ul ex-4510 4-1-05 page 1-4 - suppression...the 24 vdc electric actuator is required to electrically...
TRANSCRIPT
System ComponentsUL EX-4510 4-1-05 Page 1-4
REV. 1
The 24 VDC electric actuator is required to electrically actu-ate the tank valve. An electric signal is required from theAUTOPULSE Control panel which operates the solenoid inthe actuator. This causes the actuator to open the tankvalve and discharge the agent. On multiple tank systems,only one actuator is required, on the master valve. Theremaining tanks will be actuated pneumatically through1/4 in. stainless steel hose and a pneumatic actuatorinstalled on the top of each tank valve.
The actuator draw is 0.2A.
Note: Composite cap attached to actuator is used as thereset tool. To reset actuator, put cap in place and turnknurled swivel coupling until cap threads are completelyengaged. A small “click” will be heard while resetting.
Note: Actuator has a 10-year shelf life.
Electric Actuator – 24 VDC
TYCO SAFETY PRODUCTS, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003186-1 ©2005 Ansul Incorporated Litho in U.S.A.
ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.
Shipping AssemblyPart No. Description
570537 Electric Actuator
ThreadComponent Material Type Approvals
Electric Body: Steel 1 in. UL ListedActuator Swivel Nut: BSPP ULC Listed
Brass FM ApprovedActuation Pin:StainlessSteel
006763
1.8 IN.(45 mm)
3.3 IN.(85 mm)
1 IN. BSP