CONDITION OUTDOOR AIR EFFICIENTLY AND SUSTAINABLY DOAS DEDICATED OUTDOOR AIR SYSTEMS

Upload: others

Post on 07-Oct-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: u w EV SERIES DOAS - RenewAire...Supply Fan Speed Control ECM / VFD Supply Fan Vibration Isolation Neoprene / spring (VFD only) Supply Fan Motor HP (kW) 200 - 277V 1P 1.35 kW N / A

C O N D I T I O N O U T D O O R A I RE F F I C I E N T L Y A N D S U S T A I N A B L Y

u Residential ERVs— two-duct design

u 40-140 CFM

BR SERIES

LE SERIESu Commercial ERVs—

large capacity

u 1,500-11,000 CFM

HE SERIESu Commercial ERVs—

packaged solutions

u 250-7,950 CFM

EV SERIESu Residential and light

commercial ERVs— four-duct design

u 40-540 CFM

PA SERIESu Applied ERVs—

modular panels

u 1,500-unlimited CFM

OPTIONS &ACCESSORIESu ECM motorsu Variable frequency drivesu Motorized isolation dampersu Combo curbsu Bypass economizersu Electric duct heatersu Indirect gas-fired duct furnacesu Filter alarmsu Integrated programmable

controls

RD SERIESu Commercial—Dedicated

Outdoor Air System (DOAS)

u 500-4,250 CFM

F O R C E R T I F I C A T I O N D E T A I L S , S E E U N I T S U B M I T T A L S O N R E N E W A I R E . C O M

E V E R Y G E O G R A P H Y, E V E R Y C L I M A T E , E V E R Y H O M E , E V E R Y B U I L D I N G A N D E V E R Y A P P L I C A T I O N

R ENE WA I R E E V E RY WHE RE

CA SERIESu Applied ERVs—

modular cabinets

u 500-4,400 CFM

u Stackable to 20,000 CFM

R e n e w A i r e . c o m8 0 0 . 6 2 7 . 4 4 9 9

LIT109_00 (01/18)

DO

AS

FE

AT

UR

ES

AN

D O

PT

ION

S

w Indoor and outdoor models w 20-gauge galvanized steel for inner and outer wall material

w Double-wall, foam- in-place panels

w 1" or 2" double-wall construction

w 1" R6.5 foam insulation for 1" double-wall units

w 2" thermally broken R13 insulation for 2" double- wall units

w Stainless steel double-sloped drain pan

CONSTRUCTION

w RenewAire’s Enthalpic Fixed Plate

w High sensible and latent energy recovery

w Low pressure drop

w 0% Cross-contamination (EATR)

w No freeze concerns w No condensate concerns w No microbial growth

INTEGRAL ENERGY RECOVERY

w Can handle higher ESP (Up to 3.0" ESP)

w Neoprene or spring vibration isolation

w Fan control via factory-installed ECM / VFD

w Energy-efficient, direct-drive, backward-curved plenum fans

w Premium high- efficiency motors

SUPPLY & EXHAUST

w Factory-mounted, wired microprocessor controller and sensors

w Night-setback and recirculation-mode controls

w Factory-preprogrammed sequence of operations

w Optional remote interface w Airflow monitoring

CONTROLS

w Split DX coil, chilled water coil, heat pump

COOLING OPTIONS

w Electric heat with SCR control

w Indirect gas-fired furnace with electronic modulation

w Hot water coil w Steam coil w Heat pump

HEATING OPTIONS

w Spacing between DX and reheat coil components to prevent evaporation

w Optional modulating hot gas reheat

REHEAT OPTIONS

w 2" MERV 8 / 13 / 14 filters, 4" filter optional

w AMCA Class I low-leakage isolation dampers with actuator

w Internal enthalpy-based modulating bypass that will allow full economizer bypass of ERV supply air

FILTERS, DAMPERS & BYPASS

DOASd e d i c a t e d o u t d o o r

a i r s y s t e m s

Page 2: u w EV SERIES DOAS - RenewAire...Supply Fan Speed Control ECM / VFD Supply Fan Vibration Isolation Neoprene / spring (VFD only) Supply Fan Motor HP (kW) 200 - 277V 1P 1.35 kW N / A

DOAS WITH ENERGY RECOVERYRenewAire’s DOAS EFFECTIVELY CONDITIONS OUTDOOR AIR with efficient and sustainable technology.

By enabling HVAC UNITS TO OPERATE INDEPENDENTLY , depending on building load, our DOAS unit with fixed-

plate energy recovery, innovative cooling and heating features and hot-gas reheat will optimize your ventilation strategy, downsize equipment,

decrease capital costs and realize significant operating savings.

u Enhanced IAQ

u Reduced energy consumption

u Downsized HVAC equipment

u Improved humidity control

u Increased system flexibility

u Simplified ventilation design

and control

u Decreased ventilation operation

and installation costs

KEY BENEFITS

FILTRATIONHOT-GAS REHEAT

COOLING COIL

HEATING SECTION ELECTRIC, GAS OR

HOT WATER/STEAM COIL

RECIRCULATION DAMPER

(BEHIND CORE)

INTERNAL MODULATING BYPASS ECONOMIZER

AND DEFROST

DIRECT-DRIVE FANS WITH EC MOTORS

ENERGY RECOVERY

CORE

DOUBLE-WALL, FOAM-IN-PLACE

PANELS

INTEGRATED PROGRAMMABLE

CONTROLS

LOW-LEAKAGE ISOLATION DAMPERS

FEATURES

SMALL MEDIUM LARGE

UNIT

Airflow Range 375 - 1,650 CFM 750 - 3,300 CFM 1,125 - 4,950 CFM

Installation Location Indoor / Outdoor

Airflow Orientation Vertical / Horizontal

Available Voltages 208 - 230V 1P (EC small only) / 3P (all); 460V 3P (all); 575V (VFD only)

Unit Disconnect Yes

Energy Recovery Enthalpic fixed plate

Internal Bypass of Energy Recovery Yes, modulating bypass using face and bypass dampers

CAB

INET

Wall Construction 1" or 2" double-wall, foam-in-place panels

Insulation 1" R - 6.5 / 2" R - 13.0

Panels with Thermal Break Yes, all 2" double-wall units

Painted Cabinets Yes (optional)

Salt Spray Rated Paint Yes (optional)

SUPP

LY F

AN

Supply Blower High-efficiency plenum fans

Supply Fan Type Direct-drive

Supply Fan Speed Control ECM / VFD

Supply Fan Vibration Isolation Neoprene / spring (VFD only)

Supply Fan Motor HP (kW)

200 - 277V 1P 1.35 kW N / A N / A

200 - 240V 3P 2.70 kW 2.70 kW 2.70 kW x2

380 - 480V 3P 3.70 kW 3.70 kW 3.70 kW x2

VFD 3 HP 5 HP 5 HP x2

Supply Fan ESP 2" WC at 1,500 CFM 2.5" WC at 3,000 CFM 3" WC at 4,500 CFM

EXH

AUS

T FA

N

Exhaust Blower High-efficiency plenum fans

Exhaust Fan Type Direct-drive

Exhaust Fan Speed Control ECM / VFD

Exhaust Fan Vibration Isolation Neoprene / spring (VFD only)

Exhaust Fan Motor HP (kW)

200 - 277V 1P 1.35 kW N / A N / A

200 - 240V 3P 2.70 kW 2.70 kW 2.70 kW x2

380 - 480V 3P 3.70 kW 3.70 kW 3.70 kW x2

VFD 3 HP 5 HP 5 HP x2

Exhaust Fan ESP 2" WC at 1,500 CFM 2.5" WC at 3,000 CFM 3.0" WC at 4,500 CFM

COOL

ING/

HE

ATIN

G Cooling Coil Direct expansion, chilled water, heat pump (optional)

Heating Section Electric heat, indirect gas furnace, hot water, heat pump, steam (optional)

Hot Gas Reheat Yes, modulating (optional)

CON

TRO

LS

Defrost Capability Yes, modulating

Microprocessor Controller Yes, RenewAire’s Premium Integrated Programmable Controls

Control Hardware Carel c.pCO Mini

Optional Communications BACnet MS / TP or IP, Modbus RTU, IP

Airflow Monitoring Yes

Recirculation Mode Yes

OTH

ER

GFCI Convenience Outlet Yes

Filtration MERV 8 / 13 / 14

Isolation Dampers AMCA Class I dampers

Page 3: u w EV SERIES DOAS - RenewAire...Supply Fan Speed Control ECM / VFD Supply Fan Vibration Isolation Neoprene / spring (VFD only) Supply Fan Motor HP (kW) 200 - 277V 1P 1.35 kW N / A

DOAS WITH ENERGY RECOVERYRenewAire’s DOAS EFFECTIVELY CONDITIONS OUTDOOR AIR with efficient and sustainable technology.

By enabling HVAC UNITS TO OPERATE INDEPENDENTLY , depending on building load, our DOAS unit with fixed-

plate energy recovery, innovative cooling and heating features and hot-gas reheat will optimize your ventilation strategy, downsize equipment,

decrease capital costs and realize significant operating savings.

u Enhanced IAQ

u Reduced energy consumption

u Downsized HVAC equipment

u Improved humidity control

u Increased system flexibility

u Simplified ventilation design

and control

u Decreased ventilation operation

and installation costs

KEY BENEFITS

FILTRATIONHOT-GAS REHEAT

COOLING COIL

HEATING SECTION ELECTRIC, GAS OR

HOT WATER/STEAM COIL

RECIRCULATION DAMPER

(BEHIND CORE)

INTERNAL MODULATING BYPASS ECONOMIZER

AND DEFROST

DIRECT-DRIVE FANS WITH EC MOTORS

ENERGY RECOVERY

CORE

DOUBLE-WALL, FOAM-IN-PLACE

PANELS

INTEGRATED PROGRAMMABLE

CONTROLS

LOW-LEAKAGE ISOLATION DAMPERS

FEATURES

SMALL MEDIUM LARGEUN

ITAirflow Range 375 - 1,650 CFM 750 - 3,300 CFM 1,125 - 4,950 CFM

Installation Location Indoor / Outdoor

Airflow Orientation Vertical / Horizontal

Available Voltages 208 - 230V 1P (EC small only) / 3P (all); 460V 3P (all); 575V (VFD only)

Unit Disconnect Yes

Energy Recovery Enthalpic fixed plate

Internal Bypass of Energy Recovery Yes, modulating bypass using face and bypass dampers

CAB

INET

Wall Construction 1" or 2" double-wall, foam-in-place panels

Insulation 1" R - 6.5 / 2" R - 13.0

Panels with Thermal Break Yes, all 2" double-wall units

Painted Cabinets Yes (optional)

Salt Spray Rated Paint Yes (optional)

SUPP

LY F

AN

Supply Blower High-efficiency plenum fans

Supply Fan Type Direct-drive

Supply Fan Speed Control ECM / VFD

Supply Fan Vibration Isolation Neoprene / spring (VFD only)

Supply Fan Motor HP (kW)

200 - 277V 1P 1.35 kW N / A N / A

200 - 240V 3P 2.70 kW 2.70 kW 2.70 kW x2

380 - 480V 3P 3.70 kW 3.70 kW 3.70 kW x2

VFD 3 HP 5 HP 5 HP x2

Supply Fan ESP 2" WC at 1,500 CFM 2.5" WC at 3,000 CFM 3" WC at 4,500 CFM

EXH

AUS

T FA

N

Exhaust Blower High-efficiency plenum fans

Exhaust Fan Type Direct-drive

Exhaust Fan Speed Control ECM / VFD

Exhaust Fan Vibration Isolation Neoprene / spring (VFD only)

Exhaust Fan Motor HP (kW)

200 - 277V 1P 1.35 kW N / A N / A

200 - 240V 3P 2.70 kW 2.70 kW 2.70 kW x2

380 - 480V 3P 3.70 kW 3.70 kW 3.70 kW x2

VFD 3 HP 5 HP 5 HP x2

Exhaust Fan ESP 2" WC at 1,500 CFM 2.5" WC at 3,000 CFM 3.0" WC at 4,500 CFM

COOL

ING/

HE

ATIN

G Cooling Coil Direct expansion, chilled water, heat pump (optional)

Heating Section Electric heat, indirect gas furnace, hot water, heat pump, steam (optional)

Hot Gas Reheat Yes, modulating (optional)

CON

TRO

LS

Defrost Capability Yes, modulating

Microprocessor Controller Yes, RenewAire’s Premium Integrated Programmable Controls

Control Hardware Carel c.pCO Mini

Optional Communications BACnet MS / TP or IP, Modbus RTU, IP

Airflow Monitoring Yes

Recirculation Mode Yes

OTH

ER

GFCI Convenience Outlet Yes

Filtration MERV 8 / 13 / 14

Isolation Dampers AMCA Class I dampers

Page 4: u w EV SERIES DOAS - RenewAire...Supply Fan Speed Control ECM / VFD Supply Fan Vibration Isolation Neoprene / spring (VFD only) Supply Fan Motor HP (kW) 200 - 277V 1P 1.35 kW N / A

C O N D I T I O N O U T D O O R A I RE F F I C I E N T L Y A N D S U S T A I N A B L Y

u Residential ERVs— two-duct design

u 40-140 CFM

BR SERIES

LE SERIESu Commercial ERVs—

large capacity

u 1,500-11,000 CFM

HE SERIESu Commercial ERVs—

packaged solutions

u 250-7,950 CFM

EV SERIESu Residential and light

commercial ERVs— four-duct design

u 40-540 CFM

PA SERIESu Applied ERVs—

modular panels

u 1,500-unlimited CFM

OPTIONS &ACCESSORIESu ECM motorsu Variable frequency drivesu Motorized isolation dampersu Combo curbsu Bypass economizersu Electric duct heatersu Indirect gas-fired duct furnacesu Filter alarmsu Integrated programmable

controls

RD SERIESu Commercial—Dedicated

Outdoor Air System (DOAS)

u 500-4,250 CFM

F O R C E R T I F I C A T I O N D E T A I L S , S E E U N I T S U B M I T T A L S O N R E N E W A I R E . C O M

E V E R Y G E O G R A P H Y, E V E R Y C L I M A T E , E V E R Y H O M E , E V E R Y B U I L D I N G A N D E V E R Y A P P L I C A T I O N

R ENE WA I R E E V E RY WHE RE

CA SERIESu Applied ERVs—

modular cabinets

u 500-4,400 CFM

u Stackable to 20,000 CFM

R e n e w A i r e . c o m8 0 0 . 6 2 7 . 4 4 9 9

LIT109_00 (01/18)

DO

AS

FE

AT

UR

ES

AN

D O

PT

ION

S

w Indoor and outdoor models w 20-gauge galvanized steel for inner and outer wall material

w Double-wall, foam- in-place panels

w 1" or 2" double-wall construction

w 1" R6.5 foam insulation for 1" double-wall units

w 2" thermally broken R13 insulation for 2" double- wall units

w Stainless steel double-sloped drain pan

CONSTRUCTION

w RenewAire’s Enthalpic Fixed Plate

w High sensible and latent energy recovery

w Low pressure drop

w 0% Cross-contamination (EATR)

w No freeze concerns w No condensate concerns w No microbial growth

INTEGRAL ENERGY RECOVERY

w Can handle higher ESP (Up to 3.0" ESP)

w Neoprene or spring vibration isolation

w Fan control via factory-installed ECM / VFD

w Energy-efficient, direct-drive, backward-curved plenum fans

w Premium high- efficiency motors

SUPPLY & EXHAUST

w Factory-mounted, wired microprocessor controller and sensors

w Night-setback and recirculation-mode controls

w Factory-preprogrammed sequence of operations

w Optional remote interface w Airflow monitoring

CONTROLS

w Split DX coil, chilled water coil, heat pump

COOLING OPTIONS

w Electric heat with SCR control

w Indirect gas-fired furnace with electronic modulation

w Hot water coil w Steam coil w Heat pump

HEATING OPTIONS

w Spacing between DX and reheat coil components to prevent evaporation

w Optional modulating hot gas reheat

REHEAT OPTIONS

w 2" MERV 8 / 13 / 14 filters, 4" filter optional

w AMCA Class I low-leakage isolation dampers with actuator

w Internal enthalpy-based modulating bypass that will allow full economizer bypass of ERV supply air

FILTERS, DAMPERS & BYPASS

DOASd e d i c a t e d o u t d o o r

a i r s y s t e m s

Page 5: u w EV SERIES DOAS - RenewAire...Supply Fan Speed Control ECM / VFD Supply Fan Vibration Isolation Neoprene / spring (VFD only) Supply Fan Motor HP (kW) 200 - 277V 1P 1.35 kW N / A

R e n e w A i r e . c o m8 0 0 . 6 2 7 . 4 4 9 9

LIT109_00 (01/18)

DO

AS

FE

AT

UR

ES

AN

D O

PT

ION

S w Indoor and outdoor models w 20-gauge galvanized steel for inner and outer wall material

w Double-wall, foam- in-place panels

w 1" or 2" double-wall construction

w 1" R6.5 foam insulation for 1" double-wall units

w 2" thermally broken R13 insulation for 2" double- wall units

w Stainless steel double-sloped drain pan

CONSTRUCTION

w RenewAire’s Enthalpic Fixed Plate

w High sensible and latent energy recovery

w Low pressure drop

w 0% Cross-contamination (EATR)

w No freeze concerns w No condensate concerns w No microbial growth

INTEGRAL ENERGY RECOVERY

w Can handle higher ESP (Up to 3.0" ESP)

w Neoprene or spring vibration isolation

w Fan control via factory-installed ECM / VFD

w Energy-efficient, direct-drive, backward-curved plenum fans

w Premium high- efficiency motors

SUPPLY & EXHAUST

w Factory-mounted, wired microprocessor controller and sensors

w Night-setback and recirculation-mode controls

w Factory-preprogrammed sequence of operations

w Optional remote interface w Airflow monitoring

CONTROLS

w Split DX coil, chilled water coil, heat pump

COOLING OPTIONS

w Electric heat with SCR control

w Indirect gas-fired furnace with electronic modulation

w Hot water coil w Steam coil w Heat pump

HEATING OPTIONS

w Spacing between DX and reheat coil components to prevent evaporation

w Optional modulating hot gas reheat

REHEAT OPTIONS

w 2" MERV 8 / 13 / 14 filters, 4" filter optional

w AMCA Class I low-leakage isolation dampers with actuator

w Internal enthalpy-based modulating bypass that will allow full economizer bypass of ERV supply air

FILTERS, DAMPERS & BYPASS