thermselect - esi · 1. safety thermselect® 4/100 1 safety 1.1 general assembly, commissioning and...

100
ThermSelect ® As of 9 March 2011

Upload: others

Post on 09-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® As of 9 March 2011

Page 2: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

Table of Contents

1 Safety ............................................................................................................................................................ 4 1.1 General .......................................................................................................................................................................... 4 1.2 Intended use .................................................................................................................................................................. 5 1.3 Explanation of symbols .................................................................................................................................................. 6 1.4 Personnel requirements ................................................................................................................................................ 7 1.5 Special dangers ............................................................................................................................................................. 8

2 Standards and Regulations ...................................................................................................................... 11 2.1 Standards and Regulations ......................................................................................................................................... 11

3 Transport, Packaging, Storage ................................................................................................................ 14 3.1 Safety notes for transport ............................................................................................................................................ 14 3.2 Inspection of the delivery ............................................................................................................................................. 15 3.3 Notes on storage ......................................................................................................................................................... 15 3.4 Handling of packaging material ................................................................................................................................... 15 3.5 Disposal of packaging ................................................................................................................................................. 16 3.6 Disposal of the device ................................................................................................................................................. 16

4 General ....................................................................................................................................................... 17 4.1 Product description ...................................................................................................................................................... 17 4.2 What is included .......................................................................................................................................................... 18 4.3 Accessories ................................................................................................................................................................. 18

5 Technical data ............................................................................................................................................ 20 5.1 Dimensions and connection ratings ............................................................................................................................. 20 5.2 Identification plate ........................................................................................................................................................ 22 5.3 Technical data ............................................................................................................................................................. 24 5.4 Electrical data .............................................................................................................................................................. 26

6 Installation .................................................................................................................................................. 36 6.1 Safety during assembly ............................................................................................................................................... 36 6.2 Requirements on the erection location of the heat pump ............................................................................................ 36 6.3 Assembly tools ............................................................................................................................................................ 39 6.4 Installation information ................................................................................................................................................. 39 6.5 Hydraulic connection ................................................................................................................................................... 50 6.6 Electrical connection .................................................................................................................................................... 52

Page 3: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

Table of Contents

7 Commissioning ......................................................................................................................................... 62 7.1 Safety during startup ................................................................................................................................................... 62 7.2 Inspection prior to startup ............................................................................................................................................ 62 7.3 Commissioning ............................................................................................................................................................ 63 7.4 Setting the controller .................................................................................................................................................... 65 7.5 Parameterisation ......................................................................................................................................................... 66 7.6 Commissioning record ................................................................................................................................................. 66

8 Maintenance ............................................................................................................................................... 67 8.1 Maintenance ................................................................................................................................................................ 67 8.2 Components relevant to safety .................................................................................................................................... 68 8.3 Work to be carried out ................................................................................................................................................. 68 8.4 Spare part drawing and legend .................................................................................................................................... 72

9 Troubleshooting ........................................................................................................................................ 73 9.1 Troubleshooting ........................................................................................................................................................... 73

10 Warranty ..................................................................................................................................................... 76 10.1 Warranty ...................................................................................................................................................................... 76 10.2 Manufacturer Certificate / EU Design Conformity Declaration ..................................................................................... 79 10.3 Proof of Service ........................................................................................................................................................... 81

11 Hydraulic diagrams ................................................................................................................................... 86 11.1 Hydraulic diagrams ...................................................................................................................................................... 86

12 Index ........................................................................................................................................................... 98

Page 4: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

1. Safety ThermSelect®

4/100

1 Safety

1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating companies. - Contains important information for safe handling of the device.

Compliance with all specified safety information and handling in-structions is the prerequisite for safe working.

- Must be following by all persons working on the device. The information contained in this document is accurate and up to date to the best of our knowledge at the time of writing. The information provided serves as a reference for the safe operation of the product named in the Assembly, Startup, and Maintenance Instructions. The information provided is not transferable to any other products.

Safekeeping of documentation

NOTE! These instructions must remain on the device, so that they are also available if required later. With a change of operator, the instructions must be handed over to the subsequent operator.

Page 5: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 1. Safety

5/100

1.2 Intended use The devices are intended as heat sources for closed warm water central heating systems and for central warm water preparation. Any other or more comprehensive use is not as intended. MHG Heiztechnik does not assume any liability for consequential damages. The risk will be borne by the owner of the equipment alone. MHG devices have been built in accordance with the applicable standards and guidelines as well as the valid safety rules. However, personal injuries or property damage may occur if not used properly. To avoid hazards, the device may only be used: - For its intended purpose - In a proper condition, in terms of safety equipment - In compliance with the instructions for Assembly, Startup and

Maintenance, as well as the operating instructions - In compliance with the necessary maintenance activities - In compliance with the technologically required minimum and max-

imum values - If malfunctions that may compromise safety have been remedied

immediately - If all of the safety and warning signs attached on and in the device

are not removed and remain legible

CAUTION! Device damage through weather impacts! Electrical hazard through water and corrosion of the enclosure and the components. Therefore: - The internal unit may not be operated outdoors. It is

suitable only for operation in rooms.

CAUTION! System damage from frost! The heating system can freeze in case of frost. Therefore: - Leave the heating system in operation during a

frost period, so that the rooms are sufficiently tem-pered. This also applies in the case of the opera-tor's absence or if the rooms are vacant.

Page 6: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

1. Safety ThermSelect®

6/100

1.3 Explanation of symbols The section provides an overview of all important safety aspects for optimum personal safety, as well as for safe and fault-free opera-tion. The handling instructions and safety notes specified in these instruc-tions must be followed to prevent accidents, personal injuries and property damages.

DANGER! … indicates life-threatening situations due to electric current.

WARNING! … indicates a possibly hazardous situation, which can lead to death or serious injuries, if not avoided.

PRECAUTION! … indicates a possibly hazardous situation, which can lead to minor or slight injuries, if not avoided.

CAUTION! ... indicates a possibly hazardous situation, which can lead to property damage, if not avoided.

NOTE! ... highlights useful tips and recommendations, as well as information for efficient and fault-free opera-tion.

Page 7: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 1. Safety

7/100

1.4 Personnel requirements

WARNING! Danger to life if not sufficiently qualified! Improper handling leads to considerable personal injuries and property damages. Therefore: - Assembly, startup and maintenance works, repairs

or change to the set fuel quantity may only be car-ried out by a heating and/or air conditioning professional.

- Consult professionals in case of doubt. The following qualifications for various task areas are listed in the instructions: - Equipment operator

must be informed about the handling of the equipment; in particu-lar, he must receive the operating instructions for the device. He is responsible for the proper operation of the system and must en-sure that it is regularly serviced by a specialist fitter.

- Technical personnel are able because of their technical training, know-how and expe-rience as well as knowledge of the relevant regulations to carry out the work activities assigned to them and to detect possible dangers on their own.

- Cooling systems technician must provide certification in accordance with Article 5 of the Commission Regulation (EC) No 303/2008 establishing, pursuant to Regulation (EC) No 842/2006 of the European Parliament and of the Council. 2, Sentence 1 of ChemKlimaschutzV (Chemicals- Climate Protection Regulation)

Page 8: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

1. Safety ThermSelect®

8/100

1.5 Special dangers In the following section the remaining risks are specified which result based on the risk analysis. The safety information listed here and the warning instructions in the subsequent chapters of this manual must be followed to reduce health risks and to avoid dangerous situations.

Electrical current

DANGER! Risk to life through electrical current! Contact with live components can cause serious inju-ries. Therefore: - Work on electrical systems may only be performed

by professional electricians. - Turn off electric power before beginning the work

activities and secure against being turned on again.- In case of damaged insulation, immediately cut off

the power supply and initiate the repair.

Hot surfaces

PRECAUTION! Risk of burning from hot surfaces! Contact with hot components can cause burns. Therefore: - Always wear protective gloves when working near

hot components. - Make sure that all components have cooled down

to the ambient temperature before commencing any work.

- Do not touch the compressor and hot gas line dur-ing operation.

Page 9: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 1. Safety

9/100

Refrigerant The safety datasheet concerning refrigerant R 407 C is available for download at www.mhg.de\Download\Sicherheitsdatenblätter.

NOTE! in case of emergencies, ring the telephone number below: +44(0)208 762 83 22 [CareChem 24] (Europe)

WARNING! Danger to life through lack of oxygen! Vapours of the refrigerants R 407 C are heavier than air and may cause suffocation by displacing oxygen. Therefore: - Exercise special caution when entering lower lying

closed rooms. - Work on the refrigerant circulation may only be per-

formed by persons possessing a refrigeration cer-tificate in accordance with ChemKlimaschutzV.

- Do not smoke when handling refrigerant as its products of decomposition in the lit cigarette act as an irritant and a poison!

PRECAUTION! Risk of injury due to refrigerant! Refrigerant is corrosive and causes cold burns upon contact with skin. Therefore: - Wear chemical-resistant protective gloves when

handling refrigerant at any time. - Wear protective glasses to avoid contact with eyes.

Page 10: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

1. Safety ThermSelect®

10/100

Changes to the device WARNING! Risk of life through electrical shock as well as de-struction of the device from water leakage! The operating permit becomes void when making modifications to the device! Therefore: Do not make any modifications to the following items: - To the safety valve and to the outlet line for the

heating water - To structural circumstances, which can have an

influence on the operating safety of the device. - Opening and/or repairing original parts (e.g. drive,

controller)

WARNING! Risk to life and damage to the environment through refrigerant leakage! The operating permit becomes void when making modifications to the device! Therefore: Do not make any modifications to the following items: - To the interior or exterior unit of the device - On the lines for water, electrical power and refrige-

rant

Heating water

WARNING! Risk of poisoning through heating water! The use of heating water leads to poisoning. Therefore: - Never use heating water as drinking water because

it is contaminated from dissolved deposits.

Page 11: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 2. Standards and Regulations

11/100

2 Standards and Regulations

2.1 Standards and Regulations The following standards and regulations must be observed with the installation and operation of the heating system.

Standards

Standards Publication date Title

DIN EN 12056 01.2001 Drainage systems

DIN EN 12502 01.2001 Corrosion protection of metallic ma-

terials

DIN EN 12828 06.2003

Heating systems in buildings, safety equipment of warm water heating systems

DIN EN 60335, Part 1 2004 Safety of electrical appliances for

household and similar purposes

DIN 1986 --- Materials drainage system / Proper-ty drainage

DIN 1988 12.1988 Technical rules for drinking water installations (TRWI)

DIN 4726 01.2001 Plastic pipes for warm water floor heating

DIN 4753 03.1988 Water heaters and water heating systems for drinking and service water

DIN 18380 10.2006 Heating systems and central water heating systems (VOB)

Regulations

The erection and operation of the heating system requires com-pliance with the technical building supervision rules as well as other legal stipulations of the individual countries.

Regulations Publication date Title

EC Regula-tion No 842/2006

07.2006

F-Gas Directive regulates all chlorine-free fluori-nated refrigerants (CFC and HFC, i.e. R134A, R404A, R407C, R410A, R507)

EnEV (Ger-man Energy Conservation Regulations)

12.2004 Energy savings directive

ATV ---

Worksheet ATV-A 115 "Discharging non-household waste water into a public waste water sys-tem"

Page 12: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

2. Standards and Regulations ThermSelect®

12/100

Regulations Publication date Title

TA Noise 03.2000

Sixth General Administrative Regu-lation to the Federal Immission Con-trol Act (Technical Instruction on Noise Protection)

TRGS 521 Part 4 --- Technical rules for hazardous sub-

stances

VDI 2035 12.2006

Guidelines for the prevention of damages in warm water heating systems - calcification in drinking water heating systems and warm water heating systems

VDE --- Stipulations and special require-ments of the public utility companies

Additional Standards / Regulations for Austria

In Austria, the local building regulations as well as the ÖVGW regu-lations must be observed with the installation.

Standards Publication date Title

ÖNORM EN 14336 2004 Heating systems in buildings - Plan-

ning of warm water planning systems

ÖNORM H 5195-1 05.2006

Prevention of damages through cor-rosion and calcification in closed warm water heating systems with op-erating temperatures up to 100 °C

ÖNORM M 7550 02.2002

Boilers with operation temperatures up to 100 °C - Terms, requirements, tests, designations

Page 13: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 2. Standards and Regulations

13/100

Additional Standards / Regulations for Switzerland

Assembly, startup and maintenance may only be carried out by an approved installation company. Work on electric system compo-nents may only be carried out by a licensed electrical technician. The legal standards and stipulations on electrical installations must be followed, especially:

Directives / Guidelines by

LRV Swiss air purification directive VKF Association of cantonal fire insurances SVGW Swiss association of gas and water technologies

SEV Swiss association for electrical, energy and in-formation technology

SWKI Swiss Association of Heating and Air Condition-ing Engineers

Gebäude-Klima Schweiz

Association of the Heat, Ventilation and Air Con-ditioning Technology Industry

GebäudeKlima Schweiz Technical Bulletins

(formerly PROCAL)

Corrosion damages through oxygen in heating water - oxygen cor-rosion Corrosion through halogenated hydrocarbons Information regarding corrosion damage from water heating Procal / AWP Guideline on the processing and quality of water in the heating system Procal / AWP

BUWAL Technical Bulletins

Approval of systems with refrigerants stable in air

Page 14: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

3. Transport, Packaging, Storage ThermSelect®

14/100

3 Transport, Packaging, Storage

3.1 Safety notes for transport CAUTION! Damage through improper transport! Significant property damage may be incurred by im-proper transport. Therefore: - Be careful when unloading packaging items upon

delivery as well as during in-plant transport and obey the symbols on the packaging.

- Do not expose the device to hard shocks. - Use only the intended slinging points. - Remove the packaging only shortly before assem-

bly.

CAUTION! Device damage through improper handling! The machine oil shifts. Therefore: - The heat pump may only be transported standing

and never horizontally. - The heat pump may only be tilted up to 45° for a

short time.

CAUTION! Device damage through improper handling! The copper pipes can be easily bent! Therefore: - Do not hold on to the insulated pipe (hot gas line)! - Apply force only to the base plate or the frame!

PRECAUTION! Risk of injury through improper handling! Improper handling can cause injuries like contusions, cuts and bruises. Therefore: - Personal safety equipment: Safety shoes and safety

gloves must be worn for handling and transport.

Page 15: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 3. Transport, Packaging, Storage

15/100

3.2 Inspection of the delivery Inspect the delivery immediately upon receipt for completeness and transport damages. Proceed as follows when noting eternally visible transport damages: - Do not accept the delivery or only conditionally. - Note the extent of the damage on the transport documents or the

delivery bill of the freight forwarder. - Initiate complaint.

NOTE! Report each defect as soon as it is detected. Damage compensation claims can only be asserted within the respective claim periods.

3.3 Notes on storage The shaft of the circulation pump may seize during extended sto-rage. Moisture condensation, icing and water impact are not permitted. Temperature range: -10°C … +50°C Humidity: < 95% rel. hum.

3.4 Handling of packaging -material

WARNING! Risk of suffocation from plastic foils! Plastic foils and bags, etc. can become a dangerous toy for children. Therefore: - Do not allow packaging material to lie carelessly

about. - Packaging material must never get into the hands

of children!

Page 16: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

3. Transport, Packaging, Storage ThermSelect®

16/100

3.5 Disposal of packaging Recycling: The entire packaging material (carton material, routing sheets, plastic foils and pouches) are completely recyclable.

3.6 Disposal of the device

NOTES FOR DISPOSAL! - The device contains electrical and electronic com-

ponents. - Please do not dispose of device or replaced parts in

household waste. Proper disposal of hazardous waste is required.

- End-of-life devices must be taken to the respective public collection point for proper disposal.

- Disposal must be in accordance with current local laws and regulations.

CAUTION! Environmental damage due to improper disposal! Refrigerant and compressor leak. Therefore: - In accordance with EC Regulation No 842/2006, op-

erators of stationary facilities are responsible for putting in place arrangements for the proper recov-ery of fluorinated greenhouse gases by certified personnel to ensure their recycling, reclamation or destruction.

Page 17: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 4. General

17/100

4 General

4.1 Product description ThermSelect® is is available in the versions,

• ThermSelect® • ThermSelect® Pro • ThermSelect® Sun • ThermSelect® Sun Pro

and with extensive accessory sets. The standard sizes are available for a capacity range from 10.4-40.9 kW. ThermSelect® mode of operation Ground or air heat are alternatively used after specifying a bivalence point. ThermSelect® Pro mode of operation Ground and/or air heat are used in parallel or alternatively. ThermSelect® Sun mode of operation Ground or air heat are alternatively used on the source side and so-lar heat on the sink side. ThermSelect® Sun Pro mode of operation Ground and air heat plus solar heat are used on the source side, so-lar heat is fed into the heat sink if there is an excess. Inner part: - Combined, space-saving air-brine/water heat pump hybrid system

in a compact design with 2 integrated, weather-controlled heat pump controllers

- Size width x depth x height • Version 1:: 690x600x900 • Version 2: 1,030x730x900

- Quiet running through sound-decoupled cooling unit, low noise de-velopment through sound-decoupled compressor and sound-insulated housing

- High-performance evaporator for brine operation - Outdoor temperature sensor, as well as flow and return heat pump

sensors, heat source inlet air, heat source inlet and outlet brine, evaporation, suction gas, refrigerant liquid and hot water sensor included in the scope of delivery

- Refrigerant R 407 C for heating water temperatures up to 55 °C at outside temperatures up to -7 °C

- Min. outside temperature -15 °C (constant mode) Outer part - Air evaporator with enlarged lamella spacing, as well as under-

cooling coil, drip plate heating, bend and expansion valve - Whisper ventilator with highly efficient electronic motor - Weather-resistant design with snow protection roof - Colour: Light-grey (RAL 7035) - Condensation drainage on gravel bed

Page 18: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

4. General ThermSelect®

18/100

4.2 What is included - Heat pump with interior and exterior unit, including 2 heat pump

controllers RVS 61.483 and 2 control units AVS 37.294 - From ThermSelect 10 soft-start control - Module for thawing the split evaporator via hot-gas bypass con-

trols

4.3 Accessories

Control unit QAA 75 94.88147-5019

Cable-linked control unit optionally usable as a control unit, service device or room device. Setting of all parameters in the RVS control-ler, mode reserve for time greater than 12 hours

Control unit QAA 78 94.88147-5021

Radio-linked control unit optionally usable as a control unit, service device or room device. Setting of all parameters in the RVS control-ler, range of radio link approx. 30 m

Radio module AVS 13.399/201 94.88147-5022

Transmitter and receiver for external temperature sensor QAC 34

Repeater AVS 14.390/101 94.88147-5017

Range expansion for controller RVS 61.843 The radio repeater is used for rand expansion. It is not an amplifier, but rather, a device for receiving and forwarding signals.

Contact temperature sensor QAD 36.101 94.19314-5015

NTC 10 kOhm

Page 19: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 4. General

19/100

Service water sensor QAZ 36 94.19314-5013 (2 m) 94.19314-5012 (6 m)

Service water sensor QAZ 36 for recording the hot water storage temperature for Boiler Management Unit LMU and RVS with con-nection cable 2x0.5 mm², NTC 10 kOhm, 10000 Ohm at 25°C.

Collector sensor QAZ 36.481/101 94.19314-5018 (1.5 m)

For RVS or LMU

Additional heater 6.0 kW 98.38400-6302

Additional electric heater 6.0 kW (3 x 2 kW, 400 V) incl. contactor and connection cable set for controller RVS 61.843

Reservoir

Heat pumps require special reservoirs. MHG carries all required special high-capacity buffer and zone reservoirs in its program.

Page 20: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

5. Technical Data ThermSelect®

20/100

5 Technical data

5.1 Dimensions and connection ratings

Connections at rear wall of heat pump

Sk09-6200-023_aStand: 06.11.09

Fig. 1: Connections at rear wall of heat pump ThermSelect 15 (Version 1) schematic diagram. The device illustrated does not cor-respond to the supplied interior unit.

Fig. 2: Connections at rear wall of heat pump ThermSelect 19 to

41 (Version 2)

Page 21: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 5. Technical Data

21/100

Erection measurements and dimensions, split evaporator for ThermSelect®

Fig. 3: Erection measurements and dimensions, split evaporator for ThermSelect®

Legend for Fig. 3:

Abbreviation Meaning ThermSelect®... 15 19 28 34 41

1 Fluid line 15 18 22 2 Suction gas line 28 35 42 3 Hot-gas thawing 12 15 18

A Weather guard in mm 2155 3080 B Floor mount in mm 1880 2805 C Min. distance to walls and obstacles > 200 mm D Min. distance to walls and obstacles > 500 mm

EAL Electrical connection of fan (split evaporator) 3x0.75 mm² supply line 0-10 V signal 2x0.75 mm²

FA Foundation Take note of the following information! KB Gravel bed min. 250 mm deep KRS Refrigerant pipe connection STR Direction of flow

ZAF Supply line temperature sensor 2x2x0.75 mm² (see also page 34 "Electrotechnical data controller")

NOTE! It Fig. 3 represents a schematic diagram. It is not to be used instead of a professional layout de-signed by professionals. The foundation and the gravel bed must reach at least across a width of 400 mm. The gravel bed must reach up to approx. to the foundation.

Page 22: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

5. Technical Data ThermSelect®

22/100

5.2 Identification plate

Fig. 4: Sample identification plate

Page 23: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 5. Technical Data

23/100

Legend for Fig. 4:

Abbrev-iation Meaning

1 Type 2 Part no. / Item number 3 Country of destination 4 Serial number 5 Refrigerant 6 Refrigerant dosage 7 Output A2/W35 8 Output B0/W35 9 Output W10/W35

10 Output W7/W35 11 Rated thermal output 12 max. positive operating pressure 13 max. flow temperature 14 Pressure limiter 15 Electric connection 16 Power consumption 17 Power current 18 Control current 19 Rated current 20 Operating current 21 Starting current (compressor) 22 Protection class 23 Manufacturer 24 CAUTION HIGH VOLTAGE

Page 24: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

5. Technical Data ThermSelect®

24/100

5.3 Technical data

Air+Brine/Water Head Pumps* ThermSelect® 15 to 41

ThermSelect®.. 15 19 28 34 41

Output A2/W35* Nominal heating capacity kW 16,2 20,5 28,8 35,4 43,0 Power consumption condenser* kW 3,3 4,6 6,1 7,5 9,2 Cooling capacity* kW 13,0 16,1 23,1 28,2 34,3 Performance number* COP 4,7 4,4 4,6 4,5 4,5 Output B0/W35* Nominal heating capacity kW 15,1 19,1 26,9 33,1 40,2 Power consumption condenser** kW 3,3 4,5 6,0 7,4 9,0 Cooling capacity** kW 12,0 14,9 21,2 26,0 31,7 Performance number** COP 4,4 4,1 4,3 4,3 4,3 Refrigerant R 407 c for hot water temperatures up to 55 °C Refrigerant dosage for max. 20 m line length*** kg 10,0 12,0 15,5 20,2 20,7

Refrigerant lines Liquid (1)

mm 15 18 22

Suction gas (2) 28 35 42 Thawing (3) 12 15 18

Nominal power consumption A 7,4 12,6 14,3 16,2 18,6 Operating current, max. A 11,8 16,0 21,0 25,0 32,0 Starting current with soft-start A 37,0 49,5 63,5 83,5 99,0 Blocked rotor current A 74,0 99,0 127,0 167,0 198,0 Power circuit breaker / Automatic circuit breaker, slow (C characteristic) A 3x25 3x32 3x40 3x63

Recommended wire gauge mm² 3x4.0 3x6.0 3x10.0Electric connection Compressor control current 3NPE, 400 V

1NPE, 230 V Protection class heat pump according to EN 60529 IP 40

Protection class split evaporator according to EN 60529 IP 54

Evaporated air flow rate, nominal m³/h 5220 6670 10820 16010 14800 Sound pressure at 5 m dB (A) 35 41 43 53 53 Mass flow heating system nominal kg/h 2630 3340 4700 5780 6900 Pressure loss heating water at nominal flow rate kPa 5,8 3,2 4,5 4,2 5,2 Heating connection AG“ 1 1½ Outer dimensions W x D x H inner part mm 690x600x900 1030x730x900 Outer dimensions W x D x H outer part mm 2155x880x1030 3080x880x1030 Weight of inner part kg 198 225 238 250 258 Weight of outer part kg 138 152 202 223

* Heating capacity and COP at A2/W35 as well as source side 3 K and heating side 5K spread ** Output ratings at B0/W35 as well as source side 3K and heating side 5K spread *** When changes to refrigerant lines lead to lengths exceeding 20 m, refrigerant dosage will change as follows: Pipe

with max. Ø 22 mm +/- 100 g/m, pipe with max. Ø 28 mm +/- 150 g/m, pipe with max. Ø 35 mm +/- 200 g/m

NOTE! Refrigerant R407C for heating water temperatures up to H55 °C.

Page 25: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 5. Technical Data

25/100

Page 26: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

5. Technical Data ThermSelect®

26/100

5.4 Electrical data

Circuit diagram for ThermSelect® 15

AVS37.294/209

RVS 61.843

KP

Stand: 10.05.2010Sk10-0504-165

VER

M1

S1

LG

NOTHS

(STf) (NTf)

V-SPMV-A MV-Hz MV-FLL MV-FLL

22

L PE N E9 E10 Ex1 Ex2 Ex3 Ex4 Ex5 Ex7 K1 N PE Q3 N PE Y2 N PE N PE PE Qx2 N PE Qx3 N PE Qx4 Qx5 NPE Y1 N Q9 Qx1 NE11 Q8K19

Q2Ex6 PE Qx6

MUXMBx5MBx4MBx3MBx2MBx1MB84MB91MB71MB1MB21MB9MB92

B3MB81H3MH1CL- G+CL+CL-CL+CL-CL+MBDBX50X30

ZYXWVUTSRQPKL PE N

Zyxwutsrqpnkhfebbba

A2

A1

K614

QP

RVS 61.843

RL-WP

QE QA SG

7

A2

A1

K714

111121

24

823

PKZM 0-...I > I >I >

Fig. 5: Sk10-0504-165

Circuit diagram for ThermSelect® 15

Page 27: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 5. Technical Data

27/100

Legend for Fig. 5:

Abbrevi-ation Meaning Abbrevi-

ation Meaning

- When using fault current circuit breakers, pay attention to separate neutral lead for normal and special tariff!

- Observe identical phase potential of the control circuits for normal and special tariff!

- The individual relay outputs of the heating controller withstand a max. load of 4 A (at cos Phi>0.6).

- Maximum total current for terminals: 6 A. - This must be noted with the selection of the circulation pumps. Use

contactor, if necessary.

KMT Refrigerant temperature liquid KP Condenser pump LG Performance limit M Motor M1 Condenser motor MV-A Solenoid refrigerant circulation thawing (normally closed) MV-FLL Solenoid refrigerant circulation liquid gas line (normally closed) MV-Hz Solenoid refrigerant circulation heating (normally closed)

A1 Relay coil L N / N1 Neutral lead A2 Relay coil N ND Pressure switch low pressure AF Outdoor temperature sensor NOT Control switch or emergency switch (if required) AVS 37 Control unit (NTf) Normal tariff F1 Fine-wire fuse condenser pump / ventilator split evaporator 4 AT QA Source output (sensor) F2 Fine-wire fuse controller RVS 61.843 4 A slow QE Source intake (sensor) HD Pressure switch high pressure QP Source pump HS Main switch RVS 61 Heat pump controller K2 Relay toggle heating/thawing RL-WP Return heat pump (sensor) K3 Relay condenser pump S1 Motor control unit RSHL K4 Relay ventilator split evaporator SG Suction gas K5 Relay output compressor air (STf) Special tariff K6 Relay output compressor brine V-SP Ventilator split evaporator K7 Relay source pump brine VDT Evaporator temperature K8 Relay heat requirement brine VER Compressor VL-WP Flow - heat pump

NOTE! Terminal assignment of the heat pump controller RVS 61 s. pages 32-32

Page 28: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

5. Technical Data ThermSelect®

28/100

Circuit diagram for ThermSelect® 19-41

AVS37.294/209

RVS 61.843

KP

Stand: 10.05.2010Sk10-0504-167

VER

M1

S1

LG

NOTHS

(STf) (NTf)

V-SPMV-A MV-Hz MV-FLL MV-FLL

22

L PE N E9 E10 Ex1 Ex2 Ex3 Ex4 Ex5 Ex7 K1 N PE Q3 N PE Y2 N PE N PE PE Qx2 N PE Qx3 N PE Qx4 Qx5 NPE Y1 N Q9 Qx1 NE11 Q8K19

Q2Ex6 PE Qx6

MUXMBx5MBx4MBx3MBx2MBx1MB84MB91MB71MB1MB21MB9MB92

B3MB81H3MH1CL- G+CL+CL-CL+CL-CL+MBDBX50X30

ZYXWVUTSRQPKL PE N

Zyxwutsrqpnkhfebbba

A2

A1

K614

QP

RVS 61.843

RL-WP

QE QA SG

7

A2

A1

K714

111121

24

823

INT 69

PKZM 0-...I > I >I >

Fig. 6: Sk10-0504-167

Circuit diagram for ThermSelect® 19-41

Page 29: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 5. Technical Data

29/100

Legend for Fig. 5:

Abbrev-iation Meaning Abbrev-

iation Meaning

- When using fault current circuit breakers, pay attention to separate neutral lead for normal and special tariff!

- Observe identical phase potential of the con-trol circuits for normal and special tariff!

- The individual relay outputs of the heating controller withstand a max. load of 4 A (at cos Phi>0.6).

- Maximum total current for terminals: 6 A. - This must be noted with the selection of the

circulation pumps. Use contactor, if neces-sary.

KMT Refrigerant temperature liquid KP Condenser pump LG Performance limit M Motor M1 Condenser motor MV-A Solenoid refrigerant circulation thawing

(normally closed) MV-FLL Solenoid refrigerant circulation liquid

gas line (normally closed) MV-Hz Solenoid refrigerant circulation heating

(normally closed) N / N1 Neutral lead

A1 Relay coil L ND Pressure switch low pressure A2 Relay coil N

NOT Control switch or emergency switch (if required) AF Outdoor temperature sensor

AVS 37 Control unit (NTf) Normal tariff

F1 Fine-wire fuse condenser pump / ventilator split evaporator 4 AT

QA Source output (sensor) QE Source intake (sensor)

F2 Fine-wire fuse controller RVS 61.843 4 A slow QP Source pump HD Pressure switch high pressure RVS 61 Heat pump controller HS Main switch RL-WP Return heat pump (sensor) INT Winding protection INT S1 Motor control unit RSHL K2 Relay toggle heating/thawing SG Suction gas K3 Relay condenser pump (STf) Special tariff K4 Relay ventilator split evaporator V-SP Ventilator split evaporator K5 Relay output compressor air VDT Evaporator temperature K6 Relay output compressor brine VER Compressor K7 Relay source pump brine VL-WP Flow - heat pump K8 Relay heat requirement brine

NOTE! Terminal assignment of the heat pump controller RVS 61 s. pages 32-32

Page 30: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

5. Technical Data ThermSelect®

30/100

Sensor positions

T

T

T

T

T

T

49.1

49.2

48.2 42.6

42.348.1

T

42.442.2

42.5

T

49.0

48.0

Fig. 7: Sensor positions

Legend for Fig. 7:

De-scrip-tion

Termin-al RVS 61 Air

Termin-al RVS

61 BrineMeaning

T T Temperature sensor 42.2 B21 Sensor air-heat pump flow 42.3 B71 Sensor air-heat pump return 42.4 B21 Sensor brine-heat pump flow 42.5 B71 Sensor brine-heat pump return 42.6 Bx1 Sensor track flow (B10) 48.0 Bx2 Sensor refrigerant liquid air (B83) 48.1 B84 Sensor KM evaporator air (VDF) 48.2 Bx1 Sensor refrigerant suction gas brine49.0 B91 Sensor source inlet air (QE) 49.1 B91 Sensor source inlet brine (QE) 49.2 B92 Sensor source outlet brine (QE)

Page 31: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 5. Technical Data

31/100

Page 32: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

5. Technical Data ThermSelect®

32/100

Terminal assignment on the heat pump controller RVS 61

Z Y X W V U T S R Q P K N L

z y x w u t s r q p n k h f e b b b a

NVD1BWLHK1PHK1MWQP-SPLPMFA1

RG2RG1BWAT

VLWPMFE1

MFE2MFE3

MFE4 LPB

NDHD

MFE

-AM

FE-B

MFE

-CM

FE-D

MFE

-EM

FE-F

MFE

-G

MFA2MFA3

MFA4MFA5

MFA6

BSBH1

H2VL1RLWP

WQEWQA

MFE5MFA7

Fig. 8: Terminal assignment on the heat pump controller RVS 61

Legend for Fig. 8:

Ab-brevia-

tion Meaning

Ab-brevia-

tion Meaning

AT Outside temperature sensor plug k, terminals M, B9

MFE4 Multifunctional sensor input 4 (functions, see MFE1) plug x, terminals M, BX4

BSB Service tool OCI 700

plug b, terminals CL- (ground), CL+ (data)

MFE5 Multifunctional sensor input 5

(functions, see MFE1) plug y, terminals M, BX5

BW Service water sensor

plug k, terminals M, B3 MFE-A Multifunctional input A

e.g. external heat pump block, low tariff, over-load-compressor, overload-source, pressure controller-source, flow controller source, flow controller-consumer, thawing manual, collec-tive fault heat pump plug P, terminal EX1

BWL Service water load pump / reversing valve plug R, terminals Q3, , N

H1 Digital-/O..10V input plug e, terminals H3, M, H1

H2 Digital input plug f, terminals M, B81

HD High-pressure pressostat plug K, terminal E10

MFE-B Multifunctional input B (Functions, see MFE-A) Connector P, terminal EX2

HK1M Heating circuit mixer 1

plug T, terminals Y2 (mixer motor close), , N, Y2 (mixer motor open)

MFE-C Multifunctional input C

(Functions, see MFE-A) plug P, terminal EX3

HK1P Heating circuit pump 1

plug S, terminals Q2, , N MFE-D Multifunctional input D

(Functions, see MFE-A) plug P, terminal EX4

LPB BUS plug a, terminals MB, DB

Page 33: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 5. Technical Data

33/100

Ab-brevia-

tion Meaning

Ab-brevia-

tion Meaning

MFA1 Multifunctional output 1 e.g. collector pump, circulation pump, by-pass pump or heating circuit pump/electrical insert, generator shutoff valve plug W, terminal QX1, , N

MFE-E Multifunctional input E (Functions, see MFE-A) plug P, terminal EX5

MFE-F Multifunctional input F

(Functions, see MFE-A) plug P, terminal EX6

MFA2 Multifunctional output 2 (functions, see MFA1) plug W, terminal QX2, , N

MHE-G Multifunctional input G

(Functions, see MFE-A) plug P, terminal EX7

MFA3 Multifunctional output 3

(functions, see MFA1) plug X, terminals QX3, , N

N Power input

plug N, , L / terminal N, , L MFA4 Multifunctional output 4

(functions, see MFA1) plug Y, terminals QX4, , N

ND Low-pressure pressostat plug K, terminal E9

PLP Buffer loading pump plug V, terminals Q9, , N MFA5 Multifunctional output 5

(functions, see MFA1) plug Z, terminal QX5, , N

RG1 Room device 1

plug b, terminals G+, CL-, CL+ MFA6 Multifunctional output 6

(functions, see MFA1) plug Z, terminal QX6, , N

RG2 Room device 2 plug b, terminals CL-, CL+

RLWP Return sensor heat pump plug q, terminals M, B71 MFA7 Multifunctional analogue output

e.g. drinking water pump, intermediate cir-cuit pump, collector pump, solar pump, heating circuit pump plug z, terminals M, UX

VD1 Condenser compressor 1

plug Q, terminals K1, E11 VL1 Flow sensor heating circuit 1

plug p, terminals M, B1 MFE1 Multifunctional sensor input 1 e.g. buffer memory sensor, collector sen-sor, return sensor, drinking water sensor or swimming pool sensor plug t, terminals M, BX1

VLWP Flow sensor heat pump

plug n, terminals M, B21 WQA Heat source output

plug s, terminals M, B84/B92 MFE2 Multifunctional sensor input 2

(functions, see MFE1) plug u, terminals M, BX2

WQE Heat source input plug r, terminals M, B91

WQP-S Heat source pump/protection for pump plug U, terminals Q8/K19, , N MFE3 Multifunctional sensor input 3

(functions, see MFE1) plug w, terminals M, BX3

Page 34: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

5. Technical Data ThermSelect®

34/100

Electrotechnical data controller

Input (controller)

Rated voltage AC 230 V (± 10%) Rated frequency 50/60 Hz Max. power consumption 11 VA Fuse protection of supply lines max. 10 A slow Wire gauge internal resistance

1 wire: 1.0 mm2 - 1.5 mm2 > 100 kΩ

Terminal wir-ing (Outputs)

Wire or stranded wire (twisted or with wire end ferrule): 1 wire: 0.5 mm2...2.5 mm2 2 wires 0.5. mm2..1.5 mm2

Functional -data Mode of functioning according to EN 60730 1b (automatic function)

Inputs

Digital inputs H1, 3

Extra-low voltage for potential-free extra-low voltage capable contacts: Voltage with opened contact: DC 12 V Voltage at closed contact: DC 3 mA

Analogue input H1, 3 Extra-low voltage work area: DC (0...10) V internal resistance: > 100 kΩ

Line inputs EX1…EX7, E9-E11 AC 230 V (± 10 %) Internal resistance > 100 kΩ

Sensor input B9 Sensor inputs B1, B3, B4, B21, B41, B71, B81, B82, B91 and B92 Sensor inputs BX1…BX5

NTC1k (QAC34) NTC10k (QAZ36, QAD36) NTC10K (QAZ36, QAD36), PT 1000

Permitted sensor lines (Cu) At wire gauge: Max. length:

0.25 0.5 0.75 1.0 1.5 (mm2) 20 40 60 80 120 (m)

Outputs

Relay outputs Q2, Q3, Q8, Q9, QX1..QX6, Y1, Y2 Rated current range Maximum starting current Maximum total current (all relays) Rated current range

AC 0.02...2 (2) A 15 A during ≤1 s AC 6 A AC (24...230) V (for potential-free outputs)

Output Q4 Mod rated current range ON/OFF mode RPM controller Maximum starting current

AC 0.05...2 (2) A AC 0.05...1.4 (1.4) A 4 A during ≤1 s

Analogue output UX Output voltage Current load Ripple Precision zero point Error remaining area

Output is short-circuit-proof Uout = 0 ... 10.0 V ±2 mA RMS; ±2.7 mA peak ≤ 50 mVpp < ± 80 mV ≤ 130 mV

Page 35: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 5. Technical Data

35/100

Interfaces

BSB Max. line length base device-peripheral device Max. total line length Minimum wire gauge

2-wire connection, not interchangeable 200 m 400 m (Max. cable capacity: 60 nF) 0.5 mm2

LPB with controller-bus feed (per controller) with central bus feed bus load figure

Cu cable 1.5 mm2, 2-wire, not interchangeable250 m 460 m E = 3

Standards, safety, EMC, etc.)

CE conformity according to EMC guideline - stability - emissions Low-voltage guideline - electrical safety

2004/108/EC - EN 61000-6-2 - EN 61000-6-3 2006/95/EC - EN 60730-1, EN 60730-2-9

Page 36: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

36/100

6 Installation

6.1 Safety during assembly

WARNING! Risk of injury due to improper assembly! Improper assembly leads to serious personal injuries and property damages. Therefore: - Assembly and startup must take place by an autho-

rised heating and/or air conditioning professional. - Provide sufficient installation clearance before be-

ginning with the work. - Be careful with open components with sharp edges.

DANGER! Risk to life through electrical current! Contact with live components can cause serious inju-ries. Therefore: - Work on electrical systems may only be performed

by professional electricians. - Turn off electric power before beginning the work

activities and secure against being turned on again.

6.2 Requirements on the erection location of the heat pump

Before doing the installation, make sure that the erection location meets the following requirements: - Operating temperature +5 °C to +30� - Dry, frost-proof, good air supply and ventilation - No heavy dust build-up - No high humidity - No air pollution through halogenated hydrocarbons (e.g. in sol-

vents, adhesives, spray cans) - No sulphur compounds - No vibrations and shocks - Stable, smooth and horizontal surface

NOTE! In case of existing systems, a dirt filter must be in-stalled on the heating side to protect the condenser.

Systems with above average temperature loads also require consultation with MHG Heiztechnik.

Page 37: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

37/100

WARNING! Risk of life through fire! Easily flammable materials or liquids can catch fire. Therefore: - Do not use or store explosive or easily flammable

substances (i.e. fuel, paints, paper, wood) in the area where the device is installed.

- Do not dry or store laundry or clothes in the area where the device is installed.

- Do not operate device in explosive atmosphere un-der any circumstances.

The following aspects must be taken into consideration already dur-ing the planning of the system, in addition to proper dimensioning: - Future location of the heat pump under the aspect of sound

transmission through air and structure-borne sound. The acoustics in the erection rooms with reverberating walls can increase the operating sound significantly. Countermeasure: acoustic insulation on one of the opposite wall or ceiling surfaces.

- To reduce the structure-borne sound transmission, create a sepa-rate pedestal (e.g. heavy concrete) in mounted in floating fashion (e.g. on rubber).

- A pedestal is recommended for easier maintenance and care.

NOTE! MHG Heiztechnik recommends the installation of an oil sump-pump especially if the condenser is located shut off in a room for several hours (below 12 °C) and it becomes colder than the evaporator. This condition can occur especially in combination with special so-lar systems.

NOTE! Thorough planning with adequately dimensioned heat source is especially important for reasons of operational reliability and improved working output.

Page 38: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

38/100

Planning information for brine op-eration

The heat source for operation as a brine/water heat pump (horizon-tal absorber or vertical heating elements) must be configured in ac-cordance with the cooling capacity specified in the technical data. With the ThermSelect® version, the cooling capacity to be provided by the heat source can be reduced by up to 25%, as the source is not fully utilised over the entire heating period. With the ThermSelect® Pro version, the cooling capacity to be pro-vided by the heat source can be reduced by up to 50%, as the brine evaporator is exclusively operated in parallel with the air evaporator with outdoor temperatures of below approx. 5°C and the source is therefore utilised to a minor extent.

CAUTION! Freezing of the heat source due to incorrect operat-ing setting! Heat source becomes unusable for a long period of time. Therefore: - With this version, it is compulsory to exclusively

operate the brine evaporator in parallel with the air evaporator.

- A changeover to alternative mode, i.e. exclusive operation as a brine/water heat pump, overloads the heat source.

CAUTION! Freezing of the heat source due to incorrect dimen-sioning (overload)! Heat source becomes unusable for a long period of time. Therefore: - In case of doubt regarding the efficiency of the sur-

face, a geothermal response test must be carried out by an appropriate professional.

CAUTION! Damage to devices through freezing! The plate heat exchanger is destroyed on the source side, if the brine freezes. Therefore: - Monitor flow with safety devices (flow switch, pres-

sure switch). - The safety devices must be installed on site. The

regulations of the responsible authorities must be complied with.

Furthermore, dirt catchers, bubble separators and a rinsing device must be envisaged.

NOTE! Warranty becomes void if this information is disre-garded and damages can be traced to one of the listed causes.

Page 39: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

39/100

Application limits Heating water 20-55°C with refrigerant R 407 C

Installation clearances

Minimum clearances according to Fig. 3 are to be complied with, so that all work (assembly, startup, maintenance) can be carried out unhindered. - Observe the lateral clearance to the heat pump (min. 20 cm) to al-

low access for service and inspection.

6.3 Assembly tools The assembly and maintenance of the heating system requires standard tools from the field of heating installations, cooling installa-tion technology and water systems installations.

6.4 Installation information

CAUTION! Environmental damage through substances hazard-ous to groundwater! Substances hazardous to groundwater, such as greases, oils, refrigerants, solvent-based cleaning agents and the like, can burden the ground or get in-to the sewage system. Therefore: - These substances must be collected, stored and

transported in suitable containers and be disposed off.

The regulations of the heating and plumbing trade (DVGW, DIN, etc.) and of electrotechnics (potential equalization, utility company connection conditions, DIN, VDE, etc.) must be followed in particu-lar.

Page 40: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

40/100

Transport NOTE! The heat pump may only be transported standing and never horizontally.

The heat pump is delivered standing on a wooden pallet. It can be transported on the pallet to the installation site. The heat pump can also be transported by 2 persons with carrying straps or transport cart.

CAUTION! Device damage through improper handling! The copper pipes can be easily bent! Therefore: - Do not hold on to the insulated pipe (hot gas line)! - Apply force only to the base plate or the frame!

Refrigerant

The safety datasheet concerning refrigerant R 407 C is available for download at www.mhg.de\Download\Sicherheitsdatenblätter.

NOTE! in case of emergencies, ring the telephone number below: +44(0)208 762 83 22 [CareChem 24] (Europe)

WARNING! Danger to life through lack of oxygen! Vapours of the refrigerants R 407 C are heavier than air and may cause suffocation by displacing oxygen. Therefore: - Exercise special caution when entering lower lying

closed rooms. - Work on the refrigerant circulation may only be per-

formed by persons possessing a refrigeration cer-tificate in accordance with ChemKlimaschutzV.

- Do not smoke when handling refrigerant as its products of decomposition in the lit cigarette act as an irritant and a poison!

PRECAUTION! Risk of injury due to refrigerant! Refrigerant is corrosive and causes cold burns upon contact with skin. Therefore: - Wear chemical-resistant protective gloves when

handling refrigerant at any time. - Wear protective glasses to avoid contact with eyes.

Page 41: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

41/100

NOTE! For operators of equipment containing 3kg or more of refrigerant the following duties of documentation apply: - Amount and type of refrigerant - Any amounts of refrigerant refills - Any amounts of refrigerant retrieved during startup,

maintenance or final disposal - Details identifying the company or technical per-

sonnel that carried out the installation, startup, or any maintenance work

- Dates and results of all inspections The recorded information must be presented to the relevant authorities and the commission upon re-quest.

Welding work

NOTE! If any welding work is scheduled on the refrigerant line, a protective gas (i.e. nitrogen) will need to be passed through the pipe in order to prevent scale formation. Scale and other contamination impair the proper operation and lead to faults.

Split evaporator assembly

PRECAUTION! Risk of injury due to refrigerant! Refrigerant is corrosive and causes cold burns upon contact with skin. Therefore: - Wear chemical-resistant protective gloves when

handling refrigerant at any time. - Wear protective glasses to avoid contact with eyes.

- The location of the evaporator must always be higher than the

heat pump unit (on slopes, pay attention to laying of the cooling line).

NOTE! Always install the split evaporator in flow direction parallel to the property boundary (not towards the neighbouring plot) in order to reduce noise transmis-sion to neighbouring properties.

NOTE! Ensure that no plants or objects are located in flow direction in order to guarantee efficient operation.

Page 42: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

42/100

CAUTION! Device damage due to improper installation of cool-ing lines or improper positioning of the evaporator. Mechanical damage to the device can occur due to insufficient lubrication. Therefore: - Dimensioning and installation of cooling lines must

be carried out by technicians authorised by MHG. - The length of the cooling line may not exceed 15m

single distance. - The rise of the cooling line from the split evaporator

to the heat pump must not exceed 1.5 m. - The line dimensions are matched exactly to the capacity of the

heat pump (line length between heat pump and split evaporator 20 m). Altered line routing and clearances between heat pump and split evaporator must be agreed upon with MHG. Long line paths extend the duration of thawing and are to be avoided.

- The lines are insulated with diffusion-proof material. The gaps of the insulation must be glued.

CAUTION! Environmental damage due to improper assembly of the refrigerant line! Refrigerant and compressor oil can leak! Therefore: - Only use tools that are recommended for used in

the cooling unit: Bending wrench, pipe separator, deburrer and bordering tool

- Take note of bending radius to avoid bending or breaking of pipes.

- To avoid brittle or cracking pipes, do not bend the pipes repeatedly.

- In order to reduce loss of pressure and to ensure return of compressor oil, avoid unnecessary bend-ing of the pipes.

- Use appropriate fastening and insulation during refrigerant line installation.

- Use only non-cutting tools (special pipe cutting tools) to shorten refrigerant lines.

Page 43: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

43/100

CAUTION! Device damage through dirt and humidity. Dirt and humidity can enter the pipes when installing them. Therefore: - Make sure that no dirt or humidity enters the pipes

while installing them. - When laying pipelines underground, the laying

depth must be a minimum of 25 cm (on passable routes, a minimum of 50 cm).

- The installation of the pipelines must be carried out using a protective DN 100 pipe.

- The ends of the protective pipe must be sealed and waterproofed.

- The wall duct must be watertight. - Do not let clipping particles get into the refrigerant

line as these cause the destruction of the compres-sor.

NOTE! The heating pump contains refrigerant for a 15m max. length cooling line. Any shortening or lengthening of the line may only be carried out by a certified technician. The refrige-rant dosage must be checked for line lengths exceed-ing 20m, and be adjusted where required (approx. dosage values are available in chap. 5.3).

NOTE! The split evaporator contains a protective gas (nitro-gen) and must be evacuated simultaneously with the refrigerant lines.

NOTE! The technician must check the installation and mountings of the pipe, and establish a proper con-nection with the heating pump and the split evapora-tor.

NOTE! Ball valves must remain shut (delivery condition)!

Page 44: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

44/100

Fig. 9: Connections split evaporator

Legend for Fig. 9:

Abbrev-iation Meaning

1 Fluid line 2 Suction gas line 3 Hot-gas line 4 Sensor cable heat source evaporation

Page 45: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

45/100

Fig. 10: Sensor cable heat source inlet 5

Page 46: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

46/100

Heat pump installation The heat pump is delivered standing on a wooden pallet. Remove the foil/packaging and install the heat pump according to the following steps.

Fig. 11: Heating pump without enclosure

Fig. 12: Place the heat pump with the pallet next to the actual

erection location. Remove the transport locks 1 (marked in red) on the base plate of the heat pump and lift it to its final installation site.

Page 47: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

47/100

Fig. 13: Pre-assemble the enclosure ass seen in the image prior

to installing the hydraulic and cooling lines.

CAUTION! Water damage through condensation or humidity in the air! Extremely low temperatures at the refrigerant lines lead to condensation or humidity in the air and can cause water damage. Therefore: - The heat source lines are lined with diffusion-

resistant insulation which must not be damaged. - Installation-related damage must be closed again in

a diffusion-resistant manner with suitable refrige-rant pipelines.

- Contact between heat source lines carrying refrige-rant with ambient air, by ensuring insulation is sealed without any gaps and absolutely diffusion-resistant, must be ensured.

Fig. 14: Place the counter nut into the insulation and screw in the

cable gland.

Page 48: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

48/100

Connection of split evaporator with heat pump

PRECAUTION! Risk of injury due to refrigerant! Refrigerant is corrosive and causes cold burns upon contact with skin. Therefore: - Wear chemical-resistant protective gloves when

handling refrigerant at any time. - Wear protective glasses to avoid contact with eyes.

- Connect the heat pump and the split evaporator with the refrige-

rant lines.

CAUTION! Environmental damage due to improper assembly of the refrigerant line! Refrigerant and compressor oil can leak! Therefore: - Only use tools that are recommended for used in

the cooling unit: Bending wrench, pipe separator, deburrer and bordering tool

- Take note of bending radius to avoid bending or breaking of pipes.

- To avoid brittle or cracking pipes, do not bend the pipes repeatedly.

- In order to reduce loss of pressure and to ensure return of compressor oil, avoid unnecessary bend-ing of the pipes.

- Use appropriate fastening and insulation during refrigerant line installation.

- Use only non-cutting tools (special pipe cutting tools) to shorten refrigerant lines.

NOTE! The heating pump contains refrigerant for a 20 m max. length cooling line. Any shortening or lengthening of the line may only be carried out by a certified technician. The refrige-rant dosage must then be checked accordingly.

NOTE! The technician must check the installation and mountings of the pipe, and establish a proper con-nection with the heating pump and the split evapora-tor.

NOTE! Ball valves must remain shut (delivery condition)!

Page 49: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

49/100

Fig. 15: Heat pump connections

Legend for Fig. 15:

Abbrev-iation Meaning

1 Fluid line 2 Suction gas line 3 Hot-gas line

- Evacuate the suction, liquid and hot-gas lines. To evacuate the

devices, connect to the Schrader valves (s. Fig. 9). - After the evacuation has been completed, open the ball valves to

allow the refrigerant to distribute. The system is operational after the hydraulic and electrical installation has been made.

Page 50: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

50/100

6.5 Hydraulic connection

Requirements for the heat transfer liquid

The heat transfer liquid (brine) in the heat source should be set to frost protection of approx. -12°C. This is achieved with a water-glycol mixture with a share of 25% Tyfocor L (available as an acces-sory). The frost protection must be checked using a refractometer (availa-ble as an accessory) or similar testing device.

Requirements on the heating water

To prevent corrosion damage in the heating system, heating water in potable quality must be used under consideration of the require-ments according to VDI guideline 2035 "Preventing damage in warm water heating systems" / SWKI guideline 97-1 "Water quality for heating, steam, refrigeration and air conditioning systems".

CAUTION! Damage to devices/components from contamination! Partial clogging in the heat exchanger can lead to its destruction. Therefore: - For installations in older systems pre-filtration/silt

separation must be installed in order to protect the plate heat exchanger.

NOTE! Do not use any chemical additives!

Fig. 16: Hydraulic connections

Page 51: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

51/100

Legend for Fig. 16:

Abbrev-iation Meaning

1 Flow heat pump 2 Return heat pump 3 Inlet heat source brine 4 Outlet heat source brine

With the hydraulic connection, it must be ensure that the correct flow directions are adhered to. At the condenser, the in-flow is at the bot-tom (heating water return to heat pump). The temperature spread of 3-4 K at the heat source and 5- 10 K at the heat drop must be maintained under normal operating conditions while observing the application limits. This spread is nor-mally achieved when the volume flows specified in the technical da-ta are observed. In comparison to conventional combustion systems, heat pumps operate with larger mass flows. This results in larger pipe diameters and relevant pump configurations.

CAUTION! Device damage through improper system setup! Water and/or glycol mixture can leak. Therefore: - In the brine system, as well as on the heating side,

safety devices and expansion containers must be installed.

Page 52: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

52/100

6.6 Electrical connection

DANGER! Risk to life through electrical current! Contact with live components can cause serious inju-ries. Therefore: - When working on the device, all supply lines must

be without current. - Make sure that all electrical parts are without cur-

rent. - The applicable VDE and utility company regulations

as well as the respective regulations and guidelines of the country of destinations must be complied with.

- The electrical connections must be inspected by a responsible technician before establishing the con-nection with the line supply.

- An external separator (e.g. main switch) must be envisaged for all electrical supply lines to the ma-chine.

- Only operate the heat pump within the implementa-tion frequency (s. chapter 5.3 Type of electricity for compressor) (in Germany 50 Hz).

CAUTION! Interferences through electrical fields! Supply lines (230 V) may interfere with sensor lines (electrical low voltage). Therefore: - Sensor and supply lines may not be routed in the

same cable conduit.

Fig. 17: Overview of electric connections

Page 53: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

53/100

Fig. 18: Electrical connection ThermSelect® 15 -19

Legend for terminal diagram electrics board:

1 4 7 10 13 16 19 22 25 28

Con

dens

er

pum

p L

Ven

tilat

or L

Hea

t sou

rce

pum

p L

Nor

mal

tarif

f L

Win

ding

pro

tect

ion

INT6

9 L

Win

ding

pro

tect

ion

INT6

9 L*

Sol

enoi

d liq

uid

line

air L

Sol

enoi

d liq

uid

line

brin

e L

Sol

enoi

d he

ater

L

Sol

enoi

d th

aw-

ing

L

2 5 8 11 14 17 20 23 26 29

Con

dens

er

pum

p N

Ven

tilat

or N

Hea

t sou

rce

pum

p N

Nor

mal

tarif

f N

Pres

sure

sw

itch

high

pre

ssur

e L

Pres

sure

sw

itch

high

pre

ssur

e L*

Sol

enoi

d liq

uid

line

air N

Sol

enoi

d liq

uid

line

brin

e N

Sol

enoi

d he

a-te

r N

Sol

enoi

d th

aw-

ing

N

3 6 9 12 15 18 21 24 27 30

Con

dens

er

pum

p P

E

Ven

tilat

or P

E

Hea

t sou

rce

pum

p P

E

Nor

mal

tarif

f PE

Pres

sure

sw

itch

low

pre

ssur

e L

Pres

sure

sw

itch

low

pre

ssur

e L*

Sol

enoi

d liq

uid

line

air P

E

Sol

enoi

d liq

uid

line

brin

e P

E

Sol

enoi

d he

a-te

r PE

Sol

enoi

d th

aw-

ing

PE

The electrical connection occurs in accordance with the circuit dia-grams in chap. 0. The circuit protection in the distributor (meter cabinet) must be made with a 3-pole power circuit breaker (C-characteristics) according to the output ratings of the heat pump. The potential equalization is to be connected at the M6 or M8 connecting screw marked for this purpose.

Page 54: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

54/100

Highly reliable spring clips are used as connection terminals. The clips are opened with the appropriate, included tool (small screw driver) which is inserted in the respective square opening and is then moved in the direction away from the lead intake opening.

Electrical connection for compres-sor

The connection for the supply lines from the special tariff (3c400 V, N, PE) occur directly on the motor protection switch (L1, L2, L£) and for N and PE on the relevant terminal connectors on the top-hat rail.

Fig. 19: Special tariff connection

Electrical connections for RVS con-troller

Component Connection to Line on site

Sensor outside RVS controller, slot k, terminal B9, M

Cable interchangea-ble

Sensor source inlet 49.0

RVS controller, slot r, terminal B91, M

Cable interchangea-ble

Sensor evaporator 48.1

RVS controller, slot s, terminal B84, M

Cable interchangea-ble

Control signal 0-10 V

RVS controller, slot z, terminal UX, M Terminal connectors ventilator terminal 0-10 V/PWM, GND

Comply with polarity

Page 55: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

55/100

Connection terminals ventilator(s)

M1 M2 M3

RSA

RSB

RSA

RSB

GND

0-10V PWM

0-10V PWM

4-20mA

+20V

+10V

GND

OUT

NO

COM

NC

N

L

(L1)

(L2)

(L3)

L1

NPE

230V

50/

60 H

z

1)

R2

R12)

0-10V PWM out

RSA

RSB

RSA

RSB

GND

0-10V PWM

0-10V PWM

4-20mA

+20V

+10V

GND

OUT

NO

COM

NC

N

L

(L1)

L1

NPE

230V

50/

60 H

z

1)

R2

2)

RSA

RSB

RSA

RSB

GND

0-10V PWM

0-10V PWM

4-20mA

+20V

+10V

GND

OUT

NO

COM

NC

N

L

(L1)

L1

NPE

230V

50/

60 H

z

1)

R2

2)

Sk09-6200-125Stand: 19.11.09

R1 R1

(L2)

(L3)

(L2)

(L3)

3)

Fig. 20: Connection terminals ventilator(s)

Page 56: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

56/100

Enclosure assembly

Fig. 21: Snap the catches of the side panel of the enclosure into

the rear panel.

Fig. 22: Fix side panels on the rear panel of the enclosure.

Page 57: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

57/100

Fig. 23: Insert the spring plates in the side enclosures.

Fig. 24: Snap the front panel onto the catches of the side panel.

Page 58: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

58/100

Fig. 25: Screw the closing journals into the lid of the enclosure.

Fig. 26: Position the lid.

Fig. 27: Insert the bracket.

Page 59: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

59/100

Fig. 28: Screw in the upper and lower wing nut of the bracket.

Fig. 29: Reach through the openings of the brackets to remove

the control unit and attach it from the outside.

Page 60: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

6. Assembly ThermSelect®

60/100

Motor control unit RSBT 4016, 4025, 4032 EV 11 for ThermSelect®

Fig. 30: Dimensions RSBT 4016, 4025, 4032 EV 11

Number of flashing signals red LED

Status Action

2 Incorrect phase sequence Physical change

3 Power supply not in accor-dance with regulations

Auto reset with 5 min. recovery

4 Frequency not in accor-dance with regulations

Auto reset with 5 min. recovery

5 Rotor blocking status (while ramping)

Auto reset with 5 min. recovery

6 Startup time > 1 sec. Auto reset with 5 min. recovery

7 Excess temperature Auto reset

8 Excess current (during bypass)

Auto reset with 5 min. recovery

9 Supply voltage unbalance

Auto reset with 5 min. re-covery, provided that all phases (L1, L2, L3) are connected.

Page 61: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 6. Assembly

61/100

Fig. 31: Flashing sequence RSBT 4016, 4025, 4032 EV 1

Controller and control unit

At this point, MHG refers to the Assembly-Operation-Maintenance manual RVS 61.843 / AVS 37.. / QAA 75.. / QAA 78.. (Part No. 98.18803-6105)

Red LE Red LED off

Page 62: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

7. Operation Startup ThermSelect®

62/100

7 Commissioning

7.1 Safety during startup WARNING! Risk of injury through improper operation! Improper operation leads to serious personal injuries or property damages. Therefore: - Installation and assembly must be performed by a

heating systems dealer. - Work on the refrigerant circulation may only be per-

formed by persons possessing a refrigeration cer-tificate in accordance with ChemKlimaschutzV.

- Carry out all of the operating steps in accordance with the information in these instructions.

- Before starting with the work activities, make sure that electrical and hydraulic lines are shut off and secured against inadvertent opening.

- Use only suitable tools.

7.2 Inspection prior to startup Make sure of the following after proper assembly: - the electrical connection has been correctly installed. - the polarity of the line connection is correct - electrical voltage is applied - the heating system and possibly existing reservoir are correctly

filled and ventilated - the heat source system is correctly filled and ventilated - the correct installation of all required safety devices was made. - proper circulation of the heating water and hot water circuit exists - all refrigerant lines and valves are sealed intact - refrigerant lines are covered with diffusion-resistant insulation,

without any gaps - all attachments, suspensions, etc. are fastened properly and have

been verified as to their proper height

NOTE! After installation and prior to startup of the system, the protective earth resistance and the insulation re-sistance must be tested according to DIN VDE 0701 and DIN VDE 0702 and documented. These tests need to be repeated according to the applicable local time intervals or according to the DIN VDE - regulations, series DIN VDE 0701 and 0702 (repair, restarting, etc.).

Page 63: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 7. Operation Startup

63/100

7.3 Commissioning

NOTE! The customer / owner of the system must be present when starting up the system. A startup protocol is established on site.

NOTE! For operators of equipment containing 3kg or more of refrigerant, the following duties of documentation apply: - Amount and type of refrigerant - Any amounts of refrigerant refills - Any amounts of refrigerant retrieved during startup,

maintenance or final disposal - Details identifying the company or technical per-

sonnel that carried out the installation, startup, or any maintenance work

- Dates and results of all inspections The recorded information must be presented to the relevant authorities and the commission upon re-quest.

PRECAUTION! Risk of injury due to refrigerant! Refrigerant leakage damages the environment 100- 24,000 times more than carbon dioxide (CO2). Therefore: - Hermetically sealed systems that contain 6 kg of

refrigerant or more must not exceed a leakage rate of 1%.

CAUTION! Device damage through wrong direction of rotation of the condenser! A reverse run over several hours or days causes se-rious damage with a loss of guarantee. Therefore: - The use of the compressor requires the correct ro-

tational direction to be set and adhered to (clock-wise rotating field).

- When turning in the wrong direction, the condenser works much louder than usual and does not pro-duce any output (compressed gas neck remains cold). A brief reverse run of a few minutes is not harmful.

CAUTION! Device damage through dry pump running. If the brine circuit is not connected or not filled, the pump can be damaged. Therefore: - The device can only be started up with a filled heat-

ing and brine circuit. Refer also to the "Startup order form".

Page 64: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

7. Operation Startup ThermSelect®

64/100

Pump control - Circulating pump control - Unscrew pump stopper and turn pump shaft as illustrated below. - Screw pump stopper back in - Caution: Collect drops

Fig. 32: Loosen pump stopper

Switching on the device

After proper inspection of the installation, the power connection can be switched on. For this, activate the installed power switch and au-tomatic circuit breaker.

Refrigerant dosage

The quantity of refrigerant is determined during operation by mea-suring and comparing the refrigerant condensation temperature and the heat pump flow temperature. The heat pump / compressor must be activated for min. of 10 min. and a flow temperature of approx. 50°C must be reached before measurement or the results will not be reliable and the amount of refrigerant indicated will not be correct. The difference between both of these temperatures should be be-tween 0 and 3 K (condensation temperature - flow temperature).

Test for leak-tightness

Once operating, the refrigerant circuit must be rechecked for lea-kage using a sensitive leak detection device/substance.

Page 65: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 7. Operation Startup

65/100

7.4 Setting the controller

Control unit AVS 37

Fig. 33: Control unit AVS 37

Legend for Fig. 33:

Abbrev-iation Meaning

1 Select drinking water mode 2 Service connector for BSB data BUS 3 Exit settings 4 Select heating mode 5 Display information 6 Accept settings

7 Room comfort target value, adjusting, navigation and settings

Symbol Display options

Heating in constant mode day (comfort mode) Heating in constant mode night (reduced mode) Heating on standby (freeze protection mode) Process running - please wait Replace battery Holiday function active Reference to heating circuit Maintenance / Special functions Error messages Info level activated Programming activated

Heating temporarily switched off, ECO function active

Page 66: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

7. Operation Startup ThermSelect®

66/100

7.5 Parameterisation At this point, MHG refers to the Assembly-Operation-Maintenance manual RVS 61.843 / AVS 37.. / QAA 75.. / QAA 78.. (Part No. 98.18803-6105) The factory parameterisation is shown in the table on pages 90-95. It may need to be adapted to the local system conditions.

7.6 Commissioning record NOTE! The work carried out must be entered in a separate commissioning record.

Page 67: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 8. Maintenance

67/100

8 Maintenance

8.1 Maintenance

NOTE! The respective regulations and guidelines of the country of destination must be complied with!

NOTE! Depending on the quantity of refrigerant, the system operator must have it checked at least once every twelve months. This is also necessary for reasons of operating readiness, function and efficiency. Work on the refrigerant circuit may only be per-formed by certified personnel.

The total system shall be inspected here for flawless function and any defects encountered shall be repaired without delay.

NOTE! Professional annual maintenance is stipulated ac-cording to the warranty conditions of MHG Heiztech-nik.

DANGER! Risk to life through electrical current! Contact with live components can cause serious inju-ries. Therefore: - Work on electrical systems may only be performed

by professional electricians. - Turn off electric power before beginning the work

activities, e.g. heating emergency switch, and se-cure against turning on again.

- Set the operating switch on the boiler to "OFF". - In case of damaged insulation, immediately cut off

the power supply and initiate the repair.

NOTE! Inspect threaded joints for leaks during the annual maintenance. Replace defective or worn seals.

Page 68: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

8. Maintenance ThermSelect®

68/100

8.2 Components relevant to safety

For ensure the long-term availability and safety of heat generators and components and to fulfil the requirements of the EU Guideline 2002/91/EC, it is necessary to replace the following components af-ter they reach the service life specified by the manufacturer, as time or switching cycles. With modern devices, the switching cycles can usually read on a display/indicator. In cases where the switching cycle cannot be read, the time is relevant for the replacement.

Nominal service life of the heat ge-nerator components

Components relevant to safety Time [a] Switching cycles [-]

Controller 10 250.000 Pressure relief valves 10 n/a

8.3 Work to be carried out

PRECAUTION! Risk of injury due to refrigerant! Refrigerant is corrosive and causes cold burns upon contact with skin. Therefore: - Wear chemical-resistant protective gloves when

handling refrigerant at any time. - Wear protective glasses to avoid contact with eyes.

NOTE! For operators of equipment containing 3kg or more of refrigerant the following duties of documentation apply: - Amount and type of refrigerant - Any amounts of refrigerant refills - Any amounts of refrigerant retrieved during startup,

maintenance or final disposal - Details identifying the company or technical per-

sonnel that carried out the installation, startup, or any maintenance work

- Dates and results of all inspections The recorded information must be presented to the relevant authorities and the commission upon re-quest.

Page 69: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 8. Maintenance

69/100

PRECAUTION! Risk of injury due to refrigerant! Refrigerant leakage damages the environment 100- 24,000 times more than carbon dioxide (CO2). Therefore: - Hermetically sealed systems that contain 6 kg of

refrigerant or more must not exceed a leakage rate of 1%.

- Hermetically sealed systems that contain 6 kg of refrigerant or more must have leak-tightness in-spected and verified at least every 12 months.

- All leaks from which refrigerant can escape must be repaired immediately.

Confirm the work activities performed in the following commission-ing record with an X or a .

Maintenance work Description Done

Document amount and type of refrigerant used ---

Document any amounts of refrigerant refills ---

Document any retrieved refrigerant --- Document details identifying the compa-ny or technical personnel that carried out the maintenance work

---

Document dates and results of all inspec-tions ---

Check cooling circulation: Screw connections, seals, (sight glass), refrigerant regulation

---

Check heating cycle: System pressure, expansion container function, ventilation, pump rotational di-rection and quantity setting

---

Check the controller settings ---

CAUTION! Environmental damage through substances hazard-ous to groundwater! Substances hazardous to groundwater, such as greases, oils, refrigerants, solvent-based cleaning agents and the like, can burden the ground or get in-to the sewage system. Therefore: - These substances must be collected, stored and

transported in suitable containers and be disposed off.

With regard to the remaining heating system (distribution system), especially the circulation pumps, valves and adjustment devices must be checked for leaks and also the filters (if water is the heat source) must be inspected and cleaned, if applicable, and the prop-er operation of the flow guard must be verified.

Page 70: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

8. Maintenance ThermSelect®

70/100

Disassembly of the control unit

NOTE! Loosen the catches with a screwdriver. It must be ensured that the catches are not broken off when dismantling the control unit.

Fig. 34: Insert a screw driver, as per the illustration, first into the

right and then the left upper recess, push the catch down and the screw driver forward at the same time.

Fig. 35: Insert a screw driver first into the right and then the left

lower recess, push the catch down and the screw driver forward at the same time.

Page 71: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 8. Maintenance

71/100

Fig. 36: Remove the control unit from the bracket and insert

through the opening of the bracket and place inside. Repeat the steps of Fig. 34-Fig. 36 with the second control unit.

Page 72: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

8. Maintenance ThermSelect®

72/100

8.4 Spare part drawing and legend

Fig. 37:

Page 73: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 9. Troubleshooting

73/100

9 Troubleshooting

9.1 Troubleshooting It is frequently noticeable that the heat pump heating systems are not operating properly because the heating circuit does not have the required volume flow. The consequence of this is the activation of safety devices on the heat pump. In case of insufficient or no flow in the heat exchange on the heating circuit side, this leads to a high-pressure disruption. It cannot be ruled out that the safety temperature limiter will also switch the sys-tem off with insufficient hot water flow. The causes of the listed faults have their origin in the periphery and in the rarest cases, in the heat pump itself. Incorrect settings on the controller can have similar effects. The activation of relevant sen-sors and the signalisation of a fault are for the protection of the sys-tem and are generally not an indication of a defective heat pump.

Faults and their removal

If the heat transfer is suddenly disrupted when the heat pump is running (e.g. due to standstill of circulating heat pump or closed valves), it can (due to the thermal inertia of the system) occur that the high-pressure safety limit switch in the heat pump is activated. The heat pump is thereby shut off and an automatic restart is pre-vented for safety reasons.

NOTE! Reduction of the service life of the high-pressure -safety limit switch, as well as the compressor, through excess wear and tear. Therefore: - If the high-pressure limit switch is activated, check

and rectify the cause. Another possible reason for triggering this high pressure safety limi-ter may also be related to the local conditions of the heat pump's in-stallation site which may necessitate the installation of an oil sump heater (strip heater on the condenser) or a "pump-down function".

Course of action for malfunctions

If electrical errors (e.g. defective sensors) can be ruled out, begin with checking the circulation pump and valves of the heating system and heat source.

NOTE! If all errors can be ruled out on the external system, the cooling cycle of the heat pump must be checked by an authorized technician.

Page 74: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

9. Troubleshooting ThermSelect®

74/100

Troubleshooting

Fault Cause Remedy

Defect on input side (LP fault)

Ventilator(s) is/are not running Check fuse, check relay Check control signal 0-10 V

Heat source pump not running Check fuse, relay and pump

Condenser dirty/iced over Clean condenser, initiate thawing; check temperatures on condenser

Expansion valve incorrectly set / defective Request factory service

Refrigerant circulation interrupted (shut-off valve closed, filter dryer dirty).

Request factory service

Water inside the refrigerant circulation (hu-midity indicator in the refrigerant sight glass yellow/red)

Request factory service

Temperature of the heat source too low -15°C application limit reached

Water in the condenser too cold (below 20 °C)

Pre-heat heating water electric heating insert

Quick temperature change in the condenser Check volume flow

Low refrigerant level (see sight glass) Request factory service

Controller parameter set incorrectly Set parameters according to guide

Contact interrupted Check LP switch wiring

Manual unlocking necessary if the low pres-sure monitor triggers.

Defect on input side (HD fault)

Heating pump is not running Check fuse; check relay/ contactor K4; Check running wheel for dirt build-up

Water circulation interrupted or insufficient (possibly not enough heating circuits open)

Check water circulation in heating system; open radiator valves or positioning drives

Heating water temperature too high

No heat discharge, e.g. heat exchanger in the boiler of the service water heater is too small

Check technical specifications for service wa-ter heater, min. heat exchanger surface 0.2m²/kW heat output

Air in water circulation Vent the water circulation

Dirt catcher clogged Clean dirt catcher

Circulation pump defective or wrong rotation direction

Check circulation pump and rotate/replace, if necessary

Controller parameter set incorrectly. Set parameters according to guide

Manual unlocking may possibly be neces-sary if the high pressure monitor triggers.

Page 75: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 9. Troubleshooting

75/100

Fault Cause Remedy

Fault with con-denser motor con-denser overload (overheating of the motor winding)

Failure of a phase Check supply line of 3-phase current

Mechanical failure due to lack of lubrication Request factory service

Winding protection defective Replace winding protection

Low refrigerant level Request factory service

Defect in the refrigerant regulation Request factory service

Operation with incorrect refrigerant Request factory service

Pressure gas temperature too high Request factory service

Fault current (FI) circuit breaker ac-tivates

Wrong allocation of neutral lead for spe-cial/normal tariff

Check device wiring

heating pump locked

Special tariff supply line interrupted (off-time preset by utility company); bivalence point undercut

Check blocking times for the special tariff connection; check parameters (RVS 61, Line 2910)

Evaporator ices up quickly

High humidity and temperatures of 3-8°C lead to quick icing up of the evaporator.

Decrease time until forced thaw (parameter line 2963)

Page 76: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

10. Warranty ThermSelect®

76/100

10 Warranty

10.1 Warranty

Limit of liability All specifications and information in these installation instructions were compiled under consideration of the applicable standards and regulations, the state of technology as well as our experience and insights of many years. MHG Heiztechnik does not assume any liability for damages due to: - Non-compliance with the instructions for Assembly, Startup and

Maintenance, as well as the operating instructions - Use other than intended - Employment of untrained personnel - Unauthorized modifications - Technical changes - Use of unapproved spare parts - Inappropriate change of refrigerant dosage The actual scope of delivery may deviate from the explanations and representations described here due to special designs, additional ordering options or latest technical changes.

Copyright

These instructions are copyright protected by MHG Heiztechnik. Duplications of any type and in any form - also excerpts - as well as the exploitation, notification and/or communication of its contents, or parts thereof, are not permitted without the written release declara-tion of MGH Heiztechnik. Any person violating these rules will be li-able for damages. Additional claims are reserved. The instructions are to be treated confidentially. They are exclusive-ly intended for persons working with the device. Leaving the instruc-tions to a third party without written approval of the manufacturer is not permitted. The instructions shall remain with the heating device to allow them to be used at a later time, if needed. MHG shall not be held liable for damages resulting from non-compliance with these instructions.

NOTE! The content, texts, drawings, illustrations and other presentations are protected by copyright and subject to commercial property rights. Any misuse is liable to prosecution.

Page 77: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 10. Warranty

77/100

Warranty The ThermSelect® heat pump by MHG renders its perfect function only when installed and started professionally. Warranty conditions of MHG can be taken from the warranty certifi-cate.

Spare parts

NOTE! Use only original MHG spare parts in case of re-placements: Some components have been designed and manufactured especially for MHG devices. Al-ways specify the serial number when ordering spare parts.

PRECAUTION! Device damage from the use of incorrect compo-nents! Using parts not manufactured/supplied by MHG can cause material decomposition. Therefore: - Only parts specified by MHG must be installed in

the cooling unit.

Warranty claim for wearing parts

(See recommendation EHI European Heating Industry, information bulletin 14) The spare parts list also contains "spare parts" that must be re-placed when the device is used as intended within the warranty pe-riod. The warranty periods have been extended by law makers, however, this does not preclude possible wear and tear from operation. It is known that a device may operate up to 8,760 hours a year when used as intended if this is a permanent operation system. According to customary commercial treatment, the costs incurred in these con-ditions are not covered by the warranty obligation or commitment of the manufacturer. The components listed in the spare parts list have been divided into the following categories: 1. Spare parts Spare parts are used for the repair of products

a) Parts are replaced that have not reached the expected ser-vice life although the device was operated as intended.

b) Furthermore, parts that are replaced due to improper opera-tion or unintended use (e.g. wrong burner settings, water flow to low or too high, boiler scale through unsuitable filling water, use of incorrect refrigerant, etc.).

Page 78: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

10. Warranty ThermSelect®

78/100

2. Wearing parts Wearing parts are such parts which must be replaced sever-

al times within the scope of service life while the product is used as intended (e.g. during maintenance).

3. Auxiliary materials Auxiliary materials are required with the repair and mainten-

ance of devices. Typical auxiliary materials are, for example, seals of all kinds,

hemp, lead oxide red or fuses. Auxiliary materials are not subject to any warranty claims, except

the necessary use in the context of replacing parts in the frame-work of an existing warranty claim.

Warranty certificate MHG provides warranty for compliance with explicitly promised properties, for non-defective construction and manufacturing as well as for flawless material in the manner that the parts which have become unusable as a result of such defects or where there usefulness was significantly compromised are delivers as new at their own costs and risk. MHG provides warranty for replaced parts to the same extent as for the original delivery item. The following warranty periods apply for the ThermSelect® heat pump:

- 2 years material warranty on all electrical and other components , as well as on the heat pump function.

The ordering party can only assert warranty claims from MHG if the startup of the delivered item was performed by staff of MHG, companies trained by MHG or a qualified refrigeration company, the order-ing party has observed the MHG regulations of the handling and maintenance of the delivered item, the prescribed inspections were done properly and no spare parts of third-party origin were installed. The complete and current delivery and warranty conditions can be taken from the MHG price list, on the back of the order confirmations, delivery notes and invoices as well as in the Internet at www.mhg.de. Per request, MHG can send the current general delivery and warranty conditions as printout via postal service. MHG Heiztechnik GmbH

M. Niedermayer ppa Gieseler

Page 79: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 10. Warranty

79/100

10.2 Manufacturer Certificate / EU Design Conformity Declaration

Manufacturer Certificate Buchholz i.d.n., 03.03.2011 MHG Heiztechnik GmbH hereby certifies the following for the heat pumps listed below: The heat pumps are equipped with different safety circuit devices for pressure limitation in the refrigerant cycle in compliance with DIN 32733. The high pressure guard safety limit switch shuts off the condenser automatically if the pressure of the medium in the refrigerant cycle exceeds 28 bar. The refrigerants R407C and the cooling equipment machine oil (diester oil) are environmentally compatible. According to the EU safety data sheet, the refrigerant R407C consists of 23% difluoromethane (HFKW 32), 25% pentafluoroethane (HFKW 125) and 52% tetrafluoroethane (HFKW 125). The RVS 61 heat pump controller used by MHG in the system is equipped with sensors for the recording and control of the source outlet temperature and the heating flow temperature. If temperatures reach levels endan-gering the system, the heat pump is shut off automatically. MHG Heiztechnik GmbH

M. Niedermayer ppa Gieseler

Page 80: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

10. Warranty ThermSelect®

80/100

EU Design Conformity Declaration According to EG Machine Guideline 98/37/EG Buchholz i.d.n., 05.05.10 MHG Heiztechnik GmbH hereby declares that the ThermSelect® heat pumps comply with the following EU guidelines and standards:

EU Guideline Standard Machine guideline 98/37/EC

Low voltage guideline 73/23/EEC EN 60335-1 (2004) EN 50165 (1998) + A1 (2001)

EMC guideline 89/336/EEC EN 55014-1 (2001) EN 55014-2 (2001) EN 50165 (1998) + A1 (2001)

Pressure equipment guideline 97/23/EC EN 13445 (01.2002) VDE 0113 Electrical Equipping of Machines - Safety of Machines DIN EN 60204 (1998)

VDE 0660-500 Low-Voltage Switching Device Combinations DIN EN 60439 (01.2005)

Cooling systems and heat pumps - Safety and envi-ronmentally relevant requirements DIN EN 378 (01.2000)

Air conditioners, liquid cooling sets and heat pumps with electrically powered compressors - heating DIN EN 255 (07.1997)

DIN EN 14511 (02.2008) Safety switching mechanism for the pressure limitation in cooling systems and heat pumps - Requirements and testing

DIN 32733 (1989.01)

Cooling systems and heat pumps - Protection of soil, groundwater and surface water - Safety and environ-mentally relevant requirements and testing

DIN 8901 (12.2002)

Cooling Systems - Safety Principles for Design, Fitting and setup - Part 12: Recovery Systems DIN 8975 (01.2004)

DruckbehV (06.1999) Regulation on Pressure Containers, Pressurised Gas Containers and Filling Systems

This declaration looses its validity in changes not authorized by MHG Heiztechnik are made to the machine. MHG Heiztechnik GmbH

M. Niedermayer ppa Gieseler

Page 81: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 10. Warranty

81/100

10.3 Proof of Service

Maintenance record ThermSelect®, ThermSelect®Pro, ThermSelect®Sun, ThermSelect®Sun Pro Heat Pump

Customer:

Maintenance Contract/Customer No.:

The following work was carried out on your heating system in the context of your yearly maintenance:

1) Type of refrigerant

2) Quantity of refrigerant according to identification plate

3) Refrigerant refilled g

4) Refrigerant recycled g

5) Functional check of cooling cycle

6) Leak-tightness check of cooling cycle

7) Electric connections check

8) Inspection of seals and replacement where necessary

9) Test for water/gas leak-tightness in operation

10) Functional check of pump

11) Function check of mixer/mixer motor, if applicable

12) Parameter controller/room unit check

13) Electric meter reading

14) Heat meter reading

15)

16)

17)

Comments:

We acknowledge and verify proper implementation. Place, Date

Stamp

Signature

Next yearly maintenance due in: (Month, Year)

Page 82: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

10. Warranty ThermSelect®

82/100

1. Maintenance 2. Mainten-ance

Amount of refri-gerant refilled kg Amount of re-

frigerant refilled kg

Amount of refri-gerant retrieved kg

Amount of re-frigerant re-trieved

kg

Electric meter reading Electric meter

reading

Heat meter reading Heat meter

reading

Leak-tightness verification completed

Date Leak-tightness verification completed

Leaks repaired yes/no Leaks repaired Inspection due (after 4 weeks) Date Inspection due

(after 4 weeks) Date

Inspection car-ried out: Date Inspection car-

ried out: Date

Next mainten-ance due: Date Next mainten-

ance due: Date

Address of certi-fied company Address of cer-

tified company

Name of service technician Name of ser-

vice technician

Page 83: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 10. Warranty

83/100

3. Mainten-ance 4. Mainten-

ance

Amount of re-frigerant refilled kg Amount of re-

frigerant refilled kg

Amount of re-frigerant re-trieved

kg Amount of re-frigerant re-trieved

kg

Electric meter reading Electric meter

reading

Heat meter reading Heat meter

reading

Leak-tightness verification completed

Date Leak-tightness verification completed

Leaks repaired yes/no Leaks repaired Inspection due (after 4 weeks) Date Inspection due

(after 4 weeks) Date

Inspection car-ried out: Date Inspection car-

ried out: Date

Next mainten-ance due: Date Next mainten-

ance due: Date

Address of cer-tified company Address of cer-

tified company

Name of ser-vice technician Name of ser-

vice technician

Page 84: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

10. Warranty ThermSelect®

84/100

5. Mainten-ance 6. Mainten-

ance

Amount of re-frigerant refilled kg Amount of re-

frigerant refilled kg

Amount of re-frigerant re-trieved

kg Amount of re-frigerant re-trieved

kg

Electric meter reading Electric meter

reading

Heat meter reading Heat meter

reading

Leak-tightness verification completed

Date Leak-tightness verification completed

Leaks repaired yes/no Leaks repaired Inspection due (after 4 weeks) Date Inspection due

(after 4 weeks) Date

Inspection car-ried out: Date Inspection car-

ried out: Date

Next mainten-ance due: Date Next mainten-

ance due: Date

Address of cer-tified company Address of cer-

tified company

Name of ser-vice technician Name of ser-

vice technician

Page 85: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 10. Warranty

85/100

7. Mainten-ance 8. Mainten-

ance

Amount of re-frigerant refilled kg Amount of re-

frigerant refilled kg

Amount of re-frigerant re-trieved

kg Amount of re-frigerant re-trieved

kg

Electric meter reading Electric meter

reading

Heat meter reading Heat meter

reading

Leak-tightness verification completed

Date Leak-tightness verification completed

Leaks repaired yes/no Leaks repaired Inspection due (after 4 weeks) Date Inspection due

(after 4 weeks) Date

Inspection car-ried out: Date Inspection car-

ried out: Date

Next mainten-ance due: Date Next mainten-

ance due: Date

Address of cer-tified company Address of cer-

tified company

Name of ser-vice technician Name of ser-

vice technician

Page 86: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

11. Hydraulic Diagrams ThermSelect®

86/100

11 Hydraulic diagrams

11.1 Hydraulic diagrams

NOTE! The hydraulic diagram represent an installation suggestion (without any claim to completeness). The installation must be adjusted by a professional to the circumstances on site. Additional re-quired components must be provided on site.

ThermSelect® air+brine/water heat pump with heating/water change-over valve

M42.242.442.6

42.342.5

48.048.2

49.1

49.2

22.0

41.0

49.0

43.0

48.1

Fig. 38: Sk10-0504/163

ThermSelect® air+brine/water heat pump with heating/warm water change-over valve

Legend for Fig. 38:

Abbrev-iation Meaning Abbrev-

iation Meaning

22.0 Ventilator 1 FIL Filter 42.2 Sensor air-heat pump flow (B21) FL Fluid line 42.3 Sensor air-heat pump return (B71) HG Hot-gas line 42.4 Sensor brine-heat pump flow (B21) HK Heating circuit 42.5 Sensor brine-heat pump return (B71) KW Cooling circuit 42.6 Sensor track flow (B10) RL Return 48.0 Sensor refrigerant liquid air (B83) SG Suction gas line 48.1 Sensor refrigerant evaporator (B84) T Temperature 48.2 Sensor refrigerant suction gas brine (Bx1) VL Flow 49.0 Sensor source inlet air (B91) WQL Heat source air 49.1 Sensor source inlet brine (B91) WQS Heat source brine 49.2 Sensor source outlet brine (B92) Z Circulation

Page 87: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 11. Hydraulic Diagrams

87/100

Components

Component Type Part number Comment

MHG ThermSelect®

15 19 28 34 41

98.30000-8954 98.30000-8956 98.30000-8958 98.30000-8960 98.30000-8962

Included in scope of delivery: 2 x controllers RVS 61.843 2 x control unit AVS 37.390 outdoor temperature sensor QAC 34 service water sensor QAZ 36

Mounting kit (heating side) for ThermSelect 10-15 98.38500-6111

Mounting kit (source side) for ThermSelect 10-15 98.38500-6110

Mounting kit 1 1/2" (Heating or source side)

for ThermSelect 19-41 98.38500-6114

Electrical heating cartridge 6 kW module upon request Flexible connection hoses heating flow and return for ThermSelect® 15 upon request

THERAMAT heat pump high-performance storage

EMH 150-1 EMH 200-1 EMH 300-1 EMH 400-1 EMH 500-1

94.71000-5615 94.71000-5621 94.71000-5631 94.71000-5641 94.71000-5651

Expansion vessel Heating Design of the MAG on site Fresh water connection To be provided on site

Electrical Connections RVS 61.843

Component Connection to Line on site

Sensor outside 1 41.0 RVS controller air, slot k, terminal B9, M Cable interchangeable

Sensor service water top 43.0

RVS controller air, slot h, terminal B3, M

Cable interchangeable, place sensor in top section of storage

Sensor evaporator 48.1 RVS controller air, slot s, terminal B84, M Cable interchangeable

Sensor source inlet 49.0 RVS controller air, slot r, terminal B91, M Cable interchangeable

Control signal 0-10 V

RVS controller air, slot z, terminal UX, M Terminal connectors ventilator terminal 0-10 V/PWM, GND

Comply with polarity

Drinking water change-over valve

RVS controller, slot R, terminal Q3, N, PE

Do not interchange neutral and positive, cable 3x1-1.5 mm²

Parameterisation

The system can be started with the factory settings. It may need to be adapted to the local system conditions.

Page 88: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

11. Hydraulic Diagrams ThermSelect®

88/100

ThermSelect® air+brine/water heat pump with heating/water change-over valve and buffer storage

NOTE! The hydraulic diagram represent an installation suggestion (without any claim to completeness). The installation must be adjusted by a professional to the circumstances on site. Additional re-quired components must be provided on site.

M42.242.442.6

42.3

42.548.0

48.2

49.1

49.2

22.0

41.0

49.043.0

48.1

Fig. 39: Sk10-0504/162

ThermSelect® air+brine/water heat pump with heating/warm water change-over valve and buffer storage

Legend for Fig. 39:

Abbrev-iation Meaning Abbrev-

iation Meaning

22.0 Ventilator 1 FIL Filter 42.2 Sensor air-heat pump flow (B21) FL Fluid line 42.3 Sensor air-heat pump return (B71) HG Hot-gas line 42.4 Sensor brine-heat pump flow (B21) HK Heating circuit 42.5 Sensor brine-heat pump return (B71) KW Cooling circuit 42.6 Sensor track flow (B10) RL Return 48.0 Sensor refrigerant liquid air (B83) SG Suction gas line 48.1 Sensor refrigerant evaporator (B84) T Temperature 48.2 Sensor refrigerant suction gas brine (Bx1) VL Flow 49.0 Sensor source inlet air (B91) WQL Heat source air 49.1 Sensor source inlet brine (B91) WQS Heat source brine 49.2 Sensor source outlet brine (B92) Z Circulation

Page 89: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 11. Hydraulic Diagrams

89/100

Components

Component Type Part number Comment

MHG ThermSelect®

15 19 28 34 41

98.30000-8954 98.30000-8956 98.30000-8958 98.30000-8960 98.30000-8962

Included in scope of delivery: 2 x controllers RVS 61.843 2 x control unit AVS 37.390 outdoor temperature sensor QAC 34 service water sensor

Mounting kit (heating side) for ThermSelect 10-15 98.38500-6111

Mounting kit (source side) for ThermSelect 10-15 98.38500-6110

Mounting kit 1 1/2" (Heating or source side)

for ThermSelect 19-41 98.38500-6114

Electrical heating cartridge 6 kW module upon request Flexible connection hoses heating flow and return for ThermSelect® 15 upon request

Buffer reservoir THERAMAT SP-200-0 SP-300-0 SP-500-0

94.71000-5920 94.71000-5930 94.71000-5950

THERAMAT heat pump high-performance storage

EMH 150-1 EMH 200-1 EMH 300-1 EMH 400-1 EMH 500-1

94.71000-5615 94.71000-5621 94.71000-5631 94.71000-5641 94.71000-5651

Overflow valve To be provided on site Expansion vessel Heating Design of the MAG on site Fresh water connection To be provided on site

Electrical Connections RVS 61.843

Component Connection to Line on site

Sensor outside 1 41.0 RVS controller air, slot k, terminal B9, M Cable interchangeable

Sensor service water top 43.0

RVS controller air, slot h, terminal B3, M

Cable interchangeable, place sensor in top section of storage

Sensor evaporator 48.1 RVS controller air, slot s, terminal B84, M Cable interchangeable

Sensor source inlet 49.0 RVS controller air, slot r, terminal B91, M Cable interchangeable

Control signal 0-10 V

RVS controller air, slot z, terminal UX, M Terminal connectors ventilator terminal 0-10 V/PWM, GND

Comply with polarity

Drinking water change-over valve

RVS controller air, slot R, terminal Q3, N, PE

Do not interchange neutral and positive, cable 3 x 1 – 1.5 mm²

Parameterisation

The system can be started with the factory settings. It may need to be adapted to the local system conditions.

Page 90: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

11. Hydraulic Diagrams ThermSelect®

90/100

Factory parameterisation for ThermSelect® design

Control bar

User -level Function / Default value

Set value RVS Air 15

Air 19-28

Air 34-41

Brine 15

Brine 19-41

561-566 E Timer setting 4 Monday 06:00 – 22:00 561-566 E Timer setting 4 Tuesday 06:00 – 22:00 561-566 E Time setting 4 Wednesday 06:00 – 22:00 561-566 E Timer setting 4 Thursday 06:00 – 22:00 561-566 E Timer setting 4 Friday 06:00 – 22:00 561-566 E Timer setting 4 Saturday 06:00 – 22:00 561-566 E Timer setting 4 Sunday 06:00 – 22:00

2801 I Condenser pump control Temperature request ¦ Parallel condenser operation

Temperature request

2803 I Run-on time condenser pump 120 2816 F Source temp min brine -10 2819 I Lead time source 5 2842 I Condenser run time min. 0 2843 I Condenser idle time min 10 2845 F Reduction shut-off temp. Max 0 2853 O Low pressure delay operational 5

2854 O LP monitoring Always ¦ Without thawing

Always

2893 F Number of TWW loading attempts 3 2910 F Clearance above TA 0 --- 2951 I Thawing clearance below TA 10 2954 O Evaporator temp. Thawing end 5 2963 I Time until forced thaw 180 2964 I Thawing time max 20 2971 O Thawing ventilator above 7 3010 O Max. speed V'lator/Q'pump 40 60 100

3541 F Auto sequential exclusion None ¦ First ¦ Last ¦ First and Last

First None

5093 F With solar integration No ¦ Yes

No

5710 I Heating circuit 1 Off

5731 I Drinking water control element Q3 None ¦ Charge pump ¦ Reversing valve

Reversing valve

5800 I Heat source Brine ¦ Water ¦ Air ¦ External

Air Brine

Page 91: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 11. Hydraulic Diagrams

91/100

Control bar

User -level Function / Default value

Set value RVS Air 15

Air 19-28

Air 34-41

Brine 15

Brine 19-41

5890 I

Relay output QX1 None ¦ Condenser stage 2 K2 ¦ Process reversing valve Y22 ¦ Hot gas temperature K31 ¦ Electrical insert1 Flow K25 ¦ Electrical insert2 Flow K26 ¦ Reversing valve cool-ing Track2 Y28 ¦ Delivery pump Q14 ¦ Cascade pump Q25 ¦ Generator shut-off valve Y4 ¦ Electrical insert TWW K6 ¦ Circulation pump Q4 ¦ Storage charge-over pump Q11 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Mixing pump Q35 ¦ Collector pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump ext.exchanger K9 ¦ Solar con-trol element buffer K8 ¦ Solar control element swimming pool K18 ¦ Electrical insert buffer K16 ¦ H1-Pump Q15 ¦ H2-Pump Q18 ¦ H3-Pump Q19 ¦ Heating cycle pump HkP Q20 ¦ 2nd Pump stage HK1 Q21 ¦ 2. Pump stage HK2 Q22 ¦ 2nd Pump stage HKP Q23 ¦ Reversing valve cooling Y21 ¦ Air dehumidifier K29 ¦ Heat request K27 ¦ Refrigeration request

Process reversing valve Y22 None

5891 I

Relais output QX2 None ¦ Condenser stage 2 K2 ¦ Process reversing valve Y22 ¦ Hot gas temperature K31 ¦ Electrical insert1 Flow K25 ¦ Electrical insert2 Flow K26 ¦ Reversing valve cool-ing Track2 Y28 ¦ Delivery pump Q14 ¦ Cascade pump Q25 ¦ Generator shut-off valve Y4 ¦ Electrical insert TWW K6 ¦ Circulation pump Q4 ¦ Storage charge-over pump Q11 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Mixing pump Q35 ¦ Collector pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump ext.exchanger K9 ¦ Solar con-trol element buffer K8 ¦ Solar control element swimming pool K18 ¦ Electrical insert buffer K16 ¦ H1-Pump Q15 ¦ H2-Pump Q18 ¦ H3-Pump Q19 ¦ Heating cycle pump HkP Q20 ¦ 2nd Pump stage HK1 Q21 ¦ 2. Pump stage HK2 Q22 ¦ 2nd Pump stage HKP Q23 ¦ Reversing valve cooling Y21 ¦ Air dehumidifier K29 ¦ Heat request K27 ¦ Refrigeration request

Heat requirement K27 None

5930 I

Sensor input BX1 None ¦ Buffer reservoir sensor B4 ¦ Buffer reservoir sen-sor B41 ¦ Collector sensor B6 ¦ Drinking water sensor B31* ¦ Hot gas sensor B82 ¦ Refrigerant sensor liquid B83 ¦ TWW Charge sensor B36 ¦ TWW Tapping sensor B38 ¦ TWW Circulation sensor B39 ¦ Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64 ¦ Buffer reservoir sensor B42 ¦ Track flow sensor B10 ¦ Cascade return sensor B70 ¦ Special temperature sensor 1 ¦ Special tempera-ture sensor 2

Track flow sensor B10

Special -temperature

sensor 1

5931 I

Sensor input BX2 None ¦ Buffer reservoir sensor B4 ¦ Buffer reservoir sen-sor B41 ¦ Collector sensor B6 ¦ Drinking water sensor B31* ¦ Hot gas sensor B82 ¦ Refrigerant sensor liquid B83 ¦ TWW Charge sensor B36 ¦ TWW Tapping sensor B38 ¦ TWW Circulation sensor B39 ¦ Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64 ¦ Buffer reservoir sensor B42 ¦ Track flow sensor B10 ¦ Cascade return sensor B70 ¦ Special temperature sensor 1 ¦ Special tempera-ture sensor 2

Refrigerant liquid B83

Page 92: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

11. Hydraulic Diagrams ThermSelect®

92/100

Control bar

User -level Function / Default value

Set value RVS Air 15

Air 19-28

Air 34-41

Brine 15

Brine 19-41

5950 I

Function input H1 BA toggle HK's+TWW ¦ BA toggle HK's ¦ BA toggle HK1 ¦ BA toggle HK2 ¦ BA toggle HKP ¦ Error / alarm mes-sage ¦ Minimum flow targe value ¦ Heat requirement 10V ¦ Thaw point guard ¦ Flow target value increase hygro ¦ Refrigeration request ¦ Refrigeration request 10V ¦ Pres-sure measurement 10V ¦ Relative room humidity 10V ¦ Room temperature 10V ¦ Clearance swimming pool ¦ Switch-on command WP level 1 ¦ Switch-on command WP level 2

Switch-on command WP level 1

5952 I Function value contact H1 55

5981 O Control direction input EX1 Break contact ¦ Working contact

Break contact

5999 O Control direction LP guard E9 Break contact ¦ Working contact

Break contact

6000 O Control direction HP guard E10 Break contact ¦ Working contact

Break contact

6001 O Cntrl dir. Evap1 overload E11 Break contact ¦ Working contact

Work -

con-tact

Break contact

Work -

con-tact

Nor-mally closed con-

tact

6070 I

Function output UX None ¦ Source pump Q8/Venti K19 ¦ Drinking water pump Q3 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Instantaneous water filter Q34 ¦ Collector pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump buffer K8 ¦ Solar pump ext. exchanger K9 ¦ Solar pump swimming pool K18 ¦ Heating circuit pump HK1 Q2 ¦ Heating circuit pump HK2 Q6 ¦ Heating circuit pump HKP Q20 ¦ Heat pump target value ¦ Output target value ¦ Heat require-ment ¦ Cold requirement ¦ Heat pump modulating

Source pump Q8/Venti K19

6128 O Heat request below outdoor temp 0 --- 6600 I Device address 1 2

6640 I Timer mode Autonomous ¦ Slave without remote adjustment ¦ Slave with remote adjustment ¦ Master

Master Slave without remote ad-justment

Error No. 35 ST Repeat of error 225: Low pressure 0

Page 93: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 11. Hydraulic Diagrams

93/100

Factory parameterisation for ThermSelect®Pro design

Control bar

User -level Function / Default value

Set value RVS Air 15

Air 19-28

Air 34-41

Brine 15

Brine 19-41

561-566 E Timer setting 4 Monday 06:00 – 22:00 561-566 E Timer setting 4 Tuesday 06:00 – 22:00 561-566 E Time setting 4 Wednesday 06:00 – 22:00 561-566 E Timer setting 4 Thursday 06:00 – 22:00 561-566 E Timer setting 4 Friday 06:00 – 22:00 561-566 E Timer setting 4 Saturday 06:00 – 22:00 561-566 E Timer setting 4 Sunday 06:00 – 22:00

2801 I Condenser pump control Temperature request ¦ Parallel condenser operation

Temperature request

2803 I Run-on time condenser pump 120 2816 F Source temp min brine -10 2819 I Lead time source 5 2842 I Condenser run time min. 0 2843 I Condenser idle time min 10 2845 F Reduction shut-off temp. Max 0 2853 O Low pressure delay operational 5

2854 O LP monitoring Always ¦ Without thawing

Always

2893 F Number of TWW loading attempts 3 2910 F Clearance above TA --- 2951 I Thawing clearance below TA 10 2954 O Evaporator temp. Thawing end 5 2963 I Time until forced thaw 180 2964 I Thawing time max 20 2971 O Thawing ventilator above 7 3010 O Max. speed V'lator/Q'pump 40 60 100

3541 F Auto sequential exclusion None ¦ First ¦ Last ¦ First and Last

First None

5093 F With solar integration No ¦ Yes

No

5710 I Heating circuit 1 Off

5731 I Drinking water control element Q3 None ¦ Charge pump ¦ Reversing valve

Reversing valve

5800 I Heat source Brine ¦ Water ¦ Air ¦ External

Air Brine

Page 94: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

11. Hydraulic Diagrams ThermSelect®

94/100

Control bar

User -level Function / Default value

Set value RVS Air 15

Air 19-28

Air 34-41

Brine 15

Brine 19-41

5890 I

Relay output QX1 None ¦ Condenser stage 2 K2 ¦ Process reversing valve Y22 ¦ Hot gas temperature K31 ¦ Electrical insert1 Flow K25 ¦ Electrical insert2 Flow K26 ¦ Reversing valve cool-ing Track2 Y28 ¦ Delivery pump Q14 ¦ Cascade pump Q25 ¦ Generator shut-off valve Y4 ¦ Electrical insert TWW K6 ¦ Circulation pump Q4 ¦ Storage charge-over pump Q11 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Mixing pump Q35 ¦ Collector pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump ext.exchanger K9 ¦ Solar con-trol element buffer K8 ¦ Solar control element swimming pool K18 ¦ Electrical insert buffer K16 ¦ H1-Pump Q15 ¦ H2-Pump Q18 ¦ H3-Pump Q19 ¦ Heating cycle pump HkP Q20 ¦ 2nd Pump stage HK1 Q21 ¦ 2. Pump stage HK2 Q22 ¦ 2nd Pump stage HKP Q23 ¦ Reversing valve cooling Y21 ¦ Air dehumidifier K29 ¦ Heat request K27 ¦ Refrigeration request

Process reversing valve Y22 None

5891 I

Relais output QX2 None ¦ Condenser stage 2 K2 ¦ Process reversing valve Y22 ¦ Hot gas temperature K31 ¦ Electrical insert1 Flow K25 ¦ Electrical insert2 Flow K26 ¦ Reversing valve cool-ing Track2 Y28 ¦ Delivery pump Q14 ¦ Cascade pump Q25 ¦ Generator shut-off valve Y4 ¦ Electrical insert TWW K6 ¦ Circulation pump Q4 ¦ Storage charge-over pump Q11 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Mixing pump Q35 ¦ Collektor pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump ext.exchanger K9 ¦ Solar con-trol element buffer K8 ¦ Solar control element swimming pool K18 ¦ Electrical insert buffer K16 ¦ H1-Pump Q15 ¦ H2-Pump Q18 ¦ H3-Pump Q19 ¦ Heating cycle pump HkP Q20 ¦ 2. Pump stage HK1 Q21 ¦ 2. Pump stage HK2 Q22 ¦ 2. Pump stage HKP Q23 ¦ Reversing valve cooling Y21 ¦ Air dehumidifier K29 ¦ Heat request K27 ¦ Refrigeration request

Heat requirement K27 None

5930 I

Sensor input BX1 None ¦ Buffer reservoir sensor B4 ¦ Buffer reservoir sen-sor B41 ¦ Collector sensor B6 ¦ Drinking water sensor B31* ¦ Hot gas sensor B82 ¦ Refrigerant sensor liquid B83 ¦ TWW Charge sensor B36 ¦ TWW Tapping sensor B38 ¦ TWW Circulation sensor B39 ¦ Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64 ¦ Buffer reservoir sensor B42 ¦ Track flow sensor B10 ¦ Cascade return sensor B70 ¦ Special temperature sensor 1 ¦ Special tempera-ture sensor 2

Track flow sensor B10

Special -temperature

sensor 1

5931 I

Sensor input BX2 None ¦ Buffer reservoir sensor B4 ¦ Buffer reservoir sen-sor B41 ¦ Collector sensor B6 ¦ Drinking water sensor B31* ¦ Hot gas sensor B82 ¦ Refrigerant sensor liquid B83 ¦ TWW Charge sensor B36 ¦ TWW Tapping sensor B38 ¦ TWW Circulation sensor B39 ¦ Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64 ¦ Buffer reservoir sensor B42 ¦ Track flow sensor B10 ¦ Cascade return sensor B70 ¦ Special temperature sensor 1 ¦ Special tempera-ture sensor 2

Refrigerant liquid B83

Page 95: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® 11. Hydraulic Diagrams

95/100

Control bar

User -level Function / Default value

Set value RVS Air 15

Air 19-28

Air 34-41

Brine 15

Brine 19-41

5950 I

Function input H1 BA toggle HK's+TWW ¦ BA toggle HK's ¦ BA toggle HK1 ¦ BA toggle HK2 ¦ BA toggle HKP ¦ Error / alarm mes-sage ¦ Minimum flow targe value ¦ Heat requirement 10V ¦ Thaw point guard ¦ Flow target value increase hygro ¦ Refrigeration request ¦ Refrigeration request 10V ¦ Pres-sure measurement 10V ¦ Relative room humidity 10V ¦ Room temperature 10V ¦ Clearance swimming pool ¦ Switch-on command WP level 1 ¦ Switch-on command WP level 2

Switch-on command WP level 1

5952 I Function value contact H1 55

5981 O Control direction input EX1 Break contact ¦ Working contact

Break contact

5999 O Control direction LP guard E9 Break contact ¦ Working contact

Break contact

6000 O Control direction HP guard E10 Break contact ¦ Working contact

Break contact

6001 O Cntrl dir. Evap1 overload E11 Break contact ¦ Working contact

Work -

con-tact

Break contact

Work -

con-tact

Break con-tact

6070 I

Function output UX None ¦ Source pump Q8/Venti K19 ¦ Drinking water pump Q3 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Instantaneous water filter Q34 ¦ Collector pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump buffer K8 ¦ Solar pump ext. exchanger K9 ¦ Solar pump swimming pool K18 ¦ Heating circuit pump HK1 Q2 ¦ Heating circuit pump HK2 Q6 ¦ Heating circuit pump HKP Q20 ¦ Heat pump target value ¦ Output target value ¦ Heat require-ment ¦ Cold requirement ¦ Heat pump modulating

Source pump Q8/Venti K19

6128 O Heat request below outdoor temp 5 --- 6600 I Device address 1 2

6640 I Timer mode Autonomous ¦ Slave without remote adjustment ¦ Slave with remote adjustment ¦ Master

Master Slave without remoten ad-

justment

Error No. 35 ST Repeat of error 225: Low pressure 0

Page 96: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

Your notes ThermSelect®

96/100

Page 97: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® Your Notes

97/100

Page 98: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

Your notes ThermSelect®

98/100

12 Index

Page 99: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

ThermSelect® Index

99/100

A

Application limits .......................................................... 39, 51

C

Changes to the device ....................................................... 10 Circuit diagram for ThermSelect® 15 ................................. 26 Circuit diagram for ThermSelect® 19-41 ............................ 28 Circuit diagram für ThermSelect® 15 ................................. 26 Connection of split evaporator with heat pump .................. 48 Connection split evaporator ............................................... 44 Connection terminals ventilator ......................................... 55 Connections at rear wall of heat pump .............................. 20 Control unit AVS ................................................................ 65

D

Device damage ..................................... 5, 40, 42, 43, 63, 77 Disassembly of the control unit .......................................... 70 Duty of documentation........................................... 41, 63, 68

E

Electrical connection for compressor ................................. 54 Electrical connections for RVS controller ........................... 54 Electrical current .................................................................. 8 Electrotechnical data controller ......................................... 34 Enclosure assembly .......................................................... 56 Environmental damage .......................................... 10, 42, 48 EU Design Conformity Declaration .................................... 80

F

Factory parameterisation for ThermSelect® design ........... 90 Factory parameterisation for ThermSelect® Pro design ..... 93

G

Generator shut-off valve ........................................ 33, 91, 94

H

Heat pump connections ..................................................... 49 Heat pump installation ....................................................... 46 Heating water ........................................................ 10, 50, 74 Hot surfaces ........................................................................ 8 Hydraulic connections ....................................................... 50

I Installation clearances ....................................................... 39

L

Limit of liability ................................................................... 76

M

Maintenance record .................................................... 69, 81 Motor control unit .............................................................. 60

P

Planning information for brine operation ........................... 38 Pump control ..................................................................... 64

R

Refrigerant ................................. 9, 17, 39, 40, 43, 48, 63, 69 Refrigerant dosage............................... 24, 43, 48, 64, 67, 76 Requirements for the heat transfer liquid .......................... 50

S

Safekeeping of documentation ............................................ 4 Sensor positions ............................................................... 30 Spare parts ................................................................. 77, 78 Special tariff connection .................................................... 54 Split evaporator ......................................... 21, 41, 42, 43, 48 Split evaporator assembly ................................................. 41 Standards / Regulations for Austria .................................. 12 Standards / Regulations for Switzerland ........................... 13 Switching on the device .................................................... 64

T

Terminal assignment on the heat pump controller ............ 32 Transport ..................................................................... 14, 40

W

Warranty ......................................................... 38, 76, 77, 78 Warranty certificate ........................................................... 78 Water damage .................................................................. 47 Wearing parts .................................................................... 78 Welding work .................................................................... 41

Page 100: ThermSelect - ESI · 1. Safety ThermSelect® 4/100 1 Safety 1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating

Your notes ThermSelect®

100/100