thermal power station report

Upload: syed-muhammad-munavvar-hussain

Post on 11-Feb-2018

233 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/23/2019 Thermal Power Station Report

    1/36

    Thermal Power Station phase-II

    THERMAL POWER STATION

    Very Brief Account of Visit to Thermal Power Station

    ENGR. SYED MUHAMMAD MUNAVVAR HUSSAIN

    Engr. Syed Muhammad Munavvar Hussain 1

  • 7/23/2019 Thermal Power Station Report

    2/36

    Thermal Power Station phase-II

    Thermal power stationA thermal power station is a power plant in which the prime mover is steam driven.

    Water is heated, turns into steam and spins a steam turbine which either drives an electrical

    generatoror does some other work, like ship propulsion. After it passes through the turbine, the

    steam is condensed in a condenser and recycled to where it was heated; this is known as a

    Rankine cycle. The greatest variation in the design of thermal power stations is due to thedifferent fuel sources. Some prefer to use the term energy center because such facilities convert

    forms ofheatenergy into electrical energy.

    T.P.S. Muzaffar Garh:

    Installed Capacity

    This Power Station is a vital and major thermal power generating installation connected

    with National grid system in Pakistan. This Power Station was constructed in different Phases

    having total capacity of 1370 MW. It consists of:

    Three Russian units of 210 MW each

    Two Chinese units of 200 MW each

    One Chinese unit of 320 MW

    Fuel

    Dual fuel combustion provision (Gas & Furnace Oil) has been made for all the machines.Furnace oil is transported through Railway Wagons and tank Lorries.

    Unit NoInstalled

    Capacity

    Rated

    Capacity

    MakeCommg.

    Date

    Fuel Type

    ST-1 210 MW 200 MW USSR Sep. 1993 P. Gas, F. Oil

    ST-2 210 MW 200 MW USSR Mar. 1994 P. Gas, F. Oil

    ST-3 210 MW 200 MW USSR Feb. 1995 P. Gas, F. Oil

    ST-4 320 MW 300 MW China Dec. 1996 P. Gas, F. Oil

    ST-5 210 MW 200 MW China Dec. 1995 P. Gas, F. Oil

    ST-6 210 MW 200 MW China Dec. 1995 P. Gas, F. Oil

    Total 1370MW 1300MW

    Table 1.1 brief views of TPS units

    Engr. Syed Muhammad Munavvar Hussain 2

    http://en.wikipedia.org/wiki/Power_planthttp://en.wiktionary.org/wiki/prime_moverhttp://en.wikipedia.org/wiki/Steamhttp://en.wikipedia.org/wiki/Steam_turbinehttp://en.wikipedia.org/wiki/Electrical_generatorhttp://en.wikipedia.org/wiki/Electrical_generatorhttp://en.wikipedia.org/wiki/Ship#Propulsion_systemshttp://en.wikipedia.org/wiki/Condensationhttp://en.wikipedia.org/wiki/Surface_condenserhttp://en.wikipedia.org/wiki/Rankine_cyclehttp://en.wikipedia.org/wiki/Heathttp://en.wikipedia.org/wiki/Energyhttp://en.wikipedia.org/wiki/Power_planthttp://en.wiktionary.org/wiki/prime_moverhttp://en.wikipedia.org/wiki/Steamhttp://en.wikipedia.org/wiki/Steam_turbinehttp://en.wikipedia.org/wiki/Electrical_generatorhttp://en.wikipedia.org/wiki/Electrical_generatorhttp://en.wikipedia.org/wiki/Ship#Propulsion_systemshttp://en.wikipedia.org/wiki/Condensationhttp://en.wikipedia.org/wiki/Surface_condenserhttp://en.wikipedia.org/wiki/Rankine_cyclehttp://en.wikipedia.org/wiki/Heathttp://en.wikipedia.org/wiki/Energy
  • 7/23/2019 Thermal Power Station Report

    3/36

    Thermal Power Station phase-II

    Amid sand dunes of area known as Rakh Khanpur, at a distance of 6 km. from

    Muzaffargarh City, is located Thermal Power Complex. A few years back nobody perceived that

    such a desert would yield green trees, more than 1,500 families would be residing here and aPower Station will turn into a huge Power Complex. Now, with the day and night efforts of

    foreign as well as Pakistani engineers, technicians and workers, the complex has grown to the

    realities with three sky-high chimneys, being highest concrete structure in Pakistan and visiblefrom the bridge of River Chenab, which is flowing to the east of the site at distance of 8 kms. In

    September, 1987 contract of supply and erection of a 3x210 MW capacity Thermal Power

    Station was signed with M/s. TECHNOPROMEXPORT of ex-USSR, Moscow, and 1,134 acresof government land was acquired.

    Initially, about 230 acres land for the Power Station and 164 acres for residential colony

    was leveled and subsequently construction was started. Later on contracts with Chinese firm,

    M/s. CMEC, were signed for three units in two stages - Two Units each of 210 MW and one unitof 320 MW. In this way a power complex emerged which is going to be the biggest of all

    Thermal Stations in Pakistan with the possibility of construction of two more units. Presently, the

    total generation capability of three phases is envisaged as 1,370 MW.

    Phase - 1 (Units 1, 2 & 3):

    This phase consists of three steam units each capable of generating 210 MW electricity.The supplier started delivery of equipment to site in January, 1989, and after pre-assembly of

    equipment at Site, erection started in July, 1990. Unit No. 1 was commissioned in September,

    1993 and Unit No. 2 in March, 1994.

    Main Building:

    It contains the turbine hall having a span of 45 meters and dearator bay, 12 meters wide.

    The steam turbines which drive generators are of three stages condensing type arrangedtransversely to the axis of turbine hall. The operational platform is at elevation 12.6 meters and a

    maintenance bay at ground floor near Unit No. 1. The power plant is designed on the block

    principle: boiler-turbine-generator-unit transformer. The fuel gas exhaust section of two units isconnected with a 200 meter high stack, outer section of which is a 195-meter high concrete shell.

    Combined Auxiliary Building:

    The building is connected with the main building and it houses water treatment plant to

    produce 100 t/h demineralized water for the replenishment of station losses, hydrogen plant to

    provide hydrogen for cooling of generators rotors, maintenance shops, laboratories and central

    control room.

    Fuel & Oil Facilities:

    Fuel oil facilities are constructed for decanting, oil storage, preparation and supply of fuelto boiler nozzles. It also includes HSD storage as well as oil facilities for reception, storage,

    purification and centralized delivery of turbine oil and insulating oil to power plant.

    Hydraulic Structures:

    The cooling water used in condensers is re-circulated in closed cycle with inducted draft

    cooling towers. The water is being cooled for each unit in two cooling towers each consisting of

    eight fans. Two cooling towers carry 27,500 Cu m/h circulating water for condensers of one unit.

    Engr. Syed Muhammad Munavvar Hussain 3

  • 7/23/2019 Thermal Power Station Report

    4/36

    Thermal Power Station phase-II

    Startup Boiler:

    One startup boiler using diesel oil as fuel with steam output of 50 t/h is provided to meet

    steam requirement for initial start of unit as well as a backup of power plant auxiliaries. Aseparate stack of 30-meter high has been constructed for it.

    Electrical Part:The electricity generated at 15.75 KV is brought out from Unit transformer at 220 KV

    and fed to the National Grid via a switchyard. Power Plant auxiliaries are fed at 6.6 KV.

    Phase-II (Units 5 & 6):

    It consists of two units of 210 MW each having equipment similar to Phase-I. Turbines

    are placed longitudinally in main building. Outdoor boilers exhaust of two units is connected to

    one stack

    Overview:

    There are many different types of power plants including thermal power plants and hydel

    power plants. Thermal power plants use fuel such as Gas, HSD, Furnace Oil or nuclear fuel toproduce heat energy that is converted to electrical energy through a series of intermediate

    processes. Hydel power plants convert the potential energy of water to electrical power as itflows from higher to lower elevations.

    The "traditional" thermal power plant is the Rankine cycle plant, named after the man who

    invented the cycle. A power plant cycle is a series of processes in which a fluid, generally

    water/steam, is used to convert heat energy to mechanical energy. The Rankine cycle in itssimplest form consists of a boiler, a turbine, a condenser, and a boiler feed pump. Early plants

    had thermal efficiencies of approximately 25% to 30%. Only 25% to 30% of the heat energy in

    the fuel burned in these plants was converted to electrical energy. The rest was lost in variousways.

    The Rankine cycle has been refined considerably over the years and made more efficient

    by the addition of components like Economizer, Feed water heaters, Super heaters and Re-heaters. The efficiency of the Rankine cycle has also been improved by increasing the pressure

    and temperature of the cycle. The laws of thermodynamics and considerations such as material

    limitations have prevented any significant improvement since then. Power plants commonly useheat rate to measure efficiency.

    Engr. Syed Muhammad Munavvar Hussain

    Fuel Energy Boiler Heat Energy

    TurbineMechanical

    Energy

    GeneratorElectrical

    Energy

    4

  • 7/23/2019 Thermal Power Station Report

    5/36

    Thermal Power Station phase-II

    BoilerThe boiler is the main part of any thermal power plant. It converts the fuel energy into

    steam energy. The fuel may be furnace oil, diesel oil, natural gas or coal. The boilers may be

    fired from the multiple fuels.

    The type of boiler used in the TPS phase-II is water tube type.

    Water Tube Boilers:

    In watertube boilers, boiler water passes through the tubes while the exhaust gases remain

    in the shell side, passing over the tube surfaces. Since tubes can typically withstand higherinternal pressure than the large chamber shell in a firetube, watertube boilers are used where high

    steam pressures (as high as 3,000 psi) are required.

    Watertube boilers are also capable of high efficiencies and can generate saturated orsuperheated steam. The ability of watertube boilers to generate superheated steam makes these

    boilers particularly attractive in applications that require dry, high-pressure, high-energy steam,

    including steam turbine power generation.

    Parameter of Boiler:Rated evaporating amount 680 t/h

    Reheat steam amount 575.8 t/hMain steam pressure 140 kg/cm2 g

    Temperature 541 C

    Outlet pressure of Reheat System 23.8 kg/cm2 gOutlet Temperature of Reheat System 541 C

    Inlet pressure of Reheat System 25.8 kg/cm2 g

    Inlet Temperature of Reheat System 310 CFeed water Temperature 251 C

    Boiler Efficiency (burn oil) 90.26 %

    Boiler Efficiency (burn gas) 85 %Exit gas Temperature (burn oil) 153 CExit gas Temperature (burn gas) 136 C

    Consumption of crude oil 48.2 t/h

    Consumption of natural gas 59650 Nm 2 /h

    Main Parts of Boiler:

    The boilers consist of the following main parts:

    Forced Draft Fan (FDF)

    Air Preheater (RAH)

    Burners

    Furnace

    Up Rise Tubes

    Down Comer Tubes

    Water Tubes

    Super Heaters

    Gas Recirculation Fan (GRCF)

    Re-Heater

    Induced Draft Fan (IDF)

    Engr. Syed Muhammad Munavvar Hussain 5

  • 7/23/2019 Thermal Power Station Report

    6/36

    Thermal Power Station phase-II

    Chimney

    Boiler Drum

    Economizer

    Forced Draft Fan (FDF):

    The forced draft fan (FDF) sucks the air from the atmosphere which is used in the furnacefor burning. The air from the atmosphere is passed through the filter to remove the dust and other

    particles from the air. The air from the FDF is then feeded to the regenerative air heaters.

    The motor of the FDF has following specification;

    Type KK 800 11- 8

    Rated Voltage 6.6KVRated Current 114 /121.3A

    Rated Speed 747rpm

    Output 1000KWConnection of Stator /Rotor Y

    Insulation Class FPermissible Rise 80K

    Ambient Temperature 40C No. Of Phase 3

    Rated Frequency 50Hz

    Power Factor 0.81Degree Of Protection IP54

    Moment Of Inertia 310Kg.m2

    Weight 12020K/13250Kg

    Induced Draft Fan (IDF):

    ID fan sucks the flue gases from boiler and exhaust through chimney.

    The motor of the IDF has following specification;

    Type YKK 800 11- 6

    Rated Power 2000kwRated Voltage 6.6KV

    Rated Current 20 A

    Rated Speed 991rpmConnection of Stator Winding 2Y

    Insulation Class F

    Permissible Rise 80k

    Ambient Temperature 40C No. Of Phase 3

    Rated Frequency 50Hz

    Degree of Protection IP54Moment Of Inertia 410Kg.m2

    Weight 15970Kg

    Engr. Syed Muhammad Munavvar Hussain 6

  • 7/23/2019 Thermal Power Station Report

    7/36

    Thermal Power Station phase-II

    Gas Recirculation Fan (GRCF):

    The motor of the GRCF has following specification;

    Type KK 400 11- 4Rated Power 315KW

    Rated Voltage 6600V

    Rated Current 34 ARated Speed 1491rpm

    Connection of Stator Winding Y

    Insulation Class FPermissible Rise 70k

    Ambient Temperature 50C

    No. Of Phase 3

    Rated Frequency 50HzDegree of Protection IP54

    Moment Of Inertia 11.7Kg.m2

    Weight 3200Kg

    Cooling Towers:

    Cooling towers are heat removal devices used to transfer process waste heat to theatmosphere. Cooling towers may either use the evaporation of water to remove process heat and

    cool the working fluid to near the wet-bulb air temperature or rely solely on air to cool the

    working fluid to near the dry-bulb air temperature. Common applications include cooling the

    circulating water used in oil refineries,chemical plants,power stations.

    Cooling Water Pump:

    The motor of the CWP has following specification;Type Y1600-16/2150

    Out Put Power 1600KW

    Stator Voltage 6.6KVSpeed 372rpm

    Frequency 50Hz

    Stator Rated Current 182AStator Connection 2Y

    Ambient Temperature 50C

    Insulation Class B

    Weight 17500Kg

    CW Pump:

    Type is single stage double suction centrifugal pumpType 1400S25-1

    Capacity 16000m3/H

    Speed 370rpmPower 1600KW

    Weight 35000kg

    Head 25m

    NP SHR 8.5m

    Engr. Syed Muhammad Munavvar Hussain 7

    http://en.wikipedia.org/wiki/Atmospherehttp://en.wikipedia.org/wiki/Evaporationhttp://en.wikipedia.org/wiki/Wet-bulb_temperaturehttp://en.wikipedia.org/wiki/Dry-bulb_temperaturehttp://en.wikipedia.org/wiki/Oil_refinerieshttp://en.wikipedia.org/wiki/Chemical_planthttp://en.wikipedia.org/wiki/Power_stationhttp://en.wikipedia.org/wiki/Atmospherehttp://en.wikipedia.org/wiki/Evaporationhttp://en.wikipedia.org/wiki/Wet-bulb_temperaturehttp://en.wikipedia.org/wiki/Dry-bulb_temperaturehttp://en.wikipedia.org/wiki/Oil_refinerieshttp://en.wikipedia.org/wiki/Chemical_planthttp://en.wikipedia.org/wiki/Power_station
  • 7/23/2019 Thermal Power Station Report

    8/36

    Thermal Power Station phase-II

    Air Preheater:

    An air preheater or air heater is a general term to describe any device designed to heat air

    before another process (for example, combustion in a boiler) with the primary objective ofincreasing the thermal efficiency of the process. They may be used alone or to replace a

    recuperative heat system or to replace a steam coil.

    The purpose of the air preheater is to recover the heat from the boiler flue gas whichincreases the thermal efficiency of the boiler by reducing the useful heat lost in the flue gas. As a

    consequence, the flue gases are also sent to the flue gas stack (or chimney) at a lower

    temperature, allowing simplified design of the ducting and the flue gas stack. It also allowscontrol over the temperature of gases leaving the stack.

    Economizers:

    Flue gases from large boilers are typically 450 - 650F. Stack Economizers recover someof this heat for pre-heating water. The water is most often used for boiler make-up water or some

    other need that coincides with boiler operation. Stack Economizers should be considered as an

    efficiency measure when large amounts of make-up water are used (i.e. not all condensate is

    returned to the boiler or large amounts of live steam are used in the process so there is nocondensate to return) or there is a simultaneous need for large quantities of hot water for some

    other use. The savings potential is based on the existing stack temperature, the volume of make-up water needed, and the hours of operation. Economizers are available in a wide range of sizes,

    from small coil-like units to very large waste heat recovery boilers.

    The savings potential is a function of how much heat can be recovered, which is a

    function of how much cold water needs to be heated. A generally accepted "rule of thumb" isthat about 5% of boiler input capacity can be recovered with a properly sized economizer. A

    higher percentage can be recovered with a Flue Gas Condenser, assuming there is enough cold

    water to condense all of the flue gas that is available. Therefore, for 'ball parking' purposes, startby comparing boiler input capacity with the need to heat water.

    An economizer that recovers 5% of boiler input should easily have a 2 year payback in a

    year-round application.

    Boiler Protection:

    Fuel protection

    Gas pressure protection

    Diesel oil protection

    Furnace oil protection

    FD fan trip

    ID fan trip

    Regenerative air pre heater trip Drum level high

    Drum low level

    Reheat steam pressure drop

    Furnace pressure low

    Furnace flame out

    Natural gas pressure high

    Engr. Syed Muhammad Munavvar Hussain 8

    http://en.wikipedia.org/wiki/Airhttp://en.wikipedia.org/wiki/Combustionhttp://en.wikipedia.org/wiki/Boilerhttp://en.wikipedia.org/wiki/Recuperatorhttp://en.wikipedia.org/wiki/Flue_gashttp://en.wikipedia.org/wiki/Flue_gas_stackhttp://en.wikipedia.org/wiki/Chimneyhttp://en.wikipedia.org/wiki/Ducthttp://en.wikipedia.org/wiki/Airhttp://en.wikipedia.org/wiki/Combustionhttp://en.wikipedia.org/wiki/Boilerhttp://en.wikipedia.org/wiki/Recuperatorhttp://en.wikipedia.org/wiki/Flue_gashttp://en.wikipedia.org/wiki/Flue_gas_stackhttp://en.wikipedia.org/wiki/Chimneyhttp://en.wikipedia.org/wiki/Duct
  • 7/23/2019 Thermal Power Station Report

    9/36

    Thermal Power Station phase-II

    Steam Cycle:

    Engr. Syed Muhammad Munavvar Hussain

    Boiler Drum HP Cylinder Re- Heater IP Cylinder

    Condenser

    Condensate

    Pump

    Ejector

    LP Cylinder

    Economizer

    HP Heaters

    Feed Water

    Pumps

    Feed WaterTank

    De-aerator LP Heaters

    STEAM CYCLE

    CirculatingWater

    9

  • 7/23/2019 Thermal Power Station Report

    10/36

    Thermal Power Station phase-II

    Steam Turbine

    Turbine is used to convert the heat energy into mechanical energy. Turbine used in tps

    Muzaffar Garh is impulse-reaction steam turbine.The load requirement is controlled by the steam flow through a governing valve.

    Maximum steam flow at full load is 670 tons/hour. When the load at the generator is suddenly

    decreased then the rpm (frequency) of the generator is increased and to decrease the frequencywe lower down the steam flow which decreases the speed and maintains the frequency.

    If load is suddenly increased rotor speed becomes slower, to increase the speed, steam flow is

    increased.

    Steam turbine has three parts.

    1. HP turbine

    2. IP turbine

    3. LP turbine.

    HP (High Pressure) Turbine:

    First of all steam from boiler comes into the HP turbine. Steam in the HP turbine is called

    live steam or main steam. Rotor blades diameter of this part of turbine is smallest of the other

    parts of the turbine.

    Inlet steam temperature of the HP turbine is 540 C and pressure is 130 kg/cm2.

    Outlet steam temperature of the HP turbine is 290 C and pressure is 15 kg/cm2.

    HP turbine has total of 12 stages including one is governing stage.

    IP (Intermediate Pressure) Turbine:Steam comes into the IP turbine from HP turbine via reheaters. The steam pressure in this

    section of the turbine is 14 kg/cm2 and temperature is 540 C. This part has total of 10 pressure

    stages. .

    LP (Low Pressure) Turbine:

    The outgoing steam of the IP turbine entered into the LP turbine. Steam from the LP turbine

    goes into the condenser.

    Specification of the steam turbine:

    Maximum load 210 MWLive steam pressure 132 kg/cm-2

    Live steam temperature 538 C

    Rated speed 3000 rpmHP cycle Exhaust steam temperature 310 C

    HP cycle Exhaust steam pressure 24 kg/cm2

    Reheat steam temperature 538 CReheat steam pressure 14 kg/cm2

    Engr. Syed Muhammad Munavvar Hussain 10

  • 7/23/2019 Thermal Power Station Report

    11/36

    Thermal Power Station phase-II

    Turbine Protection:

    Lube oil pressure (low and high)

    Vacuum drop

    Live steam temperature drop

    Axial shift displacement

    Gas cooling pump tripping

    HP heater level high

    All FW pump trip high vibration tipping

    Trip unit by switch/emergency

    Engr. Syed Muhammad Munavvar Hussain 11

  • 7/23/2019 Thermal Power Station Report

    12/36

    Thermal Power Station phase-II

    Furnace Safeguard Supervisory System (FSSS)

    The FSSS station consists of the following parts; De-kending area

    Fuel oil tanks

    First Lift pump

    Main Heaters

    Second Lift pump

    Diesel pumps

    Recirculation pumps

    Recirculation heaters

    Filters

    control Room

    De-kending Area:

    The furnace oil that is used as a fuel in the burners of the boiler furnace to produce the

    steam is transported to the TPS through two ways;

    Oil Tankers

    trainFor unloading of the fuel from oil tankers and train there is separate unloading or

    dekending station for each. The unloaded fuel oil is initially stored in the underground reservoir;

    from there it is filled in the main storage tanks.02 pumps are used to fill the main storage tanks from the oil tankers de-kending area.

    One of them is active (on load) and other is standby.

    Fuel Oil Tanks:

    From the de-kending area the furnace oil is filled in the storage tanks. From there it is

    supplied to the burners of the boiler furnace after proper heating.Usually one storage tank is called service tank, from there furnace oil is supplied to the

    units. The furnace oil is filled in the other tanks first and then filled in the service tanks through

    recirculation pumps (RCP). The oil in the tanks is kept heated at the temperature 75 C to 80 C.

    There are total 06 storage tanks for furnace oil each having a volume of 20,000 cubicmeters hence each can store 2, 00,00,000 liters.

    There are 2 diesel oil storage tanks each having capacity of 1000 ton.

    First Lift Pump:

    First lift pump takes the furnace oil from the service tank and supplied to the main

    heaters. There are total 04 first lift pumps which are operated according to the unit loadconditions.

    The specification of fist lift pump motor is as under;

    3 phase 50 Hz Induction Motor

    Connection: Star

    Engr. Syed Muhammad Munavvar Hussain 12

  • 7/23/2019 Thermal Power Station Report

    13/36

    Thermal Power Station phase-II

    Power: 55KW

    Power factor: 0.9

    Efficiency: 90%Voltage 230/400V

    Speed 2950rpm

    Current 177/102A

    Main Heaters:

    There are 04 main heaters each is connected to the respective first lift pump. The mainheaters heat the furnace oil through the steam which comes from the boiler. Steam is use to heat

    the oil in the recirculation heaters.

    The seam flows through the pipes which heats the oil outside the tube. The temperature

    and pressure of the steam in the main heaters isTemp 270 C

    Pressure 11 to 13 kg/cm2

    Second Lift Pump:Second lift pumps take the furnace oil from the main heaters and supplied to boilers of

    the units. There are total 04 second lift pumps which are operated according to the unit loadconditions. The temperature of the oil that is supplied to the boiler is 105 C to 120 C.

    The specification of second lift pump motor is as under;

    3 phase 50 Hz Induction Motor

    Power: 250KWVoltage 6.6kV

    Speed 2950rpm

    Current 252A

    Fuel Oil Cycle:

    Engr. Syed Muhammad Munavvar Hussain 13

  • 7/23/2019 Thermal Power Station Report

    14/36

    Thermal Power Station phase-II

    The GeneratorThe generator is a device which converts the mechanical energy into electrical energy.

    Working Principle:

    The working principle of generator is based on the Faradays law of electromagnetic

    induction, which states thatThe emf is always produced in the conductor which is placed in the magnetic field when

    there is a relative motion between conductor and the magnetic field.

    If the output electrical energy is AC, it is called AC generator or alternator. If the output

    electrical energy is DC, it is called DC generator. In fact there is no difference between alternatorand DC generator except the way the output is obtained from the generator. In alternator the AC

    supply is produced in the armature and supply is obtained through slip rings where as in the DC

    generator the generated AC supply is obtained from the armature through split rings orcommutator which converts the AC into DC.

    The following three things are necessary for the generation of electrical energy;

    Magnetic field

    Conductor

    Relative motion between conductor and Magnetic field

    Engr. Syed Muhammad Munavvar Hussain

    Furnace Oil

    TanksOil Heaters

    Burners(Boiler Furnace)

    Flue Gases

    ID Fan

    Air

    Pre Heater

    Exhaust

    (Chimney)

    FUEL OIL CYCLE

    Gate & Quick

    Closing

    Valves

    14

  • 7/23/2019 Thermal Power Station Report

    15/36

    Thermal Power Station phase-II

    In the small generator the magnetic field is being produced in the stator and the emf is

    produced in the rotor through Faradays law of electromagnetic induction. The electromagnetic

    are used in the generator to produce the magnetic field.In the large generator the magnetic field is produced by the electromagnetic in the rotor

    and the emf is produced in the stator. The output is taken from the stator because if the output is

    taken from the rotor, the rotor must have high insulation due to the high voltage induction and itmust have heavy insulation which may increase the size of the rotor, and require more power for

    the prime mover to rotate this heavy rotor.

    Synchronous Generator:

    The generators used in the TPS are synchronous generator.

    Synchronous generators are by definition synchronous, meaning that the electrical

    frequency produced is locked in or synchronized with the mechanical rate of rotation of thegenerator.

    A DC current is applied to the rotor winding, which then produces a rotor magnetic field.

    The rotor is then turned by a prime mover (e.g. Steam, water etc.) producing a rotating magnetic

    field. This rotating magnetic field induces a 3-phase set of voltages within the stator windings ofthe generator.

    Field windings applies to the windings that produce the main magnetic field in amachine, and armature windings applies to the windings where the main voltage is induced.

    For synchronous machines, the field windings are on the rotor, so the terms rotor windings and

    field windings are used interchangeably.

    Generally a synchronous generator must have at least 2 components:

    a) Rotor Windings or Field Windings

    Salient Pole

    Non Salient Poleb) Stator Windings or Armature WindingsThe rotor of a synchronous generator is a large electromagnet and the magnetic poles on

    the rotor can either be salient or non salient construction. Non-salient pole rotors are normally

    used for rotors with 2 or 4 poles rotor, while salient pole rotors are used for 4 or more polesrotor.

    Engr. Syed Muhammad Munavvar Hussain 15

  • 7/23/2019 Thermal Power Station Report

    16/36

    Thermal Power Station phase-II

    A dc current must be supplied to the field circuit on the rotor. Since the rotor is rotating, a

    special arrangement is required to get the dc power to its field windings. The common ways are:

    Supply the dc power from an external dc source to the rotor by means of slip rings and

    brushes.

    Supply the dc power from a special dc power source mounted directly on the shaft of the

    synchronous generator.

    Slip rings are metal rings completely encircling the shaft of a machine but insulated fromit. One end of the dc rotor winding is tied to each of the 2 slip rings on the shaft of the

    synchronous machine, and a stationary brush rides on each slip ring.A brush is a block of graphite like carbon compound that conducts electricity freely but has

    very low friction; hence it doesnt wear down the slip ring. If the positive end of a dc voltage

    source is connected to one brush and the negative end is connected to the other, then the same dcvoltage will be applied to the field winding at all times regardless of the angular position or

    speed of the rotor.

    Some problems with slip rings and brushes:

    They increase the amount of maintenance required on the machine, since the brushes

    must be checked for wear regularly. Brush voltage drop can be the cause of significant power losses on machines with larger

    field currents.

    Small synchronous machines use slip rings and brushes.Larger machines brushless exciters are used to supply the dc field current.

    A brushless exciter is a small ac generator with its field circuit mounted on the stator and its

    armature circuit mounted on the rotor shaft. The 3-phase output of the exciter generator is

    Engr. Syed Muhammad Munavvar Hussain 16

  • 7/23/2019 Thermal Power Station Report

    17/36

    Thermal Power Station phase-II

    rectified to direct current by a 3-phase rectifier circuit also mounted on the shaft of the generator,

    and is then fed to the main dc field circuit. By controlling the small dc field current of the exciter

    generator (located on the stator), we can adjust the field current on the main machine without sliprings and brushes. Since no mechanical contacts occur between the rotor and stator, a brushless

    exciter requires less maintenance.

    The Speed of Rotation of a Synchronous Generator:

    Synchronous generators are by definition synchronous, meaning that the electrical frequencyproduced is locked in or synchronized with the mechanical rate of rotation of the generator. A

    synchronous generators rotor consists of an electromagnet to which direct current is supplied.The rotors magnetic field point in the direction the rotor is turned. Hence, the rate of rotation of

    the magnetic field in the machine is related to the stator electrical frequency by:

    Excitation of Generator:

    Excitation of synchronous generator is done via DC supply which is given to the field

    winding of the generator to produce the magnetic field.The generator can be classified, with respect to the excitation, as under;

    Separately Excited Generator:

    The generator in which the DC supply is given to the field winding of the generator

    through the external source is called separately excited generator.

    Self Excited Generator:

    Engr. Syed Muhammad Munavvar Hussain 17

  • 7/23/2019 Thermal Power Station Report

    18/36

    Thermal Power Station phase-II

    The generator in which the DC supply is given to the field winding of the generator

    through its own generated supply is called self excited generator.

    Synchronous Generator in TPS:

    The main generators used in the TPS phase-I are separately excited generators. For this

    purpose another synchronous generator is installed on the same shaft of the turbine and maingenerator which is called Exciter.

    The exciter is a self excited synchronous generator. In the initial startup the DC supply is

    given to the field winding (rotor) of the exciter by the DC batteries for 4 seconds. After that theDC batteries are cut off and the DC supply is given to the field of the exciter by its own

    generated supply after the rectification.

    The AC supply generated by the exciter is also given to the field winding (rotor) for its

    excitation after the rectification. The AC produced by the exciter is sent to the rectifier roomwhere it is converted to the controlled DC supply by thyristers. The firing angles of the thyristers

    are controlled by the AVR (automatic voltage regulator) and hence the excitation of the

    generator is controlled.

    Exciter generator:

    Excitor generator of the excitor provides independent power supply(3-phase, 50 Hz) tothe excitation system. The exciter generator is installed on the same shaft with the turbo

    generator.

    The exciter is excited by two water cooling thyristor converters. The thyrister converters

    are connected in parallel and operate in turn: one is in operation while other is in automaticstand-by duty. The ac and dc circuits of the thyristers includes several knife switches for removal

    either of the converters from service for repair.

    Initial excitation of the exciter generator is carried out by a short term connection of thestorage batteries through a contactor and rectification bridge.

    Main Generator Parameters

    Pilot Exciter:

    Type Tfy-46-500

    Rated Voltage 93/161V

    Rated Current 286/165A

    Rated Speed 3000rpmRated Power Factor 0.875

    Phase 3

    Rated Frequency 500HzArmature Connection /Y

    Specification OEA.513.039

    Mfg. Date 1993-3-1Rated Capacity 46KVA

    Alternating Excitor:

    Engr. Syed Muhammad Munavvar Hussain 18

  • 7/23/2019 Thermal Power Station Report

    19/36

    Thermal Power Station phase-II

    Type Tl-1165-4

    Rated Voltage 431V

    Rated Current 1562ARated Speed 3000rpm

    Rated Power Factor 0.91

    Phase 3Rated Frequency 100Hz

    Armature Connection Y

    Specification OEA.513.039Mfg. Date 1993-8-24

    Rated Capacity 1165KVA

    Turbine Generator Water Hydrogen Cooled

    Type QFSN-210-2

    Rated Capacity 246MVARated Output 210MW

    Rated Voltage 15.75KVRated Current 9056A

    Rated Speed 3000rpm

    Rated Frequency 50Hz

    Phase 3Connection Of Stator Winding 2-Y

    Insulation Class F

    Power Factor 0.85Excitation Voltage 289V

    Excitation Current 18.67A

    Max.Inlet Water Temp. For Stator Winding 50CMax.Inlet Cooling Hydrogen 50C

    Water Flow For Stator Winding 35m2/h

    Rate H2 Pressure 0.3MPaSpecification OEA.512.137

    Mfg. Date 1993-2

    Cooling System of Turbo Generator:

    The first question arises here is that why we need cooling of the generator?

    As the current flow in the stator and rotor of the generator is very high so it increases thetemperature of the stator and rotor winding. As a result the resistance of the stator and rotor

    windings increases which increase the power losses and may cause the insulation breakdown.

    Two types of cooling is used in the turbo generator of TPS phase-II1. Stator cooling

    2. Rotor cooling

    Stator cooling:

    Engr. Syed Muhammad Munavvar Hussain 19

  • 7/23/2019 Thermal Power Station Report

    20/36

    Thermal Power Station phase-II

    The stator of the turbo generator is cooled by the distillated or demineralized (demi)

    water. For this purpose a special plant is installed which prepares the demi water for the stator

    cooling. This demi water is also used for the cooling system of the thyrister converters. Thewater is passed though the hollow conductors of the stator winding for its cooling.

    The demi water is necessary for the cooling of the stator winding because raw water is

    not a pure insulator which may cause the flow of leakage current when passed through statorwinding.

    The demineralized water plant removes the impurities and minerals of the raw water and

    make it good insulator whose Resistivity is taken at a minimum level of 200 k.cm.The demi water that passes through the stator winding absorbs the heat of the stator

    winding making it cool and becomes hot itself. The demi water then passes through heat

    exchangers (coolers) where its temperature is decreased by the circulating water coming from the

    cooling towers. This demi water is also passed through the mechanical and magnetic filtersbefore passing through stator winding and thyrister converters. The stator and thyristers cooling

    circle is shown in figure below;

    Water parameters in Heat Exchangers

    Rated temp.of cold water at inlet 32 CMin: temp of cold water 15 C

    No. of gas heat exchangers 02

    Rated water flow in on heat exchangers 150 m3/h

    Rotor Cooling:

    The rotor cooling is done by the Hydrogen gas.

    Hydrogen gas is used for the following purposes:1. Its heat exchange capability is much better than other gases

    2. It is very lighter than other gases so do not overload the rotor.

    3. Its preparation is very easy and cheap.

    Hydrogen gas is filled in the generator and maintained at a pressure of 4kg/cm2. It takes

    all the heat of the rotor and cools the rotor winding and gets warmed itself. For the cooling of thegas there are four gas coolers inside the generator on each corner. Circulating water of the

    cooling tower is used in the gas cooler for the hydrogen cooling.

    Hydrogen gas is explosive if it is combined with oxygen under pressure so to avoid any

    leakage of gas and entrance of air inside the generator the rotor assembly is sealed by the seal oilwhose pressure is at least 0.7kg/cm2 more than hydrogen gas inside the generator.

    When the generator is turned off for a long time for maintenance purpose hydrogen is

    released from the generator in the air using special method. Method involves that firstly fill thegenerator with CO2 which release the hydrogen in the air and then in the end air is filled in the

    generator and CO2 is released in the air. This method is adopted because if hydrogen is released

    using air instead of CO2 then it can cause explosion due to oxygen in the air which will meethydrogen under pressure in the generator.

    After maintenance hydrogen gas is refilled in the generator using the reverse process as

    described above.

    Engr. Syed Muhammad Munavvar Hussain 20

  • 7/23/2019 Thermal Power Station Report

    21/36

    Thermal Power Station phase-II

    Water parameters in gas cooler

    Rated temp.of cold water at inlet 32 C

    Min: temp:of cold water 15 CMax: water pressure 3 kg/cm2

    No. of gas coolers 04

    Rated water flow in on gas cooler 76.5 m3

    /h

    Protections of Generator:The following protection are installed for the protection of the generator in TPS phase-I;

    1. Longitudinal differential current protection

    This system is intended to protect against multi phase short circuit in generator stator

    winding and at its leads including against double earth fault, one of which being in the generator.

    2. Lateral differential current protection

    This system is intended to protect against turn-to-turn short circuit of one phase in thegenerator stator winding.

    3. Earth fault protection of stator winding

    This system is intended to reveal and disconnect one phase earth fault of generator stator

    winding.

    4. Differential protection of the unit

    This system is intended to backup longitudinal differential protection of generator.

    5. Negative sequence current protection

    This system is intended to prevent damage of generator incase of overloading by negative

    sequence current caused by asymmetric load or external asymmetric short circuit and abnormaloperating condition of power grid.

    6. Over current protection against overloading of generator

    This system is intended for signaling at symmetric overloading of generator stator.

    7. External symmetrical short circuit protection

    This system is intended to protect the generator against external symmetric short circuit.

    8. Protection against asynchronous mode, when excitation loss

    This system is intended to protect against asynchronous mode. One of the elements ofresistance block relay for protection of the unit against external symmetrical short circuit is

    used.

    9. Protection of generator rotor against overloading

    This system is intended to protect against overloading under emergency condition as well

    as incase of failure of generator excitation system which cause long term flow of current ofabnormal value along the rotor winding.

    Engr. Syed Muhammad Munavvar Hussain 21

  • 7/23/2019 Thermal Power Station Report

    22/36

    Thermal Power Station phase-II

    10. Earth fault protection in one point of excitation circuit

    This system is intended to protect the generator incase of earth fault at one point ofexcitation circuit.

    11. Protection against voltage increase at generator at idle operationThis system is intended to prevent inadmissible increase in voltage at turbo generator and

    transformer of unit during idle operation of the unit incase of failure of excitation system.

    12. Zero sequence current protection

    This system is intended to backup protection operating at one phase short circuit in the

    220KV network. It is also used to backup unit protections when short circuit at the 220KV side

    of the unit.

    13. Differential protection of the exciter

    This system is intended to protect against all kind of short circuit in the exciter winding

    and on its leads.

    14. Over current protection of exciter against external short circuit

    This system is intended to protect against over current in the external system of the

    exciter.

    Transformer

    Generally following type of transformers are used in our power house.

    Main transformer

    Stand by transformer

    Auxiliary transformer

    Parts of Transformer:

    Main transformer consists of following parts:

    Engr. Syed Muhammad Munavvar Hussain 22

  • 7/23/2019 Thermal Power Station Report

    23/36

    Thermal Power Station phase-II

    1. Power fans

    2. Condenser type bushing

    3. Oil conservator4. Bucholz relay

    5. Winding temperature controller

    6. Thermostat and thermometer7. Current transformers

    8. Tap changer

    9. Earthing tower10. Fire protection cooling system

    11. Automatic voltage regulator

    Power Fans:

    The natural cooling of the transformer can be increased by the addition of power fans placed at

    the base or along the side of radiators, whether they are fitted directly to the tank or groups in

    outside gangs.

    The fans are of helical type and are of capable of generating an air flow. The motordesigned for an absorbed power .25 1 HP is closed, self cooling, with cage rotor and mounted

    on bearing.Normally the fans are controlled automatically through a thermostat. In addition to make

    manual operation possible as well, a preselector is often built into the system, allowing operation

    by means of push buttons on the protection and control cover.

    When forced cooling is provided the power fans unit is split into two units eachcontrolled through its own switch by same thermal relay.

    Condenser type Bushing:

    The bushing is packaged in cases, generally in the vertical position. Packing is providing to

    protect the bushing from blows and moisture during transients. Moreover, the part of each

    bushing normally immersed in oil is protected from moisture by a cup shaped metal or plasticcovering directly fitted to the bushing flange.

    On spare bushing, not used for transformer testing, a water proof film may be found for

    some construction type on the surface of resin paper. Before using the bushing, this film shouldbe removed with a blunt tool, for not to damage the surface underneath.

    The bushing should be stored in dry place, always in the vertical position, even for short

    period.

    Atmoseal Type air-cell oil conservator:

    For air cell conservator the contact between oil and outside air is prevented. Moreover the

    pressure on the oil surface remains constant and equal to the atmosphere pressure. Whentransformer is running, it requires a very small maintenance limited to routine inspection.

    In conservator an oil resistant, flexible, rubber oil-cell is arranged in communication with the

    outside through a drier that prevents condensation in the cell. The air cell gets bigger or smallerso as to compensate oil volume variations and to keep pressure an oil surface at the atmospheric

    valve. The working condition of the Buchholz relays, installed on the tank to conservator pipe, is

    not out all affected by the air cell.

    Engr. Syed Muhammad Munavvar Hussain 23

  • 7/23/2019 Thermal Power Station Report

    24/36

    Thermal Power Station phase-II

    Buchholz type gas accumulation relay:

    This relay is provided for transformer protection when electrical breakdown occurs between the

    live parts, or in the event of fault to ground, short circuits between turns, phase interruptions,burning of core, oil leakage in the tank or in the oil cooling system.

    This relay will operate on the occurrence of gas formation or on sudden variations of oil level

    resulting from abnormal transformer conditions by actuating an alarm signal and if the fault isserious or persistent, by putting the transformer out of service. The Buchholz relay is installed

    directly on the oil pipe connecting the tank to the conservator and is normally flooded with oil, in

    which its inner armature is permanently immersed with the actuating device.The upper contact for signaling purpose is closed by operation of pertaining float, when due to

    an inflow of gas to the relay or the other reason, the oil level contained in the upper part of the

    relay is lowered. The lower contact which controls the tripping circuit is operated by the

    corresponding float when the oil level reaches the lower part of the relay.Whenever the Buchholz relay operates the alarm and the tripping circuit, it is necessary to open

    the gas drawing cock and to make sure that gas is released.

    Winding temperature controllerA thermal image device is used to detect the Hot Spot temperature in the winding of a power

    transformer. A coil is immersed in the hottest oil layer of the transformer, transmits through thecapillary tube, the temperature variation to the temperature indicator. A heater coil is placed

    around the thermometer bulb and is supplied by the secondary of main current transformer. The

    current in the heater is proportional to that is flowing in the winding. The heater is designed to

    obtain a temperature rise and a thermal inertia equal to those of transformer winding.It should be noted that the temperature values read on the indicator are Hot Spot values, i.e.

    maximum local winding temperature. Therefore, when the transformer operates at full load, the

    reading may exceed the temperature limit by the standards for the average winding temperature.

    Temperature indicator:

    The indicator is sealed in the tank; it is a potentiometer for remote indication and is mounted atmans height at the tank of the transformer. The thermometer bulb located in the probe, is

    connected through the capillary tube to the actuating bellows of the instruments. A second

    capillary tube runs parallel to the preceding one and is connected to the compensating bellows tocancel the influence of the ambient temperature. The system is filled with a special stable and

    non corrosive liquid.

    The instrument dial is graduated from 0 to 150 C over an arc of 270. The index 7 is actuated

    through a sector gear, the latter is also operates the lever , moving the slider of potentiometer ifrequired and the lever which controls the fixed differential switch and the variable differential

    switch. The device is fitted with a maximum index that can be reset to zero. The switches and the

    potentiometer are connected to terminal boards and the potentiometer has fine and zeroadjustments.

    Thermostat and thermometerThis device is used for the temperature control and consists of a bulb at the top part of the

    transformer tank and connected through the capillary tube to a dial indicator. Besides indicating

    the temperature, this instrument closed a circuit connected to an alarm device and subsequently a

    second circuit directly connected to the main breaker and capable to cause the detachment of the

    Engr. Syed Muhammad Munavvar Hussain 24

  • 7/23/2019 Thermal Power Station Report

    25/36

    Thermal Power Station phase-II

    transformer from the line. The measurement system can be of liquid thermometer type. The scale

    is not linear but approximately logarithmic expandable with the temperature

    Main Transformer:

    The specification of main transformer is;

    Type SFP7-250000/235TA

    Phase 3Frequency 50HZ

    Rated Power 250000KVA

    Rated Voltage 235 3/5*2.5% /15.75 KVA

    Type Of Cooling OFAFInsulation Class A

    Connection Symbol YN.D1

    Current 0.25%

    No-load Noise Level 90dbImpedance Voltage 13.9%

    No Load Losses 170.2 KWLoad Losses 675.9KW

    Temp. Rise 60K

    WEIGHTActive Part 158t

    Oil 55.6t

    Bell Tank 17.9tTotal 261.83t

    Stand By Transformer:

    Type SFP7-250000/235TA

    Phase 3

    Frequency 50HzRated Power 2500/25000/8400KVA

    Rated Voltage 230 8*1.25% /6.9 /3.984KVA

    Type of Cooling OFAFInstallation Outdoor

    Connection Symbol YN yno d1

    Noise Level 90db

    No Load Current 0.33%

    Engr. Syed Muhammad Munavvar Hussain 25

  • 7/23/2019 Thermal Power Station Report

    26/36

    Thermal Power Station phase-II

    No-load Losses 34KW

    Load Losses 113.8KW

    Temp. Rise 60K

    WEIGHT

    Active Part 35.1tOil 34.54t

    Bell Tank 10t

    Total 98.64tQuantity Of Cooler 4

    Spare Cooler 1

    Temperature Classification A

    NOTE:

    This transformer can be operated with out coolers for 20 minutes.

    Auxiliary Transformer:

    Type S27-2500/15TAPhase 3

    Frequency 50HZ

    Rated Power 25000KVA

    Rated Voltage 15.75 7*2% /6.9 KVARated Current 916.4/2092A

    Type Of Cooling ONAN

    Insulation Class AConnection Symbol D.yn11

    Noise Level 69db

    Impedance Voltage 12.2% No Load Current 0.336%

    No-load Losses 22.5 KW

    Load Losses 109.4 KW

    Limit for Temperature Rise:

    Winding 60KTop Oil 50K

    Insulation Level LI150AC55/LI60AC25

    WEIGHT

    Active Part 27500kg

    Oil 19500kgTotal 58580kg

    Transformer Protections:

    Engr. Syed Muhammad Munavvar Hussain 26

  • 7/23/2019 Thermal Power Station Report

    27/36

    Thermal Power Station phase-II

    Differential current protection of unit t/f

    Gas protection of unit transformer

    Gas protection of on-load tap changer section

    Remote protection at 6kv side

    Current different of working and standby power supply 6kv section

    Over current protection against over-loading of 6kv winding Arc protection at 6kv side/winding

    MT Buchholz

    MT cooling fan stop

    Relief value

    SWITCH YARD

    Mainly there are different but most important things for the protection, measurement, meteringand for the other purposes

    Circuit Breaker

    Isolator

    Insulator

    Insulator strings

    Bus Bar

    Engr. Syed Muhammad Munavvar Hussain 27

  • 7/23/2019 Thermal Power Station Report

    28/36

    Thermal Power Station phase-II

    Current transformer (C.T.)

    Potential transformer (P.T.)

    Conductor

    Control Switch

    Relays

    Power Line communication box

    Circuit Breaker:

    This is the basic and the most important part of the switchyard. Isolators are used for its

    protection because the minimum cost of the circuit breaker which has been installed in KAPCO

    is of 10 million rupees. So, we are required to provide protection to it to avoid the burning andthe familiar of the breaker.

    Objective:

    This is installed to protect or making some disconnection or connection part, So that there can be

    a bridge between the two parts.This is an automatic device which opens and closes by sensing the characteristics defined

    by the designer. Suppose if we want to work on the transmission line going to any other region,then we make open the connections of the circuit breaker.

    On the other hand, if any fault occurs on any side of the breaker, then current transformer which

    is certainly installed with a breaker senses the abnormal current and sends information to thecentral control room and also performs some action to protect the system from any accident.

    Any of the line is no longer in contact with the generator, all lines are coming out from the bus

    bar and there is a circuit breaker in between the line and the bus bar. So, by chance, if occurs afault in transmission line then we can easily recover it by opening the breaker. Similarly the line

    from the step-up transformer to the bus bar is also protected by a circuit breaker.

    So, this circuit breaker is a kind of connection and disconnection between the generator, bus barand the transmission line. So, by this way, the transmission line or substation or bus bar itself andalso generator are protected from any kind of small or big accidents.

    The Necessary Capabilities of Breaker:

    1. It should be capable of extinguishing the arc without undue delay.

    2. It should withstand the transient voltage that appears across the contacts immediately

    after the current flow ceases. So it should provide sufficient dielectric strength immediatelyafter the rupture of current.

    Components of the circuit breaker:

    Auxiliary switch

    This is only for the purpose of the taking information about the working of the C.B. e.g. it

    consists of PLCs which take information that whether the breaker is open or close. Theinformation about the opening and the closing of the breaker is taken by such a way that there are

    Engr. Syed Muhammad Munavvar Hussain 28

  • 7/23/2019 Thermal Power Station Report

    29/36

    Thermal Power Station phase-II

    some normally open and normally closed contacts in auxiliary switch. So, if the breaker is closed

    then information from the normally closed contacts is sent to C.C.R. (Central Control Room) and

    a light is made ON there showing that Breaker is in closed condition. Similarly is the breaker isopen, then Normally open contacts are closed and in the similar fashion described above, light is

    made ON in C.C.R. showing that breaker is in open condition.

    Mechanical switching:

    This process is done with help of the oil pressure. A certain oil pressure is obtained and then

    according to the information supplied by the manufacturer, opening and closing of the breaker isdone at some pressure defined, i.e. if pressure goes less than 273 bars than breaker is opened and

    then does not close itself until it is done manually.

    Inside protection:

    As because of the opening and closing of contacts by some other reasons, arcs are produced

    inside the breaker which is dangerous for the life and the characteristics of the breaker. So, these

    arcs must be quenched.

    There are many methods for quenching these arcs, e.g. Air quenching

    Gas quenching

    Vacuum quenching

    Now days, most commonly used methods for quenching the arch is the use of the SF 6 gas which

    is very much efficient for doing this task.

    Types of Circuit Breakers:

    They can be classified with respect to two criteria

    1. arc quenching media

    2. constructionWith respect to arc quenching media , we have most used types listed below

    The oil circuit breakers

    The air circuit breakers

    The SF6 circuit breakers

    The vacuum type

    Oil Type:

    In the oil type circuit breaker, the arc is produced in the oil thus oil decomposes and replacedby the surrounding oil thus provides both cooling and give proper dielectric strength. Such an

    arrangement can work for breaking duty not exceeding 150MVA.Addition can be done to increase the rating by providing pressure pot and externally generated

    pressure to extinguish the arc by pushing it and also by dividing it into sections by means of

    insulators .By these means, a rating of 7500MVA at 132 kV is possible. Also low oil content

    breaker can be used to decrease the size and increase the life and performance of oil.

    Engr. Syed Muhammad Munavvar Hussain 29

  • 7/23/2019 Thermal Power Station Report

    30/36

    Thermal Power Station phase-II

    Air Type:

    Axial, radial or cross blast is used in these breakers to extinguish arc and also insulators can be

    added to increase the dielectric strength.

    Vacuum Type:

    In this type, the vacuum is created at the contact position. When the contacts open, theresistance becomes very high since no ionization in the medium occurs. only source of electrons

    is the harmonic emission through the surfaces. So no chance of re-striking arc after it is once

    extinguished.

    Current transformers:

    Current transformers are used in power transformers as a source of energy for operation

    of relays, to measure the equipment of a thermal image plant, a line drop compensator andprotection system etc.

    The current transformers normally incorporated in power transformers may be of

    bushing type with primary winding.

    The primary is formed by connection which goes from the winding of each individualphase of the transformer to the corresponding insulator and which crosses the transformer

    centrally. If the transformer ratio is very low and the accuracy is high, it is advisable to use thetype with the primary winding. As far as possible, these current transformers are arranged on

    the machine in an easily accessible position.

    Chemical section

    The chemical section consists of the following sections;

    Hydrogen plant

    Demineralization plant

    Oil testing lab

    Water testing lab

    Hydrogen Plant:

    Engr. Syed Muhammad Munavvar Hussain 30

  • 7/23/2019 Thermal Power Station Report

    31/36

    Generation of

    HYDROGEN

    Alkaline

    SolutionElectrolyzer

    Dryer Gas Scrubber(Gas Washer)

    Separating

    Columns

    AirCompressor

    Rotor(Generator)

    StorageTanks

    DC PowerSupply

    (330A)

    Purifier

    Thermal Power Station phase-II

    Hydrogen plant prepares the hydrogen gas which is used for the cooling of the rotor of

    the turbo generator. The hydrogen gas is used for the cooling of the rotor of the turbo generator

    because it has better heat transfer characteristics, cheap and easy preparation and also it is verylight and hence do not over load the rotor.

    The hydrogen is prepared by electrolyses of the water. For this DC supply is given to the

    electrolyzer. This Dc supply is produced after step down of the 6.6 kV supply to 400 V and thenby 3-pahe rectifier.

    Raw water is used for the preparation of the hydrogen as it supports fast electrolyses

    action then de-mineralized water.Potassium Hydro oxide (KOH) is used as a catalyst. The oxygen and hydrogen are

    prepared in the ratio of 1:2.

    A generalized layout of the hydrogen plant is shown in the figure below;

    DC Power Supply:

    The 3-phase 6.6 kV supply is stepped down to 400 V through step down transformers.For this purpose 02 transformers are installed in the section which has a specification as follow;

    Rated Power: 96 kVARated Voltage: 415 V

    Rated Current: 133.6 A

    Engr. Syed Muhammad Munavvar Hussain 31

  • 7/23/2019 Thermal Power Station Report

    32/36

    Thermal Power Station phase-II

    Each transformer follows a 3-phase thyrister rectifier converting the 3-phase AC into DC

    supply which is given to the electrolyzers. The thyrister converters can provide the 60 V, 1250 A

    DC supply to the electrolyzers. .

    Electrolyzer:

    The process of electrolyses of the water takes place in the electrolyses.

    The process in which DC current is passed through the water resulting the separation of

    the cation and anion is known as electrolyses.The electrolyzer has 25 cells each takes 2.2 V, a total of 55 V DC and a maximum current

    of 1000 A. The separated hydrogen and oxygen then leaves the electrolyzer on its own ways.

    Separating Column:

    The hydrogen leaving the perforated flash box (PFB) enters the separating column which

    removes the small parts of alkali from it

    Gas Scrubber:Gas scrubber is also called gas washer. It removes the impurities from the hydrogen such

    as dust particles etc.

    Dryer:

    The dryer dry the hydrogen coming out from the gas scrubber. As gas scrubber do the

    washing of the hydrogen gas so it has to be dried.

    Receiver Tanks:

    The receiver tanks store the prepared hydrogen gas. For this purpose 06 receiver tanks areused. The pressure inside the tanks is kept 10kg/cm2.

    03 tanks are for oxygen and 03 are for carbon dioxide storage.

    Demineralization plant

    The water which is free of all the impurities, minerals, gases like Oxygen Nitrogen and

    consists of only pure water (H2O) is called demineralized water.Demineralized plant is used for the preparation of demineralized water. Demineralized

    water is used for the preparation of steam, for the cooling of stator of generator and for the

    cooling of thyristors in the excitation system.

    Engr. Syed Muhammad Munavvar Hussain 32

  • 7/23/2019 Thermal Power Station Report

    33/36

    Thermal Power Station phase-II

    The plant has total generation capacity of 90 tons/hour. Raw water is used for the

    preparation of the demi water. Raw water is pumped out by the tube wells and stored in the raw

    water storage tanks.Demi water is passed through the hollow conductors of stator winding for the stator

    cooling. It is used for this purpose because demi water acts as an insulator & has a resistivity of

    200kOhms.it does not short circuit the windings. Demi water is used for the steam preparation inthe boiler for the following reasons:

    Raw water contains mineral like Calcium, Magnesium and sulphur. These minerals cause

    the stacks and corrosion in the boiler tubes which causes the heat loses and may damage theboiler tubes. The designed loss of the demi water in the steam cycle is 2%. Make up demi water

    is done in the hot well and feed water tank.

    A generalized layout of the demi water plant is shown in the figure below;

    .

    _____________________________________________________________________________

    _

    Mech. Clarifier filters:In mechanical clarifier filter coal and gravels are is used to remove the unresolved

    particles from the water.

    Cation filter:

    In the cation filter resins is used which replaces the Na+ & Ca2+ ions in the water from the

    H+ ions. In the end water becomes acidic.

    Engr. Syed Muhammad Munavvar Hussain

    Raw Water

    Mixed bed

    Anion Filter

    Cation filterMech.

    Clarifier filter

    Storage tank

    Decarbonized

    Exhaust

    Cation 2nd

    filter

    Preparation of demineralized water

    33

  • 7/23/2019 Thermal Power Station Report

    34/36

    Thermal Power Station phase-II

    Decarbonizer exhaust:

    It removes the carbonates from the water.CO2 is removed by showering of the water

    against air. It is also known as degasifier.

    Anion filter:

    In Anion filter castic soda (NaOH) is used which replaces the Cl-

    or SO4 ions with theOH- ions forming partial demi water.

    Cation 2nd filter:

    It also removes the positive ions from the water.

    Mixed filter:

    In the mixed filter both the remaining anions and cations are removed. The water leavingthe mixed bed is the pure distilled water.

    Storage tanks:

    This prepared demineralized water is then stored in the storage tanks.

    Water treatment:

    Ammonium hydroxide, Hydrazine and Trisodium phosphate are dozed at different points

    in the boiler such as boiler drum, for water treatment.

    The nature of this water is acidic, to minimize the acidity of this water ammonium hydroxide

    (NH4OH) is used.Hydrazine (N2H4) removes the Oxygen from water and protects the boiler tubes against

    corrosion.

    Trisodium phosphate (Na3PO4) is used in the boiler drum which removes the Ca, Mg and addsNa.

    Oil Testing Lab:

    Different tests of the furnace oil and the lubrication oil are performed in the oil testing

    laboratory to check their characteristics.

    The test on the transformer oil is also performed in this lab.

    The following tests are performed on the furnace and lube oil:-

    1. Moisture test

    Engr. Syed Muhammad Munavvar Hussain 34

  • 7/23/2019 Thermal Power Station Report

    35/36

    Thermal Power Station phase-II

    2. Flash point test.

    3. Viscosity test.

    4. Specific gravity test.5. Acidity test.

    6. Solubility test.

    7. Mechanical impurity test.8. Chlorification test.

    LIST OF SYMBOLS AND ABBREVATIONS

    TPS Thermal power stationG/R GeneratorT/F TransformerT/R Transformer

    Engr. Syed Muhammad Munavvar Hussain 35

  • 7/23/2019 Thermal Power Station Report

    36/36

    Thermal Power Station phase-II

    M.T Main TransformerA.T Auxiliary TransformerH.V.S High Voltage SideL.V.S Low Voltage SideB.B Bus Bar

    A.S.B Auxiliary System BusC.B Circuit BreakerC.T Current TransformerP.T Potential TransformerR.C Relay CoilL.A Lightning arrestorTemp. TemperaturePCB Printed Circuit BoardICs Integrated Circuits

    MW Mega WattMVAR Mega Volt Ampere ReactiveMVA Mega Volt AmpereEMF Electromotive force

    AC Alternating currentDC Direct current