uno
DESCRIPTION
MODEL On-Line Uninterruptible Power Systems UPS model: 6, 8, 10, 12, 15, 20 KVA • LCD display front panel • Network surge protection • Emergency Power Off function • On-line technology • Support USB communication • High efficiency mode selectable • Battery remain time display • Pure sine-wave output with less than 3% THD • Input Power Factor Correction • Insolation Transformer Included • Digitized microprocessor controlled • Cold start function (DC power on)TRANSCRIPT
![Page 1: UNO](https://reader031.vdocument.in/reader031/viewer/2022020421/568bf3e11a28ab89339bed1c/html5/thumbnails/1.jpg)
UPS model: 10KVA - 15KVA - 20KVA - 30KVA - 40KVA
Three PhaseOn-Line UPS
• Input Power Factor Correction PFC(0.98)• Extended Input Voltage Range• Rectifier and Inverter with IGBT Technology • 208/120V / 60Hz Models• Digital Signal Processor (DSP) • Expandable battery for longer run times• EPO (Emergency Power Off)• Transformerless design• Low Total Harmonic Distortion Level ( THDi ≤ 4% )• Generator Synchronization• High Efficiency ( up to 95% )
• High Efficiency ( up to 95% ) • Generator Compatible Technology• Special voltage applications other than stated values• Modular Parallel Systems • Static and Manual Bypass Included• Battery Management System (BMS) for longer lifetime of batteries
Optional Accesories- Remote Monitoring Panel &25m Cable For Remote Panel
- UPSMAN (Management Software)
- Multiserver Shutdown Software
- SNMP: Internal Slot Card
- SNMP Adapter with Modbus (external)
- Split bypass - Parallel Kit
ti PFC(0 98) Hi h Effi i
On-LineUninterruptiblePower Systems
Doubleconversion
On-Line UPS
208/120V/60Hz
External Cabinet
<1%
Overload
10 KVA 15 KVA 20 KVA 30 KVA 40 KVA
Authorized Dealer
Output Power (KVA) MODEL Nominal Active Power (KW) INPUT Number of PhasesNominal Voltage (phase-phase) (VAC) Voltage Range (100% load) Nominal Frequency (Hz) Frequency Range Input Current THD Input Power Factor OUTPUT Power FactorNumber of Phases Voltage (phase-neutral) (VAC) Voltage (phase-phase) (VAC) Static Voltage Regulation ( at 100% Linear Load)On line & Battery Mode Dynamic Response to 100% Load StepVoltage THD (at 100% Linear Load)Crest Factor Frequency (Hz) Free Running Frequency (Hz) Efficiency BATTERY Type Battery Protection Battery TestDC VoltageBattery (Standard Internal Batteries)Run Time at Full Load Run Time at half Load DISPLAY LED Display LCD Display STATIC BYPASS Voltage Range for Bypass Operation Frequency Range COMMUNICATIONS Interface ( Communication Ports) Dry Contact SignalsSNMP InterfaceModbus Interface Others ENVIRONMENTAL Storage Temperature Range Operating Temperature Range Relative Humidity Range Altitude Without DeratingCabinet Protection levelAudible Noise
PHYSICAL SPECIFICATIONS
Dimensions W x D x H (cm)Weight w/o Internal Batteries (Kg)Weight with Internal Batteries (Kg)
CERTIFICATIONS
WARRANTY
• LCD display front panel• Network surge protection• Emergency Power Off function• On-line technology• Support USB communication• High efficiency mode selectable• Battery remain time display• Pure sine-wave output with less than 3% THD• Input Power Factor Correction• Insolation Transformer Included• Digitized microprocessor controlled• Cold start function (DC power on)
• Lightning and surge protection• Short Circuit and overload protection• Battery management system (BMS)• Automatic battery charge in UPS when UPS is OFF• Battery replacement warning• Automatic diagnostics & battery check• RS-232 communication port with monitoring software• SNMP card (optional)• Fan speed auto control when load varies• UPSMON plus monitoring software• On line output voltage selected
Tower model (with LCD display) Model: ASP
CAPACITY
OUTPUT
ASP-6000 ASP-8000 ASP-10000 ASP-12000 ASP-15000
Capacity (VA) 6000VA 8000VA 10000VA 12000VA 15000VA
Capacity (W) 4200W 5600W 7000W 8400W
Transfer Time 0 ms
10500W
ASP-20000
20000VA
14000W
Range (0 ~ 100% load)
208V , 220V , 230V , 240V
180 ~ 276V
Voltage / Load
Frequency 50 / 60 Hz Auto Sensing
Voltage (on battery) 120 / 208V , 220V , 230V , 240V +/-2% (Selectable Output Voltage)
Frequency (on battery) 50 / 60 Hz +/-0.5%
PROTECTION AND
FILTERING
SYSTEM
DISPLAY / WARNING
INPUT
Surge Protection IEC61000-4-5 level 3
Overload Protection 125% for 1 minutes and 150% for 10 seconds (On-line)
130% for 10 seconds and 150% for 1.5 seconds (On-battery)
Short Circuit Protection UPS output cut off immediately or input fuse / circuit breaker protection
High Efficiency mode (AC to AC) > 97 %
UPS Design Technology On-Line / digitized microprocessor controlled
Output W ave Form Sinewave
Harmonic distortion < 3% of T.H.D. at linear load
Crest Factor 3 : 1
T
240 VDC
Visual Display (LCD model) Input / output voltage, input / output frequency , on-line mode, back up mode, battery capacity, load level
Audible Alarm (Battery back-up) Beep every 5 sec
UPS Fault Continuous beeping sound and LCD display
Communication RS-232 Serial Port and USB (included ) / SNMP card (optional)
Type Sealed, maintenance-free lead acid batteries
DC Voltage (V) Battery
Input lnlet Hardwire
Receptacles Hardwire
Typical Recharge Time
to 90% Full4 hours
Management Self-test, adjustable battery transfer points and alarm settings
Battery Protection Cut of f without draining any current when battery is low
Cold Start (DC start) YES
Back Up Time (Tower model) About 6 min Full load / 15min Half load
145.0 (319.0) 151.5 (333.3) 201.5 (443.3) 246.5 (542.3)
257 x 590 x 700 342 x 690 x 715 342 x 690 x 878 342 x 863 x 905Tower Dimensions
mm W x D x H W/ ISOTR
Shipping Weight kg (lb) W/ ISOTR
123.0 (270.6) 130.0 (286.0) 180.0 (396.0) 225.0 (495.0)Net Weight kg (lb) W/ ISOTR
Operating Temperature 0 - 40 ºC / 32 ~ 104 ºF
Storage Temperature -20 ~ 50 ºC / -4 ~ 122 ºF
Altitude 3000 meters max without derating
Audible Noise
(1 meter from surface)< 55 dBA
Relative Humidity 0 ~ 95% humidity , non-condensing
Safety UL 1778, CE
EMC (EMS / EMI) IEC 61000-4, FCC Part 15, CISPR 22
Warranty 2 years
PHYSICAL
BA TTERY
ENVIRONMENT
CONFORMANCE
Authorized Dealer
ATPMODEL ASP
MODEL
ATP 10 ATP 15 ATP 20 ATP 30 ATP 40 8 12 16 24 32
3Ph+N+G 208 - 220
-15% + 27%50 or 60+/- 10%
≤ 4%0.98
0.83Ph+N+G 120 - 127208 - 220
<3%+/- 2%
3:150 or 60
+/- 0.01%125% 10 min150% 1 min93% Typical
Maintenance-Free Lead Acid BatteriesDeep Discharge Protection With Auto Cut Off
Standard (Automatic and Manual)+/- 204 VDC
10 min24 min
Line, Bypass, Battery, Inverter, Load, Fault IndicationsLoad %, Input and Output Frequency, Voltage and Current, Bypass Voltage,
Battery Voltage and Current, Temperature, Alarms
+/- 10%+/- 6% (configurable)
RS-232 and RS-422 AC Failure, Battery Under Voltage, Bypass Operation, Output Failure
Optional SNMP CardOptional SNMP Card with Modbus
EPO, Generator Interface
-15 to +55 ºC0 to 40 ºC (20 to 25 ºC Recommended For Long Battery Life Time)
0 to 95% (Non Condensing)< 3000 m
IP20< 60dBA at 1 Meter Distance
40 x 78 x 107 52 x 90 x 130 67 x 73 x 153 110 242 260 203 233 428 488 540
EN 62040-1-1 (Safety), EN 62040-2 (EMC), EN 62040-3 (VFI-SS-111)
2 YEARS
UPS model: 6, 8, 10, 12, 15, 20 KVA
September - 2011 September - 2011
![Page 2: UNO](https://reader031.vdocument.in/reader031/viewer/2022020421/568bf3e11a28ab89339bed1c/html5/thumbnails/2.jpg)
UPS model: 10KVA - 15KVA - 20KVA - 30KVA - 40KVA
Three PhaseOn-Line UPS
• Input Power Factor Correction PFC(0.98)• Extended Input Voltage Range• Rectifier and Inverter with IGBT Technology • 208/120V / 60Hz Models• Digital Signal Processor (DSP) • Expandable battery for longer run times• EPO (Emergency Power Off)• Transformerless design• Low Total Harmonic Distortion Level ( THDi ≤ 4% )• Generator Synchronization• High Efficiency ( up to 95% )
• High Efficiency ( up to 95% ) • Generator Compatible Technology• Special voltage applications other than stated values• Modular Parallel Systems • Static and Manual Bypass Included• Battery Management System (BMS) for longer lifetime of batteries
Optional Accesories- Remote Monitoring Panel &25m Cable For Remote Panel
- UPSMAN (Management Software)
- Multiserver Shutdown Software
- SNMP: Internal Slot Card
- SNMP Adapter with Modbus (external)
- Split bypass - Parallel Kit
ti PFC(0 98) Hi h Effi i
On-LineUninterruptiblePower Systems
Doubleconversion
On-Line UPS
208/120V/60Hz
External Cabinet
<1%
Overload
10 KVA 15 KVA 20 KVA 30 KVA 40 KVA
Authorized Dealer
Output Power (KVA) MODEL Nominal Active Power (KW) INPUT Number of PhasesNominal Voltage (phase-phase) (VAC) Voltage Range (100% load) Nominal Frequency (Hz) Frequency Range Input Current THD Input Power Factor OUTPUT Power FactorNumber of Phases Voltage (phase-neutral) (VAC) Voltage (phase-phase) (VAC) Static Voltage Regulation ( at 100% Linear Load)On line & Battery Mode Dynamic Response to 100% Load StepVoltage THD (at 100% Linear Load)Crest Factor Frequency (Hz) Free Running Frequency (Hz) Efficiency BATTERY Type Battery Protection Battery TestDC VoltageBattery (Standard Internal Batteries)Run Time at Full Load Run Time at half Load DISPLAY LED Display LCD Display STATIC BYPASS Voltage Range for Bypass Operation Frequency Range COMMUNICATIONS Interface ( Communication Ports) Dry Contact SignalsSNMP InterfaceModbus Interface Others ENVIRONMENTAL Storage Temperature Range Operating Temperature Range Relative Humidity Range Altitude Without DeratingCabinet Protection levelAudible Noise
PHYSICAL SPECIFICATIONS
Dimensions W x D x H (cm)Weight w/o Internal Batteries (Kg)Weight with Internal Batteries (Kg)
CERTIFICATIONS
WARRANTY
• LCD display front panel• Network surge protection• Emergency Power Off function• On-line technology• Support USB communication• High efficiency mode selectable• Battery remain time display• Pure sine-wave output with less than 3% THD• Input Power Factor Correction• Insolation Transformer Included• Digitized microprocessor controlled• Cold start function (DC power on)
• Lightning and surge protection• Short Circuit and overload protection• Battery management system (BMS)• Automatic battery charge in UPS when UPS is OFF• Battery replacement warning• Automatic diagnostics & battery check• RS-232 communication port with monitoring software• SNMP card (optional)• Fan speed auto control when load varies• UPSMON plus monitoring software• On line output voltage selected
Tower model (with LCD display) Model: ASP
CAPACITY
OUTPUT
ASP-6000 ASP-8000 ASP-10000 ASP-12000 ASP-15000
Capacity (VA) 6000VA 8000VA 10000VA 12000VA 15000VA
Capacity (W) 4200W 5600W 7000W 8400W
Transfer Time 0 ms
10500W
ASP-20000
20000VA
14000W
Range (0 ~ 100% load)
208V , 220V , 230V , 240V
180 ~ 276V
Voltage / Load
Frequency 50 / 60 Hz Auto Sensing
Voltage (on battery) 120 / 208V , 220V , 230V , 240V +/-2% (Selectable Output Voltage)
Frequency (on battery) 50 / 60 Hz +/-0.5%
PROTECTION AND
FILTERING
SYSTEM
DISPLAY / WARNING
INPUT
Surge Protection IEC61000-4-5 level 3
Overload Protection 125% for 1 minutes and 150% for 10 seconds (On-line)
130% for 10 seconds and 150% for 1.5 seconds (On-battery)
Short Circuit Protection UPS output cut off immediately or input fuse / circuit breaker protection
High Efficiency mode (AC to AC) > 97 %
UPS Design Technology On-Line / digitized microprocessor controlled
Output W ave Form Sinewave
Harmonic distortion < 3% of T.H.D. at linear load
Crest Factor 3 : 1
T
240 VDC
Visual Display (LCD model) Input / output voltage, input / output frequency , on-line mode, back up mode, battery capacity, load level
Audible Alarm (Battery back-up) Beep every 5 sec
UPS Fault Continuous beeping sound and LCD display
Communication RS-232 Serial Port and USB (included ) / SNMP card (optional)
Type Sealed, maintenance-free lead acid batteries
DC Voltage (V) Battery
Input lnlet Hardwire
Receptacles Hardwire
Typical Recharge Time
to 90% Full4 hours
Management Self-test, adjustable battery transfer points and alarm settings
Battery Protection Cut of f without draining any current when battery is low
Cold Start (DC start) YES
Back Up Time (Tower model) About 6 min Full load / 15min Half load
145.0 (319.0) 151.5 (333.3) 201.5 (443.3) 246.5 (542.3)
257 x 590 x 700 342 x 690 x 715 342 x 690 x 878 342 x 863 x 905Tower Dimensions
mm W x D x H W/ ISOTR
Shipping Weight kg (lb) W/ ISOTR
123.0 (270.6) 130.0 (286.0) 180.0 (396.0) 225.0 (495.0)Net Weight kg (lb) W/ ISOTR
Operating Temperature 0 - 40 ºC / 32 ~ 104 ºF
Storage Temperature -20 ~ 50 ºC / -4 ~ 122 ºF
Altitude 3000 meters max without derating
Audible Noise
(1 meter from surface)< 55 dBA
Relative Humidity 0 ~ 95% humidity , non-condensing
Safety UL 1778, CE
EMC (EMS / EMI) IEC 61000-4, FCC Part 15, CISPR 22
Warranty 2 years
PHYSICAL
BA TTERY
ENVIRONMENT
CONFORMANCE
Authorized Dealer
ATPMODEL ASP
MODEL
ATP 10 ATP 15 ATP 20 ATP 30 ATP 40 8 12 16 24 32
3Ph+N+G 208 - 220
-15% + 27%50 or 60+/- 10%
≤ 4%0.98
0.83Ph+N+G 120 - 127208 - 220
<3%+/- 2%
3:150 or 60
+/- 0.01%125% 10 min150% 1 min93% Typical
Maintenance-Free Lead Acid BatteriesDeep Discharge Protection With Auto Cut Off
Standard (Automatic and Manual)+/- 204 VDC
10 min24 min
Line, Bypass, Battery, Inverter, Load, Fault IndicationsLoad %, Input and Output Frequency, Voltage and Current, Bypass Voltage,
Battery Voltage and Current, Temperature, Alarms
+/- 10%+/- 6% (configurable)
RS-232 and RS-422 AC Failure, Battery Under Voltage, Bypass Operation, Output Failure
Optional SNMP CardOptional SNMP Card with Modbus
EPO, Generator Interface
-15 to +55 ºC0 to 40 ºC (20 to 25 ºC Recommended For Long Battery Life Time)
0 to 95% (Non Condensing)< 3000 m
IP20< 60dBA at 1 Meter Distance
40 x 78 x 107 52 x 90 x 130 67 x 73 x 153 110 242 260 203 233 428 488 540
EN 62040-1-1 (Safety), EN 62040-2 (EMC), EN 62040-3 (VFI-SS-111)
2 YEARS
UPS model: 6, 8, 10, 12, 15, 20 KVA
September - 2011 September - 2011