to test or not to test. that is the (design) question...eurocode 7 approach to pile design zeurocode...
TRANSCRIPT
To test or not to test – that is the (design) question
Dr Andrew Bond (Geocentrix)
Eurocode 7 approach to pile design
Eurocode 7 Part 1 §7 ‘Pile foundations’Emphasizes design based on field testingDesign using ground parameters is presented as an ‘alternative’ (yet is main approach in UK)Base and shaft factors vary with method of installation (bored or CFA or driven)
Design from field test resultsDesign resistance related to number of testsCorrelation factors for static load tests, ground tests (e.g. CPTs), and dynamic impact tests
Design using ground parametersUK National Annex adjusts base, shaft, and model factors according to the amount and type of static load testing
Design using ground parametersTo test or not to test – that is the (design) question
Pile design using ground parameters
Resistance factor
Modelfactor
Combinationfactor
Actionfactor
Pile resistance factors for DA1-2 (from UK NA to BS EN 1997-1)
1.3 1.61.3-1.5
1.31.6/1.45
1.5ENV 1997-1: 1994
Shaft (γs)
Base (γb)
1.3
1.5
Shaft (γs)
Base (γb)
1.4
1.6
1.2
2.0As base
1.72.0Default values
Eurocode
UK National Annex to BS EN 1997-1
?EN 1997-1: 2004
1.4
Model factor (γRd)
DrivenBored/CFA Tens-ion (γst)
Total (γt)
1.71.51.7> 1% constructed piles taken to 1.5 x representative load (or settlement no concern)Maintained load test to calculated unfactored ultimate load
Resistance factors from Set R4Static load tests on piles loaded to…
Case study – piles in sand
Ground test results from site in Richmond (courtesy CL Associates, 2004)
4 CPTs in dense (becoming loose gravelly) SANDDesign of 4 x 6m long piles x φ400mm bored piles
ActionsPermanent Gk = 1400 kN + Variable Qk = 500 kN
4-8m1-4m
38-42(say 40)
Angle of shearing resistance φ (°)
36-38(say 37)
2650(assuming
qb/qc ≈0.2)
qb (kPa)
15
27
21
30
1-4m 4-8m
08
05
03
02
CPT number
(15)
9
15
90(assuming Ks = 2.0)
14
qs (kPa)Average qc(MPa)
Verification of ULS (DA1-2) – with no explicit verification of SLS
, ,
333 6784 1686
1.4 2.0 1.4 1.6
b calc s calcd
Rd b Rd s
R RR
kN
γ γ γ γ= +
× ×
⎛ ⎞= + × =⎜ ⎟× ×⎝ ⎠
2 2
,
0.42650 333
4b calc b b
mR q A kPa kN
π⎛ ⎞×= = × =⎜ ⎟
⎝ ⎠
( ), 90 0.4 6 678s calc s sR q A kPa m m kNπ= = × × × =
( )( )1.0 1400 79 1.3 500 2129
d G G G Q QF V W V
kN
γ γ= × + + ×
= × + + × =
Conventional soil mechanics theory
Model factor
Resistance factors from Set R4
Resistance factors
Action factors from Set A2
Action factors
Fd > Rd → ULS NOT verified!
Reliability of calculated resistance depends on amount of testing
With no static pile load testsFactors on base = 1.4 x 2.0 = 2.8Factors on shaft = 1.4 x 1.6 = 2.24Fd = 2129 kN > Rd = 1686 kN (not verified)
With 1% working static pile load testsFactors on base = 1.4 x 1.7 = 2.38Factors on shaft = 1.4 x 1.4 = 1.96Fd = 2129 kN > Rd = 1943 kN (just not verified)
With preliminary static pile load testFactors on base = 1.2 x 1.7 = 2.04Factors on shaft = 1.2 x 1.4 = 1.68Fd = 2129 kN < Rd = 2267 kN (verified)
Traditional lumped factors of safetyGlobal factor of safety for replacement piles
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0% 20% 40% 60% 80% 100%
Qs/Qult
F =
Qul
t / Q
a
Burland et al.
Tomlinson
Lord (for chalk)
Ignore base
Global factor of safety for replacement piles(with 25% variable action)
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0% 20% 40% 60% 80% 100%
Qs/Qult
F =
Qul
t / Q
a
Eurocode 7 vs traditional
No explicit SLS check
Tests on 1% working piles
Preliminary load tests
Design using field test resultsTo test or not to test – that is the (design) question
Pile design from field test results
Resistance factor
Correlationfactor
Combinationfactor
Actionfactor
Correlation factors from UK NA to BS EN 1997-1
(1.18)(1.32)(8)
1.201.337
For structures that can transfer loads from ‘weak’ to ‘strong’piles, ξ1 to ξ4 may be divided by 1.1 provided ξ1 ≥ 1.0 and ξ3 ≥ 1.0
(1.17)(1.31)(9)
1.151.30≥ 10
Figures in (brackets) provide values ‘missing’ from EN 1997†Values chosen to match static load tests
(1.23)(1.34)(6)
1.661.81≥ 201.261.3651.081.35≥ 5
Min.MeanMin.MeanMin.Mean
≥ 15
≥ 10
≥ 5
≥ 2
No
Dynamic impact tests
1.82
1.83
1.85
1.94
ξ5
1.67
1.70
1.76
1.90
ξ6
4
3
2
1
No
Ground tests
1.38
1.42†
1.47†
1.55†
ξ3
1.29
1.33
1.39
ξ4
1.151.384
1.23
1.35
ξ2
1.423
1.472
1.551
ξ1
No
Static load tests
Case study – piles in sand
Data from site in Richmond (courtesy CL Associates, 2004)4 CPTs in dense (becoming loose gravelly) SANDDesign of 4 x 6m long piles x φ400mm bored pilesActions: Gk = 1400 kN + Qk = 500 kN
TotalBaseShaft
3000
2000
3000
2800
pb(kPa)
754
628
754
754
377
251
377
352
15
27
21
30
1-4m 4-8m
08
05
03
02
CPT number
1131120(15)
8791009
113112015
110612014
Calculated resistance (kN)
ps (kPa)Average qc(MPa)
, ,
1062 879770 681 681
1.38 1.29
calc mean calc mink
mean min
R RR or
or or kN
ξ ξ⎛ ⎞ ⎛ ⎞
= ⎜ ⎟ ⎜ ⎟⎝ ⎠⎝ ⎠
⎛ ⎞ ⎛ ⎞= = =⎜ ⎟ ⎜ ⎟⎝ ⎠ ⎝ ⎠
Verification of ULS (DA1-2)– with 1% working pile load tests
, ,
4 4
251 6294 1851
1.29 1.7 1.29 1.4
b calc s calcd
b s
R RR
kN
ξ γ ξ γ= +
× ×
⎛ ⎞= + × =⎜ ⎟× ×⎝ ⎠
( )( )1.0 1400 79 1.3 500 2129
d G G G Q QF V W V
kN
γ γ= × + + ×
= × + + × =
Correlation factor
Resistance factors from Set R4 (1% working tests)
Resistance factors
Correlation factors for 4 test results
Minimum governs
Fd > Rd → ULS NOT verified!
Action factors from Set A2
ConclusionTo test or not to test – that is the (design) question
Conclusion
“…Much of the design of pile foundations is still dominated by estimation of axial
capacity…where the critical issue is more likely to be magnitude of displacements
under operating conditions…”
Mark Randolph (2003 Rankine Lecture)
‘Decoding the Eurocodes’ blogFor a limited period, you can download this presentation from my ‘Decoding the Eurocodes’ blog
Blog started May 2006Aim to post articles monthly
www.eurocode7.com