typical laboratory retrofit
TRANSCRIPT
Typical Laboratory Retrofit
Project Submittal Package 2021/02/26
Typical Laboratory Retrofit
Sales Rep
Antec Controls by Price
Consulting Engineer
Antec Controls by Price
Typical Laboratory Retrofit
Schedule 2021/02/26
Valve and Controller Schedule
Val
ve M
od
el
Val
ve T
ag
Ro
om
Ap
plic
atio
n
Un
it S
ize
MA
X F
low
(CF
M)
MIN
Flo
w(C
FM
)
MIN
Un
occ
up
ied
Flo
w(C
FM
)
Ro
om
Off
set
(CF
M)
Bo
dy
Typ
e
Pre
ssu
re R
ang
e
Ori
enta
tio
n
Co
atin
g
Insu
lati
on
Co
nn
ecti
on
Typ
e
Co
ntr
ol T
ype
Co
ntr
ols
Act
uat
or
Co
ntr
ol
Act
uat
or
Res
po
nse
Act
uat
or
Fai
l Po
siti
on
Acc
esso
ries
En
clo
sure
Ass
emb
ly
Cal
ibra
tio
n M
eth
od
VA
Req
uir
ed
Qu
anti
ty
No
tes
VVR SAV-R Laboratory SAV 114 1280 2150 1280 200 - M - - - - - PACE VDC HSA FLP - ENCL FLDC 41.0 1 1, 2VVR GEV-R Laboratory GEV 114 530 2150 530 200 - M - - - - - PACE VDC HSA FLP - ENCL FLDC 41.0 1 1, 2VVR FEV-R-1 Laboratory FEV 108 100 400 0 200 - M - - - - - FHC VDC HSA FLP - ENCL FLDC 63.0 1 1, 2VVR FEV-R-2 Laboratory FEV 108 100 400 0 200 - M - - - - - FHC VDC HSA FLP - ENCL FLDC 63.0 1 1, 2
Nomenclature:
108 8" Diameter - Single Body 114 14" Diameter - Single Body ENCL Controller Enclosure Assembly
FEV Fume Hood Exhaust Valve FHC Fume Hood Controller FLDC Field Calibrated Curve
FLP Fail Last Position GEV General Exhaust Valve HSA High Speed Actuator
M Medium Pressure (0.6 to 3.0 in.w.c) PACE Pace Controller SAV Supply Air Valve
VDC Modulating (0-10 VDC) Actuator VVR-1-3 Venturi Valve Retrofit
Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
Typical Laboratory Retrofit
Schedule 2021/02/26
ES Schedule
Ro
om
Co
ntr
ol A
cces
sori
esM
od
el
Val
ve T
ag
Ro
om
Nam
e
Sen
sor
Typ
e
Dis
pla
y T
ype
Set
po
int
Ad
just
men
t
Rel
ativ
e H
um
idit
y
Car
bo
n D
ioxi
de
Occ
up
ancy
Qu
anti
ty
No
tes
ES SAV-R Laboratory RM LCD BTN 1 1, 2ES SAV-R Laboratory DT 1 1, 2
Nomenclature:
BTN Pushbutton Setpoint Adjustment
DT Duct Mounted Sensor
ES-1-3 Environmental Sensor
LCD LCD Display
RM Room Temperature Sensor
Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
Typical Laboratory Retrofit
Schedule 2021/02/26
POT Schedule
Ret
rofi
t A
cces
sori
es M
od
el
Typ
e
Qu
anti
ty
No
tes
POT SPR 1 1, 2
Nomenclature:
POT-1-1 Potentiometer
SPR Standard Potentiometer Replacement
Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
Typical Laboratory Retrofit
Schedule 2021/02/26
FHC Accessories Schedule
FH
C A
cces
sori
es M
od
el
Val
ve T
ag
Sas
h L
eng
th
Ret
rofi
t A
cces
sory
Qu
anti
ty
No
tes
FHI FEV-R-1 - MP7 1 1, 2FHI FEV-R-2 - MP7 1 1, 2FPS FEV-R-1 - MP8 1 1, 2SPS FEV-R-1 50 - 1 1, 2SPS FEV-R-2 50 - 1 1, 2SWS FEV-R-1 - - 1 1, 2
Nomenclature:
FHI-1-2 Fume Hood Interface
FPS-1-2 Fume Hood Presence Sensor
MP7 Mounting Plate - 6.80" Hole Spacing
MP8 Mounting Plate - 8.25" Hole Spacing
SPS-1-1 Sash Position Sensor
SWS-1-1 Sidewall Face Velocity Sensor
Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
VVR-1-X
270213Rev.D
2020/05/11
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Venturi Valve Retrofit Kit
Product Submittal
CONTROLLER ENCLOSURE ASSEMBLY (ENCL),
CONTROLLER ENCLOSURE OPTIONS:
SINGLE VALVE DUAL VALVE
TRIPLE VALVE*SINGLE VALVE DUAL VALVE
FAIL IN PLACE (FLP)
FAIL OPEN POSITION (FOP)
FAIL CLOSED POSITION (FCP)
ACTUATOR FAIL SAFE OPTIONS:
STANDARD SPEED (SSA), FLP ONLY
HIGH SPEED (HSA)
ACTUATOR SPEED OPTIONS:
ENVIRONMENTAL (OPERATING) 50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)
VVR SPECIFICATIONS:
MOUNTING PLATE
.060in (2mm) GALV STEEL,
TO BE MOUNTED IN THE FIELD DIRECTLY ON RETROFIT VALVE,
NO MOUNTING HARDWARE INCLUDED
MOUNTING SPECIFICATIONS:
MEDIUM PRESSURE (M) - 0.6 to 3.0 in.w.c. (150-750 Pa), MEASURED ACROSS VALVE
LOW PRESSURE (L) - 0.3 to 3.0 in.w.c. (75-750 Pa), MEASURED ACROSS VALVE
PRESSURE RANGE OPTIONS:
*COMBINATION OF SINGLE VALVE AND DUAL VALVE RETROFIT KITS.
VDC CONTROL SIGNAL (VDC)
2-POSITION CONTROL SIGNAL (2P)
ACTUATOR CONTROL OPTIONS:
13.5" (343)
5.5" (140)
3.0" (76) CONTROLLER ENCLOSURE,OPTIONAL
CONTROLLER ENCLOSURE,OPTIONAL
PACE, FHC or LMX ENCLOSURE MOUNTED
11.5" (292)
2.9" (74)
5.0" (127)
7.0" (178)
11.5" (292)
5.0" (127)
CONTROLLER ENCLOSURE,OPTIONAL
Sheet 1 of 2
NOTE: PLEASE REFER TO PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
VVR-1-X
270213Rev.D
2020/05/11
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Venturi Valve Retrofit Kit
Product Submittal
UNIT
SIZE
ACTUATOR
CONTROL
ACTUATOR
RESPONSE
ACTUATOR
FAIL POSITIONPART # QTY
SSA 019127-002 1
019127-001 1
FOP/FCP 019127-003 1
SSA 019128-001 1
019128-003 1
FOP/FCP 019127-007 1
SSA 019127-002 1
019127-001 1
FOP/FCP 019127-003 1
SSA 019128-001 1
019128-003 1
FOP/FCP 019127-007 1
SSA 019127-005 1
019127-004 1
FOP/FCP 019127-003 1
SSA 019128-002 1
019128-009 1
FOP/FCP 019127-007 1
SSA 019127-005 1
019127-004 1
FOP/FCP 019127-003 1
SSA 019128-002 1
019128-009 1
FOP/FCP 019127-007 1
SSA 019127-005 1
019127-004 1
FOP/FCP 019127-003 1
SSA 019128-002 1
019128-009 1
FOP/FCP 019127-007 1
SSA 019127-005 1
019127-004 1
FOP/FCP 019127-003 1
SSA 019128-002 1
019128-009 1
FOP/FCP 019127-007 1
SSA 019127-005 1
019127-004 1
FOP/FCP 019127-003 1
SSA 019128-002 1
019128-009 1
FOP/FCP 019127-007 1
214
2P
VDC
VDC
2P
VDC
2P
VDC
2P
VDC
108
110
112
114
210
212
2P
VDC
2P
VDC
2P
FLP
HSA
HSA
HSA
HSA
HSA
FLP
FLP
FLP
FLP
FLP
HSA
HSA
HSA
HSA
FLP
FLP
FLP
FLP
HSA
HSA
HSA
HSA
HSA
FLP
FLP
FLP
FLP
ACTUATOR REFERENCE CHART
Sheet 2 of 2
NOTE: SEE VALVE ACTUATOR PRODUCT SUBMITTAL FOR ACTUATOR SPECIFICATIONS.
NOTE: PLEASE REFER TO PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
PACE-1-X
270117Rev. K
2020/11/20
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Pace™ - Critical Space Controller
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
Sheet 1 of 7
VENTURI VALVE (VV)
DIMENSIONS:
AIRFLOW DEVICE TYPE:
PRESSURE SENSOR 0 to 4.0 in.w.c. (0 to 1000 Pa)
VENTURI FX (VFX) OR TERMINAL (TU)
PRESSURE SENSOR 0 to 2.0 in.w.c. (0 to 500 Pa)
PANEL MOUNTED (PM)
AIRFLOW DEVICE MOUNTED (DEFAULT)
MOUNT:
8.90 (226)
1.89 (48)
9.55 (243)
4.48 (114)
1.22 (31)
8.31 (211)
3.77 (114)
ENVIRONMENTAL (OPERATING)
ENVIRONMENTAL (STORAGE)
INDICATORS
HOUSING
RATED IMPULSE VOLTAGE
COMMUNICATION PROTOCOL
DEVICE TYPE B-AAC
COMMUNICATION TYPE MS/TP (RS-485)
COMMUNICATION SPEED 9600, 19200, 38400, 76800
CERTIFICATION BTLBACNET
CONTROL PRIORITY ORDER1. ANTEC TOOLBOX2. BACNET3. NORMAL OPERATION
STATUS LED
UL 94 V-0, PC-ABS PLASTIC
330 V (AFTER TRANSFORMER)
BACNET MS/TP
OUTPUTS
INPUTS
INPUT POWER
PACE SPECIFICATIONS:
32⁰F to 130⁰F (0⁰C to 55⁰C), 5% to 95% R.H.(NON-CONDENSING)
-22⁰F to 158⁰F (-30⁰C to 70⁰C), 0% to 95% R.H.(NON-CONDENSING)
24 VAC, 50/60 Hz SINGLE PHASE, 75 VA MAX (18 VA EXCLUDING EXTERNAL LOADS), CLASS 2 or LPS PELV
2 BINARY INPUTS (CONTACT CLOSURE),4 ANALOG INPUTS (0 to 10 VDC), 2 10K TYPE 2 THERMISTORS INPUTS, ROOM INFORMATION NETWORK,SENSOR INFORMATION NETWORK,2 POT INPUTS,2 RS485 NETWORK (FHN, BACNET),1 TRANSDUCER (VV: 0-4 in.w .c., VFX: 0-2 in.w .c.)
2 ACTIVE BINARY OUTPUTS (24 VAC, MAX: 500 mA),4 ANALOG OUTPUTS (0 to 10 VDC, MAX:10 mA)
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
PACE-1-X
270117Rev. K
2020/11/20
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Pace™ - Critical Space Controller
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
Sheet 2 of 7
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Object Name Units Range DescriptionWrite
Setting
AI#1 [Pace name] AI1 – [AI1 Device name] Dynamic DynamicAnalog Input w ith multiple usesSee Input section of the Antec Toolbox manual for options
R
AI#2 [Pace name] AI2 – [AI2 Device name] Dynamic DynamicAnalog Input w ith multiple usesSee Input section of the Antec Toolbox manual for options
R
AI#3 [Pace name] AI3 – [AI3 Device name] Dynamic DynamicAnalog Input w ith multiple usesSee Input section of the Antec Toolbox manual for options
R
AI#4 [Pace name] AI4 – [AI4 Device name] Dynamic DynamicAnalog Input w ith multiple usesSee Input section of the Antec Toolbox manual for options
R
AI#5 [Pace name] T1 – [T1 Device name] °F or °C-40 to 250 °F
(-40 to 121 °C)Thermistor reading R
AI#6 [Pace name] T2 – [T2 Device name] °F or °C-40 to 250 °F
(-40 to 121 °C)Thermistor reading R
BI#1 [Pace name] BI1 – [BI1 Device name] Open/Closed Open/ClosedBinary Input w ith multiple usesSee Input section of the Antec Toolbox manual for options
R
BI#2 [Pace name] BI2 – [BI2 Device name] Open/Closed Open/ClosedBinary Input w ith multiple usesSee Input section of the Antec Toolbox manual for options
R
AO#1 [Pace name] AO1 – [AO1 Device name] VDC 0 to 10Analog Output w ith multiple usesSee Output section of the Antec Toolbox manual for options
R/W
AO#2 [Pace name] AO2 – [AO2 Device name] VDC 0 to 10Analog Output w ith multiple usesSee Output section of the Antec Toolbox manual for options
R/W
AO#3 [Pace name] AO3 – [AO3 Device name] VDC 0 to 10Analog Output w ith multiple usesSee Output section of the Antec Toolbox manual for options
R/W
AO#4 [Pace name] AO4 – [AO4 Device name] VDC 0 to 10Analog Output w ith multiple usesSee Output section of the Antec Toolbox manual for options
R/W
BO#1 [Pace name] BO1 – [BO1 Device name] Active/Inactive Active/InactiveBinary Output w ith multiple usesSee Output section of the Antec Toolbox manual for options
R/W
BO#2 [Pace name] BO2 – [BO2 Device name] Active/Inactive Active/InactiveBinary Output w ith multiple usesSee Output section of theAntec Toolbox manual for options
R/W
AV1 Room Pressure Setpoint in.w .c.; Pa-5.0 to 5.0 in.w .c.
(-1245 to 1245 Pa)Current room pressure setpointHidden when pressure control not used
R/W
AV2 Room Pressure in.w .c.; Pa-5.0 to 5.0 in.w .c.
(-1245 to 1245 Pa)Current room pressure R
AV3 Room Pressure Low Alarm in.w .c.; Pa-5.0 to 5.0 in.w .c.
(-1245 to 1245 Pa)Low room pressure alarm setpoint (+/-) R/W
AV4 Room Pressure High Alarm in.w .c.; Pa-5.0 to 5.0 in.w .c.
(-1245 to 1245 Pa)High room pressure alarm setpoint (+/-) R/W
AV5 Airf low Offset Setpoint CFM; L/s-50000 to 50000 CFM(-23600 to 23600 L/s)
Current airf low offset setpointHidden when offset control not used
R/W
Note: Analog output AO1 will display as AO11 for Pace™ Controller 1, AO21 for Pace™ Controller 2, etc.
Note: Analog output BO1 will display as BO11 for Pace™ Controller 1, BO21 for Pace™ Controller 2, etc.
ANALOG VALUE
BINARY OUTPUTS
BACNET POINTS LIST v1.2.0 OR NEWER
BINARY INPUTS
ANALOG OUTPUTS
ANALOG INPUTS
Note: Analog input AI1 will display as AI11 for Pace™ Controller 1, AI21 for Pace™ Controller 2, etc.
Note: Binary input BI1 will display as BI11 for Pace™ Controller 1, BI21 for Pace™ Controller 2, etc.
PACE-1-X
270117Rev. K
2020/11/20
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Pace™ - Critical Space Controller
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
Name Units Range DescriptionWrite
Setting
AV6 Airf low Offset Actual CFM; L/s-50000 to 50000 CFM(-23600 to 23600 L/s)
Current airf low offset (+/-) R
AV7 Total Exhaust Airf low Target CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Total room exhaust airf low target R
AV8 Total Exhaust Airf low Actual CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Total room exhaust airf low R
AV9 Total Supply Airf low Target CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Total room supply airf low target R
AV10 Total Supply Airf low Actual CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Total room supply airf low R
AV11 Total Fume Hood Exhaust CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Total fume hood exhaust airf lowHidden if no fume hoods connected
R
AV12 Room Volume ft3; m30 to 100000 ft3
(0 to 2830 m3)Room volume R/W
AV13 Current Air Change Rate # 0.0 to 100.0 Current air change rate R
AV14 Temperature Setpoint - Zone 1 °F;°C-40 to 250 °F
(-40 to 121 °C)
Temperature setpoint in zone 1Hidden if there are no temperature zones
R/W
AV15 Temperature Reading - Zone 1 °F;°C-40 to 250 °F
(-40 to 121 °C)Current temperature in zone 1 R
AV16 Temperature Setpoint - Zone 2 °F;°C-40 to 250 °F
(-40 to 121 °C)
Temperature setpoint in zone 2Hidden if multiple zones have not been configured
R/W
AV17 Temperature Reading - Zone 2 °F;°C-40 to 250 °F
(-40 to 121 °C)
Current temperature in zone 2Hidden if multiple zones have not been configured
R
AV18 Temperature Setpoint - Zone 3 °F;°C-40 to 250 °F
(-40 to 121 °C)
Temperature setpoint in Zone 3Hidden if multiple zones have not been configured
R/W
AV19 Temperature Reading - Zone 3 °F;°C-40 to 250 °F
(-40 to 121 °C)
Current Temperature in zone 3Hidden if multiple zones have not been configured
R
AV20 Room Temperature Setpoint - Low Limit °F;°C-40 to 250 °F
(-40 to 121 °C)Low est user-adjustable temperature setpoint on the thermostat R/W
AV21 Room Temperature Setpoint - High Limit °F;°C-40 to 250 °F
(-40 to 121 °C)Highest user-adjustable temperature setpoint on the thermostat R/W
AV22 DAT Low Limit °F;°C-40 to 250 °F
(-40 to 121 °C)
Discharge air temperature low temperature limitHidden if DAT limits are not enabled
R/W
AV23 DAT High Limit °F; °C-40 to 250 °F
(-40 to 121 °C)
Discharge air temperature high temperature limit Hidden if DAT limits are not enabled
R/W
AV24 Supply Airf low Setpoint CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Supply airf low setpointHidden if Supply airflow control not used
R/W
AV25 Supply Airf low Actual CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Supply airf lowHidden if Supply airflow control not used
R
AV26 Temperature Load - Zone 1 % -100% to 100%Temperature load in Zone 1 Hidden if there are no temperature zones
R
AV27 Temperature Load - Zone 2 % -100% to 100%Temperature load in Zone 2Hidden if multiple zones have not been configured
R
AV28 Temperature Load - Zone 3 % -100% to 100%Temperature load in Zone 3Hidden if multiple zones have not been configured
R
BACNET POINTS LIST v1.2.0 OR NEWER (CONTINUED)
Object
ANALOG VALUE
Sheet 3 of 7
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
PACE-1-X
270117Rev. K
2020/11/20
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Pace™ - Critical Space Controller
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
Sheet 4 of 7
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Object Name Units Range DescriptionWrite
Setting
AV29 Exhaust Airf low Setpoint CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Exhaust airf low setpointHidden if Exhaust airflow control not used
R/W
AV30 Exhaust Airf low Actual CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Exhaust airf lowHidden if Exhaust airflow control not used
R
AV81 [Mode name #1] - Room Min CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low minimum for the default room mode R/W
AV82 [Mode name #1] - Room Heating Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low heating maximum for the default room mode R/W
AV83 [Mode name #1] - Room Cooling Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low cooling maximum for the default room mode R/W
AV84 [Mode name #2] - Room Min CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low minimum for the second room modeHidden if using using less than 2 room modes
R/W
AV85 [Mode name #2] - Room Heating Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low heating maximum for the second room modeHidden if using using less than 2 room modes
R/W
AV86 [Mode name #2] - Room Cooling Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low cooling maximum for the second room modeHidden if using using less than 2 room modes
R/W
AV87 [Mode name #3] - Room Min CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low minimum for the third room modeHidden if using using less than 3 room modes
R/W
AV88 [Mode name #3] - Room Heating Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low heating maximum for the third room modeHidden if using using less than 3 room modes
R/W
AV89 [Mode name #3] - Room Cooling Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low cooling maximum for the third room modeHidden if using using less than 3 room modes
R/W
AV90 [Mode name #4] - Room Min CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low minimum for the fourth room modeHidden if using using less than 4 room modes
R/W
AV91 [Mode name #4] - Room Heating Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low heating maximum for the fourth room modeHidden if using using less than 4 room modes
R/W
AV92 [Mode name #4] - Room Cooling Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low cooling maximum for the fourth room modeHidden if using using less than 4 room modes
R/W
AV93 [Mode name #5] - Room Min CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low minimum for the f if th room modeHidden if using using less than 5 room modes
R/W
AV94 [Mode name #5] - Room Heating Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low heating maximum for the f if th room modeHidden if using using less than 5 room modes
R/W
AV95 [Mode name #5] - Room Cooling Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low cooling maximum for the fifth room modeHidden if using using less than 5 room modes
R/W
AV96 [Mode name #6] - Room Min CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low minimum for the sixth room modeHidden if using using less than 6 room modes
R/W
AV97 [Mode name #6] - Room Heating Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low heating maximum for the sixth room modeHidden if using using less than 6 room modes
R/W
AV98 [Mode name #6] - Room Cooling Max CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Room f low cooling maximum for the sixth room modeHidden if using using less than 6 room modes
R/W
BACNET POINTS LIST v1.2.0 OR NEWER (CONTINUED)
PACE-1-X
270117Rev. K
2020/11/20
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Pace™ - Critical Space Controller
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
Sheet 5 of 7
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Object Name Units Range DescriptionWrite
Setting
AV#01 [Pace name] Flow - [POT1 Device name] CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
POT1 airf low readingHidden when POT1 is not used
R
AV#02 [Pace name] Flow - [POT2 Device name] CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
POT2 airf low readingHidden when POT2 is not used
R
AV#03 [Pace name] - Valve Pressure in.w .c.; Pa-5.0 to 5.0 in.w .c.(-1245 to 1245 Pa)
Valve PressureHidden when device type is not VV
R
AV#04[Pace name] Flow - [Transducer Device name]
CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Transducer airf low readingHidden when airflow source is not transducer
R
AV#05 [Pace name] AI1 - DAT Setpoint °F;°C-40 to 250 °F
(-40 to 121 °C)Discharge Air Temperature Setpoint for AI1Hidden when DAT control is not enabled
R/W
AV#06 [Pace name] AI2 - DAT Setpoint °F;°C-40 to 250 °F
(-40 to 121 °C)Discharge Air Temperature Setpoint for AI2Hidden when DAT control is not enabled
R/W
AV#07 [Pace name] AI3 - DAT Setpoint °F;°C-40 to 250 °F
(-40 to 121 °C)Discharge Air Temperature Setpoint for AI3Hidden when DAT control is not enabled
R/W
AV#08 [Pace name] AI4 - DAT Setpoint °F;°C-40 to 250 °F
(-40 to 121 °C)Discharge Air Temperature Setpoint for AI4Hidden when DAT control is not enabled
R/W
AV#09 [Pace name] T1 - DAT Setpoint °F;°C-40 to 250 °F
(-40 to 121 °C)Discharge Air Temperature Setpoint for T1Hidden when DAT control is not enabled
R/W
AV#10 [Pace name] T2 - DAT Setpoint °F;°C-40 to 250 °F
(-40 to 121 °C)Discharge Air Temperature Setpoint for T2Hidden when DAT control is not enabled
R/W
AV#11 Fume Hood # Airf low CFM; L/s0 to 50000 CFM(0 to 23600 L/s)
Displays the current airf low being exhausted from the fume hood
R
AV#12 Fume Hood # Face Velocity FPM; m/s0 to 1000 FPM(0 to 5.08 m/s)
Displays the current face velocity across the fume hood R
AV#13 Fume Hood # Sash Position % 0 to 100 Displays the current position of the sash on the fume hood R
AV#14 Fume Hood # Valve Pressure in.w .c.; Pa-5.0 to 5.0 in.w .c.(-1245 to 1245 Pa)
Displays the current pressure across the valve on the fume hood
R
MV1 Airf low Control Sequence Text 3 states
Displays the current airf low control sequence1 - Constant Flow Control2 - Pressure Control3 - Offset Control
R
MV2 Room Pressure Mode Text 2 statesDisplays the current room pressure mode1 - Positive2 - Negative
R
MULTISTATE VALUE
BACNET POINTS LIST v1.2.0 OR NEWER (CONTINUED)
Note: Analog value AV#01 will display as AV101 for Pace™ Controller 1, AV201 for Pace™ Controller 2, etc.
Note: Analog value AV#11 will display as AV111 for Fume Hood Controller (FHC) 1, AV211 for Fume Hood Controller (FHC) 2, etc.
PACE-1-X
270117Rev. K
2020/11/20
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Pace™ - Critical Space Controller
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
Object Name Units Range DescriptionWrite
Setting
MV3 Room Alarm Status Text 13 states
Displays the current room alarm status1 - Controller Not Responding2 - Missing Room Pressure Sensor3 - Diversity4 - Binary Input5 - Mode Alarm6 - Door Open 7 - Room Low Pressure8 - Room High Pressure9 - Low Airf low10 - Low Valve Pressure11 - High Airf low12 - High Valve Pressure13 - No Alarm
R
MV4 Room Mode Text 6 states
Displays the current room mode1 - [Default Room Mode Name]2 - [Custom Room Mode 1 Name]3 - [Custom Room Mode 2 Name]4 - [Custom Room Mode 3 Name]5 - [Custom Room Mode 4 Name]6 - [Custom Room Mode 5 Name]
R/W
MV5 Room Mode Override Text 6 states
Displays the current room mode override1 - [Default Room Mode Name]2 - [Custom Room Mode 1 Name]3 - [Custom Room Mode 2 Name]4 - [Custom Room Mode 3 Name]5 - [Custom Room Mode 4 Name]6 - [Custom Room Mode 5 Name]
R/W
MV99 Firmw are Update Status Text 4 states
Displays the current f irmw are update status1 - Idle2 - Start Firmw are Update3 - Updating Firmw are4 - Firmw are Update Failed
R/W
MV#1 Fume Hood # Status Text 6 states
Displays the status of the fume hoods1 - Missing FHC2 - Normal3 - Caution4 - Alarm5 - Setback6 - Off
R
Note: Multistate value MV#1 will display as MV11 for Fume Hood Controller (FHC) 1, MV21 for Fume Hood Controller (FHC) 2, etc…
BACNET POINTS LIST v1.2.0 OR NEWER (CONTINUED)
MULTISTATE VALUE
Sheet 6 of 7
PACE-1-X
270117Rev. K
2020/11/20
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Pace™ - Critical Space Controller
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
Sheet 7 of 7
NOTE: The BACnet point names can be overridden using Antec Toolbox and may not match the names listed in this table. The instance numbers can be used in this case to identify the points.
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Object Name Units Range DescriptionWrite
Setting
MV#2 Fume Hood # Error Type Text 21 states
Displays the cause of any alarms or cautions on the fume hoods1 - No Error2 - Emergency3 - Netw ork4 - Contact Input5 - No Primary Sensor6 - No Sec. Sensor7 - No Sash18 - No Sash29 - No Sash 310 - Low Velocity11 - High Velocity12 - Low Pressure13 - High Pressure14 - Venturi Out of Range15 - Sash Height16 - Low Airf low17 - High Airf low18 - Sash Broken19 - BI120 - BI221 - Setback Sash Height
R
FIL1 Firmw are - -The file object used for f irmw are upgrades - feature only available if supported by BAS
W
CAL1 Calendar Object - - The calendar object used for scheduling R/W
EVC1 Notif ication Class object - - The notif ication class object for alarming R/W
SCH1 Room Mode Schedule - - The scheduling object for scheduling room mode changes R/W
NOTIFICATION CLASS
SCHEDULE
BACNET POINTS LIST v1.2.0 OR NEWER (CONTINUED)
CALENDAR
FILE
Note: Multistate value MV#1 will display as MV11 for Fume Hood Controller (FHC) 1, MV21 for Fume Hood Controller (FHC) 2, etc…
VARIABLE DEFAULT COV INCREMENT UNITS
Airflow 50 CFM
Offset 20 CFM
Actuator 0.001 V
Heating 0.001 V
Pressure 0.001 in.w .c.
Valve Pressure 0.2 in.w .c.
ACH 1 ACH
CO2 100 ppm
Face Velocity 10 FPM
Humidity 1 %
Position 1 %
Room Volume 100 ft³
Temperature 0.5 °F
Temperature Load 0.1 %
VOC 100 ppm
Voltage 0.05 V
PACE DEFAULT CHANGE OF VALUE (COV) INCREMENTS
FHC-1-X
270113Rev.B
2019/06/19
© Copyright Antec Controls by PRICE 2019
So
lid E
dge
Fume Hood Controller
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
DIMENSIONS:
7.0 (178)
2.50 (64)4.0 (102)
7.5 (191)
2.4 (61)
6.2 (157) .7 (17)
3.56 (90)
Sheet 1 of 3
VENTURI VALVE (VV)
AIRFLOW DEVICE TYPE:
PRESSURE SENSOR 0 to 5.0 in.w.c. (0 to 1250 Pa)
VENTURI FX (VFX) OR TERMINAL (TU)
PRESSURE SENSOR 0 to 2.0 in.w.c. (0 to 500 Pa)
PANEL MOUNTED (PM)
AIRFLOW DEVICE MOUNTED (DEFAULT)
MOUNT:
NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ENVIRONMENTAL (OPERATING)
ENVIRONMENTAL (STORAGE)
INPUT POWER
INDICATORS
HOUSING
COMMUNICATION PROTOCOL
DEVICE TYPE B-ASC
COMMUNICATION TYPE MS/TP (RS-485)
COMMUNICATION SPEED 9600, 19200, 38400, 76800
CERTIFICATION BTLBACNET
FHC SPECIFICATIONS:
50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
-22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)
24 VAC +/- 10%, 50/60 Hz, 40 VA (EXTERNAL LOADS NOT INCLUDED), CLASS 2
2 BINARY INPUTS,
2 SIDEWALL SENSOR INPUTS,
3 SASH POSITION SENSOR INPUTS
2 ANALOG OUTPUTS (0 to 10 VDC, MAX:10 mA),
1 BINARY OUTPUT (DRY CONTACT),
2 BINARY OUTPUTS (MAX: 24 VAC, 500 mA)
STATUS LEDs
UL 94V - 0, ABS PLASTIC
FHN (FUME HOOD NETWORK), BACNET (*ONLY WHEN FHN NOT USED)
1. BACNET
2. NORMAL OPERATIONCONTROL PRIORITY ORDER
INPUTS
OUTPUTS
270736Rev. E
2020/02/21
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Valve Actuator
Product Submittal
DIMENSIONS:
ACTUATOR - 35 in-lbs (4 Nm), VDC, HSA, FLP
Sheet 2 of 14
TERMINATION:
3.15 (80)
1.97 (50)
2.95 (75)
7.35 (187)
.98 (25)
4.88 (124)
BLACKREDWHITEORANGE
RED INPUT POWER, HOT
BLACK INPUT POWER, COM M ON
WHITE CONTROL SIGNAL
ORANGE NOT USED
DIRECTION OF ROTATION SWITCH
POWER ADAPTION BUTTON
MANUAL OVERRIDE BUTTONNOTE: DO NOT PRESS WHEN AIRFLOW IS PRESENT
10
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
ENVIRONMENTAL (OPERATING) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -40⁰F to 176⁰F (-40⁰C to 80⁰C), 5% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 20%, 50/60 Hz, 23 VA, CLASS 2
CONTROL SIGNAL RANGE 2 to 10 VDC
DIRECTION OF ROTATION REVERSIBLE WITH BUILT-IN SWITCH (FACTORY SET TO 0)
TORQUE 35 in-lb (4 Nm)
MANUAL OVERRIDE EXTERNAL PUSH BUTTON
RUNNING TIME 2.5 sec
HOUSING NEMA 2, IP54, UL ENCLOSURE TYPE 2
HOUSING MATERIAL UL94 -5VA
WEIGHT 1.8 lbs (0.85 kg)
PART # (BELIMO MODEL) 019127-001 (LMQB24-MFT)
SPECIFICATIONS:
ANGLE OF ROTATIONMIN 30°, MAX 95°, ADJUSTABLE WITH MECHANICAL STOP
ELECTRONICALLY VARIABLE (POWER ADAPTION)
270736Rev. E
2020/02/21
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Valve Actuator
Product Submittal
Sheet 5 of 14
DIMENSIONS:
TERMINATION:
BLACKREDWHITEORANGE
RED INPUT POWER, HOT
BLACK INPUT POWER, COM M ON
WHITE CONTROL SIGNAL
ORANGE NOT USED
ACTUATOR - 70 in-lbs (8 Nm), VDC, HSA, FLP
2.49 63
1.18 30
4.06 103
5.20 132
5.24 133.1
8.30 211
3.46 88
DIRECTION OF ROTATION SWITCH
POWER ADAPTION BUTTON
MANUAL OVERRIDE BUTTONNOTE: DO NOT PRESS WHEN AIRFLOW IS PRESENT
1.69 43
10
ENVIRONMENTAL (OPERATING) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -40⁰F to 176⁰F (-40⁰C to 80⁰C), 5% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 20%, 50/60 Hz, 23 VA, CLASS 2
CONTROL SIGNAL RANGE 2 to 10 VDC
DIRECTION OF ROTATION REVERSIBLE WITH BUILT-IN SWITCH (FACTORY SET TO 0)
TORQUE 70 in-lbs (8 Nm)
MANUAL OVERRIDE EXTERNAL PUSH BUTTON
RUNNING TIME 4 sec
HOUSING NEMA 2, IP54, UL ENCLOSURE TYPE 2
HOUSING MATERIAL UL94 -5VA
WEIGHT 1.8 lbs (0.85 kg)
PART # (BELIMO MODEL) 019127-004 (NMQB24-MFT)
SPECIFICATIONS:
ANGLE OF ROTATIONMIN 30°, MAX 95°, ADJUSTABLE WITH MECHANICAL STOP
ELECTRONICALLY VARIABLE (POWER ADAPTION)
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
ES-1-X
270215Rev. G
2020/06/09
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Environmental Sensor
Product Submittal
DIMENSIONS:
ROOM TEMPERATURE SENSOR (RM) WITH DISPLAY (LCD) ANDPUSHBUTTON SETPOINT ADJUSTMENT (BTN)
3.0 (76)
4.4 (112)
1.0 (28)
3.28 (83)
CLOSED CELL FOAM
.7 (18)
COMMUNICATION PORT:
Sheet 4 of 11
RJ-45CKJ-B - PUSHDOWN CONNECTIONTO PACE CONTROLLERWHERE APPLICABLE
WALLMOUNT PLATE
WALLMOUNT PLATEFACE PLATE
TERMINATION:
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
EXT-TEMP
SET2
SET1
OVR1
SEN2
SEN1
OVR2
EXT-GND
OCCUPY
W1GND
V+
V + INPUT POWER, HOT
GND INPUT POWER, GROUND
SEN1
SEN2
SET1 TEM PERATURE SETPOINT OUTPUT
THERM ISTOR RESISTANCE OUTPUT
ENVIRONMENTAL (OPERATING) 32⁰F to 122⁰F (0⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
DISPLAY LCD SCREEN
INPUT TYPE KEYPAD
TEMPERATURE READING 10K-2 THERMISTOR, ±0.36⁰F, 32⁰ to 158⁰F (±0.2⁰C, 0 to 70⁰C)
HOUSING UL 94 V-0, ABS PLASTIC
COMMUNICATION PORT RJ-45
ES-RM-LCD-BTN SPECIFICATIONS:
MOUNTSTANDARD 2in. x 4in. (51mm x 102mm) J-BOX or
DRYWALL MOUNT
OUTPUT1 ANALOG (0 to 10 VDC):
TEMPERATURE SETPOINT - RANGE: 50⁰F to 90⁰F (10⁰C to 32⁰C)
INPUT POWER15 to 40 VDC or 15 to 28 VAC. (DO NOT RUN AC POWER IN THE
SAME CONDUIT AS SIGNAL WIRES)
°F/C
DISPLAY SWITCH (vF or vC)
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
ES-1-X
270215Rev. G
2020/06/09
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Environmental Sensor
Product Submittal
DIMENSIONS:
DUCT MOUNTED SENSOR (DT)
ENVIRONMENTAL (OPERATING) -40⁰F to 185⁰F (-4⁰C to 85⁰C), 0 to 95% R.H.(NON-CONDENSING)
TEMPERATURE READING 10K-2 THERMISTOR, ±0.36⁰F, 32⁰ to 158⁰F (±0.2⁰C, 0 to 70⁰C)
PROBE 304 STAINLESS STEEL PROBE, 0.25in. (7mm) DIAMETER, 6in. (152mm) LENGTH
HOUSING PC PLASTIC, UL 94 V-0, IP10, NEMA1
ES-DT SPECIFICATIONS:
2.1 (53)
3.0 (76) 2.67 (68)
1.78 (45)
TERMINATION:
YELLOW
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
YELLOW
YELLOW
THERM ISTOR RESISTANCE OUTPUT
YELLOW
Sheet 10 of 11
6.0 152
.25 6
8.0 202
POT-1-X
272002Rev. 0
2020/03/26
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Retrofit Potentiometer Replacement
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
1.6 42
1.1 29
24.0 ( 61 )
NOTE: PLEASE REFER TO VVR MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ENVIRONMENTAL (OPERATING) -67⁰F to 221⁰F (-50⁰C to 105⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -67⁰F to 221⁰F (-50⁰C to 105⁰C), 5% to 95% R.H.(NON-CONDENSING)
OUTPUT SIGNAL VOLTAGE DIVIDER UTILIZING 10K POT
RANGE SINGLE TURN ROTATION
CONNECTION TYPE 3-WIRE
HOUSING MATERIAL HIGH TEMP. THERMOPLASTIC
SHAFT MATERIAL STAINLESS STEEL
MATERIAL ALUMINUM
HEX SIZE 3/32"
MOUNTING BRACKETS MATERIAL 16 Ga GALVANIZED STEEL
EXTENSION PIN MATERIAL STAINLESS STEEL
POTENTIOMETER
SHAFT COUPLER
POT SPECIFICATIONS:
STANDARD POTENTIOMETER REPLACEMENT (SPR)
POTPACE
(POT 1 OR POT 2)
FHC/LM X
(RGB TERM INAL BLOCK)
RED + R
GREEN SIG G
BLACK - B
DIMENSIONS:
TERMINATION:
1.5 ( 38 )
GREEN
RED
BLACK
Sheet 1 of 2
FHI-1-X
270114Rev. C
2020/04/01
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Fume Hood Interface
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
DIMENSIONS:
NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
3.7 (94) MAX
2.94 (75) MIN
1.5 (38)
1.1 (28)
5.15 (131)
3.29 (84)
2.0 x 2.0(51 x 51)CUTOUT
.76 (19)
.36 (9)
ENVIRONMENTAL (OPERATING) 50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)
INPUT POWER POWERED FROM FUME HOOD CONTROLLER (FHC)
INDICATORS LCD SCREEN, 180⁰ SIDEVIEW RGB LED, SPEAKER
CONNECTION TYPE RJ-45
INPUT TYPE KEYPAD
HOUSING UL 94 V-0, ABS PLASTIC
FHI SPECIFICATIONS:
Sheet 1 of 2
FHI-1-X
270114Rev. C
2020/04/01
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Fume Hood Interface
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Sheet 2 of 2
RETROFIT ACCESSORY:
MOUNTING PLATE - 6.00" HOLE SPACING (MP6)
MOUNTING PLATE - 6.80" HOLE SPACING (MP7)
MOUNTING PLATE - 9.38" HOLE SPACING (MP9)
7.00 178
7.80 198
10.38 264
3.25 83
3.25 83
3.25 83
6.00 1526.80 173
9.38 238
MP6 PLATE MP7 PLATE MP9 PLATE
O .19 5
O .19 (5)
O .19 (5)
MP6 PLATE SHOWN
MOUNTING PLATE MATERIAL 16ga STAINLESS STEEL, BRUSHED
SCREW #10 x .5", STAINLESS STEEL
ACCESSORY SPECIFICATIONS:
DIMENSIONS:
FPS-1-X
270115Rev. C
2020/03/30
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Fume Hood Presence Sensor
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
DIMENSIONS:
ENVIRONMENTAL (OPERATING) 50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 10%, 2 VA, CLASS 2
DETECTION DOPPLER SHIFT RADAR
DETECTION PATTERN SELECTABLE, WIDE OR NARROW
OUTPUTS 1 BINARY OUTPUT
FPS SPECIFICATIONS:
6.38 (162)
1.75 (44) 2.38 (60)
O 2.75 (70)
NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
TERMINATION:
BLACK
RED
GREEN
WHITEWHITE
BROWN
BLACK INPUT POWER, GROUND
RED INPUT POWER, HOT
BROWN RELAY, N/O
WHITE RELAY, COM M ON
GREEN RELAY, N/C
5.75 (146)
1.13 (29)
Sheet 1 of 2
FPS-1-X
270115Rev. C
2020/03/30
© Copyright Antec Controls by PRICE 2020
So
lid E
dge
Fume Hood Presence Sensor
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
Sheet 2 of 2
MOUNTING PLATE - 8.25" HOLE SPACING (MP8)
18.50 470
3.00 76
3.00 76
9.50 241
17.50 444
8.25 210
O .19 5
O .19 5
NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
RETROFIT ACCESSORY:
MOUNTING PLATE - 17.50" HOLE SPACING (MP18)
MOUNTING PLATE MATERIAL 16ga STAINLESS STEEL, BRUSHED
SCREW #10 x .5", STAINLESS STEEL
ACCESSORY SPECIFICATIONS:
MP8 PLATE SHOWN
DIMENSIONS:
MP8 PLATE
MP18 PLATE
SPS-1-X
270123Rev. C
2019/04/26
© Copyright Antec Controls by PRICE 2019
So
lid E
dge
Sash Position Sensor
Product Submittal
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
SASH POSITION SENSOR - 50in. (1270mm) STROKE RANGE
DIMENSIONS:
Sheet 1 of 2
3.5 (90)
3.6 (91)
1.45 (37)
O.14 (4)(2x)
2.0 (51)
2.0 (51)
1.8 (46)1.4 (36)
O.19 (5)
NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ENVIRONMENTAL (OPERATING) -50⁰F to 120⁰F (-10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
OUTPUT SIGNAL VOLTAGE DIVIDER UTILIZING 10K POT
CONNECTION TYPE 2-WIRE
MEASURING CABLE NYLON COATED STAINLESS STEEL
STROKE RANGE 0 to 50in. (0 to 1270mm)
HOUSING IP 50 PLASTIC
ACCURACY ±0.25% FS
SPS SPECIFICATIONS:
TERMINATION:
GREEN
RED
BL
AC
K
GREEN
RED
BLACK NOT REQUIRED
SASH POSITION FEEDBACK
SWS-1-X
270124Rev. C
2019/04/26
© Copyright Antec Controls by PRICE 2019
So
lid E
dge
Sidewall Sensor
Product Submittal
Sheet 1 of 1
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION INSTRUCTIONS SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
DIMENSIONS:
2.20 (56)
3.38 (86)
1.55 (39)
.38 (10)
ENVIRONMENTAL (OPERATING) 32⁰F to 120⁰F (0⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)
OUTPUT SIGNAL DIGITAL
CONNECTION TYPE CABLE, RJ12 TO HR30 ADAPTER, 25ft
RANGE ±0.1 in.w .c. (25 Pa)
HOUSING UL 94V - 0, ABS PLASTIC
ACCURACY 3% OF READING
SWS SPECIFICATIONS:
4.50 (114)
CONNECTIONS:
CABLE, 25ft
RJ12
HR30
Typical Laboratory Retrofit
Sequence of Operations 2021/02/26
Sequence Number: 1
Sequence Type: Flow Offset ControlRoom(s): Laboratory
Flow Offset Control:
Supply and General Exhaust with Fume Hoods: The Airflow Control System (ACS) will modulate the supply and general exhaust to maintain
the scheduled flow offset target. The ACS will sum the total exhaust airflow from all sources, including fume hoods and will modulate the
general exhaust air device to maintain the flow offset target. With no thermal demand, the supply will maintain the minimum scheduled value.
As airflow demand increases (see section: Temperature Control) the supply and general exhaust will be increased to maintain the scheduled
flow offset. With additional control sequences, the sequence with the highest demand for airflow will take priority.
Modes of Operation:
Occupied Mode (Default): Occupied Mode is the default room mode. While in Occupied Mode, the Airflow Control System (ACS) will target
the scheduled occupied airflows.
Emergency Mode: The Airflow Control System (ACS) will activate Emergency Mode by contact input.
While in Emergency Mode, the room air change rate will increase to the scheduled emergency room flow value. The ACS will maintain the
scheduled flow offset.
Fume Hood Control:
Hybrid Control: The Fume Hood Controller uses a sash position sensor (SPS) and a sidewall sensor (SWS) together to control the face
velocity of the fume hood. When a user moves the fume hood sash, the SPS measures the height of the vertical fume hood sash. The FHC will
calculate the correct airflow to result in the target face velocity and will modulate the air device to the airflow target. The FHC will then use the
SWS to adjust the airflow until the measured face velocity meets the target face velocity. The FHC will maintain a minimum airflow at all times
when the sash is closed to ensure the proper fume hood air change rate.
Fume Hood Occupancy: The Fume Hood Controller (FHC) uses a Fume Hood Presence Sensor (FPS) to determine if there is an occupant
present in front of the fume hood. When no occupant is detected, the FHC will modulate the exhaust device to maintain an unoccupied face
velocity target. When an occupant is detected, the fume hood controller will modulate the exhaust air device to target the occupied face velocity
target.
Fume Hood Emergency Purge: An emergency purge feature will activate when the Emergency button on the fume hood interface is pressed.
The air device will modulate to its fully open position to purge the fume hood. A visual and audible alarm will activate to indicate that the fume
hood is being purged. The emergency purge feature can be deactivated by pushing and holding the Emergency button for 5 seconds.
Fume Hood Alarms:
While the unit is in alarm, the LED light bars will be red. The audible alarm can be silenced but will re-engage after an adjustable time delay.
Audible and visual alarms are available for face velocity, low/high valve pressure, sash height, and emergency purge.
Typical Laboratory Retrofit
Sequence of Operations 2021/02/26
Face Velocity: The Fume Hood Controller (FHC) will alarm if the measured face velocity drops below the adjustable low alarm limit, or rises
above the adjustable high alarm limit.
Valve Pressure Alarms: The Fume Hood Controller (FHC) will alarm if the pressure across the venturi valve drops below the minimum or
rises above the maximum operating pressure for the valve.
Sash Alarm: The Fume Hood Controller (FHC) will alarm if the sash height is above the sash height alarm limit. The FHC will also alarm if the
sash position sensor cable fails or reports a value outside of the initially calibrated range.
Room Temperature Monitoring:
A room temperature sensor will measure the room temperature. Room temperature is available to the building management system (BMS).
The ES will display room temperature locally on the LCD display.
Duct Temperature Monitoring:
A duct temperature sensor will measure the duct temperature. Duct temperature is available to the building management system (BMS).
Valve Pressure Monitoring:
The PACE will monitor valve pressure. Valve pressure is available to the building management system (BMS).
The FHC will monitor valve pressure. Valve pressure is available to the building management system (BMS).
Local/Room Level Communication:
All valves and controllers in the Airflow Control System (ACS) within the room will communicate via an independent high-speed room level
network called the Room Information Network (RIN).
Building Network Communication:
The Airflow Control System (ACS) will communicate over a native BACnet MS/TP trunk to the building automation network. All points are
available to the building management system (BMS) with no network gateway required.
Space Temperature Control:
Single Stage Reheat: Stage I: Modulating Reheat Coil: The Airflow Control System (ACS) will monitor room temperature from a wall
mounted room temperature sensor. In the first heating stage, the reheat coil will modulate to maintain space temperature.
If there are multiple reheat coils, all coils will modulate together to maintain space temperature.
Second Fume Hood Control:
Sash Position Control: The Fume Hood Controller (FHC) uses a Sash Position Sensor (SPS) to control the face velocity of the fume hood.
When a user moves the fume hood sash, the SPS measures the height of the vertical fume hood sash. The FHC will calculate the correct
airflow to result in the target face velocity and will modulate the air device to the airflow target. The FHC will maintain a minimum airflow at all
times when the sash is closed to ensure the proper fume hood air change rate.
Fume Hood Emergency Purge: An emergency purge feature will activate when the Emergency button on the Fume Hood Interface (FHI) is
pressed. The air device will modulate to its fully open position to purge the fume hood. A visual and audible alarm will activate to indicate that
the fume hood is being purged. The emergency purge feature can be deactivated by pushing and holding the Emergency button for 5 seconds.
Typical Laboratory Retrofit
Sequence of Operations 2021/02/26
Second Fume Hood Alarms:
Face Velocity: The Fume Hood Controller (FHC) will alarm if the measured face velocity drops below the adjustable low alarm limit, or rises
above the adjustable high alarm limit.
Valve Pressure Alarms: The Fume Hood Controller (FHC) will alarm if the pressure across the Venturi Valve drops below the minimum or rises
above the maximum operating pressure for the valve.
Sash Alarm: The Fume Hood Controller (FHC) will alarm if the sash height is above the sash height alarm limit. The FHC will also alarm if the
Sash Position Sensor (SPS) cable fails or reports a value outside of the initially calibrated range.