TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 2, 08/03/2011 1
Installation InstructionsTB/TI
Thermistor Insertion Temperature Sensor
Important: Retain these instructions
1 Dimensions
UnpackIng
InSTallaTIon
6 m
m (0
.24”
)
TB/TI Installation Instructions TG200727
/L 400 mm (15.75”)/S 150 mm (5.91”)
85 m
m (3
.35”
)
57 mm (2.24”)
105 mm (4.13”) 15 mm (0.59”)
130 mm (5.12”)
9.5
mm
(0
.37”
)
27 m
m (1
.06”
)
½” BSPT
2 mm hexagonal socket grub screw (each side)
105
mm
(4.1
3”)
Pockets for use as immersion sensorBrass (POC/B/6)Stainless steel (POC/SS/6)
ACC/DF
50 m
m
(1.9
7”)
6 mm compression fitting3 x 4 mm diam. holes
on a 30 mm (1.18”) PCD(Pitch Circle Diameter)
Mounting flange for use as duct sensor
clip
brass brush
hexagonal socket grub screw
Universal Fitting Kit for immersion sensor use in existing pockets (ACC/UF)
spring
2 TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 2, 08/03/2011
TB/TI Installation Instructions
2 Requirements
InSTallaTIon (continued)
Ensure no stratification (e.g. downstream of mixing dampers, heating coils, cooling coils) otherwise use averaging sensor.
g
f
-40 °C (-40 °F)
+50 °C (+122 °F)
to
-40 °C (-40 °F)
+110 °C (+230 °F)
to
Duct
Duct
H O2
0 %RH 95 %RH
protection :IP67 (NEMA6)
Ensure no stratification (e.g. downstream of mixing valves, junctions)
a b
c
d
-40 °C (-40 °F)
+50 °C (+122 °F)
to
-40 °C (-40 °F)
+110 °C (+230 °F)
to
Immersion
Immersion
measurement range
-30 °C (-22 °F)
+110 °C (+230 °F)
to
(minimum distance from junctions =10xd).
d Immersion
e Immersion
Cl2
Note that POC/SS/6 or POC/B/6 are NOT suitable for use in chlorine rich environments
TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 2, 08/03/2011 3
Installation Instructions TB/TI
3 Install Imersion Sensor
InSTallaTIon (continued)
a2a3(if installing new pocket)
b *Install Sensor into pocket
a
Drill hole for boss Fix threaded boss
*Screw pocket into boss
½” BSPT threaded boss
apply sealent to boss thread
If using compatible pocket
use 2 mm hexagonal socket key
tighten screws
Install pocketa1
c1If using Universal Fitting Kit
Push adaptor onto probe Adjust probe length
*Mount in pocket
if pocket has grub screw, discard spring and clip
clipspring
brass brush
tighten
use 2 mm hexagonal socket key
pocket length
clip engages in groove
probe is forced against end of
tighten screw over bush
c Install Sensor into pocket
c3
c2
if pocket has clip retaining groove, push clip over pocket
*If used for chilled water ensure pocket is sealed around probe or fill pocket with thermally conducting oil to avoid the build up of condensation in bottom of pocket.
use M27 Spanner
4 TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 2, 08/03/2011
TB/TI Installation Instructions
4 Install Duct Sensor
drill and tap 1/8” BSPT
or b3 (for thinner material) use complete mounting flange
3 off pilot holes
either b2 (for thicker material) use compression fitting only
>6 mm
3 off No 6 3/4” s/s self tapping screws
30 mm (1.18”)
<6 mm
either or
b4 adjust depth of probe
(1) tap hole (2) screw in fitting
(1) drill 3 holes
(2) screw on flange (3) mounted flange
either a Direct mount sensor on ducta1 Drill hole in duct
Ø 7 mm (0.28”)
a2 Drill 2 pilot holes
42.5 mm (1.67”)
85 mm (3.35”)
a3
2 off
2 off No 6 3/4” s/s self tapping screws
integral foam gasket
or b Use compression fitting
compression fitting
duct mounting flange
Separate compression fittingb1(1) Loosen nut
(2) Unscrew fitting
InSTallaTIon (continued)
TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 2, 08/03/2011 5
Installation Instructions TB/TI
5 Remove lid 6 Insert cable
7 Wire to controller
8 Replace lid
either use M20 flexible conduit
or use M16 cable gland
Sensor IQ1xx/2xx
COM (0V)IN
polarity independent Analogue input
channel linked for thermistor (T)
terminate screen at IQ end only T
terminal size 0.5 to 2.5 mm2 (14 to 20 AWG)TP/1/1/22/HP/200 (Belden 8761) cable recommended
Note that IP67 (NEMA6) rating is only achieved if the sensor is correctly installed with cable or conduit connection fully tightened.
Sensor IQ30 (0V)
N (in)+ (24 V)
InSTallaTIon (continued)
6 TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 2, 08/03/2011
TB/TI Installation Instructions
10 Set up IQ Sensor Type
9 Configure IQ
InSTallaTIon (continued)
� �
IQ Configuration Manual 90-1533IQ3 Configuration Manual TE200768
� �
or
Thermistor (-30 °C to +110 °C, -22 °F to +230 °F)
It is recommended to use SET (software tool) for the setting of the sensor type module. For all IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers, the following SET Unique Sensor References should be used:
Units: °c °FY Input type 1 (therm V)E Exponent 3U Upper 115 239l Lower -35 -31p Points 20x Ix ox1 0.480 110 2302 0.549 105 2203 0.630 100 2124 0.724 95 2035 0.833 90 1946 0.961 85 1857 1.110 80 1768 1.484 70 1589 1.985 60 14010 2.641 50 12211 3.470 40 10412 4.460 30 8613 6.663 10 5014 7.668 0 3215 8.102 -5 2316 8.482 -10 1417 8.807 -15 518 9.078 -20 -419 9.299 -25 -1320 9.476 -30 -22
Thermistor: Thermistor TBTI (-30 °C to +110 °C) Thermistor TBTI F (-22 °F to +230 °F)
Alternatively set scaling mode to 5 (characterise) and enter scaling manually as defined in the table below. Note that for IQ3, scaling mode and exponent do not need to be set up.
For all other IQ controllers see Sensor Scaling Reference Card TB100521A.
TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 2, 08/03/2011 7
Installation Instructions TB/TI
11 Test System
InSTallaTIon (continued)
∆ TIQ
8 TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 2, 08/03/2011
TB/TI Installation Instructions
Please send any comments about this or any other Trend technical publication to [email protected]
© 2011 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control Systems LimitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control System USA6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trendcontrols.com
DISpoSal
WEEE Directive :At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.
Do not dispose of with normal household waste. Do not burn.