trane comercial

152
Refrigeration Specialties By Alco Controls RSP-PRC022-EN April 2003

Upload: martin-bourgon

Post on 03-Mar-2015

1.077 views

Category:

Documents


10 download

DESCRIPTION

Refrigeration Specialty product solution by Alco Controls.Also, fundamentals section on Thermo Expansion Valves, Solenoid Valves, System Protectors, HFC Refrigerants and POE Lubricants, HeadMaster Head Pressure Controls, Hotgas Bypass Valves, Temperature Pressure Controls

TRANSCRIPT

Refrigeration Specialties

By Alco Controls

RSP-PRC022-ENApril 2003

© 2003 American Standard Inc. All rights reserved. RSP-PRC022-EN

3RSP-PRC022-EN

Alpha-Numeric Quick Select Guide

Thermo Expansion Valves

Solenoid Valves

System Protectors

Accumulators

Acid Test Kit

Regulators

Temperature Pressure Controls

Fundamentals of:

Thermo Expansion ValvesSolenoid ValvesSystem ProtectorsHFC Refrigerants and POE LubricantsHeadMaster Head Pressure ControlsHotgas Bypass ValvesTemperature Pressure Controls

Competitive Cross Reference

Sporlan to AlcoDanfoss to AlcoVirginia to AlcoParker to AlcoAC&R to Alco

4

20

47

60

82

85

98

107

54157848691

105

119140143146149

Contents

RSP-PRC022-EN4

Quick Select - Alpha and Numeric by Product

Alpha PageProduct Number

FD113-ZU (K) 115FD113-ZU-S 116

HF 22HFK 24

HP/HPC 103LCL 39

PS1 110PS2 112

RV 53SFD 75

STAS 67

TRAE 29

TRAE+ 28TS1 107

T-SERIES 31100RB 47

200RB 49240RA 51

704RB/RC 54708RA 55

Alpha PageProduct Number

A-AS 82

AA 20AACE 21

AAU 85ADK 61

ADKS 69ALF 65

ALM 81AMI 78

AN 20ASD 74

ASK-HH 77BFK 62

BLOCKS 71BOK 64

BTAS 72COILS 56

CORES 71CPH(E) 100

CSFD 76

CU 66

DGR(E) 99EBF 62

EGR(E) 98EK 60

Quick Select

5RSP-PRC022-EN

Fundamentals of Thermo®

Expansion Valves

ALCO’s thermostatic expansion valvesare designed for a wide range of airconditioning, refrigeration, heat pumpand chiller applications.

ALCO’s integral valve line includesvalves for commercial and refrigerationapplications, as well as heat pump andresidential applications. The “Take-A-PartSeries” valves are the answer to yourunique needs, available for almost anytype of application, temperature range,or any known refrigerant. ALCO alsooffers a complete line of specialty valves.Consult us for your specific systemrequirements.

The Thermo® Expansion Valve is aprecision device designed to regulate therate of refrigerant liquid flow into theevaporator in the exact proportion to therate of evaporation of the refrigerantliquid in the evaporator. The amount ofrefrigerant gas leaving the evaporatorcan be regulated since the Thermo Valveresponds to 1. the temperature of therefrigerant gas leaving the evaporatorand 3. the pressure in the evaporator.This controlled flow prevents the returnof refrigerant liquid to the compressor.The Thermo Expansion Valve (TEV)controls the flow of gas by maintaining apre-determined superheat.

Three forces which govern the TEV’soperation are: 1. the power element andremote bulb pressure, P1; 2. theevaporator pressure, P2; and 3. thesuperheat spring equivalent pressure, P3.See figure 1.

We are here concerned with a singleoutlet type of TEV and shall discuss itunder 2 headings: 1. A valve with aninternal equalizer, and 2. the use of theexternal equalizer feature.

Three conditions present themselves inthe operation of this valve: first, thebalanced forces; second, an increase insuperheat; third, a decrease insuperheat. The remote bulb and powerelement make up a closed system(power assembly), and in thefollowingdiscussion, it is assumed that the remotebulb and power element are chargedwith the same refrigerant as that in thesystem. The remote bulb and powerelement pressure (P1), whichcorresponds to the saturation pressure

Thermo Expansion Valves

of the refrigerant gas temperatureleaving the evaporator, moves the valvepin in the opening direction.

Opposed to this opening force on theunderneath side of the diaphragm andacting in the closing direction are twoforces: 1. the force exerted by theevaporator pressure (P2) and 2. thatexerted by the superheat spring (P3). Inthe first condition, the valve will assumea stable control position when thesethree forces are in balance (see figure 2)that is, when P1= P2 + P3. In the next step,the temperature of the refrigerant gas atthe evaporator outlet (remote bulblocation) increases above the saturationtemperature corresponding to theevaporator pressure as it becomessuperheated. The pressure thusgenerated in the remote bulb, due to thishigher temperature, increases above thecombined pressures of the evaporatorpressure and the superheat spring (P1

greater than P2 + P3) and causes thevalve pin to move in an openingdirection.

Figure 1. Thermo expansion valve withinternal equalizer on evaporator with nopressure drop. Note internal equalizer hole.

Conversely, as the temperature of therefrigerant gas leaving the evaporatordecreases, the pressure in the remotebulb and power assembly alsodecreases and the combined evaporatorand spring pressure cause the valve pinto move in a closing direction (P1 lessthan P2 + P3). For example, when theevaporator is operating with R-22 at atemperature of 40°F or a pressure of 69psig and the refrigerant gas leaving theevaporator at the remote bulb location is50°F, a condition of 10°F superheatexists. Since the remote bulb and powerassembly are charged with the samerefrigerant as that used in the system, R-22, its pressure (P1) will follow itssaturation pressure & temperature

characteristics. With the liquid in theremote bulb at 50°F the pressure insidethe remote bulb and power assemblywill be 85 psig acting in an openingdirection. Beneath the diaphragm andacting in a closing direction are theevaporator pressure (P2) of 69 psig andthe spring pressure (P3) for a 10°Fsuperheat setting of 16 psig (69 + 16 =85) making a total of 85 psig. The valve isin balance, 85 psig above the diaphragmand 85 psig below the diaphragm.Changes in load, increasing thesuperheat, will cause the TEV pin tomove in an opening direction.Conversely, a change, decreasing thesuperheat, will cause the TEV pin tomove in a closing direction (see figure 1).

Figure 2. Thermo valve equilibrium

P1 = P2 + P3

Charge pressure = spring + outletpressures

RSP-PRC022-EN6

TEV’s Factory SettingThe factory superheat settingof Thermo Expansion Valves (TEVs) ismade with the valve pin just starting tomove away from the seat. The superheatincrease necessary to get the pin readyto move is called static superheat. TEVsare so designed that an increase insuperheat of the refrigerant gas leavingthe evaporator, usually 4 to 6°F over andbeyond the factory static superheatsetting, is necessary for the valve pin toopen to its rated position. This additionalsuperheat is known as gradient. Forexample, if the factory static setting is6°F superheat, the operating superheatat the rated stroke or pin position (fullload rating of valve) will be 10 to 14°Fsuperheat (see figure 3). Manufacturersusually furnish the adjustable type TEVswith a factory static superheat setting of6 to 10°F, unless otherwise specified bythe customer.

When using non-adjustable TEVs, it isimportant that they be ordered with thecorrect factory superheat setting. Formanufacturer’s production lines it isrecommended that an adjustable TEV beused in a pilot model lab test todetermine the correct factory settingbefore ordering the non-adjustable typeof Thermo Expansion Valves. If theoperating superheat is raisedunnecessarily high, the evaporatorcapacity decreases, since more of theevaporator surface is required toproduce the superheat necessary tooperate the TEV. It also is obvious thenthat a minimum change of superheat toopen the valve is of vital importancebecause it provides savings in both initialevaporator cost and cost of operation.

The TEV operation discussed thus farpertains to the internal equalizer type ofThermo Valve. The evaporator pressureat the valve outlet is admitted internallyand allowed to exert its force beneaththe diaphragm.

Thermo Expansion Valves

Figure 3. Thermo expansion valve staticsuperheat and gradient

External EqualizerWhen the pressure drop through theevaporator is of any consequence, (i.e.,in general a pressure drop of 3°F in theair conditioning range; 2°F in thecommercial temperature range; and 1°Fin the low temperature range) it will holdthe TEV in a relatively “restricted”position and reduce the system capacity,unless a TEV with an external equalizeris used. The evaporator should bedesigned or selected for the operatingconditions and the TEV selected andapplied accordingly.

For example, an evaporator is fed by aTEV with an internal equalizer, where asizeable pressure drop of 10 psi ispresent (see figure 4). The pressure atpoint “C” is 59 psig or 10 psi lower thanat the valve outlet, point “A”; however,the pressure of 69 psig at point “A” isthe pressure acting on the lower side ofthe diaphragm in a closing direction.With the valve spring set at acompression equivalent to 10°Fsuperheat or a pressure of 16 psig, therequired pressure above the diaphragmto equalize the forces is (69 + 16) or 85psig. This pressure corresponds to asaturation temperature of 50°F. It isevident that the refrigerant temperatureat point “C” must be 50°F if the valve isto be in equilibrium. Since the pressureat this point is only 59 psig and thecorresponding saturation temperature is33°F, a superheat of 17°F (50° – 33°F) isrequired to open the valve. This increasein superheat, from 10 to 17°F makes itnecessary to use more of the evaporatorsurface to produce this highersuperheated refrigerant gas. Therefore,the amount of evaporator surfaceavailable for absorption of latent heat ofvaporization of the refrigerant is reduced;the evaporator is starved before therequired superheat is reached.

Since the pressure drop across theevaporator, which caused this highsuperheat condition, increases with theload because of friction, this “restricting”or “starving” effect is increased whenthe demand on the TEV capacity isgreatest. In order to compensate for anexcessive pressure drop through anevaporator, the TEV must be of theexternal equalizer type, with theequalizer line connected either into theevaporator at a point beyond thegreatest pressure drop or into thesuction line at a point on the compressorside of the remote bulb ocation. Ingeneral and as a rule of thumb, theequalizer line should be connected to thesuction line at the evaporator outlet. Ifthe external equalizer type of TEV isused, with the equalizer line connectedto the suction line, the true evaporatoroutlet pressure is exerted beneath theTEV diaphragm. The operatingpressures on the valve diaphragm arenow free from any effect of the pressuredrop through the evaporator, and theTEV will respond to the superheat of therefrigerant gas leaving the evaporator.

Figure 4. Thermo expansion valve withinternal equalizer on evaporator with 10 psidrop. Note internal equalizer hole.

When the same conditions of pressuredrop exist in a system with a TEV whichhas the external equalizer feature (seefigure 5), the same pressure drop stillexists through the evaporator; however,the pressure under the diaphragm isnow the same as the pressure at the endof the evaporator, point “C”, or 59 psig.The required pressure above thediaphragm for equilibrium is 59 +16 or75 psig. This pressure, 75 psig,corresponds to a saturation temperatureof 44°F and the superheat required isnow 11°F (44° – 33°F). The use of anexternal equalizer has reduced the

7RSP-PRC022-EN

Thermo Expansion Valves

superheat from 17 to 11°F. Thus, thecapacity of a system, having anevaporator with a sizable pressure drop,will be increased by the use of a TEVwith the external equalizer as comparedto the use of an internally equalizedvalve.When the pressure drop through anevaporator is in excess of the limitspreviously defined, or when a refrigerantdistributor is used at the evaporatorinlet, the TEV must have the externalequalizer feature for best performance.

The diagrams used thus far have shownthe single outlet type of TEV. Although amulti-circuit evaporator in itself may nothave an excessive pressure drop, thedevice used to obtain liquid distributionwill introduce a pressure drop that willlimit the action of the TEV withoutexternal equalizer, because thedistributor is installed between the valveoutlet and the evaporator inlet (seefigure 6).

Figure 5. Thermo expansion valve withexternal equalizer on evaporator with 10 psidrop.

Installation Location of ExternalEqualizerAs pointed out earlier, the externalequalizer line must be installed beyondthe point of greatest pressure drop.Since it may be difficult to determine thispoint, as a general rule it is safest toconnect the equalizer line to the suctionline at the evaporator outlet on the com-pressor side of the remote bulb location(see figures 5 and 6). When the externalequalizer is connected to a horizontalline, always make the connection at thetop of the line in order to avoid oillogging in the equalizer line.

Figure 6. Single outlet thermo expansionvalve and distributor.

On a multi-evaporator system includingtwo or more evaporators each fed by aseparate Thermo Expansion Valve (TEV),the external equalizer lines must belocated so that they will be free from theeffect of pressure changes in theevaporators fed by the other TEVs. At notime should the equalizer lines be joinedtogether in one common line to the mainsuction line. If individual suction linesfrom the separate evaporator outlets tothe common suction line are short, theninstall the external equalizer lines intothe separate evaporator suction headers,or as described in the precedingparagraph.

Do not under any circumstances cap orplug the external equalizer connectionon a TEV, as it will not operate. If the TEVis furnished with the external equalizerfeature, the external equalizer line mustbe installed (see figures 5 and 6).

SuperheatA vapor is superheated whenever itstemperature is higher than the saturationtemperature corresponding to itspressure. The amount of the superheatequals the amount of temperatureincrease above the saturationtemperature at the existing pressure.

For example, a refrigeration evaporatoris operating with Refrigerant 22 at 69psig suction pressure (see figure 7). TheRefrigerant 22 saturation temperature at69 psig is 40°F. As long as any liquidexists at this pressure, the refrigeranttemperature will remain 40°F, as itevaporates or boils off in the evaporator.

As the refrigerant moves along in thecoil, the liquid boils off into a vapor,causing the amount of liquid present todecrease. All of the liquid is finallyevaporated at point B because it hasabsorbed sufficient heat from thesurrounding atmosphere to change therefrigerant liquid to a vapor. Therefrigerant gas continues along the coiland remains at the same pressure (69psig); however, its temperature increasesdue to continued absorption of heatfrom the surrounding atmosphere.When the refrigerant gas reaches theend of the evaporator (point C), itstemperature is 50°F. This refrigerant gasis now superheated and the amount ofsuperheat is 10°F (50 – 40). The degree towhich the refrigerant gas is superheateddepends on (1) the amount of refrigerantbeing fed to the evaporator by the TEVand (2) the heat load to which theevaporator is exposed.

Adjustment of SuperheatThe function of a TEV is to control thesuperheat of the suction gas leaving theevaporator in accordance with the valvesetting.

A TEV which is performing this functionwithin reasonable limits can be said tobe operating in a satisfactory manner.

Good superheat control is the criterion ofTEV performance. It is important thatthis function be measured as accuratelyas possible, or in the absence ofaccuracy, to be aware of the magnitudeand direction of whatever error ispresent.

When the pressure drop thru theevaporator is known to be within thelimits defined on page 6, it is permissibleto install the external equalizerconnection at one of the return bendsmidway through the evaporator. Such anequalizer location will provide smoothervalve control particularly when the TEVis used in conjunction with anEvaporator Pressure Regulator. However,in all cases where any type of controlvalve is installed in the suction line, theexternal equalizer line for the TEV mustalways be connected on the evaporatorside of such a control valve or regulator.

RSP-PRC022-EN8

Thermo Expansion Valves

Superheat has been previously definedas the temperature increase of therefrigerant gas above the saturationtemperature at the existing pressure.Based on this definition, the pressureand temperature of the refrigerantsuction gas passing the TEV remote bulbare required for an accuratedetermination of superheat.

Thus, when measuring superheat, therecommended practice is to install acalibrated pressure gauge in a gaugeconnection at the evaporator outlet. Inthe absence of a gauge connection, a teeinstalled in the TEV external equalizerline can be used just as effectively.

A refrigeration type pocket thermometerwith appropriate bulb clamp may beused, or more effective is the use of aservice type potentiometer (electricthermometer) with thermocouples(leads and probes).

Figure 7. Thermo expansion valve withinternal equalizer on evaporator with nopressure drop.

The temperature element from yourTemperature Meter should be clampedto the suction line at the point of remotebulb location and must be insulatedagainst the ambient. Temperatureelements of this type, as well asthermometers, will give an averagereading of suction line and ambient if notinsulated. Assuming an accurate gaugeand Temperature Meter, this method willprovide sufficiently accurate superheatreadings for all practical purposes.

On installations where a gaugeconnection is not available and the valveis internally equalized there are twoalternate methods possible. Both ofthese methods are approximations onlyand their use is definitely notrecommended.

The first of these is the two temperaturemethod, which utilizes the difference intemperature between the evaporatorinlet and outlet as the superheat. Thismethod is in error by the temperatureequivalent of the pressure drop betweenthe two points of temperature.

Where the pressure drop between theevaporator inlet and outlet is 1 psi orless, the two temperature method willyield fairly accurate results. However,evaporator pressure drop is usually anunknown and will vary with the load. Forthis reason, the two temperature methodcannot be relied on for absolutesuperheat readings. It should be notedthat the error in the two temperaturemethod is negative and always indicatesa superheat lower than the actual figure.

The other method commonly used tocheck superheat involves taking thetemperature at the evaporator outlet andutilizing the compressor suctionpressure as the evaporator saturationpressure. The error here is obviously dueto the pressure drop in the suction linebetween the evaporator outlet and thecompressor suction gauge.

On self-contained equipment, thepressure drop and resulting error areusually small. However, on large built-upsystems or systems with long runs ofsuction line, considerable discrepancieswill usually result.

Since estimates of suction line pressuredrop are usually not accurate enough togive a true picture of the superheat, thismethod cannot be relied on for absolutevalues. It should be noted that the errorin this instance will always be positiveand the superheat resulting will behigher than the actual value.

Restating, the only method of checkingsuperheat that will yield an absolutevalue involves a pressure andtemperature reading at the evaporatoroutlet.

Other methods employed will yield afictitious superheat that can provemisleading when used to analyze TEVperformance.

By realizing the limitations of theseapproximate methods and the directionof the error, it is often possible todetermine that the cause of a trouble callis due to the use of improper methods ofinstrumentation rather than anymalfunction of the valve.

One other error that will be presentwhen troubleshooting in mountain areas(such as Denver, Colorado or Salt LakeCity, Utah) is the low gauge pressurecompared to sea level readings. Use aPressure-Temperature chart that hascorrected readings such as ALCO’s 5000foot correction pocket chart.

Factors Involved in Valve SelectionThese design conditions must beavailable: maximum evaporator load;evaporator temperature; maximum andminimum condensing and liquidtemperatures; and refrigerant.

ALCO has prepared extended capacitytables for use with the above mentionedconditions in mind. Specific valveextended capacity tables can be found inthis catalog.

Where possible, always select ThermoExpansion Valves (TEVs) for actualoperating conditions rather thannominal valve capacities.

The conditions from above along withthe following considerations willdetermine if the specific valve hasenough capacity for the evaporatorbeing considered:1. Determine pressure drop across valve,

using both the maximum andminimum condensing pressures,subtract the evaporating pressurefrom each to obtain the total high-to-low side pressure drop. From thesevalues subtract the other possiblepressure losses–piping and heatexchanger losses; pressure drop thruaccessories; vertical lift pressure drop;and the pressure drop across therefrigerant distributor. This last item isvery important to obtain properrefrigerant distribution under alloperating conditions. The exampleprovided at the end of this sectionillustrates all these factors in theselection process.

2. Consider the maximum and minimumliquid temperatures of the refrigerantentering the valve and select thecorrection factors for thosetemperatures from the table below

9RSP-PRC022-EN

Thermo Expansion Valves

the capacity ratings. Determine thecorrected capacity requirement bydividing the maximum evaporatorload in tons by the liquid correctionfactors. These values will allow thefinal selection to be made.

3. Select the valve size from theappropriate capacity table for theevaporator temperature, pressuredrop available, and corrected capacityrequirement. If the valve has lesscapacity than required, contact yourALCO Sales Engineer or Alco Controlsfor assistance.

4. Select the proper thermostatic chargebased on the evaporator temperature,refrigerant, and whether a MOP typecharge is needed.

5. Appropriate connections and whetheran externally equalized model isrequired completes the selection.Always use an externally equalizedvalve when a distributor is used.

Since the capacity and the performanceof the TEV is based on solid liquidentering the valve, careful considerationmust be given to the total pressure dropin the liquid line to determine if therewill be sufficient subcooling of the liquidrefrigerant to prevent the formation offlash gas. If the subcooling of the liquidrefrigerant from the condenser is notadequate, then a heat exchanger, liquidsubcooler, or some other means must beused to obtain enough subcooling of theliquid refrigerant to insure solid liquidentering the TEV at all times.

Thermo Valve ChargesOver the years, or more precisely, sinceALCO produced the first valve forammonia in 1925, the matter of a propercharge in the thermal sensing elementhas been of major concern. Liquidcharges, gas charges, cross liquidcharges, cross vapor charges, hightemperature charges, ultralowtemperature charges, commercialcharges, etc., all have been tried withvarying degrees of success.

M.O.P.Maximum Operating Pressure (or MotorOverload Protection) is the ability of theTEV to close down, starve, or completelyshut off if the suction pressure shouldapproach a dangerously highpredetermined limit condition. Acondition such as to cause overheating a

suction cooled compressor, or loadingthe crankcase with too dense a vaporpressure.

With the TEV in a closed condition dueto MOP, the compressor has a chance togain on the excess low side pressure andpull the suction back down tosatisfactory operating conditions. At thispoint (below the MOP) the TEV will re-open and feed in a standard manner oruntil such time as there is an overloadagain.

Certain bulb charges can be suppliedwith this MOP feature. One of the mostcommon is the “G” (gas) charge. It isalways supplied with “MOP”.

The ALCO “W” charge can be suppliedwith the MOP feature if needed forsystem protection. This need rarelyoccurs in modern day refrigerationexcept such conditions as immediatelyafter defrost or on gasoline drivencompressors such as truck refrigeration.

CAUTION: Any bulb charge with MOPwill be affected by extreme crossambient conditions. If this conditionshould exist, install an electric stripheater around the top part of the TEV.

Power Element ChargesFor many years ALCO used a variety ofbulb charges in their expansion valves.Letters such as L, G, W, C, X, Z, A, Q andothers designated a particular chemicalor mixture of ingredients that gave aspecific curve or line on a graph tomatch a definite pattern of a refrigerantcondition.

In 1978, ALCO introduced a new bulbcharge (BA) to assist the outside coil ofair-to-air heat pumps using R-22 inproviding 0°F superheat, or “wet gas”,back to the windings of hermetic heatpump compressors during very lowoutdoor temperatures.

At 40°F ambients (or higher) this chargeoperates the same as any regular airconditioning bulb charge with a standardsuperheat. In 1983, the charge wasimproved and given the designation CA.

C = +50°F to –20°FZ = +10°F to –50°F

W-(MOP) = MOP to –50°FL = +50°F to –50°F

G-(MOP) = Depends on therefrigerant.Some, such asR-14 to –200°F

CA = Heat pump chargeoutside coil

When G charges, and any other type ofMOP charge (i.e. W-MOP) is used for lowtemperature applications (–40°F andlower) a small heater strip should bewrapped around the head of the TEV. Forspecial applications, other charges maybe used from time to time.

For assistance in selecting a charge withMotor Overload Protection (if requiredby compressor manufacturer) see thetable below and the TEV Charge Selectoron page 9.

Table 1. Maximum dehydration temperature (in °F)

Thermostatic ChargeRefrigerant L C Z G WMOP/CA X

R134a 195 190 250 250 250 N/AR22 160 160 185 250 250 N/A

R404A/R507 150 150 170 250 250 N/AR717 N/A N/A 150 N/A N/A 200

The table above refers to the maximumdehydration temperatures when thebulb and valve body are subjected to thesame temperature. On L, C, Z, and Xcharges, 250°F maximum valve bodytemperature is permissible (if the bulbtemperature) does not exceed thoseshown in the table.

RSP-PRC022-EN10

Thermo Expansion Valves

TEV Charges: What they do,and How they do it

The basic function of a thermalexpansion valve (TEV) is to controlsuperheat. But there are several types ofTEVs, and several types of charges inthem. Each has its own specific use;understanding the power elementcharge and how it affects the pressure tothe power diaphragm is basic to goodvalve service.

There are several basic types of chargesin use today. Most common are the:liquid charge; gas charge; liquid cross-charge; gas cross-charge; and theadsorption charge.

Liquid ChargesThe power element contains the samerefrigerant as the system in which thevalve is used. When manufactured, it isput into the remote bulb in a liquid state.Volume is controlled so that within thedesign temperature range of the powerelement, some liquid always remains inthe bulb. Therefore, power elementpressure is always the saturationpressure corresponding to thetemperature of the remote bulb.

Liquid charges have both advantagesand disadvantages. They include: notsubject to cross-ambient control loss;little or no superheat at start-up;superheat increases at lower evaporatortemperatures; and slow suction pressurepulldown after start-up.

Liquid Cross-ChargesThe power element contains a liquidrefrigerant different from the systemrefrigerant in which the valve is used.The pressure temperature curve of thecharge crosses the curve of the systemrefrigerant (hence, cross-charge).

Among the liquid cross-chargeadvantages are:• Moderately slow pull down.• Insensitive to cross-ambient

conditions.• Dampened response to suction line

temperature changes (minimizestendency for valve “hunting”).

• Superheat characteristics can betailored for special applications.

NOTE: ALCO charges “C” and “Z” areliquid cross-charges.

Gas & Gas Cross-ChargesUsing a gas charge in place of a liquidalters the operational characteristics,because gas compresses. At somepredetermined temperature, the gas inthe remote bulb becomes superheated,limiting the force it exerts. This produceshigher superheats at higher evaporatorpressures and is labelled the MaximumOperating Pressure (MOP) effect.

Any MOP point temperature depends onhow that bulb was initially charged andwhere it will be used. All gas charges aresusceptible to cross-ambient control losswhen the power element is colder thanthe remote bulb. They are inherentlyfaster to respond, but tend to “hunt” forthe proper operating level — so a ballastis often added to the remote bulb tominimize that tendency.

As in liquid charges, the remote bulb canbe filled with the same refrigerant as thesystem refrigerant (producing a gascharge). Or, it can be filled with adifferent refrigerant, producing a gascross-charge.

Which Charge to Use?To help you match the correct charge toyour specific application, see the TEVCharge Code Selector on the next page.Also provided here are some typicalexamples of applications by refrigerantcharge.

Liquid Charge – LIce makers, pilots, liquid injection valves

Liquid Cross-Charges – C, ZCommercial refrigeration (low &medium temp.), ice makers, transportrefrigeration and air conditioning

Gas Charge – GAir conditioning (including mobile),water chillers

Gas Cross-Charge – CAHeat pumps and air conditioning

Gas Cross-Charge – HAAHeat pumps and air conditioning

W(MOP)Maximum Operating Pressure

Refrigerant Code Names

ARI Standard 750-81 recommends the following color coding of thermostaticexpansion valves: R-12 White; R-22 Green; R-502 Orchid; R-40 Red; R-500 Orange.

Uncommon refrigerants with no designated color should use Blue.ASHRAE Trade or Alco Code Alco CodeRef. No. Chemical Name Color Letter

R-12 Dichlorodifluoromethane white FR-22 Chlorodifluoromethane Green HR-502 22/115 Purple RR-134a Tetrafluoroethane Blue MR-404A 125/134a/143A Light Orange SR-401A 22/152A/124 Coral XR-507 125/143A Teal P

11RSP-PRC022-EN

Thermo Expansion Valve Charge Code Selector

Thermo Expansion Valves

Applications Operating Ranges

R12/R134aDomestic refrigerators

and freezersIce Makers

DehumidifiersTransport refrigerationMedium temperature

supermarketequipment

Medium temperaturecommercial equipment

R22Residential airconditioners &

heat pumpsCommercial andindustrial chillers

Medium temperaturesupermarketequipment

Commercial airhandlers

R502/R404A/R507Low temperature

freezers &display cases

Ice MakersCommercial air

conditionersSoft ice cream

machinesEnvironmental

chambers

FC/MC

FZ/MZ

FW 5/MW 15 (MOP)

FW 35/MW 35 (MOP)

MW 55

HCA Air Cond. & Heat Pump

HAA Air Cond. & Heat Pump

HW 100

HC

HW 35 (MOP)

HW 65 (MOP)

HZ

RC/SC/PC

RZ/SZ/PZ

RW 45/SW 45/PW 45 (MOP)

RW 65/SW 65/PW 65 (MOP)

-50 -40 -30 -20 -10 0 +10 +20 +30 +40 +50

RSP-PRC022-EN12

TEV Replacement Charge Symbols Cross ReferenceOld Bulb Charges vs. New Replacement Bulb Charge

Air Conditioning Commercial Refrigeration Low TemperatureOld Charge Replacement Old Charge Replacement Old Charge Replacement

Refrigerant R12/R134aF or FL — —

FC FC —FW FW FWZ

FG55 FC FG35 — —FW55 FW35 FW35 FW15FQ55 FQ35 FW15FGAFLA — —FGS FGS35 FGS35

FWS FWS FWSFWS FWS FWS FZ/MZ FZ/MZ

FX FXRefrigerant R22

H or HL — —HC HC —

HW HCA HW HWZHG100 HG65 — —HW100 HW65 HW65 HW35HQ100 HC HQ65 HQ35HGAHLA — —

HW85 HW85 — —HGS HGS65 HGS65

HWS HWSHWS HWS HWS HWS HZ HZ

HX HXRefrigerant R502/R404A/R507

RL — —RW RC/SC/PC RW RWZ RZ

RW110 RW65 RW65 RW35 RW45/SW45RWS RWS

RWS RWS RWS RWS RZ RZ/SZ/PZ

Thermo Expansion Valves

FC

FWS

HC

HWS

HC

RC/SC/PC

FC

FW35

FZ

—— —

FW15/MW15

HZ

— —

RC/SC/PC

HWS

HC

HW65

— —

HWS

Note: All other charge symbols must be replaced with an identical model or at the option of the Alco technical service department who may make engineering authorized substitutionof equivalent type to provide equivalent operation and performance.Note: For field replacement purposes, hc can be used to replace hca.

13RSP-PRC022-EN

Thermo Expansion Valves

Thermo Valve ApplicationIn general, for best evaporatorperformance, the Thermo ExpansionValve (TEV) should be applied as close tothe evaporator as possible and in such alocation as to make it easily accessiblefor adjustment and servicing. Onpressure drop and centrifugal typedistributors, apply the valve as close tothe distributor as possible. (See figure 8.)

Figure 8. Thermo expansion valve andpressure drop type distributor feeding anevaporator.

All expansion valves [with the exceptionof the W-(MOP), G-(MOP), or GS-(MOP)gas charged types] may be installed inany location in the system. The gascharged type must always be installed insuch a manner that the power assemblywill be warmer than the remote bulb.The remote bulb tubing must not beallowed to touch a surface colder thanthe remote bulb location. If the powerassembly or remote bulb tubingbecomes colder than the remote bulb,the vapor change will condense at thecoldest point and the remote bulb willlose control.

Remote Bulb Location

Strap-on Type Remote BulbSince evaporator performance dependslargely upon good TEV control, andgood valve control depends uponresponse to temperature change of therefrigerant gas leaving the evaporator,considerable care must be given to typesof remote bulbs and their locations. Ingeneral, the external remote bulb meetsthe requirements of most installations. Itshould be clamped to the suction linenear the evaporator outlet, and on ahorizontal run. If more than one TEV isused on adjacent evaporators orevaporator sections, make sure that theremote bulb of each valve is applied tothe suction line of the evaporator fed bythat valve.

Clean the suction line thoroughly beforeclamping the remote bulb in place.When a steel suction line is used, it isadvisable to paint the line withaluminum paint to minimize futurecorrosion and faulty remote bulb contactwith the line. On lines over 7/8" OD theremote bulb should be installed at theposition of about 4 or 8 o’clock. Seefigure 9.

If it is necessary to protect the remotebulb from the effect of an air stream,after it is clamped to the line, usematerial that will not absorb water withevaporator temperatures above 32°F.Below 32°F, cork or similar materialsealed against moisture is suggested toprevent ice logging at the remote bulblocation. The use of hair felt is notrecommended. When the remote bulblocation is below the water or brine levelof a submerged coil, use a waterproofingmaterial or pitch, that does not requireheating above 120°F in applying it, toprotect the remote bulb tubing andremote bulb.

Remote Bulb WellWhen it becomes desirable to increasethe sensitivity of the remote bulb to achange in the refrigerant gastemperature leaving the evaporator, itmay be necessary to use a remote bulbwell. This is particularly true for shortcoupled installations and installationswith large suction lines (2-1/8" OD orlarger). Remote bulb wells should beused (1) when very low super-heats aredesired and (2) where convected heatfrom a warm room can influence theremote bulb (see figure 10).

Do not under any circumstances locateeither type of remote bulb in a locationwhere the suction line is trapped (seefigure 11). If the liquid refrigerantcollects at the point of remote bulblocation, the TEV operation will be erraticand possibly the valve thought to bedefective. Large fluctuations in superheatin the suction gas are usually the resultof trapped liquid at the remote bulblocation. Even on properly designedsuction lines, it is sometimes necessaryto move the remote bulb a few incheseither way from the original location toobtain best valve action. Always locatethe remote bulb on the evaporator sideof any heat exchanger.

On multi-circuit evaporators fed by onevalve, locate the remote bulb away fromimmediate suction outlet at point wherethe suction gas from the several parallelcircuits has had an opportunity to mix inthe suction header.

Be sure to pull up tight on clamps so thatthe remote bulb makes good contactwith the suction line. Never apply heatnear the remote bulb location withoutfirst removing the remote bulb.

Figure 10.

Figure 9.

RSP-PRC022-EN14

Thermo Expansion Valves

Thermo Valve Hunting“Hunting” of the Thermo ExpansionValve can be defined as the alternateoverfeeding and starving of therefrigerant flow to the evaporator. It isrecognized by extreme cyclic changes inboth the superheat or the refrigerant gasleaving the evaporator and theevaporator or suction pressure.

“Hunting” is a function of the evaporatordesign, length and diameter of tubing ineach circuit, load per circuit, refrigerantvelocity in each circuit, temperaturedifference under which the evaporator isoperated, arrangement of suction pipingand application of the TEV remote bulb.

“Hunting” can be minimized oreliminated by the correct rearrangementof the suction piping, relocation of theremote bulb and use of therecommended remote bulb and powerassembly charge for the ThermoExpansion Valve.

Operation at Reduced CapacityThe conventional TEV is a self-contained,direct operated regulator which does nothave any built-in anticipating orcompensating factors. Therefore, theTEV is susceptible to “hunting” forcauses which are peculiar to both valvedesign and the design of the systems towhich it is applied.

The ideal TEV flow rate would require avalve with perfect dynamic balance,capable of instantaneous response toany change in the rate of evaporation(anticipation) and with a means ofpreventing the valve from overshootingthe control point due to inertia(compensation). With these features theTEV would be in phase with the systemdemand at all times and “hunting”would not occur.

A conventional TEV does not have built-in anticipating or compensating factors.This means that a time lag will existbetween demand and response, alongwith the tendency to overshoot thecontrol point. Thus the conventional TEVmay get out of phase with the systemand “hunt”.

Figure 11.

Assume that an increase in load occurs,causing the superheat of the suction gasto increase. The time interval betweenthe instant the remote bulb senses theincreased superheat and causes thevalve pin to move in the openingdirection, allows the superheat of the gasto increase still further.

In response to the rising superheatduring the time lags, the valve hasmoved further in the opening direction,overshot the control point and admittedmore refrigerant to the evaporator thancan be boiled off by the load. During thetime lag between the instant the remotebulb senses the returning liquidrefrigerant and the valve responds bymoving in the closing direction, the valvecontinues to overfeed the coil. Thus,when the valve does move in the closingdirection, it will again overshoot thecontrol point and remain in an overlythrottled position until most of the liquidrefrigerant has left the evaporator. Theensuing time delay before the valvemoves in the opening direction allowsthe superheat of the suction gas to againrise beyond the control point. This cycle,being self-propagating, continues torepeat itself.

Experience has shown that a TEV ismore liable to “hunt” at low loadconditions when the valve pin is close tothe valve seat. This is generally thoughtto be due to an unbalance between theforces which operate the valve.

In addition to the three main forces thatoperate a TEV, the pressure differenceacross the valve port acts against theport area, and depending on valveconstruction, tends to force the valveeither open or closed. When operatingwith the pin close to the seat, thefollowing will occur.

With the valve closed, we have liquidpressure on the inlet side of the pin andevaporator pressure on the outlet. Whenthe valve starts to open allowing flow totake place, the velocity through the valvethroat will cause a point of lowerpressure at the throat, increasing thepressure difference across the pin andseat. This sudden increase in pressuredifferential acting on the port area willtend to force the valve pin back into theseat. When the valve again opens, thesame type of action occurs and the pinbounces off the seat with a rapidfrequency.

This type of phenomenon is morefrequently encountered with the largersingle ported TEVs as the force due tothe pressure differential is magnified bythe larger port area.

We have seen that a TEV may “hunt”due to lack of anticipating andcompensating features and anunbalance in the equilibrium forces atthe lower end of its stroke.

We know from experience that a TEVwhen intelligently selected and applied,will overcome these factors and operatewith virtually no “hunt” over a fairlywide load range.

Single ported TEVs will generallyoperate satisfactory to somewhat below50% of nominal capacity but this is againdependent on evaporator design,refrigerant piping, size and length ofevaporator circuits, load per circuits,refrigerant velocity, air flow over theevaporator, and rapid changes inloading.

Nothing will cause a TEV to “hunt”quicker than unequal feeding of theparallel circuits by the distributor orunequal air loading across theevaporator circuits.

15RSP-PRC022-EN

Thermo Expansion Valves

Balanced Port Thermo Valve OperationIn conventional expansion valves, as thepressure drop across the valve portchanges due to changes in headpressure and/or suction pressure; theoperating superheat of the expansionvalve varies due to this “unbalance”.

Depending on the operating conditionsunder which the superheat wasoriginally set, this “unbalance” can insome situations result in compressorflooding or evaporator starvation. Anunique design concept called “BalancedPort” cancels the effect of this pressureunbalance, permitting the expansionvalve to operate at a relatively constantsuperheat over a wide range ofoperating conditions.

Any refrigeration system whichexperiences changes in operatingpressures due to varying ambients, gasdefrost, heat reclaim, or swings inevaporator load will benefit from usingALCO’s Super HF Balanced Port ThermoExpansion Valve.

Double Ported Balanced Ported TEVsThe flow pattern of the single ported TEVcan cause difficulties at low loadconditions. The larger the port area(larger tonnages) the more prone is thevalve to “hunt”. Certain type ALCOThermo Valves have been designed withtwo ports or “double ported”. The inletis so designed as to create a“counterflow” against the double portedbalance ported valves and thus eliminateany unbalance across the two ports. Seefigure 13.

Flow through the upper port enters theupper radial holes of the cage seatassembly, moves upward and across theupper seat, down through the internalpassage of the spool and out the holes inthe bottom of the spool. The pressuredrop across this port exerts a force in aclosing (upward) direction.

Flow through the bottom port enters thelower radial holes of the cage seatassembly and moves downwardthrough the port formed by the cage seatand the valve spool. High pressure liquidacts downward on the spool and thepressure drop across the spool and seatexerts a force in an opening direction.

Since the effective port area of both theupper and lower cage ports is verynearly the same, the net forceunbalanced across them is negligible.

Figure 12. Cutaway view of Alco’s super HFbalanced port and thermo expansion valve.

This feature makes it possible for thenew double ported cage assemblies tomodulate over a much wider load rangethan was possible with the old style,single port valves. The reverse-flowvalves provide satisfactory control atloads less than 15% of nominal valvecapacity. Their performance is superiorto any competitive product available.Actual field performance has proven thesuperiority of double ported ALCOThermo Valves and their ability to reduce“hunting” to a very minimum.

Figure 13.

Bleed Holes for System PressureEqualizationWhen a permanent split-capacitor motoris used to drive a refrigerationcompressor, it is necessary to providesome means of equalizing the high andlow side pressures during the “off” cycleso that the motor can start withminimum torque.

Note: An external equalizer feature onTEVs does not perform this function; aseparate internal bleed hole is required.

The letter “B” is used after the valveseries number to denote a valve withbleed hole construction. For example:TCLEBHC. The body flange is stampedwith the letter “B” followed by the bleedhole diameter, for example: B036. Seefigure 14.

The required bleed hole size for aparticular system is a function of thehigh side and low side volumes, thepressure difference across the valve attime of shut-down, the equalization timerequired and quantity of refrigerantcharge. Due to the many variables, eachapplication must be tested to determinethe correct size required. It should beremembered that bleed hole size adds tothe total effective port area of the TEVand may affect size selection. Finalselection of bleed hole size should bemade ONLY after thorough testing.

RSP-PRC022-EN16

Thermo Expansion Valves

Ammonia Expansion ValveThe same Take-A-Part construction anddesign principles found in ALCO ThermoValves for the common halocarbonrefrigerants are also found in the ALCOTG line of Ammonia Thermo Valves.

Except for a built-in Y-type strainer andbody construction of high grade steelalloy, the approach to application ofammonia TEVs is the same as the brasshalocarbon TEVs.

The internal cage construction of the TGammonia expansion valve is the sameas its brass counterpart, except in someinstances a small discharge tube ororifice is used for the refrigerant outlet ofthe cage.

The function of this discharge tube is toprovide a secondary restriction toprovide more accurate tonnagerequirements, and to slow down thevelocity of the liquid ammonia acrossthe primary orifice.

Figure 14. Bleed hole for sysem equalization.

** Bleed hole size stamped on body here

Any vapor present (flash gas) in theliquid line will cause the ammonia toenter the primary orifice at exceptionallyhigh velocities thereby causing erosionof the pin and seat. The discharge tubeor secondary orifice helps to reduce thisvelocity and increase the life of the pinand seat.

CAUTION: Should an ALCO TGammonia Thermo Valve be used on anevaporator with a refrigerant distributoremploying an orifice plate, the dischargetube in the cage must be removed priorto installation.

The combination of the discharge tubeand distributor orifice plate will createtoo much pressure drop and a starvingcondition will probably be noted.

Solder Bodies Take-A-Part Style ThermoValvesWhen soldering, remove powerassembly, cage assembly, and allgaskets. Keep heat away from all valveparts, except body flange. Use a brazingalloy or low temperature solder. Becareful to retain all the solder in theconnection. For integral (one-piece) bodytypes, be sure to use plenty of wet ragsor chill blocks and direct the flame awayfrom the valve body.

For external adjustment of ALCO Take-A-Part Valves–Types TCL, TJL, TJR, TER,TIR and THR: To adjust, remove seal capon side of valve and turn adjusting stem.Turning stem to right decreases flow andraises superheat. Turning stem to leftincreases flow and lowers superheat.Adjust all “T” series 2 turns (1°F) at atime.

Adjust each valve separately and waitbetween each adjustment to observe allresults. Always tighten any loosenedconnections and replace seal cap.

It should be noted that superheatadjustment of “W–MOP”, “G”, and“GS” charged valves will change theMOP point. An increase in superheatsetting will lower the MOP point and adecrease in superheat setting will raisethe MOP.

Direction of FlowAlways be sure the flow of refrigerant isin the direction indicated by the arrow onthe valve body.

Installation and ServiceALCO “T” Series Thermo Valves havethree component parts: the powerassembly, cage assembly, and bodyflange. There are no working parts in thebody flange. It is never necessary tobreak the line connections to service thevalve.

ALCO types HF, AFA and other hermeticintegral Thermo Valves are assembledunits which cannot be taken apart in thefield, except that the strainer may beeasily removed for inspection andcleaning by disconnecting the valve fromthe liquid line and removing the inletflare connection.

Servicing

����� WARNING

Before opening any system forservicing, use EPA approved methods tobring the system to atmosphericpressure. Failure to comply may result insystem damage and/or personal injury.

To inspect, clean, or replace parts on allTake-A-Part Valves, remove the two capscrews—lift off the power assembly—and remove cage assembly. Be suregaskets are replaced in proper placeswhen reassembling valve (see figure 15).When assembling external adjustmentvalves (TCL, TJL, TER, TIR, or THR) besure the two lugs on the cage assemblyfit into the grooves provided for them inthe power assembly (see figure 16).Don’t force valve together—make thecage fit properly before tightening bodyflange.

Solenoid Liquid Stop ValvesThe TEV, while produced as a tightseating device, cannot be depended onfor positive shut-off since the seatingsurfaces are exposed to dirt, moisture,corrosion, and erosion. In addition, if theremote bulb is installed in a locationwhere during the “off” cycle it isinfluenced by a higher ambienttemperature than the evaporator, thevalve will open during a portion of the“off” cycle, and admit liquid to theevaporator. For these reasons theinstallation of a Solenoid Liquid StopValve ahead of any Thermo ExpansionValve (TEV) is highly recommended.

17RSP-PRC022-EN

Thermo Expansion Valves

Filter-Driers for System ProtectionTo protect the precision working parts ofcontrol valves from dirt and chips whichcan damage them and render theminoperative, and to protect the entiresystem from the damaging effects ofmoisture, sludge and acids a filter-driershould be installed on every system.

The ALCO Liquid Line Filter-Drierprovides the finest possible protectionavailable with superior filtering actionand the removal of moisture, sludges,corrosive acids and waxes.

Figure 15.

Figure 16.

Factory Superheat SettingUnless otherwise specified, all valves willbe preset at the factory at a bathtemperature which is predetermined bythe charge symbol and/or the MOPrating.

The bath temperature at which the valvesuperheat has been set is codedalphabetically in the superheat block onthe valve nameplate, as shown in thetable below.

Bath CodeTemperature Letter

+32°F A+10°F B0°F C

–10°F D–20°F E

Thus a valve with “10A” stamped in thenameplate superheat block has been setfor 10°F static superheat with a 32°Fbath. In like manner, a valve stamped“10C” has been set for 10°F staticsuperheat with a 0°F bath.

When ordering a valve for an exactreplacement, specify the code letter aswell as the superheat setting desired.When ordering for general stock, it willnot be necessary to specify either thesuperheat or the code letter, since thestandard setting will cover mostapplications and minor superheatadjustments may be made in the field.

Pressure Switch SettingOn valves with MOP—the PressureSwitch must be set to cut in at a pressurelower than the MOP rating of the valve.

RSP-PRC022-EN18

Thermo Expansion Valves

Selection of Thermo®

Expansion Valves

Expansion Valve SelectionThe following conditions must be knownto correctly size an expansion valve:1) Refrigerant type2) Evaporator Temperature3) Evaporator Capacity4) Condensing Temperature/Pressure5) Liquid Temperature6) Distributor type (if used)

NOTE: The valve is sized to theevaporator and not the compressor.

Refrigerant TypeA valve’s capacity will change fordifferent refrigerants.

Evaporator TemperatureAs the evaporator temperature changesthe valve capacity will also change. Asthe evaporator temperature drops, thevalve capacity will decrease, and as thetemperature increases, so does the valvecapacity.

Evaporator CapacityThe valve is sized to the evaporatorcapacity since it is the evaporatorsuperheat that the valve controls.

Condensing TemperatureWhat we really want here is the highside pressure. The condensing pressurealong with the evaporator pressure willgive us the pressure drop (Delta P)across the valve.

Liquid TemperatureThe valve capacity is directly related tothe liquid temperature.

Distributor TypeWe need to know this to determine if weneed an external or internal equalizer forthe valve. We also need the type tocalculate the pressure drop across thevalve. The higher the pressure drop, thehigher the capacity of the valve.

NOTE: The valve is sized to theevaporator and not the compressor.

NOTE: There is no mention here aboutline sizes. They are selected last, after thecorrect sized valve has been selected.

• Pressure drop across the valve isdetermined by the difference betweenthe inlet pressure and the outletpressure of the valve.

• If the condensing pressure is notknown, it can be found by using theabove temperatures and converting topressures using a P/T chart.

• Along with the distributor pressuredrop, the line losses and any other highside pressure losses should besubtracted from the condensingpressure to get the valve inlet pressure.

• If only the evaporator temperature isknown then a P/T chart is used to findthe pressure.

• Always select thermostatic expansionvalves for actual operating conditionsrather than nominal valve capacities.

Net Pressure Drop Across the Valve

Condensing PressureMedium Temp. = 110°F, orLow Temp. = 105°F, orAir Conditioning = 120°F

– Distributor Pressure DropOrifice Type = 35 psi, orVenturi Type = 15 psi

– Evaporator Pressure

= Net Pressure Drop

19RSP-PRC022-EN

Thermo Expansion Valves

Our first step toward sizing the TXV willbe to calculate the pressure drop acrossthe valve. The diagram at right will helpus to visualize how the pressure drop iscalculated.

Our condensing temperature is 271 psigand since we have no high side losses,the pressure at the inlet of the valve is271 psig.

The low side is a little different, we havean evaporator pressure of 55.6 psig andnow we have a 35 psi drop across thedistributor, which means that thepressure at the outlet of the valve is 35psi greater than the evaporator pressure.The pressure at the outlet of the valve isthe sum of the distributor pressure dropplus the evaporator pressure, or 90.6 psi(35 + 55.6).

The pressure drop across the valve is thedifference between the valve inlet andthe valve outlet or in this case 180.4 psi(271 – 90.6).

TXV Pressure Drop Calculation with distributor

CondensingTemperature = 110°F

271 psig

271 psig

EvaporatorTemp. = +20°F

Conditions• R-404A• Orifice Distributor = 35 psi• Evaporator = +20°F• Condensing Temp = 110°

55.6 + 35 = 90.6 psi

Pressure Drop Across TXV271 – 90.6 = 180.4 psi

55.6 psig

RSP-PRC022-EN20

Thermo Expansion Valves

A-Series Thermo® Expansion Valve

“A” Series Thermo Expansion Valvesare used for heat pump, air conditioning,food service and commercialapplications.“A” Series valves provide stable andaccurate control over a wide range ofoperating conditions.

Features• Hermetic construction eliminates

external leakage• Compact size allows installation in

limited spaces• Mass spectrometer tested to ensure

less than 0.10 oz/yearexternal leakage rate

• Stainless steel power elementeliminates corrosion andprevents valve failure

Options• HAA wide range charge allows two

valves ( 2 1/2 and 5 ton, R-22) to coverall capacities from 1 to 5 tons onmost residential systems (see below)

• New ZW155 charge available for R-410A systems

• Available adjustable or non-adjustablesuperheat for application flexibility

• SAE or ODF connections standard –chatleff or aeroquip are available

• Available external or internal equalizerto satisfy the broadest possible rangeof applications

• Available internal check valve allowsreverse flow heat pump applications,eliminating the need for external pipingand external check valve, thus reducinginstallation costs (ANC Series)

• Bleed type pressure equalizationavailable to accommodate PSC typecompressors

• Pressure limiting charges (MOP)available – consult factory

SpecificationsMaximum working pressure: 600 psig

Nomenclature example: AACEB 2 HC 30 IN 3/8 X 1/2 ODF ANG

A A C E B 2 H C 30 IN 3/8 x 1/2 ODF ANGVVVVValvealvealvealvealve Superheat AdjustmentSuperheat AdjustmentSuperheat AdjustmentSuperheat AdjustmentSuperheat Adjustment InternalInternalInternalInternalInternal EqualizerEqualizerEqualizerEqualizerEqualizer Bleed HoleBleed HoleBleed HoleBleed HoleBleed Hole CapacityCapacityCapacityCapacityCapacity RefrigerantRefrigerantRefrigerantRefrigerantRefrigerant ChargeChargeChargeChargeCharge CapillaryCapillaryCapillaryCapillaryCapillary Inlet x OutletInlet x OutletInlet x OutletInlet x OutletInlet x Outlet ConnectionConnectionConnectionConnectionConnection Config-Config-Config-Config-Config-SeriesSeriesSeriesSeriesSeries CheckCheckCheckCheckCheck (optional) Nominal Rating CodeCodeCodeCodeCode CodeCodeCodeCodeCode TTTTTubeubeubeubeube ConnectionConnectionConnectionConnectionConnection TTTTTypeypeypeypeype urationurationurationurationuration

Economy, A = Adjustable VVVVValvealvealvealvealve E=External in Tons F = R12 LengthLengthLengthLengthLength SizesSizesSizesSizesSizes SAE =Hermetic (optional) Omit for H = R22 C = medium temp I O flare S/T =Design N = Non-Adjustable Reverse (Omit for no bleed See nominal M = R134a CA = heat pump 30 IN (std) 1/4 3/8 ODF = straight-

Flow Internal) hole capacity N = R407C W(MOP)=press. limiting other 3/8 1/2 solder thruBypass table P = R507 Z = low temp lengths are 1/2 5/8 Chatleff

Application below R = R502 AA = wide range available 5/8 7/8 (optional) ANG =S = R404A Aeroquip 90°Z = R410A (optional) angle

21RSP-PRC022-EN

Valve Capacity ServiceFirst CapSeries Tons Connections Part Number TubeAAEB 1 3/8" x 1/2" ODF S/T VAL02368 5’ Cap

1 1/2 3/8" x 1/2" ODF S/T VAL02369 5’ Cap2 3/8" x 1/2" ODF S/T VAL02370 5’ Cap

2 1/2 3/8" x 1/2" ODF S/T VAL02371 5’ Cap2 1/2 3/8" x 1/2" ODF S/T VAL00889 30" Cap

3 3/8" x 1/2" ODF S/T VAL02372 5’ Cap3 3/8" x 5/8" ODF S/T VAL00891 30" Cap4 3/8" x 1/2" ODF S/T VAL02373 5’ Cap4 3/8" x 5/8" ODF S/T VAL02374 5’ Cap4 1/2" x 7/8" ODF S/T VAL02375 5’ Cap5 3/8" x 1/2" ODF S/T VAL02376 5’ Cap5 1/2" x 5/8" ODF S/T VAL02377 5’ Cap5 1/2" x 7/8" ODF S/T VAL02378 5’ Cap

Thermo Expansion Valves

Ordering Information for A-Series Valves (15% Bleed), HCA Charge

Universal Replacement

HAA Wide Range Charge for HVACApplications• The AACE wide range valve allowsseveral TXV to replace the majority ofresidential air conditioning and heatpump applications.

• The new HAA charge is a special highstability charge designed for R-22 HVACapplications and is used by leadingoriginal equipment manufacturers.

• The HAA is a wide range chargeproviding greater superheat stability,allowing in most cases two valves tocover a wide range of capacities from 1to 5 tons.

Table 1

ServiceFirst R-22 CapacityPart Number Description Range

VAL07065 AACE 2 1/2 HAA ODF EE 30” 3/8 x 1/2 ODF S/T 6A 1 to 3 TonsVAL07066 AACE 5 HAA ODF EE 30” 3/8 x 1/2 ODF S/T 6A 3 1/2 to 5 TonsVAL07067 AACE 2 1/2 HAA Cap Tube EE w/Nut

30” Chatleff x Chatleff S/T 6A 1 to 3 TonsVAL07068 AACE 5 HAA Cap Tube EE w/Nut

30” Chatleff x Chatleff S/T 6A 3 1/2 to 5 Tons

• The HAA charge also offers customersthe benefit of inventory reduction byreplacing several valves with two HAAwide range valves, while continuing tomeet system performance needs.

• The HAA charge is now available for“A” series expansion valves for R-22applications. With the addition of anintegral check valve, four expansionvalves can meet the majority ofresidential HVAC, light commercial andheat pump applications as shown inTable 1.

RSP-PRC022-EN22

Thermo Expansion Valves

HF Balanced Port Thermo® Expansion Valve

Features• Large, removable power element• Balanced port construction

compensates for changes in operatingpressures due to varying ambients, gasdefrost, heat reclaim, or widely varyingevaporator loads

• Two body sizes provide capacities from1/4 to 20 tons

• Bi-Flow capability up to 5-1/2 tons R22allows one valve to control thesuperheat in both cooling and heatingmodes for package unit heat pumpapplications

• Wrench flats on inlets and outlets (SAEonly) for easy installation

• Stainless steel power element formaximum corrosion resistance

Options• Bleed type pressure equalizationavailable to accomodate PSC typecompressors

• ODF or SAE connections• Removable strainer• Adjustable or non-adjustable superheat

Specifications• Maximum Working Pressure: 450 psig• Operating Temperature: -40°F to 50°F• 5' capillary tube length (standard)• Use with R-22, R134a, R-404A, R-507, R-12, R-502

For Ordering Information, see page 23.

Replacement Screen KitKIT04955

HFESC

ODF Connections

Nomenclature example: HFNESCB 2 HC 5 FT 3/8 X 1/2 ODF S/THF N E S C B 2 H C 5 FT 3/8 x 1/2 ODF S/T

VVVVValvealvealvealvealve SuperheatSuperheatSuperheatSuperheatSuperheat EqualizerEqualizerEqualizerEqualizerEqualizer ConnectionConnectionConnectionConnectionConnection RemovableRemovableRemovableRemovableRemovable Bleed HoleBleed HoleBleed HoleBleed HoleBleed Hole CapacityCapacityCapacityCapacityCapacity RefrigerantRefrigerantRefrigerantRefrigerantRefrigerant ChargeChargeChargeChargeCharge CapillaryCapillaryCapillaryCapillaryCapillary Inlet x OutletInlet x OutletInlet x OutletInlet x OutletInlet x Outlet ConnectionConnectionConnectionConnectionConnection Config-Config-Config-Config-Config-SeriesSeriesSeriesSeriesSeries AdjustmentAdjustmentAdjustmentAdjustmentAdjustment TTTTTypeypeypeypeype InletInletInletInletInlet (optional) Nominal Rating CodeCodeCodeCodeCode CodeCodeCodeCodeCode TTTTTubeubeubeubeube ConnectionConnectionConnectionConnectionConnection TTTTTypeypeypeypeype urationurationurationurationuration

E=External S=Solder StrainerStrainerStrainerStrainerStrainer in Tons F = R12 LengthLengthLengthLengthLength SizesSizesSizesSizesSizesN = Non- (optional) Omit for H = R22 C = medium temp I O SAE = S/T =

Adjustable (Omit for (Omit for no bleed See nominal M = R134a CA = heat pump 5 FT (std) 1/4 3/8 flare straight-Internal) SAE C=Inlet hole capacity *P = R507 W(MOP)=press. limiting other 3/8 1/2 thru

Omit for Flare) Strainer table *R = R502 Z = low temp lengths are 1/2 5/8 ODF =Adjustable (ODF only) (on page 17) *S = R404A available 5/8 7/8 solder ANG =

90°angle

* P, R and S charges are interchangeable

Replacement Power Assemblies

R12 POWER ASSEMBLY R22 POWER ASSEMBLY R502 POWER ASSEMBLY

ServiceFirst ServiceFirst ServiceFirstDescription Part Number Description Part Number Description Part NumberX26300-FC-1 HED00344 X26300-HC-1 HED00348 X26300-RC-1 HED00355X26300-FZ-1 HED00347 X26300-HZ-1 HED00351 X26300-RZ-1 HED00358

X26300-FW15-1 HED00345 X26300-HW35-1 HED00349 X26300-RW45-1 HED00357X26300-FW35-1 HED00346 X26300-HW65-1 HED00350

Torque Power Element 300-360 inch pounds.

Tailored Bulb ChargesThe use of ALCO tailored charges makesthe HF valve reliable for HVAC,refrigerated display cases, walk-incoolers, reach-in coolers, and all othersmall refrigeration systems — both lowand medium temperature.

The thermostatic charge is selected onthe basis of the evaporator temperatureonly, as indicated in Table 2.

Table 2

RefrigerantR502,

Evaporator R12 R134a R22 R404A,Temperature R507

Med temp (– 20 to +50°F) FC MC HC *CLow temp (–50 to +10°F) FZ MZ HZ *Z

MOP low temp (–50 to 0°F) FW15 MW15 HW35 *W45MOP med temp (0 to +25°F) – MW35 HW65 *W65

* Add refrigerant code: “R” for R502, “S” for R404A, “P” for R507.

Replacement parts - HFSC & HFESC only

ServiceFirstPart Number DescriptionKIT04955 Repair Kit (KT20264) includes seal cap, gasket, o-ring, screen, spring

23RSP-PRC022-EN

Thermo Expansion Valves

HF(E)/HFK(E) Extended Product Information

TXV Superheat Change

Listed below are superheat change per turn for the listed refrigerants in °F.

HF(E)/HFK(E) < 5 1/2 tons R-22

HF(E)/HFK(E) < 3 1/2 tons R-502

Approximate Superheat change per turn @ 20°F

Charge Type R404A R507 R22 R12 R502 R134aC,Z 1.5 - 2.0 1.5 - 2.0 2 - 2.5 3 - 4 1.5 - 2 3 - 4

Approximate Superheat change per turn @ -20°F

Charge Type R404A R507 R22 R502C,Z 3 - 3.5 3 - 3.5 4 - 4.5 3 - 3.5

HF(E)/HFK(E) valves typically have between 9 and 11 turns of adjustment dependingon tolerances from full lower stop to upper stop.

HF(E)/HFK(E) > 5 1/2 tons R-22

HF(E)/HFK(E) > 3 1/2 tons R-502

Approximate Superheat change per turn @ 20°F

Charge Type R404A R507 R22 R12 R502 R134aC,Z 3.5 - 4 3.5 - 4 3.5 - 4 6 - 6.5 3.5 - 4 6 - 6.5

Approximate Superheat change per turn @ -20°F

Charge Type R404A R507 R22 R502C,Z 6 - 6.5 6 - 6.5 7 - 7.5 6 - 6.5

HF(E)/HFK(E) extended valves typically have between 4 and 6 turns of adjustmentdepending on tolerances from full lower stop to upper stop.

Ordering Information for HF Series Valves

ServiceFirst Part NumberValve Capacity ExternalSeries Tons Connections HCA Refrig.

1/2 x 7/8 ODF S/T VAL049118 5/8 x 7/8 ODF S/T VAL05516

5/8 x 7/8 ODF S/T VAL0444410 5/8 x 1 1/8 ODF S/T VAL04445

HF(E)(S) 7/8 x 1 1/8 ODF S/T VAL04406 R-2215 5/8 x 7/8 ODF S/T VAL05471

7/8 x 1 1/8 ODF S/T VAL044485/8 x 1 1/8 ODF S/T 5' CAP VAL044477/8 x 1 3/8 SAE EE 5' S/T VAL04407

20 7/8 x 1 1/8 ODF S/T VAL05487

RSP-PRC022-EN24

HFK Balanced Port Thermo® Expansion Valve

Thermo Expansion Valves

Features• The new HFK features interchangeable

bodies, cages, and power elementsproviding maximum flexibility for ¼ to5½ ton applications (nom. R-22).

• The HFK is offered several ways:— Pre-packaged service kits – Include a

mix of bodies and power elementswith a complete set of cages toserve the most applications with aminimum of parts.

— Individual components - Bodies,cages, & power elements may beordered separately and can be usedto build personalized service kits orreplenish pre-packaged kits.

— Finished valves – Assembled valvesready for immediate installation.

• All HFK valves use a balanced port cagedesign that compensates for changesin operating pressures due to varyingambients, gas defrost, heat reclaim, orwidely varying evaporator loads.

• The HFK offers the following additionalfeatures:— Bi-Flow capability— Stainless steel power element— Adjustable superheat— Solid copper connections

Options• ODF or SAE connections• Straight-through or angle flowconfigurations

• Removable inlet strainer available (ODFonly)

• Internal or external equalizer

Specifications• Maximum working pressure: 450 psig• Operating Temperature: -40°F to 50°F• Use with R-22, R-134a, R-404A, R-507,R-12, R-502

Note: HFK cages are not interchangeablewith HF valve bodies. Power elementscan be interchanged.

Nomenclature example: HFKESC 2 HC 5 FT 3/8 X 1/2 ODF S/THFK E S C 2 H C 5 FT 3/8 x 1/2 ODF S/T

VVVVValvealvealvealvealve EqualizerEqualizerEqualizerEqualizerEqualizer ConnectionConnectionConnectionConnectionConnection RemovableRemovableRemovableRemovableRemovable CapacityCapacityCapacityCapacityCapacity RefrigerantRefrigerantRefrigerantRefrigerantRefrigerant ChargeChargeChargeChargeCharge CapillaryCapillaryCapillaryCapillaryCapillary Inlet x OutletInlet x OutletInlet x OutletInlet x OutletInlet x Outlet ConnectionConnectionConnectionConnectionConnection Config-Config-Config-Config-Config-SeriesSeriesSeriesSeriesSeries TTTTTypeypeypeypeype InletInletInletInletInlet Nominal Rating CodeCodeCodeCodeCode CodeCodeCodeCodeCode TTTTTubeubeubeubeube ConnectionConnectionConnectionConnectionConnection TTTTTypeypeypeypeype urationurationurationurationuration

E=External S=Solder StrainerStrainerStrainerStrainerStrainer in Tons F = R12 LengthLengthLengthLengthLength SizesSizesSizesSizesSizes(optional) H = R22 C = medium temp See Body SAE = S/T =

(Omit for (Omit for See nominal M = R134a CA = heat pump 5 FT (std) Table on flare straight-Internal) SAE C=Inlet capacity N = R407C W(MOP)=press. limiting other page 23 thru

Flare) Strainer table P = R507 Z = low temp lengths are ODF =(ODF only) (on page 23) R = R502 available solder ANG =

S = R404A 90°Z = R410A angle

Replacement Screen KitKIT04955

HFKESCODF Connections

25RSP-PRC022-EN

Thermo Expansion Valves

HFK Balanced Port TEV

HFK Selection Process

Step 1: Body Selection

Body Selection Table

ServiceFirstPart Number Description Type Connections (Inlet x Outlet)BOD00819 KT-20298-1 HFK 1/4 x 1/2 SAE Ang InletBOD00820 KT-20298-2 HFK 3/8 x 1/2 SAE Ang InletBOD00821 KT-20298-3 HFKE 1/4 x 1/2 SAE Ang InletBOD00822 KT-20298-4 HFKE 3/8 x 1/2 SAE Ang InletBOD00823 KT-20298-5 HFKSC 3/8 x 1/2 ODF Ang Inlet w/ StrainerBOD00824 KT-20298-6 HFKESC 3/8 x 1/2 ODF Ang Inlet w/ StrainerBOD00825 KT-20298-7 HFKS 3/8 x 1/2 ODF S/TBOD00826 KT-20298-8 HFKS 3/8 x 5/8 ODF S/TBOD00827 KT-20298-9 HFKS 1/2 x 5/8 ODF S/TBOD00828 KT-20298-10 HFKS 1/2 x 7/8 ODF S/TBOD00829 KT-20298-11 HFKES 3/8 x 1/2 ODF S/TBOD00830 KT-20298-12 HFKES 3/8 x 5/8 ODF S/TBOD00831 KT-20298-13 HFKES 1/2 x 5/8 ODF S/TBOD00832 KT-20298-14 HFKES 1/2 x 7/8 ODF S/T

RSP-PRC022-EN26

Thermo Expansion Valves

Step 3: Power Element Selection

Power Element Table1

ServiceFirstPart Number Description System Refrigerant(s) ApplicationHED00346 X26300-FW35-1 R-12/R-134a Low Temp MOPHED00631 X26300-HW100-1 R-22/R-407C AC MOPHED00214 X26300-HCA-1 R-22/R-407C Heat PumpHED00635 X26300-SW45-1 R-404/ R-507/ R-502 Low Temp MOPHED00344 X26300-FC-1 R-12/R-134a Medium TempHED00348 X26300-HC-1 R-22/R-407C A/C Med. TempHED00634 X26300-SC-1 R-404/ R-507/ R-502 Medium TempHED00347 X26300-FZ-1 R-12/R-134a Low TempHED00351 X26300-HZ-1 R-22/R-407C Low TempHED00633 X26300-SZ-1 R-404/ R-507/ R-502 Low Temp

1 Additional power element charges available, call for availability.

Step 2: Cage Selection

Cage Capacity Table (Nominal)

ServiceFirst CagePart Number Description1 Code R-12 R-22 R-134a R-404 R-507 R-502 R-407CCAG00127 KT-20299-0 0 1/8 1/4 1/4 1/8 1/8 1/8 1/4CAG00128 KT-20299-1 1 1/4 1/2 1/2 1/4 1/4 1/4 1/2CAG00129 KT-20299-2 2 1/2 1 3/4 1/2 1/2 1/2 1CAG00130 KT-20299-3 3 1 1 1/2 1 1 1 1 1 1/2CAG00131 KT-20299-4 4 1 1/4 2 1 1/2 1 1/4 1 1/4 1 1/4 2CAG00132 KT-20299-5 5 1 1/2 2 1/2 1 3/4 1 1/2 1 1/2 1 1/2 2 1/2CAG00133 KT-20299-6 6 2 3 2 1/2 2 2 2 3CAG00134 KT-20299-7 7 3 1/2 5 1/2 4 3 1/2 3 1/2 3 1/2 5 1/2

1Cage Kit includes Cage, Insertion Tool and ID Clips.

27RSP-PRC022-EN

Thermo Expansion Valves

HFK Balanced Port TEV

HFK Assembly Procedure

(see 6 assembly steps & diagramsbelow)

1. Remove adjusting stem from body.2. Lubricate o-rings on cage.3. Place cage into insertion tool (using

¼” nut driver) and insert into body (donot over tighten).

4. Screw adjusting stem into bottom ofbody and hand tighten plus onewrench flat.(300-360 inch lbs. – Do not overtighten.)

5. Attach cage identification clip onpower element cap tube.

6. Screw power element onto top ofbody and hand tighten plus onewrench flat.(300-360 inch lbs. – Do not overtighten.)

HFK Pre-Packaged KitsThe HFK is available in a pre-packagedkit consisting of a mix of popular bodiesand power elements with a completeselection of cages. These kits providegreat flexibility allowing valves to beassembled as needed for eachapplication. Three kits are provided asshown below. In addition, custom kitscan be assembled by stocking an emptykit case with desired components.

Cage Kit – KIT07524

ServiceFirst

Item # Description Qty

CAG00127 Size 0 cage (1/4 ton R-22) 2CAG00128 Size 1 cage (1/2 ton R-22) 2CAG00129 Size 2 cage (1 ton R-22) 2CAG00130 Size 3 cage (1-1/2 ton R-22) 2CAG00131 Size 4 cage (2 ton R-22) 2CAG00132 Size 5 cage (2-1/2 ton R-22) 2CAG00133 Size 6 cage (3 ton R-22) 2CAG00134 Size 7 cage (5-1/2 ton R-22) 2TOL01494 Insertion tool 1BOT00009 Oil Bottle 1

Cage ID tags —

R-22 Kit – KIT07555

ServiceFirst

Item # Description Qty

BOD00825 HFKS 3/8 x 1/2 body 1BOD00829 HFKES 3/8 x 1/2 body 3BOD00830 HFKES 3/8 x 5/8 body 1BOD00831 HFKES 1/2 x 5/8 body 1HED00631 HW power element 1HED00214 HCA power element 2HED00348 HC power element 1KIT07524 Cage Kit 1

Kit Accessories

ServiceFirst

Item # Mfg. # Description

BOX01428 KT-20302-1 HFK Replacement Service Box (Empty)

BOX01429 KT-20303 HFK Replacement Boxfor Cage Kit (Empty)

TOL01494 KT-20304 HFK Insertion ToolBOT00009 Oil Bottle HFK Oil Bottle

SAE Kit – KIT07521

ServiceFirst

Item # Description Qty

BOD00819 HFK 1/4 x 1/2 body 1BOD00820 HFK 3/8 x 1/2 body 1BOD00822 HFKE 3/8 x 1/2 body 2HED00344 FC power element 2HED00348 HC power element 1HED00351 HZ power element 1HED00633 SZ power element 2KIT07524 Cage Kit 1

ODF Kit – KIT07522

ServiceFirst

Item # Description Qty

BOD00823 HFKSC 3/8 x 1/2 body 1BOD00829 HFKES 3/8 x 1/2 body 1BOD00824 HFKESC 3/8 x 1/2 body 2HED00344 FC power element 2HED00348 HC power element 1HED00351 HZ power element 1HED00633 SZ power element 2KIT07524 Cage Kit 1

ODF/SAE Mix Kit – KIT07523

ServiceFirst

Item # Description Qty

BOD00820 HFK 3/8 x 1/2 body 1BOD00822 HFKE 3/8 x 1/2 body 1BOD00823 HFKSC 3/8 x 1/2 body 1BOD00824 HFKESC 3/8 x 1/2 body 1HED00344 FC power element 2HED00348 HC power element 1HED00351 HZ power element 1HED00633 SZ power element 2KIT07524 Cage Kit 1

1. Remove adjusting stemfrom body.

3. Place cage intoinsertion tool(using 1/4” square nutdriver) and insert intobody (do not overtighten).

2. Lubricate O-rings on cage.

4. Screw adjustingstem into bottom ofbody and handtighten plus onewrench flat. (300-360inch lbs. – Do notover tighten.)

5. Attach cageidentification clip onpower element captube.

6. Screw powerelement onto top ofbody and handtighten plus onewrench flat. (300-360inch lbs. – Do notover tighten.)

RSP-PRC022-EN28

Thermo Expansion Valves

TRAE+ Thermo® Expansion Valve

Alco’s TRAE Plus thermostatic expansionvalve (TXV) is a large capacity seriesdesigned for refrigeration, airconditioning, heat pump, and chillerapplications. The new series introducesa new replaceable stainless steel powerelement, a fully interchangeable cageassembly and a square body.

This valve type features double balancedport design, which provides stable andaccurate control over wide loads andevaporator temperature ranges.Furthermore, a permanent inlet strainerand external adjustment are standard onevery valve.

Features• Suitable for Bi-Flow applications.• Removable power element and cage

assembly for full serviceability.• Stainless steel power element for

enhanced corrosion resistance• Double balanced port design improves

operation and stability under low loadconditions.

• Square body with straight-thruconnections.

• Solid copper connections.• External superheat adjustment.• Large diaphragm provides superiorstability

• HCA charge designed especially forR22 air conditioning applications.

Options• Cages KIT07318 thru KIT07322• Remote Bulb Tubing Length 10’standard, other lengths are available

• Replaceable Power AssemblyHED00567 (X-28458)

Specifications• Ratings from 10 to 40 tons.• Maximum working pressure: 450 psig• Torque Power Assembly: 375 - 425 in.lb.

• Torque Cage: 60 in. lb.

For ordering information, see page 30.

Nomenclature example: TRAE+ 30 HC 10 Ft 7/8 X 1 1/8 ODF S/TTRA E + 30 H C 10 FT 7/8 x 11/8 ODF S/T

VVVVValvealvealvealvealve EqualizerEqualizerEqualizerEqualizerEqualizer ReplaceableReplaceableReplaceableReplaceableReplaceable CapacityCapacityCapacityCapacityCapacity RefrigerantRefrigerantRefrigerantRefrigerantRefrigerant ChargeChargeChargeChargeCharge CapillaryCapillaryCapillaryCapillaryCapillary Inlet x OutletInlet x OutletInlet x OutletInlet x OutletInlet x Outlet ConnectionConnectionConnectionConnectionConnection Config-Config-Config-Config-Config-SeriesSeriesSeriesSeriesSeries ComponentsComponentsComponentsComponentsComponents Nominal Rating CodeCodeCodeCodeCode CodeCodeCodeCodeCode TTTTTubeubeubeubeube ConnectionConnectionConnectionConnectionConnection TTTTTypeypeypeypeype urationurationurationurationuration

E=External in Tons F = R12 LengthLengthLengthLengthLength SizesSizesSizesSizesSizes1/4” SAE Cage and H = R22 C = medium temp I O ODF = solder S/T =

Power See nominal M = R134a CA = heat pump 10 Ft 5/8 7/8 (Only) Straight-Assembly capacity N = R407C W(MOP)=press. limiting (standard) 7/8 11/8 thru

table P = R507 Z = low temp 11/8 13/8 (Only)(below) R = R502 Other

S = R404A lengths areavailable

TRAE+ Series – Nominal Capacity Table in Tons (kWatts)

R12 R134a R22 R502 R507/R404A R407C7½ (27) 9 (32) 10 (35) 8 (28) 8 (28) 10 (35)10 (35) 13 (46) 15 (53) 12 (42) 12 (42) 15 (53)12 (42) 14 (50) 20 (71) 14 (50) 14 (50) 20 (71)18 (64) 22 (78) 30 (106) 20 (71) 20 (71) 30 (106)25 (88) 30 (106) 40 (142) 30 (106) 30 (106) 40 (142)

29RSP-PRC022-EN

Thermo Expansion Valves

TRAE Thermo® Expansion ValveTRAE Thermo Valves are a large capacityseries for chiller, heat pump,refrigeration, and air conditioningapplications. Its balanced port designprovides stable and accurate controlover wide load and evaporatortemperature ranges.

Features• Suitable for Bi-Flow applications.• External superheat adjustment.• Integral body with straight-thruconnections.

• TRAE’s balanced port design improvesvalve operation & stability under lowload conditions.

Seal Nut27676-1

• Solid copper connections.• Large diaphragm provides superior

stability.• Stainless steel power element for

maximum corrosion resistance

Options• HCA charge designed especially for

R22 air conditioning applications.

Specifications• Ratings from 50 to 70 tons.• Maximum Working Pressure: 450 psig

For ordering information, see page 30.

Nomenclature example: TRAE 50 HC 10 Ft 7/8 X 1 1/8 ODF S/T

TRA E 50 H C 10 FtT 7/8 x 1 1/8 ODF S/TValve Equalizer Capacity Refrigerant Charge Capillary Inlet x Outlet Connection Configuration

Series Nominal Rating Code Code Tube Connection Type

Hermetic E=External in Tons F = R12 Length Sizes S/T =Design, 1/4” SAE H = R22 C = medium temp I O ODF = solder Straight-Solder See nominal M = R134a CA = heat pump/AC 10 FT 1/4 3/8 (Only) thru

Connections, capacity N = R407C W(MOP)=press. limiting (standard) 3/8 1/2 (Only)Balanced table P = R507 Z = low temp other lengths

Port, (below) R = R502 are availableLarger S = R404A

Tonnages

RSP-PRC022-EN30

Thermo Expansion Valves

Ordering Information for TRAE/TRAE+ Series ValvesServiceFirst Valve PCN Cap Tube

Item # Series Charge Length ConnectionsVAL06618 TRAE+ 10 HCA 10 Ft. 7/8 x 1 1/8 ODF S/TVAL06619 TRAE+ 15 HCA 10 Ft. 7/8 x 1 1/8 ODF S/TVAL06605 TRAE+ 10 HCA 5 Ft. 1/2 x 7/8 SAE S/TVAL06606 TRAE+ 10 HCA 5 Ft. 5/8 x 7/8 SAE S/TVAL06607 TRAE+ 15 HCA 5 Ft. 5/8 x 7/8 SAE S/TVAL06608 TRAE+ 15 HCA 5 Ft. 5/8 x 1 1/8 SAE S/TVAL06609 TRAE+ 20 HCA 5 Ft. 5/8 x 1 1/8 SAE S/TVAL06610 TRAE+ 20 HCA 5 Ft. 7/8 x 1 1/8 SAE S/TVAL06611 TRAE+ 20 HCA 5 Ft. 7/8 x 1 3/8 SAE S/TVAL06612 TRAE+ 30 HCA 5 Ft. 7/8 x 1 1/8 SAE S/TVAL06613 TRAE+ 30 HCA 5 Ft. 7/8 x 1 3/8 SAE S/TVAL06614 TRAE+ 40 HCA 5 Ft. 7/8 x 1 1/8 SAE S/TVAL06615 TRAE+ 40 HCA 5 Ft. 1 1/8 x 1 3/8 SAE S/TVAL07765 TRAE 50 HC 10 Ft. 1 1/8 x 1 3/8 SAE S/TVAL07766 TRAE 60 HC 10 Ft. 1 1/8 x 1 3/8 SAE S/TVAL07767 TRAE 70 HC 10 Ft. 1 1/8 x 1 3/8 SAE S/T

Cage Replacement Kits for TRAE+ SeriesValvesReplacement cage assemblies for TRAE+are available as separate sale items.Cage kits are cross referenced bycapacity and tonnage in the table to theright. Each cage kit consists of areplacement cage and cage removalwrench. In addition, the cage removalwrench (KIT07323) can be ordered as aseparate item.

Nominal Capacity - TonsServiceFirst

Item # TRAE+ Kit R-22 R-12/R-134a R-507/R-404A R-502KIT07318 KT-20289 Cage Kit 10 9 8 8KIT07319 KT-20290 Cage Kit 15 13 12 12KIT07320 KT-20291 Cage Kit 20 14 14 14KIT07321 KT-20292 Cage Kit 30 22 20 20KIT07322 KT-20293 Cage Kit 40 30 30 30KIT07323 KT-20294 Cage Wrench Kit

Power Assembly Replacement: HED00567

31RSP-PRC022-EN

Thermo Expansion Valves

T-Series Take-A-Part Thermo®

ValveALCO Take-A-Part Series TEVs, withadjustable superheat and replaceable,interchangeable components are idealfor original equipment and fieldreplacements in air conditioning, heatpump, and refrigeration applications.

Features• Take-A-Part construction for easy fieldservice

• External superheat adjustment• Bi-Flo capability• Stainless steel power assembly up to20 ton

Options• Interchangeable, replaceable cages for

TEV versatility (1/4 to 100 tons capacity)• Interchangeable body flanges for any

connection you need• Interchangeable power heads for

refrigerants listed• Charges for other applications available

(consult Alco Application Engineering)

Specifications• Maximum working pressure: 450 psig• Torque Bolts: 300 in. lb.

Nomenclature Example: TCLEB 5 HC 5 Ft 3/8 X 1/2 SAE ANG

TCL E B 5 H C 5 FT 3/8 x 1/2 SAE ANGVVVVValvealvealvealvealve EqualizerEqualizerEqualizerEqualizerEqualizer Bleed HoleBleed HoleBleed HoleBleed HoleBleed Hole CapacityCapacityCapacityCapacityCapacity RefrigerantRefrigerantRefrigerantRefrigerantRefrigerant ChargeChargeChargeChargeCharge CapillaryCapillaryCapillaryCapillaryCapillary Inlet x OutletInlet x OutletInlet x OutletInlet x OutletInlet x Outlet ConnectionConnectionConnectionConnectionConnection Config-Config-Config-Config-Config-

Series*Series*Series*Series*Series* (optional) Nominal Rating CodeCodeCodeCodeCode CodeCodeCodeCodeCode TTTTTubeubeubeubeube ConnectionConnectionConnectionConnectionConnection TTTTTypeypeypeypeype urationurationurationurationurationTake- E=External in Tons F = R12 LengthLengthLengthLengthLength SizesSizesSizesSizesSizesA-Part B = Bleed Hole H = R22 C = medium temp SAE = flare ANG =

Adjustable Omit for Internal See Cage M = R134a CA = heat pump Various Various sizes are 90° AngleOmit for Assembly N = R407C W(MOP)=press. limiting lengths are available ODF = solder

*See p. 30 no bleed hole Interchangeability P = R507 Z = low temp available (see p.32-33) S/T =for other Tables R = R502 (see p.34-35) also, valve is Straight-T-Series (pages 32-33) S = R404A available thrufamilies less flange

Bolt TorqueThe cap screws on all ALCO Take-A-PartTEVs require 300 inch pound bolt torque.

Field Replacement of Valve Types TL(E),TLXFor field replacement of valve types TLX& TL(E), substitute a valve type TCL(E) ofequivalent tonnage and re-use the oldbody flange. This substitution provides avalve equal in performance withprovision for external superheatadjustment and eliminates the need toremove the old flange.

RSP-PRC022-EN32

Size & Style Body FlangeValve Connections Part ServiceFirstType Flow Inlet Outlet Number Item #

3/8 SAE 1/2 SAE C500-4 FLG002403/8 SAE 5/8 SAE C500-5 FLG002411/2 SAE 5/8 SAE C500-6 FLG002421/4 ODF 3/8 ODF C501-1 FLG00243

Angle 3/8 ODF 1/2 ODF C501-4 FLG002443/8 ODF 5/8 ODF C501-5 FLG002451/2 ODF 5/8 ODF C501-7 FLG00246

5/8 ODF or 7/8 ODF or A576 FLG00247TCL 7/8 ODM 1-1/8 ODM

TCLE 3/8 SAE 1/2 SAE X6669-4 FLG002483/8 SAE 5/8 SAE X6669-1 FLG002491/2 SAE 1/2 SAE X6669-5 FLG002501/2 SAE 5/8 SAE X6669-2 FLG002513/8 ODF 1/2 ODF 9761-5 FLG002523/8 ODF 5/8 ODF 9761-3 FLG00253

Straight- 1/2 ODF 1/2 ODF 9761-6 FLG00254Thru 1/2 ODF 5/8 ODF 9761-4 FLG00255

1/2 ODF 7/8 ODF 9761-2 FLG002565/8 ODF 5/8 ODF X6346-16 FLG002575/8 ODF 7/8 ODF X6346-17 FLG002585/8 ODF 1-1/8 ODF X6346-18 FLG002597/8 ODF 1-1/8 ODF X6346-34 FLG00260

Thermo Expansion Valves

T-Series Take-A-Part Valve Small Capacity ½ to 18 tons

(R22 Nominal – Bi Flow)

Step 1: Select Cage from Capacity Table !Externally AdjustableCage Assembly

Note: Nominal capacities shown here are based on 40°Fevaporator temperature and 100°F vapor-free liquidrefrigerant entering the valve. R-12 and R-134a rated at60 PSID. All other refrigerants rated at 100 PSID.

Nominal Capacity – Tons Cage Assembly1

Valve R404A/ ServiceFirstType R12 R134a R22 R507 R502 R407C Part # Item #

1/4 1/4 1/2 1/4 1/4 1/2 X22440B1B CAG000451/2 3/4 1 1/2 1/2 1 X22440B2B CAG00046

TCL 1 1-1/2 2 1 1 2 X22440B3B CAG00047TCLE 2 2-1/2 3 2 2 3 X22440B4B CAG00048

3 3-1/2 5 3 3 5 X22440B5B CAG000494 5-1/2 7-1/2 4-1/2 4-1/2 7-1/2 X22440B6B CAG00050

6-1/2 7-1/2 10 7 7 10 X22440B7B CAG000517-1/2 9 12 8 8 12 X22440B8B CAG00052

Step 2: Select Flange

Angle, ODF Straight-Thru SAE

!

Nominal Capacity – Tons Cage Assembly1

Valve R404A/ ServiceFirstType R12 R134a R22 R507 R502 R407C Part # Item #

7 9 11 7 7 11 XC724B4B CAG00106TJLE

8 11 14 9 9 14 XC724B5B CAG00107

Nominal Capacity – Tons Cage Assembly1

Valve R404A/ ServiceFirstType R12 R134a R22 R507 R502 R407C Part # Item #

8 11 14 9 9 14 X11873B4B CAG00053TJR

11 13 18 12 12 18 X11873B5B CAG000541Gaskets included on cage.Gasket strip GKT01836 replaces all older T-Series Gasket kits.

Size & Style Body FlangeValve Connections Part ServiceFirstType Flow Inlet Outlet Number Item #

5/8 ODF or 7/8 ODF orAngle7/8 ODM 1-1/8 ODM

B504 FLG00571

TJLE Straight- 5/8 ODF 1-1/8 ODF X6347-2 FLG00582 Thru 7/8 ODF 1-1/8 ODF X6347-6 FLG00583

7/8 ODF 1-3/8 ODF X6347-7 FLG00584

Size & Style Body FlangeValve Connections Part ServiceFirstType Flow Inlet Outlet Number Item #

7/8 ODF or 7/8 ODF orAngle1-1/8 ODM 1-1/8 ODM

10331 FLG00261TJR2

Straight- 7/8 ODF or 7/8 ODF orThru 1-1/8 ODM 1-1/8 ODM

10332 FLG00262

2 TJR is balanced ported. TJR flange includes extended length capscrews.

33RSP-PRC022-EN

Thermo Expansion Valves

Step 3: Select Power Assembly

TCL-TCLE-TJLE-TJR Power Assemblies 3

Refrig- Equalizer Cap Tube Application Power ServiceFirsterant Type Length Temp Range MOP 4 (psi) Assembly Item #

Internal 5 Ft. -20 to +50 None XB-1019 FC 1A¼ SAE 5 Ft. -20 to +50 None XB-1019 FC 1BInternal 10 Ft. -20 to +50 None XB-1019 FC 2A¼ SAE 10 Ft. -20 to +50 None XB-1019 FC 2B

R12 ¼ SAE 15 Ft. -20 to +50 None XB-1019 FC 3B¼ SAE 5 Ft. -50 to +30 35 XB-1019 FW 35 1B¼ SAE 5 Ft. -50 to +50 55 XB-1019 FW 55 1B¼ SAE 10 Ft. -50 to +50 55 XB-1019 FW 55 2B¼ SAE 5 Ft. -50 to +10 None XB-1019 FZ 1BInternal 5 Ft. -20 to +50 None XB-1019 HC 1A¼ SAE 5 Ft. -20 to +50 None XB-1019 HC 1B HED00371¼ SAE 5 Ft. -20 to +50 None XB-1019 HW 1B HED00013¼ SAE 10 Ft. -20 to +50 None XB-1019 HC 2B¼ SAE 5 Ft. -50 to +5 35 XB-1019 HW35 1B

R22 ¼ SAE 5 Ft. -50 to +20 55 XB-1019 HW55 1B¼ SAE 5 Ft. -50 to +30 65 XB-1019 HW65 1B HED00374¼ SAE 5 Ft. -20 to +50 100 XB-1019 HW100 1B HED00373¼ SAE 10 Ft. -20 to +50 100 XB-1019 HW100 2B¼ SAE 5 Ft. -50 to +10 None XB-1019 HZ 1B HED00376¼ SAE 10 Ft. -50 to +10 None XB-1019 HZ 2B¼ SAE 5 Ft. -20 to +50 None XB-1019 MC 1B¼ SAE 10 Ft. -20 to +50 None XB-1019 MC 2B¼ SAE 10 Ft. -50 to +30 35 XB-1019 MW35 2B

R134a ¼ SAE 5 Ft. -50 to +50 55 XB-1019 MW55 1B HED00331¼ SAE 10 Ft. -50 to +50 55 XB-1019 MW55 2B¼ SAE 5 Ft. -50 to +10 None XB-1019 MZ 1B¼ SAE 10 Ft. -50 to +10 None XB-1019 MZ 2B¼ SAE 5 Ft. -20 to +50 None XB-1019 NC 1B

R407C¼ SAE 5 Ft. -20 to +50 100 XB-1019 NW100 1B¼ SAE 5 Ft. -20 to +50 None XB-1019 SC 1B¼ SAE 5 Ft. -50 to 0 40 XB-1019 SW40 1B

R404A¼ SAE 5 Ft. -50 to +25 65 XB-1019 SW65 1B¼ SAE 10 Ft. -50 to +10 None XB-1019 SZ 2B

Capscrews included with Power Assembly4 Maximum Operating Pressure Limit to prevent motor overload

(Old) X13826-1 (ODF)(New) X28124-1 (ODM)

Capscrews

Power Assembly Cap

RSP-PRC022-EN34

Thermo Expansion Valves

T-Series Take-A-Part Valve Large Capacity 22 to 100 tons

(R22 Nominal – Balanced Ported and Bi Flow)

Note: Nominal capacities shown here are based on 40°Fevaporator temperature and 100°F vapor-free liquid refrigerantentering the valve. R-12 and R-134a rated at 60 PSID. All otherrefrigerants rated at 100 PSID.

Step 1: Select Cage from Capacity Table !Externally AdjustableDouble PortedCage Assembly

Nominal Capacity – Tons Cage Assembly1

Valve R404A/ ServiceFirstType R12 R134a R22 R507 R502 R407C Part # Item #

13 16 22 14 14 22 X9117B6B CAG0005515 19 26 16 16 26 X9117B7B CAG00056

TER 20 25 35 21 21 35 X9117B8B CAG0005725 31 45 27 27 45 X9117B9B CAG00058

Nominal Capacity – Tons Cage Assembly1

Valve R404A/ ServiceFirstType R12 R134a R22 R507 R502 R407C Part # Item #TIR 35 45 55 37 37 55 X9166B10B CAG00059

Nominal Capacity – Tons Cage Assembly1

Valve R404A/ ServiceFirstType R12 R134a R22 R507 R502 R407C Part # Item #

45 55 70 48 48 70 X9144B11B CAG00060THR

55 68 85 60 60 85 X9144B13B CAG000611Gaskets included on cage.Gasket strip GKT01836 replaces all older T-Series Gasket kits.

Step 2: Select Flange !Angle, ODF Straight-Thru

ODF

Size & Style Body FlangeValve Connections Part ServiceFirstType Flow Inlet Outlet Number Item #

7/8 ODF or 7/8 ODF orAngle 1-1/8 ODM 1-1/8 ODM

9153 FLG00263TER2

Straight- 7/8 ODF or 7/8 ODF orThru 1-1/8 ODM 1-1/8 ODM

9152 FLG00264

Size & Style Body FlangeValve Connections Part ServiceFirstType Flow Inlet Outlet Number Item #

7/8 ODF or 7/8 ODF orAngle 1-1/8 ODM 1-1/8 ODM

9151 FLG00265TIR

Straight- 7/8 ODF or 7/8 ODF orThru 1-1/8 ODM 1-1/8 ODM

9150 FLG00266

Size & Style Body FlangeValve Connections Part ServiceFirstType Flow Inlet Outlet Number Item #

ANGLE 1-1/8 ODM 1-1/8 ODM 9149 FLG00267THR

Straight-Thru 1-1/8 ODM 1-1/8 ODM 9148 FLG002682 TER flange includes extended length capscrews.

35RSP-PRC022-EN

Thermo Expansion Valves

Step 3: Select Power Assembly Power Assembly

Capscrews

Cap(Old) X13826-1 (ODF)

(New) X28124-1 (ODM)

TER-TIR-THR-TMR Power Assemblies 3

Refrig- Equalizer Cap Tube Application Power ServiceFirsterant Type Length Temp Range MOP 4 (psi) Assembly Item #

¼ SAE 10 Ft. -20 to +40 None XC-726 FC 2B HED00387¼ SAE 10 Ft. -50 to 0 15 XC-726 FW15 2B

R12¼ SAE 10 Ft. -50 to +50 55 XC-726 FW55 2B HED00389¼ SAE 10 Ft. -50 to 0 None XC-726 FZ 2B¼ SAE 10 Ft. -20 to +50 None XC-726 HC 2B¼ SAE 10 Ft. -20 to +50 None XC-726 HW 2B HED00015¼ SAE 10 Ft. -50 to +5 35 XC-726 HW35 2B HED00393

R22 ¼ SAE 10 Ft. -50 to +30 65 XC-726 HW65 2B¼ SAE 10 Ft. -20 to +50 100 XC-726 HW100 2B HED00392¼ SAE 10 Ft. -50 to +10 None XC-726 HZ 2B HED00394¼ SAE 10 Ft. -20 to +50 None XC-726 MC 2B

R134a ¼ SAE 10 Ft. -50 to +50 55 XC-726 MW55 2B¼ SAE 10 Ft. -50 to +10 None XC-726 MZ 2B¼ SAE 10 Ft. -20 to +50 None XC-726 RC 2B HED00395¼ SAE 10 Ft. -50 to -20 15 XC-726 RW15 2B

R502 ¼ SAE 10 Ft. -50 to +5 35 XC-726 RW35 2B HED00396¼ SAE 10 Ft. -50 to +25 65 XC-726 RW65 2B HED00397¼ SAE 10 Ft. -50 to +10 None XC-726 RZ 2B¼ SAE 10 Ft. -20 to +50 None XC-726 SC 2B¼ SAE 10 Ft. -50 to +10 40 XC-726 SW40 2B

R404A¼ SAE 10 Ft. -50 to +25 65 XC-726 SW65 2B¼ SAE 10 Ft. -50 to +10 None XC-726 SZ 2B

Capscrews included with Power Assembly4 Maximum Operating Pressure Limit to prevent motor overload

RSP-PRC022-EN36

Thermo Expansion Valves

Ordering Information for T-Series Valves (complete valves – lessflange – VLF)

TCL, TCLE, TJLE & TJRE SAE External 5 Ft. Cap Tube Length

Valve Description

ServiceFirst ServiceFirst

R-12 Item # R-22 Item #

TCLE ½ FC VAL05690 TCLE 3 HC VAL03014TCLE 1 FC VAL05682 TCLE 5 HC VAL03015TCLE 2 FC VAL05697 TCLE 7½ HC VAL03016TCLE 3 FC VAL05704 TCLE 10 HC VAL03017TCLE 4 FC VAL05708 TCLE 12 HC VAL03018

TCLE 6½ FC VAL05710 TJLE 11 HC* VAL05735TCLE 7½ FC VAL05711 TJLE 14 HC* VAL05736TJLE 8 FC* VAL05738 TJRE 14 HC VAL05740TJRE 8 FC – TJRE14 HW VAL03019TJRE 11 FC VAL05739 TJRE 18 HC VAL05741

TJRE 18 HW VAL03020

TER, TIR & THR 10 Ft. Cap Tube Length

Valve Description

ServiceFirst ServiceFirst

R-12 Item # R-22 Item #

TER 20 FC VAL05719 TER 22 HW VAL03021TER 25 FC VAL05723 TER 26 HW VAL03022THR 55 FC VAL05729 TER 35 HW VAL03023

TER 45 HW VAL03024TIR 55 HW VAL03025THR 75 HW VAL03026THR 100 HW VAL03027

TJLE New Nomenclature

New OldTJLE 7 TJLE 800

R-12 TJLE 8 TJLE 1100TJLE 11 TJLE 1400

R-22 TJLE 14 TJLE 1800TJLE 7 TJLE 900

R-502 TJLE 9 TJLE 1200

37RSP-PRC022-EN

Thermo Expansion Valves

Ordering Information for T-Series Valves (Cont’d)

Note:TCL/TCLE Remote Bulb Tubing Length

R-12 (FC) = 30’’1/4 thru 3 ton

R-22 (HC) = 30’’1/2 thru 3 ton

R-502 (RC) = 30’’1/4 thru 3 ton

TER, TIR & THR5 FT Cap Tube Length

TCLE External Equalized — SAE External, 30’’ Cap Tube Length

Valve DescriptionServiceFirst ServiceFirst

R-12 Item # R-22 Item #TCLE ¼ FC VAL05694 TCLE ½ HC VAL05687TCLE ½ FC VAL05689 TCLE 2 HC VAL05695

TCLE 3 HC VAL05702

Note: T-Series does not include flange.

TER, TIR & THR 5 Ft. Cap Tube Length

Valve DescriptionServiceFirst ServiceFirst

R-12 Item # R-22 Item #TIR 35 FC VAL05732 TIR 55 HW VAL00339THR 45 FC VAL05729

Alternate Refrigerant Charge Codes

Refrigerant CodeR134a MR507 R

R404A RR402A RMP39 X

Replacement Cap Screw Kits

ServiceFirst Contains Pcs. PerItem # Description Screw # Pkg.**

SCR02021 KT-30021 PS-286-5 10SCR02011 KT-30022 PS-168-5 10SCR02013 KT-30023 PS-259 10SCR02012 KT-30024 PS-370 10

** 10 Pc. kits are in poly bags for hanging on peg board.

RSP-PRC022-EN38

Thermo Expansion Valves

Expansion Valve Accessories

Replacement Flange Cap for ObsoleteALCO Multi-Outlet Valves

Occasionally it becomes necessary toreplace out-dated or obsolete ALCOmulti-outlet Thermo® Valves. Wherereplacements are not readily available,the following procedure may befollowed.

1. Remove multi-outlet cage and powerassembly, save capscrews.

2. Install flange cap FLG00269 (A3436)and flange gasket A625-A4 (packedwith A3436).

Replacement Flange Cap for Multi-Outlet Thermo® Valves

ServiceFirstObsolete Valve Types Flange Cap # Item #TN, TO, TOC, TU, TV, TS, TP, TRZZU, ZZO, ZZS, ZZP, ZZR

A3436 FLG00269

For additional information, contact yourABU sales or ALCO representative.

3. Move backward a few inches, cut theliquid line, and install a standardexternally equalized single outlet Take-A-Part Thermo® Valve properlyselected for an equivalent capacity andrefrigerant to that of the old multi-outlet valve.

4. Attach the remote bulb of the newvalve and connect the externalequalizer in a standard manner.

The capped multi-outlet flangeeffectively serves as an adequaterefrigerant distributor.

39RSP-PRC022-EN

Thermo Expansion Valves

LCL Take-A-Part DeSuperheating Thermo® Valve

Application• Desuperheating (Liquid Injection) valveused in conjunction with hot gasbypass to prevent excessive suctionline superheat.

• Interstage cooling for compoundsystems

Features• Take-A-Part construction for easy fieldservice

• Contoured, durable power element forlong life

• Stainless steel power assembly

Options• Interchangeable, replaceable cages forversatility

• External superheat adjustment• Interchangeable body flanges for anyconnection you need

• Interchangeable power heads fordifferent temperature ranges

• Charges for all applications

Specifications• Maximum working pressure: 450 psig

See the section on Liquid InjectionApplications, pages 88-90.

RSP-PRC022-EN40

Thermo Expansion Valves

LCL DeSuperheating Thermo® Valves

NomenclatureLCL E 2 B 5 Ft. 3/8 x 1/2 ODF S/T

VVVVValvealvealvealvealve EqualizerEqualizerEqualizerEqualizerEqualizer CapacityCapacityCapacityCapacityCapacity ChargeChargeChargeChargeCharge CapillaryCapillaryCapillaryCapillaryCapillary Inlet x OutletInlet x OutletInlet x OutletInlet x OutletInlet x Outlet ConnectionConnectionConnectionConnectionConnection ConfigurationConfigurationConfigurationConfigurationConfigurationSeriesSeriesSeriesSeriesSeries Note: This is not CodeCodeCodeCodeCode TTTTTube Lengthube Lengthube Lengthube Lengthube Length ConnectionConnectionConnectionConnectionConnection TTTTTypeypeypeypeype

DeSuperheating E = External system capacity. See Hot Gas Bypass SizesSizesSizesSizesSizes ANG = 90° angleLiquid Injection See hot gas bypass charts for selection 5 Ft. SAE = flare

Take-A-Part (omit for Internal) charts for valve sizing (p. 97) (standard) S/T = straight-thru(p. 97) and chart below ODF = solder

For new applications, consult the factoryfor proper selection and sizing. For fieldreplacement, select a LCL/LCLE valvewith the exact same capacity and charge.

Ordering Information for LCL Valves

PCN* By ChargeEqualizer Select fromTable Below

Description Type A B C ConnectionsLCL 11 VAL05847 VAL05848LCL 21 Internal VAL05850 VAL05851 VAL05852 Same asLCL 31 VAL05853 VAL05854 TCL &LCL 61 VAL05858 – TCLE

LCLE 11 VAL05859LCLE 21 ¼" SAE VAL05861 VAL05862 –LCLE 31 External VAL05863 VAL05864 –LCLE 41 VAL05865LCLE 71 VAL05867

1 Note: Add charge suffix symbol “A”, “B” or “C” based on the following table.Example: LCLE 4-A

Note: Standard remote bulb tubing is 5'.

LCL (LA) Charge Codes

RefrigerantSat’d R-134a R-22 R-404A/R-507

Suction Required Suction Gas Temp Required Suction Gas Required Suction GasTemp. 45°F 65°F 45°F 65°F 45°F 65°F40°F — B (GL) — A (CL) — —30°F B (GL) B (GL) — A (CL) — A (CL)20°F B (GL) C (UL) A (CL) B (GL) — A (CL)10°F B (GL) C (UL) B (GL) B (GL) A (CL) B (GL)0°F C (UL) C (UL) B (GL) B (GL) A (CL) B (GL)

– 10°F C (UL) C (UL) B (GL) C (UL) B (GL) B (GL)– 20°F C (UL) C (UL) B (GL) C (UL) B (GL) C (UL)– 30°F C (UL) C (UL) C (UL) C (UL) B (GL) C (UL)– 40°F C (UL) C (UL) C (UL) C (UL) B (GL) C (UL)

( ) Denotes LA Series Valve Charge Code

41RSP-PRC022-EN

Solenoid Valves

Fundamentals of SolenoidValves

IntroductionIn most refrigeration applications, inorder to automatically control the flow offluids in a system, it is necessary to beable to start or stop the flow in therefrigerant circuit. An electricallyoperated solenoid valve is usually usedfor this purpose. Its basic function is thesame as a manually operated shutoffvalve, but it can be positioned in remotelocations, and may be convenientlycontrolled by simple electrical switches.Solenoid valves can be operated by athermostatic switch (the most commonin refrigeration systems), float switches,low pressure switches, high pressureswitches or any other device used formaking or breaking an electric circuit.

What are Solenoid Valves?A solenoid valve consists of two distinct,but integral acting parts, a solenoid anda valve. The solenoid is nothing morethan electrical wire wound in a spiralaround the surface of a cylindrical form,usually of circular cross section. Whenan electric current is sent through thewindings, they act as an electro-magnet.The force field created in the center ofthe solenoid is the driving force foropening the valve. Inside is a moveablemagnetic iron plunger that is drawntoward the center of the coil whenenergized. See figure 1.

Figure 1. Solenoid operation – coil energized

Principles of Solenoid OperationThe valve contains an orifice throughwhich fluid flows when open. A needleor rod is seated on or in the orifice, andis attached directly to the lower part ofthe plunger. When the coil is energized,the plunger is forced toward the centerof the coil, lifting the needle valve off theorifice and allowing flow. When the coilis de-energized, the weight of theplunger, and in some designs a spring,causes it to fall and close off the orifice,stopping the flow through the valve. Seefigure 2.

Types of SolenoidsSolenoids are either direct acting or pilotoperated. The application determines thetype of solenoid used. The direct actingsolenoid is used on valves with lowcapacities and small port sizes. The pilotoperated solenoid is used on largervalves, eliminating the need for largercoils and plungers.

Direct Acting SolenoidsIn the direct acting valve, the plunger ismechanically connected to the needlevalve or poppet. When the coil isenergized, the plunger pulling the needleoff the orifice is raised into the center ofthe coil. This type of valve will operatefrom zero pressure differential to itsmaximum operating pressuredifferential (MOPD), regardless of theline pressure. See figure 2.

The following forces act on a solenoidvalve to keep it closed, or to keep it openand flowing.

When closed:A. Inlet pressure pushes the plunger or

poppet down onto the orifice.B. Gravity pulls the plunger down on the

orifice.C. Difference between high inlet and

lower outlet pressure holds theplunger on the orifice.

Note: The greater the pressuredifferential between inlet and outletpressure, the more difficult it is to openthe valve.

When open:A. Inlet flow passing through the orifice

tends to help hold the plunger up oropen.

B. Magnetic attraction holds the plungerup.

Forces available for opening or closing asolenoid valve:1. Inlet pressure2. Outlet pressure3. Weight of plunger on the orifice4. Spring force applied to the plunger5. Magnetic attraction of the plunger

RSP-PRC022-EN42

Solenoid Valves

Fundamentals of SolenoidValves

To open the direct acting valve whenclosed, or shutoff with the plunger,poppet, or pin resting on the orifice orport, allowing no flow:A. Energize the coil (electrical flow in

wires).B. Magnetic attraction jerks plunger up

and off of orifice.C. Inlet pressure being greater, flow

occurs from inlet to outlet.

To close the valve when open with flowoccurring:A. De-energize coil (electrical flow stops).B. Magnetic attraction stops, plunger

falls by gravity and/or is assisted byspring action in a closing direction.

C. Blockage of the orifice by the plungercauses all flow to stop.

Maximum Opening Pressure Differential(MOPD)The greater the inlet pressure, or thegreater the difference between the inletand outlet pressures, the tighter theplunger is held down on the orifice. Thelarger the orifice, the greater is the areaaffected by the pressure differential,holding the plunger closed. Therefore, asmall orifice with low pressuredifferential is easy to open magnetically.Increase the orifice size or the pressure

differential, the harder it becomes toopen the plunger. If both the plungerarea is large and the pressure differentialis great, it is possible to exceed theability of the magnet to pull the plungerup or open the valve orifice. When theability of the magnet to open isovercome by the forces holding theplunger closed, it is said that the MOPDhas been exceeded.

When the MOPD is low (area of orifice issmall and the difference between inletand outlet pressures is small), it does nottake much effort for the solenoid coil topull the plunger open. As the orificebecomes larger and the pressure dropgreater, a larger magnetic coil must beused to create a greater magnetic forcefor opening.

The MOPD is determined by how muchmagnetic attraction is necessary toovercome the resistance to stay closed.When the pressure differential is belowthe MOPD rating, the solenoid valve willopen quickly, and easily when energized.When the MOPD is exceeded, the valvewill not open when energized, and maypossibly overheat with dangerousresults unless de-energized quickly.

The direct acting valve is only used onsmall capacity circuits. To use the coilsize required to counteract the largepressure differential of large capacitieswould be uneconomical, and notfeasible for very large capacity circuits. Inorder to overcome this problem, pilotoperated solenoid valves are used.

Figure 3. Pilot operated solenoids – coilenergized & de-energized

Figure 2. Direct acting solenoids – coilenergized & de-energized

Pilot Operated SolenoidsThe pilot operated solenoid valves use acombination of the solenoid coil and linepressure to operate. In this valve, theplunger is attached to a needle valvecovering a pilot orifice rather than themain port. The line pressure holds afloating or independent piston ordiaphragm closed against the main port.See figure 3.

When the coil is energized, the plunger ispulled into the center of the coil, openingthe pilot orifice. Once the pilot port isopened, the line pressure above thediaphragm is allowed to bleed off to thelow side or outlet of the valve, relievingthe pressure on the top of thediaphragm. The inlet pressure thenpushes the diaphragm up and off of themain valve port and holds it thereallowing full flow of the fluid.

43RSP-PRC022-EN

Solenoid Valves

Fundamentals of SolenoidValves

When the coil is de-energized, theplunger drops and closes the pilotorifice. Pressure begins to build upabove the diaphragm by means of ableed hole in the piston or diaphragmuntil it, plus the diaphragm’s weight andspring, cause it to close on the mainvalve port. The pilot operated solenoidvalve requires a minimum openingpressure differential, between the inletand outlet, in order to open the mainport.

Minimum Opening Pressure Differential(MinOPD)As previously explained, the directoperated solenoid valve must notexceed its MOPD or it will not openwhen energized. If pressure differential istoo great or orifices are too large indiameter, it would take a very large andvery expensive coil to overcome thelarge MOPD. Therefore, the pilotoperated valve is used on larger sizesolenoid valves. The main idea is toopen the pilot orifice with as little effortas possible. However, a certain amountof pressure differential is required tofloat the piston or diaphragm off of themain orifice after the pilot orifice hasallowed both the inlet and outletpressure to equalize. This small amountof required pressure is called theminimum opening pressure differential(MinOPD).

All pilot operated solenoids require aMinOPD to raise the main poppet orfloating piston or diaphragm off of themain orifice. Direct operated solenoidsdo not require a MinOPD, but both directoperated and pilot operated have toavoid exceeding their MOPD in order toflow properly.

The manual stem shown in figure 3 isused to manually open the valve if theline current is not available, or forflushing in cleanup, or other servicemaintenance functions.

Figure 4. Two-way solenoid: 200RB

The above basic principles of operationhold true for all refrigerant solenoidvalves, although certain mechanicalvariations in construction can be found.Examples of these variations are:1. Short stroke plungers, which arerigidly connected to the valve or poppet(these will always be the “direct acting”type).2. Long stroke lost motion plungers,which during opening, impart a“hammer blow” to the valve.3. Mechanically interlinked piston toplunger construction, which is usedwhere no pressure differential is avail-able to float the piston. This constructionenables a large solenoid valve to openand remain in an open position with aminimum pressure drop across thevalve. It is used primarily for suction lineduty.4. Pilot operated spring loaded valvesused in large port sizes.5. Condenser pressure powered stopvalves which use a high pressure pilotconnection.

Solenoid valves having a spring loadedplunger may be installed and operated inany position. These valves include mostall modern day refrigeration solenoids.

Different Types of ValvesSo far we have explained how asolenoid valve operates. Now we willdiscuss the many types of valves andtheir respective applications. The threemain types of valves are: two-way, three-way, and four-way.

Two–Way ValvesThe two-way valve, which is the mostcommon type of solenoid valve, controlsfluid flow in one line. It has an inlet andan outlet connection. This valve can be adirect acting or pilot operated valve,depending on the need. When the coil isde-energized, the two-way valve is“normally closed.” Although normally-closed is the most widely used, two-wayvalves are also manufactured to be“normally-open” when the coil is de-energized. See figure 4.

Select Two-way valves can be convertedto reverse flow operation by theaddition of a bi-flow kit.

RSP-PRC022-EN44

Solenoid Valves

Figure 5. Three-way solenoid: 3031RC

Fundamentals of SolenoidValves

Three–Way “Diverting” ValvesThe three-way valve has a connectionwhich is common to either of twodifferent outlets and controls refrigerantflow in two different lines. It is usedchiefly on commercial refrigeration unitsfor heat reclaiming applications, hot gasdefrost, and discharge gas unloadingapplications. See figure 5 for anillustration of a three-way solenoid valve.

Heat Reclaiming ApplicationsThe three-way valve has its commoninlet attached to the compressordischarge line. The other two outletsconnect to the normal condenser andthe auxiliary condenser, as shown infigures 6 and 7.

When the solenoid coil is de-energized,the pilot line to the suction side of thecompressor is closed. Discharge gaspressure escapes thru the bleed portonto the top of the piston and drives itdownward, closing the bottom seat. Thisallows discharge gas to flow to the

Figure 6. Heat reclaiming system condensers in series

Figure 7. Heat reclaiming system condensers in parallel

normal, or outside condenser. Energizingthe solenoid opens the pilot line to thesuction side of the compressor, andpermits the discharge gas pressure ontop of the piston to escape to the suctionside. The discharge gas pressure belowthe piston now causes the piston to bedriven upward closing the outlet to thecondenser and diverting the dischargegas to the auxiliary condenser. Somevalves are available with an internalbleed, which drains the reclaim coilduring normal operation.

45RSP-PRC022-EN

Solenoid Valves

Fundamentals of SolenoidValves

Discharge Gas Unloading (Using a3-Way Valve)The three-way solenoid valve (figure 5),is designed to meet the requirements ofhigh temperatures and pressuresexisting in compressor discharge gasapplications. It is specifically designedfor discharge gas diverting incompressor unloading. In most cases,when de-energized, the compressordischarge gas follows the normal cycleto the condenser. When energized,discharge gas is then diverted to flow tothe system low side for defrost orcompressor unloading. These valves areavailable over a wide tonnage range.Small size three-way solenoids aresometimes used for cylinder unloadingcompressor capacity reduction. Seefigure 8. These valves for compressorunloading applications are usuallydesigned to provide mounting directlyon the compressor. Some are specificallydesigned for OEMs (ALCO 700 Series).

Figure 8. Small three-way solenoid 702RA Figure 11. 401RD 4-way valve used in home& small building equipment.

Four–Way “Reversing” ValvesFour-way solenoid valves, often calledreversing valves, are used almostexclusively on reverse cycle heat pumps,to select either the heating or coolingmode, depending upon requirements.These valves have one common inletand three outlets. Figure 11 is a drawingof a typical four-way valve used in homeor small building equipment.

A heat pump is a central air conditionerwith reverse cycle for heating. In thesummer, the refrigerant absorbs heatfrom the house and exhausts itoutdoors. In winter, the cycle is reversed,with the refrigerant absorbing heat fromoutdoors and releasing it inside thehouse. The next sections explain howthe reversing valve operates.

Four–Way “Reversing” Valve OperationFigures 12 and 13 are schematicdiagrams of a four-way valve on a typicalreverse cycle heat pump system.

RSP-PRC022-EN46

Solenoid Valves

Fundamentals of SolenoidValves

4–Way Valve Heating CycleIn figure 12, the system is in the heatingcycle with the discharge gas from thecompressor flowing thru the reversingvalve ports D to C2, which makes theindoor coil the condenser. The suctiongas is flowing from the outdoor coil(now the evaporator) through reversingvalve ports C1 to S and back to thecompressor. With the 4-way solenoidpilot de- energized, the high pressuredischarge gas builds up on “top” of themain slide holding the main slide down(or on the bottom). The area below themain slide is isolated from the highpressure by a seal and is exposed to lowpressure suction gas by way of port A toS1 and on to S. Thus the unbalancedforces acting on the end areas of themain slide (top vs. bottom) hold the slidein the down position as shown in figure12. The compressor discharge gas nowflows to the indoor coil and heats theinterior.

4–Way Valve Cooling CycleWhen the coil is energized, the slide inthe pilot solenoid moves to its top, nowconnecting pilot ports D1 to A and B toS1 and on to S. With the pilot solenoidso positioned, the discharge pressure isimposed on the bottom of the main slideand it will move to the top of the mainvalve. This unbalanced force will moveand hold the main slide to the UPposition as shown in figure 13. Thecompressor discharge gas now flows tothe outdoor coil allowing the indoor coilto cool the interior.

Solenoid Valve SelectionThe selection of a solenoid valve for aparticular control application requires thefollowing information:1. Fluid to be controlled.2. Capacity required.3. Maximum operating pressure

differential (MOPD).4. Electrical characteristics.5. Safe working pressure required

(SWP).

The capacities of solenoid valves fornormal liquid or suction gas refrigerantservice are given in tons of refrigerationat some nominal pressure drop andstandard conditions. Manufacturers’

Figure 13.

Figure 12.

catalogs provide extended tables tocover nearly all operating conditions forcommon refrigerants. Follow themanufacturer’s sizing recommendations.Do not select a valve based on line size.Pilot operated valves require a minimumpressure drop to operate, and selectingan oversized valve will result in the valvefailing to open. Undersized valves resultin excessive pressure drops.

The solenoid valve selected must have aMOPD rating equal to or in excess of themaximum possible differential againstwhich the valve must open. The MOPDtakes into consideration both the inletand outlet valve pressures. If a valve hasa 500 psi inlet pressure and a 250 outletpressure, and a MOPD rating of 300 psi,it will operate, since the difference (500–250 = 250) is less than the 300 MOPDrating. If the pressure difference is largerthan the MOPD rating, the valve will notopen.

Consideration of the safe workingpressure required is also important forproper and safe operation. A solenoidvalve should not be used for anapplication when the working pressure ishigher than the safe working pressuremaximum.

Solenoid valves are designed for a giventype of fluid so that the materials ofconstruction will be compatible with thatfluid. Steel or ferrous metals andaluminum are used in solenoid valvesfor ammonia service. Special seatmaterials and synthetics may be used forhigh temperature or ultra-lowtemperature service. Special materialsare required for corrosive fluids.

Attention to the electrical characteristicsis also important. Required voltage andhertz must be specified to ensure properselection. Valves for DC service oftenhave different internal construction thanvalves for AC application, so it isimportant to study the manufacturer’scatalog information carefully.

Solenoid Valve InstallationSolenoid valves having a spring loadedplunger or diaphragm may be installedand operated in any position. However,the older, conventional solenoid valvewith a plunger which depends on gravity

to close, must always be installed withthe plunger in an upright verticalposition, with the pipe horizontal. Anadequate strainer or filter drier should beinstalled ahead of each solenoid valve tokeep scale, pipe dope, solder, and otherforeign matter out of the valve.

Before installation, disconnect electricalpower source, shut off fluid powersource, and bring the system pressure toatmospheric. When installing a solenoidvalve, be sure the arrow on the valvebody points in the direction of refrigerantflow. With brazing or solder typeconnections, do not use too hot a torch,and point the flame away from the valvebody. Allow the valve body to coolbefore replacing the valve’s operatinginternal parts to insure that the seatmaterial and gaskets are not damagedby the heat. Wet rags and or chill blocksare recommended during brazing. Theyare necessary to keep the valve bodycool so that body warpage on closecoupled valves will not occur. Whenreassembling, do not overtorque.

47RSP-PRC022-EN

Solenoid Valves

100RB Solenoid Valves

Application• Used for liquid or discharge gasrefrigerant service

• Direct-acting, 2-way, normally closedvalve

• Solenoid actuated shut-off valve

Features• One coil fits all valve sizes• Extended ends for easy installation(standard)

• Long-life molded coils provide water,shock, and vibration protection in coilwinding

Note: Coil sold separately - see page 56.See Nomenclature for orderinginformation.

Options• Connection sizes to fit your system• SAE or ODF connection sizes in 1/4”

and 3/8”, 1/4 NPTF• Coil voltages: 120V 50/60Hz, 208V 50/

60HZ, 24V 50/60HZ• Use with R-22, R-134a, R-404A, R-507

Specifications• Maximum fluid temp: 250°F• Maximum working pressure: 500 psig• MOPD: 300 psig• UL file number: MP604• CSA file number: LR44912• CV and TUV approved

Note: Mounting enclosing tube morethan 90o off vertical up position is notrecommended.

Nomenclature Example: 100RB 2F2 VLC100R B 2 F 2 VLCValve Design Port Size Connection Type Connection Size Coil*Series Series (in 1/16") F = SAE (in 1/8")

S = ODFP = FPT

*Note: Valves are shipped without the solenoid coils (VLC = Valve Less Coil) See page 56 for available coils.

Ordering Information and Nominal Capacity Table for 100RB Valves - Tons

ServiceFirstItem # Product Description Connection Size R-12 R-134a R-22 R-407C R-404A/R-507 R-502

VAL04122 100RB 2S2 VLC 1/4” ODFVAL02395 100RB 2S3 VLC 3/8” ODFVAL02396 100RB 2S4 VLC 1/2” ODFVAL02397 100RB 2F2 VLC 1/4” SAE

.80 .96 1.27 1.21 .85 .83

VAL02398 100RB 2F3 VLC 3/8” SAECapacities based on 100°F liquid and 40°F saturated evaporator for ARI standard 760-87.

RSP-PRC022-EN48

Solenoid Valves

100RB Exploded View & Parts Kit Data

Valve Kit: “K” indicates part is suppliedin valve repair kit KIT04959 (KS30112).

Note: Spanner wrench X11981-1included in complete valve kit.

KIT04959

Coil AssemblyConsists of coil, coil nameplate, andconversion spacer (AMG). For voltagesand frequencies available see the tableson page 56.

49RSP-PRC022-EN

Solenoid Valves

200RB Solenoid Valves

Application• Pilot-operated, 2-way, normally closedvalves

• Ideal for liquid, discharge or suction gasrefrigerant service

• Solenoid actuated shut-off valves

Features• One coil fits all valve sizes• Extended ends for easy installation(standard)

• Long-life molded coils provide water,shock, and vibration protection in coilwinding

Note: Coil sold separately - see page 56.See Nomenclature for orderinginformation.

• Low pressure differential required forfull opening

Options• Connection sizes to fit your system• Can be converted for bi-flo applications• Available in 8 orifice sizes• Manual stem or mounting bracket

adapter

Specifications• Maximum fluid temp: 250°F• Maximum working pressure: 500 psig• MOPD: 300 psig• UL file number: MP604• CSA file number: LR44912

Nomenclature Example: 200RB 4T3M VLC200R B 4 T 3 M VLCValve Design Port Size Connection Type Connection Size M = manual stem Coil*Series Series (in 1/16") F = SAE (in 1/8") T = mounting

S = ODF bracket adapterP = FPT (M & T optional)

T = Copper Extended Ends*Note: Valves are shipped without the solenoid coils (VLC = Valve Less Coil) See page 56 for available coils.

Ordering Information and Nominal Capacity Table for 200RB Valves - Tons (kW)

ServiceFirst Part NumberStandard Manual

Valve Stem2 Description Connection Size R-12 R-134a R-22 R-407C R-404A/R-507 R-502VAL0 N/A 200RB 2 F 3 3/8 SAE 2.0 2.4 3.1 2.9 2.1 2.0

VAL05126 N/A 200RB 2 T 2 1/4 ODFVAL05128 N/A 200RB 2 T 3 3/8 ODFVAL05130 N/A 200RB 3 F 2 1/4 SAEVAL05131 N/A 200RB 3 F 3 3/8 SAEVAL05133 N/A 200RB 3 F 4 1/2 SAE 3.0 3.6 4.8 4.5 3.2 3.1VAL04441 N/A 200RB 3 T 3 3/8 ODFVAL05136 N/A 200RB 3 T 4 1/2 ODFVAL05137 VAL05138 200RB 4 F 3 3/8 SAEVAL05144 VAL05139 200RB 4 S 3 3/8 ODF x 1/2 ODM 3.6 4.3 5.6 5.3 3.7 3.6VAL05147 VAL05145 200RB 4 S 4 1/2 ODF x 5/8 ODMVAL02399 VAL05148 200RB 4 T 3 3/8 ODFVAL04442 VAL05149 200RB 4 T 4 1/2 ODFVAL04444 VAL04443 200RB 4 T 5 5/8 ODFVAL05152 VAL05151 200RB 5 F 4 1/2 SAE

VAL05153 200RB 5 F 5 5/8 ODFVAL05155 200RB 5 S 4 1/2 ODF x 5/8 ODMVAL05158 200RB 5 S 5 5/8 ODF 5.3 6.4 8.2 7.8 5.4 5.3VAL05163 200RB 5 T 4 1/2 ODF

VAL02403 VAL05164 200RB 5 T 5 5/8 ODFVAL05167 200RB 6 F 4 1/2 SAEVAL05169 200RB 6 F 5 5/8 SAEVAL05171 200RB 6 S 4 1/2 ODF x 5/8 ODM 6.4 7.7 10.0 9.5 6.5 6.5

VAL05175 VAL05173 200RB 6 S 5 5/8 ODFVAL05176 200RB 6 T 4 1/2 ODF

VAL02407 VAL05178 200RB 6 T 5 5/8 ODFVAL07768 -- 200RB 7 S 5 5/8 ODF x 7/8 ODMVAL07769 -- 200RB 7 T 4 1/2 ODF 10.0 12.1 15.6 14.8 10.3 10.1VAL07770 VAL07777 200RB 7 T 5 5/8 ODFVAL07771 VAL07778 200RB 7 T 7 7/8 ODFVAL07772 VAL07779 200RB 9 T 5 5/8 ODF 14.9 18.0 23.3 22.2 15.3 15.1VAL07773 VAL07780 200RB 9 T 7 7/8 ODF 19.6 23.6 30.5 29.0 20.1 19.8VAL07774 VAL07781 200RB 9 T 9 1 1/8 ODFVAL07775 VAL07782 200RB 12 T 7 7/8 ODF 22.5 27.1 34.9 33.2 23.0 22.7VAL07776 VAL07783 200RB 12 T 9 1 1/8 ODF

1 Add “T” to the end of description for Mounting Stud 2 Add “M” to the end of the description for Manual Stem

Note: Mounting enclosing tube morethan 90o off vertical up position is notrecommended.

RSP-PRC022-EN50

Solenoid Valves

200RB Bi-Flow ConversionStandard 200RB uni-directional valvescan be converted to Bi-Flow operation byreplacing the internal parts with thecomponents in kit KIT04961. Unlike thestandard valve which permits flow in onedirection only when energized, the Bi-Flow version allows the valve to flow ineither direction, depending on differentialpressures, when energized. If the valveis not energized when flowing in thereverse direction, valve “flutter” willoccur. Also, with the valve de-energized,a higher downstream pressure thanupstream (back-flow) will force the valveopen. Note: A 200RB7, 200RB9 and200RB12 cannot be converted to a Bi-Flow valve.

“K” indicates part is supplied in valverepair kit KIT04960.Gasket Kit KIT06344 (contains 12 pieces).Bi-Flo Conversion Kit KIT04961.Manual stem kit KS30117 (not availablefor 200RB2, 200RB3).

Coil AssemblyFor voltages and frequencies availablesee the tables on page 56.

200RB Exploded View & Parts Kit Data

200RB Valve Kits

ServiceFirst Manual ServiceFirst ServiceFirst ServiceFirstValve Complete Kit Item # Opening Kit Item # Bi-flow Kit Item # Gasket Kit Item #

200RB2 KS30115 KIT04960 KS30293 KIT04961 KG10025 KIT06344200RB3 KS30115 KIT04960 KS30293 KIT04961 KG10025 KIT06344200RB4 KS30115 KIT04960 KS30293 KIT04961 KG10025 KIT06344200RB5 KS30115 KIT04960 KS30293 KIT04961 KG10025 KIT06344200RB6 KS30115 KIT04960 KS30293 KIT04961 KG10025 KIT06344200RB7 KS30354 KIT08285 KS30361 KIT08288 N/A N/A KG00002 KIT08290200RB9 KS30362 KIT08286 KS30364 KIT08289 N/A N/A KG00003 KIT08291200RB12 KS30365 KIT08287 KS30364 KIT08289 N/A N/A KG00004 KIT08292

Ordering Information and Nominal Capacity Table for 200RB BiFlow Solenoids - Tons

Standard ValveServiceFirst Connection

Part # Description Size R-12 R-134a R-22 R-407C R-404A/R-507 R-502VAL05180 200RB GS-1925 3 T 3 3/8 ODF 3.0 3.6 4.8) 4.5 3.2 3.1VAL05181 200RB GS-1926 4 T 3 1/2 ODF 3.6 4.3 5.6 5.3 3.7 3.6VAL05183 200RB GS-1928 5 T 4 1/2 ODFVAL05184 200RB GS-1929 5 T 5 5/8 ODFVAL05185 200RB GS-1930 6 T 5 5/8 ODF 6.4 7.7 10.0 9.5 6.5 6.5

* Product Code Number

51RSP-PRC022-EN

Solenoid Valves

240RA Solenoid Valves

Application• 2-way, normally closed diaphragmvalves

• Ideal for liquid, suction and hot gasservice

• Solenoid actuated shut-off valve

Features• One coil fits all valve sizes• Can be brazed into the line withoutdisassembly

• Reinforced Teflon diaphragm withwoven fiberglass for superior control

• Durable, stainless enclosing tube• Extended ends for easy installation(standard)

• Long-life molded coils provide water,shock, and vibration protection in coilwinding

• Low pressure differential required forfull opening

• Mounting stud models can be fieldconverted to manual lift stem

Options• Connection sizes to fit your system• Manual stem or mounting bracket

adapter

Specifications• Maximum fluid temp: 250°F• Maximum working pressure: 500 psig• MOPD: 300 psig• UL file number: MP604• CSA file number: LR44912

Note: Mounting enclosing tube morethan 90o off vertical up position is notrecommended.

Nomenclature Example: 240RA 8T5M VLC240R A 8 T 5 M VLCValve Design Port Size Connection Type Connection Size M = manual stem Coil*Series Series (in 1/16") T = copper (in 1/8") (optional)

extended ends T = mounting bracketadapter (optional)

*Note: Valves are shipped without the solenoid coils (VLC = Valve Less Coil). See page 56 for available coils.

Ordering Information and Nominal Liquid Capacity Table for 240RA Valves - Tons

ServiceFirst Part NumberStandard Manual

Valve Stem1 Description Connection Size R-12 R-134a R-22 R-407C R-404A/R-507 R-502VAL05199 VAL05198 240RA 8 T 5 5/8 ODFVAL05201 VAL05200 240RA 8 T 7 7/8 ODF

10.0 12.1 15.6 14.8 10.3 10.1

VAL05203 VAL05202 240RA 9 T 5 5/8 ODF 14.9 18.0 23.3 22.1 15.3 15.1VAL05205 240RA 9 T 7 7/8 ODFVAL05207 VAL05206 240RA 9 T 9 1 1/8 ODF

19.6 23.6 30.5 29.0 21.0) 19.8

VAL05186 VAL05909 240RA 12 T 7 7/8 ODFVAL05187 VAL05010 240RA 12 T 9 1 1/8 ODF

22.5 27.1 34.9 33.2 23.0 22.7

VAL05191 VAL05190 240RA 16 T 9 1 1/8 ODFVAL05189 VAL05188 240RA 16 T 11 1 3/8 ODF

37.3 45.0 58.0 55.2 38.3 37.7

VAL05193 VAL05192 240RA 20 T 11 1 3/58 ODFVAL05194 240RA 20 T 13 1 5/8 ODF 58.8 70.9 95.4 90.8 65.7 62.0

VAL05196 VAL05195 240RA 20 T 17 2 1/8 ODF1 Add “M” to the end of the description for Manual Stem

Note: Coil sold separately - see page 56.See Nomenclature for orderinginformation.

RSP-PRC022-EN52

Solenoid Valves

240RA Valve Kits

ServiceFirst Manual ServiceFirstValve Complete Kit Item # Opener Kit Item #

240RA8 KS30321 KIT04979 KS30066 KIT04963240RA9 KS30322 KIT04980 KS30067 KIT04964240RA12 KS30323 KIT04981 KS30067 KIT04964240RA16 KS30324 KIT04982 KS30068 KIT04965240RA20 KS30325 KIT04983 KS30098 KIT04969

Gasket Kit all 240RA valves is KIT05054 (KG10028)

“K” indicates part is supplied incomplete valve repair kit.“M” indicates part is supplied in manualopener kit.“G” indicates gasket is supplied ingasket kit.Note: Spanner wrench (X11981-1 servicetool) included in complete valve kit.

Coil AssemblyFor voltages and frequencies availablesee the tables on page 56.

240RA Exploded View & Parts Kit Data

53RSP-PRC022-EN

RV Suction Gas Extended Capacity Table in Tons for R22 and R410A

Pressure Drop Across Valve – PSIEvaporator Valve R22/R407C R410ATemp. °F Type 1 2 3 4 5 1 2 3 4 5

RV2 1.66 2.35 2.87 3.32 3.71 2.14 3.03 3.71 4.29 4.56RV3 2.23 3.15 3.86 4.46 4.99 2.88 4.07 4.99 5.76 6.16

+ 45°FRV4 3.24 4.58 5.61 6.48 7.25 4.19 5.92 7.25 8.37 8.69RV6 4.51 6.38 7.81 9.02 10.08 5.83 8.24 10.09 11.65 12.31RV2 1.36 1.92 2.35 2.71 3.03 1.75 2.48 3.03 3.50 3.92RV3 2.57 3.63 4.45 5.13 5.74 3.42 4.84 5.93 6.84 7.65

+ 25°FRV4 2.65 3.75 4.59 5.30 5.92 2.35 3.33 4.08 4.71 5.26RV6 3.69 5.21 6.39 7.37 8.25 4.76 6.73 8.25 9.52 10.65RV2 1.09 1.54 1.88 2.06 2.27 1.41 1.99 2.44 2.64 2.90RV3 1.46 2.07 2.53 2.78 3.02 1.89 2.67 3.27 3.54 3.83

+ 5°FRV4 2.12 3.00 3.68 3.93 4.27 2.75 3.88 4.76 5.01 5.42RV6 2.95 4.18 5.12 5.57 6.08 3.82 5.41 6.62 7.11 7.75RV2 0.86 1.21 1.39 1.56 1.70 1.11 1.57 1.77 1.98 2.14RV3 1.15 1.63 1.87 2.06 2.19 1.49 2.10 2.35 2.57 2.71

- 15°FRV4 1.67 2.37 2.64 2.91 3.11 2.16 3.06 3.33 3.65 3.86RV6 2.33 3.29 3.75 4.17 4.49 3.01 4.26 4.75 5.26 5.62

Valve capacities are based on 120°F liquid, saturated evaporator, and 10°F superheat at the valve inlet.

Solenoid Valves

RV Brass Reversing Valves

Application• Designed for use on heat pumpsystems

• Reverse cycle gas defrost

Features• High strength slide carrier• Fewer parts• High capacity pilot– Greater tolerance to contaminates

• Low heat transfer slide• Greater wear resistance of seals• Stainless steel pilot bracket

OptionsTube connection sizes:• Discharge 1/2 and 5/8 ODF/ODM• Suction & Coil 3/4 and 7/8 ODF

Specifications• Nominal 2, 3, 4 & 6 ton sizes• Maximum working pressure: 500 psig• MOPD: 400 psig• Minimum operating pressure

differential: 10 psi• Maximum operating temperature:

250°F• External leakage: 0.1 oz/yr• UL file number: MP604• CSA file number: LR44912

Nomenclature Example: RV 4F46RV 4 F 4 6

Valve Nominal Rating F=ODF Discharge SuctionSeries (in tons) connections Connection Connection

*(omit for ODM) (in 1/8’’) (in 1/8’’)

Ordering Information for RV Series Valves

ServiceFirstItem # Description

VAL07034 RV 2 - F 34 VLCVAL06370 RV 2 - 35 VLC*VAL06011 RV 2 - F 35 VLCVAL06010 RV 3 - F 45 VLCVAL04971 RV 4 - F 46 VLCVAL05052 RV 4 - 56 VLCVAL04972 RV 4 - 57 VLC*VAL04973 RV 6 - F 46 VLCVAL04974 RV 6 - F 47 VLCVAL04975 RV 6 - F 57 VLCVAL04976 RV6 - F 67 VLC

Coil sold separately - see page 56.

RSP-PRC022-EN54

Solenoid Valves

704RB/RC Unloader Valve

Application• 2-Way Unloader Valves• Electrically operated valve for

compressor unloading

Features• Stainless steel and brass construction• OEM drop-in replacement

Specifications• Maximum working pressure: 450 psig• MOPD: 300 psig• 704RB - Drop-in replacement for Trane

part number X13320486-01• 704RC - Drop-in replacement for Trane

part number X13320310-01

Coil sold separately - see page 56.

Nomenclature Example: 704RC VLC704RC VLCValve Coil*Series

*Note: Valves are shipped without the solenoid coils (VLC= Valve Less Coil). See page 56 for available coils.

Ordering Information

ServiceFirst OEMItem # Description Part Number

VAL05111 704RB-001 VLC X13320486-01VAL02236 704RC-001 VLC X13320310-01

Note: Body gasket not included. Consult compressormanufacturer for body gasket information.

Dimensional Data

704RC

704RB

Dimensions shown are in inches: Fractions (Decimal)

55RSP-PRC022-EN

Solenoid Valves

708RA Unloader Valve

Application• 3-Way Unloader Valves• Electrically operated valve forcompressor unloading

Features• Stainless steel and brass construction• OEM drop-in replacement

Specifications• Maximum working pressure: 450 psig• MOPD: 300 psig• U.L. approved: File number MP604• Drop-in replacement for Trane partnumber VAL05774 (X13320676-01)

Nomenclature Example: 708RA VLC708RA VLCValve Coil*Series

*Note: Valves are shipped without the solenoid coils (VLC= Valve Less Coil). See page 56 for available coils.

Coil sold separately - see page 56.

Ordering Information

ServiceFirst OEMItem # Description Part Number

VAL05774 708RA-001 VLC X13320676-01VAL05054 708RA-003 VLC X133206740-01

Note: Body gasket not included. Consult compressormanufacturer for body gasket information.

Dimensional Data

Dimensions shown are in inches: Fractions (Decimal)

1 1/32 (1.03)

1/2 (.51)

2 3/4 (2.75)

1/2 (.50)

1 1/8 (1.13)

1 7/64 (.265)9/16 (.56)

2 1/2(2.50)

1 7/8(1.88)

1 3/4 (1.75)

15/16 (.94)

RSP-PRC022-EN56

Solenoid Valves

Solenoid Valve Coils

Ordering Information for Coils

Note: All Alco coils fit on all Alco Solenoid Valves

Alco Voltage Lead ServiceFirstCoil Style Configuration Frequency Length Item #AMG Junction Box 24V 50/60Hz 6" COL03779AMG Junction Box 120V 50/60Hz 6" COL03780AMG Junction Box 208-220/208-240 50/60Hz 6" COL03781AMG Junction Box 480V 50/60Hz 6" COL03782AMG Junction Box 120-240V 50/60Hz 6" COL09638AMG Junction Box 277V 60Hz 6" COL09637AMG Junction Box 12V DC1 6" COL09634AMG Junction Box 24V DC1 6" COL09635AMG Junction Box 32V DC1 6" COL09636AHG Hi Temp Junction Box 120/50-60 6" COL09651AHG Hi Temp Junction Box 208-240/50-60 6" COL09649AHG Hi Temp Junction Box 24/50-60 6" COL09650DMG Junction Box 24/50-60 6" COL09647DMG Junction Box 120/50-60 6" COL09648DMG Junction Box 208-240/50-60 6" COL09646AMC Conduit 24/50-60 18" COL05345AMC Conduit 120/50-60 18" COL09468AMC Conduit 208-220/208-240 50/60 18" COL01639AMC Conduit 480/50-60 18" COL09628AMC Conduit 12/DC 18" COL05347AHC Conduit Hi Temp 24/50-60 18" COL09654AHC Conduit Hi Temp 120/50-60 18" COL09652AHC Conduit Hi Temp 208-240/50-60 18" COL09653AMS 1/4" Spade 24/50-60 None COL09641AMS 1/4" Spade 120/50-60 None COL01638AMS 1/4" Spade 208-240/50-60 None COL09640AMS 1/4" Spade 277/60 None COL09642AMF Open Frame 24/50-60 18" COL09629AMF Open Frame 120/50-60 18" COL09630AMF Open Frame 208-240/50-60 18" COL09633AMF Open Frame 277/60 18" COL09631AMF Open Frame 480/50-60 18" COL09632ASC2 Molded2 24V 50/60Hz None COI01038ASC2 Molded2 120V 50/60 Hz None COL11850

1AM style DC coils should not be used for direct replacements on OEM equipment. The use of this coil on newapplications may result in the valve not opening. New applications should use the MM coil because of the significantincrease in opening power of the MM coil over the standard AM style DC coil.2ASC2 female connector X-28616 - 18" in length.

Junction Box

6"Leads

Lead Wires

18"Leads

Open Frame/Spaded

Molded

Coil Enclosure Options Options CodeJunction Box GConduit, 18" Leads COpen Frame, 18" Leads FOpen Frame, Spades S

57RSP-PRC022-EN

System Protectors

Fundamentals of SystemProtectors

Alco’s liquid line and suction line filter-driers are often referred to as SystemProtectors because they remove harmfulelements from the circulating refrigerantbefore serious damage results.

Keeping the system clean and free offoreign contaminants that can restrict theoperation of valves, block capillary tubesor damage compressors is the best wayto assure trouble-free operation. Thesecontaminants can be solids, such asmetal filings, flux, dust and dirt. Otherequally menacing contaminants aresolubles, such as acid, water, resins andwax.

No matter how many precautions aretaken during assembly and installationor servicing of a system, contaminantscan find a way into the system. Filter-driers are designed to protect a systemduring operation. It is the function of thisall important unit to remove thoseresidual elements that can attack andeventually destroy the systemcomponents.

All of the liquid line filter-driers on themarket today are a variation of one oftwo types: the molded block type or thebead type.

A. The block style filter-drier ismanufactured by mixing the dryingelements, which remove the solublecontaminants, with a suitablebonding element. This mixture isthen poured into molds and finallyplaced in ovens where the blocks takea permanent form and the dryingingredients are activated.

B. The bead style filter-drier uses a lesscomplicated manufacturing process,so there is less change of error. Theactive drying material is in the form ofbeads or pellets. No bondingmaterial is used to hold the beadstogether, but rather compacting isnormally performed through sometype of mechanical pressure. On theupstream side of the compactedbeads is a filter network whichcushions flow and traps the solidcontaminants.

Alco’s filter-driers protect the refrigerantsystem from liquid and solidcontaminants. They incorporate variousdesiccants for maximum moisture andacid removal and a special compound toprevent wax build-up.

Certain characteristics of systemprotectors must be understood in orderto make the proper selection. Whenperforming service work on arefrigeration system in the field it is nextto impossible to determine the quantityor type of contamination which may bein the system. For this reason it is goodpractice to select the largest size filter-drier which fits the available space andeconomical considerations.

Filtration CapacitySolid particles or semi-solids such assludges circulating in a refrigerantsystem can destroy valve seats, plugcontrol valves, and score cylinder wallsor compressor bearings. Thesecontaminants can be the result ofmanufacturing, servicing, or can begenerated during normal systemoperation.

Of prime importance, is removing thesecontaminants as quickly as possible andpreventing them from returning to thesystem. All Alco filter-driers aredesigned to trap and hold largequantities of these contaminants whilemaintaining acceptable flow rates duringtheir service life.

Moisture CapabilityMoisture in a refrigeration system canmean frozen valves, copper plating,damaged motor insulation, corrosion,and resulting sludges. Filter-driersaccomplish the task of removing andretaining moisture through the use ofone or more desiccants. The mostpopular and effective desiccant in usetoday for the removal of moisture ismolecular sieve which can hold three tofour times the water of other commercialabsorbents. Moisture capacity of a filter-drier is normally given in drops of water

per ARI Standard 710. These ratedcapacities are in addition to any residualmoisture that might be absorbed duringmanufacturing.

Acid Pick-Up CapabilityVarious organic acids result during thedecomposition of the refrigerant and oilin a system. This decomposition can bethe result of moisture in the system,excessive temperatures, air, or exposureto foreign substances in the system. It isimportant that acid in a system isabsorbed as soon as it is formed toprevent the acid from causing systemdamage. Activated alumina is the mostpopular of the desiccants used toremove acid.

Wax RemovalThe ability of a filter-drier to remove waxand resins is of major importance in lowtemperature applications that use R-22 .Wax when present in a system has atendency to solidify on valve seats andpins, resulting in system malfunctions.

Flow RatePublished flow rates for Alco filter-driersare established in accordance with ARIStandard 710 for liquid line driers, andARI Standard 730 for suction line driers.

RSP-PRC022-EN58

System Protectors

10. Observe the system during the first 4hours. Repeat step 9 as often asrequired, until no further change inpressure drop is observed.

11. After the system has been inoperation for 48 hours, check thecondition of the oil with the Alco AcidAlert test kit. If the oil test indicatesan acid condition, replace both theliquid and suction line filter-drier.

12. Check the system again afterapproximately 2 weeks of operation.If the oil is still discolored, replace theliquid and suction line filter-drier.

13. Clean-up is complete when the oil isclean and odor-free, and isdetermined to be acceptable with theAlco Acid Alert test kit.

Clean-up Procedure ForCompressor Motor Burnout

1. Determine the extent of the burnout.For mild burnouts wherecontamination has not spread thru thesystem - it may be economical to savethe refrigerant charge, if the systemhas service valves on the compressor.A severe burnout exists if the oil isdiscolored, an acid odor is present,and contamination products are foundon the high and low side. In thiscondition, caution should be exercisedto avoid breathing the acid vapors -also, avoid skin contact with thecontaminated liquid.

2. Thoroughly clean and replace allsystem controls such as Thermovalves, solenoids, check valves,reversing valves, etc.. Remove allstrainers and filter-driers.

3. Install replacement compressor andmake a complete electrical check.

4. Make sure that the suction lineadajacent to compressor is clean.Install an over-sized liquid line filter-drier and an Alco suction linefilter-drier.

5. Pressure and leak-test the systemaccording to unit manufacturer’srecommendations.

6. Triple evacuate to at least 500 microns.Break the vacuum with clean, dryrefrigerant at 0 psig.

7. Charge the system through an Alco EKfilter-drier to equipmentmanufacturer’s recommendations.

8. Start the compressor and put thesystem in operation. Record thepressure drop across the Alco suctionline filter-drier on the enclosed labeland apply label to the side of the shell.

9. Replace the suction line filter-drier ifthe pressure drop becomes excessive.

59RSP-PRC022-EN

System Protectors

Recommended System Tonnage For kW, Multiply tons by 3.51

Take Apart Liquid Line Filter Driers

Air ConditioningAlco Refrigeration, Low Temp. & Field Replacement OEM

Description Commercial Installations & Field Installations Self Contained EquipmentR-12/134a R-22/407C R-404A/507A R-12/134a R-22/407C R-12/134a R-22/407C

STAS 485T 8 10 8 8 10 13 15STAS 487T 10 13 10 10 12 1/2 15 20STAS 489T 10 15 10 10 15 15 20STAS 4811T 13 20 13 13 20 20 25STAS 967T 20 25 15 20 25 25 35STAS 969T 25 30 20 25 30 35 45STAS 9611T 30 35 25 30 35 35 45STAS 9613T 35 40 30 35 40 40 50

A-TD-9625S-V 40 45 35 40 45 50 60STAS 1449T 30 40 30 30 40 40 55STAS 14411T 40 50 35 40 50 50 65STAS 14413T 45 55 40 45 55 55 75STAS 14417T 60 50 45 50 60 60 80STAS 19211T 50 70 45 50 70 60 80STAS 19213T 60 80 55 60 80 75 100STAS 19217T 65 85 60 65 85 80 110ADKS 30013T 50 65 45 50 65 55 70ADKS 30017T 60 80 50 60 80 65 90ADKS 40017T 65 85 55 65 85 70 95ADKS 40021T 75 100 65 75 100 80 105

Spun Copper Liquid Line Service Driers

Air ConditioningAlco Refrigeration, Low Temp. & Field Replacement OEM

Description Commercial Installations & Field Installations Self Contained EquipmentR-12/134a R-22/407C R-404A/507A R-12/134a R-22/407C R-12/134a R-22/407C

CU-80, 619 1/3 1/2 1/3 1/3 1/2 1/2 1/2CU-620, 621 1/2 3/4 1/2 1 2 1 1/5 2

CU-200 1/2 3/4 1/2 3/4 1 1 1 1/2CU-319 1/2 3/4 1/2 1 2 1 1/2 2

1Example: 1.0 tons x 3.5 = 3.5 kW

Hermetic Liquid Line Filter Driers (EK, ADK, UDK, BFK, BOK)

Air ConditioningAlco Refrigeration, Low Temp. & Field Replacement OEM

Description Commercial Installations & Field Installations Self Contained EquipmentR-12/134a R-22/407C/R-410A R-404A/507A R-12/134a R-22/407C/R-410A R-12/134a R-22/407C

032, 032S, 033, 033S 1/4 1/4 1/4 1/2 3/4 3/4 1052, 052S 1/3 1/3 1/3 3/4053, 053S 1 1/2 2 2 3082, 082S 1/2 1/2 1/2 3/4 1 1/2 1 2

0825S083, 083S 1 1 1 2 3 3 4

084, 084S 1.5 2 1 3 5 4 7162, 162S 1 1 1/2 3/4 1 2 2 2 1/2

1625S 2 2 1/2 2 3 4 4 5163, 163S164, 164S 2 4 2 4 6 5 7 1/2

165, 165S 3 5 2 1/2 5 7 1/2 7 1/2 10303, 303S 3 3 2 3 4 1/2 4 5304, 304S 3 5 3 5 7 1/2 7 1/2 9305, 305S 5 7 1/2 5 8 10 10 14

306S307S 7 1/2 7 1/2 5 7 1/2 12 1/2 15 20

309S 7 1/2 10 7 1/2 10 12 1/2 15 20413 3 4 3 3 4 4 5

414, 414S 5 6 5 6 10 7 1/2 11415, 415S 7 1/2 7 1/2 7 1/2 7 1/2 12 1/2 10 15

417S 10 10 7 1/2 10 15 15 20419S 10 12 1/2 10 12 1/2 15 20 25757S 15 15 10 15 20 20 25759S 20 25 15 20 25 25 30

RSP-PRC022-EN60

System Protectors

EK Extra-Klean Liquid LineFilter-Drier

R-410A - Premium Universal replacementliquid line filter-drier for CFC, HCFC andHFC refrigerants including R-410A (R-410A through 16” size only).

Application• Alco’s premium compacted bead filter-

drier with a finer 20 micron final outletpad for maximum filtration

Features• Filtration first for more effective use of

surface area of desiccant

Nomenclature Example: EK-083SEK 08 3 S

Drier Unit Size Connection Size S = ODFSeries (in cu. in.) (in 1/8”) connections

(omit for SAE)

F Dia.

• High moisture and acid removal• Solid copper fittings• Corrosion resistant epoxy powder paint

finish• Copeland approved for POE Oils

Specifications• Desiccant blend - 75% molecular sieve

and 25% activated alumina• Filtration: 20 microns• Maximum working pressure:

Sizes: 03-16 600 psig30-75 500 psig

• UL file number: SA 3124• CSA file number: LR 100624

LR 32462Ordering Information for EK

ServiceFirst Model Dimensions ShipItem # Number A B D E F1 Wt. Lbs.

DHY00131 EK-032 4 3/8 — —DHY00132 EK-032S 3 7/8 3-1/8 3/8DHY00133 EK-032FM 3 1/2 — — 2 9/16 1 5/8 1/2DHY00816 EK-032MF 3 1/2 — —DHY00135 EK-033 4 11/16 — —DHY00136 EK-033S 4 1/16 3 3/16 7/16DHY00137 EK-052 4 13/16 — —DHY00817 EK-052MF 4 1/2 — —DHY00138 EK-052S 4 7/16 3 11/16 3/8 3 2 5/8 7/8DHY00139 EK-053 5 1/8 — —DHY00140 EK-053S 4 1/2 3 5/8 7/16DHY00141 EK-082 5 5/8 — —DHY00142 EK-082S 5 1/4 4 1/2 3/8DHY00324 EK-0825SDHY00143 EK-083 5 15/16 — —DHY00144 EK-083S 5 5/16 4 7/16 7/16 3 13/16 2 5/8 1 1/4DHY00145 EK-084 6 3/16 — —DHY00146 EK-084S 5 3/8 4 3/8 1/2DHY00147 EK-162 6 9/16 — —DHY00148 EK-162S 6 3/16 5 7/16 3/8DHY00818 EK-1625S 5 15/16 5 5/16 5/16DHY00149 EK-163 6 7/8 — —DHY00150 EK-163S 6 1/4 5 7/16 7/16 4 3/4 2 5/8 1 1/2DHY00151 EK-164 7 1/16 — —DHY00152 EK-164S 6 5/16 5 5/16 1/2DHY00153 EK-165 7 1/2 — —DHY00154 EK-165S 6 9/16 5 5/16 5/8DHY00155 EK--167SDHY00156 EK-303 9 5/8 — —DHY00157 EK-303S 9 8 1/8 7/16DHY00158 EK-304 9 7/8 — —DHY00159 EK-304S 9 1/8 8 1/8 1/2DHY00160 EK-305 10 5/16 — — 7 1/2 3 1/16 3 3/4DHY00161 EK-305S 9 5/16 8 1/16 5/8DHY00819 EK-306S 9 11/16 8 7/16 5/8DHY00820 EK-307S 9 7/8 8 3/8 3/4DHY00821 EK-309S 10 1/4 8 7/16 15/16DHY00165 EK-413 9 3/4 — —DHY00166 EK-414 10 — —DHY00167 EK-414S 9 1/4 8 1/4 1/2DHY00168 EK-415 10 7/16 — — 7 5/8 3 11/16 4 3/4DHY00169 EK-415S 9 7/16 8 3/16 5/8DHY00170 EK-417S 10 8 1/2 3/4DHY00171 EK-419S 10 5/16 8 1/2 3/4DHY00172 EK-757S 15 7/16 13 15/16 3/4DHY00173 EK-759S 15 3/4 13 7/8 15/16 13 1/16 3 11/16 7 1/2

1Does not include weld bead

Dimensional Data

F Dia.

E

B*

A

D

* Indicates Lay-in Length

Depth ofSocket

E

A

61RSP-PRC022-EN

ADK Block Style Liquid LineFilter-Drier

R-410A - Although Alco recommendsthe EK or UDK driers for R-410Aapplications, the ADK filter-drier is ULlisted for 600 PSIG maximum workingpressure for all sizes through 16 cubicinches.

Application• Economy solid core liquid line filter-drier ideal for use with CFC and HCFCrefrigerants (R-410A through 16” sizeonly

Features• Solid copper fittings• Shock resistant steel shell construction

System Protectors

Nomenclature Example: ADK 083SADK 08 3 S

Series Unit Size Connection S = ODF(in cu. in.) Size connection

(in 1/8”) (Omit for SAE)

• High moisture and acid removalcapacity

• Corrosion resistant epoxy powder paintfinish

Specifications• Desiccant Blend: Activated Alumina

with Molecular Sieve• Filtration: 40 microns• Maximum working pressure:

Sizes: 03-16 600 psig30-75 500 psig

• UL file number: SA 3124• CSA file number: LR 100624

LR 32462

Dimensional Data

E

A

F Dia.

E

B*A

D

F Dia.

* Indicates lay-in length

DepthofSocket

Ordering Information for ADK

DimensionsServiceFirst Part Connection Ship

Item # Number Size A B D E F 1 Wt. Llbs.DHY00387 ADK-032 1/4 SAE 4 3/8 — — 2 9/16 1 5/8 1/2DHY00388 ADK-032S 1/4 ODF 3 7/8 3 1/8 3/8 2 9/16 1 5/8 1/2DHY00389 ADK-033 3/8 SAE 4 11/16 — — 2 9/16 1 5/8 1/2DHY00390 ADK-033S 3/8 ODF 4 1/16 3 3/16 7/16 2 9/16 1 5/8 1/2DHY00391 ADK-052 1/4 SAE 4 13/16 — — 3 2 5/8 3/4DHY00392 ADK-052S 1/4 ODF 4 7/16 3 11/16 3/8 3 2 5/8 3/4DHY00393 ADK-053 3/8 SAE 5 1/8 — — 3 2 5/8 3/4DHY00097 ADK-053S 3/8 ODF 4 1/2 3 5/8 7/16 3 2 5/8 3/4DHY00395 ADK-082 1/4 SAE 5 5/8 — — 3 13/16 2 5/8 1 1/4DHY00396 ADK-082S 1/4 ODF 5 1/4 4 1/2 3/8 3 13/16 2 5/8 1 1/4DHY00825 ADK-083 3/8 SAE 5 15/16 — — 3 13/16 2 5/8 1 1/4DHY00826 ADK-083S 3/8 ODF 5 5/16 4 7/16 7/16 3 13/16 2 5/8 1 1/4DHY00827 ADK-084S 1/2 ODF 5 3/8 4 3/8 1/2 3 13/16 2 5/8 1 1/4DHY00828 ADK-162 1/4 SAE 6 7/16 — — 4 5/8 2 5/8 2DHY00829 ADK-163 3/8 SAE 6 3/4 — — 4 5/8 2 5/8 2DHY00830 ADK-163S 3/8 ODF 6 1/8 5 1/4 7/16 4 5/8 2 5/8 2DHY01025 ADK-164 1/2 SAE 6 15/16 — — 4 5/8 2 5/8 2DHY00831 ADK-164S 1/2 ODF 6 3/16 5 3/16 1/2 4 5/8 2 5/8 2DHY00402 ADK-165 5/8 SAE 7 7/16 — — 4 5/8 2 5/8 2DHY00832 ADK-165S 5/8 ODF 6 3/8 5 1/8 5/8 4 5/8 2 5/8 2DHY00834 ADK-303 3/8 SAE 9 5/8 — — 4 5/8 2 5/8 2DHY00854 ADK-303S 5/8 ODF 9 8 1/8 7/16 7 1/2 3 1/16 3 3/4DHY00404 ADK-304 1/2 SAE 9 7/8 — — 7 1/2 3 1/16 3 3/4DHY00835 ADK-304S 1/2 ODF 9 1/8 8 1/8 1/2 7 1/2 3 1/16 3 3/4DHY01026 ADK-305 5/8 SAE 10 5/16 — — 7 1/2 3 1/16 3 3/4DHY00836 ADK-305S 5/8 ODF 9 5/16 8 1/16 5/8 7 1/2 3 1/16 3 3/4DHY00837 ADK-307S 7/8 ODF 9 7/8 8 3/8 3/4 7 1/2 3 1/16 3 3/4DHY00838 ADK-309S 1 1/8 ODF 10 3/16 8 3/8 15/16 7 1/2 3 1/16 3 3/4DHY01022 ADK-414 1/2 SAE 10 — — 7 5/8 3 11/16 4 3/4DHY00839 ADK-414S 1/2 ODF 9 1/4 8 1/4 1/2 7 5/8 3 11/16 4 3/4DHY01023 ADK-415 5/8 SAE 10 7/16 — — 7 5/8 3 11/16 4 3/4DHY00840 ADK-415S 5/8 ODF 9 7/16 8 3/16 5/8 7 5/8 3 11/16 4 3/4DHY00841 ADK-417S 7/8 ODF 10 8 1/2 3/4 7 5/8 3 11/16 4 3/4DHY00842 ADK-419S 1 1/8 ODF 10 5/16 8 1/2 15/16 7 5/8 3 11/16 4 3/4DHY01024 ADK-757S 7/8 ODF 15 7/16 13 15/16 3/4 13 1/16 3 11/16 7 1/2DHY00843 ADK-759S 1 1/8 ODF 15 3/4 13 7/8 15/16 13 1/16 3 11/16 7 1/2

RSP-PRC022-EN62

System Protectors

BFK/EBF Liquid Line Bi-Directional Heat Pump

R-410A - The BFK filter-drier is UL listedfor 600 PSIG maximum workingpressure for all sizes through 16 cubicinches.

Application• Bi-directional liquid line filter-drier for

heat pump applications• For use with CFC, HCFC, HFC

refrigerants

Features• 16 cubic inches in a 2 1/2” diameter

shell• Internal check valves allow flow and

filtration in either direction. Externalcheck valves eliminated

Nomenclature Example: BFK 165SBFK 16 5 S

Series Unit Size Connection Size S = ODF(in cu. in.) (in 1/8”) connections

(omit for SAE)

• High moisture and acid removal• Corrosion resistant epoxy powder paintfinish

• Copeland approved for POE oils

Specifications• Desiccant blend - 75% molecular sieveand 25% activated alumina (Bead)

• Filtration 40 microns• Maximum working pressure:Sizes: 05-16 600 psig

30 500 psig• UL file number: SA 3124• CSA file number: LR 100624

LR 32462

Note: For sizing, see recommendedsystem tonnage on page 59.

DImensional Data

E

E(Socket Depth)

B

C(Layin Length)

A

D Dia.

D Dia.

BA

DimensionsServiceFirst Part Connection Ship

Item # Number Size A B C D E Wt. Llbs.DHY00098 BFK-083 3/8 SAE 5.94DHY00099 BFK-083S 3/8 ODF 5.29 4.48 .40DHY00809 BFK-084 1/2 SAE 6.16 2.62DHY00101 BFK-084S 1/2 SAE 5.38DHY00103 BFK-085S 5/8 ODF 5.60 4.35 .63DHY00325 BFK-0825S 5/16 ODFDHY00104 BFK-163 3/8 SAE 6.74 4.61DHY00105 BFK-163S 3/8 ODF 6.08 4.61 5.28 .40 2DHY00899 EBF 163S 3/8” ODF 6 1/8 4 5/8 5 1/4 2 5/8 7/16DHY00106 BFK-164 1/2 SAE 6.96 4.61DHY00107 BFK-164S 1/2 ODF 6.17 4.61 5.17 .50DHY00900 EBF 164S 1/2” ODF 6 3/16 4 5/8 5 3/16 1/2DHY00108 BFK-165 5/8 SAE 7.41 4.61DHY00109 BFK-165S 5/8 ODF 6.39 4.61 5.14 .63DHY00970 BFK 307S 7/8 ODF 9.91 7.50 8.41 .75

3.82 2.62

3.15 3.85

2

1

2 5/8

63RSP-PRC022-EN

System Protectors

BFK Internal Construction• The BFK uses a conventional blockstyle desiccant filter-driersupplemented with a final outlet filterpad and a heavy steel perforatedretaining screen

• The valving system and filter issymmetrical end to end

BFK Basic Flow Patterns• Refrigerant always flows from outersurface of block, through block tocenter core and through final filter pad

• This construction guarantees thattrapped particles are not flushed outwhen flow through the BFK is reversedor surged, even while the BFK isagitated or rapped

• On actual system tests, BFK’s havebeen submitted to over one millionflow cycles with no detrimental effecton the check valves

• Filtration: Large particles retained onsurface of or within the block; smallerparticles are retained in outlet filterpads

RSP-PRC022-EN64

System Protectors

BOK-HH Liquid Line BurnoutFilter-Drier

Application• Alco’s BOK-HH incorporates an HH

blended solid core for the effectiveclean-up of systems following a severeburnout

NomenclatureBOK 30 5 S HH

Series Unit Size Connection S = ODF Charcoal(in cu. in.) Size connections Blend

(in 1/8”) (omit for SAE)Above example: BOK 305S-HH

• Liquid line filter drier for Burnout clean-up and wax removal

Features• Designed for maximum effectiveness in

the clean-up of systems following asevere burnout

• Corrosion resistant epoxy powder paintfinish

• Charcoal blend for soluble contaminantand wax removal

• Solid copper fittings

Dimensional Data

E

A

F Dia.

EB*

A

D

F Dia.

* Indicates lay-in length

DepthofSocket

Note: For sizing, see recommendedsystem tonnage on page 59.

Specifications• Filtration: 40 microns• Maximum working pressure:

08-16 600 psig30-41 500 psig

• UL file number: SA 3142• CSA file number: LR 100624

LR 32462

DimensionsServiceFirst Part Connection Ship

Item # Number Size A B D E F1 Wt. Llbs.DHY00887 BOK-082-HH 1/4 SAE 5 5/8 — —DHY00888 BOK-083-HH 3/8 SAE 5 15/16 — —DHY00889 BOK-162-HH 1/4 SAE 6 7/16 — — 3 15/16 2 15/16 1DHY00890 BOK-163-HH 3/8 SAE 6 3/4 — —DHY00891 BOK-163S-HH 3/8 ODF 6 1/8 5 1/4 7/16DHY00892 BOK-164-HH 1/2 SAE 6 15/16 — —DHY00893 BOK-164S-HH 1/2 ODF 6 3/16 5 3/16 1/2 4 5/8 2 7/8 2DHY00894 BOK-165-HH 5/8 SAE 7 7/16 — —DHY00895 BOK-165S-HH 5/8 ODF 6 3/8 5 1/8 5/8DHY00201 BOK-303-HH 3/8 SAE 9 5/8 — —DHY00326 BOK-303S-HH 3/8 ODFDHY00898 BOK-304-HH 1/2 SAE 9 7/8 — —DHY00810 BOK-304S-HH 1/2 ODF 9 1/8 8 1/8 1/2 7 1/2 3 1/16 3 3/4DHY00896 BOK-305-HH 5/8 SAE 10 5/16 — —DHY00328 BOK-305S-HH 5/8 ODF 9 5/16 8 1/16 5/8DHY00897 BOK-414-HH 1/2 SAE 10 — —DHY00207 BOK-415-HH 5/8 SAE 9 1/4 8 1/4 1/2 7 5/8 3 11/16 4 3/4DHY00208 BOK-417S-HH 7/8 ODF 10 7/16 — —

1Does not include weld bead

65RSP-PRC022-EN

System Protectors

ALF Liquid Filter

The ALF liquid line refrigerant filter isideal for protecting solenoid andexpansion valve parts from debris.

Application• Liquid Line Filter• Recovery, recycle and reclaim filter

Nomenclature Example: ALF 033SALF 03 3 S

Series Unit Size Connection Size S = ODFInlet (in 1/8”)

Connection StyleOmit for SAE (Male in-Male Out)

MF = Male SAE in femaile SAE OutFM = Female SAE in - Male SAE Out

Features• Filtering media that maximizes removalof finer particles

• Corrosion resistant epoxy powder paintfinish

Specifications• Filtration: 40 microns• Maximum working pressure: 500 psig• UL file number: SA 3124• CSA file number: LR 100624

LR 32462

DimensionsServiceFirst Part Connection

Item # Number Size A B1 CFLR03843 ALF-032S 1/4 ODF 2 9/16 1 5/8 3 7/8FLR03842 ALF-032MF 1/4 SAE Male in

1/4 SAE Female out 2 9/16 1 5/8 4

FLR03841 ALF-032FM 1/4 SAE Female in1/4 SAE Male out 2 9/16 1 5/8 4

FLR03844 ALF-0323 1/4 SAE MaleFLR03845 ALF-033S 3/8 ODF 2 9/16 1 5/8 4FLR03846 ALF-034S 1/2 ODF 2 9/16 1 5/8 4 1/8

Dimensional Data

A

B

C

ALF-032-MF Pictured

Spring

Fiberglass Pad

Filter Retainer

Recovery, Recycle and ReclaimRefrigerant Flow Capacity

(lbs./min. liquid)R-134a R-22 R-404A/R-507

7.6 8.0 8.0

RSP-PRC022-EN66

System Protectors

Spun Copper Liquid Line Filter-Drier

Application• Large capacity spun copper solid core

driers for superior corrosion resistancein ocean going vessels and coastalapplications

Features• All copper construction• 100% molecular sieve solid core drier• Corrosion resistant• For use with CFC, HCFC and HFC

refrigerants

NomenclatureCU 16 3 S

ConnectionSeries Unit Size ODF

Size in 1/8”

CU Capacity Tables and Ordering Information

Flow Capacity Water Capacity2

Tons @ 1 psi DP 1 4 Drops of Water3

ServiceFirst ALCO (For kW, multiply tons by 3.5 ) R-12 R-134a R-22 R-407C R-404A/507 R-502Item # Description Connections R-12 R-134a R-22 R-407C R-404A/507 R-502 75°F 125°F 75°F 125°F 75°F 125°F 75°F 125°F 75°F 125°F 75°F 125°F

DHY00939 CU 08 3 S 3/8 ODF 2.9 3.5 3.8 3.7 2.5 2.5 212 191 205 191 191 177 156 122 212 205 198 177DHY00957 CU 08 4 S 1/2 ODF 3.5 4.2 4.6 4.5 3.1 3.0DHY00940 CU 16 3 S 3/8 ODF 3.3 4.0 4.3 4.2 2.9 2.8 287 257 277 257 257 237 207 158 287 277 267 237DHY00958 CU 16 4 S 1/2 ODF 3.9 4.7 5.1 5.0 3.4 3.3

Specifications• Maximum Working Pressure: 500 psig• Filtration: 40 microns• UL file number:

1 All ratings in accordance with ARI Standard 710-86. 86oF liquid refrigerant temperature 2 Water Capacities are based on: 3 20 drops of water = 1 gram = 1 cc5oF saturated vapor temperature Equilibrium Point Dryness (EPD) of:3.1 lbs./min./ton for R-134a 50 parts per million for R-134a, R404-A/507,2.9 lbs./min./ton for R-22 and R-407C R-410A and R-407C 4 For 2 PSI ∆P, Multiply values by 1.44.0 lbs./min./ton for R-404A/507 and R-12 60 parts per million for R-224.4 lbs./min./ton for R-502 15 parts per million for R-12

30 parts per million for R-502

Dimensional Data

C

B

A

Overall Lay-InLength Dimension Diameter

Model A B CCU 03 3 15/16” 3 1/4” 1 5/8”CU 05 5 3/16” 4 1/2” 1 5/8”CU 08 6 1/16” 5 3/8” 2 1/8”CU 16 6 5/8” 6” 2 1/8”

67RSP-PRC022-EN

System Protectors

STAS Steel Liquid and SuctionFilter-Drier

Application• Replaceable core filter-drier for CFC,

HCFC and HFC refrigerants for use inlarge commercial air conditioning andrefrigeration systems

Features• Unique internal hardware for hassle-

free installation• Full flow fittings for low pressure drop• Corrosion resistant epoxy powder paint

finish• Sturdy steel shells for long life

durability• Solid copper fittings• 100 mesh outlet screen

Nomenclature Example: STAS 489TSTAS 48 9 T

System Unit Size Connection Size System ServiceProtector (in cu. in.) (in 1/8”) T = Liquid Line Service

Series SV = Suction Line Service

Specifications• Filtration (with block): 40 microns• Maximum working pressure:

500 psig T (Liquid Line)400 psig SV (Suction Line)

• UL file number: SA 3124• CSA file number: LR 100624

LR 32462• Bolt torque: 25 foot-lbs

Options• Blocks: page 71• Filters: page 71

A

B

D

D

C

4.98

6.19

Dimensional Data

STAS models are shipped without filtercores or filter-drier blocks - see page 71for block information.

Ordering Information for STAS

Number DesiccantServiceFirst Catalog Connection of Volume Dimensions

Item # Number Size & Type Blocks Cu. In. A B C DDHY00110 STAS-485T 5/8 ODF 9 15/32 6 3 25/32 5/8DHY00111 STAS-487T 7/8 ODF 9 11/16 6 1/4 3 3/4 25/32DHY00112 STAS-489T 1 1/8 ODF 9 3/4 6 5/16 3 27/32 15/16DHY00343 STAS-489SV 1 1/8 ODFDHY00113 STAS-4811T 1 3/8 ODF 1 4 8 9 27/32 6 7/16 3 31/32 15/16DHY00345 STAS-4813SV* 1 5/8 ODF 9 7/8 6 1/2 4 1/32 1 1/8DHY00114 STAS-4813T 1 5/8 ODFDHY00339 STAS-4817SV* 2 1/8 ODF 10 1/16 6 9/16 4 9/16 1 11/32DHY00340 STAS-4821SV* 2 5/8 ODF 10 7/16 7 1/32 4 3/4 1 1/2DHY00115 STAS-967T 7/8 ODF 15 3/16 11 23/32 3 3/4 25/32DHY00116 STAS-969T 1 1/8 ODF 15 7/32 11 25/32 3 27/32 15/16DHY00117 STAS-9611T 1 3/8 ODF 15 5/16 11 29/32 3 31/32 1 1/32DHY00118 STAS-9613T 1 5/8 ODF 2 9 6 15 3/8 11 31/32 4 1/32 1 1/8DHY00346 STAS-9617SV* 2 1/8 ODF 15 9/16 12 1/32 4 9/16 1 11/32DHY00119 STAS-9617T 2 1/8 ODFDHY00341 STAS-9621SV* 2 5/8 ODF 15 15/16 12 1/2 4 3/4 1 1/2DHY00342 A-TD-9625SV* 3 1/8 ODF 15 11/16 10 5/16 4 5/8 1 3/4DHY00120 STAS-1449T 1 1/8 ODF 21 1/4 17 3/8 3 27/32 15/16DHY00121 STAS-14411T 1 3/8 ODF 21 11/32 17 17/32 3 31/32 1 1/32DHY00122 STAS-14413T 1 5/8 ODF 21 3/8 17 19/32 4 1/32 1 1/8DHY00123 STAS-14417T 2 1/8 ODF 21 9/16 17 5/8 4 9/16 1 11/32DHY00124 STAS-19211T 1 3/8 ODF 26 29/32 23 3 31/32 1 1/32DHY00125 STAS-19213T 1 5/8 ODF 4 1 9 2 26 15/16 23 1/6 4 1/32 1 1/8DHY00126 STAS-19217T 2 1/8 ODF 27 1/8 23 1/8 4 9/16 1 11/32NOTE: “T” style can be used for suction by removing pipe plug and installing X-11562-2.* “SV” style include stainless steel bolts and access valve.

1 4 8

2

3

4 1 9 2

9 6

1 4 4

RSP-PRC022-EN68

System Protectors

ServiceFirstFlange Cover Assembly Part Number Item #All STAS driers - include flange cover, X12176-3 KIT05023compression spring and pipe plug

Shell Strainer Assembly

STAS-48 X27458-1 KIT05019STAS-96 X27458-2 KIT05020STAS-144 X27458-3 KIT05021STAS-192 X27458-4 KIT05022

Miscellaneous Parts

Cover Bolts (Stainless Steel-Suction LineService) X25787-7 KIT05018Cover Gasket (Includes Felt Set) X11983-1 KIT04993Handle 26446-1 KIT04999Inlet Retainer 26447-1 KIT05000Spring 26439-1 KIT04998

Replacement Parts For STAS

Mounting Bracket for STAS 48*

*More than one mounting bracket may be required forshell sizes 96 and above.

See page 71 for block information.

CompressionSpring

Shell

Felt Outlet Seal

Outlet Retainer

Support Rod

Felt Seal Ring

Block

Block

Felt SealRings

Handle

CoverGasket

Access ValveStandard

Pipe PlugStandard

Cover BoltsStainless Steel

Inlet Retainer

Coupling

STAS Internals

Liquid (T)

Grade 5

Suction (SV)

Felt Set

69RSP-PRC022-EN

System Protectors

ADKS Liquid and Suction LineFilter-Drier

Application• Replaceable core filter-drier for CFC,HCFC and HFC refrigerants for verylarge commercial air conditioning andrefrigeration systems

Features• Full flow fittings for low pressure drop• Corrosion resistant epoxy powder paintfinish

• Sturdy steel shells for long lifedurability

Nomenclature Example: ADKS 30013TADKS 300 13 T

System Unit Size Connection Size T = Tap AccessProtector (in cu. in.) (in 1/8”) Connection

Series

AB

E C

15/647/16

1/4” FPTAccessConnection

D

F*

D DepthofSocket

G

Dimensional Data

Specifications• Maximum working pressure: 500 psig• UL file number: SA 3124• CSA file number: LR 100624• Filtration (with block) 40 micron• Bolt torque: 25 ft., lb.

Options• Blocks: Order separately on page 71• Filters: Order separately on page 71

Note: For sizing, see recommendedsystem tonnage on page 59.

DimensionsServiceFirst Catalog Connections Ship

Item # Number Size & Type A B C D E F* G H 1 Wt. Lbs.DHY00127 ADKS-30013T 1 5/8 ODF 25 1/2 19 15/32 4 3/16 1 1/8DHY00128 ADKS-30017T 2 1/8 ODF 25 19/32 1 9 3 25/32 1 22/32 23 3/16 22 1/4 39DHY00129 ADKS-40017T 2 1/8 ODF 32 3/32 25 1/2 3 25/32 1 21/32 6 7 9/16DHY00130 ADKS-40021T 2 5/8 ODF 33 1/8 26 23/32 4 13/16 1 15/32 29 31/32 28 7/8 46

* Does not include weld bead1 “H” Dimension is the clearance required to change the internal hardware assemblyT = 1/4” FPT access connection

23 3/16

29 31/326 7 9/16

22 1/4

28 7/8

39

46

Ordering Information for ADKS

See page 71 for block information.

RSP-PRC022-EN70

System Protectors

Replacement Parts For ADKS

ServiceFirstFlange Cover Part Number Item #ADKS-300, ADKS-400 X12176-2 KIT05023

ServiceFirstShell Strainer Assembly Part Number Item #ADKS-300 X10574-5 KIT05010ADKS-400 X10574-6 KIT05011

Filter-drierBlock

Inlet BlockRetainer

Gasket

Filter-drierBlock

Shell StrainerAssembly

ADKS Internals

ADKS models are shipped without filter cores or filter-drier blocks.

See page 71 for block information.

71RSP-PRC022-EN

System Protectors

Blocks and Filter Cores

Application• Universal replacement cores for use inAlco and all other take-apart type filter-drier shells

Features• Water capacities to suit specific systemconditions

• Exceptional acid capacities for normalsystem protection, or to effectivelyclean-up following a compressorburnout

• Wax removal capabilities for completeclean-up following a compressorburnout (W Series)

Specifications• Interchangeable with competitive

products

Note: Blocks are suitable for use withR-11 but filters are not suitable.

NomenclatureH 48

Series Cubic Inch

Ordering Information and Capacity Tables

Water Capacity 1

Recommended Drops Of Water 2

ServiceFirst ALCO Refrigerant R-12 R-134a R-22 R-407C R-404A/507 R-502Item # Description Type Function 75 F 125 F 75 F 125 F 75 F 125 F 75 F 125 F 75 F 125 F 75 F 125 F

COR00053 D-42 CFC, HCFC High Acid Removal 782 515 493 384 432 303 320 196 528 378 473 339COR00052 H-42 CFC,HCFC High Acid And Water Removal 933 681 686 576 617 491 478 333 724 587 656 519COR00018 D-48 CFC, HCFC High Acid Removal 810 453 415 340 363 254 225 95 457 343 388 225COR00019 H-48 CFC, HCFC High Acid And Water Removal 1020 688 676 538 597 436 445 285 721 535 643 475COR00020 W-48-HH CFC, HCFC, HFC Burnout Cleanup 772 488 387 294 335 226 290 165 417 289 444 306COR00057 UK-48 CFC, HCFC, HFC Universal Replacement 1579 1319 1272 1168 1181 1072 1033 786 1319 1241 1332 1150COR00021 H-100 CFC, HCFC High Acid And Water Removal 1958 1225 1112 834 962 673 726 418 1199 839 1109 758COR00022 W-100-HH CFC, HCFC, HFC Burnout Cleanup 1668 1054 1077 812 938 621 629 363 1162 792 960 663COR00067 F-48R CFC, HCFC, HFC Filter (Suction Only) — — — — — — — — — — — —KIT07667 F-100 CFC, HCFC, HFC Filter (Suction Only) — — — — — — — — — — — —

1 Water Capacities are based on: 2 20 drops of water = 1 gram = 1 ccEquilibrium Point Dryness (EPD) of:50 parts per million for R-134a, R404-A/507 and R-407C60 parts per million for R-2215 parts per million for R-1230 parts per million for R-502

Dimensional Data

B Dia.C Dia.

AReplaceableDrier Block

Filter-drierBlock Dimensions ShipSize A B C Wt. Lbs.42 6 1.58 3.12 148 5.5 1.77 3.72 1 1/2100 6.5 2.06 4.81 4

B Dia.C Dia.

A Filter Core

Catalog Dimensions ShipNumber A B C Wt. Lbs.

F-48/F-48R 5 1/2 2 13/16 3 7/8 3/4F-100 6 1/2 3 3/4 4 13/16 1 1/2

RSP-PRC022-EN72

Type A-F Replaceable Filter Cartridges

ServiceFirst Filter For Core Core Filter Area WeightItem # Core Shell No. O.d. Length Sq. In. Lb.

COR00061 A2F BTAS-2 1 29/32” 6 3/8” 66 1/3COR00063 A3F BTAS-3 2 3/4 6 7/8 115 1/2COR00064 A4F BTAS-4 3 3/4 7 1/2 189 7/8COR00065 A5F BTAS-5 4 5/16 8 1/2 270 1

System Protectors

BTAS Brass Take-ApartSuction Line Filter-Drier

Application• Replaceable core filter-drier for suction

line service is ideal for commercialrefrigeration applications

Features• Full flow fittings for low pressure drop• Corrosion resistant brass body with

stainless steel bolts• Special cartridge design exclusive to

brass shell

Nomenclature Example: BTAS 311SVBTAS 3 11 SV

System Unit Size Connection Size SuctionProtector (in 1/8”) Line

Series Service

Specifications• Filtration (with cartridge) 40 microns• Maximum working pressure: 400 psig• UL file number: SA 3124

Options• Flexibility of using either filter-driers orfilter cartridges

A

B

E

D

C

F

Dimensional Data

Ordering Information for BTAS

Nominal DimensionsServiceFirst Catalog Connection Shell Ship

Item # Number Size Size A B C D E F Wt. Lbs.DHY00245 BTAS-39 S-V 1 1/8 ODF 3” 10 5/16 6 13/16 3 5/16 4 5/8 .910 3 15/32 10 1/4DHY00246 BTAS-311 S-V 1 3/8 ODF 3” 11 1/16 6 15/16 3 7/16 4 5/8 .970 3 15/32 10 1/2DHY00366 BTAS-313 S-V 1 5/8 ODF 3” 11 1/4 7 1/8 3 5/8 4 5/8 1.090 3 15/32 11DHY00367 BTAS-317 S-V 2 1/8 ODF 3” 11 1/2 7 3/8 3 7/8 4 5/8 1.340 3 15/32 11 1/2DHY00247 BTAS-413 S-V 1 5/8 ODF 4” 12 1/32 7 13/16 4 1/8 5 3/4 1.090 4 15/32 16 3/4DHY00248 BTAS-417 S-V 2 1/8 ODF 4” 12 9/32 8 1/16 4 3/8 5 3/4 1.340 4 15/32 17 1/2DHY00368 BTAS-421 S-V 2 5/8 ODF 4” 12 13/32 8 3/16 4 15/16 5 3/4 1.470 4 15/32 18DHY00369 BTAS-517 S-V 2 1/8 ODF 5” 13 7/16 8 13/32 4 3/16 7 3/32 1.340 5 9/16 28 3/4DHY00249 BTAS-521 S-V 2 5/8 ODF 5” 13 9/16 8 15/32 4 15/16 7 3/32 1.470 5 9/16 29DHY00250 BTAS-525 S-V 3 1/8 ODF 5” 13 1/4 8 5/32 4 5/8 7 3/32 1.660 5 9/16 29 1/4

Type A-F-D Replaceable Filter-Drier Cartridges

DesiccantServiceFirst Filter-drier For Cartridge Cartridge Volume Weight

Item # Cartridge Shell No. O.D. Length Cu. In. Lb.COR00062 A2F-D BTAS-2 1 29/32” 6 3/8” 4.2 1/2COR00043 A3F-D BTAS-3 2 3/4 6 7/8 13.3 7/8COR00044 A4F-D BTAS-4 3 3/4 7 1/2 26.0 1 1/2COR00045 A5F-D BTAS-5 4 5/16 8 1/2 36.5 2

73RSP-PRC022-EN

System Protectors

Replacement Parts For BTAS

ServiceFirstMiscellaneous Parts Part Number Item #Seal Ring BTAS-2 PS23380-2 KIT05002Seal Ring BTAS-3 PS23380-3 KIT05003Seal Ring BTAS-4 PS23380-4 KIT05004Seal Ring BTAS-5 PS23380-5 KIT05005

BTAS Internals

Spring

Access Valve

Cover

Filter CoreOrFilter-drier Cartridge(Supplied Separately)

Seal Ring Square Cut Included witheach Filter or Filter-Drier Cartridge

Flange Bolts

BTAS models are shipped without filter cartridge or filter-drier cartridge.

See page 71 for core information.

RSP-PRC022-EN74

System Protectors

ASD Premium Suction LineFilter-drier

Application• Alco’s ASD is a premium suction line

filter-drier that incorporates beadeddesiccant plus a filter

• Premium suction line filter drier formoisture, acid and contaminantremoval

•For use with CFC, HCFC and HFCrefrigerants

Features• Premium filtration• Dual access valves• Solid copper fittings• Corrosion resistant epoxy powder paintfinish

Specifications• Filtration: 40 microns• Maximum working pressure: 500 psig• UL file number: SA 3124• CSA file number: LR 100624

LR 32462

Nomenclature/SelectionASD 35 S 5 VV

Series Unit S = ODF Connection DualSize connections Size Access

(in cu. in.) F = SAE (in 1/8”) ValvesAbove example: ASD 35S5VV

Dimensional Data

A

B

E

C D

Ordering Information for ASD

DimensionsServiceFirst Catalog Connection Ship

Item # Number Size A B C D E 1 Wt. Lbs.DHY00174 ASD 28S3-VV 3/8 ODF 5 19/32 4 23/32 7/16 4 1/8 3 11/16 2DHY00361 ADS28F3-VV 3/8 SAEDHY00175 ASD 28S4-VV 1/2 ODF 5 11/16 4 11/16 1/2 4 1/8 3 11/16 2DHY00176 ASD 35F5-VV 5/8 SAE 7 9/16 — — 4 3/4 3 11/16 2 1/2DHY00177 ASD 35S5-VV 5/8 ODF 6 17/32 5 9/32 5/8 4 3/4 3 11/16 2 1/2DHY00178 ASD 45S6-VV 3/4 ODF 7 3/4 6 1/2 5/8 5 9/16 3 11/16 3DHY00179 ASD 45S7-VV 7/8 ODF 7 15/16 6 7/16 3/4 5 9/16 3 11/16 3DHY00180 ASD 50S9-VV 1 1/8 ODF 8 27/32 7 1/32 29/32 6 1/8 3 11/16 3 1/2DHY00181 ASD 75S11-VV 1 3/8 ODF 12 1/4 10 5/16 31/32 8 1/4 3 11/16 5DHY00182 ASD 75S13-VV 1 5/8 ODF 12 5/32 9 29/32 1 1/8 8 1/4 3 11/16 5

75RSP-PRC022-EN

System Protectors

SFD Suction Line Filter-Drier

Application• Alco’s standard compacted beadsuction filter-drier for use after aburnout or when major work has beenperformed

• Suction line filter drier for moisture,acid and contaminant removal

• For use with CFC, HCFC and HFCrefrigerants

Features• Solid copper fittings• Dual access valves• Corrosion resistant epoxy powder paint

finish

Specifications• Filtration: 40 microns• Maximum working pressure: 400 psig• UL file number: SA 3124• CSA file number: LR 100624

LR 32462

Nomenclature Example: SFD 13S5-VVSFD 13 S 5 VV

Series Unit S= ODF Connection DualSize Connections Size Access

(in cu. in.) F = SAE (in 1/8”) Valves

Ordering Information for SFD

DimensionsServiceFirst Catalog Connection Shipping

Item # Number Size A B C D Weight Lbs.DHY00284 SFD 13F3-VV 3/8 SAE — 3 3/8 5 1/2 3 11/16 2DHY00235 SFD 13S3-VV 3/8 ODF 3 31/32 3 3/8 4 27/32 3 11/16 2DHY00236 SFD 13S4-VV 1/2 ODF 3 15/16 3 3/8 4 15/16 3 11/16 2DHY00237 SFD 13S5-VV 5/8 ODF 3 29/32 3 3/8 5 5/32 3 11/16 2DHY00238 SFD 13S6-VV 3/4 ODF 4 3 3/8 5 1/4 3 11/16 2DHY00239 SFD 13S7-VV 7/8 ODF 4 1/4 3 3/8 5 3/4 3 11/16 2DHY00240 SFD 27S7-VV 7/8 ODF 6 5 1/8 7 1/2 3 11/16 3DHY00241 SFD 27S9-VV 1 1/8 ODF 5 13/16 5 1/8 7 5/8 3 11/16 3DHY00242 SFD 54S11-VV 1 3/8 ODF 10 5/16 8 1/4 12 1/4 3 11/16 4 1/2DHY00243 SFD 54S13-VV 1 5/8 ODF 9 29/32 8 1/4 12 5/32 3 11/16 4 1/2

Dimensional Data

C + .078A + .062B + .020

D

RSP-PRC022-EN76

System Protectors

CSFD Compact Suction LineFilter-Drier

Application• The CSFD has a compact 14 cubic inch,

solid block desiccant core, design thatis perfect for short lay-ins

• Compact suction line filter drier formoisture, acid and contaminantremoval

• For use with CFC, HCFC and HFCrefrigerants

Features• Dual access valves• High acid removal• Solid copper fittings• Corrosion resistant epoxy powder paintfinish

Specifications• Maximum working pressure:500 psig**

• UL file number: SA 3124• CSA file number: LR 100624• Filtration: 40 micron

Nomenclature Example: CSFD 14S4- VVCSFD 14 S 4 VVSeries Unit Size S = ODF Connection Dual

Connection Size (in 1/8”) Access Valves

Dimensional Data

A

B

C

ServiceFirst Connection Dimensions (in)Item # Model Type (in) A B C

DHY00811 CSFD-14S4-VV 1/2 SOLDER 4 1/4 2 3/4 4 5/8DHY00812 CSFD-14S5-VV 5/8 SOLDER 4 1/2 2 3/4 4 5/8DHY00813 CSFD-14S6-VV 3/4 SOLDER 4 3/8 2 3/4 4 5/8DHY00814 CSFD-14S7-VV 7/8 SOLDER 4 9/16 2 3/4 4 5/8DHY00815 CSFD-14S9-VV** 1 1/8 SOLDER 4 7/8 2 3/4 4 5/8

**400 Maximum Working Pressure

77RSP-PRC022-EN

System Protectors

ASK-HH Suction Line Filter-Drier

Application• Alco’s ASK utilizes a solid core with anHH blend to maximize acid, moistureand wax removal

• Suction line filter drier for moisture,acid and contaminant removal

• For use with CFC, HCFC and HFCrefrigerants

Features• Dual access valves• Corrosion resistant epoxy powder paint

finish• Charcoal blend for soluble contaminant

and wax removal• Solid copper fittings

Specifications• Maximum working pressure: 500 psi• UL file number: SA 3124• CSA file number: LR 100624

LR 32462• Filtration: 40 micron

Nomenclature Example: ASK 165S-V-HHASK 16 5 S VV HH

Series Unit Size Connection S = ODF Dual Charcoal(in cu. in.) Size connection Access Blend

(in 1/8”) Valves

ServiceFirst Catalog Connection Dimensions ShipItem # Number Size & Style A B D E F 1 Wt. Lbs.

DHY00905 ASK 165S-VV-HH 5/8 ODF 6 3/8 5 1/8 5/8 4 5/8 3 9/64 2DHY00806 ASK 166S-VV-HH 3/4 ODF 6 3/4 5 1/2 3/8 4 5/8 3 9/64 2DHY00807 ASK 167S-VV-HH 7/8 ODF 6 15/16 5 7/16 3/4 4 5/8 3 9/64 2DHY00972 ASK 306S-VV-HH 3/4 ODF 9 11/16 8 9/16 5/8 7 1/2 3 9/64 3 3/4DHY00973 ASK-307S-VV-HH 7/8 ODF 9 7/8 8 3/8 3/4 7 1/2 3 9/64 3 3/4DHY00808 ASK 309S-VV-HH 1 1/8 ODF 10 3/16 8 3/8 15/16 7 1/2 3 9/64 3 3/4

Dimensional Data

*B Indicates lay-in length

D

F Dia.

!

E

B*

A

RSP-PRC022-EN78

System Protectors

AMI Moisture-LiquidIndicators

Application• Alco’s AMI was designed to provide an

accurate methodof determining themoisture content of a system’srefrigerant

• Premium Patented 3% High AccuracyMoisture Indicator for CFC, HCFC, andHFC refrigerants including R-410A

• AMI-2 Series for OEM T-Drillapplications (through 1 1/8” sizes) - Seepage 79

Features• 3% relative humidity indication

compared to 10% paper indicators• Single indicator for all common

refrigerants• Accurate color calibration at low ppm

levels and higher temperatures• Wide angle viewing/high visibility

window for ease of monitoring• All brass corrosion resistant body• Solid copper fittings

Specifications• 3% relative humidity sensitivity• Maximum working pressure: 600 psig•

• UL file number: SA 4876• CSA file number: LR 32462

Nomenclature Example: AMI 1SS4AMI 1 SS 4

Moisture Design Series Connection ConnectionLiquid 1 = standard Style Size

Indicator connection SS - Sweat x Sweat (in 1/8”)Series 2 = bushing style

Ordering Information For AMI

ServiceFirst Catalog ConnectionItem # Number Size

GLS00112 AMI-1MM2 1/4 SAEGLS00113 AMI-1MM3 3/8 SAEGLS00114 AMI-1MM4 1/2 SAEGLS00115 AMI-1MM5 5/8 SAEGLS00116 AMI-1FM2 1/4 SAEGLS00117 AMI-1FM3 3/8 SAEGLS00118 AMI-1FM4 1/2 SAEGLS00119 AMI-1MU2 1/4 SAEGLS00120 AMI-1MU3 3/8 SAEGLS00121 AMI-1MU4 1/2 SAEGLS00122 AMI-1MU5 5/8 SAEGLS00124 AMI-1FU4 1/2 SAEGLS00125 AMI-1SS2 1/4 SAEGLS00126 AMI-1SS3 3/8 ODFGLS00127 AMI-1SS4 1/2 ODFGLS00128 AMI-1SS5 5/8 ODFGLS00129 AMI-1SS7 7/8 ODFGLS00130 AMI-1SS9 1 1/8 ODFGLS00131 AMI-1SU2 1/4 ODF x 1/4 SAEGLS00132 AMI-1SU3 3/8 ODF x 3/8 SAEGLS00133 AMI-1SU4 1/3 ODF x 1/2 SAEGLS00836 AMI-1TT2 1/4 ODFGLS00837 AMI-1TT3 3/8 ODFGLS00838 AMI-1TT4 1/2 ODFGLS00839 AMI-1TT5 5/8 ODFGLS00840 AMI-1TT7 7/8 ODFGLS00841 AMI-1TT9 1 1/8 ODFGLS00842 AMI-1TT11 1 3/8 ODF

Moisture Content Color Code (ppm H2O)

Indication Very Dry (Dark Blue) Dry/Caution (Purple) Caution/Wet (Pink) Wet (Salmon)Liquid Temperature 75°F 100°F 125°F 75°F 100°F 125°F 75°F 100°F 125°F 75°F 100°F 125°F

R-12 1.4 2.5 4 5 9 15 15 27 45 25 43 70R-134A 20 35 60 35 55 85 90 120 150 130 160 190

R-22 25 35 50 40 65 90 90 130 185 145 205 290R-407C 26 40 64 42 68 109 94 144 230 150 230 370R-410A 30 55 75 50 85 120 110 190 270 165 290 420

R-404A/507 15 25 45 33 50 80 80 110 140 120 150 180R-502 2.6 5 8 10 18 30 30 54 90 50 90 150

A minimum period of 12 hours is recommended after installation of the Moisture-Liquid Indicator before attempting to accurately determine system moisture content.

Replacement Parts For AMI

ServiceFirstItem # Part Number

KIT04996 Lens Cap 12740-1KIT06235 “O” Ring PS1525-2KIT05013 Lens Assembly Kit X12978-1

(Consists of lens assembly,lens cap and “O” ring)

AMI Internals

O-Ring

LensAssembly

Lens Cap

Body

79RSP-PRC022-EN

System Protectors

Dimensional Data

Type “MM”(Male Flare s Male Flare)

B

A

D

BA

D

CC

Type “FM”(Female Flare x Male Flare)

Type “MU”(Male Flare x Female Flare Swivel Nut)

B

A

D

Type “SS”(Sweat x Sweat)

A

B

E

DC

Type “TT”

A

D

E C

Type “UU”

C

D

A

C

A

BE

D

Type “FU” And “SU”(Female Flare x Female Flare Swivel Nut)And (Sweat x Female Flare Swivel Nut)

C

SpecificationsType Connection

Number Size A B C D EAMI - 1MM2 1/4 SAE 3 1/8 1 9/16 11/32 1 3/16AMI - 1MM3 3/8 SAE 3 3/8 1 11/16 11/32 1 3/16AMI - 1MM4 1/2 SAE 3 5/8 1 13/16 15/32 1 7/16AMI - 1MM5 5/8 SAE 3 7/8 1 15/16 15/32 1 7/16AMI - 1FM2 1/4 SAE 2 3/4 1 3/16 11/32 1 3/16 --AMI - 1FM3 3/8 SAE 3 1 5/16 15/32 1 7/16AMI - 1FM4 1/2 SAE 3 7/32 1 13/32 15/32 1 7/16AMI - 1MU2 1/4 SAE 3 29/32 1 9/16 11/32 1 3/16AMI - 1MU3 3/8 SAE 4 3/8 1 11/16 11/32 1 3/16AMI - 1MU4 1/2 SAE 4 23/32 1 13/16 15/32 1 7/16AMI - 1MU5 5/8 SAE 5 3/32 1 15/16 15/32 1 7/16AMI - 1FU3 3/8 SAE 4 1 5/16 15/32 1 7/16AMI - 1FU4 1/2 SAE 4 5/16 1 13/32 15/32 1 7/16AMI - 1SS2 1/4 ODF 2 1/4 1 1/8 11/32 1 3/16 5/16AMI - 1SS3 3/8 ODF 2 1/4 1 1/8 11/32 1 3/16 5/16AMI - 1SS4 1/2 ODF 2 5/8 1 5/16 15/32 1 7/16 3/8AMI - 1SS5 5/8 ODF 2 5/8 1 5/16 15/32 1 7/16 1/2AMI - 1SS7 7/8 ODF 3 1/8 1 9/16 39/64 1 3/4 3/4AMI - 1SS9 1 1/8 ODF 3 3/8 1 11/16 43/64 1 59/64 7/8AMI - 1SU2 1/4 ODF x 1/4 SAE 3 15/32 1 1/8 11/32 1 3/16 5/16AMI - 1SU3 3/8 ODF x 3/8 SAE 3 9/16 1 1/8 11/32 1 3/16 5/16AMI - 1SU4 1/2 ODF x 1/2 SAE 4 3/32 1 5/16 15/32 1 7/16 3/8AMI - 1SU5 5/8 ODF x 5/8 SAE 4 7/32 1 5/16 15/32 1 7/16 1/2AMI - 1TT2 1/4 ODF 4 57/64 11/32 1 3/16 5/16AMI - 1TT3 3/8 ODF 4 57/64 11/32 1 3/16 5/16AMI - 1TT4 1/2 ODF 4 59/64 15/32 1 7/16 3/8AMI - 1TT5 5/8 ODF 4 29/32 15/32 1 7/16 1/2AMI - 1TT7 7/8 ODF 6 23/64 39/64 1 3/4 3/4AMI - 1TT9 1 1/8 ODF 6 19/64 43/64 1 59/64 7/8AMI - 1UU3 3/8 x 3/8 FLARE SWIVEL 4 7/8 11/32 1 3/16AMI - 1UU4 1/2 x 1/2 FLARE SWIVEL 5 9/16 15/32 1 7/16AMI - 1UU5 5/8 x 5/8 FLARE SWIVEL 6 1/64 15/32 1 7/16 --

RSP-PRC022-EN80

B

System Protectors

AMI-2 Series

Dimensions

A Dia.

C

Roughing In Dimensions

SpecificationsServiceFirst Type Connection

Item # Number Size A Dia. B CAMI-2S5 5/8 ODM .63 1.41 1.16AMI-2S7 7/8 ODM .875 1.34 1.09AMI-2S9 1 1/8 ODM 1.13 1.25 1.00

Roughing In Dimensions

SpecificationsServiceFirst Type Connection

Item # Number Size A Dia. B CAMI-2S11 1 3/8 ODM 1 3/8 1 9/16 1 5/16AMI-2S13 1 5/8 ODM 1 5/8 1 11/16 1 7/16AMI-2S17 2 1/8 ODM 2 1/8 1 15/16 1 11/16

A Dia.

CB

AMI - 2 And TeeStraight Thru Configuration

AMI - 2 And TeeReplacing An Elbow

81RSP-PRC022-EN

System Protectors

ALM Liquid Moisture Indicator

Application• Alco’s economical hermetic moistureindicator utilizes a 10% relativehumidity indicator

• Hermetic Moisture Indicator for CFC,HCFC, and HFC refrigerants

Nomenclature Example: ALM 1TT4ALM 1 TT 4

Liquid Moisture Design Series Connection Style Connection SizesIndicator 1 = standard TT = ODF (in 1/8”)

Series connection extended ends

D

Dimensional Data

A

B B

CC

“TT”

Ordering Information For ALM

ServiceFirstItem # Type Connection A B C D

GLS00181 ALM 1TT2 1/4 x 1/4 ODF 4 61/64 1/4 5/16 1 1/8GLS00182 ALM 1TT3 3/8 x 3/8 ODF 4 61/64 3/8 5/16 1 1/8GLS00183 ALM 1TT4 1/2 x 1/2 ODF 4 63/64 1/2 3/8 1 1/8GLS00184 ALM 1 TT5 5/8 x 5/8 ODF 4 27/32 5/8 1/2 1 1/8GLS00185 ALM 1 TT7 7/8 x 7/8 ODF 6 9/32 7/8 3/4 1 1/8

Moisture Content Color Code (ppm H2O)

Indication Dry (Green) Caution Wet (Salmon)Liquid Temperature 75°F 100°F 125°F 75°F 100°F 125°F 75°F 100°F 125°F

R-12 Below 7 Below 13 Below 22 7-12 13-18 22-28 Above 12 Above 18 Above 28R-134A Below 100 Below 130 Below 175 100-150 130-160 175-220 Above 150 Above 160 Above 220

R-22 Below 100 Below 140 Below 175 100-150 140-200 175-220 Above 150 Above 200 Above 220R-404A/507 Below 75 Below 90 Below 100 75-110 90-120 100-130 Above 110 Above 120 Above 130

R-502 Below 50 Below 65 Below 80 50-70 65-90 80-105 Above 70 Above 90 Above 105

Features• Hermetically sealed to eliminate thepotential of external leakage

• Color calibrated and easily read• Solid copper fitting

Specifications• 10% relative humidity sensitivity• Maximum working pressure: 500 psig• UL file number: SA 4876• CSA file number: LR 32462

RSP-PRC022-EN82

Storage Devices

A-AS Suction Accumulators

Application• Alco’s A-AS suction line accumulators

are available for systems through 28.5tons nominal capacity

NomenclatureA AS 3 12 5

FittingAlco Accumulator Diameter Height Size

Suction (in inches) (in inches) in 1/8”Above Example: A-AS 3 125

• Suction line accumulator for CFC,HCFC, HFC refrigerants

Features• Designed to operate in a range of +40oF

to -40oF evaporator temperature• Fusible plug on larger diameter units• Solid copper fittings• Corrosion resistant epoxy powder paint

finish• Inlet deflector that blends refrigerant

flow to prevent internal splashing andaid in the collection of refrigerant oil inthe bottom connection of theaccumulator

Specifications• Maximum working pressure: 300 psig• UL file number: SA 7973• CSA file number: LR 100624• Fusible Plug 430oF

Ordering Information for A-AS

A B C D Holding Capacity (Lbs.)FItting Unit Diameter Height Fitting Tons 50%Full

ServiceFirst Model Size Weight In In Separation R-22 40°F LIQUID 40°F LiquidItem # Number Nominal (Lbs.) Inches Inches (In.) (+40°F) R22/R134a R404A/R507

ACC00120 A-AS 3 841 1/2 2.0 3 8 1.63 2 1.5 1.5ACC00121 A-AS 3 1051 5/8 2.4 3 10 1.63 3 2 2ACC00122 A-AS 3 1251 5/8 2.9 3 12 1.63 3 3 2.5ACC00123 A-AS 3 1261 3/4 2.9 3 12 1.63 4 3 2.5ACC00124 A-AS 3 1451 5/8 3.3 3 1 5 1.63 3 3.5 3ACC00125 A-AS 3 1461 3/4 3.3 3 14 1.63 4 3.5 2.75ACC00126 A-AS 4 64 1/2 2.8 4 6 2.5 2 2.5 2ACC00127 A-AS 4 65 5/8 2.8 4 6 2.5 3 2.5 2ACC00128 A-AS 4 105 5/8 4.6 4 10 2.5 3 4 3.5ACC00129 A-AS 4 106 3/4 4.6 4 10 2.5 4 4 3.5ACC00130 A-AS 5 96 3/4 5.1 5 9 2.75 4 6 5.5ACC00131 A-AS 5 97 7/8 5.1 5 9 2.75 7.3 6 5.5ACC00132 A-AS 5 126 3/4 6.6 5 12 2.75 4 8 7.5ACC00133 A-AS 5 127 7/8 6.6 5 12 2.75 7.3 8 7.5ACC00135 A-AS 5 137 7/8 7.1 5 13 2.75 7.3 8.5 8ACC00134 A-AS 5 139 1 1/8 7.1 5 13 2.75 11.8 8.5 8ACC00136 A-AS 5 179 1 1/8 8.4 5 17 2.75 11.8 12 10ACC00137 A-AS 5 1711 1 3/8 8.4 5 17 2.75 18.8 12 10ACC00138 A-AS 6 117 7/8 10.0 6 1 1 2.94 7.3 10 9ACC00139 A-AS 6 137 7/8 11.7 6 13 2.94 7.3 12 1 1ACC00140 A-AS 6 139 1 1/8 11.7 6 13 2.94 11.8 12 1 1ACC00141 A-AS 6 1411 1 3/8 12.1 6 14 2.94 18.8 1 5 12ACC00142 A-AS 6 1713 1 5/8 15.4 6 17 2.94 28.5 1 6 1 5ACC00143 A-AS 6 2013 1 5/8 18.1 6 20 2.94 28.5 20 1 6ACC00144 A-AS 6 2513 1 5/8 22.6 6 25 2.94 28.5 25 20

1Not supplied with a fusible plug

Dimensional Data

3/8” - 16 UNC Thread

Oil ReturnOrifice.055”

Inlet Deflector

Fusible Plug

AINLET

D

OUTLET

C

B

83RSP-PRC022-EN

Storage Devices

Accumulator Capacity Tables in Tons of Refrigeration

R-22Model Number -40oF -20oF 0oF +20oF +40oFA-AS 3 84 .4 .6 0.9 1.4 2.0A-AS 3 105 .5 .8 1.4 2.1 3.0A-AS 3 125 .5 .8 1.4 2.1 3.0A-AS 3 126 .72 1.1 1.8 2.8 4.0A-AS 3 145 .5 .8 1.4 2.1 3.0A-AS 3 146 .72 1.1 1.8 2.8 4.0A-AS 4 64 .4 .6 0.9 1.4 2.0A-AS 4 65 .5 .8 1.4 2.1 3.0A-AS 4 105 .5 .8 1.4 2.1 3.0A-AS 4 106 .72 1.1 1.8 2.8 4.0A-AS 5 96 .72 1.1 1.8 2.8 4.0A-AS 5 97 1.3 2.0 3.3 5.1 7.3A-AS 5 126 .72 1.1 1.8 2.8 4.0A-AS 5 127 1.3 2.0 3.3 5.1 7.3A-AS 5 137 1.3 2.0 3.3 5.1 7.3A-AS 5 139 2.1 3.3 5.3 8.3 11.8A-AS 5 179 2.1 3.3 5.3 8.3 11.8A-AS 5 1711 3.4 5.3 8.5 13.2 18.8A-AS 6 117 1.3 2.0 3.3 5.1 7.3A-AS 6 137 1.3 2.0 3.3 5.1 7.3A-AS 6 139 2.1 3.3 5.3 8.3 11.8A-AS 6 1411 3.4 5.3 8.5 13.2 18.8A-AS 6 1713 5.1 8.0 12.8 20.0 28.5A-AS 6 2013 5.1 8.0 12.8 20.0 28.5A-AS 6 2513 12.8 20.8 28.5

The maximum capacity in tons recommended is based on a pressure drop through the accumulator equivalent to 1.0oF.Note: 1. The minimum capacity in tons must be no less that 15% of the recommended capacity in order to ensure a

positive return of oil.2. All of the data is based on tons of refrigeration and is not related to horsepower.3. Minimum evaporator temperature of -40oF. Minimum temperature of the suction gas through the accumulator

is 12oF. For operation under conditions that are not within the recommended range, please contact ALCOControls’ Applications Department before proceeding with the installation.

RSP-PRC022-EN84

The use of HFC refrigerants andPolyolester (POE) lubricants for air-conditioning and refrigeration havegenerated new system chemistry relatedproblems. New and redesigned systemprotectors have been developed tocounteract these problems and provide along, reliable life for the operatingrefrigeration system.

Moisture is the major problem causingcontaminate for HFC/POE oil systemsjust as it was for CFC and HCFC systemsusing Mineral oil. Many HFC’s can holdmuch more water than their CFCcounterparts but the oil differences aremuch worse than those of therefrigerant. POE oil can hold as much as10 times more water than Mineral oils.In addition, evacuation has provenineffective at removing this moisture soa filter-drier is required to perform thisfunction.

Water poses a new problem for POE oilsabove and beyond those experiencedwith Mineral oil. POE oil will react withwater to form organic acids at normaloperating conditions in refrigerating andair-conditioning systems. This reactionstarts at water levels as low as 75 ppm.These acids attack system componentsincluding motor insulation and metalliccomponents reducing system life.

To combat the detrimental effects ofwater in HFC and POE oil systems it isimperative to hold moisture levels aslow as possible. It is generally acceptedthat water level must be maintained lessthan 50 ppm in the refrigerant and thesame for the oil. In order to monitorsystem water level a moisture indicatormust be used that can sense changes inmoisture in this ppm range.

Many commercial sightglasses cannotindicate a change at this level in liquidlines that exceed 100°F. This means thatharmful organic acids may be attackingsystem components while the indicatoris showing dry. The AMI has a uniqueelement that has the ability to changecolor at low ppm levels so that properaction can be taken before any systemcomponents are damaged.

It was necessary to redesign standardfilter-driers for increased water removalcapacity to achieve these low moisturelevels. However, since no system isentirely devoid of water upon startupsome organic acids will be generated

and must be removed. The desiccantformulation for the EK and UDK series offilter-driers was designed to provide theoptimal mix of water capacity and acidcapacity to ensure that both harmfulcontaminates are effectively removed.This desiccant mixture contains bothmolecular sieve and activated alumina.The molecular sieve is specificallydesigned to provide maximum drying intoday’s systems. The activated aluminais ideal for capturing the large organicacids that the molecular sieve cannot.

Another aspect of POE oil is the ability tokeep more solid particles in suspensionthan Mineral oil. This is particularlyimportant in retrofitted systems wherepockets of solid contamination are nowflushed from low flow areas and need tobe removed before moving parts in thesystem are damaged. The filter-drier forPOE oils needs to have increased solidparticle holding capacity with minimalimpact to refrigerant flow capacity orpressure drop.

HFC Refrigerants andPOE Lubricants

Figure 2. Acid generation in a 1.5 ton R-134a air-conditioning system

The filter-drier should also haveimproved contaminate removalefficiency as well to ensure that allparticles are captured the first time theyenter the filter-drier. The ability toremove smaller particles is alsoadvantageous. The EK series filter-driersprovide a unique combination of thesecharacteristics to provide outstandingfiltration as shown in Figure 3.

The filter-driers for use in HFC and POEoil systems must maintain the systemdry and free of any acids that may havebeen generated. However, since watercapacity is of primary importance thefilter-drier should contain a higherpercentage of molecular sieve than wasrequired for CFC and HCFC systems. Butmolecular sieve alone is insufficientsince it has virtually no organic acidcapacity. An organic acid removaldesiccant must be used such asactivated alumina to ensure low acidlevels are maintained. In addition, thefilter-drier should also have increasedfiltration capacity and efficiency. The EKseries of filter-driers provides the optimalcombination of these properties toensure the long, trouble-free life of anyair-conditioning or refrigeration system.

Figure 1.

85RSP-PRC022-EN

Figure 4. Filtration capability of filter-driers

Figure 3. Dry indication water level

HFC Refrigerants andPOE Lubricants

The moisture indicating sightglass mustalso indicate moisture level in the rangeof less than 50 ppm moisture. Also, itmust be able to perform this function atthe temperature of the liquid line onwhich it is placed. Many sightglassescannot perform this function at all liquidline temperatures. This low levelindication ability is necessary to ensurethat the system moisture never exceedsthe level at which organic acid formationstarts. The AMI moisture indicatingsightglass provides this low leveldetection ability.

Universal Acid Test Kit

ApplicationThe Universal Acid Alert Test Kitprovides a positive indication of whetherthe acid level of the refrigeration oil issafe or unsafe.

For use with both Mineral and POE Oils!

Features• Quick and easy test kit• Universal acid test kit for use with allrefrigeration lubricants

• By changing the percentage of oilsample taken, the acid number of theoil can be accurately determined

• Phase separation of the chemicals inthe kit provide a positive color changeregardless of the color and condition ofthe oil

Ordering Information

ServiceFirstItem # Description

KIT06815 AA Kit Universal

RSP-PRC022-EN86

Regulators

The application of air-cooled condensersfor year-round operation, or duringperiods of low ambient temperatures,requires some means of control tomaintain adequate condensing pressuresthat ensure proper system performance.It is essential that proper liquid refrigerantpressure be controlled to:

1. Maintain liquid subcooling and preventliquid line flash gas.

2. Provide adequate pressure at the inletside of the Thermo Valve to obtainsufficient pressure drop across thevalve port.

3. Properly operate systems with hot gasdefrost or hot gas bypass.

4. Provide adequate temperature foroperation of heat reclaim systems.

Without proper control of condensingpressure, serious consequences in theway of poor refrigeration and componentdamage can occur. ALCO’s HeadMasterControl offers an efficient and economicalapproach to this common industryproblem on air cooled condensers.

The HeadMaster 3-Way Head PressureControl eliminates the need for specialpiping or multiple control valves. As asingle unit it simplifies piping andreduces installation costs.

Fundamentals of HeadMaster Head Pressure Controls

Figure 1: HeadMaster HP Valve CutAwayView

HeadMaster HP OperationThe HP control is a three-waymodulating valve controlled by thedischarge pressure. The charged domeexerts a constant pressure on top of thediaphragm. At high ambient airtemperature, bypass gas entering Port Bis allowed under the diaphragm where itcounteracts the pressure of the domecharge. This upward push on thediaphragm allows the seat disc to sealagainst the top seat, preventing flowfrom Port B (discharge gas) while flowfrom Port C is unrestricted (see Figure 1).

As ambient air temperature falls, anuncontrolled air cooled condenser willexhibit a corresponding decrease inhead pressure. As the discharge (bypass)pressure falls, it no longer counteractsthe dome charge pressure and thediaphragm moves downward, movingthe pushrod and seat disc towards thebottom seat. NOTE: This allowsdischarge (bypass) gas to be meteredinto the receiver, creating a higherpressure at the condenser outlet. Thehigher pressure at the condenser outletreduces the flow from Port C and causesthe level of condensed liquid to rise inthe condenser.

87RSP-PRC022-EN

Regulators

Figure 2: Typical 3-Way Valve Head Pressure Control Application

Charge TypeService Reference Code A B C

To Be Used With Refrigerant TypeR-134a R-22 R-404A/R-507

System Condensing Pressure Set Point* (PSIG)Valve HP5, HP8 110 185 215Type HP14 120 175 215

* For Corresponding Condensing Temperature, see P-T Chart.

The flooding of the condenser withliquid reduces the available condensingsurface. The result is to increase thepressure in the condenser and maintainan adequate high side pressure. Figure 2illustrates a typical application of the 3-way control valve. This system isperhaps the most economical andreliable means to accomplish dischargepressure control. The three-way valve asshown in figure 1 is a fixed, non-adjustable valve. The wholesalerreplacement setting is normallyfurnished for a pressure correspondingto 95° to 98°F condensing temperaturefor the given system refrigerant.

As with all head pressure controlapplications, additional liquid receivercapacity is required to prevent loss of aliquid seal in the receiver when thecondenser is flooded. The receiver mustbe large enough to hold the total systemcharge. The total system charge consistsof the following:

A. An operating charge which is thenecessary pounds of refrigerant tooperate the system during summer(high ambient temperature)conditions.

B. An additional charge equaling thenumber of pounds of refrigerantrequired to flood the condenser withliquid. The condenser must be filledwith liquid to point where a minimumhead pressure is created for coldweather (low ambient temperature)conditions.

NOTE: Should the outdoor temperaturefall below design conditions, additionalrefrigerant will be required.

The total of A and B is the total chargenecessary for satisfactory systemperformance during the lowest expectedambient air temperature conditions.During summer operation the receivermust be sized to safely hold the totalsystem charge. Good refrigerationpractice states that the total systemcharge should not exceed 75% of thereceiver capacity.

CAUTION:

1. The HP control should not be used ona system which does not have a liquidreceiver or on one with a receiverwhich is too small. If the receiver doesnot have adequate storage space, therefrigerant will back up in thecondenser to produce excessivelyhigh discharge pressures during highambient air temperatures, with re-sulting system damage and/orpersonal injury.

2. The HP control should be used onlyon systems which employ aThermostatic Expansion Valve.

RSP-PRC022-EN88

Regulators

Fundamentals of HeadPressure Controls

Installation of HeadMaster HP SeriesIn general, head pressure controlsystems of this type are used onrefrigeration systems that aretemperature operated. This means thatthe compressor is started by athermostat or the system operates on apump down cycle, where the thermostatcontrols the liquid line solenoid valveand the compressor starts on a rise insuction pressure with a low pressureswitch.

On systems that are pressure operated,migration of the refrigerant to the coldcondenser on the “off” cycle should beprevented. If the system does notoperate on a pump down cycle,migration can take place through somecompressors, from the suction line to thecondenser. The use of crankcase heaterswill prevent liquid from condensing inthe crankcase, but will not eliminatemigration to the cold condenser. If thesystem is properly charged, the filledcondenser will permit the excess toremain in the receiver and low side.

Under certain conditions where thereceiver is located in a warm ambient, acheck valve in the liquid drain linebetween the HeadMaster control and thereceiver may be required to prevent theliquid receiver pressure from equalizingto that of the condenser during the “off”cycle. This enables the system to start ona pressure switch. Some systems mayrequire a time delay on the low pressureswitch. Condenser fans should not becycled when using the HeadMastercontrol. The sudden changes in highside pressure caused by fan cycling willresult in erratic Thermostatic ExpansionValve performance, and shortened headpressure control life.

UL File No. SA5312CSA File No. LR44005

HP Series Capacity and SelectionThe nominal HP control capacity in tonsfor various refrigerants is shown in Table1 (see page XX) for R134a, R22 andR404A/R507. The nominal capacity isbased on 100°F liquid, 40°F evaporatorand the pressure drop shown. To obtaincapacities in tons at other liquid andevaporator conditions, multiply thenominal capacity at the desired pressuredrop by the factor in Table 2 (page XX)given for the existing liquid temperatureand evaporator temperature.

NOTE: Do not select a valve for a capacityrating exceeding 5 psi pressure drop fromPort C to Port B or for a system with morethan 20 psi pressure drop across thecondenser.

During normal ambient conditions, theavailable liquid sub-cooling in thecondenser will be adequate to cover theexisting pressure drop through theHeadMaster control.

If a valve is selected for a given flow rate,the resulting pressure drop must notcause the liquid pressure to drop belowsaturation and produce flash gas.

If sufficient sub-cooling is not available tocover this pressure drop, it is suggestedthat more than one valve be installed inparallel to reduce the pressure drop totolerable limits. Do not parallel valves ofdifferent capacities. Liquid drain linesfrom the condenser to receiver aregenerally sized for a velocity of150 ft./min.

Additional RefrigerantOn most systems, an additional amountof refrigerant will be required. It isessential to have enough to completelyfill the condenser for the lowest ambientcondition.

Factory SettingThe HeadMaster Control is factory-setto provide an average condensingtemperature consistent with goodsystem performance. The completetype number includes the servicereference code, port size, connectionsize and style. When ordering, be sureto specify the complete type number.

HP Parallel Piping

R

R

C

B C

B

89RSP-PRC022-EN

Regulators

Complaint

Low head pressureduring operation.

Possible Cause

Valve unable to throttle ‘C’ port:

a) foreign material wedged between ‘C’ portseat & seat disc.

b) power element lost its charge.

c) insufficient wintertime system charge.

Wrong charge pressure in valve for systemrefrigerant.

Receiver exposed to low ambient conditions isacting as condenser.

Hot gas bypass line restricted or shut off.

Compressor not pumping or restriction in liquidline, or low side causing very low suctionpressure.

Condenser fan or fans not running or turning inthe wrong direction.

Fan cycling.

Pressure drop through condenser exceedsallowable 20 psi forcing ‘B’ port partially open.

Condenser unersized or air flow restricted orshort circuiting.

‘B’ port wedged open due to foreign materialbetween seat and seat disc.

‘B’ port seat damaged due to foreign material.

Wrong charge pressure in valve for systemrefrigerant.

Excess system charge or air in system.

Obstruction or valve closed in discharge orcondenser drain line.

Liquid line solenoid fails to open.

Remedy

a) Artificially raise head pressure & tap valvebody to dislodge foreign material.

b) Change valve.

c) Add refrigerant per table 3.

Change valve.

Insulate the receiver.

Clear obstruction or open valve.

Change or repair compressor or clear obstructionor other reason for low suction pressure.

Replace or repair fan motor, belts, wiring orcontrols as required.

Run condenser fans continuously while thesystem is running.

Repipe, recircuit, or change condenser asrequired to reduce condenser pressure drop toless than 20 psi.

Increase size of condenser or remove air flowrestriction or short circuit as required.

Artificially reduce head pressure below valve setpoint and tap valve body with system running todislodge foreign material.

Change valve.

Change valve.

Purge or bleed off refrigerant ornoncondensables as system requires.

Clear obstruction or open valve.

Check solenoid.

System runshigh head pressureorcycles onhigh pressure cut-out.

HeadMaster Service Hints (during low ambient operation)

RSP-PRC022-EN90

Regulators

Head Pressure Control

Coils in ParallelOne HP Series Valve controlling both coils.

Coils in ParallelOne HP Series Valve controlling each coil.

Coils in ParallelOne HP Series Valve controlling outdoor coil only.

Coils in SeriesOne HP Series Valve for both coils.

Coils in SeriesTwo HP Series Valves – one on each coil.

91RSP-PRC022-EN

Fundamentals of Hot GasBypass

Demand continues to mount forimproved comfort conditioningcombined with lower operating costs.New architectural designs have createdreal problems for contractors andengineers to maintain humidity controlat reduced loads, and to control loadvariations. Refrigeration and airconditioning systems are usuallydesigned to provide a given capacity atmaximum conditions. These operatewith little fluctuation throughout anarrow load range. However, only thelarger size machines make anyprovisions for operation at reducedcapacity. In some systems, integralcylinder unloading, the installation of agas engine drive with variable speedcontrol, or even multiple smallersystems, provide a logical solution.

Function — Hot Gas Bypass MethodMany manufacturers now recommenduse of a modulating control valve toprovide a metered flow of compressordischarge gas to the system low side, ina proportion that will balance the systemcapacity to the load demand. This iscommonly known as the hot gas bypassmethod. It permits full modulation ofcapacity on all types of reciprocatingcompressors, and extends capacityreduction below the last step of cylinderunloading.

Basically, the system must provide ameans of bypassing high pressurerefrigerant to the system low pressureside, in order to maintain operation at agiven minimum suction pressure. Properbypass control can be accomplished bya modulating type pressure regulator,which opens on a decrease in valveoutlet pressure.

Operation of Bypass ValvesBypass pressure regulators are groupedinto the following categories:1. Direct acting unbalanced port valves

(figure 3).2. Direct acting balanced port valves

(figure 4)3. Pilot operated valves (figure 5)

Any of these regulators are availablewith either an adjustable setting, or afixed, non-adjustable setting.

Figure 3. DGRE adjustable hot gas bypassregulator.

Figure 4. Balance port CPHE adjustable field-serviceable hot gas bypass regulator.

Figure 5. FA8 pilot operated hot gas bypassregulator.

Regulators

RSP-PRC022-EN92

Regulators

Figure 6. Hot gas bypass from discharge through FA8 regulator to suction.

Note: Bypass flows against suction to create a good mix.

! !

!

!

!

!

Discharge

Compressor

FA8Bypass

Regulator

Suction

OptionalElbow Or Tee

! !

LiquidInjectionThermo

Valve

LiquidInjection Solenoid

Valve

Applications

Hot Gas Bypass to Compressor SuctionLineFigure 6 shows what is possibly themost common hot gas bypass system.In this system, the bypass line is takendirectly from the compressor dischargeline, through a bypass regulator, and intothe suction line at the compressor. Whilethe hot gas bypass regulator isconsidered a downstream control, thereis a big difference in function between aCrankcase Regulator (FA5) and a hot gasregulator (FA8).

Pilot operated bypass valve mainregulators have a long stroke stem witha restrictor plug characterized by either aparabolic or vee port restrictor plugdesign. This prevents the valve fromoperating close to the seat wherepressure differential unbalance mayoccur, eliminating the need for abalanced port design.

The characterized port will providesmooth bypass flow modulation. Pilotoperated valves usually have the extrafeatures of a manual opening stem fortesting or emergency operation, flangedconnections, synthetic tight seatingseats, and replaceable parts. Hot gasbypass valves can be applied to asystem in several general ways, differingonly in the point to which the hot gas isto be bypassed. Several mixing methodsare available. The one generallyrecommended is piped so that dischargegas is admitted to the suction line to flowagainst the direction of the suction gasas in figure 6.

Figure 7. Hot gas bypass using type LCL liquid injection valve.

93RSP-PRC022-EN

Regulators

Applications

Bypass to Evaporator InletAnother method is to bypass the hotdischarge gas to the evaporator inlet,usually between the Thermo Valve andthe refrigerant distributor (see figures 9and 10). This provides distinctadvantages. The artificial load imposedon the evaporator causes the ThermoValve to respond to the increase insuperheat, eliminating the need for theliquid injection valve. The evaporatorserves as an excellent chamber toprovide homogeneous mixing of thegases before reaching the compressor. Itis essential that this type system beequipped with a Venturi flow typerefrigerant distributor (i.e., no restrictororifice).

Hot gas bypass into the evaporator issuggested when the evaporatorelevation is below the compressor, toprevent oil trapping due to low velocityat low loads. This assures proper oilreturn. Although there are manyadvantages to this system, it is notgenerally used on a multiple coil system,or where the evaporator sections may belocated a distance from the compressor.The coil should be a free drainingcircuiting design to prevent the increasein velocity, due to forcing a largequantity of trapped liquid out of the lowside, which in some cases may have

enough volume to flood the compressorcrankcase. NOTE: Separate regulatorsmust be used for each evaporator whenbypassing to multiple evaporatorslocated below the compressor tofacilitate oil return.

Bypass to flooded evaporators andsuction line accumulators also presentspecial cases. Contact the equipmentmanufacturer or the bypass control valvemanufacturer for specific, detailedinformation.

Solenoid Valve for Positive Shut-off &Pump-down CycleIt is recommended that a solenoid valvebe installed ahead of the bypassregulator. This permits the system tooperate on an automatic pump-downcycle. Applications which use the pilotoperated FA8 series valve are factoryassembled with integral solenoid andneed no separate solenoid installed inthe discharge line.

Liquid Injection Applications

Thermo Valves for Liquid InjectionWhen hot gas is bypassed directly intothe suction line, it is necessary to makesome provision for desuper-heating thegas returning to the compressor.Without a small Thermo valve to reducesuction gas temperature to tolerablelimits, compressor damage may occur.Standard Thermo Valves cannot be

adjusted for control in excess of 20°Fsuperheat and, therefore, are notgenerally recommended. Liquid InjectionThermo Valves with special adjustmentranges are used to conform withcompressor manufacturer temperaturerecommendations.

To simplify selection, ALCO hasdeveloped Liquid Injection ThermoValves with four basic adjustmentranges. These are designated as modelsA, B, C and D. The adjustable superheatrange chart (Table 5, page 97) shows theproper power assembly charge symbolsuffix for a given saturated suctiontemperature and a given superheatedsuction gas temperature entering thecompressor.

Nearly all Thermo valves for liquidinjection may be internally equalized.However, if pressure drop occurs at thevalve outlet due to a distributor, spraynozzle or other restrictive device,externally equalized valves may benecessary.

Model LER and LIR valves are furnishedwith a 1/4” SAE male flare externalequalizer as standard. Other modelsmust include the code letter “E” tospecify the 1/4” SAE male flare externalequalizer connection. Example: LCLEand LJLE.

Figure 9. Direct acting hot gas regulator admitting flow betweenTEV and venturi distributor.

Figure 8. Bullhead the Hot Gas and Liquid Injection in a tee to permitgood mixing.

RSP-PRC022EN94

Regulators

Application and InstallationLiquid injected into a gas to bedesuperheated should be injected in amanner which provides a homogeneousmixing of the liquid and superheatedgas. Desuperheating hot gas bypass inthe suction line may be accomplished inseveral ways.

The preferred method is to bullhead thehot gas and liquid injection in a tee topermit good mixing before it enters thesuction line. A good mix with the suctiongas may be gained by injecting theliquid/hot gas mixture into the suctionline at approximately a 45° angle againstthe flow of suction gas to thecompressor. See figures 7 and 8.

For suction lines 7/8” OD and smaller,the bypass mixture may be introducedinto a tee rather than an angleconnection. For lines larger than 2-5/8”OD, introduce the desuperheated bypassmixture into a 90° ell inserted against theflow of suction gas to the compressor.

Arranging a bypass directly into asuction accumulator is often aconvenient way to obtain properdesuperheating of suction gas.

Introducing the hot gas and liquid intothe suction line with separateconnections is not generallyrecommended.

Note: Excessive suction gas superheatcan cause serious damage to thecompressor. As a safety precaution, thebypass line solenoid valve should bewired in series with a discharge linethermostat.

Figure 10. Hot gas bypass using type LCLliquid injection valve.

95RSP-PRC022-EN

Regulators

Liquid Injection Applications

Special ApplicationsOn systems where evaporator pressureregulators are used, better control can beachieved by locating the bypassregulator equalizer line on thedownstream (outlet) side of the EPR so itresponds to compressor suctionpressure, not evaporator pressure. Thisresults in nearly constant evaporatorload balance (see figure 11).

Extremely close control can be obtainedwith pneumatic compensation. Anypneumatic controller may be applied toCPH and FA8 regulators with external airconnection. Controllers that respond to:leaving water or air temperature, orentering water or air temperature, aswell as humidity, pressure, etc., are oftenused to reset the hot gas bypassregulator to a setting appropriate for thedesired condition (see figure 12).

Figure 11.

Figure 12.

Solenoid Connection Size Chart

Valve Type Connection Size (in inches)100RB 2T2 1/4 ODF200RB 3 3/8 ODF

200RB 4T4 1/2 ODF200RB 5T5 5/8 ODF200RB 6T5 5/8 ODF240RA 8T5 5/8 ODF240RA 9T7 7/8 ODF240RA 12T7 7/8 ODF240RA 16T9 1-1/8 ODF

Standard Voltage & Frequency Table

FA8 Series Regulators

Voltage Frequency24, 120, 208-240, 480 50/60 Hz. AC

100RB, 200RB, 240RA Series Solenoid Valves

Voltage Frequency24, 120, 120/240, 208-240, 480 50/60 Hz. AC

RSP-PRC022EN96

Regulators

Ordering Instructions PressureRegulators

A. Direct Operated – CPH SeriesWhen ordering, specify:1. The complete valve type number.2. Size and style of connections.3. Type of equalizer.4. Pressure adjustment range.

B. Pilot Operated – FA8 SeriesWhen ordering, specify:1. The complete valve type number.2. Size connections. Flanges are sold separately.3. Solenoid coil voltage & frequency.

Example: FA8-15F, 120/50-60, 1-3/8’’ ODF.

For 1/4’’ male SAE external airconnection for FA8 regulators, orderX10227-2 EAC conversion kit.

Discharge Gas Solenoids

A. Companion Discharge Line Solenoidwith CPH SeriesWhen ordering, specify:1. The complete solenoid type number.2. Solenoid coil voltage & frequency.3. Size line connections.

Liquid Injection Valves & Solenoids

A. Liquid Injection ValveWhen ordering, specify:1. The complete valve type number,

including type equalizer (external orinternal) and charge symbol.

2. Remote bulb tubing length.3. Line connection size & style.

Example: LJLE12B, 5 ft. tubing, 5/8’’ x7/8’’ ODF angle

Flange Interchangeability Table Style & Connections

Angle ConfigurationSize & Style Body Flange Cap Screw

Valve Connections Part PartType Inlet Outlet Number Number

3/8 SAE 1/2 SAE C500-4TCL 3/8 SAE 5/8 SAE C500-5

TCLE 1/2 SAE 5/8 SAE C500-6LCL 1/4 ODF 3/8 ODF C501-1 PS286-5

LCLE 3/8 ODF 1/2 ODF C501-43/8 ODF 5/8 ODF C501-51/2 ODF 5/8 ODF C501-7

Straight-thru Configuration3/8 SAE 1/2 SAE X6669-43/8 SAE 5/8 SAE X6669-11/2 SAE 1/2 SAE X6669-51/2 SAE 5/8 SAE X6669-2

TCL 3/8 ODF 1/2 ODF 9761-5TCLE 3/8 ODF 5/8 ODF 9761-3LCL 1/2 ODF 1/2 ODF 9761-6 PS286-5

LCLE 1/2 ODF 5/8 ODF 9761-41/2 ODF 7/8 ODF 9761-25/8 ODF 5/8 ODF X6346-165/8 ODF 7/8 ODF X6346-175/8 ODF 1-1/8 ODF X6346-187/8 ODF 1-1/8 ODF X6346-34

97RSP-PRC022-EN

Ordering Instructions

Liquid Injection Valves & Solenoids(cont.)

B. Companion Liquid Line SolenoidValveWhen ordering, specify:1. The complete solenoid type number.2. Solenoid coil voltage & frequency (see

chart on p. 95-96).3. Size line connections (see chart on

page 95-96).

Hot Gas Bypass ValveWhen ordering, determine each itembelow & specify:1. System Refrigerant.2. Capacity to be bypassed in tons

(compressor capacity minus systemload equals tons to be bypassed).

3. Evaporator temperature at whichregulator is to operate.

4. Select the appropriate Hot Gas Bypassvalve from Quick Selection Charts thatbegin on page 304 for tons, and page322 for kW.

Example: A refrigerant 134a systemoperating at 30°F evaporator has acompressor capacity of 20 tons against asystem load of 15 tons. To balance theload between compressor and system, 5tons must be bypassed (20 – 15 = 5 tons).Referring to the R134a quick selectionchart for 30°F evaporator and 5 tons tobe bypassed, we find the FA8-12M hasthe proper capacity for this installation. Ifthe hot gas is to be bypassed into thesuction line, a liquid injection valve maybe needed to desuperheat this dischargegas in order to protect the compressor.The proper liquid injection valve isshown with each regulator selection.

Note:1. Selection of regulators is based on a

6° gradient. i.e.: Rated capacity ofregulator will be attained when thesuction pressure falls 6° below thepilot set point.

2. Applications which vary from normalsystem conditions will not affectselection of the regulator, as selectionsare based on average conditions at65°F superheated suction gas enteringthe compressor with isentropiccompression to 100°F saturation plus50°.

Regulators

Table 4. Selection of liquid injection thermo® & solenoid valves to assist hot gas bypasssystems

Liquid Power CompanionInjection All-purpose Assembly Solenoid ForValve!!!!! Cage Part Part Liquid Injection ValveNumber Number Number R134a R22 R404A/R507LCL"""""1##### X22440-1$$$$$ 100RB2 100RB2 100RB2LCL"""""2##### X22440-2$$$$$ 100RB2 100RB2 100RB2LCL"""""3##### X22440-3$$$$$ 100RB2 200RB4 100RB2LCL"""""4##### X22440-4$$$$$ 200RB4 200RB4 200RB4LCL"""""6##### X22440-5$$$$$ XB1019-##### 1$$$$$ 200RB4 200RB5 200RB4LCL"""""7##### X22440-6$$$$$ 200RB5 200RB6 200RB5LCL"""""8##### X22440-7$$$$$ 200RB6 240RA8 200RB6LCL"""""10##### X22440-8$$$$$ 200RB6 240RA8 240RA8LJL"""""11##### XC724-B4$$$$$ 200RB6 240RA8 240RA8LJL"""""12##### XC724-B5$$$$$ 240RA8 240RA9 240RA8LERE13##### X9117-B6B 240RA9 240RA12 240RA9LERE14##### X9117-B7B 240RA9 240RA12 240RA9LERE15##### X9117-B8B XC726-#####2B 240RA12 240RA12 240RA12LERE16##### X9117-B9B 240RA16 240RA16 240RA16LIRE17##### X9166-B10B 240RA16 240RA16 240RA16

!!!!! Type LA(E) Valves are also available for liquid injection valve applications.""""" Add letter “E” for external equalizer. Example: LCLE3.##### Add charge designation A, B, C, or D. (See table below.)$$$$$ Add letter “A” for internal equalizer or “B” for 1/4” SAE male flare external equalizer.*Nominal capacity based on 40°F evaporator and 100°F condensing.

Table 5. LCL (LA) charge codes

RefrigerantSat’d R-134a R-22 R-404A/R-507

Suction Required Suction Gas Temp Required Suction Gas Required Suction GasTemp. 45°F 65°F 45°F 65°F 45°F 65°F40°F — B (GL) — A (CL) — —30°F B (GL) B (GL) — A (CL) — A (CL)20°F B (GL) C (UL) A (CL) B (GL) — A (CL)10°F B (GL) C (UL) B (GL) B (GL) A (CL) B (GL)0°F C (UL) C (UL) B (GL) B (GL) A (CL) B (GL)

– 10°F C (UL) C (UL) B (GL) C (UL) B (GL) B (GL)– 20°F C (UL) C (UL) B (GL) C (UL) B (GL) C (UL)– 30°F C (UL) C (UL) C (UL) C (UL) B (GL) C (UL)– 40°F C (UL) C (UL) C (UL) C (UL) B (GL) C (UL)

( ) Denotes la series valve charge code

RSP-PRC022EN98

Regulators

EGR(E) Direct Acting Hot GasBypass Regulator

EGRE Series Direct Acting Hot GasBypass Regulators are designed for useon light commercial systems. Theyprovide precision system capacitybalance at an economical price. TheEGRE is an adjustable valve.

The adjustable EGR Regulators aresupplied with a factory set point of 50psig (point at which the regulator startsto open), which can be changed byadjustment. Capacity of these regulatorsis based on 6° gradient. Rated capacitywill be attained when the suctionpressure falls 6° below the

Catalog Line Connections Standard Adjustment ShippingNumber Code Size & Style Equalizer 2 Range WeightEGRE-4 1 S3 3/8 ODF 1/4 SAE orEGRE-6 1 S4 1/2 ODF 1/4 ODF 0-80 psig 2-1/2 lbs.EGRE-8 1 S5 5/8 ODF External

1Add connection code to complete catalog number. Example: EGRE-4S4.2Internal equalized style available. To order, omit “E” from catalog number. Example: EGR-4S3.

Ordering Information

ServiceFirst ServiceFirstItem # Description Item # Description

REG00435 EGRE 4 S 4 B SAE EE VAL06394 EGRE 6 S 4 C ODF EEREG00436 EGRE 4 S 5 B SAE EE REG00438 EGRE 6 S 5 B SAE EEREG00437 EGRE 6 S 4 B SAE EE REG00429 EGRE 8 S 4 B SAE EE

VAL07515 EGRE 8 S 5 B SAE EE

Features• Compact hermetic construction.• Contoured power assembly for long

life.• ODF line connections.• Balanced port design.

Options• External or internal equalizer.• Sizes available: 4 thru 8.

Specifications• Safe working pressure: 440 psig• Adjustment range: 0-80 psig (factory

setting 50 psig)• UL file number SA5312• CSA file number LR44005

Nomenclature Example: EGRE 6S4 B SAE EEEGR E 6 S 4 B SAE EE

Valve Series External Equalizer Size Connection Connection External Equalizer Connection External(omit for internal S = ODF connections (in 1/8") A = NONE, B = 1/4” SAE Equalizer

equalizer) C = 1/4” ODF Type

Nominal Capacity Table in Tons (kW)

Valve R-12 R-134a R-22 R-407C R-507/R-404A R-502EGR(E)-4 1.6 (5.6) 1.8 (6.2) 2.9 (10.1) 2.9 (10.1) 2.8 (9.7) 2.6 (9.0)EGR(E)-6 2.0 (6.9) 2.4 (8.3) 3.8 (13.2) 3.8 (13.2) 3.5 (12.1) 2.9 (10.1)EGR(E)-8 3.6 (12.5) 4.2 (14.6) 6.7 (23.2) 6.7 (23.2) 6.3 (21.9) 5.9 (20.5)

See EGRE Extended Capacity Tables (page 102 in tons) before completing selection.

corresponding set point saturationtemperature. This lower temperature, atwhich the regulator is rated, is termed“evaporator temperature” in theselection tables (on page 102).

When the suction pressure decreasesbelow the set point, the regulator opensand allows discharge gas to bebypassed. The discharge gas may bebypassed into the evaporator or thesuction line. When bypassed to thesuction line, a liquid injection ThermoValve must be installed to properlydesuperheat the suction gas returning tothe compressor.

99RSP-PRC022-EN

Regulators

DGR(E) Direct Acting Hot Gas Bypass Regulator

DGRE Series Direct Acting Hot GasBypass Regulators are designed for useon residential and light commercialsystems. They provide precision systemcapacity balance at an economical price.The DGRE is an adjustable valve.

The adjustable DGR Regulators aresupplied with a factory set point of 50psig (point at which the regulator startsto open), which can be changed byadjustment. Capacity of these regulatorsis based on 6° gradient. Rated capacitywill be attained when the suctionpressure falls 6° below thecorresponding set point saturationtemperature. This lower temperature, atwhich the regulator is rated, is termed‘‘evaporator temperature’’ in theselection tables (on page 102).

When the suction pressure decreasesbelow the set point, the regulator opensand allows discharge gas to bebypassed. The discharge gas may bebypassed into the evaporator or the

Nomenclature example: DGRE 12S7 B SAE EE

DGR E 12 S 7 B SAE EEValve Series External Equalizer Size Connection Connection EE Connection External

(omit for internal S = ODF connections (in 1/8") A = NONE, B = 1/4” SAE Equalizerequalizer) C = 1/4” ODF Type

Nominal Capacity Table in Tons (kW)

VALVE R-12 R-134a R-22 R-407C R-507/R-404A R-502DGR(E)-12 8.3 (29.4) 9.7 (34.2) 15.4 (54.6) 15.4 (54.6) 14.5 (51.3) 13.6 (48.0)

All capacities shown are based on 40°F Evaporator Temperature, 100°F Condensing Temperature, Valve Full Open, Compressor Discharge Temperature is 50°F higher than IsentropicCompression and 25°F Superheat at the compressor inlet.

See page 102 for DGRE Extended Capacity Tables in tons before completing selection.

DIMENSIONS SHOWN ARE IN INCHES.

DGRE Dimensional Data

suction line. When bypassed to thesuction line, a liquid injection ThermoValve must be installed to properlydesuperheat the suction gas returning tothe compressor.

Features• Compact hermetic construction• Contoured power assembly for long

life

Options• External or internal equalizer

Specifications• Maximum working pressure: 440 psig• Adjustment range: 0-80 psig (factory

setting 50 psig)• UL file number SA5312, CSA file

number 44005

Ordering Information for DGRE Valves

ServiceFirstItem # Description

REG00253 DGRE 12 S 7 B SAE EEREG00254 DGRE 12 S 9 B SAE EE

RSP-PRC022EN100

Regulators

CPH(E) Direct Operated Hot Gas Bypass Regulator

Nomenclature example: CPHE 3 SAE EE 3/8 X 5/8 ODF ANG

CPH E 3 SAE EE 3/8 x 5/8 ODF ANGValve External Equalizer Size 1/4” SAE male Inlet Outlet Connection ConnectionSeries (omit on CPHE1 & 2 for External Connection Connection Type Style

internal equalizer) Equalizer Size Size

Ordering Information for CPH(E) Valves

ServiceFirst ServiceFirstItem # Description Item # Description

VAL05757 CPHE 1 SAE EE 3/8 x 5/8 ODF ANG VAL05763 CPHE 4 SAE EE 7/8 ODF/1-1/8 ODM ANGVAL05758 CPHE 1 SAE EE 3/8 x 5/8 ODF S/T VAL05764 CPHE 4 SAE EE 7/8 ODF/1-1/8 ODM S/TVAL05759 CPHE 2 SAE EE 1/2 x 5/8 ODF ANG VAL05765 CPHE 5 SAE EE 7/8 ODF/1-1/8 ODM ANGVAL05760 CPHE 2 SAE EE 1/2 x 5/8 ODF S/T VAL05766 CPHE 5 SAE EE 7/8 ODF/1-1/8 ODM S/TVAL05761 CPHE 3 SAE EE 3/8 x 5/8 ODF ANG VAL05767 CPHE 6 SAE EE 1-1/8X1-1/8 ODM ANGVAL05762 CPHE 3 SAE EE 7/8 ODF/1-1/8 ODM S/T VAL05768 CPHE 6 SAE EE 1-1/8X1-1/8 ODM S/T

Nominal Capacity Table in Tons

VALVE R-12 R-134a R-22 R-407C R-507/R-404A R-502CPH(E)-1 0.4 0.5 0.7 0.7 0.7 0.6CPH(E)-2 0.7 0.8 1.2 1.2 1.2 1.0CPH(E)-3 1.2 1.6 2.3 2.3 2.2 2.0CPH(E)-4 3.0 3.8 5.5 5.5 5.3 4.8CPH(E)-5 3.6 4.5 6.7 6.7 6.4 5.8CPH(E)-6 4.6 5.8 8.5 8.5 8.2 7.4

All capacities shown are based on 40°F Evaporator Temperature, 100°F Condensing Temperature, Valve Full Open, Compressor Discharge Temperature is 50°F higher than IsentropicCompression and 25°F Superheat at the compressor inlet

CPH(E) Dimensional Data

VALVE A BCPH(E)1 6.81CPH(E)2 2.94CPH(E)3 8.25 2.75CPH(E)4 8.25CPH(E)5 8.75CPH(E)6 8.75

The above dimensions are maximum height and widthvariations, dependent on flange selection.

CPHE Series Direct Operated Regulatorsare furnished with an adjustment rangeof 0-80 psig. Other features include: Take-A-Part construction for service easewithout removing the body flange fromthe line; stainless steel diaphragm;contoured power element; and the “U”gland packing material which eliminatesstem friction and packing leaks. Vacuumservice is possible by counterclockwiseadjustment of the side-mountedadjusting screw. Chart below showsbreakdown of parts by number andconnection sizes.

A 1/4’’ SAE male flare external equalizeris standard. Types 1 and 2 can befurnished with internal equalizer—omit‘‘E’’ from the type number (i.e. CPH1 orCPH2). Types CPHE3 thru CPHE6 use abalanced double-ported cage assembly.

Features• SAE external equalizer standard

Options• Sizes available: 1 thru 6• ODF and ODF x ODM connections are

available• External air connection available for

pneumatic compensation (add EACprefix – example: EAC CPHE)

Specifications• Adjustment Range: 0-80 psig (factory

setting 20 psig)• UL file #SA5312, CSA file #LR44005

DIMENSIONS SHOWN ARE IN INCHES.

See CPHE Extended Capacity Tables (intons page 102) before completingselection.

101RSP-PRC022-EN

Regulators

CPH(E) Replacement Parts And Exploded View

Body Flange

ServiceFirstAngle Style Part # Item #3/8 x 5/8 ODF C501-5 FLG002451/2 x 5/8 ODF C501-7 FLG002467/8 ODF x 1-1/8 ODM 10331 FLG002617/8 ODF x 1-1/8 ODM 9153 FLG002637/8 ODF x 1-1/8 ODM 9151 FLG002651-1/8 x 1-1/8 ODM 9149 FLG00267

ServiceFirstStraight-thru Style Part # Item #3/8 x 5/8 ODF 9761-3 FLG002531/2 x 5/8 ODF 9761-4 FLG002557/8 ODF x 1-1/8 ODM 10332 FLG002627/8 ODF x 1-1/8 ODM 9152 FLG002647/8 ODF x 1-1/8 ODM 9150 FLG002661-1/8 x 1-1/8 ODM 9148 FLG00268

Consists of body flange.

Cage Assembly

ServiceFirstValve Part # Item #

CPH(E)1 X22440-B5B CAG00049CPH(E)2 X22440-B8B CAG00052CPH(E)3 X11873-B5B CAG00054CPH(E)4 X9117-B9B CAG00058CPH(E)5 X9166-B10B CAG00059CPH(E)6 X9144-B13B CAG00061

Consists of cage assembly and gaskets.

Power Assembly

ServiceFirstValve Part # Item #

CPH(E)1, 2, 3 X7118-4 HED00645CPH(E)4, 5, 6 X7428-2 KIT05340

Consists of power assembly and body flange gasket.

RSP-PRC022EN102

Regulators

DGR(E) & EGR(E) Valves for R22 in Tons

Total Tons Component Evaporator Temperature °FBypassed Type 40° 30° 20° 10° 0° –10° –20° –30° –40°

Bypass Regulator EGRE4 EGRE4 EGRE6 EGRE6 EGRE6 EGRE6 EGRE6 EGRE6 EGRE81/2 Hot Gas Sol. 100RB2 100RB2 100RB2 100RB2 100RB2 100RB2 100RB2 100RB2 100RB2

Liq. Inj. Valve LCL1A LCL1A LCL1B LCL1B LCL1B LCL1C LCL1C LCL1C LCL1CBypass Regulator EGRE4 EGRE6 EGRE6 EGRE6 EGRE8 EGRE8 EGRE8 EGRE8 EGRE8

1 Hot Gas Sol. 200RB3 200RB3 200RB3 200RB3 200RB3 200RB3 200RB3 200RB3 200RB3Liq. Inj. Valve LCL1A LCL1A LCL1B LCL1B LCL1B LCL1C LCL1C LCL1C LCL1CBypass Regulator EGRE8 EGRE8 EGRE8 EGRE8 EGRE8 EGRE8 DGRE12 DGRE12 DGRE12

2 Hot Gas Sol. 200RB4 200RB4 200RB4 200RB4 200RB4 200RB4 200RB4 200RB4 200RB4Liq. Inj. Valve LCL1A LCL1A LCL1B LCL1B LCL1B LCL1C LCL1C LCL1C LCL1CBypass Regulator EGRE8 EGRE8 EGRE8 DGRE12 DGRE12 DGRE12 DGRE12 DGRE12 –

3 Hot Gas Sol. 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5 –Liq. Inj. Valve LCL1A LCL1A LCL1B LCL1B LCL1B LCL2C LCL2C LCL2C –Bypass Regulator EGRE8 EGRE8 DGRE12 DGRE12 DGRE12 DGRE12 DGRE12 – –

4 Hot Gas Sol. 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5 – –Liq. Inj. Valve LCL2A LCL2A LCL2B LCL2B LCL2B LCL2C LCL3C – –Bypass Regulator DGRE12 DGRE12 DGRE12 DGRE12 DGRE12 DGRE12 – – –

5 Hot Gas Sol. 200RB6 200RB6 200RB6 200RB6 200RB6 200RB6 – – –Liq. Inj. Valve LCL2A LCL2A LCL2B LCL2B LCL2B LCL2C – – –Bypass Regulator DGRE12 DGRE12 DGRE12 DGRE12 DGRE12 – – – –

6 Hot Gas Sol. 200RB6 200RB6 200RB6 200RB6 200RB6 – – – –Liq. Inj. Valve LCL2A LCL2A LCL2B LCL2B LCL2B – – – –Bypass Regulator DGRE12 DGRE12 DGRE12 DGRE12 – – – – –

7 Hot Gas Sol. 240RA8 240RA8 240RA8 240RA8 – – – – –Liq. Inj. Valve LCL2A LCL2A LCL2B LCL3B – – – – –Bypass Regulator DGRE12 DGRE12 DGRE12 – – – – – –

8 Hot Gas Sol. 240RA8 240RA8 240RA8 – – – – – –Liq. Inj. Valve LCL3A LCL3A LCL3B – – – – – –Bypass Regulator DGRE12 DGRE12 – – – – – – –

9 Hot Gas Sol. 240RA8 240RA8 – – – – – – –Liq. Inj. Valve LCL3A LCL3A – – – – – – –Bypass Regulator DGRE12 – – – – – – – –

10 Hot Gas Sol. 240RA8 – – – – – – – –Liq. Inj. Valve LCL3A – – – – – – – –

CPH(E) & FA8 Valves for R22 in Tons

Total Tons Component Evaporator Temperature °FBypassed Type 40° 30° 20° 10° 0° –10° –20° –30° –40°

Bypass Regulator CPHE-1 CPHE-1 CPHE-1 CPHE-1 CPHE-1 CPHE-1 CPHE-1 CPHE-1 CPHE-11/2 Hot Gas Sol. 100RB2 100RB2 100RB2 100RB2 100RB2 100RB2 100RB2 100RB2 100RB2

Liq. Inj. Valve LCL1A LCL1A LCL1B LCL1B LCL1B LCL1C LCL1C LCL1C LCL1CBypass Regulator CPHE-3 CPHE-3 CPHE-3 CPHE-3 CPHE-3 CPHE-3 CPHE-3 CPHE-2 CPHE-2

1 Hot Gas Sol. 200RB3 200RB3 200RB3 200RB3 200RB3 200RB3 200RB3 200RB3 200RB3Liq. Inj. Valve LCL1A LCL1A LCL1B LCL1B LCL1B LCL1C LCL1C LCL1C LCL1CBypass Regulator CPHE-4 CPHE-4 CPHE-4 CPHE-4 CPHE-4 CPHE-4 CPHE-4 CPHE-4 CPHE-4

2 Hot Gas Sol. 200RB4 200RB4 200RB4 200RB4 200RB4 200RB4 200RB4 200RB4 200RB4Liq. Inj. Valve LCL1A LCL1A LCL1B LCL1B LCL1B LCL1C LCL1C LCL1C LCL1CBypass Regulator CPHE-4 CPHE-4 CPHE-4 CPHE-4 CPHE-4 CPHE-4 CPHE-4 CPHE-4 CPHE-4

3 Hot Gas Sol. 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5Liq. Inj. Valve LCL1A LCL1A LCL1B LCL1B LCL1B LCL1C LCL2C LCL2C LCL2CBypass Regulator CPHE-5 CPHE-5 CPHE-5 CPHE-5 CPHE-5 CPHE-5 CPHE-4 CPHE-4 CPHE-4

4 Hot Gas Sol. 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5 200RB5Liq. Inj. Valve LCL2A LCL2A LCL2B LCL2B LCL2B LCL2C LCL3C LCL3C LCL3CBypass Regulator CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-5 CPHE-5 CPHE-5 CPHE-5

5 Hot Gas Sol. 200RB6 200RB6 200RB6 200RB6 200RB6 200RB6 200RB6 200RB6 200RB6Liq. Inj. Valve LCL2A LCL2A LCL2B LCL2B LCL2B LCL2C LCL2C LCL2C LCL2CBypass Regulator CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-5

6 Hot Gas Sol. 200RB6 200RB6 200RB6 200RB6 200RB6 200RB6 200RB6 200RB6 200RB6Liq. Inj. Valve LCL2A LCL2A LCL2B LCL2B LCL2B LCL3C LCL3C LCL3C LCL3CBypass Regulator CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-6 CPHE-6

7 Hot Gas Sol. 240RA8 240RA8 240RA8 240RA8 240RA8 240RA8 240RA8 240RA8 240RA8Liq. Inj. Valve LCL2A LCL2A LCL2B LCL3B LCL3B LCL3C LCL3C LCL3C LCL3C

Extended Capacities Table

103RSP-PRC022-EN

Regulators

HeadMaster HP/HPC Series 3-Way HeadPressure Control Valves are controlled bythe system discharge pressure.Adequate head pressure, the systempressure imposed by the compressor, isnecessary for optimum systemperformance. When ambient airtemperature flowing thru air-cooledcondensers is warm enough, there is noproblem maintaining head pressure.However, when ambient temperaturefalls, there is a corresponding headpressure drop and a method ofcontrolling this situation is necessary.The HP/HPC is designed specifically tomaintain proper air-cooled condenserpressures during periods of low ambientconditions. The HP/HPC eliminates theneed for special piping or multiplecontrol valves. As a single unit, the HP/HPC simplifies piping and reducesinstallation costs.

HP/HPC HeadMaster® Head Pressure Controls

Nomenclature Example: HP 8T4 180 1/2 x 1/2 x 1/2 ODF

HP 8 T 4 180 1/2 x 1/2 x 1/2 ODFValve Size Connection Style Connection Size Condensing Pressure Bypass Receiver Condenser ConnectionSeries T = ODF (in 1/8") Set Point (for corresponding Connection Connection Connection Type

HP or HPC F = SAE Condensing Temp. see P-T Chart) Size Size Size

HPC

2,3,5

HP 8HP 14

Ordering Information for HP/HPC Valves

ServiceFirstItem # HP Valve ConnectionsREG00294 HP 5 T 3-110 3/8 x 3/8 x 3/8 ODFREG00295 HP 5 T 3-185 3/8 x 3/8 x 3/8 ODFREG00296 HP 5 T 4-110 1/2 x 1/2 x 1/2 ODFREG00297 HP 5 T 4-185 1/2 x 1/2 x 1/2 ODFREG00298 HP 8 T 4-110 1/2 x 1/2 x 1/2 ODFREG00299 HP 8 T 4-185 1/2 x 1/2 x 1/2 ODFREG00313 HP 8 T 5-110 5/8 x 5/8 x 5/8 ODFREG00300 HP 8 T 5-185 5/8 x 5/8 x 5/8 ODF

Features• Accurate head pressure control, even

at low ambient temperatures• Precise control in maintaining

optimum pressure• Maintains liquid subcooling and

prevents liquid line flash gas• Eliminates the need for special piping

or multiple control valves• Superior operation at low ambients

Options• ODF or SAE connections available – HP

Series• 3/8’’ or 1/2’’ ODF connections – HPC

Series

Specifications• Maximum working pressure:

HP5,8 – 500 psigHP14 – 440 psig

• Shipping weights:HP5 & HP8 = 2-1/2 lbsHP14 = 5 lbs

• UL file #SA5312, CSA file #LR44005

ServiceFirstItem # HP Valve ConnectionsREG00314 HP 8 T 7-110 7/8 x 7/8 x 7/8 ODFREG00301 HP 8 T 7-185 7/8 x 7/8 x 7/8 ODFREG00311 HP 14 T 7-120 7/8 x 7/8 x 7/8 ODFREG00390 HP 14 T 7-175 7/8 x 7/8 x 7/8 ODFREG00312 HP 14 T 9-120 1-1/8 x 1-1/8 x 1-1/8 ODFREG00291 HP 14 T 9-175 1-1/8 x 1-1/8 x 1-1/8 ODFREG00292 HP 14 T11-120 1-3/8 x 1-3/8 x 1-3/8 ODFREG00293 HP 14 T11-175 1-3/8 x 1-3/8 x 1-3/8 ODF

RSP-PRC022EN104

Regulators

HP/HPC Sizing Selection

Consideration must be given to thesystem design requirements, such as:equivalent line length (vertical lift orunusual pressure drop), equipmentlocation, etc., to determine if theminimum control range meets designrequirements. There are numerousalternatives involving head pressurecontrol applications worth considering.

For engineering assistance, consult yourALCO field engineer or ALCO TechnicalServices Department, Alco Controls,St.Louis.

Note: Be sure the HP valve is notrequired to operate at conditionsexceeding the maximum workingpressure.

Note: Not recommended for systemsutilizing patented subcooling coils inconjunction with low head pressuresystems or on systems where thecondensate line bypasses the receiver inorder to maintain subcooling effect inthe liquid line.

Table 1 – Nominal Capacity Table in Tons

Pressure Drop – psi (kPa)1 (7) 2 (14) 3 (21) 4 (28) 5 (35)

Refrigerant Valve Tons Tons Tons Tons TonsHPC-2 1.0 1.4 1.8 2.0 2.3HPC-3 1.7 2.4 3.0 3.5 3.9

R-134a HPC-5 2.2 3.2 3.9 4.5 5.0HP-5 2.0 2.9 3.6 4.1 4.6HP-8 5.5 7.8 9.6 11.0 12.4HP-14 14.0 19.8 24.2 28.3 31.7HPC-2 1.1 1.6 1.9 2.2 2.5

R-22/ HPC-3 1.9 2.7 3.3 3.8 4.2R-407C HPC-5 2.4 3.4 4.2 4.9 5.4

HP-5 2.2 3.2 3.9 4.5 5.0HP-8 6.0 8.5 10.5 12.0 13.5HP-14 14.7 20.8 25.6 29.7 33.8HPC-2 0.7 1.0 1.3 1.5 1.7HPC-3 1.3 1.8 2.2 2.5 2.8

R-404A/ HPC-5 1.6 2.3 2.8 3.3 3.6R-507 HP-5 1.5 2.1 2.6 3.0 3.3

HP-8 3.9 5.5 6.7 7.8 8.7HP-14 10.1 14.3 17.6 20.5 23.0HPC-2 0.9 1.2 1.5 1.7 1.9HPC-3 1.5 2.1 2.6 3.0 3.4

R-12 HPC-5 1.8 2.5 3.1 3.6 4.0HP-5 1.7 2.4 3.0 3.4 3.8HP-8 4.6 6.5 8.0 9.2 10.3HP-14 11.7 16.5 20.2 23.6 26.4HPC-2 0.7 1.0 1.3 1.5 1.6HPC-3 1.3 1.8 2.3 2.6 2.9

R-502 HPC-5 1.6 2.3 2.8 3.2 3.6HP-5 1.5 2.1 2.6 3.0 3.3HP-8 3.9 5.5 6.7 7.8 8.7HP-14 10.1 14.3 17.6 20.5 23.0

All capacities shown are based on 40°F Evaporator Temperature and 100°F liquid.

Table 2 – Multiplier Factors for Capacities at Conditions Other Than Nominal Ratings

Evaporator Temperature °FLiquid R-134a/R-12 R-22/R-407C R-404A/R-507/R-502

Temp. °F 40° 20° 0° -20° -40° 40° 20° 0° -20° -40° 40° 20° 0° -20° -40°120° 0.87 0.82 0.78 0.71 0.69 0.89 0.86 0.84 0.82 0.78 0.84 0.79 0.74 0.69 0.63100° 1.00 0.96 0.91 0.86 0.82 1.00 0.98 0.95 0.93 0.89 1.00 0.96 0.90 0.85 0.7980° 1.13 1.08 1.04 0.99 0.95 1.12 1.09 1.06 1.03 1.00 1.14 1.09 1.04 0.99 0.9360° 1.27 1.22 1.17 1.12 1.07 1.22 1.20 1.17 1.14 1.10 1.32 1.27 1.21 1.16 1.0940° – 1.34 1.29 1.24 1.19 – 1.30 1.27 1.24 1.21 – 1.42 1.37 1.31 1.2620° – – 1.42 1.38 1.32 – – 1.39 1.35 1.32 – – 1.51 1.46 1.41

105RSP-PRC022-EN

Temperature-Pressure Controls

Fundamentals of TemperaturePressure Controls

IntroductionPressure controls serve variousfunctions, which may be divided intocontrol and protection functions.Examples for control functions arecompressor cycling, pump-down ordefrost control. Protection functionsinclude, pressure limiting and cut outagainst excessive pressures, against lossof charge or for freeze protection.

ALCO pressure controls are equippedwith display scale and pointers toindicate the approximate settings. Thedisplay scales are printed in relativepressure units “bar” and “psi”. Forprecise setting of the controls, externalgauges must be used.

Pressure sensingAll pressures are understood as gaugepressures. PS1/PS2 and TS1 controlssense pressure by means of bellowswhich expand or contract when exposedto medium pressure. PS3 controls use adiaphragm rather than a bellows.

High pressure limiters and pressure cutouts with type approval according to DIN32733 feature a double bellows design.The inner bellows serves as theoperating bellows and is enclosed by theouter bellows featuring a larger surfacearea.

Should the inner bellows leak, then thelarger surface area of the outer bellowscreates a larger force and causes thepressure control to a pre-empted cut out.This represents a fail-safe function.Bellows Diagram

Standard controls for refrigerationapplications are equipped with a bronzebellows and can be used with allcommon HFC, HCFC and CFCrefrigerants. For ammonia applicationscontrols with stainless steel bellows areavailable on request.

Pressure connectorsA variety of pressure connectors,including male and female flare typeconnectors, capillary and solderconnectors are available. The standardconnector is a 7-16”-20 UNF male flareconnector, which, in its high pressureversions, is equipped with a snubber toprotect against pressure pulsations.

Refer to the Nomenclature Section for acomplete listing of available connectortypes.

Electrical contactsPS1/PS2/PS3 and TS1 controls areequipped with high rated double snapaction contacts for chatter-free andreliable operation. All contactsthroughout this range of controls aredesigned as Single Pole Double Throw(SPDT) contacts. One contact may beused for control and the other contact foralarm/status indication or auxilliarycontrol. In addition, Dual PressureControls PS2 come with twoindependendly actuated SPDT contacts,providing for even further applicationflexibility by allowing for a variety ofwiring options.

Gold plated contacts are available onrequest for low electrical loads, forexample in electronic signalling D.C.applications.

Electrical Ratings

Maximum Load 120VAC 240VACFull Load Amps 24 FLA 24 FLALocked Rotor Amps 144 LRA 144 LRAHorsepower 2 HP 3 HPPilot Duty 720VA 720VANonInductive 24 amps 24 amps

SetpointsPS1/PS2 and TS1 are adjustable controlswith either internal or externaladjustment spindles for range anddifferential1 . By turning the rangespindle, the upper setpoint is definedand by adjusting the differential spindle,the differential and hence the lowersetpoint is changed (upper setpointdoes not change).

The dependency between upper andlower setpoint is always as follows:

lower setpoint = upper setpoint –differential

1 Manual reset controls have a fixeddifferential and no differential spindle

Contact FunctionAll PS1, PS2 and TS1 Controls havecontacts labelled 1-2-4 where ‘1’ refersto the common pole, ‘2’ refers to thelower setpoint and ‘4’ refers to the uppersetpoint.

The contact function for automatic andmanual reset versions is as describedbelow.

The following two rules should be keptin mind:• An adjustment of the range spindle

always affects both, upper and lowersetpoint.

• An adjustment of the differentialspindle affects the lower setpoint, only.

The following diagrams depict thisdependency:

RSP-PRC022-EN106

For operational safety, all PS1/PS2 withmanual reset are designed as trip-freecontrols, i.e. pressing the manual resetbutton while the pressure has notreached its reset treshold will notoperate the electrical contacts.

The contact function for controls withinternal and external manual reset isalike. The only difference between thetwo is that for internal manual reset thecover has to be undone, whereas theexternal reset controls can be resetwithout removing the cover.

As Dual Pressure Controls, PS2 have twocomplete sets of contacts, their functionis the same as on Single PressureControls PS1 with the only differencethat the contact labels are preceded byan additional index. One side of thecontrol is labeled 11-12-14 whereas thesecond side is 21-22-24.

The contact function of controls withconvertible reset is as described abovebut depends on the actual position of theconvertible reset toggle, i.e. automatic ormanual reset position.

Automatic ResetOn temperature/pressure rise above theupper setpoint, contacts 1-2 open andcontacts 1-4 close. On decreasingtemperature/pressure lower setpointcontacts 1-4 open and contacts 1-2 close

Manual Reset–Low Temperature orPressureOn decreasing temperature or pressurebelow the lower setpoint, contacts 1-4open, contacts 1-2 close and latch. Onlyon pressure rise above upper setpointand after pressing the manual resetbutton contacts 1-2 will open andcontacts 1-4 will close again.

Manual Reset–High Temperature orPressureOn increasing temperature or pressureabove the upper setpoint, contacts 1-2open, contacts 1-4 close and latch. Onlyon falling temperature or pressure belowlower setpoint and after pressing themanual reset button, contacts 1-4 willopen and contacts 1-2 will close again.

Installation and maintenanceControls come with a lockplate whichmay be used to protect the settings bywire-seal if desired. Range anddifferential spindle may be sealedindependent from each other.

A front access manual toggle is providedfor checking out control operation. Onlow pressure controls this toggle may beused to override the low pressure signalduring system evacuation, avoiding theneed to undo the electrical wiring for thispurpose.

All PS1 / PS2 controls come with heavyduty terminal blocks which are finger-proof and feature wire clamps plusnon-loosening terminal screws for easeof wiring.

Available accessories include mountingbrackets of various types, including flatand angle brackets. A universalmounting bracket which matches themost common whole patternsencounted in the field is also available.

The standard mounting holes formounting brackets are equipped with auniversal thread to fit both, M4 and UNC8-32 screws. The standard wholesalepackage includes two mounting screws.Several hole patterns for surfacemounting are provided.

Temperature-Pressure Controls

107RSP-PRC022-EN

TS1 Series TemperatureControlsThe TS1 Series is ALCO’s range ofadjustable thermostats for application inrefrigeration and heat pump systems. Inthese systems, thermostats serve controland monitoring functions, such as spacetemperature control, high/lowtemperature alarming or defrosttermination. By operating a set ofelectrical contacts, a temperature value iskept inside a certain limit.

Several housing variants and sensorsare provided in order to suit a control toa specific application.

Features• Adjustable temperatures and

differentials• Range and differential pointer in units

°C and °F• Range and differential individually

lockable by wire seal• Captive terminal and cover screws• Manual toggle for system checkout and

override• Bellows heater for thermostats with

vapour charge• Room thermostats with insulation

console

• Standard accessories include mountingbrackets andknob with lockplate on all individuallypacked controls

• Non-ambient sensitive• Heavy-duty SPDT switch allows

handling of most loadsdirectly without the use of relays

Specifications• Ambient temperature ranges -50°C to

+70°C (-58°F to 158°F)• SPDT switch rated for 120VAC/240VAC

at 24FLA and 144LRA• Agency approvals include: UL/CUL file

#E85974, VDE 0631/0660, TÜV,CE 73/23/EWG, CE 93/68/EWG

Options• Housing variants for top and front

operation• Flush mounted version• Vapor, liquid and cross-ambient

charges• Sensor shapes for various applications• Versions with and without manual

override• Factory set to customer specification• Different types of mounting brackets• Sensor bulb wells and capillary tube

holders• Special approvals

Nomenclature – Example TS! BIE

TS1 B 1 E

Product Name Housing Variant/function Temperature Range Sensor Type

TS1 = Adjustable thermostat A = Wall mount design, top adjustment 0 = +40 to +68°F (+4.5 to +20°C) A = Vapor Charge, 2 m. capillaryTSA = Customer specials B = Wall mount design, top adjustment, off-switch 1 = -50 to +14°F (-45 to -10°C) C = Liquid Charge, 2 m. bulb

C = Frost monitor, auto reset 2*=-22 to +50°F (-30 to +10°C) E = Vapor Charge, 0 m. coilD = Frost monitor, manual reset -22 to +59°F (-30 to +15°C) F = Adsorption Charge, 2 m. bulbE = Wall mount design, front adjustment 3*=+14 to +77°F (-10 to +25°C) P = Vapor Charge, 2 m. capillaryF = Wall mount design, front adjustment, off-switch +14 to +95°F (-10 to +35°C) for housing variant A/B/E/F/G/H/R.G =Flush mount design, front adjustment 4*=-13 to +86°F (-25 to +30°C) 6 m. capillary for housingH = Flush mount design, front adjustment, off switch -22 to +95°F (-30 to +35°C) variant C/D/X/Y.R = Wall mounting, top adjustment, manual reset 5*=+68 to +140°F (+20 to +60°C)X = Wall mount design, top adjustment +77 to +167°F (+25 to +75°C)Y = Frost monitor, manual reset 6 = +122 to +212°F (+50 to +100°C)

7 = +32 to +50°F (0 to +10°C)8 = +194 to +284°F (+90 to +140°C)9 = +266 to +356°F (+130 to +180°C)

NOTESTemp ranges 0-4:manual reset for falling temperatureoff-switchTemp ranges 5-9:manual reset for rising temperature*First line is range for controls with

housing variant/function A, B, C, D,R, X or Y. Second temperature rangeapplies to controls with housingvariant/function E, F, G or H.

Temperature-Pressure Controls

TF115 Replacement

See page 109 for Old to New CrossReference (TF115 to TS1)

RSP-PRC022-EN108

Temperature-Pressure Controls

Temperature SensorsTS1 thermostats sense temperature bymeans of a thermal system, consisting oftemperature charge, bulb, capillary andbellows. The temperature chargechanges its pressure based on therefrigerant temperature to be sensed.The sensor is the portion of the systemwhich is in thermal contact with therefrigerant, the capillary connects thesensor with the bellows and the bellowscontracts or expands depending on thepressure, causing the thermostat tooperate the electrical contacts. Anexception are capillary type of sensors,which do not have a bulb, instead, theircapillary serves as the bulb directly.Charges and sensor types are matchedto temperature ranges and otherapplication specific characteristics.

TS1 thermostats come with one of threecharge types: vapor charges, adsorptioncharges or liquid charges. Theapplication temperature range coveredby each charge type is shown in thechart below.

Vapor Charge–Sensor Type A, E, PThese sensing elements always sensefrom the coldest point on the capillary,coil, bulb or power element head. Forproper operation it must be ensured thatthis coldest point is at the sensor portionwhich is exposed to the temperature tobe sensed. The sensing location shouldbe at least 4°F (2 K) colder than the otherparts of the thermal system.

In order to avoid unwanted effects ofheat transfer, e.g. from a cold wall, ALCOvapour charged thermostats come withan integrated bellows heater, which israted for 230 V applications. For otherapplications the heater must be disabled,alternatively, a bellows heater with adifferent rating may be available.

In addition to the bellows heater, roomthermostats are supplied with aninsulation console for the same reason.

Sensor type ‘A’ is a coiled bulb sensorwith two meter capillary, which may beused with or without a bulb well. Style‘E’ is a coil sensor for space temperaturesensing, and type ‘P’ is a capillary type ofsensor which can be wrapped around aheat exchanger’s surface in order tosense the coldest point on the heatexchanger for frost protectionapplications.

Vapor charges respond faster totemperature changes than adsorptionand liquid charges.

Adsorption Charge–Sensor Type FAdsorption charged sensor typesoperate on the basis of a temperaturedependent adsorption material, which islocated inside the bulb only. Thereforethese sensor types always respond totemperature changes at the bulb only.This makes them suitable to applicationswhere it is not always defined which partof the thermal system the coldest pointis (cross ambient applications). Anexample for such applications is defrostcontrol.

Adsorption charges are slower inresponse to temperature changes thanvapour charges.

TEMPERATURE RANGELOW HIGH

Liquid Charge–Sensor Type CLiquid charge sensors of type ‘C’ alwayssense from the warmest point of thethermal system. This condition mustalways be ensured. The sensing locationshould always be warmer than 4°F (2 K)than other parts of the thermal system.

Housing VariantsTS1 controls can be delivered in threemain housing variants, top operated,front operated and flush mounted. Allthree variants are available either with orwithout off-switch, which cuts off powersupply to the thermostat in off position.

Top operated controls–Function/Housing Variant A,B,C,D,R,X,YHave adjustment spindles at the top anda display scale, indicating temperaturesetpoint and differential, at the front. Aknob which may be permanentlyplugged onto one of the adjustmentspindles comes with every control. Frostmonitors and room thermostats arederivatives of top operated thermostats.They differ by their sensors and otherfeatures to suit their particular targetapplications.

Front operated controls–Function/Housing Variant E,FHave an adjustment knob at the front forthe temperature setpoint with anapproximate scale imprinted on theknob. In order to adjust the temperaturedifferential, the cover of the control mustbe removed.

Flush Mounted controls–Function/Housing Variant G,HDesigned in a way that they can beintegrated into a panel or housing, forexample into display cases.

109RSP-PRC022-EN

Temperature-Pressure Controls

Old To New Cross Reference(TF115 To TS1) Replaces The Competition

ServiceFirst

Old Model New Model Item # Ranco Penn White-Rodgers Honeywell

TF115-S2-AA10 TS1-X2A 21/30 CNT02202 010-1408, 010-1409 1609-90 T4031A1008010-1410, 010-104

TF115-S4-AF10 TS1-X4F 32/41 CNT02200 060-100 A19ABC-24 1609-101, 1609-102 T6031A1029F25-107 A19ZBC-2 1609-103

TF115-S2-AE00 TS1-X2E 36/40 CNT02203 010-1418, 016-594 A19BBC-2 201-20 T605010-1072

TF115-S3-AE00 TS1-X3E 64/68 CNT02204 010-301, 016-165 A19BAB-3, A19BAC-1 201-8 T6054BTF115-S1-AA10 TS1-X1A -4/0 CNT02201 010-1433 1609-100TF115-S0-DP20 TS1-Y0P-36 CNT03258

Ordering Information for TS1 Temperature Controls

Adjustment Range Factory Temperature SensorServiceFirst Upper Setpoint Differ. Setpoint Setting

Type Item # °F (°C) °F (°K) °F (°C) Charge TypeTop Operated Thermostats Without Off-switch (Capillary Type Sensor)

TS1-X1A CNT02201 -49 to 14 (-45...-10) 3 to 29 (2 to 16) 0/-4 (-18/-20) Vapor 6 Ft. (2 m.) capillaryTS1-X2A CNT02202 -22 to 59 (-30...+15) 3 to 29 (2 to 16) 30/21 (-1/-6) Vapor 6 Ft. (2 m.) capillaryTS1-X4F CNT02200 -22 to 95 (-30...+35) 5 to 36 (3...20) 41/32 (+5/0) Adsorption 6 Ft. (2 m.) cap. & bulb

Room Thermostats Top Operated Without Off-switch (Includes Insulation Console And Coil Type Sensor)

TS1-X2E CNT02203 -22 to 59 (-30...+15) 3 to 29 (2 to 16) 39/35 (+4/+2) Vapor CoilTS1-X3E CNT02204 14 to 95 (-10...+35) 3 to 29 (2 to 16) 68/64 (+20/+18) Vapor Coil

Freeze-Stat, Top Operated Without Off-switch

TS1-Y0P CNT03258 40 to 68 (+45...+20) Man Reset Ca .5 (3) fix 36 (+2) Vapor 20 Ft. (6 m.) capillary1 Low Temperature Cut Out2 Defrost & Universal Thermostat

RSP-PRC022-EN110

Temperature-Pressure Controls

Nomenclature – Example PS1-A5K

PS1 A 5 K

Product Name Function Pressure Range Pressure Connector Type

TS1 = Adjustable thermostat A = Wall mount design, top adjustment 0 = +40 to +68°F (+4.5 to +20°C) A = Vapor Charge, 2 m. capillaryPS1 = Adjustable single A = Pressure control, automatic reset, 1 = 24”Hg to 42 psi (-0.75 to 3 bar) A = 7/16”-20 UNF male for 1/4” SAE

Pressure Control internal range & differential adjustments 2 = 26”Hg to 21 psi (-0.8 to 1.5 bar) male flareB = Pressure cut out, external manual 3 = 15”Hg to 100 psi (-0.5 to 7 bar) C = R 1/4” stainless steel with

PSA = Customer specials reset, DIN/TUV approved, internal 4 = 15 to 290 psi (1 to 20 bar) steel bellowsrange and differential adjustmentsÀ,Á 5 = 90 to 450 psi (6 to 31 bar) F = 1/4”-18 NPTF stainless steel

R = Pressure cut out, external manual reset, with steel bellowsinternal range and differential adjustmentsÀ,Á K* = 7/16”-20 UNF flare nut with

S = Safety pressure cut out, internal manual 1 meter (3 ft.) cap tubereset, DIN/TUV approved, internal L = 1/4” ODF solder with 1 meterrange & differential adjustmentsÀ,Á (3 ft.) cap tube

U = Convertible from R to A R = R 1/4”W = Pressure control, automatic reset, U = 6 mm ODF solder,

DIN/TUV approved, internal range and 80 mm tube lengthdifferential adjustments X = 1/4” ODF solder,

X = Pressure control, automatic reset, external 80 mm tube lengthrange and differential adjustments

Y = Pressure cut out, external manual reset, * Controls with housing variant X/Yexternal range and differential adjustments have extended copper ends, without

schrader valve depressor. All other1 Function types B, R, S in combination with housing variants have schrader valvePressure Range 1 or 3 have a low pressure depressor and brass end fitting withmanual reset function. (15 psi differential) copper gasket.2 Function types B, R, S in combination withPressure Range 4 or 5 have a highpressure manual reset function. (60 psi diff.)

PS1 Series Single PressureControlsPS1 Single Pressure Controls aredesigned for use on high and lowpressure applications in refrigeration andheat pump systems. By operating a setof electrical contacts, a pressure is keptinside a certain limit.

Features• Adjustable pressures and differentials• Narrow adjustable differential

depending on model• Range and differential pointer in units

bar and psig• Range and differential individually

lockable by wire seal• High rated SPDT contacts for all

versions• Captive terminal and cover screws

FF115 ReplacementSee page 111 for Old to New CrossReference (FF115 to PS1)

• Manual toggle for system checkout andoverride

• Factory installed wire bridge forreduced installation effort

Options• Different pressure connections• Automatic and manual reset versions• Factory set to customer specification• Different types of mounting brackets

Specifications• SPDT switch rated for 120VAC/240VAC

at 24FLA and 144LRA• Agency approvals include: UL/CUL file

#E85974, VDE 0631/0660, TÜV,CE 73/23/EWG, CE 93/68/EWG

• Low pressure and high pressureversions available with TÜV approvalaccording to EN 12263 (supercedesDIN 32733) to meet requirements ofDIN 8901 and EN378 (supercedesDIN 8975)

111RSP-PRC022-EN

Ordering Information for PS1 Single Pressure Controls

Single Adjustment Range FactoryPressure ServiceFirst. Upper Setpoint Diff. Setpoint Setting PressureControl Item # PSI (BAR) PSI (BAR) PSI (BAR) ConnectionLow Pressure Controls

PS1-X1K CNT02198 24” Hg to 42 (-.75 to 3) 4 to 29 (.25 to 2) 7/15 (.5/1) Capillary/ nutPS1-X3A CNT02187 15” Hg to 100 (-0.5 ... +7) 7 to 73 (0.5 ... 5) 50/65 (3.5/4.5) 7/16”-20 UNF, 1/4” SAE malePS1-X3K CNT02188 15” Hg to 100 (-0.5 ... +7) 7 to 73 (0.5 ... 5) 50/65 (3.5/4.5) Capillary/ nutHigh Pressure Controls

PS1-X4K CNT02189 15 to 290 (1 to 20) 15 to 100 (1 to 7) 145/115 (10/8) Capillary/ nutPS1-X5A CNT02190 90 to 450 (6 ... 31) 29 to 217 (2 ... 15) 190/280 (10/19) 7/16”-20 UNFPS1-X5K CNT02192 90 to 450 (6 ... 31) 29 to 217 (2 ... 15) 230/290 (16/20) Capillary/ nutPS1-Y5A CNT02191 90 to 450 (6 ... 31) External Manual Reset 390 (27) 7/16”-20 UNF, 1/4” SAE male

High Pressure60 psi (4 bar) fixed

PS1-Y5K CNT02193 90 to 450 (6 ... 31) External Manual Reset 290 (20) Capillary/ nutHigh Pressure

60 psi (4 bar) fixed

Temperature-Pressure Controls

Old To New Cross Reference (TF115 to TS1) Replaces The Competition

ServiceFirstOld Model New Model Item # Copeland ➀ Ranco Penn Danfoss SaginomiyaFF115-S1-BAK PS1-X1K 7/15 CNT02198 085-0098-21 010-1402 P70AB-12

985-CP1A-1K 016-557FF115-S4-BAK PS1-X4K 115/145 CNT02189 085-0098-33 010-2000 P70AA-2

016-593FF115-S3-BAK PS1-X3K 50/65 CNT02188 085-0098-00 010-1483, 011-3099 P70AB-12, P70AB-2

985-CP1A-3K 016-527 P70CA-2FF115-S5-BAK PS1-X5K 230/290 CNT02192 085-0098-08 010-2054, 011-1711 P70AA-118

985-CP1A-5K 016-108, 020-7006 P70CA-3FF115-S5-BRK PS1-Y5K 230/290 CNT02193 016-200 P70DA-1

P70KA-1FF115-S3-BAA PS1-X3A 50/65 CNT02187 985-CP1A-3A 010-1401, 010-1831 P170AB-12 KP1 60-1101 SNS-C106X

011-1799, 016-106 P170AB-2016-107

FF115-S5-BAA PS1-X5A 140/280 CNT02190 985-CP1A-5A 010-1894, 011-1713 P170AA-118, P170CA-3 KP5 60-1171 SNS-C130X, SNS-C135X016-503, 016-570 P77AAA-9350

016-106 P77AAA-9370F115-S5-BRA PS1-Y5A 330/390 CNT02191 016-209, 016-106 P170DA-1, P77BEA-9350 KP5 60-1173

P77BEA-9370PS1-U5A 385 985-CP1U-5APS1-U5K 385 985-CP1U-5K

➀ The Alco control may be used with bracket (PCN 097221) to allow replacement of the Copeland control with the same mounting configuration.

RSP-PRC022-EN112

Temperature-Pressure Controls

PS2 Series Dual PressureControls

PS2 Dual Pressure Controls are designedfor use on high and low pressureapplications in refrigeration and heatpump systems. By operating a set ofelectrical contacts, a pressure is keptinside certain limits.

Features• Adjustable pressures and differentials• Narrow adjustable differential

depending on model• Range and differential pointer in units

bar and psig• Range and differential individually

lockable by wire seal• High rated SPDT contacts for all

versions• Captive terminal and cover screws• Manual toggle for system checkout and

override• Factory installed wire bridge for

reduced installation effort

Options• Different pressure connections• Automatic and manual reset versions• Factory set to customer specification• Different types of mounting brackets

Specifications• SPDT switch rated for 120VAC/240VAC

at 24FLA and 144LRA• Agency approvals include: UL/CUL file

#E85974, VDE 0631/0660, TÜV, CE 73/23/EWG, CE 93/68/EWG

• Low pressure and high pressureversions available with TÜV approvalaccording to DIN 32733 to meetrequirements of DIN 8901 and DIN8975

FF215 Replacement

See page 114 for Old to New CrossReference (FF215 to PS2)

113RSP-PRC022-EN

Nomenclature – Example PS2-G8A

PS2 G B A

Product Name Function Pressure Range Pressure Connector Type

PS2 = Adjustable Dual 7 = Left side: 15”Hg to 100 psi A = 7/16”-20 UNF male forPressostat (-0.5 to 7 bar) 1/4” SAE flare fitting

Right side: 90 to 450 psi C = R 1/4” stainless steel withPSB = Customer special (6 to 31 bar) steel bellows

Version F = 1/4”-18 NPTF stainless steelwith steel bellows

8 = Left side: 90 to 450 psi K* = 7/16”-20 UNF flare nut with(6 to 31 bar) 1 meter (3 ft.) cap tubeRight side: 90 to 450 psi L = 1/4” ODM solder with 1 meter(6 to 31 bar) (3 ft.) cap tube

R = R 1/4”U = 6 mm ODF solder, 80 mm tube

length9 = Left side: 24”Hg to 45 psi X = 1/4” ODF solder, 80 mm tube

(-0.75 to 3 bar) lengthRight side: 90 to 450 psi(6 to 31 bar)

A = Both sides: Pressure controls, Automatic reset,Internal range and differential adjustments.

B = Both sides: Pressure cut out, External manualreset, DIN/TÜV approved, internal range anddifferential adjustments.

C = Left side: Pressure control, Automatic reset, DIN/TÜV approved, Internal range and differentialadjustments. Right side: Safety cut out, Externalmanual reset, DIN/TÜV approved, Internal range &differential adjustments.

G = Left side: Pressure control, Automatic reset, DIN/TÜV approved, Internal range and differentialadjustments. Right Side: Safety limiter, internalmanual reset, DIN/TÜV approved, Internal range &differential adjustments.

L = Left side: Pressure control, Automatic reset,Internal range and differential adjustments. Rightside: Pressure cut out, External manual reset,Internal range and differential adjustments.

M = Left side: Pressure control, Automatic reset,Internal range and differential adjustments. Rightside: Convertible reset from R to A, Internal rangeand differential adjustments.

R = Both sides: Pressure cut out, External manualreset, Internal range and differential adjustments.

S = Both sides: Pressure safety cut out, Internalmanual reset, DIN/TÜV approved, Internal rangeand differential adjustments.

T = Left side: Pressure control, Automatic reset, DIN/TÜV approved, Internal range and differentialadjustments. Right Side: Safety limiter, internalmanual reset, DIN/TÜV approved, Internal range &differential adjustments.

U = Both sides: Convertible from R to A.W = Both sides: Pressure control, Automatic reset, TÜV

approved, Internal range and differentialadjustments.

X = Both sides: Pressure controls, Automatic reset,External range and differential adjustments.

Y = Left side: Pressure control, Automatic reset,External range and differential adjustments. Rightside: Convertible from external manual reset toautomatic reset, External range and differentialadjustments.

Z = Both sides: Convertible from External manualreset to automatic reset, External range anddifferential adjustments.

LOW PRESSURE MANUAL RESET: Cut outs withmanual reset function and in combination with the lowpressure side of Pressure Ranges 7 & 9 have a lowpressure manual reset function (15 psi differential).HIGH PRESSURE MANUAL RESET: Cut outs withmanual reset function and in combination with thehigh pressure side of Pressure Ranges 7 & 9 have ahigh pressure manual reset function (60 psidifferential).

* Controls with housing variants X/Y/Zhave extended copper ends, withoutschrader valve depressor. All otherhousing variants have schrader valvedepressor and brass end fitting withcopper gasket.

Temperature-Pressure Controls

PS2 Series Dual Pressure Controls

RSP-PRC022-EN114

Ordering Information for PS2 Dual Pressure Controls

Adjustment RangeSingle Upper Setpoint Differential Factory SettingPressure ServiceFirst Left Right Left Right Left Right PressureControl Item # PSI (Bar) PSI (Bar) PSI (Bar) PSI (Bar) PSI (Bar) PSI (Bar) ConnectionPS2-Y7A CNT02194 Convertible 50/65 (3.5/4.5) 290 (20) 7/16”-20 UNF

PS2-Y7K CNT02195 Auto/Man Capillary/ nutPS2-Y9K CNT02199 24” Hg to 45 90 to 450 4 to 29 Reset 7/15 Capillary/ nut

( -0.8...3) (6...31) (.25...2)

ConvertibleAuto/Man

Reset

Temperature-Pressure Controls

Old To New Cross Reference (TF215 to TS1) Replaces The Competition

ServiceFirstOld Model New Model Item # Copeland ➀ Ranco PennFF215-S7-BAUK PS2-Y7K 50/65* CNT02195 085-0098-02, 085-7000-00 012-1549 P70LB-1, P70LB-6

230/290 985-CP2M-7K 012-4834 P70MA-1, P70MA-18FF215-S9-BAUK PS2-Y9K 7/15* CNT02199 085-0098-22, 085-0098-23 012-1502, 012-1506 P70LB-1, P70LB-6

230/290 012-1554, 012-4833 P70MA-1, P70MA-18FF215-S7-BAUA PS2-Y7A 50/65* CNT02194 985-CP2M-7A 012-1550 P170LB-1

230/290 P170MA-1➀ The Alco Control may be used with bracket (PCN 097221) to allow replacement of the Copeland control with the same mounting configuration.

15” Hg. to 100 90 to 450 7 to 72(-0.5...7) (6...31) (0.5...5)

115RSP-PRC022-EN

Temperature-Pressure Controls

FD113-ZU(K) Oil PressureSafety Controls

The FD113 Oil Pressure Safety Controlsenses the effective oil pressure onpressure lubricate compressors. Ifinadequate oil pressure exists, a timedelay is energized. If the oil pressuredoes not recover to safe levels within thetime delay setting, the compressor isshut down. The time delay allows thecompressor adequate time to establishoil pressure on start up and avoidsnuisance shutdowns on pressure drop ofshort duration during the run cycle.

Maximum application flexibility isassured by providing an adjustabledifferential pressure switch which can beadjusted to the compressor’s minimumrequired oil pressure needs and an

A typical 3 wire hookupwith the factory installedjumper.

Dimensions shown are in inches.

adjustable electronic time delay whichallows you to select the length of timethe compressor runs below theminimum pressure before shutdown.The minimum pressure setting and timedelay values specified by thecompressor manufacturer should beused when installing the FD113 control.

Features• Pressure Range adjustable from 4 to 65

PSID; Timer start pressure–timer stoppressure is 3 PSID above timer startpressure

• A SPDT switch is used in the pressureportion of the control which allows theaddition of a “safe light” if desired

• Electronic Timer is Time-Adjustablefrom 20 to 150 secondsSupply voltage—24 to 240 Volt AC/DC;Timing unaffected by voltage orambient temperature variations

• A SPDT Manual Reset Switch is used inthe Timer Module; Upon time-out, thecompressor is stopped and an alarmcircuit is energized; To restart thecompressor and de-energize the alarmcircuit, the reset button is pushed

• A factory installed Jumper allows theFD113 to be powered from a singlepower source; Should separate circuitsbe desired for the timer and “Lockout”switch, the Jumper can be removed

Specifications• Agency approvals include: UL/CUL file

#E85974, VDE 0631/0660, TÜV, CE 73/23/EWG, CE 93/68/EWG

FD113 Dimensional Data

Ordering Information for FD113-ZU(K) Oil Pressure Safety Controls

ServiceFirst ALCO Adjustable Adjustable Supply Pressure ReplacesItem # Part Number Pressure Range Time Delay Voltage Connection Penn Copeland Ranco

P45NCA-12P45NCA-82 P30-5826

(2) 36’’ P28AA-1,-2 P30-3601 CNT02197 FD113–ZUK 20 to 150 24 to 240V capillary with P28AA-17,-18 085-0062-00 P30-3701

4-65 PSID second AC/DC 1/4’’ flare nut P28DA-1 P30-3801P28GA-2P28NA-5

Factory-set at P128AA-1,-2,-3FD113–ZU 120 seconds (2) 1/4’’ male flare1 P145NCA-12,-82 P30-5827

P145NCB-12,-821 For applications where the condensing unit/control is exposed to temperatures below 20°F, 1/4” lines are recommended.

Oil Pump

Compressor Crankcase

RSP-PRC022-EN116

Temperature-Pressure Controls

FD113-ZU-S Pressure DropAlarm Control

The FD113 Filter Alarm Control sensesthe differential pressure across a filterand if the pressure drop exceeds thesetpoint value, the timer is energized. Ifthe pressure drop does not decrease 4PSI below the setpoint during the timedelay period, the manual reset timerrelay trips and the alarm circuit isenergized.

Typical Pressure Drop MonitoringApplications• Liquid Line Filters/Driers• Suction Line Filters• Oil Line Filters

Dimensions shown are in inches.

FD113 Dimensional Data

Ordering Information for FD113-ZU-S Pressure Drop Alarm Controls

ServiceFirst ALCO Adjustable Adjustable Supply PressureItem # Part Number Pressure Range Time Delay Voltage Connection Application

4-65 psidFD113–ZU–S factory set at 20 to 150 24 to 240V Oil filter pressure drop alarm

50 psid seconds AC/DC (2) 1/4’’ male flare fittings on HVAC chillerfactory set at

4-65 psid 120 sec.FD113–ZU–S factory set at 25 psid

Standard Product Offering* Product Code Number

Filter Inlet Pressure

Filter Outlet Pressure

Wiring forPressure DropAlarm Control

Features• Wide Adjustable Pressure Range: 4 to

60 PSID• Narrow Cut-in/Cut-out Differential at

PSID setpoint 4 PSI• Wide reference pressure capabilities

10’’ to 300 PSIG with minimum changein setpoint or differential settings

• Electronic Time Delay–Manual ResetAdjustable from 20 to 150 secondsSupply voltage–24 to 240 VACTiming unaffected by voltage orambient temperature variations

• Prevents nuisance alarms fromtemporary surges in pressure changesduring start-up

• Output: SPDT Isolated Manual ResetRelay–times out on increasing pressuredifferential above setpoint.

• Rating: 360 VA Max. 120/240 VAC.

Specifications• Ambient Temperature Range

• Operating –10°F to +120°F.• Agency approvals include: UL/CUL file

#E85974, VDE 0631/0660, TÜV,CE 73/23/EWG, CE 93/68/EWG

117RSP-PRC022-EN

Temperature-Pressure Controls

PS3 Mini-Pressure Controls

The PS3 Mini-Pressure Control providesthe ultimate in reliability and flexibility ina commercial grade mini-pressurecontrol. A standard plug connectabledesign simplifies installation and service.The SPDT switch allows the addition ofalarm circuits on high or low pressureapplications. The PS3 makes yourapplication and selection easy. Modelswith high temperature diaphragms andbuilt-in pressure pulsation snubbersmake the PS3 ideally suited forcompressor head mounting high

Features• Commercial Grade High/Low/

Condenser Fan CyclingPressure Controls for use onRefrigeration/AC Applications

• Mini-Size 2’’ x 1-1/2’’ x 2-3/4’’• Standard SPDT Switch Action• Automatic or Manual Reset• Models available with high

temperature double diaphragms andbuilt-in pressure pulsation snubber fordirect head mount high pressuresensing/limit applications

• Plug Connectable with hub for 1/2’’flexible conduit or Compression Fittingfor cable

• Factory preset to customer’s desiredpressure specifications

• Selected Models Field ‘‘Trimable’’ tomatch application pressurerequirements

• Precise, repeatable settings• Narrow differential ‘‘Micro’’ switch

available on low pressure models• Panel Mount configurations with fitting

or capillary available on special order• Terminal Covers available for

protecting individual wire connectionswhen 1/4’’ QC’s used on Panel Mountconfigurations

Nomenclature – Example PS3-AF1HNB

PS3 A F 1 H N BProduct Function Mounting Pressure Range Electrical Connection Contact Type Pressure ConnectionName A = Automatic Reset, High Pressure

with Single Bronze DiaphragmMaterial

W = Automatic Reset, High Pressurewith safety cut-out with DoubleBronze Diaphragm Material, DIN/TUV approved

X = Automatic Reset, High Pressurewith Double Nickel BerylliumDiaphragm Material (High Temp),DIN/TUV approved

B = Manual Reset, High PressureSafety Limiter with Double BronzeDiaphragm Material, DIN/TUVapproved

C = Manual Reset, High PressureSafety Limiter with Double NickelBeryllium Diaphragm Material(High Temp), DIN/TUV approved

D = Manual Reset, Low Pressure withSingle Bronze Diaphragm Material

R = Manual Reset, High Pressure withSingle Bronze Diaphragm Material

S = Manual Reset (only with specialreset tool), High Pressure SafetyLimiter with Double BronzeDiaphragm Material, DIN/TUVapproved

T = Manual Reset (only with specialreset tool), High Pressure SafetyLimiter with Double NickelBeryllium Diaphragm Material(High Temp), DIN/TUV approved

F = Free StandingP = Panel Mount

design withmounting flange

1 = 15” Hg to 90 psig(-0.6 to 6 bar)

3 = 2 to 230 psig(0.1 to 16 bar)

5 = 100 to 465 psig(6 to 32 bar)

H = Spade for DINconnector

T = 1/4” x .032” Spadeconnections

N = StandardM = MicroSwitchG = MicroSwitch

with Goldplatedcontacts

O = Standardswitch withGold platedcontacts

S = 1/4” SAE Female(7/16”-20 UNF)with Schradervalve depressor

A = 1/4”SAE Male(7/16”-20 UNF)

B = 1/4” SAE Female(7/16”-20 UNF)with Snubberorifice andSchrader valvedepressor forHigh Temp/PressureApplication

L = 1/4” ODM Solderwith 36” capillarytube

K = 1/4” SAE FemaleFlare Nut (7/16”-20 UNF) with36”capillary tube

pressure limit control applications—automatic or manual reset versions areavailable.

Pressure Ranges/Differential also makethe PS3 controls ideally suited forcondenser fan cycling applications. FieldTrimable Low Pressure versions withstandard or narrow differential switchesmake these controls ideally suited lowpressure limit or back-up safety controlson electronically controlled systems.Numerous options, such as panel mountor capillary connections are available onhigh volume applications. Standard onall models are worldwide agencyapprovals.

Typical Applications• High Pressure Limit/Alarm• Condenser Fan Cycling• Low Pressure Limit/Alarm• Low Pressure Cycling (Back-Up)• Defrost Termination/Fan Delay• Rupture Guard Alarm

Specifications• Worldwide Approvals: UL/CUL/VDE/

TUV• UL file #E85974

RSP-PRC022-EN118

Temperature-Pressure Controls

PS3 Mini-Pressure Control Specifications Selection Table

ServiceFirst High Event Differential Pressure Electrical Electrical MaximumItem # Type & PCN Range PSIG Range PSID Settings Reset Conn. Conn. Ratings 2 Overpressure MountingLOW PRESSURE CONTROLS

PS3-AF1 HMS 1 1.5/6 4 DIN PlugLow End 1.5/6 1/4” SAE with 1/2” NPTF 2.5 FLA Free

PS3-AF1 HMS 1 24/3015"-90 7 Female Hub for Flex 15 LRA 360 PSIG StandingHigh End 24/30 AUTO with Valve Conduit Direct

PS3-AF1 HNS 5/15 9 Low End Depressor Connection 6 FLA Mount15 High End 5/15 36” Cable 36 LRA

HIGH PRESSURE CONTROLSPS3-XF5 HNB 285/350 285/350

45PS3-XF5 HNB 300/370 Low End 300/370 AUTO 1/4” SAE

80 Female DIN PlugCNT03269 PS3-XF5 HNB 320/395 High End 320/395 with Valve with 1/2” NPTF Free

Depressor Hub for Flex StandingPS3-CF5 HNB 350 350 & High Temp Conduit Direct

Double Connection 6 FLA 520 PSIG MountCNT03640 PS3-CF5 HNB 370 100-465 370 Diaphragm 36” Cable 36 LRA

& SnubberPS3-CF5 HNB 395 Manual 395 Manual

ResetPS3-BP5 TNLM0 340 36” capillary 1/4” Quick Panel

with 1/4” Connects MountPS3-BP5 TNL 440 440 ODM sweat w/terminal (Flange)

connection

Specifications

Electrical Ratings–SPDT Switch• Standard Switch – High/Low Pressure

Load Contact6 FLA – 36 LRA – 120/240 VACPilot Duty: 240VA @ 120480VA @ 240 VACBack Contact0.5 Amp 120/240 VAC Pilot Duty

Micro Switch – Low Pressure• 2.5 FLA – 15 LRA – 120/240 VAC

Pilot Duty: 120VA @ 120240VA @ 240 VAC

• Back Contact0.5 Amp 120/240 VAC Pilot Duty

Ambient Temperature• Storage: –30° to +160°F

Operating: –20° to +140°F

Protection• Protect from rain, direct sunlight and

exterior damage.

Weight• Approximately 0.25 pound, depending

upon configuration.

Compatibility• HFC, HCFC, CFC

Agency Approvals• UL/CUL/DIN/TUV, depending upon

configuration.

Switch Action• SPDT Standard

1–2 Open on RiseClose on Fall

1–4 Close on RiseOpen on Fall

Construction

• Low PressureSingle DiaphragmMaximum Media Temp. 150°F.

• High PressureDouble DiaphragmMaximum Media Temp. 300°F.

• Internal Pressure Pulsation Snubberavailable for direct head mount.

NOTE: Single Diaphragm High PressureConfigurations are also available.

1Micro-Switch Construction.2All switches SPDT ratings stated are 1 side only 120/240 VAC. Opposite switch side – 1/2 amp pilot duty 120/240.*Product Code Number

119RSP-PRC022-EN

Cross Reference - Upgrade to Alco

Sporlan to ALCOProduct Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOSOLENOID ....... 180 ................... 1/4 SAE ........................ 702RA - 001 ..................... SAME ................... HARD SHUT-OFF VALVEDIST ................. 1112 ................. DISTRIBUTOR ............. 701 .................................. SAME ................... USE NOZZLE GDIST ................. 1113 ................. DISTRIBUTOR ............. 702 .................................. SAME ................... USE NOZZLE GDIST ................. 1115 ................. DISTRIBUTOR ............. 901 .................................. SAME ................... USE NOZZLE EDIST ................. 1116 ................. DISTRIBUTOR ............. 902 .................................. SAME ................... USE NOZZLE EDIST ................. 1117 ................. DISTRIBUTOR ............. 1101 ................................ SAME ................... USE NOZZLE CDIST ................. 1125 ................. DISTRIBUTOR ............. 1301 ................................ SAME ................... USE NOZZLE ADIST ................. 1126 ................. DISTRIBUTOR ............. 1102 ................................ SAME ................... USE NOZZLE CDIST ................. 1128 ................. DISTRIBUTOR ............. 1103 ................................ SAME ................... USE NOZZLE CDIST ................. 1147 ................. DISTRIBUTOR ............. F501 ................................ SAME ................... USE NOZZLE J - WITH FLARE NUTKITS ................. 1538 ................. INLET STRAINER .................................................. NONE ................... FOR SPORLAN TXV ONLYDIST ................. 1603 ................. DISTRIBUTOR ............. F401 ................................ SAME ................... USE NOZZLE L - WITH FLARE NUTDIST ................. 1604 ................. DISTRIBUTOR ............. S401 ................................ SAME ................... USE NOZZLE LDIST ................. 1605 ................. DISTRIBUTOR ............. F403 ................................ SAME ................... USE NOZZLE L - WITH FLARE NUTDIST ................. 1606 ................. DISTRIBUTOR ............. F402 ................................ SAME ................... USE NOZZLE L - WITH FLARE NUTDIST ................. 1607 ................. DISTRIBUTOR ............. S402 ................................ SAME ................... USE NOZZLE LDIST ................. 1608 ................. DISTRIBUTOR ............. F404 ................................ SAME ................... USE NOZZLE L - WITH FLARE NUTDIST ................. 1613 ................. DISTRIBUTOR ............. 401 .................................. SAME ................... USE NOZZLE LDIST ................. 1616 ................. DISTRIBUTOR ............. 402 .................................. SAME ................... USE NOZZLE LDIST ................. 1620 ................. DISTRIBUTOR ............. 501 .................................. SAME ................... USE NOZZLE JDIST ................. 1622 ................. DISTRIBUTOR ............. 502 .................................. SAME ................... USE NOZZLE JDIST ................. 1650 ................. DISTRIBUTOR ............. F405 ................................ SAME ................... AUX. SIDE INLET AND FLARE NUTDIST ................. 1651 ................. DISTRIBUTOR ............. 503 .................................. SAME ................... AUX. SIDE INLETDIST ................. 1652 ................. DISTRIBUTOR ............. F503 ................................ SAME ................... AUX. SIDE INLET AND FLARE NUTDIST ................. 1653 ................. DISTRIBUTOR ............. 703 .................................. SAME ................... AUX. SIDE INLETDIST ................. 1654 ................. DISTRIBUTOR ............. F504 ................................ SAME ................... AUX. SIDE INLET AND FLARE NUTDIST ................. 1655 ................. DISTRIBUTOR ............. 903 .................................. SAME ................... AUX. SIDE INLETDIST ................. 1656 ................. DISTRIBUTOR ............. F505 ................................ SAME ................... AUX. SIDE INLET AND FLARE NUTDIST ................. 1657 ................. DISTRIBUTOR ............. 1104 ................................ SAME ................... AUX. SIDE INLETDIST ................. 1659 ................. DISTRIBUTOR ............. 1302 ................................ SAME ................... AUX. SIDE INLETKITS ................. 1935 ................. INLET STRAINER ........ NONE ............................. NONE ................... FOR SPORLAN TXV ONLYKITS ................. 3427 ................. INLET STRAINER ........ NONE ............................. NONE ................... FOR SPORLAN TXV ONLYSTRAINER ........ 6022 ................. NONE .......................... NONE ............................. NONE ................... REFRIGERANT SERVICESTRAINER ........ 6023 ................. NONE .......................... NONE ............................. NONE ................... REFRIGERANT SERVICESTRAINER ........ 6034 ................. NONE .......................... NONE ............................. NONE ................... REFRIGERANT SERVICESTRAINER ........ 6056 ................. NONE .......................... NONE ............................. NONE ................... REFRIGERANT SERVICESTRAINER ........ 6088 ................. NONE .......................... NONE ............................. NONE ................... REFRIGERANT SERVICESTRAINER ........ 8004 ................. NONE .......................... NONE ............................. NONE ................... REFRIGERANT SERVICESTRAINER ........ 8004 ................. NONE .......................... NONE ............................. NONE ................... REFRIGERANT SERVICESTRAINER ........ 8004 ................. NONE .......................... NONE ............................. NONE ................... REFRIGERANT SERVICESTRAINER ........ 8004 ................. NONE .......................... NONE ............................. NONE ................... REFRIGERANT SERVICESOLENOID ....... 10G79B ............ 7/8 X 11/8 ..................... NONE ............................. NONE ................... HOT GAS DEFROSTSOLENOID ....... 12D11B ............ 13/8 ODF ...................... 3031RB 20S11B .............. SAME ................... HEAT RECLAIMSOLENOID ....... 12D13B ............ 15/8 ODF ...................... 3031RB 20S13B .............. SAME ................... HEAT RECLAIMSOLENOID ....... 12D17B ............ 21/8 ODF ...................... 3031RB 20S17B .............. SAME ................... HEAT RECLAIMPARTS .............. 825-005 ............ STRAINER ................... NONE ............................. NONE ................... FOR SPORLAN REGULATORPARTS .............. 825-007 ............ STRAINER ................... NONE ............................. NONE ................... FOR SPORLAN REGULATORPARTS .............. 825-009 ............ STRAINER ................... NONE ............................. NONE ................... FOR SPORLAN REGULATORPARTS .............. 825-011 ............ STRAINER ................... NONE ............................. NONE ................... FOR SPORLAN REGULATORSOLENOID ....... 8D7B ................ 7/8 ODF ....................... 3031RC 12S7B ................ SAME ................... HEAT RECLAIMSOLENOID ....... 8D7B-CV ........... 7/8 ODF ....................... NONE ............................................................ HEAT RECLAIM WITH CHECKSOLENOID ....... 8D9B ................ 11/8 ODF ...................... 3031RC 12S9B ................ SAME ................... HEAT RECLAIMKITS ................. A-3- .................. DOME .......................... NONE ............................. NONE ................... FOR SPORLAN BYPASS VALVESOLENOID ....... A3F1 ................. 3/8 SAE ........................ 100RB 2F3 ....................... SAME ................... REFRIGERANT SERVICE - VLCSOLENOID ....... A3P1 ................ 3/8 FPT ........................ 100RB 2S3 ...................... 3/8 ODF ................ REFRIGERANT SERVICE - VLCSOLENOID ....... A3S1 ................ 3/8 ODF ....................... 100RB 2S3 ...................... SAME ................... REFRIGERANT SERVICE - VLCKITS ................. A-4 ................... PILOT ASSY ................ NONE ............................. NONE ................... FOR SPORLAN REGULATORKITS ................. A-8- .................. DOME .......................... NONE ............................. NONE ................... FOR SPORLAN BYPASS VALVETXV .................. AA 20 ............... 20 TON R717 ............... TG 20 .............................. SAME ................... CHOOSE AZ OR AX BULB CHARGETXV .................. AA 30 ............... 30 TON R717 ............... NONE ............................. NONE ................... AMONIA SERVICETXV .................. AA 50 ............... 50 TON R717 ............... NONE ............................. NONE ................... AMONIA SERVICETXV .................. AA100 .............. 100 TON R717 ............. NONE ............................. NONE ................... AMONIA SERVICETXV .................. AA75 ................ 75 TON R717 ............... NONE ............................. NONE ................... AMONIA SERVICETXV .................. AAE 100 ........... 100 TON R717 ............. NONE ............................. NONE ................... AMONIA SERVICETXV .................. AAE 20 ............. 20 TON R717 ............... NONE ............................. NONE ................... AMONIA SERVICETXV .................. AAE 30 ............. 30 TON R717 ............... NONE ............................. NONE ................... AMONIA SERVICETXV .................. AAE 50 ............. 50 TON R717 ............... NONE ............................. NONE ................... AMONIA SERVICETXV .................. AAE 75 ............. 75 TON R717 ............... NONE ............................. NONE ................... AMONIA SERVICEREGULATORS .. ADRH ............... HOT GAS .................... CPHE ............................... SAME ................... SELECT CAPACITYREGULATORS .. ADRP ............... HOT GAS .................... CPHE ............................... SAME ................... SELECT CAPACITYREGULATORS .. ADRS ............... HOT GAS .................... CPHE ............................... SAME ................... SELECT CAPACITYSOLENOID ....... B10F2 ............... 1/2 SAE ........................ 200RB 6F4 ....................... SAME ................... REFRIGERANT SERVICE - VLCSOLENOID ....... B10S2 .............. 5/8 ODF ....................... 200RB 6S5 ...................... SAME ................... REFRIGERANT SERVICE - VLC

RSP-PRC022-EN120

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOSOLENOID ....... B14P2 ............... 1/2 FPT ........................ 240RA 8T4 ...................... 1/2 ODF ................ REFRIGERANT SERVICE - VLCSOLENOID ....... B14S2 .............. 5/8 ODF ....................... 240RA 8T5 ...................... SAME ................... REFRIGERANT SERVICE - VLCSOLENOID ....... B19P2 ............... 3/8 FPT ........................ 240RA 9T5 ...................... 5/8 ODF ................ REFRIGERANT SERVICE - VLCSOLENOID ....... B19S2 .............. 7/8 ODF ....................... 240RA 9T7 ...................... SAME ................... REFRIGERANT SERVICE - VLCSOLENOID ....... B25P2 ............... 1 FPT ......................... 240RA 12T9 ..................... 11/8 ODF ............... REFRIGERANT SERVICE - VLCSOLENOID ....... B25S2 .............. 7/8 ODF ....................... 240RA 12T7 ..................... SAME ................... REFRIGERANT SERVICE - VLCSOLENOID ....... B33S2 .............. 11/8 ODF ...................... 240RA 16T9 ..................... SAME ................... REFRIGERANT SERVICE - VLCKITS ................. B-3H-AR ........... DOME .................................................................... NONE ................... FOR SPORLAN BYPASS VALVEKITS ................. B-3P-AR ............ DOME .................................................................... NONE ................... FOR SPORLAN BYPASS VALVESOLENOID ....... B6F1 ................. 3/8 SAE ........................ 2OORB 3F3 ..................... SAME ................... REFRIGERANT SERVICE - VLCSOLENOID ....... B6P1 ................. 3/8 FPT ........................ 200RB 3T3 ....................... 3/8 ODF ................ REFRIGERANT SERVICE - VLCSOLENOID ....... B6S1 ................ 1/2 ODF ....................... 200RB 3T4 ...................... SAME ................... REFRIGERANT SERVICE - VLCSOLENOID ....... B9F2 ................. 3/8 SAE ........................ 200RB 5T3 ....................... 3/8 ODF ................ REFRIGERANT SERVICE - VLCSOLENOID ....... B9P2 ................. 3/8 FPT ........................ 200RB 5T3 ....................... 3/8 ODF ................ REFRIGERANT SERVICE - VLCSOLENOID ....... B9S2 ................ 1/2 ODF ....................... 200RB 5S4 ...................... SAME ................... REFRIGERANT SERVICE - VLCTXV .................. BFF-A -* ........... 1 TON R12 .................. HF 1 F * ........................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFF-AA -* ......... 1/2 TON R12 ................ HF 1/2 F * ........................ SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFF-AAA -* ...... 1/4 TON R12 ................ HF 1/4 F * ........................ SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFF-B - * ........... 11/2 TON R12 .............. HF 11/2 F * ...................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFF-C - * ........... 3 TON R12 ................. HF 31/2 F * ...................... 31/2 TON R12 ....... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFFE-A - * ........ 1 TON R12 ................... HFE 1 F * ......................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFFE-AA - * ...... 1/2 TON R12 ................ HFE 1/2 F * ...................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFFE-AAA - * ... 1/4 TON R12 ................ HFE 1/4 F * ...................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFFE-B - * ........ 11/2 TON R12 .............. HFE 11/2 F * .................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFFE-C - * ........ 3 TON R12 ................... HFE 31/2 F * .................... 31/2 TON R12 ....... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFJ-A - * .......... 11/4 TON R134 ............ HF1 M * .......................... 1 TON R134 .......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFJ-AA - * ........ 1/2 TON R134 .............. HF 1/2 M * ....................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFJ-AAA - * ..... 1/4 TON R134 .............. HF 1/4 M * ....................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFJ-B - * ........... 2 TON R134 ................. HF 13/4 M * ..................... 13/4 TON R134 .... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFJ-C - * ........... 31/2 TON R134 ............ HF 4 M * .......................... 4 TON R134 .......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFJE-A - * ........ 11/4 TON R134 ............ HFE 1 M * ....................... 1 TON R134 .......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFJE-AA - * ...... 1/2 TON R134 .............. HFE 1/2 M * ..................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFJE-AAA - * ... 1/4 TON R134 .............. HFE 1/4 M * ..................... SAME ................... *REPLACE SPORLAN C, Z, ZPWITH ALCO C, Z, MOPTXV .................. BFJE-B - * ........ 2 TON R134 ................. HFE 13/4 M * ................... 13/4 TON R134 ..... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFJE-C - * ........ 31/2 TON R134 ............ HFE 4 M * ....................... 4 TON R134 .......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFR-A - * .......... 1 TON R502 ................. HF 1 R * .......................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFR-AA - * ........ 1/2 TON R502 .............. HF 1/2 R * ........................ SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFR-AAA - * ..... 1/4 TON R502 .............. HF 1/4 R * ....................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFR-B - * .......... 2 TON R502 ................. HF 2 R * .......................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFR-C - * .......... 3 TON R502 ................. HF 31/2 R * ...................... 31/2 TON R502 ..... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFRE-A - * ........ 1 TON R502 ................. HFE 1 R * ........................ SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFRE-AA - * ..... 1/2 TON R502 .............. HFE 1/2 R * ...................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFRE-AAA - * ... 1/4 TON R502 .............. HFE 1/4 R * ...................... SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV .................. BFRE-B - * ........ 2 TON R502 ................. HFE 2 R * ........................ SAME ................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOP

Cross Reference - Upgrade to Alco

121RSP-PRC022-EN

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV .................. BFRE-C - * ........ 3 TON R502 ................. HFE 31/2 R * ................................................... 31/2 R502 .......... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFS-A -* ........... 1 TON R404 ................. HF 1 S * ......................................................... SAME ............... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFS-AA - * ........ 1/2 TON R404 .............. HF 1/2 S * ....................................................... SAME ............... *REPLACE SPORLAN C, Z, ZPP

WITH ALCO C, Z, MOPTXV .................. BFS-AAA - * ..... 1/4 TON R404 .............. HF 1/4 S * ....................................................... SAME ............... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFS-B - * .......... 2 TON R404 ................. HF 2 S * ......................................................... SAME ............... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFS-C - * .......... 3 TON R404 ................. HF 31/2 S * ..................................................... 31/2 TON R404 .. *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFSE-A - * ........ 1 TON R404 ................. HFE 1 S * ....................................................... SAME ............... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFSE-AA - * ..... 1/2 TON R404 .............. HFE 1/2 S * ..................................................... SAME ............... *REPLACE SPORLAN C, Z, ZP.............................................................................................................................................................................................. WITH ALCO C, Z, MOPTXV .................. BFSE-AAA - * ... 1/4 TON R404 .............. HFE 1/4 S * ..................................................... SAME ............... *REPLACE SPORLAN C, Z, ZP.............................................................................................................................................................................................. WITH ALCO C, Z, MOPTXV .................. BFSE-B - * ........ 2 TON R404 ................. HFE 2 S * ....................................................... SAME ............... *REPLACE SPORLAN C, Z, ZP.............................................................................................................................................................................................. WITH ALCO C, Z, MOPTXV .................. BFSE-C - * ........ 3 TON R404 ................. HFE 31/2 S * ................................................... 31/2 TON R404 .. *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFV-A - * .......... 11/2 TON R22 .............. HF 11/2 H * ..................................................... SAME ............... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFV-AA - * ........ 3/4 TON R22 ................ HF 1 H * ......................................................... 1 TON R22 ........ *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFV-AAA - * ..... 1/2 TON R22 ................ HF 1/2 H * ....................................................... SAME ............... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFV-B - * .......... 23/4 TON R22 ............. HF21/2 H * ...................................................... 21/2 TON R22 ... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFV-C - * .......... 51/4 TON R22 .............. HF 51/2 H * ..................................................... 51/2 TON R22 ... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFVE-A - * ........ 11/2 TON R22 .............. HFE 11/2 H * ................................................... SAME ............... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFVE-AA - * ..... 3/4 TON R22 ................ HFE 1 H * ....................................................... 1 TON R22 ........ *REPLACE SPORLAN C, Z, ZPP

WITH ALCO C, Z, MOPTXV .................. BFVE-AAA - * ... 1/2 TON R22 ................ HFE 1/2 H * .................................................... SAME ............... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFVE-B - * ........ 23/4 TON R22 .............. HFE 21/2 H * ................................................... 21/2 TON R22 ... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. BFVE-C - * ........ 51/4 TON R22 .............. HFE 51/2 H * ................................................... 51/2 TON R22 ... *REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPSOLENOID ....... BR183P1 .......... 3/8 FPT ........................ 210CA 3/8B 5/8B ............................................. 1/2 FPT .............. WATER SERVICESOLENOID ....... BR184P1 .......... 1/2 FPT ........................ 210CA 1/2B 1/2B ............................................. SAME ............... WATER SERVICESOLENOID ....... BR246P1 .......... 3/4 FPT ........................ 210CA 3/4B 3/4B ............................................. SAME ............... WATER SERVICEDRIER ............... C-032 ................ 1/4 SAE ........................ EK O32 ........................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-032-FM ......... 1/4 F X 1/4 M ................ EK 032 FM ...................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-032-S ............ 1/4 ODF ....................... EK 032 S ........................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-033 ................ 3/8 SAE ........................ EK O33 ........................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-033-S ............ 3/8 ODF ....................... EK 033S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-052 ................ 1/4 SAE ........................ EK 052 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-052-HH .......... 1/4 SAE ........................ BOK 052 ......................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-052-S ............ 1/4 ODF ....................... EK 052S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-052-S-HH ...... 1/4 ODF ....................... BOK 052S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-082 ................ 1/4 SAE ........................ EK 082 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-0825-S .......... 5/16 ODF ...................... EK 0825S ....................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-082-HH .......... 1/4 SAE ........................ BOK 082 ......................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-082-S ............ 1/4 ODF ....................... EK 082S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-082-S-HH ...... 1/4 ODF ....................... BOK 082S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-083 ................ 3/8 SAE ........................ EK 083 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-083-HH .......... 3/8 SAE ........................ BOK 083 ......................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-083-S ............ 3/8 ODF ....................... EK 083S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-083-S-HH ...... 3/8 ODF ....................... BOK 083S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-084 ................ 1/2 SAE ........................ EK 084 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-084-S ............ 1/2 ODF ....................... EK 084S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-084-S-T-HH .... 1/2 ODF ....................... SFD 08S4VV ................................................... SAME ............... SUCTION FILTER DRIERDRIER ............... C-14411 ............ 13/8 ODF ...................... STAS 14413T ................................................. SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-14413-G ........ 15/8 ODF ...................... STAS 14413T ................................................. SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-1449 .............. 11/8 ODF ...................... STAS 1449T ................................................... SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-144-S-TT-HH . 1/2 ODF ....................... CSFD 14S4VV ................................................ SAME ............... SUCTION FILTER DRIERDRIER ............... C-145-S-TT-HH . 5/8 ODF ....................... CSFD 14S5VV ................................................ SAME ............... SUCTION FILTER DRIERDRIER ............... C-146-S-TT-HH . 3/4 ODF ....................... CSFD 14S6VV ................................................ SAME ............... SUCTION FILTER DRIERDRIER ............... C-147-S-TT-HH . 7/8 ODF ....................... CSFD 14S7VV ................................................ SAME ............... SUCTION FILTER DRIERDRIER ............... C-149-S-TT-HH . 11/8 ODF ...................... CSFD 14S9VV ................................................ SAME ............... SUCTION FILTER DRIER

Cross Reference - Upgrade to Alco

RSP-PRC022-EN122

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCODRIER ............... C-162 ................ 1/4 SAE ........................ EK 162 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-1625-S .......... 5/16 ODF ...................... EK 1625S ....................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-162-HH .......... 1/4 SAE ........................ BOK 162 ......................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-162-S ............ 1/4 ODF ....................... EK 162S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-162-S-HH ...... 1/4 ODF ....................... BOK 162S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-163 ................ 3/8 SAE ........................ EK 163 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-163-HH .......... 3/8 SAE ........................ BOK 163 ......................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-163-S ............ 3/8 ODF ....................... EK 163S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-163-S-HH ...... 3/8 ODF ....................... BOK 163S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-164 ................ 1/2 SAE ........................ EK 164 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-164-HH .......... 1/2 SAE ........................ BOK 164 ......................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-164-S ............ 1/2 ODF ....................... EK 164S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-164-S-HH ...... 1/2 ODF ....................... BOK 164S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-164-S-T-HH .... 1/2 ODF ....................... ASK 165S-VV-HH ........................................... 5/8 ODF ............. SUCTION FILTER DRIERDRIER ............... C-165 ................ 5/8 SAE ........................ EK 165 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-165-HH .......... 5/8 SAE ........................ BOK 165 ......................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-165-S ............ 5/8 ODF ....................... EK 165S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-165-S-HH ...... 5/8 ODF ....................... BOK 165S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-165-S-T-HH .... 5/8 ODF ....................... ASK 165S-VV-HH ........................................... SAME ............... SUCTION FILTER DRIERDRIER ............... C-166-S-T-HH .... 3/4 ODF ....................... ASK 166S-VV-HH ........................................... SAME ............... SUCTION FILTER DRIERDRIER ............... C-167-S ............ 7/8 ODF ....................... EK 167S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-167-S-T-HH .... 7/8 ODF ....................... ASK 167S-VV-HH ........................................... SAME ............... SUCTION FILTER DRIERDRIER ............... C-19211 ............ 13/8 ODF ...................... STAS 19211T ................................................. SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-19213 ............ 15/8 ODF ...................... STAS 19213T ................................................. SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-19217-G ........ 21/8 ODF ...................... STAS 19217T ................................................. SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-30013 ............ 15/8 ODF ...................... ADKS 30013T ................................................. SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-30017-G ........ 21/8 ODF ...................... ADKS 30017T ................................................. SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-303 ................ 3/8 SAE ........................ EK 303 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-303-HH .......... 3/8 SAE ........................ BOK 303 ......................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-303-S ............ 3/8 ODF ....................... EK 303S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-303-S-HH ...... 3/8 ODF ....................... BOK 303S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-304 ................ 1/2 SAE ........................ EK 304 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-304-HH .......... 1/2 SAE ........................ BOK 304 ......................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-304-S ............ 1/2 ODF ....................... EK 304S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-304-S-HH ...... 1/2 ODF ....................... BOK 304S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-305 ................ 5/8 SAE ........................ EK 305 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-305-HH .......... 5/8 SAE ........................ BOK 305 ......................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-305-S ............ 5/8 ODF ....................... EK 305S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-305-S-HH ...... 5/8 ODF ....................... BOK 305S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-305-S-T-HH .... 5/8 ODF ....................... ASD 35S5VV .................................................. SAME ............... SUCTION FILTER DRIERDRIER ............... C-306-S ............ 3/4 ODF ....................... EK 306S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-306-S-T-HH .... 3/4 ODF ....................... ASK 306S-VV-HH ........................................... SAME ............... SUCTION FILTER DRIERDRIER ............... C-307-S ............ 7 8 ODF ....................... EK 307S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-307-S-T-HH .... 7/8 ODF ....................... ASK 307S-VV-HH ........................................... SAME ............... SUCTION FILTER DRIERDRIER ............... C-309-S ............ 11/8 ODF ...................... EK 309S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-309-S-T-HH .... 11/8 ODF ...................... ASK 309S-VV-HH ........................................... SAME ............... SUCTION FILTER DRIERDRIER ............... C-40017 ............ 21/8 ODF ...................... ADKS 40017T ................................................. SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-40021-G ........ 25/8 ODF ...................... ADKS 40021T ................................................. SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-40025-G ........ 31/8 ODF ...................... NONE ............................................................ NONE ............... 25/8 IS LARGESTDRIER ............... C-40029-G ........ 35/8 ODF ...................... NONE ............................................................ NONE ............... 25/8 IS LARGESTDRIER ............... C-40033-G ........ 41/8 ODF ...................... NONE ............................................................ NONE ............... 25/8 IS LARGESTDRIER ............... C-413 ................ 3/8 SAE ........................ EK 413 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-413-P ............. 3/8 FPT ........................ NONE ............................................................ NONE ............... NO PIPE THREADDRIER ............... C-414 ................ 1/2 SAE ........................ EK 414 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-414-HH .......... 1/2 SAE ........................ BOK 414 ......................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-414-S ............ 1/2 ODF ....................... EK 414S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-414-S-HH ...... 1/2 ODF ....................... BOK 414S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-415 ................ 5/8 SAE ........................ EK 415 ............................................................ SAME ............... LIQUID LINE SERVICEDRIER ............... C-415-S ............ ODF ............................. EK 415S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-417-S ............ 7/8 ODF ....................... EK 417S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-417-S-HH ...... 7/8 ODF ....................... BOK 417S ...................................................... SAME ............... BURN OUT - LIQUID LINEDRIER ............... C-417-S-T-HH .... 7/8 ODF ....................... ASD 45S7VV .................................................. SAME ............... SUCTION FILTER DRIERDRIER ............... C-419-S ............ 11/8 ODF ...................... EK 419S ......................................................... SAME ............... LIQUID LINE SERVICEDRIER ............... C-419-S-T-HH .... 11/8 ODF ...................... ASD 50S9VV .................................................. SAME ............... SUCTION FILTER DRIERDRIER ............... C-4311-S-T-HH .. 13/8 ODF ...................... SFD 54S11VV ................................................. SAME ............... SUCTION FILTER DRIERDRIER ............... C-4313-S-T-HH .. 15/8 ODF ...................... SFD 54S13VV ................................................. SAME ............... SUCTION FILTER DRIERDRIER ............... C-437-S-T-HH .... 7/8 ODF ....................... ASD 45S7VV .................................................. SAME ............... SUCTION FILTER DRIERDRIER ............... C-439-S-T-HH .... 11/8 ODF ...................... ASD 50S9VV .................................................. SAME ............... SUCTION FILTER DRIERDRIER ............... C-4811-G .......... 13/8 ODF ...................... STAS 4811T ................................................... SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-4813-G .......... 15/8 ODF ...................... STAS 4813T ................................................... SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-485 ................ 5/8 ODF ....................... STAS 485T ..................................................... SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-487 ................ 7/8 ODF ....................... STAS 487T ..................................................... SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-489-G ............ 11/8 ODF ...................... STAS 489T ..................................................... SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-607-S ............ 7 8 ODF ....................... EK 757S ......................................................... 75 CU. IN. ......... LIQUID LINE SERVICE

Cross Reference - Upgrade to Alco

123RSP-PRC022-EN

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCODRIER ............... C-607-S-T-HH .... 7/8 ODF ................................................................................................ SAME ............... SUCTION FILTER DRIERDRIER ............... C-609-S ............ 11/8 ODF ...................... EK 759S ......................................................... 75 CU. IN. ......... LIQUID LINE SERVICEDRIER ............... C-609-S-T-HH .... 11/8 ODF ...................... ASD 75S13VV ................................................ 13/8 ODF ........... SUCTION FILTER DRIERDRIER ............... C-9611-G .......... 13/8 ODF ...................... STAS 9611T ................................................... SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-9613-G .......... 15/8 ODF ...................... STAS 9613T ................................................... SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-967 ................ 7/8 ODF ....................... STAS 967T ..................................................... SAME ............... TAKE APART SHELL - LIQUIDDRIER ............... C-969 ................ 11/8 ODF ...................... STAS 969T ..................................................... SAME ............... TAKE APART SHELL - LIQUIDREGULATORS .. CCF .................. CONSTANT PRES. ...... ACP ................................................................ SAME ............... AUTO. EXPANSION VALVESOLENOID ....... CE .................... REVERSE FLOW .......... 200RB ............................................................ SAME ............... CHECK CAPACITYTXV .................. CF 2 - * ............. 2 TON R12 ................... HF 2 F * .......................................................... SAME ............... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CF 3 - * ............. 3 TON R12 ................... HF 31/2 F * ..................................................... 31/2 TON R12 ... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CFE 3 - * ........... 3 TON R12 ................... HFE 31/2 F * ................................................... 31/2 TON R12 ... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CJ 21/2 - * ........ 21/2 TON R134 ............ HF 21/2 M * .................................................... SAME ............... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CJE 21/2 - * ...... 21/2 TON R134 ............ HFE 21/2 M * .................................................. SAME ............... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPSOLENOID ....... CME ................. REVERSE FLOW .......... 200RB ............................................................ SAME ............... CHECK CAPACITYREGULATORS .. CPF .................. CONSTANT PRES. ...... CPHE .............................................................. SAME ............... AUTO. EXPANSION VALVETXV .................. CR 2 - * ............. 2 TON R502 ................ HF 2 R * ......................................................... SAME ............... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CR 4 - * ............. 4 TON R502 ................. HF 31/2 R * ..................................................... 31/2 TON R502 .. * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CRE 2 - * ........... 2 TON R502 ................. HFE 2 R * ....................................................... SAME ............... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CRE 4 - * ........... 4 TON R502 ................. HFE 31/2 R * ................................................... 31/2 TON R502 .. * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPREGULATORS .. CRO-10 ............. CRANKCASE ............... OPR-10 ........................................................... SAME ............... SELECT PRES. AND CONN.REGULATORS .. CRO-6 .............. CRANKCASE ............... OPR-6 ............................................................. SAME ............... SELECT PRES. AND CONN.REGULATORS .. CROT-10 ........... CRANKCASE ............... OPR-10 ........................................................... SAME ............... W/ ACCESS VALVEREGULATORS .. CROT-6 ............. CRANKCASE ............... OPR-6 ............................................................. SAME ............... W/ ACCESS VALVETXV .................. CS 2 - * ............. 2 TON R404 ................. HF 2 S * ......................................................... SAME ............... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CS 4 - * ............. 4 TON R404 ................. HF 31/2 S * ..................................................... 31/2 TON R404 .. * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CSE 4 - * ........... 4 TON R404 ................. HFE 31/2 S * ................................................... 31/2 TON R404 .. * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPREGULATORS .. CSF .................. CONSTANT PRES. ...... ACP ................................................................ SAME ............... AUTO. EXPANSION VALVETXV .................. CV 3 - * ............. 3 TON R22 ................... HF 3 H * ......................................................... SAME ............... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CV 5 - * ............. 5 TON R22 ................... HF 51/2 H * ..................................................... 51/2 TON R22 ... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CVE 5 - * ........... 5 TON R22 ................... HFE 51/2 H * ................................................... 51/2 TON R22 ... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPTXV .................. CVE 8 - * ........... 8 TON R22 ................... HFE 8 H * ....................................................... SAME ............... * REPLACE SPORLAN C, Z, ZP

WITH ALCO C, Z, MOPKITS ................. D-3H- ................ DOME .......................... NONE ............................................................ NONE ............... FOR SPORLAN BYPASS VALVEKITS ................. D-3P- ................ DOME .......................... NONE ............................................................ NONE ............... FOR SPORLAN BYPASS VALVEKITS ................. D-3P- ................ ELEMENT .................... NONE ............................................................ NONE ............... FOR SPORLAN BYPASS VALVEKITS ................. D-8- .................. DOME .......................... NONE ............................................................ NONE ............... FOR SPORLAN BYPASS VALVETXV .................. DA 1 ................. 1 TON R717 ................. TG 1 ............................................................... SAME ............... CHOOSE AZ OR AX BULB CHARGETXV .................. DA 10 ............... 10 TON R717 ............... TG 10 ............................................................. SAME ............... CHOOSE AZ OR AX BULB CHARGETXV .................. DA 15 ............... 15 TON R717 ............... TG 15 ............................................................. SAME ............... CHOOSE AZ OR AX BULB CHARGETXV .................. DA 2 ................. 2 TON R717 ................. TG 2 ............................................................... SAME ............... CHOOSE AZ OR AX BULB CHARGETXV .................. DA 5 ................. 5 TON R717 ................. TG 5 ............................................................... SAME ............... CHOOSE AZ OR AX BULB CHARGETXV .................. DAE 1 ............... 1 TON R717 ................. TG 1 ............................................................... SAME ............... CHOOSE AZ OR AX BULB CHARGETXV .................. DAE 10 ............. 10 TON R717 ............... TG 10 ............................................................. SAME ............... CHOOSE AZ OR AX BULB CHARGETXV .................. DAE 15 ............. 15 TON R717 ............... TG 15 ............................................................. SAME ............... CHOOSE AZ OR AX BULB CHARGETXV .................. DAE 2 ............... 2 TON R717 ................. TG 2 ............................................................... SAME ............... CHOOSE AZ OR AX BULB CHARGETXV .................. DAE 5 ............... 5 TON R717 ................. TG 5 ............................................................... SAME ............... CHOOSE AZ OR AX BULB CHARGEKITS ................. DK-12 ............... SEAT + PUSHRODS .... NONE ............................................................ NONE ............... FOR SPORLAN TXV ONLYKITS ................. DK-13 ............... SEAT + PUSHRODS .... NONE ............................................................ NONE ............... FOR SPORLAN TXV ONLYKITS ................. DK-8 ................. SEAT + PUSHRODS .... NONE ............................................................ NONE ............... FOR SPORLAN TXV ONLYREGULATORS .. DRP .................. HOT GAS .................... NONE ............................................................ TEMP. SENSINGSOLENOID ....... E10S240 ........... 1/2 ODF ....................... 200RB 6S4 ..................................................... SAME ............... REFRIGERANT SERVICE - VLCSOLENOID ....... E10S250 ........... 5/8 ODF ....................... 200RB 6S5 ..................................................... SAME ............... REFRIGERANT SERVICE - VLCSOLENOID ....... E14S250 ........... 5/8 ODF ....................... 240RA 8T5 ..................................................... SAME ............... REFRIGERANT SERVICE - VLCSOLENOID ....... E19S250 ........... 5/8 ODF ....................... 240RA 9T5 ..................................................... SAME ............... REFRIGERANT SERVICE - VLCSOLENOID ....... E19S270 ........... 7/8 ODF ....................... 240RA 9T7 ..................................................... SAME ............... REFRIGERANT SERVICE - VLCSOLENOID ....... E25S270 ........... 7/8 ODF ....................... 240RA 12T7 .................................................... SAME ............... REFRIGERANT SERVICE - VLCSOLENOID ....... E25S290 ........... 11/8 ODF ...................... 240RA 12T9 .................................................... SAME ............... REFRIGERANT SERVICE - VLC

Cross Reference - Upgrade to Alco

RSP-PRC022-EN124

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOSOLENOID ...... E34S2110 .......... 13/8 ODF .......... 905H - 14 .................................. SAME .................... REFRIGERANT SERVICE - VLCSOLENOID ...... E34S290 ............ 11/8 ODF .......... 905H - 14 .................................. SAME .................... REFRIGERANT SERVICE - VLCSOLENOID ...... E3S120 .............. 1/4 ODF ........... 100RB 2S2 ................................ SAME .................... REFRIGERANT SERVICE - VLCSOLENOID ...... E42S2130 .......... 15/8 ODF .......... 905H - 15 .................................. SAME .................... REFRIGERANT SERVICE - VLCSOLENOID ...... E42S2170 .......... 21/8 ODF .......... 905H - 15 .................................. 15/8 ODF ................ REFRIGERANT SERVICE - VLCSOLENOID ...... E5S130 .............. 3/8 ODF ........... 2OORB 2T3 .............................. SAME .................... REFRIGERANT SERVICE - VLCSOLENOID ...... E6S130 .............. 3/8 ODF ........... 200RB 3T3 ................................ SAME .................... REFRIGERANT SERVICE - VLCSOLENOID ...... E6S140 .............. 1/2 ODF ........... 200RB 3T4 ................................ SAME .................... REFRIGERANT SERVICE - VLCSOLENOID ...... E9S230 .............. 3/8 ODF ........... 200RB 5T3 ................................ SAME .................... REFRIGERANT SERVICE - VLCSOLENOID ...... E9S240 .............. 1/2 ODF ........... 200RB 5S4 ................................ SAME .................... REFRIGERANT SERVICE - VLCTXV ................. EBFF-A * ........... 1 TON R12 ....... HFS 1 F * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFF-AA - .......... 1/2 TON R12 .... HFS 1/2 F * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFF-AAA -* ..... 1/4 TON R12 .... HFS 1/4 F * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFF-B - * .......... 13/4 TON R12 .. HFS 11/2 F * ............................. 11/2 TON R12 ........ * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFF-C - * .......... 3 TON R12 ....... HFS 31/2 F * ............................. 31/2 TON R12 ........ * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFFE-A - * ....... 1 TON R12 ....... HFES 1 F * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFFE-AA - * ..... 1/2 TON R12 .... HFES 1/2 F * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFFE-AAA - * .. 1/4 TON R12 .... HFES 1/4 F * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFFE-B - * ....... 13/4 TON R12 .. HFES 11/2 F * ........................... 11/2 TON R12 ........ * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFFE-C - * ....... 3 TON R12 ....... HFES 31/2 F * ........................... 31/2 R12 ................. * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFJ-A - * ......... 11/4 TON R134 HFS 1 M * ................................. 1 TON R134 ........... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFJ-AA - * ....... 1/2 TON R134 .. HFS 1/2 M * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFJ-AAA - * .... 1/4 TON R134 .. HFS 1/4 M * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFJ-B - * .......... 2 TON R134 ..... HFS 13/4 M * ............................ 13/4 TON R134 ...... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFJ-C - * .......... 31/2 TON R134 HFS 4 M * ................................. 4 TON R134 ........... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFJE-A - * ....... 11/4 TON R134 HFES 1 M * .............................. 1 TON R134 ........... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFJE-AA - * ..... 1/2 TON R134 .. HFES 1/2 M * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFJE-AAA - * .. 1/4 TON R134 .. HFES 1/4 M * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFJE-B - * ....... 2 TON R134 ..... HFES 13/4 M * .......................... 13/4 TON R134 ...... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFJE-C - * ....... 31/2 TON R134 HFES 4 M * .............................. 4 TON R134 ........... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPV ...................... EBFR-A - * ......... 1 TON R502 ..... HFS 1 R * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFR-AA - * ...... 1/2 TON R502 .. HFS 1/2 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFR-AAA - * .... 1/4 TON R502 .. HFS 1/4 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFR-B - * ......... 2 TON R502 ..... HFS 2 R * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFR-C - * ......... 3 TON R502 ..... HFES 31/2 R * ........................... 31/2 TON R502 ...... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFRE-A - * ....... 1 TON R502 ..... HFES 1 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFRE-AA - * .... 1/2 TON R502 .. HFES 1/2 R * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFRE-AAA - * .. 1/4 TON R502 .. HFES 1/4 R * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFRE-B - * ....... 2 TON R502 ..... HFES 2 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFRE-C - * ....... 3 TON R502 ..... HFES 31/2 R * ........................... 31/2 TON R502 ...... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFS-A - * ......... 1 TON R404 ..... HFS 1 S * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFS-AA - * ...... 1/2 TON R404 .. HFS 1/2 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFS-AAA - * .... 1/4 TON R404 .. HFS 1/4 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFS-B - * ......... 2 TON R404 ..... HFS 2 S * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFS-C - * ......... 3 TON R404 ..... HFS 31/2 S * ............................. 31/2 TON R404 ...... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFSE-A - * ....... 1 TON R404 ..... HFES 1 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFSE-AA - * .... 1/2 TON R404 .. HFES 1/2 S * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFSE-AAA - * .. 1/4 TON R404 .. HFES 1/4 S * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFSE-B - * ....... 2 TON R404 ..... HFES 2 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFSE-C - * ....... 3 TON R404 ..... HFES 31/2 S * ........................... 31/2 TON R404 ...... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFV-A - * ......... 11/2 TON R22 .. HFS 11/2 H * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFV-AA - * ....... 3/4 TON R22 .... HFS 1 H * ................................. 1 TON R22 ............. * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFV-AAA - * .... 1/2 TON R22 .... HFS 1/2 H * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFV-B - * ......... 23/4 TON R22 .. HFS 21/2 H * ............................. 21/2 TON R22 ........ * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFV-C - * ......... 51/4 TON R22 .. HFS 51/2 H * ............................. 51/2 TON R22 ........ * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFVE-A - * ...... 11/2 TON R22 .. HFES 11/2 H * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFVE-AA - * .... 3/4 TON R22 .... HFES 1 H * ............................... 1 TON R22 ............. * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFVE-AAA - * .. 1/2 TON R22 .... HFES 1/2 H * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFVE-B - * ....... 23/4 TON R22 .. HFES 21/2 H * ........................... 21/2 TON R22 ........ * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBFVE-C - * ....... 51/4 TON R22 .. HFES 51/2 H * ........................... 51/2 TON R22 ........ * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBSJE 5 - * ........ 5 TON R134 ..... HFES 6 M * .............................. 6 TON R134 ........... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBSJE 7 - * ........ 7 TON R134 ..... HFES 71/2 M * .......................... 71/2 TON R134 ...... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBSRE 71/2 - * ... 71/2 TON R502 HFES 7 R * ............................... 7 TON R502 ........... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBSSE 71/2 - * ... 71/2 TON R404 HFES 7 S * ............................... 7 TON R404 ........... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBSVE 11 - * ..... 11 TON R22 ..... HFES 10 H * ............................. 10 TON R22 ........... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EBSVE 8 - * ....... 8 TON R22 ....... HFES 8 H * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFF 1 - * ............ 1 TON R12 ..... AA 1 F * .................................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFF 1/2 - * .......... 1/2 TON R12 .... AA 1/2 F * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFF 1/4 - * .......... 1/4 TON R12 .... AA 1/4 F * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFF 11/2 - * ........ 11/2 TON R12 .. AA 11/2 F * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFFE 1 - * .......... 1 TON R12 ....... AAE 1 F * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFFE 1/2 - * ........ 1/2 TON R12 .... AAE 1/2 F * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFFE 1/4 - * ........ 1/4 TON R12 .... AAE 1/4 F * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOP

Cross Reference - Upgrade to Alco

125RSP-PRC022-EN

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ................. EFFE 11/2 - * ...... 11/2 TON R12 .. AAE 11/2 F * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFFE 2 - * .......... 2 TON R12 ....... AAE 2 F * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFJ 1 - * ............ 1 TON R134 ..... AA 1 M * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFJ 1/2 - * .......... 1/2 TON R134 .. AA 1/2 M * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFJ 1/4 - * .......... 1/4 TON R134 .. AA 1/4 M * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFJ 11/2 - * ........ 11/2 TON R134 AA 11/2 M * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFJE 1 - * .......... 1 TON R134 ..... AAE 1 M * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFJE 1/2 - * ........ 1/2 TON R134 .. AAE 1/2 M * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFJE 1/4 - * ........ 1/4 TON R134 .. AAE 1/4 M * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFJE 11/2 - * ...... 11/2 TON R134 AAE 11/2 M * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFJE 2 - * .......... 2 TON R134 ..... AAE 2 M * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFR 1 - * ............ 1 TON R502 ..... AA 1 R * ................................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFR 1/2 - * ......... 1/2 TON R502 .. AA 1/2 R * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFR 1/4 - * ......... 1/4 TON R502 .. AA 1/4 R * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFR 11/2 - * ....... 11/2 TON R502 AA 11/2 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFRE 1 - * .......... 1 TON R502 ..... AAE 1 R * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFRE 1/2 - * ....... 1/2 TON R502 .. AAE 1/2 R * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFRE 1/4 - * ....... 1/4 TON R502 .. AAE 1/4 R * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFRE 11/2 - * ..... 11/2 TON R502 AAE 11/2 R * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFRE 2 - * .......... 2 TON R502 ..... AAE 2 R * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFS 1 - * ............ 1 TON R404 ..... AA 1 S * ................................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFS 1/2 - * ......... 1/2 TON R404 .. AA 1/2 S * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFS 1/4 - * ......... 1/4 TON R404 .. AA 1/4 S * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFS 11/2 - * ....... 11/2 TON R404 AA 11/2 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFSE 1 - * .......... 1 TON R404 ..... AAE 1 S * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFSE 1/2 - * ....... 1/2 TON R404 .. AAE 1/2 S * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFSE 1/4 - * ....... 1/4 TON R404 .. AAE 1/4 S * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFSE 11/2 - * ..... 11/2 TON R404 AAE 11/2 S * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFSE 2 - * .......... 2 TON R404 ..... AAE 2 S * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFV 1 - * ........... 1 TON HC ...... AA 1 H * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFV 1/2 - * ......... 1/2 TON HC ..... AA 1/2 H * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFV 11/2 - * ....... 11/2 TON HC .... AA 11/2 H * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFV 21/2 - * ....... 21/2 TON HC .... AA 21/2 H * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFVE 1 - * ......... 1 TON R22 ....... AAE 1 H * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFVE 1/2 - * ....... 1/2 TON R22 .... AAE 1/2 H * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFVE 11/2 - * ..... 11/2 TON R22 .. AAE 11/2 H * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFVE 2 - * .......... 2 TON R22 ....... AAE 2 H * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EFVE 3 - * .......... 3 TON R22 ....... AAE 3 H * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGF 1 - * ............ 1 TON R12 ....... HFS 1 F * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGF 1/2 - * ......... 1/2 TON R12 .... HFS 1/2 F * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGF 1/4 - * ......... 1/4 TON R12 .... HFS 1/4 F * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGF 1/8 - * ......... 1/8 TON R12 .... HFS 1/8 F * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGF 11/2 - * ....... 11/2 TON R12 .. HFS 11/2 F * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGFE 1 - * .......... 1 TON R12 ....... HFES 1 F * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGFE 1/2 - * ....... 1/2 TON R12 .... HFES 1/2 F * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGFE 1/4 - * ....... 1/4 TON R12 .... HFES 1/4 F * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGFE 1/8 - * ....... 1/8 TON R12 .... HFES 1/8 F * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGFE 11/2 - * ..... 11/2 TON R12 .. HFES 11/2 F * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGFE 2 - * .......... 2 TON R12 ...... HFES 2 F * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGJ 1 - * ............ 1 TON R134 ..... HFS 1 M * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGJ 1/2 - * ......... 1/2 TON R134 .. HFS 1/2 M * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGJ 1/4 - * ......... 1/4 TON R134 .. HFS 1/4 M * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGJ 11/2 - * ....... 11/2 TON R134 HFS 11/2 M * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGJE 1 - * .......... 1 TON R134 ..... HFES 1 M * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGJE 1/2 - * ....... 1/2 TON R134 .. HFES 1/2 M * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGJE 1/4 - * ....... 1/4 TON R134 .. HFES 1/4 M * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGJE 11/2 - * ..... 11/2 TON R134 HFES 11/2 M * .......................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGJE 2 - * .......... 2 TON R134 ..... HFES 21/2 M * .......................... 21/2 TON R134 ...... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGR 1 - * ........... 1 TON R502 ..... HFS 1 R * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGR 1/2 - * ........ 1/2 TON R502 .. HFS 1/2 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGR 1/4 - * ........ 1/4 TON R502 .. HFS 1/4 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGR 11/2 - * ....... 11/2 TON R502 HFS 11/2 R * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGRE 1 - * ......... 1 TON R502 ..... HFES 1 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGRE 1/2 - * ...... 1/2 TON R502 .. HFES 1/2 R * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGRE 1/4 - * ...... 1/4 TON R502 .. HFES 1/4 R * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGRE 11/2 - * .... 11/2 TON R502 HFES 11/2 R * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGRE 2 - * ......... 2 TON R502 ..... HFES 2 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGS 1 - * ........... 1 TON R404 ..... HFS 1 S * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGS 1/2 - * ........ 1/2 TON R404 .. HFS 1/2 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGS 1/4 - * ........ 1/4 TON R404 .. HFS 1/4 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGS 11/2 - * ....... 11/2 TON R404 HFS 11/2 S * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGSE 1 - * ......... 1 TON R404 ..... HFES 1 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGSE 1/2 - * ...... 1/2 TON R404 .. HFES 1/2 S * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOP

Cross Reference - Upgrade to Alco

RSP-PRC022-EN126

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ................. EGSE 1/4 - * ...... 1/4 TON R404 .. HFES 1/4 S * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGSE 11/2 - * .... 11/2 TON R404 HFES 11/2 S * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGSE 2 - * ......... 2 TON R404 ..... HFES 2 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGV 1 - * ........... 1 TON R22 ....... HFS 1 H * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGV 1/2 -* ......... 1/2 TON R22 .... HFS 1/2 H * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGV 1/5 - * ........ 1/5 TON R22 .... HFS 1/4 H * ............................... 1/4 TON R22 .......... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGV 11/2 - * ....... 11/2 TON R22 .. HFS 11/2 H * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z,TXV ................. EGV 21/2 - * ....... 21/2 TON R22 .. HFS 21/2 H * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGVE 1 - * ......... 1 TON R22 ....... HFES 1 H * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGVE 1/2 - * ...... 1/2 TON R22 .... HFES 1/2 H * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGVE 1/5 - * ...... 1/5 TON R22 .... HFES 1/4 H * ............................ 1/4 TON R22 .......... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGVE 11/2 - * .... 11/2 TON R22 .. HFES 11/2 H * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EGVE 21/2 - * .... 21/2 TON R22 .. HFES 21/2 H * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 10 F - * ...... 3/16 TON R12 .. HFS 1/4 F * ............................... 1/4 TON R12 .......... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 10 J - * ...... 1/4 TON R134 .. HFS 1/4 M * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 10 R - * ...... 1/4 TON R502 .. HFS 1/4 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 10 S - * ...... 1/4 TON R404 .. HFS 1/4 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 10 V - * ...... 1/4 TON R22 .... HFS 1/4 H * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 11 F - * ...... 1/2 TON R12 .... HFS 1/2 F * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 11 J - * ...... 1/2 TON R134 .. HFS 1/2 M * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 11 R - * ...... 1/2 TON R502 .. HFS 1/2 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 11 S - * ...... 1/2 TON R404 .. HFS 1/2 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 11 V - * ...... 1 TON R22 ....... HFS 1 H * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 12 F - * ...... 3/4 TON R12 .... HFS 1 F * .................................. 1 TON R12 ............. * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 12 J - * ...... 1 TON R134 ..... HFS 1 M * ................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 12 R - * ...... 1 TON R502 ..... HFS 1 R * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 12 S - * ...... 1 TON R404 ..... HFS 1 S * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 12 V - * ...... 11/4 TON R22 .. HFS 11/2 H * ............................. 11/2 TON R22 ........ * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 13 F - * ...... 1 TON R12 ....... HFS 1 F * .................................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 13 J - * ...... 11/4 TON R134 HFS 11/2 M * ............................ 11/2 TON R134 ...... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 13 R - * ...... 11/4 TON R502 HFS 11/4 R * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 13 S - * ...... 11/4 TON R404 HFS 11/4 S * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 13 V - * ...... 13/4 TON R22 .. HFS 2 H * ................................. 2 TON R22 ............. * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 20 F - * ...... 3/16 TON R12 .. HFSB 1/4 F * ............................. 1/4 TON R12 .......... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 20 J - * ...... 1/4 TON R134 .. HFSB 1/4 M * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 20 R - * ...... 1/4 TON R502 .. HFSB 1/4 R * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 20 S - * ...... 1/4 TON R404 .. HFSB 1/4 S * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 20 V - * ...... 1/4 TON R22 .... HFSB 1/4 H * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 21 F - * ...... 1/2 TON R12 .... HFSB 1/2 F * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 21 J - * ...... 1/2 TON R134 .. HFSB 1/2 M * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 21 R - * ...... 1/2 TON R502 .. HFSB 1/2 R * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 21 S - * ...... 1/2 TON R404 .. HFSB 1/2 S * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 21 V - * ...... 1 TON R22 ....... HFSB 1 H * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 22 F - * ...... 3/4 TON R12 .... HFSB 1/2 F * ............................. 1/2 TON R12 .......... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 22 J - * ...... 3/4 TON R134 .. HFSB 3/4 M * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 22 R - * ...... 1 TON R502 ..... HFSB 1 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 22 S - * ...... 1 TON R404 ..... HFSB 1 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 22 V - * ...... 11/4 TON R22 .. HFSB 11/2 H * .......................... 11/2 TON R22 ........ * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 23 F - * ...... 1 TON R12 ....... HFSB 1 F * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 23 J - * ...... 1 TON R134 ..... HFSB 1 M * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 23 R - * ...... 11/4 TON R502 HFSB 11/4 R * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 23 S - * ...... 11/4 TON R404 HFSB 11/4 S * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMC 23 V - * ...... 11/2 TON R22 .. HFSB 11/2 H * .......................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 10 F - * .... 3/16 TON R12 .. HFES 1/4 F * ............................. 1/4 TON R12 .......... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 10 J - * .... 1/4 TON R134 .. HFES 1/4 M * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 10 R - * ... 1/4 TON R502 .. HFES 1/4 R * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 10 S - * ... 1/4 TON R404 .. HFES 1/4 S * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 10 V - * ... 1/4 TON R22 .... HFES 1/4 H * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 11 F - * .... 1/2 TON R12 .... HFES 1/2 F * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 11 J - * .... 1/2 TON R134 .. HFES 1/2 M * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 11 R - * ... 1/2 TON R502 .. HFES 1/2 R * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 11 S - * ... 1/2 TON R404 .. HFES 1/2 S * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 11 V - * ... 1 TON R22 ....... HFES 1 H * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 12 F - * .... 3/4 TON R12 .... HFES 1 F * ................................ 1 TON R12 ............. * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 12 J - * .... 1 TON R134 ..... HFES 1 M * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 12 R - * ... 1 TON R502 ..... HFES 1 R * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 12 S - * ... 1 TON R404 ..... HFES 1 S * ............................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 12 V - * ... 11/4 TON R22 .. HFES 11/2 H * ........................... 11/2 TON R22 ........ * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 13 F - * .... 1 TON R12 ....... HFES 1 F * ................................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 13 J - * .... 11/4 TON R134 HFES 11/2 M * .......................... 11/2 TON R134 ...... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 13 R - * ... 11/4 TON R502 HFES 11/4 R * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 13 S - * ... 11/4 TON R404 HFES 11/4 S * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 13 V - * ... 13/4 TON R22 .. HFES 2 H * ............................... 2 TON R22 ............. * REPLACE SPORLAN C, Z, ZP P WITH ALCO C, Z, MOP

Cross Reference - Upgrade to Alco

127RSP-PRC022-EN

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTTXV ............... EMCE 20 F - * .... 3/16 TON R12 .. HFSEB 1/4 F * ........................... 1/4 TON R12 .......... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 20 J - * .... 1/4 TON R134 .. HFESB 1/4 M * ......................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 20 R - * ... 1/4 TON R502 .. HFESB 1/4 R * .......................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 20 S - * ... 1/4 TON R404 .. HFESB 1/4 S * .......................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 20 V - * ... 1/4 TON R22 .... HFESB 1/4 H * .......................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 21 F - * .... 1/2 TON R12 .... HFSEB 1/2 F * ........................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 21 J - * .... 1/2 TON R134 .. HFESB 1/2 M * ......................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 21 R - * ... 1/2 TON R502 .. HFESB 1/2 R * .......................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 21 S - * ... 1/2 TON R404 .. HFESB 1/2 S * .......................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 21 V - * ... 1 TON R22 ....... HFESB 1 H * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 22 F - * .... 3/4 TON R12 .... HFSEB 1/2 F * ........................... 1/2 TON R12 .......... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 22 J - * .... 3/4 TON R134 .. HFESB 3/4 M * ......................... SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 22 R - * ... 1 TON R502 ..... HFESB 1 R * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 22 S - * ... 1 TON R404 ..... HFESB 1 S * ............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 22 V - * ... 11/4 TON R22 .. HFESB 11/2 H * ........................ 11/2 TON R22 ........ * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 23 F - * .... 1 TON R12 ....... HFSEB 1 F * .............................. SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 23 J - * .... 1 TON R134 ..... HFESB 1 M * ............................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 23 R - * ... 11/4 TON R502 HFESB 11/4 R * ........................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 23 S - * ... 11/4 TON R404 HFESB 11/4 S * ........................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EMCE 23 V - * ... 11/2 TON R22 .. HFESB 11/2 H * ........................ SAME .................... * REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. EQ-0-FC ............. 1/5 TON R12 .... HFS 1/8 FC ................................ 1/8 TON R12 .......... HF IS BALANCED PORTTXV ................. EQ-0-JC ............. 1/4 TON R134 .. HFS 1/4 MC .............................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-0-RC ............ 1/5 TON R502 .. HFS 1/4 RC ............................... 1/4 TON R502 ........ HF IS BALANCED PORTTXV ................. EQ-0-VC ............ 1/4 TON R22 .... HFS 1/4 HC ............................... SAME .................... HF IS BALANCED PORTTXV ................. EQ-1-FC ............. 1/2 TON R12 .... HFS 1/2 FC ................................ SAME .................... HF IS BALANCED PORTTXV ................. EQ-1-JC ............. 1/2 TON R134 .. HFS 1/2 MC .............................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-1-RC ............ 1/2 TON R502 .. HFS 1/2 RC ............................... SAME .................... HF IS BALANCED PORTTXV ................. EQ-1-VC ............ 3/4 TON R22 .... HFS 1 HC .................................. 1 TON R22 ............. HF IS BALANCED PORTTXV ................. EQ-2-FC ............. 5/8 TON R12 .... HFS 1/2 FC ................................ 1/2 TON R12 .......... HF IS BALANCED PORTTXV ................. EQ-2-JC ............. 3/4 TON R134 .. HFS 3/4 MC .............................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-2-RC ............ 5/8 TON R502 .. HFS 1/2 RC ............................... 1/2 TON R502 ........ HF IS BALANCED PORTTXV ................. EQ-2-VC ............ 1 TON R22 ....... HFS 1 HC .................................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-3-FC ............. 1 TON R12 ....... HFS 1 FC .................................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-3-JC ............. 11/4 TON R134 HFS 11/2 MC ............................ 11/2 TON R134 ...... HF IS BALANCED PORTTXV ................. EQ-3-RC ............ 1 TON R502 ..... HFS 1 RC .................................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-3-VC ............ 11/2 TON R22 .. HFS 11/2 HC ............................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-4-FC ............. 11/2 TON R12 .. HFS 11/2 FC .............................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-4-JC ............. 11/2 TON R134 HFS 11/2 MC ............................ SAME .................... HF IS BALANCED PORTTXV ................. EQ-4-RC ............ 11/2 TON R502 HFS 11/2 RC ............................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-4-VC ............ 21/2 TON R22 .. HFS 21/2 HC ............................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-5-FC ............. 2 TON R12 ....... HFS 2 FC .................................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-5-JC ............. 21/2 TON R134 HFS 21/2 MC ............................ SAME .................... HF IS BALANCED PORTTXV ................. EQ-5-RC ............ 2 TON R502 ..... HFS 2 RC .................................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-5-VC ............ 31/2 TON R22 .. HFS 3 HC .................................. 3 TON R22 ............. HF IS BALANCED PORTTXV ................. EQ-6-RC ............ 3 TON R502 ..... HFS 3 RC .................................. SAME .................... HF IS BALANCED PORTTXV ................. EQ-6-VC ............ 5 TON R22 ....... HFS 51/2 HC ............................. 51/2 TON R22 ........ HF IS BALANCED PORTTXV ................. EQE-0-FC ........... 1/5 TON R12 .... HFES 1/8 FC .............................. 1/8 TON R12 .......... HF IS BALANCED PORTTXV ................. EQE-0-JC ........... 1/4 TON R134 .. HFES 1/4 MC ............................ SAME .................... HF IS BALANCED PORTTXV ................. EQE-0-RC .......... 1/5 TON R502 .. HFES 1/4 RC ............................. 1/4 TON R502 ........ HF IS BALANCED PORTTXV ................. EQE-0-VC .......... 1/4 TON R22 .... HFES 1/4 HC ............................. SAME .................... HF IS BALANCED PORTTXV ................. EQE-1-FC ........... 1/2 TON R12 .... HFES 1/2 FC .............................. SAME .................... HF IS BALANCED PORTTXV ................. EQE-1-JC ........... 1/2 TON R134 .. HFES 1/2 MC ............................ SAME .................... HF IS BALANCED PORTTXV ................. EQE-1-RC .......... 1/2 TON R502 .. HFES 1/2 RC ............................. SAME .................... HF IS BALANCED PORTTXV ................. EQE-1-VC .......... 3/4 TON R22 .... HFES 1 HC ................................ 1 TON R22 ............. HF IS BALANCED PORTTXV ................. EQE-2-FC ........... 5/8 TON R12 .... HFES 1/2 FC .............................. 1/2 TON R12 .......... HF IS BALANCED PORTTXV ................. EQE-2-JC ........... 3/4 TON R134 .. HFES 3/4 MC ............................ SAME .................... HF IS BALANCED PORTTXV ................. EQE-2-RC .......... 5/8 TON R502 .. HFES 1/2 RC ............................. 1/2 TON R502 ........ HF IS BALANCED PORTTXV ................. EQE-2-VC .......... 1 TON R22 ....... HFES 1 HC ................................ SAME .................... HF IS BALANCED PORTTXV ................. EQE-3-FC ........... 1 TON R12 ....... HFES 1 FC ................................ SAME .................... HF IS BALANCED PORTTXV ................. EQE-3-JC ........... 11/4 TON R134 HFES 11/2 MC .......................... 11/2 TON R134 ...... HF IS BALANCED PORTTXV ................. EQE-3-RC .......... 1 TON R502 ..... HFES 1 RC ................................ SAME .................... HF IS BALANCED PORTTXV ................. EQE-3-VC .......... 11/2 TON R22 .. HFES 11/2 HC ........................... SAME .................... HF IS BALANCED PORTTXV ................. EQE-4-FC ........... 11/2 TON R12 .. HFES 11/2 FC ............................ SAME .................... HF IS BALANCED PORTTXV ................. EQE-4-JC ........... 11/2 TON R134 HFES 11/2 MC .......................... SAME .................... HF IS BALANCED PORTTXV ................. EQE-4-RC .......... 11/2 TON R502 HFES 11/2 RC ........................... SAME .................... HF IS BALANCED PORTTXV ................. EQE-4-VC .......... 21/2 TON R22 .. HFES 21/2 HC ........................... SAME .................... HF IS BALANCED PORTTXV ................. EQE-5-FC ........... 2 TON R12 ....... HFES 2 FC ................................ SAME .................... HF IS BALANCED PORTTXV ................. EQE-5-JC ........... 21/2 TON R134 HFES 21/2 MC .......................... SAME .................... HF IS BALANCED PORTTXV ................. EQE-5-RC .......... 2 TON R502 ..... HFES 2 RC ................................ SAME .................... HF IS BALANCED PORTTXV ................. EQE-5-VC .......... 31/2 TON R22 .. HFES 3 HC ................................ 3 TON R22 ............. HF IS BALANCED PORT

Cross Reference - Upgrade to Alco

RSP-PRC022-EN128

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ................. EQE-6-RC .......... 3 TON R502 ..... HFES 3 RC ................................ SAME .................... HF IS BALANCED PORTTXV ................. EQE-6-VC .......... 5 TON R22 ....... HFES 51/2 HC ........................... 51/2 TON R22 ........ HF IS BALANCED PORTTXV ................. FF 1 - * .............. 1 TON R12 .... AFA 1 F * .................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FF 1/2 - * ............ 1/2 TON R12 .... AFA 1/2 F * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FF 1/4 - * ............ 1/4 TON R12 .... AFA 1/4 F * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FF 1/8 - * ............ 1/8 TON R12 .... AFA 1/8 F * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FF 11/2 - * .......... 11/2 TON R12 .. AFA 11/2 F * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FFE 1 - * ............ 1 TON R12 ....... AFAE 1 F * ................................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FFE 1/2 - * .......... 1/2 TON R12 .... AFAE 1/2 F * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FFE 1/4 - * .......... 1/4 TON R12 .... AFAE 1/4 F * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FFE 11/2 - * ........ 11/2 TON R12 .. AFAE 11/2 F * ........................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FFE 2 - * ............ 2 TON R12 ....... AFAE 2 F * ................................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FJ 1 - * .............. 1 TON R134 ..... AFA 1 M * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FJ 1/2 - * ............ 1/2 TON R134 .. AFA 1/2 M * .............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FJ 1/4 - * ............ 1/4 TON R134 .. AFA 1/4 M * .............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FJ 11/2 - * .......... 11/2 TON R134 AFA 11/2 M * ............................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FJE 1 - * ............ 1 TON R134 ..... AFAE 1 M * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FJE 1/2 - * .......... 1/2 TON R134 .. AFAE 1/2 M * ............................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FJE 1/4 - * .......... 1/4 TON R134 .. AFAE 1/4 M * ............................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FJE 11/2 - * ........ 11/2 TON R134 AFAE 11/2 M * .......................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FJE 2 - * ............ 2 TON R134 ..... AFAE 2 M * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FR 1 - * .............. 1 TON R502 .... AFA 1 R * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FR 1/2 - * ........... 1/2 TON R502 .. AFA 1/2 R * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FR 1/4 - * ........... 1/4 TON R502 .. AFA 1/4 R * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FR 11/2 - * ......... 11/2 TON R502 AFA 11/2 R * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FRE 1 - * ............ 1 TON R502 ..... AFAE 1 R * ................................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FRE 1/2 - * ......... 1/2 TON R502 .. AFAE 1/2 R * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FRE 1/4 - * ......... 1/4 TON R502 .. AFAE 1/4 R * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FRE 11/2 - * ....... 11/2 TON R502 AFAE 11/2 R * ........................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FRE 2 - * ............ 2 TON R502 ..... AFAE 2 R * ................................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FS 1/2 - * ........... 1/2 TON R404 .. AFA 1/2 S * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FS 1/4 - * ........... 1/4 TON R404 .. AFA 1/4 S * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FS 11/2 - * ......... 11/2 TON R404 AFA 11/2 S * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FS1 - * ............... 1 TON R404 ..... AFA 1 S * .................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FSE 1 - * ............ 1 TON R404 ..... AFAE 1 S * ................................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FSE 1/2 - * ......... 1/2 TON R404 .. AFAE 1/2 S * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FSE 1/4 - * ......... 1/4 R404 ........... AFAE 1/4 S * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FSE 11/2 - * ....... 11/2 TON R404 AFAE 11/ 2 S * .......................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FSE 2 - * ............ 2 TON R404 ..... AFAE 2 S .................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FV 1 - * .............. 1 TON R22 ....... AFA 1 H * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FV 1/2 - * ........... 1/2 TON R22 .... AFA 1/2 H * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FV 11/2 - * ......... 11/2 TON R22 .. AFA 11/2 H * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FV 2 - * .............. 2 TON R22 ....... AFA 2 H * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FVE 1 - * ............ 1 TON R22 ....... AFAE 1 H * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FVE 1/2 - * ......... 1/2 TON R22 .... AFAE 1/2 H * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FVE 11/2 - * ....... 11/2 TON R22 .. AFAE 11/2 H * ........................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FVE 2 - * ............ 2 TON R22 ....... AFAE 2 H * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. FVE 3 - * ............ 3 TON R22 ....... AFAE 3 H * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GF 1 - * .............. 1 TON R12 ....... HF 1 F * .................................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GF 1/2 - * ........... 1/2 TON R12 .... HF 1/2 F * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GF 1/4 - * ........... 1/4 TON R12 .... HF 1/4 F * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GF 1/8 - * ........... 1/8 TON R12 .... HF 1/8 F * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GF 11/2 - * ......... 11/2 TON R12 .. HF 11/2 F * ................................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GFE 1 - * ............ 1 TON R12 ....... HFE 1 F * .................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GFE 1/2 - * ......... 1/2 TON R12 .... HFE 1/2 F * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GFE 1/4 - * ......... 1/4 TON R12 .... HFE 1/4 H * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GFE 1/8 - * ......... 1/8 TON R12 .... HFE 1/8 F * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GFE 11/2 - * ....... 11/2 TON R12 .. HFE 11/2 F * ............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GFE 2 - * ............ 2 TON R12 ....... HFE 2 F * .................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GJ 1 - * .............. 1 TON R134 ..... HF 1 M * ................................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GJ 1/2 - * ........... 1/2 TON R134 .. HF 1/2 M * ................................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GJ 1/4 - * ........... 1/4 TON R134 .. HF 1/4 M * ................................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GJ 11/2 - * ......... 11/2 TON R134 HF11/2 M * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GJE 1 - * ............ 1 TON R134 ..... HFE 1 M * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GJE 1/2 - * ......... 1/2 TON R134 .. HFE 1/2 M * .............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GJE 1/4 - * ......... 1/4 TON R134 .. HFE 1/4 M * .............................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GJE 11/2 - * ....... 11/2 TON R134 HFE 11/2 M * ............................ SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GJE 2 - * ............ 2 TON R134 ..... HFE 2 M * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GR 1 - * ............. 1 TON R502 ..... HF 1 R * .................................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GR 1/2 - * ........... 1/2 TON R502 .. HF 1/2 R * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GR 1/4 - * ........... 1/4 TON R502 .. HF 1/4 R * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GR 1/8 - * ........... 1/8 TON R502 .. HF 1/8 R * ................................. SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GR 11/2 - * ......... 11/2 TON R502 HF 11/2 R * ............................... SAME .................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOP

Cross Reference - Upgrade to Alco

129RSP-PRC022-EN

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ................. GRE 1 - * ........... 1 TON R502 ................. HFE 1 R * ................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GRE 1/2 - * ........ 1/2 TON R502 .............. HFE 1/2 R * ................................. SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GRE 1/2 - * ........ 1/2 TON R502 .............. HFE 1/2 R * ................................. SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GRE 1/4 - * ........ 1/4 TON R502 .............. HFE 1/4 R * ................................. SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GRE 11/2 - * ....... 11/2 TON R502 ............ HFE 11/2 R * ............................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GRE 2 - * ........... 2 TON R502 ................. HFE 2 R * ................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GS 1 - * ............. 1 TON R404 ................. HF 1 S * ..................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GS 1/2 - * ........... 1/2 TON R404 .............. HF 1/2 S * ................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GS 1/4 - * ........... 1/4 TON R404 .............. HF 1/4 S * ................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GS 1/8 - * ........... 1/8 TON R404 .............. HF 1/8 S * ................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GS 11/2 - * ......... 11/2 TON R404 ............ HF 11/2 S * ................................. SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GSE 1 - * ........... 1 TON R404 ................. HFE 1 S * ................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GSE 1/2 - * ........ 1/2 TON R404 .............. HFE 1/2 S * ................................. SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GSE 1/4 - * ........ 1/4 TON R404 .............. HFE 1/4 S * ................................. SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GSE 11/2 - * ....... 11/2 TON R404 ............ HFE 11/2 S * ............................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GSE 2 - * ........... 2 TON R404 ................. HFE 2 S * ................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GV 1 - * ............. 1 TON R22 ................... HF 1 H * ..................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GV 1/2 - * ........... 1/2 TON R22 ................ HF 1/2 H * ................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GV 11/2 - * ......... 11/2 TON R22 .............. HF 11/2 H * ................................. SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GV 21/2 - * ......... 21/2 TON R22 .............. HF 21/2 H * ................................. SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GVE 1 - * .......... 1 TON R22 ................... HFE 1 H * ................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GVE 1/2 - * ........ 1/2 TON R22 ................ HFE 1/2 H * ................................ SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GVE 11/2 - * ....... 11/2 TON R22 .............. HFE 11/2 H * ............................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GVE 21/2 - * ....... 21/2 TON R22 .............. HFE 2 H * ................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. GVE 3 - * ........... 3 TON R22 ................... HFE 3 H * ................................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HFE 11/2 - * ....... 11/2 TON R12 .............. HFES 11/2 F * ............................. SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HFE 12 - * .......... 12 TON R12 ................. HFES 12 F * ................................ 12 TON R12 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HFE 3 - * ............ 3 TON R12 ................... HFES 31/2 F * ............................. 31/2 TON R12 ...... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HFE 4 - * ............ 4 TON R12 ................... HFES 31/2 F * ............................. 31/2 TON R12 ...... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HFE 5 - * ............ 5 TON R12 ................... HFES 5 F * .................................. SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HFE 8 - * ............ 8 TON R12 ................... HFES 9 F * .................................. 9 TON R12 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HJE 11/2 - * ....... 11/2 TON R134 ............ HFES 11/2 M * ........................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HJE 12 - * .......... 12 TON R134 ............... HFES 11 M * .............................. 11 TON R134 ....... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HJE 4 - * ............ 4 TON R134 ................. HFES 4 M * ................................ SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HJE 5 - * ............ 5 TON R134 ................. HFES 6 M * ................................ 6 TON R134 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HJE 8 - * ............ 8 TON R134 ................. HFES 71/2 M * ........................... 71/2 TON R134 ..... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPDRIER .............. HPC-103 ............ 3/8 SAE ........................ BFK 083 ...................................... SAME .................. BI - FLOWDRIER .............. HPC-103-S ......... 3/8 ODF ....................... BFK 083S ................................... SAME .................. BI - FLOWDRIER .............. HPC-104 ............ 1/2 SAE ........................ BFK 084 ...................................... SAME .................. BI - FLOWDRIER .............. HPC-104-S ......... 1/2 ODF ....................... BFK 084S ................................... SAME .................. BI - FLOWDRIER .............. HPC-163-HH ...... 3/8 SAE ........................ BFK 163 ...................................... SAME .................. BI - FLOWTXV ................. GRE 1/4 - * ........ 1/4 TON R502 .............. HFE 1/4 R * ................................. SAME .................. *REPLACE SPORLAN C, Z, ZPDRIER .............. HPC-164-HH ...... 1/2 SAE ........................ BFK 164 ...................................... SAME .................. BI - FLOWDRIER .............. HPC-164-S-HH ... 1/2 ODF ....................... BFK 164S ................................... SAME .................. BI - FLOWDRIER .............. HPC-165-HH ...... 5/8 SAE ........................ BFK 165 ...................................... SAME .................. BI - FLOWDRIER .............. HPC-165-S-HH ... 5/8 ODF ....................... BFK 165S ................................... SAME .................. BI - FLOWTXV ................. HRE 11/2 - * ....... 11/2 TON R502 ............ HFES 11/2 R * ............................ 11/2 TON R502 ..... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HRE 12 - * .......... 12 TON R502 ............... HFES 13 R * ............................... 13 TON R502 ....... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPIXV .................. HRE 3 - * ........... 3 TON R502 ................. HFES 31/2 R * ............................ 31/2 TON R502 ..... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HRE 4 - * ........... 4 TON R502 ................. HFES 31/2 R * ............................ 31/2 TON R502 ..... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HRE 61/2 - * ....... 61/2 TON R502 ............ HFES 7 R * ................................. 7 TON R502 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HRE 9 - * ........... 9 TON R502 ................. HFES 10 R * ............................... 10 TON R502 ....... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HSE 11/2 - * ....... 11/2 TON R404 ............ HFES 11/2 S * ............................ SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HSE 12 - * .......... 12 TON R404 ............... HFES 13 S * ............................... 13 TON R404 ....... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HSE 3 - * ........... 3 TON R404 ................. HFES 31/2 S * ............................ 31/2 TON R404 ..... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HSE 4 - * ........... 4 TON R404 ................. HFES 31/2 S * ............................ 31/2 TON R404 ..... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HSE 61/2 - * ....... 61/2 TON R404 ............ HFES 7 S * ................................. 7 TON R404 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HSE 9 - * ........... 9 TON R404 ................. HFES 10 S * ............................... 10 TON R404 ....... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HVE 11 - * .......... 11 TON R22 ................. HFES 10 H * ............................... 10 TON R22 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HVE 16 - * .......... 16 TON R22 ................. HFES 15 H * ............................... 15 TON R22 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HVE 20 - * .......... 20 TON R22 ................. HFES 20 H * ............................... SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HVE 21/2 - * ....... 21/2 TON R22 .............. HFES 21/2 H * ............................ SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HVE 51/2 - * ....... 51/2 TON R22 .............. HFES 51/2 H * ............................ SAME .................. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. HVE 7 - * ........... 7 TON R22 ................... HFES 8 H * ................................. 8 TON R22 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPKITS ................ K-1178 ............... ADAPTOR-FLANGE ..... NONE ........................................ NONE .................. FOR SPORLAN TXV ONLYKITS ................ K-1800E-1 .......... DOME .......................... NONE ........................................ NONE .................. FOR SPORLAN BYPASS VALVEKITS ................ K-1800E-2 .......... DOME .......................... NONE ........................................ NONE .................. FOR SPORLAN BYPASS VALVEKITS ................ KA-1 .................. SEAL CAP .................... NONE ........................................ NONE .................. FOR SPORLAN TXV ONLYKITS ................ KA-2 .................. SEAL CAP .................... NONE ........................................ NONE .................. FOR SPORLAN TXV ONLYKITS ................ KA-3 .................. SEAL CAP .................... NONE ........................................ NONE .................. FOR SPORLAN TXV ONLYKITS ................ KA-4 .................. SEAL CAP .................... NONE ........................................ NONE .................. FOR SPORLAN TXV ONLYKITS ................ KA-5X ................ SEAL CAP .................... NONE ........................................ NONE .................. FOR SPORLAN TXV ONLYKITS ................ KA-6 .................. SEAL CAP .................... NONE ........................................ NONE .................. FOR SPORLAN TXV ONLY

Cross Reference - Upgrade to Alco

RSP-PRC022-EN130

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOKITS ................ KA-7 .................. SEAL CAP .................... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KA-8 .................. SEAL CAP .................... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYSOLENOID ...... KBR183P1 ......... 3/8 FPT ........................ NONE ................................... STAINLESS STEEL ... NONESOLENOID ...... KBR184P1 ......... 1/2 FPT ........................ NONE ................................... STAINLESS STEEL ... NONESOLENOID ...... KBR246P1 ......... 3/4 FPT ........................ NONE ................................... STAINLESS STEEL ... NONEKITS ................ KE-10 ................ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-18 ................ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-19 ................ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-25 ................ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-3 .................. ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-33 ................ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-6 .................. ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-8D ................ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-9 .................. ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-MA32 ........... ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-MA42 ........... ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-MA5 ............. ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-MA50 ........... ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KG-SORIT-P1 ..... GASKETS .................... NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KM-1 ................. MANUAL STEM .......... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KM-2 ................. MANUAL STEM .......... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KM-3 ................. MANUAL STEM .......... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KM-4 ................. MANUAL STEM .......... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KM-5 ................. MANUAL STEM .......... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KM-6 ................. MANUAL STEM .......... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KO-10 ................ SPRING ....................... NONE ................................... NONE ....................... FOR SPORLAN BYPASS VALVEKITS ................ KO-8 .................. SPRING ....................... NONE ................................... NONE ....................... FOR SPORLAN BYPASS VALVEKITS ................ K-ORIT-P1 .......... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KP01 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KP02 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KP03 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KP08 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KP09 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KP10 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KP12 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KP13 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KP16 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KP17 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KP19 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ K-P1-E ............... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KP20 .................. SEAT + PUSHRODS .... NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYSOLENOID ...... KR183P1 ............ 3/8 FPT ........................ NONE ................................... STAINLESS STEEL ... NONESOLENOID ...... KR184P1 ............ 1/2 FPT ........................ NONE ................................... STAINLESS STEEL ... NONESOLENOID ...... KR246P1 ............ 3/4 FPT ........................ NONE ................................... STAINLESS STEEL ... NONEKITS ................ KS-10G .............. ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-10GP-B ........ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-10GP-C ........ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-12DB ............ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-12DB-SC ...... ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-12DC ............ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-12DC-SC ...... ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-12D-CV ........ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-12DP ............ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-16DB ............ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-16DB-SC ...... ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-16DC ............ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-16DC-SC ...... ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-16D-CV ........ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-16DP ............ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-16DP-SC ...... ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-73 ................ STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-8D ................ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-8DB ............. ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-8DB-SC ........ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-8DC ............. ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-8DC-SC ........ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-A10 .............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSSIGHT GLASS . K-SA-4 ............... KIT ............................... NONE ................................... NONE ....................... REFRIGERANT SERVICEKITS ................ KS-B10 .............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-B10 .............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-B14 .............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDS

Cross Reference - Upgrade to Alco

131RSP-PRC022-EN

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOKITS ................ KS-B14 .............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-B19 .............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-B19 .............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-B25 .............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-B25 .............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-B33 .............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-10 ................ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KE-10 ................ ENCLOSING TUBE ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSTS ................... KS-B6 ................ STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-B9 ................ STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-B9 ................ STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-BR18 ............ COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-BR24 ............ COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-CB10 ............ STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-CB14 ............ STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-CB19 ............ STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-CDA-12P ...... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-CDA-12S ...... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-CDA-15P ...... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-CDA-20P ...... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-DB14 ............ COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-DB19 ............ COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-DMA17 ........ COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-DMA24 ........ COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-DMA32 ........ COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-E34 .............. COIL HOUSING ........... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-E42 .............. COIL HOUSING ........... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-MA17A ........ STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-MA32 ........... STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-MA42 ........... STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-MA50 ........... STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-MA5A .......... STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-OB10 ........... COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-OB14 ........... COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-OB19 ........... COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-OB25 ........... COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-OB33 ........... COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-OB9 ............. COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-OE33 ............ COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-OE34 ............ COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-OE42 ............ COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-ORI-12 ......... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-ORI-15 ......... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-ORI-15 ......... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-ORI-20 ......... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-ORI-20 ......... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ K-SORIT-P1 ....... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-R18 .............. COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-R24 .............. COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-RW3 ............. COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-SHGB-15 ...... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN BYPASS VALVEKITS ................ KS-SORIT-P12 ... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-SORIT-P13 ... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-SORIT-P14 ... PILOT ASSY ................ NONE ................................... NONE ....................... FOR SPORLAN REGULATORKITS ................ KS-W14 ............. COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-W19 ............. COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-W25 ............. COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-W3 ............... COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-W6 ............... COMPLETE REPAIR ..... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-XJH ............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-XPO ............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-XRM ............ STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-XRN ............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KS-XUP ............. STEM + PLUNGER ...... NONE ................................... NONE ....................... FOR SPORLAN SOLENOIDSKITS ................ KT-23 ................. POWER ASSY. ............. NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KT-33 ................. POWER ASSY. ............. NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KT-43 ................. POWER ASSY. ............. NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KT-63 ................. POWER ASSY. ............. NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KY-12 ................. POWER ASSY. ............. NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KY-53 ................. POWER ASSY. ............. NONE ................................... NONE ....................... FOR SPORLAN TXV ONLYKITS ................ KY-83 ................. POWER ASSY. ............. NONE ................................... NONE ....................... FOR SPORLAN TXV ONLY

Cross Reference - Upgrade to Alco

RSP-PRC022-EN132

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOKITS ................ K-Y917 .............. PILOT ASSY ......... NONE ........................................... NONE ....................... FOR SPORLAN BYPASS VALVEREGULATORS . LAC-4 ................ HEAD PRES. ......... HPC5 ............................................. SAME ....................... SELECT PRES. AND CONN.TXV ................. LMC .................. VARIOUS .............. NONE ........................................... NONE ....................... LEVEL MASTER CONTROLSOLENOID ...... MA17A3 ............ 1/2 FPT ................. 905H - 12 ....................................... SAME ....................... AMMONIA SERVICE - VLCSOLENOID ...... MA32P3 ............ 11/4 FPT ................ 905H - 14 ....................................... SAME ....................... AMMONIA SERVICE - VLCSOLENOID ...... MA42P3 ............ 11/2 FPT ................ 905H - 15 ....................................... 11/4 FPT ................... AMMONIA SERVICE - VLCSOLENOID ...... MA50P3 ............ 2 FPT .................... 905H - 16 ....................................... 11/2 FPT ................... REFRIGERANT SERVICE - VLCSOLENOID ...... MA50P3 ............ 2 FPT .................... 905H - 16 ....................................... 11/2 FPT ................... AMMONIA SERVICE - VLCSOLENOID ...... MA5A3 .............. 1/4 FPT ................. NONE .............................................................................. AMMONIA SERVICESOLENOID ...... MB10S2 ............ 5/8 ODF ................ 200RB6T5M .................................. SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... MB10S240 ........ 5/8 ODF ................ 200RB 6T5M ................................. SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... MB14S2 ............ 5/8 ODF ................ 240RA 8T5M ................................. SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... MB19S2 ............ 5/8 ODF ................ 240RA 9T5M ................................. SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... MB25S2 ............ 7/8 ODF ................ 240RA 12T7M ............................... SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... MB33S2 ............ 11/8 ODF ............... 240RA 16 T9M .............................. SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... MB6S1 .............. 1/2 ODF ................ 200RB 3T4T .................................. SAME ....................... ADD MANUAL STEM KITSOLENOID ...... MB9S2 .............. 1/2 ODF ................ 200RB 5T4M ................................. SAME ....................... REFRIGERANT SERVICE - VLCTXV ................. MC 10 F - * ........ 3/16 TON R12 ....... HF 1/4 F * ...................................... 1/4 TON R12 ............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 10 J - * ........ 1/4 TON R134 ....... HF 1/4 M * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 10 R - * ........ 1/4 TON R502 ....... HF 1/4 R * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 10 S - * ........ 1/4 TON 404 .......... HF 1/4 S * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 10 V - * ........ 1/4 TON R22 ......... HF 1/4 H * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 11 F - * ........ 1/2 TON R12 ......... HF 1/2 F * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 11 J - * ........ 1/2 TON R134 ....... HF 1/2 M * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 11 R - * ........ 1/2 TON R502 ....... HF 1/2 R * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 11 S - * ........ 1/2 TON R404 ....... HF 1/2 S * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 11 V - * ........ 1 TON R22 ............ HF 1 H * ........................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 12 F - * ........ 3/4 TON R12 ......... HF 1 F * ......................................... 1 TON R12 ................ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 12 J - * ........ 1 TON R134 .......... HF 1 M * ....................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 12 R - * ........ 1 TON R502 .......... HF 1 R * ........................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 12 S - * ........ 1 TON R404 .......... HG 1 S * ....................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 12 V - * ........ 11/2 TON R22 ....... HF 11/2 H * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 13 F - * ........ 1 TON R12 ............ HF 1 F * ......................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 13 J - * ........ 11/4 TON R134 ..... HF 11/2 M * ................................... 11/2 TON R134 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 13 R - * ........ 11/4 TON R502 ..... HF 11/4 R * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 13 S - * ........ 11/4 TON R404 ..... HF 11/4 S * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 13 V - * ........ 13/4 TON R22 ....... HF 2 H * ........................................ 2 TON R22 ................ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 20 F - * ........ 3/16 TON R12 ....... HFB 1/4 F * .................................... 1/4 TON R12 ............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 20 J - * ........ 1/4 TON R134 ....... HFB 1/4 M * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 20 R - * ........ 1/4 TON R502 ....... HFB 1/4 R * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 20 S - * ........ 1/4 TON R404 ....... HFB 1/4 S * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 20 V - * ........ 1/4 TON R22 ......... HFB 1/4 H * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 21 F - * ........ 1/2 TON R12 ......... HFB 1/2 F * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 21 J - * ........ 1/2 TON R134 ....... HFB 1/2 M * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 21 R - * ........ 1/2 TON R502 ....... HFB 1/2 R * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 21 S - * ........ 1/2 TON R404 ....... HFB 1/2 S * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 21 V - * ........ 1/2 TON R22 ......... HFB 1/2 H * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPKITS ................ KE-10 ................ ENCLOSING TUBENONE ........................................... NONE ....................... FOR SPORLAN SOLENOIDSTXV ................. MC 22 F - * ........ 3/4 TON R12 ......... HFB 1/2 F * .................................... 1/2 TON R12 ............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 22 J - * ........ 1 TON R134 .......... HFB 1 M * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 22 R - * ........ 1 TON R502 .......... HFB 1 R * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 22 S - * ........ 1 TON R404 .......... HFB 1 S * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 22 V - * ........ 1 TON R22 ............ HFB 1 H * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 23 F - * ........ 1 TON R12 ............ HFB 1 F * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 23 J - * ........ 11/4 TON R134 ..... HFB 1 M * ..................................... 1 TON R134 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 23 R - * ........ 11/4 TON R502 ..... HFB 1 R * ...................................... 1 TON R502 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 23 S - * ........ 11/4 TON R404 ..... HFB 1 S * ...................................... 1 TON R404 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MC 23 V - * ........ 11/4 TON R22 ....... HFB 1 H * ...................................... 1 TON R22 ................ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 10 F - * ...... 3/16 TON R12 ....... HFE 1/4 F * .................................... 1/4 TON R12 ............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 10 J - * ...... 1/4 TON R134 ....... HFE 1/4 M * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 10 R - * ...... 1/4 TON R502 ....... HFE 1/4 R * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 10 S - * ...... 1/4 TON R404 ....... HFE 1/4 S * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 10 V - * ...... 1/4 TON R22 ......... HFE 1/4 H * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 11 F - * ...... 1/2 TON R12 ......... HFE 1/2 F * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 11 J - * ...... 1/2 TON R134 ....... HFE 1/2 M * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 11 R - * ...... 1/2 TON R502 ....... HFE 1/2 R * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 11 S - * ...... 1/2 TON R404 ....... HFE 1/2 S * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 11V - * ...... 1 TON R22 ............ HFE 1 H * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 12 F - * ...... 3/4 TON R12 ......... HFE 1 F * ....................................... 1 TON R12 ................ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 12 J - * ...... 1 TON R134 .......... HFE 1 M * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 12 R - * ...... 1 TON R502 .......... HFE 1 R * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 12 S - * ...... 1 TON R404 .......... HFE 1 S * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 12 V - * ...... 11/2 TON R22 ....... HFE 11/2 H * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP

Cross Reference - Upgrade to Alco

133RSP-PRC022-EN

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ................. MCE 13 F - * ...... 1 TON R12 ............ HFE 1 F * ....................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 13 J - * ...... 11/4 TON R134 ..... HFE 11/2 M * ................................ 11/2 TON R134 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 13 R - * ...... 11/4 TON R502 ..... HFE 11/4 R * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 13 S - * ...... 11/4 TON R404 ..... HFE 11/4 S * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 13 V - * ...... 13/4 TON R22 ....... HFE 2 H * ...................................... 2 TON R22 ................ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 20 F - * ...... 3/16 TON R12 ....... HFBE 1/4 F * ................................. 1/4 TON R12 ............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 20 J - * ...... 1/4 TON R134 ....... HFEB 1/4 M * ................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 20 R - * ...... 1/4 TON R502 ....... HFEB 1/4 R * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 20 S - * ...... 1/4 TON R404 ....... HFEB 1/4 S * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 20 V - * ...... 1/4 TON R22 ......... HFEB 1/4 H * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 21 F - * ...... 1/2 TON R12 ......... HFBE 1/2 F * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 21 J - * ...... 1/2 TON R134 ....... HFEB 1/2 M * ................................ SAME ....................... *REPLACE SPORLAN C, Z, ZPTXV ................. MCE 21 R - * ...... 1/2 TON R502 ....... HFEB 1/2 R * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 21 S - * ...... 1/2 TON R404 ....... HFEB 1/2 S * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 21 V - * ...... 1/2 TON R22 ......... HFEB 1/2 H * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 22 F - * ...... 3/4 TON R12 ......... HFBE 1/2 F * ................................. 1/2 TON R12 ............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 22 J - * ...... 1 TON R134 .......... HFEB 1 M * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 22 R - * ...... 1 TON R502 .......... HFEB 1 R * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 22 S - * ...... 1 TON R404 .......... HFEB 1 S * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 22 V - * ...... 1 TON R22 ............ HFEB 1 H * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 23 F - * ...... 1 TON R12 ............ HFBE 1 F * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 23 J - * ...... 11/4 TON R134 ..... HFEB 1 M * ................................... 1 TON R134 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 23 R - * ...... 11/4 TON R502 ..... HFEB 1 R * .................................... 1 TON R502 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 23 S - * ...... 11/4 TON R404 ..... HFEB 1 S * .................................... 1 TON R404 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MCE 23 V - * ...... 11/4 TON R22 ....... HFEB 1 H * .................................... 1 TON R22 ................ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPSOLENOID ...... ME14S250 ......... 5/8 ODF ................ 240RA 8T5M ................................. SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... ME19S250 ......... 5/8 ODF ................ 240RA 9T5M ................................. SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... ME25S270 ......... 7/8 ODF ................ 240RA 12T7M ............................... SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... ME25S290 ......... 11/8 ODF ............... 240RA 12T9M ............................... SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... ME34S2110 ....... 13/8 ODF ............... 905H - 14 ....................................... SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... ME34S290 ......... 11/8 ODF ............... 905H - 14 ....................................... SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... ME4232130 ....... 15/8 ODF ............... 905H - 15 ....................................... SAME ....................... REFRIGERANT SERVICE - VLCSOLENOID ...... ME42S2170 ....... 21/8 ODF ............... 905H - 15 ....................................... 15/8 ODF .................. REFRIGERANT SERVICE - VLCSOLENOID ...... ME6S130 ........... 3/8 ODF ................ 200RB3T3T ................................... SAME ....................... ADD MANUAL STEM KITSOLENOID ...... ME6S140 ........... 1/2 ODF ................ 200RB 3T4T .................................. SAME ....................... ADD MANUAL STEM KITSOLENOID ...... ME9S240 ........... 1/2 ODF ................ 200RB 5T4M ................................. SAME ....................... REFRIGERANT SERVICE - VLCTXV ................. MFE 15 - * ......... 15 TON R12 .......... TER 15 F * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPV ...................... MFE 20 - * ......... 20 TON R12 .......... TER 20 F * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MFE 25 - * ......... 25 TON R12 .......... TER 25 F * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MJE 13 - * ......... 13 TON R134 ........ TJRE 13 M * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MJE 15 - * ......... 15 TON R134 ........ TER 16 M * ................................... 16 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MJE 20 - * ......... 20 TON R134 ........ TER 19 M * ................................... 19 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MJE 25 - * ......... 25 TON R134 ........ TER 25 M * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPCOIL ................ MKC-1 ............... COIL ..................... AMG ............................................. SAME ....................... NOT INTERCHANGABLECOIL ................ MKC-2 ............... COIL ..................... AMG ............................................. SAME ....................... NOT INTERCHANGABLETXV ................. MRE 15 - * ......... 15 TON R502 ........ TER 16 R * .................................... 16 TON R502 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MRE 20 - * ......... 20 TON R502 ........ TER 21 R * .................................... 21 TON R502 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MRE 25 - * ......... 25 TON R502 ........ TER 27 R * .................................... 27 TON R502 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MSE 15 - * ......... 15 TON R404 ........ TER 16 S * .................................... 16 TON R404 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MSE 20 - * ......... 20 TON R404 ........ TER 21 S * .................................... 21 TON R404 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MSE 25 - * ......... 25 TON R404 ........ TER 27 S * .................................... 27 TON R404 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MVE 21 - * ......... 21 TON R22 .......... TER 22 H * .................................... 22 TON R22 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MVE 26 - * ......... 26 TON R22 .......... TER 26 H * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MVE 34 - * ......... 34 TON R22 .......... TER 35 H * .................................... 35 TON R22 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. MVE 42 - * ......... 42 TON R22 .......... TER 45 H * .................................... 45 TON R22 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIF 1 - * ............. 1 TON R12 ............ AFA 1 F * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIF 1/2 - * .......... 1/2 TON R12 ......... AFA 1/2 F * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIF 1/4 - * .......... 1/4 TON R12 ......... AFA 1/4 F * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIF 1/8 - * .......... 1/8 TON R12 ......... AFA 1/8 F * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIJ 1 - * ............. 1 TON R134 .......... AFA 1 M * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIJ 1/2 - * .......... 1/2 TON R134 ....... AFA 1/2 M * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIJ 1/4 - * .......... 1/4 TON R134 ....... AFA 1/4 M * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIJ 1/8 - * .......... 1/8 TON R134 ....... NONE ........................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIR 1 - * ............ 1 TON R502 .......... AFA 1 R * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIR 1/2 - * .......... 1/2 TON R502 ....... AFA 1/2 R * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIR 1/4 - * .......... 1/4 TON R502 ....... AFA 1/4 R * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIS 1 - * ............ 1 TON R404 .......... AFA 1 S * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIS 1/2 - * .......... 1/2 TON R404 ....... AFA 1/2 S * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIS 1/4 - * .......... 1/4 TON R404 ....... AFA 1/4 S * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................. NIS 1/8 - * .......... 1/8 TON R404 ....... HF 1/8 S * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOP

Cross Reference - Upgrade to Alco

RSP-PRC022-EN134

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ...................... NIV 1 - * ........ 1 TON R22 ............ AFA 1 H * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... NIV 1/2 - * ..... 1/2 TON R22 ......... AFA 1/2 H * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... NIV 1/4 - * ..... 1/4 TON R22 ......... AFA 1/4 H * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPSOLENOID ........... OB10F2 ......... 1/2 SAE ................. 500RB 6F4 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OB10S2 ........ 5/8 ODF ................ 500RB 6S5 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OB14P2 ........ 1/2 FPT ................. 500RB 7T4 .................................... 1/2 ODF .................... 2 WAY - NORMALLY OPENSOLENOID ........... OB14S2 ........ 5/8 ODF ................ 500RB 7S5 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OB19P2 ........ 3/4 FPT ................. 540RA 9T7 .................................... 7/8 ODF .................... 2 WAY - NORMALLY OPENSOLENOID ........... OB19S2 ........ 5/8 ODF ................ 540RA 9T5 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OB25P2 ........ 1 FPT .................... 540RA 12T9 .................................. 11/8 ODF .................. 2 WAY - NORMALLY OPENSOLENOID ........... OB25S2 ........ 11/8 ODF ............... 540RA 12T9 .................................. SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OB33S2 ........ 13/8 ODF ............... 540RA 16T11 ................................ SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OB9F2 .......... 3/8 SAE ................. 500RB 5F4 .................................... 1/4 SAE .................... 2 WAY - NORMALLY OPENSOLENOID ........... OB9P2 .......... 3/8 FPT ................. 500RB 5P3 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OB9S2 .......... 1/2 ODF ................ 500RB 5S4 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE10S240 ..... 1/2 ODF ................ 500RB 6T4 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE10S250 ..... 5/8 ODF ................ 500RB 6T5 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE14S250 ..... 5/8 ODF ................ 500RB 7T5 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE19S250 ..... 5/8 ODF ................ 540RA 9T5 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE19S270 ..... 7/8 ODF ................ 540RA 9T7 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE25S270 ..... 7/8 ODF ................ 540RA 12T7 .................................. SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE25S290 ..... 11/8 ODF ............... 540RA 12T9 .................................. SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE34S2110 ... 13/8 ODF ............... 540RA 16T11 ................................ SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE34S290 ..... 11/8 ODF ............... 540RA 16T9 .................................. SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE42S2130 ... 15/8 ODF ............... 540RA 20T13 ................................ SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE42S2170 ... 21/8 ODF ............... 540RA 20T17 ................................ SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE9S230 ....... 3/8 ODF ................ 500RB 5T3 .................................... SAME ....................... 2 WAY - NORMALLY OPENSOLENOID ........... OE9S240 ....... 1/2 ODF ................ 500RB 5T4 .................................... SAME ....................... 2 WAY - NORMALLY OPENTXV ...................... OFE 12 - * ..... 12 TON R12 .......... TER 13 F * ..................................... 13 TON R12 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OFE 16 - * ..... 16 TON R12 .......... TER 15 F * ..................................... 15 TON R12 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OFE 23 - * ..... 23 TON R12 .......... TER 25 F * ..................................... 25 TON R12 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OFE 32 - * ..... 32 TON R12 .......... TIR 35 F * ...................................... 35 TON R12 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OFE 40 - * ..... 40 TON R12 .......... THR 45 F * .................................... 45 TON R12 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OFE 9 - * ....... 9 TON R12 ............ HFES 9 F * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPOIL RESERVOIRS . OR- 1 1/2 ....... 1/2 GALLON ......... AOR-2 ........................................... 2 GALLON ................ 2 SIGHT GLASSESTXV ...................... OJE 16 - * ..... 16 TON R134 ........ TER 16 M * ................................... 16 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OJE 23 - * ..... 23 TON R134 ........ TER 25 M * ................................... 25 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OJE 32 - * ..... 32 TON R134 ........ TER 31 M * ................................... 31 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OJE 40 - * ..... 40 TON R134 ........ TIR 45 M * .................................... 45 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OJE 9 - * ....... 9 TON R134 ......... TJRE 11 M * ................................. 11 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... ORE 12 - * ..... 12 TON R502 ........ TRAE+ 12 R * ................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... ORE 21 - * ..... 21 TON R502 ........ TRAE+ 20 R * ................................ 20 TON R502 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... ORE 30 - * ..... 30 TON R502 ........ TER 27 R * .................................... 27 TON R502 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... ORE 35 - * ..... 35 TON R502 ........ TIR 37 R * ..................................... 37 TON R502 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... ORE 45 - * ..... 45 TON R502 ........ THR 48 R * .................................... 48 TON R502 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... ORE 9 - * ....... 9 TON R502 .......... TRAE+ 8 R * .................................. 8 TON R502 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPREGULATORS ...... ORI-10 .......... EVAPORATOR ...... IPR-10 ........................................... SAME ....................... SELECT PRES. AND CONN.REGULATORS ...... ORI-6 ............ EVAPORATOR ...... IPR-6 ............................................. SAME ....................... SELECT PRES. AND CONN.REGULATORS ...... ORIT-10 ......... EVAPORATOR ...... IPR-10 ........................................... SAME ....................... W/ ACCESS VALVEREGULATORS ...... ORIT-12 ......... EVAPORATOR ...... EPRB-12 ........................................ SAME ....................... BRASS BODYREGULATORS ...... ORIT-20 ......... EVAPORATOR ...... EPRB-20 ........................................ SAME ....................... BRASS BODYREGULATORS ...... ORIT-6 ........... EVAPORATOR ...... IPR-6 ............................................. SAME ....................... W/ ACCESS VALVEREGULATORS ...... OROA5 ......... HEAD PRES. ......... HP8 ............................................... SAME ....................... SELECT PRES. AND CONN.TXV ...................... OSE 12 - * ..... 12 TON R404 ........ TRAE+ 12 S * ................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OSE 21 - * ..... 21 TON R404 ........ TRAE+ 20 S * ................................ 20 TON R404 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OSE 30 - * ..... 30 TON R404 ........ TER 27 S * .................................... 27 TON R404 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OSE 35 - * ..... 35 TON R404 ........ TIR 37 S * ..................................... 37 TON R404 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OSE 45 - * ..... 45 TON R404 ........ THR 48 S * .................................... 48 TON R404 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OSE 9 - * ....... 9 TON R404 .......... TRAE+ 8 S * ................................. 8 TON R404 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OVE 15 - * ..... 15 TON R22 .......... TRAE+ 15 * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OVE 20 - * ..... 20 TON R22 .......... TRAE+ 20 * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OVE 30 - * ..... 30 TON R22 .......... TRAE+ 30 * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OVE 40 - * ..... 40 TON R22 .......... TRAE+ 40 * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OVE 55 - * ..... 55 TON R22 .......... TIR 55 H * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OVE 70 - * ..... 70 TON R22 .......... THR 75 H * .................................... 75 TON R22 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... PFE 12 - * ...... 12 TON R12 .......... TER 13 F * ..................................... 13 TON R12 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... PFE 8 - * ........ 8 TON R12 ............ TJRE 8 F * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... PJE 12 - * ...... 12 TON R134 ........ TJRE 11 M * ................................. 11 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... PJE 8 - * ........ 8 TON R134 .......... TJLE 9 M * .................................... 9 TON R134 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... PRE 12 - * ..... 12 TON R502 ........ HFES 13 R * .................................. 13 TON R502 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... PRE 9 - * ....... 9 TON R502 .......... HFES 10 R * .................................. 10 TON R502 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... PSE 12 - * ..... 12 TON R404 ........ HFES 13 S * .................................. 13 TON R404 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOP

Cross Reference - Upgrade to Alco

135RSP-PRC022-EN

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ...................... PSE 9 - * ....... 9 TON R404 .......... HFES 10 S * .................................. 10 TON R404 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... PVE 10 - * ..... 10 TON R22 .......... HFES 10 H * .................................. 10 TON R22 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... PVE 11 - * ..... 11 TON R22 .......... HFES 10 H * .................................. 10TON R22 ............... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OJE 12 - * ..... 12 TON R134 ........ TJRE 13 M * ................................. 13 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OJE 12 - * ..... 12 TON R134 ........ TJRE 13 M * ................................. 13 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... OJE 12 - * ..... 12 TON R134 ........ TJRE 13 M * ................................. 13 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... PVE 16 - * ..... 16 TON R22 .......... HFES 15 H * .................................. 15 TON R22 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... PVE 20 - * ..... 20 TON R22 .......... HFES 20 H * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... Q-0-JC .......... 1/4 TON R134 ....... HF 1/4 MC ..................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-0-RC .......... 1/5 TON R502 ....... HF 1/4 RC ...................................... 1/4 TON R502 ........... HF IS BALANCED PORTTXV ...................... Q-0-VC .......... 1/4 TON R22 ......... HF 1/4 HC ...................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-1-FC .......... 1/2 TON R12 ......... HF 1/2 FC ...................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-1-JC .......... 1/2 TON R134 ....... HF 1/2 MC ..................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-1-RC .......... 1/2 TON R502 ....... HF 1/2 RC ...................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-1-VC .......... 3/4 TON R22 ......... HF 1 HC ........................................ 1 TON R22 ................ HF IS BALANCED PORTTXV ...................... Q-2-FC .......... 5/8 TON R12 ......... HF 1/2 FC ...................................... 1/2 TON R12 ............. HF IS BALANCED PORTTXV ...................... Q-2-JC .......... 3/4 TON R134 ....... HF 3/4 MC ..................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-2-RC .......... 5/8 TON R502 ....... HF 1/2 RC ...................................... 1/2 TON R502 ........... HF IS BALANCED PORTTXV ...................... Q-2-VC .......... 1 TON R22 ............ HF 1 HC ........................................ SAME ....................... HF IS BALANCED PORTTXV ...................... Q-3-FC .......... 1 TON R12 ............ HF 1 FC ......................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-3-JC .......... 11/4 TON R134 ..... HF 11/2 MC ................................... 11/2 TON R134 ......... HF IS BALANCED PORTTXV ...................... Q-3-RC .......... 1 TON R502 .......... HF 1 RC ......................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-3-VC .......... 11/2 TON R22 ....... HF 11/2 HC .................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-4-FC .......... 11/2 TON R12 ....... HF 11/2 FC .................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-4-JC .......... 11/2 TON R134 ..... HF 11/2 MC ................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-4-RC .......... 11/2 TON R502 ..... HF 11/2 RC .................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-4-VC .......... 21/2 TON R22 ....... HF 21/2 HC .................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-5-FC .......... 2 TON R12 ............ HF 2 FC ......................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-5-JC .......... 21/2 TON R134 ..... HF 21/2 MC ................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-5-RC .......... 2 TON R502 .......... HF 2 RC ......................................... SAME ....................... HF IS BALANCED PORTTXV ...................... Q-5-VC .......... 31/2 TON R22 ....... HF 3 HC ........................................ 3 TON R22 ................ HF IS BALANCED PORTTXV ...................... Q-6-RC .......... 3 TON R502 .......... HF 31/2 RC .................................... 31/2 TON R502 ......... HF IS BALANCED PORTTXV ...................... Q-6-VC .......... 5 TON R22 ............ HF 51/2 HC .................................... 51/2 TON R22 ........... HF IS BALANCED PORTTXV ...................... QE-0-FC ........ 1/5 TON R12 ......... HFE 1/8 FC .................................... 1/8 TON R12 ............. HF IS BALANCED PORTTXV ...................... QE-0-JC ........ 1/4 TON R134 ....... HFE 1/4 MC ................................... SAME ....................... HF IS BALANCED PORTTXV ...................... QE-0-RC ........ 1/5 TON R502 ....... HFE 1/4 RC .................................... 1/4 TON R502 ........... HF IS BALANCED PORTTXV ...................... QE-0-VC ........ 1/4 TON R22 ......... HFE 1/4 HC .................................... SAME ....................... HF IS BALANCED PORTTXV ...................... QE-1-FC ........ 1/2 TON R12 ......... HFE 1/2 FC .................................... SAME ....................... HF IS BALANCED PORTTXV ...................... QE-1-JC ........ 1/2 TON R134 ....... HFE 1/2 MC ................................... SAME ....................... HF IS BALANCED PORTTXV ...................... QE-1-RC ........ 1/2 TON R502 ....... HFE 1/2 RC .................................... SAME ....................... HF IS BALANCED PORTTXV ...................... QE-1-VC ........ 3/4 TON R22 ......... HFE 1 HC ...................................... 1 TON R22 ................ HF IS BALANCED PORTTXV ...................... QE-2-FC ........ 5/8 TON R12 ......... HFE 1/2 FC .................................... 1/2 TON R12 ............. HF IS BALANCED PORTTXV ...................... QE-2-JC ........ 3/4 TON R134 ....... HFE 3/4 MC ................................... SAME ....................... HF IS BALANCED PORTTXV ...................... QE-2-RC ........ 5/8 TON R502 ....... HFE 1/2 RC .................................... 1/2 TON R502 ........... HF IS BALANCED PORTTXV ...................... QE-2-VC ........ 1 TON R22 ............ HFE 1 HC ...................................... 2 TON R22 ................ HF IS BALANCED PORTTXV ...................... QE-3-FC ........ 1 TON R12 ............ HFE 1 FC ....................................... SAME ....................... HF IS BALANCED PORTTXV ...................... QE-3-JC ........ 11/4 TON R134 ..... HFE 11/2 MC ................................. 11/2 TON R134 ......... HF IS BALANCED PORTTXV ...................... QE-3-RC ........ 1 TON R502 .......... HFE 1 RC ....................................... SAME ....................... HF IS BALANCED PORTTXV ...................... QE-3-VC ........ 11/2 TON R22 ....... HFE 11/2 HC .................................. SAME ....................... HF IS BALANCED PORTTXV ...................... QE-4-FC ........ 11/2 TON R12 ....... HFE 11/2 FC .................................. SAME ....................... HF IS BALANCED PORTTXV ...................... QE-4-JC ........ 11/2 TON R134 ..... HFE 11/2 MC ................................. SAME ....................... HF IS BALANCED PORTTXV ...................... QE-4-RC ........ 11/2 TON R502 ..... HFE 11/2 RC .................................. SAME ....................... HF IS BALANCED PORTTXV ...................... QE-4-VC ........ 21/2 TON T22 ....... HFE 21/2 HC .................................. SAME ....................... HF IS BALANCED PORTTXV ...................... QE-5-FC ........ 2 TON R12 ............ HFE 2 FC ....................................... SAME ....................... HF IS BALANCED PORTTXV ...................... QE-5-JC ........ 21/2 TON R134 ..... HFE 21/2 MC ................................. SAME ....................... HF IS BALANCED PORTTXV ...................... QE-5-RC ........ 2 TON R502 .......... HFE 2 RC ....................................... SAME ....................... HF IS BALANCED PORTTXV ...................... QE-5-VC ........ 31/2 TON R22 ....... HFE 3 HC ...................................... 3 TON R22 ................ HF IS BALANCED PORTTXV ...................... QE-6-RC ........ 3 TON R502 .......... HFE 31/2 RC .................................. 31/2 TON R502 ......... HF IS BALANCED PORTTXV ...................... QE-6-VC ........ 5 TON R22 ............ HFE 51/2 HC .................................. 51/2 TON R22 ........... HF IS BALANCED PORTTXV ...................... Q-O-FC ......... 1/5 TON R12 ......... HF 1/8 FC ...................................... 1/8 TON R12 ............. HF IS BALANCED PORTSOLENOID ........... R183P1 ......... 3/8 ODF ................ 231SB 08P04 ................................. 1/2 FPT ..................... STEAM SERVICESOLENOID ........... R184P1 ......... 1/2 FPT ................. 231SB 08P04 ................................. SAME ....................... STEAM SERVICESOLENOID ........... R246P1 ......... 3/4 FPT ................. 231SB 12P06 ................................. SAME ....................... STEAM SERVICEKITS ..................... R-3H- ............ DOME ................... NONE ........................................... NONE ....................... FOR SPORLAN BYPASS VALVEKITS ..................... R-3L- ............. DOME ................... NONE ........................................... NONE ....................... FOR SPORLAN BYPASS VALVEKITS ..................... R-3P- ............. DOME ................... NONE ........................................... NONE ....................... FOR SPORLAN BYPASS VALVEKITS ..................... R-8- ............... DOME ................... NONE ........................................... NONE ....................... FOR SPORLAN BYPASS VALVEDRIER ................... RC-10098 ...... 100 CU. IN. ........... H100 ............................................. SAME ....................... DRIER BLOCKDRIER ................... RC-10098-HH 100 CU. IN. ........... W100 ............................................ SAME ....................... DRIER BLOCKDRIER ................... RC-4267 ........ 42 CU. IN. ............. D42 ............................................... SAME ....................... DRIER BLOCKDRIER ................... RC-4864 ........ 48 CU. IN. ............. D48 ............................................... SAME ....................... DRIER BLOCKDRIER ................... RC-4864-HH .. 48 CU. IN. ............. W48 .............................................. SAME ....................... DRIER BLOCK

Cross Reference - Upgrade to Alco

RSP-PRC022-EN136

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ...................... RCVE 2 GA ... 2 TON R22 ............ HFES 2 HCA .................................. SAME ....................... ODF CONNECTIONSTXV ...................... RCVE 3 GA ... 3 TON R22 ............ HFES 3 HCA .................................. SAME ....................... ODF CONNECTIONSTXV ...................... RCVE 4 GA ... 4 TON R22 ............ TCLE 3 HCA .................................. 3 TON R22 ................ ODF CONNECTIONSTXV ...................... RCVE 5 GA ... 5 TON R22 ............ HFES 51/2 HCA ............................. 51/2 TON R22 ........... ODF CONNECTIONSDRIER ................... RCW-100 ...... 100 CU. IN. ........... W100 ............................................ SAME ....................... DRIER BLOCKDRIER ................... RCW-42 ........ 42 CU. IN. ............. D42 ............................................... STD .......................... DRIER BLOCKDRIER ................... RCW-48 ........ 48 CU. IN. ............. H48 ............................................... SAME ....................... DRIER BLOCKTXV ...................... RIVE 2 ........... 2 TON R22 ............ AAE 2 HCA ................................... SAME ....................... ODF CONNECTIONSTXV ...................... RIVE 3 ........... 31/2 TON R22 ....... AAE 3 HCA ................................... 31/2 TON R22 ........... ODF CONNECTIONSTXV ...................... RIVE 4 ........... 4 TON R22 ............ AAE 4 HCA ................................... SAME ....................... ODF CONNECTIONSTXV ...................... RIVE 5 ........... 41/2 TON R22 ....... AAE 4 HCA ................................... 4 TON R22 ................ ODF CONNECTIONSDRIER ................... RPE-100 ........ 100 CU. IN. ........... F100 .............................................. SAME ....................... FILTER ELEMENTDRIER ................... RPE-48-BD .... 48 CU. IN. ............. F48R ............................................. SAME ....................... FILTER ELEMENTDRIER ................... RSF-4811-T ... 13/8 ODF ............... STAS 4811SV ............................... SAME ....................... TAKE APART SHELL - SUCTIONDRIER ................... RSF-4813-T ... 15/8 ODF ............... STAS 4813SV ............................... SAME ....................... TAKE APART SHELL - SUCTIONDRIER ................... RSF-4817-T ... 21/8 ODF ............... STAS 4817SV ............................... SAME ....................... TAKE APART SHELL - SUCTIONDRIER ................... RSF-4821-T ... 25/8 ODF ............... STAS 4821SV ............................... SAME ....................... TAKE APART SHELL - SUCTIONDRIER ................... RSF-487-T ..... 7/8 ODF ................ STAS 487SV ................................. SAME ....................... TAKE APART SHELL - SUCTIONDRIER ................... RSF-489-T ..... 11/8 ODF ............... STAS 489SV ................................. SAME ....................... TAKE APART SHELL - SUCTIONDRIER ................... RSF-9617-T ... 21/8 ODF ............... STAS 9617SV ............................... SAME ....................... TAKE APART SHELL - SUCTIONDRIER ................... RSF-9621-T ... 25/8 ODF ............... STAS 9621SV ............................... SAME ....................... TAKE APART SHELL - SUCTIONDRIER ................... RSF-9625-T ... 31/8 ODF ............... ATD 9625SV ................................ SAME ....................... TAKE APART SHELL - SUCTIONOIL CONTROL ...... S1A1 ............. OIL LEVEL ............ OMA-JB1 ...................................... SAME ....................... TRAX OIL - STANDARDOIL CONTROL ...... S1AU-1 ......... OIL LEVEL ............ OMA-MO1 .................................... SAME ....................... TRAX OIL - HUSSMANNSIGHT GLASS ...... SA-12 ........... 1/4 SAE ................. AMI-1MM2 ................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-12FM ...... 1/4 M X F SAE ...... AMI-1FM2 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-12S ......... 1/4 ODF ................ ALM-1TT2 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-13 ........... 3/8 SAE ................. AMI-1MM3 ................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-13FM ...... 3/8 M X F SAE ...... AMI-1FM3 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-13FU ....... 3/8 F SAE X SWIV . AMI-1FU3 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-13S ......... 3/8 ODF ................ ALM-1TT3 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-13SU ....... 3/8 ODF X SWIV ... AMI-1SU3 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-13U ......... 3/8 M SAE X SWIV AMI-1MU3 .................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-13UU ...... 3/8 SWIV X SWIV . AMI-1UU3 .................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-14 ........... 1/2 SAE ................. AMI-1MM4 ................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-14FM ...... 1/2 M X F SAE ..... AMI-1FM4 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-14FU ....... 1/2 F SAE X SWIV . AMI-1FU4 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-14S ......... 1/2 ODF ................ ALM-1TT4 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-14SU ....... 1/2 ODF X SWIV ... AMI-1SU4 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-14U ......... 1/2 M SAE X SWIV AMI-1MU4 .................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-14UU ...... 1/2 SWIV X SWIV . AMI-1UU4 .................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-15 ........... 5/8 SAE ................. AMI-1MM5 ................................... SAME ....................... MOISTURE INDICATURETXV ...................... OJE 16 - * ..... 16 TON R134 ........ TER 16 M * ................................... 16 TON R134 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPSIGHT GLASS ...... SA-15S ......... 5/8 ODF ................ ALM-1TT5 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-15SU ....... 5/8 ODF X SWIV ... AMI-1SU5 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-15U ......... 5/8 M SAE X SWIV AMI-1MU5 .................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-15UU ...... 5/8 SWIV X SWIV . AMI-1UU5 .................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-17S ......... 7/8 ODF ................ ALM-1TT7 ..................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-19S ......... 11/8 ODF ............... AMI-1TT9 ...................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-211 .......... 13/8 ODF ............... AMI-2S11 ...................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-213 .......... 15/8 ODF ............... AMI-2S13 ...................................... SAME ....................... MOISTURE INDICATURESIGHT GLASS ...... SA-217 .......... 21/8 ODF ............... AMI-2S17 ...................................... SAME ....................... MOISTURE INDICATURETXV ...................... SBFF-A - * ..... 1 TON R12 ............ HFSC 1 F * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFF-AA - * .. 1/2 TON R12 ......... HFSC 1/2 F * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFF-AAA - * 1/4 TON R12 ......... HFSC 1/4 F * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFF-B - * ..... 13/4 TON R12 ....... HFSC 11/2 F * ............................... 11/2 TON R12 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFF-C - * ..... 3 TON R12 ............ HFSC 31/2 F * ............................... 3 TON R12 ................ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFFE-A - * .. 1 TON R12 ............ HFESC 1 F * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFFE-AA - * 1/2 TON R12 ......... HFESC 1/2 F * ............................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFFE-AAA -*1/4 TON R12 ......... HFESC 1/4 F* ................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFFE-B - * ... 13/4 TON R12 ....... HFESC 11/2 F * ............................. 11/2 TON R12 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFFE-C - * ... 3 TON R12 ............ HFESC 31/2 F * ............................. 31/2 TON R12 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFJ-A - * ..... 11/4 TON R134 ..... HFSC 1 M * ................................... 1 TON R134 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFJ-AA - * .. 1/2 TON R134 ....... HFSC 1/2 M * ................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFJ-AAA - * 1/4 TON R134 ....... HFSC 1/4 M * ................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFJ-B - * ..... 2 TON R134 .......... HFSC 13/4 M * .............................. 13/4 TON R134 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFJ-C - * ..... 31/2 TON R134 ..... HFSC 4 M * ................................... 4 TON R134 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFJE-A - * .. 11/4 TON R134 ..... HFESC 1 M * ................................. 1 TON R134 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFJE-AA - * 1/2 TON R134 ....... HFESC 1/2 M * .............................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFJE-AAA -*1/4 TON R134 ....... HFESC 1/4 M* ............................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFJE-B - * ... 2 TON R134 .......... HFESC 13/4 M * ............................ 13/4 TON R134 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ...................... SBFJE-C - * ... 31/2 TON R134 ..... HFESC 4 M * ................................. 4 TON R134 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOP

Cross Reference - Upgrade to Alco

137RSP-PRC022-EN

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ................ SBFR-A - * .......... 1 TON R502 .......... HFSC 1 R * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFR-AA - * ........ 1/2 TON R502 ....... HFSC 1/2 R * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFR-AAA - * ..... 1/4 TON R502 ....... HFSC 1/4 R * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFR-B - * .......... 2 TON R502 .......... HFSC 2 R * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFR-C - * .......... 3 TON R502 .......... HFSC 31/2 R * ............................... 31/2 TON R502 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFRE-A - * ........ 1 TON R502 .......... HFESC 1 R * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFRE-AA - * ...... 1/2 TON R502 ....... HFESC 1/2 R * ............................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFRE-AAA - * ... 1/4 TON R502 ....... HFESC 1/4 R * ............................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFRE-B - * ........ 2 TON R502 .......... HFESC 2 R * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFRE-C - * ........ 3 TON R502 .......... HFESC 31/2 R * ............................. 31/2 TON R502 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFS-A - * .......... 1 TON R404 .......... HFSC 1 S * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFS-AA - * ........ 1/2 TON R404 ....... HFSC 1/2 S * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFS-AAA - * ..... 1/4 TON R404 ....... HFSC 1/4 S * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFS-B - * .......... 2 TON R404 .......... HFSC 2 S * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFS-C - * .......... 3 TON R404 .......... HFSC 31/2 S * ............................... 31/2 TON R404 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFSE-A - * ........ 1 TON R404 .......... HFESC 1 S * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFSE-AA - * ...... 1/2 TON R404 ....... HFESC 1/2 S * ............................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFSE-AAA - * ... 1/4 TON R404 ....... HFESC 1/4 S * ............................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFSE-B - * ........ 2 TON R404 .......... HFESC 2 S * .................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFSE-C - * ........ 3 TON R404 .......... HFESC 31/2 S * ............................. 31/2 TON R404 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFV-A - * .......... 11/2 TON R22 ....... HFSC 11/2 H * ............................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFV-AA - * ........ 3/4 TON R22 ......... HFSC 1 H * ................................... 1 TON R22 ................ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFV-AAA - * ...... 1/2 TON R22 ......... HFSC 1/2 H * ................................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFV-B - * ........... 23/4 TON R22 ....... HFSC 21/2 H * ............................... 21/2 TON R22 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFV-C - * ........... 51/4 TON R22 ....... HFSC 51/2 H * ............................... 51/2 TON R22 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFVE-A - * ........ 11/2 TON R22 ....... HFESC 11/2 H * ............................. SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFVE-AA - * ...... 3/4 TON R22 ......... HFESC 1 H * ................................. 1 TON R22 ................ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFVE-AAA - * ... 1/2 TON R22 ......... HFESC 1/2 H * ............................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFVE-B - * ........ 23/4 TON R22 ....... HFESC 21/2 H * ............................. 21/2 TON R22 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SBFVE-C - * ........ 51/4 TON R22 ....... HFESC 51/2 H * ............................. 51/2 TON R22 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPKITS ............... S-CB9 ................. STEM + PLUNGER NONE ........................................... NONE ....................... FOR SPORLAN SOLENOIDSTXV ................ SF 2 - * ................ 2 TON R12 ............ HF 2 F * ......................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SF 3 - * ................ 3 TON R12 ............ HF 31/2 F * .................................... 31/2 TON R12 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPDRIER ............. SF-114 ................ 1/2 ODF ................ ASF 28S4-VV ................................ SAME ....................... SUCTION FILTERDRIER ............. SF-114F .............. 1/2 SAE ................. ASF 28S4-VV ................................ 1/2 ODF .................... SUCTION FILTERDRIER ............. SF-115 ................ 5/8 ODF ................ ASF 35S5-VV ................................ SAME ....................... SUCTION FILTERDRIER ............. SF-115F .............. 5/8 SAE ................. ASF 35F5-VV ................................. SAME ....................... SUCTION FILTERDRIER ............. SF-283F .............. 3/8 SAE ................. ASF 35F3-VV ................................. SAME ....................... SUCTION FILTERDRIER ............. SF285F-T ............ 5/8 SAE ................. ASF 35F5-VV ................................. SAME ....................... SUCTION FILTERDRIER ............. SF-285-T ............. 5/8 ODF ................ ASF 35S5-VV ................................ SAME ....................... SUCTION FILTERDRIER ............. SF-286-T ............. 3/4 ODF ................ ASF 45S6-VV ................................ SAME ....................... SUCTION FILTERDRIER ............. SF-287-T ............. 7/8 ODF ................ ASF 45S7-VV ................................ SAME ....................... SUCTION FILTERDRIER ............. SF-289-T ............. 11/8 ODF ............... ASF 50S9-VV ................................ SAME ....................... SUCTION FILTERDRIER ............. SF-4811-T ........... 13/8 ODF ............... ASF 75S11-VV .............................. SAME ....................... SUCTION FILTERDRIER ............. SF-4813-T ........... 15/8 ODF ............... ASF 75S13-VV .............................. SAME ....................... SUCTION FILTERDRIER ............. SF-489-T ............. 11/8 ODF ............... ASF 50S9-VV ................................ SAME ....................... SUCTION FILTERTXV ................ SFE 2 - * .............. 2 TON R12 ............ HFE 2 F * ....................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SFE 3 - * .............. 3 TON R12 ............ HFE 31/2 F * .................................. 31/2 TON R12 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SFE 5 - * .............. 5 TON R12 ............ HFE 5 F * ....................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SFE 6 - * .............. 6 TON R12 ............ HFE 6 F * ....................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPREGULATORS SHGBE-15 ........... HOT GAS ............. FA8-16H ........................................ SAME ....................... MODULATING VALVETXV ................ SJ 2 - * ................ 2 TON R134 .......... HF 21/2 M * ................................... 21/2 TON R134 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SJ 21/2 - * ........... 21/2 TON R134 ..... HF 21/2 M * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SJE 2 - * .............. 2 TON R134 .......... HFE 21/2 M * ................................ 21/2 TON R134 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SJE 6 - * .............. 6 TON R134 .......... HFE 6 M * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPREGULATORS SORIT ................. EVAPORATOR ...... EPRBS .......................................... SAME ....................... SELECT CAPACITYTXV ................ SQ-0-FC .............. 1/5 TON R12 ......... HFSC 1/8 FC .................................. 1/8 TON R12 ............. HF IS BALANCED PORTTXV ................ SQ-0-JC .............. 1/4 TON R134 ....... HFSC 1/4 MC ................................ SAME ....................... HF IS BALANCED PORTTXV ................ SQ-0-RC .............. 1/5 TON R502 ....... HFSC 1/4 RC ................................. 1/4 TON R502 ........... HF IS BALANCED PORTTXV ................ SQ-0-VC .............. 1/4 TON R22 ......... HFSC 1/4 HC ................................. SAME ....................... HF IS BALANCED PORTTXV ................ SQ-1-FC .............. 1/2 TON R12 ......... HFSC 1/2 FC .................................. SAME ....................... HF IS BALANCED PORTTXV ................ SQ-1-JC .............. 1/2 TON R134 ....... HFSC 1/2 MC ................................ SAME ....................... HF IS BALANCED PORTTXV ................ SQ-1-RC .............. 1/2 TON R502 ....... HFSC 1/2 RC ................................. SAME ....................... HF IS BALANCED PORTTXV ................ SQ-1-VC .............. 3/4 TON R22 ......... HFSC 1 HC .................................... 1 TON R22 ................ HF IS BALANCED PORTTXV ................ SQ-2-FC .............. 5/8 TON R12 ......... HFSC 1/2 FC .................................. 1/2 TON R12 ............. HF IS BALANCED PORTTXV ................ SQ-2-JC .............. 3/4 TON R134 ....... HFSC 3/4 MC ................................ SAME ....................... HF IS BALANCED PORTTXV ................ SQ-2-RC .............. 5/8 TON R502 ....... HFSC 1/2 RC ................................. 1/2 TON R502 ........... HF IS BALANCED PORTTXV ................ SQ-2-VC .............. 1 TON R22 ............ HFSC 1 HC .................................... SAME ....................... HF IS BALANCED PORTTXV ................ SQ-3-FC .............. 1 TON R12 ............ HFSC 1 FC .................................... SAME ....................... HF IS BALANCED PORTTXV ................ SQ-3-JC .............. 11/4 TON R134 ..... HFSC 11/2 MC .............................. 11/2 TON R134 ......... HF IS BALANCED PORTTXV ................ SQ-3-RC .............. 1 TON R502 .......... HFSC 1 RC .................................... SAME ....................... HF IS BALANCED PORTTXV ................ SQ-3-VC .............. 11/2 TON R22 ....... HFSC 11/2 HC ............................... SAME ....................... HF IS BALANCED PORTTXV ................ SQ-4-FC .............. 11/2 TON R12 ....... HFSC 11/2 FC ................................ SAME ....................... HF IS BALANCED PORT

Cross Reference - Upgrade to Alco

RSP-PRC022-EN138

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ................ SQ-4-JC .............. 11/2 TON R134 ..... HFSC 11/2 MC .............................. SAME ....................... HF IS BALANCED PORTTXV ................ SQ-4-RC .............. 11/2 TON R502 ..... HFSC 11/2 RC ............................... SAME ....................... HF IS BALANCED PORTTXV ................ SQ-4-VC .............. 21/2 TON R22 ....... HFSC 21/2 HC ............................... SAME ....................... HF IS BALANCED PORTTXV ................ SQ-5-FC .............. 2 TON R12 ............ HFSC 2 FC .................................... SAME ....................... HF IS BALANCED PORTTXV ................ SQ-5-JC .............. 21/2 TON R134 ..... HFSC 21/2 MC .............................. SAME ....................... HF IS BALANCED PORTTXV ................ SQ-5-RC .............. 2 TON R502 .......... HFSC 2 RC .................................... SAME ....................... HF IS BALANCED PORTTXV ................ SQ-5-VC .............. 31/2 TON R22 ....... HFSC 3 HC .................................... 3 TON R22 ................ HF IS BALANCED PORTTXV ................ SQ-6-RC .............. 3 TON R502 .......... HFSC 3 RC .................................... SAME ....................... HF IS BALANCED PORTTXV ................ SQ-6-VC .............. 5 TON R22 ............ HFSC 51/2 HC ............................... 51/2 TON R22 ........... HF IS BALANCED PORTTXV ................ SQE-0-FC ............ 1/5 TON R12 ......... HFESC 1/8 FC ................................ 1/8 TON R12 ............. HF IS BALANCED PORTTXV ................ SQE-0-JC ............ 1/4 TON R134 ....... HFESC 1/4 MC .............................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-0-RC ............ 1/5 TON R502 ....... HFESC 1/4 RC ............................... 1/4 TON R502 ........... HF IS BALANCED PORTTXV ................ SQE-0-VC ............ 1/4 TON R22 ......... HFESC 1/4 HC ............................... SAME ....................... HF IS BALANCED PORTTXV ................ SQE-1-FC ............ 1/2 TON R12 ......... HFESC 1/2 FC ................................ SAME ....................... HF IS BALANCED PORTTXV ................ SQE-1-JC ............ 1/2 TON R134 ....... HFESC 1/2 MC .............................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-1-RC ............ 1/2 TON R502 ....... HFESC 1/2 RC ............................... SAME ....................... HF IS BALANCED PORTTXV ................ SQE-1-VC ............ 3/4 TON R22 ......... HFESC 1 HC .................................. 1 TON R22 ................ HF IS BALANCED PORTTXV ................ SQE-2-FC ............ 5/8 TON R12 ......... HFESC 1/2 FC ................................ 1/2 TON R12 ............. HF IS BALANCED PORTTXV ................ SQE-2-JC ............ 3/4 TON R134 ....... HFESC 3/4 MC .............................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-2-RC ............ 5/8 TON R502 ....... HFESC 1/2 RC ............................... 1/2 TON R502 ........... HF IS BALANCED PORTTXV ................ SQE-2-VC ............ 1 TON R22 ............ HFESC 1 HC .................................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-3-FC ............ 1 TON R12 ............ HFESC 1 FC .................................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-3-JC ............ 11/4 TON R134 ..... HFESC 11/2 MC ............................ 11/2 TON R134 ......... HF IS BALANCED PORTTXV ................ SQE-3-RC ............ 1 TON R502 .......... HFESC 1 RC .................................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-3-VC ............ 11/2 TON R22 ....... HFESC 11/2 HC ............................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-4-FC ............ 11/2 TON R12 ....... HFESC 11/2 FC .............................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-4-JC ............ 11/2 TON R134 ..... HFESC 11/2 MC ............................ SAME ....................... HF IS BALANCED PORTTXV ................ SQE-4-RC ............ 11/2 TON R502 ..... HFESC 11/2 RC ............................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-4-VC ............ 21/2 TON R22 ....... HFESC 21/2 HC ............................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-5-FC ............ 2 TON R12 ............ HFESC 2 FC .................................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-5-JC ............ 21/2 TON R134 ..... HFESC 21/2 MC ............................ SAME ....................... HF IS BALANCED PORTTXV ................ SQE-5-RC ............ 2 TON R502 .......... HFESC 2 RC .................................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-5-VC ............ 31/2 TON R22 ....... HFESC 3 HC .................................. 3 TON R22 ................ HF IS BALANCED PORTTXV ................ SQE-6-RC ............ 3 TON R502 .......... HFESC 3 RC .................................. SAME ....................... HF IS BALANCED PORTTXV ................ SQE-6-VC ............ 5 TON R22 ............ HFESC 51/2 HC ............................. 51/2 TON R22 ........... HF IS BALANCED PORTTXV ................ SR 2 - * ............... 2 TON R502 .......... HF 2 R * ........................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SR 3 - * ............... 3 TON R502 .......... HF 31/2 R * .................................... 31/2 TON R502 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SRE 2 - * ............. 2 TON R502 .......... HFE 2 R * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SRE 3 - * ............. 3TON R502 ........... HFE 31/2 R * ................................. 31/2 TON R502 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SRE 7 - * ............. 7 TON R502 .......... HFE 7 R * ...................................... 7 TON R502 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SS 2 - * ............... 2 TON R404 .......... HF 2 S * ........................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SS 3 - * ............... 3 TON R404 .......... HF 31/2 S * .................................... 31/2 TON R404 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SSE 2 - * ............. 2 TON R404 .......... HFE 2 S * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SSE 3 - * ............. 3 TON R404 .......... HFE 31/2 S * ................................. 31/2 TON R404 ......... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SSE 7 - * ............. 7 TON R404 .......... HFE 7 S * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SV 2 - * ............... 2 TON R22 ............ HF 2 H * ........................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SV 3 - * ............... 3 TON R22 ............ HF 3 H * ........................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SV 5 - * ............... 5 TON R22 ............ HF 51/2 H * ................................... 51/2 TON R22 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SVE 10 - * ........... 10 TON R22 .......... HFE 10 H * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SVE 2 - * ............. 2 TON R22 ............ HFE 2 H * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SVE 3 - * ............. 3 TON R22 ............ HFE 3 H * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SVE 5 - * ............. 5 TON R22 ............ HFE 51/2 H * ................................. 51/2 TON R22 ........... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ SVE 8 - * ............. 8 TON R22 ............ HFE 8 H * ...................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VFE 35 - * ............ 35 TON R12 .......... T1R 35 F * ..................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VFE 45 - * ............ 45 TON R12 .......... THR 45 F * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VFE 55 - * ............ 55 TON R12 .......... THR 55 F * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VJE 45 - * ............ 45 TON R134 ........ TIR 45 M * .................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VJE 55 - * ............ 55 TON R134 ........ THR 55 M * ................................... SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VRE 38 - * ........... 38 TON R502 ........ TIR 37 R * ..................................... 37 TON R502 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VRE 50 - * ........... 50 TON R502 ........ THR 48 R * .................................... 48 TON R502 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VSE 38 - * ........... 38 TON R404 ........ TIR 37 S * ..................................... 37 TON R404 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VSE 50 - * ........... 50 TON R404 ........ THR 48 S * .................................... 48 TON R404 ............ *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VVE 1OO - * ........ 100 TON R22 ........ THR 100 H - * ................................ SAME ....................... *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VVE 52 - * ........... 52 TON R22 .......... TIR 55 H * ..................................... 55 TON R22 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPTXV ................ VVE 70 - * ........... 70 TON R22 .......... THR 75 H * .................................... 75 TON R22 .............. *REPLACE SPORLAN C, Z, ZP WITH ALCO C, Z, MOPSOLENOID ..... W14P2 ................ 1/2 FPT ................. 231WB 08P04 ............................... SAME ....................... WATER SERVICESOLENOID ..... W19P2 ................ 3/4 FPT ................. 231WB 12P06 ............................... SAME ....................... WATER SERVICESOLENOID ..... W25P2 ................ 1 FPT .................. 231WB 16P08 ............................... SAME ....................... WATER SERVICESOLENOID ..... W3P1 .................. 1/4 FPT ................. 204CD 1/4 B 1/8 B ......................... SAME ....................... WATER SERVICESOLENOID ..... W6P1 .................. 3/8 FPT ................. 203 CA 3/8B 1/4 B ......................... SAME ....................... WATER SERVICE

Cross Reference - Upgrade to Alco

139RSP-PRC022-EN

Product Type Sporlan No. Spor. Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ................ WFE 110 ............. 110 TON R12 ........ POS 100F1 ....................................................................... HAS INTEGRAL SOLENOIDTXV ................ WFE 80 ............... 80 TON R12 .......... POS 75 F1 ..................................... 75 TON R 12 ............. HAS INTEGRAL SOLENOIDTXV ................ WJE 110 ............. 110 TON R134 ................................................................................................ NO REPLACEMENTTXV ................ WJE 80 ............... 80 TON R134 ........ POS 90 M1 .................................... 90 TON R134 ............ HAS INTEGRAL SOLENOIDTXV ................ WRE 100 ............. 100 TON R502 ................................................................................................ NO REPLACEMENTTXV ................ WRE 70 ............... 70 TON R502 .................................................................................................. NO REPLACEMENTTXV ................ WSE 100 ............. 100 TON R404 ................................................................................................ NO REPLACEMENTTXV ................ WSE 70 ............... 70 TON R404 .................................................................................................. NO REPLACEMENTTXV ................ WVE 135 ............. 135 TON R22 ........ POS 125 H1 .................................. 125 TON R22 ............ HAS INTEGRAL SOLENOIDTXV ................ WVE 180 ............. 180 TON R22 .................................................................................................. NO REPLACEMENTSTRAINER ...... XD-074 ................ NONE .......................................................................... AMMONIA SERVICESOLENOID ..... XPO .................... RAPID CYCLING ... NONE ..................SOLENOID ..... XRM ................... RAPID CYCLING ... NONE ..................SOLENOID ..... XRN .................... RAPID CYCLING ... NONE ..................SOLENOID ..... XUP .................... RAPID CYCLING ... NONE ..................TXV ................ Y 1037 FV 1 ......... LIQUID INJ. .......... LCL ............................................... NONE ....................... CHECK APPLICATIONTXV ................ Y 1037 FV 1/2 ...... LIQUID INJ. .......... LCL ............................................... NONE ....................... CHECK APPLICATIONTXV ................ Y 1037 FV 11/2 .... LIQUID INJ. .......... LCL ............................................... NONE ....................... CHECK APPLICATIONTXV ................ Y 1037 FV 2 ......... LIQUID INJ. .......... LCL ............................................... NONE ....................... CHECK APPLICATIONTXV ................ Y 1037 FV 3 ......... LIQUID INJ. .......... LCL ............................................... NONE ....................... CHECK APPLICATIONTXV ................ Y 1037 FV 5 ......... LIQUID INJ. .......... LCL ............................................... NONE ....................... CHECK APPLICATIONTXV ................ Y 362 .................. VARIOUS .............. NONE ........................................... NONE ....................... OEM SPECIAL - DEFROST PORTTXV ................ Y 735 .................. VARIOUS .............. NONE ........................................... NONE ....................... DOUBLE DIAPHRAGMTXV ................ Y 750 .................. VARIOUS .............. NONE ........................................... NONE ....................... DOUBLE DIAPHRAGMTXV ................ Y 755 .................. VARIOUS .............. NONE ........................................... NONE ....................... DOUBLE DIAPHRAGMTXV ................ Y 781 .................. VARIOUS .............. NONE ........................................... NONE ....................... OEM SPECIAL - DEFROST PORT

Cross Reference - Upgrade to Alco

RSP-PRC022-EN140

Cross Reference - Upgrade to Alco

Danfoss to AlcoProduct Type Danfoss No. Danfoss Descrip. Alco No. Alco Descrip. Comment - ALCODRIER ............. ** 032 ................ 1/4 SAE ................. EK 032 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 032S .............. 1/4 ODF ................ EK 032S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 033 ................ 3/8 SAE ................. EK 033 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 033S .............. 3/8 ODF ................ EK 033S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 052 ................ 1/4 SAE ................. EK 052 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 052S .............. 1/4 ODF ................ EK 052S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 053 ................ 3/8 SAE ................. EK 053 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 053S .............. 3/8 ODF ................ EK 053S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 082 ................ 1/4 SAE ................. EK 082 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 082S .............. 1/4 ODF ................ EK 082S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 083 ................ 3/8 SAE ................. EK 083 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 083S .............. 3/8 ODF ................ EK 083S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 084 ................ 1/2 SAE ................. EK 084 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 084S .............. 1/2 ODF ................ EK 084S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 162 ................ 1/4 SAE ................. EK 162 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 162S .............. 1/4 ODF ................ EK 162S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 163 ................ 3/8 SAE ................. EK 163 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 163S .............. 3/8 ODF ................ EK 163S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 164 ................ 1/2 SAE ................. EK 164 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 164S .............. 1/2 ODF ................ EK 164S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 165 ................ 5/8 SAE ................. EK 165 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 165S .............. 5/8 ODF ................ EK 165S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 303 ................ 3/8 SAE ................. EK 303 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 303S .............. 3/8 ODF ................ EK 303S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 304 ................ 1/2 SAE ................. EK 304 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 304S .............. 1/2 ODF ................ EK 304S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 305 ................ 5/8 SAE ................. EK 305 .......................................... SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 305S .............. 5/8 ODF ................ EK 305S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. ** 307S .............. 7/8 ODF ................ EK 307S ........................................ SAME ....................... ** DANFOSS PREFIX DN, DCL, DU, DML, DXDRIER ............. 48DA ................... 48 CU. IN. ............. W48 .............................................. SAME ....................... REPLACABLE DRIER BLOCKDRIER ............. 48DN .................. 48 CU. IN. ............. H48 ............................................... SAME ....................... REPLACABLE DRIER BLOCKDRIER ............. 48DU .................. 48 CU. IN. ............. UK48 ............................................. SAME ....................... REPLACABLE DRIER BLOCKDRIER ............. 48F ...................... 48 CU. IN. ............. F48R ............................................. SAME ....................... REPLACABLE FILTER COREDRIER ............. DCR 0485 ............ 5/8 ODF ................ STAS 485T .................................... SAME ....................... DRIER SHELL - 1 COREDRIER ............. DCR 0487 ............ 7/8 ODF ................ STAS 487T .................................... SAME ....................... DRIER SHELL - 1 COREDRIER ............. DCR 0967 ............ 7/8 ODF ................ STAS 967T .................................... SAME ....................... DRIER SHELL - 2 COREDRIER ............. DCR 0969 ............ 11/8 ODF ............... STAS 969T .................................... SAME ....................... DRIER SHELL - 2 COREDRIER ............. DCR 14411 .......... 13/8 ODF ............... STAS 14411T ................................ SAME ....................... DRIER SHELL - 3 COREDRIER ............. DCR 19213 .......... 15/8 ODF ............... STAS 19213T ................................ SAME ....................... DRIER SHELL - 4 CORESOLENOID ..... EVR 10 ................ 5/8 ODF ................ 200RB 6T5T .................................. SAME ....................... REFRIGERATION SERVICE - VLCSOLENOID ..... EVR 15 ................ 7/8 ODF ................ 240RA 8T7T .................................. SAME ....................... REFRIGERATION SERVICE - VLCSOLENOID ..... EVR 2 .................. 1/4 ODF ................ 100RB2T2 ..................................... SAME ....................... REFRIGERATION SERVICE - VLCSOLENOID ..... EVR 20 ................ 11/8 ODF ............... 240RA1279T ................................. SAME ....................... REFRIGERATION SERVICE - VLCSOLENOID ..... EVR 25 ................ 13/8 ODG .............. 240RA 16T11M ............................. SAME ....................... REFRIGERATION SERVICE - VLCSOLENOID ..... EVR 3 .................. 3/8 ODF ................ 200RB 3T3 .................................... SAME ....................... REFRIGERATION SERVICE - VLCSOLENOID ..... EVR 6 .................. 1/2 ODF ................ 200RB 4T4T .................................. SAME ....................... REFRIGERATION SERVICE - VLCTPC ................ KP1 60-1101 ........ LOW PRES ........... PS1-X3A ....................................... SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSTPC ................ KP15 60-1241 ...... DUAL PRES .......... PS2-A7A ....................................... SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSTPC ................ KP15 60-1243 ...... DUAL PRES .......... PS2-L7A ........................................ SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSTPC ................ KP15 60-1264 ...... DUAL PRES .......... PS2-L7A ........................................ SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSTPC ................ KP15 60-1265 ...... DUAL PRES .......... PS2-A7A ....................................... SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSTPC ................ KP2 60-1120 ........ LOW PRES ........... PS1-X1A ....................................... SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSTPC ................ KP5 60-1171 ........ HIGH PRES ........... PS1-X5A ....................................... SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSTPC ................ KP5 60-1173 ........ HIGH PRES ........... PS1-Y5A ....................................... SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSTPC ................ KP61 60L1100 ..... TEMP CONTROL .. TS1-X2P ....................................... SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSTPC ................ KP62 60L1106 ..... TEMP CONTROL .. TS1- * ........................................... SAME ....................... * SEE CATALOG SECTION TO COMPLETE PART NO.TPC ................ KP63 60L1107 ..... TEMP CONTROL .. TS1- * ........................................... SAME ....................... * SEE CATALOG SECTION TO COMPLETE PART NO.TPC ................ KP71 60L1113 ..... TEMP CONTROL .. TS1-A4F ........................................ SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSTPC ................ KP73 60L1117 ..... TEMP CONTROL .. TS1-A4F ........................................ SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSTPC ................ KP75 60L1120 ..... TEMP CONTROL .. TS1-A4F ........................................ SAME ....................... SEE CATALOG SECTION FOR MORE SPECIFICSREGULATOR .. KVP12 ................. 1/2 ODF ................ IPR - 6 ........................................... SAME ....................... VARIOUS PRESSURE RANGES AVAILABLEREGULATOR .. KVP15 ................. 5/8 ODF ................ IPR - 6 ........................................... SAME ....................... VARIOUS PRESSURE RANGES AVAILABLEREGULATOR .. KVP22 ................. 7/8 ODF ................ IPR - 6 ........................................... SAME ....................... VARIOUS PRESSURE RANGES AVAILABLEREGULATOR .. KVP28 ................. 11/8 ODF ............... IPR - 10 ......................................... SAME ....................... VARIOUS PRESSURE RANGES AVAILABLEREGULATOR .. KVP35 ................. 13/8 ODF ............... IPR - 10 ......................................... SAME ....................... VARIOUS PRESSURE RANGES AVAILABLETXV ................ PHTF - 125 .......... 125 TON R12 ........ POS 125 F1 ................................... SAME ....................... PILOT OPERATED SOLENOID - LESS COILTXV ................ PHTF - 300 - 1 ...... 200 TON R12 ........ POS 200 F1 ................................... SAME ....................... PILOT OPERATED SOLENOID - LESS COILTXV ................ PHTF - 300 - 2 ...... 300 TON R12 ........ POS 300 F1 ................................... SAME ....................... PILOT OPERATED SOLENOID - LESS COILTXV ................ PHTF 85 - 2 ......... 20 TON R12 .......... POS 20 F1 ..................................... SAME ....................... PILOT OPERATED SOLENOID - LESS COILTXV ................ PHTF 85 - 3 ......... 40 TON R12 .......... POS 40 F1 ..................................... SAME ....................... PILOT OPERATED SOLENOID - LESS COILTXV ................ PHTF 85 - 4 ......... 50 TON R12 .......... POS 50 F1 ..................................... SAME ....................... PILOT OPERATED SOLENOID - LESS COIL

141RSP-PRC022-EN

Product Type Danfoss No. Danfoss Descrip. Alco No. Alco Descrip. Comment - ALCO

TXV ................ PHTX 125 ............ 200 TON R22 ........ POS 200 H1 .................................. SAME ....................... PILOT OPERATED SOLENOID - LESS COILTXV ................ PHTX 300 - 1 ....... 350 TON R22 ........ POS 350 H1 .................................. SAME ....................... PILOT OPERATED SOLENOID - LESS COILTXV ................ PHTX 85 - 1 ......... 30 TON R22 .......... POS 30 H1 .................................... SAME ....................... PILOT OPERATED SOLENOID - LESS COILTXV ................ PHTX 85 - 2 ......... 50 TON R22 .......... POS 50 H1 .................................... SAME ....................... PILOT OPERATED SOLENOID - LESS COILTXV ................ PHTX 85 - 3 ......... 75 TON R22 .......... POS 75 H1 .................................... SAME ....................... PILOT OPERATED SOLENOID - LESS COILTXV ................ PHTX 85 - 4 ......... 125 TON R22 ........ POS 125 H1 .................................. SAME ....................... PILOT OPERATED SOLENOID - LESS COILREGULATOR .. PKV12 ................. 11/8 ODF ............... EPRB12T9 ..................................... SAME ....................... BRASS BODY EPRREGULATOR .. PKV15 ................. 13/8 ODF ............... EPRB16T11 ................................... SAME ....................... BRASS BODY EPRREGULATOR .. PKV20 ................. 15/8 ODF ............... EPRB20T13 ................................... SAME ....................... BRASS BODY EPRREGULATOR .. PKVS12 ............... 11/8 ODF ............... EPRBS12T9 .................................. SAME ....................... BRASS BODY EPR WITH INTEGRAL SOLENOIDREGULATOR .. PKVS15 ............... 13/8 ODF ............... EPRBS16T11 ................................. SAME ....................... BRASS BODY EPR WITH INTEGRAL SOLENOIDREGULATOR .. PKVS20 ............... 15/8 ODF ............... EPRBS20T13 ................................. SAME ....................... BRASS BODY EPR WITH INTEGRAL SOLENOIDREGULATOR .. PM1-10 ............... VLF ....................... EPRV - 13 ...................................... SAME ....................... IRON BODY EPRREGULATOR .. PM1-15 ............... VLF ....................... EPRV - 14 ...................................... SAME ....................... IRON BODY EPRREGULATOR .. PM1-20 ............... VLF ....................... EPRV - 15 ...................................... SAME ....................... IRON BODY EPRREGULATOR .. PM1-25 ............... VLF ....................... EPRV - 16 ...................................... SAME ....................... IRON BODY EPRREGULATOR .. PM1-32 ............... VLF ....................... EPRV - 18 ...................................... SAME ....................... IRON BODY EPRREGULATOR .. PM1-5 ................. VLF ....................... EPRV - 12 ...................................... SAME ....................... IRON BODY EPRREGULATOR .. PM3-10 ............... VLF ....................... EPRVS - 13 .................................... SAME ....................... IRON BODY EPR WITH INTEGRAL SOLENOIDREGULATOR .. PM3-15 ............... VLF ....................... EPRVS - 14 .................................... SAME ....................... IRON BODY EPR WITH INTEGRAL SOLENOIDREGULATOR .. PM3-20 ............... VLF ....................... EPRVS - 15 .................................... SAME ....................... IRON BODY EPR WITH INTEGRAL SOLENOIDREGULATOR .. PM3-25 ............... VLF ....................... EPRVS - 16 .................................... SAME ....................... IRON BODY EPR WITH INTEGRAL SOLENOIDREGULATOR .. PM3-32 ............... VLF ....................... EPRVS - 18 .................................... SAME ....................... IRON BODY EPR WITH INTEGRAL SOLENOIDREGULATOR .. PM3-5 ................. VLF ....................... EPRVS - 12 .................................... SAME ....................... IRON BODY EPR WITH INTEGRAL SOLENOIDTXV ................ TDEX 11 ............. 10 TON R22 .......... TFES 10 HCA ................................ SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 12.5 ........... 12 TON R22 .......... TFES 12 HCA ................................ SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 18 ............. 20 TON R22 .......... TRAE+ 20 HCA .............................. SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 19 ............. 20 TON R22 .......... TRAE+ 20 HCA .............................. SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 20 ............. 20 TON R22 .......... TRAE+ 20 HCA .............................. SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 25 ............. 30 TON R22 .......... TRAE+ 30 HCA .............................. SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 3 ............... 3 TON R22 ............ BAE 3 HCA .................................... SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 30 ............. 30 TON R22 .......... TRAE+ 30 HCA .............................. SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 4 ............... 4 TON R22 ............ BAE 4 HCA .................................... SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 40 ............. 40 TON R22 .......... TRAE+ 40 HCA .............................. SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 6 ............... 6 TON R22 ............ HFES 51/2 HCA ............................. SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 7.5 ............. 8 TON R22 ............ TFES 8 HCA .................................. SAME ....................... ALCO IS BALANCED PORTTXV ................ TDEX 8 ............... 8 TON R22 ............ TFES 8 HCA .................................. SAME ....................... ALCO IS BALANCED PORTTXV ................ TEF 12 - 12* ........ 12 TON R12 .......... TJRE 11 F* .................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEF 12 - 3* .......... 3 TON R12 ............ TCLE 3 F* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEF 12 - 5* .......... 4 TON R12 ............ TCLE 4 F* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEF 12 - 8* .......... 71/2 TON R12 ....... TCLE 71/2 F* ................................. SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEF 2 - 0.3* ......... 1/3 TON R12 ......... TIE 1 F* ......................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEF 2 - 0.5* ......... 1/2 TON R12 ......... TIE 2 F* ......................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEF 2 - 1.0* ......... 1 TON R12 ............ TIE 3 F* ......................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEF 2 - 1.5* ...... 11/2 TON R12 ....... TIE 4 F* ......................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEF 2 - 2.0* ...... 2 TON R12 ............ TIE 5 F* ......................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEF 2 - 3.0* ...... 21/2 TON R12 ....... TIE 6 F* ......................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEF 20 - 20* ..... 20 TON R12 .......... TER 20 F* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEF 5 - 2* ......... 2 TON R12 ............ TCLE 2 F* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEF 5 - 3* ......... 3 TON R12 ............ TCLE 3 F* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEF 5 - 5* ......... 4 TON R12 ............ TCLE 4 F* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEF 5 - 8* ......... 8 TON R12 ............ TCLE 71/2 F* ................................. SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEF 55 - 33* ..... 35 TON R12 .......... TIR 35 F* ....................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEF 55 - 55* ..... 55 TON R12 .......... THR 55 F* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 12 - 12* .... 12 TON R22 .......... TCLE 12 H* ................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 12 - 18* .... 18 TON R22 .......... TJRE 18 H* ................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 12 - 4.5* .... 5 TON R22 ............ TCLE 5 H* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 12 - 7.5* .... 71/2 TON R22 ....... TCLE 71/2 H* ................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 2 - 0.7* ..... 1/3 TON R22 ......... TIE 0 H* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 2 - 1.0* ..... 3/4 TON R22 ......... TIE 1 H* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 2 - 1.5* ..... 1 TON R22 ............ TIE 2 H* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 2 - 2.3* ..... 2 TON R22 ............ TIE 3 H* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 2 - 3.0* ..... 3 TON R22 ............ TIE 4 H* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 2 - 4.5* ..... 4 TON R22 ............ TIE 5 H* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 20 - 30* .... 30 TON R22 .......... TER 26 H* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 5 - 12* ...... 12 TON R22 .......... TCLE 12 H* ................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 5 - 3* ........ 3 TON R22 ............ TCLE 3 H* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 5 - 4.5* ..... 5 TON R22 ............ TCLE 5 H* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 5 - 7.5* ..... 71/2 TON R22 ....... TCLE 71/2 H* ................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 55 - 50* .... 50 TON R22 .......... TER 45 H* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................... TEX 55 - 85* .... 85 TON R22 .......... THR 100 H* ................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOP

Cross Reference - Upgrade to Alco

RSP-PRC022-EN142

Product Type Danfoss No. Danfoss Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ................ TEY 12 - 3* .......... 2 TON R502 .......... TCLE 2 R* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 12 - 5* .......... 5 TON R502 .......... TCLE 41/2 R* ................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 12 - 8* .......... 7 TON R502 .......... TCLE 7 R* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 12 -12* ......... 12 TON R502 ........ TJRE 12 R* ................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 2 - 0.2* ......... 1/4 TON R502 ....... TIE 0 R* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 2 - 0.3* ......... 1/2 TON R502 ....... TIE 1 R* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 2 - 0.6* ......... 3/4 TON R502 ....... TIE 2 R* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 2 - 1.0* ......... 11/2 TON R502 ..... TIE 3 R* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 2 - 1.5* ......... 2 TON R502 .......... TIE 4 R* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 2 - 2.0* ......... 21/2 TON R502 ..... TIE 5 R* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 2 - 3.0* ......... 3 TON R502 .......... TIE 6 R* ........................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 20 - 20* ........ 20 TON R502 ........ TER 16 R* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 5 - 2* ........... 2 TON R502 .......... TCLE 2 R* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 5 - 3* ........... 3 TON R502 .......... TCLE 3 R* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 5 - 5* ........... 5 TON R502 .......... TCLE 41/2 R* ................................ SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 5 - 8* ........... 8 TON R502 .......... TCLE 8 R* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 55 - 33* ........ 33 TON R502 ........ TER 27 R* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TEY 55 - 55* ........ 55 TON R502 ........ THR 48 R* ..................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TF 2 - 0.2* ........... 1/6 TON R12 ......... TI 0 F* ........................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TF 2 - 0.3* ........... 1/3 TON R12 ......... T1 1 F* .......................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TF 2 - 0.5* ........... 1/2 TON R12 ......... TI 2 F* ........................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TF 2 - 1.0* ........... 1 TON R12 ............ TI 3 F* ........................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TF 2 - 1.5* ........... 11/2 TON R12 ....... TI 4 F* ........................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TF 2 - 2.0* ........... 2 TON R12 ............ TI 5 F* ........................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TF 2 - 3.0* ........... 21/2 TON R12 ....... TI 6 F* ........................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOPTXV ................ TKEF 20 - 10* ...... 10 TON R12 .......... TJRE 11 F* .................................... SAME ....................... *REPLACE DANFOSS N,NM,NL,B WITH ALCO C, MOP

Cross Reference - Upgrade to Alco

143RSP-PRC022-EN

Virginia to AlcoProduct Type Virginia No. Virginia Descrip. Alco No. Alco Descrip. Comment - ALCOSIGHT GLASS ....... LDE-2 .................. 1/4 SAE ................... AMI-1MM2 .................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-2MF ............. 1/4 SAE MXF .......... AMI-1MU2 ..................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-2S ................ 1/4 ODF ................... ALM-1TT2 ...................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-3 .................. 3/8 SAE ................... AMI-1MM3 .................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-3MF ............. 3/8 SAE MXF .......... AMI-1MU3 ..................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-3S ................ 3/8 ODF ................... ALM-1TT3 ...................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-4 .................. 1/2 SAE ................... AMI-1MM4 .................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-4MF ............. 1/2 SAE MXF .......... AMI-1MU4 ..................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-4S ................ 1/2 ODF ................... ALM-1TT4 ...................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-5 .................. 5/8 SAE ................... AMI-1MM5 .................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-5MF ............. 5/8 SAE MXF .......... AMI-1MU5 ..................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-5S ................ 5/8 ODF ................... ALM-1TT5 ...................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-7S ................ 7/8 ODF ................... ALM-1TT7 ...................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... LDE-9S ................ 11/8 ODF ................. AMI-1TT9 ....................................... SAME .................... MOISTURE INDICATORBALL VALVE .......... RB11S ................. 13/8 ODF ................. ABV11 ............................................ SAME .................... FULL PORTBALL VALVE .......... RB11SP ............... 13/8 ODF ................. ABV11A ......................................... SAME .................... WITH ACCESS VALVEBALL VALVE .......... RB13S ................. 15/8 ODF ................. ABV13 ............................................ SAME .................... FULL PORTBALL VALVE .......... RB13SP ............... 15/8 ODF ................. ABV13A ......................................... SAME .................... WITH ACCESS VALVEBALL VALVE .......... RB17S ................. 21/8 ODF ................. ABV17 ............................................ SAME .................... FULL PORTBALL VALVE .......... RB17SP ............... 21/8 ODF ................. ABV17A ......................................... SAME .................... WITH ACCESS VALVEBALL VALVE .......... RB21S ................. 25/8 ODF ................. ABV21 ............................................ SAME .................... FULL PORTBALL VALVE .......... RB21SP ............... 25/8 ODF ................. ABV21A ......................................... SAME .................... WITH ACCESS VALVEBALL VALVE .......... RB25S ................. 31/8 ODF ................. ABV25 ............................................ SAME .................... FULL PORTBALL VALVE .......... RB25SP ............... 31/8 ODF ................. ABV25A ......................................... SAME .................... WITH ACCESS VALVEBALL VALVE .......... RB2S ................... 1/4 ODF ................... ABV2 .............................................. SAME .................... FULL PORTBALL VALVE .......... RB2SP ................. 1/4 ODF ................... ABV2A ........................................... SAME .................... WITH ACCESS VALVEBALL VALVE .......... RB3S ................... 3/8 ODF ................... ABV3 .............................................. SAME .................... FULL PORTBALL VALVE .......... RB3SP ................. 3/8 ODF ................... ABV3A ........................................... SAME .................... WITH ACCESS VALVEBALL VALVE .......... RB4S ................... 1/2 ODF ................... ABV4 .............................................. SAME .................... FULL PORTBALL VALVE .......... RB4SP ................. 1/2 ODF ................... ABV4A ........................................... SAME .................... WITH ACCESS VALVEBALL VALVE .......... RB5S ................... 5/8 ODF ................... ABV5 .............................................. SAME .................... FULL PORTBALL VALVE .......... RB5SP ................. 5/8 ODF ................... ABV5A ........................................... SAME .................... WITH ACCESS VALVEBALL VALVE .......... RB7S ................... 7/8 ODF ................... ABV7 .............................................. SAME .................... FULL PORTBALL VALVE .......... RB7SP ................. 7/8 ODF ................... ABV7A ........................................... SAME .................... WITH ACCESS VALVEBALL VALVE .......... RB9S ................... 11/8 ODF ................. ABV9 .............................................. SAME .................... FULL PORTBALL VALVE .......... RB9SP ................. 11/8 ODF ................. ABV9A ........................................... SAME .................... WITH ACCESS VALVESIGHT GLASS ....... TDE-2 .................. 1/4 SAE ................... A-IHN2 ........................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... TDE-3 .................. 3/8 SAE ................... A-IHN3 ........................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... TDE-3S ................ 3/8 ODF ................... A-IHN3S ......................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... TDE-4 .................. 1/2 SAE ................... A-IHN4 ........................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... TDE-4S ................ 1/2 ODF ................... A-IHN4S ......................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... TDE-5 .................. 5/8 SAE ................... A-IHN5 ........................................... SAME .................... MOISTURE INDICATORSIGHT GLASS ....... TDE-5S ................ 5/8 ODF ................... A-IHN5S ......................................... SAME .................... MOISTURE INDICATORACCUMULATOR ... VA-30-4S ............. 1/2 ODF ................... A-AS-384 ....................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-31-5S ............. 5/8 ODF ................... A-AS-3105 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-32-5S ............. 5/8 ODF ................... A-AS-3125 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-32-6S ............. 3/4 ODF ................... A-AS-3126 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-35-5S ............. 5/8 ODF ................... A-AS-3145 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-35-6S ............. 3/4 ODF ................... A-AS-3146 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-44-6SRD ........ 3/4 ODF ................... A-AS-4106 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-54-6SRD ........ 3/4 ODF ................... A-AS-4105 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-54-6SRD ........ 3/4 ODF ................... A-AS-596 ....................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-54-7SRD ........ 7/8 ODF ................... A-AS-597 ....................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-56-6SRD ........ 3/4 ODF ................... A-AS-5126 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-56-7SRD ........ 7/8 ODF ................... A-AS-5127 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-57-7SRD ........ 7/8 ODF ................... A-AS-5137 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-57-9SRD ........ 11/8 ODF ................. A-AS-5139 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-59-11SRD ...... 13/8 ODF ................. A-AS-51711 .................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-59-9SRD ........ 11/8 ODF ................. A-AS-5179 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-610-7SRD ...... 7/8 ODF ................... A-AS-6137 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-610-9SRD ...... 11/8 ODF ................. A-AS-6139 ...................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-611-11SRD ..... 13/8 ODF ................. A-AS-61411 .................................... SAME .................... SUCTION SERVICEACCUMULATOR ... VA-616-13SRD ..... 15/8 ODF ................. A-AS-62013 .................................... SAME .................... SUCTION SERVICEOIL SEPARATOR ... VOF-410-4 ........... 1/2 ODF ................... A-F58824 ........................................ SAME .................... FLANGEDOIL SEPARATOR ... VOF-414-5 ........... 5/8 ODF ................... A-F58855 ........................................ SAME .................... FLANGEDOIL SEPARATOR ... VOF-417-7 ........... 7/8 ODF ................... A-F58877 ........................................ SAME .................... FLANGEDOIL SEPARATOR ... VOF-421-11 ......... 13/8 ODF ................. A-F589011 ...................................... SAME .................... FLANGEDOIL SEPARATOR ... VOF-421-9 ........... 11/8 ODF ................. A-F58889 ........................................ SAME .................... FLANGEDOIL SEPARATOR ... VOF-620-13 ......... 15/8 ODF ................. A-F579213 ...................................... SAME .................... FLANGEDOIL SEPARATOR ... VOF-620-17 ......... 21/8 ODF ................. A-F57917 ........................................ SAME .................... FLANGEDOIL SEPARATOR ... VOS-414-5 ........... 5/8 ODF ................... A-W55855 ...................................... SAME .................... SEALED

Cross Reference - Upgrade to Alco

RSP-PRC022-EN144

Product Type Virginia No. Virginia Descrip. Alco No. Alco Descrip. Comment - ALCOOIL SEPARATOR ... VOS-417-7 ........... 7/8 ODF ................... A-W55877 ...................................... SAME .................... SEALEDOIL SEPARATOR ... VOS-421-11 ......... 13/8 ODF ................. A-W559011 .................................... SAME .................... SEALEDOIL SEPARATOR ... VOS-421-9 ........... 11/8 ODF ................. A-W55889 ...................................... SAME .................... SEALEDOIL SEPARATOR ... VOS-619-13 ......... 15/8 ODF ................. A-W559213 .................................... SAME .................... SEALEDOIL SEPARATOR ... VOS-619-17 ......... 21/8 ODF ................. A-W569417 .................................... SAME .................... SEALEDDRIER .................... VS-100H .............. 100 CU. IN. .............. H100 .............................................. SAME .................... BLOCKDRIER .................... VS-42R ................ 42 CU. IN. ................ W42 ............................................... SAME .................... BLOCKDRIER .................... VS-48F ................ 48 CU. IN. ................ F48R ............................................... SAME .................... FILTERDRIER .................... WAH 032 ............. 1/4 SAE ................... EK 032 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 032S .......... 1/4 ODF ................... EK 032S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 033 ............. 3/8 SAE ................... EK 033 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 033S .......... 3/8 ODF ................... EK 033S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 052 ............. 1/4 SAE ................... EK 052 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 0525S ......... 5/16 ODF ................. EK 0525S ....................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 052S .......... 1/4 ODF ................... EK 052S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 053 ............. 3/8 SAE ................... EK 053 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 053S .......... 3/8 ODF ................... EK 053S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 082 ............. 1/4 SAE ................... EK 082 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 0825S ......... 5/16 ODF ................. EK 0825S ....................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 082S .......... 1/4 ODF ................... EK 082S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 083 ............. 3/8 SAE ................... EK 083 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 083S .......... 3/8 ODF ................... EK 083S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 084 ............. 1/2 SAE ................... EK 084 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 084S .......... 1/2 ODF ................... EK 084S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 162 ............. 1/4 SAE ................... EK 162 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 1625S ......... 5/16 ODF ................. EK 1625S ....................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 162S .......... 1/4 ODF ................... EK 162S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 164 ............. 1/2 SAE ................... EK 164 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 164S .......... 1/2 ODF ................... EK 164S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 165 ............. 5/8 SAE ................... EK 165 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 165S .......... 5/8 ODF ................... EK 165S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 303 ............. 3/8 SAE ................... EK 303 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 303S .......... 3/8 ODF ................... EK 303S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 304 ............. 1/2 SAE ................... EK 304 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 304S .......... 1/2 ODF ................... EK304S .......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 305 ............. 5/8 SAE ................... EK 305 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 305S .......... 5/8 ODF ................... EK 305S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 307S .......... 7/8 ODF ................... EK 307S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 413 ............. 3/8 SAE ................... EK 413 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 414 ............. 1/2 SAE ................... EK 414 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 414S .......... 1/2 ODF ................... EK 414S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 415 ............. 5/8 SAE ................... EK 415 ............................................ SAME .................... STANDARD OPERATIONDRIER .................... WAH 415S .......... 5/8 ODF ................... EK 415S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 417S .......... 7/8 ODF ................... EK 417S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 757S .......... 7/8 ODF ................... EK 757S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WAH 759S .......... 11/8 ODF ................. EK 759S ......................................... SAME .................... STANDARD OPERATIONDRIER .................... WC-48H .............. 48 CU. IN. ................ H48 ................................................ SAME .................... BLOCKDRIER .................... WC-48S ............... 48 CU. IN. ................ W48 ............................................... SAME .................... BLOCKDRIER .................... WHP-083 ............. 3/8 SAE ................... BFK 083 ......................................... SAME .................... BI - FLOWDRIER .................... WHP-083S ........... 3/8 ODF ................... BFK 083S ....................................... SAME .................... BI - FLOWDRIER .................... WHP-084 ............. 1/2 SAE ................... BFK 084 ......................................... SAME .................... BI - FLOWDRIER .................... WHP-084S ........... 1/2 ODF ................... BFK 084S ....................................... SAME .................... BI - FLOWDRIER .................... WHP-163 ............. 3/8 SAE ................... BFK 163 ......................................... SAME .................... BI - FLOWDRIER .................... WHP-163S ........... 3/8 ODF ................... BFK 163S ....................................... SAME .................... BI - FLOWDRIER .................... WHP-164 ............. 1/2 SAE ................... BFK 164 ......................................... SAME .................... BI - FLOWDRIER .................... WHP-164S ........... 1/2 ODF ................... BFK 164S ....................................... SAME .................... BI - FLOWDRIER .................... WHP-165 ............. 5/8 SAE ................... BFK 165 ......................................... SAME .................... BI - FLOWDRIER .................... WHP-165S ........... 5/8 ODF ................... BFK 165S ....................................... SAME .................... BI - FLOWDRIER SHELL ........ WRK 14411 ......... 13/8 ODF ................. STAS 14411T ................................. SAME .................... 3 REPLACABLE COREDRIER SHELL ........ WRK 14413 ......... 15/8 ODF ................. STAS 14413T ................................. SAME .................... 3 REPLACABLE COREDRIER SHELL ........ WRK 14417 ......... 21/8 ODF ................. STAS 14417T ................................. SAME .................... 3 REPLACABLE COREDRIER SHELL ........ WRK 19211 ......... 13/8 ODF ................. STAS 19211T ................................. SAME .................... 4 REPLACABLE COREDRIER SHELL ........ WRK 19213 ......... 15/8 ODF ................. STAS 19213T ................................. SAME .................... 4 REPLACABLE COREDRIER SHELL ........ WRK 19217 ......... 21/8 ODF ................. STAS 19217T ................................. SAME .................... 4 REPLACABLE COREDRIER SHELL ........ WRK 4811 ........... 13/8 ODF ................. STAS 4811T ................................... SAME .................... 1 REPLACABLE COREDRIER SHELL ........ WRK 4813 ........... 15/8 ODF ................. STAS 4813T ................................... SAME .................... 1 REPLACABLE COREDRIER SHELL ........ WRK 4817 ........... 21/8 ODF ................. STAS 4817T ................................... SAME .................... 1 REPLACABLE COREDRIER SHELL ........ WRK 4821 ........... 25/8 ODF ................. STAS 4821SV ................................. SAME .................... 1 REPLACABLE COREDRIER SHELL ........ WRK 485 ............. 5/8 ODF ................... STAS 485T ..................................... SAME .................... 1 REPLACABLE COREDRIER SHELL ........ WRK 487 ............. 7/8 ODF ................... STAS 487T ..................................... SAME .................... 1 REPLACABLE COREDRIER SHELL ........ WRK 489 ............. 11/8 ODF ................. STAS 489T ..................................... SAME .................... 1 REPLACABLE CORE

Cross Reference - Upgrade to Alco

145RSP-PRC022-EN

Product Type Virginia No. Virginia Descrip. Alco No. Alco Descrip. Comment - ALCODRIER SHELL ........ WRK 9611 ........... 13/8 ODF ................. STAS 9611T ................................... SAME .................... 2 REPLACABLE COREDRIER SHELL ........ WRK 9613 ........... 15/8 ODF ................. STAS 9613T ................................... SAME .................... 2 REPLACABLE COREDRIER SHELL ........ WRK 9617 ........... 21/8 ODF ................. STAS 9617T ................................... SAME .................... 2 REPLACABLE COREDRIER SHELL ........ WRK 9621 ........... 25/8 ODF ................. STAS 9621SV ................................. SAME .................... 2 REPLACABLE COREDRIER SHELL ........ WRK 967 ............. 7/8 ODF ................... STAS 967T ..................................... SAME .................... 2 REPLACABLE COREDRIER SHELL ........ WRK 969 ............. 11/8 ODF ................. STAS 969T ..................................... SAME .................... 2 REPLACABLE COREDRIER .................... WSC 032 ............. 1/4 SAE ................... UDK 032 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 032S ........... 1/4 ODF ................... UDK 032S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 033 ............. 3/8 SAE ................... UDK 033 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 033S ........... 3/8 ODF ................... UDK 033S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 052 ............. 1/4 SAE ................... UDK 052 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 052S ........... 1/4 ODF ................... UDK 052S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 053 ............. 3/8 SAE ................... UDK 053 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 053S ........... 3/8 ODF ................... UDK 053S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 082 ............. 1/4 SAE ................... UDK 082 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 082S ........... 1/4 ODF ................... UDK 082S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 083 ............. 3/8 SAE ................... UDK 083 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 083S ........... 3/8 ODF ................... UDK 083S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 084 ............. 1/2 SAE ................... UDK 084 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 084S ........... 1/2 ODF ................... UDK 084S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 162 ............. 1/4 SAE ................... UDK 162 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 162S ........... 1/4 ODF ................... UDK 162S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 163 ............. 3/8 SAE ................... UDK 163 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 163S ........... 3/8 ODF ................... UDK 163S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 164 ............. 1/2 SAE ................... UDK 164 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 164S ........... 1/2 ODF ................... UDK 164S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 165 ............. 5/8 SAE ................... UDK 165 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 165S ........... 5/8 ODF ................... UDK 165S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 303 ............. 3/8 SAE ................... UDK 303 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 303S ........... 3/8 ODF ................... UDK 303S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 304 ............. 1/2 SAE ................... UDK 304 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 304S ........... 1/2 ODF ................... UDK 304S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 305 ............. 5/8 SAE ................... UDK 305 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 305S ........... 5/8 ODF ................... UDK 305S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 307S ........... 7/8 ODF ................... UDK 307S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 413S ........... 3/8 ODF ................... UDK 413S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 414 ............. 1/2 SAE ................... UDK 414 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 414S ........... 1/2 ODF ................... UDK 414S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 415 ............. 5/8 SAE ................... UDK 415 ......................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 415S ........... 5/8 ODF ................... UDK 415S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSC 417S ........... 7/8 ODF ................... UDK 417S ...................................... SAME .................... EXTRA WATER REMOVALDRIER .................... WSD-4S .............. 1/2 ODF ................... CSFD 14S4VV ................................ SAME .................... SUCTION SERVICEDRIER .................... WSD-5S .............. 5/8 ODF ................... CSFD 14S5VV ................................ SAME .................... SUCTION SERVICEDRIER .................... WSD-6S .............. 3/4 ODF ................... CSFD 14S6VV ................................ SAME .................... SUCTION SERVICEDRIER .................... WSD-7S .............. 7/8 ODF ................... CSFD 14S7VV ................................ SAME .................... SUCTION SERVICEDRIER .................... WSD-9S .............. 11/8 ODF ................. CSFD 14S9VV ................................ SAME .................... SUCTION SERVICEDRIER .................... WSF-11S ............. 13/8 ODF ................. ASF 75S11VV ................................. SAME .................... SUCTION SERVICEDRIER .................... WSF-13S ............. 15/8 ODF ................. ASF 75S13VV ................................. SAME .................... SUCTION SERVICEDRIER .................... WSF-5S ............... 5/8 ODF ................... ASF 35S5VV .................................. SAME .................... SUCTION SERVICEDRIER .................... WSF-6S ............... 3/4 ODF ................... ASF 45S6VV .................................. SAME .................... SUCTION SERVICEDRIER .................... WSF-7S ............... 7/8 ODF ................... ASF 45S7VV .................................. SAME .................... SUCTION SERVICEDRIER .................... WSF-9S ............... 11/8 ODF ................. ASF 50S9VV .................................. SAME .................... SUCTION SERVICEDRIER .................... WSL 163S ........... 3/8 ODF ................... ASD 28S3VV .................................. SAME .................... SUCTION SERVICEDRIER .................... WSL 164S ........... 1/2 ODF ................... ASD 28S4VV .................................. SAME .................... SUCTION SERVICEDRIER .................... WSL 165S ........... 5/8 ODF ................... ASD 35S5VV .................................. SAME .................... SUCTION SERVICEDRIER .................... WSL 166S ........... 3/4 ODF ................... ASD 45S6VV .................................. SAME .................... SUCTION SERVICEDRIER .................... WSL 167S ........... 7/8 ODF ................... ASD 45S7VV .................................. SAME .................... SUCTION SERVICEDRIER .................... WSL 419S ........... 11/8 ODF ................. ASD 50S9VV .................................. SAME .................... SUCTION SERVICEDRIER .................... WSL 75S11 ......... 13/8 ODF ................. ASD 75S11VV ................................ SAME .................... SUCTION SERVICEDRIER .................... WSL 75S13 ......... 15/8 ODF ................. ASD 75S13VV ................................ SAME .................... SUCTION SERVICEDRIER .................... WTD-12 ............... 12 CU. IN. ................ A-TFD-12 ........................................ SAME .................... USE WITH A-IHN SIGHT GLASSDRIER .................... WTD-20 ............... 20 CU. IN. ................ A-TFD-20 ........................................ SAME .................... USE WITH A-IHN SIGHT GLASSDRIER .................... WTD-30 ............... 30 CU. IN. ................ A-TFD-30 ........................................ SAME .................... USE WITH A-IHN SIGHT GLASSDRIER .................... WTD-8 ................. 8 CU. IN. ................. A-TFD-08 ........................................ SAME .................... USE WITH A-IHN SIGHT GLASS

Cross Reference - Upgrade to Alco

RSP-PRC022-EN146

Parker to AlcoProduct Type Parker No. Parker Descrip. Alco No. Alco Descrip. Comment - ALCODRIER .................... 032S .................... 1/4 ODF ............ EK 032S ........................................... SAME ................. LIQUID LINEDRIER .................... 0525S .................. 5/16 ODF .......... EK 0525S ......................................... SAME ................. LIQUID LINEDRIER .................... 052S .................... 1/4 ODF ............ EK 052S ........................................... SAME ................. LIQUID LINEDRIER .................... 053S .................... 3/8 ODF ............ EK 053S ........................................... SAME ................. LIQUID LINEDRIER .................... 0825S .................. 5/16 ODF .......... EK 0825S ......................................... SAME ................. LIQUID LINEDRIER .................... 082S .................... 1/4 ODF ............ EK 082S ........................................... SAME ................. LIQUID LINEDRIER .................... 083S .................... 3/8 ODF ............ EK 083S ........................................... SAME ................. LIQUID LINEDRIER .................... 084S .................... 1/2 ODF ............ EK 084S ........................................... SAME ................. LIQUID LINEDRIER .................... 1625S .................. 5/16 ODF .......... EK 1625S ......................................... SAME ................. LIQUID LINEDRIER .................... 162S .................... 1/4 ODF ............ EK 162S ........................................... SAME ................. LIQUID LINEDRIER .................... 163S .................... 3/8 ODF ............ EK 163S ........................................... SAME ................. LIQUID LINEDRIER .................... 164S .................... 1/2 ODF ............ EK 164S ........................................... SAME ................. LIQUID LINEDRIER .................... 165S .................... 5/8 ODF ............ EK 165S ........................................... SAME ................. LIQUID LINEDRIER .................... 303S .................... 3/8 ODF ............ EK 303S ........................................... SAME ................. LIQUID LINEDRIER .................... 304S .................... 1/2 ODF ............ EK 304S ........................................... SAME ................. LIQUID LINEDRIER .................... 305S .................... 5/8 ODF ............ EK 305S ........................................... SAME ................. LIQUID LINEDRIER .................... 307S .................... 7/8 ODF ............ EK 307S ........................................... SAME ................. LIQUID LINEDRIER .................... 414S .................... 1/2 ODF ............ EK 414S ........................................... SAME ................. LIQUID LINEDRIER .................... 415S .................... 5/8 ODF ............ EK 415S ........................................... SAME ................. LIQUID LINEDRIER .................... 417S .................... 7/8 ODF ............ EK 417S ........................................... SAME ................. LIQUID LINEDRIER .................... 757S .................... 7/8 ODF ............ EK 757S ........................................... SAME ................. LIQUID LINEDRIER .................... 759S .................... 11/8 ODF .......... EK 759S ........................................... SAME ................. LIQUID LINEDRIER .................... BF082S ............... 1/4 ODF ............ BFK 082S ......................................... SAME ................. BI FLOWDRIER .................... BF083 .................. 3/8 SAE ............ BFK 083 ........................................... SAME ................. BI FLOWDRIER .................... BF083S ............... 3/8 ODF ............ BFK 083S ......................................... SAME ................. BI FLOWDRIER .................... BF084 .................. 1/2 SAE ............ BFK 084 ........................................... SAME ................. BI FLOWDRIER .................... BF084S ............... 1/2 ODF ............ BFK 084S ......................................... SAME ................. BI FLOWDRIER .................... BF163 .................. 3/8 SAE ............ BFK 163 ........................................... SAME ................. BI FLOWDRIER .................... BF163S ............... 3/8 ODF ............ BFK 163S ......................................... SAME ................. BI FLOWDRIER .................... BF164 .................. 1/2 SAE ............ BFK 164 ........................................... SAME ................. BI FLOWDRIER .................... BF164S ............... 1/2 ODF ............ BFK 164S ......................................... SAME ................. BI FLOWDRIER .................... BF165S ............... 5/8 ODF ............ BFK 165S ......................................... SAME ................. BI FLOWTXV ....................... C 1 F* ............... 1 TON R12 ..... HF 1 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C 1 R* ................. 1 TON R502 ..... HF 1 R* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C 1/2 F* ............... 1/2 TON R12 .... HF 1/2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C 1/2 R* ............... 1/2 TON R502 ... HF 1/2 R* ......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C 11/2 V* ............. 11/2 TON R22 ... HF 11/2 H* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C 2 F* ................ 2 TON R12 ..... HF 2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C 2 R* ................. 2 TON R502 ..... HF 2 R* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPV ............................ C 3 F* ................ 3 TON R12 ..... HF 31/2 F* ........................................ 31/2 TON R12 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C 3 V* ................. 3 TON R22 ....... HF 3 H* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C 3/4 V* ............... 3/4 TON R22 .... HF 1 H* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C 4 R* ................. 4 TON R502 ..... BAES 4 S* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C 5 V* ................. 5 TON R22 ....... HF 51/2 H* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C A F* ............... 1 TON R12 ..... HF 1 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C A R* ................. 1 TON R502 ..... HF 1 R* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C A V* ................. 11/2 TON R22 ... HF 11/2 H* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C AA F * .............. 1/2 TON R12 .... HF 1/2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C AA R* .............. 1/2 TON R502 ... HF 1/2 R* ......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C AA V* .............. 3/4 TON R22 .... HF 1 H* ............................................ 1 TON R22 .......... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C B F* ................ 2 TON R12 ..... HF 2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C B R* ................. 2 TON R502 ..... HF 2 R* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C B V* ................. 3 TON R22 ....... HF 3 H* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C C F* ................ 3 TON R12 ..... HF 31/2 F* ........................................ 31/2 TON R12 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C C R* ................. 4 TON R502 ..... BAES 4 S* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... C C V* ................. 5 TON R22 ....... HF 51/2 H* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 1 F* ............... 1 TON R12 ..... HFE 1 F* ......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 1 R* ............... 1 TON R502 ..... HFE 1 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 1/2 F* ............. 1/2 TON R12 .... HFE 1/2 F* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 1/2 R* ............. 1/2 TON R502 ... HFE 1/2 R* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 11/2 V* ........... 11/2 TON R22 ... HFE 11/2 H* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 2 F* ................ 2 TON R12 ...... HFE 2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 2 R* ............... 2 TON R502 ..... HFE 2 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 3 F* ................ 3 TON R12 ...... HFE 31/2 F* ...................................... 312 TON R12 ...... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 3 V* ............... 3 TON R22 ....... HFE 3 H* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 3/4 V* ............. 3/4 TON R22 .... HFE 1 H* .......................................... 1 TON R22 .......... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 4 R* ............... 4 TON R502 ..... BAES 4 S* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE 5 V* ............... 5 TON R22 ....... HFE 51/2 H* ..................................... 51/2 TON R22 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE A F* .............. 1 TON R12 ..... HFE 1 F* ......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE A R* ............... 1 TON R502 ..... HFE 1 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE A V* ............... 11/2 TON R22 ... HFE 11/2 H* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOP

Cross Reference - Upgrade to Alco

147RSP-PRC022-EN

Product Type Parker No. Parker Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ....................... CE AA F* ............. 1/2 TON R12 .... HFE 1/2 F* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE AA R* ............ 1/2 TON R502 ... HFE 1/2 R* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE AA V* ............ 3/4 TON R22 .... HFE 1 H* .......................................... 1 TON R22 .......... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE B F* ............... 2 TON R12 ...... HFE 2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE B R* ............... 2 TON R502 ..... HFE 2 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE B V* ............... 3 TON R22 ....... HFE 3 H* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE C F* ............... 3 TON R12 ..... HFE 31/2 F* ...................................... 31/2 TON R12 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE C R* ............... 4 TON R502 ..... BAES 4 S* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... CE C V* ............... 5 TON R22 ....... HFE 51/2 H* ..................................... 51/2 TON R22 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 1 F* .................. 1 TON R12 ....... HF 1 F* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 1 R* ................. 1 TON R502 ..... HF 1 R* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 1 V* ................. 1 TON R22 ....... HF 1 H* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 1/2 F* ............... 1/2 TON R12 .... HF 1/2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 1/2 R* .............. 1/2 TON R502 ... HF 1/2 R* ......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 1/2 V* .............. 1/2 TON R22 .... HF 1/2 H* ......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 1/4 F* ............... 1/4 TON R12 .... HFE 1/4 F* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 1/4 R* .............. 1/4 TON R502 ... HF 1/4 R* ......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 11/2 F* ............. 11/2 TON R12 ... HF 11/2 F* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 11/2 R* ............. 11/2 TON R502 . HF 11/2 R* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 11/2 V* ............. 11/2 TON R22 ... HF 11/2 H* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 2 F* .................. 2 TON R12 ....... HF 2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 2 R* ................. 2 TON R502 ..... HF 2 R* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 21/2 V .............. 21/2 TON R22 ... HF 21/2 H* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 3 F* .................. 3 TON R12 ....... HF 31/2 F* ........................................ 31/2 TON R12 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 3 R* ................. 3 TON R502 ..... HF 31/2 R* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 3 V* ................. 3 TON R22 ....... HF 3 H* ............................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 4 R* ................. 4 TON R502 ..... BAES 4 S* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 4 V* ................. 4 TON R22 ....... TCL 3 H* .......................................... 3 TON R22 .......... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... D 5 V* ................. 5 TON R22 ....... HF 51/2 H* ....................................... 51/2 TON R22 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 1 F* ................ 1 TON R12 ....... HFE 1 F* ......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 1 R* ............... 1 TON R502 ..... HFE 1 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 1 V ................. 1 TON R22 ....... HFE 1 H* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 1/2 F* ............. 1/2 TON R12 .... HFE 1/2 R12 ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 1/2 R* ............ 1/2 TON R502 ... HFE 1/2 R* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 11/2 F* ........... 11/2 TON R12 ... HFE 11/2 F* ...................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 11/2 R* ........... 11/2 TON R502 . HFE 11/2 R* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 11/2 V* ........... 11/2 TON R22 ... HFE 11/2 H* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 2 F* ................ 2 TON R12 ....... HFE 2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 2 R* ............... 2 TON R502 ..... HFE 2 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 21/2 V* ........... 21/2 TON R22 ... HFE 21/2 H* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 3 F* ................ 3 TON R12 ....... HFE 31/2 F* ...................................... 31/2 TON R12 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 3 R* ............... 3 TON R502 ..... HFE 3 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 3 V* ............... 3 TON R22 ....... HFE 3 H* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 4 R* ............... 4 TON R502 ..... BAES 4 S* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 4 V* ............... 4 TON R22 ....... TCLE 3 H* ........................................ 3 TON R22 .......... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... DE 5 V* ............... 5 TON R22 ....... HFE 51/2 H* ..................................... 51/2 TON R22 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC 1 F* ................ 1 TON R12 ....... HFS 1 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC 1 R* ............... 1 TON R502 ..... HFS 1 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC 1/2 F* ............. 1/2 TON R12 .... HF 1/2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC 1/2 R* ............. 1/2 TON R502 ... HFS 1/2 R* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC 11/2 V* ........... 11/2 TON R22 ... HFS 11/2 R22 ................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC 2 F* ................ 2 TON R12 ....... HFS 2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC 3 F* ................ 3 TON R12 ....... HFS 3 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC 3 V* ............... 3 TON R22 ....... HFS 3 H* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC 3/4 V* ............. 3/4 TON R22 .... HFS 1 H* .......................................... 1 TON R22 .......... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC 4 R* ............... 4 TON R502 ..... BAES 4 S* ....................................... EXTERNAL ......... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC 5 V* ............... 5 TON R22 ....... HFS 51/2 H* ..................................... 51/2 TON R22 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC A F* ............... 1 TON R12 ....... HFS 1 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC A R* ............... 1 TON R502 ..... HFS 1 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC A V* ............... 11/2 TON R22 ... HFS 11/2 R22 ................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC AA F* ............. 1/2 TON R12 .... HFS 1/2 F* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC AA R* ............ 1/2 TON R502 ... HFS 1/2 R* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC AA V* ............ 3/4 TON R22 .... HFS 1 H* .......................................... 1 TON R22 .......... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC B F* ............... 2 TON R12 ....... HFS 2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC B R* ............... 2 TON R502 ..... HFS 2 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC B V* ............... 3 TON R22 ....... HFS 3 H* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC C F* ............... 3 TON R12 ....... HFS 3 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC C R* ............... 4 TON R502 ..... BAES 4 S* ....................................... EXTERNAL ......... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EC C V* ............... 5 TON R22 ....... HFS 51/2 H* ..................................... 51/2 TON R22 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE 1 F* .............. 1 TON R12 ....... HFES 1 F* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE 1 R* ............. 1 TON R502 ..... HFES 1 R* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOP

Cross Reference - Upgrade to Alco

RSP-PRC022-EN148

Product Type Parker No. Parker Descrip. Alco No. Alco Descrip. Comment - ALCOTXV ....................... ECE 1/2 F* ........... 1/2 TON R12 .... HFES 1/2 F* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE 1/2 R* ........... 1/2 TON R502 ... HFES 1/2 R* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE 11/2 V* ......... 11/2 TON R22 ... HFES 11/2 H* ................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE 2 F* .............. 2 TON R12 ....... HFES 2 F* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE 2 R* ............. 2 TON R502 ..... HFES 2 R* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE 3 F* .............. 3 TON R12 ....... HFES 31/2 F* ................................... 31/2 TON R12 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE 3 H* ............. 3 TON R22 ....... HFES 3 H* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE 3/4 V* ........... 3/4 TON R22 .... HFES 1 H* ....................................... 1 TON R22 .......... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE 4 R* ............. 4 TON R502 ..... BAES 4 S* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE 5 V* ............. 5 TON R22 ....... HFES 51/2 H* ................................... 51/2 TON R22 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE A F* ............. 1 TON R12 ....... HFES 1 F* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE A R* ............. 1 TON R502 ..... HFES 1 R* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE A V* ............. 11/2 TON R22 ... HFES 11/2 H* ................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE AA F* ........... 1/2 TON R12 .... HFES 1/2 F* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE AA R* .......... 1/2 TON R502 ... HFES 1/2 R* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE AA V* .......... 3/4 TON R22 .... HFES 1 H* ....................................... 1 TON R22 .......... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE B F* ............. 2 TON R12 ....... HFES 2 F* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE B R* ............. 2 TON R502 ..... HFES 2 R* ........................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE B V* ............. 3 TON R22 ....... HFES 3 H* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE C F* ............. 3 TON R12 ....... HFES 31/2 F* ................................... 31/2 TON R12 ..... *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... ECE C R* ............. 4 TON R502 ..... BAES 4 S* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 1 F* ............... 1 TON R12 ....... HFS 1 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 1 H* ............... 1 TON R22 ....... HFS 1 H* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 1 R* ............... 1 TON R502 ..... HFS 1 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 1/2 F* ............. 1/2 TON R12 .... HFS 1/2 F* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 1/2 R* ............ 1/2 TON R502 ... HFS 1/2 R* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 1/2 V* ............ 1/2 TON R22 .... HFS 1/2 H* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 1/4 F* ............. 1/4 TON R12 .... HFS 1/4 F* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 1/4 R* ............ 1/4 TON R502 ... HFS 1/4 R* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 1/4 V* ............ 1/4 TON R22 .... HFS 1/4 H* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 1/8 F* ............. 1/8 TON R12 .... HFS 1/8 F* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 1/8 R* ............ 1/8 TON R502 ... HFS 1/8 R* ....................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 11/2 ............... 11/2 TON R22 ... HFS 11/2 H* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 11/2 F* ........... 11/2 TON R12 ... HFS 11/2 F* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 11/2 R* .......... 11/2 TON R502 . HFS 11/2 R* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 2 F* ............... 2 TON R12 ....... HFS 2 F* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 2 R* ............... 2 TON R502 ..... HFS 2 R* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 2 V* ............... 2 TON R22 ....... HFS 2 H* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 21/2 V* .......... 21/2 TON R22 ... HFS 21/2 H* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EG 3 V* ............... 3 TON R22 ....... HFS 3 H* .......................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 1 F* ............. 1 TON R12 ....... HFESC 1 F* ...................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 1 R* ............. 1 TON R502 ..... HFESC 1 R* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 1 V* ............. 1 TON R22 ....... HFESC 1 H* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 1/2 F* ........... 1/2 TON R12 .... HFESC 1/2 F* ................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 1/2 R* .......... 1/2 TON R502 ... HFESC 1/2 R* ................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 1/2 V* .......... 1/2 TON R22 .... HFESC 1/2 H* .................................. SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 1/4 F* ........... 1/4 TON R12 .... HFESC 1/4 F* ................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 1/4 R* .......... 1/4 TON R502 ... HFESC 1/4 R* ................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 1/4 V* .......... 1/4 TON R22 .... HFESC 1/4 H* .................................. SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 1/8 F* ........... 1/8 TON R12 .... HFESC 1/8 F* ................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 1/8 R* .......... 1/8 TON R502 ... HFESC 1/8 R* ................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 11/2 F* ......... 11/2 TON R12 ... HFESC 11/2 F* ................................. SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 11/2 R* ........ 11/2 TON R502 . HFESC 11/2 R* ................................. SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 11/2 V* ........ 11/2 TON R22 ... HFESC 11/2 H* ................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 2 F* ............. 2 TON R12 ....... HFESC 2 F* ...................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 2 R* ............. 2 TON R502 ..... HFESC 2 R* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 2 V* ............. 2 TON R22 ....... HFESC 2 H* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 21/2 V* ........ 21/2 TON R22 ... HFESC 21/2 H* ................................ SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOPTXV ....................... EGE 3 V* ............. 3 TON R22 ....... HFESC 3 H* ..................................... SAME ................. *REPLACE PARKER Z,W,X WITH ALCO C, Z, MOP

Cross Reference - Upgrade to Alco

149RSP-PRC022-EN

AC& R to AlcoProduct Type AC&R No. AC& R Descrip. Alco No. Alco Descrip. Comment - ALCOOIL SEPARATOR ... S-5182 ......... HELICAL ...................... A-W55824 ........................................ CONVENTIONAL .............. SEALED UNIT 4 X 1/2 ODOIL SEPARATOR ... S-5185 ......... HELICAL ...................... A-W55855 ........................................ CONVENTIONAL .............. SEALED UNIT 4 X 5/8 ODOIL SEPARATOR ... S-5187 ......... HELICAL ...................... A-W55877 ........................................ CONVENTIONAL .............. SEALED UNIT 4 X 7/8 ODOIL SEPARATOR ... S-5188 ......... HELICAL ...................... A-W55889 ........................................ CONVENTIONAL .............. SEALED UNIT 4 X 1 1/8 ODOIL SEPARATOR ... S-5190 ......... HELICAL ...................... A-W569011 ...................................... CONVENTIONAL .............. SEALED UNIT 6 X 1 3/8 ODOIL SEPARATOR ... S-5192 ......... HELICAL ...................... A-W569213 ...................................... CONVENTIONAL .............. SEALED UNIT 6 X 1 5/8 ODOIL SEPARATOR ... S-5292 ......... HELICAL ...................... A-F579213 ........................................ CONVENTIONAL .............. FLANGED UNIT 6 X 1 7/8 ODOIL SEPARATOR ... S-5294 ......... HELICAL ...................... A-F579417 ........................................ CONVENTIONAL .............. FLANGED UNIT 6 X 2 1/8 ODOIL SEPARATOR ... S-5582 ......... CONVENTIONAL ......... A-W55824 ........................................ CONVENTIONAL .............. SEALED UNIT 4 X 1/2 ODOIL SEPARATOR ... S-5585 ......... CONVENTIONAL ......... A-W55855 ........................................ CONVENTIONAL .............. SEALED UNIT 4 X 5/8 ODOIL SEPARATOR ... S-5587 ......... CONVENTIONAL ......... A-W55877 ........................................ CONVENTIONAL .............. SEALED UNIT 4 X 7/8 ODOIL SEPARATOR ... S-5588 ......... CONVENTIONAL ......... A-W55889 ........................................ CONVENTIONAL .............. SEALED UNIT 4 X 1 1/8 ODOIL SEPARATOR ... S-5590 ......... CONVENTIONAL ......... A-W559011 ...................................... CONVENTIONAL .............. SEALED UNIT 4 X 1 3/8 ODOIL SEPARATOR ... S-5690 ......... CONVENTIONAL ......... A-W569011 ...................................... CONVENTIONAL .............. SEALED UNIT 6 X 1 3/8 ODOIL SEPARATOR ... S-5692 ......... CONVENTIONAL ......... A-W569213 ...................................... CONVENTIONAL .............. SEALED UNIT 6 X 1 5/8 ODOIL SEPARATOR ... S-5792 ......... CONVENTIONAL ......... A-F579213 ........................................ CONVENTIONAL .............. FLANGED UNIT 6 X 1 5/8 ODOIL SEPARATOR ... S-5794 ......... CONVENTIONAL ......... A-F579417 ........................................ CONVENTIONAL .............. FLANGED UNIT 6 X 2 1/8 ODOIL SEPARATOR ... S-5882 ......... CONVENTIONAL ......... A-F58824 .......................................... CONVENTIONAL .............. FLANGED UNIT 4 X 1/2 ODOIL SEPARATOR ... S-5885 ......... CONVENTIONAL ......... A-F58855 .......................................... CONVENTIONAL .............. FLANGED UNIT 4 X 5/8 ODOIL SEPARATOR ... S-5887 ......... CONVENTIONAL ......... A-F58877 .......................................... CONVENTIONAL .............. FLANGED UNIT 4 X 7/8 ODOIL SEPARATOR ... S-5888 ......... CONVENTIONAL ......... A-F5889 ............................................ CONVENTIONAL .............. FLANGED UNIT 4 X 1 1/8 ODOIL SEPARATOR ... S-5890 ......... CONVENTIONAL ......... A-F589011 ........................................ CONVENTIONAL .............. FLANGED UNIT 4 X 1 3/8 ODOIL SEPARATOR ... S-9108 ......... 4 GALLON ................... A0R4 ................................................ CONVENTIONAL .............. 3 SIGHT GLASSESOIL SEPARATOR ... S-9109 ......... 2 GALLON ................... A0R2 ................................................ CONVENTIONAL .............. 2 SIGHT GLASSES

Cross Reference - Upgrade to Alco

Trane has a policy of continuous product and product data improvement and reserves the right to change designand specifications without notice.

Literature Order Number

Filing Hierarchy

Date

Supersedes

Stocking Location

RSP-PRC022-EN

Service Products/Refrigeration Components

April 2003

RSP-D-101 0597

Inland