Split Sleeve Firestop
System Installation
![Page 2: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/2.jpg)
UNIQUE Split Sleeve Firestop System
is a UL tested retrofit solution
designed for sleeving, firestopping
and smoke sealing cables or wires
already installed without a sleeve and
in violation of the firewall rating.
![Page 3: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/3.jpg)
The system includes:
(2) 12 inch long threaded 1/2 sleeves
(4) slotted washers
(2) slotted couplings
(2) split bushings
2 documentation/
warning labels
a package of
UNIQUE Intumescent Putty
![Page 4: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/4.jpg)
The threaded sleeves comes in 4-inches,
2-inches, and 1-inch diameter.
![Page 5: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/5.jpg)
INSTALLATION PICTORIAL
![Page 6: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/6.jpg)
A common penetration
violation in a sheet
rock firewall. A Sleeve
will control and direct
the expansion of the
fire-rated intumescent
putty. Without a sleeve, this penetration may fail to restore
the hourly rating of this wall.
![Page 7: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/7.jpg)
Clean-up the firewall penetration (both sides
of wall) ensuring not to nick the cable
jacket(s).
![Page 8: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/8.jpg)
After you clean up the hole, slide the bottom
half of the threaded sleeve under the
cables. Look for the machine holes near the
ends of the sleeve halves to maintain polarity.
![Page 9: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/9.jpg)
Slide the top half over the cables, maintaining
sleeve polarity, until both halves protrude
evenly. Position the sleeve with the seams at 9
and 3 o’clock.
![Page 10: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/10.jpg)
Work the cables through the slot in the first
washer and work the washer down the sleeve,
against the wall. The first washer’s slot should
be positioned at the 6 o’clock position.
![Page 11: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/11.jpg)
Install the second slotted washer, inverting
the slots 180 degrees from each other (12
o’clock).
![Page 12: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/12.jpg)
Work the slotted coupling around the cables
(again, maintaining polarity) and screw it down
against the washers. The coupling should be
hand tightened only. Repeat this procedure on
the other side of the wall.
![Page 13: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/13.jpg)
Install the “split bushings”, taking care not to
open the bushing any more than is needed to
get the cables in.
![Page 14: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/14.jpg)
Install a minimum 1-inch thickness of the
supplied UNIQUE intumescent firestop putty in
both ends of the Sleeve System. See our UL Systems documentation for Systems rated up to 4 hours.
Intumescent putty is supplied with the system.
![Page 15: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/15.jpg)
Install the documentation labels provided
with the system and take a picture of your
installed system.
![Page 16: Unique Firestop Split Sleeve System Installation Guide](https://reader036.vdocument.in/reader036/viewer/2022062523/5876503f1a28ab0d198b69ad/html5/thumbnails/16.jpg)
NOW BRING ON THE
INSPECTOR!