uno

2
On-Line Uninterruptible Power Systems Double conversion On-Line UPS • LCD display front panel • Network surge protection • Emergency Power Off function • On-line technology • Support USB communication • High efficiency mode selectable • Battery remain time display • Pure sine-wave output with less than 3% THD • Input Power Factor Correction • Insolation Transformer Included • Digitized microprocessor controlled • Cold start function (DC power on) • Lightning and surge protection • Short Circuit and overload protection • Battery management system (BMS) • Automatic battery charge in UPS when UPS is OFF • Battery replacement warning • Automatic diagnostics & battery check • RS-232 communication port with monitoring software • SNMP card (optional) • Fan speed auto control when load varies • UPSMON plus monitoring software • On line output voltage selected ASP MODEL UPS model: 6, 8, 10, 12, 15, 20 KVA

Upload: alejandra-cuesta

Post on 11-Mar-2016

215 views

Category:

Documents


0 download

DESCRIPTION

MODEL On-Line Uninterruptible Power Systems UPS model: 6, 8, 10, 12, 15, 20 KVA • LCD display front panel • Network surge protection • Emergency Power Off function • On-line technology • Support USB communication • High efficiency mode selectable • Battery remain time display • Pure sine-wave output with less than 3% THD • Input Power Factor Correction • Insolation Transformer Included • Digitized microprocessor controlled • Cold start function (DC power on)

TRANSCRIPT

Page 1: UNO

UPS model: 10KVA - 15KVA - 20KVA - 30KVA - 40KVA

Three PhaseOn-Line UPS

• Input Power Factor Correction PFC(0.98)• Extended Input Voltage Range• Rectifier and Inverter with IGBT Technology • 208/120V / 60Hz Models• Digital Signal Processor (DSP) • Expandable battery for longer run times• EPO (Emergency Power Off)• Transformerless design• Low Total Harmonic Distortion Level ( THDi ≤ 4% )• Generator Synchronization• High Efficiency ( up to 95% )

• High Efficiency ( up to 95% ) • Generator Compatible Technology• Special voltage applications other than stated values• Modular Parallel Systems • Static and Manual Bypass Included• Battery Management System (BMS) for longer lifetime of batteries

Optional Accesories- Remote Monitoring Panel &25m Cable For Remote Panel

- UPSMAN (Management Software)

- Multiserver Shutdown Software

- SNMP: Internal Slot Card

- SNMP Adapter with Modbus (external)

- Split bypass - Parallel Kit

ti PFC(0 98) Hi h Effi i

On-LineUninterruptiblePower Systems

Doubleconversion

On-Line UPS

208/120V/60Hz

External Cabinet

<1%

Overload

10 KVA 15 KVA 20 KVA 30 KVA 40 KVA

Authorized Dealer

Output Power (KVA) MODEL Nominal Active Power (KW) INPUT Number of PhasesNominal Voltage (phase-phase) (VAC) Voltage Range (100% load) Nominal Frequency (Hz) Frequency Range Input Current THD Input Power Factor OUTPUT Power FactorNumber of Phases Voltage (phase-neutral) (VAC) Voltage (phase-phase) (VAC) Static Voltage Regulation ( at 100% Linear Load)On line & Battery Mode Dynamic Response to 100% Load StepVoltage THD (at 100% Linear Load)Crest Factor Frequency (Hz) Free Running Frequency (Hz) Efficiency BATTERY Type Battery Protection Battery TestDC VoltageBattery (Standard Internal Batteries)Run Time at Full Load Run Time at half Load DISPLAY LED Display LCD Display STATIC BYPASS Voltage Range for Bypass Operation Frequency Range COMMUNICATIONS Interface ( Communication Ports) Dry Contact SignalsSNMP InterfaceModbus Interface Others ENVIRONMENTAL Storage Temperature Range Operating Temperature Range Relative Humidity Range Altitude Without DeratingCabinet Protection levelAudible Noise

PHYSICAL SPECIFICATIONS

Dimensions W x D x H (cm)Weight w/o Internal Batteries (Kg)Weight with Internal Batteries (Kg)

CERTIFICATIONS

WARRANTY

• LCD display front panel• Network surge protection• Emergency Power Off function• On-line technology• Support USB communication• High efficiency mode selectable• Battery remain time display• Pure sine-wave output with less than 3% THD• Input Power Factor Correction• Insolation Transformer Included• Digitized microprocessor controlled• Cold start function (DC power on)

• Lightning and surge protection• Short Circuit and overload protection• Battery management system (BMS)• Automatic battery charge in UPS when UPS is OFF• Battery replacement warning• Automatic diagnostics & battery check• RS-232 communication port with monitoring software• SNMP card (optional)• Fan speed auto control when load varies• UPSMON plus monitoring software• On line output voltage selected

Tower model (with LCD display) Model: ASP

CAPACITY

OUTPUT

ASP-6000 ASP-8000 ASP-10000 ASP-12000 ASP-15000

Capacity (VA) 6000VA 8000VA 10000VA 12000VA 15000VA

Capacity (W) 4200W 5600W 7000W 8400W

Transfer Time 0 ms

10500W

ASP-20000

20000VA

14000W

Range (0 ~ 100% load)

208V , 220V , 230V , 240V

180 ~ 276V

Voltage / Load

Frequency 50 / 60 Hz Auto Sensing

Voltage (on battery) 120 / 208V , 220V , 230V , 240V +/-2% (Selectable Output Voltage)

Frequency (on battery) 50 / 60 Hz +/-0.5%

PROTECTION AND

FILTERING

SYSTEM

DISPLAY / WARNING

INPUT

Surge Protection IEC61000-4-5 level 3

Overload Protection 125% for 1 minutes and 150% for 10 seconds (On-line)

130% for 10 seconds and 150% for 1.5 seconds (On-battery)

Short Circuit Protection UPS output cut off immediately or input fuse / circuit breaker protection

High Efficiency mode (AC to AC) > 97 %

UPS Design Technology On-Line / digitized microprocessor controlled

Output W ave Form Sinewave

Harmonic distortion < 3% of T.H.D. at linear load

Crest Factor 3 : 1

T

240 VDC

Visual Display (LCD model) Input / output voltage, input / output frequency , on-line mode, back up mode, battery capacity, load level

Audible Alarm (Battery back-up) Beep every 5 sec

UPS Fault Continuous beeping sound and LCD display

Communication RS-232 Serial Port and USB (included ) / SNMP card (optional)

Type Sealed, maintenance-free lead acid batteries

DC Voltage (V) Battery

Input lnlet Hardwire

Receptacles Hardwire

Typical Recharge Time

to 90% Full4 hours

Management Self-test, adjustable battery transfer points and alarm settings

Battery Protection Cut of f without draining any current when battery is low

Cold Start (DC start) YES

Back Up Time (Tower model) About 6 min Full load / 15min Half load

145.0 (319.0) 151.5 (333.3) 201.5 (443.3) 246.5 (542.3)

257 x 590 x 700 342 x 690 x 715 342 x 690 x 878 342 x 863 x 905Tower Dimensions

mm W x D x H W/ ISOTR

Shipping Weight kg (lb) W/ ISOTR

123.0 (270.6) 130.0 (286.0) 180.0 (396.0) 225.0 (495.0)Net Weight kg (lb) W/ ISOTR

Operating Temperature 0 - 40 ºC / 32 ~ 104 ºF

Storage Temperature -20 ~ 50 ºC / -4 ~ 122 ºF

Altitude 3000 meters max without derating

Audible Noise

(1 meter from surface)< 55 dBA

Relative Humidity 0 ~ 95% humidity , non-condensing

Safety UL 1778, CE

EMC (EMS / EMI) IEC 61000-4, FCC Part 15, CISPR 22

Warranty 2 years

PHYSICAL

BA TTERY

ENVIRONMENT

CONFORMANCE

Authorized Dealer

ATPMODEL ASP

MODEL

ATP 10 ATP 15 ATP 20 ATP 30 ATP 40 8 12 16 24 32

3Ph+N+G 208 - 220

-15% + 27%50 or 60+/- 10%

≤ 4%0.98

0.83Ph+N+G 120 - 127208 - 220

<3%+/- 2%

3:150 or 60

+/- 0.01%125% 10 min150% 1 min93% Typical

Maintenance-Free Lead Acid BatteriesDeep Discharge Protection With Auto Cut Off

Standard (Automatic and Manual)+/- 204 VDC

10 min24 min

Line, Bypass, Battery, Inverter, Load, Fault IndicationsLoad %, Input and Output Frequency, Voltage and Current, Bypass Voltage,

Battery Voltage and Current, Temperature, Alarms

+/- 10%+/- 6% (configurable)

RS-232 and RS-422 AC Failure, Battery Under Voltage, Bypass Operation, Output Failure

Optional SNMP CardOptional SNMP Card with Modbus

EPO, Generator Interface

-15 to +55 ºC0 to 40 ºC (20 to 25 ºC Recommended For Long Battery Life Time)

0 to 95% (Non Condensing)< 3000 m

IP20< 60dBA at 1 Meter Distance

40 x 78 x 107 52 x 90 x 130 67 x 73 x 153 110 242 260 203 233 428 488 540

EN 62040-1-1 (Safety), EN 62040-2 (EMC), EN 62040-3 (VFI-SS-111)

2 YEARS

UPS model: 6, 8, 10, 12, 15, 20 KVA

September - 2011 September - 2011

Page 2: UNO

UPS model: 10KVA - 15KVA - 20KVA - 30KVA - 40KVA

Three PhaseOn-Line UPS

• Input Power Factor Correction PFC(0.98)• Extended Input Voltage Range• Rectifier and Inverter with IGBT Technology • 208/120V / 60Hz Models• Digital Signal Processor (DSP) • Expandable battery for longer run times• EPO (Emergency Power Off)• Transformerless design• Low Total Harmonic Distortion Level ( THDi ≤ 4% )• Generator Synchronization• High Efficiency ( up to 95% )

• High Efficiency ( up to 95% ) • Generator Compatible Technology• Special voltage applications other than stated values• Modular Parallel Systems • Static and Manual Bypass Included• Battery Management System (BMS) for longer lifetime of batteries

Optional Accesories- Remote Monitoring Panel &25m Cable For Remote Panel

- UPSMAN (Management Software)

- Multiserver Shutdown Software

- SNMP: Internal Slot Card

- SNMP Adapter with Modbus (external)

- Split bypass - Parallel Kit

ti PFC(0 98) Hi h Effi i

On-LineUninterruptiblePower Systems

Doubleconversion

On-Line UPS

208/120V/60Hz

External Cabinet

<1%

Overload

10 KVA 15 KVA 20 KVA 30 KVA 40 KVA

Authorized Dealer

Output Power (KVA) MODEL Nominal Active Power (KW) INPUT Number of PhasesNominal Voltage (phase-phase) (VAC) Voltage Range (100% load) Nominal Frequency (Hz) Frequency Range Input Current THD Input Power Factor OUTPUT Power FactorNumber of Phases Voltage (phase-neutral) (VAC) Voltage (phase-phase) (VAC) Static Voltage Regulation ( at 100% Linear Load)On line & Battery Mode Dynamic Response to 100% Load StepVoltage THD (at 100% Linear Load)Crest Factor Frequency (Hz) Free Running Frequency (Hz) Efficiency BATTERY Type Battery Protection Battery TestDC VoltageBattery (Standard Internal Batteries)Run Time at Full Load Run Time at half Load DISPLAY LED Display LCD Display STATIC BYPASS Voltage Range for Bypass Operation Frequency Range COMMUNICATIONS Interface ( Communication Ports) Dry Contact SignalsSNMP InterfaceModbus Interface Others ENVIRONMENTAL Storage Temperature Range Operating Temperature Range Relative Humidity Range Altitude Without DeratingCabinet Protection levelAudible Noise

PHYSICAL SPECIFICATIONS

Dimensions W x D x H (cm)Weight w/o Internal Batteries (Kg)Weight with Internal Batteries (Kg)

CERTIFICATIONS

WARRANTY

• LCD display front panel• Network surge protection• Emergency Power Off function• On-line technology• Support USB communication• High efficiency mode selectable• Battery remain time display• Pure sine-wave output with less than 3% THD• Input Power Factor Correction• Insolation Transformer Included• Digitized microprocessor controlled• Cold start function (DC power on)

• Lightning and surge protection• Short Circuit and overload protection• Battery management system (BMS)• Automatic battery charge in UPS when UPS is OFF• Battery replacement warning• Automatic diagnostics & battery check• RS-232 communication port with monitoring software• SNMP card (optional)• Fan speed auto control when load varies• UPSMON plus monitoring software• On line output voltage selected

Tower model (with LCD display) Model: ASP

CAPACITY

OUTPUT

ASP-6000 ASP-8000 ASP-10000 ASP-12000 ASP-15000

Capacity (VA) 6000VA 8000VA 10000VA 12000VA 15000VA

Capacity (W) 4200W 5600W 7000W 8400W

Transfer Time 0 ms

10500W

ASP-20000

20000VA

14000W

Range (0 ~ 100% load)

208V , 220V , 230V , 240V

180 ~ 276V

Voltage / Load

Frequency 50 / 60 Hz Auto Sensing

Voltage (on battery) 120 / 208V , 220V , 230V , 240V +/-2% (Selectable Output Voltage)

Frequency (on battery) 50 / 60 Hz +/-0.5%

PROTECTION AND

FILTERING

SYSTEM

DISPLAY / WARNING

INPUT

Surge Protection IEC61000-4-5 level 3

Overload Protection 125% for 1 minutes and 150% for 10 seconds (On-line)

130% for 10 seconds and 150% for 1.5 seconds (On-battery)

Short Circuit Protection UPS output cut off immediately or input fuse / circuit breaker protection

High Efficiency mode (AC to AC) > 97 %

UPS Design Technology On-Line / digitized microprocessor controlled

Output W ave Form Sinewave

Harmonic distortion < 3% of T.H.D. at linear load

Crest Factor 3 : 1

T

240 VDC

Visual Display (LCD model) Input / output voltage, input / output frequency , on-line mode, back up mode, battery capacity, load level

Audible Alarm (Battery back-up) Beep every 5 sec

UPS Fault Continuous beeping sound and LCD display

Communication RS-232 Serial Port and USB (included ) / SNMP card (optional)

Type Sealed, maintenance-free lead acid batteries

DC Voltage (V) Battery

Input lnlet Hardwire

Receptacles Hardwire

Typical Recharge Time

to 90% Full4 hours

Management Self-test, adjustable battery transfer points and alarm settings

Battery Protection Cut of f without draining any current when battery is low

Cold Start (DC start) YES

Back Up Time (Tower model) About 6 min Full load / 15min Half load

145.0 (319.0) 151.5 (333.3) 201.5 (443.3) 246.5 (542.3)

257 x 590 x 700 342 x 690 x 715 342 x 690 x 878 342 x 863 x 905Tower Dimensions

mm W x D x H W/ ISOTR

Shipping Weight kg (lb) W/ ISOTR

123.0 (270.6) 130.0 (286.0) 180.0 (396.0) 225.0 (495.0)Net Weight kg (lb) W/ ISOTR

Operating Temperature 0 - 40 ºC / 32 ~ 104 ºF

Storage Temperature -20 ~ 50 ºC / -4 ~ 122 ºF

Altitude 3000 meters max without derating

Audible Noise

(1 meter from surface)< 55 dBA

Relative Humidity 0 ~ 95% humidity , non-condensing

Safety UL 1778, CE

EMC (EMS / EMI) IEC 61000-4, FCC Part 15, CISPR 22

Warranty 2 years

PHYSICAL

BA TTERY

ENVIRONMENT

CONFORMANCE

Authorized Dealer

ATPMODEL ASP

MODEL

ATP 10 ATP 15 ATP 20 ATP 30 ATP 40 8 12 16 24 32

3Ph+N+G 208 - 220

-15% + 27%50 or 60+/- 10%

≤ 4%0.98

0.83Ph+N+G 120 - 127208 - 220

<3%+/- 2%

3:150 or 60

+/- 0.01%125% 10 min150% 1 min93% Typical

Maintenance-Free Lead Acid BatteriesDeep Discharge Protection With Auto Cut Off

Standard (Automatic and Manual)+/- 204 VDC

10 min24 min

Line, Bypass, Battery, Inverter, Load, Fault IndicationsLoad %, Input and Output Frequency, Voltage and Current, Bypass Voltage,

Battery Voltage and Current, Temperature, Alarms

+/- 10%+/- 6% (configurable)

RS-232 and RS-422 AC Failure, Battery Under Voltage, Bypass Operation, Output Failure

Optional SNMP CardOptional SNMP Card with Modbus

EPO, Generator Interface

-15 to +55 ºC0 to 40 ºC (20 to 25 ºC Recommended For Long Battery Life Time)

0 to 95% (Non Condensing)< 3000 m

IP20< 60dBA at 1 Meter Distance

40 x 78 x 107 52 x 90 x 130 67 x 73 x 153 110 242 260 203 233 428 488 540

EN 62040-1-1 (Safety), EN 62040-2 (EMC), EN 62040-3 (VFI-SS-111)

2 YEARS

UPS model: 6, 8, 10, 12, 15, 20 KVA

September - 2011 September - 2011