Wise HP33 THREE PHASE HIGH PRECISION AVR SURVO-MOTOR AUTOMATIC VOLTAGE STABILIZER LEN.MAN.STA.111 Rev.4.00/2010

Upload: trandien

Post on 15-Mar-2018

215 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

Wise HP33THREE PHASE HIGH PRECISION AVRSURVO-MOTOR AUTOMATIC VOLTAGE STABILIZER

LEN.MAN.STA.111 Rev.4.00/2010

Page 2: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

CONTENTS

1. SAFETY INSTRUCTIONS 1

2. INTRODUCTION 2

3. FRONT PANEL AND CONNECTION BOARD 3

4. INSTALLATION AND OPERATION 7

5. DATA DISPLAY 10

6. SETTING 12

7. TROUBLESHOOTING 13

Page 3: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

SAFETY INSTRUCTIONS

Please read carefully and follow this LEONICS Wise HP33-series AVR guide.

Important: Please keep this user's guide for reference in order to use the LEONICS AVR properly and safety.

This user's guide contains instructions for installation, operation, display, setting and troubleshooting.

For product safety, please check this product annually by our service qualified personnel or if there are any

symptoms of problems which are not mentioned in this guide or an queries, please contact your Leonics local

distributor, Leonics Service Center, send e-mail to [email protected] or visit www.leonics.com.

For your convenience and quick reference for our service, please fill the

requested information in the blanks below.

Wise HP33-series model : _______________________________________

Serial number : ______________________________________________

Purchased date : ______________________________________________

Purchased from : ______________________________________________

WARNING

Risk of electric shock, DO NOT remove cover. No user serviceable part inside, please

refer servicing to qualified service personnel.

1.1 Electrical safety

1.1.1 Do not work alone where there are electrically hazardous conditions.

1.1.2 Contact with live conductors will cause burns and dangerous electric shock.

1.1.3 Only qualified electricians should install or service this unit, PV panel and batteries.

1.1.4 Properly install and ground ( ) the equipment in accordance with the instruction manual.

1.1.5 To reduce risk from electric shock when you could not check building electric ground system, turn off

the Input breaker of this unit before connecting the loads.

1.1.6 Periodically check your cable, terminal and power source to make sure that they are in good condition.

1.1.7 To reduce risk from electric shock , disconnect all power source before connecting / disconnecting the

loads or when maintaining or servicing this unit.

1.1.8 Use ONLY one hand when connect and disconnect the cable from equipment to equipment in order to

avoid electric shock from touching two surfaces with differential potential.

1.2 Safety instruction for installation and operation

1.2.1 Before installing or using this unit, read all instructions and caution markings on this unit or loads and

all sections of this user guide.

1.2.2 Install this unit in a temperature and humidity controlled indoor area with adequate air flow and away

from chemical particles or flammable substances. Avoid installing the unit near radio transmission

station, heat dissipation equipment and direct sunlight.

1.2.3 This unit has ventilation grills. Ensure that sufficient ventilation is provided. DO NOT block the

ventilation grills. Install this unit at least 20 cm. from the wall to the side of the unit for good ventilation

and at least 30 cm. from the wall to the back of the unit for easy access when maintenance or repair.

1.2.4 Use insulated tools to reduce your risk of electric shock.

1.2.5 Remove all jewelry or other metal objects such as rings, necklace, bracelets and watches when

installing this product.

- 1 -

Page 4: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

1.2.6 Connect the wires to the terminals of this unit as mentioned in the diagram and installation procedure

to prevent the damages.

1.3 Safety instruction for transport

1.3.1 Use forklift truck or stacker for transport this unit.

1.3.2 Keep this unit upright all the time.

1.3.3 Carry with its packaging to avoid damage.

INTRODUCTION

2.1 General

Wise HP33-series AVR is a 3 phase 4 wire automatic voltage regulator or stabilizer which each phase is

controlled independently by servo motor or also called "3 phase 4 wire independent phase control". Wise

HP33-series AVR supplies pure sine wave output with low harmonic distortion. It has LED display and LCD

screen to display operating status and electrical data and audible alarm to alarm when the AVR has faults.

2.2 Features

- 3 phase 4 wire independent phase control

- Pure sine wave output

- Overload and short circuit protection

- Automatic shut down when main electricity supply is abnormal

- Easy installation

- Surge protection

- Display operating status and electrical data via LED display and LCD screen

- Volt meter and Amp meter

- EMI/RFI filter or noise filter (Option)

2.3 Principle

Normal operation mode: Wise HP33-series AVR takes power from main electricity supply. Then, the

current flows to automatic voltage regulator (AVR) circuit to regulate the voltage level. This process is

controlled by servo motor. If the voltage is too high or too low, the AVR circuit will regulate it to the level that

is safe for the loads. Then, flows to EMI/RFI noise filter circuit (option) and check load level at Power watcher to

protect overload. If the AVR is overloaded, it will alarm. You have to disconnect some loads. If the AVR is under

these situations; output over/under voltage, overload, input frequency fault, over temperature (option), and

etc., it will shut itself down and restart automatically when it returns to normal (for automatic restart mode

only).

Maintenance bypass mode: When the AVR is stop and disconnected from main electricity supply for

maintenance, user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR SELECTOR SWITCH to

position "2" (select maintenance bypass mode), the loads will take power directly from main electricity supply.

- 2 -

����� ����������

�� ����

� ����� � �����

� ��� ������

���������

����� ������

�� ���� � ����

������ �

�������

� ��� ������

��������

Page 5: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

Note: There are 2 restart modes (automatic and manual restart). After the AVR shuts down and the restart

mode is manual, once it detects no more faults, it will alarm. You can restart the AVR by pressing

simultaneously once.

- 3 -

FRONT PANEL AND CONNECTION BOARD

3.1 Front panel

�����

�����

�������

�������L1-N

L2-NL2-L3

L3-NL3-L1

L1-L2

�������

������� L1

0

L3

Page 6: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

- 4 -

3.1.1 DISPLAY:

3.1.1.1 AVR ON: The lamp shows that the AVR is operating under AVR mode.

3.1.1.2 ALARM: The lamp shows that the AVR has faults.

3.1.1.3 LCD SCREEN: The screen displays electrical data such as voltage, current, frequency and the

percentage of AVR capacity taken by loads, and etc.

3.1.1.4 CONTROL BUTTONS: The buttons to select display, change setting and control the AVR

operation. There are , , and . See more information in Section DATA

DISPLAY and SETTING.

3.1.1.5 LOAD LEVEL: The lamps show how much power is being taken by the loads in each phase in

percentage.

3.1.1.6 AVR: The lamps show that the AVR is operating under AVR mode. Each lamp represents each

phase.

3.1.1.2

3.1.1.3

3.1.1.4

3.1.1.1

3.1.1.6

3.1.1.7

3.1.1.8

3.1.1.9

3.1.1.5

Page 7: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

- 5 -

3.1.1.7 SURGE PROTECTOR: Each lamp shows the operating status of surge protector system in each

phase.

3.1.1.8 INPUT STATUS: Each lamp shows the status of input voltage in each phase.

3.1.1.9 AVR/BYPASS: The lamps show that the AVR is operating under automatic voltage regulator mode

or maintenance bypass mode (that means the loads are taking the power directly from main

electricity supply).

3.1.2 VOLT METER AND AMP METER:

3.1.2.1 Volt meter

3.1.2.2 Selector switch to select the display of Line-Neutral voltage value of each phase, or Line-Line

voltage value.

3.1.2.3 Amp meter

3.1.2.4 Selector switch to select the display of current value of each phase.

3.1.3 Door

3.2 Connection Board

3.2.1 INPUT BREAKER: The circuit breaker for protecting the AVR from input over current or input short

circuit.

3.2.2 MAINTENANCE BYPASS/AVR SELECTOR SWITCH: The selector switch to select operating mode;

position 0 : no power supply to load

postion 1 : automatic voltage regulator mode

position 2 : maintenance bypass mode .

3.2.3 INPUT terminal (N): The terminal for connecting the neutral cables from main electricity supply to

the AVR.

Note: The L1, L2 and L3 cables of AC Input connect to the INPUT BREAKER poles.

3.2.4 OUTPUT terminal (L1, L2, L3, N): The terminal for connecting the cables from the AVR to the equipment

(or loads) or load panel.

3.2.5 PE: The EARTH terminal or screw for connecting to ground.

3.2.6 RS232-PC: The communication port for connecting computer or transceiver (if any).

3.2.7 SURGE BREAKER: The circuit breaker for protecting the transient voltage surge suppressor and the AVR

from lightning surge damage.

Indicator lamp

AVR ON(green)

ALARM(red)

The AVR is OFF.

The AVR is operatingproperly.

-

There is fault.

The AVR is operating under AVRmode.

The voltage from main electricitysupply is low or there is fault.

OFF BLINK BRIGHT

Status of indicator lamps and AVR operation

Relationship between indicator lamps and AVR operation

Page 8: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

- 6 -

Wise HP33-series AVR (when open the door)

3.2.2

3.2.6

01 2

RS232-PC

INPUT

L1 L2 L3

L1 L2 L3

N

OUTPUT INPUT

N

3.2.7

3.2.4

3.2.3

3.2.5

3.2.1

3.2.5

PE

PE

TransientVoltageSurge

Suppressor

Page 9: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

- 7 -

Rating 3kVA 6kVA 10kVA 15kVA 24kVA 30kVA 40kVA 45kVA 50kVA 60kVA 75kVA 100kVA 125kVA 150kVA

Input wire 2.5 2.5 4 10 16 25 16 x 2 16 x 2 25 x 2 25 x 2 35 x 2 35 x 3 50 x 3 70 x 3

(L1, L2, L3, N) (mm2)

Output wire 2.5 2.5 4 10 16 25 25 35 16 x 2 16 x 2 25 x 2 35 x 2 25 x 3 35 x 3

(L1, L2, L3, N) (mm2)

Earth wire (mm2) 2.5 2.5 2.5 6 16 16 16 25 25 25 25 35 50 50

INSTALLATION AND OPERATION

Caution: The warranty will be voided, if this product has been improper installation, not following the

installation instruction that mentioned in this user's guide.

4.1 Preparation

4.1.1 Before you install the AVR, give it a through visual examination to ensure it has not been subjected to

shipping damage. If it is not in perfect condition, please contact your local distributor or service center

or e-mail to [email protected].

4.1.2 Installation of the AVR must be done by professional technicians only. Before installing or using this

unit, read all instructions, caution markings on the AVR and all connected load, and all sections of this

user guide.

4.1.3 Check the mains input voltage and alll connected load power rating to suit for UPS power rating.

4.1.4 Transportation

4.1.4.1 UPS has been fitted with casters to allow ease of transportation. UPS must be moved vertically.

4.1.4.2 Transport the UPS with its packaging until it arrive the installation location to avoid shipping

damages.

4.1.5 Location

4.1.5.1 Install this unit at least 20 cm. from the wall to the side of the unit for good ventilation and

at least 30 cm. from the wall to the back of the unit for easy access when maintenance or repair.

4.1.5.2 Install at the floor that is capable of supporting the weight of the UPS.

4.1.6 Cable sizing

- For your safety, all cables should be wire in the suitable size conduits.

- The cable sizes in the following table are calculated based on TIS 11-2531 PVC insulated copper

wire, 70˚C conductor temperature, 750 Volts, 40˚C ambient temperature and maximum 3 wires per

conduit.

Note: Maximum cable length must not exceed 5 metres. If in need of cable longer than 5 metres,

properly increase cable size to accommodate excessive length.

Page 10: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

- 8 -

4.2 Installation

01 2

RS232-PC

INPUT

L1 L2 L3

L1 L2 L3

N

OUTPUT INPUT

N

PE

PE

TransientVoltageSurge

Suppressor

COMPUTER(if available)

L1 (R)L2 (S)L3 (T)

N

AC LOADSor

LOAD PANELL1 (R)

N

L2 (S)L3 (T)

AC LINE

Page 11: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

- 9 -

4.2.1 Cut off 3 phase main electricity supply which will connect to the AVR.

4.2.2 Open the AVR door and turn off INPUT BREAKER.

4.2.3 Remove the terminal cover.

4.2.4 Connect grounding cable at the PE terminal or screw of the AVR.

4.2.5 Connect the cable from INPUT TERMINAL (N) to Neutral of the main electricity supply as shown in the

diagram.

4.2.6 Connect the cable from INPUT BREAKER (L1, L2, L3) to L1 (R), L2 (S), L3 (T) of the main electricity supply

as shown in the diagram respectively.

4.2.7 Connect the cable from OUTPUT TERMINAL (N, L1, L2, L3) to N, L1 (R), L2 (S), L3 (T) of the load panel or

loads as shown in the diagram respectively.

Note: The loads connecting to the AVR should not exceed the AVR capacity. It is recommended to

utilize the AVR maximum at 75% of its capacity and spare 25% of its capacity for some loads

that consume high power in some period.

4.2.8 Verify all connections.

4.2.9 Turn on the SURGE BREAKER.

4.2.10 Replace the terminal cover.

4.3 Start up procedure

4.3.1 Turn off all loads that connected to the AVR.

4.3.2 Turn on 3 phase main electricity supply to the AVR. 3 INPUT STATUS lamps at the front panel will lit.

4.3.3 Open the AVR door and turn MAINTENANCE BYPASS/AVR SELECTOR SWITCH to "AVR (position 1)".

4.3.4 Turn on the INPUT BREAKER.

4.3.5 If the AVR restart mode is MANUAL, you will hear the audible alarm. Press simultaneously

once to mute the alarm. Then press simultaneously once to start the AVR. For more details,

please refer to section 5.5 and 7.7.

4.3.6 Turn on the breaker at load panel and turn on the loads.

4.4 Shutdown procedure

4.4.1 Turn off all loads that connected to the AVR.

4.4.2 Open the AVR door.

4.4.3 Turn off the INPUT BREAKER and close the door.

Note: INPUT STATUS lamps at the front panel are still lit due to the AVR still takes power from main

electricity power supply.

4.5 Operation when the AVR has faults (Maintenance bypass)

4.5.1 Turn off all loads that connected to the AVR.

4.5.2 Open the AVR door and turn off the INPUT BREAKER.

4.5.3 Turn MAINTENANCE BYPASS/AVR SELECTOR SWITCH to "MAINTENANCE BYPASS (position 2)".

4.5.4 Turn on the loads. Now, the loads are taking power directly from main electricity supply.

Caution: User must turn off all loads and INPUT BREAKER respectively before selecting the MAINTENANCE

BYPASS/AVR selector switch.

Page 12: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

DATA DISPLAY

You can check electrical data by pressing , , and .

5.1 is to display input electrical data such as input voltage and frequency.

5.2 is to display output electrical data such as output voltage, output frequency and load

percentage.

- 10 -

Press once Shows input voltage of each phase (Line-Neutral).

Press twice Shows input voltage of each phase (Line-Line).

Press 3 times Shows frequency of each phase.

Press 4 times Returns to the first screen.

Press once Shows output voltage of each phase (Line-Neutral).

Press twice Shows output voltage of each phase (Line-Line).

Press 3 times Shows output current of each phase (Line-Neutral).

Press 4 times Shows load percentage of each phase.

Press 5 times Returns to the first screen.

Page 13: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

5.3 is to display nominal phase voltage and output restart mode.

5.4 is to display system status such as operating status.

Note: When you hear the audible alarm, you can press until you notice the fault shown on the LCD.

Press this button until the display returns to the first screen. See more information in section

TROUBLESHOOTING.

5.5 Press two buttons simultaneously

- 11 -

Press to start the AVR (for manual restart mode only) or return to main menu

during setting.

Press to access password input screen.

Press to mute the alarm.

Press once Shows present operating status.

Press once Shows output restart mode.

Press twice Shows nominal phase voltage.

Press 3 times Shows output control mode

Press 4 times Returns to the first screen.

Page 14: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

SETTING

Do not change any setting before allowing from To return to main menu, press simulta-

neously once or wait for 30 seconds.

6.1 Input password to access to setting menu

6.1.1 Press simultaneously once to enter password input screen.

(The password of the following sample is 2468.)

6.1.2 Press twice to input the first digit of the password.

(Refer to the above sample, it is 2.)

6.1.3 Press 4 times to input the second digit of the password.

(Refer to the above sample, it is 4.)

6.1.4 Press 6 times to input the third digit of the password.

(Refer to the above sample, it is 6.)

6.1.5 Press 8 times to input the last digit of the password.

(Refer to the above sample, it is 8.)

6.1.6 Press simultaneously once to confirm password entry.

6.1.7 Now, you reach main setting menu. Press to select setting item.

6.2 System control setting

6.2.1 Press once to enter system control setting screen. This screen

displays the value of the nominal phase voltage of

each Phase-Neutral.

6.2.2 Press once to edit the nominal voltage. The voltage value blinks.

Note: Press or to change the voltage value. Then press to confirm the new setting or

press to cancel the change and return to main menu.

6.2.3 Press once to enter restart mode setting screen.

Note: Press or to change the restart mode. Then press to confirm the new setting or

press to cancel the change and return to main menu.

- 12 -

Page 15: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

TROUBLESHOOTING

If the Wise HP33-series AVR does not operate properly and you cannot solve the problems using this

troubleshooting information in this user's guide, please contact your Leonics local distributor, Leonics Service

Center, send e-mail to [email protected] or visit www.leonics.com.

You can access the screen to view the fault by pressing until you notice the fault shown on the LCD. Press

this button until the display returns to the first screen.

- 13 -

ItemMessage on

the LCD screen

7.1

7.2

7.3

7.4

7.5

7.6

7.7

Causes

The AVR shuts itself down

due to fault.

The output voltage is fault.

The input voltage is fault.

The input frequency is fault.

The voltage of main

electricity supply is low.

There is fault.

The AVR is waiting for restart

command (for manual restart

mode only).

Solutions

Find out the cause and solve. The AVR

will restart automatically when it returns

to normal (for automatic restart mode

only).

Turn off the AVR and check the wiring at

the behind whether it is correct. Turn on

the AVR again. The AVR will restart

automatically when it returns to normal.

Turn off the AVR and check the wiring at

the behind whether it is correct. Turn on

the AVR again. The AVR will restart

automatically when it returns to normal.

Turn off the AVR and check the wiring at

the behind whether it is correct. Turn on

the AVR again. The AVR will restart

automatically when it returns to normal.

The AVR will restart automatically when it

returns to normal.

Contact Leonics local distributors,

Leonics Service Center, send e-mail to

[email protected] or visit

www.leonics.com.

Press simultaneously once.

AVR will restart when it detects no fault.

Page 16: User's Guide Wise HP33 AVR - · PDF fileWise HP33-series AVR is a 3 phase 4 wire automatic ... -Automatic shut down ... user turns off the INPUT BREAKER and turns MAINTENANCE BYPASS/AVR

ItemMessage on

the LCD screen

7.8

(Availble in the AVR with

temperature sensor only.)

7.9

(Availble in the AVR with

temperature sensor only.)

7.10

7.11

7.12

Causes

The internal temperature is

extremely high.

The internal temperature is

higher than the set point.

The AVR is overload.

The AVR is going to shut

down due to overload.

The AVR shuts itself down

due to running overload for

long time.

Solutions

- Check the AVR ventilation whether

anything is blocking.

- Disconnect some loads due to the AVR

is overload.

- Check the AVR ventilation whether

anything is blocking.

- Disconnect some loads due to the AVR

is overload.

Disconnect some loads until the load level

shows less than 100%.

Disconnect some loads until the load level

shows less than 100%.

Disconnect some loads until the load level

shows less than 100% and wait for 11

minutes. The AVR will restart

automatically (for automatic restart

mode) or press

simultaneously once (for manual restart

mode).

- 14 -