the basics of room air distribution · 2013-05-05 · adpi • adpi is the percentage of points...

40
THE BASICS OF ROOM AIR DISTRIBUTION Dan Int-Hout Chief Engineer / Krueger Richardson Texas 3/22/2011

Upload: others

Post on 18-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

THE BASICS OF ROOM AIR DISTRIBUTION

Dan Int-HoutChief Engineer / Krueger

Richardson Texas

3/22/2011

Page 2: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Why Air Distribution?

What are we trying to accomplish with air distribution system?

• Provide Occupant Thermal Comfort• Provide sufficient ventilation to meet codes• Control Latent loads (Humidity)

Page 3: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

What supplies the air we are Distributing?

• Most systems provide air from overhead and attempt to provide “well mixed”spaces.

• Sources include rooftops, VAV, WSHP, Chilled beams, etc

• Some systems are partially or fully stratified.

• Lets start by understanding basic terminology:

Page 4: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Understanding The Terminology

Primary Air Jets - Air jets from free round openings, grilles, perforated panels, ceiling diffusers and other outlets can be defined by three variables.

• Throw • Drop • Spread

Page 5: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Understanding The Terminology

THROWDROP

Page 6: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Understanding The Terminology

50 fpm

Typical 100 fpm

150 fpm22.5

22.5

Spread - is defined as the divergence of the airstream in a horizontal or vertical plane after it leaves the outlet.

Page 7: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Understanding The Terminology

Coanda Effect

Coanda Effect - a negative or low pressure area is created between the moving air mass and the ceiling at or near the supply air outlet. This low

pressure area causes the moving air mass to cling to and flow close to the ceiling surface and increases the throw.

Page 8: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Understanding The Terminology

Understanding primary air jet variables enables

• Accurate prediction of room air flow

• Improvement of thermal comfort

• Proper selection of grilles, registers and diffusers

• Adherence with ASHRAE Ventilation Std 62.1 is a Leed PREREQUISITE, and is required by many codes.

Page 9: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Understanding The Terminology

The Basis of Catalog Performance Data

• Throw – The horizontal or vertical axial distance an airstream travels after leaving an air outlet, usually assumes a surface adjacent to the air outlet

• Pressure – Can be total pressure or static pressure

• Sound – Can be either NC or Octave Band data

Page 10: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Throw• Throws are cataloged for 150, 100 and 50 fpm terminal velocities.• Throws should be selected so that jets do not collide, but have sufficient projection for the area to be served.

7 – 8 – 12

150fpm100fpm

50fpm

Page 11: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Pressure

Pressure – Air outlet pressure data is required to properly size the air delivery system within a building.

• Static Pressure – The outward force of air within a duct, measured in inches of water column.

• Velocity Pressure – The forward moving force of air within a duct, measured in inches of water column.

• Total Pressure – The sum of the velocity and static pressures, expressed in inches of water column and can be obtained by use of a pitot tube.

PT = PV + PS

PT

PS

PS PT

Page 12: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Sound

Sound levels reported for diffusers are conducted in accordance with ASHRAE Standard 70.

• Catalog sound data assumes 10 diameters of straight duct.

• Room absorption is assumed to be 10dB in all bands.

• In practice however, room sound levels are probably 5 NC higher than reported.

Page 13: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

NonNon--Inductive Air DistributionInductive Air Distribution--Laminar and Radial Flow Laminar and Radial Flow

OutletsOutlets

• Hospital Operating Suites• Hi-Tech Electronics and other industrial

applications• Clean Rooms• Laboratories

Laminar Flow Radial Flow

Page 14: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Pressurized plenum for coreDucted perimeter with fan powered boxes, or other techniques, depending on climate, glass load, etc..

UFAD: Underfloor Air DistributionUFAD: Underfloor Air Distribution

• A raised floor allows electrical and communication circuits to be easily accessed and changed.

• Air may be distributed within this space, without ductwork.

Page 15: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Interior Outlet Selection Interior Outlet Selection ––1/workstation1/workstation

Page 16: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

UFAD Perimeter Outlet SelectionUFAD Perimeter Outlet Selection

• Perimeter solutions vary considerably• Avoid condensing coils under the floor• Hydronic coils often leak• Exhaust at the perimeter to draw heat

away• Best solutions seem to be heat and cool

from overhead

Page 17: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

17

Displacement SystemsDisplacement Systems

To be added

Page 18: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Select based on ”adjacent zone”

Page 19: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

ApplicationsClassrooms KitchenRestaurantAuditoriumsAtriumsGymsAnd more…

Page 20: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Well Mixed-High Induction Diffusers

• Commercial Office Spaces• High Velocity Jets• Long Throw• Designed to Mix in Zone PLQ-R

1400

Prism

Page 21: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Air Distribution, Poor PatternAir Distribution, Poor Pattern

THERMOSTAT

POORLY ADJUSTED / SELECTED DIFFUSER

Page 22: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

PROPERLY ADJUSTED/SELECTED DIFFUSER

THERMOSTAT

Air Distribution, Good PatternAir Distribution, Good Pattern

Page 23: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Thermal ComfortASHRAE Standard 55-2010 mandates a maximum 5.4�F vertical temperature

stratification in Occupied Zone

2’ 2’Floor to Occupants’ Head Level

(3.5 ft. for seated, 6 ft. for standing occupants)

Velocities within the occupied zone shall be ≤ 50 FPM

Velocities within the occupied zone shall be ≤ 50 FPM

Page 24: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Understanding ADPI

Page 25: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

ADPI

• ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3� to +2� of average room temperature at a coincident air velocity less than 70 FPM.

• ADPI is essentially a measure of the degree of mixing in zones served by overhead cooling systems.

• When air distribution is designed with a minimum ADPI of 80% the probability of vertical temperature stratification or horizontal temperature non-uniformity is low and conformance with ASHRAE Standard 55 (Thermal Comfort) requirements is high.

• ADPI does not apply to heating situations or ventilation-related mixing.

Page 26: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

• ADPI selection using T50 / L was developed in the ‘60s where L is the distance to the nearest wall or halfway to the nearest air outlet..

• A relationship was found between 50 FPM/min isothermal throw and cooling throw,

• Using this table engineers can assure clients that diffuser selections will provide acceptable mixing and air change effectiveness.

ASHRAE Fundamentals Chapter 20, Table 3

Page 27: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Perforated 24X24, 10” inlet, 4 way, 20� Delta-T

2

4

6

8

10

12

14

16

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0CFM/Sq.Ft.

1/2

Uni

t Sep

arat

ion

Dis

tanc

e

420350300250160Range

Spacing for 80% ADPI

NC=35

CFM

Page 28: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Prism 24x24

0

4

8

12

16

20

24

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

cfm/SqFt

1/2

Uni

t Sep

arat

ion

Dis

tanc

e, L

600

545

436

273

109

10in. Neck

NC=37

Prism, 24”x24”, 10” inlet, 20�ΔTSpacing for 80% ADPI

Page 29: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Room Air SpeedRoom Air SpeedIssues and FactorsIssues and Factors

• Standard 55 says thermal comfort can be achieved with 0 fpm air motion.

• Uniform air temperatures indicate good mixing when loads are present.

• With conventional (well-mixed) systems, room air speed is driven primarily by room loads when air supply is below 0.9 CFM/sq. ft. and air diffusion is adequate per ASHRAE sponsored research

• Partitions can provide excellent comfort with ceiling diffusers when cooling.

Page 30: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

LEED & ASHRAE Code LEED & ASHRAE Code ComplianceCompliance

• In LEED 2009, in order to get ANY LEED points, one must fully meet the Ventilation Rate Procedure calculation in ASHRAE Standards 62.1 (Ventilation)

• ASHRAE 62.1-2010 VRP requires that if heating air supplied from the ceiling is less than 15� above room temperature but does not reach within 4.5 feet of the floor at 150FPM the outdoor air supply must be increased by 25%.

• ASHRAE 62.1-2010 VRP requires that if the heating air supplied from the ceiling is greater than 15� above room temperature the outdoor air supply must also be increased by 25%.

• LEED 2009 Ventilation points are gained by increased ventilation 30% beyond 62.1 minimums.

Page 31: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Non Typical Throw Analysis

Page 32: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Special Applications High bay application - Ceilings over 12’ high• Heating is a challenge due to buoyancy.

– Take advantage of vertical stratification where possible– Required Heating airflow rate may exceed cooling airflow

rate.– Keep heating supply air temperature to room

temperature ΔT to a minimum• If supplying air distribution from the ceiling, consider using

round diffusers, drum louvers, or diffusers with some vertical projection.

• One cannot use ADPI to predict heating performance.• Consider Displacement Ventilation for cooling applications

Page 33: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Diffuser Selection & Buoyancy

• ADPI isn’t always the best way to analyze, select and place diffusers, especially with heating and high bay applications.

• One can estimate Throw as a function of ΔT and buoyancy.

• Simple rule: Distance to 75ft/min is affected by 1%/degree(F) ΔT.

Example:1. 20�ΔT Cooling, Vertical Down = +20% projection2. 20�ΔT Heating, Vertical Down = -20% projection3. 20�ΔT Heating, Along Ceiling = +20% projection

Page 34: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Side Wall Register Selection & Buoyancy

• Horizontal free jet:• Vertical change @ 75ft/min is affected by

1% of 75fpm throw/F0 ΔT.

T75

Example: 15oF Delta T heating

15% T75

Note: T150 is not affected by Delta-t

Page 35: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Entrained vs. Free Jets

• Most catalog throw data assumes jet is along a surface.

• Exceptions include drum louvers, duct mounted grilles and vertical linear diffusers.

• A free jet will be shorter than an entrained jet because it has more surface area to induce surrounding air, which shortens throw.

Page 36: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Special Applications

Continuous Duct Application Suggestions:

• Use multiple drum louvers, duct mounted grilles and continuous linear applications (longer than 10’).

• Size duct as large a possible (Duct inlet velocity < 1000fpm).

• If inlet velocities are less than 1000fpm, maintain constant duct size through entire length of run and balancing will be minimal.

Page 37: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

ReturnsReturns

• Typically, returns are located in the ceiling in offices.

• Returns have an almost immeasurable effect on room air flows below 1.5 cfm/sf.

• Suspended ceilings typically leak 1cfm/sf at 0.1” differential pressure.

• Spaces with high airflow rates can benefit from low returns.

Page 38: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

Air Distribution SummaryAir Distribution Summary• LEED 2009 requires meeting Standard 62.1 for

project approval-No compliance=No Leed project designation!

• Documented use of ADPI is the ONLY way to assure compliance to ASHRAE Std. 55 in the design phase for cooling.

• Reheat needs to be carefully considered in terms of discharge temperatures and velocities. High heating supply temperatures will void meeting Standard 55 (and loose a potential LEED point).

• Software is available to assist in selecting the best mix of products.

• I’ll discuss “the rules” in the next session!

Page 39: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

ANY QUESTIONS?

Page 40: THE BASICS OF ROOM AIR DISTRIBUTION · 2013-05-05 · ADPI • ADPI is the percentage of points within the occupied zone having a range of effective draft temperatures of -3— to

ContactContact

dintdint--hout@[email protected]

www.kruegerwww.krueger--hvac.comhvac.com

EXCELLENCE IN AIR DISTRIBUTION

KRUEGER

Read my “Air Distribution Blog”