uhben1835-1 usermanual 431836 exhaustairheatpump …

88
UHB EN 1835-1 431836 USER MANUAL Exhaust air heat pump NIBE F750

Upload: others

Post on 17-Nov-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

UHB EN 1835-1431836

USER MANUAL

Exhaust air heat pumpNIBE F750

Page 2: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Quick guideNavigation

Ok button (confirm/select)

Back button (back/undo/exit)

Control knob (move/increase/reduce)

A detailed explanation of the button functions can be found on page13.

How to scroll throughmenus andmake different settings is describedon page 17.

Set the indoor climate

2X

INDOOR CLIMATE

HEAT PUMP INFO

HOTWATER

The mode for setting the indoor temperature is accessed by pressingthe OK button twice, when in the start mode in the main menu. Readmore about the settings on page 34.

Increase hot water volume

2X

1X

To temporarily increase the amount of hot water, first turn the controlknob to mark menu 2 (water droplet) and then press the OK buttontwice. Read more about the settings on page 50.

In event of disturbances in comfort

If a disturbance in comfort of any type occurs there are some meas-ures that can be taken before you need to contact your installer. Seepage 73 for instructions.

Page 3: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

41 Important information4Installation data

5Safety information

6Symbols

7Serial number

8F750 – An excellent choice

92 The heat pump – the heart of the house10Heat pump function

12Contact with F750

22Maintenance of F750

333 F750 – at your service33Set the indoor climate

50Set the hot water capacity

55Get information

58Adjust the heat pump

724 Disturbances in comfort72Info-menu

72Manage alarm

73Troubleshooting

775 Technical data786 Glossary

83Item register

87Contact information

3Table of ContentsNIBE F750

Table of Contents

Page 4: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Installation dataF750Product

Serial number

Installation date

Installer

Accessories✔

Extra shunt ECS40/41

Extra hot waterheater VPB(S)

Solar panels NIBEPV

SetFact.sett.

NameNo.

-1temperature (curve offset)1.1

5heating curve (curve slope)1.9.1

20min. flow line temp.1.9.3

75%fan sp. exhaust air (normal)5.1.5

MaxInstalled electrical output

Serial number must always be given

Certification that the installation is carried out according to instructionsin the accompanying installer manual and applicable regulations.

_________________________Signed__________________Date

NIBE F750Chapter 1 | Important information4

1 Important information

Page 5: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Safety information

This appliance can be used by children aged from 8years and above and persons with reduced physical,sensory or mental capabilities or lack of experience andknowledge if they have been given supervision or in-struction concerning use of the appliance in a safe wayand understand the hazards involved. Children shall notplay with the appliance. Cleaning and user maintenanceshall not be made by children without supervision.

Rights to make any design or technical modificationsare reserved.

©NIBE 2018.

Do not start F750 if there is a risk that the water in thesystem has frozen.

Water may drip from the safety valve’s overflow pipe, sothe overflow pipe’s opening must be open. The safetyvalves must be actuated regularly to remove dirt and tocheck that they are not blocked.

If the supply cable is damaged, only NIBE, its servicerepresentative or similar authorised person may replaceit to prevent any danger and damage.

5Chapter 1 | Important informationNIBE F750

Page 6: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Symbols

NOTEThis symbol indicates danger to person or machine .

CautionThis symbol indicates important information about what youshould observe when maintaining your installation.

TIPThis symbol indicates tips on how to facilitate using the product.

NIBE F750Chapter 1 | Important information6

Page 7: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Serial numberThe serial number can be found at the bottom right of the front coverand in the info menu (menu 3.1).

Serial number

CautionYou need the product's (14 digit) serial number for servicingand support.

7Chapter 1 | Important informationNIBE F750

Page 8: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

F750 – An excellent choiceF750 is part of a new generation of heat pumps, which have been intro-duced to supply your homewith inexpensive and environmentally friendlyheating. Heat production is safe and economical with integrated hotwater heater, immersion heater, circulation pump and control system.

The heat pump can be connected to an optional low temperature heatdistribution system. e.g. radiators, convectors or under floor heating. Itis also prepared for connection to several different products and accessor-ies, e.g. extra water heater and climate systems with different temper-atures.

F750 is equipped with a control computer for good comfort, good eco-nomy and safe operation. Clear information about status, operation timeand all temperatures in the heat pump are shown on the large and easyto read display. This means, for example, that external unit thermometersare not necessary.

EXCELLENT PROPERTIES FOR F750:• Inverter controlled compressorThe heat pump has an inverter-controlled compressor that automaticallyadapts itself optimally and economically to your house and suppliesyour installation with heating and hot water.

• Buffer vesselThere is a buffer vessel integrated in the heat pump that equalises thetemperature of the water that is sent out in the climate system.

• Scheduling the indoor comfort and hot waterHeating and hot water as well as ventilation, can be scheduled for eachday of the week or for longer periods (vacation).

• Display with user instructionsThe heat pump has a large display with easy-to-understand menus thatfacilitate setting a comfortable climate.

• Simple troubleshootingIn the event of a fault, the heat pump display shows what happenedand the actions to be taken.

NIBE F750Chapter 1 | Important information8

Page 9: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

A

DF

B

C

E

H

I

G

80 °C

22 °C 0 °C

5 °C 0 °C

55 °C 45 °C

Heating medium

Ventilation airRefrigerant

Evaporator

Condenser

Compressor

1

2

3

Expansion valve

The temperatures are only examples and may vary between different installations andtime of year.

9Chapter 2 | The heat pump – the heart of the houseNIBE F750

2 The heat pump – the heart ofthe house

Page 10: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Heat pump functionAn exhaust air heat pump makes use of the heat in the building's ventil-ation air to heat up the accommodation. The conversion of the ventilationair's energy to accommodation heating is done in three different circuits.From the outgoing ventilation air (1), free heating energy is retrievedfrom the accommodation and transported to the heat pump. The heatpump increases the retrieved heat's low temperature to a high temper-ature in the refrigerant circuit, (2). The heat is distributed around thebuilding in the heating medium circuit (3).

Ventilation airThe hot air is transferred from the rooms to the heat pump via the houseventilation system.

A

The fan then routes the air to the heat pump’s evaporator. Here, the air re-leases the heating energy and the air's temperature drops significantly. Thecold air is then blown out of the house.

B

Refrigerant circuitA liquid, a refrigerant, circulates in a closed system in the heat pump whichalso passes the evaporator. The refrigerant has a very low boiling point. Inthe evaporator the refrigerant receives the heat energy from the ventilationair and starts to boil.

C

The gas that is produced during boiling is routed into an electrically poweredcompressor. When the gas is compressed, the pressure increases and thegas’s temperature increases considerably, from approx. -5°C to approx.100°C.

D

From the compressor, the gas is forced into a heat exchanger, condenser,where it releases heat energy to the heat pump’s heating section, whereuponthe gas is cooled and condenses to liquid form again.

E

As the pressure is still high, the refrigerant can pass an expansion valve,where the pressure drops so that the refrigerant returns to its original tem-perature. The refrigerant has now completed a full cycle. It is routed to theevaporator again and the process is repeated.

F

Heat medium circuitThe heat energy that the refrigerant produces in the condenser is retrievedby the climate system's water, heating medium, which is heated to 55 °C(supply temperature).

G

The heating medium circulates in a closed system and transports the heatedwater's heat energy to the heat pump's integrated hot water heater and theradiators/heating coils of the house.

H

Buffer vessel

NIBE F750Chapter 2 | The heat pump – the heart of the house10

Page 11: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

The heating medium passes the heat pump's integrated buffer vesselwhereupon the temperature is equalised. It is then transported to the heatingsystem of the house.

I

The temperatures are only examples and may vary between different installations andtime of year.

11Chapter 2 | The heat pump – the heart of the houseNIBE F750

Page 12: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Contact with F750EXTERNAL INFORMATIONWhen the heat pump door is closed, information can be received via aninformation window and a status lamp.

Information window

Status lamp

Information windowThe information window shows part of the display that is on the displayunit (located behind the door to the heat pump). The information windowcan display different type of information, e.g. temperatures, clock, etc.

You determine what is to be displayed in the information window. Yourown combination of information is entered using the display unit. Thisinformation is specific to the information window and disappears whenthe heat pump door is opened.

Instructions on how to set the information window can be found on page65.

Status lampThe status lamp indicates the status of the heat pump: continuous greenlight during normal function, continuous yellow light during activatedemergency mode or continuous red light in the event of a deployedalarm.

Alarm management is described on page 72.

NIBE F750Chapter 2 | The heat pump – the heart of the house12

Page 13: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

DISPLAY UNIT

A

B

C

D

E

F

Display

Status lamp

OK button

Back button

Control knob

Switch

INDOOR CLIMATE

HEAT PUMP INFO

HOTWATER

F750G USB port

There is a display unit behind the heat pump door, which is used tocommunicate with F750. Here you:

• switch on, switch off or set the heat pump in emergency mode.

• sets the indoor climate and hot water as well as adjusts the heat pumpto your needs.

• receive information about settings, status and events.

• see different types of alarms and receive instructions about how theyare to be rectified.

DisplayInstructions, settings and operational information are shown on thedisplay. You can easily navigate between the different menus andoptions to set the comfort or obtain the information you require.

A

Status lampThe status lamp indicates the status of the heat pump. It:

• lights green during normal operation.

• lights yellow in emergency mode.

• lights red in the event of a deployed alarm.

B

13Chapter 2 | The heat pump – the heart of the houseNIBE F750

Page 14: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

OK buttonThe OK button is used to:

• confirm selections of submenus/options/set values/page in the startguide.

C

Back buttonThe back button is used to:

• go back to the previous menu.

• change a setting that has not been confirmed.

D

Control knobThe control knob can be turned to the right or left. You can:

• scroll in menus and between options.

• increase and decrease the values.

• change page in multiple page instructions (for example help textand service info).

E

SwitchThe switch assumes three positions:

• On ( )

• Standby ( )

• Emergency mode ( )

Emergency mode must only be used in the event of a fault on theheat pump. In this mode, the compressor switches off and the immer-sion heater engages. The heat pump display is not illuminated and thestatus lamp illuminates yellow.

F

USB portThe USB port is hidden beneath the plastic badge with the productname on it.

The USB port is used to update the software.

Visit nibeuplink.com and click the "Software" tab to download the latestsoftware for your installation.

G

NIBE F750Chapter 2 | The heat pump – the heart of the house14

Page 15: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

MENU SYSTEMWhen the door to the heat pump is opened, the menu system’s fourmain menus are shown in the display as well as certain basic information.

INDOOR CLIMATE

HEAT PUMP INFO

HOTWATER

Indoor temperature - (if room sensors are installed)

Hot water temp.

Temporary lux (if activated)

Outdoortemperature

Estimated amount of hot water

Information aboutoperation

INDOOR CLIMATESetting and scheduling the indoor climate. See page 33.

Menu 1

HOT WATERSetting and scheduling hot water production. See page 50.

Menu 2

INFODisplay of temperature and other operating information and access to the alarmlog. See page 55.

Menu 3

HEAT PUMPSetting time, date, language, display, operating mode etc. See page 58.

Menu 4

15Chapter 2 | The heat pump – the heart of the houseNIBE F750

Page 16: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Symbols in the displayThe following symbols can appear in the display during operation.

DescriptionSymbol

This symbol appears by the information sign if there is informa-tion in menu 3.1 that you should note.

These two symbols indicate whether the compressor or additionis blocked in F750.

These can, for example, be blocked depending on which oper-ating mode is selected in menu 4.2, if blocking is scheduled inmenu 4.9.5 or if an alarm has occurred that blocks one of them.

Blocking the compressor.

Blocking additional heat.

This symbol appears if periodic increase or lux mode for the hotwater is activated.

This symbol indicates whether "holiday setting" is active in 4.7.

This symbol indicates whether F750 has contact with NIBEUplink.

This symbol indicates the actual speed of the fan if the speedhas changed from the normal setting.

This symbol is visible in installations with active solar accessor-ies.

NIBE F750Chapter 2 | The heat pump – the heart of the house16

Page 17: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

INDOOR CLIMATE

HEAT PUMP INFO

HOTWATER

temperature

INDOOR CLIMATE 1

ventilation

scheduling

advanced

off

normal

Marked main menu

Menu number – marked sub menu Name and menu number – main menu

Symbol – mainmenu

Status information – sub menusName – sub menusSymbols – sub menus

OperationTo move the cursor, turn the control knob to the left or theright. The marked position is white and/or has a turned up tab.

Selecting menuTo advance in the menu system select a main menu bymarking it and then pressing the OK button. A new window then openswith sub menus.

Select one of the sub menus by marking it and then pressing the OKbutton.

17Chapter 2 | The heat pump – the heart of the houseNIBE F750

Page 18: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Selecting options

economy

comfort mode2.2

normal

luxury

Alternative

In an options menu the current selected option is indicated by agreen tick.

To select another option:

1. Mark the applicable option. One of the options is pre-selected(white).

2. Press the OK button to confirm the selected option. The selectedoption has a green tick.

NIBE F750Chapter 2 | The heat pump – the heart of the house18

Page 19: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Setting a value

time & date4.4time

day

year

month

24 h

12 h

date

Values to be changed

To set a value:

1. Mark the value you want to set using the control knob.

2. Press the OK button. The background of the value becomesgreen, which means that you have accessed the setting mode.

3. Turn the control knob to the right to increase the value and tothe left to reduce the value.

4. Press the OK button to confirm the value you have set. Tochange and return to the original value, press the Back button.

19Chapter 2 | The heat pump – the heart of the houseNIBE F750

Page 20: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Use the virtual keyboard

Different keyboards

In some menus where text may require entering, a virtual keyboard isavailable.

Depending on the menu, you can gain access to different character setswhich you can select using the control knob. To change character table,press the Back button. If a menu only has one character set the keyboardis displayed directly.

When you have finished writing, mark "OK" and press the OK button.

NIBE F750Chapter 2 | The heat pump – the heart of the house20

Page 21: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Scroll through the windowsA menu can consist of several windows. Turn the control knob to scrollbetween the windows.

Current menuwindow

Number of windowsin the menu

Scroll through the windows in the start guide

language4.6

If the start guide is left on this page it closesautomatically in

60 min

Arrows to scroll through window in start guide

1. Turn the control knob until one of the arrows in the top left corner(at the page number) has been marked.

2. Press the OK button to skip between the steps in the start guide.

Help menuIn many menus there is a symbol that indicates that extra help isavailable.

To access the help text:

1. Use the control knob to select the help symbol.

2. Press the OK button.

The help text often consists of several windows that you can scrollbetween using the control knob.

21Chapter 2 | The heat pump – the heart of the houseNIBE F750

Page 22: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Maintenance of F750REGULAR CHECKSYour heat pump requires minimal maintenance after commissioning. Onthe other hand, it is recommended that you check your installation regu-larly.

If something unusual occurs, messages about the malfunction appearin the display in the form of different alarm texts. See alarmmanagementon page 72.

Service hatchThe vent valves etc. are behind the service hatch. Remove the hatch bypulling it towards you.

LEK

Cleaning the ventilation devicesThe building’s ventilation devices should becleaned regularly with, for example, a smallbrush to maintain the correct ventilation.

The device settings must not be changed.

NOTEIf you take down more than oneventilation device for cleaning, do notmix them up.

NIBE F750Chapter 2 | The heat pump – the heart of the house22

Page 23: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Cleaning the air filterClean the F750's air filter regularly, how often depends on the amountof dust in the ventilation air. Select what is most suitable for your install-ation.

You will receive a reminder about filter cleaning in the display. The defaultsetting for the reminder is every three months, however, if the powerto F750 is interrupted the countdown begins again.

1. Switch off the heat pump.

2. Remove the upper front cover by pulling straight out.

3. Pull out the filter cassette.

4. Carry out assembly in reverse order.

NOTEWater or other liquids must not be used for cleaning.

LEK

Filter

23Chapter 2 | The heat pump – the heart of the houseNIBE F750

Page 24: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Check pressureF750 has a pressure gauge which shows the heating system pressure.The pressure should be between 0.5 and 1.5 bar, but varies duringtemperature changes. If the pressure drops to 0 or rises to 2.5 frequently,contact your installer for troubleshooting.

LEKLEK

Pressure gauge

NIBE F750Chapter 2 | The heat pump – the heart of the house24

Page 25: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Safety valvesF750 has two safety valves, one for the hot water heater and one forthe climate system.

The water heater’s safety valve sometimes releases a little water afterhot water usage. This is because the cold water, which enters the waterheater, expands when heated causing the pressure to rise and the safetyvalve to open. The climate system’s safety valve must be completelyclosed and must not normally release any water.

The function of the safety valves must be checked regularly. The valvesare accessed via the service hatch. Perform checks as follows:

1. Open the valve by turning the knob anti-clockwise carefully.

2. Check that water flows through the valve.

3. Close the valve by releasing it. If it does not close automatically whenreleased, turn it anti-clockwise slightly.

4. The climate systemmay need to be refilled after checking the safetyvalve, see the section “Filling the climate system”.

F750, copper

N

UN

LEK

Safety valve for water heater

Safety valve for climate system

25Chapter 2 | The heat pump – the heart of the houseNIBE F750

Page 26: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

F750, stainless steel

LEK

Safety valve for climate system

Safety valve for water heater

NIBE F750Chapter 2 | The heat pump – the heart of the house26

Page 27: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Cleaning the overflow cupCondensation forms when the heat pump is working. This condensationis led off and collected in an overflow cup. In addition to water, a certainamount of dust and particles also collect in the overflow cup.

F750, copper

N

UN

LEK

Overflow cup

F750, stainless steel

LEK

Overflow cup

Regularly check that the overflow cup and any floor drains are notblocked; water must be able to run through freely. Clean, if necessary.

27Chapter 2 | The heat pump – the heart of the houseNIBE F750

Page 28: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Filling the climate systemIf the pressure is too low, increase as follows:

1. For F750, stainless steel: Check if the flexi hose supplied is connectedbetween the two filler valves. Adjust the hose if this has not beendone.

2. For F750, stainless steel: Open the filling valves. The heating unitand the rest of the climate system fill with water.

For F750, copper: Open the filler valve . The heating section and therest of the climate system are filled with water.

3. After a while the pressure rises on the pressure gauge. When it isapprox. 1.0 bar close the filler valve.

F750, copper

N

UN

LEK

Pressuremeter

Filler valve

Venting valve

Bleed valves

NIBE F750Chapter 2 | The heat pump – the heart of the house28

Page 29: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

F750, stainless steel

LEK

Filler valve 1

Pressuremeter

Filler valve 2

Venting valve

Bleed valves

Venting the climate systemIn event of repeated filling of the climate system or if bubbling soundsare heard from the heat pump the system may need venting. This iscarried out as follows:

1. Set the switch in mode and wait approx. 30 seconds.

2. Turn off the power supply to the heat pump.

3. Vent the heat pump via the vent valves and the rest of the climatesystem via its respective vent valves.

NOTEThe vent hoses from the container must be drained of waterbefore air can be released. This means that the system is notnecessarily vented despite the flow of water when the ventvalves are opened.

Therefore hold the vent valves open at least 5 seconds.

29Chapter 2 | The heat pump – the heart of the houseNIBE F750

Page 30: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

SAVING TIPSYour heat pump installation produces heat and hot water. This occursvia the control settings you made.

Factors that affect the energy consumption are, for example, indoortemperature, hot water consumption, the insulation level of the houseand whether the house has many large window surfaces. The positionof the house, e.g. wind exposure is also an affecting factor.

Also remember:

• During the adjustment period (winter time) all thermostat valves shouldbe fully open. The heat pump's heating settings are then adjusted sothat the correct indoor temperature is obtained, in most rooms, regard-less of the outdoor temperature. In rooms where a lower temperatureis required, the thermostat valves are lowered to the desired level.After a fewmonths, the remaining thermostats can be lowered slightlyto avoid an increase of the room temperature due to solar radiation,stove heat etc. Further reductions may be required later on.

• You can lower the temperature when away from the house byscheduling "holiday setting" in menu 4.7. See page 66 for instructions.

• You can reduce the ventilation speed when you are away by enteringa schedule in menu 1.3.3. See page 38 for instructions.

• If you activate "Hot water Economy", less energy is used.

Power consumption

Approximate energy consumption for F750 spread across the year

Energiförbrukning fördelat över året

0%

5%

10%

15%

20%

25%

jan feb mars april maj juni juli aug sep okt nov dec

Månad

% a

v å

rsfö

rbru

knin

gen

Month

Jan Feb Mar April May June July Aug Sep Oct Nov Dec

% of annualconsumption

NIBE F750Chapter 2 | The heat pump – the heart of the house30

Page 31: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Increasing the indoor temperature one degree increases the energyconsumption by approx. 5%.

Domestic electricity

In the past it has been calculated that an average Swedish householdhas an approximate annual consumption of 5000 kWh domestic electri-city/year. In today's society it is usually between 6000-12000 kWh/year.

Appr.ann. con-sump(kWh)

Normal Output (W)Equipment

StandbyOperation3802200TV (Operation: 5 h/day, Standby: 19 h/day)901011Digital box (Operation: 5 h/day, Standby: 19

h/day)45515DVD (Operation: 2 h/week)672160TV games console (Operation: 6 h/week)50140Radio/stereo (Operation: 3 h/day)1202100Computer incl. screen (Operation: 3 h/day,

standby 21 h/day)175-60Bulb (Operation 8 h/day)58-20Spot light, Halogen (Operation 8 h/day)165-100Cooling (Operation: 24 h/day)380-120Freezer (Operation: 24 h/day)365-1500Stove, hob (Operation: 40 min/day)310-3000Stove, oven (Operation: 2 h/week)730-2000Dishwasher, cold water connection (Opera-

tion 1 time/day)730-2000Washing machine (Operation: 1 times/day)730-2000Tumble drier (Operation: 1 times/day)100-1000Vacuum cleaner (Operation: 2 h/week)50-400Engine block heater (Operation: 1 h/day, 4

months a year)100-800Passenger compartment heater (Operation:

1 h/day, 4 months a year)

These values are approximate example values.

31Chapter 2 | The heat pump – the heart of the houseNIBE F750

Page 32: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Example: A family with 2 children live in a house with 1 flat-screen TV,1 digital box, 1 DVD player, 1 TV games console, 2 computers, 3 stereos,2 bulbs in the WC, 2 bulbs in the bathroom, 4 bulbs in the kitchen, 3bulbs outside, a washing machine, tumble drier, fridge, freezer, oven,vacuum cleaner, engine block heater = 6240 kWh domestic electri-city/year

Energy meter

Check the accommodation's energy meter regularly, preferably once amonth. This will indicate any changes in power consumption.

Newly built houses usually have twin energy meters, use the differenceto calculate your domestic electricity.

New builds

Newly built houses undergo a drying out process for a year. The housecan then consume significantly more energy than it would thereafter.After 1-2 years the heating curve should be adjusted again, as well asthe offset heating curve and the building's thermostat valves, becausethe heating system, as a rule, requires a lower temperature once thedrying process is complete.

NIBE F750Chapter 2 | The heat pump – the heart of the house32

Page 33: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Set the indoor climateOVERVIEW

Sub-menus

temperature

INDOOR CLIMATE 1

ventilation

scheduling

advanced

off

normal

For the menu INDOOR CLIMATEthere are several sub-menus. Statusinformation for the relevant menu canbe found on the display to the right ofthe menus.

temperature Setting the temperaturefor the climate system. The status in-formation shows the set values forthe climate system.

ventilation Setting the fan speed. The status information shows theselected setting.

scheduling Scheduling heating and ventilation. Status information "set"is displayed if you set a schedule but it is not active now, "holiday setting"is displayed if the vacation schedule is active at the same time as theschedule (the vacation function is prioritised), "active" displays if any partof the schedule is active, otherwise it displays "off".

advanced Setting of heat curve, adjusting with external contact, minim-um value for supply temperature, room sensor and night cooling.

33Chapter 3 | F750 – at your serviceNIBE F750

3 F750 – at your service

Page 34: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

TEMPERATUREtemperature heating1.1.1Set the temperature (with room

sensors installed and activated):

heatingSetting range: 5 – 30 °C

Default value: 20

The value in the display appears as atemperature in °C if the climate system iscontrolled by a room sensor.

Menu1.1

CautionA slow heat-releasing heating system, such as for example, underfloorheating, may not be suitable for control using the heat pump's roomsensor.

To change the room temperature, use the control knob to set the desired tem-perature in the display. Confirm the new setting by pressing the OK button. Thenew temperature is shown on the right-hand side of the symbol in the display.

Setting the temperature (without room sensors activated):

Setting range: -10 to +10

Default value: -1

The display shows the set values for heating (curve offset). To increase or reducethe indoor temperature, increase or reduce the value on the display.

Use the control knob to set a new value. Confirm the new setting by pressingthe OK button.

The number of steps the value has to be changed to achieve a degree changeof the indoor temperature depends on the heating installation. One step is usuallyenough but in some cases several steps may be required.

Setting the desired value. The new value is shown on the right-hand side of thesymbol in the display.

NIBE F750Chapter 3 | F750 – at your service34

Page 35: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

CautionAn increase in the room temperature can be slowed by the thermostats for the radiators or under floor heating. Therefore, open the thermostats fully, except in those rooms where a cooler temperature is required, e.g. bedrooms.

If the exhaust air temperature falls below 6 °C the compressor is blocked and electric additional heat is permitted. Heat is not recovered from the exhaust air when the compressor is blocked.

TIPWait 24 hours before making a new setting, so that the room temper-ature has time to stabilise.

If it is cold outdoors and the room temperature is too low, increasethe curve slope in menu 1.9.1.1 by one increment.

If it is cold outdoors and the room temperature is too high, reduce thecurve slope in menu 1.9.1.1 by one increment.

If it is warm outdoors and the room temperature is too low, increasethe value in menu 1.1.1 by one increment.

If it is warm outdoors and the room temperature is too high, reducethe value in menu 1.1.1 by one increment.

VENTILATION

normal(50%)

ventilation1.2

speed 1 (0%)

speed 2 (40%)

speed 3 (80%)

speed 4 (100%)

Setting range: normal and speed 1-4

Default value: normal

Menu1.2

The ventilation in the accommodation can be temporarily increased or reducedhere.

When you have selected a new speed a clock starts a count down. When thetime has counted down the ventilation speed returns to the normal setting.

35Chapter 3 | F750 – at your serviceNIBE F750

Page 36: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

If necessary, the different return times can be changed in menu 1.9.6.

The fan speed is shown in brackets (in percent) after each speed alternative.

TIPIf longer time changes are required use the holiday function orscheduling.

CautionThe heat pump requires a minimum ventilation flow in order to workproperly. An insufficient ventilation flow can result in an alarm andblocking of compressor operation.

SCHEDULINGscheduling1.3

ventilation off

heating off

In the menu scheduling indoor climate(heating/ventilation) is scheduled for eachweekday.

You can also schedule a longer periodduring a selected period (vacation) in menu4.7.

Menu1.3

HEATINGIncreases or decreases in the accommodation temperature can be scheduledhere for up to three time periods per day. If a room sensor is installed and activ-ated the desired room temperature (°C) is set during the time period. Without

Menu1.3.1

an activated room sensor the desired change is set (of setting in menu 1.1). Onestep is usually enough to change the room temperature by one degree, but insome cases several steps may be required.

NIBE F750Chapter 3 | F750 – at your service36

Page 37: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

SCHEDULING HEATING 1.3.1

activated

schedule 2

system

schedule 3schedule 1

all

mon

tues

wed

thur

fri

sat

sun

21:30 - 06:00 20.5°

Time period AdjustingDay

Activated Schedule System

Conflict

Schedule: The schedule to be changed is selected here.

Activated: Scheduling for the selected period is activated here. Set times arenot affected at deactivation.

System: The climate system that the relevant schedule relates to is selectedhere. This alternative is only displayed if there is more than one climate system.

37Chapter 3 | F750 – at your serviceNIBE F750

Page 38: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Day: Select which day or days of the week the scheduling is to apply to here.To remove the scheduling for a particular day, the time for that day must be resetby setting the start time to the same as the stop time. If the row "all" is used, alldays in the period are set according to that row.

Time period: The start and stop time for the selected day for scheduling are se-lected here.

Adjustment: How much the heating curve is to be offset in relation to menu 1.1during scheduling is set here. If a room sensor is installed, the desired roomtemperature is set in °C.

Conflict: If two settings conflict with each other, a red exclamation mark is dis-played.

TIPIf you wish to set similar scheduling for every day of the week startby filling in “all” and then changing the desired days.

TIPSet the stop time earlier than the start time so that the period extendsbeyond midnight. Scheduling then stops at the set stop time the dayafter.

Scheduling always starts on the date that the start time is set for.

CautionChanges of temperature in accommodation take time. For example, short time periods in combination with underfloor heating will not give a noticeable difference in room temperature.

If the exhaust air temperature falls below 6 °C the compressor is blocked and electric additional heat is permitted. When the compressor is blocked heat is not recovered from the exhaust air.

VENTILATIONIncreases or decreases in the ventilation to the accommodation can be scheduledhere for up to two time periods per day.

Menu1.3.3

NIBE F750Chapter 3 | F750 – at your service38

Page 39: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

all

mon

tues

wed

thur

fri

sat

sun

activated

schedule 2schedule 1

SCHEDULING VENTILATION 1.3.3

21:30 - 06:00 speed 3

Activated Schedule

Time period AdjustingDay Conflict

Schedule: The schedule to be changed is selected here.

Activated: Scheduling for the selected period is activated here. Set times arenot affected at deactivation.

Day: Select which day or days of the week the scheduling is to apply to here.To remove the scheduling for a particular day, the time for that day must be resetby setting the start time to the same as the stop time. If the row "all" is used, alldays in the period are set according to that row.

Time period: The start and stop time for the selected day for scheduling are se-lected here.

Adjustment: The desired fan speed is set here.

Conflict: If two settings conflict with each other, a red exclamation mark is dis-played.

TIPIf you wish to set similar scheduling for every day of the week startby filling in “all” and then changing the desired days.

39Chapter 3 | F750 – at your serviceNIBE F750

Page 40: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

TIPSet the stop time earlier than the start time so that the period extendsbeyond midnight. Scheduling then stops at the set stop time the dayafter.

Scheduling always starts on the date that the start time is set for.

CautionA significant change over a longer period of timemay cause poor indoorenvironment and worse operating economy.

ADVANCEDadvanced 1.9

heating curve

external adjustment

min. flow line temp.

room sensor settings

fan return time

own curve

Menu advanced has orange text and isintended for the advanced user. This menuhas several sub-menus.

heating curve Setting the heating curveslope.

external adjustment Setting the heatcurve offset when the external contact isconnected.

min. flow line temp. Setting minimumpermitted flow line temperature.

Menu1.9

room sensor settings Settings regarding the room sensor.

fan return time Fan return time settings in the event of temporary ventilationspeed change.

own curve Setting own heat curve.

point offset Setting the offset of the heating curve at a specific outdoor temper-ature.

night cooling Setting night cooling.

NIBE F750Chapter 3 | F750 – at your service40

Page 41: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

HEATING CURVE

heating curveheating curve1.9.1.1

system

outdoor temp. °C

flow temperature °C

Setting range: 0 - 15

Default value: 5

Menu1.9.1

The prescribed heating curve for your house can be viewed in the menu heatingcurve . The task of the heating curve is to give an even indoor temperature, re-gardless of the outdoor temperature, and thereby energy efficient operation. Itis from this heating curve that the heat pump's control computer determinesthe temperature of the water to the heating system, supply temperature, andtherefore the indoor temperature. Select the heating curve and read off how thesupply temperature changes at different outdoor temperatures here.

Curve coefficientThe slope of the heating curve indic-ates how many degrees the supplytemperature is to be increased/re-ducedwhen the outdoor temperaturedrops/increases. A steeper slopemeans a higher supply temperatureat a certain outdoor temperature.

200 10 0 -10 -20 -30 -40

30

40

50

60

70

80

Framledningstempereratur

(°C)

Utetemperatur

(°C)

Steeper curve slope

Supply temperature

Outdoor temperature

The optimum slope depends on the climate conditions in your location, if thehouse has radiators or under floor heating and how well insulated the house is.

The heating curve is set when the heating installation is installed, but may needadjusting later. Thereafter the heating curve should not need further adjustment.

41Chapter 3 | F750 – at your serviceNIBE F750

Page 42: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

CautionIn the event of making fine adjustments for the indoor temperature,the heat curve must be offset up or down instead, this is done in menu1.1 temperature .

Curve offsetAn offset of the heating curvemeansthat the supply temperature ischanged by the same amount for alloutdoor temperatures, e.g. a curveoffset of +2 steps increases thesupply temperature by 5 °C at alloutdoor temperatures.

200 10 0 -10 -20 -30 -40

30

40

50

60

70

80

Framledningstempereratur

(°C)

Utetemperatur

(°C)

Offset heating curve

Supply temperature

Outdoor temperature

Flow line temperature–maximum and minimumvaluesBecause the flow line temperaturecannot be calculated higher than theset maximum value or lower than theset minimum value the heating curveflattens out at these temperatures.

200 10 0 -10 -20 -30 -40

30

40

50

60

70

80

Framledningstempereratur

(°C)

Utetemperatur

(°C)

Maximum value

Supply temperature

Outdoor temperature

Minimum value

CautionUnderfloor heating systems are normally max flow line temperatureset between 35 and 45 °C.

Check the max temperature for your floor with your installer/floorsupplier.

The figure at the end of the curve indicates the curve slope. The figure besidethe thermometer gives the curve offset. Use the control knob to set a new value.Confirm the new setting by pressing the OK button.

Curve 0 is an own heating curve created in menu 1.9.7.

NIBE F750Chapter 3 | F750 – at your service42

Page 43: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

To select another heat curve (slope):

NOTEIf you only have one heating system, the number of the curve is alreadymarked when the menu window opens.

1. Select the system (if more than one) for which the heat curve is to bechanged.

2. When the system selection has been confirmed the heat curve number ismarked.

3. Press the OK button to access the setting mode

4. Select a new heating curve. The heating curves are numbered from 0 to 15,the greater the number, the steeper the slope and the greater the supplytemperature. Heating curve 0 means that own curve (menu 1.9.7) is used.

5. Press the OK button to exit the setting.

To read off a heating curve:1. Turn the control knob so that the ring on the shaft with the outdoor temper-

ature is marked.

2. Press the OK button.

3. Follow the grey line up to the heat curve and out to the left to read off thevalue for the supply temperature at the selected outdoor temperature.

4. You can now select to take read outs for different outdoor temperatures byturning the control knob to the right or left and read off the correspondingflow temperature.

5. Press the OK or Back button to exit read off mode.

43Chapter 3 | F750 – at your serviceNIBE F750

Page 44: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

TIPWait 24 hours before making a new setting, so that the room temper-ature has time to stabilise.

If it is cold outdoors and the room temperature is too low, increasethe curve slope by one increment.

If it is cold outdoors and the room temperature is too high, lower thecurve slope by one increment.

If it is warm outdoors and the room temperature is too low, increasethe curve offset by one increment.

If it is warm outdoors and the room temperature is too high, lower thecurve offset by one increment.

EXTERNAL ADJUSTMENT

external adjustment1.9.2

climate system 1

climate system 2

climate system 3

climate system 4

°C

°C

climate systemSetting range: -10 to +10.

Or desired room temperature if theroom sensor is installed. See illustra-tion.

Default value: 0

Menu1.9.2

Connecting an external contact, for example, a room thermostat or a timer allowsyou to temporarily or periodically raise or lower the room temperature whileheating. When the contact is on, the heating curve offset is changed by thenumber of steps selected in themenu. If a room sensor is installed and activatedthe desired room temperature (°C) is set.

If there is more than one climate system the setting can be made separately foreach system.

NIBE F750Chapter 3 | F750 – at your service44

Page 45: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

MIN. FLOW LINE TEMP.

min. flow line temp.1.9.3

climate system 1

climate system 2

climate system 3

climate system 4

°C

°C

°C

°C

20

20

20

20

heatingSetting range: 20-70 °C

Default value: 20 °C

Menu1.9.3

Set theminimum temperature on the supply temperature to the climate system.This means that F750 never calculates a temperature lower than that set here.

If there is more than one climate system the setting can be made separately foreach system.

TIPThe value can be increased if you have, for example, a cellar that youalways want to heat, even in summer.

You may also need to increase the value in "stop heating" menu 4.9.2"auto mode setting".

45Chapter 3 | F750 – at your serviceNIBE F750

Page 46: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

ROOM SENSOR SETTINGS

room sensor settings 1.9.4

factor system 1

control room sensor syst 2

control room sensor syst 3

factor system 3

control room sensor syst 1

control room sensor syst 4

factor systemSetting range: 0.0 - 6.0

Default value: 2.0

Menu1.9.4

Room sensors to control the room temperature can be activated here.

CautionA slow heating system such as underfloor heating may not be suitablefor control using the installation’s room sensors.

Here you can set a factor (a numerical value) that determines howmuch an overor sub normal temperature (the difference between the desired and actual roomtemperature) in the room is to affect the supply temperature to the climatesystem. A higher value gives a greater and faster change of the heating curve'sset offset.

NOTEToo high a set value for "factor system" can (depending on your climatesystem) produce an unstable room temperature.

If several climate systems are installed the above settings can be made for therelevant systems.

NIBE F750Chapter 3 | F750 – at your service46

Page 47: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

FAN RETURN TIME

fan return time1.9.6

speed 1

speed 2

speed 3

speed 4

hrs

hrs

hrs

hrs

speed 1-4Setting range: 1 – 99 h

Default value: 4 h

Here you select the return time for temporary speed change (speed 1-4) on theventilation in menu 1.2.

Return time is the time it takes before ventilation speed returns to normal.

Menu1.9.6

OWN CURVE

own curve1.9.7

flow line temp. at -20 °C

flow line temp. at -10 °C

flow line temp. at 0 °C

flow line temp. at 10 °C

flow line temp. at -30 °C

flow line temp. at 20 °C

°C

°C

°C

°C

°C

°C

supply temperatureSetting range: 0 – 80 °C

You can create your own heating curve here, if there are special requirements,by setting the desired supply temperatures for different outdoor temperatures.

Menu1.9.7

CautionCurve 0 in menu 1.9.1 must be selected for own curve to apply.

47Chapter 3 | F750 – at your serviceNIBE F750

Page 48: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

POINT OFFSET

point offset 1.9.8

change in curve

outdoor temp. point

°C

°C

outdoor temp. °C

flow temperature °C

outdoor temp. pointSetting range: -40 – 30 °C

Default value: 0 °C

change in curveSetting range: -10 – 10 °C

Default value: 0 °C

Menu1.9.8

Select a change in the heating curve at a certain outdoor temperature here. Onestep is usually enough to change the room temperature by one degree, but insome cases several steps may be required.

The heat curve is affected at ± 5 °C from set outdoor temp. point.

It is important that the correct heating curve is selected so that the room tem-perature is experienced as even.

TIPIf it is cold in the house, at, for example -2 °C, "outdoor temp. point"is set to "-2" and "change in curve" is increased until the desired roomtemperature is maintained.

CautionWait 24 hours before making a new setting, so that the room temper-ature has time to stabilise.

NIBE F750Chapter 3 | F750 – at your service48

Page 49: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

NIGHT COOLING

night cooling1.9.9

min diff. outdoor-exhaust

start temp. exhaust air

°C

°C

night cooling

start temp. exhaust airSetting range: 20 – 30 °C

Default value: 25 °C

min diff. outdoor-exhaustSetting range: 3 – 10 °C

Default value: 6 °C

Menu1.9.9

Activate night cooling here.

When the temperature in the house is high and the outdoor temperature is lower,a cooling effect can be obtained by forcing the ventilation.

If the temperature difference between the exhaust air and the outdoor air tem-perature is greater than the set value ("min diff. outdoor-exhaust") and the exhaustair temperature is higher than the set value ("start temp. exhaust air") run theventilation at speed 4 until one of the conditions is no longer met.

CautionNight cooling can only be activated when house heating has been de-activated. This is done in menu 4.2.

49Chapter 3 | F750 – at your serviceNIBE F750

Page 50: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Set the hot water capacityOVERVIEW

Sub-menus

temporary lux

HOTWATER 2

comfort mode

scheduling

advanced

active

economy

off

For themenu HOTWATER there areseveral sub-menus. Status informationfor the relevant menu can be foundon the display to the right of themenus.

temporary lux Activation of tempor-ary increase in the hot water temper-ature. Status information displays “off"or what length of time of the tempor-ary temperature increase remains.

comfort mode Setting hot water comfort. The status information displayswhat mode is selected, "economy", "normal" or "luxury".

scheduling Scheduling hot water comfort. The status information "set"appears if you have set scheduling but it is not currently active, "holidaysetting" appears if holiday setting is active at the same time as scheduling(when the holiday function is prioritised), "active" appears if any part ofscheduling is active, otherwise "off" appears.

advanced Setting periodic increase in the hot water temperature.

TEMPORARY LUX

off

temporary lux2.1

3 hrs

6 hrs

12 hrs

one timeincrease

Setting range: 3, 6 and 12 hours andmode "off" and "one time increase"

Default value: "off"

Menu2.1

When hot water requirement has temporarily increased this menu can be usedto select an increase in the hot water temperature to lux mode for a selectabletime.

NIBE F750Chapter 3 | F750 – at your service50

Page 51: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

CautionIf comfort mode "luxury" is selected in menu 2.2 no further increasecan be carried out.

The function is activated immediately when a time period is selected and con-firmed using the OK button. The remaining time for the selected setting is shownto the right.

When the time has run out F750 returns to the mode set in menu 2.2.

Select “off" to switch off temporary lux .

COMFORT MODE

economy

comfort mode2.2

normal

luxury

Setting range: economy, normal, luxury

Default value: normal

Menu2.2

The difference between the selectable modes is the temperature of the hot tapwater. Higher temperature means that the hot water lasts longer.

economy: This mode produces less hot water than the others, but is more eco-nomical. This mode can be used in smaller households with a small hot waterrequirement.

normal:Normal mode gives a larger amount of hot water and is suitable for mosthouseholds.

luxury: Lux mode gives the greatest possible amount of hot water. In this mode,the immersion heater is used to heat hot water as well as the compressor, whichincreases operating costs.

51Chapter 3 | F750 – at your serviceNIBE F750

Page 52: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

SCHEDULING

all

mon

tues

wed

thur

fri

sat

sun

activated

schedule 2schedule 1

SCHEDULING HOTWATER 2.3

normal

Activated Schedule

Time period AdjustingDay Conflict

What hot water comfort the heat pump isto work with can be scheduled here for upto two different time periods per day.

Scheduling is activated/deactivated byticking/unticking"activated". Set times arenot affected at deactivation.

Schedule: The schedule to be changed isselected here.

Activated: Scheduling for the selectedperiod is activated here. Set times are notaffected at deactivation.

Menu2.3

Day: Select which day or days of the week the scheduling is to apply to here.To remove the scheduling for a particular day, the time for that day must be resetby setting the start time to the same as the stop time. If the row "all" is used, alldays in the period are set according to that row.

Time period: The start and stop time for the selected day for scheduling are se-lected here.

Adjustment: Set the hot water comfort that is to apply during scheduling here.

Conflict: If two settings conflict with each other, a red exclamation mark is dis-played.

TIPIf you wish to set similar scheduling for every day of the week startby filling in “all” and then changing the desired days.

TIPSet the stop time earlier than the start time so that the period extendsbeyond midnight. Scheduling then stops at the set stop time the dayafter.

Scheduling always starts on the date that the start time is set for.

NIBE F750Chapter 3 | F750 – at your service52

Page 53: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

ADVANCEDadvanced 2.9

periodic increase

hot water recirc.

Menu advanced has orange text and isintended for the advanced user. This menuhas several sub-menus.

Menu2.9

PERIODIC INCREASE

periodic increase 2.9.1

activated

period

start time

Next periodic increase

days

periodSetting range: 1 - 90 days

Default value: 14 days

start timeSetting range: 00:00 - 23:00

Default value: 00:00

Menu2.9.1

To prevent bacterial growth in the water heater, the compressor and the immer-sion heater can increase the hot water temperature for a short time at regularintervals.

The length of time between increases can be selected here. The time can beset between 1 and 90 days. Factory setting is 14 days. Tick/untick "activated" tostart/switch off the function.

53Chapter 3 | F750 – at your serviceNIBE F750

Page 54: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

HOT WATER RECIRC.

hot water recirc.2.9.2

operating time

downtime min

min

period1

period2

period3

operating timeSetting range: 1 - 60 min

Default value: 60 min

downtimeSetting range: 0 - 60 min

Default value: 0 min

Menu2.9.2

Set the hot water circulation for up to three periods per day here. During the setperiods the hot water circulation pump will run according to the settings above.

"operating time" decide how long the hot water circulation pump must run peroperating instance.

"downtime" decide how long the hot water circulation pump must be stationarybetween operating instances.

NIBE F750Chapter 3 | F750 – at your service54

Page 55: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Get informationOVERVIEW

Sub-menus

service info

INFO 3

compressor info

add. heat info

alarm log

off

runs

indoor temp. log

For the menu INFO there are severalsub-menus. No settings can be madein these menus, they just display in-formation. Status information for therelevant menu can be found on thedisplay to the right of the menus.

service info shows temperaturelevels and settings in the installation.

compressor info shows operatingtimes, number of starts etc for the compressor in the heat pump.

add. heat info displays information about the additional heat's operatingtimes etc.

alarm log displays the latest alarm and information about the heat pumpwhen the alarm occurred.

indoor temp. log the average temperature indoors week by week duringthe past year.

SERVICE INFOMenu3.1

service info 3.1

status internal add.

set max electrical add.

EB100

off5

Information about the heat pump’s actualoperating status (e.g. current temperat-ures etc.) can be obtained here. Nochanges can be made.

The information is on several pages. Turnthe control knob to scroll between thepages.

55Chapter 3 | F750 – at your serviceNIBE F750

Page 56: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Symbols in this menu:

HeatingCompressor

Hot waterAddition

VentilationCirculation pump, climatesystem

Solar accessory

COMPRESSOR INFOcompressor info 3.2

status:

number of starts:

total operating time:

- of which hot water:

initiating

time factor:

- of which hot water:

hrs

hrs

Information about the compressor’s oper-ating status and statistics can be obtainedhere. No changes can be made.

The information is on several pages. Turnthe control knob to scroll between thepages.

Menu3.2

ADD. HEAT INFOadd. heat info3.3

status:

time factor:

off

Information about the additional heat'ssettings, operating status and statisticscan be obtained here. No changes can bemade.

The information is on several pages. Turnthe control knob to scroll between thepages.

Menu3.3

NIBE F750Chapter 3 | F750 – at your service56

Page 57: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

ALARM LOGalarm log3.4

TB alarm

LP alarm

Sensor flt:BT6

Sens flt:BT20

Sensor flt:BT2

Sensor flt:BT1

To facilitate fault-finding the heat pumpoperating status at alarm alerts is storedhere. You can see information for the 10most recent alarms.

To view the run status in the event of analarm, mark the alarm and press the OKbutton.

alarm log3.4

outdoor temp.

heat medium flow

heat medium return

hot water charging

condenser out

operating time

op. mode

Temperature limiter alarm(52)

-5.6 °C

30.5 °C

25.0 °C

49.0 °C

30 min

off

6.2 °C

Information about an alarm.

Menu3.4

INDOOR TEMP. LOG

week

exhaust air °C

indoor temp. log3.5Here you can see the average temperatureindoors week by week during the pastyear. The dotted line indicates the annualaverage temperature.

To read off an averagetemperature1. Turn the control knob so that the ring

on the shaft with the week number ismarked.

2. Press the OK button.

3. Follow the grey line up to the graph and out to the left to read off the averageindoor temperature at the selected week.

4. You can now select to take read outs for different weeks by turning thecontrol knob to the right or left and read off the average temperature.

5. Press the OK or Back button to exit read off mode.

Menu3.5

57Chapter 3 | F750 – at your serviceNIBE F750

Page 58: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Adjust the heat pumpOVERVIEW

Sub-menus

op. mode

HEAT PUMP 4

my icons

time & date

language/ language

off

auto

plus functions

holiday setting

svenska

For the menu HEAT PUMP there areseveral sub-menus. Status informationfor the relevant menu can be foundon the display to the right of themenus.

plus functions Settings applying toany installed extra functions in theheating system.

op. mode Activation of manual orautomatic operating mode. The status information shows the selectedoperating mode.

my icons Settings regarding which icons in the heat pump's user inter-face that are to appear in the slot when the door is closed.

time & date Setting current time and date.

language Select the language for the display here. The status informationshows the selected language.

holiday setting Vacation scheduling heating, hot water and ventilation.Status information "set" is displayed if you set a vacation schedule butit is not active at the moment, "active" is displayed if any part of the va-cation schedule is active, otherwise it displays " off".

advanced Setting heat pump work mode.

PLUS FUNCTIONSplus functions4.1

internet

sms

Settings for any additional functions in-stalled in F750 can be made in the submenus.

Menu4.1

NIBE F750Chapter 3 | F750 – at your service58

Page 59: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

INTERNET

nibe uplink

internet4.1.3

tcp/ip settings

proxy settings

Here you make settings for connectingF750 to the internet.

NOTEFor these functions to work thenetwork cable must be connec-ted.

Menu4.1.3

NIBE UPLINK

request new connection string

serial number

nibe uplink 4.1.3.1

switch off all users

connection string

number of users

Here you can manage the installation'sconnection to NIBE Uplink(nibeuplink.com) and see the number ofusers connected to the installation via theinternet.

A connected user has a user account inNIBE Uplink , which has been given per-mission to control and/or monitor your in-stallation.

Request new connection stringTo connect a user account on NIBE Uplink to your installation, you must requesta unique connection code.

Menu4.1.3.1

1. Mark “request new connection string" and press the OK button.

2. The installation now communicates with NIBE Uplink to create a connectioncode.

3. When a connection string has been received, it is shown in this menu at"connection string" and is valid for 60 minutes.

Disconnect all users1. Mark “switch off all users" and press the OK button.

2. The installation now communicates with NIBE Uplink to release your install-ation from all users connected via the internet.

59Chapter 3 | F750 – at your serviceNIBE F750

Page 60: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

NOTEAfter disconnecting all users none of them can monitor or control yourinstallation via NIBE Uplink without requesting a new connection string.

TCP/IP SETTINGStcp/ip settings4.1.3.8

confirm reset

automatic

ip-address

net mask

gateway

dns

You can set TCP/IP settings for your install-ation here.

Automatic setting (DHCP)

Menu4.1.3.8

1. Tick “automatic". The installation nowreceives the TCP/IP settings usingDHCP.

2. Mark “confirm" and press the OKbutton.

Manual setting1. Untick "automatic", you now have access to several setting options.

2. Mark “ip-address" and press the OK button.

3. Enter the correct details via the virtual keypad.

4. Mark “OK" and press the OK button.

5. Repeat 1 - 3 for "net mask", "gateway" and "dns".

6. Mark “confirm" and press the OK button.

CautionThe installation cannot connect to the internet without the correctTCP/IP settings. If unsure about applicable settings use the automaticmode or contact your network administrator (or similar) for further in-formation.

TIPAll settings made since opening the menu can be reset by marking"reset" and pressing the OK button.

NIBE F750Chapter 3 | F750 – at your service60

Page 61: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

PROXY SETTINGS

confirm reset

proxy settings 4.1.3.9

use proxy

server

port

user name

password

You can set proxy settings for your install-ation here.

Proxy settings are used to give connectioninformation to a intermediate server (proxyserver) between the installation and Inter-net. These settings are primarily usedwhen the installation connects to the Inter-net via a company network. The installa-tion supports proxy authentication of theHTTP Basic and HTTP Digest type.

Menu4.1.3.9

If unsure about applicable settings, contact your network administrator (or similar)for further information.

Setting1. Tick “use proxy" if you do not want to use a proxy.

2. Mark “server" and press the OK button.

3. Enter the correct details via the virtual keypad.

4. Mark “OK" and press the OK button.

5. Repeat 1 - 3 for "port", "user name" and "password".

6. Mark “confirm" and press the OK button.

TIPAll settings made since opening the menu can be reset by marking"reset" and pressing the OK button.

SMS (ACCESSORY IS REQUIRED)

phone number alarm receiver

sms 4.1.4Make settings for the accessory SMS 40here.

Add the mobile numbers that are to haveaccess to change and receive status in-formation from the heat pump. Mobilenumbers must include country code e.g.+46 XXXXXXXX.

If you want to receive an SMS messagein the event of the alarm mark the box tothe right of the telephone number.

Menu4.1.4

61Chapter 3 | F750 – at your serviceNIBE F750

Page 62: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

NOTETelephone numbers providedmust be able to receive SMSmessages.

SG READY

affect room temperature

affect hot water

SG Ready 4.1.5This function can only be used in mainsnetworks that support the "SGReady"-standard .

Make settings for the function "SG Ready"here.

affect room temperatureHere you set whether room temperatureshould be affected when activating "SGReady".

Menu4.1.5

With low price mode on "SG Ready" the parallel offset for the indoor temperatureis increased by "+1". If a room sensor is installed and activated, the desired roomtemperature is instead increased by 1 °C.

With over capacity mode on "SG Ready" the parallel offset for the indoor temper-ature is increased by "+2". If a room sensor is installed and activated, the desiredroom temperature is instead increased by 2 °C.

affect hot waterHere you set whether the temperature of the hot water should be affected whenactivating "SG Ready".

With low price mode on "SG Ready" the stop temperature of the hot water isset as high as possible at only compressor operation (immersion heater notpermitted).

With over capacity mode of "SG Ready" the hot water is set to "luxury" (immersionheater permitted).

NOTEThe function must be connected and activated in your F750.

NIBE F750Chapter 3 | F750 – at your service62

Page 63: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

SMART PRICE ADAPTION™

affect room temperature

activated

affect hot water

price of electricityoverview

area

smart price adaption 4.1.6affect room temperatureSetting range: 1 - 10

Factory setting: 5

affect hot waterSetting range: 1 - 4

Factory setting: 2

Menu4.1.6

areaIn this menu you state where the heat pump is located and how great a role theelectricity price should play. The greater the value, the greater the effect theelectricity price has and the possible savings are larger, but at the same timethere is an increased risk of affecting comfort.

price of electricity overviewHere you can obtain information on howthe electricity price varies over up to threedays.

Smart price adaption™ moves the heatpump's consumption over 24 hours toperiods with the cheapest electricity tariff,which gives savings for hourly rate basedelectricity contracts. The function is basedon hourly rates for the next 24 hours beingretrieved via NIBE Uplink and therefore aninternet connection and an account for NIBE Uplink are required.

Deselect "activated" to switch off Smart price adaption™.

63Chapter 3 | F750 – at your serviceNIBE F750

Page 64: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

OP. MODE

op. mode4.2

auto

manual

add. heat only

op. modeSetting range: auto, manual, add. heatonly

Default value: auto

functionsSetting range: compressor, addition,heating

Menu4.2

The heat pump operating mode is usually set to "auto". It is also possible to setthe heat pump to "add. heat only", but only when an addition is used, or "manual"and select yourself what functions are to be permitted.

Change the operating mode by marking the desired mode and pressing the OKbutton. When an operating mode is selected, it shows what is permitted in theheat pump (crossed out = not permitted) and selectable alternatives to the right.To select selectable functions that are permitted or not, mark the function usingthe control knob and press the OK button.

Operating mode autoIn this operating mode the heat pump automatically selects what functions arepermitted.

Operating mode manualIn this operating mode you can select what functions are permitted. You cannotdeselect "compressor" in manual mode.

Operating mode add. heat onlyIn this operating mode the compressor is not active, only additional heat is used.

CautionIf you choose mode "add. heat only" the compressor is deselected andthere is a higher operating cost.

Functions"compressor" is the unit that produces heating and hot water for the home. If"compressor" is deselected, this is indicated with a symbol in the main menu onthe heat pump symbol. You cannot deselect "compressor" in manual mode.

NIBE F750Chapter 3 | F750 – at your service64

Page 65: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

"addition" is the unit that helps the compressor to heat the home and/or the hotwater when it cannot manage the entire requirement alone.

"heating" means you obtain heating in the home. You can deselect the functionwhen you do not wish to have the heating on.

CautionIf you deselect "addition" it may mean that insufficient hot water and/orheating in the accommodation is achieved.

MY ICONSmy icons 4.3

outdoor/indoor temperature

hot water temperature

digital clock

analog clock

You can select what icons should be vis-ible when the door to F750 is closed. Youcan select up to 3 icons. If you selectmore, the ones you selected first will dis-appear. The icons are displayed in the or-der you selected them.

Menu4.3

TIME & DATEtime & date4.4

time

day

year

month

24 h

12 h

date

Set time and date, display mode and timezone here.

TIPTime and date are set automat-ically if the heat pump is connec-ted to NIBE Uplink. To obtainthe correct time, the time zonemust be set.

Menu4.4

65Chapter 3 | F750 – at your serviceNIBE F750

Page 66: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

LANGUAGElanguage4.6Choose the language that you want the

information to be displayed in here.

Menu4.6

HOLIDAY SETTINGholiday setting4.7

activated

start date

stop date

heating

hot water

ventilation

0

normal

economy

To reduce energy consumption during aholiday you can schedule a reduction inheating, ventilation and hot water temper-ature. Solar panel cooling can also bescheduled if the function is connected.

If a room sensor is installed and activated,the desired room temperature (°C) is setduring the time period. This setting appliesto all climate systems with room sensors.

If a room sensor is not activated, the de-sired offset of the heating curve is set. One step is usually enough to changethe room temperature by one degree, but in some cases several steps may berequired. This setting applies to all climate systems without room sensors.

Menu4.7

Vacation scheduling starts at 00:00 on the start date and stops at 23:59 on thestop date.

TIPComplete holiday setting about a day before your return so that roomtemperature and hot water have time to regain usual levels.

TIPSet the vacation setting in advance and activate just before departurein order to maintain the comfort.

NIBE F750Chapter 3 | F750 – at your service66

Page 67: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

CautionIf the exhaust air temperature falls below 6 °C the compressor is blocked and electric additional heat is permitted. When the compressor is blocked heat is not recovered from the exhaust air.

CautionThe heat pump requires a minimum ventilation flow in order to workproperly. An insufficient ventilation flow can result in an alarm andblocking of compressor operation.

CautionIn installations with water heaters without an immersion heater con-nected to F750"hot water" should not be set to "off" when holidaysetting is activated.

ADVANCEDadvanced 4.9

op. prioritisation

auto mode setting

degree minute setting

factory setting user

schedule blocking off

Menu advanced has orange text and isintended for the advanced user. This menuhas several sub-menus.

Menu4.9

67Chapter 3 | F750 – at your serviceNIBE F750

Page 68: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

OP. PRIORITISATION

min

min

hot water

heating

op. prioritisation 4.9.1op. prioritisationSetting range: 0 to 180 min

Default value: 30 min

Choose here how long the heat pump should work with each requirement ifthere are two requirements at the same time. If there is only one requirementthe heat pump only works with that requirement.

The indicator marks where in the cycle the heat pump is.

If 0 minutes is selected it means that requirement is not prioritised, but will onlybe activated when there is no other requirement.

Menu4.9.1

AUTO MODE SETTING

stop heating

stop additional heat

filtering time

°C

°C

hrs

auto mode setting4.9.2stop heatingSetting range: -20 – 40 °C

Default values: 15

stop additional heatSetting range: -25 – 40 °C

Factory setting: 5

filtering timeSetting range: 0 – 48 h

Default value: 24 h

Menu4.9.2

When the operating mode is set to "auto", the heat pump selects when start andstop of additional heat and heat production is permitted, dependent on the aver-age outdoor temperature.

Select the average outdoor temperatures in this menu.

NIBE F750Chapter 3 | F750 – at your service68

Page 69: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

CautionIt cannot be set "stop additional heat" higher than "stop heating".

filtering time: You can also set the time (filtering time) over which the averagetemperature is calculated. If you select 0, the current outdoor temperature isused.

DEGREE MINUTE SETTING

current value

start compressor

start diff additional heat

diff. between additional steps

DM

DM

DM

DM

degree minute setting4.9.3current valueSetting range: -3000 – 3000

start compressorSetting range: -1000 – -30

Default value: -60

start diff additional heatSetting range: 100 – 1000

Factory setting: 700

diff. between additional stepsSetting range: 0 – 1000

Factory setting: 50

Menu4.9.3

Degree minutes are a measurement of the current heating requirement in thehouse and determine when the compressor respectively additional heat willstart/stop.

CautionHigher value on "start compressor" gives more compressor starts,which increasewear on the compressor. Too low value can give unevenindoor temperatures.

69Chapter 3 | F750 – at your serviceNIBE F750

Page 70: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

FACTORY SETTING USER

Do you want to reset all user settings tofactory settings?

factory setting user4.9.4

yesno

All settings that are available to the user(including advanced menus) can be resetto default values here.

CautionAfter factory setting, personalsettings such as heating curves,ventilation etc must be reset.

Menu4.9.4

SCHEDULE BLOCKING

activated

schedule 2schedule 1

all

mon

tues

wed

thur

fri

sat

sun

schedule blocking4.9.5

Activated Schedule

Time period BlockingDay Conflict

The compressor can be scheduled to beblocked for up to two different time periodshere.

When scheduling is active the actualblocking symbol in the main menu on theheat pump symbol is displayed.

Schedule: The period to be changed is se-lected here.

Activated: Scheduling for the selectedperiod is activated here. Set times are notaffected at deactivation.

Menu4.9.5

Day: Select which day or days of the week the scheduling is to apply to here.To remove the scheduling for a particular day, the time for that day must be resetby setting the start time to the same as the stop time. If the row "all" is used, alldays in the period are set according to that row.

Time period: The start and stop time for the selected day for scheduling are se-lected here.

Blocking: The desired blocking is selected here.

Conflict: If two settings conflict with each other, a red exclamation mark is dis-played.

Blocking the compressor.

Blocking additional heat.

NIBE F750Chapter 3 | F750 – at your service70

Page 71: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

TIPIf you wish to set similar scheduling for every day of the week startby filling in “all” and then changing the desired days.

TIPSet the stop time earlier than the start time so that the period extendsbeyond midnight. Scheduling then stops at the set stop time the dayafter.

Scheduling always starts on the date that the start time is set for.

CautionLong term blocking can cause reduced comfort and operating economy.

71Chapter 3 | F750 – at your serviceNIBE F750

Page 72: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

In most cases, the heat pump notes operational interference (operationalinterference can lead to disturbance in comfort) and indicates this withalarms and shows action instructions in the display.

Info-menuAll the heat pump measurement values are gathered under menu 3.1 inthe heat pump menu system. Looking through the values in this menucan often simplify finding the fault source. See page 55 for more inform-ation about menu 3.1.

Manage alarm

info / action

reset alarm

aid mode

Low pressure alarm

alarm

In the event of an alarm, some kindof malfunction has occurred, which isindicated by the status lamp changingfrom green continuously to red con-tinuously. In addition, an alarm bellappears in the information window.

ALARMIn the event of an alarm with a redstatus lamp a malfunction has oc-curred that the heat pump cannot remedy itself. In the display, by turningthe control knob and pressing the OK button, you can see the type ofalarm it is and reset it. You can also choose to set the heat pump to aidmode.

info / action Here you can read what the alarm means and receive tipson what you can do to correct the problem that caused the alarm.

reset alarm In many cases, it is sufficient to select “reset alarm” in orderfor the product to revert to normal operation. If a green light comes onafter selecting “reset alarm”, the alarm has been remedied. If a red light

NIBE F750Chapter 4 | Disturbances in comfort72

4 Disturbances in comfort

Page 73: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

is still visible and a menu called “alarm” is visible in the display, theproblem causing the alarm still remains. If the alarm initially disappearsand then returns, you should contact your installer.

aid mode “aid mode” is a type of emergency mode. This means thatthe heat pump produces heat and/or hot water even though there issome kind of problem. This couldmean that the heat pump’s compressoris not running. In this case, the immersion heater produces heat and/orhot water.

CautionSelecting "aid mode” is not the same as correcting the problemthat caused the alarm. The status lamp will therefore continueto be red.

If the alarm does not reset, contact your installer for suitable remedialaction.

NOTEAlways state the product’s serial number (14 digits) when re-porting a fault.

TroubleshootingIf the operational interference is not shown in the display the followingtips can be used:

BASIC ACTIONSStart by checking the following possible fault sources:

• The switch's position.

• Group and main fuses of the accommodation.

• Earth-fault breaker.

• Correctly set load monitor (if installed).

LOW HOT WATER TEMPERATURE OR A LACK OF HOTWATER• Closed or choked filling valve for the hot water heater.

– Open the valve.

73Chapter 4 | Disturbances in comfortNIBE F750

Page 74: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

• Mixing valve (if there is one installed) set too low.

– Adjust the mixer valve.

• Heat pump in incorrect operating mode.

– Enter menu 4.2. If mode "auto" is selected, select a higher value on"stop additional heat" in menu 4.9.2.

– If mode "manual" is selected, select "addition".

• Large hot water consumption.

– Wait until the hot water has heated up. Temporarily increased hotwater capacity (temporary lux) can be activated in menu 2.1.

• Too low hot water setting.

– Enter menu 2.2 and select a higher comfort mode.

• Too low or no operating prioritisation of hot water.

– Enter menu 4.9.1 and increase the time for when hot water is to beprioritised. Note that if the time for hot water is increased, the timefor heating production is reduced, which can give lower/uneven roomtemperatures.

• Filter blocked.

– Clean or replace filter (see page 23).

LOW ROOM TEMPERATURE• Closed thermostats in several rooms.

– See section "Saving tips" on page 30 and menu 1.1 on page 34 formore detailed information about how to best set the thermostats.

• Heat pump in incorrect operating mode.

– Enter menu 4.2. If mode "auto" is selected, select a higher value on"stop heating" in menu 4.9.2.

– If mode "manual" is selected, select "heating". If this is not enough,select "addition".

• Too low set value on the automatic heating control.

– Enter menu 1.1 "temperature" and adjust the offset heating curveup. If the room temperature is only low in cold weather the curveslope in menu 1.9.1 "heating curve" needs adjusting up.

NIBE F750Chapter 4 | Disturbances in comfort74

Page 75: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

• Too low or no operating prioritisation of heat.

– Enter menu 4.9.1 and increase the time for when heating is to beprioritised. Note that if the time for heating is increased the time forhot water production is reduced, which can give smaller amounts ofhot water.

• "comfort mode" "luxury" selected in combination with large hot wateroutlet.

– Enter menu 2.2 and select "economy" or "normal".

• "Holiday mode" activated in menu 4.7.

– Enter menu 4.7 and select "Off".

• External switch for changing the room heating activated.

– Check any external switches.

• Air in the heating system.

– Vent the heating system.

• Closed valve to the heating system.

– Open the valve (contact your installer for assistance in finding them).

• Filter blocked.

– Clean or replace filter (see page 23).

HIGH ROOM TEMPERATURE• Too high set value on the automatic heating control.

– Enter menu 1.1 (temperature) and reduce the offset heating curve.If the room temperature is only high in cold weather the curve slopein menu 1.9.1 "heating curve" needs adjusting down.

• External switch for changing the room heating activated.

– Check any external switches.

LOW SYSTEM PRESSURE• Not enough water in the heating system.

– Top up the water in the heating system.

LOW OR A LACK OF VENTILATION• Filter blocked.

75Chapter 4 | Disturbances in comfortNIBE F750

Page 76: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

– Clean or replace filter (see page 23).

• The ventilation is not adjusted.

– Order ventilation adjustment.

• Exhaust air device blocked or throttled down too much.

– Check and clean the exhaust air devices (see page 22).

• Fan speed in reduced mode.

– Enter menu 1.2 and select "normal".

• External switch for changing the fan speed activated.

– Check any external switches.

HIGH OR DISTRACTING VENTILATION• Filter blocked.

– Clean or replace filter (see page 23).

• The ventilation is not adjusted.

– Order ventilation adjustment.

• Fan speed in forced mode.

– Enter menu 1.2 and select "normal".

• External switch for changing the fan speed activated.

– Check any external switches.

THE COMPRESSOR DOES NOT START• There is no heating requirement.

– The heat pump does not call on heating nor hot water.

– The heat pump defrosts.

• Compressor blocked due to the temperature conditions.

– Wait until the temperature is within the product’s working range.

• Minimum time between compressor starts has not been reached.

– Wait for at least 30 minutes and then check if the compressor hasstarted.

• Alarm tripped.

– Follow the display instructions.

NIBE F750Chapter 4 | Disturbances in comfort76

Page 77: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Detailed technical specifications for this product can be found in the in-stallation manual (nibe.eu).

77Chapter 5 | Technical dataNIBE F750

5 Technical data

Page 78: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

ADDITIONAL HEATThe additional heat is the heat produced in addition to the heat suppliedby the compressor in your heat pump. Additional heaters can be for ex-ample, immersion heater, electric heater, gas/oil/pellet/wood burner ordistrict heating.

BUFFER VESSELA buffer vessel increases the system volume and removes the unwantedtemperature variations that can otherwise be sent out on the climatesystem. This ensure the running of the heat pump and reduces the heatspikes that could otherwise be heard from the climate system.

CALCULATED FLOW LINE TEMPERATUREThe temperature that the heat pump calculates that the heating systemrequires for an optimum accommodation temperature. The colder theoutdoor temperature, the higher the calculated supply temperature.

CIRCULATION PUMPPump that circulates liquid in a pipe system.

CLIMATE SYSTEMClimate systems can also be called heating systems. The building isheated using radiators, under floor coils or convector fans.

COMPRESSORCompresses the gas state refrigerant. When the refrigerant is com-pressed, the pressure and the temperature increase.

CONDENSERHeat exchanger where the hot gas state refrigerant condenses (cooledand becomes a liquid) and releases heat energy to the house heatingand hot water systems.

NIBE F750Chapter 6 | Glossary78

6 Glossary

Page 79: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

DISTURBANCES IN COMFORTDisturbances in comfort are undesirable changes to the hot water/indoorcomfort, for example when the temperature of the hot water is too lowor if the indoor temperature is not at the desired level.

A malfunction in the heat pump can sometimes be noticed in the formof a disturbance in comfort.

Inmost cases, the heat pump notes operational interference and indicatesthis with alarms and shows instructions in the display.

DOMESTIC HOT WATERThe water one showers in for example.

ELECTRICAL ADDITIONThis is the electricity that, for example, an immersion heater produceswhen the compressor's output is not sufficient to fulfil the property'sheating demand.

EMERGENCY MODEA mode that can be selected using the switch in the event of a fault,which means that the compressor stops. When the heat pump is inemergencymode, the building is heated using an immersion heater. Hotwater is not produced.

EVAPORATORHeat exchanger where the refrigerant evaporates by retrieving heat en-ergy from the air which then cools.

EXHAUST AIRThe air that comes from the exhaust air device in the various rooms ofthe accommodation, to F750.

EXHAUST AIR DEVICESVents, usually in the ceiling, in the kitchen/bathroom/clothes closet wherethe air is drawn in to be forwarded to F750.

79Chapter 6 | GlossaryNIBE F750

Page 80: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

EXPANSION VALVEValve that reduces the pressure of the refrigerant, whereupon the tem-perature of the refrigerant drops.

EXPANSION VESSELVessel with heatingmedium fluid with the task of equalising the pressurein the heating medium system.

EXTRACT AIRThe air that the heat pump has retrieved heat from and which hastherefore been cooled. This air is blown out of the building.

FILTERING TIMEIndicates the time the average outdoor temperature is calculated on.

FLOW PIPEThe line in which the heated water is transported from the heat pumpout to the house heating system (radiators/heating coils).

HEAT EXCHANGERDevice that transfers heat energy from one medium to another withoutmixing mediums. Examples of different heat exchangers include evapor-ators and condensers.

HEAT FACTORMeasurement of how much heat energy the heat pump gives off in re-lation to the electric energy it needs to operate. Another term for this isCOP.

HEATING CURVEThe heating curve determines which heat the heat pump is to producedepending on the temperature outdoors. If a high value is selected, thistells the heat pump that it must produce a lot of heat when it is coldoutdoors in order to achieve a warm indoor temperature.

HEATING MEDIUMHot liquid, usually normal water, which is sent from the heat pump tothe house climate system and makes the accommodation warm. Theheating medium also heats the hot water.

NIBE F750Chapter 6 | Glossary80

Page 81: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

HEATING MEDIUM SIDEPipes to the house’s climate system make up the heating medium side.

MIXING VALVEA valve that mixes the cold water with the hot water leaving the heater.

OUTSIDE SENSORA sensor that is located outdoors. This sensor tells the heat pump howhot it is outdoors.

PRESSOSTATPressure switch that triggers an alarm and/or stops the compressor ifnon-permitted pressures occur in the system. A high pressure pressostattrips if the condensing pressure is too great. A low pressure pressostattrips if the evaporation pressure is too low.

RADIATORAnother word for heating element. Theymust be filled with water in orderto be used with F750.

REFRIGERANTSubstance that circulates around a closed circuit in the heat pump andthat, through pressure changes, evaporates and condenses. Duringevaporation, the refrigerant absorbs heating energy andwhen condensinggives off heating energy.

RETURN PIPEThe line in which the water is transported back to the heat pump fromthe house heating system (radiators/heating coils).

RETURN TEMPThe temperature of the water that returns to the heat pump after releas-ing the heat energy to the radiators/heating coils.

ROOM SENSORA sensor that is located indoors. This sensor tells the heat pump howhot it is indoors.

81Chapter 6 | GlossaryNIBE F750

Page 82: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

SAFETY VALVEA valve that opens and releases a small amount of liquid if the pressureis too high.

SHUNTA valve that mixes the hot water with a small amount of slightly coolerwater.

SHUTTLE VALVEA valve that can send liquid in two directions. A shuttle valve that enablesliquid to be sent to the climate system, when the heat pump producesheating for the house, and to the hot water heater, when the heat pumpproduces hot water.

SUPPLY TEMPERATUREThe temperature of the heated water that the heat pump sends out tothe heating system. The colder the outdoor temperature, the higher thesupply line temperature becomes.

WATER HEATERContainer where domestic water is heated. Is located inside the heatpump, but an extra hot water heater can be installed in the event of largehot water requirements.

NIBE F750Chapter 6 | Glossary82

Page 83: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

A

Adjust the heat pump, 58Alarm, 72

B

Back button, 14

C

Contact with F750, 12Display unit, 13External information, 12Menu system, 15

Control knob, 14

D

Display, 13Display unit, 13

Back button, 14Control knob, 14Display, 13OK button, 14Status lamp, 13Switch, 14

Disturbances in comfort, 72Alarm, 72Manage alarm, 72Troubleshooting, 73

E

External information, 12Information window, 12Status lamp, 12

F

F750 – An excellent choice, 8

F750 – at your service, 33Adjust the heat pump, 58Get information, 55Set the hot water capacity, 50Set the indoor climate, 33

G

Get information, 55Glossary, 78

H

Heat pump function, 10Help menu, 21

I

Important informationF750 – An excellent choice, 8Installation data, 4Serial number, 7

Information window, 12Installation data, 4

M

Maintenance of F750, 22Regular checks, 22Saving tips, 30

Manage alarm, 72Menu system, 15

Help menu, 21Operation, 17Scroll through the windows, 21Selecting menu, 17Selecting options, 18Setting a value, 19Use the virtual keyboard, 20

83Item registerNIBE F750

Item register

Page 84: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

O

OK button, 14Operation, 17

P

Power consumption, 30

R

Regular checks, 22

S

Saving tips, 30Power consumption, 30

Scroll through the windows, 21Selecting menu, 17Selecting options, 18Serial number, 7Set the hot water capacity, 50Set the indoor climate, 33Setting a value, 19Status lamp, 12–13Switch, 14

T

Technical data, 77The heat pump – the heart of thehouse, 9Troubleshooting, 73

U

Use the virtual keyboard, 20

NIBE F750Item register84

Page 85: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …
Page 86: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …
Page 87: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

Contact informationKNV Energietechnik GmbH, Gahberggasse 11, AT-4861 SchörflingTel: +43 (0)7662 8963 E-mail: [email protected] www.knv.at

AT

NIBE Wärmetechnik c/o ait Schweiz AG,Industriepark, CH-6246 Altishofen Tel: +41 58 252 21 00E-mail: [email protected] www.nibe.ch

CH

Druzstevni zavody Drazice s.r.o,Drazice 69, CZ - 294 71 Benatky nad JizerouTel: +420 326 373 801 E-mail: [email protected] www.nibe.cz

CZ

NIBE Systemtechnik GmbH, Am Reiherpfahl 3, 29223 CelleTel: +49 (0)5141 7546-0 E-mail: [email protected] www.nibe.de

DE

Vølund Varmeteknik A/S, Member of the Nibe Group,Brogårdsvej 7, 6920 Videbæk Tel: +45 97 17 20 33E-mail: [email protected] www.volundvt.dk

DK

NIBE Energy Systems OY, Juurakkotie 3, 01510 VantaaTel: +358 (0)9-274 6970 E-mail: [email protected] www.nibe.fi

FI

NIBE Energy Systems France Sarl,Zone industrielle RD 28, Rue du Pou du Ciel,01600 ReyrieuxTel : 04 74 00 92 92 E-mail: [email protected] www.nibe.fr

FR

NIBE Energy Systems Ltd,3C Broom Business Park, Bridge Way, S419QG ChesterfieldTel: +44 (0)845 095 1200 E-mail: [email protected] www.nibe.co.uk

GB

NIBE Energietechniek B.V., Postbus 634, NL 4900 AP OosterhoutTel: 0168 477722 E-mail: [email protected] www.nibenl.nl

NL

ABK AS, Brobekkveien 80, 0582 Oslo, Postboks 64 Vollebekk, 0516 OsloTel: +47 23 17 05 20 E-mail: [email protected]

NO

NIBE-BIAWAR Sp. z o. o. Aleja Jana Pawła II 57, 15-703 BIALYSTOKTel: +48 (0)85 662 84 90 E-mail: [email protected]

PL

© "EVAN" 17, per. Boynovskiy, RU-603024 Nizhny NovgorodTel: +7 831 419 57 06 E-mail: [email protected] www.nibe-evan.ru

RU

NIBE AB Sweden, Box 14, Hannabadsvägen 5, SE-285 21 MarkarydTel: +46 (0)433 27 3000 E-mail: [email protected] www.nibe.se

SE

For countries not mention in this list, please contact Nibe Sweden or checkwww.nibe.eu for more information.

Page 88: UHBEN1835-1 USERMANUAL 431836 Exhaustairheatpump …

NIBE Energy SystemsHannabadsvägen 5Box 14SE-285 21 [email protected]

UHBEN18

35-1

4318

36

This manual is a publication from NIBE Energy Systems. All product illustrations,

facts and data are based on the available information at the time of the publica-

tion’s approval. NIBE Energy Systems makes reservations for any factual or

printing errors in this manual.

©2018 NIBE ENERGY SYSTEMS431836

WS name: Frånluft - FVPvår2018 o F470WS version: a48 (working edition)Publish date: 2018-08-29 14:20