test report iec 62040-1 uninterruptible power systems (ups

53
VDE File No 1924400-3335-0067/218478 Test Report issued under the responsibility of: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS) Part 1: General and safety requirements for UPS Report Number. .............................. : 218478-CI3-1 CB / DE1-54209/M2 Date of issue................................... : 2015-12-14 Total number of pages ................... 53 Applicant’s name ........................... : APC by Schneider Electric Address........................................... : Boston ONE Campus; 800 Federal Street; ANDOVER MA 01810-1067; USA Test specification: Standard ......................................... : DIN EN 62040-1 (VDE 0558-510):2013-11 EN 62040-1:2008 + A1:2013-05 IEC 62040-1:2008 (First Edition) + Am 1:2013 Test procedure ............................... : VDE-GS, CB Scheme Non-standard test method ............ : N/A Test Report Form No. .................... : IEC62040_1C Test Report Form(s) Originator .... : TÜV Rheinland Japan Ltd. Master TRF ..................................... : Dated 2014-01 Copyright © 2014 Worldwide System for Conformity Testing and Certification of Electrotechnical Equipment and Components (IECEE), Geneva, Switzerland. All rights reserved. This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context. If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed. This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.

Upload: others

Post on 01-Oct-2021

33 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

VDE File No 1924400-3335-0067/218478

Test Report issued under the responsibility of:

TEST REPORT

IEC 62040-1 Uninterruptible power systems (UPS) –

Part 1: General and safety requirements for UPS

Report Number. .............................. : 218478-CI3-1 CB / DE1-54209/M2

Date of issue ................................... : 2015-12-14

Total number of pages ................... 53

Applicant’s name ........................... : APC by Schneider Electric

Address ........................................... : Boston ONE Campus; 800 Federal Street; ANDOVER MA 01810-1067; USA

Test specification:

Standard ......................................... : DIN EN 62040-1 (VDE 0558-510):2013-11 EN 62040-1:2008 + A1:2013-05 IEC 62040-1:2008 (First Edition) + Am 1:2013

Test procedure ............................... : VDE-GS, CB Scheme

Non-standard test method ............ : N/A

Test Report Form No. .................... : IEC62040_1C

Test Report Form(s) Originator .... : TÜV Rheinland Japan Ltd.

Master TRF ..................................... : Dated 2014-01

Copyright © 2014 Worldwide System for Conformity Testing and Certification of Electrotechnical Equipment and Components (IECEE), Geneva, Switzerland. All rights reserved.

This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context.

If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed.

This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.

Page 2: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 2 of 53 Report No. 218478-CI3-1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

Test item description ..................... : Uninterruptible power supply (UPS)

Trade Mark ...................................... :

Manufacturer .................................. : APC by Schneider Electric; Boston ONE Campus; 800 Federal Street; ANDOVER MA 01810-1067; USA

Model/Type reference .................... : SRT3000RMXLI; SRT3000RMXLW; SRT3000XLI; SRT3000XLW; SRT2200RMXLI; SRT2200RMXLW; SRT2200XLI; SRT2200XLW; (see model matrix)

Ratings ............................................ : See below 2 tables for UPS and External battery pack

Ambient: 40 °C

Rating of UPS:

Input 208-240Vac, 50/60Hz; Output 3000VA, 2700W

Model matrix:

SRT 3000 RM XL I xxxxxxxxxx A B C D E F A: SRT, means series name B: 3000, 2200, means maximum VA output C: RM (means Rack Mounted) or none (means Tower Stand) D: XL, means Extended Run E: I = International (220-230-240V), W = Worldwide (208-220-230-240V) F: xxxxxxxxxx (x=0-9, a-z, A-Z, +, *, #, _, - or blank) for marketing purpose

UPS: Rating difference:

SRT3000RMXLI; SRT3000RMXLW; SRT3000XLI; SRT3000XLW;

Input 220-240Vac or 208-240Vac, Max. 16A, 50-60Hz;

Output 3000VA, 2700W

SRT2200RMXLI; SRT2200RMXLW; SRT2200XLI; SRT2200XLW;

Input 220-240Vac or 208-240Vac, 50-60Hz, Max. 13A

Output 2200VA, 1980W

Rating of external battery pack:

External battery pack: Rating:

SRT72BP, SRT72RMBP 72Vdc (for 2200VA models)

SRT96BP, SRT96RMBP 96Vdc (for 3000VA models)

Page 3: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS
Page 4: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 4 of 53 Report No. 218478-CI3-1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

List of Attachments (including a total number of pages in each attachment):

Appendix No.

Description Page(s)

1 Critical Component list 46-52

2 Modifications covered by this report 53

Summary of testing:

Tests performed (name of test and test clause):

Under this procedure no tests have been performed, only Identity Check performed.

See previous test reports for test results

Testing location:

American Power Conversion Holding Inc. Taiwan Branch 3F., No. 205, Sec. 3, Beixin Rd., Xindian Dist., New Taipei City 23143, Taiwan (TDAP File No. 5003241-9501-0001)

Summary of compliance with National Differences

List of countries addressed:

Note: EN Group Differences together with National Differences and Special National Conditions, see previous test reports

The product fulfils the requirements of

DIN EN 62040-1 (VDE 0558-510):2013-11 EN 62040-1:2008 + A1:2013-05 IEC 62040-1:2008 (First Edition) + Am 1:2013

Page 5: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 5 of 53 Report No. 218478-CI3-1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

Copy of marking plate

The artwork below may be only a draft. The use of certification marks on a product must be authorized by the respective NCBs that own these marks.

See previous test reports

Page 6: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 6 of 53 Report No. 218478-CI3-1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

Test item particulars................................................... :

Equipment mobility .................................................... : [] movable [] transportable [X] stationary [X] Rack Mount

Connection to the mains ........................................... : [X] pluggable equipment [X] type A [] type B [] permanent connection [X] detachable power supply cord [] non-detachable power supply cord

Operating condition ................................................... : [X] continuous [] rated operating / resting time:

Access location ......................................................... : [] operator accessible [X] restricted access location

Over voltage category (OVC) ................................... : [] OVC I [X] OVC II [] OVC III [] OVC IV [] other:

Mains supply tolerance (%) or absolute mains supply values ............................................................. :

- 10 % / +6%

Tested for IT power systems .................................... : [] Yes [X] No

IT testing, phase-phase voltage (V) ......................... : N/A

Class of equipment ................................................... : [X] Class I [] Class II [] Not classified

Considered current rating of protective device as part of the building installation (A) .......................... :

16 A Wall Breaker

Pollution degree (PD) ................................................ : [] PD 1 [X] PD 2 [] PD 3

IP protection class ..................................................... : IP --

Elevation during operation (m) ................................ : ≤ 2000 m

Elevation of test laboratory (m) ............................... : 76 m

Mass of equipment (kg) ............................................ : >18 kg

Possible test case verdicts:

- test case does not apply to the test object ........... : N/A

- test object does meet the requirement.................. : P (Pass)

- test object does not meet the requirement ........... : F (Fail)

Testing .......................................................................... :

Date of receipt of test item ........................................ : 2015-Dec

Date (s) of performance of tests ............................... : 2015-Dec see also see previous Test Reports

General remarks:

The test results presented in this report relate only to the object tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. "(See Enclosure #)" refers to additional information appended to the report. "(See appended table)" refers to a table appended to the report. Throughout this report a comma / point is used as the decimal separator.

Page 7: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 7 of 53 Report No. 218478-CI3-1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

Manufacturer’s Declaration per sub-clause 4.2.5 of IECEE 02:

APC by Schneider Electric; Boston ONE Campus; 800 Federal Street; ANDOVER MA 01810-1067; USAThe application for obtaining a CB Test Certificate includes more than one factory location and a declaration from the Manufacturer stating that the sample(s) submitted for evaluation is (are) representative of the products from each factory has been provided ............................................................... :

Yes

Not applicable

When differences exist; they shall be identified in the General product information section.

Name and address of factory (ies) .......................... : 1. American Power Conversion Corporation (A.P.C.) B.V.

LOT 3 BLK 14, PHASE III, PEZA, 4106 ROSARIO, CAVITE, PHILIPPINES

2. American Power Conversion Corporation (A.P.C.) B.V.

LOT 10, BLK 16, PHASE IV, PEZA, 4106 ROSARIO, CAVITE, PHILIPPINES

3. American Power Conversion Corporation (A.P.C.) B.V.

2ND ST, PEZA, Cavite Economic Zone, 4106 ROSARIO, CAVITE, PHILIPPINES

Page 8: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 8 of 53 Report No. 218478-CI3-1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

General product information:

Complete details of construction and testing as well as supporting documentation such as photographs and schematics are done by previous Test Reports. The UPS provides reinforced insulation between primary and secondary circuits. Conditions of Installation: The units are suitable for a maximum manufacturer’s recommended ambient operating temperature (Tma) of 40 °C. Unit is designed and approved for use in installation category II. Unit intended for continuous operation while charging. UPS are Class 1 and designed for Pollution Degree 2. Unit could be used as stand-alone (tower) or rack mounted version. VDE approved appliance inlets and outlets are used.

– Alternative construction for AC power input and/or output power outlet to be terminal block structure.

See installation manual for detail. Secondary circuits are designed in 3 areas, (MB + DCLPS board and Communication Boards) other boards are defined as Primary circuit area. Model differences: All models are identical except:

UPS, Main differences: 1. Electric Ratings 2. Transformers: Charger transformer, DC/DC transformer, and Logic Power Supply transformer 3. Chokes: Input choke (for EMI), PFC choke L1203, Inverter choke L1207 4. TRIAC (for improving relay transfer time), Hall Sensor (for current sense) 5. Size of PCB (2.2KVA is 2 inch shorter than 3KVA). Layout in the area of PFC choke, Inverter choke

External Battery Pack: (for example: SRT96BP/72BP) 1. Electric rating; 2. Quantity of batteries inside 3. Metal chassis is same as 2.2KVA of UPS.

In accordance with "§ 6 of the German Product

Safety Act (ProdSG)", the manufacturers have to

indicate their name and contact address on the

consumer product or, where that is not possible, on

its packaging.

If the manufacturer is not domiciled in the European

Economic Area (EEA), the name and the contact

address of the authorised person(s) within the EEA

or importer must be indicated.

Pass

Fail

Not applicable

Page 9: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 9 of 53 Report No. 218478-CI3-1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

Information to test report reference No. : 218478-CI3-1

VDE Test- and Certification Institute GmbH Merianstrasse 28

D - 63069 Offenbach

DIN EN 62040-1 (VDE 0558-510):2013-11 EN 62040-1:2008 + A1:2013-05 IEC 62040-1:2008 (First Edition) + Am 1:2013

Test item description: Uninterruptible power supply

Made by : APC by Schneider Electric; Boston ONE Campus; 800 Federal Street; ANDOVER MA 01810-1067; USA

Trade mark :

Model/type ref. : Refer to page 2

Rated : Refer to page 2

Commission received from -- Date: --

Modification on the appliance:

1. Upgrade to: DIN EN 62040-1 (VDE 0558-510):2013-11 EN 62040-1:2008 + A1:2013-05 IEC 62040-1:2008 (First Edition) + Am 1:2013

2. Revise the definition of model name. SRT 3000 RM XL I xxxxxxxxxx A B C D E F A: SRT, means series name B: 3000, 2200, means maximum VA output C: RM (means Rack Mounted) or none (means Tower Stand) D: XL, means Extended Run E: I = International (220-230-240V), W = Worldwide (208-220-230-240V) F: xxxxxxxxxx (x=0-9, a-z, A-Z, +, *, #, _, - or blank) for marketing purpose

3. Add an alternate source for relay RY1204.

Relay RY1204 Omron Corp G2RG-2A4 8A, 250Vac, Coil 24Vdc

4. Add an alternate source for MOV MV1204A, MV1205A.

Page 10: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 10 of 53 Report No. 218478-CI3-1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

Test Report History:

This report may consist of more than one report and is valid only with additional or previous issued reports:

Date: (jjjj-mm-dd)

VDE-Certificate: CB-Ref. No.:

VDE File No.: Test Report Number

Modifications:

2015-12-14 CB / DE1-54209/M2 218478-CI3-1 Additional test report (This report): --Upgrade to DIN EN 62040-1 (VDE 0558-510):2013-11 EN 62040-1:2008 + A1:2013-05 IEC 62040-1:2008 (First Edition) + Am 1:2013 --Revise definition of model name --Alternative components (RY1204, MV1204A, MV1205A)

2014-11-10 CB / DE1-54209/M1 1924400-3335-0067/203983 Additional test report: Addition of alternate model SRT3000RMXLI-IEC with alternate components

2013-10-31 CB / DE1-54209 1924400-3335-0067/203209 Main test report approved to DIN EN 62040-1 (VDE 0558-510):2009-06 EN 62040-1:2008 IEC 62040-1 : 2008 (1st Edition)

Page 11: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 11 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

4 GENERAL CONDITIONS FOR TESTS P

4.5 Components P

Comply with IEC 62040-1 or relevant component standard

(see appended table 4.5) P

1.5.2/RD Evaluation and testing of components Certified components are used in accordance with their ratings and certifications, and they comply with applicable parts of this standard. Components not certified are used in accordance with their ratings and they comply with applicable parts of IEC 60950-1 2

nd and the relevant

component standard. Components, for which no relevant IEC-Standard exists, have been tested under the conditions occurring in the equipment, using applicable parts of IEC 60950-1 2

nd

P

1.5.3/RD Thermal controls No thermal controls N/A

1.5.4/RD Transformers See annex C for details P

1.5.5/RD Interconnecting cables Interconnecting cables are not

used in this application

N/A

1.5.6/RD Capacitors bridging insulation Certified to IEC60384-14 2nd

Edition. See Components List for details.

Y2 capacitors used between Lines and Ground and one Y1 between SELV and Primary circuits

X2 capacitors used between Line and Neutral.

See clause 2.4 RD for details of requirements and compliance of limited current circuits.

P

1.5.7/RD Resistors bridging insulation Bridging resistor between Line and ground

P

1.5.7.1/RD Resistors bridging functional, basic or supplementary insulation

Functional insulation only N/A

1.5.7.2/RD Resistors bridging double or reinforced insulation between a.c. mains and other circuits

N/A

1.5.7.3/RD Resistors bridging double or reinforced insulation between a.c. mains and antenna or coaxial cable

N/A

1.5.8/RD Components in equipment for IT power systems N/A

Page 12: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 12 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

4.6 Power interface P

1.6.1/RD AC power distribution systems TN-System P

1.6.2/RD Input current (see appended table 4.6) P

4.6 1.6.4/RD

Neutral conductor Neutral is insulated from earth with basic insulation. Components connected between phases and earth are rated and certified for a minimum working voltage of 250 V. See Components List

P

4.7 Marking and instructions P

4.7.1 General P

4.7.2 1.7.1/RD

Power rating Refer to copy of rating label P

Input rated voltage/range (V) ........................... : See page 2 P

Input rated current/range (A) ............................ : See page 2 P

Input symbol for nature of supply (d.c.) ........... : AC Unit P

Input rated frequency/range (Hz) ..................... : See page 2 P

Number of Input phases and neutral ................ : one phase P

Output rated voltage/range (V) ........................ : See page 2 P

Output rated current/range (A) ........................ : See page 2 P

Output rated power factor, if less than unity, or active power and apparent power or active power and rated current ............................................. :

See page 2 P

Number of output phases and neutral ............. : One phase P

Output rated active power (W or kW) .............. : See page 2 P

Output rated apparent power (VA or kVA) ...... : See page 2 P

Output symbol for nature of supply (d.c.) ........ : N/A

Output rated frequency/range (Hz) .................. : See page 2 P

Ambient operating temperature range (C) ..... : 40 °C P

Rated short-time withstand current (Icw) or rated conditional short-circuit current (Icc)

N/A

Manufacturer’s name or trademark or identification mark ................................................................. :

P

Type/model or type reference .......................... : See page 2 P

Symbol for Class II equipment only ................. : Class I equipment N/A

Other symbols ................................................. : P

Certification marks ........................................... : VDE GS P

Page 13: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 13 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

Instructions for units with automatic bypass/maintenance bypass, additional input a.c. supply, or external batteries, having text "See installation instructions before connecting to the supply" ............................................................. :

See Safety Instructions P

4.7.3 Safety instructions See Safety Instructions P

4.7.3.1 General See Safety Instructions P

4.7.3.2 Installation ........................................................ : Unit is an auto-ranging type N/A

Location in a restricted access location only ... : N/A

Permanent connector UPS ............................... : P

Pluggable type A or Pluggable type B UPS .... : P

4.7.3.3 Operation .......................................................... : P

4.7.3.4 Maintenance ..................................................... : P

4.7.3.5 Distribution related backfeed ............................ : P

4.7.4 1.7.4/RD

Main voltage adjustment ................................. : N/A

Methods and means of adjustment; reference to installation instructions .................................... :

Unit is an auto-ranging type N/A

4.7.5 1.7.5/RD

Power outlets .................................................... : N/A

4.7.6 1.7.6/RD

Fuse identification (marking, special fusing characteristics, cross-reference) ..................... :

Fuses are marked with ratings

or symbols like F1, fuses are

not customer replaceable.

P

4.7.7 1.7.7/RD

Wiring terminals See previous reports P

1.7.7.1/RD Protective earthing and bonding terminals ...... : See previous reports P

1.7.7.2/RD Terminals for a.c. mains supply conductors ..... : See previous reports P

1.7.7.3/RD Terminals for d.c. mains supply conductors ..... : See previous reports P

4.7.8 Battery terminals ............................................. : P

4.7.9 1.7.8/RD

Controls and indicators P

1.7.8.1/RD Identification, location and marking ................. : P

1.7.8.2/RD Colours ........................................................... : No indicators with colours N/A

1.7.8.3/RD Symbols ........................................................... : P

1.7.8.4/RD Markings using figures ................................... : P

4.7.10 1.7.9/RD

Isolation of multiple power sources ................. : No multiple power sources N/A

4.7.11 1.7.2.4/RD

IT power systems Not evaluated for IT power systems

N/A

4.7.12 Protection in building installation P

Page 14: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 14 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

Rated short-time withstand current (Icw) ........ : Over shoot and under shoot max. 4% of rated Voltage for duration of 40 ms.

P

Rated conditional short circuit current (Icc) ..... : Over shoot and under shoot max. 4% of rated Voltage for duration of 40 ms.

P

a) If higher Icp stated ≤ 10 kA N/A

a) If higher Icp stated > 10 kA N/A

4.7.13 5.1/RD

High leakage current (mA) .............................. : Statement in the instructions that the unit is connected to a separate ground connector in the back of the unit near the appliance inlet , screw is marked with the ground symbol

P

4.7.14 1.7.10/RD

Thermostats and other regulating devices No adjustable thermal devices

employed

N/A

4.7.15 1.7.2.1/RD and 1.7.8.1/RD

Language(s) .................................................... :

4.7.16 1.7.11/RD

Durability of markings P

4.7.17 1.7.12/RD

Removable parts No marking on removable parts

P

4.7.18 1.7.13/RD

Replaceable batteries Replaceable Lead Acid Batteries

P

Language(s) .................................................... :

4.7.19 1.7.2.5/RD

Operator access with a tool .............................. : Cannot access hazardous part.

P

4.7.20 Battery See component list P

Clearly legible information ............................... : P

Battery type (lead-acid, NiCd, etc.) and number of blocks or cells .................................................. :

Sealed Lead Acid P

Nominal voltage of total battery (V) ................. : P

Nominal capacity of total battery (optional) ..... : P

Warning label .................................................. : P

Instructions ...................................................... : P

2.1.1.5/RD Protection against energy hazards Battery terminals are protected

N/A

4.7.21 1.7.2.4/RD

Installation instructions See previous reports P

Page 15: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 15 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

5 FUNDAMENTAL DESIGN REQUIREMENTS P

5.1 Protection against electric shock and energy hazards

P

5.1.1 2.1.1/RD

Protection for UPS intended to be used in operator access areas

No operator access to hazardous parts.

All user accessible outputs fulfill SELV Requirements.

P

2.1.1.1/RD Access to energized parts See clause 2.1.1 P

Test by inspection ........................................... : all wires in the front and back of the unit which are accessible with the test pin are double insulated or have an thickness of insulation > 0.4 mm

P

Test with test finger (Figure 2A) ...................... : P

Test with test pin (Figure 2B) .......................... : P

Test with test probe (Figure 2C) ...................... : P

2.1.1.2/RD Battery compartments P

2.1.1.3/RD Access to ELV wiring No ELV circuits N/A

Working voltage (Vpeak or Vrms); minimum distance through insulation (mm)

See previous reports

2.1.1.4/RD Access to hazardous voltage circuit wiring No access to hazardous voltage circuit wiring

N/A

2.1.1.5/RD Energy hazards ............................................... : Battery terminal are provided P

2.1.1.6/RD Manual controls P

2.1.1.7/RD Discharge of capacitors in equipment P

Measured voltage (V); time-constant (s) .......... :

2.1.1.8/RD Energy hazards – d.c. mains supply AC unit N/A

a) Capacitor connected to the d.c. mains supply .. : N/A

b) Internal battery connected to the d.c. mains supply .............................................................. :

N/A

2.1.1.9/RD Audio amplifiers in information technology equipment ........................................................ :

No audio Amplifiers N/A

5.1.2 2.1.1.5 c) /RD

Protection for UPS intended to be used in service access areas

P

Hazardous energy level ................................... : N/A

5.1.3 2.1.1.5 c) /RD

Protection for UPS intended to be used in restricted access areas

N/A

Hazardous energy level ................................... : N/A

5.1.4 Backfeed protection (see appended table 5.7)

Page 16: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 16 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

Shock hazard after de-energization of a.c. input for UPS

Output is not grounded, Relays with 1.4 mm contact gap are provided.

The measured voltage in previous Test Reports is voltage from the filter capacitors (leakage current is very low) refer to test results.

P

Measured voltage (V); time-constant (s) .......... :

Description of the construction ........................ : Considered. P

Air gap is employed for backfeed protection See also previous test reports.

P

5.1.5 Emergency switching (disconnect) device N/A

5.2 Requirements for auxiliary circuits P

5.2.1 2.2/RD

Safety extra low voltage circuit - SELV 2.2.3.1 – 2.2.3.3/RD P

2.2.1/RD General requirements Data Circuits fulfil SELV requirements. SELV circuits considered as safe touchable under normal operating condition and after a single fault.

P

2.2.2/RD Voltages under normal conditions (V) ............. : Less than or equal to 42.4Vpk or 60Vdc

P

2.2.3/RD Voltages under fault conditions (V) ................. : Less than or equal to 42.4Vpk or Vdc

Maximum voltage under fault condition less than 71Vpk or 12Vdc for not longer than 0.2 sec.

There are no single faults which can cause voltage levels on the outputs to exceed the SELV limits.

P

2.2.4/RD Connection of SELV circuits to other circuits .. : SELV circuit are considered to be connected only to SELV or earth.

P

5.2.2 2.3/RD

Telephone network voltage circuits - TNV No TNV circuit N/A

2.3.1/RD Limits N/A

Type of TNV circuits ......................................... :

2.3.2/RD Separation of TNV circuits from other circuits and from accessible parts

N/A

2.3.2.1/RD General requirements N/A

2.3.2.2/RD Protection by basic insulation N/A

Page 17: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 17 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

2.3.2.3/RD Protection by earthing N/A

2.3.2.4/RD Protection by other constructions .................... : N/A

2.3.3/RD Separation from hazardous voltages N/A

Insulation employed ......................................... :

2.3.4/RD Connection of TNV circuits to other circuits N/A

Insulation employed ......................................... :

2.3.5/RD Test for operating voltages generated externally N/A

5.2.3 2.4/RD

Limited current circuits N/A

2.4.1/RD General requirements N/A

2.4.2/RD Limit values

Frequency (Hz) ................................................. :

Measured current (mA) .................................... :

Measured voltage (V) ....................................... :

Measured circuit capacitance (nF or µF) .......... :

2.4.3/RD Connection of limited current circuits to other circuits

N/A

5.2.4 3.5/RD

External signaling circuits P

3.5.1/RD General requirements Interconnection of P/S outputs (SELV) with other circuits is to be evaluated in end-use product

P

3.5.2/RD Types of interconnection circuits ..................... : SELV circuits P

3.5.3/RD ELV circuits as interconnection circuits No ELV interconnection N/A

3.5.4/RD Data ports for additional equipment P

5.2.5 2.5/RD

Limited power source See previous test reports P

a) Inherently limited output N/A

b) Impedance limited output P

c) Regulating network limited output under normal operating and single fault condition

P

d) Overcurrent protective device limited output P

Max. output voltage (V), max. output current (A), max. apparent power (VA) ............................... :

Current rating of overcurrent protective device (A) .:

Use of integrated circuit (IC) current limiters

5.3 Protective earthing and bonding P

5.3.1 General P

Page 18: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 18 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

2.6/RD Provisions for earthing and bonding P

2.6.1/RD Protective earthing Accessible metal parts are reliably earthed, refer to installation instructions

P

2.6.2/RD Functional earthing Functional earthing not provided

N/A

2.6.3/RD Protective earthing conductors and protective bonding conductors

VDE approved appliance inlet P

2.6.3.1/RD General P

2.6.3.2/RD Size of protective earthing conductors Construction is designed for the expected current.

P

Rated current (A), cross-sectional area (mm2),

AWG ................................................................. :

2.6.3.3/RD Size of protective bonding conductors See 2.6.3.2 P

Rated current (A), cross-sectional area (mm2),

AWG ................................................................. :

Protective current rating (A), cross-sectional area (mm

2), AWG ..................................................... :

2.6.3.4/RD Resistance of earthing conductors and their

terminations; resistance (), voltage drop (V), test current (A), duration (min) ................................ :

Considered. P

2.6.3.5/RD Colour of insulation ........................................... : Green/Yellow used only for protective earthing

P

2.6.4/RD Terminals Unit is provided with two appliance inlet’s for input

N/A

2.6.4.1/RD General N/A

2.6.4.2/RD Protective earthing and bonding terminals Unit is provided with two appliance inlet’s for input

N/A

Rated current (A), type, nominal thread diameter (mm) ................................................................. :

2.6.4.3/RD Separation of the protective earthing conductor from protective bonding conductors

N/A

2.6.5/RD Integrity of protective earthing P

2.6.5.1/RD Interconnection of equipment N/A

2.6.5.2/RD Components in protective earthing conductors and protective bonding conductors

None N/A

2.6.5.3/RD Disconnection of protective earth P

2.6.5.4/RD Parts that can be removed by an operator N/A

2.6.5.5/RD Parts removed during servicing N/A

2.6.5.6/RD Corrosion resistance P

2.6.5.7/RD Screws for protective bonding P

Page 19: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 19 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

2.6.5.8/RD Reliance on telecommunication network or cable distribution system

N/A

5.3.2 2.6.1/RD

Protective earthing Accessible metal parts are reliable earthed.

Unit is provided with appliance inlet’s for input

P

2.10/RD Clearances, creepage distances and distances through insulation

Installation Category II is assumed for this unit.

P

4.2/RD Mechanical strength P

5.2/RD Electric strength P

5.3.3 Protective bonding P

5.4 AC and d.c. power isolation P

5.4.1 General P

3.4/RD Disconnection from the mains supply P

3.4.1/RD General requirement P

3.4.2/RD Disconnect devices Unit is provided with Appliance Inlet for input

P

3.4.3/RD Permanently connected equipment See 3.4.1 P

3.4.4/RD Parts which remain energized P

3.4.5/RD Switches in flexible cords N/A

3.4.6/RD Number of poles - single-phase and d.c. equipment See 3.4.1 P

3.4.7/RD Number of poles - three-phase equipment See 3.4.1 P

3.4.8/RD Switches as disconnect devices N/A

3.4.9/RD Plugs as disconnect devices N/A

3.4.10/RD Interconnected equipment N/A

3.4.11/RD Multiple power sources N/A

5.4.2 Disconnect devices P

5.5 Overcurrent and earth fault protection P

5.5.1 General P

2.7.3/RD Short-circuit backup protection Protective devices have adequate breaking (rupturing) capacity to interrupt the max. fault current (including short circuit), see 2.7.1

P

2.7.4/RD Number and location of protective devices ..... : See schematics and component list for details.

Schematics available on request.

P

2.7.5/RD Protection by several devices N/A

Page 20: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 20 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

2.7.6/RD Warning to service personnel .......................... : N/A

5.5.2 Basic requirements P

5.5.3 Battery circuit protection P

5.5.3.1 Overcurrent and earth fault protection P

5.5.3.2 Location of protective device P

5.5.3.3 Rating of protective device P

5.3.1/RD Protection against overload and abnormal operation

(see table 5.3 on RD Test Report according to IEC 60950-1 2

nd )

P

5.5.4 Short-time withstand current Exemption from testing:

UPS with declared Icw or Icc not exceeding 10 kA

N/A

5.5.4.1 General N/A

5.5.4.2 Modes of operation N/A

5.5.4.3 Test procedure Exemption from testing:

UPS with declared Icw or Icc not exceeding 10 kA

N/A

5.5.4.3.1 General application N/A

Rated UPS output current/(r.m.s) (A) .............. : ---

Prospective test current/(r.m.s) (A) ................. : ---

Typical power factor ........................................ : ---

Initial asymmetric peak current ration (Ipk / Icw) . : ---

Minimum durating of prospective test current (cycles 50/60 Hz) ............................................. :

---

5.5.4.3.2 Exemption from testing Exemption from testing:

UPS with declared Icw or Icc not exceeding 10 kA

P

5.6 Protection of personnel – Safety interlocks N/A

5.6.1 Operator protection N/A

2.8/RD General principles N/A

2.8.1/RD Protection requirements N/A

2.8.2/RD Inadvertent reactivation N/A

2.8.3/RD Fail-safe operation N/A

2.8.4/RD Protection against extreme hazard N/A

2.8.5/RD Moving parts N/A

2.8.6/RD Overriding N/A

2.8.7/RD Switches, relays and their related circuits N/A

Page 21: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 21 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

2.8.7.1/RD Separation distances for contact gaps and their related circuits ................................................. :

N/A

2.8.7.2/RD Overload test N/A

2.8.7.3/RD Endurance test N/A

2.8.7.4/RD Electric strength test N/A

2.8.8/RD Mechanical actuators N/A

5.6.2 Service person protection P

5.6.2.1 Introduction P

5.6.2.2 Covers P

5.6.2.3 Location and guarding of parts P

5.6.2.4 Parts on doors N/A

5.6.2.5 Component access P

2.8.3/RD Fail-safe operation N/A

5.6.2.6 Moving parts P

5.6.2.7 Capacitor banks N/A

5.6.2.8 Internal batteries P

5.7 2.10/RD

Clearances, creepage distances and distances through insulation P

2.10.1/RD General Over voltage Category II is assumed for this unit.

P

2.10.1.1/RD

Frequency ....................................................... : Considered P

2.10.1.2/RD

Pollution degrees ............................................. : Pollution Degree 2 considered.

P

2.10.1.3/RD

Reduced values for functional insulation Functional insulation provided, unit meets criteria for functional insulation as per 5.3.4 a) or c).

P

2.10.1.4/RD

Intervening unconnected conductive parts Considered P

2.10.1.5/RD

Insulation with varying dimensions Considered P

2.10.1.6/RD

Special separation requirements Considered P

2.10.1.7/RD

Insulation in circuits generating starting pulses No starting pulses N/A

2.10.2/RD Determination of working voltage P

2.10.2.1/RD

General P

2.10.2.2/RD

RMS working voltage P

Page 22: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 22 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

2.10.2.3/RD

Peak working voltage P

2.10.3/RD Clearances P

2.10.3.1/RD

General P

2.10.3.2/RD

Mains transient voltages Overvoltage Category II P

a) AC mains supply ......................................... : Between the phases AC250V

2500 V transient

P

b) Earthed d.c. mains supplies ........................ : N/A

c) Unearthed d.c. mains supplies .................... : N/A

d) Battery operation ......................................... : N/A

2.10.3.3/RD

Clearances in primary circuits P

2.10.3.4/RD

Clearances in secondary circuits P

2.10.3.5/RD

Clearances in circuits having starting pulses N/A

2.10.3.6/RD

Transients from a.c. mains supply .................. : P

2.10.3.7/RD

Transients from d.c. mains supply .................. : N/A

2.10.3.8/RD

Transients from telecommunication networks and cable distribution systems ............................... :

N/A

2.10.3.9/RD

Measurement of transient voltage levels Transient levels not measured.

N/A

a) Transients from a mains supply N/A

For an a.c. mains supply ................................. : N/A

For a d.c. mains supply ................................... : N/A

b) Transients from a telecommunication network : N/A

2.10.4/RD Creepage distances P

2.10.4.1/RD

General P

2.10.4.2/RD

Material group and comparative tracking index P

CTI tests .......................................................... : Material group IIIb is assumed to be used

2.10.4.3/RD

Minimum creepage distances P

2.10.5 /RD Solid insulation P

2.10.5.1/RD

General P

Page 23: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 23 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

2.10.5.2/RD

Distances through insulation P

2.10.5.3/RD

Insulating compound as solid insulation See clause 2.10.5.4 P

2.10.5.4/RD

Semiconductor devices All Opto-isolators have either a distance through insulation of 0.4 mm, which has been tested for 5000 VAC Electric Strength and for compliance of clause 2.10.5.5, or an internal creepage distance of > 4 mm and a Thermal Cycling Test to clause 2.10.10 has been performed to fulfil the requirements for Pollution Degree 1. All Opto-isolators are also certified to VDE 0884 and/or IEC 60747-5-5

See critical component list for details on Opto-isolators

P

2.10.5.5/RD

Cemented joints See 2.10.5.4 and 2.10.6.3 P

2.10.5.6/RD

Thin sheet material – General P

2.10.5.7/RD

Separable thin sheet material 3 layers, see annex C P

Number of layers (pcs) .................................... :

2.10.5.8/RD

Non-separable thin sheet material Not used N/A

2.10.5.9/RD

Thin sheet material – standard test procedure See 2.10.5.10 N/A

Electric strength test

2.10.5.10 /RD

Thin sheet material – alternative test procedure Alternative test procedure used

N/A

Electric strength test (see appended table 8.2)

2.10.5.11 /RD

Insulation in wound components N/A

2.10.5.12 /RD

Wire in wound components N/A

Working voltage ............................................... :

a) Basic insulation not under stress ................ : N/A

b) Basic, supplementary, reinforced insulation : N/A

c) Compliance with Annex U ........................... : N/A

Two wires in contact inside wound component;

angle between 45 and 90 ............................. :

N/A

Page 24: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 24 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

2.10.5.13 /RD

Wire with solvent-based enamel in wound components

Not used N/A

Electric strength test

Routine test N/A

2.10.5.14 /RD

Additional insulation in wound components N/A

Working voltage ............................................... :

- Basic insulation not under stress .................. : N/A

- Supplementary, reinforced insulation ............ : N/A

2.10.6/RD Construction of printed boards P

2.10.6.1/RD

Uncoated printed boards P

2.10.6.2/RD

Coated printed boards N/A

2.10.6.3/RD

Insulation between conductors on the same inner surface of a printed board

Compliance with clause 2.10.5.5 “c)”,

N/A

2.10.6.4/RD

Insulation between conductors on different layers of a printed board

N/A

Distance through insulation (see appended table 2.10.5) N/A

Number of insulation layers (pcs) .................... : N/A

2.10.7/RD Component external terminations (see appended table 2.10.3 and 2.10.4)

N/A

2.10.8/RD Tests on coated printed boards and coated components

Coating not applied. N/A

2.10.8.1/RD

Sample preparation and preliminary inspection N/A

2.10.8.2/RD

Thermal conditioning N/A

2.10.8.3/RD

Electric strength test (see appended table 5.2) N/A

2.10.8.4/RD

Abrasion resistance test N/A

2.10.9/RD Thermal cycling See clause 2.10.5.4, 2.10.5.5, 2.10.6.3

N/A

2.10.10/RD Test for Pollution Degree 1 environment and insulating compound

See clause 2.10.5.4 N/A

2.10.11/RD Tests for semiconductor devices and cemented joints

See clause 2.10.5.4, 2.10.6.3 N/A

2.10.12/RD Enclosed and sealed parts N/A

6 Wiring, connections and supply P

6.1 General P

Page 25: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 25 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

6.1.1 Introduction P

3.1/RD General P

3.1.1/RD Current rating and overcurrent protection Internal wiring is adequate for the current. Protection is adequate for the application

P

3.1.2/RD Protection against mechanical damage Wires do not touch sharp edges and heat sinks that could damage the insulation and cause hazard.

P

3.1.3/RD Securing of internal wiring Wires are adequately fixed to prevent excessive strain or damage of the conductors' insulation.

P

3.1.4/RD Insulation of conductors The insulation of the individual conductors is suitable for the application and the working voltage.

(see appended table 5.2)

P

3.1.5/RD Beads and ceramic insulators Beads or ceramic insulators are not used

N/A

3.1.6/RD Screws for electrical contact pressure Electrical and earthing connections engage at least two complete threads into metal.

No screws of insulating material are used for electrical and earthing connections.

P

3.1.7/RD Insulating materials in electrical connections Current carrying and protective earthing connections are metal to metal. Screws with star/spring washer are used for the connection between ground trace (PWB) and chassis

P

3.1.8/RD Self-tapping and spaced thread screws Thread cutting or space thread screw not used for current carrying electrical connections.

P

3.1.9/RD Termination of conductors Conductors are suitable terminated, creepage and clearances maintained, second securing for soldered terminations provided.

P

10 N pull test 10 N applied to relevant conductors.

P

3.1.10/RD Sleeving on wiring Sleeving if safety related reliably kept in position.

P

Page 26: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 26 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

6.1.2 Dimensions and rating of busbars and insulated conductors

P

6.2 Connection to power P

6.2.1 General provisions for connection to power P

3.2.2/RD Multiple supply connections Only one supply connection N/A

3.2.3/RD Permanently connected equipment UPS.

Unit is provided with an appliance inlet.

N/A

Number of conductors, diameter of cable and conduits (mm) .................................................. :

3.2.4/RD Appliance inlets see component list for details on appliance inlet

P

3.2.5/RD Power supply cords AC Power Cord was not part of this investigation

N/A

3.2.5.1/RD AC power supply cords See 3.2.5 N/A

Type ................................................................. :

Rated current (A), cross-sectional area (mm²), AWG ................................................................ :

3.2.5.2/RD DC power supply cords Power cord for external batteries are not part of this investigation

N/A

3.2.6/RD Cord anchorages and strain relief N/A

Mass of equipment (kg), pull (N) .................... :

Longitudinal displacement (mm) ..................... :

3.2.7/RD Protection against mechanical damage P

3.2.8/RD Cord guards N/A

Diameter or minor dimension D (mm); test mass (g) .................................................................... :

Radius of curvature of cord (mm) ..................... :

6.2.2 Means of connection ....................................... : P

More than one supply connection ................... : N/A

6.3 Wiring terminals for external power conductors P

3.3/RD Wiring terminals for connection of external conductors

P

3.3.1/RD Wiring terminals N/A

3.3.2/RD Connection of non-detachable power supply cords N/A

3.3.3/RD Screw terminals N/A

3.3.4/RD Conductor sizes to be connected N/A

Page 27: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 27 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

Rated current (A), cord/cable type, cross-sectional area (mm

2) ........................................................ :

3.3.5/RD Wiring terminal sizes N/A

Rated current (A), type, nominal thread diameter (mm) ................................................................ :

3.3.6/RD Wiring terminal design N/A

3.3.7/RD Grouping of wiring terminals N/A

3.3.8/RD Stranded wire N/A

7 Physical requirements P

7.1 Enclosure P

7.2 4.1/RD

Stability P

Angle of 10 P

Test force (N) .................................................. : P

7.3 4.2/RD

Mechanical strength P

4.2.1/RD General P

4.2.2/RD Steady force test, 10 N Applied to relevant parts. No hazard.

P

4.2.3/RD Steady force test, 30 N Applied to relevant parts. No hazard.

P

4.2.4/RD Steady force test, 250 N Applied to relevant parts. No hazard.

P

4.2.5/RD Impact test Test performed on the top, bottom and on the side of the unit. No hazard.

P

Fall test P

Swing test P

4.2.6/RD Drop test; height (mm) ..................................... : N/A

4.2.7/RD Stress relief test N/A

4.2.8/RD Cathode ray tubes No CRT’s N/A

Picture tube separately certified ...................... : N/A

4.2.9/RD High pressure lamps No High Pressure Lamps N/A

4.2.10/RD Wall or ceiling mounted equipment; force (N) . : Unit is not intended for wall or ceiling mounting

N/A

Page 28: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 28 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

7.4 Construction details P

7.4.1 Introduction P

4.3.1/RD Edges and corners All edges and corners were judged to be sufficiently well rounded as to not constitute a hazard.

P

4.3.2/RD Handles and manual controls; force (N) ........... : No handles and manual controls.

N/A

4.3.3/RD Adjustable controls No adjustable controls. N/A

4.3.4/RD Securing of parts No loosening of parts impairing creepage distances or clearances is likely to occur.

P

4.3.5/RD Connection by plugs and sockets P

4.3.7/RD Heating elements in earthed equipment Not heating elements N/A

4.3.11/RD Containers for liquids or gases No such a container N/A

4.4/RD Protection against hazardous moving parts P

4.4.1/RD General Unit is provided with a DC fan P

4.4.2/RD Protection in operator access areas ................ : UPS. Fan guards provided P

4.4.3/RD Protection in restricted access locations ......... : N/A

4.4.4/RD Protection in service access areas P

4.4.5/RD Protection against moving fan blades P

4.4.5.1/RD General P

Not considered to cause pain or injury. a) ....... : P

Is considered to cause pain, not injury. b) ....... : N/A

Considered to cause injury. c) ....... : N/A

4.4.5.2 Protection for users UPS. Fan guards provided P

Use of symbol or warning ................................ : N/A

4.4.5.3 Protection for service persons UPS. Fan guards provided P

Use of symbol or warning ................................ : N/A

4.5/RD Thermal requirements P

4.5.1/RD General P

4.5.2/RD Temperature tests See previous test reports P

Normal load condition per Annex L ................. : P

4.5.3/RD Temperature limits for materials P

4.5.4/RD Touch temperature limits P

4.5.5/RD Resistance to abnormal heat .......................... : P

7.4.2 Openings P

Page 29: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 29 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

7.4.3 Gas Concentration P

7.4.4 Equipment movement P

7.5 4.7/RD

Resistance to fire P

4.7.1/RD Reducing the risk of ignition and spread of flame Risk of ignition due to high temperatures minimized by design and components. Materials with the required flammability classes are used.

Safety relevant components used within their specified rating.

Electrical parts are not likely to ignite nearby materials.

Temperatures see 4.5.1

P

Method 1, selection and application of components wiring and materials

(see appended table 7.5) P

Method 2, application of all of simulated fault condition tests

(see appended table 7.5) N/A

4.7.2/RD Conditions for a fire enclosure Enclosure is entirely made of metal

P

4.7.2.1/RD Parts requiring a fire enclosure P

4.7.2.2/RD Parts not requiring a fire enclosure P

4.7.3/RD Materials P

4.7.3.1/RD General P

4.7.3.2/RD Materials for fire enclosures P

4.7.3.3/RD Materials for components and other parts outside fire enclosures

Front Bezel rated HB (for decorative only); Bezel for Display (UI interface) is rated HB (LPS circuits are complied.)

P

4.7.3.4/RD Materials for components and other parts inside fire enclosures

All internal materials are rated V-2 or better, or are mounted on printed wiring boards rated V-1 or better

P

4.7.3.5/RD Materials for air filter assemblies No air filter assemblies N/A

4.7.3.6/RD Materials used in high-voltage components No high-voltage components N/A

Page 30: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 30 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

7.6 Battery location P

7.6.1 Battery location and installation See manual, additional battery data available on request

P

7.6.2 Accessibility and maintainability P

7.6.3 Distance P

7.6.4 Case insulation P

7.6.5 Wiring P

7.6.6 Electrolyte spillage P

7.6.7 Ventilation N/A

7.6.8 Charging voltage P

7.7 Temperature rise P

4.5/RD Thermal requirements P

4.5.1/RD General P

4.5.2/RD Temperature tests P

Normal load condition per Annex L ................. : (see appended table 7.7) P

4.5.3/RD Temperature limits for materials (see appended table 7.7) P

4.5.4/RD Touch temperature limits P

4.5.5/RD Resistance to abnormal heat .......................... : (see appended table 4.5.5) Based on the physical characteristic of the thermoplastic materials employed in the power supply, this test was not considered necessary

P

8 Electrical requirements and simulated abnormal conditions P

8.1 General provisions for earth leakage P

5.1.1/RD General P

5.1.7/RD Equipment with touch current exceeding 3,5 mA N/A

8.2 5.2/RD

Electric strength P

5.2.1/RD General (see appended table 8.2) P

5.2.2/RD Test procedure (see appended table 8.2) P

8.3 Abnormal operating and fault conditions P

8.3.1 General P

Page 31: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 31 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

5.3.1/RD Protection against overload and abnormal operation

(see appended table 8.3) P

5.3.2/RD Motors (see appended Annex B) P

5.3.3/RD Transformers (see appended Annex C) P

5.3.4/RD Functional insulation ......................................... : P

5.3.5/RD Electromechanical components N/A

5.3.9/RD Compliance criteria for abnormal operating and fault conditions

P

5.3.9.1/RD During the tests P

5.3.9.2/RD After the tests P

8.3.2 Simulation of faults P

8.3.3 Conditions for tests P

9 6/RD

Connection to telecommunication networks N/A

6.1/RD Protection of telecommunication network service persons, and users of other equipment connected to the network, from hazards in the equipment

N/A

6.1.1/RD Protection from hazardous voltages N/A

6.1.2/RD Separation of the telecommunication network from earth

N/A

6.1.2.1/RD Requirements N/A

Supply voltage (V) ........................................... : ---

Current in the test circuit (mA) ...................... : ---

6.1.2.2/RD Exclusions ....................................................... : N/A

6.2/RD Protection of equipment users from overvoltages on telecommunication networks N/A

6.2.1/RD Separation requirements N/A

6.2.2/RD Electric strength test procedure N/A

6.2.2.1/RD Impulse test N/A

6.2.2.2/RD Steady-state test N/A

6.2.2.3/RD Compliance criteria N/A

6.3/RD Protection of the telecommunication wiring system from overheating

N/A

Max. output current (A) .................................... : ---

3.5/RD Interconnection of equipment N/A

3.5.1/RD General requirements N/A

3.5.2/RD Types of interconnection circuits ..................... : N/A

3.5.3/RD ELV circuits as interconnection circuits N/A

3.5.4/RD Data ports for additional equipment N/A

2.1.3/RD Protection in restricted access locations N/A

Page 32: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 32 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

2.3.1/RD Limits N/A

Type of TNV circuits ......................................... : ---

2.3.2/RD Separation from other circuits and from accessible parts

N/A

2.3.2.1/RD General requirements N/A

2.3.2.2/RD Protection by basic insulation N/A

2.3.2.3/RD Protection by earthing N/A

2.3.2.4/RD Protection by other constructions .................... : N/A

2.3.3/RD Separation from hazardous voltages N/A

Insulation employed ......................................... : ---

2.3.4/RD Connection of TNV circuits to other circuits N/A

Insulation employed ......................................... : ---

2.3.5/RD Test for operating voltages generated externally N/A

2.6.5.8/RD Reliance on telecommunication network or cable distribution system

N/A

2.10.3.3/RD

Clearances in primary circuits N/A

2.10.3.4/RD

Clearances in secondary circuits N/A

2.10.4/RD Creepage distances N/A

2.10.4.1/RD

General N/A

2.10.4.2/RD

Material group and comparative tracking index N/A

CTI tests ........................................................... : ---

2.10.4.3/RD

Minimum creepage distances N/A

M/RD Annex M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1/RD) N/A

M.1/RD Introduction N/A

M.2 /RD Method A N/A

M.3/RD Method B N/A

M.3.1/RD Ringing signal N/A

M.3.1.1/RD Frequency (Hz) ................................................ : ---

M.3.1.2/RD Voltage (V) ...................................................... : ---

M.3.1.3/RD Cadence; time (s), voltage (V) ........................ : ---

M.3.1.4/RD Single fault current (mA) .................................. : ---

M.3.2/RD Tripping device and monitoring voltage .......... : N/A

M.3.2.1/RD Conditions for use of a tripping device or a monitoring voltage

---

M.3.2.2/RD Tripping device N/A

Page 33: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 33 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

M.3.2.3/RD Monitoring voltage (V) ..................................... : N/A

A/RD Annex A, Tests for resistance to heat and fire N/A

A.1/RD Flammability test for fire enclosures of movable equipment having a total mass exceeding 18 kg, and of stationary equipment (see 4.7.3.2/RD)

N/A

A.1.1/RD Samples ............................................................ : ---

Wall thickness (mm) ......................................... : ---

A.1.2/RD Conditioning of samples; temperature (C) ..... : N/A

A.1.3/RD Mounting of samples ....................................... : N/A

A.1.4/RD Test flame (see IEC 60695-11-3) N/A

Flame A, B, C or D .......................................... : ---

A.1.5/RD Test procedure N/A

A.1.6/RD Compliance criteria N/A

Sample 1 burning time (s) ................................ : ---

Sample 2 burning time (s) ................................ : ---

Sample 3 burning time (s) ................................ : ---

A.2/RD Flammability test for fire enclosures of movable equipment having a total mass not exceeding 18 kg, and for material and components located inside fire enclosures (see 4.7.3.2/RD and 4.7.3.4/RD)

N/A

A.2.1/RD Samples, material ............................................. : ---

Wall thickness (mm) ......................................... : ---

A.2.2/RD Conditioning of samples; temperature (°C) ..... : N/A

A.2.3/RD Mounting of samples ....................................... : N/A

A.2.4/RD Test flame (see IEC 60695-11-4) N/A

Flame A, B or C ............................................... : ---

A.2.5/RD Test procedure N/A

A.2.6/RD Compliance criteria N/A

Sample 1 burning time (s) ................................ : ---

Sample 2 burning time (s) ................................ : ---

Sample 3 burning time (s) ................................ : ---

A.2.7/RD Alternative test acc. to IEC 60695-11-5, cl. 5 and 9 N/A

Sample 1 burning time (s) ................................ : ---

Sample 2 burning time (s) ................................ : ---

Sample 3 burning time (s) ................................ : ---

A.3/RD Hot flaming oil test (see 4.6.2/RD) N/A

A.3.1/RD Mounting of samples N/A

A.3.2/RD Test procedure N/A

A.3.3/RD Compliance criterion N/A

Page 34: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 34 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

B/RD Annex B, Motor tests under abnormal conditions (see 4.7.2.2/RD and 5.3.2/RD)

B.1/RD General requirements DC Fans are used P

Position ............................................................ : See Components List

Manufacturer ................................................... :

Type ................................................................. :

Rated values .................................................. :

B.2/RD Test conditions P

B.3/RD Maximum temperatures P

B.4/RD Running overload test N/A

B.5/RD Locked-rotor overload test N/A

Test duration (days) ........................................ :

Electric strength test: test voltage (V) ............. :

B.6/RD Running overload test for d.c. motors in secondary circuits

Fans are VDE or TÜV certified to IEC/EN 60950-1

P

B.6.1/RD General See B.6 P

B.6.2/RD Test procedure See B.6 P

B.6.3/RD Alternative test procedure See B.6 P

B.6.4/RD Electric strength test; test voltage (V) ............. : See B.6 P

B.7/RD Locked-rotor overload test for d.c. motors in secondary circuits

Fans are VDE or TÜV certified to IEC/EN 60950-1 2

nd Edition

P

B.7.1/RD General See B.7 P

B.7.2/RD Test procedure See B.7 P

B.7.3/RD Alternative test procedure See B.7 P

B.7.4/RD Electric strength test; test voltage (V) ............. : See B.7 N/A

B.8/RD Test for motors with capacitors N/A

B.9/RD Test for three-phase motors N/A

B.10/RD Test for series motors N/A

Operating voltage (V) ...................................... : ---

C/RD Annex C, Transformers (see 1.5.4/RD and 5.3.3/RD) P

Position ............................................................ : See previous Test Reports

Manufacturer ................................................... :

Type ................................................................. :

Rated values .................................................. :

Method of protection ......................................... :

Page 35: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 35 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

C.1/RD Overload test P

C.2/RD Insulation P

Protection from displacement of windings ........ : P

D/RD Annex D, Measuring instruments for touch current tests (see 5.1.4/RD) P

D.1/RD Measuring instrument N/A

D.2/RD Alternative measuring instrument P

E/RD Annex E, Temperature rise of a winding (see Annex E/RD) N/A

F/RD Annex F, Measurements of clearances and creepage distance (see 2.10/RD and Annex G/RD)

P

G/RD Annex G, Alternative method for determining minimum clearances N/A

G.1/RD Clearances N/A

G.1.1/RD General N/A

G.1.2/RD Summary of the procedure for determining minimum clearances N/A

G.2/RD Determination of mains transient voltage (V) N/A

G.2.1/RD AC mains supply ............................................. : N/A

G.2.2/RD Earthed d.c. mains supplies ............................ : N/A

G.2.3/RD Unearthed d.c. mains supplies ........................ : N/A

G.2.4/RD Battery operation ............................................. : N/A

G.3/RD Determination of telecommunication network transient voltage (V) ........................................ :

N/A

G.4/RD Determination of required withstand voltage (V) N/A

G.4.1/RD Mains transients and internal repetitive peaks : N/A

G.4.2/RD Transients from telecommunication networks . : N/A

G.4.3/RD Combination of transients N/A

G.4.4/RD Transients from cable distribution systems N/A

G.5/RD Measurement of transient voltages (V) N/A

a) Transients from a mains supply N/A

For an a.c. mains supply N/A

For a d.c. mains supply N/A

b) Transients from a telecommunication network N/A

G.6/RD Determination of minimum clearances ............ : N/A

H Annex H, Guidance on protection against ingress of water and foreign objects (see IEC 60529)

N/A

Page 36: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 36 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

I Annex I, Backfeed protection test P

I.1 General See previous test reports P

I.2 Test for pluggable UPS P

I.3 Test for permanently connected UPS N/A

I.4 Load-induced change of reference potential See previous test reports P

I.5 Solid-state backfeed protection (see clause 7.1-7.5 of IEC 62040-2 and clause 7.1-7.2 of IEC 62040-3)

P

J/RD Annex J, Table of electrochemical potentials (see 2.6.5.6/RD) P

Metal(s) used ................................................... :

K/RD Annex K, Thermal controls (see 1.5.3/RD and 5.3.8/RD) N/A

K.1/RD Making and breaking capacity N/A

K.2 /RD Thermostat reliability; operating voltage (V) .... : N/A

K.3/RD Thermostat endurance test; operating voltage (V) .......................................................................... :

N/A

K.4/RD Temperature limiter endurance; operating voltage (V) .................................................................... :

N/A

K.5/RD Thermal cut-out reliability N/A

K.6/RD Stability of operation N/A

L Annex L, Reference loads P

L.1 General P

L.2 Reference resistive load P

L.3 Reference inductive-resistive load

L.4 Reference capacitive-resistive loads N/A

L.5 Reference non-linear load N/A

L.5.1 General N/A

L.5.2 Test method N/A

L.5.3 Connection of the non-linear reference load

M Annex M, Ventilation of battery compartments P

M.1 General Refer to test data, none ventilation batteries

P

M.2 Normal conditions P

M.3 Blocked conditions P

M.4 Overcharge conditions P

Page 37: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 37 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

N Annex N, Minimum and maximum cross-sections of copper conductors suitable for connection (see 6.3)

N/A

U/RD Annex U, Insulated winding wires for use without interleaved insulation (see 2.10.5.4/RD)

P

V/RD Annex V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1/RD) P

V.1/RD Introduction P

V.2/RD TN power distribution systems P

V.3/RD TT power distribution systems P

V.4/RD IT power distribution systems N/A

Page 38: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 38 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

4.6, 1.6.2/RD

TABLE: Electrical Data (in normal conditions) P

fuse # I rated (A) U (V) P (W) I (mA) I fuse (mA)

condition/status

Supplementary information: refer to previous Test Reports

5.1.1 2.1.1.5/RD

TABLE: Max. V, A, VA Test P

Voltage (rated) (V)

Current (rated) (A)

Voltage (max.) (V)

Current (max.) (A)

VA (max.) (VA)

Supplementary information: refer to previous Test Reports

5.1.1 2.1.1.5/RD

TABLE: Stored Energy P

Capacitance C (µF) Voltage U (V) Energy E (J)

Supplementary information: refer to previous Test Reports

5.1.1 2.1.1.7/ RD

TABLE: discharge of capacitors in the primary circuit P

Condition calculated

(s)

measured

(s)

t u 0V (s)

Comments

Supplementary information: refer to previous Test Reports

Page 39: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 39 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

5.2.1 2.2/RD

TABLE: Evaluation Of Voltage Limiting Components In SELV Circuits P

Component (measured between) max. voltage (V) (normal operation)

Voltage Limiting Components

V peak V d.c.

Fault test performed on voltage limiting components

Voltage measured (V) in SELV circuits (V peak or V d.c.)

Supplementary information: refer to previous Test Reports ; Opto-isolator between mains and SELV output

5.2.5 2.5/RD

TABLE: Limited Power Sources P

Circuit output tested:

Note: Measured Uoc (V) with all load circuits disconnected:

Components Sample No. Uoc (V) Isc (A) VA

Meas. Limit Meas. Limit

Supplementary information: refer to previous Test Reports

5.7 2.10.2/RD

Table: Working Voltage Measurement P

Location RMS voltage (V) Peak voltage (V) Comments

supplementary information: refer to previous Test Reports

Page 40: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 40 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

5.7 2.10.3/RD

TABLE: Clearance And Creepage Distance Measurements P

clearance cl and creepage distance dcr at/of:

Up (V)

U r.m.s. (V)

Required cl (mm)

cl (mm)

required dcr (mm)

dcr (mm)

Supplementary information: refer to previous Test Reports

5.7 2.10.5.2/ RD

TABLE: Distance Through Insulation Measurements P

Distance through insulation di at/of: U r.m.s. (V)

Test voltage (V)

Required di (mm)

di (mm)

Supplementary information: refer to previous Test Reports

5.7 and 2.10.4/RD

TABLE: Clearance and creepage distance measurements P

Clearance (cl) and creepage distance (cr) at/of/between:

U peak (V)

U r.m.s. (V)

Required cl (mm)

cl (mm)

Required cr (mm)

cr (mm)

Basic / supplementary:

Reinforced:

Supplementary information: refer to previous Test Reports;

Page 41: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 41 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

7.7 4.5/RD

TABLE: Heating Test P

Test voltage (V) ...................................................... :

Ambient (oC) ........................................................... :

Thermocouple Locations max. temperature measured,

(oC)

max. temperature limit, (oC)

Supplementary information:

TABLE: Heating test, resistance method

Test voltage (V) ...................................................... :

Ambient, t1 (C) ....................................................... :

Ambient, t2 (C) ....................................................... :

Temperature rise of winding R1 (Ω) R2 (Ω) ΔT (K) Max. dT (K) Insulation class

Supplementary information: refer to previous Test Reports

7.4 4.5.5/RD

TABLE: Ball Pressure Test of Thermoplastics P

Allowed impression diameter (mm) ................... :

Part Test temperature (C) Impression diameter (mm)

Supplementary information: refer to previous Test Reports

Page 42: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 42 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

5.7 2.10.5

TABLE: Dielectric Strength P

Test voltage applied between: Test potential applied (V)

Breakdown / flashover (Yes/No)

Supplementary information: refer to previous Test Reports

7.5 4.7/RD

TABLE: Resistance to fire P

Part Manufacturer of material

Type of material Thickness (mm)

Flammability class

Evidence

Supplementary information: refer to previous Test Reports

8 5.1/RD

TABLE: touch current measurement P

Measured between: Measured (mA)

Limit (mA)

Comments/conditions

Supplementary information: refer to previous Test Reports

8.3 5.3/RD

TABLE: Fault condition tests P

Ambient temperature (C) ................................ :

Power source for EUT: Manufacturer, model/type, output rating ................................. :

Com-ponent

No.

Fault Supply voltage

(V)

Test time

Fuse # Fuse current

(A)

Observation

Supplementary information: refer to previous Test Reports

Page 43: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 43 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

C.2/RD TABLE: transformers P

Loc. Tested insulation Working

voltage

peak / V

(2.10.2)

Working

voltage

rms / V

(2.10.2)

Required

electric

strength

(5.2)

Required

clearance /

mm

(2.10.3)

Required

creepage

distance /

mm

(2.10.4)

Required

distance thr.

insul.

(2.10.5)

Loc.

Tested insulation Test

voltage/

V

Measured

clearance /

mm

Measured

creepage

dist./ mm

Measured

distance thr.

insul. / mm;

number of

layers

Supplementary information: see Appendix or/and refer to previous Test Reports

C.2/RD TABLE: transformers P

Transformers

refer to previous Test Reports

Page 44: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 44 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

M Ventilation of battery compartments N/A

The required dimension for the ventilation openings will be calculated with the following formula:

A ≥ Q/360 [m²]

with Q = 0.054 * n * I * C

where:

Q : airflow in m³/h

n : number of battery cells

I : constant factor (0,2A/100Ah for valve regulated lead acid batteries)

C : is the battery nominal capacity in Ah at the 10h discharge rate

With the specific data for the UPS the following dimension for the ventilation openings is required:

n : ?

C : ?

A ≥ (0.054 * n * 0.2 A/100 Ah * C)/360

A ≥ ? m²

Verdict

The size of ventilation openings in battery cabinet exceeds the required airflow by far (as well as the UPS).

Battery has no ventilation openings

Page 45: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 45 of 53 Report No. 218478-CI3-1

IEC 62040-1

Clause Requirement + Test Result - Remark Verdict

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

4.5 TABLE: Critical components information P

Object / part No.

Manufacturer/ trademark

Type / model Technical data Standard Mark(s) of conformity

1)

See Appendix 1

Supplementary information:

1) Provided evidence ensures the agreed level of compliance. See OD-CB2039.

Page 46: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 46 of 53 Report No. 218478-CI3-1

Critical Component list APPENDIX 1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

4.5 TABLE: List of critical components

Object/part no. Manufacturer/ trademark

Type/model Technical data Standard Mark(s) of conformity

1.

Printed Circuit Board Various Various V-0 UL 796 UL

UPS

Fan (490-1059) Kaimei JF0825B2SRAR 24Vdc, 0.17A, max. 48.53 CFM

IEC/EN 60950-1 50029788 (TUV)

Appliance Inlet (770-0339)

Rong Feng SS-3B 16A, 250Vac IEC/EN 60320-1 40013645 (VDE)

ELCOM EMI-18 16A, 250Vac 40014433 (VDE)

Alternate – Input Terminal Block (740-0076A)

WECO Electrical Connectors Inc.

327-HDS 3P 600V 1924400-3335-0065 / 180170

UL, CSA, 40039779 (VDE)

AC Output Socket (770-0006-Z-001)

ELCOM EMO-14 10A, 250Vac IEC/EN 60320-1 40005067 (VDE)

Alternate -Output Terminal Block (740-0067-Z)

MOLEX 39910-0103 3P 600V, 65A 1924400-3335-0065 / 180170

UL

Internal Battery Connector

Anderson SBS50 50A UL1977 E26226 (UL)

Connector for external battery

Anderson SBS75X 75A UL1977 E26226 (UL)

Case of display module

-- -- HB min. UL746C UL

Main Board (640-3700x for 3KVA, 640-3699x for 2.2KVA)

Choke (L1200) for model SRT3000XLI, SRT3000RMXLI (420-2213-Z)

APC 420-2213XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Choke (L1200) for model SRT2200XLI, SRT2200RMXLI (420-2209-Z)

APC 420-2209XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Choke (L1206) (420-0006-Z)

APC 420-0006XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Page 47: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 47 of 53 Report No. 218478-CI3-1

Critical Component list APPENDIX 1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

4.5 TABLE: List of critical components

Object/part no. Manufacturer/ trademark

Type/model Technical data Standard Mark(s) of conformity

1.

Choke (L1203)

for model SRT3000XLI, SRT3000RMXLI (420-2214-Z)

APC 420-2214XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1

Tested within equipment

Choke (L1203)

for model SRT2200XLI, SRT2200RMXLI

APC 420-2210XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Choke (L1207)

for model SRT3000XLI, SRT3000RMXLI

APC 420-2215XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Choke (L1207)

for model SRT2200XLI, SRT2200RMXLI

APC 420-2211XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Choke (L1208)

(420-2202-Z)

APC 420-2202XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Choke (L1201, L1202)

APC 422-0016XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Charger Transformer (T1204)

for model SRT3000XLI, SRT3000RMXLI

APC 433-0136XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Page 48: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 48 of 53 Report No. 218478-CI3-1

Critical Component list APPENDIX 1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

4.5 TABLE: List of critical components

Object/part no. Manufacturer/ trademark

Type/model Technical data Standard Mark(s) of conformity

1.

Charger Transformer (T1204)

for model SRT2200XLI, SRT2200RMXLI I

APC 433-0132XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

AUX Charger Transformer (T1201) SRT3000XLI, SRT3000RMXLI

APC 433-0133XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

AUX Charger Transformer (T1201) SRT2200XLI, SRT2200RMXL

APC 433-0123XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

DC to DC transformer (T1203)

SRT3000XLI, SRT3000RMXLI

APC 433-0135XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

DC to DC transformer (T1203)

SRT2200XLI, SRT2200RMXL

APC 433-0130XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Current Sense Transformer (CT1200)

APC 460-1003 XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Current Sense Transformer (CT1201)

APC 460-1032 XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Current Sense Transformer (CT1202)

APC 460-1006 XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Page 49: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 49 of 53 Report No. 218478-CI3-1

Critical Component list APPENDIX 1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

4.5 TABLE: List of critical components

Object/part no. Manufacturer/ trademark

Type/model Technical data Standard Mark(s) of conformity

1.

Transformer (T1200)

(430-7205-Z)

APC 430-7205 XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Backfeed Relay (RY1205) (450-3005-Z)

Song Chuan 832A-1A-F-C-H-24VDC

20A, 250Vac Coil 24 Vdc

EN 61810-1 UL60947-1

6615 (VDE) E88991 (UL)

Omron G8P-1A4P-BG 20A, 250Vac Coil 24 Vdc

EN 61810-1 400004714 (VDE )

Backfeed Relay (RY1206) (450-0029-Z)

HASCO HAT901CSDC24-1-4K

30A, 240Vac Coil 24 Vdc

EN 61810-1 R 50194653 (TUV)

Relay (RY1204) (450-2151A-Z)

SongChuan 894H-2AH1-F-S 8A, 240Vac Coil 24 Vdc

EN 61810-1 40007827 (VDE)

Alternative Omron Corp G2RG-2A4 8A, 250Vac, Coil 24Vdc

EN 61810-1 VDE

Relay (RY1202, RY1203) (450-3006-Z)

SongChuan 832A-1A-F-C U29 30A, 250Vac Coil 24 Vdc

UL60947-1 E88991 (UL)

OMRON G8P-1A4P-A04 30A, 250Vac Coil 24 Vdc

UL60947-1 E41643 (UL)

Relay (RY1200) (450-3004-Z)

HASCO HATF905ASDC24

50A, 28Vdc Coil 24 Vdc

UL60947-1 E75887 (UL)

Capacitor X2 (C1226, C1227, C1228) (232-1225-Z-001)

CAMEL Technology

MPX series 250Vac min., 2.2uF IEC/EN 60384-14 136014 (VDE)

EPCOS Electronic

B3292 Series 40005524, 40005536, 40010694, 40019254, 40021331 (VDE)

ARCOTRONICS

R.46 V4413 (ENEC03)

Capacitor Y2 (C1239, C1240,

Murata KH 250Vac, 4700pF IEC/EN 60384-14 40002796 (VDE)

C1241, C1242, C1243, C1244, C1245, C1246) (221-1502-Z)

Apex NU 40023096 (VDE)

MOV (MV1200) (380-4200-Z)

Panasonic V14681U 680V, 190J max. IEC/EN 61051 5912 (VDE)

Epcos S14K420 420V, 90J IEC/EN 61051 40027582 (VDE)

Thinking TVR14681 680V, 130J IEC/EN 61051 5944 (VDE)

Page 50: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 50 of 53 Report No. 218478-CI3-1

Critical Component list APPENDIX 1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

4.5 TABLE: List of critical components

Object/part no. Manufacturer/ trademark

Type/model Technical data Standard Mark(s) of conformity

1.

MOV (MV1204A, MV1205A) (380-0511-Z)

MAIDA D65ZOV511RA190

510Vac, 470J IEC/EN 61051 40031393 (VDE)

Alternative Panasonic Creamic products

ERZV20D471 300Vac IEC/EN 61051-1 VDE

Alternative Ceramate Technical Co. Ltd

GNR20D471 300Vac IEC/EN 61051-1 VDE

Alternative Maida D63 series 300Vac IEC/EN 61051-1 VDE

Alternative Wujin Thinking Electronic Co. Ltd

TVR20471 300Vac IEC/EN 61051-1 VDE

Alternative Epcos Electronic Components

S20K series 300Vac IEC/EN 61051-1 VDE

Fuse (F1202, F1203) (512-0030-Z)

COOPER BUSSMANN

MDA-V-R 250Vac, 30A UL 248-14 E19180 (UL)

Fuse (F1204, F1205) (513-0020-Z)

LITTELFUSE TE5 808 250Vac, 3A UL 248-14 E67006 (UL)

COOPER BUSSMANN

PCB-3-R 250Vac, 3A UL 248-14 E19180 (UL)

Fuse (F1200) (513-0022-Z)

BEL FUSE MRT 4 250Vac, 4A EN 60127-3 139937 (VDE)

Schurter AG

MST 250 250Vac, 4A EN 60127-3 40013529 (VDE)

LITTELFUSE

372 250Vac, 4A EN 60127-3 097187 (VDE)

Fuse (F1201) (515-1030A-Z)

COOPER BUSSMANN

GBH-V030A6F 500V , 30A UL 248-1 E19180 (UL)

LITTELFUSE

505030 500V , 30A UL 248-1 E10480 (UL)

DC LPS board (640-3708x)

Isolated Transformer (T701)

(433-0129-Z)

APC 433-0129XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B

See attached datasheet

IEC 60950-1 Tested within equipment

Diode (D709)

(330-3100-Z)

-- -- 3A, 200V -- --

Diode (D710)

(339-0030-Z)

-- -- 1A, 200V -- --

Page 51: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 51 of 53 Report No. 218478-CI3-1

Critical Component list APPENDIX 1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

4.5 TABLE: List of critical components

Object/part no. Manufacturer/ trademark

Type/model Technical data Standard Mark(s) of conformity

1.

Inverter Driver Board

Transformer (T801, T802, T803)

APC 4300516XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

SOG Board

Output Relay (RY881, RY882)

(450-3006-Z)

SongChuan 832A-1A-F-C 30A, 250Vac Coil 24 Vdc

UL60947-1 UL (E88991)

OMRON G8P-1A4P 30A, 250Vac Coil 24 Vdc

UL60947-1 UL (E41643)

PFC Driver Board (640-3711x)

Transformer (T831)

(430-5016-Z)

APC 430-5016XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Communication Board (640-6009x)

Optical Isolator (IC1715, IC1710, IC1718)

(349-0100-Z)

Liteon LTV-817 Dti > 0.8 mm 5000V min. isolation

UL1577

IEC/EN 60747-5-5

40015248 (VDE) E113898(UL)

FAIRCHILD FOD817B Dti > 1 mm 5000V min. isolation

40026857 (VDE) E90700 (UL)

ISOCOM ISP817X Dti > 0.6 mm 5000V min. isolation

40028086 (VDE) E91231(UL)

VISHAY SFH6156 Dti > 0.5 mm 5000V min. Isolation

91888(VDE) E52744(UL)

EVERLIGHT EL816 Dti > 0.4 mm 5000V min. isolation

132249(VDE) E214129(UL)

AVAGO Technologies

HCPL-817 Dti > 0.4 mm 5000V min. isolation

40016429 (VDE) E55361(UL)

Optical Isolator ( IC1707, IC1708, IC1711, IC1712)

(349-0137-Z-001)

AVAGO Technologies

6N137-360E (for Tube)

6N137-560E (for Tape and Reel)

Single channel, 1000V

/us, 630V

IEC/EN 60747-5-5

40009430 (VDE)

Battery Pack

Fuse (F1, F2)

(512-0030-Z)

COOPER BUSSMANN

MDA-V-R 250Vac, 30A UL 248-14 E19180 (UL)

Page 52: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 52 of 53 Report No. 218478-CI3-1

Critical Component list APPENDIX 1

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

4.5 TABLE: List of critical components

Object/part no. Manufacturer/ trademark

Type/model Technical data Standard Mark(s) of conformity

1.

Battery

(910-6003-001)

CSB HR1221W 12V, 21W UL 1989 MH14533(UL)

B&B BP5-12 12V, 5Ah MH19884(UL)

Case (876-1046) (876-1047)

LG AF312A 5V, 2.1mm min. UL746C E67171 (UL)

Optional Battery Pack SRT72BP, SRT72RMBP, SRT96BP, SRT96RMBP

Front Bezel -- -- HB min. UL746C --

Shunt Board (640-9926x)

Fuse (F1, F2) COOPER BUSSMANN

MDA-V-R 125Vdc, 30A UL 248-14 E19180 (UL)

Fuse (F3)

(513-0002-Z) Conquer MET Series 250V, 2A UL 248-14 40017155 (VDE)

COOPER BUSSMANN

SR-5-2A-AP 40020046 (VDE)

LITTELFUSE 372 097187 (VDE)

Transformer (T1)

(430-10056-Z)

APC 430-10056XXXXXXXXXX

(X can be any alphanumeric, +, *, #, _, - or blank)

Class B IEC 60950-1 Tested within equipment

Battery Pack

Fuse (F1, F2) (512-0030-Z)

COOPER BUSSMANN

MDA-V-R 250Vac, 30A UL 248-14 E19180 (UL)

Battery (910-6003-001)

6 or 8 used *)

KUNG LONG WP5-12 12V, 5Ah UL 1989 MH16982 (UL)

B&B BP5-12 12V, 5Ah MH19884(UL)

Case (876-1046) (876-1047)

LG AF312A 5V, 2.1mm min. UL746C E67171 (UL)

1) an asterisk indicates a mark which assures the agreed level of surveillance

*) Number of batteries: 6 for battery pack SRT72BP, SRT72RMBP or 8 for SRT96BP, SRT96RMBP

Page 53: TEST REPORT IEC 62040-1 Uninterruptible power systems (UPS

Page 53 of 53 Report No. 218478-CI3-1

Modifications covered by this report APPENDIX 2

VDE File No 1924400-3335-0067/218478 TRF No. IEC62040_1C

1. Revise the definition of model name. SRT 3000 RM XL I xxxxxxxxxx A B C D E F A: SRT, means series name B: 3000, 2200, means maximum VA output C: RM (means Rack Mounted) or none (means Tower Stand) D: XL, means Extended Run E: I = International (220-230-240V), W = Worldwide (208-220-230-240V) F: xxxxxxxxxx (x=0-9, a-z, A-Z, +, *, #, _, - or blank) for marketing purpose

2. Add an alternate source for relay RY1204.

Relay RY1204 Omron Corp G2RG-2A4 8A, 250Vac, Coil 24Vdc

3. Add an alternate source for MOV MV1204A, MV1205A.