twinsoft 11.06 sp3- release notes€¦ · twinsoft 11.06 sp3- release notes september 12, 2016...

28
TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox MS32-S2 OS version: 1.37.410 TBox LT2 OS version: 1.37.410 MS32 LINUX version: 2.6.27 MS32-S2 LINUX version: 3.12.56 LT2 LINUX version: 3.12.56 MS-CPU32 with OS < 1.29, OpenSSL ver. 0.98.g MS-CPU32 and LT2, OS >= 1.37, OpenSSL ver. 1.0.1.r TBox MS16 OS version: 3.29.735 TBox LITE OS version: 3.34.792 TBox WM, new LP OS version: 3.34.792 TBox LP100, LP200 OS version: 2.00.230 TBox LP 300 OS version: 3.34.792 Flocom OS version: 3.34.792 TWinSoft 11.06 Release notes 1 All new features and corrections require the highest version of OS to run in your CPU. When receiving a TBox CPU, check its current version using TWinSoft doing a: “Communication” → “ RTU Identification”

Upload: others

Post on 23-Aug-2020

18 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

TWinSoft 11.06 SP3- Release notes

September 12, 2016

TWinSoft build number: 1468WebformStudio 2.0 11.06TBox MS32 OS version: 1.37.410TBox MS32-S2 OS version: 1.37.410TBox LT2 OS version: 1.37.410MS32 LINUX version: 2.6.27MS32-S2 LINUX version: 3.12.56LT2 LINUX version: 3.12.56 MS-CPU32 with OS < 1.29, OpenSSL ver. 0.98.g MS-CPU32 and LT2, OS >= 1.37, OpenSSL ver. 1.0.1.rTBox MS16 OS version: 3.29.735TBox LITE OS version: 3.34.792TBox WM, new LP OS version: 3.34.792TBox LP100, LP200 OS version: 2.00.230TBox LP 300 OS version: 3.34.792Flocom OS version: 3.34.792

TWinSoft 11.06 Release notes 1

All new features and corrections require the highest version of OS to run in your CPU.When receiving a TBox CPU, check its current version using TWinSoft doing a:

“Communication” → “ RTU Identification”

Page 2: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

Table of contents

IMPORTANT – TWINSOFT INSTALLATION.....................................................................................................3

TBOXUSB DRIVER.................................................................................................................................................3

SOME TBOX'S HAVE USB PORT THAT CAN BE USED FOR PROGRAMMING. A DRIVER IN WIDOWS IS REQUIRED. WHEN CONNECTED TO INTERNET, THE DRIVER IS AVAILABLE FROM WINDOWS UPDATE..........................................................................................3

IF NOT CONNECTED TO INTERNET, A DRIVER (WINDOWS SIGNED) CAN BE DOWNLOADED FROM HTTP://HELPDESK.SERVELEC-TECHNOLOGIES.COM → DOWNLOAD → TBOX → SOFTWARE → TBOXUSB DRIVER.............................................................3

1. SYSTEM REQUIREMENT............................................................................................................................4

1.1. HELP FILES UNDER WINDOWS VISTA AND HIGHER................................................................................................4

2. UPLOAD OS.........................................................................................................................................4

2.1. UPLOAD OS / KERNEL WITH -MS32 - LT2.........................................................................................................4

2.2. UPLOAD OS / LOADER WITH -MS16, -LT, -WM, -LP..........................................................................................5

2.3. UPLOAD OS WITH -TBOX CPU3.......................................................................................................................5

3. KNOWN ISSUES......................................................................................................................................6

4. NEW FEATURES.....................................................................................................................................7

4.1. NEW CONFIGURATION FROM THE WIZARD (MS-CPU32 AND LT2)...........................................................................7

4.2. NEW SECURITY WIZARD...................................................................................................................................84.2.1.Firewall.......................................................................................................................................................9

4.2.2.HTTPS.......................................................................................................................................................10

4.2.3.SSH............................................................................................................................................................10

4.3. OPTION TO STORE WEBFILES ON SD CARD.........................................................................................................11

4.4. NEW ANALOG SYSTEM VARIABLE “HTTPSESSION”...............................................................................................12

4.5. NEW DIGITAL SYSTEM VARIABLE......................................................................................................................12

4.6. WEBFORM STUDIO 2.0.................................................................................................................................134.6.1.New object: Sound...................................................................................................................................13

4.6.2.Image: URL property................................................................................................................................14

4.6.3.Rectangle: Edge Style Property................................................................................................................15

4.6.4.List of Alarms: Translation of the Column................................................................................................16

4.7. NEW REMOTE DEVICE: RM2..........................................................................................................................16

4.8. REPORT STUDIO: MULTIPLE COLUMN TABLE.......................................................................................................17

4.9. OPENVPN: FIX IP ADDRESS CONFIGURATION FOR CLIENTS....................................................................................18

5. NEW SMS SERVER ENTRIES....................................................................................................................19

6. FIXES & ENHANCEMENTS........................................................................................................................20

6.1. IN TWINSOFT 11.06.1468 -SP3 + OS 1.37.410...........................................................................................20

6.2. IN TWINSOFT 11.06.1466 -SP2 + OS 1.37.410...........................................................................................21

6.3. IN TWINSOFT 11.06.1464 -SP1+ OS 1.37.410............................................................................................22

6.4. IN TWINSOFT 11.06.1463 + OS 1.37.409...................................................................................................23

TWinSoft 11.06 Release notes 2

Page 3: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

IMPORTANT – TWinSoft Installation.

TWinSoft Suite requires some windows components to run properly. When required, these components are installed during setup if connected to Intenet.

With old versions of Windows, Windows Installer 4.5 is a pre-requesite to TWinSoft installation. If connected to Internet it will be downloaded, then installed. After that a rebootis required and TWinsoft setup will keep on running upon restart.

The following versions of Windows are concerned:• Windows XP SP2, XP SP3• Windows Server 2003 SP1, 2003 SP2• Windows Vista, Vista SP1• Windows Server 2008

If not connected to Internet, the package can be donwloaed at the following url:

Runtime : following three packages are required with all versions of Windows:

VC++ 2008 :http://download.microsoft.com/download/5/D/8/5D8C65CB-C849-4025-8E95-C3966CAFD8AE/vcredist_x86.exe

VC++ 2010 :http://download.microsoft.com/download/1/6/5/165255E7-1014-4D0A-B094-B6A430A6BFFC/vcredist_x86.exe

.Net 3.5 :http://download.microsoft.com/download/c/d/c/cdc0f321-4f72-4a08-9bac-082f3692ecd9/DotNetFx35Client.exe

.Net 3.5 for Windows 8 or Windows 8.1: Off line installation is not possible :

FR: https://msdn.microsoft.com/fr-fr/library/hh506443%28v=vs.110%29.aspx

US: https://msdn.microsoft.com/en-us/library/hh506443%28v=vs.110%29.aspx

Installer : the one corresponding to the version of Windows OS:

Installer 4.5 (XP x86) :

http://download.microsoft.com/download/2/6/1/261fca42-22c0-4f91-9451-0e0f2e08356d/WindowsXP-KB942288-v3-x86.exe

Installer 4.5 (XP/Server 2003 x64) :

http://download.microsoft.com/download/2/6/1/261fca42-22c0-4f91-9451-0e0f2e08356d/WindowsServer2003-KB942288-v4-x64.exe

Installer 4.5 (Vista/Server 2008 x86) :

http://download.microsoft.com/download/2/6/1/261fca42-22c0-4f91-9451-0e0f2e08356d/Windows6.0-KB942288-v2-x86.msu

Installer 4.5 (Vista/Server 2008 x64) :

http://download.microsoft.com/download/2/6/1/261fca42-22c0-4f91-9451-0e0f2e08356d/Windows6.0-KB942288-v2-x64.msu

Installer 4.5 (Server 2003 x86) :

http://download.microsoft.com/download/2/6/1/261fca42-22c0-4f91-9451-0e0f2e08356d/WindowsServer2003-KB942288-v4-x86.exe

TBoxUSB driver

Some TBox's have USB port that can be used for programming. A driver in Widows is required. When connected to Internet, the driver is available from Windows update.

If not connected to Internet, a driver (Windows signed) can be downloaded from http://helpdesk.servelec-technologies.com → Download → TBox → Software → TBoxUSB driver

TWinSoft 11.06 Release notes 3

Page 4: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

1. System Requirement

TWinSoft runs under Windows XP, VISTA, W7, W8, W2012 (see above for pre-requesites)

Windows XP is not supported anymore by Microsoft since April 2014

1.1. HELP files under Windows VISTA and higher

Help files of TWinSoft are under the format .hlp and requires winhelp32.exe. It is not supported anymore in Windows VISTA, W7 and W8. It must be installed manually, from the web site:

http://support.microsoft.com/kb/917607/en-us

2. Upload OS

Some new features and corrections apply to TWinSoft only or to OS only. Some concern both TWinSoft and OS.

In order to take benefit of all those features, you need to upload the new OS in your RTU.From the main menu of TWinSoft: ‘Communication’ -> ‘Send to TBox’ -> ‘Operating system’,select the higher version.

We advise to upload the OS locally and with an empty program.

2.1. Upload OS / Kernel with -MS32 - LT2

The 32 bits RTU (MS32, -LT2) runs on LINUX, several libraries and drivers.New Operating System may also require uploading of LINUX component(s). Version of the different modules is checked automatically when uploading the OS.

As of TWinSoft 10.02 and OS 1.06.xxx,TBOX MS32 supports direct uploading of LINUX module(s) from TWinSoft, including handling of versions.In order to get to OS 1.06.xxx or higher, you need first to upload the intermediate OS 1.05.55During upload from 1.05 to 1.06 or higher, current Tag values will be lost (due to the new organization of Tags to support TEXT Tags)If generating Pack&Go file, the same sequence needs to be achieved.

When OS 1.06 or higher has been uploaded, it is not possible to download to a lower version.

Upload to OS 1.06.xx and higher is only possible as of OS 1.04.xx and CPU shipped as of February 2008.With lower version of OS, the CPU must be sent back to your distributor

TWinSoft 11.06 Release notes 4

Page 5: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

To upload from OS 1.06 to 1.09 or higher, use the following sequence:- upload from 1.06 to 1.08- upload from 1.08 to 1.09- upload from 1.09 to any higher OS

As of TWinSoft 10.04 and OS 1.09.xxxLINUX Kernel is automatically uploaded if needed. We do not advise you upload LINUX kernel through modem, GSM or GPRS connections.

As of TWinSoft 10.07 and OS 1.17.xxxA new procedure of package, OS and application uploaded assures more reliability.– It works when OS 1.17 runs already in the TBox, then not during the first upload.– In case a downgrade to OS < 1.17 is required, it can only be done using TWinSoft 10.07

or higher; then a lower version of TWinSoft can be used with lower version of OS.

As of TWinSoft 11.01-SP1 and OS 1.29.314– With these versions, TWinSoft updates also cURL and OpenSSL libraries.

It is not allowed from then to downgrade <= 1.23.

2.2. Upload OS / Loader with -MS16, -LT, -WM, -LP

With TBOX MS16 , TBOX LITE, TBOX WM, TBOX LP a new Loader might also be available.When uploading OS, if TWinSoft detects the loader in the RTU is older, it will prompt you toupload the new version of loader: say YES !

2.3. Upload OS with -TBox CPU3

NOTE: with TBOX CPU-3, OS 5499 should only be used to upgrade from 54xx to 55xx withCPU shipped as of August 2005.

TWinSoft 11.06 Release notes 5

Page 6: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

3. Known Issues

TMA files support maximum 247 Sampling TablesAbove this quantity, the tables will not be included into the TMA file.No problem to retrieve more than 247 tables with TView using “Download Scheduling”.

TBox Dial it! under VISTA, W7 and W8This utility, used to dial to TBox from IE to display Webforms, does not work under VISTA and Windows 7

You have now to use TConnect, the standard tool to access TBox Webform, through modem, GPRS or Ethernet.See http://helpdesk.servelec-semaphore.com

CameraA camera with Ethernet port and TCP/IP protocol can be connected to TBox. Working with TBOX MS16 and TBOX LITE, there are some camera time out issues we cannot bypass. It is due to the mechanism of data transfer of some camera (frames sent by half packet, without known reason). This limit today to use to camera with slow image size, like D-LINK DCS900, or AXIS 207.

Working with TBOX MS32 or TBOX LT2 as there is much more resource and it runs LINUX, we don't encounter those problems.

% in WebForms 1.0- The character % can be used when displaying Tag value to select predefined format. For

instance: %V (to display the value), %U (to display the unit), %3.2f (to fix the display of Floating point variable), ...

- If you want to display the character %, you have to indicate %%.Up to TWinSoft 10.03, a mistake in using the character % had no effect.

- As of TWinSoft 10.03 and a new development environment (VS2008), a new “C” library is automatically used which requires proper use of %.

TWinSoft 11.06 Release notes 6

Page 7: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

4. New Features

4.1. New Configuration from the Wizard (MS-CPU32 and LT2)

These new Wizard windows help you in configuring the modem IP configuration (APN) and a VPN configuration through TConnect, the “facilitator” of TBox connections.

3G modem: APN and PIN code:

VPN configuration through TConnect:

TWinSoft 11.06 Release notes 7

Page 8: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

4.2. New Security Wizard

With the opening of TBox to the IT world, it becomes crucial to reinforce access protection and data encryption.

A new sequence of wizards helps you in configuring three features that are concerned by cyber security:

– Firewall– HTTPS– SSH

When sending your application you are informed on the status of those three features:

To modify one or more of them, click “Security Wizard”:

TWinSoft 11.06 Release notes 8

Page 9: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

According to the features already configured, click next to carry on with configuration:

4.2.1.FirewallYou can activate the firewall (all incoming IP will be blocked) and define some basic exceptions to filter access to TBox.

More exceptions can be configured in TWinSoft folder “IP Security” → “Firewall” → “Input”.

Click “Next”.

TWinSoft 11.06 Release notes 9

Page 10: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

4.2.2.HTTPSHTTPS secures communication from a browser. It encrypts all communication from/to TBox.

Click “Next”

4.2.3.SSHSSH protocol is used to access TBox in console mode, at LINUX level.

Click “Next”

TWinSoft 11.06 Release notes 10

Page 11: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

Your TBox is secured.

4.3. Option to store WebFiles on SD card

This option requires a SD card in TBox ...Available for MS-CPU32 and LT2.When selected, only webfiles that have changed (based on md5 signature on the files) will be updated into TBox, upon TWinSoft sending of the application.

TWinSoft 11.06 Release notes 11

Page 12: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

4.4. New Analog System Variable “HttpSession”

This variable indicates the number of users that have logged in HTTP to TBox.

This requires HTTP protection to be activated as well as HTTP session Authentication:

We do not use sockets as several sockets might be opened/closed during one HTTP session.

4.5. New Digital System Variable

These variable indicates the presence of a SD card, and gives an indication on the volume of data present on the card, when the card is full at 90%.To remove files on the SD card, you can connect using a FTP client and delete files. The FTP protection must be activated to delete files on the SD card (see in TWinSoft help → How to use FTP Server)

TWinSoft 11.06 Release notes 12

Page 13: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

4.6. WebForm Studio 2.0

4.6.1.New object: SoundThis new object is based of HTML5 audio Tag.

The files supported are .MP3 and .WAV.

MIND that wave files are not supported by Internet Explorer.However, all browsers support MP3, which then should be preferred.

You declare sound file as property of the object. The file will be automatically sent to TBox.The object does not appear in runtime.

To activate the sound, you will use script:

It can be on a any Tag on the webform or from the “TagToWatch” if the Tag is not visible.

TWinSoft 11.06 Release notes 13

Page 14: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

4.6.2.Image: URL property

Instead of declaring an image present in TBox, you can link to a URL.Check TBox can access this URL; if it is a URL on Internet, TBox must be able to access Internet.

MIND the special HTML character.If the link contains characters like “&” or “<”, … it has to be replaced by its HTML entity.

Some examples:

Punctuation HTML Entity(case sensitive)

ISO Latin-1code

name or meaning

– &ndash; &#8211; en dash

— &mdash; &#8212; em dash

" &quot; &#34; double quote

Symbols

& &amp; &#38; ampersand

© &copy; &#169; copyright

> &gt; &#62; greater than

< &lt; &#60; less than

€ &euro; &#8364; Euro

£ &pound; &#163; British Pound Sterling

° &deg; &#176; Degree

Source: https://www.utexas.edu/learn/html/spchar.html

TWinSoft 11.06 Release notes 14

Page 15: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

The URL can also be used, as it is, with the event “OnClick” and the method Webforms.Goto();

4.6.3.Rectangle: Edge Style Property

TWinSoft 11.06 Release notes 15

Page 16: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

4.6.4.List of Alarms: Translation of the Column.

The text of the columns is available for translation, or any customization:You type the new text corresponding to each column.

4.7. New Remote Device: RM2

A new remote device is available in the list:

When adding an RM2 device, you can select the model of RM2 (-530, -532, -540 or -542).When creating the device, you are prompted by TWinSoft to create the Tags and the ModBus transactions:

TWinSoft 11.06 Release notes 16

Page 17: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

4.8. Report Studio: Multiple Column Table

This object allows now maximum 32 columns.It still must be data of sampling tables with identical size and period.

TWinSoft 11.06 Release notes 17

Page 18: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

4.9. OpenVPN: Fix IP Address Configuration for ClientsWhen requiring fix IP addresses for a client, the configuration is applied in the “Server” only.A file in the Server, with the name of the client used to create the certificates contains the IP address to give to the client when connecting.

This is now possible through a new command in “Server” configuration file.This is not a standard behavior! There is a preprocess of advanced parameters to allow this... And it requires some manual configuration.

The new command allowing to create an external configuration file is entered in the “Advanced” parameters:

<file name="/tmp/openvpn/my_config_file">content of my file</file>

This command will create a file called my_config_file in /tmp/openvpn/ and with associatedcontent.Due to security, files can be created in this directory only. It is also not allowed to create sub-directoriesThe file is re-created on startup, no issue if this is in /tmp, it will be re-created all the time (even in case of reboot).

So, to provide a fix IP to clients, we have to create the file associated to each client, with the command ifconfig-push into it.And reference its path with the standard command client-config-dir..

Example:With a OpenVPN client named “RTU1”:

TWinSoft 11.06 Release notes 18

Page 19: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

5. New SMS Server Entries

- Add Czeck Republic: "O2 -> GSM" - Add Mexico: "Telcel -> GSM" - Add Malaysia: "TuneTalk -> GSM" - Add Malaysia: "U Mobile -> GSM"

For TAP and UCP protocols, SYNCHRO=30 has been reduced to SYNCHRO=20

TWinSoft 11.06 Release notes 19

Page 20: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

6. Fixes & Enhancements

6.1. In TWinSoft 11.06.1468 -SP3 + OS 1.37.410

FPGA (ref. 5416): MS-CPU32-S2 + MS-8AIVC & MS-COMBOWith MS-CPU32-S2 running with either MS-8AIVC or MS-COMBO together with serial communication on the BUS (MS-SERIAL, MS-GSM-3G, …), the reading of analog inputs might be corrupted. This is very intermittent. It does not happen with MS-CPU32.Correction applied to the code of FPGA and LINUX ADC driver.In order to apply the correction to TBox, one needs to upload OS, even if it is the same version of the one running in TBox.

After update of OS, you can check the 2 modules concerned have been updated, doing a “RTU Identification” → “Advanced...”:

TWinSoft with OS-C (ref. 5400): SetupWhen using report with multiple columns table, with TBox-MS16, TBox-LITE, TBox-WM or TBox-LP, TWinSoft 11.06.1466 generates a compilation error.Corrected.

TWinSoft MS-CPU32-S2 (ref. 5315): Communication PortsRenumbering of communication ports (COMx), taking USB ports into account.COM1, 2, 3, 4, then USB1, 2, 3 are now COM5, 6, 7, then following ports COM8, COM9, …You might have to check add-on configuration if it uses communication ports > COM4

TWinSoft 11.06 Release notes 20

Page 21: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

6.2. In TWinSoft 11.06.1466 -SP2 + OS 1.37.410

TWinSoft (ref. 5373): SetupIssue during WebFormViewer installation. Registration method has been changed.

TWinSoft (ref. 5372): SetupIssue during TWinSoft installation if user's name uses different characters set as the Windows language (like name in Hebrew and Windows in UK).Corrected.

TWinSoft (ref. 5371): RM2Issue with ModBus Transactions created for RM2. Tags associated to DO's are configured as DIs.Corrected.

TWinSoft (ref. 5354): BridgeSending a program to communication ports configured as bridge, TWinSoft returns a message “RTU send failed”.Corrected.

TWinSoft (ref. 5353): Program SourcesRetrieving sources through SSH works only once.Corrected.

TWinSoft (ref. 5347): Program SourcesRetrieve program sources does not work anymore (Seen with CPU3 and MS-CPU16).Corrected.

TWinSoft (ref. 5342): ConversionConversion form MS-CPU16 to MS-CPU32-S2 is now possible.

TWinSoft (ref. 5339): French TranslationIn RTU Indentification, installation status “Iddle” is now translated “Terminé”.

TWinSoft (ref. 5335): Copy/PasteCopy/Paste of Remote Devices does not work when the name is composed of 2 characters, like D1. TWinSoft crashes after D9.Corrected.

TWinSoft (ref. 5323): Import/ExportImport/Export of Tags for CPU3: initial value not supported.Corrected.

TWinSoft (ref. 5238): AutomationTWinSoft might crash when 2 sessions are opened.Automatic periodical recovery has been disabled when running TWinSoft trough Automation.

TWinSoft 11.06 Release notes 21

Page 22: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

6.3. In TWinSoft 11.06.1464 -SP1+ OS 1.37.410

TBox-MS32 / LT2 (ref. 5327): GSMWhen connected in IP and sending SMS, does not reconnect in IP after the sending of SMS.Corrected.To prevent futur issue because of this problem, OS 1.37.409 has been removed from the setup

TBox-MS32 / LT2 (ref. 5325): TConnectUnable to login to TConnect when HTTP are fragmented.Corrected.

TBox-MS32 / LT2 (ref. 5324): HTTPS postHTTP post alarm does not work in secure communication (HTTPS).Corrected.

TBox-MS32 / LT2 (ref. 5258): DiagnosticMake the url to diagnostic to be relative. This allows to display diagnostic from TConnect for instance.

TWinSoft 11.06 Release notes 22

Page 23: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

6.4. In TWinSoft 11.06.1463 + OS 1.37.409

TBox-MS32 / LT2 (ref. 5275): GSMGSM fails to connect to GPRS/3G when declaring a fix IP. Issue appeared with OS 1.35 and new implementation of PPP.Corrected.

TBox-LP450 (ref. 5273 - 5200): GSM + PIN codeWith PIN code, modem does not initialize, as of 3.34.792. Due to a time too short.ModenPintime has been increased to 10 seconds for HiLo GSM used with LP450.

TBox-MS32 / LT2 (ref. 5270 - 5245): GSMIssue with close / start of PPP session, for instance when APN is not available.Corrected.

TWinSoft (ref. 5267): SetupSetup may fail due to disk1.cab not found.Corrected.

WebForm Studio 2.0 (ref. 5265): DisplayDepending on the Windows version, browser version, country of installation, Webforms 2.0 do not display anymore. Due to a verification on the content-length of the web file.Corrected.

WebForm Studio 2.0 (ref. 5261): ButtonChoice menu with “Special characters” (not LATIN) does not display in the browser.Corrected.

TBox-MS32 / LT2 (ref. 5275): InitSMSTBox crash if there is no +CPMS command (used to checked the different memories of SIM card).Corrected.

TBox-MS32 / LT2 (ref. 5257): OpenSSLVersion 1.0.1r.

TBox-MS32 / LT2 (ref. 5256): OpenVPNOpenVPN has been upgraded to version 2.3.10 which supports TLS ver. 1.2.

TBox-MS32 / LT2 (ref. 5255): ModBus“Invalid timer handler” message seen in log when the option “Modbus TCP protection on socket” is active.Corrected

TWinSoft (ref. 5240): ConversionWrong conversion of PT inputs.Corrected.

TWinSoft 11.06 Release notes 23

Page 24: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

WebForm Studio 2.0 (ref. 5239): iFrameEvent “OnClick” is not allowed on an iFrame.It has been removed.

TWinSoft (ref. 5236): TConnectImpossible to login when opening a document which is protected.Corrected.

TWinSoft (ref. 5234): ConversionDigital filtrers are not converted.Corrected.

TWinSoft (ref. 5233): AddonsTWinSoft compares the version of the addon in TWinSoft directory in regards to the one in the directory of the application. When it is newer in TWinSoft directory a warning appears at compiltaiton in the Results window.

WebForm Studio 2.0 (ref. 5232): Multistate ImageVisibility level not handled properly on Multistate image object.Corrected.

TWinSoft (ref. 5230): CompilationWrong max. calculation of SRam capacity: 1 Mb is 1024 * 1024 → 1048576 bytes.Instead of previously 1024000Corrected.

TBox-MS32 / LT2 (ref. 5228): ModBus TransactionsFails to read block of 62 “Float” and 125 “Word”.Corrected.

TWinSoft (ref. 5223): AutomationChanging a Tag format “16bits” to “32bits”, one should adapt address to have an even address.Corrected.

TWinSoft (ref. 5222): CertificatesWith advice from the certifying company, the certificate of executables have been updated. As of January 1, 2017, old version will be blocked by Windows 7, 8,....Corrected.

TWinSoft (ref. 5219): ConversionInactivity timeout of modem is not converted.Corrected.

TWinSoft (ref. 5214): AutomationDriver OSC cannot be configured with an IP port.Corrected.

TWinSoft 11.06 Release notes 24

Page 25: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

TWinSoft (ref. 5211): Conversion from CPU3Alarms with both edges (not available with LITE, MS, …) are not converted. A warning is generated in the log. One should create two alarms, one with positive edge, one with negative edge.

TWinSoft (ref. 5210): ConversionFloat variable with Initial value with decimal may not be converted properly according to regional settings of PC (decimal character).Corrected.

TWinSoft (ref. 5208): ConversionConversion of Analog Input from LT -> LT2 does not keep the format of analog signals.Corrected.

TWinSoft (ref. 5207): ConversionConverting LT → LT2, put a warning for relay which cannot be converted.

TBox-MS32 / LT2 (ref. 5203): ModBus TransactionsImprovement of TCP transactions in case of poor connection.Corrected.

TWinSoft (ref. 5199): ExportTWinSoft hangs-up exporting Tags.Corrected.

TWinSoft (ref. 5182): CompilationIssue with compiling a program of CPU3 developed in TWinSoft 9.03.Corrected.

TWinSoft (ref. 5180): ConversionConverting MS32 -MS32-S2, remove the message related to libraries which is useless."This program uses 1 external library""You need to convert theses libraries ... blabla …"Corrected.

TBox-MS32 / LT2 (ref. 5172): Alarm in Webform 2An alarm can be ack'ed from the list of alarm in WF2. This is not possible when the system variable “AlaCur” has been tagged.Corrected.

TWinSoft (ref. 5171): AutomationPhone number in Recipient is limited to 16 characters when it is allowed up to 20 characters in TWinSoft. Corrected, except with CPU3/leacy LP where it is still limited to 16.

TWinSoft 11.06 Release notes 25

Page 26: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

TWinSoft (ref. 5160): VPNCreating a VPN by right-clicking in the list, the option “Import OpenVPN Configuration” is missing. Corrected.

WebForm Studio 2.0 (ref. 5148): TagToWatchScript in TagToWatch is not executed when value is changed from a button.Corrected.

TWinSoft (ref. 5143): AlarmsWhen a pager service is not available, TWinSoft generates an error opening any alarm recipient.Corrected.

WebForm Studio 2.0 (ref. 5116): Text TagDepending on configuration of “decimal” character in “localization” setting in TWinSoft a “.” can be transformed in a “,” in a TExt Tag.Corrected.

TBox-MS32 / LT2 (ref. 5109): GSMSwitch Off modem when o SIM card is detected.New Modem States:- 254 : Power Off (if available) in progress.- 255 : Modem stopped and Powered Off (if available).

TWinSoft (ref. 5102): DHCPSending an application through an Ethernet port which is configured in DHCP, TWinSoft loses communication at the end of sending and TBox does not restart.Corrected.

MIND to check the option in PC Setup: “Don't change IP address...”

After sending, TWinSoft launches TBox and disconnects, with the following message:

TWinSoft 11.06 Release notes 26

Page 27: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

TBox-MS32 / LT2 (ref. 5090): GPSIncorrect positionning (longitude and latitude) with some GPS with high resolution.Corrected.

TWinSoft (ref. 5082): Watch WindowSending Tag in Watch Window from “Alarm Conditions” does not always send the selected Tag.Corrected.

TWinSoft (ref. 5054): backupTWinSoft backup document not handled as expected.As of TWinSoft 11.06, the .tbk is saved before the .tws is saved.

TWinSoft (ref. 5054): CPU3When creating a new application with COM4, COM4 is always protected.Corrected.

TWinSoft (ref. 4984): DataloggingSome datalogging configuration is not saved when done from the Tag properties → Datalogging.Corrected.

TWinSoft (ref. 4940): AutomationCompileProgress callback's are not called in case of Plug&Go and Pack&Go.Corrected.

WebForm Studio 2.0 (ref. 4861): Timeout MessageWhen a timeout has been reached downloading data, a message appears in top of the WebForm:

TWinSoft 11.06 Release notes 27

Page 28: TWinSoft 11.06 SP3- Release notes€¦ · TWinSoft 11.06 SP3- Release notes September 12, 2016 TWinSoft build number: 1468 WebformStudio 2.0 11.06 TBox MS32 OS version: 1.37.410 TBox

WebForm Studio 2.0 (ref. 4755): GridFormat of Tags not respected like configured in Presentation. It concerns the number of decimals of Float and digital states.Corrected.

TWinSoft (ref. 4696): ReportUnique file name of report does not support special characters, like “|”. This might not be supported by FTP or Mail server.TWinSoft now puts a warning in the result tab when used.

TWinSoft (ref. 4685): LP450Wrong display of AI in the resources. AI Tagged does not appereared with the Analog logo in the resources.Corrected.

TWinSoft (ref. 4488): ConversionInputs not always converted as Inputs, but as Outputs.Corrected.

TWinSoft (ref. 4404): Pack&GoAfter Pack&Go including libraries, TWinSoft indicates a difference between running application and the one opened, but nothing has changed.Corrected.

TWinSoft (ref. 4338): Cross ReferenceFrom the Watch Window you have now access to the Cross Reference menu by right-clicking the Tag.

TWinSoft (ref. 3615): Simulation ModeOne cannot write into validity bit of analog inputs when running TBox in “simulation”mode.Corrected.

TBox-MS16 (ref. ): TCPIPProvide API with TCP context for driver “C”. Needed with driver IEC-60870-104 (1.00.21) which requires OS 3.29.735

TWinSoft 11.06 Release notes 28