Q31504/09tN4 Wiring Center 315
1 of 2 © 2009 Q 315 - 04/09
- Quick Setup Guide
Control Location
•• The Wiring Center can be mounted either directly to the wall,or to a 4”x4” electrical box.
•• Mount the enclosure to a solid backing.
•• Wiring will enter through either side knockouts or between the
base of the enclosure and the cover on the sides and top. SeeFigure 1 and Figure 2.
Note: The nonmetallic enclosure does not provide groundingbetween conduit connections. Conduit connections must begrounded by other means.
U s e a t l e a s t 1 6 7 ° F
( 7 5 ° C ) c o n d u c t o r s
Input Power: 24V (ac) ±10%60Hz
2 VA (98VAmax)
Class 2End Switch: 24 V (ac) 2AZone Output: 2 Aper zone 4 A (max) total
Power
Zone1
Zone2
Zone3
Zone4
Zone5
Zone6
End Switch
C
Zone 2W
tN4R
C
Zone 3W
tN4R
C
Zone 4W
tN4R
tN4 Wiring Center 315S ix Z o n e V a l v e s
W
t N 4
C
t N 4
C
X
Z o n e 1
E x p a n s i o n
VlvC
Zone 1
VlvC
Zone 2
VlvC
Zone 3
VlvC
Zone 4
VlvC
Zone 5
VlvC
Zone 6
X
C
I n p u t P o w e r
R
R
W
t N 4
C
Z o n e 5
R
W
t N 4
C
Z o n e 6
R
H8001A
E n d S w i t c h
Made inCanadatektra 1032-01
Basic Installation
Valve Valve Valve Valve Valve Valve
C Vlv C Vlv C Vlv C Vlv C Vlv C Vlv
tN4 C R
This Quick Setup Guide contains the basic information required to get your new tekmar tN4 Wiring Center 315 installedand operational. An Installation and Operation Manual D 315 containing all available features and operational details is
included with this control or can be found at www.tekmarcontrols.com/literature.html
The tN4 Wiring Center 315 is designed to be mounted near a zone manifold and will operate up to 6 zone valves in a
hydronic heating system.
Wire the Thermostats
tN4 Thermostats:
•• Connect tN4, C, R and W conductors to the correspondingterminals on the 315, paying special attention to ensure that thetN4 and C wires are not reversed. See the terminal labelling inFigure 2.
Wire the Zone Valves
•• Wire the zone valves to the Vlv and C terminals on the 315,as shown in Figure 3.
•• End switches on zone valves are not required when using
the 315.
Connect to the Mechanical System
•• If the 315 is to be connected to a tN4 network, connect thetN4 and C expansion terminals to the tN4 connection on theassociated tN4 device.
•• If the 315 is to be connected to another control, such as atekmar Boiler Control, use the end switch terminals to create
a ‘Boiler Demand’ on this external control. See application onnext page.
Figure 1
Wire the Power Supply
Once the transformer has been correctly sized, connect the 24 V(ac) leads from the transformer to the R and C terminals marked
“Input Power” on the Wiring Center. See “Sizing the ExternalTransformer” in the Installation and Operation Manual D 315 formore detailed information.
Figure 2
Figure 3
OUTDOO
F
HEAT
FLOOR
8/8/2019 Tekmar 315 tN2 Wiring Center - Six Zone Valves
http://slidepdf.com/reader/full/tekmar-315-tn2-wiring-center-six-zone-valves 2/2
Product design, software and literature are Copyright © 2009 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc. 2 of 2 All specifications are subject to change without notice.
Printed in Canada. Q 315 - 04/09.
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com
Refer to Transformer Data Sheets for Maximum Allowable Loads
Valve Valve Valve Valve Valve Valve
tN4 C R W
tN4Thermostat
tN4 C R W
tN4Thermostat
tN4 C R W
tN4Thermostat
tN4 C R W
tN4Thermostat
tN4 C R W
tN4Thermostat
Use tekmarNet ® 4 Thermostats to achieve better system performance.
tN4 C R W
tN4Thermostat
U s e a t l e a s t 1 6 7 ° F
( 7 5 ° C ) c o n d u c t o r s
Input Power: 24 V (ac) ±10% 60 Hz2 VA (98 VA max)
Class 2
End Switch: 24 V (ac) 2 AZone Output: 2 A per zone
4 A (max) total
PowerZone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
End Switch
CZone 2
WtN4 R CZone 3
WtN4 R CZone 4
WtN4 R
tN4 Wiring Center 315Six Zone Valves
W
t N 4
C
t N 4
C
X
Z o n e 1
E x p a n s i o n
VlvC
Zone 1
VlvC
Zone 2
VlvC
Zone 3
VlvC
Zone 4
VlvC
Zone 5
VlvC
Zone 6
X
C
I n p u t P o w e r
R
R
W
t N 4
C
Z o n e 5
R
W
t N 4
C
Z o n e 6
R
H8001
A
E n d S
wi t c h Made in Canada
tektra 1032-01
OR
CC
RR
F u s e
t N 4
C
X
E x p a n s i o n
X
C
I n p u t P
o w e r
R
E n d S wi t c h
OR
TT
TT
t N 4
C
X
E x p a n s i o n
X
E n d S w
i t c h
E x p a n s i o n E n d S wi t c h
tN4
C
t N 4
C
X
X
B o i l e r
D e m a n d
L
N
tekmarTransformer 009
24 V (ac)
Wiring Conventional Thermostats:
The tN4 Wiring Center 315 may be used with conventionalthermostats instead.
•• Connect the thermostat wires to the R and W terminals ofthe 315.
•• Do not mix conventional and tekmarNet ® Thermostats onthe same Wiring Center.
•• See the Installation & Operation Manual D315 for moredetailed wiring information.
Application Drawing
Sizing the External Transformer:
Add up all the thermostat and zone valve loads (VA)connected to the Wiring Center. The transformer must havehigher capacity than this total load.
+ + 2 VA =
T-stats + Zone Valves + Control Total Load
tN4 connection to tN4Outdoor Reset Control
Call for heat to directlyenable a boiler control
Boiler demand to stand-alone tekmar Boiler Control
External tN4Connection (ie:Zone Manager orReset Module)
Directly EnabledBoiler Control
Powered boilerdemand (ie: Inputto tekmar BoilerControl 260)