Guided Radar with 2-wire system TGF2200 Micro Pulse Level Meter OUTLINE The TGF2200 series is a unique 2-wire continuous level-measuring instrument using TDR technology. The simple and compact design suitable for tank-top installation with no moving parts has a high cost performance with the maintenance-free and low cost installation by the simple 2-wire loop powered system. Thanks to the coaxial probe, single probe and twin probes this continuous level meter is applicable to wide services including liquids, slurries, powders and granules. The keypad operation on the front display allows easy parameter setting including zero point adjustment and measuring range. The micro pulse level meter is suitable for tank and silo inventory for liquids and powders as well as level controls of the intermediate or underground tanks. FEATURES 2-wire loop powered system with less cable and low installation cost Wide applications by TDR method Elimination of false signals by DPR (Dynamic Parasite Rejection) From −50°C to 300°C and from vacuum to 4.0 MPa No influence from changes in temperature, pressure or density The probe can be used in segment to make it easy to use Measuring Max. 40 m in liquids, powders and granules Horizontal or vertical housing position to make the display easy to read Remote converter allows a free selection of installation Easy checking and changing of parameters without opening the cover Quick coupling system permits removal of the housing and full rotation No moving parts and maintenance free MEASURING PRINCIPLE The Guided Radar level meter TGF2200 is a continuous level meter which has been developed from a proven technology called Time Domain Reflectometry (TDR). The device transmits intermittently low-intensity electromagnetic pulse called micro-pulses along a conductor called probe. These pulses travel along the probe at a very high speed. When the pulses reach the interface of gas and liquids, or gas and powders, the pulses are reflected on the interface and travel back along the probe to the level device. The device measures the time from when the pulse is transmitted to when it is received. The traveling speed of the pulses is constant. The half of this time is equivalent to the direct distance from level meter to the surface of the products. The direct distance determined by above calculation is converted into a level value from the predetermined reference point. In some applications the direct distance is converted into the volume or mass using the tank table. These values are output as current signals in the form of output requirements. The traveling speed of the pulses is almost constant which is little affected by changes in pressure and temperature in the tank and is not affected by changes in temperature of the measuring object, its dielectric constant or density. Transmitted pulse Reflected pulse Signal wave pattern Measuring range Air : Er 1 Measured objects: Dielectric constant Er > 1.6 for direct mode Er > 1.1 for TBF mode TG-L1016-0E Apr 2017 1st edition K

Upload: nguyenkien

Post on 31-Aug-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Guided Radar with 2-wire system

TGF2200 Micro Pulse Level Meter

OUTLINE

The TGF2200 series is a unique 2-wire continuous level-measuring

instrument using TDR technology.

The simple and compact design suitable for tank-top installation

with no moving parts has a high cost performance with the

maintenance-free and low cost installation by the simple 2-wire

loop powered system. Thanks to the coaxial probe, single probe

and twin probes this continuous level meter is applicable to wide

services including liquids, slurries, powders and granules. The

keypad operation on the front display allows easy parameter

setting including zero point adjustment and measuring range. The

micro pulse level meter is suitable for tank and silo inventory for

liquids and powders as well as level controls of the intermediate or

underground tanks.

FEATURES

❏ 2-wire loop powered system with less cable and low installation

cost

❏ Wide applications by TDR method

❏ Elimination of false signals by DPR (Dynamic Parasite Rejection)

❏ From −50°C to 300°C and from vacuum to 4.0 MPa

❏ No infl uence from changes in temperature, pressure or density

❏ The probe can be used in segment to make it easy to use

❏ Measuring Max. 40 m in liquids, powders and granules

❏ Horizontal or vertical housing position to make the display easy

to read

❏ Remote converter allows a free selection of installation

❏ Easy checking and changing of parameters without opening the

cover

❏ Quick coupling system permits removal of the housing and full

rotation

❏ No moving parts and maintenance free

MEASURING PRINCIPLE

The Guided Radar level meter TGF2200 is a continuous level meter

which has been developed from a proven technology called Time

Domain Reflectometry (TDR). The device transmits intermittently

low-intensity electromagnetic pulse called micro-pulses along a

conductor called probe. These pulses travel along the probe at

a very high speed. When the pulses reach the interface of gas

and liquids, or gas and powders, the pulses are reflected on the

interface and travel back along the probe to the level device. The

device measures the time from when the pulse is transmitted to

when it is received. The traveling speed of the pulses is constant.

The half of this time is equivalent to the direct distance from

level meter to the surface of the products. The direct distance

determined by above calculation is converted into a level value from

the predetermined reference point. In some applications the direct

distance is converted into the volume or mass using the tank table.

These values are output as current signals in the form of output

requirements. The traveling speed of the pulses is almost constant

which is little affected by changes in pressure and temperature

in the tank and is not affected by changes in temperature of the

measuring object, its dielectric constant or density.

① Transmitted pulse

② Reflected pulse

③ Signal wave pattern

④ Measuring range

⑤ Air : Er ≈ 1

⑥ Measured objects: Dielectric constant Er > 1.6 for direct mode

Er > 1.1 for TBF mode

TG-L1016-0EApr 20171st edition K

Page 2: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

2 TOKYO KEISO CO., LTD. TG-L1016-0E

STANDARD SPECIFICATIONS

Objects Item Contents

Measuring

objects

Measuring material Liquids, slurries, powders, granules

Measuring principle Time Domain Reflectometry (TDR)

Output variables Level, distance, volume, mass

Probe type

TGF2211 Single rod probe (ϕ8 mm) with PVDF sheath of ϕ16 mm

TGF2212 Twin rod probe (2 × ϕ8 mm)

TGF2221 Single cable probe (ϕ2 mm, ϕ4 mm, ϕ8 mm)

TGF2222 Twin cable probe (2 × ϕ4 mm)

TGF2231 Coaxial probe (ϕ22 mm)

Min. length of dead zone

Top : 150 mm Bottom : 20 mm

Above figures are Min. lengths of dead zone. Length of dead zone may require more

depending on type of probes and measuring conditions. See probe specifications and

measuring length for details.

Outputs

Outputs 4 to 20 mA DC or 3.8 to 20.5 mA DC

Resolution ±3μA

Temperature drift Analog : 50ppm/K Digital : ±15 mm in the Max. specified temperature

Error outputs 22 mA DC, 3.6 mA DC, Fixed by parameter setting

Load resistance*1

R [Ω] ≦ (supply voltage − 11.5 V) / 22 mA for non-explosionproof and intrinsically

safe (Ex i)

R [Ω] ≦ (supply voltage − 13.5 V) / 22 mA for flameproof (Ex d)

The allowable load resistance varies with supplied voltage. See Supply Voltage.

Accuracy

dependent

on reference

conditions

Accuracy

±10 mm for less than 10 m and ±0.1% of the reading for 10 m or more

TBF mode : ±20 mm

Powder and granule measurement : ±20 mm

Resolution 1 mm

Repeatability ±1 mm

Measuring

conditions

Temperature of process connection−50 to +150°C (Standard type), −50 to +300°C (High temperature type : ϕ2 mm Single

cable probe)

Pressure 0 kPa (abs) to 4.0 MPa

Dielectric constant*2Min.1.4 for coaxial probe

Min. 1.1 for TBF mode

Max. dia. of powder and granules 5 mm or less in diameter

Max. following speed 10 m/min. dependent on measuring conditions

Specification of

instrument

Protection classIP66 / IP67 [IEC60529]

NEMA250: NEMA type 4X (Converter housing, 6P (Probe housing)

Ambient

temperature

Without display −40 to +80°C

With display −20 to +60°C Display becomes off when temperature is out of range

Storage temperature −50 to +85°C Meter with display Min.−40°C

Electric

connection

Type 2-wire loop-powered

Power supply voltage

Rated voltage : 24 V DC

Allowable range : 11.5 to 30 V DC for non-explosionproof and intrinsically safe (Ex i)

Allowable range : 13.5 to 36 V DC for flameproof (Ex d)

Cable entries M20 × 1.5 female thread, 1/2˝NPT female thread

Terminals 0.5 to 2.5 mm2

Materials

Housing Aluminum (polyester coating), Stainless steel (SUS316L)

Process connection Stainless steel (SUS316L), Hastelloy® C-22

Probe Stainless steel (SUS316), Stainless steel (SUS316L), Hastelloy® C-22

Seal FKM/FPM, /EPDM, Karlez® 6375

Process

connection

Thread G male thread, NPT male thread

Flange JIS RF flange, ASME RF flange

DisplayDisplay

LCD 128 × 64 pixels in 8-step greyscales

English, Japanese , others

Key pad 4 buttons (right, enter, up, down keys)

*1 See item “Power supply voltage” for the allowable load resistance at 22 mA output.*2 The minimum dielectric constant of measuring objects depends on the type of probe. See specifications of probe. However, in some measuring conditions measurement may not be possible.

Page 3: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

TOKYO KEISO CO., LTD. 3TG-L1016-0E

Probe specifications

Probe type /

length

TGF2211Single rod probe (ϕ8 mm), with PVDF sheath of (ϕ16 mm) / 1 to 3 m / for liquids

Single rod probe (ϕ8 mm) / 1 to 6 m / for liquids / segmented type

TGF2212 Twin rod probe (2 × ϕ8 mm) / 1 to 3 m / for liquids

TGF2221

Single cable probe (ϕ2 mm) / 1 to 40 m / for liquids

Single cable probe (ϕ4 mm) / 1 to 40 m / for liquids

Single cable probe (ϕ8 mm) / 1 to 40 m / for powders and granules

TGF2222 Twin cable probe (2 × ϕ4 mm) / 1 to 28 m / for liquids

TGF2231Coaxial probe (ϕ22 mm) / 0.60 to 3 m / for liquids

Coaxial probe (ϕ22 mm) / 0.60 to 6 m / for liquids / segmented type

Min. length of

dead zone

TGF2211 : Single rod probe Top : 250 mm Bottom : 50 mm

TGF2212 : Twin rod probe Top : 200 mm Bottom : 20 mm

TGF2221 : Single cable probe (ϕ2 mm) Top : 250 mm Bottom : 200 mm

TGF2221 : Single cable probe (ϕ4 mm) Top : 250 mm Bottom : 200 mm

TGF2221 : Single cable probe (ϕ8 mm) Top : 250 mm Bottom : 300 mm

TGF2222 : Twin cable probe Top : 200 mm Bottom : 80 mm

TGF2231 : Coaxial probe Top : 150 mm Bottom : 20 mm

Above figures are Min. lengths of dead zone. Length of dead zone may require more depending on measuring conditions.

See measuring length for details.

Measuring

conditionsDielectric constant*1

Min.1.8 (Single rod probe, single cable probe)

Min.1.6 (Twin rod probes, Twin cable probes)

Min.1.4 (Coaxial probe)

Materials

TGF2211 : Single rod probe Stainless steel (SS316L), PVDF

TGF2211 : Single rod probe (segmented type) Stainless steel (SS316L)

TGF2212 : Twin rod probe Stainless steel (SS316L)

TGF2221 : Single cable probe (ϕ2 mm) Stainless steel (SS316), HASTELLOY® C-22

TGF2221 : Single cable probe (ϕ4 mm) Stainless steel (SS316)

TGF2221 : Single cable probe (ϕ8 mm) Stainless steel (SS316)

TGF2222 : Twin cable probe Stainless steel (SS316)

TGF2231 : Coaxial probe Stainless steel (SS316L), HASTELLOY® C-22

TGF2231 : Coaxial probe (segmented type) Stainless steel (SS316L)

*1 The minimum dielectric constant of measuring objects depends on the measuring conditions. In some measuring conditions measurement may not be possible.

DIMENSIONS

Process connections

h

h h

h

Φ 2 mm single cable probe

For high temperature service

Φ 8 mm single cable probe Other probes

Flangeconnection

Threadconnection

Flangeconnection

Threadconnection

Flangeconnection

Threadconnection

Flangeconnection

Threadconnection

Dimension

mm

ϕ2 mm single cable probeϕ2 mm single cable probe for

high temperature service

ϕ8 mm single cable probe for

powders and granulesOther probes

Thread

connection

Flange

connection

Thread

connection

Flange

connection

Thread

connection

Flange

connection

Thread

connection

Flange

connection

h 43 61 169 186 95 127 45 73

(mm)

Page 4: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

4 TOKYO KEISO CO., LTD. TG-L1016-0E

Housing

Horizontal housing for compact converter Vertical housing for compact converter

Housings for remote converter

Converterhousing

Probehousing

Dimension

mm

Horizontal housing for compact converter Vertical housing for compact converter Housings for remote converter

Non-explosionproof

Intrinsically safeFlameproof

Non-explosionproof

Intrinsically safeFlameproof

Non-explosionproof

Intrinsically safeFlameproof

a 191 258 147 210 104 104

b 175 175 218 218 142 142

c 127 127 127 127 129 129

d ー ー ー ー 195 195

e ー ー ー ー 146 209

f ー ー ー ー 100 100

g ー ー ー ー 130 130

(mm)

Page 5: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

TOKYO KEISO CO., LTD. 5TG-L1016-0E

Probe

Single probe

① ② ③ ④ ⑤ ⑥

Probe typeDimension mm

L (Min.) L (Max.) m t

① Single rod probe 1,000 3,000 ― ―② Single rod probe (segmented type) 1,000 6,000 ― ―③ ϕ2 mm single cable probe 1,000 40,000 100 ϕ14

④ ϕ4 mm single cable probe 1,000 40,000 100 ϕ20

⑤ ϕ8 mm single cable probe 1,000 40,000 245 ϕ38

⑥ ϕ8 mm single cable probe 1,000 40,000 100 ϕ12

Twin probe, Coaxial probe

① ② ③ ④

Probe typeDimension mm

L (Min.) L (Max.) q t

① Twin rod probe 1,000 3,000 ― 25

② Twin cable probe 1,000 28,000 60 ϕ38

③ Coaxial probe 600 3,000 ― ϕ22

④ Coaxial probe (segmented type) 600 6,000 ― ϕ28

Page 6: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

6 TOKYO KEISO CO., LTD. TG-L1016-0E

Weather protection

Verticalhousing

Horizontalhousing

① ② ③

① ② ③

Housing typeDimension [mm]

Mass [kg]a b c d

Vertical housing 244 170 274 245 1.6Horizontal housing 221 170 274 229 1.6

① Left-side view when weather protection is open

② Front view when weather protection is closed

③ Right-side view when weather protection is closed

Mass

Housing

Housing type

Mass [kg]

Aluminum

housing

Stainless steel

housing

Non-explosionproof, Intrinsically safe housing

Compact type housing 2.8 6.4

Remote type converter housing 2.5 5.9

Remote type probe housing 1.8 3.9

Flameproof housing

Compact type housing 3.2 7.5

Remote type converter housing 2.9 7.1

Remote type probe housing 1.8 3.9

Probe

Probe type Mass *1 [kg/m]

ϕ2 mm single cable probe 0.016

ϕ4 mm single cable probe 0.12

ϕ8 mm single cable probe 0.41

Twin cable probe 0.24

Single rod probe 0.41

Twin rod probe 0.82

Coaxial probe 0.79

*1 Counter weight and flange are not included.

Page 7: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

TOKYO KEISO CO., LTD. 7TG-L1016-0E

MEASUREMENT LIMITS

Single probe

① ②

⑨⑩

⑨⑩

① Single cable probe

② Single rod probe

③ Top dead zone : Top part of the probe where measurement is not possible

④ Top non-linearity zone : Top part of the probe where accuracy is out of guarantee

⑤ Bottom non-linearity zone : Bottom part of the probe where accuracy is out of guarantee

⑥ Bottom dead zone : Bottom part of the probe where measurement is not possible

⑦ Gas phase

⑧ Measuring object

⑨ Probe length

⑩ Tank height

⑪ Minimum distance from the probe to a tank wall : 300 mm

Dead zone and non-linearity zone

Dielectric constant of product (Er) > 40 ≦ 40

Dead zone Top ③ Bottom ⑥ Top ③ Bottom ⑥① ϕ2 mm single cable probe with a

counter weight of ϕ14 mm × 100 mm250 200 350 250

① ϕ4 mm single cable probe with a

counter weight of ϕ20 mm × 100 mm250 200 350 250

① ϕ8 mm single cable probe with a

counter weight of ϕ12 mm × 100 mm250 200 350 250

① ϕ8 mm single cable probe with a

counter weight of ϕ38 mm × 245 mm250 300 350 350

② Single rod probe 250 50 350 170

(mm)Dielectric constant of product (Er) > 40 ≦ 40

Non-linearity zone Top ④ Bottom ⑤ Top ④ Bottom ⑤① ϕ2 mm single cable probe with a

counter weight of ϕ14 mm × 100 mm50 50 50 50

① ϕ4 mm single cable probe with a

counter weight of ϕ20 mm × 100 mm50 50 50 70

① ϕ8 mm single cable probe with a

counter weight of ϕ12 mm × 100 mm50 50 50 50

① ϕ8 mm single cable probe with a

counter weight of ϕ38 mm × 245 mm50 50 50 100

② Single rod probe 50 50 50 50

(mm)

Page 8: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

8 TOKYO KEISO CO., LTD. TG-L1016-0E

Twin probe

① ②

⑨⑩

⑨⑩

① Twin cable probe

② Twin rod probe

③ Top dead zone : Top part of the probe where measurement is not possible

④ Top non-linearity zone : Top part of the probe where accuracy is out of guarantee

⑤ Bottom non-linearity zone : Bottom part of the probe where accuracy is out of guarantee

⑥ Bottom dead zone : Bottom part of the probe where measurement is not possible

⑦ Gas phase

⑧ Measuring object

⑨ Probe length

⑩ Tank height

⑪ Minimum distance from the probe to a tank wall : 100 mm

Dead zone and non-linearity zone

Dielectric constant of product (Er) > 40 ≦ 40

Dead zone Top ③ Bottom ⑥ Top ③ Bottom ⑥① Twin cable probe with a counter weight

of ϕ38 mm × 60 mm200 80 300 200

② Twin rod probe 200 20 300 200

(mm)Dielectric constant of product (Er) > 40 ≦ 40

Non-linearity zone Top ④ Bottom ⑤ Top ④ Bottom ⑤① Twin cable probe with a counter weight

of ϕ38 mm × 60 mm100 50 50 70

② Twin rod probe 100 50 50 70

(mm)

Page 9: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

TOKYO KEISO CO., LTD. 9TG-L1016-0E

Coaxial probe

⑧⑨

① Coaxial cable ② Top dead zone : Top part of the probe where measurement is not possible

③ Top non-linearity zone : Top part of the probe where accuracy is out of guarantee

④ Bottom non-linearity zone : Bottom part of the probe where accuracy is out of guarantee

⑤ Bottom dead zone : Bottom part of the probe where measurement is not possible

⑥ Gas phase

⑦ Measuring object

⑧ Probe length

⑨ Tank height

⑩ Minimum distance from the probe to a tank wall : 0 mm

Dead zone and non-linearity zone

Dielectric constant of product (Er) > 40 ≦ 40

Dead zone Top ② Bottom ⑤ Top ② Bottom ⑤① Coaxial cable 150 20 200 20

(mm)Dielectric constant of product (Er) > 40 ≦ 40

Non-linearity zone Top ③ Bottom ④ Top ③ Bottom ④① Coaxial cable 0 50 0 150

(mm)

Page 10: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

10 TOKYO KEISO CO., LTD. TG-L1016-0E

WIRING

Terminals

Compact type converter housing

① Grounding terminal inside housing (used for shield cable of signal)

② Signal (Power) cable ( - )③ Signal (Power) cable ( + )④ Grounding terminal outside housing on the lower end of converter

Remote converter housing

① Grounding terminal inside housing (used for shield cable of signal)

② Signal (Power supply) cable ( - )③ Signal (Power supply) cable ( + )④ Grounding terminal on the mounting plate of converter

Wiring connection between converter and probe

① Remote type converter housing

② Remote type probe housing

③ Power supply cable ( - )④ Power supply cable ( + )⑤ Digital communication cable (B)⑥ Digital communication cable (A)⑦ Shield wire connected to the terminals of converter housing and probe housing

Page 11: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

TOKYO KEISO CO., LTD. 11TG-L1016-0E

Wiring

① Power source

② Resistance for HART communication

③ Grounding

④ 2-wire loop powered for supplying 24 V DC and outputting 4 to 20 mA

⑤ Terminals at level meter

● The stranded cable with 0.5 to 2.5 mm2 is recommended for signal cable.

● Strip the sheath of cable 5 to 7 mm in length and insert the conductor directly to terminals.

● Lay the signal cable apart from power lines.

● Use a separate power source from other power equipment.

● Use a shield cable preferably.

● Ground the level meter and tank or silo when measuring powders or granules.

Power supply

Following graph shows the minimum supply voltage when a load

resistance is included in the loop.

For non-explosionproof and intrinsically safe level meter

Supply voltage : 11.5 to 30 V DC

*Supply voltage (V)

Load resistance (Ω)

For flameproof level meter

Supply voltage : 13.5 to 36 VDC

*Supply voltage (V)

Load resistance (Ω)

* Minimum supply voltage for an output of 22 mA

Page 12: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

12 TOKYO KEISO CO., LTD. TG-L1016-0E

EXPLOSIONPROOF SPECIFICATIONS

ATEX explosionproof [ATEX Directive 94/9/EC]

DEKRA 13 ATEX 0200X Equipment and protective systems intended for use in potentially explosive atmospheres - Directive 94/9/ECEC-Type Examination Certifi cate Number: DEKRA 13ATEX0200 X

Marking codes

Compact version

II 1/2 G or II 2G Ex ia IIC T6...T2 Ga/Gb or Ex ia IIC T6...T2 Gb

II 1/2 D or II 2D Ex ia IIIC T90°C Da/Db or Ex ia IIIC T90°C Db

or

II 1/2 G or II 2G Ex d ia IIC T6...T2 Ga/Gb or Ex d ia IIC T6...T2 Gb

II 1/2 D or II 2D Ex ia tb IIIC T90°C Da/Db or Ex ia tb IIIC T90°C Db

Remote version transmitter

II 2G Ex ia [ia Ga] IIC T6...T4 Gb

II 2D Ex ia [ia Da] IIIC T90°C Db

or

II 2G Ex d ia [ia Ga] IIC T6...T4 Gb

II 2D Ex ia tb [ia Da] IIIC T90°C Db

Remote version sensor

II 1/2 G or II 2 G Ex ia IIC T6...T2 Ga/Gb or Ex ia IIC T6...T2 Gb

II 1/2 D or II 2 D Ex ia IIIC T90°C Da/Db or Ex ia IIIC T90°C Db

Compact version of the TGF2200

Equip-

ment

category

Max. ambient temperature

Max.

flange

temp.

Temp.

class2 mm

probe

2 mm

probe

and HT

extension

All other

probes

II1/2 G

52°C 54°C 53°C 60°C T6

70°C 70°C 70°C 60°C T5

80°C 80°C 80°C 60°C T4

II 2 G

52°C 54°C 53°C 60°CT6

42°C 51°C 45°C 85°C

67°C 69°C 68°C 75°CT5

57°C 66°C 60°C 100°C

77°C 79°C 78°C 85°C

T467°C 76°C 70°C 110°C

57°C 73°C 62°C 135°C

51°C 71°C 57°C 1) 150°C

T3Not allowed 68°C Not allowed 180°C 2)

Not allowed 65°C Not allowed 200°C 2)

Not allowed 60°C Not allowed 250°C 2)

T2Not allowed 54°C Not allowed 300°C 2)

Equip-

ment

category

Min. ambient temperature

Min.

flange

temp.

Temp.

class2 mm

probe

2 mm

probe

and HT

extension

All other

probes

II 1/2 G −40°C −40°C −40°C −20°C T6-T2

II 2G−40°C −40°C −40°C −40°C 2)

T6-T2−36°C −39°C −37°C −50°C 2)

1) Not allowed for the TGR2000 probes without extension.2) Permitted gasket temperature ranges must be observed.

Remote version of the TGF2200

Equip-

ment

category

Max. ambient temperature

Max.

flange

temp.

Temp.

class2 mm

probe

2 mm

probe

and HT

extension

All other

probes

II 1/2 G

49°C 51°C 49°C 60°C T6

70°C 70°C 70°C 60°C T5

80°C 80°C 80°C 60°C T4

II 2 G

49°C 51°C 49°C 60°CT6

39°C 48°C 43°C 85°C

64°C 66°C 64°C 75°CT5

54°C 65°C 58°C 100°C

77°C 79°C 78°C 85°C

T464°C 75°C 68°C 110°C

51°C 71°C 59°C 135°C

43°C 69°C 54°C 1) 150°C

T3Not allowed 65°C Not allowed 180°C 2)

Not allowed 62°C Not allowed 200°C 2)

Not allowed 54°C Not allowed 250°C 2)

T2Not allowed 47°C Not allowed 300°C 2)

Equip-

ment

category

Min. ambient temperature

Min.

flange

temp.

Temp.

class2 mm

probe

2 mm

probe

and HT

extension

All other

probes

II 1/2 G −40°C −40°C −40°C −20°C T6-T2

II 2G−40°C −40°C −40°C −40°C 2)

T6-T2−35°C −39°C −36°C −50°C 2)

1) Not allowed for the TGR2000 probes without extension.2) Permitted gasket temperature ranges must be observed.

Electrical data

Apparatus in type of protection intrinsic safety “ia” with 4-20

mA-HART output

Supply and output circuit (terminals output 1, + and -):

In type of protection intrinsic safety Ex ia IIC and Ex ia IIIC, only for

connection to a certified intrinsically safe circuit, with the following

maximum values:

Ui = 30 V; li = 300 mA; Pi = 1 W; Ci = 30 nF; Li = 30 μH.

Apparatus with terminal compartment in type of protection

flameproof enclosures “d” and dust ignition protection by

enclosure “t” with 4-20 mA-HART output

Power supply ......................... max. 36 Vdc

Output ................................... 4 - 20 mA

Intrinsically safe circuits ........ Um = 250 V

● When using TGF2200 at the hazardous area as intrinsically safe

instrument, the intrinsically safe barrier shall be used.

● The items as mentioned in “EXPLOSIONPROOF SPECIFICA-

TIONS” shall be observed when used as explosionproof equip-

ment.

● When using an isolation barrier, check the supply voltage of the

barrier.

Page 13: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

TOKYO KEISO CO., LTD. 13TG-L1016-0E

IEC Explosionproof

IECEx DEK 13.0078X

Compact version

Ex ia IIC T6 ...T2 Ga/Gb or Ex ia IIC T6... T2 Gb or Ex ic IIC T6...T2 Gc

Ex ia IIIC T90°C Da/Db or Ex ia IIIC T90°C Db or Ex ic IIIC T90°C Dc

or

Ex d ia IIC T6 ...T2 Ga/Gb or Ex d ia IIC T6... T2 Gb

Ex ia tb IIIC T90°C Da/Db or Ex ia tb IIIC T90°C Db

Remote version transmitter

Ex ia [ia Ga] IIC T6...T4 Gb or Ex ic [ic] IIC T6 ...T4 Gc

Ex ia [ia Da] IIIC T90°C Db or Ex ic [ic] IIIC T90°C Dc

or

Ex d ia [ia Ga] IIC T6...T4 Gb

Ex ia tb [ia Da] IIIC T90°C Db

Remote version sensor

Ex ia IIC T6 ...T2 Ga/Gb or Ex ia IIC T6... T2 Gb or Ex ic IIC T6...T2 Gc

Ex ia IIIC T90°C Da/Db or Ex ia IIIC T90°C Db or Ex ic IIIC T90°C Dc

Compact version of the TGF2200

Equip-

ment

Protection

Level

Max. ambient temperature

Max.

flange

temp.

Temp.

class2 mm

probe

2 mm

probe

and HT

extension

All other

probes

Ga/Gb

52°C 54°C 53°C 60°C T6

70°C 70°C 70°C 60°C T5

80°C 80°C 80°C 60°C T4

Gb

and

Gc

52°C 54°C 53°C 60°CT6

42°C 51°C 45°C 85°C

67°C 69°C 68°C 75°CT5

57°C 66°C 60°C 100°C

77°C 79°C 78°C 85°C

T467°C 76°C 70°C 110°C

57°C 73°C 62°C 135°C

51°C 71°C 57°C 1) 150°C

T3Not allowed 68°C Not allowed 180°C 2)

Not allowed 65°C Not allowed 200°C 2)

Not allowed 60°C Not allowed 250°C 2)

T2Not allowed 54°C Not allowed 300°C 2)

Equip-

ment

Protection

Level

Min. ambient temperature

Min.

flange

temp.

Temp.

class2 mm

probe

2 mm

probe

and HT

extension

All other

probes

Ga/Gb −40°C −40°C −40°C −20°C T6-T2

Gb and Gc

−40°C −40°C −40°C −40°C 2)

T6-T2−36°C −39°C −37°C −50°C 2)

1) Not allowed for the TGR2000 probes without extension.2) Permitted gasket temperature ranges must be observed.

Remote version of the TGF2200

Equip-

ment

Protection

Level

Max. ambient temperature

Max.

flange

temp.

Temp.

class2 mm

probe

2 mm

probe

and HT

extension

All other

probes

Ga/Gb

49°C 51°C 49°C 60°C T6

70°C 70°C 70°C 60°C T5

80°C 80°C 80°C 60°C T4

Gb

and

Gc

49°C 51°C 49°C 60°CT6

39°C 48°C 43°C 85°C

64°C 66°C 64°C 75°CT5

54°C 65°C 58°C 100°C

77°C 79°C 78°C 85°C

T464°C 75°C 68°C 110°C

51°C 71°C 59°C 135°C

43°C 69°C 54°C 1) 150°C

T3Not allowed 65°C Not allowed 180°C 2)

Not allowed 62°C Not allowed 200°C 2)

Not allowed 54°C Not allowed 250°C 2)

T2Not allowed 47°C Not allowed 300°C 2)

Equip-

ment

Protection

Level

Min. ambient temperature

Min.

flange

temp.

Temp.

class2 mm

probe

2 mm

probe

and HT

extension

All other

probes

Ga/Gb −40°C −40°C −40°C −20°C T6-T2

Gb and Gc

−40°C −40°C −40°C −40°C 2)

T6-T2−35°C −39°C −36°C −50°C 2)

1) Not allowed for the TGR2000 probes without extension.2) Permitted gasket temperature ranges must be observed.

Electrical data

Apparatus in type of protection intrinsic safety “ia” with 4-20

mA-HART output

Supply and output circuit (terminals output 1, + and -):

In type of protection intrinsic safety Ex ia IIC and Ex ia IIIC, only for

connection to a certified intrinsically safe circuit, with the following

maximum values:

Ui = 30 V; li = 300 mA; Pi = 1 W; Ci = 30 nF; Li = 30 μH.

Apparatus with terminal compartment in type of protection

flameproof enclosures “d” and dust ignition protection by

enclosure “t” with 4-20 mA-HART output

Power supply ......................... max. 36 Vdc

Output ................................... 4 - 20 mA

Intrinsically safe circuits ........ Um = 250 V

● When using TGF2200 at the hazardous area as intrinsically safe

instrument, the intrinsically safe barrier shall be used.

● The items as mentioned in “EXPLOSIONPROOF SPECIFICA-

TIONS” shall be observed when used as explosionproof equip-

ment.

● When using an isolation barrier, check the supply voltage of the

barrier.

Page 14: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

14 TOKYO KEISO CO., LTD. TG-L1016-0E

① Install the level meter in order to avoid touching the probe with fluid.

② Touching the probe with fluid by incorrect installation causes incorrect measurement.

③ Take a necessary measure by changing direction of inflow from product inlet nozzle, when the probe touches with fluid.

PRECAUTIONS FOR INSTALLING AND USING TGF2200

Observe followings when installing and using TGF2200.

● Install the level meter in the ambient temperature -40 to +80°C around housing.

● Provide a weather protection or the likes to avoid the direct sunshine and rain splash if the level meter is exposed to them.

● Do not install the level meter in the place where a strong vibration is expected.

● Decide the installation location and height considering the dead zone (non-measurable zone) of the TGF2200. The dead zone varies with

the probe to be used and operating conditions. See the section “MEASUREMENT LIMITS.”

● When installing two or more TGF2200s on the same tank, place them at least apart 1 m.

● ln order to prevent the cable from slackening when using the cable probe, set the counter weight afloat above tank base. 0r fix the counter

weight with a tension in the cable.

● Consider the shape and location of the nozzle so that the probe does not touch the nozzle or tank wall.

● Avoid the ingress of foreign materials and coagulation of liquids inside the coaxial probe.

● Fasten the end of the probe to prevent it from vibration for the services where sloshing of liquid is expected in the tank.

● Install the probe apart from agitator or fix the probe at its end to avoid entanglement.

● You can fasten the probe at the end of it, if required so, but not at other positions except coaxial probe. Fixing the probe at the intermediate

position using a supporting lug or other structure is allowed. However, the upper end of supporting structure to fix the probe becomes the

end of probe under which non-measurable zone starts.

● When fixing coaxial probe, do not add an excessive force on it to avoid bending.

● Design the nozzle or installation location to keep a distance to avoid touching the probe with fluid from product inlet nozzle. Touching the

probe with fluid causes a malfunction of the level meter. When the location of level meter cannot be changed, take a necessary measure

such as changing direction of inflow from product inlet nozzle.

Page 15: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

TOKYO KEISO CO., LTD. 15TG-L1016-0E

Install the level meter preferably directly on the roof of the tank without a nozzle.

Avoid adherence of sticky liquids inside installation nozzle.

① When measuring sticky liquids, avoid the accumulation of the remnants inside installation nozzle.

② Installing the level meter directly on the flange without a nozzle on the roof of the tank is recommended for flange connection

type.

③ Installing the level meter directly on the thread (socket) on the roof of the tank is recommended for thread connection type.

When installing the level meter on the nozzle, do not make it too longer nor protrude it into the inside of tank.

① When installing TGF2200 on the nozzle, make the nozzle length shorter than 150 mm.

The diameter of nozzle must be larger than or at least same as the height of nozzle: Nozzle diameter (d) ≧ nozzle height (h).

lf this condition is not satisfied, the minimum required length of the dead zone starts from the bottom end of the nozzle. It

makes the dead zone longer or may cause a malfunction.

② Do not protrude the end of nozzle into the inside of tank.

Install TGF2200 preferably on the threaded connection (socket)

① Typical installation on threaded connection (socket)

② Do not protrude the end of threaded connection (socket) into the inside of tank.

Page 16: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

16 TOKYO KEISO CO., LTD. TG-L1016-0E

Installing twin cable probe or twin rod probe

When installing twin cable probe, the diameter of nozzle must be larger than or at least 50 mm: Nozzle diameter (d) ≧ 50 mm. Make

the nozzle length (h) shorter as much as possible.

Installing coaxial probe

The nozzle diameter and length has no effect on the measuring performance.

Installing probes on concrete roof

① When installing probes on the concrete roof, the diameter of hole (d) must be larger than thickness of concrete (t) (+ installation nozzle). The

surface of hole must be smooth.

② When the thickness of concrete (t) is larger than the diameter of hole (d), make the hole larger and install the probe on the pedestal made of

metal, not installing it on the concrete.

① The diameter of hole (d) must be larger than thickness of concrete (t). The diameter (d) ≧ thickness of concrete (t).

② When the thickness of concrete (t) is larger than the diameter of hole (d), make the hole larger.

Page 17: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

TOKYO KEISO CO., LTD. 17TG-L1016-0E

Installing probes on a non-metallic tank

Observe followings when installing single rod probe or single cable probe with thread connection.

● Insert a metallic sheet between the level meter and its connection seat on the tank.

● The diameter of metallic sheet is 200 mm or larger.

● Make sure that the connection thread on the level meter is screwed into the end of thread through the sheet.

● Use a flange of 200 mm or larger in diameter instead of connection thread if the metallic sheet is not available.

If you have a device with twin rod probe, twin cable probe or coaxial probe, you can ignore these instructions.

① Non-metallic tank or sump tank

② Metal sheet with 200 mm or larger in diameter

Precautions for installing probes for measuring liquids

Do not install TGF2200 near internal obstacles. Keep a distance from the probe to any obstacles. When installing the probe in a standpipe or

stilling well, do not make the probe contact with inside the pipe.

① Keep a distance from the probe to any obstacles to prevent micro-pulses near probe from being influenced by them. The range

in which the micro-pulses are influenced varies with the type of probe. See table below.

② Provide a standpipe or stilling well either internally or externally to measure the level inside the pipe to avoid obstacles in the

vessel.

③ Keep the probe straight inside the standpipe. Do not make the probe contact with inside wall of the pipe. Do not make it

slack. The contact or slack causes a failure in measurement. Shorten the probe in such cases.

④ The necessary space between the probes and obstacles varies with type of probes. See table below.

Type of probe Necessary space around probe

Coaxial probe 0.0m

Twin rod probe, Twin cable probe Min. 0.1 m

Single rod probe, Single cable probe Min. 0.3 m

Page 18: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

18 TOKYO KEISO CO., LTD. TG-L1016-0E

Measuring liquids inside pipes

Using a stilling well (internal chamber) and bypass chamber (external chamber) is recommended. Use a standpipe if the level meter is installed

near the tank wall, internal obstacles, agitators or product inlet. Using a standpipe by installing the probe in stilling well (internal chamber) or

bypass chamber (external chamber) reduces the influences from sloshing, foams or bubbles of liquids.

① Stilling well (internal chamber)

② Bypass chamber (external chamber)

③ Vent hole

④ Max. liquid level

Requirements for the stilling well or bypass chamber

● The internal and external pipes must be metallic or electrically-conductive. If the pipe is not made of metal, provide a pipe

with enough size to secure necessary space for the probe.

● The pipe must be straight. The inside surface must be smooth with its roughness less than 0.1 mm.

● The accuracy of inside diameter must be less than ± 1 mm

● The Internal stilling well must have a vent hole at the higher point than the Max. liquid level.

● The Internal stilling well must have enough gaps between the counter weight and the inside of the pipe to make the liquids

go through easily.

● Install the pipes vertically.

Precautions for using the stilling well or bypass chamber

● Place the probe in the center of the internal stilling well.

● The span of the bypass chamber must cover the Max. and Min. liquid levels: One nozzle must be higher than the Max. level

and another lower than the Min. level.

● The liquids and gases must move smoothly inside the pipes.

● The corrosion or adherence by fluids inside pipe is not allowed.

● Do not let any foreign objects into the pipe.

● The lower zone than bottom of internal stilling well cannot be measured.

Page 19: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

TOKYO KEISO CO., LTD. 19TG-L1016-0E

Precautions for measuring powders

● Install the probe used for the powders while the tank or silo is empty. Install the level meter without any slack of cable probe.

● Use the probe with the end of probe unfixed when measuring powders.

● Design the shape of nozzle, threaded connection (socket) and their location so that the probe does not touch inside surface

of tank, nozzle or socket.

● Install the probe apart more than 300 mm from the tank or silo wall.

● Install the probe so that its counter weight is located more than 300 mm above the bottom of tank or silo.

● Do not adhere anything on the threaded connection (nozzle) or inside of nozzle when the product is adherent.

● Install the probe as far as possible from the internal obstacles to prevent the probe from being entangled with them even

when the probe moves back and forth.

● Use single cable probe for the measurement of powders. Use the probe with the end of probe unfixed. Make it free to move.

a>300mmd>300mm

● Do not install the probe near a product inlet. Avoid the probe from touching with infl ow of products.

Start-up

● The start-up indication will appear in 5 seconds after power-on.

● The indication appears in 30 seconds later. Further 10 seconds later the correct measurement starts. The necessary time to get the

correct measurement depends on the measuring conditions.

● The current output becomes approximately 2.8 mA just after power-on. About 10 seconds later 3.6 mA is given and 30 seconds later,

the correct output is given.

● The necessary time to get the correct output depends on the measuring conditions.

Page 20: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

20 TOKYO KEISO CO., LTD. TG-L1016-0E

PROBE SELECTION GUIDE

Model TGF2211 TGF2212 TGF2231 TGF2222 TGF2221

Probe typeSingle rod

probeTwin rod probe Coaxial probe

Twin cable

probe

Single cable probe

ϕ2 mm ϕ4 mm ϕ8 mm

Probe length

3 m

6 m

(Segmented type)

3 m

3 m

6 m

(Segmented type)

28 m 40 m 40 m 40 m

Measuring objects

Dielectric constant >1.8 >1.6 >1.4 >1.6 >1.8 >1.8 >1.8

Viscosity<10,000mPa.s

*1

<1,500mPa.s

*1

<500 mPa.s

*1

<10,000mPa.s

*1

<10,000mPa.s

*1

<10,000mPa.s

*1―

Crystallizing liquids ○ × × × ○ ○ ―Powders ― ― ― ― ― ― ○Granules less than 5

mm in diameter― ― ― ― ― ― ○

Installation method and applications

Storage tank ○ ○ ○ ○ ○ ○ ×Open sump tank ○ ○ ○ ○ ○ ○ ×Bypass chamber ○ △ ○ △ ○ ○ ×Stilling well ○ △ ○ △ ○ ○ ×

Tank with agitator △ ○ ○ △Fix end of probe

△Fix end of probe

△Fix end of probe

×

Small size nozzle

Long nozzle△ ○ ○ ○ △ △ ×

Silo × × × × ― △ ○Process connection

G 1/2” 1/2 NPT × × × × ○ × ×G 3/4”3/4 NPT ○ × ○ × ○ ○ ×G 1, 1 NPT ○ × ○ × ○ ○ ×G 1-1/2”1-1/2 NPT ○ ○ ○ ○ ○ ○ ○40 A JIS 10K ○ ○ ○ ○ ○ ○ ×50 A JIS 10K ○ ○ ○ ○ ○ ○ ×80 A JIS 10K ○ ○ ○ ○ ○ ○ ○100 A JIS 10K ○ ○ ○ ○ ○ ○ ○150 A JIS 10K ○ ○ ○ ○ ○ ○ ○200 A JIS 10K ○ ○ ○ ○ ○ ○ ○ASME 1” ○ × × × ○ ○ ×ASME 1 – 1/2 “ ○ ○ ○ ○ ○ ○ ×ASME 2” ○ ○ ○ ○ ○ ○ ×ASME 3” ○ ○ ○ ○ ○ ○ ○ASME 4” ○ ○ ○ ○ ○ ○ ○ASME 6” ○ ○ ○ ○ ○ ○ ○ASME 8” ○ ○ ○ ○ ○ ○ ○ ○:Most suitable △:Suitable ×:Not suitable -:Not applicable

* 1 A general guidance to select the probe

Page 21: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

TOKYO KEISO CO., LTD. 21TG-L1016-0E

MODEL AND SPECIFICATION CODES

TGF2200 standard specifications for liquids

Spec. code VF20 4 ※※※ 1 4 0 0 0 0 0 Contents

Converter housing/housing material

1 Compact type/Aluminum

2 Compact type/Stainless steel

3 Remote type/Converter and probe housing : Aluminum

4 Remote type/Converter and probe housing : Stainless steel

Approval

0 Non-explosionproof

1 ATEX Ex ia IIC T2...T6 Intrinsically safe

2 ATEX Ex d ia IIC T2..T6 Flameproof

6 IECEx Ex ia IIC T2...T6 Intrinsically safe

7 IECEx Ex d ia IIC T2...T6 Flameproof

Other approval0 Without

1 SIL2 only compact type

Sealing (material/temperature /pressure)

1 FKM/FPM / ー40 to +150°C / 0 kPa (abs) to 4 MPa

2 Kalrez® 6375 / ー20 to +150°C / 0 kPa (abs) to 4 MPa

3 EPDM / ー50 to +150°C / 0 kPa (abs) to 4 MPa

Probe (type/material/length)

1 Single rod probe ϕ8 mm / Stainless steel SS316 L(1.4404) / 1 to 3 m

2 Single rod probe ϕ8 mm segmented type / Stainless steel SS316 L(1.4404) / 1 to 6 m

4 Single cable probe ϕ4 mm / Stainless steel SS316(1.4401) / 1 to 40 m

6 Twin rod probe 2 × ϕ8 mm / Stainless steel SS316 L(1.4404) / 1 to 3 m

7 Twin cable probe 2 × ϕ4 mm / Stainless steel SS316(1.4401) / 1 to 28 m

A Coaxial probe ϕ22 mm / Stainless steel SS316 L(1.4404) / 0.6 to 3 m

B Coaxial probe ϕ22 mm segmented type / Stainless steel SS316 L(1.4404) / 0.6 to 6 m

E Coaxial probe ϕ22 mm / Hastelloy® C22 / 0.6 to 3 m

P Single rod probe ϕ8 mm with / PVDF sheath of ϕ16 mm IIB only / 1 to 3 m

Probe (end type/material/applica-ble probe)

0 Without

2 Counter weight ϕ20 × 100 mm / Stainless steel SS316 L(1.4404)/ ϕ4 mm Single cable probe

5 Counter weight ϕ38 × 60 mm / Stainless steel SS316 L(1.4404)/ ϕ4 mm Twin cable probes

Process connection ※※※ Select one from process connection table.

Output 1 4 to 20 mA in two wire system, passive (HART)

Cable entries/cable gland

1M20 × 1.5 / without cable gland. For flameproof type the flameproof cable glands are available as an optional attachment if required.

2 M20 × 1.5 / with cable glands made of plastics.

3 M20 × 1.5 / with cable glands made of metal

A 1/2 NPT / without cable gland

Housing (orientation/display/weather protection)

1 Horizontal / Without / Without for compact type only

2 Horizontal / Display on side / Without for compact type only

3 Horizontal / Without / With weather protection for compact type only

4 Horizontal / Display on side / With weather protection for compact type only

A Vertical / Without / Without

B Vertical / Display on top / Without

C Vertical / Display on side / Without not for flameproof

D Vertical / Without / With weather protection

E Vertical / Display on top / With weather protection

F Vertical / Display on side / With weather protection not for flameproof

Display language

0 Without display

1 English

7 Japanese

Fixed code 4 0 Always 40

Cable length of remote type

0 Without

6 10 m

7 25 m

8 50 m

A 75 m

B 100 m

Fixed code 0 0 0 0 Always 0000

Probe length / Specify the length in the unit of cm *1

Special featureblank Without

/Z Included *2

*1 Specify the length of probe in integer of 4 digits in the unit of cm. For example: Specify as “0258” cm for the length of 2580 mm and “1258” cm for 12.58 m. The smaller length than 1 cm is not allowed. Consult us for the availability before ordering if the length of the rod or coaxial probe except the segmented types is longer than 3 m. *2 Add code “/Z” to a series of above mentioned codes with explanation for the other requirements not mentioned in above code table.

Page 22: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

22 TOKYO KEISO CO., LTD. TG-L1016-0E

TGF2200 specifications for powders and granules

Spec. code VF20 4 ※※※ 1 4 0 0 0 0 0 Contents

Converter housing/housing material

1 Compact type/Aluminum

2 Compact type/Stainless steel

3 Remote type/Converter and probe housing : Aluminum

4 Remote type/Converter and probe housing : Stainless steel

Approval

0 Non-explosionproof

1 ATEX Ex ia IIC T2...T6 Intrinsically safe

2 ATEX Ex d ia IIC T2..T6 Flameproof

6 IECEx Ex ia IIC T2...T6 Intrinsically safe

7 IECEx Ex d ia IIC T2...T6 Flameproof

Other approval0 Without

1 SIL2 only compact type

Sealing (material/tempera-ture/pressure)

1 FKM/FPM / ー40 to +150°C /0kPa(abs) to 4MPa

2 Kalrez® 6375 / ー20 to +150°C /0kPa(abs) to 4MPa

3 EPDM / ー50 to +150°C /0kPa(abs) to 4MPa

Probe (type/material/length) 5 Single rod probe ϕ8 mm / Stainless steel SS316(1.4401) / 1 to 40 m

Probe (end type/material/applica-ble probe)

3 Counter weight ϕ12 × 100 mm / Stainless steel SS316 L(1.4404) / ϕ8 mm Single cable probe

4 Counter weight ϕ38 × 245 mm / Stainless steel SS316 L(1.4404)/ ϕ8 mm Single cable probe

Process connection ※※※ Select one from process connection table.

Output 1 4 to 20 mA in two wire system, passive (HART)

Cable entries/cable gland

1M20 × 1.5 / without cable gland. For flameproof type the flameproof cable glands are available as an optional attachment if required.

2 M20 × 1.5 / with cable glands made of plastics.

3 M20 × 1.5 / with cable glands made of metal

A 1/2 NPT / without cable gland

Housing (orientation/display/weather protection)

1 Horizontal /Without /Without for compact type only

2 Horizontal /Display on side /Without for compact type only

3 Horizontal /Without /With weather protection for compact type only

4 Horizontal /Display on side /With weather protection for compact type only

A Vertical /Without /Without

B Vertical /Display on top /Without

C Vertical /Display on side /Without not for flameproof

D Vertical /Without /With weather protection

E Vertical /Display on top /With weather protection

F Vertical /Display on side /With weather protection not for flameproof

Display language

0 Without display

1 English

7 Japanese

Fixed code 4 0 Always 40

Cable length of remote type

0 Without

6 10 m

7 25 m

8 50 m

A 75 m

B 100 m

Fixed code 0 0 0 0 Always 0000

Probe length / Specify the length in the unit of cm *1

Special featureblank Without

/Z Included *2

*1 Specify the length of probe in integer of 4 digits in the unit of cm. For example: Specify as “0258” cm for the length of 2580 mm and “1258” cm for 12.58 m. The smaller length than 1 cm is not allowed. Consult us for the availability before ordering if the length of the rod or coaxial probe except the segmented types is longer than 3 m. *2 Add code “/Z” to a series of above mentioned codes with explanation for the other requirements not mentioned in above code table.

Page 23: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

Micro pulse level meter with 2-wire system TGF2200

TOKYO KEISO CO., LTD. 23TG-L1016-0E

TGF2200 specifications for high temperature liquids

Spec. code VF20 4 ※※※ 1 4 0 0 0 0 0 Contents

Converter housing/housing material

1 Compact type/Aluminum

2 Compact type/Stainless steel

3 Remote type/Converter and probe housing : Aluminum

4 Remote type/Converter and probe housing : Stainless steel

Approval

0 Non-explosionproof

1 ATEX Ex ia IIC T2...T6 Intrinsically safe

2 ATEX Ex d ia IIC T2..T6 Flameproof

6 IECEx Ex ia IIC T2...T6 Intrinsically safe

7 IECEx Ex d ia IIC T2...T6 Flameproof

Other approval0 Without

1 SIL2 only compact type

Sealing (material/tempera-ture/pressure)

6 FKM/FPM / ー40 to +300°C /0 kPa (abs) to 4 MPa / for ϕ2mm single cable probe with high temperature extension

7 Kalrez® 6375 / ー20 to +300°C /0 kPa (abs) to 4 MPa / for ϕ2mm single cable probe with high temperature extension

8 EPDM / ー50 to +250°C /0 kPa (abs) to 4 MPa / for ϕ2mm single cable probe with high temperature extension

Probe (type/material/length)3 Single cable probe ϕ2 mm / Stainless steel SS316 (1.4401) / 1 to 40 m

D Single cable probe ϕ2 mm / Hastelloy® C22 / 1 to 40 m

Probe (end type/material/applica-ble probe)

1 Counter weight ϕ14 × 100 mm / Stainless steel SS316 L (1.4404) / ϕ2 mm Single cable probe

F Counter weight ϕ14 × 100 mm / Hastelloy® C22 / ϕ2 mm Single cable probe

Process connection ※※※ Select one from process connection table.

Output 1 4 to 20 mA in two wire system, passive (HART)

Cable entries/cable gland

1M20 × 1.5 / without cable gland. For flameproof type the flameproof cable glands are available as an optional attachment if required.

2 M20 x 1.5 / with cable glands made of plastics.

3 M20 x 1.5 / with cable glands made of metal

A 1/2 NPT / without cable gland

Housing (orientation/display/weather protection)

1 Horizontal /Without /Without for compact type only

2 Horizontal /Display on side /Without for compact type only

3 Horizontal /Without /With weather protection for compact type only

4 Horizontal /Display on side /With weather protection for compact type only

A Vertical /Without /Without

B Vertical /Display on top /Without

C Vertical /Display on side /Without not for flameproof

D Vertical /Without /With weather protection

E Vertical /Display on top /With weather protection

F Vertical /Display on side /With weather protection not for flameproof

Display language

0 Without display

1 English

7 Japanese

Fixed code 4 0 Always 40

Cable length of remote type

0 Without

6 10 m

7 25 m

8 50 m

A 75 m

B 100 m

Fixed code 0 0 0 0 Always 0000

Probe length / Specify the length in the unit of cm *1

Special featureblank Without

/Z Included *2

*1 Specify the length of probe in integer of 4 digits in the unit of cm. For example: Specify as “0258” cm for the length of 2580 mm and “1258” cm for 12.58 m. The smaller length than 1 cm is not allowed. Consult us for the availability before ordering if the length of the rod or coaxial probe except the segmented types is longer than 3 m. *2 Add code “/Z” to a series of above mentioned codes with explanation for the other requirements not mentioned in above code table.

Process connection table

Flange connection

JIS Flange

Code Flange rating

G U P 40 A JIS 10K RF

H U P 50 A JIS 10K RF

L U P 80 A JIS 10K RF

M U P 100 A JIS 10K RF

P U P 150 A JIS 10K RF

R U P 200 A JIS 10K RF

Thread connection

Code Thread rating

C P 0 G1/2 A Male (for ϕ2 mm single cable probe)

D P 0 G3/4 A Male (not for twin probe)

E P 0 G1 A Male (not for twin probe)

G P 0 G1 1/2 A Male

C B 0 1/2 NPTF - B1.20.3 (for ϕ2 mm single cable probe)

D A 0 3/4 NPT - B1.20.1 (not for twin probe)

E A 0 1 NPT - B1.20.1 (not for twin probe)

G A 0 1 1/2 NPT - B1.20.1

ASME flange

Code Flange rating

E 1 A 1" 150 lbs RF (not for twin probe)

E 2 A 1" 300 lbs RF (not for twin probe)

G 1 A 1 1/2" 150 lbs RF (not for twin probe)

G 2 A 1 1/2" 300 lbs RF (not for twin probe)

H 1 A 2" 150 lbs RF

H 2 A 2" 300 lbs RF

L 1 A 3" 150 lbs RF

L 2 A 3" 300 lbs RF

M 1 A 4" 150 lbs RF

M 2 A 4" 300 lbs RF

P 1 A 6" 150 lbs RF

P 2 A 6" 300 lbs RF (available for non-explosionproof only)

R 1 A 8" 150 lbs RF

R 2 A 8" 300 lbs RF (available for non-explosionproof only)

Page 24: TGF2200 TG-L1016-0E - TOKYO KEISO · The half of this time is equivalent to the direct distance from ... The traveling speed of the ... Micro pulse level meter with 2-wire system

TG-L1016-0E

Micro pulse level meter with 2-wire system TGF2200

24

Head Office : Shiba Toho Building, 1 – 7 – 24 Shibakoen, Minato-ku, Tokyo 105 – 8558

Tel : +81-3 – 3431 – 1625 (KEY) ; Fax : +81-3 – 3433 – 4922

e-mail : [email protected] ; URL : http://www.tokyokeiso.co.jp

* Specification is subject to change without notice.

ORDERING INFORMATION

Basic information

Purpose :□ to measure a level height   □ to measure a distance Measuring range : m Max. fl uid level : m A distance from the point where the sensor is installed.

Measuring objects

Name of substance : Dielectric constant Er : Property :□ Liquids □ Slurries □ Powders Max. diameter 0.1 mm □ Granules diameter mm Corrosion :□ No □ Medium □ High Viscosity :□ Low □ Medium □ High □ Sticky Crystallizing :□ No □ Medium □ High Sloshing :□ No □ Medium □ High Foaming :□ No □ Medium □ High

Operating conditions

Measuring condition :□ Outdoor □ Indoor Product temperature : ℃ Ambient temperature : ℃ Pressure : Explosionproof :□ Not required      □ Required

Vessel

Shape or location :□ Ground □ Underground □ Closed sump tank □ Open sump tank Height : Diameter or width : Obstacles in vessel :□ No □ Yes: □ Agitator(shape ) □ Temperature sensor  □ Level switch □ Reinforce or stay    □ Ladder    □ Others Materials of vessel :□Metal           Coating :□ Yes □ No  □ Non-metal        

Installation conditions

Location :Distance from tank wall mm Distance from inlet nozzle mm Distance from obstacles mm Nozzle :Diameter mm Length mm

STANDARD ACCESSORIES

● Parameter sheet : 1

● Instruction manual : 1

OPTION

● M20 × G1/2 female adapter :[GA]

● Flameproof cable gland (G1/2) :[DG]

● Individual setting of output range :[DS]

ORDERING INSTRUCTIONS

1. Model and spec. code Example Model :TGF2211 Spec. code :VF204100120HUP12274000000/2. Probe length Specify the length in cm3. 0ption (if required) Specify by the symbol referring to “OPTION”.4. Special request (if required) Please state special requests clearly. Consult Tokyo Keiso or representative before ordering.5. Intrinsically safe A safety barrier is required.