2.50

7 Resistance at 20 °C (Ω/KM)(Max)

7.56

8 Resistivity(Ω-mm2/meter)

0.01724 0.28264

9 Density (Gm/Cu-Cm)

8.89 2.703

10 Constant Mass Temperature Coefficient for resistance - For Copper-per °C

0.0039 0.004

Page 62: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

11 Elongation in % , Minimum

18 ---

12 Coefficient of Linear Expansion per °C

17 x 10-6 23 x 10-6

13 Modulus of Elasticity (Kg/sq.cm)

9 to 10.5 x 103 6.96 x 103

CORE INSULATION- 14 Material PVC, Type-A 15 Thickness of PVC

Core Insulation (mm)- (1) Nominal (2) Minimum

0.9

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1 X 1013

(2)1 X 1010

17 Tensile Strength (N/mm2)(Min)

12.5

18 Elongation in % 150 19 Color code for

Core Identification As per IS 1554 Clause 10

INNER SHEATH- 20 Material PVC, Type-ST-1 21 Thickness of PVC

Inner Sheath(mm)- (1) Nominal (2) Minimum

(1)0.35 (2)0.3

22 Tensile Strength (N/mm2)(Min)

12.5

23 Elongation in % 150

Page 63: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

24 Color code for Identification

Black

OUTER SHEATH- 25 Material PVC, Type-ST-1 26 Thickness of PVC

Outer Sheath(mm)-(Minimum)

1.24 1.24 1.24 1.24 1.24 1.4 1.4 1.4 1.4 1.4 1.24

27 Tensile Strength (N/mm2)(Min)

12.5

28 Elongation in % 150 29 Color code for

Identification Black

ARMOUR- 30 Material/Type Galvani

z-ed Steel

Round Wire

Galvaniz-ed Steel Round Wire

Galvaniz-ed Steel Round Wire

Galvani-zed

Steel Round Wire

Galvanized

Steel Flat Strip

Galvanized

Steel Flat Strip

Galvanized

Steel Flat Strip

Galvanized

Steel Flat Strip

Galvanized

Steel Flat Strip

Galvanized Steel Flat Strip

Galvaniz-ed Steel Round Wire

31 Diameter Of Armour Wire-(mm) (1)Nominal (2) Minimum

(1)1.40 (2)1.34

(1) 0.85 x 4 (2) 0.8 x 4

(1)1.40 (2)1.34

32 Resistance at 20 °C (Ω/KM)(Max)

5.54

33 Tensile Strength (N/mm2)(Min)

As per IS

34 Elongation in % As per IS 35 Density at 20 °C

(Gm/Cu-Cm) 7.78

36 Coefficient of Linear Expansion per °C

19.5 x 10-6

Page 64: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

37 Modulus of Elasticity (Kg/sq.cm)

19.7 x 103

38 Overall Diameter of Armour-(mm) (min)

As per IS

GENERAL- 39 Overall Diameter

of cable-(mm)(min)

14 15 16 17 18 20 22 23 25 29 14

40 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

(1)32 (2)27 (3)27

(1)27 (2)24 (3)24

(1)27 (2)24 (3)24

(1)27 (2)24 (3)24

(1)20 (2)17 (3)17

(1)18 (2)15 (3)15

(1)17 (2)14 (3)14

(1)16 (2)13 (3)13

(1)14 (2)12 (3)12

(1)13 (2)11 (3)11

(1)25 (2)21 (3)21

41 Short Time Current Rating for 1 Sec. (KA)

0.288 0.188

42 Rated DC Voltage (VOLTS)

220

43 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

(1)1 X 1014

(2) 1 X 1010

44 Approximate Reactance per 1000 m at 50 Hz (Ω)

0.11

45 Approximate Capacitance per 1000 m at 50 Hz (μF)

0.41

Page 65: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

46 Safe Pulling Force - 5 Kg/mm2 OR

50 N/mm2

3 Kg/mm2 OR 30 N/mm2

47 Minimum Radius of Insulation

12 x Outer Diameter of Cable

48 Length per Drum (meter)- (1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

1)500 (2)525 (3)475

Page 66: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – B11 GUARANTEED TECHNICAL PARAMETER

HEAT RTESISTANT CABLE 1 2 3 4 5

SR. NO

DESCRIPTION 1 C X 1.5 mm2

1 C X 2.5 mm2 1 C X 4 mm2

1 Voltage Grade(VOLT) 1100 2 Suitable for earthed or

unearthed system Both

CONDUCTOR- 3 Material Stranded, Tinned, Annealed copper as per IS 8130 4 No. of strands per core 19 19 19 5 Diameter Of the

conductor-(mm)(min) As per IS 8130

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1)1.5 (2)1.5

(1)2.5 (2)2.5

(1)4.0 (2)4.0

7 Resistance at 20 °C (Ω/KM)(Max)

13.7 8.21 5.09

8 Resistivity(Ω-mm2/meter) 0.01724 9 Density (Gm/Cu-Cm) 8.89

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

0.0039

11 Elongation in % , Minimum 18 12 Coefficient of Linear

Expansion per °C 17 x 10-6

13 Modulus of Elasticity (Kg/cm2)

9 to 10.5 x 103

CORE INSULATION- 14 Material TEFLON coated PVC 15 Thickness of PVC Core

Insulation (mm)- (1) Nominal (2) Minimum

As per IS

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

As per IS

17 Tensile Strength (N/mm2)(Min)

As per IS

18 Elongation in % As per IS 19 Color code for Core

Identification As per IS

Page 67: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

GENERAL- 20 Overall Dimension of

Cable-(mm)(max) As per IS

21 Continuous Current Rating (Amp)-

24 18 31

22 Short Time Current Rating for 1 Sec. (KA)

0.219 0.365 0.584

23 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

(1)1 X 1013

(2)1 X 1010

24 High Temperature Operation Capacity

150 ° C

24 Approximate Reactance per 1000 m at 50 Hz (Ω)

As per IS

25 Approximate Capacitance per 1000 m at 50 Hz (μF)

As per IS

26 Safe Pulling Force - 5 Kg/mm2 OR

50 N/mm2 27 Minimum Radius of

Insulation 12 x Outer Diameter of Cable

28 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

Page 68: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – B12 GUARANTEED TECHNICAL PARAMETER

OPTIC FIBER CABLE

CHARACTERISTIC

MIN. REQUIRED SPECIFICATION FOR OFC

GENERAL

Unitube Armoured fiber optic cable The fiber type is a Matched Cladding Single Mode The fiber is optimized for operation at 1310 nm and at 1550 nm Outer Sheath HDPE – Black/Suitable colour Should fulfill the requirements of: IEC 793-2: 1992, EN 188101 ITU-T Recommendation G.652

Testing methods are in accordance with the following standards: ISO 11801 IEC 60793-1/60794-1-2 ITU-T G.652.D

GEOMETRICAL PROPERTIES

Nominal mode field diameter 9.2 µm

Number of Core 12 (twelve) Mode field diameter tolerance ±4% Cladding diameter 125 µm Cladding diameter tolerance ±1 µm Mode field concentricity error < 1 µm Cladding non-circularity < 2 % MATERIALS CORE

Germanium doped core with no phosphorus i.e. reduced tendency for hydrogen degradation

COATING UV-curable dual layer acryl ate coating, which ensures excellent micro bending and abrasion resistance.

PHYSICAL PROPERTIES

Strength Member-FRP 1.8 ± 0.1

OPTICAL PROPERTIES

Attenuation (of cable with fibers):

At 1310 nm <= 0.38 dB/km In the range 1285-1330 nm <= 0.40dB/km At 1550 nm <= 0.25 dB/km DRUM As per IS

Page 69: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – B13 GUARANTEED TECHNICAL PARAMETER

POWER CABLE FOR EXCITATION SYSTEM 1 2 3

SR. NO

DESCRIPTION 1 C X 630 mm2

1 Voltage Grade (VOLT) 1100 2 Suitable for earthed or

unearthed system Both

CONDUCTOR- 3 Material Stranded Annealed Tinned High Conductivity

Copper Conductor as per IS 8130 4 No. of strands/Diameter

(For reference only) 2257/0.6

(As per IS and to meet DC Resistance) 5 Diameter Of the

conductor-(mm)(min) As per IS

6

Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1) 630 (2) 630

7 Resistance at 20 °C (Ω/KM)(Max)

0.0292

8 Resistivity(Ω-mm2/meter) 0.01724 9 Density (Gm/Cu-Cm) 8.89

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

0.0039

11 Elongation in % , Minimum

18

12 Coefficient of Linear Expansion per °C

17 x 10-6

13 Modulus of Elasticity (Kg/cm2)

9 to 10.5 x 103

CORE INSULATION- 14 Material Extruded PVC, Type-A 15 Thickness of PVC Core

Insulation (mm)- Nominal

3.9

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1 X 1013

(2)1 X 1010

17 Tensile Strength (N/mm2)(Min)

12.5

18 Elongation in % 150

Page 70: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

19 Color code for Core Identification

As per IS 1554 Clause 10

OUTER SHEATH- 20 Material Extruded PVC, FRLS, Type-ST-1

21 Thickness of PVC Outer Sheath(mm)-(Minimum)

2.04

22 Tensile Strength (N/mm2)(Min)

12.5

23 Elongation in % 150 24 Color code for Core

Identification Black

25 Overall Diameter of cable-(mm)(min)

53

ARMOUR- 26 Material/Type Galvanized Steel Flat Strip

27 Diameter Of Armour Wire-(mm) (1)Nominal (2) Minimum

(1) 0.85 x 4 (2) 0.8 x 4

28 Resistance at 20 °C (Ω/KM)(Max)

As per IS

29 Tensile Strength (N/mm2)(Min)

As per IS

30 Elongation in % As per IS 31 Density at 20 °C (Gm/Cu-

Cm) 7.78

32 Coefficient of Linear Expansion per °C

11.5 x 10-6

33 Modulus of Elasticity (Kg/sq.cm)

19.7 x 103

GENERAL- 34 Overall Diameter of

Armour-(mm)(min) As per IS

35 Continuous Current Rating (A)- (1) In Ground (2) In Duct (3) In Air

(1) 470 (2) 375 (3) 660

36 Short Time Current Rating for 1 Sec. (KA)

72.5

37 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

(1)1 X 1013

(2)1 X 1010

Page 71: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

38 Approximate Reactance per 1000 m at 50 Hz (Ω)

0.083

39 Approximate Capacitance per 1000 m at 50 Hz (μF)

1.6

40 Safe Pulling Force - 5 Kg/mm2 OR

50 N/mm2 41 Minimum Radius of

Insulation 15 x Outer Diameter of Cable

42 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

43 Purpose For excitation system: For Field voltage/current from Excitation panel to Generator slip-rings.

SCHEDULE – B14

GUARANTEED TECHNICAL PARAMETER INSTRUMENT CABLE

1 2 3 4 5 6 SR. NO

DESCRIPTION 2 P X 0.5 mm2

4 P X 0.5 mm2

8 P X 0.5 mm2

10 P X 0.5 mm2

1 Voltage Grade (VOLT)

1100

2 Suitable for earthed or unearthed system

Both

CONDUCTOR- 3 Material Stranded Annealed Tinned High Conductivity Copper

Conductor as per IS 8130 4 No. of strands per

core 7

5 Diameter Of the conductor-(mm)(min)

As per IS

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

(1)0.5 (2)0.5

7 Resistance at 20 °C (Ω/KM)(Max)

As per IS

8 Resistivity(Ω-mm2/meter)

0.01724

9 Density (Gm/Cu-Cm)

8.89

10 Constant Mass Temperature Coefficient for resistance – For Aluminium-per °C

0.0039

Page 72: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

11 Elongation in % , Minimum

18

12 Coefficient of Linear Expansion per °C

17 x 10-6

13 Modulus of Elasticity (Kg/cm2)

9 to 10.5 x 103

CORE INSULATION- 14 Material PVC, Type-C 15 Thickness of PVC

Core Insulation (mm)- Minimum

0.6

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

(1)1 X 1013

(2)1 X 1010

17 Tensile Strength (N/mm2)(Min)

12.5

18 Elongation in % 150 19 Color code for Core

Identification As per IS

OVERALL SCREENING- 20 Material Aluminium Polyester Tap Screen with Copper Drain Wire

INNER SHEATH- 21 Material PVC, FRLS, Type-ST-1 22 Thickness of PVC

Inner Sheath(mm)- Nominal

1.3 1.4 1.6 1.6

23 Tensile Strength (N/mm2)(Min)

12.5

24 Elongation in % 150 25 Color code for Core

Identification As per IS

OUTER SHEATH- 26 Material PVC, FRLS, Type-ST-1 27 Thickness of PVC

Outer Sheath(mm)-(Minimum)

1.3 1.4 1.6 1.6

28 Tensile Strength (N/mm2)(Min)

12.5

29 Elongation in % 150 30 Color code for Core

Identification As per IS

31 Overall Diameter of cable-(mm)(min)

12 17 20 22

ARMOUR- 32 Material/Type Galvanized Steel Round Wire 33 Diameter Of Armour

Wire-(mm) Nominal

0.9 0.9 1.25 1.25

Page 73: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

34 Resistance at 20 °C (Ω/KM)(Max)

As per IS

35 Tensile Strength (N/mm2)(Min)

As per IS

36 Elongation in % As per IS 37 Density at 20 °C

(Gm/Cu-Cm) 7.78

38 Coefficient of Linear Expansion per °C

11.5 x 10-6

39 Modulus of Elasticity (Kg/sq.cm)

19.7 x 103

GENERAL- 40 Continuous Current

Rating (A) As per IS 3961

41 Safe Pulling Force - 5 Kg/mm2 OR

50 N/mm2 42 Minimum Radius of

Insulation 12 x Outer Diameter of Cable

43 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

(1)500 (2)525 (3)475

Page 74: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – C1 GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

TELEPHONE CABLE 1 2 3 4 5 6 7 8

SR. NO DESCRIPTION 5 P X 0.5 mm

20 P X 0.5 mm

50 P X 0.5 mm

10 P X 0.63 mm

20 P X 0.63 mm

50 P X 0.63 mm

1 Voltage Grade(AC, VOLT)

2 Suitable for earthed or unearthed system

CONDUCTOR- 3 Material

4 No. of Pair 5 Diameter Of the

conductor-(mm)(min)

7 Resistance at 20 °C (Ω/KM)(Max)

8 Resistivity(Ω-mm2/meter) 9 Density (Gm/Cu-Cm)

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

Elongation in % , Minimum

11 Coefficient of Linear Expansion per °C

12 Modulus of Elasticity (Kg/cm2)

CORE INSULATION- 13 Material 14 Thickness of PVC Core

Insulation(mm)- (Minimum)

15 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

Page 75: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

16 Tensile Strength (N/mm2)(Min)

17 Elongation in % 18 Color code for Core

Identification

INNER SHEATH- 19 Material 20 Thickness of PVC Inner

Sheath(mm)- (Minimum)

21 Tensile Strength (N/mm2)(Min)

22 Elongation in % 23 Color code for Core

Identification

OUTER SHEATH- 24 Material 25 Thickness of PVC Outer

Sheath(mm)-(Minimum)

26 Tensile Strength (N/mm2)(Min)

27 Elongation in % 28 Color code for Core

Identification

29 Overall Diameter of cable-(mm)(min)

ARMOUR- 30 Material/Type 31 Diameter Of Armour

Wire-(mm) (1)Nominal (2) Minimum

32 Resistance at 20 °C (Ω/KM)(Max)

33 Tensile Strength (N/mm2)(Min)

34 Elongation in % 35 Density at 20 °C(Gm/Cu-

Cm)

36 Coefficient of Linear Expansion per °C

37 Modulus of Elasticity (Kg/sq.cm)

38 Overall Diameter of Armour-(mm)(min)

GENERAL- 39 Mutual Capacitance-

(nF/KM)(Max)

Page 76: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

40 Short Time Current Rating for 1 Sec. (KA)

41 Insulation Resistance (MΩ/KM)-(min)

44 Safe Pulling Force -

45 Minimum Radius of Insulation

46 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_________

SCHEDULE – C2(1) GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

TRAILING CABLE (LT) 1 2 3

SR. NO DESCRIPTION 12C X 2.5 mm2 + 12C X 2.5 mm2 (Screen) 1 Voltage Grade(VOLT) 2 Suitable for earthed or

unearthed system

3 Applicable Standard CONDUCTOR-

4 Material 5 No. of strands per

core/Dia(max)(mm)

6 Diameter Of the conductor-(mm)(min)

7 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

8 Resistance at 20 °C (Ω/KM)(Max)

Page 77: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

9 Resistivity(Ω-mm2/meter)

10 Density (Gm/Cu-Cm) 11 Constant Mass

Temperature Coefficient for resistance - For Copper-per °C

12 Elongation in % , Minimum

13 Coefficient of Linear Expansion per °C

14 Modulus of Elasticity (Kg/cm2)

CORE INSULATION- 15 Material 16 Thickness of PVC Core

Insulation (mm)-(Nominal)

17 Insulation Resistance(MΩ-cm)- (1)At 20 °C (2)At 90 °C

18 Tensile Strength (N/mm2)(Min)

19 Elongation in % 20 Color code for Core

Identification

CONDUCTOR SCREEN- 21 Material/Type

INSULATION SCREEN- 22 Material/Type

REINFORCEMENT- 23 Material/Type

SHEATH- 24 Material 25 Thickness of PVC

Sheath(mm)- (1) Inner (2) Outer

26 Tensile Strength (N/mm2)(Min)

27 Elongation in % 28 Color code for Core

Identification

29 Overall Diameter -(mm)(min)

GENERAL- 30 Continuous Current

Rating at 40 ºC(Amp)-

Page 78: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

31 Short Time Current Rating for 1 Sec. (KA)

32 Safe Pulling Force - 33 Minimum Radius of

Insulation

34 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

35 Net Weight of Cable (KG)

36 Drum Weight (KG)

Name of Bidder: ______________ Signature of the Bidder: ___________ Name : __________________________

Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_________

SCHEDULE – C2(2) GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder)

The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

TRAILING CABLE (HT) 1 2 3 4

SR. NO DESCRIPTION 3C X 25 mm2 + 3C X 25/3(8.33) mm2

4C X 35 mm2

1 Voltage Grade(VOLT) 2 Suitable for earthed or

unearthed system

3 Applicable Standard CONDUCTOR-

4 Material 5 No. of strands per

core/Dia(max)(mm)

6 Diameter Of the conductor-(mm)(min)

7 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

8 Resistance at 20 °C (Ω/KM)(Max)

9 Resistivity(Ω-mm2/meter)

Page 79: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

10 Density (Gm/Cu-Cm) 11 Constant Mass

Temperature Coefficient for resistance - For Copper-per °C

12 Elongation in % , Minimum

13 Coefficient of Linear Expansion per °C

14 Modulus of Elasticity (Kg/cm2)

CORE INSULATION- 15 Material 16 Thickness of PVC Core

Insulation (mm)-(Nominal)

17 Insulation Resistance(MΩ-cm)- (1)At 20 °C (2)At 90 °C

18 Tensile Strength (N/mm2)(Min)

19 Elongation in % 20 Color code for Core

Identification

CONDUCTOR SCREEN- 21 Material/Type

INSULATION SCREEN- 22 Material/Type

REINFORCEMENT- 23 Material/Type

SHEATH- 24 Material 25 Thickness of PVC

Sheath(mm)- (1) Inner (2) Outer

26 Tensile Strength (N/mm2)(Min)

27 Elongation in % 28 Color code for Core

Identification

29 Overall Diameter -(mm)(min)

GENERAL- 30 Continuous Current

Rating at 40 ºC(Amp)-

31 Short Time Current Rating for 1 Sec. (KA)

32 Safe Pulling Force -

Page 80: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

33 Minimum Radius of Insulation

34 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

35 Net Weight of Cable (KG)

36 Drum Weight (KG)

Name of Bidder: ______________ Signature of the Bidder: ___________ Name : __________________________

Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_________

SCHEDULE – C3 GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

CONTROL CABLE (1.5 mm2)

1 2 3 4 5 6 SR. NO DESCRIPTION 3C X 1.5

mm2 7C X 1.5

mm2 12C X 1.5

mm2 24C X 1.5

mm2 1 Voltage Grade

(VOLT)

2 Suitable for earthed or

unearthed system

CONDUCTOR- 3 Material 4 No. of strands per

core

5 Diameter Of the conductor-(mm)(min)

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

7 Resistance at 20 °C (Ω/KM)(Max)

8 Resistivity(Ω-

mm2/meter)

Page 81: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

9 Density (Gm/Cu-Cm)

10 Constant Mass

Temperature Coefficient for resistance - For Aluminium-per °C

11 Elongation in % , Minimum

12 Coefficient of

Linear Expansion per °C

13 Modulus of Elasticity (Kg/cm2)

CORE INSULATION-

14 Material 15 Thickness of PVC

Core Insulation (mm)- (1) Nominal (2) Minimum

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

17 Tensile Strength (N/mm2)(Min)

18 Elongation in % 19 Color code for

Core Identification

INNER SHEATH- 20 Material 21 Thickness of PVC

Inner Sheath(mm)- (1) Nominal (2) Minimum

22 Tensile Strength (N/mm2)(Min)

23 Elongation in % 24 Color code for

Core Identification

OUTER SHEATH- 25 Material 26 Thickness of PVC

Outer Sheath(mm)-(Minimum)

27 Tensile Strength (N/mm2)(Min)

28 Elongation in % 29 Color code for

Core Identification

30 Overall Diameter

Page 82: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

of cable-(mm)(min)

ARMOUR- 31 Material/Type 32 Diameter Of

Armour Wire-(mm) (1)Nominal (2) Minimum

33 Resistance at 20 °C (Ω/KM)(Max)

34 Tensile Strength

(N/mm2)(Min)

35 Elongation in % 36 Density at 20 °C

(Gm/Cu-Cm)

37 Coefficient of Linear Expansion per °C

38 Modulus of Elasticity (Kg/sq.cm)

GENERAL- 39 Overall Diameter

of Armour-(mm)(min)

40 Continuous Current Rating (A)- (1) In Ground (2) In Duct (3) In Air

41 Short Time Current Rating for 1 Sec. (KA)

42 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

43 Approximate Reactance per 1000 m at 50 Hz (Ω)

44 Approximate Capacitance per 1000 m at 50 Hz (μF)

45 Safe Pulling Force - 46 Minimum Radius of

Insulation

47 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

Page 83: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

48 Net Weight of Cable (KG)

49 Drum Weight (KG)

Name of Bidder: ______________ Signature of the Bidder: ___________ Name : __________________________

Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_________

SCHEDULE – C4 GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

FLEXIBLE CABLE 1 2 3 4 5 6 7

SR. NO DESCRIPTION 1C X 50 mm2

1C X 70 mm2

1C X 16 mm2

4C X 6 mm2

3C X 2.5 mm2

1 Voltage Grade(VOLT)

2 Suitable for earthed

or unearthed system

CONDUCTOR- 3 Material 4 No. of strand/wires

per core

5 Diameter/Size Of the conductor-(mm)(min)

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

7 Resistance at 20 °C (Ω/KM)(Max)

8 Resistivity(Ω-mm2/meter)

9 Density (Gm/Cu-

Cm)

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

11 Elongation in % , Minimum

Page 84: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

12 Coefficient of Linear Expansion per °C

13 Modulus of Elasticity

(Kg/cm2)

CORE INSULATION- 14 Material 15 Thickness of PVC

Core Insulation (mm)-(Nominal)

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

17 Tensile Strength (N/mm2)(Min)

18 Elongation in % 19 Color code for Core

Identification

SHEATH- 20 Material 21 Thickness of PVC

Inner Sheath(mm)- Nominal

22 Tensile Strength (N/mm2)(Min)

23 Elongation in % 24 Color code for Core

Identification

GENERAL- 25 Overall Diameter of

cable-(mm)(min)

26 Continuous Current Rating (Amp)-

27 Short Time Current Rating for 1 Sec. (KA)

28 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

29 Approximate Reactance per 1000 m at 50 Hz (Ω)

30 Approximate Capacitance per 1000 m at 50 Hz (μF)

31 Safe Pulling Force - 32 Minimum Radius of

Insulation

33 Length per Drum(meter)-(1)Nominal (2)Maximum

Page 85: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

(3)Minimum 34 Net Weight of Cable

(KG)

35 Drum Weight (KG)

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:________

SCHEDULE – C5

GURANTEED TECHNICAL PARTICULARS (To be filled by the Bidder)

The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

FLAT CABLE FLAT/FLEXIBLE 1 2 3 4 5

SR. NO

DESCRIPTION 3C X 4 mm2

(SUB-MERSIBLE) 3C X 2.5 mm2 3C X 6 mm2

1 Voltage Grade(VOLT) 2 Suitable for earthed or

unearthed system

CONDUCTOR- 3 Material 4 No. of strands/Diameter

(mm) per core

5 Diameter Of the conductor-(mm)(min)

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

7 Resistance at 20 °C (Ω/KM)(Max)

8 Resistivity(Ω-mm2/meter) 9 Density (Gm/Cu-Cm)

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

11 Elongation in % , Minimum 12 Coefficient of Linear

Expansion per °C

13 Modulus of Elasticity (Kg/cm2)

Page 86: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

CORE INSULATION- 14 Material 15 Thickness of PVC Core

Insulation (mm)- (1) Nominal (2) Minimum

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

17 Tensile Strength (N/mm2)(Min)

18 Elongation in % 19 Color code for Core

Identification

INNER SHEATH- 20 Material 21 Thickness of PVC Inner

Sheath(mm)- Nominal

22 Tensile Strength (N/mm2)(Min)

23 Elongation in %

24 Color code for Core Identification

GENERAL- 25 Overall Dimension of

Cable-(mm)(max)

26 Continuous Current Rating (Amp)-

27 Short Time Current Rating for 1 Sec. (KA)

28 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

29 Approximate Reactance per 1000 m at 50 Hz (Ω)

30 Approximate Capacitance per 1000 m at 50 Hz (μF)

31 Safe Pulling Force - 32 Minimum Radius of

Insulation

33 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

Page 87: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

34 Net Weight of Cable (KG)

35 Drum Weight (KG)

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_________

Page 88: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – C6 GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

OTHER TYPES 1 2 3 4 5 6 7 8 9 10 11 12

SR. NO

DESCRIPTION 2C X 4 mm2

4C X 4 mm2

2C X 4 mm3

4C X 6 mm2

4C X 16 mm2

4C X 16mm2

4C X 10 mm3

4C X 4 mm2

4C X 10 mm2

4C X 25 mm2

1 Voltage Grade(VOLT)

2 Suitable for earthed or unearthed system

CONDUCTOR- 3 Material 4 No. of strands per

core

5 Diameter Of the conductor-(mm)(min)

6

Cross-sectional area(mm2)- (1)Nominal (2)Minimum

7 Resistance at 20 °C (Ω/KM)(Max)

8 Resistivity(Ω-mm2/meter)

9 Density (Gm/Cu-Cm)

Page 89: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

11 Elongation in % , Minimum

12 Coefficient of Linear Expansion per °C

13 Modulus of Elasticity (Kg/cm2)

CORE INSULATION- 14 Material

15 Thickness of PVC Core Insulation (mm)- (1) Nominal (2) Minimum

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

17 Tensile Strength (N/mm2)(Min)

18 Elongation in % 19 Color code for

Core Identification

INNER SHEATH- 20 Material 21 Thickness of PVC

Page 90: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

Inner Sheath (mm)- (1) Nominal (2) Minimum

22 Tensile Strength (N/mm2)(Min)

23 Elongation in % 24 Color code for

Identification

OUTER SHEATH- 25 Material

26 Thickness of PVC Outer Sheath (mm)-(Minimum)

27 Tensile Strength (N/mm2)(Min)

28 Elongation in %

29 Color code for Identification

ARMOUR- 30 Material/Type 31 Diameter Of

Armour Wire-(mm) (1)Nominal (2) Minimum

32 Resistance at 20 °C (Ω/KM)(Max)

Page 91: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

33 Tensile Strength (N/mm2)(Min)

34 Elongation in %

35 Density at 20 °C (Gm/Cu-Cm)

36 Coefficient of Linear Expansion per °C

37 Modulus of Elasticity (Kg/sq.cm)

38 Overall Diameter of Armour-(mm)(min)

GENERAL- 39 Overall Diameter -

(mm)(min)

40 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

41 Short Time Current Rating for 1 Sec. (KA)

42 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

Page 92: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

43 Approximate Reactance per 1000 m at 50 Hz (Ω)

44 Approximate Capacitance per 1000 m at 50 Hz (μF)

45 Safe Pulling Force - 46 Minimum Radius of

Insulation

47 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

48 Net Weight of Cable (KG)

49 Drum Weight (KG)

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:________

Page 93: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – C8 (1) GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

LT CABLE (3 CORE)(PVC INSULATION) 1 2 3 4 5 6 7 8 9 10 11 12 13

SR. NO

DESCRIPTION 3C X 16 mm2

3C X 6 mm3

3C X 10 mm3

3C X 25 mm2

3C X 35 mm2

3C X 50 mm2

3C X 70 mm3

3C X 95 mm2

3C X150 mm2

3C X185 mm2

3C X300 mm2

1 Voltage Grade(VOLT)

2 Suitable for earthed or unearthed system

CONDUCTOR- 3 Material 4 No. of strands per

core

5 Diameter Of the conductor-(mm)(min)

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

7 Resistance at 20 °C (Ω/KM)(Max)

8 Resistivity(Ω-mm2/meter)

Page 94: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

9 Density (Gm/Cu-Cm)

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

11 Coefficient of Linear Expansion per °C

12 Modulus of Elasticity (Kg/cm2)

CORE INSULATION- 13 Material 14 Thickness of PVC

Core Insulation (mm) - (1) Nominal (2) Minimum

15 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

16 Tensile Strength (N/mm2)(Min)

17 Elongation in % 18 Color code for

Core Identification

INNER SHEATH- 19 Material

Page 95: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

20 Thickness of PVC Inner Sheath (mm)- (1) Nominal (2) Minimum

21 Tensile Strength (N/mm2)(Min)

22 Elongation in % 23 Color code for

Identification

OUTER SHEATH- 24 Material 25 Thickness of PVC

Outer Sheath(mm)-(Minimum)

26 Tensile Strength (N/mm2)(Min)

27 Elongation in % 28 Color code for

Identification

ARMOUR- 29 Material/Type 30 Diameter Of

Armour Wire-(mm) (1)Nominal (2) Minimum

31 Resistance at 20 °C (Ω/KM)(Max)

32 Tensile Strength (N/mm2)(Min)

33 Elongation in %

Page 96: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

34 Density at 20 °C (Gm/Cu-Cm)

35 Coefficient of Linear Expansion per °C

36 Modulus of Elasticity (Kg/sq.cm)

37 Overall Diameter of Armour-(mm)(min)

GENERAL- 38 Overall Diameter

of cable-(mm)(min)

39 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

40 Short Time Current Rating for 1 Sec. (KA)

41 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

42 Approximate Reactance per 1000 m at 50 Hz (Ω)

Page 97: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

43 Approximate Capacitance per 1000 m at 50 Hz (μF)

44 Safe Pulling Force

45 Minimum Radius of Insulation

46 Length per Drum (meter)- (1)Nominal (2)Maximum (3)Minimum

47 Net Weight of Cable (KG)

48 Drum Weight (KG)

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_________

Page 98: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – C8 (2) GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

LT CABLE (3 CORE)(XLPE INSULATION) 1 2 3 4 5 6

SR. NO

DESCRIPTION 3C X 70 mm3 3C X120 mm2 3C X185 mm2 3C X300 mm2

1 Voltage Grade(VOLT)

2 Suitable for earthed or unearthed system

CONDUCTOR- 3 Material 4 No. of strands

per core

5 Diameter Of the conductor-(mm)(min)

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

7 Resistance at 20 °C (Ω/KM)(Max)

8 Resistivity(Ω-

Page 99: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

mm2/meter) 9 Density (Gm/Cu-

Cm)

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

11 Coefficient of Linear Expansion per °C

12 Modulus of Elasticity (Kg/cm2)

CORE INSULATION- 13 Material 14 Thickness of PVC

Core Insulation (mm) - (1) Nominal (2) Minimum

15 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

16 Tensile Strength (N/mm2)(Min)

17 Elongation in % 18 Color code for

Core Identification

Page 100: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

INNER SHEATH- 19 Material

20 Thickness of PVC Inner Sheath (mm)- (1) Nominal (2) Minimum

21 Tensile Strength (N/mm2)(Min)

22 Elongation in % 23 Color code for

Identification

OUTER SHEATH- 24 Material

25 Thickness of PVC Outer Sheath (mm)-(Minimum)

26 Tensile Strength (N/mm2)(Min)

27 Elongation in % 28 Color code for

Identification

ARMOUR- 29 Material/Type

30 Diameter Of Armour Wire-(mm) (1)Nominal (2) Minimum

Page 101: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

31 Resistance at 20 °C (Ω/KM)(Max)

32 Tensile Strength (N/mm2)(Min)

33 Elongation in % 34 Density at 20 °C

(Gm/Cu-Cm)

35 Coefficient of Linear Expansion per °C

36 Modulus of Elasticity (Kg/sq.cm)

37 Overall Diameter of Armour-(mm)(min)

GENERAL- 38 Overall Diameter

of cable-(mm)(min)

39 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

40 Short Time Current Rating for 1 Sec. (KA)

41 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

Page 102: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

42 Approximate Reactance per 1000 m at 50 Hz (Ω)

43 Approximate Capacitance per 1000 m at 50 Hz (μF)

44 Safe Pulling Force

45 Minimum Radius of Insulation

46 Length per Drum (meter)-

(1)Nominal (2)Maximum (3)Minimum

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_________

Page 103: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – C9(1) GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

LT CABLE (3½ CORE)(PVC INSULATION) 1 2 3 4 5 6 7 8 9 10 11 12

SR. NO

DESCRIPTION 3½ C X 16 mm2

3½ C X 25 mm2

3½ C X 35 mm2

3½ C X 50 mm2

3½ C X 70 mm2

3½ C X 95 mm2

3½ C X 120 mm2

3½ C X 150

mm2

3½ C X 185 mm2

3½ C X 240

mm2 1 Voltage

Grade(VOLT)

2 Suitable for earthed or unearthed system

CONDUCTOR- 3 Material

4 No. of strands per core- (1) Main Core (2) Neutral

5 Diameter Of the conductor-(mm)

6 Nominal Cross-sectional area(mm2)- (1)Main (2)Neutral

Page 104: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

7 Resistance at 20 °C (Ω/KM)(Max) (1) Main (2) Neutral

8 Resistivity(Ω-mm2/meter)

9 Density (Gm/Cu-Cm)

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

11 Coefficient of Linear Expansion per °C

12 Modulus of Elasticity (Kg/cm2)

CORE INSULATION- 13 Material 14 Thickness of PVC

Core Insulation (mm)- (1) Nominal (2) Minimum (3) Neutral

15 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

16 Tensile Strength (N/mm2)(Min)

17 Elongation in %

Page 105: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

18 Color code for Core Identification

INNER SHEATH- 19 Material

20 Thickness of PVC Inner Sheath(mm)- (1) Nominal (2) Minimum

21 Tensile Strength (N/mm2)(Min)

22 Elongation in % 23 Color code for

Identification

OUTER SHEATH- 24 Material 25 Thickness of PVC

Outer Sheath(mm)-(Minimum)

26 Tensile Strength (N/mm2)(Min)

27 Elongation in % 28 Color code for

Identification

ARMOUR- 29 Material/Type 30 Diameter Of Armour

Wire-(mm) (1)Nominal (2) Minimum

31 Resistance at 20 °C

Page 106: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

(Ω/KM)(Max)

32 Tensile Strength (N/mm2)(Min)

33 Elongation in % 34 Density at 20 °C

(Gm/Cu-Cm)

35 Coefficient of Linear Expansion per °C

36 Modulus of Elasticity (Kg/sq.cm)

37 Overall Diameter of Armour-(mm)(min)

GENERAL- 38 Overall Diameter of

cable-(mm)(min)

39 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

40 Short Time Current Rating for 1 Sec. (KA)

41 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

42 Approximate Reactance per 1000 m at 50 Hz (Ω)

Page 107: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

43 Approximate Capacitance per 1000 m at 50 Hz (μF)

44 Safe Pulling Force -

45 Minimum Radius of Insulation

46 Length per Drum(meter)-

(1)Nominal (2)Maximum (3)Minimum

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_________

Page 108: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – C9(2) GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

SCHEDULE – B9(2) GUARANTEED TECHNICAL PARAMETER

LT CABLE (3½ CORE)(XLPE INSULATION) 1 2

SR. NO

DESCRIPTION

1 Voltage Grade(VOLT)

2 Suitable for earthed or unearthed system

CONDUCTOR- 3 Material 4 No. of strands

per core- (1) Main Core (2) Neutral

5 Diameter Of the conductor-(mm)(min)

Page 109: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

7 Resistance at 20 °C (Ω/KM)(Max)

8 Resistivity(Ω-mm2/meter)

9 Density (Gm/Cu-Cm)

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

11 Coefficient of Linear Expansion per °C

12 Modulus of Elasticity (Kg/cm2)

CORE INSULATION- 13 Material 14 Thickness of PVC

Core Insulation (mm) - (1) Nominal (2) Minimum (3) Neutral

15 Volume Resistivity (Ω/cm)- (1)At 20 °C

Page 110: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

(2)At 70 °C

16 Tensile Strength (N/mm2)(Min)

17 Elongation in % 18 Color code for

Core Identification

INNER SHEATH- 19 Material 20 Thickness of PVC

Inner Sheath (mm)- (1) Nominal (2) Minimum

21 Tensile Strength (N/mm2)(Min)

22 Elongation in % 23 Color code for

Identification

OUTER SHEATH- 24 Material 25 Thickness of PVC

Outer Sheath (mm)-(Minimum)

26 Tensile Strength (N/mm2)(Min)

27 Elongation in % 28 Color code for

Identification

ARMOUR-

Page 111: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

29 Material/Type 30 Diameter Of

Armour Wire-(mm) (1)Nominal (2) Minimum

31 Resistance at 20 °C (Ω/KM)(Max)

32 Tensile Strength (N/mm2)(Min)

33 Elongation in % 34 Density at 20 °C

(Gm/Cu-Cm)

35 Coefficient of Linear Expansion per °C

36 Modulus of Elasticity (Kg/sq.cm)

37 Overall Diameter of Armour-(mm)(min)

GENERAL- 38 Overall Diameter

of cable-(mm)(min)

39 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

Page 112: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

40 Short Time Current Rating for 1 Sec. (KA)

41 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

42 Approximate Reactance per 1000 m at 50 Hz (Ω)

43 Approximate Capacitance per 1000 m at 50 Hz (μF)

44 Safe Pulling Force

45 Minimum Radius of Insulation

46 Length per Drum (meter)-

(1)Nominal (2)Maximum (3)Minimum

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_________

Page 113: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – C10 GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

CONTROL CABLE (2.5 mm2) 1 2 3 4 5 6 7 8 9 10 11 12 13

SR. NO

DESCRIPTION 2C X 2.5 mm2

3C X 2.5 mm2

4C X 2.5 mm2

5C X 2.5 mm2

7C X 2.5 mm2

9C X 2.5 mm2

12C X 2.5 mm2

14C X 2.5 mm

19C X 2.5 mm2

24C X 2.5 mm2

2C X 2.5 mm2

1 Voltage Grade(VOLT)

2 Suitable for earthed or unearthed system

CONDUCTOR- 3 Material 4 No. of strands per

core

5 Diameter Of the conductor-(mm) (1)Nominal (2) Minimum

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

7 Resistance at 20 °C (Ω/KM)(Max)

Page 114: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

8 Resistivity(Ω-mm2/meter)

9 Density (Gm/Cu-Cm)

10 Constant Mass Temperature Coefficient for resistance - For Copper-per °C

11 Elongation in % , Minimum

12 Coefficient of Linear Expansion per °C

13 Modulus of Elasticity (Kg/sq.cm)

CORE INSULATION- 14 Material 15 Thickness of PVC

Core Insulation (mm)- (1) Nominal (2) Minimum

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

17 Tensile Strength (N/mm2)(Min)

18 Elongation in % 19 Color code for

Core Identification

Page 115: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

INNER SHEATH- 20 Material 21 Thickness of PVC

Inner Sheath(mm)- (1) Nominal (2) Minimum

22 Tensile Strength (N/mm2)(Min)

23 Elongation in %

24 Color code for Identification

OUTER SHEATH- 25 Material 26 Thickness of PVC

Outer Sheath(mm)-(Minimum)

27 Tensile Strength (N/mm2)(Min)

28 Elongation in % 29 Color code for

Identification

ARMOUR- 30 Material/Type

31 Diameter Of Armour Wire-(mm) (1)Nominal (2) Minimum

Page 116: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

32 Resistance at 20 °C (Ω/KM)(Max)

33 Tensile Strength (N/mm2)(Min)

34 Elongation in % 35 Density at 20 °C

(Gm/Cu-Cm)

36 Coefficient of Linear Expansion per °C

37 Modulus of Elasticity (Kg/sq.cm)

38 Overall Diameter of Armour-(mm) (min)

GENERAL- 39 Overall Diameter

of cable-(mm)(min)

40 Continuous Current Rating (Amp)- (1) In Ground (2) In Duct (3) In Air

41 Short Time Current Rating for 1 Sec. (KA)

42 Rated DC Voltage (VOLTS)

Page 117: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

43 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

44 Approximate Reactance per 1000 m at 50 Hz (Ω)

45 Approximate Capacitance per 1000 m at 50 Hz (μF)

46 Safe Pulling Force -

47 Minimum Radius of Insulation

48 Length per Drum (meter)- (1)Nominal (2)Maximum (3)Minimum

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_________

Page 118: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – C11 GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

HEAT RTESISTANT CABLE 1 2 3 4 5

SR. NO

DESCRIPTION 1 C X 1.5 mm2

1 C X 2.5 mm2 1 C X 4 mm2

1 Voltage Grade(VOLT) 2 Suitable for earthed or

unearthed system

CONDUCTOR- 3 Material 4 No. of strands per core 5 Diameter Of the

conductor-(mm)(min)

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

7 Resistance at 20 °C (Ω/KM)(Max)

8 Resistivity(Ω-mm2/meter) 9 Density (Gm/Cu-Cm)

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

11 Elongation in % , Minimum 12 Coefficient of Linear

Expansion per °C

13 Modulus of Elasticity (Kg/cm2)

CORE INSULATION- 14 Material 15 Thickness of PVC Core

Insulation (mm)- (1) Nominal (2) Minimum

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

17 Tensile Strength (N/mm2)(Min)

18 Elongation in %

Page 119: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

19 Color code for Core Identification

GENERAL- 20 Overall Dimension of

Cable-(mm)(max)

21 Continuous Current Rating (Amp)-

22 Short Time Current Rating for 1 Sec. (KA)

23 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

24 High Temperature Operation Capacity

24 Approximate Reactance per 1000 m at 50 Hz (Ω)

25 Approximate Capacitance per 1000 m at 50 Hz (μF)

26 Safe Pulling Force - 27 Minimum Radius of

Insulation

28 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

29 Net Weight of Cable (KG)

30 Drum Weight (KG)

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_________

Page 120: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – C12

GURANTEED TECHNICAL PARTICULARS (To be filled by the Bidder)

The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

OPTIC FIBER CABLE

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:________

CHARACTERISTIC

MIN. REQUIRED SPECIFICATION FOR OFC

GENERAL

Unitube Armoured fiber optic cable The fiber type is a Matched Cladding Single Mode The fiber is optimized for operation at 1310 nm and at 1550 nm Outer Sheath HDPE – Black/Suitable colour Should fulfill the requirements of: IEC 793-2: 1992, EN 188101 ITU-T Recommendation G.652

Testing methods are in accordance with the following standards: ISO 11801 IEC 60793-1/60794-1-2 ITU-T G.652.D

GEOMETRICAL PROPERTIES

Nominal mode field diameter Number of Core Mode field diameter tolerance Cladding diameter Cladding diameter tolerance Mode field concentricity error Cladding non-circularity

MATERIALS CORE

COATING PHYSICAL PROPERTIES

Strength Member-FRP

OPTICAL PROPERTIES

Attenuation (of cable with fibers): At 1310 nm In the range 1285-1330 nm At 1550 nm

Page 121: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

SCHEDULE – C13

GURANTEED TECHNICAL PARTICULARS (To be filled by the Bidder)

The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

POWER CABLE FOR EXCITATION SYSTEM 1 2 3

SR. NO

DESCRIPTION 1 C X 630 mm2

1 Voltage Grade (VOLT) 2 Suitable for earthed or

unearthed system

CONDUCTOR- 3 Material 4 No. of strands/Diameter

(For reference only)

5 Diameter Of the conductor-(mm)(min)

6

Cross-sectional area(mm2)- (1)Nominal (2)Minimum

7 Resistance at 20 °C (Ω/KM)(Max)

8 Resistivity(Ω-mm2/meter) 9 Density (Gm/Cu-Cm)

10 Constant Mass Temperature Coefficient for resistance - For Aluminium-per °C

11 Elongation in % , Minimum

12 Coefficient of Linear Expansion per °C

13 Modulus of Elasticity (Kg/cm2)

14 Material 15 Thickness of PVC Core

Insulation (mm)- Nominal

Page 122: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

17 Tensile Strength (N/mm2)(Min)

18 Elongation in % 19 Color code for Core

Identification

OUTER SHEATH- 20 Material 21 Thickness of PVC Outer

Sheath(mm)-(Minimum)

22 Tensile Strength (N/mm2)(Min)

23 Elongation in % 24 Color code for Core

Identification

25 Overall Diameter of cable-(mm)(min)

ARMOUR- 26 Material/Type 27 Diameter Of Armour

Wire-(mm) (1)Nominal (2) Minimum

28 Resistance at 20 °C (Ω/KM)(Max)

29 Tensile Strength (N/mm2)(Min)

30 Elongation in % 31 Density at 20 °C (Gm/Cu-

Cm)

32 Coefficient of Linear Expansion per °C

33 Modulus of Elasticity (Kg/sq.cm)

GENERAL- 34 Overall Diameter of

Armour-(mm)(min)

35 Continuous Current Rating (A)- (1) In Ground (2) In Duct (3) In Air

36 Short Time Current Rating for 1 Sec. (KA)

37 Insulation Resistance (Ω/mm)- (1)At 20 °C (2)At 75 °C

Page 123: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

38 Approximate Reactance per 1000 m at 50 Hz (Ω)

39 Approximate Capacitance per 1000 m at 50 Hz (μF)

40 Safe Pulling Force -

41 Minimum Radius of Insulation

42 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

43 Net Weight of Cable (KG)

44 Drum Weight (KG)

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_______

SCHEDULE – C14 GURANTEED TECHNICAL PARTICULARS

(To be filled by the Bidder) The Guaranteed Technical particulars furnished below for each size of cable shall be duly attested by the Bidder. Any correction / alterations in this GTP will lead to outright rejection of the Bid. Blank Space shown in the Column of details shall be furnished by bidder invariably. In no case any column should be left blank.

INSTRUMENT CABLE 1 2 3 4 5 6

SR. NO

DESCRIPTION 2 P X 0.5 mm2

4 P X 0.5 mm2

8 P X 0.5 mm2

10 P X 0.5 mm2

1 Voltage Grade (VOLT)

2 Suitable for earthed or unearthed system

CONDUCTOR- 3 Material

4 No. of strands per core

Page 124: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

5 Diameter Of the conductor-(mm)(min)

6 Cross-sectional area(mm2)- (1)Nominal (2)Minimum

7 Resistance at 20 °C (Ω/KM)(Max)

8 Resistivity(Ω-mm2/meter)

9 Density (Gm/Cu-Cm)

10 Constant Mass Temperature Coefficient for resistance – For Aluminium-per °C

11 Elongation in % , Minimum

12 Coefficient of Linear Expansion per °C

13 Modulus of Elasticity (Kg/cm2)

CORE INSULATION- 14 Material 15 Thickness of PVC

Core Insulation (mm)- Minimum

16 Volume Resistivity (Ω/cm)- (1)At 20 °C (2)At 70 °C

17 Tensile Strength (N/mm2)(Min)

18 Elongation in % 19 Color code for Core

Identification

OVERALL SCREENING- 20 Material

INNER SHEATH- 21 Material 22 Thickness of PVC

Inner Sheath(mm)- Nominal

23 Tensile Strength (N/mm2)(Min)

24 Elongation in % 25 Color code for Core

Identification

Page 125: TECHNICAL SPECIFICATION OF CABLES FOR … Office/GEN_GP_5253B_… · TECHNICAL SPECIFICATION OF CABLES FOR POWER STATIONS Installed . I N D E X CLAUSE NO. TITLE Special Instruction

OUTER SHEATH- 26 Material 27 Thickness of PVC

Outer Sheath(mm)-(Minimum)

28 Tensile Strength (N/mm2)(Min)

29 Elongation in % 30 Color code for Core

Identification

31 Overall Diameter of cable-(mm)(min)

ARMOUR- 32 Material/Type 33 Diameter Of Armour

Wire-(mm) Nominal

34 Resistance at 20 °C (Ω/KM)(Max)

35 Tensile Strength (N/mm2)(Min)

36 Elongation in % 37 Density at 20 °C

(Gm/Cu-Cm)

38 Coefficient of Linear Expansion per °C

39 Modulus of Elasticity (Kg/sq.cm)

GENERAL- 40 Continuous Current

Rating (A)

41 Safe Pulling Force -

42 Minimum Radius of Insulation

43 Length per Drum(meter)-(1)Nominal (2)Maximum (3)Minimum

Name of Bidder: ______________ Signature of the Bidder: ___________

Name : __________________________ Date: _________________________ Designation: ______________________ Authorized common rubber Stamp / seal of the bidder:_______