DOUBLE FLOW VENTILATION
UNITS WITH HIGH EFFICIENCY
ENERGY RECOVERY
titanium.flat.
GENERAL 06
AREAS OF APPLICATION 08
SUMMARY / QUICK SELECTION 09
SELECTION PROGRAMMES, ASSEMBLY / DISASSEMBLY 10
TAC4 CONTROL SYSTEM 11
GENERAL 06
AREAS OF APPLICATION 08
SUMMARY / QUICK SELECTION 09
SELECTION PROGRAMMES, ASSEMBLY / DISASSEMBLY 10
TAC4 CONTROL SYSTEM 11
Flat SERIES 12
Flat SERIES - TECHNICAL CHARACTERISTICS 16
Flat SERIES - ACCESSORIES 24
The Indoor Climate Company
Swegon produces Titanium Flat units in our Factory in
Gembloux, Belgium. The local company employs a team of
more than 50 in modern buildings exceeding 7500 m² of floor
space, and focuses on developing and producing intelligent
products relating to air movement.
Swegon has acquired real proficiency on the matter over the
years. The Total Airflow Control (TAC) technology is one of the
major fruits of this proficiency (cf. p. 11) and is currently in its
fifth generation. This proficiency is applied also to producing
and distributing developed products.
Swegon was a visionary, so TAC technology is applied to
all the ranges of products produced in this facility. These
products have consequently been ‘ERP2015 Compliant’ for more
than 15 years.
In other words, Swegon has been declared, through audits, to
comply with the selective criteria of “positive economy” ®, a
labelling concept intended to reconcile economy and ecology.
TAC technology is at the base of its growth and is today
distributed throughout Europe.
GENERAL
Titanium - high efficiency double flow ventilation units
Swegon specialises in the design and production of double flow
ventilation units with energy recovery. The aim from the outset
was to focus on efficiency. Brochures of that period stressed
that “it is absurd to want to recover heat energy when electric
energy was being wasted…” This is why the first generation TAC
technology was already applied to this product. Accordingly,
direct current Electronically Commutated Motor (ECM) fans
with permanent magnets were systematically selected for the
development of the range. Today, with the latest product
developments, PLC anticipated the ECO design requirements
and as a direct consequence, the Flat series is compliant with
the ErP2016/2018 standards, simply thanks to a philosophical
choice…The control systems have been further improved and
are now open to MODBUS and KNX communication, as well as
to Ethernet & WIFI technologies and all their advantages.
Plug & Play
All the Flat range units are supplied as ‘Plug&Play’. The standard
settings are pre-programmed in the factory, so just connect the
power supply, the control signals and/or the remote control, and
enter the specific settings for the application. Putting the units
into use becomes a breeze…
Accessibility of components The units are designed to give the user easy access to the
different components. The doors are largely sized and fitted
with handles and / or hinges. They are removable, for easy
access, even when installed in limited space. The control panel is
likewise easy to access and centralizes all the wiring.
Counterflow exchangers
The same focus on efficiency led us to opt for counterflow
exchangers.
• These are far superior to other types of exchanger (96%).
• They ensure flawless tightness between the 2 airflows,
thereby constituting great advantage in terms of hygiene
compared with rotary exchangers.
The exchangers are in “salt-air resistant” aluminum and are
suitable for temperatures up to 80°C. They are compliant with
the DIN1946 tightness standard and are Eurovent approved
according to the EN 308 standard (measurement of heat
efficiency and validity of technical data).
High efficiency fans
The TAC fans are equipped with high efficiency DC motors at
the cutting edge of the latest technologies. They can achieve
sizeable external pressure levels, whilst guaranteeing low
consumption throughout the entire operating range.
The TAC control system guarantees the known precision from
the operating point of view and makes an active contribution to
optimized consumption.
The efficiency levels are naturally compliant with the
ErP2016/2018 standards.
Modulating bypass
All Flat units are by default equipped with a modulating bypass.
Operated entirely by control, this system cools the rooms
during the night when the differences of indoor and outdoor
temperature permit. By using the modulating bypass it can be
arranged that the supply temperature does not go below a set
value. This system can be connected to a ground-coupled heat
exchanger to improve efficiency even more. The control settings
can be adjusted by the operator.
Air filters
All the units of the Flat line are supplied as a standard with
oversized air filters (to reduce the pressure drop) that protect
the exchanger and improve the quality of the incoming air. F7
filters are mounted on the fresh air suction (outdoor air) and G4
filters on the room suction (indoor air). Replacement filter kits
are also available.
Tac4 regulation completes the system
The Flat units are fitted with a complete electronic control system
called TAC4 which is used to operate the fans, the bypass,
the anti-freeze protection of the exchanger, the valves, the
preheating coil (option), and post-heating coil (option) as well as
the external hot and/or cold exchangers (option). It is equipped
with a MODBUS, KNX , ETHERNET or WIFI communication bus
used for its interfacing and complete integration with a standard
centralized control system, or a cell phone / tablet.
6 flat
GEN
ERAL
flat 7
Assembly / disassembly
The Titanium units can be installed easily everywhere.
The units of the Flat range are at times too bulky to be
introduced in certain rooms. That is why they can be partially
disassembled so they can be brought in the room where they
have to be installed.
In such a case, it is possible to deliver the unit ready to
be easily disassembled and reassembled on the spot.
It is nonetheless preferable to provide for this functionality,
which requires a specific assembly in the factory, from the
outset. This operation can be carried out by the installer by
following the instructions of the manual provided for this
purpose.
This is however an option which needs to be specified
beforehand when placing the order.
Contact our sales department or consult our ad hoc brochure
for more information on the subject.
Selection programmes
A selection software is available for all Titanium products series.
It can be used to determine:
• The technical characteristics of the unit under the conditions of application: power
consumption, heat efficiency, air characteristics, sound levels, etc
• The commercial aspects such as the options, price & order information
This user-friendly tool can be requested from [email protected]
Selection programmeS, aSSembly/DiSaSSembly
GEN
ERAL
The Titanium Flat can be used in Commercial Ventilation applications and in residential projects, both in the case of new construction or refurbishment :
� Retail Shops
� Supermarkets
� Cafeterias, restaurants
� Small & large offices
� Fitness centers, gyms
� Hotels, cinemas, theatres
� Schools, College & Universities
� Medical centers
� Hospitals
� Day-care centers
They have to be selected in accordance with the application and the desired result in terms of efficiency and sound level.
Ventilation systems
With the Flat range, Swegon presents a wide, mature and
complete range of centralised ventilation units with energy
recovery. There is a unit that corresponds to each application,
if it is between 25 and 1,700 l/s. Whether the application is
commercial or residential residential or otherwise, all the
units have high efficiency, high-tech EC fans operated by an
intelligent TAC4 system, and exchangers are used to recover up
to 96% of the heat energy contained in the ventilation cycle.
These characteristics guarantee an optimal efficiency for the
unit. Since April 2015, our Flat Series features an ECO version.
Each of these ECO units is equipped with backward fans (plug
fans). This innovation, in line with new market requirements,
cares for better fan yield and lower electrical consumption.
� Apartment buildings
� Individual houses
� New residential complexes
� Swimming pools
areaS of application
Areas of application
8 flat
GEN
ERAL
flat 9
titanium SerieS centraliSeD ventilation SyStem Summary / Selection
Flat SizeAIRFLOW RATE [l/s] CiD
AUTOMATIC BYPASS
BUILT-IN PRE-/POST-HEATING
EXTERNAL POST-HEATING/COOLING
Flat 450 15-125 Yes - 100% YES YES YES
Flat 600 15-170 Yes - 100% YES YES YES
Flat 1000 30-300 Yes - 100% YES YES YES
Flat 1600 30-450 Yes - 100% YES YES YES
Flat 2000 30-560 Yes - 100% YES YES YES
Summary
Advantages of Titanium units
� The Flat are units with high efficiency with low operating
and maintenance costs .
� All Flat units can be configured simply by using a (graphical)
remote control or a dedicated PLC App or by using a more
sophisticated network (SAT Modbus or KNX).
� The air breathed in the buildings is always pleasantly fresh
and healthy.
� The systems avoid the damages caused by humidity and
mildew.
� Extensive energy savings thanks to high efficiency energy
exchangers.
� The constant pressure mode (CPs) ensures individualised
centralised ventilation in an apartment building. The
constant torque mode (TQ) allows an external system to
control the fans via the torque or the rotationspeed of the
fan.
� The constant airflow mode (CA) ensures that the flow rate
is maintained irrespective of the pressure drop.
� The constant airflow mode linked to a 0-10V (LS) signal
links the flow rate directly to a sensor value (example, an air
quality sensor).
� The post-heating and/or cooling coils (option) ensure a
desired comfort temperature of the supply air.
GEN
ERAL
titanium.flat.
Flat units for installation in false ceilings.
Flat is a range of controlled mechanical ventilation
units with high efficiency heat recovery (up to 96%),
composed of a counter flow aluminium plate exchanger,
a stainless steel condensate collection tray, filters (class
G4/F7), a 100% bypass and centrifugal fans with high
efficiency electronic motor (TAC series), from which it
draws all the advantages. It is designed for applications
going up to 2000 m³/h. The efficiency of the heat
exchanger often makes adding a post-heating (or post-
cooling) system superfluous, although such a system is
provided as an option (external module).
Their “flat” design (320 to 400 mm high) makes
them ideal for false ceiling applications, which means
substantial savings in terms of the use of the available
surface area (€/m²).
It is delivered ready to use, entirely pre-wired - the
options too -- and with a remote control (to choose)
or a MODBUS/KNX communication for controlling the
device without opening it… Just connect it to the power
supply (outside the unit and to the remote control or the
MODBUS/KNX communication to activate the unit, and
it’s ready to run -- irrespective of the options chosen:
electric preheating (anti-frosting), water or electric post-
heating, post-cooling, valves, etc.
Control modules available as an option
RC REMOTE CONTROL
GRC GRAPHIC REMOTE
CONTROL
SAT TAC4 MODBUS INTERFACE
SAT TAC4 BA/KW INTERFACE
Available options
� Electric preheating coil (KWin)
� External post-heating/cold coil (BA+/-)
� Motorised dampers (CTm)
SAT3
� High efficiency counterflow heat exchange (up to 96% efficiency) in aluminum resistant to seawater and for temperatures between -30° C and +100° C. It is Eurovent approved according to EN308.
� High efficiency motors: direct current motor with permanent magnets and electronically commutated (ECM):
� High efficiency fans: choice between forward curved and backward inclined wheels (ECO Version).
� Setting and piloting of the TAC fans in 4 different modes:
1. CPs mode (constante pressure measured via an optional external sensor)
2. TQ mode (constant torque)
3. CA mode (constant airflow)
4. LS mode (link to signal 0-10V).
� Compact casing made of anodised aluminium structure and acoustically and thermally insulated panels (rockwool 50 mm) in painted steel on the outside (RAL9002) and galvanised steel inside.
� Stainless steel condensate tray.
� Filters: F7 for incoming air and G4 (F7 as an option) for outgoing air.
� 125 mm base in galvanised steel (except Flatup 450).
� Filter replacement alarm based on a measurement of pressure and/or operating time of the unit.
� Automatic 100% bypass activated by an actuator for free cooling in summer (temperature settings adjustable by the user). The bypass can also be operated by built-in clock and/or by external contact.
� Automatic antifrost system by means of modulating air flows or by electric preheating coil (option KWin – not available for the Flatup 450).
� Operation and control of a water (NV) or electric (KWout) post-heating coil (not available for the Flatup 450) to maintain a constant user defined supply air temperature.
� Operation and control of external reversible water heat exchanger, or with direct expansion (evaporation/
condensation, Heat pumps) for postheating/ cooling.
� External direct expansion coil or heat pump post heating / cooling
� Non-return valve, motorised or operated by control (option CT). Not available for Flatup 450 and 800.
� Fire alarm management by activation of supply and extraction airflow with possible override by the fire brigade via the external contacts.̀
� Connection to a BMS system via a digital and/or analogue system (if the MODBUS communication cannot be used). BMS control functions via a MODBUS RTU protocol or KNX (SAT MODBUS or SAT KNX: option).
� Indoors or outdoors assembly (option VEX – not available for Flatup modules) with roof, with roof, air intake hood ith protective grid and louvre for exhaust air.
� The units are available in a left or right version (except Flatup 450).
Technical characteristics
PLC APP SAT WIFI
SAT TAC4 KNX INTERFACE
SAT ETHERNET
MODBUS RTU/ TCP IP
WIFI
KNX
ETHERNET
LCD REMOTE CONTROL
GRCUser friendly graphicaltouch screen
Swegon APPSwegon dedicatedapp for tablet andsmartphone
STANDARD APPStandard availableapp for tablet andsmartphone
ANY KNX DISPLAY OR INTERFACE
Integration in BuildingManagement system usingthe MODBUS
or KNX
WORKING MODES Constant Airflow Air quality (CO2, VOC and HR) Constant PressureUP TO 74 SPECIFIC ALARMS
BOOST
TIME TABLE
SEASONAL MANAGEMENT
FREECOOLING
POSTHEATING / COOLING
CONFORT SUPPLY T° CONTROL
DAMPER CONTROL
ADVANCED ANTI FROST PROTECTION
COMMUNICATION BUS
MODBUS RTU/ TCP IP
WIFI
KNX
ETHERNET
LCD REMOTE CONTROL
GRCUser friendly graphicaltouch screen
Swegon APPSwegon dedicatedapp for tablet andsmartphone
STANDARD APPStandard availableapp for tablet andsmartphone
ANY KNX DISPLAY OR INTERFACE
Integration in BuildingManagement system usingthe MODBUS
or KNX
WORKING MODES Constant Airflow Air quality (CO2, VOC and HR) Constant PressureUP TO 74 SPECIFIC ALARMS
BOOST
TIME TABLE
SEASONAL MANAGEMENT
FREECOOLING
POSTHEATING / COOLING
CONFORT SUPPLY T° CONTROL
DAMPER CONTROL
ADVANCED ANTI FROST PROTECTION
HMI BMS
14 Flat
General characteristics
Technical data
Technical characteristics
• AIRFLOW 15 - 125 l/s
• DIMENSIONS (L X W X H) 1100 x 665 x 360
• WEIGHT 87 kg
• NOMINAL VOLTAGE 1 x 230V - 50Hz
• MAXIMUM INTENSITY 3,0 A
• RECOMMENDED ELECTRICAL PROTECTION 8 A / D-10000A-AC3
• SUPPLY / EXTRACTION FILTER G4 / G4 (F7 optional)
• AVAILABLE OPTIONS KWin / BA+/- / CTm / ER and SR by default
• AUTOMATIC FREE COOLING Yes / 100%
• OPERATING TEMPERATURE RANGE -20°C (lower value if option KWin) to +50°C
• COLOUR OF PANELS RAL 9002
• CID
FLOW RATEPOWER
ABSORBEDSFP
EXCHANGER EFFI-CIENCY
OUTLET T° AFTER EXCHANGER
SOUND LEVEL Conditions:
1. values calculated on the basis of an external 100 Pa system curve at maximum flow rate.
2. efficiency calculations for external conditions of -10°C, 90% RH and internal conditions of +22°C, 50% RH.
3. Sound level in the free field at 3m.
l/s W w/l/s % °C dB(A)
30 7 0,25 95,6 20,6 11,7
60 39 0,65 93,4 19,9 22,6
90 106 1,17 92,1 19,5 29,5
120 344 2,86 90,7 19 36,4
Flat.450
Flow rate (l/s)
Δpst [Pa]700
600
500
400
300
200
100V [l/s]
30 60 90 120 150
Exte
rnal
pre
ssur
e (P
a)
FLAT
DIMENSIONS (mm)
From the outside From the inside To the outside To the inside
Flat 15
Flat 450 Flat : Dimensions
Flat 450
1
1
2
2 4
3
4
3
FLAT
16 Flat
General characteristics
Technical data
Technical characteristics
• AIRFLOW 15 - 170 l/s
• DIMENSIONS (L X W X H) 1490 x 955 x 320
• WEIGHT 142 kg
• NOMINAL VOLTAGE 1 x 230V - 50Hz
• MAXIMUM INTENSITY 3,0 A
• RECOMMENDED ELECTRICAL PROTECTION 8 A / D-10000A-AC3
• SUPPLY / EXTRACTION FILTER G4 / G4 (F7 optional)
• AVAILABLE OPTIONS KWin / BA+/- / CTm / ER and SR by default
• AUTOMATIC FREE COOLING Yes / 100%
• OPERATING TEMPERATURE RANGE -20°C (lower value if option KWin) to +50°C
• COLOUR OF PANELS RAL 9002
• CID
Flat.600
FLOW RATEPOWER
ABSORBEDSFP
EXCHANGER EFFI-CIENCY
OUTLET T° AFTER EXCHANGER
SOUND LEVEL Conditions:
1. values calculated on the basis of an external 100 Pa system curve at maximum flow rate.
2. efficiency calculations for external conditions of -10°C, 90% RH and internal conditions of +22°C, 50% RH.
3. Sound level in the free field at 3m.
l/s W w/l/s % °C dB(A)
45 11 0,25 95,3 20,5 13,8
90 56 0,62 93,1 19,8 25,3
120 159 1,33 91,8 19,4 32,2
150 344 2,30 90,8 19,1 37,2
Flow rate (l/s)
Δpst [Pa]700
600
500
400
300
200
100V [l/s]
30 60 90 120 150 180
Exte
rnal
pre
ssur
e (P
a)
FLAT
DIMENSIONS (mm)
From the outside From the inside To the outside To the inside
Flat 17
Flat 600 Flat : Dimensions
Flat 600
1
2 4
3
1 3
2 4
FLAT
18 Flat
General characteristics
Technical data
Technical characteristics
• AIRFLOW 30 - 300 l/s
• DIMENSIONS (L X W X H) 1550 x 1105 x 400
• WEIGHT 171 kg
• NOMINAL VOLTAGE 1 x 230V - 50Hz
• MAXIMUM INTENSITY 6,2 A
• RECOMMENDED ELECTRICAL PROTECTION 8 A / D-10000A-AC3
• SUPPLY / EXTRACTION FILTER G4 / G4 (F7 optional)
• AVAILABLE OPTIONS KWin / BA+/- / CTm / SR and ER by default
• AUTOMATIC FREE COOLING Yes / 100%
• OPERATING TEMPERATURE RANGE -20°C (lower value if option KWin) to +50°C
• COLOUR OF PANELS RAL 9002
• CID
Flat.1000
FLOW RATEPOWER
ABSORBEDSFP
EXCHANGER EFFI-CIENCY
OUTLET T° AFTER EXCHANGER
SOUND LEVEL Conditions:
1. values calculated on the basis of an external 100 Pa system curve at maximum flow rate.
2. efficiency calculations for external conditions of -10°C, 90% RH and internal conditions of +22°C, 50% RH.
3. Sound level in the free field at 3m.
l/s W w/l/s % °C dB(A)
70 21 0,30 95,5 20,6 16,8
140 99 0,71 93,4 19,9 27,8
210 271 1,29 92,1 19,5 34,7
280 555 1,98 91,1 19,2 39,6
Flow rate (l/s)
800Δpst [Pa]
700
600
500
400
300
200
100V [l/s]
60 120 170 220 280 1200
Exte
rnal
pre
ssur
e (P
a)
FLAT
DIMENSIONS (mm)
From the outside From the inside To the outside To the inside
Flat 19
Flat 1000 Flat : Dimensions
Flat 1000
1
2 4
3
1 3
2 4
FLAT
20 Flat
General characteristics
Technical data
Technical characteristics
• AIRFLOW 30 - 450 l/s
• DIMENSIONS (L X W X H) 1550 x 1745 x 400
• WEIGHT 228 kg
• NOMINAL VOLTAGE 1 x 230V - 50Hz
• MAXIMUM INTENSITY 9,2 A
• RECOMMENDED ELECTRICAL PROTECTION 16 A / D-10000A-AC3
• SUPPLY / EXTRACTION FILTER G4 / G4 (F7 optional)
• AVAILABLE OPTIONS KWin / BA+/- / CTm / IRS / SR by default
• AUTOMATIC FREE COOLING Yes / 100%
• OPERATING TEMPERATURE RANGE -20°C (lower value if option KWin) to +50°C
• COLOUR OF PANELS RAL 9002
• CID
Flat.1600
FLOW RATEPOWER
ABSORBEDSFP
EXCHANGER EFFI-CIENCY
OUTLET T° AFTER EXCHANGER
SOUND LEVEL Conditions:
1. values calculated on the basis of an external 100 Pa system curve at maximum flow rate.
2. efficiency calculations for external conditions of -10°C, 90% RH and internal conditions of +22°C, 50% RH.
3. Sound level in the free field at 3m.
l/s W w/l/s % °C dB(A)
110 27 0,25 95,5 20,6 18,1
220 153 0,69 93,4 19,9 31,2
330 446 1,35 92,1 19,5 40,6
440 961 2,18 91,1 19,2 47,3
Flow rate (l/s)
Δpst [Pa]1050
900
750
600
450
300
150V [l/s]
50 100 150 200 250 300 350 400
Exte
rnal
pre
ssur
e (P
a)
FLAT
DIMENSIONS (mm)
From the outside From the inside To the outside To the inside
Flat 21
Flat 1600 Flat : Dimensions
1
2 4
3
1 3
2 4
Flat 1600
FLAT
22 Flat
General characteristics
Technical data
Technical characteristics
• AIRFLOW 30 - 600 l/s
• DIMENSIONS (L X W X H) 1700 x 2045 x 400
• WEIGHT 250 kg
• NOMINAL VOLTAGE 1 x 230V - 50Hz
• MAXIMUM INTENSITY 11,2 A
• RECOMMENDED ELECTRICAL PROTECTION 16 A / D-10000A-AC3
• SUPPLY / EXTRACTION FILTER G4 / G4 (F7 optional)
• AVAILABLE OPTIONS KWin / BA+/- / CTm / IRS / SR by default
• AUTOMATIC FREE COOLING Yes / 100%
• OPERATING TEMPERATURE RANGE -20°C (lower value if option KWin) to +50°C
• COLOUR OF PANELS RAL 9002
• CID
Flat.2000
FLOW RATEPOWER
ABSORBEDSFP
EXCHANGER EFFI-CIENCY
OUTLET T° AFTER EXCHANGER
SOUND LEVEL Conditions:
1. values calculated on the basis of an external 100 Pa system curve at maximum flow rate.
2. efficiency calculations for external conditions of -10°C, 90% RH and internal conditions of +22°C, 50% RH.
3. Sound level in the free field at 3m.
l/s W w/l/s % °C dB(A)
140 40 0,28 95,5 20,6 19,8
280 211 0,75 93,4 19,9 30,9
420 601 1,43 92,1 19,5 38,5
560 1283 2,29 91,1 19,2 44,6
Flow rate (l/s)
Δpst [Pa]1400
1200
1000
800
600
400
200V [l/s]
140 280 420 560 700
Exte
rnal
pre
ssur
e (P
a)
FLAT
DIMENSIONS (mm)
From the outside From the inside To the outside To the inside
Flat 23
Flat 2000 Flat : Dimensions
Flat 2000
1
2 4
3
1 3
2 4FLAT
24 Flat
MODEL MAXIMUM POWER ΔT (1) MINIMUM EXTE-
RIOR T°(1) (3)
MAXIMUM INTENSITY
ADMISSIBLE PER PHASE
PRESSURE DROP (2) CID
[KW] [°C] [°C] [A] [PA]
Flat 450 1,5 9/14/29 -22/-26/-41 6,5 8 Pa 882435
Flat 600 2 9/14/29 -22/-26/-41 8,7 8 Pa 882436
Flat 1000 3 8/13/26 -21/-25/-38 13,0 9 Pa 882437
Flat 1600 6 11/16/33 -23/-28/-44 8,8 5 Pa 882438
Flat 2000 6 8/13/26 -21/-25/-38 8,3 11 Pa 882438
The Flat units can be equipped with heat-ing elements (pre-heating). On the incom-ing air side.It is possible to insert an electric pre-heat-ing coil to avoid the risk of the exchanger frosting in case of very low exterior suc-tion temperatures. It is supplied entirely pre-wired to the TAC4 regulation and can withstand a temperature as low as about -40°C (see table below) for suction at an interior temperature of +22°C, without
risk of frosting, depending on the flow and humidity rates concerned. The power of the KWin exchanger is modulated to maintain the post-exchange temperature equal to the no frost set point of the coun-ter flow exchanger. If the temperatures are such that this temperature cannot be attained even though the KWin is at maxi-mum power, the regulation will reduce the supply and exhaust air flow rates (balance maintained) to attain the set point.
Electrical pre-heating coils (kwin)
electric pre- anD post-heating coils Flat series: accessories
(1) Calculated at 100 %, 66% and 33% of the maximum flow rate.(2) Calculated at maximum flow rate.
(3) Calculated with extract air at 22°C - 50%RH.
Replacement filter kits
MODEL CID Filters fresh air in Filters stale airout
Flat 450 510045 G4 G4
Flat 450 510017 F7 G4
Flat 600 510046 G4 G4
Flat 600 510018 F7 G4
Flat 1000 510047 G4 G4
Flat 1000 510019 F7 G4
Flat 1600 510048 G4 G4
Flat 1600 510020 F7 G4
Flat 2000 510049 G4 G4
Flat 2000 510021 F7 G4
The Flat units are delivered as a stand-ard with G4 filters on incoming and out-going airstreams.Class F7 filtering on incoming air is avail-able as an option. A replacement kit with all the necessary filters is available for each unit.It exists in 2 versions :
• G4 filters for incoming and outgo-ing air.
• G7 filter(s) for incoming air and G4 for outgoing air
FLAT
Flat 25
This external module is provided for the Titanium flat models and
can be mounted either in the supply air ductway, or directly on the
unit. It comprises a water (+/-) or evaporation/condensation 4-row
coil .
It can be used for the post-heating and/or post-cooling of the
supply airstream.
If the module takes a water coil, it is supplied ready to be
connected to the hydraulic network (+/-), with the full regulation
and a motorised 3-way valve. It suffices to set the requested
supply air temperature; the regulation will modulate the capacity
of the coil to attain it.
Module BA+/-
moDule Ba +/- Flat series: accessories
MODEL CONNEC-TIONS
MAXIMUM POWER
(1) (2) (3) ΔT (1) (3) PRESSURE
DROP AIR (2)FLUID FLOW RATE (2) (3)
PRESSURE DROP FLUID
(2) (3)CID
[MM] [KW] [°C] [PA] [KG/H] [KPA]
Flat 450 12/22 2,5 / 1,6 11 / 13 53 61,1 0,6 882446
Flat 600 12/22 3,0 / 1,9 10 / 12 80 73,1 0,8 882446
Flat 1000 12/28 6,1 / 3,7 12 /14 48 147,9 4,9 882448
Flat 1600 12/28 10,1 / 5,7 12 / 13 62 243,6 16,0 882450
Flat 2000 12/28 11,9 / 6,9 11 / 13 86 286,0 22,5 882450
EVAPORATION -
Conditions : Outside air: 30°C and 40% RH, Extract air: +22°C and 50% RH, supply air temperature without BA evap: 23.5°C
(1) Calculated at 100% and 50% of the maximum flow rate.(2) Calculated at maximum flow rate.(3) R410A / Evaporation temperature = 4°C
CONDENSATION +
MODEL CONNEC-TIONS
MAXIMUM POWER (1) (3)
ΔT (1) (3)
PRESSURE DROP AIR (2)
FLUID FLOW RATE (2) (3)
PRESSURE DROP FLUID
(2) (3)CID
[MM] [KW] [°C] [PA] [KG/H] [KPA]
Flat 450 22/12 1,9 / 1,2 13 / 16 40 27,2 0,1 882446
Flat 600 22/12 2,3 / 1,4 11 / 14 61 32,3 0,1 882446
Flat 1000 28/12 6,0 / 3,5 18 / 21 37 83,5 0,6 882448
Flat 1600 28/12 9,5 / 5,6 18 / 21 47 132,6 1,8 882450
Flat 2000 28/12 10,9 / 6,6 16 / 20 65 152,5 2,4 882450
Conditions : Outside air:-10°C and 90% RH, Extract air: +22°C and 50% RH, supply air temperature without BA cond: 19°C
(1) Calculated at 100% and 50% of the maximum flow rate.(2) Calculated at maximum flow rate.(3) R410A / Condensation temperature = 40°C
FLAT
26 Flat
moDule Ba +/- Flat series: accessories
MODEL CONNEC-TIONS
WATER TEM-PERATURE
MAXIMUM POWER
(1)ΔT (1)
PRES-SURE
DROP AIR (2)
WATER FLOW
RATE (2)
PRES-SURE DROP
WATER (2)
CID
[°C] [KW] [°C] [PA] [L/H] [KPA]
Flat 450 3/4''
80°C / 60°C
50°C / 40°C
40°C / 35°C
6,2 / 3,5
3,0 / 1,6
2,2 / 1,2
41 / 46
20 / 21
15 / 16
43
41
40
274
262
387
0,8
0,8
1,8
882445
Flat 600 3/4''
80°C / 60°C
50°C / 40°C
40°C / 35°C
7,8 / 4,4
3,8 / 2,1
2,8 / 1,5
38 / 44
19 / 20
14 / 15
65
62
61
341
327
483
1,2
1,3
2,6
882445
Flat 1000 3/4''
80°C / 60°C
50°C / 40°C
40°C / 35°C
14,8 / 8,2
7,3 / 4
5,3 / 2,8
44 / 49
22 / 24
16 / 17
39
37
36
651
638
915
2,6
2,7
5,4
882447
Flat 1600 3/4''
80°C / 60°C
50°C / 40°C
40°C / 35°C
22,9 / 12,8
11,3 / 6,2
8,2 / 4,4
42 / 48
21 / 23
15 / 16
49
47
46
1006
986
1416
3,6
3,7
7,4
882449
Flat 2000 3/4''
80°C / 60°C
50°C / 40°C
40°C / 35°C
27,1 / 15,5
13,4 / 7,5
9,7 / 5,3
40 / 46
20 / 22
14 / 16
68
65
64
1191
1167
1680
4,8
5,1
10,1
882449
HOT WATER (BA+)
Conditions : Exterior air: -10°C and 90% RH, Interior air: +22°C and 50% RH, Exit air temperature without BA: 19 °C (at max airflow)(1) Calculated at 100% and 50% of the maximum flow rate.
(2) Calculated at maximum flow rate.
MODEL CONNEC-TIONS
WATER TEMPERA-
TURE
MAXIMUM POWER
(1)ΔT (1)
PRES-SURE
DROP AIR (2)
WATER FLOW RATE
(2)
PRES-SURE DROP
WATER (2)
CID
[°C] [KW] [°C] [PA] [L/H] [KPA]
Flat 450 3/4''
7°C/12°C
10°C/15°C
13°C/18°C
1,4 / 1,0
1,0 / 0,7
0,7 / 0,4
8 / 10
7 / 8
5 / 6
44
39
38
239
170
117
0,9
0,5
0,3
882445
Flat 600 3/4''
7°C/12°C
10°C/15°C
13°C/18°C
1,6 / 1,1
1,1 / 0,8
0,8 / 0,5
7 / 9
6 / 7
4 / 5
66
58
59
273
195
134
1,2
0,6
0,3
882445
Flat 1000 3/4''
7°C/12°C
10°C/15°C
13°C/18°C
4,5 / 2,3
2,8 / 1,5
1,6 / 1,0
10 / 10
7 / 8
5 / 6
44
38
35
770
482
266
4,9
2,1
0,7
882447
Flat 1600 3/4''
7°C/12°C
10°C/15°C
13°C/18°C
6,9 / 3,8
4,5 / 2,2
2,2 / 1,5
9 / 10
7 / 8
4 / 5
57
49
44
1188
767
373
6,7
3,0
0,8
882449
Flat 2000 3/4''
7°C/12°C
10°C/15°C
13°C/18°C
8,1 / 4,7
5,3 / 2,5
2,8 / 1,6
9 / 10
7 / 7
4 / 5
79
68
61
1394
915
474
8,9
4,1
1,3
882449
COLD WATER (BA-)
Conditions : Exterior air: 30°C and 40% RH, Interior air: +22°C and 50% RH, Exit air temperature without BA-: 23.5°C (AT MAX AIRFLOW)(1) Calculated at 100% and 50% of the maximum flow rate.
(2) Calculated at maximum flow rate.
FLAT
Flat 27
moDule Ba +/- Flat series: accessories
DIMENSIONS BA W (HOT WATER/COLD WATER)
MODEL CID A B C D E F G H J K l m n o P R s t U
[mm]
Flat 450 / 600 65 49 39 3/4" 107 250 55 400 - - - -
Flat 1000 65 53 245 39 3/4" 147 250 55 600 - - - -
Flat 1600 / 2000 65 53 245 39 3/4" 147 315 55 650 - - - -
FLAT
28 Flat
moDule Ba +/- Flat series: accessories
BA DX DIMENSIONS (EVAPORATION/CONDENSATION)
MODEL CID A B C D E F G H J K l m n o P R s t U
[mm]
Flat 450 / 600 - - - - - 39 - 107 250 - 400 55 22
Flat 1000 - - - - - 39 - 147 250 - 600 55 28
Flat 1600 / 2000 - - - - - 39 - 147 315 - 650 55 28
FLAT
Flat 29
motoriseD Dampers / rounD/square inlet Flat series: accessories
The Flat units can be equipped with mo-
torised dampers delivered pre-wired to
cut draughts when the unit is deactivat-
ed. They are delivered with a pre-wired
servomotor and are controlled entirely by
the regulation system. A starting delay of
the fans is designed to allow the damper
to open first.
They are made of galvanised steel and
are designed and sized to reduce the air
resistance optimally. They are airtight
thanks to the particular design of blades
that fit into each other.
They are 130 mm deep.
Motorised damper (CTm)
MODEL CID INTERIOR DIMENSIONS[mm]
EXTERIOR DIMENSIONS[mm]
CTm HRf 450 882454 245 x 245 335 x 335
CTm HRf 600 882455 245 x 445 335 x 535
CTm HRf 1000 882456 275 x 375 365 x 465
CTm HRf 1600 882457 275 x 905 365 x 995
CTm HRf 2000 882457 275 x 905 365 x 995
Round/square inlet (IRS)
MODEL CID
Flat 1600 168025
Flat 2000 168026
Flat 1600 Flat 2000
The inlet side of the Flat 1600 and 2000 models is rectangular. A round/square adaptation is available as an option for these 2 models to allow the use of a circular ducting.
FLAT
30 Flat
tac4 regulation system choose the right moDe oF operation.
Depending on the requirements and characteristics of the application, there is an airflow control mode that will fit the situation: constant airflow (CA), constant pressure (CPs), variable constant airflow liked to a 0-10V signal (LS) or constant (CT) are the 4 airflow controls from which to choose.The master/slave link between supply and exhaust (which may be deactivated if necessary) always ensures for a balanced ventilation. This means that the when the exhaust airflow fluctuates because there is a request for more ventilation, the supply airflow will always adapt to preserve the preset balanced between the 2 flows. This occurs, independently from the pressure conditions.
� Constant airflow (CA mode) is used when one or several stable air volumes are needed. The fan will deliver the requested airflow independently from pressure conditions. This is the simplest mode, it allows 3 different pre-set airflows (low, medium, high) and is used with simple control systems.
� Variable constant airflow (LS mode) is probably the most economical ventilation mode, because the airflow actually provided depends on the actual air renewal needed at the moment, so there will be no superfluous ventilation. In this case, the constant airflow requested is linked to a 0-10V signal, measuring the CO2 level for example. When the level is high (many people present), the airflow rate will be adjusted accordingly, and vice-versa, when there are
few people in the room. Energy consumption will follow the real ventilation requirement. is probably the most economical ventilation mode, because the airflow actually provided depends on the actual air renewal needed at the moment, so there will be no superfluous ventilation. In this case, the constant airflow requested is linked to a 0-10V signal, measuring the CO2 level for example. When the level is high (many people present), the airflow rate will be adjusted accordingly, and vice-versa, when there are few people in the room. Energy consumption will follow the real ventilation requirement..
� Variable flow rate to maintain a constant pressure (CPs mode): a particularly interesting application of this operating mode is undoubtedly the individualized ventilation of apartments by a centralized ventilation unit. Once configured, the ventilation of each apartment remains constant even if several apartments change their ventilation demand, as the pressure in the network is maintained constant. A pressure measurement sensor is used to configure this very useful mode.
� Constant torque mode (TQ mode): This mode simulates the ‘normal’ way for a fan to operate when using a frequency controller or a transformer. The fan torque is modulated instead of the airflow. The mode allows the preset of 3 different ‘percentages’ of the maximum fan torque. This mode was essentially developed for plug fan applications where constant airflow feature is not required.
The 3 operating modes: concrete examples
CA stands for “constant airflow.” This means that one (or more) airflow is selected and the TAC4 control will operate the fan to provide the actual airflow requested, irrespective of the pressure drop. Example: I request 1350 m³/h from the fan/control and I obtain, irrespective of the pressure drop of the network, not about 1350 m³/h, but exactly 1350 m³/h….
LS stands for “link to a 0-10V signal.” This means a specific linear relationship between a 0/10V value (representing temperature, humidity, CO2 rate, etc.) and the actual airflow is configured, and the fan/control will see that this link, irrespective of the pressure drop of the network, is delivered. Example: “I create a link between airflow and CO2 level as shown in graph 2. If I read a CO2 level of 1000 ppm, I need 900 m³/h of airflow. The fan will deliver 900 m³/h, independently from the pressure conditions.”
CPs stands for “constant pressure.” This means that you enter an initialization flow rate to determine the resulting pressure, which will then be stored and serve as the reference pressure value to be maintained constant by the system. It is also possible to introduce the pressure value directly, if it is known. The fan will then operate as CA fan, but with the mission to keep the stored pressure value constant. Example: “Once the network is balanced, I note that to obtain 150 m³/h in each apartment, I am creating a pressure loss of 185 Pa in the network. I store this value and the system will change its flow rate to maintain it constant. This will ensure a constant flow rate in each apartment, irrespective of the changes that each inhabitant makes to his ventilation…”
CT stands for “constant torque”. This means the fan will operate like a “normal” fan without constant airflow features, just like if normal AC motor is being powered through a variable frequency controller.
1350
Pa
m3/h
154
m3/h
Pa
185
V
m3/h m3/h
Pa
900 9000
10
2205
1800
2000
1000
ppm
Probe
TAC4: Advanced airflow control technology
FLAT
Flat 31
� Alarms :
The TAC4 can generate up to 74 specific alarms out of the
following 17 categories:
1. Fan failure alarm
2. Pressure variation alarm
3. Alarm in cas of problem during reference pressure
initialization
4. Alarm if the system cannot fulfil the set point
5. Alarm in case of data failure in the control circuit
6. Fire alarm
7. Maintenance alarm
8. Alarm reporting a communication breakdown between
the TAC4 circuit and the RC
9. T° sensor failure alarm
10. Drain pump alarm
11. Alarm reporting that the comfort T° is too low (set T°
value not achieved)
12. Alarm reporting that the comfort T° is too high (set T°
value not achieved)
13. Alarm reporting a too low supply T°
14. Alarm reporting the heat exchanger anti-frost
activation
15. Alarm reporting the hydraulic coils anti-frost
16. Alarm reporting an error on the rotary heat exchanger
rotation speed
17. Alarm reporting a bad positioning of the modulating
bypass
� Boost : activates preset configurable supply and exhaust
airflows. The activation of the boost has a higher priority than
any normal working mode.
� Basic Time table : enables the automatic working working of
the unit based on 4 time slots having their own configurable
set points. Each day of the week has the same time slots but
can be set as an offday.
� Advanced Time table (available with GRC option or through
Modbus communication) : enables the automatic working
mode of the unit following 6 time slots having their own
configurable set points. Each days of the week has its own
6 time slots with independent settings. In addition, for each
time slot, the bypass status can be forced and a different
tac4 regulation system Functionnalities.
comfort temperature can be configured.
� Seasonal management : allows to disable features such as
bypass, post heating and post cooling according to the current
period of the year.
� Free cooling : automatic free cooling of the building during
summer nights, when specific temperature conditions are met,
with:
� Open/closed bypass: based on inside and outside T°
the bypass is opened to supply fresh air in the building
without energy recovery to cool the building down.
The bypass will then be closed automatically when set
temperatures values are achieved. The opening can also
be forced independently from T° values.
� Modulating bypass: same principle as for “open/closed”
models but the opening/closing of the bypass is
modulated (0-100%) to keep a set supply T° constant.
� Post heating / cooling : automatic power control of a heating
or cooling coil to reach the set comfort temperature and keep
it constant. The reference temperature can be either on
supply or exhaust air (“room t°”).
� Comfort T° : comfort temperature control can be made via
the post heating/cooling or the free cooling with modulating
bypass.
� Damper control : temporized opening/closing of inlet dampers
(option) to avoid undesired incoming air when the unit is
stopped.
� Advanced anti frost protection of the heat exchanger : The
TAC4 controls the exhaust T° after the heat exchangers and
keep it above a set value (antifrost T°)
4 types of protection are available :
1. Warming up the incoming fresh air using an electrical or
water preheating coil.
2. Reduction of the supply airflow.
3. Control of the air quantity passing through the
modulating bypass. In this cas a postheating coil is
usually necessary.
4. If rotary heat exchanger : rotation speed modulation
of the wheel.
FLAT
32 Flat
tac4 regulation system optional moDules
The TAC4 regulation mounted in the Titanium units can be combined with different options :
� MODBUS RTU communication
circuit to be plugged in the TAC4
regulation circuit.
� It gives the possibility to
communicate in network with one
or several Titanium units and to
configure, control and display them
TAC4 SAT MODBUS
ARTICLE CID
SAT TAC4 MODBUS 025006
from a central point.
� A direct application of the SAT
MODBUS is the integration of
� MODBUS TCP/IP communication
device to be plugged in the TAC4
regulation circuit.
� Ethernet 10 base T to set in network
Titanium units to configure, control
display from one or several access
points.
TAC4 SAT ETHERNET
ARTICLE CID
TAC4 SAT ETHERNET 025072
� Interface with dedicated Apps for
smartphone and tablet.
� Configuration enabling remote
access through the internet.
� MODBUS TCP/IP communication
device to be plugged in the TAC4
regulation circuit.
� Wireless WIFI to set in network
Titanium units to configure, control
display from one or several access
points.
� Works as Access Point and creates
automatically its own Wi-Fi network
or as base station to an already
existing Wi-Fi network.
TAC4 SAT WIFI
ARTICLE CID
TAC4 SAT WIFI 025071
� Interface with dedicated Apps for
smartphone and tablet.
� Configuration enabling remote
access through the internet.
� MODBUS TCP/IP communication
device to be plugged in the TAC4
regulation circuit.
� Ethernet 10 base T to set in network
Titanium units to configure, control
display from one or several access
points.
TAC4 SAT KNX
ARTICLE CID
TAC4 SAT KNX 025045
� Interface with dedicated Apps for
smartphone and tablet.
� Configuration enabling remote
access through the internet.
FLAT
Flat 33
tac4 regulation system optional moDules
� Remote control box that includes an LCD screen (2x8 charac-
ters), LEDs and 5 control buttons.
� It is used to configure the Titanium unit based on sequential
menus and to visualize all actual parameters.
� It is used to manage 4 time slots and OFF days.
� It can be connected temporarily to set and/or to display the set-
tings, or permanently.
TAC4 RC
� This is a 4.3” colour touch screen.
� It can be mounted exposed (under
housing) or built in.
� It contains a very user-friendly and
intuitive, Windows type menus.
� It is used to configure the Titanium
unit based on sequential menus and
to visualize all actual parameters.
� It is used to manage 6 different time
slots per day, as well as the seasonal
management of the bypass, the
post-heating and post-cooling coil.
TAC4 GRC
ARTICLE CID
Kit GRC TAC4 372002
Exposed assembly kit 372020
Built-in assembly kit 372013
Dedicated Swegon App for tablet and
smartphone featuring:
� Complete control of the unit
� Synoptic view of the unit with actual
airflows, pressures and temperatures
� Basic and advanced setup
� Alarm diagnostic
� Time scheduler with 6 time slots for
each day of the week
� Seasonal management
Application
� The TAC4 control built in the Titanium units can communicate
in MODBUS RTU, which means that the unit can be networked.
A Pc application (to be developed by the user) can then be
used to communicate easily with the units.
� A converter of the COM or USB port to RS485 is needed to be
able to connect to the MODBUS RTU network.
� Each unit has to be equipped with the SAT MODBUS option.
� The gate of creativity is wide open here…
PC
� A GRC can be connected to several
units (247 maximum); provide one
SAT TAC4 MODBUS per unit.
� The RC and GRC cannot be connected
simultaneously on a Titanium unit.
� Automatic detection of the
unit(s) inside the network
for fast and easy access
To obtain the advantages of the
Swegon App you need SAT-Ethernet
or WIFI- extra board on each unit.FLAT
34 Flat
Building management systems (BMS)
The TAC4 control built in the Titanium units can
be connected in network via the communication
option boards.
Their integration into a BMS system is then possible
and very easy.
The building management system can send the
different settings (flow rate, pressure, etc.) and read
all the settings of the Titanium units in real time via
the registers of the communication protocol.
Communication is possible in several ways:
� KNX
� MODBUS
� WIFI
� ETHERNET
tac4 regulation system the user interFace
FLAT
Flat 35
� Remote 4 position switch to start/
stop the unit and control the
setpoint.
COM4
ARTICLE CID
COM 4 010007
� This boards integrates 2 relays
associated to 4 functions: Fan
alarm, Pressure alarm, Water pump
activation if internal postheating
coil is mounted, Bypass status.
� The signaling is carried out by
potential-free contact as well as by
SAT3
ARTICLE CID
SAT 3 370005
an LED placed above each relay.
� It is very simple to install: just plug it
in the TAC4 control board.
� This is a regulation circuit for hot
(water/electric) and/or cold (water)
coils.
� It regulates the external heat
exchangers (BA+ option) to maintain
constant a set temperature. It can
operate in both summer & winter
logic.
TAC SAT BA/KW
ARTICLE CID
SAT TAC4 BA/KW Kit 372004
� It is very simple to install: just plug it
in the TAC4 control circuit.
tac4 regulation system the user interFace
FLAT
Swegon LimitedThe Swegon Pavilion, St Cross ChambersUpper Marsh Lane, HoddesdonHerts, EN11 8LQ
+44 (0) 1992 [email protected]