typical laboratory retrofit - antec controls

40
Typical Laboratory Retrofit Project Submittal Package 2020/05/07 Typical Laboratory Retrofit Sales Representative: Antec Controls by Price MB Consulting Engineer: Antec Controls by Price MB

Upload: others

Post on 18-Dec-2021

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Typical Laboratory Retrofit - Antec Controls

Typical Laboratory Retrofit

Project Submittal Package 2020/05/07

Typical Laboratory Retrofit

Sales Representative:Antec Controls by Price

MB

Consulting Engineer:Antec Controls by Price

MB

Page 2: Typical Laboratory Retrofit - Antec Controls

Typical Laboratory Retrofit

Nomenclature 2020/05/07

Acronym Description108 8" diameter - Single body110 10" diameter - Single body112 12" diameter - Single body114 14" diameter - Single body210 10" diameter - Dual body212 12" diameter - Dual body214 14" diameter - Dual body312 12" diameter - Triple body314 14" diameter - Triple body412 12" diameter - Quadruple body414 14" diameter - Quadruple body°C Degrees celcius°F Degrees fahrenheit115-24V Transformer 115V supply120-1 120V single phase1L Left hand one row1R Right hand one row1RM Single room configuration208-1 208V single phase208-3 208V three phase240-1 240V single phase240-24V Transformer 240V supply24VAC 24VAC power connection277-1 277V single phase277-24V Transformer 277V supply2L Left hand two row2P 2-Position actuator2R Right hand two row2RM Two room configuration300VA 120/24VAC 300VA transformer316SS 316 stainless steel347-1 347V single phase3L Left hand three row3R Right hand three row3RM Three room configuration40VA 120/24VAC 40VA transformer480-24V Transformer 480V supply480-3 480V three phase4L Left hand four row4R Right hand four row4RM Four room configuration500VA 120/24VAC 500VA transformer50VA 120/24VAC 50VA transformer600-3 600V three phase6RM Six room configuration8RM Eight room configuration96VA 120/24VAC 96VA transformerABS ABS plastic - whiteACH Air changes per hourAD Coil access (upstream) fastened with screwsADD Coil access (upstream & downstream) fastened w/

screws

Acronym DescriptionADDL Coil access (upstream & downstream) fastened w/ snap

latchesADDQ Coil access (upstream & downstream) fastened w/

quarter turn sash latchADL Coil access (upstream) fastened w/ snap latchesADQ Coil access (upstream) fastened w/ quarter turn sash

latchAI Analog InputAL AluminumAO Analog OutputBACnet Building automation and control networkBI Binary InputBO Binary OutputBSC Biological safety cabinetBTN Pushbutton setpoint adjustmentCC Cooling coilCFL Companion flangeCFM Cubic feet per minuteCO2 Carbon dioxide sensorCOM CommonCRAF Cleanroom aluminum foil liner 5/8"CSL Heating coil shipped looseCV Constant volumeCVB Coil attached - Controls enclosure to bottomCVL Coil attached - Controls enclosure LHCVR Coil attached - Controls enclosure RHCVT Coil attached - Controls enclosure to topDBC Drawband clampDCS Door contact switchDCS-F Floor mount door contact switchDCS-S Surface mount door contact switchDDC Direct digital controlDPT Airflow pressure transducerDSF1 1 door switch - Flush mountDSF2 2 door switches - Flush mountDSF3 3 door switches - Flush mountDSS1 1 door switch - Surface mountDSS2 2 door switches - Surface mountDSS3 3 door switches - Surface mountDT Duct mounted sensorEARTH Earth groundEC Electric CoilEMCS Energy management and control systemENCL Controller enclosure assemblyEPR Extended Potentiometer ReplacementES Environmental sensorFAC Controls supplied by others - factory mountedFACC Factory calibrated curveFCP Fail closed positionFER Ferrite cable clamp (28A0593-0A2 or equivalent)FEV Fumehood exhaust valveFF Fiber free foam 3/4"FHC Fume hood controller

Page 3: Typical Laboratory Retrofit - Antec Controls

Typical Laboratory Retrofit

Nomenclature 2020/05/07

Acronym DescriptionFHI Fume hood interfaceFHN Fume hood networkFL Flange connectionFLD Controls supplied by others - field mountedFLDC Field calibrated curveFLP Fail last positionFOP Fail open positionFPI Fins per inchFPS Fume hood presence sensorFUS Main line fusingga GaugeGEV General exhaust valveGL Galvanized steelH HorizontalHC High capacity hot water coilHSA High speed actuatorHWC Hot water reheat coilHWV Modulating (0-10V) reheat valveI ImperialID Inner diameterIDSW Door interlock disconnectIN 3/4" external foam insulationin. Inchesin.w.c. Inches water columnK Kynar coatingKP KeypadKSW Isolation/setback keyswitchLMX Linearization moduleLP Low pressure (0.3 to 3.0in.w.c)M Metricmm MillimetersMP Medium pressure (0.6 to 3.0in.w.c)MP6 Mounting Plate - 6.00" Hole SpacingMP7 Mounting Plate - 6.80" Hole SpacingMP8 Mounting Plate - 8.25" Hole SpacingMP9 Mounting Plate - 9.38" Hole SpacingMP18 Mounting Plate - 17.50" Hole SpacingMS/TP Master slave token passingMVMNADNADD

Multi-varible monitorNo Coil Access (upstream)No Coil Access (upstream and downstream)

OCC Occupancy overrideOD Outer diameterOEV Other exhaust valve (eg. biosafety cabinets/ snorkels/

etc)OHC Oversized high capacity hot water coilOSC Oversized standard capacity hot water coilP1 Phenolic coating (heresite class 1)P2 Phenolic coating (heresite class 2)Pa PascalsPACE Pace™ controllerPKLS Packless silencerPM Panel mountPMT Touchscreen room pressure monitor

Acronym DescriptionPOT PotentiometerPT Pressure transducer (mounted on Pace™ controller)PTX Pressure transducerRAV Return air valveRDV Round duct terminalRH Relative humidity sensorRIN Room information networkRM Room temperature sensorRMP Room pressureRMRH Room relative humidityRMT Room temperatureRTR Bacnet MS/TP to IP routerS14 14" silencer lengthS7 7" screenSAV Supply air valveSC Standard capacity hot water coilSCRV SCR control (0-10VDC)SDV Square duct terminalsec SecondsSIL Venturi valve silencerSIN Sensor information networkSIND Sensor information network deviceSL Slip connectionSM Solid metal liner 3/4"SPR Standard Potentiometer ReplacementSPS1 One sash position sensorSPS2 Two sash position sensorsSPS3 Three sash position sensorsSRPS1 One SIN room pressure sensorSRPS2 Two SIN room pressure sensorsSRPS3 Three SIN room pressure sensorsSS Stainless steelSSA Standard speed actuatorSSO Standard shutoff valveSWS1 1 sidewall face velocity sensorSWS2 2 sidewall face velocity sensorsT# Thermistor inputTU Terminal unitVAV Variable air volumeVCT Valve connection companion typeVD Vertical downVDC Modulating (0-10VDC) actuatorVFX Venturi FX damper bladeVIT Valve installation tapeVP Valve PressureVPS Valve pressure switchVPT Valve power transformerVU Vertical upVV Venturi valveVVEC Valve electric coilVVHWC Valve hot water coilVVR Venturi valve retrofitW1 CAT5e plenum rated cable, by Others

Page 4: Typical Laboratory Retrofit - Antec Controls

Typical Laboratory Retrofit

Nomenclature 2020/05/07

Acronym DescriptionW2 1.5 twisted pair Belden® 3106A cable (or equivalent), by

OthersW3 2 conductor, #20AWG, stranded copper wire, by OthersW4 3 conductor, #20AWG, stranded copper wire, by OthersW5 4 conductor, #20AWG, stranded copper wire, by Others

Acronym DescriptionW6 5 conductor, #20AWG, stranded copper wire, by OthersW7 RJ12 to HR30 adapter, by Antec ControlsW8 6 conductor, #20AWG, stranded copper wire, by OthersWEB Webserver

Page 5: Typical Laboratory Retrofit - Antec Controls

Typical Laboratory Retrofit

Schedule 2020/05/07

Valve and Controller Schedule

Valv

e M

odel

Valv

e Ta

g

Roo

m

App

licat

ion

Uni

t Siz

e

MA

X Fl

ow(C

FM)

MIN

Flo

w(C

FM)

MIN

Uno

ccup

ied

Flow

(CFM

)

Roo

m O

ffset

(CFM

)

Bod

y Ty

pe

Pres

sure

Ran

ge

Orie

ntat

ion

Coa

ting

Insu

latio

n

Con

nect

ion

Type

Con

trol

Typ

e

Con

trol

s

Act

uato

r Con

trol

Act

uato

r Res

pons

e

Act

uato

r Fai

l Pos

ition

Acc

esso

ries

Encl

osur

e A

ssem

bly

Cal

ibra

tion

Met

hod

VA R

equi

red

Qua

ntity

Not

es

VVR SAV-R Laboratory SAV 114 2150 1280 1280 200 - M - - - - - PACE VDC HSA FLP - ENCL FLDC 41.0 1 1, 2VVR GEV-R Laboratory GEV 114 2150 530 530 200 - M - - - - - PACE VDC HSA FLP - ENCL FLDC 41.0 1 1, 2VVR FEV-R-1 Laboratory FEV 108 400 100 0 200 - M - - - - - FHC VDC HSA FLP - ENCL FLDC 63.0 1 1, 2VVR FEV-R-2 Laboratory FEV 108 400 100 0 200 - M - - - - - FHC VDC HSA FLP - ENCL FLDC 63.0 1 1, 2

Notes:1. Installation and wiring of equipment by Others.2. See Product Submittal for option details. 3. Standard valve body type.

Page 6: Typical Laboratory Retrofit - Antec Controls

Typical Laboratory Retrofit

Schedule 2020/05/07

ES Schedule

Roo

m C

ontr

olA

cces

sorie

s M

odel

Valv

e Ta

g

Roo

m N

ame

Sens

or T

ype

Dis

play

Typ

e

Setp

oint

Adj

ustm

ent

Rel

ativ

e H

umid

ity

Car

bon

Dio

xide

Occ

upan

cy

Qua

ntity

Not

es

ES SAV-R Laboratory RM LCD BTN 1 1, 2ES SAV-R Laboratory DT 1 1, 2

Notes:1. Installation and wiring of equipment by Others.2. See Product Submittal for option details.

Page 7: Typical Laboratory Retrofit - Antec Controls

Typical Laboratory Retrofit

Schedule 2020/05/07

POT Schedule

Ret

rofit

Acc

esso

ries

Mod

el

Valv

e Ta

g

Type

Qua

ntity

Not

es

POT GEV-R SPR 1 1, 2

Notes:1. Installation and wiring of equipment by Others.2. See Product Submittal for option details.

Page 8: Typical Laboratory Retrofit - Antec Controls

Typical Laboratory Retrofit

Schedule 2020/05/07

FHC Accessories Schedule

FHC

Acc

esso

ries

Mod

el

Valv

e Ta

g

Sash

Len

gth

Ret

rofit

Acc

esso

ry

Qua

ntity

Not

esFHI FEV-R-1 - MP7 1 1, 2FHI FEV-R-2 - MP7 1 1, 2FPS FEV-R-1 - MP8 1 1, 2SPS FEV-R-1 50 - 1 1, 2SPS FEV-R-2 50 - 1 1, 2SWS FEV-R-1 - - 1 1, 2

Notes:1. Installation and wiring of equipment by Others.2. See Product Submittal for option details.

Page 9: Typical Laboratory Retrofit - Antec Controls

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

VVR-1-X

270213Rev.D

2020/05/11

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Venturi Valve Retrofit Kit

Product Submittal

CONTROLLER ENCLOSURE ASSEMBLY (ENCL),

CONTROLLER ENCLOSURE OPTIONS:

SINGLE VALVE DUAL VALVE

TRIPLE VALVE*SINGLE VALVE DUAL VALVE

FAIL IN PLACE (FLP)

FAIL OPEN POSITION (FOP)

FAIL CLOSED POSITION (FCP)

ACTUATOR FAIL SAFE OPTIONS:

STANDARD SPEED (SSA), FLP ONLY

HIGH SPEED (HSA)

ACTUATOR SPEED OPTIONS:

ENVIRONMENTAL (OPERATING) 50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)

ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)

VVR SPECIFICATIONS:

MOUNTING PLATE

.060in (2mm) GALV STEEL,

TO BE MOUNTED IN THE FIELD DIRECTLY ON RETROFIT VALVE,

NO MOUNTING HARDWARE INCLUDED

MOUNTING SPECIFICATIONS:

MEDIUM PRESSURE (M) - 0.6 to 3.0 in.w.c. (150-750 Pa), MEASURED ACROSS VALVE

LOW PRESSURE (L) - 0.3 to 3.0 in.w.c. (75-750 Pa), MEASURED ACROSS VALVE

PRESSURE RANGE OPTIONS:

*COMBINATION OF SINGLE VALVE AND DUAL VALVE RETROFIT KITS.

VDC CONTROL SIGNAL (VDC)

2-POSITION CONTROL SIGNAL (2P)

ACTUATOR CONTROL OPTIONS:

13.5" (343)

5.5" (140)

3.0" (76) CONTROLLER ENCLOSURE,OPTIONAL

CONTROLLER ENCLOSURE,OPTIONAL

PACE, FHC or LMX ENCLOSURE MOUNTED

11.5" (292)

2.9" (74)

5.0" (127)

7.0" (178)

11.5" (292)

5.0" (127)

CONTROLLER ENCLOSURE,OPTIONAL

Sheet 1 of 2

NOTE: PLEASE REFER TO PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Page 10: Typical Laboratory Retrofit - Antec Controls

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

VVR-1-X

270213Rev.D

2020/05/11

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Venturi Valve Retrofit Kit

Product Submittal

UNIT

SIZE

ACTUATOR

CONTROL

ACTUATOR

RESPONSE

ACTUATOR

FAIL POSITIONPART # QTY

SSA 019127-002 1

019127-001 1

FOP/FCP 019127-003 1

SSA 019128-001 1

019128-003 1

FOP/FCP 019127-007 1

SSA 019127-002 1

019127-001 1

FOP/FCP 019127-003 1

SSA 019128-001 1

019128-003 1

FOP/FCP 019127-007 1

SSA 019127-005 1

019127-004 1

FOP/FCP 019127-003 1

SSA 019128-002 1

019128-009 1

FOP/FCP 019127-007 1

SSA 019127-005 1

019127-004 1

FOP/FCP 019127-003 1

SSA 019128-002 1

019128-009 1

FOP/FCP 019127-007 1

SSA 019127-005 1

019127-004 1

FOP/FCP 019127-003 1

SSA 019128-002 1

019128-009 1

FOP/FCP 019127-007 1

SSA 019127-005 1

019127-004 1

FOP/FCP 019127-003 1

SSA 019128-002 1

019128-009 1

FOP/FCP 019127-007 1

SSA 019127-005 1

019127-004 1

FOP/FCP 019127-003 1

SSA 019128-002 1

019128-009 1

FOP/FCP 019127-007 1

214

2P

VDC

VDC

2P

VDC

2P

VDC

2P

VDC

108

110

112

114

210

212

2P

VDC

2P

VDC

2P

FLP

HSA

HSA

HSA

HSA

HSA

FLP

FLP

FLP

FLP

FLP

HSA

HSA

HSA

HSA

FLP

FLP

FLP

FLP

HSA

HSA

HSA

HSA

HSA

FLP

FLP

FLP

FLP

ACTUATOR REFERENCE CHART

Sheet 2 of 2

NOTE: SEE VALVE ACTUATOR PRODUCT SUBMITTAL FOR ACTUATOR SPECIFICATIONS.

NOTE: PLEASE REFER TO PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Page 11: Typical Laboratory Retrofit - Antec Controls

PACE-1-X

270117Rev. J

2020/06/08

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Pace™ - Critical Space Controller

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Sheet 1 of 7

VENTURI VALVE (VV)

DIMENSIONS:

AIRFLOW DEVICE TYPE:

PRESSURE SENSOR 0 to 4.0 in.w.c. (0 to 1000 Pa)

VENTURI FX (VFX) OR TERMINAL (TU)

PRESSURE SENSOR 0 to 2.0 in.w.c. (0 to 500 Pa)

PANEL MOUNTED (PM)

AIRFLOW DEVICE MOUNTED (DEFAULT)

MOUNT:

8.90 (226)

1.89 (48)

9.55 (243)

4.48 (114)

1.22 (31)

8.31 (211)

3.77 (114)

ENVIRONMENTAL (OPERATING)

ENVIRONMENTAL (STORAGE)

INDICATORS

HOUSING

RATED IMPULSE VOLTAGE

COMMUNICATION PROTOCOL

DEVICE TYPE B-AAC

COMMUNICATION TYPE MS/TP (RS-485)

COMMUNICATION SPEED 9600, 19200, 38400, 76800

CERTIFICATION BTLBACNET

CONTROL PRIORITY ORDER

1. ANTEC TOOLBOX

2. BACNET

3. NORMAL OPERATION

STATUS LED

UL 94 V-0, PC-ABS PLASTIC

330 V (AFTER TRANSFORMER)

BACNET MS/TP

OUTPUTS

INPUTS

INPUT POWER

PACE SPECIFICATIONS:

32⁰F to 130⁰F (0⁰C to 55⁰C), 5% to 95% R.H.(NON-CONDENSING)

-22⁰F to 158⁰F (-30⁰C to 70⁰C), 0% to 95% R.H.(NON-CONDENSING)

24 VAC, 50/60 Hz SINGLE PHASE, 75 VA MAX (18 VA EXCLUDING EXTERNAL

LOADS), CLASS 2 or LPS PELV

2 BINARY INPUTS (CONTACT CLOSURE),

4 ANALOG INPUTS (0 to 10 VDC),

2 10K TYPE 2 THERMISTORS INPUTS,

ROOM INFORMATION NETWORK,

SENSOR INFORMATION NETWORK,

2 POT INPUTS,

2 RS485 NETWORK (FHN, BACNET),

1 TRANSDUCER (VV: 0-4 in.w .c., VFX: 0-2 in.w .c.)

2 ACTIVE BINARY OUTPUTS (24 VAC, MAX: 500 mA),

4 ANALOG OUTPUTS (0 to 10 VDC, MAX:10 mA)

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Page 12: Typical Laboratory Retrofit - Antec Controls

PACE-1-X

270117Rev. J

2020/06/08

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Pace™ - Critical Space Controller

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Sheet 2 of 7

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Object Name Units Range DescriptionWrite

Setting

AI#1 [Pace name] AI1 – [AI1 Device name] Dynamic DynamicAnalog Input w ith multiple uses

See Input section of the Antec Toolbox manual for optionsR

AI#2 [Pace name] AI2 – [AI2 Device name] Dynamic DynamicAnalog Input w ith multiple uses

See Input section of the Antec Toolbox manual for optionsR

AI#3 [Pace name] AI3 – [AI3 Device name] Dynamic DynamicAnalog Input w ith multiple uses

See Input section of the Antec Toolbox manual for optionsR

AI#4 [Pace name] AI4 – [AI4 Device name] Dynamic DynamicAnalog Input w ith multiple uses

See Input section of the Antec Toolbox manual for optionsR

AI#5 [Pace name] T1 – [T1 Device name] °F or °C -40 to 250 °F Thermistor reading R

AI#6 [Pace name] T2 – [T2 Device name] °F or °C -40 to 250 °F Thermistor reading R

BI#1 [Pace name] BI1 – [BI1 Device name] Open/Closed Open/ClosedBinary Input w ith multiple uses

See Input section of the Antec Toolbox manual for optionsR

BI#2 [Pace name] BI2 – [BI2 Device name] Open/Closed Open/ClosedBinary Input w ith multiple uses

See Input section of the Antec Toolbox manual for optionsR

AO#1 [Pace name] AO1 – [AO1 Device name] VDC 0 to 10Analog Output w ith multiple uses

See Output section of the Antec Toolbox manual for optionsR/W

AO#2 [Pace name] AO2 – [AO2 Device name] VDC 0 to 10Analog Output w ith multiple uses

See Output section of the Antec Toolbox manual for optionsR/W

AO#3 [Pace name] AO3 – [AO3 Device name] VDC 0 to 10Analog Output w ith multiple uses

See Output section of the Antec Toolbox manual for optionsR/W

AO#4 [Pace name] AO4 – [AO4 Device name] VDC 0 to 10Analog Output w ith multiple uses

See Output section of the Antec Toolbox manual for optionsR/W

BO#1 [Pace name] BO1 – [BO1 Device name] Active/Inactive Active/InactiveBinary Output w ith multiple uses

See Output section of the Antec Toolbox manual for optionsR/W

BO#2 [Pace name] BO2 – [BO2 Device name] Active/Inactive Active/InactiveBinary Output w ith multiple uses

See Output section of theAntec Toolbox manual for optionsR/W

AV1 Room Pressure Setpoint in.w .c.; Pa-5.0 to

5.0 in.w .c.

Current room pressure setpoint

Hidden when pressure control not usedR/W

AV2 Room Pressure in.w .c.; Pa-5.0 to

5.0 in.w .c.Current room pressure R

AV3 Room Pressure Low Alarm in.w .c.; Pa-5.0 to

5.0 in.w .c.Low room pressure alarm setpoint (+/-) R/W

AV4 Room Pressure High Alarm in.w .c.; Pa-5.0 to

5.0 in.w .c.High room pressure alarm setpoint (+/-) R/W

AV5 Airf low Offset Setpoint CFM; L/s-50000 to

50000 CFM

Current airf low offset setpoint

Hidden when offset control not usedR/W

Note: Analog output AO1 will display as AO11 for Pace™ Controller 1, AO21 for Pace™ Controller 2, etc.

Note: Analog output BO1 will display as BO11 for Pace™ Controller 1, BO21 for Pace™ Controller 2, etc.

ANALOG VALUE

BINARY OUTPUTS

BACNET POINTS LIST v1.2.0 OR NEWER

BINARY INPUTS

ANALOG OUTPUTS

ANALOG INPUTS

Note: Analog input AI1 will display as AI11 for Pace™ Controller 1, AI21 for Pace™ Controller 2, etc.

Note: Binary input BI1 will display as BI11 for Pace™ Controller 1, BI21 for Pace™ Controller 2, etc.

Page 13: Typical Laboratory Retrofit - Antec Controls

PACE-1-X

270117Rev. J

2020/06/08

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Pace™ - Critical Space Controller

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Name Units Range DescriptionWrite

Setting

AV6 Airf low Offset Actual CFM; L/s-50000 to

50000 CFMCurrent airf low offset (+/-) R

AV7 Total Exhaust Airf low Target CFM; L/s 0 to 50000 CFM Total room exhaust airf low target R

AV8 Total Exhaust Airf low Actual CFM; L/s 0 to 50000 CFM Total room exhaust airf low R

AV9 Total Supply Airf low Target CFM; L/s 0 to 50000 CFM Total room supply airf low target R

AV10 Total Supply Airf low Actual CFM; L/s 0 to 50000 CFM Total room supply airf low R

AV11 Total Fume Hood Exhaust CFM; L/s 0 to 50000 CFMTotal fume hood exhaust airf low

Hidden if no fume hoods connectedR

AV12 Room Volume ft3 0 to 100000 Room volume R/W

AV13 Current Air Change Rate # 0.0 to 100.0 Current air change rate R

AV14 Temperature Setpoint - Zone 1 °F;°C -40 to 250 °FTemperature setpoint in zone 1

Hidden if there are no temperature zonesR/W

AV15 Temperature Reading - Zone 1 °F;°C -40 to 250 °F Current temperature in zone 1 R

AV16 Temperature Setpoint - Zone 2 °F;°C -40 to 250 °FTemperature setpoint in zone 2

Hidden if multiple zones have not been configuredR/W

AV17 Temperature Reading - Zone 2 °F;°C -40 to 250 °FCurrent temperature in zone 2

Hidden if multiple zones have not been configuredR

AV18 Temperature Setpoint - Zone 3 °F;°C -40 to 250 °FTemperature setpoint in Zone 3

Hidden if multiple zones have not been configuredR/W

AV19 Temperature Reading - Zone 3 °F;°C -40 to 250 °FCurrent Temperature in zone 3

Hidden if multiple zones have not been configuredR

AV20 Room Temperature Setpoint - Low Limit °F;°C -40 to 250 °F Low est user-adjustable temperature setpoint on the thermostat R/W

AV21 Room Temperature Setpoint - High Limit °F;°C -40 to 250 °F Highest user-adjustable temperature setpoint on the thermostat R/W

AV22 DAT Low Limit °F;°C -40 to 250 °FDischarge air temperature low temperature limit

Hidden if DAT limits are not enabledR/W

AV23 DAT High Limit °F; °C -40 to 250 °FDischarge air temperature high temperature limit

Hidden if DAT limits are not enabledR/W

AV24 Supply Airflow Setpoint CFM; L/s 0 to 50000 CFMSupply airf low setpoint

Hidden if Supply airflow control not usedR/W

AV25 Supply Airflow Actual CFM; L/s 0 to 50000 CFMSupply airf low

Hidden if Supply airflow control not usedR

AV26 Temperature Load - Zone 1 % -100% to 100%Temperature load in Zone 1

Hidden if there are no temperature zonesR

AV27 Temperature Load - Zone 2 % -100% to 100%Temperature load in Zone 2

Hidden if multiple zones have not been configuredR

AV28 Temperature Load - Zone 3 % -100% to 100%Temperature load in Zone 3

Hidden if multiple zones have not been configuredR

BACNET POINTS LIST v1.2.0 OR NEWER (CONTINUED)

Object

ANALOG VALUE

Sheet 3 of 7

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Page 14: Typical Laboratory Retrofit - Antec Controls

PACE-1-X

270117Rev. J

2020/06/08

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Pace™ - Critical Space Controller

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Sheet 4 of 7

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Object Name Units Range DescriptionWrite

Setting

AV29 Exhaust Airf low Setpoint CFM; L/s 0 to 50000 CFMExhaust airf low setpoint

Hidden if Exhaust airflow control not usedR/W

AV30 Exhaust Airf low Actual CFM; L/s 0 to 50000 CFMExhaust airf low

Hidden if Exhaust airflow control not usedR

AV81 [Mode name #1] - Room Min CFM; L/s 0 to 50000 CFM Room f low minimum for the default room mode R/W

AV82 [Mode name #1] - Room Heating Max CFM; L/s 0 to 50000 CFM Room f low heating maximum for the default room mode R/W

AV83 [Mode name #1] - Room Cooling Max CFM; L/s 0 to 50000 CFM Room f low cooling maximum for the default room mode R/W

AV84 [Mode name #2] - Room Min CFM; L/s 0 to 50000 CFMRoom f low minimum for the second room mode

Hidden if using using less than 2 room modesR/W

AV85 [Mode name #2] - Room Heating Max CFM; L/s 0 to 50000 CFMRoom f low heating maximum for the second room mode

Hidden if using using less than 2 room modesR/W

AV86 [Mode name #2] - Room Cooling Max CFM; L/s 0 to 50000 CFMRoom f low cooling maximum for the second room mode

Hidden if using using less than 2 room modesR/W

AV87 [Mode name #3] - Room Min CFM; L/s 0 to 50000 CFMRoom f low minimum for the third room mode

Hidden if using using less than 3 room modesR/W

AV88 [Mode name #3] - Room Heating Max CFM; L/s 0 to 50000 CFMRoom f low heating maximum for the third room mode

Hidden if using using less than 3 room modesR/W

AV89 [Mode name #3] - Room Cooling Max CFM; L/s 0 to 50000 CFMRoom f low cooling maximum for the third room mode

Hidden if using using less than 3 room modesR/W

AV90 [Mode name #4] - Room Min CFM; L/s 0 to 50000 CFMRoom f low minimum for the fourth room mode

Hidden if using using less than 4 room modesR/W

AV91 [Mode name #4] - Room Heating Max CFM; L/s 0 to 50000 CFMRoom f low heating maximum for the fourth room mode

Hidden if using using less than 4 room modesR/W

AV92 [Mode name #4] - Room Cooling Max CFM; L/s 0 to 50000 CFMRoom f low cooling maximum for the fourth room mode

Hidden if using using less than 4 room modesR/W

AV93 [Mode name #5] - Room Min CFM; L/s 0 to 50000 CFMRoom f low minimum for the fif th room mode

Hidden if using using less than 5 room modesR/W

AV94 [Mode name #5] - Room Heating Max CFM; L/s 0 to 50000 CFMRoom f low heating maximum for the f if th room mode

Hidden if using using less than 5 room modesR/W

AV95 [Mode name #5] - Room Cooling Max CFM; L/s 0 to 50000 CFMRoom f low cooling maximum for the fif th room mode

Hidden if using using less than 5 room modesR/W

AV96 [Mode name #6] - Room Min CFM; L/s 0 to 50000 CFMRoom f low minimum for the sixth room mode

Hidden if using using less than 6 room modesR/W

AV97 [Mode name #6] - Room Heating Max CFM; L/s 0 to 50000 CFMRoom f low heating maximum for the sixth room mode

Hidden if using using less than 6 room modesR/W

AV98 [Mode name #6] - Room Cooling Max CFM; L/s 0 to 50000 CFMRoom f low cooling maximum for the sixth room mode

Hidden if using using less than 6 room modesR/W

BACNET POINTS LIST v1.2.0 OR NEWER (CONTINUED)

Page 15: Typical Laboratory Retrofit - Antec Controls

PACE-1-X

270117Rev. J

2020/06/08

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Pace™ - Critical Space Controller

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Sheet 5 of 7

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Object Name Units Range DescriptionWrite

Setting

AV#01 [Pace name] Flow - [POT1 Device name] CFM; L/s 0 to 50000 CFMPOT1 airf low reading

Hidden when POT1 is not usedR

AV#02 [Pace name] Flow - [POT2 Device name] CFM; L/s 0 to 50000 CFMPOT2 airf low reading

Hidden when POT2 is not usedR

AV#03 [Pace name] - Valve Pressure in.w .c.; Pa-5.0 to

5.0 in.w .c.

Valve Pressure

Hidden when device type is not VVR

AV#04[Pace name] Flow - [Transducer

Device name]CFM; L/s 0 to 50000 CFM

Transducer airf low reading

Hidden when airflow source is not transducerR

AV#05 [Pace name] AI1 - DAT Setpoint °F;°C -40 to 250 °FDischarge Air Temperature Setpoint for AI1

Hidden when DAT control is not enabledR/W

AV#06 [Pace name] AI2 - DAT Setpoint °F;°C -40 to 250 °FDischarge Air Temperature Setpoint for AI2

Hidden when DAT control is not enabledR/W

AV#07 [Pace name] AI3 - DAT Setpoint °F;°C -40 to 250 °FDischarge Air Temperature Setpoint for AI3

Hidden when DAT control is not enabledR/W

AV#08 [Pace name] AI4 - DAT Setpoint °F;°C -40 to 250 °FDischarge Air Temperature Setpoint for AI4

Hidden when DAT control is not enabledR/W

AV#09 [Pace name] T1 - DAT Setpoint °F;°C -40 to 250 °FDischarge Air Temperature Setpoint for T1

Hidden when DAT control is not enabledR/W

AV#10 [Pace name] T2 - DAT Setpoint °F;°C -40 to 250 °FDischarge Air Temperature Setpoint for T2

Hidden when DAT control is not enabledR/W

AV#11 Fume Hood # Airf low CFM; L/s 0 to 50000 CFMDisplays the current airf low being exhausted from the

fume hoodR

AV#12 Fume Hood # Face Velocity FPM; m/s 0 to 1000 FPM Displays the current face velocity across the fume hood R

AV#13 Fume Hood # Sash Position % 0 to 100Displays the current position of the sash on the fume

hoodR

AV#14 Fume Hood # Valve Pressure in.w .c.; Pa-5.0 to

5.0 in.w .c.

Displays the current pressure across the valve on the

fume hoodR

MV1 Airflow Control Sequence Text 3 states

Displays the current airf low control sequence

1 - Constant Flow Control

2 - Pressure Control

3 - Offset Control

R

MV2 Room Pressure Mode Text 2 states

Displays the current room pressure mode

1 - Positive

2 - Negative

R

MULTISTATE VALUE

BACNET POINTS LIST v1.2.0 OR NEWER (CONTINUED)

Note: Analog value AV#01 will display as AV101 for Pace™ Controller 1, AV201 for Pace™ Controller 2, etc.

Note: Analog value AV#11 will display as AV111 for Fume Hood Controller (FHC) 1, AV211 for Fume Hood Controller (FHC) 2, etc.

Page 16: Typical Laboratory Retrofit - Antec Controls

PACE-1-X

270117Rev. J

2020/06/08

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Pace™ - Critical Space Controller

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Object Name Units Range DescriptionWrite

Setting

MV3 Room Alarm Status Text 13 states

Displays the current room alarm status

1 - Controller Not Responding

2 - Missing Room Pressure Sensor

3 - Diversity

4 - Binary Input

5 - Mode Alarm

6 - Door Open

7 - Room Low Pressure

8 - Room High Pressure

9 - Low Airf low

10 - Low Valve Pressure

11 - High Airf low

12 - High Valve Pressure

13 - No Alarm

R

MV4 Room Mode Text 6 states

Displays the current room mode

1 - [Default Room Mode Name]

2 - [Custom Room Mode 1 Name]

3 - [Custom Room Mode 2 Name]

4 - [Custom Room Mode 3 Name]

5 - [Custom Room Mode 4 Name]

6 - [Custom Room Mode 5 Name]

R/W

MV5 Room Mode Override Text 6 states

Displays the current room mode override

1 - [Default Room Mode Name]

2 - [Custom Room Mode 1 Name]

3 - [Custom Room Mode 2 Name]

4 - [Custom Room Mode 3 Name]

5 - [Custom Room Mode 4 Name]

6 - [Custom Room Mode 5 Name]

R/W

MV99 Firmw are Update Status Text 4 states

Displays the current f irmw are update status

1 - Idle

2 - Start Firmw are Update

3 - Updating Firmw are

4 - Firmw are Update Failed

R/W

MV#1 Fume Hood # Status Text 6 states

Displays the status of the fume hoods

1 - Missing FHC

2 - Normal

3 - Caution

4 - Alarm

5 - Setback

6 - Off

R

Note: Multistate value MV#1 will display as MV11 for Fume Hood Controller (FHC) 1, MV21 for Fume Hood Controller (FHC) 2, etc…

BACNET POINTS LIST v1.2.0 OR NEWER (CONTINUED)

MULTISTATE VALUE

Sheet 6 of 7

Page 17: Typical Laboratory Retrofit - Antec Controls

PACE-1-X

270117Rev. J

2020/06/08

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Pace™ - Critical Space Controller

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Sheet 7 of 7

NOTE: The BACnet point names can be overridden using Antec Toolbox and may not match the names listed in this table. The instance numbers can be used in this case to identify the points.

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Object Name Units Range DescriptionWrite

Setting

MV#2 Fume Hood # Error Type Text 21 states

Displays the cause of any alarms or cautions on the fume hoods

1 - No Error

2 - Emergency

3 - Netw ork

4 - Contact Input

5 - No Primary Sensor

6 - No Sec. Sensor

7 - No Sash1

8 - No Sash2

9 - No Sash 3

10 - Low Velocity

11 - High Velocity

12 - Low Pressure

13 - High Pressure

14 - Venturi Out of Range

15 - Sash Height

16 - Low Airf low

17 - High Airf low

18 - Sash Broken

19 - BI1

20 - BI2

21 - Setback Sash Height

R

FIL1 Firmw are - -The file object used for f irmw are upgrades -

feature only available if supported by BASW

CAL1 Calendar Object - - The calendar object used for scheduling R/W

EVC1 Notif ication Class object - - The notif ication class object for alarming R/W

SCH1 Room Mode Schedule - - The scheduling object for scheduling room mode changes R/W

NOTIFICATION CLASS

SCHEDULE

BACNET POINTS LIST v1.2.0 OR NEWER (CONTINUED)

CALENDAR

FILE

Note: Multistate value MV#1 will display as MV11 for Fume Hood Controller (FHC) 1, MV21 for Fume Hood Controller (FHC) 2, etc…

VARIABLE DEFAULT COV INCREMENT UNITS

Airflow 50 CFM

Offset 20 CFM

Actuator 0.001 V

Heating 0.001 V

Pressure 0.001 in.w .c.

Valve Pressure 0.2 in.w .c.

ACH 1 ACH

CO2 100 ppm

Face Velocity 10 FPM

Humidity 1 %

Position 1 in

Room Volume 100 ft³

Temperature 0.5 °F

Temperature Load 0.1 %

VOC 100 ppm

Voltage 0.05 V

PACE DEFAULT CHANGE OF VALUE (COV) INCREMENTS

Page 18: Typical Laboratory Retrofit - Antec Controls

270736Rev. E

2020/02/21

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Valve Actuator

Product Submittal

DIMENSIONS:

ACTUATOR - 35 in-lbs (4 Nm), VDC, HSA, FLP

Sheet 2 of 14

TERMINATION:

3.15 (80)

1.97 (50)

2.95 (75)

7.35 (187)

.98 (25)

4.88 (124)

BLACKREDWHITEORANGE

RED INPUT POWER, HOT

BLACK INPUT POWER, COM M ON

WHITE CONTROL SIGNAL

ORANGE NOT USED

DIRECTION OF ROTATION SWITCH

POWER ADAPTION BUTTON

MANUAL OVERRIDE BUTTONNOTE: DO NOT PRESS WHEN AIRFLOW IS PRESENT

10

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

ENVIRONMENTAL (OPERATING) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)

ENVIRONMENTAL (STORAGE) -40⁰F to 176⁰F (-40⁰C to 80⁰C), 5% to 95% R.H.(NON-CONDENSING)

INPUT POWER 24 VAC +/- 20%, 50/60 Hz, 23 VA, CLASS 2

CONTROL SIGNAL RANGE 2 to 10 VDC

DIRECTION OF ROTATION REVERSIBLE WITH BUILT-IN SWITCH (FACTORY SET TO 0)

TORQUE 35 in-lb (4 Nm)

MANUAL OVERRIDE EXTERNAL PUSH BUTTON

RUNNING TIME 2.5 sec

HOUSING NEMA 2, IP54, UL ENCLOSURE TYPE 2

HOUSING MATERIAL UL94 -5VA

WEIGHT 1.8 lbs (0.85 kg)

PART # (BELIMO MODEL) 019127-001 (LMQB24-MFT)

SPECIFICATIONS:

ANGLE OF ROTATIONMIN 30°, MAX 95°, ADJUSTABLE WITH MECHANICAL STOP

ELECTRONICALLY VARIABLE (POWER ADAPTION)

Page 19: Typical Laboratory Retrofit - Antec Controls

270736Rev. E

2020/02/21

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Valve Actuator

Product Submittal

Sheet 5 of 14

DIMENSIONS:

TERMINATION:

BLACKREDWHITEORANGE

RED INPUT POWER, HOT

BLACK INPUT POWER, COM M ON

WHITE CONTROL SIGNAL

ORANGE NOT USED

ACTUATOR - 70 in-lbs (8 Nm), VDC, HSA, FLP

2.49 63

1.18 30

4.06 103

5.20 132

5.24 133.1

8.30 211

3.46 88

DIRECTION OF ROTATION SWITCH

POWER ADAPTION BUTTON

MANUAL OVERRIDE BUTTONNOTE: DO NOT PRESS WHEN AIRFLOW IS PRESENT

1.69 43

10

ENVIRONMENTAL (OPERATING) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)

ENVIRONMENTAL (STORAGE) -40⁰F to 176⁰F (-40⁰C to 80⁰C), 5% to 95% R.H.(NON-CONDENSING)

INPUT POWER 24 VAC +/- 20%, 50/60 Hz, 23 VA, CLASS 2

CONTROL SIGNAL RANGE 2 to 10 VDC

DIRECTION OF ROTATION REVERSIBLE WITH BUILT-IN SWITCH (FACTORY SET TO 0)

TORQUE 70 in-lbs (8 Nm)

MANUAL OVERRIDE EXTERNAL PUSH BUTTON

RUNNING TIME 4 sec

HOUSING NEMA 2, IP54, UL ENCLOSURE TYPE 2

HOUSING MATERIAL UL94 -5VA

WEIGHT 1.8 lbs (0.85 kg)

PART # (BELIMO MODEL) 019127-004 (NMQB24-MFT)

SPECIFICATIONS:

ANGLE OF ROTATIONMIN 30°, MAX 95°, ADJUSTABLE WITH MECHANICAL STOP

ELECTRONICALLY VARIABLE (POWER ADAPTION)

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Page 20: Typical Laboratory Retrofit - Antec Controls

FHC-1-X

270113Rev.B

2019/06/19

© Copyright Antec Controls by PRICE 2019

So

lid E

dge

Fume Hood Controller

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DIMENSIONS:

7.0 (178)

2.50 (64)4.0 (102)

7.5 (191)

2.4 (61)

6.2 (157) .7 (17)

3.56 (90)

Sheet 1 of 3

VENTURI VALVE (VV)

AIRFLOW DEVICE TYPE:

PRESSURE SENSOR 0 to 5.0 in.w.c. (0 to 1250 Pa)

VENTURI FX (VFX) OR TERMINAL (TU)

PRESSURE SENSOR 0 to 2.0 in.w.c. (0 to 500 Pa)

PANEL MOUNTED (PM)

AIRFLOW DEVICE MOUNTED (DEFAULT)

MOUNT:

NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

ENVIRONMENTAL (OPERATING)

ENVIRONMENTAL (STORAGE)

INPUT POWER

INDICATORS

HOUSING

COMMUNICATION PROTOCOL

DEVICE TYPE B-ASC

COMMUNICATION TYPE MS/TP (RS-485)

COMMUNICATION SPEED 9600, 19200, 38400, 76800

CERTIFICATION BTLBACNET

FHC SPECIFICATIONS:

50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)

-22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)

24 VAC +/- 10%, 50/60 Hz, 40 VA (EXTERNAL LOADS NOT INCLUDED), CLASS 2

2 BINARY INPUTS,

2 SIDEWALL SENSOR INPUTS,

3 SASH POSITION SENSOR INPUTS

2 ANALOG OUTPUTS (0 to 10 VDC, MAX:10 mA),

1 BINARY OUTPUT (DRY CONTACT),

2 BINARY OUTPUTS (MAX: 24 VAC, 500 mA)

STATUS LEDs

UL 94V - 0, ABS PLASTIC

FHN (FUME HOOD NETWORK), BACNET (*ONLY WHEN FHN NOT USED)

1. BACNET

2. NORMAL OPERATIONCONTROL PRIORITY ORDER

INPUTS

OUTPUTS

Page 21: Typical Laboratory Retrofit - Antec Controls

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

ES-1-X

270215Rev. G

2020/06/09

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Environmental Sensor

Product Submittal

DIMENSIONS:

ROOM TEMPERATURE SENSOR (RM) WITH DISPLAY (LCD) ANDPUSHBUTTON SETPOINT ADJUSTMENT (BTN)

3.0 (76)

4.4 (112)

1.0 (28)

3.28 (83)

CLOSED CELL FOAM

.7 (18)

COMMUNICATION PORT:

Sheet 4 of 11

RJ-45CKJ-B - PUSHDOWN CONNECTIONTO PACE CONTROLLERWHERE APPLICABLE

WALLMOUNT PLATE

WALLMOUNT PLATEFACE PLATE

TERMINATION:

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

EXT-TEMP

SET2

SET1

OVR1

SEN2

SEN1

OVR2

EXT-GND

OCCUPY

W1GND

V+

V + INPUT POWER, HOT

GND INPUT POWER, GROUND

SEN1

SEN2

SET1 TEM PERATURE SETPOINT OUTPUT

THERM ISTOR RESISTANCE OUTPUT

ENVIRONMENTAL (OPERATING) 32⁰F to 122⁰F (0⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)

DISPLAY LCD SCREEN

INPUT TYPE KEYPAD

TEMPERATURE READING 10K-2 THERMISTOR, ±0.36⁰F, 32⁰ to 158⁰F (±0.2⁰C, 0 to 70⁰C)

HOUSING UL 94 V-0, ABS PLASTIC

COMMUNICATION PORT RJ-45

ES-RM-LCD-BTN SPECIFICATIONS:

MOUNTSTANDARD 2in. x 4in. (51mm x 102mm) J-BOX or

DRYWALL MOUNT

OUTPUT1 ANALOG (0 to 10 VDC):

TEMPERATURE SETPOINT - RANGE: 50⁰F to 90⁰F (10⁰C to 32⁰C)

INPUT POWER15 to 40 VDC or 15 to 28 VAC. (DO NOT RUN AC POWER IN THE

SAME CONDUIT AS SIGNAL WIRES)

°F/C

DISPLAY SWITCH (vF or vC)

Page 22: Typical Laboratory Retrofit - Antec Controls

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

ES-1-X

270215Rev. G

2020/06/09

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Environmental Sensor

Product Submittal

DIMENSIONS:

DUCT MOUNTED SENSOR (DT)

ENVIRONMENTAL (OPERATING) -40⁰F to 185⁰F (-4⁰C to 85⁰C), 0 to 95% R.H.(NON-CONDENSING)

TEMPERATURE READING 10K-2 THERMISTOR, ±0.36⁰F, 32⁰ to 158⁰F (±0.2⁰C, 0 to 70⁰C)

PROBE 304 STAINLESS STEEL PROBE, 0.25in. (7mm) DIAMETER, 6in. (152mm) LENGTH

HOUSING PC PLASTIC, UL 94 V-0, IP10, NEMA1

ES-DT SPECIFICATIONS:

2.1 (53)

3.0 (76) 2.67 (68)

1.78 (45)

TERMINATION:

YELLOW

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

YELLOW

YELLOW

THERM ISTOR RESISTANCE OUTPUT

YELLOW

Sheet 10 of 11

6.0 152

.25 6

8.0 202

Page 23: Typical Laboratory Retrofit - Antec Controls

FHI-1-X

270114Rev. C

2020/04/01

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Fume Hood Interface

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DIMENSIONS:

NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

3.7 (94) MAX

2.94 (75) MIN

1.5 (38)

1.1 (28)

5.15 (131)

3.29 (84)

2.0 x 2.0(51 x 51)CUTOUT

.76 (19)

.36 (9)

ENVIRONMENTAL (OPERATING) 50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)

ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)

INPUT POWER POWERED FROM FUME HOOD CONTROLLER (FHC)

INDICATORS LCD SCREEN, 180⁰ SIDEVIEW RGB LED, SPEAKER

CONNECTION TYPE RJ-45

INPUT TYPE KEYPAD

HOUSING UL 94 V-0, ABS PLASTIC

FHI SPECIFICATIONS:

Sheet 1 of 2

Page 24: Typical Laboratory Retrofit - Antec Controls

FHI-1-X

270114Rev. C

2020/04/01

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Fume Hood Interface

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Sheet 2 of 2

RETROFIT ACCESSORY:

MOUNTING PLATE - 6.00" HOLE SPACING (MP6)

MOUNTING PLATE - 6.80" HOLE SPACING (MP7)

MOUNTING PLATE - 9.38" HOLE SPACING (MP9)

7.00 178

7.80 198

10.38 264

3.25 83

3.25 83

3.25 83

6.00 1526.80 173

9.38 238

MP6 PLATE MP7 PLATE MP9 PLATE

O .19 5 O .19 (5)

O .19 (5)

MP6 PLATE SHOWN

MOUNTING PLATE MATERIAL 16ga STAINLESS STEEL, BRUSHED

SCREW #10 x .5", STAINLESS STEEL

ACCESSORY SPECIFICATIONS:

DIMENSIONS:

Page 25: Typical Laboratory Retrofit - Antec Controls

SPS-1-X

270123Rev. C

2019/04/26

© Copyright Antec Controls by PRICE 2019

So

lid E

dge

Sash Position Sensor

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

SASH POSITION SENSOR - 50in. (1270mm) STROKE RANGE

DIMENSIONS:

Sheet 1 of 2

3.5 (90)

3.6 (91)

1.45 (37)

O.14 (4)(2x)

2.0 (51)

2.0 (51)

1.8 (46)1.4 (36)

O.19 (5)

NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

ENVIRONMENTAL (OPERATING) -50⁰F to 120⁰F (-10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)

OUTPUT SIGNAL VOLTAGE DIVIDER UTILIZING 10K POT

CONNECTION TYPE 2-WIRE

MEASURING CABLE NYLON COATED STAINLESS STEEL

STROKE RANGE 0 to 50in. (0 to 1270mm)

HOUSING IP 50 PLASTIC

ACCURACY ±0.25% FS

SPS SPECIFICATIONS:

TERMINATION:

GREEN

RED

BL

AC

K

GREEN

RED

BLACK NOT REQUIRED

SASH POSITION FEEDBACK

Page 26: Typical Laboratory Retrofit - Antec Controls

SWS-1-X

270124Rev. C

2019/04/26

© Copyright Antec Controls by PRICE 2019

So

lid E

dge

Sidewall Sensor

Product Submittal

Sheet 1 of 1

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION INSTRUCTIONS SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

DIMENSIONS:

2.20 (56)

3.38 (86)

1.55 (39)

.38 (10)

ENVIRONMENTAL (OPERATING) 32⁰F to 120⁰F (0⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)

OUTPUT SIGNAL DIGITAL

CONNECTION TYPE CABLE, RJ12 TO HR30 ADAPTER, 25ft

RANGE ±0.1 in.w .c. (25 Pa)

HOUSING UL 94V - 0, ABS PLASTIC

ACCURACY 3% OF READING

SWS SPECIFICATIONS:

4.50 (114)

CONNECTIONS:

CABLE, 25ft

RJ12

HR30

Page 27: Typical Laboratory Retrofit - Antec Controls

FPS-1-X

270115Rev. C

2020/03/30

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Fume Hood Presence Sensor

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DIMENSIONS:

ENVIRONMENTAL (OPERATING) 50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)

ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)

INPUT POWER 24 VAC +/- 10%, 2 VA, CLASS 2

DETECTION DOPPLER SHIFT RADAR

DETECTION PATTERN SELECTABLE, WIDE OR NARROW

OUTPUTS 1 BINARY OUTPUT

FPS SPECIFICATIONS:

6.38 (162)

1.75 (44) 2.38 (60)

O 2.75 (70)

NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

TERMINATION:

BLACK

RED

GREEN

WHITEWHITE

BROWN

BLACK INPUT POWER, GROUND

RED INPUT POWER, HOT

BROWN RELAY, N/O

WHITE RELAY, COM M ON

GREEN RELAY, N/C

5.75 (146)

1.13 (29)

Sheet 1 of 2

Page 28: Typical Laboratory Retrofit - Antec Controls

FPS-1-X

270115Rev. C

2020/03/30

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Fume Hood Presence Sensor

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Sheet 2 of 2

MOUNTING PLATE - 8.25" HOLE SPACING (MP8)

18.50 470

3.00 76

3.00 76

9.50 241

17.50 444

8.25 210

O .19 5

O .19 5

NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

RETROFIT ACCESSORY:

MOUNTING PLATE - 17.50" HOLE SPACING (MP18)

MOUNTING PLATE MATERIAL 16ga STAINLESS STEEL, BRUSHED

SCREW #10 x .5", STAINLESS STEEL

ACCESSORY SPECIFICATIONS:

MP8 PLATE SHOWN

DIMENSIONS:

MP8 PLATE

MP18 PLATE

Page 29: Typical Laboratory Retrofit - Antec Controls

POT-1-X

272002Rev. 0

2020/03/26

© Copyright Antec Controls by PRICE 2020

So

lid E

dge

Retrofit Potentiometer Replacement

Product Submittal

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

1.6 42

1.1 29

24.0 ( 61 )

NOTE: PLEASE REFER TO VVR MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

ENVIRONMENTAL (OPERATING) -67⁰F to 221⁰F (-50⁰C to 105⁰C), 5% to 95% R.H.(NON-CONDENSING)

ENVIRONMENTAL (STORAGE) -67⁰F to 221⁰F (-50⁰C to 105⁰C), 5% to 95% R.H.(NON-CONDENSING)

OUTPUT SIGNAL VOLTAGE DIVIDER UTILIZING 10K POT

RANGE SINGLE TURN ROTATION

CONNECTION TYPE 3-WIRE

HOUSING MATERIAL HIGH TEMP. THERMOPLASTIC

SHAFT MATERIAL STAINLESS STEEL

MATERIAL ALUMINUM

HEX SIZE 3/32"

MOUNTING BRACKETS MATERIAL 16 Ga GALVANIZED STEEL

EXTENSION PIN MATERIAL STAINLESS STEEL

POTENTIOMETER

SHAFT COUPLER

POT SPECIFICATIONS:

STANDARD POTENTIOMETER REPLACEMENT (SPR)

POTPACE

(POT 1 OR POT 2)

FHC/LM X

(RGB TERM INAL BLOCK)

RED + R

GREEN SIG G

BLACK - B

DIMENSIONS:

TERMINATION:

1.5 ( 38 )

GREEN

RED

BLACK

Sheet 1 of 2

Page 30: Typical Laboratory Retrofit - Antec Controls
Page 31: Typical Laboratory Retrofit - Antec Controls
Page 32: Typical Laboratory Retrofit - Antec Controls
Page 33: Typical Laboratory Retrofit - Antec Controls
Page 34: Typical Laboratory Retrofit - Antec Controls
Page 35: Typical Laboratory Retrofit - Antec Controls
Page 36: Typical Laboratory Retrofit - Antec Controls
Page 37: Typical Laboratory Retrofit - Antec Controls
Page 38: Typical Laboratory Retrofit - Antec Controls
Page 39: Typical Laboratory Retrofit - Antec Controls

Typical Laboratory Retrofit

Sequence of Operations 2020/05/07

Sequence Number: 1

Sequence Type: Flow Offset ControlRoom(s): Laboratory

Flow Offset Control:

Supply and General Exhaust with Fume Hoods and Equipment: The Airflow Control System (ACS) will modulate the supply and general exhaust to maintain the scheduled flow offset target. The ACS will sum the total exhaust airflow from all sources, including fume hoods and equipment exhaust and will modulate the general exhaust air device to maintain the flow offset target. With no thermal demand, the supply will maintain the minimum scheduled value. As airflow demand increases (see section: Temperature Control) the supply and general exhaust will be increased to maintain the scheduled flow offset. With additional control sequences, the sequence with the highest demand for airflow will take priority.

Space Temperature Control:

Single Stage Reheat – Stage I: Modulating Reheat Coil: The Airflow Control System (ACS) will monitor room temperature from a wall mounted room temperature sensor. In the first heating stage, the reheat coil will modulate to maintain space temperature.

If there are multiple reheat coils, all coils will modulate together to maintain space temperature.

Modes of Operation:

Occupied Mode (Default): Occupied Mode is the default room mode. While in Occupied Mode, the Airflow Control System (ACS) will target the scheduled occupied airflows.

Fume Hood Control:

Hybrid Control (Venturi Value only): The Fume Hood Controller uses a Sash Position Sensor (SPS) and a Sidewall Sensor (SWS) together to control the face velocity of the fume hood. When a user moves the fume hood sash, the SPS measures the height of the vertical fume hood sash. The FHC will calculate the correct airflow to result in the target face velocity and will modulate the air device to the airflow target. The FHC will then use the SWS to adjust the airflow until the measured face velocity meets the target face velocity. The FHC will maintain a minimum airflow at all times when the sash is closed to ensure the proper fume hood air change rate.

Fume Hood Occupancy: The Fume Hood Controller (FHC) uses a Fume Hood Presence Sensor (FPS) to determine if there is an occupant present in front of the fume hood. When no occupant is detected, the FHC will modulate the exhaust device to maintain an unoccupied face velocity target. When an occupant is detected, the fume hood controller will modulate the exhaust air device to target the occupied face velocity target.

Fume Hood Emergency Purge: An emergency purge feature will activate when the “Emergency” button on the fume hood interface is pressed. The air device will modulate to its fully open position to purge the fume hood. A visual and audible alarm will activate to indicate that the fume hood is being purged. The emergency purge feature can be deactivated by pushing and holding the “Emergency” button for 5 seconds.

Fume Hood Alarms:

While the unit is in alarm, the LED light bars will be red. The audible alarm can be silenced but will re-engage after an adjustable time delay. Audible and visual alarms are available for face velocity, low/high valve pressure, sash height, and emergency purge.

Face Velocity: The Fume Hood Controller (FHC) will alarm if the measured face velocity drops below the adjustable low alarm limit, or rises above the adjustable high alarm limit.

Valve Pressure Alarms: The Fume Hood Controller (FHC) will alarm if the pressure across the Venturi Valve drops below the minimum or rises above the maximum operating pressure for the valve.

Sash Alarm: The Fume Hood Controller (FHC) will alarm if the sash height is above the sash height alarm limit. The FHC will also alarm if the Sash Position Sensor (SPS) cable fails or reports a value outside of the initially calibrated range.

Equipment Exhaust:

Dual-flow Set Point (PACE controlled): A two-position switch (provided by others) will provide the binary state to the Airflow Control System (ACS). The ACS will update the airflow set point to either the active set point (when binary is in active state) or the inactive set point (when the binary is in inactive state).

Room Temperature Monitoring:

A room temperature sensor will measure the room temperature. Room temperature is available to the building management system (BMS).

Page 40: Typical Laboratory Retrofit - Antec Controls

Typical Laboratory Retrofit

Sequence of Operations 2020/05/07

The ES will display room temperature locally on the LCD display.

Duct Temperature Monitoring:

A duct temperature sensor will measure the duct temperature. Duct temperature is available to the building management system (BMS).

Room Humidity Monitoring:

A room humidity sensor will measure the room relative humidity. Room relative humidity is available to the building management system (BMS).

The ES will display room relative humidity locally on the LCD display.

Local/Room Level Communication:

All valves and controllers in the Airflow Control System (ACS) within the room will communicate via an independent high-speed room level network called the Room Information Network (RIN).

Building Network Communication:

The Airflow Control System (ACS) will communicate over a native BACnet MS/TP trunk to the building automation network. All points are available to the building management system (BMS) with no network gateway required.

Second Fume Hood Control:

Sash Position Control: The Fume Hood Controller (FHC) uses a Sash Position Sensor (SPS) to control the face velocity of the fume hood. When a user moves the fume hood sash, the SPS measures the height of the vertical fume hood sash. The FHC will calculate the correct airflow to result in the target face velocity and will modulate the air device to the airflow target. The FHC will maintain a minimum airflow at all times when the sash is closed to ensure the proper fume hood air change rate.

Fume Hood Emergency Purge: An emergency purge feature will activate when the “Emergency” button on the Fume Hood Interface (FHI) is pressed. The air device will modulate to its fully open position to purge the fume hood. A visual and audible alarm will activate to indicate that the fume hood is being purged. The emergency purge feature can be deactivated by pushing and holding the “Emergency” button for 5 seconds.

Second Fume Hood Alarms:

Face Velocity: The Fume Hood Controller (FHC) will alarm if the measured face velocity drops below the adjustable low alarm limit, or rises above the adjustable high alarm limit.

Valve Pressure Alarms: The Fume Hood Controller (FHC) will alarm if the pressure across the Venturi Valve drops below the minimum or rises above the maximum operating pressure for the valve.

Sash Alarm: The Fume Hood Controller (FHC) will alarm if the sash height is above the sash height alarm limit. The FHC will also alarm if the Sash Position Sensor (SPS) cable fails or reports a value outside of the initially calibrated range.