Motor SFU+FUSE LINK (DIN) SFU+F USE LINK (BS) Contractor Over-Load Id Output Fuse Fuse Fuse Fuse Relay Range (W Amps ' SFU type Rating Type Relay Type Rating TYP~ TY P@ 0.37 1.15 OESA 00-32 6 OFAFNOOO OESA 32G1 6 OFFNA2 A9 TA25DU1.4 1-1 4 0.55 1.4 OESA 00-32 6 OFAFNOOO OESA 32Gl 6 OFFNAP A9 TA25DU1.8 1 3-1.8 0.75 2 OESA 00-32 6 OFAFNOOO OESA 32G1 10 OFFNA2 A9 TA25DU2.4 1.7-2 4 1.1 2 5 OESA 00-32 10 OFAFNOOO OESA 32G1 10 OFFNA2 A9 TA25DU3 1 2.2-3.1 1.5 3.5 OESA 00-32 10 OFAFNOOO OESA 32G 1 16 OFFNA2 A9 TA25DU4 0 2.84 0 2.2 5 OESA 00-32 16 OFAFNOOO OESA 32G1 16 OFFNA2 A9 TA25DU6 5 4 5-6 5 3 7 7.5 OESA 00-32 20 OFAFNOOO OESA 32G1 20 OFFNA2 A9 ' TA25DU8.5 6.0-8.5 4 8.4 OESA 00-32 20 OFAFNOOO OESA 32G1 20 OFFNA2 I A9 TA25DU 11 7 5-11 5 5 11 OESAOO-32 25 OFAFN~OO OESA32G132 OFFNA2 A12 TA25DU14 10-14 7.5 14 OESA 00-32 32 OFAFNOOO OESA 32G1 32 OFFNA2 A16 TA25DU19 13-19 1 I 2 1 OESA 00-32 50 OFAFNOOO OESA 63G1 50 OFFNA3 A26 TA25DU25 18-25 15 28 OESA 00-63 63 OFAFNOOO OESA63G1 63 OFFNA3 A30 TA25DU32 24-32 18.5 35 OESA 00-63 63 OFAFNOOO OESA lOOGl 80 OFFNA4 A40 TA75DU42 2942 22 40 OESA 00-100 80 OFAFNOO OESA IOOGl 80 OFFNA4 A50 TA75DU52 36-52 30 55 OESAOO-100 100 OFAFNOO OESA I OOGl 100 OFFNA4 A63 TA75DU63 45-63 37 66 OESA 00-1 25 125 OFAFNOO OESA 100G1 125 OFFNA4 A63 TA75DU80 60-80 200 340 OESA 630D3PL 500 OFAFN3 OESA 63083PL 400 OFFNC2 AF400 Ti450DU400 280400 250 42 5 OESA 630D3PL 630 OFAFN3 OESA 63083PL 500 OFFNC2 AF580 T9OODU500 355-500 , 295 500 OESA 630D3PL 630 OFAFN3 OESA 630B3PL 560 OFFNC2 AF580 T900DU650 465-650 I) Above recommendation under test 2) Starting current is considered to be 6 times the rated current for a period of 6.0 seconds.

Upload: tsyamprasad

Post on 08-Mar-2015

2.632 views

Category:

Documents


21 download

TRANSCRIPT

Page 1: Type -2 Co-Ordination Chart of Abb

Motor SFU+FUSE LINK (DIN) SFU+F USE LINK (BS) Contractor Over-Load Id Output Fuse Fuse Fuse Fuse Relay Range

(W Amps ' SFU type

Rating Type Relay Type Rating T Y P ~ TY P@ 0.37 1.15 OESA 00-32 6 OFAFNOOO OESA 32G1 6 OFFNA2 A9 TA25DU1.4 1-1 4

0.55 1.4 OESA 00-32 6 OFAFNOOO OESA 32Gl 6 OFFNAP A9 TA25DU1.8 1 3-1.8

0.75 2 OESA 00-32 6 OFAFNOOO OESA 32G1 10 OFFNA2 A9 TA25DU2.4 1.7-2 4

1.1 2 5 OESA 00-32 10 OFAFNOOO OESA 32G1 10 OFFNA2 A9 TA25DU3 1 2.2-3.1

1.5 3.5 OESA 00-32 10 OFAFNOOO OESA 32G 1 16 OFFNA2 A9 TA25DU4 0 2.84 0

2.2 5 OESA 00-32 16 OFAFNOOO OESA 32G1 16 OFFNA2 A9 TA25DU6 5 4 5-6 5

3 7 7.5 OESA 00-32 20 OFAFNOOO OESA 32G1 20 OFFNA2 A9 ' TA25DU8.5 6.0-8.5

4 8.4 OESA 00-32 20 OFAFNOOO OESA 32G1 20 OFFNA2 I A9 TA25DU 11 7 5-11

5 5 11 OESAOO-32 25 OFAFN~OO OESA32G132 OFFNA2 A12 TA25DU14 10-14

7.5 14 OESA 00-32 32 OFAFNOOO OESA 32G1 32 OFFNA2 A16 TA25DU19 13-19

1 I 2 1 OESA 00-32 50 OFAFNOOO OESA 63G1 50 OFFNA3 A26 TA25DU25 18-25

15 28 OESA 00-63 63 OFAFNOOO OESA63G1 63 OFFNA3 A30 TA25DU32 24-32

18.5 35 OESA 00-63 63 OFAFNOOO OESA lOOGl 80 OFFNA4 A40 TA75DU42 2942

22 40 OESA 00-100 80 OFAFNOO OESA IOOGl 80 OFFNA4 A50 TA75DU52 36-52

30 55 OESAOO-100 100 OFAFNOO OESA I OOGl 100 OFFNA4 A63 TA75DU63 45-63

37 66 OESA 00-1 25 125 OFAFNOO OESA 100G1 125 OFFNA4 A63 TA75DU80 60-80

200 340 OESA 630D3PL 500 OFAFN3 OESA 63083PL 400 OFFNC2 AF400 Ti450DU400 280400

250 42 5 OESA 630D3PL 630 OFAFN3 OESA 63083PL 500 OFFNC2 AF580 T9OODU500 355-500

, 295 500 OESA 630D3PL 630 OFAFN3 OESA 630B3PL 560 OFFNC2 AF580 T900DU650 465-650

I ) Above recommendation under test 2) Starting current is considered to be 6 times the rated current for a period of 6.0 seconds.

Page 2: Type -2 Co-Ordination Chart of Abb

Motor MCCB Contactor Thermal release

Rated Rated Setting of ,+ a.

power current the magnetic Line Delta Star Type code reference

Type 'Ode

reference [A1 Pe [ k w le [A] release [A]

Motor MCCB a Contactor Thermal release

Rated Rated Setting of Power current Type code fhe magnetic Line Delta Star Type code

reference reference [A1 [ k w le [A] release [A]

Star delta Type 2 - Normal starting @ 400/415 V - 35 kA

Star delta Type 2 - Normal starting @ 400/415 V - 50 kA

36136 Ref : ABB LVP 01.06.2010