Microprocessor Transmitter/Controller for conductivity Type 262520 B 20.2520 Operating Instructions 6.96 / 00339807

Upload: others

Post on 24-May-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Transmitter/Controller for conductivity Type 262520

MicroprocessorTransmitter/Controller

for conductivityType 262520

B 20.2520Operating Instructions

6.96 / 00339807

Page 2: Transmitter/Controller for conductivity Type 262520

CONTENTS

Page

1 DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.2 Type designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.3 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.4 Displays/controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.5 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.6 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.7 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2.1 Location and climatic conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2.2 Fitting in position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2.3 Installation in the surface-mounting housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3 ELECTRICAL CONNECTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

4 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

4.1 Matrix/level scheme. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

4.2 Value and function input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

4.3 Manual operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

4.4 Temperature compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

4.5 Matrix summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

5 SWITCHING THE RANGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

6 CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

6.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

6.2 Numerical input of cell constant and temperature coefficient . . . . . . . . . . . . . . . . . . 20

6.3 Calibrating the cell constant using a calibration solution . . . . . . . . . . . . . . . . . . . . . . 20

6.4 Experimental determination of the temperature coefficient . . . . . . . . . . . . . . . . . . . . 21

6.5 Accepting old calibration data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

7 ANALOGUE OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

7.1 Process value output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Page 3: Transmitter/Controller for conductivity Type 262520

Page

8 CONTROLLER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

8.1 Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

8.2 Possible combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

8.3 Controller switched off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

8.4 Limit controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

8.5 Pulse duration controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

8.6 Pulse frequency controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

8.7 Modulating controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

8.8 Alarm contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

8.9 Notes on possible incorrect controller settings and their correction . . . . . . . . . . . 29

9 FAULTS, WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

9.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

9.2 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

9.3 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

10 ADJUSTMENTS INSIDE THE INSTRUMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

10.1Analogue output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

10.2Manual operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

10.3Input filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

10.4Code setting on the conductivity input card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

11 EXTRA FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

11.1Function of the logic inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

11.2HOLD function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

11.3Input filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

11.4Reading-in the factory setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

11.5Probe break monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

12 APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

12.1Table for parameter and configuration settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Page 4: Transmitter/Controller for conductivity Type 262520

Important installation notes:

The choice of cable and the connection ofthe supply line must conform to the require-ments of VDE 0100 "Regulations on the In-stallation of Power Circuits with nominalvoltages below 1000 V" or the appropriatelocal regulations. Both the electrical connection and any workinside the unit must only be carried out to theextent described and exclusively by properlyqualified personnel.The instrument has to be isolated from thesupply before carrying out any maintenanceor service operations.A current limiting resistor interrupts the sup-ply circuit in case of a short-circuit. The ex-ternal fuse of the supply should not be ratedabove 1 A (slow). The load circuit must befused for the maximum relay current1) in or-der to prevent welding of the output relaycontacts in case of an external short-circuit.In the neighbourhood of the unit there mustbe no magnetic or electrical fields, e.g.through transformers, portable telephonesor electrostatic discharges.Inductive loads (relays, solenoid valves etc.),if installed close to the instrument, must befitted with RC modules to prevent interfer-ence.When the network is subject to severe inter-ference (e.g. thyristor controls) the instru-ment should be supplied through anisolating transformer since supply fluctua-tions are only permitted within the specifiedvoltage range1).During maintenance or service operationson the instrument (sensors, controllers, re-corders etc.) it is essential to prevent any un-desired processes (e.g. due to the switchingof relay contacts).Input, output and supply lines should be runseparately and not parallel to each other.Sensor and interface lines should be ar-ranged as twisted and screened cables. Donot run them close to current-carrying com-ponents or cables. Ground the screen at oneend at the instrument on terminal TE.

Ground the instrument at terminal PE to the earth conductor. This line must have at least

the same cross-section as the supply lines.Ground lines should be run in a star-shapedlay-out to a common earth point which isconnected to the earth conductor of thesupply. Do not loop the ground connections,i.e. do not run them from one instrument toanother.Do not connect any additional loads to thesupply terminals of the instrument.The instrument is not suitable for installationin hazardous areas.Apart from faulty installation, there is a pos-sibility of interference or damage to control-led processes due to incorrect settings onthe controller (setpoint, data of parameterand configuration levels, internal adjust-ments). Safety devices independent of thecontroller should always be provided andshould be capable of adjustment only byspecialist personnel. Please refer to the ap-propriate safety regulations in this connec-tion.

1) see Technical data

Page 5: Transmitter/Controller for conductivity Type 262520

1

1 DESCRIPTION

NOTE:

All necessary adjustments are described inthese Operating Instructions. If, however,any difficulties should arise during start-up,you are asked not carry out any manipula-tions on the instrument which are not per-mitted. You could endanger your rightsunder the instrument warranty. Please con-tact the supplier.

1.1 Introduction

Microprocessor transmitters/controllers Se-ries 262520 are used in conjunction withsuitable sensors for continuous conductivitymeasurement in liquids.The microprocessor transmitter/controllerhas a 4-digit display for measurements andsettings and a 2-digit display for indicatingthe matrix position as guidance for the user.The transmitter has a current or voltage out-put proportional to the measured value.The unit can be provided with a second cur-rent or voltage output to reproduce the liquidtemperature.The version 262520 can be equipped withtwo relay contacts adjustable over themeasuring range. They can be arranged aschangeover contacts with pull-in or drop-outdelay, or as control contacts with pulse-du-ration or pulse-frequency action.A monitoring circuit switches the alarm relay(third relay) with a pulse or steady contact atthe end of an adjustable time delay. There isalso a visual indication through a flashingalarm LED.The parameters cell constant and tempera-ture coefficient can be adjusted by a pro-gram procedure on the conductivitymicroprocessor transmitter/controller. Con-trol parameters can be input. The solutiontemperature can be either pre-set or option-ally determined by automatic product tem-perature compensation using a Pt 100resistance thermometer.The conductivity transmitter can be re-con-figured for different ranges using internallinks and by a change at the configurationlevel.

The microprocessor transmitter/controllercan be used to operate valves, interlocks,blocking systems, pumps, motors or signal

ling units. Other applications must beagreed with the manufacturer and confirmedin writing.

1.2 Type designation

The following selections describe the stand-ard versions. Each selection is provided witha code number which is entered in the ap-propriate field of the type designation. If acontroller with customized configuration isrequired, additional ordering details in plainlanguage have to be given.

Conductivity microprocessor transmitter/controller

Conductivity ................................... 262520

No control contacts ................................ 00

with 2 control contacts and alarm- contact, controller type and structure can be configured .................................. 60

Pt 100 input for temperature measurement in 3-wire circuit provided as standard

Basic type conductivity .......................... 00

Conductivity difference input ................ 70*

Third input current/voltage .................... 80*

* version under development

(1) (2) (3) (4) (5) (6) (7)

262520 / .. - .. - ... - .. - .. / ...

(1) Basic type

(2) Controller function ..

(3) Inputs ..

Page 6: Transmitter/Controller for conductivity Type 262520

2

DESCRIPTION

Conductivity output provided as standard

on controller type 00 ............................ 000

Second output (temperature) ............... 060

Relay contacts ...................................... 100

Relay contacts and second output (temperature) ........................................ 160

93 - 263 v AC, 48 - 63 Hz ....................... 01

20 - 43 V AC, 48 - 63 Hz and

20 - 53 V DC ........................................... 10

none ....................................................... 00

RS232C ................................................. 51*

RS422/485 ............................................ 52*

none ..................................................... 000

Surface-mounting housing ................... 110

Stock versions:

262520/00-00-000-01-00/000262520/60-00-100-01-00/000

*version under development!

(4) Outputs ...

(5) Supply ..

(6) Interface (isolated) ..

(7) Extra Codes ...

Ordering example

Conductivity microprozessor transmitter/controller

(1) conductivity microprocessor tranmitter/controller

(2) Alarm contact, controller type and structure can be configured

(3) Basic type conductivity

(4) Relay contacts

(5) 93 - 263 V AC, 48 - 63 Hz

(6) none

(7) none

1.3 Accessories

1.3.1 Standard

2 mounting brackets1 operating Instruction

1.3.2 Recommended

Conductivity simulator Type 2H-SLf-1(Data Sheet 26.2712)for testing and calibrat-ing the conductivity transmitter

(1) (2) (3) (4) (5) (6) (7)

262520 / 60 - 00 - 100 - 01 - 00 / 000

Page 7: Transmitter/Controller for conductivity Type 262520

3

DESCRIPTION

1.4 Displays/controls

(1) 4-digit LED display to indicate measure-ment and settings

(2) Step key for selecting the digit to be al-tered, and switching manual mode off/on

(3) Up key to alter the selected digit; in man-ual mode activates relay contact 1

(4) Down key to alter the selected digit; in manual mode activates relay contact 2

(5) ENTER key to enter the input value

(6) 2-digit LED display to indicate the matrix position (operator display)

(7) V key for vertical movement to select the horizontal line in the matrix field

(8) H key for horizontal movement to select the vertical column in the matrix field

(9) Brief matrix for indication and operating

level

(10)LED line to indicate operating status and unit of display (

µ

S/cm, mS/cm,

°

C)

1.5 Technical data

1.5.1 Microprocessor transmitter/controller for conductivity

Input

conductivity cell with two electrodes and cell constants C of 0.01 to 10. (see Data Sheets 20.2900 and 20.2921)

Measurement frequency and ranges

see Table page 12

Measuring voltage

approx. 500 mV AC

Accuracy of indication

conductivity:

±

1 digittemperature: 0.1

°

C

Measurement spans

freely adjustable within the selected rangeReference temperature 25

°

C

Reference temperature

25

°

C

Liquid temperature compensation

manually from -50 to +250

°

C or automatical-ly within the range -50 to +250

°

C usingPt 100 resistance thermometer in 2-wire or3-wire circuit

Lead compensation Pt 100

not required with 3-wire circuit. When usinga resistance thermometer in 2-wire circuit itis necessary to provide lead compensationusing an external compensating resistance.

Relay output with floating contact

rating:690 W 3 A at 230 V AC 50 Hz, p.f. = 1 contact life:approx. 10

6

operations at rated load

Page 8: Transmitter/Controller for conductivity Type 262520

4

DESCRIPTION

Range table

Range Cell constant C(1/cm)

Meas. frequency coded

0.01 0.1 1.0 3.0 10.0 Hz

to 0.50

µ

S/cm x 85

to 1.00

µ

S/cm x 85

to 2.00

µ

S/cm x 85

to 3.00

µ

S/cm x 85

to 5.00

µ

S/cm x x 85

to 10.0

µ

S/cm x x 85

to 20.0

µ

S/cm x 85

to 50.0

µ

S/cm x x 85

to 100

µ

S/cm x 85

to 100

µ

S/cm x 1000

to 300

µ

S/cm x x 1000

to 500

µ

S/cm x x 1000

to 1000

µ

S/cm x x x 1000

to 2000

µ

S/cm x 1000

to 1.00 mS/cm x x x 1000

to 2.00 mS/cm x 1000

to 3.00 mS/cm x x 1000

to 5.00 mS/cm x x 4000

to 10.0 mS/cm x x 4000

to 20.0 mS/cm x x 4000

to 30.0 mS/cm x x x 4000

to 50.0 mS/cm x 4000

to 100 mS/cm x x 4000

to 200 mS/cm x 4000

Page 9: Transmitter/Controller for conductivity Type 262520

5

DESCRIPTION

Analogue outputConductivity and temperature(proportional to measured value and iso-lated)

Max deviation of output signal from charac-teristic: 0.25%* factory setting

1.5.2 General controller dataDeviation from characteristic

when connected to conductivity cell:1% max.

when used with resistance thermometer: 0.20% max.

Ambient temperature error

when connected to conductivity cell:0.25% max. per 10

°

C

when used with resistance thermometer: 0.05% max. per 10

°

C

Signal circuit monitoring with ATC

break or short-circuit of the temperature probe is recognised and reported.

Data back-up

EEPROM

CE mark

EN 50081 Part 1EN 50082 Part 2

Interference immunity/compatibility

NE 21 (5/93)

Supply

93 - 263 V AC 48 - 63 Hz or20 - 43 V AC 48 - 63 Hz or20 - 53 V DC

Power consumption

selected burden

0 - 20 mA* 500

Ω

max.

4 - 20 mA 500

Ω

max.

0 - 10 V 500

Ω

min.

8 VA approx.

Electrical connection

faston tags to DIN 46 244/A, 4.8 x 0.8 mm

Permitted ambient temperature

0 to +50

°

C

Transmitter/controller in surface-mounting housing-5 to +50

°

C

Permitted storage temperature

-40 to +70

°

C

Climatic conditions

Class KWF to DIN 40 040,rel. humidity not exceeding 75% annual mean, no condensation

Housing

aluminium extrusions, black anodisedwith plug-in controller chassis (connected to protective earth)

Protection

to EN 60 529front IP 54rear IP 20(not suitable for hazardous areas)

Operating position

unrestricted

Page 10: Transmitter/Controller for conductivity Type 262520

6

DESCRIPTION

1.6 Block diagram

Externalcontact

Conduc-tivity

1.7 Operation

The signals of the two inputs pass through the range cards (1) and (2), an analogue multi-plexer (3) and an amplifier (6) to the analogue/digital converter (11). The measurements, to-gether with the key inputs (10), are processed in the computer core which consists of CPU(13), EPROM (7), RAM (4) and EEPROM (5).The EEPROM stores the operating, parameter and configuration data. The DIL switch (8)can be used for various settings. An additional function is activated through the externalcontact (18). The output signals pass through the ports (14) to (16) to the output stages (20),(22), (23) and (24) and to the display (9). Each of these output stages can be equipped in-dependently.A watchdog circuit (12) resets the CPU (13) to a defined initial status in case of faults in theprogram sequence. On power-up the reset circuit (19) activates the program start.The power supply (21) provides the supplies for the individual modules.

Page 11: Transmitter/Controller for conductivity Type 262520

7

2 INSTALLATION

2.1 Location and climatic conditions

The location should be as free as possiblefrom shock and vibration. Electro-magneticfields, e.g. caused by motors, transformersetc., should be avoided. The ambient tem-perature at the location must not be outside0 to +50

°

C, the relative humidity not exceed75%. Corrosive air and fumes reduce the lifeof the instrument.

2.2 Fitting in position

The unit is inserted from the front into thepanel cut-out. The mounting brackets arehooked from the back of the panel into therecesses at the sides of the housing. The flatsides of the brackets must be against thehousing. Place the mounting bracketsagainst the back of the panel and tightenthem evenly using a screwdriver.

(1) panel (2) screwdriver (3) mounting bracket

mm inch

0.8 0.031

4.5 0.18

4.8 0.19

7 0.28

7.5 0.30

21 0.83

92

+0.5

3.62

+0.02

100 3.94

120 4.72

138 5.43

150 5.91

270 10.63

Page 12: Transmitter/Controller for conductivity Type 262520

8

INSTALLATION

The folllowing important installation notes must be observed:

– Fuses for the fitted transmitter and for the relay contacts must be provided by the in-staller.

– Separate fuses must be provided for the transmitter and for the relay contracts.

– Do not connect any control circuit (relay, contactor) to the supply terminals.

– The wiring must be connected directly to the transmitter.

– External environmental conditions must not cause the permitted ambient condi-tions inside the transmitter surface-mounting housing to be exceeded.

– The ambient temperature must not be outside the permitted range of -5 to +50

°

C.

2.3 Installation in the surface-mounting housing

Code /110

Cable glandFixing holes (knock-outs)

Conductivity mi-croprocessor

Techn. data:Protection: IP65Material: ABS

Rear cover, hinged

Front cover hinged, clear

Page 13: Transmitter/Controller for conductivity Type 262520

9

3 ELECTRICAL CONNECTION

Connection for

Terminals

Relay K1* 41 (O) n.c. (break)42 (P) common43 (S) n.o. (make)

K2 51 (O) n.c. (break)52 (P) common53 (S) n.o. (make)

K4* 95 (O) n.c. (break)96 (P) common

Measurementoutput

(isolated)

Conductivity 45 -46 +

Temperature 91 + 92 -

Supply as on label

AC/DC L1 line AC L+N neutral L-PE protective earthTE screen

positive DCnegative

* contact protection circuit 22 nF/56 Ω between common and make contact or common and

break contact

Page 14: Transmitter/Controller for conductivity Type 262520

10

ELECTRICAL CONNECTION

Input TerminalsConductivitycell

111112

Resistancethermometerin 3-wirecircuit

211212213

Resistancethermometerin 2-wirecircuit

211212213

Rcomp = lead resistance

Logic input 1 8182

82 and 84 are linked internally

Logic input 2 8384

* contact protection circuit 22 nF/56 Ω between common and make contact or common and break contact

Conductivity cell withTransmitter

connector attached cable

Outer electrode white 112

Inner electrode 2 brown 111

Temperaturecompensation

1+3

yellow+

green

211 + 212extra link212 + 213

Page 15: Transmitter/Controller for conductivity Type 262520

11

4 OPERATION

4.1 Matrix/level schemeThe instrument is operated solely using six front keys. The individually adjustable pa-rameters (e.g. control parameters) and con-figuration data (e.g. range changeover) are stored in a matrix consisting of 10 x 10 = 100 fields. A matrix field can be reached with the keys V (vertical movement) and H (horizontal movement). The matrix is divided into four levels to ensure a clear presentation of the many different actions.The individual levels are inhibited by number passwords to prevent unauthorised altera-tion.

The number passwords are as follows:(input in matrix field V9H0)

to open the indicating level:no password required

to open the operating level:0110

to open the parameter level:0020

to open the configuration level:0300

A special password permits viewing all thematrix fields but no alteration of the datacontained in them. This password is:

0009

Input of a different number inhibits the oper-ating level. This status of the instrument cor-responds to the status after power-up.

Note:

4.2 Value and function inputThe functions of the matrix fields can be di-vided into six categories. In general, any notsuccessfully completed inputs and proce-dures are followed by retention of the previ-ous status after return to the measurementmode.

4.2.1 Indication of valuesIndication of values without any possibilityof altering them is available only at the indi-cation level, i.e. in the fields of the first ma-trix column, apart from matrix field V9H0.After inputting the password 0009 via matrixfield V9H0 it is possible to show the currentvalue of all other matrix fields on the display.Matrix field V7H0 (Indicate fault codes) is anexception; additional existing errors codescan be displayed using the keys and .

following any setting or servicing operations the levels should be inhibited again in order to prevent unintended alterations of the set-ting

Indication level e.g. conductivity, temperature

Operating levele.g. calibration, select setpoints

This level consists of 10 matrix fields (V0H0 - V9H0). Data can be indicated here but can not be altered. From the matrix field V9H0 the next level can be reached by input of the appropriate number password.

This level consists of the 20 matrix fields V0H0 - V9H1.

Parameter levele.g. Tv, Tn, Xp

Configuration levele.g. controller type

This level consists of 80 matrix fields (V0H0 - V9H7)

This level consists of the 100 matrix fields (V0H0 - V9H9).

Page 16: Transmitter/Controller for conductivity Type 262520

12

OPERATION

4.2.2 Input of a number passwordOn the matrix field V9H0 any number be-tween 0000 and 9999 can be input (negativenumbers can not be set).After selecting the matrix field (direct selec-tion via ENTER, see also 4.2.10) the number0000 appears on the display, with the unitsdigit flashing. It can be altered using thekeys and . The tens digit is selected withthe key ❮ and can again be altered using thekeys and . This procedure can be con-tinued up to the last digit. If a mistake ismade during the input you can return to theunits digit with the key ❮.Operating the ENTER key causes the instru-ment to accept the value which has been in-put. The display returns to 0000.If a wrong value has been input it is possibleto repeat the input procedure by pressingthe ENTER key again.The input of a number password is ex-plained in Section 4.2.7 example 1.

4.2.3 Input of valuesWhen inputting values other than numberpasswords it must be noted that the range ofvalues is limited and is generally set to par-ticular default values. This leads to certainspecial features for otherwise similar inputsequence:

a) After selecting the matrix field the display shows the default setting (factory settings or previous setting by the user).

b) Decimal point and negative sign can ap-pear on the display.

c) When attempting to input a value outside the value range of the parameter, press-ing the ENTER key is followed by the dis-play flashing the limit which the input has exceeded upwards or downwards. The input is taken as unsuccessfully complet-ed and can be restarted by pressing the ENTER key again.

d) When the input has be completed suc-cessfully (after pressing ENTER) the edit-ed value remains steady on the display without flashing.

Example 2 (Section 4.2.8) explains the inputof a value.

4.2.4 Selection from given alternativesSeveral matrix fields permit a selection fromgiven possibilities (software switch). Afterthe matrix field has been selected the dis-play flashes the symbol for the default alter-native (a figure or alphanumerical characterssuch as "no"). The keys and can beused to display all other possible settingswhich can be entered by pressing the EN-TER key. The symbol of the selected alterna-tive then appears steady on the displaywithout flashing. The matrix fields V9H2,V1H2 and V0H3 are exceptions; when se-lected, they display a flashing "no" whichchanges to a flashing "YES" on pressing the and key. On pressing the ENTER key inthe case of V9H2, the display flashes BUSYfor about 15 seconds and then changes to asteady "no" (see Example 3 in Section 4.9.2).During the BUSY phase it is not possible toleave this matrix field and the instrumentmust not be switched off. If the supply failsduring this phase the factory setting has tobe accepted initially. In the case of V0H3and V1H2 the BUSY does not appear, thedisplay immediately shows "no". In all casesthe entry of the required data is then com-pleted.

4.2.5 Activating a procedureThe matrix fields which come under thisheading are V0H1 "Calibration of cell con-stant" and V1H1 "Experimental evaluation oftemperature coefficient" which are de-scribed in detail in Section 6.

4.2.6 Matrix fields not in use In the case of matrix fields not being usedthe display "_ _ _ _" is shown.

Page 17: Transmitter/Controller for conductivity Type 262520

13

OPERATION

4.2.7 Example 1:De-inhibiting the operating level

input of the number password 0110)

Initial status:Instrument in measurement modeDisplayed matrix position: V0H0

Step 1:Press ENTER key.Matrix field V9H0 is selected.The units digit is flashing.

Step 2:Using the key ❮ switch to the tens digit. Using the and b key set the figure 1.

Step 3:Using the ❮ key switch to the hundreds digit. Using the and key set figure 1.

Page 18: Transmitter/Controller for conductivity Type 262520

14

OPERATION

Step 4: Using the ENTER key enter the 4-digit number. The display changes to 0000.

Step 5:Following the correct input the operating level is now de-inhibited.Check: using the H key it is possible now to alternate between 0 and 1. If this is not pos-sible, repeat steps 1 to 5.The other number passwords are input sim-ilarly.

4.2.8 Example 2:Setpoint input w1 as 545 µS/cm

Initial status:Operating level de-inhibited.Indicated matrix position V9H0

Step 1:Select matrix field V4H1 using the V and H keys.The units digit is flashing.

Page 19: Transmitter/Controller for conductivity Type 262520

15

OPERATION

Step 2:Using the and key set the figure 5.

Step 3:Using the ❮ key change to the tens digit. Us-ing the and key set the figure 4.

Step 4:Using the ❮ key change to the hundreds dig-it. Using the and key set the figure 5.

Step 5:Using the ENTER key enter the 4-digitnumber. The display changes to 0545steady.This completes the procedure. After inhibit-ing the level it is possible if required to returnto the measurement mode by selecting thematrix field V0H0.

Page 20: Transmitter/Controller for conductivity Type 262520

16

OPERATION

4.2.9 Example 3:Entering factory setting

Initial status: instrument in measurement mode. Indicated matrix position: V0H0

De-inhibit the parameter level by input of the number password 0020 (see example 1, Section 4.2.7)

Select matrix field V9H2, the display flashes "no".

Press and key, the display flashes "YES".

Press ENTER key. The display flashes BUSY. After about 15 seconds the display changes automatically to "no" (steady).

This completes the procedure.After inhibiting the level it is possible if re-quired to return to the measurement modeby selecting the matrix field V0H0.

4.2.10 Special key functions.At the indicating level, operating the ENTERkey produces a jump to the matrix fieldV9H0.At all levels, simultaneous operation of the Vand H keys produces a jump to the matrixfield V0H0.

4.3 Manual operation4.3.1 De-inhibitingManual operation is de-inhibited inside theinstrument (see Section 10) using switchS201.1 (normally de-inhibited) and throughthe matrix field V2H1 (normally inhibited).If switch S201.1 is inhibited (position 0) man-ual operation is not possible.When manual operation is activated the LEDHAND lights up.

4.3.2 Auto/manual changeoverWhen changeover is not inhibited, key ❮ inmatrix field V0H0 (measurement mode) canbe used to switch between auto and manualoperation.4.3.3 Operating the relay contacts

The relay contacts can only be activated onmatrix field V0H0 (measurement mode) us-ing the following keys:

Operating key (K1) activates relay contactK1.Operating key (K2) activates relay contactK2.Pulse operation: Select 0 in matrix field

V3H9The relay contact is activated only while thecorresponding key is pressed.When the key is released the correspondingrelay contact is immediately inactive (0/man-ual).Switch operation: Select 1 in matrix field

V3H9When key and is operated for the firsttime, the corresponding relay contact is ac-tivated and remains so until the same key ispressed again.When the HOLD LED is alight no manual op-eration is possible.

4.3.4 Switching action of the controller types

Limit controllerThe appropriate relay contact switches per-manently.

Pulse duration controllerThe appropriate relay contact switches forthe duration of the pulse.

Pulse frequency controller The maximum pulse frequency is output asset in matrix field V6H4 or V7H4.

Modulating controller The actuator is opened or closed.

Page 21: Transmitter/Controller for conductivity Type 262520

17

OPERATION

4.4 Temperature compensation The temperature compensation corrects theactually present conductivity to the 25°C ref-erence temperature, using pairs of values forliquid temperature and temperature co-effi-cient. This corrected value is then indicated.Up to a product temperature of 150°C themax. temperature coefficient is 5.5%/°C; itthen decreases as follows:to 200°C down to 4%/°C and thento 250°C down to 3%/°CMatrix field V3H2 decides whether the tem-perature is determined manually or automat-ically:0 = MTC (manual input of liquid temperature

in °C in matrix field V3H1)1 = ATC (automatic evaluation of liquid tem-

perature using a Pt 100 resistance ther-mometer connected to the unit)

4.4.1 Manual temperature compensa-tion

(MTC)The liquid temperature in °C is input in matrixfield V3H1.

4.4.2 Automatic temperature compen-sation (ATC)

With automatic temperature compensationa Pt 100 resistance thermometer is used toevaluate liquid temperatures between -50°Cand +250°C.The conductivity transmitter/controller is in-tended for the use with a Pt 100 resistancethermometer in 3-wire circuit (for connectiondiagram see Section 3, Electrical connec-tion).When using a resistance thermometer in 2-wire circuit a lead compensating resistanceRcomp must be connected into the circuit.Rcomp must correspond to the resistance ofone lead of the connection from Pt 100 re-sistance thermometer to the transmitter/controller (for connection diagram see Sec-tion 3, Electrical connection).

Page 22: Transmitter/Controller for conductivity Type 262520

18

4.5

Mat

rix

sum

mar

y

Ob

serv

e no

tes

in S

ectio

n 8

CO

NFI

GU

RA

TIO

N L

EV

EL

PA

RA

ME

TE

R L

EV

EL

OP

ER

AT

ING

LE

VE

L

IND

ICA

TIN

G L

EV

EL

H0

H1

H2

H3

H4

H5

H6

H7

H8

H9

V0

Ind

icat

e m

easu

rem

ent

[µS

/cm

or

mS

/cm

]

Cal

ibra

tion

of c

ell

cons

tant

with

ca

libra

tion

solu

-tio

n s

ee S

ectio

n 6

Rea

d in

old

cel

l co

nsta

nt d

ata

see

Sec

tion

6

Sup

ply

freq

uen-

cy 0

= 5

0H

z1

= 6

0 H

z

Sel

ect

rang

e µS

/cm

or m

S/c

m

see

Sec

tion

1

V1

Ind

icat

e te

mp

erat

ure

[°C

]

Exp

erim

enta

l ev

alua

tion

of

tem

per

atur

e co

effic

ient

see

Sec

tion

6

Rea

d in

old

te

mp

. coe

ffic

ient

d

ata

see

Sec

tion

6

Sta

rt m

eas.

con

-d

uctiv

ity o

utp

ut[%

]

see

Sec

tion

7

End

mea

s. c

on-

duc

tivity

out

put

[%

]

see

Sec

tion

7

Out

put

chan

geov

er

0 =

0-2

0 m

A0-

10 V

4

= 4

-20

mA

see

Sec

tion

7

Sim

ulat

ion

out-

put

[%]

see

Sec

tion

7

Sim

ulat

ion

0 =

off

1 =

on

see

Sec

tion

7

Cha

ngeo

ver

0 =

µS

/cm

1 =

mS

/cm

see

Sec

tion

1

Mea

sure

men

tou

tput

0 =

line

ar1

= d

ual-

slop

e

see

Sec

tion

7V

2In

dic

ate

cell

cons

tant

Cha

ngeo

ver

0

= a

uto

1

= m

anua

l se

e S

ectio

n 4

Sta

rt m

eas.

tem

-p

erat

ure

outp

ut[°

C]

see

Sec

tion

7

End

mea

s. t

em-

per

atur

e ou

tput

C]

see

Sec

tion

7

Sel

ect

cell

cons

tant

se

e S

ectio

n 1,

5

Inp

ut/

ind

icat

e ce

ll co

nsta

nt

[%]

see

Sec

tion

5

V3

Ind

icat

e te

mp

er-

atur

e co

effic

ient

[%

/°C

]

Inp

ut M

TC t

em-

per

atur

e

see

Sec

tion

4

Cha

ngeo

ver

0

= M

TC1

= A

TC

see

Sec

tion

4

Inp

ut t

emp

. co-

effic

ient

[%/°

C]

see

Sec

tion

6

Cha

ngeo

ver

man

ual

0 =

pul

se o

p.

1 =

sw

itch

op.

see

Sec

tion

4

V4

Ind

icat

e se

tpoi

nt

1 [µ

S/c

m o

r m

S/

cm]

Set

set

poi

nt 1

S/c

m o

r m

S/

cm]

Pro

por

tiona

l b

and

Xp

1

[µS

/cm

or

mS

/cm

]

Der

ivat

ive

time

1

Tv 1

[sec

]

Res

et t

ime

1Tn

1

[sec

]

Out

put

lim

it Y

1

[%]

Min

. ON

tim

e 1

or

Pul

se d

ura-

tion

1 [s

ec]

Diff

eren

tial 1

S/c

m o

r m

S/

cm]

Con

trol

ler

stru

c-tu

re 1

Con

trol

ler

typ

e 1

V5

Ind

icat

e se

tpoi

nt

2 [µ

S/c

m o

r m

S/

cm]

Set

set

poi

nt 2

S/c

m o

r m

S/

cm]

Pro

por

tiona

l b

and

Xp

2[µ

S/c

m o

r m

S/

cm]

Der

ivat

ive

time

2

Tv 2

[s

ec]

Res

et ti

me

2 T

n 2

[sec

]O

utp

ut li

mit

Y 2

[%]

Min

. ON

tim

e 2

or

Pul

se d

ura-

tion

2 [s

ec]

Diff

eren

tial 2

S/c

m o

r m

S/

cm]

Con

trol

ler

stru

ctur

e 2

Con

trol

ler

typ

e 2

V6

Ver

sion

(in

dic

atio

n of

so

ftw

are

vers

ion)

Ala

rm t

oler

ance

S/c

m o

r m

S/

cm]

Pul

l-in

del

ay r

e-la

y 1

[sec

]

Dro

p-o

ut d

elay

re

lay

1 [s

ec]

Max

. pul

sefr

eque

ncy

1[1

/h]

Pul

se p

erio

d 1

[s

ec]

Cha

ngeo

ver

0 =

bre

ak c

ont.

1

1 =

mak

e co

nt. 1

Cha

ngeo

ver

0 =

min

con

tact

1

1 =

max

con

tact

1

Wor

king

poi

nt

[%]

Ala

rm c

hang

e-ov

er

0 =

ste

ady

con-

tact

1 =

pul

se c

onta

ct

V7

Ind

icat

e fa

ult

cod

es

see

Sec

tion

9

Ala

rm d

elay

[s

ec]

Pul

l-in

del

ay

rela

y 2

[sec

]

Dro

p-o

ut d

elay

re

lay

2 [

sec]

Max

. pul

se

freq

uenc

y 2

[1/h

]

Pul

se p

erio

d 2

[s

ec]

Cha

ngeo

ver

0 =

bre

ak c

ont.

21

= m

ake

cont

. 2

Cha

ngeo

ver

0 =

min

con

tact

2

1 =

max

con

tact

2

Act

uato

r st

roke

tim

e [s

ec]

Pro

be

bre

ak

mon

itor

0

= o

ff /

1 =

on

see

Sec

tion

11

V8

Inte

rfac

eIn

stru

men

t ad

dre

sses

und

er d

evel

opm

ent

V9

Inhi

bit/

de-

inhi

bit

see

Sec

tion

4

HO

LD

0 =

off

1

= o

n

see

Sec

tion

11

Fact

ory

sett

ings

(d

efau

lt)

see

Sec

tion

11

Inp

ut fi

lter

cons

tant

[sec

] se

e S

ectio

n 11

Page 23: Transmitter/Controller for conductivity Type 262520

19

frequency.Important:

Before opening the case, observe the Notesin Section 10: "Adjustments inside the in-strument"!On switching the range, all previous settingsare overwritten by a default setting (see Sec-tion 11.4).

5 SWITCHING THE RANGE

Instruments supplied from stock withoutspecific ordering details have a basic config-uration (incl. span = 0 - 1 mS/cm, cell con-stant C = 1.0 /cm; see Section 12).If the user requires a different configurationhe has to set this himself. The parameters in-volved in the range are the unit of the range(µS/cm or mS/cm, matrix field V1H8), theupper range limit (matrix field V0H8) and thenominal size of the cell constant (matrix fieldV2H8). It is essential that the choice is re-stricted to the combinations shown in therange table (see Section 1). The additionalhardware change required consists of re-coding the input card (see Section 10.4)which also sets the correct measurement

Page 24: Transmitter/Controller for conductivity Type 262520

20

6 CALIBRATION

6.1 IntroductionAfter considering Section 5 the instrumentcan be placed into operation in conjunctionwith a cell of the given cell constant, withoutrequiring any additional settings.The actual value of the cell constant is sub-ject to individual variations, and in additionthe temperature coefficient depends on theproduct being tested; it may therefore be de-sirable to determine these two parametersmore precisely in order to obtain a bettermeasurement accuracy. There are severalmethods to achieve this which are describedbelow.

6.2 Numerical input of cell con-stant and temperature coeffi-cient

If the values of cell constant and tempera-ture coefficient are known, they can be inputafter opening the configuration level, usingthe fields V2H9 (cell constant in % of nomi-nal size as input at V2H8), and V3H8 respec-tively.

6.3 Calibrating the cell constant using a calibration solution

When the precise value of the cell constantis unknown it can be determined with the aidof a calibration solution.After selecting field V0H1 the temperaturecompensation is suppressed. The cell is im-mersed in the calibration solution and thedisplay then shows a value based on thetrue value of the cell constant but withoutreference to temperature. The subsequentediting procedure presumes an accurateknowledge of the conductivity of the calibra-tion solution at the current temperature.From the value input the instrument calcu-lates the cell constant and transfers it to thememory.

6.3.1 Procedure for calibrating the cell constant with a calibration solutionNote:

Before calibration it is necessary to de-inhibit the operating level!

Select matrix field V0H1Temperature compensation is suppressed.The current value at the input is indicated,taking into account the true value of the cellconstant.

Press ENTER The HOLD LED lights up.The LED Cal 1 lights up - immerse the sensi-tive part of the cell in the calibration solution.Wait until the reading has become steady.

Press ENTERThe indicated value is "frozen" (i.e. the display no longer responds to the input).

The indicated value can now be edited (forediting of values see Example 2, Section4.2.8). The purpose of editing is to bring theindicated value to the true value of the cali-bration solution.

Press ENTER The newly determined cell constant is stored in matrix field V2H9 as a percent-age.

The LED HOLD lights up.The calibration procedure is now completed.

Note:

After moving away from matrix field V0H1the LED HOLD goes dark.

Page 25: Transmitter/Controller for conductivity Type 262520

21

CALIBRATION

6.4 Experimental determination of the temperature coefficient

An experimental determination of the prod-uct temperature coefficient after selectionthe field V1H1 requires activating the auto-matic temperature compensation (matrixfield V3H2). The display shows the tempera-ture-compensated value of the current con-ductivity. The value of the current cellconstant is taken as being correct. Afterpressing the ENTER key the display showsthe temperature measured by the tempera-ture sensor.The method is based on measuring the non-temperature-compensated conductivities(temp. coeff. = 0) at two temperatures, thereference temperature 25°C and a secondtemperature T which usually corresponds tothe temperature of the subsequent meas-urement. When accepting the measured val-ues it is important to allow for the delay ofthe temperature sensor, i.e. a steady tem-perature reading on the display has to beobtained before pressing the ENTER key.Technical reasons sometime prevent exactsetting of the product temperature to the ref-erence temperature; values within the range25.0 ± 2.5°C are therefore accepted by theinstrument. The temperature coefficient iscalculated from the two pairs of values andtransferred to the memory.In case the reference temperature is notwithin the indicated limits there is an errormessage. This disappears when making afresh experimental determination of the tem-perature coefficient using field V3H8, or onentering the old value using field V1H2.

6.4.1 Procedure for experimentaldetermination of the temperaturecoefficient

Note:

Before calibration, the operating level mustbe de-inhibited and in Matrix field V3H2 theselection ATC = 1 must be made.

When accepting the measured values it isimportant to allow for the delay of the tem-perature sensor, i.e. a steady temperaturereading has to be obtained before pressingthe ENTER key.

Select matrix field V1H1The current value at the input (conductivity)is indicated. The current temperature coeffi-cient and the current cell constant are beingused.

Press ENTER The HOLD LED lights up.The LED Cal 1 lights up.Immerse the sensitive part of the cell in thecalibration solution.Wait until the reading has become steady(liquid temperature 25°C ± 2.5°C).

Press ENTER The HOLD LED lights up.The LED Cal 1 is flashing; the pair of valuesconductivity 1 and temperature 1 is beingaccepted.After the first pair has been accepted theLED Cal 2 lights up.Bring the solution to the later working tem-perature. (Check using the indication on thedisplay. The sensitive part of the cell mustremain immersed in the liquid).Note:

Press ENTER The HOLD LED lights up.The LED Cal 2 is flashing; the value pair con-ductivity 2 and temperature 2 is being ac-cepted.After the second value pair has been accept-ed the LED HOLD is alight.

Page 26: Transmitter/Controller for conductivity Type 262520

22

CALIBRATION

The temperature coefficient is calculatedfrom the two pairs of values and stored inmatrix field V3H8.The value currently at the input (conductivity(is indicated.It is based in the newly calculated tempera-ture coefficient and on the current cell con-stant.

Note:

7 ANALOGUE OUTPUT

7.1 Process value output The transmitter/controller can output the fol-lowing standard signals proportional to theinputs conductivity (and temperature if con-figured):

0 - 20 mA4 - 20 mA 0 - 10 V

The selection between current and voltage ismade with a DIL switch, see Section 10.1,Analogue output.The change between the current outputs 0 -20 mA and 4 - 20 mA is made in matrix fieldV1H5 for conductivity and temperature.When the analogue output is being operatedas a voltage output the matrix field V1H5must be set to current output 0 - 20 mA.The measurement span to be converted intothe analogue output can be selected in ma-trix fields V1H3 Start conductivity outputand V1H4 End conductivity output, alsoV2H3 Start temperature output and V2H4End temperature output.The simulation of the output signal for con-ductivity and temperature is activated byswitching the matrix field V1H7 from 0 to 1using the keys and and pressing EN-TER. The simulated output value for conduc-tivity and temperature, set in matrix fieldV1H6 as percentage of span, is then output.The process output conductivity can be rep-resented in two ways:

linear: select 0 in matrix field V1H9

dual-slope: select 1 in matrix field V1H9

With a dual-slope signal, the output reachesmid-range at 10% of the span between startand end of conductivity range.

After moving away from matrix field V0H1the HOLD LED goes dark.

6.5 Accepting old calibration dataFollowing successful completion of the cali-bration procedures and measurements asdescribed above, it may be decided not toaccept the new values. The previous valuecan then be restored by using the matrixfields V0H3 (cell constant) and/or V1H2(temperature coefficient), or fresh inputs canbe made using V2H9 and/or V3H8.

Page 27: Transmitter/Controller for conductivity Type 262520

23

ANALOGUE OUTPUT

Example:Selected range 500 µS/cm

Start of conductivity output 20.0% of 500 µS/cm = 100 µS/cm

End of conductivity output100.0% of 500 µS/cm = 500 µS/cm

Span500 µS/cm - 100 µS/cm = 400 µS/cm

Selected output signal4 - 20 mA

The output signal is 12 mA at 140 µS/cm,20 mA at 500 µS/cm

Page 28: Transmitter/Controller for conductivity Type 262520

24

8 CONTROLLER

8.1 ConceptsAlarm contactThe limit controller monitors the active timeof the relay. If this time is exceeded by anadjustable value (delay time) the alarm con-tact is activated.The proportional and the modulating con-troller monitors the size of the control devia-tion. If this exceeds an adjustable value(alarm tolerance) an adjustable delay time isstarted and at its end the alarm contact isactivated.With both functions the delay time is resetwhen the alarm conditions are no longer ful-filled.

Alarm delayThe time during which the alarm conditionmust be fulfilled before the alarm relay andthe alarm LED are activated.

Alarm toleranceIf the control deviation exceeds the alarmtolerance the alarm delay is started. At theend of the alarm delay the alarm contact isactivated.

Changeover break/make contact0 = break contact (common connected to

n.c. contact)

1 = make contact (common connected ton.o. contact

Example break-make contact

Range I Range II Range III

LED Contact LED Contact LED Contact

min break ON 0 OFF 1 OFF 1

make ON 1 OFF 0 OFF 0

max break OFF 1 OFF 1 ON 0

make OFF 0 OFF 0 ON 1

Time

w2

w1

Con

duc

tivity Range

IRangeII

RangeIII

Page 29: Transmitter/Controller for conductivity Type 262520

25

CONTROLLER

Break contactAs long as the controller is inactive the com-mon is connected to the n.c. (break) contactand the corresponding LED is off.

Make contactAs long as the controller is inactive the com-mon is connected to the n.o. (make) contactand the corresponding LED is off.

Changeover min/max contactMin contact means that the controller is ac-tive when the process value is below the set-point.Max contact means that the controller is ac-tive when the process value is above the set-point.

0 = min contact1 = max contact

Changeover steady/pulse contactApplies only to the alarm contact and de-fines the action on activating the alarm con-tact.

0 = steady contactThe alarm relay is energised and remains so until the cause of thealarm has been removed. The alarmLED is flashing.

1 = pulse contactThe alarm relay switches once forapprox. 1 second and then returns toits original status. The alarm LEDcontinues to flash until the cause ofthe alarm has been removed.

Controller structureDetermining the controller structure of a pro-portional or quasi-proportional controller ormodulating controller.

0 = P (proportional)1 = I (integral)2 = PD (proportional, differential)3 = PI (proportional, integral)4 = PID (proportional, integral, differential)

Controller typeIt defines the controller as:0 = controller off1 = limit controller2 = quasi-proportional controller with

pulse duration output3 = quasi-proportional controller with

pulse frequency output5 = modulating controller

Derivative time TV(differentiation constant)Control parameter in a PD and PID control-ler. It determines effect and filtering of theprocess variable change.

DifferentialIn the case of a non-analogue controller thedifferential is the change in process variablerequired to produce changeover of a relaycontact with increasing and with decreasingprocess variable.

Drop-out delayThe time interval which has to elapse untilthe relay contact switches over when theswitching conditions are no longer fulfilled.

Limit controllerSingle-setpoint controller with pull-in and/ordrop-out delay.

Maximum pulse frequencyThe value based on the technical data of thedosing pumps (e.g. with magnetic dosingpumps).

Minimum ON timeThe value given by the technical data of thedosing element (in dosing pumps or sole-noid valves).

Output limitThe maximum value of the output signal of aproportional or quasi-proportional control-ler.

Page 30: Transmitter/Controller for conductivity Type 262520

26

CONTROLLER

Proportional band XpThe range of a P controller within whichthere is a proportional relationship betweencontrol deviation and controller outputchange.

Pull-in delayThe time interval until the control contactswitches over when the switching conditionis fulfilled.

Pulse periodThe value indicates the period during whichthe pulse duration modulation takes place.

Quasi-proportional controller with pulse duration outputWhen a control deviation occurs the relaystarts to output pulses of different duration(parameter: minimum ON time).The duration of the pulses depends on themagnitude of the deviation and on the setcontrol parameters. This output can be usedto control solenoid valves, for example.

Quasi-proportional controller with pulse frequency outputWhen a control deviation occurs the relaystarts to output pulses of constant duration(parameter: minimum ON time).The repeat frequency of the pulses dependson the magnitude of the deviation and on theset control parameters. This output can beused to operate magnetic dosing pumps, forexample.

Reset time Tn(integral constant)Control parameter of a PI, PID and I control-ler. The value determines the rate at whichthe control deviation is integrated in the inte-grator.

Stroke timeAdjustable on modulating controller. Thisvalue must be obtained from the data of theactuator manufacturer (e.g. for a motorisedvalve).

Working pointOutput on P and PD controllers for zero con-trol deviation.

8.2 Possible combinationsTwo of the following controllers can be com-bined as required. The selection is made inthe matrix fields V4H9 Controller type 1 andV5H9 Controller type 2.

- Controller off- Limit controller- Pulse duration controller- Pulse frequency controller

The modulating controller can only be se-lected in matrix field V4H9 Controller type 1.A selection in matrix field V5H9 Controllertype 2 is then ineffective.

8.3 Controller switched offSelection 0 (controller off)in matrix field V4H9, Controller type 1 and/ormatrix field V5H9, Controller type 2

Relevant control parameters:none

8.4 Limit controllerSelection 1 (limit controller)in matrix field V4H9, Controller type 1and/ormatrix field V5H9, Controller type 2.

Relevant parameters:

in matrix field V6H2, Pull-in delay relay 1and/ormatrix field V7H2, Pull-in delay relay 2orin matrix field V6H3, Drop-out delay relay 1and/ormatrix field V7H3, Drop-out delay relay 2

Page 31: Transmitter/Controller for conductivity Type 262520

27

CONTROLLER

in matrix field V6H7, Changeover min/maxcontact 1and/ormatrix field V7H7, Changeover min/maxcontact 2

in matrix field V6H6, Changeover break/make contact 1and/ormatrix field V7H6, Changeover break/makecontact 2

in matrix field V4H7, Differential 1and/ormatrix field V5H7, Differential 2

in matrix field V4H1, Set setpoint 1and/ormatrix field V5H1, Set setpoint 2

8.5 Pulse duration controllerSelection 2 (pulse duration controller)

T = pulse periodtON = minimum ON timetON < T

Important:

Relevant parameters:

in matrix field V4H8, Controller structure 1and/ormatrix field V5H8, Controller structure 2

in matrix field V4H3, Derivative time 1 (for PD and PID control action)and/ormatrix field V5H3, Derivative time 2 (for PD and PID control action) orin matrix field V4H4, Reset time 1 (for I, PI and PID control action)and/ormatrix field V5H4, Reset time 2 (for I, PI and PID control action)

in matrix field V4H2, Proportional band XP1(for P, PI and PID control action)and/ormatrix field V5H2, Proportional band XP2 (for P, PI, PID control action)in matrix field V6H5, Pulse period 1and/ormatrix field V7H5, Pulse period 2

in matrix field V4H6, Minimum ON time 1and/ormatrix field V5H6, Minimum ON time 2

in matrix field V6H7, Changeover min/maxcontact 1and/ormatrix field V7H7, Changeover min/maxcontact 2

in matrix field V6H6, Changeover break/make contact 1and/ormatrix field V7H6, Changeover break/makecontact 2

in matrix field V6H8, Working pointin matrix field V4H5, Output limit Y1and/ormatrix field V5H5, Output limit Y2

in matrix field V4H1, Set setpoint 1and/ormatrix field V5H1, Set setpoint 2

If both relay contacts switch for process value below setpoint then there must be w1 < w2!

If both relay contacts switch for process value above setpoint then there must be w1 > w2!

in matrix field V4H9, Controller type 1and/ormatrix field V5H9, Controller type 2.

Page 32: Transmitter/Controller for conductivity Type 262520

28

CONTROLLER

8.6 Pulse frequency controllerSelection 3 (pulse frequency controller)

tON = minimum ON timetON + tOFF = TtON = 0.2 sec min.T = 0.4 sec min.pulses/h = (3600 sec/h)/T

If tOFF would have to be less than 0.2 secthere is no steady output signal and the relaycontact goes to inactive.

Important:

and/ormatrix field V5H4, Reset time 2 (for I, PI and PID control action)

in matrix field V4H2, Proportional band XP1(for P, PI and PID control action)and/ormatrix field V5H2, Proportional band XP2 (for P, PI, PID control action)

in matrix field V6H4, Max. pulse frequency 1and/ormatrix field V7H4, Max. pulse frequency 2

in matrix field V4H6, Minimum ON time 1and/ormatrix field V5H6, Minimum ON time 2

in matrix field V6H7, Changeover min/maxcontact 1and/ormatrix field V7H7, Changeover min/maxcontact 2

in matrix field V6H6, Changeover break/make contact 1and/ormatrix field V7H6, Changeover break/makecontact 2

in matrix field V6H8, Working point

in matrix field V4H5, Output limit Y1and/ormatrix field V5H5, Output limit Y2

in matrix field V4H1, Set setpoint 1and/ormatrix field V5H1, Set setpoint 2

8.7 Modulating controllerSelection 5 (modulating controller)in matrix field V4H9, Controller type 1

Relevant parameters:

in matrix field V4H8, Controller structure 1(only PI and PID action appropriate)

in matrix field V4H4, Reset time 1 (for PI and PID control action)

in matrix field V7H8, Stroke time

in matrix field V4H2, Proportional band XP1

If both relay contacts switch for process value below setpoint then there must be w1 < w2!

If both relay contacts switch for process value above setpoint then there must be w1 > w2!

in matrix field V4H9, Controller type 1and/ormatrix field V5H9, Controller type 2.

Relevant parameters:

in matrix field V4H8, Controller structure 1and/ormatrix field V5H8, Controller structure 2

in matrix field V4H3, Derivative time 1(for PD and PID control action)and/ormatrix field V5H3, Derivative time 2 (for PD and PID control action) orin matrix field V4H4, Reset time 1(for I, PI and PID control action)

Page 33: Transmitter/Controller for conductivity Type 262520

29

CONTROLLER

(for PI and PID control action)

in matrix field V4H6, Min. ON time 1and/ormatrix field V5H6 Min. ON time 2

in matrix field V4H5, Output limit Y1and/ormatrix field V5H5, Output limit Y2

in matrix field V4H1, Set setpoint 1and/ormatrix field V5H1, Set setpoint 2

Note:Optimum

Tn too small

Tn too large

XP too small

with PID action there is a fixed ratio Tv = Tn/4.

8.8 Alarm contactin matrix field V6H1, Alarm toleranceand/orin matrix field V7H1, Alarm delay

in matrix field V6H9, Changeover steadyalarm contact/pulse alarm contact

Note:

In controller type "limit controller" the alarmtolerance is fixed internally at 0.

8.9 Notes on possible incorrect controller settings and their correction

The optimum adjustment of the controller tothe process loop can be tested by recordinga start-up with the control loop closed.The diagrams below relate to PID action andindicate possible incorrect settings and theircorrection.It is found that increasing XP and increasingTn both produce a more stable and moresluggish control action.Reducing XP or Tn leads to a less dampedcontrol action.

Page 34: Transmitter/Controller for conductivity Type 262520

30

CONTROLLER

XP too large

9 FAULTS, WARNINGS

9.1 IntroductionThe fault codes are shown in matrix fieldV7H0. If several faults occur simultaneouslythe code with the smallest number is shownfirst. All other codes can be called up withkey in increasing order. Correspondinglypressing key calls up the code with thenext lower number.

Fault codes are updated continuously. If afault code is cleared while on display, thecode with the next lower number (if it exists)is displayed. Otherwise the code with thenext higher number is displayed. If there isno fault and no warning the display showsF000.

Certain faults shift the controller to theHOLD status for the time they are present.These are the faults F020, F021, F022, F023,F024 and F025.

9.2 FaultsFaults activate the alarm relay while they arepresent.

F010Measurement above/below alarm toler-ance and controller alarm delay exceeded

Remedy: check control parameters.

F020Outside permitted tolerance range of cell constantThe cell constant differs by more than ±20%from the nominal value.

Remedy: repeat the calibration; possiblyclean cell or check calibration solutions.

F021Outside permitted range of temperature coefficientThe temperature coefficient is less than0%/°C or larger than 5.5%/°C.

Remedy: repeat the calibration(see Section 6).

Page 35: Transmitter/Controller for conductivity Type 262520

31

FAULTS, WARNINGS

F022Conductivity underrangeMeasurement below 0orprobe break monitor has operated

The probe break monitor is activated and themeasurement is below 2% of the measuringrange.

Possible cause:break in cable, conductivity of liquid lessthan 2% of range, or cell not immersed in liq-uid.

F023Conductivity overrangeMeasurement above set range

Possible cause:short-circuit in cable, range too small ortemperature coefficient of liquid too high.

F024Incorrect temperature measurement(only relevant with ATC)

Possible cause:Pt 100 resistance thermometer has short-circuit, break, is not connected, or tempera-ture is outside the range -50 to +250°C.

F025Combination of range with cell constant not permittedRemedy: use only a combination shown on page 12.

F030Process value output below permitted minimumThe process value output is smaller than theset value.

Remedy:change value in matrix field V1H3orchange value in matrix field V2H3

F031Process value output above permitted maximumThe process value is larger than the set val-ue.

Remedy:change value in matrix field V1H4orchange value in matrix field V2H4.

9.3 WarningsWarnings do not activate the alarm relay butthe alarm LED is flashing. If the instrument iscontrolling it continues to do so during warn-ings without being influenced.

F050Parameter limits for process value inter-changedThe end value of the process value output issmaller than the start value of the processvalue output.

Remedy: interchange value in matrix field V1H3 withvalue in matrix field V1H4orinterchange value in matrix field V2H3 withvalue in matrix field V2H4.

F060Pulse duration controllerMinimum ON time 1 is not less than pulseperiod 1

Remedy: reduce minimum ON time in matrix fieldV4H6and/orincrease the pulse period in matrix fieldV6H5.

Pulse frequency controllerPulse duration 1 [sec] is not less than

3600 [sec/h]max. pulse frequency 1 [1/h]

Page 36: Transmitter/Controller for conductivity Type 262520

32

FAULTS, WARNINGS

Remedy:reduce the pulse duration in matrix fieldV4H6and/orreduce the maximum pulse frequency in ma-trix field V6H4.

F061Pulse duration controllerMinimum ON time 2 is not less than pulseperiod 2

Remedy: reduce minimum ON time in matrix fieldV5H6and/orincrease the pulse period in matrix fieldV7H5.

Pulse frequency controller

Pulse duration 2 [sec] is not less than

3600 [sec/h]max. pulse frequency 2 [1/h]

Remedy:reduce the pulse duration in matrix fieldV5H6and/orreduce the maximum pulse frequency in ma-trix field V7H4.

F070Actual liquid temperature differs by more than 2.5°C from the 25°C reference tem-perature.Remedy:repeat calibrationsee Calibration (Section 6)

Note:

This warning appears only with ATC andduring the first calibration step for experi-mental determination of the temperature co-efficient.

Page 37: Transmitter/Controller for conductivity Type 262520

33

10 ADJUSTMENTS INSIDE THE INSTRUMENT

Warning:When working on the microprocessor trans-mitter/controller observe the VDE and ESDrequirements!

Conductivity output

Temperature output

Page 38: Transmitter/Controller for conductivity Type 262520

34

ADJUSTMENTS INSIDE THE INSTRUMENT

10.1 Analogue outputThe output signal is selected through DILswitches. The changeover from 0 - 20 mA to4 - 20 mA is made in software using matrixfield V1H5 (see Section 7.1).

The instrument is supplied fully calibrated. Ifa different output signal is selected on theswitches S1101.1 to S1101.4 it may be nec-essary to make a slight adjustment to theoutput signal using the "start" and "end"trimmers.

Note:

(1) Jumper for code setting on the conduc-tivity input card

end start

When the instrument is provided for temper-ature output, the switches on the tempera-ture card must be altered similarly!

Analogue output

O = off X = on

10.2 Manual operationImportant:Switch S201.7 is provided for servicing onlyand is factory-set to position 0.

The setting of switch S201.7 must not be altered!

Switch S201.1inhibited 0de-inhibited X

For description see Section 4.3

10.3 Input filterSwitch S201.4on 0off X

For description see Section 11.3

SignalSwitches

S1101.1 S1101.2 S1101.3 S1101.4

0 - 10 V O X X X

0(4)-20 mA

O O O X

Page 39: Transmitter/Controller for conductivity Type 262520

35

ADJUSTMENTS INSIDE THE INSTRUMENT

10.4 Code setting on the conductiv-ity input cardThe location of the conductivity input card isshown in Section 10.1 Analogue output.

Range: Cell constant

up to 0.50 µS/cm C = 0.01 1/cmup to 1.00 µS/cm C = 0.01 1/cmup to 2.00 µS/cm C = 0.01 1/cmup to 3.00 µS/cm C = 0.01 1/cm

up to 5.00 µS/cm C = 0.01 1/cmup to 10.0 µS/cm C = 0.01 1/cm

up to 5.00 µS/cm C = 0.1 1/cmup to 10.0 µS/cm C = 0.1 1/cmup to 20.0 µS/cm C = 0.1 1/cm

up to 50.0 µS/cm C = 0.1 1/cm

up to 50.0 µS/cm C = 1.0 1/cmup to 100 µS/cm C = 1.0 1/cm

Range: Cell constant

up to 100 µS/cm C = 0.1 1/cm

up to 300 µS/cm C = 0.1 1/cm

up to 300 µS/cm C = 1.0 1/cm

up to 500 µS/cm C = 0.1 1/cm

up to 500 µS/cm C = 1.0 1/cm

up to 1000 µS/cm C = 0.1 1/cm

up to 1000 µS/cm C = 1.0 1/cmup to 1000 µS/cm C = 3.0 1/cm

Page 40: Transmitter/Controller for conductivity Type 262520

36

ADJUSTMENTS INSIDE THE INSTRUMENT

Range: Cell constant

up to 2000 µS/cm C = 1.0 1/cm

up to 1.00 mS/cm C = 0.1 1/cm

up to 1.00 mS/cm C = 1.0 1/cmup to 1.00 mS/cm C = 3.0 1/cm

up to 2.00 mS/cm C = 1.0 1/cm

up to 3.00 mS/cm C = 1.0 1/cm

up to 3.00 mS/cm C = 3.0 1/cm

up to 5.00 mS/cm C = 0.1 1/cm

Range: Cell constant

up to 5.00 mS/cm C = 1.0 1/cmup to 10.0 mS/cm C = 1.0 1/cmup to 10.0 mS/cm C = 3.0 1/cm

up to 20.0 mS/cm C = 1.0 1/cm

up to 20.0 mS/cm C = 3.0 1/cm

up to 30.0 mS/cm C = 1.0 1/cm

up to 30.0 mS/cm C = 3.0 1/cmup to 30.0 mS/cm C = 10.0 1/cm

up to 50.0 mS/cm C = 1.0 1/cm

up to 100.0 mS/cm C = 1.0 1/cm

Page 41: Transmitter/Controller for conductivity Type 262520

37

ADJUSTMENTS INSIDE

Range: Cell constant

up to 100.0 mS/cm C = 10.0 1/cm

up to 200.0 mS/cm C = 10.0 1/cm

11.1 Function of the logic inputsThe instrument can be brought to the HOLDstatus by a link (short-circuit) at logic input 1(terminals 81, 82).The alarm via the alarm relay can be sup-pressed by a link across logic input 2 (termi-nals 83, 84). The alarm LED continues tooperate normally.

11.2 HOLD functionActivating the HOLD function makes the re-lays inactive. Any started time periods on thecontroller (e.g. derivative time) and of thealarm (alarm delay) are reset.

11.2.1 Internal HOLDThe HOLD function is activated internally byswitching the indication in matrix field V9H1from 0 to 1 using the key or , followedby pressing the ENTER key.In addition the HOLD function is automati-cally activated internally when fundamentalalterations to the instrument settings aremade. Examples: changeover to calibration,changing the controller type. After complet-ing the alteration and leaving the corre-sponding matrix field the automatic HOLD isde-activated.

11.2.2 External HOLDThe HOLD function is activated externally bya link across the connections of the logic in-put 1. In this way the HOLD function can beoperated from a PLC, for example.

11.3 Input filterThe input variables conductivity and temper-ature are passed through a second-orderdigital filter which suppressed undesirableeffects such as noise or interference pulses.The filter constant is factory-set at 0.6 sec-onds. This value can be altered in matrixfield V9H3.

11 EXTRA FUNCTIONS

Page 42: Transmitter/Controller for conductivity Type 262520

38

EXTRA FUNCTIONS

Exception: the function of the digital filterhas been switched off with the switchS201.4. In this case the setting in matrix fieldV9H3 is ineffective.

11.4 Reading-in the factory settingThe instrument offers the facility of readingin the parameter set of the factory setting.After reading in, all parameters are occupiedby the data which are stored when the in-strument is supplied.

Exception: the measuring range, the unit(µS/cm or mS/cm), the cell constant and thetemperature coefficient remain unchangedwhen reading in the factory setting. For ad-justing these parameters see Section 6, Cal-ibration.Reading in the parameters takes place byswitching the indication in matrix field V9H2from "no" to "YES" using the key or ,followed by pressing the ENTER key.

When altering the measuring range the val-ues in the following matrix fields are altered:V6H1 Alarm toleranceV4H1 Setpoint 1V5H1 Setpoint 2V4H2 Proportional band XP1V5H7 Proportional band XP2V4H7 Differential 1V5H7 Differential 2

Example 1:

range 0 - 1 mS/cm Cell constant C = 1.0 1/cm

V6H1 Alarm tolerance 0.00 mS/cm (= 0% of range)

V4H1 Setpoint 1 0.00 mS/cm (= 0% of range)

V5H1 Setpoint 2 1.00 mS/cm (= 100% of range)

V4H2 Proportional band XP1 0.50 mS/cm (= 50% of range)

V5H7 Proportional band XP2 0.50 mS/cm (= 50% of range)

V4H7 Differential 1 0.02 mS/cm (= 2% of range)

V5H7 Differential 2 0.02 mS/cm (= 2% of range)

Page 43: Transmitter/Controller for conductivity Type 262520

39

EXTRA FUNCTIONS

11.5 Probe break monitorWhen the probe break monitor is activated in matrix field V7H9, a conductivity less than 2% of range is recognised as probe break. This is indicated by the instrument as fault F022.

EXTRA FUNCTIONS

Example 2:

range 0 - 500 µS/cm Cell constant C = 0.1 1/cm

V6H1 Alarm tolerance 0 µS/cm (= 0% of range)

V4H1 Setpoint 1 0 µS/cm (= 0% of range)

V5H1 Setpoint 2 500 µS/cm (= 100% of range)

V4H2 Proportional band XP1 250 µS/cm (= 50% of range)

V5H7 Proportional band XP2 250 µS/cm (= 50% of range)

V4H7 Differential 1 10 µS/cm (= 2% of range)

V5H7 Differential 2 10 µS/cm (= 2% of range)

Page 44: Transmitter/Controller for conductivity Type 262520

40

12 APPENDIX

12.1 Table for parameter and con-figuration settings

As guidance for later changes of the instru-ment settings it is possible to enter here the appropriate parameter and configuration data. Certain parameters are omitted de-pending on the particular transmitter and controller version.

* see Section 11.4

Transmitter Factory settingconductivity

User setting

V2H1 auto ................................................................ 0manual ............................................................ 1

0

V3H9 manual operationpulse operation .............................................. 0switch operation ............................................. 1

0

V9H1 HOLD off ........................................................ 0HOLD on ........................................................ 1

0

V9H3 Input filter constant.......................................................... 0 - 20 sec

0.6 sec*

V0H4 Supply frequency 50 Hz ................................. 0Supply frequency 60 Hz ................................. 1

0

V0H8 Measuring range0.5; 1.00; 2.00; 3.00; 5.00; 10.0; 20.0;30.0, 50.0; 100; 200; 300; 500; 1000; 2000

1.00*

V1H8 UnitµS/cm ............................................................. 0mS/cm ............................................................ 1

1*

V2H8 Cell constant0.01; 0.1; 1.0; 3.0; 10.0

1.0

V2H9 nput / indicate cell constant50.0 to 150.0%

100%

V7H9 Probe break monitoroff ................................................................... 0on ................................................................... 1

0

Page 45: Transmitter/Controller for conductivity Type 262520

41

APPENDIX

* see Section 11.4

Calibration Factory settingconductivity

User setting

V3H1 MTC temperature....................................................-50 to +250°C 25.0°C

V3H2 MTC manual temp compensation .................. 0ATC automatic temp. comp. .......................... 1

0

V3H8 Temperature coefficientinput 0 - 5.5%/°C 2.30

Alarm Factory settingconductivity

User setting

V6H1 Alarm tolerance0 to ranges in µS/cm or mS/cm

0*

V7H1 Alarm delay........................................................ 0-6000 sec

20 sec

V6H9 Steady contact ............................................... 0Pulse contact ................................................. 1

0

Process output Factory settingconductivity

User setting

V1H3 Start conductivity output(conductivity at 0/4 mA or 0 V) .......... 0 - 100%

0%

V1H4 End conductivity output(conductivity at 20 mA or 10 V) ........................................................... 0 - 100%

100%

V1H5 Process value output 0-20 mA/0-10 V ........... 0Process value output 4-20 mA ...................... 4

0

V1H6 Simulation output ................................ 0-100% 50.0%

V1H7 Simulation off ................................................. 0Simulation on ................................................. 1

0

V1H9 Process outputlinear ............................................................... 0dual-slope ....................................................... 1

0

V2H3 Start temperature output -50 to +250°C -50°CV2H4 End temperature output -50 to +250°C 250°C

Interface Factory settingconductivity

User setting

V8H0 Interface (under development) 0

V8H1 Instrument address (under development) 0

Page 46: Transmitter/Controller for conductivity Type 262520

42

APPENDIX

Controller Factory settingconductivity

User setting

V4H1 Setpoint 10 to end of rangein mS/cm or mS/cm

0*

V5H1 Setpoint 20 to end of rangein µS/cm or mS/cm

1.00 mS/cm*

V4H2 Proportional band XP1................................................................ 0 digit............................................... 999 or 9999 digit

0.5 mS/cm

V5H2 Proportional band XP2................................................................ 0 digit............................................... 999 or 9999 digit

0.5 mS/cm

V6H2 Pull-in delay relay contact 1....................................................... 0-999.9 sec

1.0 sec

V7H2 Pull-in delay relay contact 2

.................................................. 0-999.9 sec1.0 sec

V4H3 Derivative time 1 Tv1

................................................... 0-9999 sec80 sec

V5H3 Derivative time 2Tv2

................................................... 0-9999 sec80 sec

V6H3 Drop-out delay relay contact 1

.................................................. 0-999.9 sec0.2 sec

V7H3 Drop-out delay relay contact 2

.................................................. 0-999.9 sec

V4H4 Reset time 1 Tn1 ........................ 0-9999 sec 350 sec

V5H4 Reset time 2 Tn2 ........................ 0-9999 sec 350 sec

V6H4 Maximum pulse frequency 1

......................................................0-9000 /h6000/h

V7H4 Maximum pulse frequency 2

......................................................0-9000 /h6000/h

V4H5 Output limit Y1 ................................ 0-100% 100%

V5H5 Output limit Y2 ........................... -100-100% -100%

V6H5 Pulse period 1 .......................... 1-999.9 sec 20.0 sec

V7H5 Pulse period 2 ........................... 1-999.9 sec

V4H6 Min. ON time 1 or pulse duration 1

............................................... 0.2-999.9 sec0.2 sec

Page 47: Transmitter/Controller for conductivity Type 262520

43

Controller Factory settingconductivity

User setting

V5H6 Min. ON time 2 or pulse duration 2

............................................... 0.2-999.9 sec0.2 sec

V6H6 Break contact 1 ......................................... 0

Make contact 1 ......................................... 10

V7H6 Break contact 2............................................... 0Make contact 2 ............................................... 1

0

V4H7 Differential 1.....................................within measuring range

0.02 mS*

V5H7 Differential 2.....................................within measuring range

0.02 mS*

V6H7 Min. contact 1 ................................................ 0Max. contact 1 ................................................ 1

0

V7H7 Min. contact 2 ................................................. 0Max. contact 2 ............................................... 1

1

V4H8 Controller structure 1P action .......................................................... 0I action ........................................................... 1PD action ........................................................ 2PI action ......................................................... 3PID action ....................................................... 4

0

V5H8 Controller structure 2P action .......................................................... 0I action ........................................................... 1PD action ........................................................ 2PI action ......................................................... 3PID action ....................................................... 4

0

V6H8 Working point ...............................-100-+100% 0%

V7H8 Strke time (modulating controller)...................................................... 15-3000 sec

60 sec

V4H9 Controller type 1off ................................................................... 0Limit controller ............................................... 1Pulse duration controller ................................ 2Pulse frequency controller ............................. 3Modulating controller ..................................... 5

1

V5H9 Controller type 2off ................................................................... 0Limit controller ............................................... 1Pulse duration controller ................................ 2Pulse frequency controller ............................. 3

1

APPENDIX

Page 48: Transmitter/Controller for conductivity Type 262520

CONFIGURATION LEVEL

PARAMETER LEVEL

OPERATING LEVEL

INDICATING LEVEL

H0 H1 H2 H3 H4 H5 H6 H7 H8 H9

V0 Indicate measurement

[

µ

S/cm or mS/cm]

Calibration of cell constant with cali-

bration solution see Section 6

Read in old cell constant data

see Section 6

Supply frequency 0 = 50 Hz 1 = 60

Hz

Select range

µ

S/cm or mS/cm see Section 1

V1 Indicate temperature

[

°

C]

Experimental evaluation of tem-

perature coeffi-cient

see Section 6

Read in old temp. coefficient data

see Section 6

Start meas. con-ductivity output

[%]

see Section 7

End meas. con-ductivity output

[%]

see Section 7

Outputchangeover

0 = 0-20 mA or 0-10 V

4 = 4-20 mAsee Section 7

Simulation output [%]

see Section 7

Simulation0 = off1 = on

see Section 7

Changeover 0 =

µ

S/cm1 = mS/cm

see Section 1

Measurementoutput

0 = linear1 = dual-slope

see Section 7

V2 Indicate cell constant

Changeover 0 = auto

1 = manual see Section 4

Start meas. tem-perature output

[

°

C] see Section 7

End meas. tem-perature output

[

°

C] see Section 7

Select cell constant

see Section 1, 5

Input/ indicate cell constant

[%] see Section 5

V3 Indicate tempera-ture coefficient

[%/

°

C]

Input MTC tem-perature

see Section 4

Changeover 0 = MTC1 = ATC

see Section 4

Input temp. coef-ficient[%/

°

C]

see Section 6

Changeovermanual

0 = pulse op.1 = switch op. see Section 4

V4 Indicate setpoint 1 [

µ

S/cm or mS/cm]Set setpoint 1

[

µ

S/cm or mS/cm]Proportional band

Xp 1 [

µ

S/cm or mS/cm]

Derivative time 1 Tv 1[sec]

Reset time 1Tn 1 [sec]

Output limit Y 1 [%]

Min. ON time 1 or Pulse duration 1

[sec]

Differential 1 [

µ

S/cm or mS/cm]Controller struc-

ture 1 Controller type 1

V5 Indicate setpoint 2 [

µ

S/cm or mS/cm] Set setpoint 2

[

µ

S/cm or mS/cm]Proportional band

Xp 2[

µ

S/cm or mS/cm]

Derivative time 2 Tv 2 [sec]

Reset time 2 Tn2 [sec]

Output limit Y 2[%]

Min. ON time 2 or Pulse duration 2

[sec]

Differential 2 [

µ

S/cm or mS/cm]Controller structure 2

Controller type 2

V6 Version (indication of soft-

ware version)

Alarm tolerance [

µ

S/cm or mS/cm]Pull-in delay

relay 1 [sec]

Drop-out delay relay 1 [sec]

Max. pulsefrequency 1

[1/h]

Pulse period 1 [sec]

Changeover 0 = break cont. 1 1 = make cont. 1

Changeover 0 = min contact 1 1 = max contact 1

Working point [%]

Alarm change-over

0 = steady contact1 = pulse contact

V7 Indicate fault codes

see Section 9

Alarm delay [sec]

Pull-in delay relay 2 [sec]

Drop-out delay relay 2 [

sec]

Max. pulse frequency 2

[1/h]

Pulse period 2 [sec]

Changeover0 = break cont. 21 = make cont. 2

Changeover 0 = min contact 2 1 = max contact 2

Actuator stroke time [sec]

Probe break monitor

0 = off / 1 = on see Section 11

V8 Interface Instrument addresses

under development

V9 Inhibit/de-inhibit

see Section 4

HOLD 0 = off 1 = on

see Section 11

Factory settings (default)

see Section 11

Input filter constant

[sec] see Section 11

Observe notes in Section 8