CORFLEX ® TYPE MC-HL POWER, CONTROL & INSTRUMENTATION CABLES

Upload: vudung

Post on 14-Mar-2018

214 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

CORFLEX®

TYPE MC-HL POWER, CONTROL &INSTRUMENTATION CABLES

Page 2: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

Nexans AmerCable believes the information presented throughout this catalog to be reliable and current. All information is subject to change without notice. The information listed is approximate, and is presented only as a guide for product selection. We make no claims or warranties for the suitability of any product for any particular application.

El Dorado, Arkansas

Made in America

INDEXCorflex MC-HL Instrumentation- Pairs and Triads (600V*)................................... 1 - 2

Power and Control Cables- Multi-conductor w/ Bare Ground(s) (600V*) ...... 3 - 4

Composite Power and Control Cables- Multi-conductor w/ Bare Ground (600V*).......... 5 - 6

Power Cables-600V* 3 and 4 Conductors with Bare Ground(s) .... 7 - 8

Medium Voltage Cables- 5kV - 133% Insulation Levels ........................... 9 - 10

- 8kV - 100% Insulation Level

- 15kV - 100% & 133% Insulation Levels .......... 11 - 12

Pulling Instructions ........................................... 13

Conductor ID ..................................................... 14

*600V/1000V Marine Shipboard Cable

Flame RetardantAll CORFLEX cablespass UL 1685 and IEEE383 vertical tray firetests at 70,000 BTU/hr,IEC 60332-3 category Afire test, IEEE 1202and CSA FT4.

CORFLEX rated lessthan 5 kV also passes

ICEAT-29-520 fire test at210,000 BTU/hr.

ArmorContinuous corrugated

and welded,impervious aluminum

sheathwith no more than0.2% trace copperprovides completeprotection against

liquid and gas ingress.

CORFLEX® Cables

CORFLEX cables are designed for reliable performance in a variety of oil and gasdownstream, industrial, commercial andutility applications which require anexternally armored cable.

Nexans CORFLEX MC-HL and MV-105 or MC-HL cables can be installed inhazardous locations designated Class I,II & III, Divisions 1 & 2 as per NEC 2014(HL Rated).

CORFLEX®

TYPE MC-HL POWER, CONTROL &INSTRUMENTATION CABLES

Page 3: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

CORFLEX® is a registered trademark of Nexans

1 www.nexansamercable.com • e-mail: [email protected]

CORFLEX® MC-HL INSTRUMENTATION600V • PAIRS & TRIADSRated 90°C • Single or Multiple Individually Shielded Pairs or Triads, Overall Cable Shield

Ratings & Approvals� 90˚C Temperature Rating� Meets UL 1569 requirements for Type MC, Metal Clad cables

� Meets UL 2225 for Hazardous Locations� Designated Type MC and MC-HL as per NEC2014 Articles 330, 501 and 505

APPLICATIONCORFLEX® instrumentation cables are designed for use onClass 1 RemoteControl Signaling circuits or where a 600Vcable is desired, as instrumentation, process control, orcomputer cable transmitting signals at levels above 100 mili-volts in circuits where maximum noise protection isrequired. Protection from interference among groups as wellas external sources is provided by individual group shields aswell as an overall cable shield. For use indoors or outdoors;wet or dry locations; in raceways; supported by a messengerwire; for direct burial; in Class I, Division 2, Class II, Division2 or Class III, Division 2 hazardous locations.

FEATURES� UL listed as Type MC-HL, 600V (File E47409)� UL listed insulated conductors� Flame retardant: UL 1685 and IEEE 383 vertical tray firetests at 70,000 BTU/hr, ICEA T-29-520 fire test at 210,000BTU/hr, IEC 60332-3 category A fire test, IEEE 1202 andCSA FT4

� Cables are marked “-40°C” and are suitable for handlingand installation down to -10°C (based on -40°C impactandbend tests per UL 1569)

� Temperature rating of 90°C dry and wet� 130°C emergency rating and 250°C short circuit rating� Continuous, impervious aluminum armor corrugated forflexibility, prevents ingress of moisture, gases and liquids

� Aluminum armor resistance exceeds requirements of theNEC 2014 Article 250.178 for equipment groundingconductor

� Minimal noise and signal interference� Excellent mechanical and physical properties� Sunlight resistant jacket� Suitable for direct burial, use in cable tray and embedment in concrete

� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2014 (HL Rated)

BEND RADIUS� Fixed position: 7 x cable overall diameter� During pulling: 12 x cable overall diameter

ConductorBare, annealed copper conforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.

AssemblyPairs/triads are cabled in concentriclayers with interstices filled with suitablenon-hygroscopic fillers, as required. A binder tape of synthetic materialassembles the core in an essentiallyround configuration.

Conductor IDPairs: black/white &

number codedTriads: black/red/white &

number coded

ArmorContinuous corrugated andwelded, impervious aluminumsheath with no more than 0.2%trace copper providingcomplete protection againstliquid and gas ingress. Provides excellent mechanicalprotection, additionalelectrostatic shielding, andserves as an easy means forgrounding equipment.

InsulationFlame-retardant PVC, 15 milsnominal thickness, nylon jacket, 4mil nominal thickness. 90°C temperature rating, per UL Standard 66.

Insulation ShieldAluminum foil/polyester shieldhelically wrapped toprovide 100% coverage andtinned copper drain wire thatis two gauge sizes smallerthan the circuit conductors.These shields are electricallyisolated from each other.

Overall Cable ShieldAluminum foil/polyester shieldhelically wrapped to provide100% coverage. Tinned copperdrain wire that is the same sizeas the circuit conductors.

JacketOverall black polyvinylchloride jacket per UL 1569,90°C temperature rating; low acid gas emission; limitedflame spread and excellentcorrosion resistance.

Inner JacketPolyvinyl chloride jacket, overcabled core as per UL1569,90°C temperature rating, withadditional resistance to flamespread. A rip cord is laidlongitudinally under thejacket to facilitate stripping.

Page 4: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

2Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009

NexansDesignNo.

654988654921654947654962665250662116

No.ofPairs248121624

(inches)0.3190.3800.5170.6470.7311.016

(mils)404050505050

(inches)0.4050.4650.6210.7530.8371.124

(inches)0.5940.6330.8360.9761.1421.420

(mils)505050505050

(inches)0.6990.7350.9401.0801.2471.525

(lb/kft)2182573736218171427

Inner JacketThickness

Nominal DiameterOver Inner Jacket

Nominal DiameterOver Armor

Outer JacketThicknessPVC

(mils)151515151515

Nylon(mils)444444

Insulation Thickness Nominal DiameterOver Outer Jacket

Approx. NetCable Weight

Nominal DiameterOver Core

PAIRS WITH INDIVIDUAL AND OVERALL SHIELD • 600V – 18 AWG (7W)

PAIRS WITH INDIVIDUAL AND OVERALL SHIELD • 600V – 16 AWG (7W)

TRIADS WITH INDIVIDUAL AND OVERALL SHIELD • 600V – 16 AWG (7W)

ELECTRICAL PROPERTIES –PAIRS/TRIADS WITH INDIVIDUAL AND OVERALL CABLE SHIELD

Conductor Size(AWG)

DC Resistance(ohms/kft @ 20°C)

Conductor–Conductor(pf/ft)

Pairs

Capacitance

Triads

Conductor–Shield(pf/ft)

Conductor–Conductor(pf/ft)

Conductor–Shield(pf/ft)

1816

6.644.18

7486

148172

6387

156180

NexansDesignNo.

645390659052645291659078650796654889654905650788

No.ofPairs124812162436

(inches)0.2090.4240.4820.6350.7970.8821.1241.312

(mils)4040505050505050

(inches)0.2930.4770.5330.6760.8350.9831.1261.370

(inches)0.4920.6390.7670.9261.1401.3201.4221.746

(mils)5050505050505060

(inches)0.6050.7440.8711.0301.2461.4311.5261.879

(lb/kft)157216375604862115114322121

Inner JacketThickness

Nominal DiameterOver Inner Jacket

Nominal DiameterOver Armor

Outer JacketThicknessPVC

(mils)1515151515151515

Nylon(mils)44444444

Insulation Thickness Nominal DiameterOver Outer Jacket

Approx. NetCable Weight

Nominal DiameterOver Core

NexansDesignNo.

654863644344670083670067

No.of

Triads14812

(inches)0.2250.4840.6800.820

(mils)40505050

(inches)0.3040.5870.7860.925

(inches)0.5070.7980.9981.212

(mils)50505050

(inches)0.6190.9001.1021.317

(lb/kft)1713004671007

Inner JacketThickness

Nominal DiameterOver Inner Jacket

Nominal DiameterOver Armor

Outer JacketThicknessPVC

(mils)15151515

Nylon(mils)4444

Insulation Thickness Nominal DiameterOver Outer Jacket

Approx. NetCable Weight

Nominal DiameterOver Core

Page 5: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

3 www.nexansamercable.com • e-mail: [email protected]

CORFLEX® MC-HL ARMORED POWER & CONTROL600V • MULTI-CONDUCTORRated 90°C • Multi-Power Conductors with Bare Ground(s)

Ratings & Approvals� 90˚C Temperature Rating� Meets UL 44, XHHW-2 600V conductors� Meets UL 1569 requirements for Type MC,Metal Clad cables

� Meets UL 2225 for Hazardous Locations (HL)� Designated Types MC and MC-HL as per NEC2014 Articles 330, 501 and 505

� Meets CSA C22.2 No. 123 for AluminumSheathed Cables

� Meets CSA C22.2 No. 174 for Hazardous Locations

APPLICATIONCORFLEX® Type MC cables with the impervious, continuous,corrugated aluminum sheath are recommended as aneconomical alternate to a wire in conduit system. They areauthorized for use on services, feeders and branch circuits forpower, lighting, control and signaling circuits in accordancewith Articles 330 and 725 of the NEC. Type MC cables may beinstalled indoors or outdoors, in wet or dry locations, as openruns of cable secured to supports spaced not more than six feetapart, in cable tray, as aerial cable on a messenger, in anyapproved raceway, direct burial, or encased in concrete. TypeMC cables are also approved for use in Class I & II, Division 2,Class III, Divisions 1 and 2, and Class I, Zone 2 hazardouslocations per NEC articles 501, 502, 503 and 505; in Zone 2,Class II Div 2, Class III Div 1 and Class III Div 2 per CEC.

FEATURES� UL listed as Type MC-HL, 600V (File E47409)� UL listed insulated conductors� Flame retardant: UL 1685 and IEEE 383 vertical tray fire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at 210,000BTU/hr, IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4

� Cables are marked “-40°C” and are suitable for handlingand installation down to -10°C (based on -40°C impact and bend tests per UL 1569)

� Temperature rating of 90°C dry and wet� 130°C emergency rating and 250°C short circuit rating� Continuous, impervious aluminum armor corrugated forflexibility, prevents ingress of moisture, gases and liquids

� Aluminum armor resistance exceeds requirements of the NEC2014 Article 250.178 for equipment grounding conductor

� Armor provides good EMI shielding so that CORFLEX can be used in certain instrumentation applications when adequately grounded

� Excellent mechanical and physical properties� Sunlight resistant jacket� Suitable for direct burial, use in cable tray and embedment in concrete

� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2014 (HL Rated)

BEND RADIUS� Fixed position: 7 x cable overall diameter� During pulling: 12 x cable overall diameter

ConductorBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.

AssemblyConductors are cabledin concentric layers withgrounding wire, intersticesare filled with suitable non-hygroscopic fillers, as required. A binder tape of synthetic material assembles the core in an essentially roundconfiguration.

InsulationCross-linked polyethylenetype XHHW-2 per UL 44.

Grounding ConductorBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8. Meets or exceeds requirements of NECTable 250.122.

JacketOverall black polyvinylchloride jacket per UL 1569,90°C temperature rating; low acid gas emission; limited flame spread andexcellent corrosion resistance.

ArmorContinuous corrugated and welded, imperviousaluminum sheath withno more than 0.2% tracecopper providing completeprotection against liquidand gas ingress. Providesexcellent mechanicalprotection, additionalelectrostatic shielding,and serves as an easymeans for groundingequipment.

CORFLEX® is a registered trademark of Nexans

Conductor IDMulti-conductor 14 AWG to 10 AWG: Method #1-E2 perICEA S-73-532

Page 6: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

4Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009

POWER & CONTROL • 600V

NexansDesignNo.

670155670142317677318345318352318360318378318386318394318402318410

670156670144317693318436318444318451318469318447318485318493318501

670157670146317719318527318535318543318550665148

23*45791215192537

23*45791215192537

23*45791237

(mils)3030303030303030303030

3030303030303030303030

3030303030303030

(inches)0.2730.3900.3360.3360.4170.4860.5610.6100.6690.7970.933

0.3450.3400.3850.4140.4780.5510.6390.6910.7600.8971.059

0.3610.4500.4490.4790.5560.6930.7451.227

(inches)0.4690.5550.5030.5320.6010.6450.7830.8110.9211.0051.218

0.5120.5550.5500.5990.6400.7770.8280.9360.9811.1901.374

0.5270.6200.6210.6410.7800.9370.9711.591

(mils)5050505050505050505050

5050505050505050505050

5050505050505060

Ω/kft2.55532.55532.55532.55532.55532.55532.55532.55532.55532.55532.5553

1.60821.60821.60821.60821.60821.60821.60821.60821.60821.60821.6082

1.01181.01181.01181.01181.01181.01181.01181.0118

InsulationThickness

NominalDiameterOver Core

NominalDiameterOver Armor

JacketThickness

(inches)0.5810.6600.6060.6350.7040.7480.8870.9151.0281.1111.323

0.6140.6600.6530.7020.7440.8810.9321.0391.0851.2951.478

0.6320.7250.7240.7430.8841.0401.0741.725

NominalDiameterOver Jacket

DCResistance20°C

Ω/kft2.60642.60642.60642.60642.60642.60642.60642.60642.60642.60642.6064

1.64041.64041.64041.64041.64041.64041.64041.64041.64041.64041.6404

1.03201.03201.03201.03201.03201.03201.03201.0320

DCResistance25°C

60 Hz Ω/kft3.25833.25833.25833.25833.25833.25833.25833.25833.25833.25833.2583

2.05072.05072.05072.05072.05072.05072.05072.05072.05072.05072.0507

1.29021.29021.29021.29021.29021.29021.29021.2902

ACResistance90°C

Ω/kft@60Hz0.03760.03760.03760.04970.05450.05960.06410.06660.06940.07430.0787

0.03530.03530.03530.04750.05260.05740.06200.06440.06720.07190.0765

0.03320.03320.03320.04540.05070.05790.06010.0744

InductiveReactance90°C

Amps/kft2.94892.94892.94892.95422.95662.95852.96042.96152.96272.96492.9668

1.86101.86101.86101.86631.86851.87061.87261.87371.87491.87691.8789

1.17561.17561.17561.18091.18321.18641.18741.1936

VoltageDropVolts/

75°C15151515141410101098

2020202018181313131110

3030282825251814

90°C1515151515151313131110

2020202020201515151412

3030303028282016

(lb/kft)155200191212263307388443572691986

1852262392803384375026357439871365

2313123193644846307321984

Approx.Net CableWeightNo. of

Cond. kcmil14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)

12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)

10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)

ConductorSizeAWG/

AWG14(7w)3x18(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)

12(7w)3x16(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)

10(7w)3x14(7)10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)

GroundWireSize

Notes:1) Ampacities are in accordance with NEC 2014 Table 310.15(B)(16) for conductors in raceway or direct buried at 30°C ambienttemperature and 90°C conductor temperature. The overcurrent protection shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambienttemperature and number of conductors have been applied (NEC 2014 Article 240.4(D)). For correction factors for different ambienttemperatures and ampacities at different conductor temperatures, see NEC 2014 Table 310.15(B)(16). Ampacities for cables having morethan three conductors have been derated per NEC 2014 Article 310.15(B)(3)(A).

*Three conductor cables with 3 grounds are also suitable for VFD applications.

Ampacities(Note 1)

Page 7: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

5 www.nexansamercable.com • e-mail: [email protected]

CORFLEX® MC-HL ARMORED COMPOSITE POWER & CONTROL • 600V • MULTI-CONDUCTORRated 90°C • 1 Bare Ground

Ratings & Approvals� 90˚C Temperature Rating� Meets UL 44, XHHW-2 600V conductors� Meets UL 1569 requirements for Type MC,Metal Clad cables

� Meets UL 2225 for Hazardous Locations (HL)� Designated Types MC and MC-HL as per NEC2014 Articles 330, 501 and 505

� Meets CSA C22.2 No. 123 for AluminumSheathed Cables

� Meets CSA C22.2 No. 174 for Hazardous Locations

APPLICATIONCORFLEX® Type MC cables with the impervious, continuous,corrugated aluminum sheath are recommended as aneconomical alternate to a wire in conduit system. They areauthorized for use on services, feeders and branch circuits forpower, lighting, control and signaling circuits in accordance withArticles 330 and 725 of the NEC. Type MC cables may beinstalled indoors or outdoors, in wet or dry locations, as openruns of cable secured to supports spaced not more than six feetapart, in cable tray, as aerial cable on a messenger, in anyapproved raceway, direct burial, or encased in concrete. TypeMC cables are also approved for use in Class I & II, Division 2,Class III, Divisions 1 and 2, and Class I, Zone 2 hazardouslocations per NEC articles 501, 502, 503 and 505; in Zone 2,Class II Div 2, Class III Div 1 and Class III Div 2 per CEC.

FEATURES� UL listed as Type MC-HL, 600V (File E47409)� UL listed insulated conductors� Flame retardant: UL 1685 and IEEE 383 vertical tray fire tests at70,000 BTU/hr, ICEA T-29-520 fire test at 210,000 BTU/hr,IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4

� Cables are marked “-40°C” and are suitable for handling and installation down to -10°C (based on -40°C impact and bend tests per UL 1569)

� Temperature rating of 90°C dry and wet� 130°C emergency rating and 250°C short circuit rating� Continuous, impervious aluminum armor corrugated forflexibility, prevents ingress of moisture, gases and liquids

� Aluminum armor resistance exceeds requirements of the NEC 2008 and NEC 2011 Article 250.178 for equipmentgrounding conductor

� Armor provides good EMI shielding so that CORFLEXcan be used in certain instrumentation applicationswhen adequately grounded

� Excellent mechanical and physical properties� Sunlight resistant jacket� Suitable for direct burial, use in cable tray and embedment in concrete

� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2014 (HL Rated)

BEND RADIUS� Fixed position: 7 x cable overall diameter� During pulling: 12 x cable overall diameter

ConductorBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.

AssemblyConductors are cabledin concentric layers withgrounding wire, intersticesare filled with suitable non-hygroscopic fillers, as required. A binder tape of synthetic material assembles the core in an essentially roundconfiguration.

InsulationCross-linked polyethylenetype XHHW-2 per UL 44.

Grounding ConductorBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.Meets or exceedsrequirements ofNEC Table 250.122.

JacketOverall black polyvinylchloride jacket per UL 1569,90°C temperature rating; lowacid gas emission; limitedflame spread and excellentcorrosion resistance.

ArmorContinuous corrugated and welded, imperviousaluminum sheath withno more than 0.2% tracecopper providing completeprotection against liquidand gas ingress. Providesexcellent mechanicalprotection, additionalelectrostatic shielding,and serves as an easymeans for groundingequipment.

CORFLEX® is a registered trademark of Nexans

Conductor IDPower Conductors8 AWG and larger:Method #4 per ICEA S-73-532Control Conductors14, 12 & 10 AWG:Method #1-E2 per ICEA S-73-532

Page 8: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

6Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009

Notes:1) Ampacities are based on NEC 2014 Table 310.15(B)(16) for not more than three current-carrying conductors (where the 4th conductor is the neutral of a 3-phase, 4 wire system) in raceway, cable, or earth (direct buried), based on an ambient temperature of 30°C (86°F). Refer to Table 310.15(B)(2)(A) for the ampacity correction factors where the ambient temperature is other than 30°C (86°F).

JacketThickness(mils)505050505050

505050505050

505050505050

505050505050

505050505050

75°C303030303030

505050505050

656565656565

858585858585

115115115115115115

90°C303030303030

555555555555

757575757575

959595959595

130130130130130130

ControlConductorsNo. x SizeAWG/kcmil

4x12(7w)3x12(7w)4x14(7w)3x14(7w)4x12(7w)4x14(7w)

4x12(7w)3x12(7w)4x14(7w)3x14(7w)4x12(7w)4x14(7w)

4x12(7w)3x12(7w)4x14(7w)3x14(7w)4x12(7w)4x14(7w)

4x12(7w)3x12(7w)4x14(7w)3x14(7w)4x12(7w)4x14(7w)

4x12(7w)3x12(7w)4x14(7w)3x14(7w)4x12(7w)4x14(7w)

NexansDesignNo.

199760665024665036665041665019665047

290783665025665037665042665020665048

290791665027665038665044665021665049

290809665028665039665045665022665050

654277665035665040665046665023665051

PowerConductorsNo. x SizeAWG/kcmil

3x10(7w)3x10(7w)3x10(7w)3x10(7w)4x10(7w)4x10(7w)

3x8(7w)3x8(7w)3x8(7w)3x8(7w)4x8(7w)4x8(7w)

3x6(7w)3x6(7w)3x6(7w)3x6(7w)4x6(7w)4x6(7w)

3x4(7w)3x4(7w)3x4(7w)3x4(7w)4x4(7w)4x4(7w)

3x2(7w)3x2(7w)3x2(7w)3x2(7w)4x2(7w)4x2(7w)

ControlInsulationThickness(mils)303030303030

303030303030

303030303030

303030303030

303030303030

PowerInsulationThickness(mils)303030303030

454545454545

454545454545

454545454545

454545454545

NominalDiameterOverArmor(in)0.7720.7500.7540.6350.7820.777

0.9170.8000.8110.8000.9140.831

0.9750.9370.9410.9210.9580.938

1.1490.9640.9610.9871.0120.999

1.1681.1601.1281.1801.2141.214

NominalDiameterOverCore(in)0.5400.4950.5100.4700.5600.550

0.6640.5900.6100.5910.6590.645

0.7500.6950.7000.6700.7250.695

0.8450.7350.7300.7700.8070.787

0.8700.8600.8200.8850.9270.927

NominalDiameterOverJacket(in)0.8760.8540.8600.7380.8870.881

1.0260.9040.9150.9041.0240.935

1.0771.0411.0451.0281.0621.042

1.2541.0681.0651.0911.1171.103

1.2731.2651.2401.2851.3191.319

Ampacities(Note 1)

DCResist.20C �/kft1.01181.01181.01181.01181.01181.0118

0.63610.63610.63610.63610.63610.6361

0.40020.40020.40020.40020.40020.4002

0.25160.25160.25160.25160.25160.2516

0.15740.15740.15740.15740.15740.1574

DCResist.25C �/kft1.03201.03201.03201.03201.03201.0320

0.64880.64880.64880.64880.64880.6488

0.40820.40820.40820.40820.40820.4082

0.25660.25660.25660.25660.25660.2566

0.16050.16050.16050.16050.16050.1605

ACResist.

90C, 60 Hz�/kft

1.29021.29021.29021.29021.29021.2902

0.81110.81110.81110.81110.81110.8111

0.51040.51040.51040.51040.51040.5104

0.32090.32090.32090.32090.32090.3209

0.20090.20090.20090.20090.20090.2009

InductiveReactance90C, 60 Hz

�/kft0.03320.03320.03320.03320.03320.0332

0.03480.03480.03480.03480.03480.0348

0.03290.03290.03290.03290.03290.0329

0.03120.03120.03120.03120.03120.0312

0.02990.02990.02990.02990.02990.0299

VoltageDropVolts/ Amps/kft1.17561.17561.17561.17561.17561.1756

0.74520.74520.74520.74520.74520.7452

0.47370.47370.47370.47370.47370.4737

0.30250.30250.30250.30250.30250.3025

0.19380.19380.19380.19380.19380.1938

GroundWire SizeAWG10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)

10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)

8(7w)8(7w)8(7w)8(7w)8(7w)8(7w)

8(7w)8(7w)8(7w)8(7w)8(7w)8(7w)

6(7w)6(7w)6(7w)6(7w)6(7w)6(7w)

Approx.Net CableWeight(lbs/Kft)425396387340463428

565473478457630535

685665640641778749

926807799788993953

119811701165114614361401

COMPOSITE POWER & CONTROL • 600V

Page 9: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

CORFLEX® MC-HL POWER CABLE • 600VRated 90°C • 3 and 4 Power Conductors with Ground(s)

Ratings & Approvals� 90˚C Temperature Rating� Meets UL 44, XHHW-2 600V conductors� Meets UL 1569 requirements for Type MC,Metal Clad cables

� Meets UL 2225 for Hazardous Locations (HL)� Designated Types MC and MC-HL as per NEC2014 Articles 330, 501 and 505

� Meets CSA C22.2 No. 123 for AluminumSheathed Cables

� Meets CSA C22.2 No. 174 for Hazardous Locations

ApplicationCORFLEX® Type MC cables with the impervious, continuous,corrugated aluminum sheath are recommended as aneconomical alternate to a wire in conduit system. They areauthorized for use on services, feeders and branch circuits forpower, lighting, control and signaling circuits in accordance with Articles 330 and 725 of the NEC. Type MC cables may beinstalled indoors or outdoors, in wet or dry locations, as openruns of cable secured to supports spaced not more than six feet apart, in cable tray, as aerial cable on a messenger, in anyapproved raceway, direct burial, or encased in concrete. TypeMC cables are also approved for use in Class I & II, Division 2,Class III, Divisions 1 and 2, and Class I, Zone 2 hazardouslocations per NEC articles 501, 502, 503 and 505; in Zone 2,Class II Div 2, Class III Div 1 and Class III Div 2 per CEC.

Features� UL listed as Type MC-HL, 600V (File E47409)� UL listed insulated conductors� Flame retardant: UL 1685 and IEEE 383 vertical tray fire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at 210,000 BTU/hr, IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4

� Cables are marked “-40°C” and are suitable for handling and installation down to -10°C (based on -40°C impactand bend tests per UL 1569)

� Temperature rating of 90°C dry and wet� 130°C emergency rating and 250°C short circuit rating� Continuous, impervious aluminum armor corrugated forflexibility, prevents ingress of moisture, gases and liquids

� Aluminum armor resistance exceeds requirements of the NEC2014 Article 250.178 for equipment grounding conductor

� Excellent mechanical and physical properties� Sunlight resistant jacket� Suitable for direct burial, use in cable tray and embedment in concrete

� Three conductor cables have three symmetrical groundingconductors suitable for PWM/VFD and other modern ACdrive/motor applications

� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2014 (HL Rated)

Bend Radius� Fixed position: 7X cable overall diameter� During pulling: 12X cable overall diameter

ConductorsBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.

AssemblyConductors are cabledin concentric layers withgrounding wire, intersticesare filled with suitable non-hygroscopic fillers, as required. A binder tape of synthetic materialassembles the core in an essentially roundconfiguration.

InsulationCross-linked polyethylenetype XHHW-2 per UL 44.

GroundingConductor(s)Bare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.Meets or exceedsrequirements ofNEC Table 250.122.

JacketOverall black polyvinylchloride jacket per UL 1569,90°C temperature rating; low acid gas emission; limited flame spread and excellent corrosion resistance.

ArmorContinuous corrugated and welded, imperviousaluminum sheath withno more than 0.2% tracecopper providing completeprotection against liquidand gas ingress. Providesexcellent mechanicalprotection, additionalelectrostatic shielding,and serves as an easymeans for groundingequipment.

CORFLEX® is a registered trademark of Nexans

7 www.nexansamercable.com • e-mail: [email protected]

Conductor IDSizes 14 AWG to 2AWG:Method #1-E2 perICEA S-73-532Sizes 1 AWG to 500kcmil: Method #4 perICEA S-73-532

Page 10: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

8Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009

NexansDesignNo.

670142317677670144317693670146317719670148317735670149317750670150317776670151317792670152698571670153317818670118317834670119660631670120317867670121670577670122317891670123317917

JacketThickness(mils)505050505050505050505050505050505050505060606060606060757575

75°C151520203030505065658585115115130130150150175175200200230230255255310310380380

90°C151520203030555575759595130130145145170170195195225225260260290290350350430430

Cond.SizeAWG/kcmil14(7w)14(7w)12(7w)12(7w)10(7w)10(7w)8(7w)8(7w)6(7w)6(7w)4(7w)4(7w)2(7w)2(7w)1(19w)1(19w)1/0(19w)1/0(19w)2/0(19w)2/0(19w)3/0(19w)3/0(19w)4/0(19w)4/0(19w)250(37w)250(37w)350(37w)350(37w)500(37w)500(37w)

No. ofCond.343434343434343434343434343434

InsulationThickness(mils)303030303030454545454545454555555555555555555555656565656565

NominalDiameterOverArmor(in)0.5550.5030.5550.5490.6200.6200.7500.7950.8020.9300.9370.9951.1271.2141.2301.3611.3501.4271.4221.5981.6061.7301.7341.9361.9252.0122.0282.2302.3402.694

NominalDiameterOverCore(in)0.3900.3360.3400.3960.4500.4500.5200.5850.6000.6800.7000.7820.8300.9270.9501.0411.0401.1341.1261.2381.2501.3561.3601.5001.4771.6531.6851.8891.9542.196

NominalDiameterOverJacket(in)0.6600.6060.6600.6520.7250.7300.8380.9000.9051.0271.0391.0951.2321.3201.3201.4661.4731.5251.5101.7321.7391.8651.8672.0692.0582.1472.1622.3872.5042.861

Ampacities(Note 1)DC

Resist.20C �/kft2.55532.55531.60821.60821.01181.01180.63610.63610.40020.40020.25160.25160.15740.15740.12550.12550.09990.09990.07970.07910.06290.06270.04970.04970.04240.04240.03010.03010.02120.0212

DCResist.25C �/kft2.60642.60641.64041.64041.03201.03200.64880.64880.40820.40820.25660.25660.16050.16050.12800.12800.10190.10190.08130.08060.06420.06400.05070.05070.04320.04320.03070.03070.02160.0216

ACResist.

90C, 60 Hz�/kft3.25833.25832.05072.05071.29021.29020.81110.81110.51040.51040.32090.32090.20090.20090.16030.16030.12780.12780.10210.10110.08080.08040.06410.06410.05840.05840.03950.03950.02900.0282

InductiveReactance90C, 60 Hz

�/kft0.03760.03750.03530.03530.03320.03320.03480.03480.03290.03290.03120.03120.02990.02990.02880.02880.02810.02830.02800.02810.02750.02760.02710.02710.02630.02640.02630.02630.02500.0251

VoltageDropVolts/ Amps/kft2.94892.93071.86101.85101.17561.17580.74520.74720.47370.47370.30250.30240.19380.19380.15680.15670.12720.12690.10410.10330.08470.08440.06950.06940.06080.06070.04700.04680.03670.0363

GroundWire SizeAWG

3x18(7w)1x14(7w)3x16(7w)1x12(7w)3x14(7w)1x10(7w)3x14(7w)1x10(7w)3x12(7w)1x8(7w)3x12(7w)1x8(7w)3x10(7w)1x6(7w)3x10(7w)1x6(7w)3x10(7w)1x6(7w)3x10(7w)1x6(7w)3x8(7w)1x4(7w)3x8(7w)1x4(7w)3x8(7w)1x4(7w)3x6(7w)1x3(7w)3x6(7w)1x2(7w)

Approx.Net CableWeight(lbs/Kft)200191226245312320413465542675735892109713321330162815921922188223932400297529103605331641104375561760267892

POWER CABLE • 600V

Notes:1) Ampacities are based on NEC 2014 Table 310.15(B)(16) for not more than three current-carrying conductors (where the 4th conductor is theneutral of a 3-phase, 4 wire system) in raceway, cable, or earth (direct buried), based on an ambient temperature of 30°C (86°F). Refer toTable 310.15(B)(2)(A) for the ampacity correction factors where the ambient temperature is other than 30°C (86°F).

2) Three conductor cables with 3 ground wires are also suitable for VFD applications.

Page 11: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

9 www.nexansamercable.com • e-mail: [email protected]

CORFLEX® MV-105 OR MC-HL MEDIUM VOLTAGE5KV 133% INSULATION LEVEL8KV 100% INSULATION LEVELRated 105°C • 3 Conductors with 3 Bare Grounds

APPLICATIONCORFLEX® MV-105 power cables are recommended as aneconomical alternate to a wire in conduit system. They aredesigned specifically for use as feeders or branch circuits inindustrial and utility power distribution systems. These cablesmay be installed in both exposed and concealed work, wetand dry locations, directly buried in the earth, or embedded in concrete. They may be installed on metal racks, troughs, in cable trays or secured to supports not greater than 6 feetapart. CORFLEX Type MC-HL cables are also approved forClasses I, II, and III, Division 1 and 2 and Class I, Zones 1and 2 hazardous locations – NEC Articles 501, 502, 503 and 505

FEATURES� UL listed as Type MV-105 5kV and 8kV (File E66901)� Flame retardant: UL 1685 and IEEE 383 vertical tray firetests at 70,000 BTU/hr, IEC 60332-3 category A fire test,IEEE 1202 and CSA FT4

� Cables are marked “-40°C” and are suitable for handlingand installation down to -10°C (based on -40°C impactand bend tests per UL 1569)

� Continuous, impervious aluminum armor corrugated forflexibility, prevents ingress of moisture, gases and liquids

� Aluminum armor resistance exceeds requirements of the NEC 2014 Article 250.178 for equipment grounding conductor.

� Excellent mechanical and physical properties� Minimal noise and signal interference� Sunlight resistant jacket� Suitable for direct burial, use in cable tray and embedment in concrete

� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2014 (HL Rated)

� Three symmetrical grounding conductors for PWM/VFD and other modern AC drive/motor applications

� Phase identification: Color coded (black, red, blue) polyesterribbon laid longitudinally under the copper shield tape

� Cables may also be provided with sealant for strandedconductors, waterblocking components for the metallic shield, or high performance conductor shield to furtherenhance their inherent superior quality

BEND RADIUS� Fixed position: 7 x cable overall diameter� During pulling: 12 x cable overall diameter

InsulationEPR meets or exceeds electrical and physicalrequirements of UL 1072.

Conductor ShieldExtruded semiconductingconductor shield meetsor exceeds electrical andphysical requirementsof UL 1072.

Insulation ShieldNonmetallicExtruded semiconductinginsulation shield meetsor exceeds electricaland physical requirementsof UL 1072.

Metallic ShieldBare copper tape shieldhelically wrapped toprovide 100% coverage.

ConductorBare, annealed copperconforming to ASTM B3 and Class B Compactstranded in accordance with ASTM B496.

JacketOverall yellow polyvinylchloride jacket per UL 1072,90°C temperature rating; low acid gas emission; limitedflame spread and excellentcorrosion resistance.

ArmorContinuous corrugated and welded, imperviousaluminum sheath withno more than 0.2% tracecopper providing completeprotection against liquidand gas ingress. Providesexcellent mechanicalprotection, additionalelectrostatic shielding,and serves as an easymeans for groundingequipment.

Binder TapeSynthetic materialassembles the core inan essentially roundconfiguration.

Ratings & Approvals� 105˚C Temperature Rating� Meets UL 1072 requirements for medium voltage power cables

� Meets UL 1569 requirements for Type MC, Metal Clad cables

� Meets UL 2225 for Hazardous Locations (MC-HL)� Designated Type MC as per NEC 2014, 2008 andNEC 2014 (HL Rated)

� Insulation meets electrical and physical requirementsof ICEA S-93-639/NEMA WC 74 and UL 1072

� Meets AEIC CS 8 - Specification for Extruded Dielectric Shielded Power Cables Rated 5 Through 46 kV

GroundingConductorsBare, annealed copperconforming to ASTM B3and Class B stranded inaccordance with ASTM B8.

Page 12: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

10Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009

CORFLEX® is a registered trademark of Nexans

5KV • 133% INSULATION LEVEL • EPR INSULATION: 90 MILS

NexansPartNo.

662776665017660072660648662186670667670669665029660075660076660349665014

JacketThickness(mils)506060606060606075758585

Cond.SizeAWG/kcmil6(7w)4(7w)2(7w)1(18w)1/0(18w)2/0(18w)4/0(18w)250(36w)350(36w)500(36w)750(58w)1000(58w)

GroundWireSizeAWG3 x 103 x 103 x 103 x 83 x 83 x 83 x 63 x 63 x 63 x 43 x 43 x 4

NominalDiameterOver

Insulation(in)0.4260.4700.5250.5560.5930.6340.7330.7860.8841.0451.1861.339

NominalDiameterOverArmor(in)1.3721.5421.6311.7311.9051.9482.1032.2402.4592.7793.3663.505

NominalDiameterOverJacket(in)1.4771.6781.7651.8642.0472.0812.2402.3872.6232.9463.5653.687

InAir

Note 1105135185210240275360400490600745860

CableTrayNote 292120165185215245320350430525635725

DirectBurialNote 3120155200225255290375410495590720810

DCResist.20C �/kft0.40080.25200.15850.12600.09990.07920.04980.04220.03020.02110.01410.0106

DCResist.25C �/kft0.40880.25700.16160.12850.10190.08080.05080.04310.03080.02150.01440.0108

ACResist.

90C, 60 Hz�/kft

0.51110.32130.20220.16070.12750.10120.06390.05430.03920.02810.01960.0159

InductiveReactance90C, 60 Hz

�/kft0.04600.04270.04000.03870.03740.03610.03380.03320.03120.03040.02920.0283

VoltageDropVolts/ Amps/kft0.48010.30780.19940.16160.13110.10690.07230.06340.04920.03860.03060.0266

AmpacitiesNominalDiameterOver

Core (in)1.0661.1621.2981.3681.4481.5341.7491.8652.0762.3352.7313.063

Approx.Net CableWeight(lbs/Kft)11021402177320922389268036734181536373231029212871

8KV • 100% INSULATION LEVEL • EPR INSULATION: 115 MILS

Notes:1) Ampacities in air are based on NEC 2014 Table 310.60(C)(71), 5001-35,000 Volts Ampacity column, for insulated three conductor coppercable isolated in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.

2) Ampacities in cable tray are based on NEC 2014 Table 310.60(C)(75), 5001-35,000 Volts Ampacity column, for insulated three conductorcopper cable in isolated conduit in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.

3) Ampacities for direct burial are based on NEC 2014 Table 310.60(C)(83), 5001-35,000 Volts Ampacity column, for insulatedthree conductor copper cable, directly buried, maximum conductor temperature of 105°C, ambient earth temperatureof 20°C, 100 percent load factor, earth thermal resistivity of 90°C cm / W.

* Three conductor cables with 3 ground wires are also suitable for VFD applications.

Notes:1) Ampacities in air are based on NEC 2014 Table 310.60(C)(71), 2001-5000 Volts Ampacity column, for insulated three conductorcopper cable isolated in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.

2) Ampacities in cable tray are based on NEC 2014 Table 310.60(C)(75), 2001-5000 Volts Ampacity column, for insulated three conductor copper cable in isolated conduit in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.

3) Ampacities for direct burial are based on NEC 2014 Table 310.60(C)(83), 2001-5000 Volts Ampacity column, for insulated three conductor copper cable, directly buried, maximum conductor temperature of 105°C, ambient earth temperatureof 20°C, 100 percent load factor, earth thermal resistivity of 90°C cm / W.

* Three conductor cables with 3 ground wires are also suitable for VFD applications.

NexansPartNo.

603837603838603839603840603841603842603843603844603845603846603847603848

JacketThickness(mils)505060606060606075758585

Cond.SizeAWG/kcmil6(7w)4(7w)2(7w)1(18w)1/0(18w)2/0(18w)4/0(18w)250(36w)350(36w)500(36w)750(58w)1000(58w)

GroundWireSizeAWG3 x 103 x 103 x 103 x 83 x 83 x 83 x 63 x 63 x 63 x 43 x 43 x 4

NominalDiameterOver

Insulation(in)0.3860.4300.4850.5170.5540.5940.6930.7470.8440.9651.1471.299

NominalDiameterOverArmor(in)1.3111.3791.5641.6081.7041.8062.0042.1152.3502.6943.1943.464

NominalDiameterOverJacket(in)1.4271.4841.6981.7411.8381.9392.1382.2492.5142.8603.3763.663

InAir

Note 188115154180205240320355440545685790

CableTrayNote 277100135155185210285315390475585660

DirectBurialNote 3115150190215245280360395475570700785

DCResist.20C �/kft0.40080.25200.15850.12600.09990.07920.04980.04220.03020.02110.01410.0106

DCResist.25C �/kft0.40880.25700.16160.12850.10190.08080.05080.04310.03080.02150.01440.0108

ACResist.

90C, 60 Hz�/kft

0.51110.32130.20220.16080.12750.10130.06400.05440.03930.02820.01990.0160

InductiveReactance90C, 60 Hz

�/kft0.04470.04090.03080.03680.03560.03450.03240.03190.03060.02940.02750.0283

VoltageDropVolts/ Amps/kft0.47920.30710.19860.19080.13030.10620.07170.06290.04870.03820.03030.0264

AmpacitiesNominalDiameterOver

Core (in)0.9811.0761.1951.2621.3451.4321.6461.7061.9732.2332.6282.958

Approx.Net CableWeight(lbs/Kft)1058123416231877216324733435389450817000983712951

Page 13: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

11 www.nexansamercable.com • e-mail: [email protected]

CORFLEX® MV-105 OR MC-HL MEDIUM VOLTAGE15KV 100% INSULATION LEVEL & 133% INSULATION LEVELRated 105°C • 3 Conductors with 1 Bare Ground

Ratings & Approvals� 105˚C Temperature Rating� Meets UL 1072 requirements for mediumvoltage power cables

� Meets UL 1569 requirements for Type MC, Metal Clad cables

� Meets UL 2225 for Hazardous Locations (MC-HL)� Insulation meets electrical and physical requirementsof ICEA S-93-639/NEMA WC 74 and UL 1072

� Meets AEIC CS 8 – Specification for Extruded Dielectric Shielded Power Cables Rated 5 Through 46 kV

APPLICATIONCORFLEX® MV-105 power cables are recommended as aneconomical alternate to a wire in conduit system. They aredesigned specifically for use as feeders or branch circuits inindustrial and utility power distribution systems. These cablesmay be installed in both exposed and concealed work, wetand dry locations, directly buried in the earth, or embedded in concrete. They may be installed on metal racks, troughs, in cable trays or secured to supports not greater than 6 feetapart. CORFLEX Type MC-HL cables are also approved forClasses I, II, and III, Division 1 and 2 and Class I, Zones 1and 2 hazardous locations - NEC Articles 501, 502, 503 and 505.

FEATURES� UL listed as Type MV-105 15 kV (File E66901)

� Flame retardant: UL 1685 and IEEE 383 vertical tray firetests at 70,000 BTU/hr, IEC 60332-3 category A fire test,IEEE 1202 and CSA FT4

� Cables are marked “-40°C” and are suitable for handlingand installation down to -10°C (based on -40°C impactand bend tests per UL 1569)

� Continuous, impervious aluminum armor corrugated forflexibility, prevents ingress of moisture, gases and liquids

� Aluminum armor resistance exceeds requirements of theNEC 2014 Article 250.178 for equipment groundingconductor

� Excellent mechanical and physical properties

� Minimal noise and signal interference

� Sunlight resistant jacket

� Suitable for direct burial, use in cable tray and embedment in concrete

� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2014 (HL Rated)

� Cables may also be provided with sealant for strandedconductors, waterblocking components for the metallic shield, or high performance conductor shield to furtherenhance their inherent superior quality

BEND RADIUS� Fixed position: 7 x cable overall diameter� During pulling: 12 x cable overall diameter

JacketOverall red polyvinylchloride jacket per UL 1072,90°C temperature rating; low acid gas emission; limitedflame spread and excellentcorrosion resistance.

InsulationEPR meets or exceeds electricaland physical requirements ofUL 1072.

Conductor ShieldExtruded semiconductingconductor shield meetsor exceeds electrical andphysical requirementsof UL 1072.

Metallic ShieldBare copper tape shieldhelically wrapped toprovide 100% coverage.

Binder TapeSynthetic materialassembles the core inan essentially roundconfiguration.

Insulation ShieldNonmetallicExtruded semiconductinginsulation shield meetsor exceeds electricaland physical requirementsof UL 1072.

ConductorBare, annealed copperconforming to ASTM B3 and Class B Compactstranded in accordance with ASTM B496.

ArmorContinuous corrugated and welded, imperviousaluminum sheath withno more than 0.2% tracecopper providing completeprotection against liquidand gas ingress. Providesexcellent mechanicalprotection, additionalelectrostatic shielding,and serves as an easymeans for groundingequipment.

Grounding ConductorBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.

Page 14: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

12Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009

15KV • 100% INSULATION LEVEL

15KV • 133% INSULATION LEVEL

NexansDesignNo.

664931664933664934664935664936664676664677664678664679

JacketThickness(mils)606060607575758585

InAir

Note 1185210240275360400490600745

CableTrayNote 2165185215245320350430525635

DirectBurialNote 3200225255290375410495590720

Cond.SizeAWG/kcmil2(7w)1(18w)1/0(18w)2/0(18w)4/0(18w)250(36w)350(36w)500(36w)750(58w)

GroundWireSizeAWG644432211/0

NominalDiameterOver

Insulation(in)0.6550.6790.7160.7560.8560.9101.0071.1281.310

NominalDiameterOverArmor(in)1.9741.9962.0362.1542.4262.4902.7843.1853.480

NominalDiameterOverJacket(in)2.1072.1292.1712.2892.5892.6532.9693.3673.671

AmpacitiesDCResist.20C �/kft0.15850.12600.09990.07920.04980.04220.03020.02110.0141

DCResist.25C �/kft0.16160.12850.10190.08080.05080.04310.03080.02150.0144

ACResist.

90C, 60 Hz�/kft

0.20220.16070.12750.10120.06390.05430.03920.02800.0196

InductiveReactance90C, 60 Hz

�/kft0.04450.04280.04120.03980.03710.03630.03460.03300.0314

VoltageDropVolts/ Amps/kft0.20130.16330.13270.10850.07370.06470.05030.03960.0313

NominalDiameterOver

Core (in)1.5861.6311.7111.8002.0142.1312.3422.6072.999

Approx.Net CableWeight(lbs/Kft)2121236026302987407845995985778910716

Notes:1) Ampacities in air are based on NEC 2014 Table 310.60(C)(71), 5001-35,000 Volts Ampacity column, for insulated three conductor coppercable isolated in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.

2) Ampacities in cable tray are based on NEC 2014 Table 310.60(C)(75), 5001-35,000 Volts Ampacity column, for insulated three conductorcopper cable in isolated conduit in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.

3) Ampacities for direct burial applications are based on NEC 2014 Table 310.60(C)(83), 5001-35,000 Volts Ampacity column, for insulatedthree conductor copper cable, directly buried, maximum conductor temperature of 105°C, ambient earth temperature of 20°C, 100 percent load factor, earth thermal resistivity of 90°C cm / W.

NexansDesignNo.

665006665007665008665005665010665011665012665013

JacketThickness(mils)6060606075758585

InAir

Note 1185210240275360400490600

CableTrayNote 2165185215245320350430525

DirectBurialNote 3200225255290375410495590

Cond.SizeAWG/kcmil2(7w)1(18w)1/0(18w)2/0(18w)4/0(18w)250(36w)350(36w)500(36w)

GroundWireSizeAWG64443221

NominalDiameterOver

Insulation(in)0.7350.7660.8030.8440.9430.9961.0941.215

NominalDiameterOverArmor(in)2.0942.1772.2992.3622.6812.7683.1543.387

NominalDiameterOverJacket(in)2.2352.3112.4422.4962.8532.9403.3363.575

AmpacitiesDCResist.20C �/kft0.15850.12600.09990.07920.04980.04220.03020.0211

DCResist.25C �/kft0.16160.12850.10190.08080.05080.04310.03080.0215

ACResist.

90C, 60 Hz�/kft

0.20220.16070.12750.10120.06390.05430.03920.0280

InductiveReactance90C, 60 Hz

�/kft0.04680.04540.04370.04210.03910.03820.03630.0345

VoltageDropVolts/ Amps/kft0.20240.16440.13380.10950.07460.06550.05100.0402

NominalDiameterOver

Core (in)1.7401.8221.9021.9892.2032.3182.5282.792

Approx.Net CableWeight(lbs/Kft)22512616295632704546510663968209

Notes:1) Ampacities in air are based on NEC 2014 Table 310.60(C)(71), 5001-35,000 Volts Ampacity column, for insulated three conductor coppercable isolated in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.

2) Ampacities in cable tray are based on NEC 2014 Table 310.60(C)(75), 5001-35,000 Volts Ampacity column, for insulated three conductorcopper cable in isolated conduit in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.

3) Ampacities for direct burial applications are based on NEC 2014 Table 310.60(C)(83), 5001-35,000 Volts Ampacity column, for insulatedthree conductor copper cable, directly buried, maximum conductor temperature of 105°C, ambient earth temperature of 20°C, 100 percent load factor, earth thermal resistivity of 90°C cm / W.

CORFLEX® is a registered trademark of Nexans

Page 15: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

13 www.nexansamercable.com • e-mail: [email protected]

CORFLEX® PULLING INSTRUCTIONSCertain installations require thepulling of CORFLEX® into ducts ortrays. These installations requirecareful planning and execution. The following provides informationon how to calculate tensionsdeveloped during pulling andwhat precautions to take to prevent damage to the cable.

Pulling TensionThe maximum tension applied to acable is limited to prevent damageor distortion of cable componentswhich could reduce the life orreliability of the cable. The methodof pulling is significant in thatdifferent methods will resultin different stresses on critical cablecomponents for the same overalltension. Nexans AmerCablerecommends that CORFLEX MC-HLInstrumentation 600V cables arepulled by means of the aluminumsheath and jacket with a grip applied over the jacketed core,sheath and overall jacket. All otherCORFLEX cable types described in this catalog should be pulled by means of the conductors, aided with a grip over the outeraluminum sheath. The conductorsand the sheath must be pulledtogether. Maximum allowablepulling tensions for CORFLEX cablesshould never exceed the valuesshown in pulling tension table.

Calculating Pulling TensionsThe tension developed in anyStraight Section of duct iscalculated as:

T = L x W x f lbf whereL = section length (feet)W = cable weight per unit length

(lb/foot)f = coefficient of dynamic friction

The tension developed in any Bend is calculated as:T = T1 x efa lbf whereT1 = tension at bend entrance (lbf)e = base of natural logarithms(2.71828)

f = coefficient of dynamic frictiona = angle of bend (radians)or efa is given in the following tablefor common conditions:BendAngle f=0.15 f=0.30 f=0.35 f=0.40

30° 1.08 1.17 1.20 1.2345° 1.13 1.27 1.32 1.3760° 1.17 1.37 1.44 1.5290° 1.27 1.60 1.73 1.88

Coefficients of dynamic friction withlubricant are given in the followingtable for common duct and cablejacket materials. These coefficientscan be used for calculation oftensions.

CoefficientDuct Type Cable Jacket of Friction

PVC PVC 0.50PE PVC 0.30Fiber PVC 0.40

Asbestos Cement PVC 0.70

Considerations must be given toSide Wall Bearing Pressure (SWBP)when pulling CORFLEX through abend. The SWBP is calculated asfollows:

For CORFLEX, Nexans AmerCablerecommends a maximum SWBPof 500 pounds force/foot. Duringinstallation of the CORFLEX cable, itis recommended that the bend radiibe as noted in thecable descriptions.

Pulling in DuctIt is extremely important for thesuccess of any pull in duct to useapproved lubricants. Lubricants mustbe compatible with the cable jacketand duct material. Lubricating thepulling rope will decrease the tensionon the pulling equipment and moreimportantly will reduce the risk ofdamage to the inside of the ductwhich in turn can damage the cable.When designing the duct layout, it is suggested that the bends beconcentrated near the end fromwhich the cable is to be pulled. Thispractice will result in lower tensions.In some cases, the tensions resultingfrom alternative directions should be calculated.

Pulling in Trays & TrenchesFor the installation of CORFLEX intrays, rollers are normally used.Using well lubricated rollers and long radius sheaves at bends willresult in a lower coefficient of friction when compared to duct. A coefficient of friction of 0.15 canbe used when calculating pullingtension using rollers. For long pullswith bends it may be necessary toinstall assist pullers before the bendsto reduce the tension on thecable entering a bend andreducing the risk of damage from excessive SWBP.

The recommendations given aboveare intended to cover a wide varietyof pulling conditions. It is possible,under ideal conditions, and withexperienced supervision, to exceedthese limits.

For further guidance, see IEEE Paper84 T & D 365-3, orcontact Nexans AmerCable.

SWBP = Pulling Tension Cable at Bend Exit (lbf)Radius of Bend (feet)

Page 16: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

14Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009

CORFLEX® is a registered trademark of Nexans

CORFLEX® CONDUCTOR ID

Conductor Insulation Stripe Conductor Insulation Stripe

1st BLACK – 19th ORANGE Blue

2nd RED – 20th YELLOW Blue

3rd BLUE – 21st BROWN Blue

4th ORANGE – 22nd BLACK Orange

5th YELLOW – 23rd RED Orange

6th BROWN – 24th BLUE Orange

7th RED Black 25th YELLOW Orange

8th BLUE Black 26th BROWN Orange

9th ORANGE Black 27th BLACK Yellow

10th YELLOW Black 28th RED Yellow

11th BROWN Black 29th BLUE Yellow

12th BLACK Red 30th ORANGE Yellow

13th BLUE Red 31st BROWN Yellow

14th ORANGE Red 32nd BLACK Brown

15th YELLOW Red 33rd RED Brown

16th BROWN Red 34th BLUE Brown

17th BLACK Blue 35th ORANGE Brown

18th RED Blue 36th YELLOW Brown

Method #1-E2 per ICEA S-73-532

Method 4 of ICEA S-73-532

Conductor Printing Details Conductor Printing Details

1st “1-ONE-1” 5th “5-FIVE-5”

2nd “2-TWO-2” 6th “6-SIX-6”

3rd “3-THREE-3” 7th “7-SEVEN-7”

4th “4-FOUR-4” 8th “8-EIGHT-8”

Page 17: TYPE MC-HL POWER, CONTROL & …amercable-com.vps-texasschoolguide-org.vps.ezhostingserver.com/... · IEC 60332-3 category A fire test, IEEE 1202 and CSA FT4. CORFLEX rated less

WHAT CAN YOU EXPECT FROM NEXANSAMERCABLE?

■ High-Quality Cable with an Emphasis on Safety

■ On-Time Delivery

■ Professional Sales, Support and Service

■ Strategic Inventory Locations

■ Short Lead Times

Nexans TrayCables

Cables for wet ordry locations incable trays,

raceways, open airor direct burial

NEXANS AMERCABLE’S DOWNSTREAM CABLE PRODUCTS

NexansInstrumentation

Cables300V & 600V Pairs

and Triads

Flame RetardantEP/CPE

Power, Control &Instrumentation

Cables

Industrial CIRCrush and ImpactResistant cableswithout externalarmoring

Industrial VFDFoil shielded,power cables

engineered for usein variable

frequency AC driveapplications.

Available in severalconstructions

Nexans AmerCable is the leading global manufacturerof jacketed power, control and instrumentation cables forharsh industrial environments.

Nexans AmerCable is an ISO 9001 certifiedcable manufacturer that combines leading-edge technology, proven manufacturingtechniques and high quality service to deliverthe finest cable products available.

Our professional field engineering and customer supportteams work directly with customers or in partnership with a network of independent distributors to deliverproductivity enhancing cable solutions for downstream facilities.

Nexans AmerCable10633 West Little York Road - Building 1 - Suite 150800-506-9473 • 713-896-5800 Fax: 713-849-9009email: [email protected]© 2018, AmerCable Incorporated 1_18

CLICK HERE TOFOLLOW US!