thermselect - esi · 1. safety thermselect® 4/100 1 safety 1.1 general assembly, commissioning and...
TRANSCRIPT
ThermSelect® As of 9 March 2011
Table of Contents
1 Safety ............................................................................................................................................................ 4 1.1 General .......................................................................................................................................................................... 4 1.2 Intended use .................................................................................................................................................................. 5 1.3 Explanation of symbols .................................................................................................................................................. 6 1.4 Personnel requirements ................................................................................................................................................ 7 1.5 Special dangers ............................................................................................................................................................. 8
2 Standards and Regulations ...................................................................................................................... 11 2.1 Standards and Regulations ......................................................................................................................................... 11
3 Transport, Packaging, Storage ................................................................................................................ 14 3.1 Safety notes for transport ............................................................................................................................................ 14 3.2 Inspection of the delivery ............................................................................................................................................. 15 3.3 Notes on storage ......................................................................................................................................................... 15 3.4 Handling of packaging material ................................................................................................................................... 15 3.5 Disposal of packaging ................................................................................................................................................. 16 3.6 Disposal of the device ................................................................................................................................................. 16
4 General ....................................................................................................................................................... 17 4.1 Product description ...................................................................................................................................................... 17 4.2 What is included .......................................................................................................................................................... 18 4.3 Accessories ................................................................................................................................................................. 18
5 Technical data ............................................................................................................................................ 20 5.1 Dimensions and connection ratings ............................................................................................................................. 20 5.2 Identification plate ........................................................................................................................................................ 22 5.3 Technical data ............................................................................................................................................................. 24 5.4 Electrical data .............................................................................................................................................................. 26
6 Installation .................................................................................................................................................. 36 6.1 Safety during assembly ............................................................................................................................................... 36 6.2 Requirements on the erection location of the heat pump ............................................................................................ 36 6.3 Assembly tools ............................................................................................................................................................ 39 6.4 Installation information ................................................................................................................................................. 39 6.5 Hydraulic connection ................................................................................................................................................... 50 6.6 Electrical connection .................................................................................................................................................... 52
Table of Contents
7 Commissioning ......................................................................................................................................... 62 7.1 Safety during startup ................................................................................................................................................... 62 7.2 Inspection prior to startup ............................................................................................................................................ 62 7.3 Commissioning ............................................................................................................................................................ 63 7.4 Setting the controller .................................................................................................................................................... 65 7.5 Parameterisation ......................................................................................................................................................... 66 7.6 Commissioning record ................................................................................................................................................. 66
8 Maintenance ............................................................................................................................................... 67 8.1 Maintenance ................................................................................................................................................................ 67 8.2 Components relevant to safety .................................................................................................................................... 68 8.3 Work to be carried out ................................................................................................................................................. 68 8.4 Spare part drawing and legend .................................................................................................................................... 72
9 Troubleshooting ........................................................................................................................................ 73 9.1 Troubleshooting ........................................................................................................................................................... 73
10 Warranty ..................................................................................................................................................... 76 10.1 Warranty ...................................................................................................................................................................... 76 10.2 Manufacturer Certificate / EU Design Conformity Declaration ..................................................................................... 79 10.3 Proof of Service ........................................................................................................................................................... 81
11 Hydraulic diagrams ................................................................................................................................... 86 11.1 Hydraulic diagrams ...................................................................................................................................................... 86
12 Index ........................................................................................................................................................... 98
1. Safety ThermSelect®
4/100
1 Safety
1.1 General Assembly, Commissioning and Maintenance Instructions - are addressed to technicians of professional heating companies. - Contains important information for safe handling of the device.
Compliance with all specified safety information and handling in-structions is the prerequisite for safe working.
- Must be following by all persons working on the device. The information contained in this document is accurate and up to date to the best of our knowledge at the time of writing. The information provided serves as a reference for the safe operation of the product named in the Assembly, Startup, and Maintenance Instructions. The information provided is not transferable to any other products.
Safekeeping of documentation
NOTE! These instructions must remain on the device, so that they are also available if required later. With a change of operator, the instructions must be handed over to the subsequent operator.
ThermSelect® 1. Safety
5/100
1.2 Intended use The devices are intended as heat sources for closed warm water central heating systems and for central warm water preparation. Any other or more comprehensive use is not as intended. MHG Heiztechnik does not assume any liability for consequential damages. The risk will be borne by the owner of the equipment alone. MHG devices have been built in accordance with the applicable standards and guidelines as well as the valid safety rules. However, personal injuries or property damage may occur if not used properly. To avoid hazards, the device may only be used: - For its intended purpose - In a proper condition, in terms of safety equipment - In compliance with the instructions for Assembly, Startup and
Maintenance, as well as the operating instructions - In compliance with the necessary maintenance activities - In compliance with the technologically required minimum and max-
imum values - If malfunctions that may compromise safety have been remedied
immediately - If all of the safety and warning signs attached on and in the device
are not removed and remain legible
CAUTION! Device damage through weather impacts! Electrical hazard through water and corrosion of the enclosure and the components. Therefore: - The internal unit may not be operated outdoors. It is
suitable only for operation in rooms.
CAUTION! System damage from frost! The heating system can freeze in case of frost. Therefore: - Leave the heating system in operation during a
frost period, so that the rooms are sufficiently tem-pered. This also applies in the case of the opera-tor's absence or if the rooms are vacant.
1. Safety ThermSelect®
6/100
1.3 Explanation of symbols The section provides an overview of all important safety aspects for optimum personal safety, as well as for safe and fault-free opera-tion. The handling instructions and safety notes specified in these instruc-tions must be followed to prevent accidents, personal injuries and property damages.
DANGER! … indicates life-threatening situations due to electric current.
WARNING! … indicates a possibly hazardous situation, which can lead to death or serious injuries, if not avoided.
PRECAUTION! … indicates a possibly hazardous situation, which can lead to minor or slight injuries, if not avoided.
CAUTION! ... indicates a possibly hazardous situation, which can lead to property damage, if not avoided.
NOTE! ... highlights useful tips and recommendations, as well as information for efficient and fault-free opera-tion.
ThermSelect® 1. Safety
7/100
1.4 Personnel requirements
WARNING! Danger to life if not sufficiently qualified! Improper handling leads to considerable personal injuries and property damages. Therefore: - Assembly, startup and maintenance works, repairs
or change to the set fuel quantity may only be car-ried out by a heating and/or air conditioning professional.
- Consult professionals in case of doubt. The following qualifications for various task areas are listed in the instructions: - Equipment operator
must be informed about the handling of the equipment; in particu-lar, he must receive the operating instructions for the device. He is responsible for the proper operation of the system and must en-sure that it is regularly serviced by a specialist fitter.
- Technical personnel are able because of their technical training, know-how and expe-rience as well as knowledge of the relevant regulations to carry out the work activities assigned to them and to detect possible dangers on their own.
- Cooling systems technician must provide certification in accordance with Article 5 of the Commission Regulation (EC) No 303/2008 establishing, pursuant to Regulation (EC) No 842/2006 of the European Parliament and of the Council. 2, Sentence 1 of ChemKlimaschutzV (Chemicals- Climate Protection Regulation)
1. Safety ThermSelect®
8/100
1.5 Special dangers In the following section the remaining risks are specified which result based on the risk analysis. The safety information listed here and the warning instructions in the subsequent chapters of this manual must be followed to reduce health risks and to avoid dangerous situations.
Electrical current
DANGER! Risk to life through electrical current! Contact with live components can cause serious inju-ries. Therefore: - Work on electrical systems may only be performed
by professional electricians. - Turn off electric power before beginning the work
activities and secure against being turned on again.- In case of damaged insulation, immediately cut off
the power supply and initiate the repair.
Hot surfaces
PRECAUTION! Risk of burning from hot surfaces! Contact with hot components can cause burns. Therefore: - Always wear protective gloves when working near
hot components. - Make sure that all components have cooled down
to the ambient temperature before commencing any work.
- Do not touch the compressor and hot gas line dur-ing operation.
ThermSelect® 1. Safety
9/100
Refrigerant The safety datasheet concerning refrigerant R 407 C is available for download at www.mhg.de\Download\Sicherheitsdatenblätter.
NOTE! in case of emergencies, ring the telephone number below: +44(0)208 762 83 22 [CareChem 24] (Europe)
WARNING! Danger to life through lack of oxygen! Vapours of the refrigerants R 407 C are heavier than air and may cause suffocation by displacing oxygen. Therefore: - Exercise special caution when entering lower lying
closed rooms. - Work on the refrigerant circulation may only be per-
formed by persons possessing a refrigeration cer-tificate in accordance with ChemKlimaschutzV.
- Do not smoke when handling refrigerant as its products of decomposition in the lit cigarette act as an irritant and a poison!
PRECAUTION! Risk of injury due to refrigerant! Refrigerant is corrosive and causes cold burns upon contact with skin. Therefore: - Wear chemical-resistant protective gloves when
handling refrigerant at any time. - Wear protective glasses to avoid contact with eyes.
1. Safety ThermSelect®
10/100
Changes to the device WARNING! Risk of life through electrical shock as well as de-struction of the device from water leakage! The operating permit becomes void when making modifications to the device! Therefore: Do not make any modifications to the following items: - To the safety valve and to the outlet line for the
heating water - To structural circumstances, which can have an
influence on the operating safety of the device. - Opening and/or repairing original parts (e.g. drive,
controller)
WARNING! Risk to life and damage to the environment through refrigerant leakage! The operating permit becomes void when making modifications to the device! Therefore: Do not make any modifications to the following items: - To the interior or exterior unit of the device - On the lines for water, electrical power and refrige-
rant
Heating water
WARNING! Risk of poisoning through heating water! The use of heating water leads to poisoning. Therefore: - Never use heating water as drinking water because
it is contaminated from dissolved deposits.
ThermSelect® 2. Standards and Regulations
11/100
2 Standards and Regulations
2.1 Standards and Regulations The following standards and regulations must be observed with the installation and operation of the heating system.
Standards
Standards Publication date Title
DIN EN 12056 01.2001 Drainage systems
DIN EN 12502 01.2001 Corrosion protection of metallic ma-
terials
DIN EN 12828 06.2003
Heating systems in buildings, safety equipment of warm water heating systems
DIN EN 60335, Part 1 2004 Safety of electrical appliances for
household and similar purposes
DIN 1986 --- Materials drainage system / Proper-ty drainage
DIN 1988 12.1988 Technical rules for drinking water installations (TRWI)
DIN 4726 01.2001 Plastic pipes for warm water floor heating
DIN 4753 03.1988 Water heaters and water heating systems for drinking and service water
DIN 18380 10.2006 Heating systems and central water heating systems (VOB)
Regulations
The erection and operation of the heating system requires com-pliance with the technical building supervision rules as well as other legal stipulations of the individual countries.
Regulations Publication date Title
EC Regula-tion No 842/2006
07.2006
F-Gas Directive regulates all chlorine-free fluori-nated refrigerants (CFC and HFC, i.e. R134A, R404A, R407C, R410A, R507)
EnEV (Ger-man Energy Conservation Regulations)
12.2004 Energy savings directive
ATV ---
Worksheet ATV-A 115 "Discharging non-household waste water into a public waste water sys-tem"
2. Standards and Regulations ThermSelect®
12/100
Regulations Publication date Title
TA Noise 03.2000
Sixth General Administrative Regu-lation to the Federal Immission Con-trol Act (Technical Instruction on Noise Protection)
TRGS 521 Part 4 --- Technical rules for hazardous sub-
stances
VDI 2035 12.2006
Guidelines for the prevention of damages in warm water heating systems - calcification in drinking water heating systems and warm water heating systems
VDE --- Stipulations and special require-ments of the public utility companies
Additional Standards / Regulations for Austria
In Austria, the local building regulations as well as the ÖVGW regu-lations must be observed with the installation.
Standards Publication date Title
ÖNORM EN 14336 2004 Heating systems in buildings - Plan-
ning of warm water planning systems
ÖNORM H 5195-1 05.2006
Prevention of damages through cor-rosion and calcification in closed warm water heating systems with op-erating temperatures up to 100 °C
ÖNORM M 7550 02.2002
Boilers with operation temperatures up to 100 °C - Terms, requirements, tests, designations
ThermSelect® 2. Standards and Regulations
13/100
Additional Standards / Regulations for Switzerland
Assembly, startup and maintenance may only be carried out by an approved installation company. Work on electric system compo-nents may only be carried out by a licensed electrical technician. The legal standards and stipulations on electrical installations must be followed, especially:
Directives / Guidelines by
LRV Swiss air purification directive VKF Association of cantonal fire insurances SVGW Swiss association of gas and water technologies
SEV Swiss association for electrical, energy and in-formation technology
SWKI Swiss Association of Heating and Air Condition-ing Engineers
Gebäude-Klima Schweiz
Association of the Heat, Ventilation and Air Con-ditioning Technology Industry
GebäudeKlima Schweiz Technical Bulletins
(formerly PROCAL)
Corrosion damages through oxygen in heating water - oxygen cor-rosion Corrosion through halogenated hydrocarbons Information regarding corrosion damage from water heating Procal / AWP Guideline on the processing and quality of water in the heating system Procal / AWP
BUWAL Technical Bulletins
Approval of systems with refrigerants stable in air
3. Transport, Packaging, Storage ThermSelect®
14/100
3 Transport, Packaging, Storage
3.1 Safety notes for transport CAUTION! Damage through improper transport! Significant property damage may be incurred by im-proper transport. Therefore: - Be careful when unloading packaging items upon
delivery as well as during in-plant transport and obey the symbols on the packaging.
- Do not expose the device to hard shocks. - Use only the intended slinging points. - Remove the packaging only shortly before assem-
bly.
CAUTION! Device damage through improper handling! The machine oil shifts. Therefore: - The heat pump may only be transported standing
and never horizontally. - The heat pump may only be tilted up to 45° for a
short time.
CAUTION! Device damage through improper handling! The copper pipes can be easily bent! Therefore: - Do not hold on to the insulated pipe (hot gas line)! - Apply force only to the base plate or the frame!
PRECAUTION! Risk of injury through improper handling! Improper handling can cause injuries like contusions, cuts and bruises. Therefore: - Personal safety equipment: Safety shoes and safety
gloves must be worn for handling and transport.
ThermSelect® 3. Transport, Packaging, Storage
15/100
3.2 Inspection of the delivery Inspect the delivery immediately upon receipt for completeness and transport damages. Proceed as follows when noting eternally visible transport damages: - Do not accept the delivery or only conditionally. - Note the extent of the damage on the transport documents or the
delivery bill of the freight forwarder. - Initiate complaint.
NOTE! Report each defect as soon as it is detected. Damage compensation claims can only be asserted within the respective claim periods.
3.3 Notes on storage The shaft of the circulation pump may seize during extended sto-rage. Moisture condensation, icing and water impact are not permitted. Temperature range: -10°C … +50°C Humidity: < 95% rel. hum.
3.4 Handling of packaging -material
WARNING! Risk of suffocation from plastic foils! Plastic foils and bags, etc. can become a dangerous toy for children. Therefore: - Do not allow packaging material to lie carelessly
about. - Packaging material must never get into the hands
of children!
3. Transport, Packaging, Storage ThermSelect®
16/100
3.5 Disposal of packaging Recycling: The entire packaging material (carton material, routing sheets, plastic foils and pouches) are completely recyclable.
3.6 Disposal of the device
NOTES FOR DISPOSAL! - The device contains electrical and electronic com-
ponents. - Please do not dispose of device or replaced parts in
household waste. Proper disposal of hazardous waste is required.
- End-of-life devices must be taken to the respective public collection point for proper disposal.
- Disposal must be in accordance with current local laws and regulations.
CAUTION! Environmental damage due to improper disposal! Refrigerant and compressor leak. Therefore: - In accordance with EC Regulation No 842/2006, op-
erators of stationary facilities are responsible for putting in place arrangements for the proper recov-ery of fluorinated greenhouse gases by certified personnel to ensure their recycling, reclamation or destruction.
ThermSelect® 4. General
17/100
4 General
4.1 Product description ThermSelect® is is available in the versions,
• ThermSelect® • ThermSelect® Pro • ThermSelect® Sun • ThermSelect® Sun Pro
and with extensive accessory sets. The standard sizes are available for a capacity range from 10.4-40.9 kW. ThermSelect® mode of operation Ground or air heat are alternatively used after specifying a bivalence point. ThermSelect® Pro mode of operation Ground and/or air heat are used in parallel or alternatively. ThermSelect® Sun mode of operation Ground or air heat are alternatively used on the source side and so-lar heat on the sink side. ThermSelect® Sun Pro mode of operation Ground and air heat plus solar heat are used on the source side, so-lar heat is fed into the heat sink if there is an excess. Inner part: - Combined, space-saving air-brine/water heat pump hybrid system
in a compact design with 2 integrated, weather-controlled heat pump controllers
- Size width x depth x height • Version 1:: 690x600x900 • Version 2: 1,030x730x900
- Quiet running through sound-decoupled cooling unit, low noise de-velopment through sound-decoupled compressor and sound-insulated housing
- High-performance evaporator for brine operation - Outdoor temperature sensor, as well as flow and return heat pump
sensors, heat source inlet air, heat source inlet and outlet brine, evaporation, suction gas, refrigerant liquid and hot water sensor included in the scope of delivery
- Refrigerant R 407 C for heating water temperatures up to 55 °C at outside temperatures up to -7 °C
- Min. outside temperature -15 °C (constant mode) Outer part - Air evaporator with enlarged lamella spacing, as well as under-
cooling coil, drip plate heating, bend and expansion valve - Whisper ventilator with highly efficient electronic motor - Weather-resistant design with snow protection roof - Colour: Light-grey (RAL 7035) - Condensation drainage on gravel bed
4. General ThermSelect®
18/100
4.2 What is included - Heat pump with interior and exterior unit, including 2 heat pump
controllers RVS 61.483 and 2 control units AVS 37.294 - From ThermSelect 10 soft-start control - Module for thawing the split evaporator via hot-gas bypass con-
trols
4.3 Accessories
Control unit QAA 75 94.88147-5019
Cable-linked control unit optionally usable as a control unit, service device or room device. Setting of all parameters in the RVS control-ler, mode reserve for time greater than 12 hours
Control unit QAA 78 94.88147-5021
Radio-linked control unit optionally usable as a control unit, service device or room device. Setting of all parameters in the RVS control-ler, range of radio link approx. 30 m
Radio module AVS 13.399/201 94.88147-5022
Transmitter and receiver for external temperature sensor QAC 34
Repeater AVS 14.390/101 94.88147-5017
Range expansion for controller RVS 61.843 The radio repeater is used for rand expansion. It is not an amplifier, but rather, a device for receiving and forwarding signals.
Contact temperature sensor QAD 36.101 94.19314-5015
NTC 10 kOhm
ThermSelect® 4. General
19/100
Service water sensor QAZ 36 94.19314-5013 (2 m) 94.19314-5012 (6 m)
Service water sensor QAZ 36 for recording the hot water storage temperature for Boiler Management Unit LMU and RVS with con-nection cable 2x0.5 mm², NTC 10 kOhm, 10000 Ohm at 25°C.
Collector sensor QAZ 36.481/101 94.19314-5018 (1.5 m)
For RVS or LMU
Additional heater 6.0 kW 98.38400-6302
Additional electric heater 6.0 kW (3 x 2 kW, 400 V) incl. contactor and connection cable set for controller RVS 61.843
Reservoir
Heat pumps require special reservoirs. MHG carries all required special high-capacity buffer and zone reservoirs in its program.
5. Technical Data ThermSelect®
20/100
5 Technical data
5.1 Dimensions and connection ratings
Connections at rear wall of heat pump
Sk09-6200-023_aStand: 06.11.09
Fig. 1: Connections at rear wall of heat pump ThermSelect 15 (Version 1) schematic diagram. The device illustrated does not cor-respond to the supplied interior unit.
Fig. 2: Connections at rear wall of heat pump ThermSelect 19 to
41 (Version 2)
ThermSelect® 5. Technical Data
21/100
Erection measurements and dimensions, split evaporator for ThermSelect®
Fig. 3: Erection measurements and dimensions, split evaporator for ThermSelect®
Legend for Fig. 3:
Abbreviation Meaning ThermSelect®... 15 19 28 34 41
1 Fluid line 15 18 22 2 Suction gas line 28 35 42 3 Hot-gas thawing 12 15 18
A Weather guard in mm 2155 3080 B Floor mount in mm 1880 2805 C Min. distance to walls and obstacles > 200 mm D Min. distance to walls and obstacles > 500 mm
EAL Electrical connection of fan (split evaporator) 3x0.75 mm² supply line 0-10 V signal 2x0.75 mm²
FA Foundation Take note of the following information! KB Gravel bed min. 250 mm deep KRS Refrigerant pipe connection STR Direction of flow
ZAF Supply line temperature sensor 2x2x0.75 mm² (see also page 34 "Electrotechnical data controller")
NOTE! It Fig. 3 represents a schematic diagram. It is not to be used instead of a professional layout de-signed by professionals. The foundation and the gravel bed must reach at least across a width of 400 mm. The gravel bed must reach up to approx. to the foundation.
5. Technical Data ThermSelect®
22/100
5.2 Identification plate
Fig. 4: Sample identification plate
ThermSelect® 5. Technical Data
23/100
Legend for Fig. 4:
Abbrev-iation Meaning
1 Type 2 Part no. / Item number 3 Country of destination 4 Serial number 5 Refrigerant 6 Refrigerant dosage 7 Output A2/W35 8 Output B0/W35 9 Output W10/W35
10 Output W7/W35 11 Rated thermal output 12 max. positive operating pressure 13 max. flow temperature 14 Pressure limiter 15 Electric connection 16 Power consumption 17 Power current 18 Control current 19 Rated current 20 Operating current 21 Starting current (compressor) 22 Protection class 23 Manufacturer 24 CAUTION HIGH VOLTAGE
5. Technical Data ThermSelect®
24/100
5.3 Technical data
Air+Brine/Water Head Pumps* ThermSelect® 15 to 41
ThermSelect®.. 15 19 28 34 41
Output A2/W35* Nominal heating capacity kW 16,2 20,5 28,8 35,4 43,0 Power consumption condenser* kW 3,3 4,6 6,1 7,5 9,2 Cooling capacity* kW 13,0 16,1 23,1 28,2 34,3 Performance number* COP 4,7 4,4 4,6 4,5 4,5 Output B0/W35* Nominal heating capacity kW 15,1 19,1 26,9 33,1 40,2 Power consumption condenser** kW 3,3 4,5 6,0 7,4 9,0 Cooling capacity** kW 12,0 14,9 21,2 26,0 31,7 Performance number** COP 4,4 4,1 4,3 4,3 4,3 Refrigerant R 407 c for hot water temperatures up to 55 °C Refrigerant dosage for max. 20 m line length*** kg 10,0 12,0 15,5 20,2 20,7
Refrigerant lines Liquid (1)
mm 15 18 22
Suction gas (2) 28 35 42 Thawing (3) 12 15 18
Nominal power consumption A 7,4 12,6 14,3 16,2 18,6 Operating current, max. A 11,8 16,0 21,0 25,0 32,0 Starting current with soft-start A 37,0 49,5 63,5 83,5 99,0 Blocked rotor current A 74,0 99,0 127,0 167,0 198,0 Power circuit breaker / Automatic circuit breaker, slow (C characteristic) A 3x25 3x32 3x40 3x63
Recommended wire gauge mm² 3x4.0 3x6.0 3x10.0Electric connection Compressor control current 3NPE, 400 V
1NPE, 230 V Protection class heat pump according to EN 60529 IP 40
Protection class split evaporator according to EN 60529 IP 54
Evaporated air flow rate, nominal m³/h 5220 6670 10820 16010 14800 Sound pressure at 5 m dB (A) 35 41 43 53 53 Mass flow heating system nominal kg/h 2630 3340 4700 5780 6900 Pressure loss heating water at nominal flow rate kPa 5,8 3,2 4,5 4,2 5,2 Heating connection AG“ 1 1½ Outer dimensions W x D x H inner part mm 690x600x900 1030x730x900 Outer dimensions W x D x H outer part mm 2155x880x1030 3080x880x1030 Weight of inner part kg 198 225 238 250 258 Weight of outer part kg 138 152 202 223
* Heating capacity and COP at A2/W35 as well as source side 3 K and heating side 5K spread ** Output ratings at B0/W35 as well as source side 3K and heating side 5K spread *** When changes to refrigerant lines lead to lengths exceeding 20 m, refrigerant dosage will change as follows: Pipe
with max. Ø 22 mm +/- 100 g/m, pipe with max. Ø 28 mm +/- 150 g/m, pipe with max. Ø 35 mm +/- 200 g/m
NOTE! Refrigerant R407C for heating water temperatures up to H55 °C.
ThermSelect® 5. Technical Data
25/100
5. Technical Data ThermSelect®
26/100
5.4 Electrical data
Circuit diagram for ThermSelect® 15
AVS37.294/209
RVS 61.843
KP
Stand: 10.05.2010Sk10-0504-165
VER
M1
S1
LG
NOTHS
(STf) (NTf)
V-SPMV-A MV-Hz MV-FLL MV-FLL
22
L PE N E9 E10 Ex1 Ex2 Ex3 Ex4 Ex5 Ex7 K1 N PE Q3 N PE Y2 N PE N PE PE Qx2 N PE Qx3 N PE Qx4 Qx5 NPE Y1 N Q9 Qx1 NE11 Q8K19
Q2Ex6 PE Qx6
MUXMBx5MBx4MBx3MBx2MBx1MB84MB91MB71MB1MB21MB9MB92
B3MB81H3MH1CL- G+CL+CL-CL+CL-CL+MBDBX50X30
ZYXWVUTSRQPKL PE N
Zyxwutsrqpnkhfebbba
A2
A1
K614
QP
RVS 61.843
RL-WP
QE QA SG
7
A2
A1
K714
111121
24
823
PKZM 0-...I > I >I >
Fig. 5: Sk10-0504-165
Circuit diagram for ThermSelect® 15
ThermSelect® 5. Technical Data
27/100
Legend for Fig. 5:
Abbrevi-ation Meaning Abbrevi-
ation Meaning
- When using fault current circuit breakers, pay attention to separate neutral lead for normal and special tariff!
- Observe identical phase potential of the control circuits for normal and special tariff!
- The individual relay outputs of the heating controller withstand a max. load of 4 A (at cos Phi>0.6).
- Maximum total current for terminals: 6 A. - This must be noted with the selection of the circulation pumps. Use
contactor, if necessary.
KMT Refrigerant temperature liquid KP Condenser pump LG Performance limit M Motor M1 Condenser motor MV-A Solenoid refrigerant circulation thawing (normally closed) MV-FLL Solenoid refrigerant circulation liquid gas line (normally closed) MV-Hz Solenoid refrigerant circulation heating (normally closed)
A1 Relay coil L N / N1 Neutral lead A2 Relay coil N ND Pressure switch low pressure AF Outdoor temperature sensor NOT Control switch or emergency switch (if required) AVS 37 Control unit (NTf) Normal tariff F1 Fine-wire fuse condenser pump / ventilator split evaporator 4 AT QA Source output (sensor) F2 Fine-wire fuse controller RVS 61.843 4 A slow QE Source intake (sensor) HD Pressure switch high pressure QP Source pump HS Main switch RVS 61 Heat pump controller K2 Relay toggle heating/thawing RL-WP Return heat pump (sensor) K3 Relay condenser pump S1 Motor control unit RSHL K4 Relay ventilator split evaporator SG Suction gas K5 Relay output compressor air (STf) Special tariff K6 Relay output compressor brine V-SP Ventilator split evaporator K7 Relay source pump brine VDT Evaporator temperature K8 Relay heat requirement brine VER Compressor VL-WP Flow - heat pump
NOTE! Terminal assignment of the heat pump controller RVS 61 s. pages 32-32
5. Technical Data ThermSelect®
28/100
Circuit diagram for ThermSelect® 19-41
AVS37.294/209
RVS 61.843
KP
Stand: 10.05.2010Sk10-0504-167
VER
M1
S1
LG
NOTHS
(STf) (NTf)
V-SPMV-A MV-Hz MV-FLL MV-FLL
22
L PE N E9 E10 Ex1 Ex2 Ex3 Ex4 Ex5 Ex7 K1 N PE Q3 N PE Y2 N PE N PE PE Qx2 N PE Qx3 N PE Qx4 Qx5 NPE Y1 N Q9 Qx1 NE11 Q8K19
Q2Ex6 PE Qx6
MUXMBx5MBx4MBx3MBx2MBx1MB84MB91MB71MB1MB21MB9MB92
B3MB81H3MH1CL- G+CL+CL-CL+CL-CL+MBDBX50X30
ZYXWVUTSRQPKL PE N
Zyxwutsrqpnkhfebbba
A2
A1
K614
QP
RVS 61.843
RL-WP
QE QA SG
7
A2
A1
K714
111121
24
823
INT 69
PKZM 0-...I > I >I >
Fig. 6: Sk10-0504-167
Circuit diagram for ThermSelect® 19-41
ThermSelect® 5. Technical Data
29/100
Legend for Fig. 5:
Abbrev-iation Meaning Abbrev-
iation Meaning
- When using fault current circuit breakers, pay attention to separate neutral lead for normal and special tariff!
- Observe identical phase potential of the con-trol circuits for normal and special tariff!
- The individual relay outputs of the heating controller withstand a max. load of 4 A (at cos Phi>0.6).
- Maximum total current for terminals: 6 A. - This must be noted with the selection of the
circulation pumps. Use contactor, if neces-sary.
KMT Refrigerant temperature liquid KP Condenser pump LG Performance limit M Motor M1 Condenser motor MV-A Solenoid refrigerant circulation thawing
(normally closed) MV-FLL Solenoid refrigerant circulation liquid
gas line (normally closed) MV-Hz Solenoid refrigerant circulation heating
(normally closed) N / N1 Neutral lead
A1 Relay coil L ND Pressure switch low pressure A2 Relay coil N
NOT Control switch or emergency switch (if required) AF Outdoor temperature sensor
AVS 37 Control unit (NTf) Normal tariff
F1 Fine-wire fuse condenser pump / ventilator split evaporator 4 AT
QA Source output (sensor) QE Source intake (sensor)
F2 Fine-wire fuse controller RVS 61.843 4 A slow QP Source pump HD Pressure switch high pressure RVS 61 Heat pump controller HS Main switch RL-WP Return heat pump (sensor) INT Winding protection INT S1 Motor control unit RSHL K2 Relay toggle heating/thawing SG Suction gas K3 Relay condenser pump (STf) Special tariff K4 Relay ventilator split evaporator V-SP Ventilator split evaporator K5 Relay output compressor air VDT Evaporator temperature K6 Relay output compressor brine VER Compressor K7 Relay source pump brine VL-WP Flow - heat pump K8 Relay heat requirement brine
NOTE! Terminal assignment of the heat pump controller RVS 61 s. pages 32-32
5. Technical Data ThermSelect®
30/100
Sensor positions
T
T
T
T
T
T
49.1
49.2
48.2 42.6
42.348.1
T
42.442.2
42.5
T
49.0
48.0
Fig. 7: Sensor positions
Legend for Fig. 7:
De-scrip-tion
Termin-al RVS 61 Air
Termin-al RVS
61 BrineMeaning
T T Temperature sensor 42.2 B21 Sensor air-heat pump flow 42.3 B71 Sensor air-heat pump return 42.4 B21 Sensor brine-heat pump flow 42.5 B71 Sensor brine-heat pump return 42.6 Bx1 Sensor track flow (B10) 48.0 Bx2 Sensor refrigerant liquid air (B83) 48.1 B84 Sensor KM evaporator air (VDF) 48.2 Bx1 Sensor refrigerant suction gas brine49.0 B91 Sensor source inlet air (QE) 49.1 B91 Sensor source inlet brine (QE) 49.2 B92 Sensor source outlet brine (QE)
ThermSelect® 5. Technical Data
31/100
5. Technical Data ThermSelect®
32/100
Terminal assignment on the heat pump controller RVS 61
Z Y X W V U T S R Q P K N L
z y x w u t s r q p n k h f e b b b a
NVD1BWLHK1PHK1MWQP-SPLPMFA1
RG2RG1BWAT
VLWPMFE1
MFE2MFE3
MFE4 LPB
NDHD
MFE
-AM
FE-B
MFE
-CM
FE-D
MFE
-EM
FE-F
MFE
-G
MFA2MFA3
MFA4MFA5
MFA6
BSBH1
H2VL1RLWP
WQEWQA
MFE5MFA7
Fig. 8: Terminal assignment on the heat pump controller RVS 61
Legend for Fig. 8:
Ab-brevia-
tion Meaning
Ab-brevia-
tion Meaning
AT Outside temperature sensor plug k, terminals M, B9
MFE4 Multifunctional sensor input 4 (functions, see MFE1) plug x, terminals M, BX4
BSB Service tool OCI 700
plug b, terminals CL- (ground), CL+ (data)
MFE5 Multifunctional sensor input 5
(functions, see MFE1) plug y, terminals M, BX5
BW Service water sensor
plug k, terminals M, B3 MFE-A Multifunctional input A
e.g. external heat pump block, low tariff, over-load-compressor, overload-source, pressure controller-source, flow controller source, flow controller-consumer, thawing manual, collec-tive fault heat pump plug P, terminal EX1
BWL Service water load pump / reversing valve plug R, terminals Q3, , N
H1 Digital-/O..10V input plug e, terminals H3, M, H1
H2 Digital input plug f, terminals M, B81
HD High-pressure pressostat plug K, terminal E10
MFE-B Multifunctional input B (Functions, see MFE-A) Connector P, terminal EX2
HK1M Heating circuit mixer 1
plug T, terminals Y2 (mixer motor close), , N, Y2 (mixer motor open)
MFE-C Multifunctional input C
(Functions, see MFE-A) plug P, terminal EX3
HK1P Heating circuit pump 1
plug S, terminals Q2, , N MFE-D Multifunctional input D
(Functions, see MFE-A) plug P, terminal EX4
LPB BUS plug a, terminals MB, DB
ThermSelect® 5. Technical Data
33/100
Ab-brevia-
tion Meaning
Ab-brevia-
tion Meaning
MFA1 Multifunctional output 1 e.g. collector pump, circulation pump, by-pass pump or heating circuit pump/electrical insert, generator shutoff valve plug W, terminal QX1, , N
MFE-E Multifunctional input E (Functions, see MFE-A) plug P, terminal EX5
MFE-F Multifunctional input F
(Functions, see MFE-A) plug P, terminal EX6
MFA2 Multifunctional output 2 (functions, see MFA1) plug W, terminal QX2, , N
MHE-G Multifunctional input G
(Functions, see MFE-A) plug P, terminal EX7
MFA3 Multifunctional output 3
(functions, see MFA1) plug X, terminals QX3, , N
N Power input
plug N, , L / terminal N, , L MFA4 Multifunctional output 4
(functions, see MFA1) plug Y, terminals QX4, , N
ND Low-pressure pressostat plug K, terminal E9
PLP Buffer loading pump plug V, terminals Q9, , N MFA5 Multifunctional output 5
(functions, see MFA1) plug Z, terminal QX5, , N
RG1 Room device 1
plug b, terminals G+, CL-, CL+ MFA6 Multifunctional output 6
(functions, see MFA1) plug Z, terminal QX6, , N
RG2 Room device 2 plug b, terminals CL-, CL+
RLWP Return sensor heat pump plug q, terminals M, B71 MFA7 Multifunctional analogue output
e.g. drinking water pump, intermediate cir-cuit pump, collector pump, solar pump, heating circuit pump plug z, terminals M, UX
VD1 Condenser compressor 1
plug Q, terminals K1, E11 VL1 Flow sensor heating circuit 1
plug p, terminals M, B1 MFE1 Multifunctional sensor input 1 e.g. buffer memory sensor, collector sen-sor, return sensor, drinking water sensor or swimming pool sensor plug t, terminals M, BX1
VLWP Flow sensor heat pump
plug n, terminals M, B21 WQA Heat source output
plug s, terminals M, B84/B92 MFE2 Multifunctional sensor input 2
(functions, see MFE1) plug u, terminals M, BX2
WQE Heat source input plug r, terminals M, B91
WQP-S Heat source pump/protection for pump plug U, terminals Q8/K19, , N MFE3 Multifunctional sensor input 3
(functions, see MFE1) plug w, terminals M, BX3
5. Technical Data ThermSelect®
34/100
Electrotechnical data controller
Input (controller)
Rated voltage AC 230 V (± 10%) Rated frequency 50/60 Hz Max. power consumption 11 VA Fuse protection of supply lines max. 10 A slow Wire gauge internal resistance
1 wire: 1.0 mm2 - 1.5 mm2 > 100 kΩ
Terminal wir-ing (Outputs)
Wire or stranded wire (twisted or with wire end ferrule): 1 wire: 0.5 mm2...2.5 mm2 2 wires 0.5. mm2..1.5 mm2
Functional -data Mode of functioning according to EN 60730 1b (automatic function)
Inputs
Digital inputs H1, 3
Extra-low voltage for potential-free extra-low voltage capable contacts: Voltage with opened contact: DC 12 V Voltage at closed contact: DC 3 mA
Analogue input H1, 3 Extra-low voltage work area: DC (0...10) V internal resistance: > 100 kΩ
Line inputs EX1…EX7, E9-E11 AC 230 V (± 10 %) Internal resistance > 100 kΩ
Sensor input B9 Sensor inputs B1, B3, B4, B21, B41, B71, B81, B82, B91 and B92 Sensor inputs BX1…BX5
NTC1k (QAC34) NTC10k (QAZ36, QAD36) NTC10K (QAZ36, QAD36), PT 1000
Permitted sensor lines (Cu) At wire gauge: Max. length:
0.25 0.5 0.75 1.0 1.5 (mm2) 20 40 60 80 120 (m)
Outputs
Relay outputs Q2, Q3, Q8, Q9, QX1..QX6, Y1, Y2 Rated current range Maximum starting current Maximum total current (all relays) Rated current range
AC 0.02...2 (2) A 15 A during ≤1 s AC 6 A AC (24...230) V (for potential-free outputs)
Output Q4 Mod rated current range ON/OFF mode RPM controller Maximum starting current
AC 0.05...2 (2) A AC 0.05...1.4 (1.4) A 4 A during ≤1 s
Analogue output UX Output voltage Current load Ripple Precision zero point Error remaining area
Output is short-circuit-proof Uout = 0 ... 10.0 V ±2 mA RMS; ±2.7 mA peak ≤ 50 mVpp < ± 80 mV ≤ 130 mV
ThermSelect® 5. Technical Data
35/100
Interfaces
BSB Max. line length base device-peripheral device Max. total line length Minimum wire gauge
2-wire connection, not interchangeable 200 m 400 m (Max. cable capacity: 60 nF) 0.5 mm2
LPB with controller-bus feed (per controller) with central bus feed bus load figure
Cu cable 1.5 mm2, 2-wire, not interchangeable250 m 460 m E = 3
Standards, safety, EMC, etc.)
CE conformity according to EMC guideline - stability - emissions Low-voltage guideline - electrical safety
2004/108/EC - EN 61000-6-2 - EN 61000-6-3 2006/95/EC - EN 60730-1, EN 60730-2-9
6. Assembly ThermSelect®
36/100
6 Installation
6.1 Safety during assembly
WARNING! Risk of injury due to improper assembly! Improper assembly leads to serious personal injuries and property damages. Therefore: - Assembly and startup must take place by an autho-
rised heating and/or air conditioning professional. - Provide sufficient installation clearance before be-
ginning with the work. - Be careful with open components with sharp edges.
DANGER! Risk to life through electrical current! Contact with live components can cause serious inju-ries. Therefore: - Work on electrical systems may only be performed
by professional electricians. - Turn off electric power before beginning the work
activities and secure against being turned on again.
6.2 Requirements on the erection location of the heat pump
Before doing the installation, make sure that the erection location meets the following requirements: - Operating temperature +5 °C to +30� - Dry, frost-proof, good air supply and ventilation - No heavy dust build-up - No high humidity - No air pollution through halogenated hydrocarbons (e.g. in sol-
vents, adhesives, spray cans) - No sulphur compounds - No vibrations and shocks - Stable, smooth and horizontal surface
NOTE! In case of existing systems, a dirt filter must be in-stalled on the heating side to protect the condenser.
Systems with above average temperature loads also require consultation with MHG Heiztechnik.
ThermSelect® 6. Assembly
37/100
WARNING! Risk of life through fire! Easily flammable materials or liquids can catch fire. Therefore: - Do not use or store explosive or easily flammable
substances (i.e. fuel, paints, paper, wood) in the area where the device is installed.
- Do not dry or store laundry or clothes in the area where the device is installed.
- Do not operate device in explosive atmosphere un-der any circumstances.
The following aspects must be taken into consideration already dur-ing the planning of the system, in addition to proper dimensioning: - Future location of the heat pump under the aspect of sound
transmission through air and structure-borne sound. The acoustics in the erection rooms with reverberating walls can increase the operating sound significantly. Countermeasure: acoustic insulation on one of the opposite wall or ceiling surfaces.
- To reduce the structure-borne sound transmission, create a sepa-rate pedestal (e.g. heavy concrete) in mounted in floating fashion (e.g. on rubber).
- A pedestal is recommended for easier maintenance and care.
NOTE! MHG Heiztechnik recommends the installation of an oil sump-pump especially if the condenser is located shut off in a room for several hours (below 12 °C) and it becomes colder than the evaporator. This condition can occur especially in combination with special so-lar systems.
NOTE! Thorough planning with adequately dimensioned heat source is especially important for reasons of operational reliability and improved working output.
6. Assembly ThermSelect®
38/100
Planning information for brine op-eration
The heat source for operation as a brine/water heat pump (horizon-tal absorber or vertical heating elements) must be configured in ac-cordance with the cooling capacity specified in the technical data. With the ThermSelect® version, the cooling capacity to be provided by the heat source can be reduced by up to 25%, as the source is not fully utilised over the entire heating period. With the ThermSelect® Pro version, the cooling capacity to be pro-vided by the heat source can be reduced by up to 50%, as the brine evaporator is exclusively operated in parallel with the air evaporator with outdoor temperatures of below approx. 5°C and the source is therefore utilised to a minor extent.
CAUTION! Freezing of the heat source due to incorrect operat-ing setting! Heat source becomes unusable for a long period of time. Therefore: - With this version, it is compulsory to exclusively
operate the brine evaporator in parallel with the air evaporator.
- A changeover to alternative mode, i.e. exclusive operation as a brine/water heat pump, overloads the heat source.
CAUTION! Freezing of the heat source due to incorrect dimen-sioning (overload)! Heat source becomes unusable for a long period of time. Therefore: - In case of doubt regarding the efficiency of the sur-
face, a geothermal response test must be carried out by an appropriate professional.
CAUTION! Damage to devices through freezing! The plate heat exchanger is destroyed on the source side, if the brine freezes. Therefore: - Monitor flow with safety devices (flow switch, pres-
sure switch). - The safety devices must be installed on site. The
regulations of the responsible authorities must be complied with.
Furthermore, dirt catchers, bubble separators and a rinsing device must be envisaged.
NOTE! Warranty becomes void if this information is disre-garded and damages can be traced to one of the listed causes.
ThermSelect® 6. Assembly
39/100
Application limits Heating water 20-55°C with refrigerant R 407 C
Installation clearances
Minimum clearances according to Fig. 3 are to be complied with, so that all work (assembly, startup, maintenance) can be carried out unhindered. - Observe the lateral clearance to the heat pump (min. 20 cm) to al-
low access for service and inspection.
6.3 Assembly tools The assembly and maintenance of the heating system requires standard tools from the field of heating installations, cooling installa-tion technology and water systems installations.
6.4 Installation information
CAUTION! Environmental damage through substances hazard-ous to groundwater! Substances hazardous to groundwater, such as greases, oils, refrigerants, solvent-based cleaning agents and the like, can burden the ground or get in-to the sewage system. Therefore: - These substances must be collected, stored and
transported in suitable containers and be disposed off.
The regulations of the heating and plumbing trade (DVGW, DIN, etc.) and of electrotechnics (potential equalization, utility company connection conditions, DIN, VDE, etc.) must be followed in particu-lar.
6. Assembly ThermSelect®
40/100
Transport NOTE! The heat pump may only be transported standing and never horizontally.
The heat pump is delivered standing on a wooden pallet. It can be transported on the pallet to the installation site. The heat pump can also be transported by 2 persons with carrying straps or transport cart.
CAUTION! Device damage through improper handling! The copper pipes can be easily bent! Therefore: - Do not hold on to the insulated pipe (hot gas line)! - Apply force only to the base plate or the frame!
Refrigerant
The safety datasheet concerning refrigerant R 407 C is available for download at www.mhg.de\Download\Sicherheitsdatenblätter.
NOTE! in case of emergencies, ring the telephone number below: +44(0)208 762 83 22 [CareChem 24] (Europe)
WARNING! Danger to life through lack of oxygen! Vapours of the refrigerants R 407 C are heavier than air and may cause suffocation by displacing oxygen. Therefore: - Exercise special caution when entering lower lying
closed rooms. - Work on the refrigerant circulation may only be per-
formed by persons possessing a refrigeration cer-tificate in accordance with ChemKlimaschutzV.
- Do not smoke when handling refrigerant as its products of decomposition in the lit cigarette act as an irritant and a poison!
PRECAUTION! Risk of injury due to refrigerant! Refrigerant is corrosive and causes cold burns upon contact with skin. Therefore: - Wear chemical-resistant protective gloves when
handling refrigerant at any time. - Wear protective glasses to avoid contact with eyes.
ThermSelect® 6. Assembly
41/100
NOTE! For operators of equipment containing 3kg or more of refrigerant the following duties of documentation apply: - Amount and type of refrigerant - Any amounts of refrigerant refills - Any amounts of refrigerant retrieved during startup,
maintenance or final disposal - Details identifying the company or technical per-
sonnel that carried out the installation, startup, or any maintenance work
- Dates and results of all inspections The recorded information must be presented to the relevant authorities and the commission upon re-quest.
Welding work
NOTE! If any welding work is scheduled on the refrigerant line, a protective gas (i.e. nitrogen) will need to be passed through the pipe in order to prevent scale formation. Scale and other contamination impair the proper operation and lead to faults.
Split evaporator assembly
PRECAUTION! Risk of injury due to refrigerant! Refrigerant is corrosive and causes cold burns upon contact with skin. Therefore: - Wear chemical-resistant protective gloves when
handling refrigerant at any time. - Wear protective glasses to avoid contact with eyes.
- The location of the evaporator must always be higher than the
heat pump unit (on slopes, pay attention to laying of the cooling line).
NOTE! Always install the split evaporator in flow direction parallel to the property boundary (not towards the neighbouring plot) in order to reduce noise transmis-sion to neighbouring properties.
NOTE! Ensure that no plants or objects are located in flow direction in order to guarantee efficient operation.
6. Assembly ThermSelect®
42/100
CAUTION! Device damage due to improper installation of cool-ing lines or improper positioning of the evaporator. Mechanical damage to the device can occur due to insufficient lubrication. Therefore: - Dimensioning and installation of cooling lines must
be carried out by technicians authorised by MHG. - The length of the cooling line may not exceed 15m
single distance. - The rise of the cooling line from the split evaporator
to the heat pump must not exceed 1.5 m. - The line dimensions are matched exactly to the capacity of the
heat pump (line length between heat pump and split evaporator 20 m). Altered line routing and clearances between heat pump and split evaporator must be agreed upon with MHG. Long line paths extend the duration of thawing and are to be avoided.
- The lines are insulated with diffusion-proof material. The gaps of the insulation must be glued.
CAUTION! Environmental damage due to improper assembly of the refrigerant line! Refrigerant and compressor oil can leak! Therefore: - Only use tools that are recommended for used in
the cooling unit: Bending wrench, pipe separator, deburrer and bordering tool
- Take note of bending radius to avoid bending or breaking of pipes.
- To avoid brittle or cracking pipes, do not bend the pipes repeatedly.
- In order to reduce loss of pressure and to ensure return of compressor oil, avoid unnecessary bend-ing of the pipes.
- Use appropriate fastening and insulation during refrigerant line installation.
- Use only non-cutting tools (special pipe cutting tools) to shorten refrigerant lines.
ThermSelect® 6. Assembly
43/100
CAUTION! Device damage through dirt and humidity. Dirt and humidity can enter the pipes when installing them. Therefore: - Make sure that no dirt or humidity enters the pipes
while installing them. - When laying pipelines underground, the laying
depth must be a minimum of 25 cm (on passable routes, a minimum of 50 cm).
- The installation of the pipelines must be carried out using a protective DN 100 pipe.
- The ends of the protective pipe must be sealed and waterproofed.
- The wall duct must be watertight. - Do not let clipping particles get into the refrigerant
line as these cause the destruction of the compres-sor.
NOTE! The heating pump contains refrigerant for a 15m max. length cooling line. Any shortening or lengthening of the line may only be carried out by a certified technician. The refrige-rant dosage must be checked for line lengths exceed-ing 20m, and be adjusted where required (approx. dosage values are available in chap. 5.3).
NOTE! The split evaporator contains a protective gas (nitro-gen) and must be evacuated simultaneously with the refrigerant lines.
NOTE! The technician must check the installation and mountings of the pipe, and establish a proper con-nection with the heating pump and the split evapora-tor.
NOTE! Ball valves must remain shut (delivery condition)!
6. Assembly ThermSelect®
44/100
Fig. 9: Connections split evaporator
Legend for Fig. 9:
Abbrev-iation Meaning
1 Fluid line 2 Suction gas line 3 Hot-gas line 4 Sensor cable heat source evaporation
ThermSelect® 6. Assembly
45/100
Fig. 10: Sensor cable heat source inlet 5
6. Assembly ThermSelect®
46/100
Heat pump installation The heat pump is delivered standing on a wooden pallet. Remove the foil/packaging and install the heat pump according to the following steps.
Fig. 11: Heating pump without enclosure
Fig. 12: Place the heat pump with the pallet next to the actual
erection location. Remove the transport locks 1 (marked in red) on the base plate of the heat pump and lift it to its final installation site.
ThermSelect® 6. Assembly
47/100
Fig. 13: Pre-assemble the enclosure ass seen in the image prior
to installing the hydraulic and cooling lines.
CAUTION! Water damage through condensation or humidity in the air! Extremely low temperatures at the refrigerant lines lead to condensation or humidity in the air and can cause water damage. Therefore: - The heat source lines are lined with diffusion-
resistant insulation which must not be damaged. - Installation-related damage must be closed again in
a diffusion-resistant manner with suitable refrige-rant pipelines.
- Contact between heat source lines carrying refrige-rant with ambient air, by ensuring insulation is sealed without any gaps and absolutely diffusion-resistant, must be ensured.
Fig. 14: Place the counter nut into the insulation and screw in the
cable gland.
6. Assembly ThermSelect®
48/100
Connection of split evaporator with heat pump
PRECAUTION! Risk of injury due to refrigerant! Refrigerant is corrosive and causes cold burns upon contact with skin. Therefore: - Wear chemical-resistant protective gloves when
handling refrigerant at any time. - Wear protective glasses to avoid contact with eyes.
- Connect the heat pump and the split evaporator with the refrige-
rant lines.
CAUTION! Environmental damage due to improper assembly of the refrigerant line! Refrigerant and compressor oil can leak! Therefore: - Only use tools that are recommended for used in
the cooling unit: Bending wrench, pipe separator, deburrer and bordering tool
- Take note of bending radius to avoid bending or breaking of pipes.
- To avoid brittle or cracking pipes, do not bend the pipes repeatedly.
- In order to reduce loss of pressure and to ensure return of compressor oil, avoid unnecessary bend-ing of the pipes.
- Use appropriate fastening and insulation during refrigerant line installation.
- Use only non-cutting tools (special pipe cutting tools) to shorten refrigerant lines.
NOTE! The heating pump contains refrigerant for a 20 m max. length cooling line. Any shortening or lengthening of the line may only be carried out by a certified technician. The refrige-rant dosage must then be checked accordingly.
NOTE! The technician must check the installation and mountings of the pipe, and establish a proper con-nection with the heating pump and the split evapora-tor.
NOTE! Ball valves must remain shut (delivery condition)!
ThermSelect® 6. Assembly
49/100
Fig. 15: Heat pump connections
Legend for Fig. 15:
Abbrev-iation Meaning
1 Fluid line 2 Suction gas line 3 Hot-gas line
- Evacuate the suction, liquid and hot-gas lines. To evacuate the
devices, connect to the Schrader valves (s. Fig. 9). - After the evacuation has been completed, open the ball valves to
allow the refrigerant to distribute. The system is operational after the hydraulic and electrical installation has been made.
6. Assembly ThermSelect®
50/100
6.5 Hydraulic connection
Requirements for the heat transfer liquid
The heat transfer liquid (brine) in the heat source should be set to frost protection of approx. -12°C. This is achieved with a water-glycol mixture with a share of 25% Tyfocor L (available as an acces-sory). The frost protection must be checked using a refractometer (availa-ble as an accessory) or similar testing device.
Requirements on the heating water
To prevent corrosion damage in the heating system, heating water in potable quality must be used under consideration of the require-ments according to VDI guideline 2035 "Preventing damage in warm water heating systems" / SWKI guideline 97-1 "Water quality for heating, steam, refrigeration and air conditioning systems".
CAUTION! Damage to devices/components from contamination! Partial clogging in the heat exchanger can lead to its destruction. Therefore: - For installations in older systems pre-filtration/silt
separation must be installed in order to protect the plate heat exchanger.
NOTE! Do not use any chemical additives!
Fig. 16: Hydraulic connections
ThermSelect® 6. Assembly
51/100
Legend for Fig. 16:
Abbrev-iation Meaning
1 Flow heat pump 2 Return heat pump 3 Inlet heat source brine 4 Outlet heat source brine
With the hydraulic connection, it must be ensure that the correct flow directions are adhered to. At the condenser, the in-flow is at the bot-tom (heating water return to heat pump). The temperature spread of 3-4 K at the heat source and 5- 10 K at the heat drop must be maintained under normal operating conditions while observing the application limits. This spread is nor-mally achieved when the volume flows specified in the technical da-ta are observed. In comparison to conventional combustion systems, heat pumps operate with larger mass flows. This results in larger pipe diameters and relevant pump configurations.
CAUTION! Device damage through improper system setup! Water and/or glycol mixture can leak. Therefore: - In the brine system, as well as on the heating side,
safety devices and expansion containers must be installed.
6. Assembly ThermSelect®
52/100
6.6 Electrical connection
DANGER! Risk to life through electrical current! Contact with live components can cause serious inju-ries. Therefore: - When working on the device, all supply lines must
be without current. - Make sure that all electrical parts are without cur-
rent. - The applicable VDE and utility company regulations
as well as the respective regulations and guidelines of the country of destinations must be complied with.
- The electrical connections must be inspected by a responsible technician before establishing the con-nection with the line supply.
- An external separator (e.g. main switch) must be envisaged for all electrical supply lines to the ma-chine.
- Only operate the heat pump within the implementa-tion frequency (s. chapter 5.3 Type of electricity for compressor) (in Germany 50 Hz).
CAUTION! Interferences through electrical fields! Supply lines (230 V) may interfere with sensor lines (electrical low voltage). Therefore: - Sensor and supply lines may not be routed in the
same cable conduit.
Fig. 17: Overview of electric connections
ThermSelect® 6. Assembly
53/100
Fig. 18: Electrical connection ThermSelect® 15 -19
Legend for terminal diagram electrics board:
1 4 7 10 13 16 19 22 25 28
Con
dens
er
pum
p L
Ven
tilat
or L
Hea
t sou
rce
pum
p L
Nor
mal
tarif
f L
Win
ding
pro
tect
ion
INT6
9 L
Win
ding
pro
tect
ion
INT6
9 L*
Sol
enoi
d liq
uid
line
air L
Sol
enoi
d liq
uid
line
brin
e L
Sol
enoi
d he
ater
L
Sol
enoi
d th
aw-
ing
L
2 5 8 11 14 17 20 23 26 29
Con
dens
er
pum
p N
Ven
tilat
or N
Hea
t sou
rce
pum
p N
Nor
mal
tarif
f N
Pres
sure
sw
itch
high
pre
ssur
e L
Pres
sure
sw
itch
high
pre
ssur
e L*
Sol
enoi
d liq
uid
line
air N
Sol
enoi
d liq
uid
line
brin
e N
Sol
enoi
d he
a-te
r N
Sol
enoi
d th
aw-
ing
N
3 6 9 12 15 18 21 24 27 30
Con
dens
er
pum
p P
E
Ven
tilat
or P
E
Hea
t sou
rce
pum
p P
E
Nor
mal
tarif
f PE
Pres
sure
sw
itch
low
pre
ssur
e L
Pres
sure
sw
itch
low
pre
ssur
e L*
Sol
enoi
d liq
uid
line
air P
E
Sol
enoi
d liq
uid
line
brin
e P
E
Sol
enoi
d he
a-te
r PE
Sol
enoi
d th
aw-
ing
PE
The electrical connection occurs in accordance with the circuit dia-grams in chap. 0. The circuit protection in the distributor (meter cabinet) must be made with a 3-pole power circuit breaker (C-characteristics) according to the output ratings of the heat pump. The potential equalization is to be connected at the M6 or M8 connecting screw marked for this purpose.
6. Assembly ThermSelect®
54/100
Highly reliable spring clips are used as connection terminals. The clips are opened with the appropriate, included tool (small screw driver) which is inserted in the respective square opening and is then moved in the direction away from the lead intake opening.
Electrical connection for compres-sor
The connection for the supply lines from the special tariff (3c400 V, N, PE) occur directly on the motor protection switch (L1, L2, L£) and for N and PE on the relevant terminal connectors on the top-hat rail.
Fig. 19: Special tariff connection
Electrical connections for RVS con-troller
Component Connection to Line on site
Sensor outside RVS controller, slot k, terminal B9, M
Cable interchangea-ble
Sensor source inlet 49.0
RVS controller, slot r, terminal B91, M
Cable interchangea-ble
Sensor evaporator 48.1
RVS controller, slot s, terminal B84, M
Cable interchangea-ble
Control signal 0-10 V
RVS controller, slot z, terminal UX, M Terminal connectors ventilator terminal 0-10 V/PWM, GND
Comply with polarity
ThermSelect® 6. Assembly
55/100
Connection terminals ventilator(s)
M1 M2 M3
RSA
RSB
RSA
RSB
GND
0-10V PWM
0-10V PWM
4-20mA
+20V
+10V
GND
OUT
NO
COM
NC
N
L
(L1)
(L2)
(L3)
L1
NPE
230V
50/
60 H
z
1)
R2
R12)
0-10V PWM out
RSA
RSB
RSA
RSB
GND
0-10V PWM
0-10V PWM
4-20mA
+20V
+10V
GND
OUT
NO
COM
NC
N
L
(L1)
L1
NPE
230V
50/
60 H
z
1)
R2
2)
RSA
RSB
RSA
RSB
GND
0-10V PWM
0-10V PWM
4-20mA
+20V
+10V
GND
OUT
NO
COM
NC
N
L
(L1)
L1
NPE
230V
50/
60 H
z
1)
R2
2)
Sk09-6200-125Stand: 19.11.09
R1 R1
(L2)
(L3)
(L2)
(L3)
3)
Fig. 20: Connection terminals ventilator(s)
6. Assembly ThermSelect®
56/100
Enclosure assembly
Fig. 21: Snap the catches of the side panel of the enclosure into
the rear panel.
Fig. 22: Fix side panels on the rear panel of the enclosure.
ThermSelect® 6. Assembly
57/100
Fig. 23: Insert the spring plates in the side enclosures.
Fig. 24: Snap the front panel onto the catches of the side panel.
6. Assembly ThermSelect®
58/100
Fig. 25: Screw the closing journals into the lid of the enclosure.
Fig. 26: Position the lid.
Fig. 27: Insert the bracket.
ThermSelect® 6. Assembly
59/100
Fig. 28: Screw in the upper and lower wing nut of the bracket.
Fig. 29: Reach through the openings of the brackets to remove
the control unit and attach it from the outside.
6. Assembly ThermSelect®
60/100
Motor control unit RSBT 4016, 4025, 4032 EV 11 for ThermSelect®
Fig. 30: Dimensions RSBT 4016, 4025, 4032 EV 11
Number of flashing signals red LED
Status Action
2 Incorrect phase sequence Physical change
3 Power supply not in accor-dance with regulations
Auto reset with 5 min. recovery
4 Frequency not in accor-dance with regulations
Auto reset with 5 min. recovery
5 Rotor blocking status (while ramping)
Auto reset with 5 min. recovery
6 Startup time > 1 sec. Auto reset with 5 min. recovery
7 Excess temperature Auto reset
8 Excess current (during bypass)
Auto reset with 5 min. recovery
9 Supply voltage unbalance
Auto reset with 5 min. re-covery, provided that all phases (L1, L2, L3) are connected.
ThermSelect® 6. Assembly
61/100
Fig. 31: Flashing sequence RSBT 4016, 4025, 4032 EV 1
Controller and control unit
At this point, MHG refers to the Assembly-Operation-Maintenance manual RVS 61.843 / AVS 37.. / QAA 75.. / QAA 78.. (Part No. 98.18803-6105)
Red LE Red LED off
7. Operation Startup ThermSelect®
62/100
7 Commissioning
7.1 Safety during startup WARNING! Risk of injury through improper operation! Improper operation leads to serious personal injuries or property damages. Therefore: - Installation and assembly must be performed by a
heating systems dealer. - Work on the refrigerant circulation may only be per-
formed by persons possessing a refrigeration cer-tificate in accordance with ChemKlimaschutzV.
- Carry out all of the operating steps in accordance with the information in these instructions.
- Before starting with the work activities, make sure that electrical and hydraulic lines are shut off and secured against inadvertent opening.
- Use only suitable tools.
7.2 Inspection prior to startup Make sure of the following after proper assembly: - the electrical connection has been correctly installed. - the polarity of the line connection is correct - electrical voltage is applied - the heating system and possibly existing reservoir are correctly
filled and ventilated - the heat source system is correctly filled and ventilated - the correct installation of all required safety devices was made. - proper circulation of the heating water and hot water circuit exists - all refrigerant lines and valves are sealed intact - refrigerant lines are covered with diffusion-resistant insulation,
without any gaps - all attachments, suspensions, etc. are fastened properly and have
been verified as to their proper height
NOTE! After installation and prior to startup of the system, the protective earth resistance and the insulation re-sistance must be tested according to DIN VDE 0701 and DIN VDE 0702 and documented. These tests need to be repeated according to the applicable local time intervals or according to the DIN VDE - regulations, series DIN VDE 0701 and 0702 (repair, restarting, etc.).
ThermSelect® 7. Operation Startup
63/100
7.3 Commissioning
NOTE! The customer / owner of the system must be present when starting up the system. A startup protocol is established on site.
NOTE! For operators of equipment containing 3kg or more of refrigerant, the following duties of documentation apply: - Amount and type of refrigerant - Any amounts of refrigerant refills - Any amounts of refrigerant retrieved during startup,
maintenance or final disposal - Details identifying the company or technical per-
sonnel that carried out the installation, startup, or any maintenance work
- Dates and results of all inspections The recorded information must be presented to the relevant authorities and the commission upon re-quest.
PRECAUTION! Risk of injury due to refrigerant! Refrigerant leakage damages the environment 100- 24,000 times more than carbon dioxide (CO2). Therefore: - Hermetically sealed systems that contain 6 kg of
refrigerant or more must not exceed a leakage rate of 1%.
CAUTION! Device damage through wrong direction of rotation of the condenser! A reverse run over several hours or days causes se-rious damage with a loss of guarantee. Therefore: - The use of the compressor requires the correct ro-
tational direction to be set and adhered to (clock-wise rotating field).
- When turning in the wrong direction, the condenser works much louder than usual and does not pro-duce any output (compressed gas neck remains cold). A brief reverse run of a few minutes is not harmful.
CAUTION! Device damage through dry pump running. If the brine circuit is not connected or not filled, the pump can be damaged. Therefore: - The device can only be started up with a filled heat-
ing and brine circuit. Refer also to the "Startup order form".
7. Operation Startup ThermSelect®
64/100
Pump control - Circulating pump control - Unscrew pump stopper and turn pump shaft as illustrated below. - Screw pump stopper back in - Caution: Collect drops
Fig. 32: Loosen pump stopper
Switching on the device
After proper inspection of the installation, the power connection can be switched on. For this, activate the installed power switch and au-tomatic circuit breaker.
Refrigerant dosage
The quantity of refrigerant is determined during operation by mea-suring and comparing the refrigerant condensation temperature and the heat pump flow temperature. The heat pump / compressor must be activated for min. of 10 min. and a flow temperature of approx. 50°C must be reached before measurement or the results will not be reliable and the amount of refrigerant indicated will not be correct. The difference between both of these temperatures should be be-tween 0 and 3 K (condensation temperature - flow temperature).
Test for leak-tightness
Once operating, the refrigerant circuit must be rechecked for lea-kage using a sensitive leak detection device/substance.
ThermSelect® 7. Operation Startup
65/100
7.4 Setting the controller
Control unit AVS 37
Fig. 33: Control unit AVS 37
Legend for Fig. 33:
Abbrev-iation Meaning
1 Select drinking water mode 2 Service connector for BSB data BUS 3 Exit settings 4 Select heating mode 5 Display information 6 Accept settings
7 Room comfort target value, adjusting, navigation and settings
Symbol Display options
Heating in constant mode day (comfort mode) Heating in constant mode night (reduced mode) Heating on standby (freeze protection mode) Process running - please wait Replace battery Holiday function active Reference to heating circuit Maintenance / Special functions Error messages Info level activated Programming activated
Heating temporarily switched off, ECO function active
7. Operation Startup ThermSelect®
66/100
7.5 Parameterisation At this point, MHG refers to the Assembly-Operation-Maintenance manual RVS 61.843 / AVS 37.. / QAA 75.. / QAA 78.. (Part No. 98.18803-6105) The factory parameterisation is shown in the table on pages 90-95. It may need to be adapted to the local system conditions.
7.6 Commissioning record NOTE! The work carried out must be entered in a separate commissioning record.
ThermSelect® 8. Maintenance
67/100
8 Maintenance
8.1 Maintenance
NOTE! The respective regulations and guidelines of the country of destination must be complied with!
NOTE! Depending on the quantity of refrigerant, the system operator must have it checked at least once every twelve months. This is also necessary for reasons of operating readiness, function and efficiency. Work on the refrigerant circuit may only be per-formed by certified personnel.
The total system shall be inspected here for flawless function and any defects encountered shall be repaired without delay.
NOTE! Professional annual maintenance is stipulated ac-cording to the warranty conditions of MHG Heiztech-nik.
DANGER! Risk to life through electrical current! Contact with live components can cause serious inju-ries. Therefore: - Work on electrical systems may only be performed
by professional electricians. - Turn off electric power before beginning the work
activities, e.g. heating emergency switch, and se-cure against turning on again.
- Set the operating switch on the boiler to "OFF". - In case of damaged insulation, immediately cut off
the power supply and initiate the repair.
NOTE! Inspect threaded joints for leaks during the annual maintenance. Replace defective or worn seals.
8. Maintenance ThermSelect®
68/100
8.2 Components relevant to safety
For ensure the long-term availability and safety of heat generators and components and to fulfil the requirements of the EU Guideline 2002/91/EC, it is necessary to replace the following components af-ter they reach the service life specified by the manufacturer, as time or switching cycles. With modern devices, the switching cycles can usually read on a display/indicator. In cases where the switching cycle cannot be read, the time is relevant for the replacement.
Nominal service life of the heat ge-nerator components
Components relevant to safety Time [a] Switching cycles [-]
Controller 10 250.000 Pressure relief valves 10 n/a
8.3 Work to be carried out
PRECAUTION! Risk of injury due to refrigerant! Refrigerant is corrosive and causes cold burns upon contact with skin. Therefore: - Wear chemical-resistant protective gloves when
handling refrigerant at any time. - Wear protective glasses to avoid contact with eyes.
NOTE! For operators of equipment containing 3kg or more of refrigerant the following duties of documentation apply: - Amount and type of refrigerant - Any amounts of refrigerant refills - Any amounts of refrigerant retrieved during startup,
maintenance or final disposal - Details identifying the company or technical per-
sonnel that carried out the installation, startup, or any maintenance work
- Dates and results of all inspections The recorded information must be presented to the relevant authorities and the commission upon re-quest.
ThermSelect® 8. Maintenance
69/100
PRECAUTION! Risk of injury due to refrigerant! Refrigerant leakage damages the environment 100- 24,000 times more than carbon dioxide (CO2). Therefore: - Hermetically sealed systems that contain 6 kg of
refrigerant or more must not exceed a leakage rate of 1%.
- Hermetically sealed systems that contain 6 kg of refrigerant or more must have leak-tightness in-spected and verified at least every 12 months.
- All leaks from which refrigerant can escape must be repaired immediately.
Confirm the work activities performed in the following commission-ing record with an X or a .
Maintenance work Description Done
Document amount and type of refrigerant used ---
Document any amounts of refrigerant refills ---
Document any retrieved refrigerant --- Document details identifying the compa-ny or technical personnel that carried out the maintenance work
---
Document dates and results of all inspec-tions ---
Check cooling circulation: Screw connections, seals, (sight glass), refrigerant regulation
---
Check heating cycle: System pressure, expansion container function, ventilation, pump rotational di-rection and quantity setting
---
Check the controller settings ---
CAUTION! Environmental damage through substances hazard-ous to groundwater! Substances hazardous to groundwater, such as greases, oils, refrigerants, solvent-based cleaning agents and the like, can burden the ground or get in-to the sewage system. Therefore: - These substances must be collected, stored and
transported in suitable containers and be disposed off.
With regard to the remaining heating system (distribution system), especially the circulation pumps, valves and adjustment devices must be checked for leaks and also the filters (if water is the heat source) must be inspected and cleaned, if applicable, and the prop-er operation of the flow guard must be verified.
8. Maintenance ThermSelect®
70/100
Disassembly of the control unit
NOTE! Loosen the catches with a screwdriver. It must be ensured that the catches are not broken off when dismantling the control unit.
Fig. 34: Insert a screw driver, as per the illustration, first into the
right and then the left upper recess, push the catch down and the screw driver forward at the same time.
Fig. 35: Insert a screw driver first into the right and then the left
lower recess, push the catch down and the screw driver forward at the same time.
ThermSelect® 8. Maintenance
71/100
Fig. 36: Remove the control unit from the bracket and insert
through the opening of the bracket and place inside. Repeat the steps of Fig. 34-Fig. 36 with the second control unit.
8. Maintenance ThermSelect®
72/100
8.4 Spare part drawing and legend
Fig. 37:
ThermSelect® 9. Troubleshooting
73/100
9 Troubleshooting
9.1 Troubleshooting It is frequently noticeable that the heat pump heating systems are not operating properly because the heating circuit does not have the required volume flow. The consequence of this is the activation of safety devices on the heat pump. In case of insufficient or no flow in the heat exchange on the heating circuit side, this leads to a high-pressure disruption. It cannot be ruled out that the safety temperature limiter will also switch the sys-tem off with insufficient hot water flow. The causes of the listed faults have their origin in the periphery and in the rarest cases, in the heat pump itself. Incorrect settings on the controller can have similar effects. The activation of relevant sen-sors and the signalisation of a fault are for the protection of the sys-tem and are generally not an indication of a defective heat pump.
Faults and their removal
If the heat transfer is suddenly disrupted when the heat pump is running (e.g. due to standstill of circulating heat pump or closed valves), it can (due to the thermal inertia of the system) occur that the high-pressure safety limit switch in the heat pump is activated. The heat pump is thereby shut off and an automatic restart is pre-vented for safety reasons.
NOTE! Reduction of the service life of the high-pressure -safety limit switch, as well as the compressor, through excess wear and tear. Therefore: - If the high-pressure limit switch is activated, check
and rectify the cause. Another possible reason for triggering this high pressure safety limi-ter may also be related to the local conditions of the heat pump's in-stallation site which may necessitate the installation of an oil sump heater (strip heater on the condenser) or a "pump-down function".
Course of action for malfunctions
If electrical errors (e.g. defective sensors) can be ruled out, begin with checking the circulation pump and valves of the heating system and heat source.
NOTE! If all errors can be ruled out on the external system, the cooling cycle of the heat pump must be checked by an authorized technician.
9. Troubleshooting ThermSelect®
74/100
Troubleshooting
Fault Cause Remedy
Defect on input side (LP fault)
Ventilator(s) is/are not running Check fuse, check relay Check control signal 0-10 V
Heat source pump not running Check fuse, relay and pump
Condenser dirty/iced over Clean condenser, initiate thawing; check temperatures on condenser
Expansion valve incorrectly set / defective Request factory service
Refrigerant circulation interrupted (shut-off valve closed, filter dryer dirty).
Request factory service
Water inside the refrigerant circulation (hu-midity indicator in the refrigerant sight glass yellow/red)
Request factory service
Temperature of the heat source too low -15°C application limit reached
Water in the condenser too cold (below 20 °C)
Pre-heat heating water electric heating insert
Quick temperature change in the condenser Check volume flow
Low refrigerant level (see sight glass) Request factory service
Controller parameter set incorrectly Set parameters according to guide
Contact interrupted Check LP switch wiring
Manual unlocking necessary if the low pres-sure monitor triggers.
Defect on input side (HD fault)
Heating pump is not running Check fuse; check relay/ contactor K4; Check running wheel for dirt build-up
Water circulation interrupted or insufficient (possibly not enough heating circuits open)
Check water circulation in heating system; open radiator valves or positioning drives
Heating water temperature too high
No heat discharge, e.g. heat exchanger in the boiler of the service water heater is too small
Check technical specifications for service wa-ter heater, min. heat exchanger surface 0.2m²/kW heat output
Air in water circulation Vent the water circulation
Dirt catcher clogged Clean dirt catcher
Circulation pump defective or wrong rotation direction
Check circulation pump and rotate/replace, if necessary
Controller parameter set incorrectly. Set parameters according to guide
Manual unlocking may possibly be neces-sary if the high pressure monitor triggers.
ThermSelect® 9. Troubleshooting
75/100
Fault Cause Remedy
Fault with con-denser motor con-denser overload (overheating of the motor winding)
Failure of a phase Check supply line of 3-phase current
Mechanical failure due to lack of lubrication Request factory service
Winding protection defective Replace winding protection
Low refrigerant level Request factory service
Defect in the refrigerant regulation Request factory service
Operation with incorrect refrigerant Request factory service
Pressure gas temperature too high Request factory service
Fault current (FI) circuit breaker ac-tivates
Wrong allocation of neutral lead for spe-cial/normal tariff
Check device wiring
heating pump locked
Special tariff supply line interrupted (off-time preset by utility company); bivalence point undercut
Check blocking times for the special tariff connection; check parameters (RVS 61, Line 2910)
Evaporator ices up quickly
High humidity and temperatures of 3-8°C lead to quick icing up of the evaporator.
Decrease time until forced thaw (parameter line 2963)
10. Warranty ThermSelect®
76/100
10 Warranty
10.1 Warranty
Limit of liability All specifications and information in these installation instructions were compiled under consideration of the applicable standards and regulations, the state of technology as well as our experience and insights of many years. MHG Heiztechnik does not assume any liability for damages due to: - Non-compliance with the instructions for Assembly, Startup and
Maintenance, as well as the operating instructions - Use other than intended - Employment of untrained personnel - Unauthorized modifications - Technical changes - Use of unapproved spare parts - Inappropriate change of refrigerant dosage The actual scope of delivery may deviate from the explanations and representations described here due to special designs, additional ordering options or latest technical changes.
Copyright
These instructions are copyright protected by MHG Heiztechnik. Duplications of any type and in any form - also excerpts - as well as the exploitation, notification and/or communication of its contents, or parts thereof, are not permitted without the written release declara-tion of MGH Heiztechnik. Any person violating these rules will be li-able for damages. Additional claims are reserved. The instructions are to be treated confidentially. They are exclusive-ly intended for persons working with the device. Leaving the instruc-tions to a third party without written approval of the manufacturer is not permitted. The instructions shall remain with the heating device to allow them to be used at a later time, if needed. MHG shall not be held liable for damages resulting from non-compliance with these instructions.
NOTE! The content, texts, drawings, illustrations and other presentations are protected by copyright and subject to commercial property rights. Any misuse is liable to prosecution.
ThermSelect® 10. Warranty
77/100
Warranty The ThermSelect® heat pump by MHG renders its perfect function only when installed and started professionally. Warranty conditions of MHG can be taken from the warranty certifi-cate.
Spare parts
NOTE! Use only original MHG spare parts in case of re-placements: Some components have been designed and manufactured especially for MHG devices. Al-ways specify the serial number when ordering spare parts.
PRECAUTION! Device damage from the use of incorrect compo-nents! Using parts not manufactured/supplied by MHG can cause material decomposition. Therefore: - Only parts specified by MHG must be installed in
the cooling unit.
Warranty claim for wearing parts
(See recommendation EHI European Heating Industry, information bulletin 14) The spare parts list also contains "spare parts" that must be re-placed when the device is used as intended within the warranty pe-riod. The warranty periods have been extended by law makers, however, this does not preclude possible wear and tear from operation. It is known that a device may operate up to 8,760 hours a year when used as intended if this is a permanent operation system. According to customary commercial treatment, the costs incurred in these con-ditions are not covered by the warranty obligation or commitment of the manufacturer. The components listed in the spare parts list have been divided into the following categories: 1. Spare parts Spare parts are used for the repair of products
a) Parts are replaced that have not reached the expected ser-vice life although the device was operated as intended.
b) Furthermore, parts that are replaced due to improper opera-tion or unintended use (e.g. wrong burner settings, water flow to low or too high, boiler scale through unsuitable filling water, use of incorrect refrigerant, etc.).
10. Warranty ThermSelect®
78/100
2. Wearing parts Wearing parts are such parts which must be replaced sever-
al times within the scope of service life while the product is used as intended (e.g. during maintenance).
3. Auxiliary materials Auxiliary materials are required with the repair and mainten-
ance of devices. Typical auxiliary materials are, for example, seals of all kinds,
hemp, lead oxide red or fuses. Auxiliary materials are not subject to any warranty claims, except
the necessary use in the context of replacing parts in the frame-work of an existing warranty claim.
Warranty certificate MHG provides warranty for compliance with explicitly promised properties, for non-defective construction and manufacturing as well as for flawless material in the manner that the parts which have become unusable as a result of such defects or where there usefulness was significantly compromised are delivers as new at their own costs and risk. MHG provides warranty for replaced parts to the same extent as for the original delivery item. The following warranty periods apply for the ThermSelect® heat pump:
- 2 years material warranty on all electrical and other components , as well as on the heat pump function.
The ordering party can only assert warranty claims from MHG if the startup of the delivered item was performed by staff of MHG, companies trained by MHG or a qualified refrigeration company, the order-ing party has observed the MHG regulations of the handling and maintenance of the delivered item, the prescribed inspections were done properly and no spare parts of third-party origin were installed. The complete and current delivery and warranty conditions can be taken from the MHG price list, on the back of the order confirmations, delivery notes and invoices as well as in the Internet at www.mhg.de. Per request, MHG can send the current general delivery and warranty conditions as printout via postal service. MHG Heiztechnik GmbH
M. Niedermayer ppa Gieseler
ThermSelect® 10. Warranty
79/100
10.2 Manufacturer Certificate / EU Design Conformity Declaration
Manufacturer Certificate Buchholz i.d.n., 03.03.2011 MHG Heiztechnik GmbH hereby certifies the following for the heat pumps listed below: The heat pumps are equipped with different safety circuit devices for pressure limitation in the refrigerant cycle in compliance with DIN 32733. The high pressure guard safety limit switch shuts off the condenser automatically if the pressure of the medium in the refrigerant cycle exceeds 28 bar. The refrigerants R407C and the cooling equipment machine oil (diester oil) are environmentally compatible. According to the EU safety data sheet, the refrigerant R407C consists of 23% difluoromethane (HFKW 32), 25% pentafluoroethane (HFKW 125) and 52% tetrafluoroethane (HFKW 125). The RVS 61 heat pump controller used by MHG in the system is equipped with sensors for the recording and control of the source outlet temperature and the heating flow temperature. If temperatures reach levels endan-gering the system, the heat pump is shut off automatically. MHG Heiztechnik GmbH
M. Niedermayer ppa Gieseler
10. Warranty ThermSelect®
80/100
EU Design Conformity Declaration According to EG Machine Guideline 98/37/EG Buchholz i.d.n., 05.05.10 MHG Heiztechnik GmbH hereby declares that the ThermSelect® heat pumps comply with the following EU guidelines and standards:
EU Guideline Standard Machine guideline 98/37/EC
Low voltage guideline 73/23/EEC EN 60335-1 (2004) EN 50165 (1998) + A1 (2001)
EMC guideline 89/336/EEC EN 55014-1 (2001) EN 55014-2 (2001) EN 50165 (1998) + A1 (2001)
Pressure equipment guideline 97/23/EC EN 13445 (01.2002) VDE 0113 Electrical Equipping of Machines - Safety of Machines DIN EN 60204 (1998)
VDE 0660-500 Low-Voltage Switching Device Combinations DIN EN 60439 (01.2005)
Cooling systems and heat pumps - Safety and envi-ronmentally relevant requirements DIN EN 378 (01.2000)
Air conditioners, liquid cooling sets and heat pumps with electrically powered compressors - heating DIN EN 255 (07.1997)
DIN EN 14511 (02.2008) Safety switching mechanism for the pressure limitation in cooling systems and heat pumps - Requirements and testing
DIN 32733 (1989.01)
Cooling systems and heat pumps - Protection of soil, groundwater and surface water - Safety and environ-mentally relevant requirements and testing
DIN 8901 (12.2002)
Cooling Systems - Safety Principles for Design, Fitting and setup - Part 12: Recovery Systems DIN 8975 (01.2004)
DruckbehV (06.1999) Regulation on Pressure Containers, Pressurised Gas Containers and Filling Systems
This declaration looses its validity in changes not authorized by MHG Heiztechnik are made to the machine. MHG Heiztechnik GmbH
M. Niedermayer ppa Gieseler
ThermSelect® 10. Warranty
81/100
10.3 Proof of Service
Maintenance record ThermSelect®, ThermSelect®Pro, ThermSelect®Sun, ThermSelect®Sun Pro Heat Pump
Customer:
Maintenance Contract/Customer No.:
The following work was carried out on your heating system in the context of your yearly maintenance:
1) Type of refrigerant
2) Quantity of refrigerant according to identification plate
3) Refrigerant refilled g
4) Refrigerant recycled g
5) Functional check of cooling cycle
6) Leak-tightness check of cooling cycle
7) Electric connections check
8) Inspection of seals and replacement where necessary
9) Test for water/gas leak-tightness in operation
10) Functional check of pump
11) Function check of mixer/mixer motor, if applicable
12) Parameter controller/room unit check
13) Electric meter reading
14) Heat meter reading
15)
16)
17)
Comments:
We acknowledge and verify proper implementation. Place, Date
Stamp
Signature
Next yearly maintenance due in: (Month, Year)
10. Warranty ThermSelect®
82/100
1. Maintenance 2. Mainten-ance
Amount of refri-gerant refilled kg Amount of re-
frigerant refilled kg
Amount of refri-gerant retrieved kg
Amount of re-frigerant re-trieved
kg
Electric meter reading Electric meter
reading
Heat meter reading Heat meter
reading
Leak-tightness verification completed
Date Leak-tightness verification completed
Leaks repaired yes/no Leaks repaired Inspection due (after 4 weeks) Date Inspection due
(after 4 weeks) Date
Inspection car-ried out: Date Inspection car-
ried out: Date
Next mainten-ance due: Date Next mainten-
ance due: Date
Address of certi-fied company Address of cer-
tified company
Name of service technician Name of ser-
vice technician
ThermSelect® 10. Warranty
83/100
3. Mainten-ance 4. Mainten-
ance
Amount of re-frigerant refilled kg Amount of re-
frigerant refilled kg
Amount of re-frigerant re-trieved
kg Amount of re-frigerant re-trieved
kg
Electric meter reading Electric meter
reading
Heat meter reading Heat meter
reading
Leak-tightness verification completed
Date Leak-tightness verification completed
Leaks repaired yes/no Leaks repaired Inspection due (after 4 weeks) Date Inspection due
(after 4 weeks) Date
Inspection car-ried out: Date Inspection car-
ried out: Date
Next mainten-ance due: Date Next mainten-
ance due: Date
Address of cer-tified company Address of cer-
tified company
Name of ser-vice technician Name of ser-
vice technician
10. Warranty ThermSelect®
84/100
5. Mainten-ance 6. Mainten-
ance
Amount of re-frigerant refilled kg Amount of re-
frigerant refilled kg
Amount of re-frigerant re-trieved
kg Amount of re-frigerant re-trieved
kg
Electric meter reading Electric meter
reading
Heat meter reading Heat meter
reading
Leak-tightness verification completed
Date Leak-tightness verification completed
Leaks repaired yes/no Leaks repaired Inspection due (after 4 weeks) Date Inspection due
(after 4 weeks) Date
Inspection car-ried out: Date Inspection car-
ried out: Date
Next mainten-ance due: Date Next mainten-
ance due: Date
Address of cer-tified company Address of cer-
tified company
Name of ser-vice technician Name of ser-
vice technician
ThermSelect® 10. Warranty
85/100
7. Mainten-ance 8. Mainten-
ance
Amount of re-frigerant refilled kg Amount of re-
frigerant refilled kg
Amount of re-frigerant re-trieved
kg Amount of re-frigerant re-trieved
kg
Electric meter reading Electric meter
reading
Heat meter reading Heat meter
reading
Leak-tightness verification completed
Date Leak-tightness verification completed
Leaks repaired yes/no Leaks repaired Inspection due (after 4 weeks) Date Inspection due
(after 4 weeks) Date
Inspection car-ried out: Date Inspection car-
ried out: Date
Next mainten-ance due: Date Next mainten-
ance due: Date
Address of cer-tified company Address of cer-
tified company
Name of ser-vice technician Name of ser-
vice technician
11. Hydraulic Diagrams ThermSelect®
86/100
11 Hydraulic diagrams
11.1 Hydraulic diagrams
NOTE! The hydraulic diagram represent an installation suggestion (without any claim to completeness). The installation must be adjusted by a professional to the circumstances on site. Additional re-quired components must be provided on site.
ThermSelect® air+brine/water heat pump with heating/water change-over valve
M42.242.442.6
42.342.5
48.048.2
49.1
49.2
22.0
41.0
49.0
43.0
48.1
Fig. 38: Sk10-0504/163
ThermSelect® air+brine/water heat pump with heating/warm water change-over valve
Legend for Fig. 38:
Abbrev-iation Meaning Abbrev-
iation Meaning
22.0 Ventilator 1 FIL Filter 42.2 Sensor air-heat pump flow (B21) FL Fluid line 42.3 Sensor air-heat pump return (B71) HG Hot-gas line 42.4 Sensor brine-heat pump flow (B21) HK Heating circuit 42.5 Sensor brine-heat pump return (B71) KW Cooling circuit 42.6 Sensor track flow (B10) RL Return 48.0 Sensor refrigerant liquid air (B83) SG Suction gas line 48.1 Sensor refrigerant evaporator (B84) T Temperature 48.2 Sensor refrigerant suction gas brine (Bx1) VL Flow 49.0 Sensor source inlet air (B91) WQL Heat source air 49.1 Sensor source inlet brine (B91) WQS Heat source brine 49.2 Sensor source outlet brine (B92) Z Circulation
ThermSelect® 11. Hydraulic Diagrams
87/100
Components
Component Type Part number Comment
MHG ThermSelect®
15 19 28 34 41
98.30000-8954 98.30000-8956 98.30000-8958 98.30000-8960 98.30000-8962
Included in scope of delivery: 2 x controllers RVS 61.843 2 x control unit AVS 37.390 outdoor temperature sensor QAC 34 service water sensor QAZ 36
Mounting kit (heating side) for ThermSelect 10-15 98.38500-6111
Mounting kit (source side) for ThermSelect 10-15 98.38500-6110
Mounting kit 1 1/2" (Heating or source side)
for ThermSelect 19-41 98.38500-6114
Electrical heating cartridge 6 kW module upon request Flexible connection hoses heating flow and return for ThermSelect® 15 upon request
THERAMAT heat pump high-performance storage
EMH 150-1 EMH 200-1 EMH 300-1 EMH 400-1 EMH 500-1
94.71000-5615 94.71000-5621 94.71000-5631 94.71000-5641 94.71000-5651
Expansion vessel Heating Design of the MAG on site Fresh water connection To be provided on site
Electrical Connections RVS 61.843
Component Connection to Line on site
Sensor outside 1 41.0 RVS controller air, slot k, terminal B9, M Cable interchangeable
Sensor service water top 43.0
RVS controller air, slot h, terminal B3, M
Cable interchangeable, place sensor in top section of storage
Sensor evaporator 48.1 RVS controller air, slot s, terminal B84, M Cable interchangeable
Sensor source inlet 49.0 RVS controller air, slot r, terminal B91, M Cable interchangeable
Control signal 0-10 V
RVS controller air, slot z, terminal UX, M Terminal connectors ventilator terminal 0-10 V/PWM, GND
Comply with polarity
Drinking water change-over valve
RVS controller, slot R, terminal Q3, N, PE
Do not interchange neutral and positive, cable 3x1-1.5 mm²
Parameterisation
The system can be started with the factory settings. It may need to be adapted to the local system conditions.
11. Hydraulic Diagrams ThermSelect®
88/100
ThermSelect® air+brine/water heat pump with heating/water change-over valve and buffer storage
NOTE! The hydraulic diagram represent an installation suggestion (without any claim to completeness). The installation must be adjusted by a professional to the circumstances on site. Additional re-quired components must be provided on site.
M42.242.442.6
42.3
42.548.0
48.2
49.1
49.2
22.0
41.0
49.043.0
48.1
Fig. 39: Sk10-0504/162
ThermSelect® air+brine/water heat pump with heating/warm water change-over valve and buffer storage
Legend for Fig. 39:
Abbrev-iation Meaning Abbrev-
iation Meaning
22.0 Ventilator 1 FIL Filter 42.2 Sensor air-heat pump flow (B21) FL Fluid line 42.3 Sensor air-heat pump return (B71) HG Hot-gas line 42.4 Sensor brine-heat pump flow (B21) HK Heating circuit 42.5 Sensor brine-heat pump return (B71) KW Cooling circuit 42.6 Sensor track flow (B10) RL Return 48.0 Sensor refrigerant liquid air (B83) SG Suction gas line 48.1 Sensor refrigerant evaporator (B84) T Temperature 48.2 Sensor refrigerant suction gas brine (Bx1) VL Flow 49.0 Sensor source inlet air (B91) WQL Heat source air 49.1 Sensor source inlet brine (B91) WQS Heat source brine 49.2 Sensor source outlet brine (B92) Z Circulation
ThermSelect® 11. Hydraulic Diagrams
89/100
Components
Component Type Part number Comment
MHG ThermSelect®
15 19 28 34 41
98.30000-8954 98.30000-8956 98.30000-8958 98.30000-8960 98.30000-8962
Included in scope of delivery: 2 x controllers RVS 61.843 2 x control unit AVS 37.390 outdoor temperature sensor QAC 34 service water sensor
Mounting kit (heating side) for ThermSelect 10-15 98.38500-6111
Mounting kit (source side) for ThermSelect 10-15 98.38500-6110
Mounting kit 1 1/2" (Heating or source side)
for ThermSelect 19-41 98.38500-6114
Electrical heating cartridge 6 kW module upon request Flexible connection hoses heating flow and return for ThermSelect® 15 upon request
Buffer reservoir THERAMAT SP-200-0 SP-300-0 SP-500-0
94.71000-5920 94.71000-5930 94.71000-5950
THERAMAT heat pump high-performance storage
EMH 150-1 EMH 200-1 EMH 300-1 EMH 400-1 EMH 500-1
94.71000-5615 94.71000-5621 94.71000-5631 94.71000-5641 94.71000-5651
Overflow valve To be provided on site Expansion vessel Heating Design of the MAG on site Fresh water connection To be provided on site
Electrical Connections RVS 61.843
Component Connection to Line on site
Sensor outside 1 41.0 RVS controller air, slot k, terminal B9, M Cable interchangeable
Sensor service water top 43.0
RVS controller air, slot h, terminal B3, M
Cable interchangeable, place sensor in top section of storage
Sensor evaporator 48.1 RVS controller air, slot s, terminal B84, M Cable interchangeable
Sensor source inlet 49.0 RVS controller air, slot r, terminal B91, M Cable interchangeable
Control signal 0-10 V
RVS controller air, slot z, terminal UX, M Terminal connectors ventilator terminal 0-10 V/PWM, GND
Comply with polarity
Drinking water change-over valve
RVS controller air, slot R, terminal Q3, N, PE
Do not interchange neutral and positive, cable 3 x 1 – 1.5 mm²
Parameterisation
The system can be started with the factory settings. It may need to be adapted to the local system conditions.
11. Hydraulic Diagrams ThermSelect®
90/100
Factory parameterisation for ThermSelect® design
Control bar
User -level Function / Default value
Set value RVS Air 15
Air 19-28
Air 34-41
Brine 15
Brine 19-41
561-566 E Timer setting 4 Monday 06:00 – 22:00 561-566 E Timer setting 4 Tuesday 06:00 – 22:00 561-566 E Time setting 4 Wednesday 06:00 – 22:00 561-566 E Timer setting 4 Thursday 06:00 – 22:00 561-566 E Timer setting 4 Friday 06:00 – 22:00 561-566 E Timer setting 4 Saturday 06:00 – 22:00 561-566 E Timer setting 4 Sunday 06:00 – 22:00
2801 I Condenser pump control Temperature request ¦ Parallel condenser operation
Temperature request
2803 I Run-on time condenser pump 120 2816 F Source temp min brine -10 2819 I Lead time source 5 2842 I Condenser run time min. 0 2843 I Condenser idle time min 10 2845 F Reduction shut-off temp. Max 0 2853 O Low pressure delay operational 5
2854 O LP monitoring Always ¦ Without thawing
Always
2893 F Number of TWW loading attempts 3 2910 F Clearance above TA 0 --- 2951 I Thawing clearance below TA 10 2954 O Evaporator temp. Thawing end 5 2963 I Time until forced thaw 180 2964 I Thawing time max 20 2971 O Thawing ventilator above 7 3010 O Max. speed V'lator/Q'pump 40 60 100
3541 F Auto sequential exclusion None ¦ First ¦ Last ¦ First and Last
First None
5093 F With solar integration No ¦ Yes
No
5710 I Heating circuit 1 Off
5731 I Drinking water control element Q3 None ¦ Charge pump ¦ Reversing valve
Reversing valve
5800 I Heat source Brine ¦ Water ¦ Air ¦ External
Air Brine
ThermSelect® 11. Hydraulic Diagrams
91/100
Control bar
User -level Function / Default value
Set value RVS Air 15
Air 19-28
Air 34-41
Brine 15
Brine 19-41
5890 I
Relay output QX1 None ¦ Condenser stage 2 K2 ¦ Process reversing valve Y22 ¦ Hot gas temperature K31 ¦ Electrical insert1 Flow K25 ¦ Electrical insert2 Flow K26 ¦ Reversing valve cool-ing Track2 Y28 ¦ Delivery pump Q14 ¦ Cascade pump Q25 ¦ Generator shut-off valve Y4 ¦ Electrical insert TWW K6 ¦ Circulation pump Q4 ¦ Storage charge-over pump Q11 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Mixing pump Q35 ¦ Collector pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump ext.exchanger K9 ¦ Solar con-trol element buffer K8 ¦ Solar control element swimming pool K18 ¦ Electrical insert buffer K16 ¦ H1-Pump Q15 ¦ H2-Pump Q18 ¦ H3-Pump Q19 ¦ Heating cycle pump HkP Q20 ¦ 2nd Pump stage HK1 Q21 ¦ 2. Pump stage HK2 Q22 ¦ 2nd Pump stage HKP Q23 ¦ Reversing valve cooling Y21 ¦ Air dehumidifier K29 ¦ Heat request K27 ¦ Refrigeration request
Process reversing valve Y22 None
5891 I
Relais output QX2 None ¦ Condenser stage 2 K2 ¦ Process reversing valve Y22 ¦ Hot gas temperature K31 ¦ Electrical insert1 Flow K25 ¦ Electrical insert2 Flow K26 ¦ Reversing valve cool-ing Track2 Y28 ¦ Delivery pump Q14 ¦ Cascade pump Q25 ¦ Generator shut-off valve Y4 ¦ Electrical insert TWW K6 ¦ Circulation pump Q4 ¦ Storage charge-over pump Q11 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Mixing pump Q35 ¦ Collector pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump ext.exchanger K9 ¦ Solar con-trol element buffer K8 ¦ Solar control element swimming pool K18 ¦ Electrical insert buffer K16 ¦ H1-Pump Q15 ¦ H2-Pump Q18 ¦ H3-Pump Q19 ¦ Heating cycle pump HkP Q20 ¦ 2nd Pump stage HK1 Q21 ¦ 2. Pump stage HK2 Q22 ¦ 2nd Pump stage HKP Q23 ¦ Reversing valve cooling Y21 ¦ Air dehumidifier K29 ¦ Heat request K27 ¦ Refrigeration request
Heat requirement K27 None
5930 I
Sensor input BX1 None ¦ Buffer reservoir sensor B4 ¦ Buffer reservoir sen-sor B41 ¦ Collector sensor B6 ¦ Drinking water sensor B31* ¦ Hot gas sensor B82 ¦ Refrigerant sensor liquid B83 ¦ TWW Charge sensor B36 ¦ TWW Tapping sensor B38 ¦ TWW Circulation sensor B39 ¦ Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64 ¦ Buffer reservoir sensor B42 ¦ Track flow sensor B10 ¦ Cascade return sensor B70 ¦ Special temperature sensor 1 ¦ Special tempera-ture sensor 2
Track flow sensor B10
Special -temperature
sensor 1
5931 I
Sensor input BX2 None ¦ Buffer reservoir sensor B4 ¦ Buffer reservoir sen-sor B41 ¦ Collector sensor B6 ¦ Drinking water sensor B31* ¦ Hot gas sensor B82 ¦ Refrigerant sensor liquid B83 ¦ TWW Charge sensor B36 ¦ TWW Tapping sensor B38 ¦ TWW Circulation sensor B39 ¦ Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64 ¦ Buffer reservoir sensor B42 ¦ Track flow sensor B10 ¦ Cascade return sensor B70 ¦ Special temperature sensor 1 ¦ Special tempera-ture sensor 2
Refrigerant liquid B83
11. Hydraulic Diagrams ThermSelect®
92/100
Control bar
User -level Function / Default value
Set value RVS Air 15
Air 19-28
Air 34-41
Brine 15
Brine 19-41
5950 I
Function input H1 BA toggle HK's+TWW ¦ BA toggle HK's ¦ BA toggle HK1 ¦ BA toggle HK2 ¦ BA toggle HKP ¦ Error / alarm mes-sage ¦ Minimum flow targe value ¦ Heat requirement 10V ¦ Thaw point guard ¦ Flow target value increase hygro ¦ Refrigeration request ¦ Refrigeration request 10V ¦ Pres-sure measurement 10V ¦ Relative room humidity 10V ¦ Room temperature 10V ¦ Clearance swimming pool ¦ Switch-on command WP level 1 ¦ Switch-on command WP level 2
Switch-on command WP level 1
5952 I Function value contact H1 55
5981 O Control direction input EX1 Break contact ¦ Working contact
Break contact
5999 O Control direction LP guard E9 Break contact ¦ Working contact
Break contact
6000 O Control direction HP guard E10 Break contact ¦ Working contact
Break contact
6001 O Cntrl dir. Evap1 overload E11 Break contact ¦ Working contact
Work -
con-tact
Break contact
Work -
con-tact
Nor-mally closed con-
tact
6070 I
Function output UX None ¦ Source pump Q8/Venti K19 ¦ Drinking water pump Q3 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Instantaneous water filter Q34 ¦ Collector pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump buffer K8 ¦ Solar pump ext. exchanger K9 ¦ Solar pump swimming pool K18 ¦ Heating circuit pump HK1 Q2 ¦ Heating circuit pump HK2 Q6 ¦ Heating circuit pump HKP Q20 ¦ Heat pump target value ¦ Output target value ¦ Heat require-ment ¦ Cold requirement ¦ Heat pump modulating
Source pump Q8/Venti K19
6128 O Heat request below outdoor temp 0 --- 6600 I Device address 1 2
6640 I Timer mode Autonomous ¦ Slave without remote adjustment ¦ Slave with remote adjustment ¦ Master
Master Slave without remote ad-justment
Error No. 35 ST Repeat of error 225: Low pressure 0
ThermSelect® 11. Hydraulic Diagrams
93/100
Factory parameterisation for ThermSelect®Pro design
Control bar
User -level Function / Default value
Set value RVS Air 15
Air 19-28
Air 34-41
Brine 15
Brine 19-41
561-566 E Timer setting 4 Monday 06:00 – 22:00 561-566 E Timer setting 4 Tuesday 06:00 – 22:00 561-566 E Time setting 4 Wednesday 06:00 – 22:00 561-566 E Timer setting 4 Thursday 06:00 – 22:00 561-566 E Timer setting 4 Friday 06:00 – 22:00 561-566 E Timer setting 4 Saturday 06:00 – 22:00 561-566 E Timer setting 4 Sunday 06:00 – 22:00
2801 I Condenser pump control Temperature request ¦ Parallel condenser operation
Temperature request
2803 I Run-on time condenser pump 120 2816 F Source temp min brine -10 2819 I Lead time source 5 2842 I Condenser run time min. 0 2843 I Condenser idle time min 10 2845 F Reduction shut-off temp. Max 0 2853 O Low pressure delay operational 5
2854 O LP monitoring Always ¦ Without thawing
Always
2893 F Number of TWW loading attempts 3 2910 F Clearance above TA --- 2951 I Thawing clearance below TA 10 2954 O Evaporator temp. Thawing end 5 2963 I Time until forced thaw 180 2964 I Thawing time max 20 2971 O Thawing ventilator above 7 3010 O Max. speed V'lator/Q'pump 40 60 100
3541 F Auto sequential exclusion None ¦ First ¦ Last ¦ First and Last
First None
5093 F With solar integration No ¦ Yes
No
5710 I Heating circuit 1 Off
5731 I Drinking water control element Q3 None ¦ Charge pump ¦ Reversing valve
Reversing valve
5800 I Heat source Brine ¦ Water ¦ Air ¦ External
Air Brine
11. Hydraulic Diagrams ThermSelect®
94/100
Control bar
User -level Function / Default value
Set value RVS Air 15
Air 19-28
Air 34-41
Brine 15
Brine 19-41
5890 I
Relay output QX1 None ¦ Condenser stage 2 K2 ¦ Process reversing valve Y22 ¦ Hot gas temperature K31 ¦ Electrical insert1 Flow K25 ¦ Electrical insert2 Flow K26 ¦ Reversing valve cool-ing Track2 Y28 ¦ Delivery pump Q14 ¦ Cascade pump Q25 ¦ Generator shut-off valve Y4 ¦ Electrical insert TWW K6 ¦ Circulation pump Q4 ¦ Storage charge-over pump Q11 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Mixing pump Q35 ¦ Collector pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump ext.exchanger K9 ¦ Solar con-trol element buffer K8 ¦ Solar control element swimming pool K18 ¦ Electrical insert buffer K16 ¦ H1-Pump Q15 ¦ H2-Pump Q18 ¦ H3-Pump Q19 ¦ Heating cycle pump HkP Q20 ¦ 2nd Pump stage HK1 Q21 ¦ 2. Pump stage HK2 Q22 ¦ 2nd Pump stage HKP Q23 ¦ Reversing valve cooling Y21 ¦ Air dehumidifier K29 ¦ Heat request K27 ¦ Refrigeration request
Process reversing valve Y22 None
5891 I
Relais output QX2 None ¦ Condenser stage 2 K2 ¦ Process reversing valve Y22 ¦ Hot gas temperature K31 ¦ Electrical insert1 Flow K25 ¦ Electrical insert2 Flow K26 ¦ Reversing valve cool-ing Track2 Y28 ¦ Delivery pump Q14 ¦ Cascade pump Q25 ¦ Generator shut-off valve Y4 ¦ Electrical insert TWW K6 ¦ Circulation pump Q4 ¦ Storage charge-over pump Q11 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Mixing pump Q35 ¦ Collektor pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump ext.exchanger K9 ¦ Solar con-trol element buffer K8 ¦ Solar control element swimming pool K18 ¦ Electrical insert buffer K16 ¦ H1-Pump Q15 ¦ H2-Pump Q18 ¦ H3-Pump Q19 ¦ Heating cycle pump HkP Q20 ¦ 2. Pump stage HK1 Q21 ¦ 2. Pump stage HK2 Q22 ¦ 2. Pump stage HKP Q23 ¦ Reversing valve cooling Y21 ¦ Air dehumidifier K29 ¦ Heat request K27 ¦ Refrigeration request
Heat requirement K27 None
5930 I
Sensor input BX1 None ¦ Buffer reservoir sensor B4 ¦ Buffer reservoir sen-sor B41 ¦ Collector sensor B6 ¦ Drinking water sensor B31* ¦ Hot gas sensor B82 ¦ Refrigerant sensor liquid B83 ¦ TWW Charge sensor B36 ¦ TWW Tapping sensor B38 ¦ TWW Circulation sensor B39 ¦ Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64 ¦ Buffer reservoir sensor B42 ¦ Track flow sensor B10 ¦ Cascade return sensor B70 ¦ Special temperature sensor 1 ¦ Special tempera-ture sensor 2
Track flow sensor B10
Special -temperature
sensor 1
5931 I
Sensor input BX2 None ¦ Buffer reservoir sensor B4 ¦ Buffer reservoir sen-sor B41 ¦ Collector sensor B6 ¦ Drinking water sensor B31* ¦ Hot gas sensor B82 ¦ Refrigerant sensor liquid B83 ¦ TWW Charge sensor B36 ¦ TWW Tapping sensor B38 ¦ TWW Circulation sensor B39 ¦ Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64 ¦ Buffer reservoir sensor B42 ¦ Track flow sensor B10 ¦ Cascade return sensor B70 ¦ Special temperature sensor 1 ¦ Special tempera-ture sensor 2
Refrigerant liquid B83
ThermSelect® 11. Hydraulic Diagrams
95/100
Control bar
User -level Function / Default value
Set value RVS Air 15
Air 19-28
Air 34-41
Brine 15
Brine 19-41
5950 I
Function input H1 BA toggle HK's+TWW ¦ BA toggle HK's ¦ BA toggle HK1 ¦ BA toggle HK2 ¦ BA toggle HKP ¦ Error / alarm mes-sage ¦ Minimum flow targe value ¦ Heat requirement 10V ¦ Thaw point guard ¦ Flow target value increase hygro ¦ Refrigeration request ¦ Refrigeration request 10V ¦ Pres-sure measurement 10V ¦ Relative room humidity 10V ¦ Room temperature 10V ¦ Clearance swimming pool ¦ Switch-on command WP level 1 ¦ Switch-on command WP level 2
Switch-on command WP level 1
5952 I Function value contact H1 55
5981 O Control direction input EX1 Break contact ¦ Working contact
Break contact
5999 O Control direction LP guard E9 Break contact ¦ Working contact
Break contact
6000 O Control direction HP guard E10 Break contact ¦ Working contact
Break contact
6001 O Cntrl dir. Evap1 overload E11 Break contact ¦ Working contact
Work -
con-tact
Break contact
Work -
con-tact
Break con-tact
6070 I
Function output UX None ¦ Source pump Q8/Venti K19 ¦ Drinking water pump Q3 ¦ TWW Intermediate circuit pump Q33 ¦ TWW Instantaneous water filter Q34 ¦ Collector pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump buffer K8 ¦ Solar pump ext. exchanger K9 ¦ Solar pump swimming pool K18 ¦ Heating circuit pump HK1 Q2 ¦ Heating circuit pump HK2 Q6 ¦ Heating circuit pump HKP Q20 ¦ Heat pump target value ¦ Output target value ¦ Heat require-ment ¦ Cold requirement ¦ Heat pump modulating
Source pump Q8/Venti K19
6128 O Heat request below outdoor temp 5 --- 6600 I Device address 1 2
6640 I Timer mode Autonomous ¦ Slave without remote adjustment ¦ Slave with remote adjustment ¦ Master
Master Slave without remoten ad-
justment
Error No. 35 ST Repeat of error 225: Low pressure 0
Your notes ThermSelect®
96/100
ThermSelect® Your Notes
97/100
Your notes ThermSelect®
98/100
12 Index
ThermSelect® Index
99/100
A
Application limits .......................................................... 39, 51
C
Changes to the device ....................................................... 10 Circuit diagram for ThermSelect® 15 ................................. 26 Circuit diagram for ThermSelect® 19-41 ............................ 28 Circuit diagram für ThermSelect® 15 ................................. 26 Connection of split evaporator with heat pump .................. 48 Connection split evaporator ............................................... 44 Connection terminals ventilator ......................................... 55 Connections at rear wall of heat pump .............................. 20 Control unit AVS ................................................................ 65
D
Device damage ..................................... 5, 40, 42, 43, 63, 77 Disassembly of the control unit .......................................... 70 Duty of documentation........................................... 41, 63, 68
E
Electrical connection for compressor ................................. 54 Electrical connections for RVS controller ........................... 54 Electrical current .................................................................. 8 Electrotechnical data controller ......................................... 34 Enclosure assembly .......................................................... 56 Environmental damage .......................................... 10, 42, 48 EU Design Conformity Declaration .................................... 80
F
Factory parameterisation for ThermSelect® design ........... 90 Factory parameterisation for ThermSelect® Pro design ..... 93
G
Generator shut-off valve ........................................ 33, 91, 94
H
Heat pump connections ..................................................... 49 Heat pump installation ....................................................... 46 Heating water ........................................................ 10, 50, 74 Hot surfaces ........................................................................ 8 Hydraulic connections ....................................................... 50
I Installation clearances ....................................................... 39
L
Limit of liability ................................................................... 76
M
Maintenance record .................................................... 69, 81 Motor control unit .............................................................. 60
P
Planning information for brine operation ........................... 38 Pump control ..................................................................... 64
R
Refrigerant ................................. 9, 17, 39, 40, 43, 48, 63, 69 Refrigerant dosage............................... 24, 43, 48, 64, 67, 76 Requirements for the heat transfer liquid .......................... 50
S
Safekeeping of documentation ............................................ 4 Sensor positions ............................................................... 30 Spare parts ................................................................. 77, 78 Special tariff connection .................................................... 54 Split evaporator ......................................... 21, 41, 42, 43, 48 Split evaporator assembly ................................................. 41 Standards / Regulations for Austria .................................. 12 Standards / Regulations for Switzerland ........................... 13 Switching on the device .................................................... 64
T
Terminal assignment on the heat pump controller ............ 32 Transport ..................................................................... 14, 40
W
Warranty ......................................................... 38, 76, 77, 78 Warranty certificate ........................................................... 78 Water damage .................................................................. 47 Wearing parts .................................................................... 78 Welding work .................................................................... 41
Your notes ThermSelect®
100/100