the international authority on air system components fan performance mark stevens director of...

38
The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

Upload: lorraine-phelps

Post on 29-Dec-2015

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Fan Performance

Mark StevensDirector of Laboratory Services

AMCA International

Page 2: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Fan Testing for Air Performance

Page 3: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Test Fan

AMCA Standard 210

Auxiliary Fan

NozzlesFan Airflow

Piezometer Ring Fan Static Pressure

Page 4: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

AMCA 210 Test Results

0

100

200

300

400

500

600

700

800

0 2 4 6 8 10 12

Air Flow, Q

Pre

ssu

re,

P

0

0.5

1

1.5

2

2.5

Po

wer, H

Page 5: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Fan Laws for Speed Change

QC = NC N ( )Q Q, Fan Airflow Rate

2

PC = NC N ( )P P, Fan Pressure

H, Fan PowerHC = NC N ( )H

3

Page 6: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

10% Speed Change

33% More H

0

100

200

300

400

500

600

700

800

0 2 4 6 8 10 12 14

Air Flow, Q

Pre

ss

ure

, P

0

0.5

1

1.5

2

2.5

Po

we

r, H

10% More Q

Page 7: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

AMCA Standards 500-D & -L

Test Damper

Auxiliary Fan

NozzlesDamper Airflow

Piezometer Ring Damper Pressure Drop

Page 8: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Fan Operating Point

Operating Point

0

100

200

300

400

500

600

700

0 2 4 6 8 10 12

Air Flow, Q

Pre

ss

ure

, P

AMCA 500-D Test Results

Page 9: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Speed Change

New Operating Point

New speed

0

100

200

300

400

500

600

700

800

0 2 4 6 8 10 12 14

Air Flow, Q

Pre

ss

ure

, P Operating Point

Page 10: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Damper Opening

New System

New Operating Point

0

100

200

300

400

500

600

700

0 2 4 6 8 10 12

Air Flow, Q

Pre

ssu

re, P

Operating Point

Page 11: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

System Effect

• Installed duct configuration does not match tested duct configuration

• Detrimental effect on fan air performance due to adverse flow conditions at the inlet or outlet of a fan

Page 12: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Test Fan

Installation Type DDucted Inlet / Ducted Outlet

Auxiliary Fan

NozzlesFan Airflow

Piezometer Ring Fan Static Pressure

Installed Fan

PlenumPlenum

Page 13: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

AMCA Catalog Ratings

• “Performance certified is forinstallation type:

◦ A: Free inlet, Free outlet”◦ B: Free inlet, Ducted outlet”◦ C: Ducted inlet, Free outlet”◦ D: Ducted inlet, Ducted outlet”

Page 14: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

System Effect

• Even when the tested duct configuration matches the installed duct configuration, improper duct design can introduce adverse flow conditions

Page 15: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Elbow Example

Page 16: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Detailed Plenum Example

Plenum

Page 17: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Detailed Plenum Example

• Centrifugal Fan

• Airflow Rate◦ 14.4 m3/s

• Blast Area/Outlet Area◦ 0.6

• Velocity◦ 14.4 m/s

Blast Area

Cutoff

Outlet Area

Page 18: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Detailed Plenum Example

E-F duct friction at 5000CMH (Q) 747 Pa (duct design)

E contraction loss-plenum to duct 50 Pa (part of duct system)

E PS energy required to create velocity at E 125 Pa (part of duct system)

D PV loss (also PT loss) at D as result of air velocity decrease 0 Pa

PS does not change from duct to plenum at D

C-D outlet duct on fan as tested 0 Pa

--------------------

REQUIRED Fan PS 922 Pa

Page 19: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Detailed Plenum Example

D-E duct friction at 5000CMH (Q) 747 Pa (duct design)

D contraction loss-plenum to duct 50 Pa (part of duct system)

D PS energy required to create velocity at D 125 Pa (part of duct system)

B-C SEF 149 Pa

B-C PV loss (also PT loss) at C as result of air velocity decrease 0 Pa

PS does not change from duct to plenum at C

------------------

REQUIRED Fan PS 1071 Pa

Page 20: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Detailed Plenum Example

Outlet Duct

100% Effective Duct Length

Calculation of SEF of 149 Pa

From AMCA Publication 210

From Figure 8.3t

Blast Area

NoDuct

12%Effective

Duct

25%Effective

Duct

50%Effective

Duc

100%Effective

Duct

U W --

Sys tem Effe ct C urve

U W --

U- V W- X --

W -X -- --

X -- --

-- -- --

0 .4

O utle t Area

0 .5

0 .6

0 .7

0 .8

0 .9

1 .0 -- -- --

P R -S

P R -S

R -S S-T

S U

T-U VW

W -W W -X

-- --

Page 21: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

14.4 m/s

Using line R from Figure 7.1

Page 22: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Plenum Example from AMCA 201

Assuming:• Use of the same fan for both systems• Can attain both operating points with a

change in speed• The increased in power consumption to

overcome System Effect is about 25%◦ (1071/922)0.5 = 1.08 (Fan Law for pressure)◦ 1.083 = 1.25 (Fan Law for Power)

Page 23: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Ducted FanFan as Tested

C-D duct friction 750 Pa (duct design)

A free inlet 0 Pa (no SEF)

B-C outlet with straight duct attached for 2 or more diam. 0 Pa (no SEF)

--------------------

REQUIRED Fan PS 750 Pa

Page 24: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Ducted FanExhaust System

A Entrance loss-sharp edge duct 100 Pa (duct design)

A-B Duct friction at 5000CMH 750 Pa (duct design)

B SEF 1 (Elbow at Inlet) 150 Pa

C SEF 2 (Obstruction) 50 Pa

E SEF 3 (Abrupt Discharge) 150 Pa

------------------

REQUIRED Fan Ps 1200 Pa

Page 25: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Deficient Fan/System

Page 26: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Speed Changes

• Before Increasing Speed◦ Check with the manufacturer for max safe

operating speed◦ Determine expected power increase

• Motor size• Electric Service

◦ Expect more noise

Page 27: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Rules of Thumb

• Minimum 2.5 duct diameters on Outlet

• Minimum 3 to 5 duct diameters on Inlet

• Avoid inlet swirl

Page 28: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Recommendations

• Allow enough space in the building design to allow for appropriate fan connections to the system

Page 29: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Recommendations

• Use allowances in the design calculations when space or other factors dictate less than optimum arrangement of the fan outlet and inlet connections

Page 30: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Recommendations

• Include adequate allowance for the effect of all accessories and appurtenances on the performance of the system and the fan

Page 31: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Page 32: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Page 33: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Page 34: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Page 35: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Page 36: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Page 37: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Page 38: The International Authority on Air System Components Fan Performance Mark Stevens Director of Laboratory Services AMCA International

The International Authority on Air System Components

Thank you

AMCA International, Inc.30 W. University Drive

Arlington Heights, IL 60004 USA

Tel: +1 847 394 0150 Fax: +1 847 253 0088

www.amca.org

Mark Stevens - [email protected]