TENANT DESIGN MANUAL
UPDATED DECEMBER 2018
PROJECT OVERVIEW
2
South Hills Village is located at US 19 (Washington Road) and Ft. Couch Road,
in the Bethel Park suburb of Pittsburgh.
PROJECT OVERVIEW
3
Anchored by Macy*s, and Barnes and Noble, South Hills Village features more
than 130 national and specialty retailers, restaurants, a Food Court and the
Carmike 10 Theater.
SITE PLAN
4
5
TENANT INFORMATION PACKAGE
• The Tenant Information Package can be accessed from Simon’s website – simon.com.
» Select the business header, search for the property name, click on the Tenant Info Package link on
the right side of the page.
» If you have any difficulties working with the website, please contact your Tenant Coordinator.
*For questions regarding the Landlord’s design and construction requirements, please
contact your Tenant Coordinator or call 317-636-1600 and ask for Tenant Coordination.
Occupancy/ Use: Mercantile
Construction Classification: Type II B
Building Levels: One (1) Level
Sprinkler System: Fully Sprinkled
MALL BUILDING DATA
6
MUNICIPAL ZONE PLAN –LOWER LEVEL
7
MUNICIPAL ZONE PLAN –UPPER LEVEL
8
STOREFRONT ELEVATIONLOWER LEVEL
9
Typical storefront height is raised to 14’-0” A.F.F (bottom of the 1x located below the mall bulkhead. 2’-0”
projections are allowed on lower level and 1’-6” projections are allowed on upper level in approved areas.
l
14’-0”
sto
refr
ont heig
ht (v
erify
in f
ield
)
l14’-0”
sto
refr
ont heig
ht (v
erify
in f
ield
)
STOREFRONT ELEVATIONUPPER LEVEL (THESE PHOTOS BELOW ARE EXAMPLES OF EXISTING, PER CRITERIA STOREFRONT HEIGHT WILL BE RAISE FOR ALL CONSTRUCTION)
10
Typical storefront height is raised to 14’-0” A.F.F (bottom of the 1x located below the mall bulkhead. 2’-0”
projections are allowed on lower level and 1’-6” projections are allowed on upper level in approved areas.
lMall Bulkhead
1x below the bulkhead
14’-0”
sto
refr
ont heig
ht (v
erify
in f
ield
)
l14’-0”
sto
refr
ont heig
ht (v
erify
in f
ield
)
l
Raise storefront 24” +/- (V.I.F.)
1x below the bulkhead
Mall Bulkhead
l
Raise storefront 24” +/- (V.I.F.)
NEUTRAL PIER DETAIL –FOR PROJECTING STOREFRONT
11
Neutral piers are 3/4” black metal reveals
located on the centerline of the lease lines
between the two storefront. Tenant’s
finishes will extend to the edge of the
metal reveals. Flushed storefronts are also
encouraged and referred to on page 13.
STOREFRONT DETAILS – NEUTRAL PIERS
12
Neutral Pier - All Sections, All Levels (except Food Court): The Neutral Pier condition for the entire Mall is a ¾” reveal
installed at the center line of the demising wall. See the Detail provided in this manual. If the old neutral pier condition
still exists, the Tenant is required to remove it during demolition and install the ¾” reveal. Tenants must extend their
storefront finishes to the edge of this ¾” reveal. If the reveal did not already exist, Tenant’s GC must also finish out the
opposite side of the new reveal to the edge of the adjacent Tenant’s storefront finishes. The Mall Operations Director or
Construction Coordinator will coordinate the finish of this area with the GC on site.
Old neutral pier
condition – all
sections, all levels.
New neutral pier
condition – all
sections, all levels.
NEUTRAL PIER DETAIL- FOR FLUSH STOREFRONTS
13
STOREFRONT SIGNS, AWNINGS &CANOPIES
14
FOOD COURT ELEVATION
15
Neutral Pier
All signs MUST be mounted to a metal sign gridl
11
’-0
” A
.F.F
. (V
eri
fy i
n F
ield
)
Blade Signs required in
food court (Coordinate
with Mall Operations on
blade sign criteria)
HVAC – RETAIL TENANTS
16
This is an enclosed chilled water mall. Tenant’s design team shall accommodate conditions that
may affect the performance of the HVAC system for their store, i.e. zoning for solar gain at the
storefront, sensor location (s) and size and quantity of return air outlets.
• System Landlord supplied chilled water.
• Supply Water Conditions Landlord has provided adequate chilled water for retail occupancies. (EWT is 42 degrees, LWT is 60
degrees minimum). 2 way modulating control valve by Tenant or reuse existing. 10’ WPD maximum for Tenant components.
• Tenant Equipment Tenant shall utilize only Central Station AHU equipment with electric heat (No fan coil units permitted) and 6
row coils. Reuse existing valved connection or new connection by Tenant.
• Condensate Route to Code approved receptacle within space through roof curb.
• HVAC Load Calculation Tenant to submit detailed computer generated load calculation to justify request for chilled water.
• Outside Air Lower level Tenants will connect to Landlord supplied duct. Upper level Tenants will be required to duct the outside
air from the roof through a Tenant supplied gravity ventilator.
• Return Plenum (Ducted return is for odor producing Tenants only and subject to Landlord approval).
• Smoke Exhaust/Relief None required.
• Toilet Exhaust Lower level – Tenant supplied fan (150 CFM max) with duct extension to Landlord duct. Interlock with light
switch. Tenant to provide for any additional exhaust requirements. Upper level - Tenants will be required to vent their toilet
exhaust through the roof.
• Odor, Thermal & Process Equipment Exhaust Size for application by Tenant.
HVAC – RETAIL TENANTS, CONT.
17
• Temperature Controls Tenant shall install Landlord specification (Andover) controller on each AHU. Landlord designated
vendor to install and connect into the system.
• Test & Balance Tenant shall employ a TAB, NEBB or AABC Certified Air Balance Contractor to perform final testing and
balancing.
• See Criteria Sheet MEP-1 for further information.
PLUMBING – RETAIL TENANTS
18
• Water Redistributed by Landlord via overhead mains, ¾” minimum valved connection at pressure available from public system
minus distribution losses. Tenant supplied meter w/remote reader for large water users only.
• Waste 4” wye connection off Landlord main. Designated connection point within or adjacent to space.
• Vent Lower level Tenants connect to Landlord provided vent stubs. Upper level Tenants vent to roof.
• Natural Gas Not available.
• Toilet Rooms As required by code.
• See Criteria Sheet MEP-1 for further information.
FIRE PROTECTION –RETAIL TENANTS
19
• Fire Protection Modify existing system to comply with Code and Landlord insurance requirements.
• Implementation Tenant shall directly employ the Landlord designated contractor.
• Tenant Flow Switch Not permitted.
• Valve for Tenant Space Not permitted.
• See Criteria Sheet MEP-1 for further information.
ELECTRICAL – RETAIL TENANTS
20
• Voltage 277/480V, 3ph, 4-wire
• Wire Color For all wire sizes install wire colors in accordance with the following:
• (A) red, (B) black, (C) blue, and (N) gray/white for circuits @ 120/208 volts single or three phase
• (A) brown, (B) orange, (C) yellow, and (N) gray/white, with one or more colored stripes for circuits @ 277/480 volts single or three phase
• Landlord Equipment Fusible switches, plug in bus duct in central locations and (2) 1” minimum conduits. One 1” conduit and 60
amp fusible switch for lighting, power and water heating. One 1” conduit and 60 amp switch for HVAC equipment.
• Power Provided by redistributed electrical system by Landlord.
• Metering Tenants to utilize existing Landlord check meter or install Landlord specified metering on light and power service.
Reuse existing conduit or install new for code required demand load. Verify with Landlord if exceeding existing fused switch size.
Submit connected and demand electrical load data to support electric service size requested.
• Telephone 3/4” minimum conduit with pull wire to designated connection point in central locations or route cable via service
corridor.
• Fire Alarm Existing Landlord system is Simplex 4100. It has no provision for connection to Tenant required devices.
• See Criteria Sheet MEP-1 for further information.
HVAC –FOOD COURT TENANTS
21
The Food Court utilizes rooftop units. Engineer is required to accommodate conditions that may
affect the performance of the HVAC system for their store.
• Equipment Downflow rooftop unit on full curb with electric or natural gas heat. Split systems are allowed with Landlord approval.
• Condensate Drain Route to Code approved receptacle within space through curb.
• Return Ducted (Plenum return is for non-odor producing Tenants only and subject to Landlord approval).
• Smoke Exhaust/Relief Tenant to provide Code required smoke exhaust fan or reuse existing. Minimum size shall be 1.5 cfm per
square foot of lease space. Tenant space shall remain negative relative to Mall.
• Toilet Exhaust By Tenant including fan, ductwork and roof cap.
• Odor, Thermal & Process Equipment Exhaust Size for application by Tenant.
• Grease Exhaust Per code. Protect roof with “Grease Guard” containment system.
• Replacement Air From Tenant outside air and dedicated makeup air units.
• Temperature Controls Stand-alone digital electric/electronic control system by Tenant.
• Test & Balance Tenant shall employ a TAB, NEBB or AABC Certified Air Balance Contractor to perform final testing and
balancing.
• See Criteria Sheet MEP-1 for further information.
• Water Redistributed by Landlord via overhead mains, 1” minimum valved connection at pressure available from public system
minus distribution losses. Tenant supplied meter w/remote reader.
• Waste 4” wye connection off Landlord main. Designated connection point within or adjacent to space.
• Vent Through roof by Tenant.
• Grease Waste Tenant to install Code compliant grease trap within premise.
• Natural Gas Available at exterior meter banks; subject to utility availability. Meter and piping by Tenant if not existing. Provide
automatic shut off valve.
• Toilet Rooms As required by code.
• See Criteria Sheet MEP-1 for further information.
PLUMBING –FOOD COURT TENANTS
22
• Fire Protection Modify existing system to comply with Code and Landlord insurance requirements.
• Implementation Tenant shall directly employ the Landlord designated contractor.
• Tenant Flow Switch Not permitted.
• Valve for Tenant Space Not permitted.
• See Criteria Sheet MEP-1 for further information.
FIRE PROTECTION –FOOD COURT TENANTS
23
ELECTRICAL –FOOD COURT TENANTS
24
• Voltage 277/480V, 3ph, 4-wire
• Wire Color For all wire sizes install wire colors in accordance with the following:
• (A) red, (B) black, (C) blue, and (N) gray/white for circuits @ 120/208 volts single or three phase
• (A) brown, (B) orange, (C) yellow, and (N) gray/white, with one or more colored stripes for circuits @ 277/480 volts single or three phase
• Landlord Equipment Metering switchboard at central location. 2” minimum conduit.
• Power Provided by redistributed electrical system by Landlord.
• Metering Tenants to utilize existing Landlord check meter or install Landlord specified metering. Reuse existing conduit or install new for code required demand load. Verify with Landlord if exceeding existing main switch size. Submit connected and demandelectrical load data to support electric service size requested.
• Telephone 1” minimum conduit with pull wire to designated connection point in central locations or route cable via service corridor.
• Fire Alarm Landlord system is a Simplex 4100U. Tenant must connect duct detector and hood extinguishing system to Landlord control and monitor modules to activate Tenant smoke fan. Final connection and programming to be by Landlord’s designated vendor.
• See Criteria Sheet MEP-1 for further information.
MEP CALCULATION FORMS
25
Tenant’s Engineer shall use their own forms
to calculate and comply with Landlord’s
MEP design criteria:
Appliance Heat Gain
•Electrical Load Summary
•Kitchen Exhaust Fan Specifications
•Kitchen Make-up Air Unit Specification
•VAV Terminal Specification
•Maintenance