IM 05P01C31-11EN page 1/12 Contents 1. Safety Precautions 2. Model and Suffix Codes 3. How to Install 4. Hardware Specifications 5. How to Connect Wires 6. Terminal Wiring Diagrams Introduction Thank you for purchasing the UT55A, UT52A Digital Indicating Controller. This operation guide describes the basic operations related to the single-loop control function of the UT55A and UT52A. The guide should be provided to the end user of this product. Be sure to read this operation guide before using the product in order to ensure correct operation. For details of each function, refer to the electronic manual. Before using the product, refer to the table of Model and Suffix Codes to make sure that the delivered product is consistent with the model and suffix codes you ordered. Also make sure that the following items are included in the package. • Digital Indicating Controller (the model you ordered) ..............................x1 • Set of Brackets ........................................................................................x1 • Terminal Cover........................................................................................x1 • Unit Label (L4502VZ) ..............................................................................x1 • Tag Label (L4502VE) (Only when ordered.) ...........................................x1 • Operation Guide for Single-loop Control (this document) .......................x6 (A3 size) (Installation and Wiring, Initial Settings, Operations, and Parameters) l Target Readers This guide is intended for the following personnel; • Engineers responsible for installation, wiring, and maintenance of the equipment. • Personnel responsible for normal daily operation of the equipment. 1. Safety Precautions The following symbol is used on the instrument. It indicates the possibility of injury to the user or damage to the instrument, and signifies that the user must refer to the operation guide or user’s manual for special instructions. The same symbol is used in the operation guide and user’s manual on pages that the user needs to refer to, together with the term “WARNING” or “CAUTION.” WARNING Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences. CAUTION Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre- cautions that should be taken to prevent such occurrences. AC AC/DC The equipment wholly protected by double insulation or reinforced insulation. Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important information required to operate the instrument. Warning and Disclaimer (1) YOKOGAWA makes no warranties regarding the product except those stated in the WARRANTY that is provided separately. (2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to any person or entity for any loss or damage, direct or indirect, arising from the use of the product or from any unpredictable defect of the product. ■ Safety, Protection, and Modification of the Product (1) In order to protect the system controlled by this product and the product itself, and to ensure safe operation, observe the safety precautions described in the operation guide. Use of the instrument in a manner not prescribed herein may compromise the product's functions and the protection features inherent in the device. We assume no liability for safety, or responsibility for the product's quality, performance or functionality should users fail to observe these instructions when operating the product. (2) Installation of protection and/or safety circuits with respect to a lightning protector; protective equipment for the system controlled by the product and the product itself; foolproof or fail-safe design of a process or line using the system controlled by the product or the product itself; and/or the design and installation of other protective and safety circuits are to be appropriately implemented as the customer deems necessary. (3) Be sure to use the spare parts approved by YOKOGAWA when replacing parts or consumables. (4) This product is not designed or manufactured to be used in critical applications that directly affect or threaten human lives. Such applications include nuclear power equipment, devices using radioactivity, railway facilities, aviation equipment, air navigation facilities, aviation facilities, and medical equipment. If so used, it is the user’s responsibility to include in the system additional equipment and devices that ensure personnel safety. (5) Modification of the product is strictly prohibited. (6) This product is intended to be handled by skilled/trained personnel for electric devices. (7) This product is UL Recognized Component. In order to comply with UL standards, end-products are necessary to be designed by those who have knowledge of the requirements. WARNING l Power Supply Ensure that the instrument’s supply voltage matches the voltage of the power supply before turning ON the power. l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H 2 S, SO X , etc.) for extended periods of time may cause a failure. l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself. l Damage to the Protective Construction Operation of the instrument in a manner not specified in the operation guide may damage its protective construction. CAUTION This instrument is an EMC class A product. In a domestic environ- ment this product may cause radio interference in which case the user needs to take adequate measures. Protection of Environment Waste Electrical and Electronic Equipment (WEEE), Directive This is an explanation of how to dispose of this product based on Waste Electrical and Electronic Equipment (WEEE), Directive. This directive is only valid in the EU. Display language (*3) -1 English (Default. Can be switched to other language by the setting.) -2 German (Default. Can be switched to other language by the setting.) -3 French (Default. Can be switched to other language by the setting.) -4 Spanish (Default. Can be switched to other language by the setting.) Case color 0 White (Light gray) 1 Black (Light charcoal gray) Fixed code -00 Always "-00" (for standard code model) Option codes /DR Additional direct input (TC, 3-wire/4-wire RTD) and current input to Remote (1 additional aux. analog) input, 1 DI to be deleted (*4) /LP 24 V DC loop power supply (*5) /HA Heater break alarm (*6) /DC Power supply 24 V AC/DC /CT Coating (*7) /MDL Mount on DIN rail (without the display parts and keys) (please see the Operation Guide IM 05P01C81-11EN.) *1: When the Type 2 code is “1” or “6”, only “0” can be specified for the Type 3 code. *2: When the /LP option is specified, the RS-485 communication of the Type 2 code “1” or “2” is 2-wire system. *3: English, German, French, and Spanish are available for the guide display. *4: The /DR option can be specified when the Type 2 code is any of “1”, “2”, “4”, “5”, or “7.” *5: The /LP option can be specified in the combination of Type 2 code (any of “0”, “2”, “3”, or “4”) and Type 3 code (any of “0” or “1”). Additionally the /LP option can be specified in the combination of Type 2 code “1” and Type 3 code “0”. *6: The /HA option can be specified only when the Type 1 code is “-0.” *7: When the /CT option is specified, the UT55A does not conform to the safety standards (UL and CSA) and CE marking (Products with /CT option are not intended for EEA-market). ■ UT52A «Standard Code Model» Model Suffix code Option code Description UT52A Digital Indicating Controller (Power supply: 100-240 V AC) (provided with retransmission output or 15 V DC loop power supply, 3 DIs, and 3 DOs) Type 1: Basic control -0 Standard type -1 Position proportional type -2 Heating/cooling type Type 2: Functions 0 None 1 Remote (1 additional aux. analog) input, 1 additional DI, and RS-485 communication (Max. 38.4 kbps, 2-wire) 2 Remote (1 additional aux. analog) input and 1 additional DI 3 2 additional DIs and 2 additional DOs Type 3: Open networks 0 None 3 CC-Link communication (with Modbus master function) (*1) Display language (*2) -1 English (Default. Can be switched to other language by the setting.) -2 German (Default. Can be switched to other language by the setting.) -3 French (Default. Can be switched to other language by the setting.) -4 Spanish (Default. Can be switched to other language by the setting.) Case color 0 White (Light gray) 1 Black (Light charcoal gray) Fixed code -00 Always "-00" (for standard code model) Option codes /DR Additional direct input (TC, 3-wire/4-wire RTD) and current input to Remote (1 additional aux. analog) input, 1 DI to be deleted (*3) /LP 24 V DC loop power supply (*4) /HA Heater break alarm (*5) /DC Power supply 24 V AC/DC /CT Coating (*6) /MDL Mount on DIN rail (without the display parts and keys) (please see the Operation Guide IM 05P01C81-11EN.) *1: The Type 3 code “3” can be specified only when the Type 1 code is “-0” and the Type 2 code is “0.” *2: English, German, French, and Spanish are available for the guide display. *3: The /DR option can be specified only when the Type 2 code is “2” and the Type 3 code is “0.” *4: The /LP option can be specified only when the Type 1 code is “-0” or “-1.” Furthermore both Type 2 and Type 3 codes should be “0.” *5: The /HA option can be specified only when the Type 1 code is “-0” and the Type 3 code is “0.” *6: When the /CT option is specified, the UT52A does not conform to the safety standards (UL and CSA) and CE marking (Products with /CT option are not intended for EEA-market). ■ Customized Product For customized product, the product is identified by the option code of /S# (where ‘#’ is a number). Contact your supplier in case your instrument has option /S#, and you are not in the possession of FX1-[Model code]-S# or IM [Model code]-S# (where [Model code] means, for example, UT55A). Accessories (sold separately) The following is an accessory sold separately. • LL50A Parameter Setting Software Model Suffix code Description LL50A -00 Parameter Setting Software • External Precision Resistor Model Suffix code Description X010 See the General Specifications (*) Resistance Module *: Necessary to input the current signal to the voltage input terminal. • Terminal Cover For UT55A: Model UTAP001; For UT52A: Model UTAP002 • Manuals * Manuals can be downloaded from a website. URL: http://www.yokogawa.com/ns/ut/im/ • Brackets Part number: L4502TP (2 pcs for upper and lower sides) 3. How to Install Installation Location The instrument should be installed in indoor locations meeting the following conditions: • Instrumented panel This instrument is designed to be mounted in an instrumented panel. Mount the instrument in a location where its terminals will not inadvertently be touched. • Well ventilated locations Mount the instrument in well ventilated locations to prevent the instrument’s inter- nal temperature from rising. However, make sure that the terminal portions are not exposed to wind. Exposure to wind may cause the temperature sensor accuracy to deteriorate. To mount mul- tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow. If mounting other instruments adjacent to the instrument, comply with these panel cutout dimensions to provide sufficient clearance between the instru- ments. • Locations with little mechanical vibration Install the instrument in a location subject to little mechanical vibration. • Horizontal location Mount the instrument horizontally and ensure that it is level, with no inclination to the right or left. Front panel of controller Keep this angle within 30° Rear of controller 30° Note If the instrument is moved from a location with low temperature and low humidity to a place with high temperature and high humidity, or if the temperature changes rapidly, condensation will result. Moreover, in the case of thermocouple inputs, measurement errors will result. To avoid such a situation, leave the instrument in the new environment under ambient conditions for more than 1 hour prior to using it. Do not mount the instrument in the following locations: • Outdoors • Locations subject to direct sunlight or close to a heater Install the instrument in a location with stable temperatures that remain close to an average temperature of 23°C. Do not mount it in locations subject to direct sunlight or close to a heater. Doing so adversely affects the instrument. • Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely affects the instrument. Do not mount the instrument in locations subject to any of these substances. • Areas near electromagnetic field generating sources Do not place magnets or tools that generate magnetism near the instrument. If the instrument is used in locations close to a strong electromagnetic field generating source, the magnetic field may cause measurement errors. • Locations where the display is difficult to see The instrument uses an LCD for the display unit, and this can be difficult to see from extremely oblique angles. Mount the instrument in a location where it can be seen as much as possible from the front. • Areas close to flammable articles Absolutely do not place the instrument directly on flam- mable surfaces. If such a circumstance is unavoidable and the instrument must be placed close to a flammable item, provide a shield for it made of 1.43 mm thick plated steel or 1.6 mm thick unplated steel with a space of at least 150 mm between it and the instrument on the top, bottom, and sides. • Areas subject to being splashed with water WARNING Be sure to turn OFF the power supply to the controller before in- stalling it on the panel to avoid an electric shock. www.yokogawa.com/ns YOKOGAWA ELECTRIC CORPORATION Network Solutions Business Division 2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN YOKOGAWA CORPORATION OF AMERICA Head office and for product sales 2 Dart Road, Newnan, Georgia 30265, USA YOKOGAWA EUROPE B.V. Headquarters Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation 150 mm 150 mm 150 mm 150 mm Operation Guide IM 05P01C31-11EN UT55A, UT52A Digital Indicating Controller (Panel Mounting Type) Operation Guide for Single-loop Control This operation guide describes installation, wiring, and other tasks required to make the controller ready for operation. 8th Edition: April 2021 «Standard Code Model» Installation and Wiring For details of the each function, refer to the electronic manual. Manuals can be downloaded or viewed at the following URL. Functional Enhancement http://www.yokogawa.com/ns/ut/im/ Marking This product complies with the WEEE Directive marking requirement. This marking indicates that you must not discard this electrical/electronic product in domestic household waste. Product Category With reference to the equipment types in the WEEE directive, this product is classified as a “Small equipment” product. Do not dispose in domestic household waste. When disposing products in the EU, contact your local Yokogawa office in Europe. 2. Model and Suffix Codes UT55A «Standard Code Model» Model Suffix code Option code Description UT55A Digital Indicating Controller (Power supply: 100-240 V AC) (provided with retransmission output or 15 V DC loop power supply, 3 DIs, and 3 DOs) Type 1: Basic control -0 Standard type -1 Position proportional type -2 Heating/cooling type Type 2: Functions 0 None 1 Remote (1 additional aux. analog) input, 6 additional DIs, 5 additional DOs, and RS-485 communication (Max.19.2 kbps, 2-wire/4-wire) (*1) (*2) 2 Remote (1 additional aux. analog) input, 1 additional DI, and RS-485 communication (Max.19.2 kpbs, 2-wire/4-wire) (*2) 3 5 additional DIs and 5 additional DOs 4 Remote (1 additional aux. analog) input and 1 additional DI 5 Remote (1 additional aux. analog) input, 6 additional DIs, and 5 additional DOs 6 5 additional DIs and 15 additional DOs (*1) 7 3 additional aux. analog inputs and 3 additional DIs Type 3: Open networks 0 None 1 RS-485 communication (Max.38.4 kbps, 2-wire/4-wire) 2 Ethernet communication (with serial gateway function) 3 CC-Link communication (with Modbus master function) 4 PROFIBUS-DP communication (with Modbus master function) 5 DeviceNet communication (with Modbus master function)

Upload: others

Post on 16-Mar-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 1/12

Contents1. Safety Precautions2. ModelandSuffixCodes3. How to Install4. HardwareSpecifications5. HowtoConnectWires6. TerminalWiringDiagrams

IntroductionThankyouforpurchasingtheUT55A,UT52ADigitalIndicatingController.Thisoperationguidedescribesthebasicoperationsrelatedtothesingle-loopcontrolfunctionoftheUT55AandUT52A.Theguideshouldbeprovidedtotheenduserofthisproduct.Besure to read thisoperationguidebeforeusing theproduct inorder toensurecorrect operation.Fordetailsofeachfunction,refertotheelectronicmanual.Beforeusingtheproduct,refertothetableofModelandSuffixCodestomakesurethatthedeliveredproductisconsistentwiththemodelandsuffixcodesyouordered.Alsomakesurethatthefollowingitemsareincludedinthepackage.

•DigitalIndicatingController(themodelyouordered) ..............................x1• Set of Brackets ........................................................................................x1•TerminalCover ........................................................................................x1•UnitLabel(L4502VZ) ..............................................................................x1•TagLabel(L4502VE)(Onlywhenordered.) ...........................................x1•OperationGuideforSingle-loopControl(thisdocument) .......................x6(A3size)(InstallationandWiring,InitialSettings,Operations,andParameters)

lTargetReadersThisguideisintendedforthefollowingpersonnel;• Engineersresponsibleforinstallation,wiring,andmaintenanceoftheequipment.• Personnelresponsiblefornormaldailyoperationoftheequipment.

1. Safety PrecautionsThefollowingsymbol isusedonthe instrument. It indicatesthepossibilityof injurytotheuserordamagetotheinstrument,andsignifiesthattheusermustrefertotheoperationguideoruser’smanualforspecialinstructions.Thesamesymbolisusedintheoperationguideanduser’smanualonpagesthattheuserneedstoreferto,togetherwiththeterm“WARNING”or“CAUTION.”

WARNING

Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences.

CAUTION

Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre-cautions that should be taken to prevent such occurrences.

AC

AC/DC

Theequipmentwhollyprotectedbydoubleinsulationorreinforcedinsulation.

Functionalgroundingterminals (Donotusethisterminalasaprotectivegroundingterminal).

NoteIdentifiesimportantinformationrequiredtooperatetheinstrument.

Warning and Disclaimer(1)YOKOGAWAmakesnowarrantiesregardingtheproductexceptthosestatedin

theWARRANTYthatisprovidedseparately.(2)Theproductisprovidedonan"asis"basis.YOKOGAWAassumesnoliabilityto

anypersonorentity forany lossordamage,director indirect,arisingfromtheuseoftheproductorfromanyunpredictabledefectoftheproduct.

Safety,Protection,andModificationoftheProduct(1) Inorder toprotect thesystemcontrolledbythisproductandtheproduct itself,

andtoensuresafeoperation,observethesafetyprecautionsdescribed in theoperationguide.Useof the instrument inamannernotprescribedhereinmaycompromise the product's functions and the protection features inherent in the device.Weassumenoliabilityforsafety,orresponsibilityfortheproduct'squality,performanceorfunctionalityshouldusersfailtoobservetheseinstructionswhenoperatingtheproduct.

(2) Installationof protectionand/or safety circuitswith respect toa lightningprotector;protectiveequipmentforthesystemcontrolledbytheproductandtheproductitself;foolprooforfail-safedesignofaprocessorlineusingthesystemcontrolledbytheproductortheproductitself;and/orthedesignandinstallationofotherprotectiveandsafetycircuitsaretobeappropriatelyimplementedasthecustomer deems necessary.

(3)BesuretousethesparepartsapprovedbyYOKOGAWAwhenreplacingpartsorconsumables.

(4)Thisproduct isnotdesignedormanufacturedtobeusedincriticalapplicationsthatdirectlyaffector threatenhuman lives.Suchapplications includenuclearpower equipment, devices using radioactivity, railway facilities, aviationequipment,airnavigation facilities,aviation facilities,andmedicalequipment.If soused, it is theuser’s responsibility to include in thesystemadditionalequipmentanddevicesthatensurepersonnelsafety.

(5)Modificationoftheproductisstrictlyprohibited.(6)Thisproductisintendedtobehandledbyskilled/trainedpersonnelforelectricdevices.(7)This product isULRecognizedComponent. In order to complywithUL

standards,end-productsarenecessary tobedesignedby thosewhohaveknowledgeoftherequirements.

WARNING

lPower Supply Ensure that the instrument’s supply voltage matches the voltage

of the power supply before turning ON the power.l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible

or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H2S, SOX, etc.) for extended periods of time may cause a failure.

l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than

YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself.

l Damage to the Protective Construction Operation of the instrument in a manner not specified in the

operation guide may damage its protective construction.

CAUTION

This instrument is an EMC class A product. In a domestic environ-ment this product may cause radio interference in which case the user needs to take adequate measures.

Protection of Environment Waste Electrical and Electronic Equipment (WEEE), Directive

ThisisanexplanationofhowtodisposeofthisproductbasedonWasteElectricalandElectronicEquipment(WEEE),Directive.ThisdirectiveisonlyvalidintheEU.

Displaylanguage(*3)

-1 English(Default.Canbeswitchedtootherlanguagebythesetting.)-2 German(Default.Canbeswitchedtootherlanguagebythesetting.)-3 French(Default.Canbeswitchedtootherlanguagebythesetting.)-4 Spanish(Default.Canbeswitchedtootherlanguagebythesetting.)

Casecolor0 White(Lightgray)1 Black(Lightcharcoalgray)

Fixedcode -00 Always"-00"(forstandardcodemodel)

Optioncodes

/DRAdditionaldirectinput(TC,3-wire/4-wireRTD)andcurrentinputtoRemote(1additionalaux.analog)input, 1DItobedeleted(*4)

/LP 24VDClooppowersupply(*5)/HA Heaterbreakalarm(*6)/DC Powersupply24VAC/DC/CT Coating(*7)

/MDLMountonDINrail(withoutthedisplaypartsandkeys)(pleaseseetheOperationGuideIM05P01C81-11EN.)

*1: WhentheType2codeis“1”or“6”,only“0”canbespecifiedfortheType3code.*2: Whenthe/LPoptionisspecified,theRS-485communicationoftheType2code“1”or“2”is

2-wiresystem.*3: English,German,French,andSpanishareavailablefortheguidedisplay.*4: The/DRoptioncanbespecifiedwhentheType2codeisanyof“1”,“2”,“4”,“5”,or“7.”*5: The/LPoptioncanbespecifiedinthecombinationofType2code(anyof“0”,“2”,“3”,or

“4”)andType3code(anyof“0”or“1”).Additionallythe/LPoptioncanbespecifiedinthecombinationofType2code“1”andType3code“0”.

*6: The/HAoptioncanbespecifiedonlywhentheType1codeis“-0.”*7: Whenthe/CToptionisspecified,theUT55Adoesnotconformtothesafetystandards(UL

andCSA)andCEmarking(Productswith/CToptionarenotintendedforEEA-market).

UT52A«Standard Code Model»Model Suffixcode Option

code Description

UT52ADigitalIndicatingController(Powersupply:100-240VAC)(providedwithretransmissionoutputor15VDClooppowersupply,3DIs,and3DOs)

Type1:Basic control

-0 Standard type-1 Position proportional type-2 Heating/coolingtype

Type2:Functions

0 None

1Remote(1additionalaux.analog)input,1additionalDI,andRS-485communication(Max.38.4kbps,2-wire)

2 Remote(1additionalaux.analog)inputand 1additionalDI

3 2additionalDIsand2additionalDOsType3:Opennetworks

0 None3 CC-Linkcommunication(withModbusmasterfunction)(*1)

Displaylanguage(*2)

-1 English(Default.Canbeswitchedtootherlanguagebythesetting.)-2 German(Default.Canbeswitchedtootherlanguagebythesetting.)-3 French(Default.Canbeswitchedtootherlanguagebythesetting.)-4 Spanish(Default.Canbeswitchedtootherlanguagebythesetting.)

Casecolor0 White(Lightgray)1 Black(Lightcharcoalgray)

Fixedcode -00 Always"-00"(forstandardcodemodel)

Optioncodes

/DRAdditionaldirectinput(TC,3-wire/4-wireRTD)andcurrentinputtoRemote(1additionalaux.analog)input, 1DItobedeleted(*3)

/LP 24VDClooppowersupply(*4)/HA Heaterbreakalarm(*5)/DC Powersupply24VAC/DC/CT Coating(*6)

/MDLMountonDINrail(withoutthedisplaypartsandkeys)(pleaseseetheOperationGuideIM05P01C81-11EN.)

*1: TheType3code“3”canbespecifiedonlywhentheType1codeis“-0”andtheType2codeis“0.”*2: English,German,French,andSpanishareavailablefortheguidedisplay.*3: The/DRoptioncanbespecifiedonlywhentheType2codeis“2”andtheType3codeis“0.”*4: The/LPoptioncanbespecifiedonlywhentheType1codeis“-0”or“-1.”Furthermoreboth

Type2andType3codesshouldbe“0.”*5: The/HAoptioncanbespecifiedonlywhentheType1codeis“-0”andtheType3codeis“0.”*6: Whenthe/CToptionisspecified,theUT52Adoesnotconformtothesafetystandards(UL

andCSA)andCEmarking(Productswith/CToptionarenotintendedforEEA-market).

CustomizedProduct Forcustomizedproduct,theproductisidentifiedbytheoptioncodeof/S#(where‘#’isanumber).

Contactyoursupplier incaseyour instrumenthasoption /S#,andyouarenotin thepossessionofFX1-[Modelcode]-S#or IM[Modelcode]-S#(where[Modelcode]means,forexample,UT55A).

Accessories (sold separately)Thefollowingisanaccessorysoldseparately.• LL50AParameterSettingSoftware

Model Suffixcode DescriptionLL50A -00 ParameterSettingSoftware

• ExternalPrecisionResistorModel Suffixcode Description

X010 SeetheGeneralSpecifications(*) ResistanceModule

*:Necessarytoinputthecurrentsignaltothevoltageinputterminal.• TerminalCover ForUT55A:ModelUTAP001;ForUT52A:ModelUTAP002• Manuals *Manualscanbedownloadedfromawebsite.URL:http://www.yokogawa.com/ns/ut/im/• Brackets Partnumber:L4502TP(2pcsforupperandlowersides)

3. How to Install

Installation LocationThe instrument shouldbe installed in indoor locationsmeeting the followingconditions:• Instrumented panel This instrument isdesignedtobemounted inan instrumentedpanel.Mount theinstrumentinalocationwhereitsterminalswillnotinadvertentlybetouched.

• Well ventilated locations Mounttheinstrumentinwellventilatedlocationstopreventtheinstrument’sinter-naltemperaturefromrising.

However,makesurethattheterminalportionsarenotexposedtowind.Exposureto wind may cause the temperature sensor accuracy to deteriorate. To mount mul-tiple indicatingcontrollers,seetheexternaldimensions/panelcutoutdimensionswhichfollow.Ifmountingotherinstrumentsadjacenttotheinstrument,complywiththesepanelcutoutdimensionstoprovidesufficientclearancebetweentheinstru-ments.

• Locations with little mechanical vibration Installtheinstrumentinalocationsubjecttolittlemechanicalvibration.• Horizontal location Mounttheinstrumenthorizontallyandensurethatitislevel,withnoinclinationtotherightorleft.

Front panelof controller

Keep this anglewithin 30°

Rear ofcontroller

30°

NoteIf the instrument ismoved froma locationwith low temperatureand lowhumiditytoaplacewithhightemperatureandhighhumidity,or if the temperaturechangesrapidly, condensationwill result.Moreover, in thecaseof thermocouple inputs,measurementerrorswillresult.Toavoidsuchasituation,leavetheinstrumentinthenewenvironmentunderambientconditionsformorethan1hourpriortousingit.

Donotmounttheinstrumentinthefollowinglocations:• Outdoors• Locations subject to direct sunlight or close to a heater Installtheinstrumentinalocationwithstabletemperaturesthatremainclosetoanaveragetemperatureof23°C.Donotmountitinlocationssubjecttodirectsunlightorclosetoaheater.Doingsoadverselyaffectstheinstrument.

• Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases

Thepresenceofoily fumes,steam,moisture,dust,orcorrosivegasesadverselyaffectstheinstrument.Donotmounttheinstrumentinlocationssubjecttoanyofthesesubstances.

• Areasnearelectromagneticfieldgeneratingsources Donotplacemagnetsortoolsthatgeneratemagnetismneartheinstrument.Iftheinstrument isusedin locationsclosetoastrongelectromagneticfieldgeneratingsource,themagneticfieldmaycausemeasurementerrors.

• Locationswherethedisplayisdifficulttosee The instrumentusesanLCDfor thedisplayunit,andthiscanbedifficult toseefromextremelyobliqueangles.Mounttheinstrumentinalocationwhereitcanbeseenasmuchaspossiblefromthefront.

• Areasclosetoflammablearticles Absolutelydonotplacetheinstrumentdirectlyonflam-mablesurfaces. Ifsuchacircumstance isunavoidableandtheinstrumentmustbeplacedclosetoaflammableitem,provideashieldforitmadeof1.43mmthickplatedsteel or 1.6 mm thick unplated steel with a space of at least150mmbetweenitandtheinstrumentonthetop,bottom,andsides.

• Areas subject to being splashed with water

WARNING

Be sure to turn OFF the power supply to the controller before in-stalling it on the panel to avoid an electric shock.

www.yokogawa.com/ns

YOKOGAWA ELECTRIC CORPORATIONNetwork Solutions Business Division

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPANYOKOGAWA CORPORATION OF AMERICA

Head office and for product sales2 Dart Road, Newnan, Georgia 30265, USA

YOKOGAWA EUROPE B.V.Headquarters

Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS

All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation

150 mm150 mm

150 mm

150 mm

OperationGuideIM 05P01C31-11EN

UT55A, UT52ADigital Indicating Controller (Panel Mounting Type)Operation Guide for Single-loop Control

This operation guide describes installation, wiring, and other tasks required to make the controller ready for operation.

8th Edition: April 2021«Standard Code Model»

Installation and Wiring

For details of the each function, refer to the electronic manual. Manuals can be downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

MarkingThis product complieswith theWEEEDirectivemarkingrequirement.Thismarkingindicatesthatyoumustnotdiscardthiselectrical/electronicproductindomestichouseholdwaste.

ProductCategoryWithreferencetotheequipmenttypesintheWEEEdirective,thisproductisclassifiedasa“Smallequipment”product.Donot dispose in domestic householdwaste.WhendisposingproductsintheEU,contactyourlocalYokogawaofficeinEurope.

2. ModelandSuffixCodes UT55A «Standard Code Model»

Model Suffixcode Option code Description

UT55ADigitalIndicatingController(Powersupply:100-240VAC)(providedwithretransmissionoutputor15VDClooppowersupply,3DIs,and3DOs)

Type1:Basic control

-0 Standard type-1 Position proportional type-2 Heating/coolingtype

Type2:Functions

0 None

1Remote(1additionalaux.analog)input,6additionalDIs,5additionalDOs,andRS-485communication(Max.19.2kbps,2-wire/4-wire)(*1)(*2)

2Remote(1additionalaux.analog)input, 1additionalDI,andRS-485communication(Max.19.2kpbs,2-wire/4-wire)(*2)

3 5additionalDIsand5additionalDOs4 Remote(1additionalaux.analog)inputand1additionalDI

5 Remote(1additionalaux.analog)input,6additionalDIs,and5additionalDOs

6 5additionalDIsand15additionalDOs(*1)7 3additionalaux.analoginputsand3additionalDIs

Type3:Opennetworks

0 None1 RS-485communication(Max.38.4kbps,2-wire/4-wire)2 Ethernetcommunication(withserialgatewayfunction)3 CC-Linkcommunication(withModbusmasterfunction)4 PROFIBUS-DPcommunication(withModbusmasterfunction)5 DeviceNetcommunication(withModbusmasterfunction)

Page 2: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 2/12

Mounting the Instrument Main UnitProvideaninstrumentedpanelsteelsheetof1to10mmthickness.Afteropeningthemountingholeonthepanel,followtheproceduresbelowtoinstallthecontroller:1) Insert thecontroller into theopening from the frontof thepanelso that the

terminalboardontherearisatthefarside.2) Setthebrackets inplaceonthetopandbottomof thecontrollerasshowninthefigure

below,thentightenthescrewsofthebrackets.Takecarenottoovertightenthem.

Bracket(top mounting hardware)

Terminal board

Bracket(bottom mounting hardware)

Panel

Insert a screwdriver into thebrackets to tighten the screws.

Direction to insert thecontroller

Appropriatetightening torque:0.25 N•m

Insert the controllerinto the opening atthe front of the panel.

CAUTION

• Tighten the screws with appropriate tightening torque within 0.25 N•m. Otherwise it may cause the case deformation or the bracket damage.

• Make sure that foreign materials do not enter the inside of the instrument through the case’s slit holes.

External Dimensions and Panel Cutout Dimensions

(25)

(53) (2.09)

[(N-1)×96+92]117 (4.61) min.

145 (5.71)min.

+0.80

+0.8092

“N” stands for the number of controllers to beinstalled.However, the measured value applies if N≥5.

65 (2.56)

20 (0.79)

11(0.43)

UT55A

1 to 10 mm (0.04 to 0.39 inch) (panel thickness)Bracket

Bracket

94.6

(3.7

2)

91.6

(3.6

1)

105.

2 (4

.14)

Unit: mm (approx. inch)96 (3.78)

96 (3

.78)

• General mounting • Side-by-side close mounting

Terminal cover

Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2

+0.8092

+0.030(3.62 )

(0.98)+0.030(3.62 )

+0.8092

+0.030(3.62 )

([(N-1)×3.78+3.62] )+0.030

[(N-1)×48+45] +0.60

65 (2.56)48 (1.89) 11 (0.43)UT52A

1 to 10 mm (0.04 to 0.39 inch) (panel thickness)

Bracket

Bracket Terminal cover

94.6

(3.7

2)

96 (3

.78)

105.

2 (4

.14)

Unit: mm (approx. inch)

70 (2.76)min.

(25)

145 (5.71)min.

+0.6045

(53) (2.09)

+0.8092

• General mounting • Side-by-side close mounting

20 (0.79)

91.6

(3.6

1)

“N” stands for the number of controllers to beinstalled.However, the measured value applies if N≥5.

Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2

+0.030(3.62 )

+0.020(1.77 ) (0.98)

+0.8092

+0.030(3.62 )

([(N-1)×1.89+1.77] )+0.020

4. HardwareSpecifications

WARNING

This instrument is for Measurement Category No.1.Do not use it for measurements in locations falling under Measure-ment Categories No.2, No.3, and No.4.

Internal Wiring

Outlet

Entrance IVCable

III TO( I )

II

Category IEC/EN/CSA/UL 61010-1 EN 61010-2-030 Remarks

No.1 Measurement CategoryI O(Other) For measurements performed on circuits not direct-

lyconnectedtoMAINS.

No.2 Measurement CategoryII

Measurement CategoryII

For measurements performed on circuits directly connectedtothelow-voltageinstallation.

No.3 Measurement CategoryIII

Measurement CategoryIII

Formeasurementsperformedinthebuildinginstal-lation.

No.4 Measurement CategoryIV

Measurement CategoryIV

For measurements performed at the source of the low-voltageinstallation.

InputSpecificationsUniversalInput(Equippedasstandard)• Numberofinputs:1• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow,

Input Type Instrument Range

AccuracyºC ºF

Thermo-couple

K-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor

0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±2%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleK±1%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleT

-270.0to1000.0ºC -450.0to2300.0ºF-200.0to500.0ºC -200.0to1000.0ºF

J -200.0to1200.0ºC -300.0to2300.0ºF

T-270.0to400.0ºC -450.0to750.0ºF

0.0to400.0ºC -200.0to750.0ºF

B 0.0to1800.0ºC 32to3300ºF

±0.15%ofinstrumentrange±1digitfor400°Cormore ±5%ofinstrumentrange±1digitforlessthan400°C

S 0.0to1700.0ºC 32to3100ºF±0.15%ofinstrumentrange±1digit

R 0.0to1700.0ºC 32to3100ºF

N -200.0to1300.0ºC -300.0to2400.0ºF±0.1%ofinstrumentrange±1digit±0.25%ofinstrumentrange±1digitforlessthan0°C

E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±1.5%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleE.

L -200.0to900.0ºC -300.0to1600.0ºF

U-200.0to400.0ºC -300.0to750.0ºF

0.0to400.0ºC -200.0to1000.0ºF

W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit(Note2)

Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit

PR20-40 0.0to1900.0ºC 32to3400ºF

±0.5%ofinstrumentrange±1digitfor800°Cormore Accuracyisnotguaranteedforlessthan800°C.

W97Re3-W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit

RTD

JPt100-200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit

(Note1)-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit

Pt100-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit

(Note1)-200.0to500.0ºC -300.0to1000.0ºF-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit

Standardsignal0.400to2.000V

±0.1%ofinstrumentrange±1digit

1.000to5.000V4.00to20.00mA

DCvoltage/current

0.000to2.000V0.00to10.00V0.00to20.00mA-10.00to20.00mV0.0to100.0mV

Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz.Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherangebetween

-100and200°C.Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988•Inputsampling(control)period:Selectfrom50,100,and200ms•Burnoutdetection: FunctionsatTC,RTD,andstandardsignal. Upscale,downscale,andoffcanbespecified. Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4mA

or less.•Inputbiascurrent:0.05µA(forTCorRTD)•Measuredcurrent(RTD):About0.16mA•Inputresistance: TCormVinput:1MΩormore Vinput:About1MΩ mAinput:About250Ω•Allowablesignalsourceresistance: TCormVinput:250Ωorless Effectsofsignalsourceresistance:0.1µV/Ωorless DCvoltageinput:2kΩorless Effectsofsignalsourceresistance:About0.01%/100Ω

• Allowablewiringresistance: RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewiresshallbeequal.)

Wiringresistanceeffect:±0.1ºC/10Ω• Allowableinputvoltage/current: TC,mV,mAandRTDinput:±10VDC Vinput:±20VDC mAinput:±40mA• Noiserejectionratio: Normalmode:40dBormore(at50/60Hz) Commonmode:120dBormore(at50/60Hz) For100-240VAC,thepowerfrequencycanbesetmanually.Automaticdetectionisalsoavailable.

For24VAC/DC,thepowerfrequencycanbesetmanually.• Referencejunctioncompensationerror: ±1.0ºC(15to35ºC) ±1.5ºC(-10to15ºCand35to50ºC)• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD

AuxiliaryAnalogInput• Use:Remotesetpointsetting,externalcompensatinginput,auxiliaryinputforcom-putation,etc.

• Numberofinputs:SeethetableofModelandSuffixCodes.• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow.

Input Type Instrument Range Accuracy

Standardsignal0.400to2.000V ±0.2%ofinstrumentrange±1digit1.000to5.000V ±0.1%ofinstrumentrange±1digit

DCvoltage0.000to2.000V ±0.2%ofinstrumentrange±1digit0.00to10.00V ±0.1%ofinstrumentrange±1digit

DCvoltageforhigh-inputimpedance

0.000to1.250V ±0.1%ofinstrumentrange±1digit

• Inputsampling(control)period:Sameasuniversalinput• Inputresistance:About1MΩ However,10MΩormoreforDCvoltageforhigh-inputimpedancerange•Burnoutdetection:Functionsatstandardsignal Burnoutisdeterminedtohaveoccurredifitis0.1Vorless.

RemoteInputwithDirectInput• Numberofinputs:SeethetableofModelandSuffixCodes.• Inputtype,instrumentrange,andmeasurementaccuracy:Sameasuniversalinputexceptthetablebelow.

Input Type Instrument Range

Accuracy°C °F

4-wireRTD

JPt100-200.0to500.0°C -300.0to1000.0°F ±0.5°C±1digit-150.00to150.00°C -200.0to300.0°F ±0.2°C±1digit

Pt100-200.0to850.0°C -300.0to1560.0°F ±0.1%ofinstrumentrange±1

digit(Note1)-200.0to500.0°C -300.0to1000.0°F ±0.5°C±1digit-150.00to150.00°C -200.0to300.0°F ±0.2°C±1digit

Note1: ±0.5°C±1digitintherangebetween-200.0and500.0°C/-300.0and1000.0°F.

• Inputsampling(control)period:Sameasuniversalinput•Burnoutdetection:Sameasuniversalinput

ContactInputSpecifications• Numberofinputs:SeethetableofModelandSuffixCodes.• Inputtype:No-voltagecontactinputortransistorcontactinput• Inputcontactrating:12VDC,10mAormore Useacontactwithaminimumon-currentof1mAorless.• ON/OFFdetection: No-voltagecontactinput: Contactresistanceof1kΩorlessisdeterminedas“ON”andcontactresistance

of50kΩormoreas“OFF.” Transistorcontactinput: Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmustnot

exceed100µAwhen“OFF.”• Minimumstatusdetectionholdtime:Controlperiod+50ms• Use:SPswitch,operationmodeswitch,andeventinput

AnalogOutputSpecifications• Numberofoutputs: Controloutput:1 Cooling-sidecontroloutputofHeating/coolingtype:1• Outputtype:Currentoutputorvoltagepulseoutput• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless) Theaccuracy is that in thestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz.

• Voltagepulseoutput: Use:Timeproportionaloutput On-voltage:12Vormore/loadresistanceof600Ωormore Off-voltage:0.1VDCorless Timeresolution:10msor0.1%ofoutput,whicheverislarger

RetransmissionOutputSpecifications• Numberofoutputs:Retransmissionoutput;1,sharedwith15VDC looppower

supply• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy(conversionaccuracyfromPVdisplayonthesetscale):±0.1%ofspan(±5%ofspanfor1mAorless)

Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH, andpowerfrequencyat50/60Hz. This isnotconversionaccuracythroughinputandoutputbut theperformanceof

transmission output itself.

15VDCLoopPowerSupplySpecifications(Sharedwithretransmissionoutput)• Powersupply:14.5to18.0VDC• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)

StepResponseTimeSpecificationsWithin500ms(whenthecontrolperiodis50msor100ms)Within1s(whenthecontrolperiodis200ms)(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspanisapplied)

RelayContactOutputSpecifications• Contacttypeandnumberofoutputs: Controloutput:contactpoint1c;1point Cooling-sidecontroloutputofHeating/cooling type:contactpoint1c;1point(forUT55Aonly)

ForUT52A,contactpoint1a;2pointsforbothheatingandcoolingsides Alarmoutput:contactpoint1a;3points(commonisindependent)• Contactrating: Contactpoint1c(controloutput):250VAC,3Aor30VDC,3A(resistanceload) Contactpoint1a(controloutput):240VAC,3Aor30VDC,3A(resistanceload)(forUT52Aonly)

Contactpoint1a(alarmoutput):240VAC,1Aor30VDC,1A(resistanceload)• Use:Timeproportionaloutput,alarmoutput,FAILoutput,etc.• Timeresolutionofcontroloutput:10msor0.1%ofoutput,whicheverislargerNote:Thecontroloutputshouldalwaysbeusedwithaloadof10mAormore. Thealarmoutputshouldalwaysbeusedwithaloadof1mAormore.

PositionProportionalOutputSpecifications• Positionsignalinput: Slideresistance:100Ωto2.5kΩoftotalresistance 100%sideandslideline:withdisconnectiondetection 0%side:withoutdisconnectiondetection Currentinput:4to20mA(withdisconnectiondetection)• Samplingperiod:50ms• Measurementresolution:0.1%ofinputspan• Positionproportionalrelayoutput: UT55A:contactpoint1a;2points,250VAC,3Aor30VDC,3A(resistanceload) UT52A:contactpoint1a;2points,240VAC,3Aor30VDC,3A(resistanceload)Note:Thisshouldalwaysbeusedwithaloadof10mAormore.

TransistorContactOutputSpecifications• Numberofoutputs:SeethetableofModelandSuffixCodes.• Outputtype:Opencollector(SINKcurrent)• Outputcontactrating:Max.24VDC,50mA• Outputtimeresolution:Min.50ms• Use:Alarmoutput,FAILoutput,etc.

HeaterBreakAlarmSpecifications• Numberofinputs:2• Numberofoutputs:2(transistorcontactoutput)• Use:Measurestheheatercurrentusinganexternalcurrenttransformer(CT)andgeneratesaheaterbreakalarmwhenthemeasuredvalueis lessthanthebreakdetectionvalue.

• Currenttransformerinputresistance:About9.4Ω• Currenttransformerinputrange:0.0to0.1Arms(0.12Armsormorecannotbeapplied.)• Heatercurrentsettingrange:OFF,0.1to300.0Arms Heatercurrentmeasuredvaluedisplayrange:0.0to360.0Arms Note:TheCTratiocanbeset.CTratiosettingrange:1to3300• RecommendedCT:CTfromU.R.D.,Ltd. CTL-6-S-H:CTratio800,measurablecurrentrange:0.1to80.0Arms CTL-12L-30:CTratio3000,measurablecurrentrange:0.1to180.0Arms• Heatercurrentmeasurementperiod:200ms• Heatercurrentmeasurementaccuracy:±5%ofcurrent transformer input rangespan±1digit(CTerrorisnotincluded.)

• Heatercurrentdetectionresolution:Within1/250ofcurrenttransformerinputrangespan• BreakdetectionOn-time:Min.0.2second(fortimeproportionaloutput)

24VDCLoopPowerSupplySpecifications• Use:Powerissuppliedtoa2-wiretransmitter.• Powersupply:21.6to28.0VDC• Ratedcurrent:4to20mADC• Maximumsupplycurrent:About30mA(withshort-circuitcurrentlimitingcircuit.)

SafetyandEMCStandards• Safety: CompliantwithIEC/EN61010-1(CE),IEC/EN61010-2-201(CE),IEC/EN61010-2-030(CE),approvedbyCAN/CSAC22.2No.61010-1(CSA),approvedbyUL61010-1.

Installationcategory:II Pollutiondegree:2 Measurementcategory:I(CATI)(UL,CSA) O(Other)(CE) Ratedmeasurementinputvoltage:Max.10VDC Ratedtransientovervoltage:1500V(*) *ThisisareferencesafetystandardvalueformeasurementcategoryIofCSA/UL61010-

1,andformeasurementcategoryOofIEC/EN61010-2-030.Thisvalueisnotnecessarilyaguaranteeofinstrumentperformance.

• EMCstandards: CompliantwithCEmarking EN61326-1ClassA,Table2(Foruseinindustriallocations), EN61326-2-3 *Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%ofthe

rangeduringtesting. EN55011ClassA,Group1 EN61000-3-2ClassA

Page 3: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 3/12

EN61000-3-3 EMCRegulatoryArrangementinAustraliaandNewZealand(forallmodelinclud-

ingLL50A) EN55011ClassA,Group1• KCmarking: Electromagneticwave interferencepreventionstandard,electromagneticwave

protection standard compliance

Construction,Installation,andWiring• Dust-proofanddrip-proof: IP66(for frontpanel) (Notavailable forside-by-sideclosemounting.)

• Material:Polycarbonate(Flameretardancy:UL94V-0)• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)• Weight:0.5kgorless• Externaldimensions(mm): UT55A:96(W)×96(H)×65(depthfromthepanelface) UT52A:48(W)×96(H)×65(depthfromthepanelface) (Depthexcepttheprojectionontherearpanel)• Installation:Directpanelmounting;mountingbracket,oneeach forupperandlowermounting

• Panelcutoutdimensions(mm): UT55A:92+0.8/0(W)×92+0.8/0(H),UT52A:45+0.6/0(W)×92+0.8/0(H)• Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)

PowerSupplySpecificationsandIsolation• Powersupply: Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz

24VAC/DC(+10%/-15%)(for/DCoption)• Powerconsumption:UT55A:18VA(DC:9VA,AC:14VAif/DCoptionisspecified)

UT52A:15VA(DC:7VA,AC:11VAif/DCoptionisspecified)• Databackup:Nonvolatilememory• Powerholduptime:20ms(for100VACdrive)• Withstandingvoltage Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute(UL,CSA) Betweenprimaryterminalsandsecondaryterminals:3000VACfor1minute(CE) Betweenprimaryterminals:1500VACfor1minute Betweensecondaryterminals:500VACfor1minute (Primary terminals:Power*and relayoutput terminals;Secondary terminals:

Analog I/Osignal terminals,contact input terminals,communication terminalsandfunctionalgroundingterminals.)

*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.• Insulationresistance:Betweenpowersupplyterminalsandagroundingterminal20MΩormoreat500VDC

• IsolationspecificationsPV (universal ) input terminals

Remote (universal) input terminals with direct input / Remote input terminals

Aux. analog (AIN2) input terminals

Control relay (contact point c / contact point a) output terminals

Alarm-1 relay (contact point a) output terminals

Alarm-2 relay (contact point a) output terminals

Alarm-3 relay (contact point a) output terminals

Position proportional relay output terminals

Contact input terminals (all)RS-485 communication terminals (2 ports)

24 V DC loop power supply terminals

Contact output (transistor) terminals

Ethernet communication terminal

PROFIBUS-DP/DeviceNet/CC-Link communication terminals

Current transformer input terminals

Control, retransmission (analog) output terminals(not isolated between the analog output terminals)Valve position (feedback) input terminals

Internal

circuits

Power

supply

The circuits divided by lines are insulated mutually.

Aux. analog (AIN4) input terminals

EnvironmentalConditionsNormal Operating Conditions:• Ambienttemperature:-10to50°C(side-by-sidemounting:-10to40°C) If theCC-Linkoption isspecified,0 to50°CforUT55A,0 to40°CforUT52A.(side-by-sidemounting:0to40°CforUT55AandUT52AwithCC-Linkoption)

• Ambienthumidity:20to90%RH(nocondensationallowed)• Magneticfield:400A/morless• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90minuteseachinthethreeaxisdirections

Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseachinthethreeaxisdirections

• Short-periodvibration:14.7m/s2,15secondsorless• Shock:98m/s2orless,11ms• Altitude:2000morlessabovesealevel• Warm-uptime:30minutesormoreafterthepoweristurnedon• Startuptime:Within10seconds*:TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.TheLCDhasa

characteristicthatthedisplayactionbecomeslateatthelowtemperature.However,thecontrol fuction is not affected.

Transportation and Storage Conditions:• Temperature:-25to70ºC• Temperaturechangerate:20ºC/horless• Humidity:5to95%RH(nocondensationallowed)

EffectsofOperatingConditions• Effectofambienttemperature: VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger Currentinput:±0.01%ofF.S./ºC RTDinput:±0.05ºC/ºC(ambienttemperature)orless Analogoutput:±0.02%ofF.S./ºCorless• Effectofpowersupplyvoltagefluctuation Analoginput:±0.05%ofF.S.orless Analogoutput:±0.05%ofF.S.orless (Eachwithinratedvoltagerange)

5. How to Connect Wires

WARNING

• Wiring work must be carried out by a person with basic electrical knowledge and practical experience.

• Be sure to turn OFF the power supply to the controller before wiring to avoid an electric shock. Use a tester or similar device to ensure that no power is being supplied to a cable to be connected.

• For the wiring cable, the temperature rating is 75 °C or more.• As a safety measure, always install a circuit breaker (an IEC

60947-compatible product, 5 A, 100 V or 220 V AC) in an easily accessible location near the instrument. Moreover, provide indication that the switch is a device for turning off the power to the instrument.

• Install the power cable keeping a distance of more than 1 cm from other signal wires.

• The power cable is required to meet the IEC standards concerned or the requirements of the area in which the instrument is being installed.

• Wiring should be installed to conform to NEC (National Electrical Code: ANSI/NFPA-70) or the wiring construction standards in countries or regions where wiring will be installed.

• Since the insulation provided to each relay output terminal is Functional insulation, provide Reinforced insulation to the external of the device as necessary. (Refer to the drawing below.)

This product

Functional insulation

A safety voltage circuit

A safety voltage circuit

This product

Reinforced insulation

Reinforced insulation

Functional insulation

A hazardous voltage circuit

A hazardous voltage circuit

A safety voltage circuit

A safety voltage circuit

This product

Reinforced insulation

Reinforced insulation

Functional insulation

A hazardous voltage circuit

A hazardous voltage circuit

A hazardous voltage circuit

A hazardous voltage circuit

CAUTION

• When connecting two or more crimp-on terminal lugs to the single terminal block, bend the crimp-on terminal lugs before tightening the screw.

• Note that the wiring of two or more crimp-on terminal lugs to the single high-voltage terminal of the power supply and relay, etc. does not comply with the safety standard.

CAUTION

• Provide electricity from a single-phase power supply. If the power is noisy, install an isolation transformer on the primary side, and use a line filter on the secondary side. When measures against noise are taken, do not install the primary and secondary power cables close to each other.

• If there is a risk of external lightning surges, use a lightning arrester etc.• For TC input, use shielded compensating lead wires for wiring.

For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires.

• Since the control output relay has a life span (resistance load of 100,000 times), use the auxiliary relay to perform ON/OFF control.

• The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.

• After completing the wiring, the terminal cover is recommended to use for the instrument.

RecommendedCrimp-onTerminalLugs

(A)

(F)

(ød)

5.5 3.3

Recommendedtighteningtorque:0.6N·m Applicablewiresize:Powersupplywiring1.25mm2 or moreApplicable terminal lug Applicable wire size mm2 (AWG#) (φd) (A) (F)M3 0.25to1.65(22to16) 3.3 5.5 4.2

CableSpecificationsandRecommendedCablesPurpose Name and Manufacturer

Powersupply,relaycontactoutputs 600VGradeheat-resistantPVCinsulatedwires,JISC3317(HIV),0.9to2.0mm2

Thermocouple Shieldedcompensatingleadwires,JISC1610Forthermocoupleinput(PVinputandremoteinputwithdirectinput),shieldedcompensatingleadwireofcross-sectionalarealessthanorequalto0.75mm2isrecommended.Ifthecross-sectionalareaiswide,thereferencejunctioncompensationerrormaybelarge.

RTD Shieldedwires(three/fourconductors),UL2482(HitachiCable)Othersignals(otherthancontactinput/output) Shielded wiresOthersignals(contactinput/output) UnshieldedwiresRS-485communication Shielded wiresEthernetcommunication 100BASE-TX(CAT-5)/10BASE-TPROFIBUS-DPcommunication DedicatedcableforPROFIBUS-DP(Shieldedtwo-wires)DeviceNetcommunication DedicatedcableforDeviceNet(Shieldedfive-wires)CC-Linkcommunication DedicatedcableforCC-Link(Shieldedthree-wires)

Wiring direction

E4-terminal area

E3-terminal area E2-terminal area

PV RET

OUT

DI

HBAVALV

ALM

OUT

OUT2

OUT2

E1-terminal area

Retransmission output

4-20 mA DC or0-20 mA DC

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

+

-

+

-

Default: 4-20 mA DC

Default: PV retransmission

Load resistance 600 Ω or less

Retransmission output

Current/voltage pulse output

0-20 mA DC,4-20 mA DC,Voltage pulse (12 V)

+

Retransmission output

+

-

Default: 4-20 mA DC

Default: Undefined

0-20 mA DC,4-20 mA DC

Control output

PV inputTC input RTD input

Voltage (mV, V) input

A

+

-

+

-

Current (mA) input

+

-

B

b

(Suffix code: Type1=-1) (Suffix code: Type 1=-2)

(Suffix code: Type1=-0, -1 or -2)

(Suffix code: Type1=-0 or -2)

(Option code /HA)

(24 V AC/DC power supply: Option code /DC)

(Equipped as standard)(Equippedas standard)

(Equipped as standard)

(Equipped as standard)

Power supply

Heater break alarm

Heater current detection input

CT1

CT2

COM

External contact output (transistor)

Transistor contact rating: 24 V DC, 50 mA

Heater break alarm-1output

Heater break alarm-2output

Common

Contact input

Contact rating: 12 V DC, 10 mA or more

External contact input

DI3

DI2

DI1

COM

AUTO when DI1=ONMAN when DI1=OFF

STOP when DI2=ONRUN when DI2=OFF

Common

DI3

DI2

DI1

COM

+5V

+5V

+5V

No-voltagecontact

Transistor contact

Factory default: No function

UT UT

Control output

101

102

Relay contact output

103

NC

NO

COM

Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)

Contact output

101

102

103

104

105

106

107

108

109

110

111

501

502

503

504

505

506

507

508

509

510

511

512

407

408

409

410

411

412

301

302

303

304

305

306

307

308

309

310

311

312

201

202

203

204

205

206

207

208

209

210

211

212

Current/voltage pulse output

0-20 mA DC,4-20 mA DC,Voltage pulse (12V)

+

-

Retransmission output

+

-

Default: 4-20 mA DC

Default: Undefined

0-20 mA DC,4-20 mA DC

Cooling-side control outputRelay contact output

NC

NO

COM

Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)

Position proportional control output

Resistance: 100 Ω to 2.5 kΩ

Feedback input100%

0%

101-112

501-512

401-412

301-312

201-212

External contact output (relay)

AL3

AL2

AL1

Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)

Alarm-3 output(PV high limit)

Alarm-2 output( PV low limit)

Alarm-1 output(PV high limit)

Common

Common

Common

UT104

105

106

107

108

109

100-240 V AC power supply

N

L

Allowable range: 100-240 V AC (+10%/-15%) (free voltage) 50/60 Hz shared

110

111

24 V AC/DC power supply

-

+

110

111

Relay contact output

HIGH(direct)

LOW(reverse)

COM

Contact rating: 250 V AC, 3A 30 V DC, 3 A (resistance load)

507

508

509

510

511

512

-

Feedback inputCurrent (mA)input

When feedback input is current

510

511

512

202

203

201

202

203

202

203

203

204

205

206

205

206

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

+

-

207

208

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

+

-

511

512

207

- 208

207

208

209

210

211

212

209

210

211

212

510

511

512

507

508

509

511

512

511

512

Factory default: PV input type is undefined.In Heating/cooling control,

relay contact output is heating-side output.Factory default: Control output is relay.

Can be used for retransmission output or 15 V DC loop power supply when current/voltage pulse output is not used for control output.Current output range can be changed.In Position proportional type, can be used for retransmission output or 15 V DC loop power supply.

Factory default: Cooling-side control output is relay.Can be used for retransmission output or 15 V DC loop power supply when current/voltage pulse output is not used for control output. Current output range can be changed.

Can be used for 15 V DC loop power supply when not used for retransmission output.

Function can be assigned to the terminals with no function.

+

HAL1

HAL2

COM

UT507

508

509

112112 112

N

L

6. Terminal Wiring Diagrams

CAUTION

• Do not use an unassigned terminal as the relay terminal.• Do not use a 100-240 V AC power supply for the 24 V AC/DC

model; otherwise, the instrument will malfunction.

UT55A

PROFIBUS-DP/CC-LinkConnector(wiringside)(Partnumber:A1987JT)DeviceNetConnector(wiringside)(Partnumber:L4502BW)Recommendedtighteningtorque:0.5to0.6N·m

DC Relay Wiring

R

External DC power supplyRelayUT55A, UT52A

UT’s contact

Diode(Mount it directlyto the relay coilterminal (socket).)

Relay(Use one with a relay coil rating

less than the UT’s contact rating.)

AC Relay Wiring

UT55A, UT52A

R

UT’s contact CR filter(Mount it directlyto the relay coilterminal (socket).)

External AC power supply

Relay(Use one with a relay coilrating less than the UT’s

contact rating.)

Transistor Output Wiring

power+ –

UTDO

LoadCOM

Page 4: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 4/12

E1-Terminal Area301-306 E2-Terminal Area307-312

(Suffix code: Type 2=3)Contact input

External contact input

DI11

DI12

DI13

DI14

DI15

COMCommon

DI11

DI12

COM+5V

+5V

No-voltage contactTransistor contact

Contact rating: 12 V DC, 10 mA or more

DI13+5V

DI14+5V

DI15+5V

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

UT UT

301

302

303

304

305

306

301

302

303

304

305

306

Function can be assigned to the terminals with no function.

DI Contact outputExternal contact output (transistor)

Transistor contact rating: 24 V DC, 50 mA

DO12

DO11

DO13

DO14

DO15

COMCommon

UT

(Suffix code: Type 2=6)

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

301

302

303

304

305

306

Function can be assigned to the terminal with no function.

DO

(Suffix code: Type 2=1, 2, 4, 5, or 7and with option code /DR)

Universal inputTC input RTD input

Voltage (mV, V) input

+

-

+

-

Current (mA) input

+

-

4-wire

302

303

302

303

303

304

RSP

a

B

b

A 301

302

303

305

(Suffix code: Type 2=1, 2, 4, 5, or 7and without option code /DR)

Remote input

Default: 1-5 V DC

+

-

Remote input / Contact inputExternal contact input

DI16

COMCommon

DI16

COM+5V

No-voltage contact Transistor contact

Contact rating: 12 V DC, 10 mA or more

UT UT

REMOTE when DI16=ONLOCAL when DI16=OFF

303

304

303

304

305

306

RSP

Specify within a range of 1-5 V DC, 0-2 V DC,0-10 V DC

Contact outputExternal contact output

Transistor contact rating: 24 V DC, 50 mA

DO22

DO21

DO23

DO24

DO25

COM

Alarm 4 (PV low limit)

Common

UT

(Suffix code: Type 2=1, 3, 5, or 6)

307

308

309

310

311

312

Function can be assigned to the terminals with no function.

DO

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

(Suffix code: Type 2=7)

Aux. analog input

Default: 1-5 V DC

+

-

Aux. analog input / Contact inputExternal contact input

DI26

COMCommon

DI26

COM+5V

No-voltage contact Transistor contact

Contact rating: 12 V DC, 10 mA or more

Factory default: No function

UT UT

309

310

309

310

311

312

Aux. analog input can be used for feedforward input in Single-loop control and Single-loop position proportional control.

Function can be assigned to the terminals with no function.

AIN2

Specify within a range of 1-5 V DC, 0-2 V DC,0-10 V DC

Wiring direction

(Suffix code: Type1=-1) (Suffix code: Type 1=-2)

Current/voltage pulse output

0-20 mA DC,4-20 mA DC,Voltage pulse (12 V)

+

-

Retransmission output

+

-

Default: 4-20 mA DC

Default: Undefined

0-20 mA DC,4-20 mA DC

Control output (Suffix code: Type1=-0, -1 or -2)

(Suffix code: Type1=-0)

(Option code /HA)

Retransmission output

4-20 mA DC or0-20 mA DC

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

+

-

+

-

Default: 4-20 mA DC

Default: PV retransmission

Load resistance 600 Ω or less

Retransmission output (Equipped as standard)PV inputTC input RTD input

Voltage (mV, V) input

A

+

-

+

-

Current (mA) input

+

-

B

b

(Equipped as standard)

(Equipped as standard)

(Equipped as standard)Power supply

24 V AC/DC power supply

-

+

100-240 V AC power supply

Allowable range: 100-240 V AC (+10%/-15%) (free voltage) 50/60 Hz shared

N

L

Control outputRelay contact output

NC

NO

COM

Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)

Contact outputExternal contact output (relay)

AL3

AL2

AL1

Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)

Alarm-3 output(PV high limit)

Alarm-2 output(PV low limit)

Alarm-1 output(PV high limit)

Common

Common

Common

UT

Heater break alarm

Heater current detection input

CT1

CT2

COM

Contact input

Contact rating: 12 V DC, 10 mA or more

External contact input

DI3

DI2

DI1

COM

AUTO when DI1=ONMAN when DI1=OFF

STOP when DI2=ONRUN when DI2=OFF

Common

DI3

DI2

DI1

COM

+5V

+5V

+5V

No-voltagecontact

Transistor contact

Factory default: No function

UT UT

111

301

302

303

304

305

306

307

308

309

310

311

312

201

202

203

204

205

206

207

208

209

210

101

102

103

104

105

106

107

108

109

110

211

212

Current/voltage pulse output

0-20 mA DC,4-20 mA DC,Voltage pulse (12 V)

-

Retransmission output

+

-

Default: 4-20 mA DC

Default: Undefined

0-20 mA DC,4-20 mA DC

Heating/cooling control outputHeating/cooling relay contact output

NO

Heating-side

Cooling-side

NO

COM

Contact rating: 240 V AC, 3 A 30 V DC, 3 A (resistance load)

(24 V AC/DC power supply: Option code /DC)

Position proportional control output

Resistance: 100 Ω to 2.5 kΩ

Feedback input100%

0%

Relay contact output

HIGH(direct)

LOW(reverse)

COM

Contact rating: 240 V AC, 3A 30 V DC, 3 A (resistance load)

+

-

Feedback inputCurrent (mA)input

When feedback input is current

E1-terminal area101-112

301-312

201-212

101

102

103

104

105

106

107

108

109

110

111

110

111

101

102

103

310

311

312

310

311

312

202

203

201

202

203

202

203

203

204

205

206

205

206

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

+

-

207

208

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

+

-

311

312

207

208

207

208

209

210

211

212

209

210

211

212

310

311

312

101

102

103

+ 311

312

311

312

Terminal wiring differs in Heating/cooling control and Position proportional control.Refer to the terminals of Position proportional control output and Heating/cooling control output below.Factory default: Control output is relay.

Function can be assigned to the terminals with no function.

Can be used for retransmission output or 15 V DC loop power suppy when current/voltage pulse output is not used for control output.Current output range can be changed.In Position proportional type, can be used for retransmission output or 15 V DC loop power supply.

Factory default: Cooling-side control output is relay.Can be used for retransmission output or 15 V DC loop power supply when current/voltage pulse output is not used for control output.Current output range can be changed.

Can be used for 15 V DC loop power supply when not used for retransmission output.

PV RET

OUT

DI

HBAVALV

ALM

OUT

OUT

OUT2

Factory default: PV input type is undefined.

External contact output (transistor)

Transistor contact rating: 24 V DC, 50 mA

Heater break alarm-1output

Heater break alarm-2output

Common

HAL1

HAL2

COM

UT307

308

309

OUT2

112112 112

N

L

UT52A

E3-Terminal Area401-412 E4-Terminal Area501-506

(Suffix code: Type 2=1)Contact inputExternal contact input

DI31

DI32

DI33

DI34

DI35

COMCommon

DI31

DI32

COM+5V

+5V

No-voltage contactTransistor contact

Contact rating: 12 V DC, 10 mA or more

DI33+5V

DI34+5V

DI35+5V

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

UT UT

407

408

409

410

411

412

407

408

409

410

411

412

Function can be assigned to the terminals with no function.

DI

(Suffix code: Type 3=2, except Type 2= 1 or 6)

Ethernet communication (with gateway function)

10BASE-T/100BASE-TXRJ45 connector

ColorLitUnlit

Amber100M bps10M bps

Green

LinkedActiveLink failure

Color

LitBlinkUnlit

Upper side LED (baud rate)

Lower side LED (link activity)

RS-485

RSB(+)

RSA(-)

SG

407

408

409

ETHR

RS-485

SDB(+)

SDA(-)

RDB(+)

RDA(-)

SG

RS-485 communication

(Suffix code: Type 3=1, except Type 2= 1 or 6)407

408

409

410

411

RS485

Contact outputExternal contact output

DO32

DO31

DO33

DO34

DO35

COM

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

Common

UT

(Suffix code: Type 2=6)

407

408

409

410

411

412

DO

Transistor contact rating: 24 V DC, 50 mA

Function can be assigned to the terminals with no function.

Contact inputExternal contact input

DI41

DI42

DI43

DI44

DI45

COMDI41

DI42

COM+5V

+5V

DI43+5V

DI44+5V

DI45+5V

UT UT

(Suffix code: Type 2=5 or 6)

CommonNo-voltage contact Transistor contact

Contact rating: 12 V DC, 10 mA or more

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

501

502

503

504

505

506

501

502

503

504

505

506

Function can be assigned to the terminals with no function.

DI

RS-485

SDB(+)

SDA(-)

RDB(+)

RDA(-)

SG

RS-485 communication

501

502

503

504

505

RS485(Suffix code: Type 2=1 or 2 and without option code /LP)

RS-485

RSB(+)

RSA(-)

SG

RS-485 communication/24 V DC loop power supply

+

24 V DC loop power supply

21.6-28.0 V DC(Max. 30 mA DC) -

501

502

503

505

506

RS485/LPS24(Suffix code: Type 2=1 or 2 and with option code /LP)

+

24 V DC loop power supply

21.6-28.0 V DC(Max. 30 mA DC)

-

24 V DC loop power supply

505

506

LPS24(Suffix code: Type 2=other than 1, 2, 5, 6, or 7and with option code /LP)

Aux. analog input

Default: 1-5 V DC

+

-

Aux. analog input/Contact inputExternal contact input

DI46

COMDI46

COM+5V

UT UT

(Suffix code: Type 2=7)

Common

No-voltage contact Transistor contact

Contact rating: 12 V DC, 10 mA or more

Factory default: No function

503

504

503

504

505

506

Function can be assigned to the terminals with no function.

AIN4

Aux. analog input can be used for feedforward input in Single-loop control and Single-loop position proportional control.

Specify within a range of 1-5 V DC, 0-2 V DC,0-10 V DC

PROFIBUS-DP communication (with Modbus master)

Pin1

2

Signal name DescriptionVP

RxD/TxD-P

3 RxD/TxD-N

4 DGND5 SHIELD

+5V bus powerData signal (positive data receive/transmit)

Data signal (negative data recive/transmit)

Signal groundShield ground

RS-485

RSB(+)

RSA(-)

SG

407

408

409

PROF

If the UT is located at the end of a segment for the PROFIBUScommunication wiring,terminating resistors are separately needed.These are to be prepared by users. (390 Ω: 2 pcs. 220 Ω: 1 pc., or an activeterminator.)

VP

RxD/TxD-PData line

Data line

390Ω

220Ω

390ΩRxD/TxD-N

DGND

CHKRDYERR

LED

CHK(red)

RDY(green)

Lit Unlit

ERR(red)

User profile error Normal

NormalNot connected, orcommunicationfailure (flashing)

NormalCommunicatingsuccessfully

No power, or Communication failure

(Suffix code: Type 3=4, except Type 2= 1 or 6)

1

2

3

45

(Suffix code: Type 3=3,except Type 2= 1 or 6)

CC-Link communication (with Modbus master)

RS-485

RSB(+)

RSA(-)

SG

407

408

409

CC-L

If the UT is located at the end of a segment for the CC-Linkcommunication wiring,terminating resistors are separately needed.These are to be prepared by users. (110 Ω: 1 pc.)

DA

DB

110Ω

LEDCHK(red)

L ERR(red)

L RUN(green)

Lit Unlit

CHK

L RUNL ERR

User profile error/Address error Normal

Normal

Pin12

Signal name Description

DADB

3 DG4

SLD

5

FG

RX/TX + signalRX/TX - signal

Frame ground

RX/TX signal groundShield

Normal Communicating successfully

Communication failure (CRC error)

No carrier detected/Connection timeout

1

2

3

45

(Suffix code: Type 3=5, except Type 2=3)

DeviceNet communication (with Modbus master)

RS-485

RSB(+)

RSA(-)

SG

407

408

409

DNET

If the UT is located at the end of a segment for the DeviceNetcommunication wiring,terminating resistors are separately needed.These are to be prepared by users. (121 Ω: 1 pc.)

CAN_H

CAN_L

121Ω

LEDCHK(red)

MNS(green/

red)

Lit/flashing Unlit

User profile error Normal

Pin12

Signal name Description

CAN_H

CAN_L

3

V+

4

V-5

DRAIN

RX/TX + signal

RX/TX - signalShield/Drain wire

DeviceNet power supply 24V

DeviceNet power supply common

Normal. Communicating successfully (green, lit).Not connected (green, flashing).Critical link failure (red, lit).Communication timeout (red, flashing)At power-on/Communication faulted (green/red, flashing)

No electricity

CHK

MNS

1

2

3

4

5

E4-terminal area

E3-terminal area

E2-terminal area

E1-terminal area

101

102

103

104

105

106

107

108

109

110

111

501

502

503

504

505

506

507

508

509

510

511

512

407

401

408

409

410

411

412

301

302

303

304

305

306

307

308

309

310

311

312

201

202

203

204

205

206

207

208

209

210

211

212

101-112

501-512

401-412

301-312

201-212

112

UT55A(Continuedfrompage3)

+

24 V DC loop power supply

21.6-28.0 V DC(Max. 30 mA DC) -

24 V DC loop power supply(Option code /LP)

Universal input (Remote input)

(Suffix code: Type 2=2 and with option code /DR)

(Suffix code: Type 2=3)

(Suffix code: Type 2=1)

External contact output

Transistor contact rating: 24 V DC, 50 mA

DO12

DO11

COMCommon

UT

Contact input / Contact outputExternal contact input

DI11

DI12

COMCommon

DI11

DI12

COM+5V

+5V

No-voltage contact Transistor contact

Contact rating: 12 V DC, 10 mA or more

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

UT UT

Remote input/ Contact input

(Suffix code: Type 2=2 and without option code /DR)

Remote input

Default: 1-5 V DC

+

-

External contact input

DI16

COMCommon

DI16

COM+5V

No-voltage contact Transistor contact

Contact rating: 12 V DC, 10m A or more

UT UT

REMOTE when DI16=ONLOCAL when DI16=OFF

RS-485

RSB(+)

RSA(-)

SG

RS-485 communication / Remote input / Contact input

Remote input

Default: 1-5 V DC

+

-

External contact input

DI16

COMCommon

DI16

COM+5V

No-voltage contact Transistor contact

Contact rating: 12 V DC, 10m A or more

UT UT

REMOTE when DI16=ONLOCAL when DI16=OFF

TC input RTD input

Voltage (mV, V) input

+

-

+

-

Current (mA) input

+

-

E1-Terminal Area301-306

301

302

303

303

304

303

304

305

306

303

304

303

304

305

306

301

302

303

301

302

303

304

305

306

305

306

302

303

303

304

302

303

RSP/RS485RSP

RSPDI/DO

LPS24

4-wirea

B

b

A 301

302

303

305

Specify within a range of 1-5 V DC, 0-2 V DC,0-10 V DC

Specify within a range of 1-5 V DC, 0-2 V DC,0-10 V DC

Function can be assigned to the terminals with no function.

CC-Link communication (with Modbus master)(Suffix code: Type 3=3)

FG: Flame ground

SLD: Shield

DG: TX/RX signal ground

DB: RX/TX signal - signal

DA: RX/TX signal + signal

CHK(red)(Lit: User profile error/Adress error, Unlit: Normal)

L ERR(red)(Lit: Communication failure(CRC error), Unlit: Normal)

L RUN(green)(Lit: Normal, Unlit: No carrier detected/Communication timeout)

Not used

301

302

303

304

305

306

307

308

309

RS-485

RSB(+)

RSA(-)

SG

310

311

312

DB

DA

110Ω

CC-LIf the UT is located at the end of a segment for the CC-Link communication wiring,terminating resistors are separately needed.These are to be prepared by users. (110 Ω: 1 pc.)

Page 5: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 5/12

Contents1. NamesandFunctionsofDisplayParts2. Setup Procedure3. QuickSettingFunction(SettingofInputandOutput)4. AdjustingValvePositionAutomatically(foraPositionProportionalTypeControllerOnly)5. SettingAlarmType6. SettingAlarmSetpoint

1. Names and Functions of Display Parts

(2) + (3) + (4) : Setpoint display

(1)(9)

(2)

(10)

(11)

(12)

(13)

(4)(8)

(11)

(10)

(13)

(3)

(5)

(6)

(7)

(8)

(2)(3)

(4)(5)

(6)

(12)

No.infigure Name Description

(1) PVdisplay (whiteorred)

DisplaysPV.Displaysanerrorcodeifanerroroccurs.DisplaysthescrollingguideintheMenuDisplayandParameterSettingDisplaywhentheguidedisplayON/OFFissettoON.

(2) Groupdisplay(green)Displaysagroupnumber(1to8orR)andterminalarea(E1toE4).1to8representSPnumbersintheOperationDisplay.RandE1toE4aredisplayedintheParameterSettingDisplay.

(3) Symboldisplay(orange) Displaysaparametersymbol.(4) Datadisplay(orange) Displaysaparametersetpointandmenusymbol.

(5) Bar-graphdisplay(orangeandwhite)

Displayscontroloutputvalue(OUT)andmeasuredinputvalue(PV).Thedatatobedisplayedcanbesetbytheparameter.Initialvalue:upperbar(deviation),lowerbar(controloutput,internalcomputedvalueinPositionproportionalcontrol);inHeating/coolingcontrol,upperbar(heating-sidecontroloutput),lowerbar(cooling-sidecontroloutput)

(6) Eventindicator (orange)

UT55A:Litwhenthealarms1to8occur.(Initialvalue:1to4)UT52A:Litwhenthealarms1to4occur.Eventdisplaysotherthanalarmscanbesetbytheparameter.

(7) Keynavigationindica-tor(green)

LitorblinkswhentheUp/DownorLeft/Rightarrowkeyoperationispossible.

(8) Parameterdisplaylevelindicator(green)

Displaysthesettingconditionsoftheparameterdisplaylevelfunction.

Parameter display level EASY PROEasysettingmode Lit UnlitStandardsettingmode Unlit UnlitProfessionalsettingmode Unlit Lit

(9)Deviationindicator (forUT55Aonly)(green)

Displaysthestatusofadeviation(PV-SP).:Litifadeviationexceedsthedeviationdisplayband.:Litwhenadeviationiswithinthedeviationdisplayband:Litifadeviationfallsbelowthedeviationdisplayband.ThedeviationindicatorisunlitiftheDisplaysotherthantheOp-erationDisplayorSELECTDisplayareshown.Deviationdisplaybandcanbesetbytheparameter.

(10) Status indicator (greenandred)

Displaystheoperatingconditionsandcontrolstatus.

Indicator Description REM Litwheninremotemode(REM).CAS Litwhenincascademode(CAS).PRG UnusedSTOP Litwheninstopmode(STOP).

MAN Litwheninmanualmode(MAN).Blinksduringauto-tuning.

(11) Securityindicator(red) Litifapasswordisset.Thesetupparametersettingsarelocked.

(12) Ladderoperationindicator(green)

Litwhiletheladderoperationisexecuted.

(13)Loop2indicator (LP2lamp)(green)

LitwhenthecontrolmodeisCascadecontrol.IntheOperationDisplay,theLP2lampislitwhiletheLoop-2datais displayed on Setpoint display.IntheParameterSettingDisplay,theLP2lampindicatestheloopofdisplayedmenusymbolorparametersymbol.TheLP2lampislitwhiletheLoop-2menusymbolorparametersymbolisdisplayed.

(4)

(5)(6)

(1)(2)

(3)

(4)

(5)

(6)

(1)

(2)

No.infigure Name Description

(1) UT55A:DISPLAYkeyUT52A:DISPkey

UsedtoswitchtheOperationDisplays.PressthekeyintheOperationDisplaytoswitchtheprovidedOperationDisplays.PressthekeyintheMenuDisplayorParameterSettingDisplaytoreturntotheOperationDisplay.

(2)UT55A:PARAMETERkeyUT52A:PARAkey

Holddownthekeyfor3secondstomovetotheOperationParameterSettingDisplay.HolddownthekeyandtheLeftarrowkeysimultaneouslyfor3secondstomovetotheSetupParameterSettingDisplay.PressthekeyintheParameterSettingDisplaytoreturntotheMenuDisplay.Pressthekeyoncetocanceltheparameterset-ting(setpointisblinking).

(3)SET/ENTERkeyUp/Down/Left/Rightarrow keys

SET/ENTERkeyPressthekeyintheMenuDisplaytomovetotheParameterSettingDisplayoftheMenu.PressthekeyintheParameterSettingDisplaytotransfertotheparametersettingmode(setpointisblinking),andtheparametercanbechanged.Pressthekeyduringparametersettingmodetoregisterthe setpoint.Up/Down/Left/RightarrowkeysPresstheLeft/RightarrowkeysintheMenuDisplaytoswitchtheDisplays.PresstheUp/Down/Left/RightarrowkeysintheParameterSettingDisplaytoswitchtheDisplays.PresstheUp/Downarrowkeysduringparametersettingmode(setpointisblinking)tochangeasetpoint.PresstheLeft/Rightarrowkeysduringparametersettingmode (setpointisblinking)tomovebetweendigitsaccordingtotheparameter.

(4) Light-loaderinterfaceItisthecommunicationinterfacefortheadaptercableusedwhensettingandstoringparametersfromaPC.TheLL50AParameterSettingSoftware(soldseparately)isrequired.

(5) A/MkeyUsedtoswitchbetweenAUTOandMANmodes.ThesettingisswitchedbetweenAUTOandMANeachtimethekey is pressed.

(6) UserfunctionkeysTheUT55AhasF1,F2,andFnkeys.TheUT52AhasonlytheFnkey.Theusercanassignafunctiontothekey.Thefunctionissetbytheparameter.

Note: Thecommunicationconnector(maintenanceport)forLL50AParameterSettingSoftwareison the top of the unit.

2. Setup ProcedureThefollowingflowchartshowsthesetupprocedureforUT55AandUT52A.

Install and wire a controller.

Monitoring and control of regular operations

Adjust PID using auto-tuning or manually for PID control.

Other setup

Operation

NO

NO NO

YES

YES YES

Control mode: Single-loop control only

Set the other parameters as needed.

PID tuning

Input setup

Output setup

Installationand wiring

Power ON

Control mode setup

Control type setup

Control type setupInput/output setup

Valve positionadjustment

UseQuick setting

function?

Positionproportional

type?

Positionproportional

type?

For Position proportional type

3. Quick Setting Function (Setting of Input and Output)TheQuicksettingfunctionisafunctiontoeasilysetthebasicfunctionofthecontrol-ler.TurnonthecontrollertostarttheQuicksettingfunction.Thisfunctionallowsyoutoeasilysetthecontroltype,input,andoutput,andquicklystart the control action.Theitems(parameters)tobesetbyQuicksettingfunctionareasfollows.(1)Controltype(PIDcontrol,Heating/coolingcontrol,etc.)(2)Inputfunction(PVinputtype,range,scale(atvoltageinput),etc.)(3)Outputfunction(controloutputtypeandcycletime)

Afterturningonthecontroller,firstdecidewhetherornottousetheQuicksettingfunc-tion.TheQuicksettingfunctioncanbeusedonlywhenthecontrolmodeisSingle-loopcontrol.Forothercontrolmodes,set thefunctionswithoutusingtheQuicksettingfunction.

Operation in Initial Display· PresstheSET/ENTERkeywhileYESisdisplayedtostarttheQuicksettingfunction.· IfyouchangeYEStoNOandpresstheSET/ENTERkey,OperationDisplaywillappearwithoutstartingtheQuicksettingfunction.

OperationGuide

Initial Settings

UT55A, UT52ADigital Indicating Controller (Panel Mounting Type)Operation Guide for Single-loop Control

This operation guide describes basic settings and operations of the UT55A and UT52A.For details of each function, see the electronic manual.The scrolling guide is displayed on PV display in the Parameter Setting Display.This guide can be turned on/off with the Fn key. For details of the each function, refer to the electronic manual. Manuals can be downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

«Standard Code Model»

Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.

· Tochangeandset theparametersetting,presstheSET/ENTERkeytostart thesetpointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/EN-TERkeytoregisterthesetting.

Making Settings Using Quick Setting FunctionExample: Setting to PID control, thermocouple type K (range of 0.0 to 500.0°C),

and current control outputForthedetailedprocedureandswitchingofdisplays,see"FlowofQuickSettingFunction"below.Fortheparameterstoset,seethenextpage.

(1)PresstheSET/ENTERkeywhileYESforQSM(Quicksettingmode)isdisplayed.(2)Setthecontroltypeparameter(CNT)toPID(PIDcontrol).(3)SetthePVinputtypeparameter(IN)toK1(-270.0to1370.0°C).(4)SetthePVinputunitparameter(UNIT)toC(DegreeCelsius).(5)SetthemaximumvalueofPVinputrangeparameter(RH)to500.0.(6)SettheminimumvalueofPVinputrangeparameter(RL)to0.0.(7)Settheoutputtypeselectionparameter(OT)toOUTterminals(current).(8)Finally,EXITisdisplayed.ChangeNOtoYESandpresstheSET/ENTERkeyto

completethesetup.OperationDisplayappears.

Press the SET/ENTER key while YES is displayed to start the Quick setting.

[NO]

Select NO with the Down arrow key and press the SET/ENTER key.

Select NO to return to the Operation Display.

Power-on

First, the control type parameter (CNT) is displayed.Initial value: PID (PID control)

 Press the Down arrow key.

The PV input type parameter (IN) is displayed.Initial value: OFF

Press the SET/ENTER key.

OFF blinks.Blinking allows you to change the setting.

 Press the Up arrow key.

K1 is displayed.

K1 has been registered.

Press the SET/ENTER key.

 Press the Down arrow key.

[YES]

1.

2.

3.

4.

5.

6.

Quick setting starts

The last digit of the upper limit value blinks.

The parameter RH (maximum value of PV input range) has been changed to 500.0.

The setpoint for the parameter RH has been registered.

Press the Down arrow key.

Operation Display

8.

9.

10.

11.

12.

The PV input unit parameter (UNIT) is displayed.Initial value: C (Degree Celsius)

7.

Press the Down arrow key.

Follow the same procedure to set RL to 0.0 and OT to 00.02.Set other parameters as needed.

Displays the measured input value (PV).Displays the target setpoint (SP).

Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.

The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).

Press the SET/ENTER key.

Press the SET/ENTER key.

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

FlowofQuickSettingFunctionInQuicksettingmode,theparameterguideappearsonPVdisplay.Thisguidecanbeturnedon/offwiththeFnkey.

Page 6: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 6/12

Parameterstobeset

Control TypeParameter Symbol Name of Parameter Setting Range

CNT Controltype

PID:PIDcontrolONOF:ON/OFFcontrol(1pointofhysteresis)ONOF2:ON/OFFcontrol(2pointsofhysteresis)2P2L:Two-positiontwo-levelcontrolH/C:Heating/coolingcontrolS-PI:SamplePIcontrolBATCH:BatchPIDcontrolFFPID:Feedforwardcontrol

Note: Somesetpointsmaynotbedisplayeddependingonthemodelandsuffixcodes.

Input FunctionParameter Symbol Name of Parameter Setting Range

IN PVinputtype

OFF:DisableK1:-270.0to1370.00C/-450.0to2500.0 0FK2:-270.0to1000.00C/-450.0to2300.0 0FK3:-200.0to500.00C/-200.0to1000.0 0FJ:-200.0to1200.00C/-300.0to2300.0 0FT1:-270.0to400.00C/-450.0to750.0 0FT2:0.0to400.00C/-200.0to750.0 0FB:0.0to1800.00C/32to3300 0FS:0.0to1700.00C/32to3100 0FR:0.0to1700.00C/32to3100 0FN:-200.0to1300.00C/-300.0to2400.0 0FE:-270.0to1000.00C/-450.0to1800.0 0FL:-200.0to900.00C/-300.0to1600.0 0FU1:-200.0to400.00C/-300.0to750.0 0FU2:0.0to400.00C/-200.0to1000.0 0FW:0.0to2300.00C/32to4200 0FPL2:0.0to1390.00C/32.0to2500.0 0FP2040:0.0to1900.00C/32to3400 0FWRE:0.0to2000.00C/32to3600 0FJPT1:-200.0to500.00C/-300.0to1000.0 0FJPT2:-150.00to150.000C/-200.0to300.0 0FPT1:-200.0to850.00C/-300.0to1560.0 0FPT2:-200.0to500.00C/-300.0to1000.0 0FPT3:-150.00to150.000C/-200.0to300.0 0F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV

UNIT PVinputunit -:Nounit,C:DegreeCelsius-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit

RH MaximumvalueofPVinputrange

Dependsontheinputtype.-Fortemperatureinput-Setthetemperaturerangethatisactuallycontrolled.(RL<RH)-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallycontrolledshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)

RL MinimumvalueofPVinputrange

SDPPVinputscaledecimal point position

0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces

3:Threedecimalplaces4:Fourdecimalplaces

SH MaximumvalueofPVinputscale

-19999to30000,(SL<SH),|SH-SL|≤30000SL Minimumvalueof

PVinputscale

Note1:SDP,SH,andSLaredisplayedonlyforvoltage/currentinput.Note2:W:W-5%Re/W-26%Re(HoskinsMfg.Co.),ASTME988

Output FunctionParameter Symbol Name of Parameter Setting Range

OT

Outputtypeselection

Upper two digitsLower two digits

ControloutputorHeating-sidecontroloutput(Lowertwodigits)00:OFF01:OUTterminals(voltagepulse)02:OUTterminals(current)03:OUTterminals(relay)04:OUT2terminals(voltagepulse)05:OUT2terminals(current)06:OUT2terminals(relay)

Cooling-sidecontroloutput(Uppertwodigits)

00:OFF01:OUTterminals(voltagepulse)02:OUTterminals(current)03:OUTterminals(relay)04:OUT2terminals(voltagepulse)05:OUT2terminals(current)06:OUT2terminals(relay)

CT

ControloutputcycletimeHeating-sidecontroloutput cycle time (inHeating/coolingcontrol)

0.5to1000.0s

CTc Cooling-sidecontroloutput cycle time

4. Adjusting Valve Position Automatically (for a Position Proportional Type Controller Only)Thefollowingoperatingproceduredescribeshowtoinputfeedbacksignalsfromthecontrolvalveandadjustthefully-openandfully-closedpositionsofthecontrolvalveautomatically.Thefully-openandfully-closedpositionsofthevalvecanbeadjustedautomaticallybyinputtingfeedbacksignalsfromthevalve.Toadjustthevalveposi-tion,youneedtocarryouttheconnectionandbringthecontrollerintomanualmode.Fortheconnection,see“6.TerminalWiringDiagrams” in"InstallationandWiring",andfor themanualmode,see“5.SwitchingbetweenAUTOandMAN” in"Opera-tions."

CTL menu is displayed. Press the Right arrow key until OUT menu appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

 Press the Up arrow key.

Hold down the keys for 3 seconds.+

Show the Operation Display.

OUT menu is displayed.

OFF blinks.

Press the SET/ENTER key.

1.

2.

3.

4.

5.

6.

7.

MAN is lit

* When a password is set, PASS is displayed. If the correct password is not entered, setup parameters cannot be changed.

The parameter V.AT (automatic valve position adjustment) is displayed.

ON is displayed.Blinks during the change.

When the adjustment is completed normally, the indication automatically returns to OFF. When VAT.E appears on PV display, it indicates an error. Check the wiring for feedback input and perform the automatic adjustment again. To perform a valve adjustment manually, see User’s Manual (IM 05P01C31-01EN).

ON has been registered and the automatic adjustment of the valve position starts.V.AT blinks during the automatic adjustment. After the adjustment is completed, press the DISPLAY key or DISP key once to return to the Operation Display.

5. Setting Alarm TypeThefollowingoperatingprocedureshowsanexampleofchangingthealarm-1type(factorydefault:PVhighlimitalarm)toPVlowlimitalarm(setpoint:02).

MODE menu is displayed.

 Press the Right arrow key until ALRM menu appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

Hold down the key for 3 seconds.

Show the Operation Display.

ALRM menu is displayed.

1.

2.

3.

4.The parameter AL1 (alarm-1 type) is displayed.

Press the SET/ENTER key.

5.

6.

Energized/De-energizedLatch action

Stand-by action

The alarm-1 type setpoint 02 (PV low limit)is registered.After the setup is completed, press the DISPLAY key or DISP key once to return to the Operation Display.

Symbol

To change the alarm type, change the last 2 digits of the 5-digit value. Stand-by action and excitation are turned on or off by selecting 1 or 0. (See “ Setting Display of Alarm Type.”) For the latch action, see User ’s Manual (IM 05P01C31-01EN).

The last digit of the setpoint blinks.

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

Hysteresis

Alarm setpoint PV, RSP, AIN2 or AIN4

SP or Target SP

Hysteresis

PV Deviation setpoint

SP or Target SP

Deviation setpoint

PV

Hysteresis Hysteresis

Open (unlit)

Closed (lit)

SP or Target SPPVDeviation setpoint

Hysteresis

- -

SP or Target SP

PV

Hysteresis Hysteresis

Deviation setpoint

Open (unlit)

SP or Target SP

Alarm setpoint

Hysteresis

SP or Target SP

Hysteresis

Alarm setpoint

Alarm setpointOutput

Hysteresis

Closed(lit)

Hysteresis

Alarm setpoint Output

Alarm setpoint

Hysteresis

PV, RSP, AIN2 or AIN4

Hysteresis

Alarm setpoint PV, RSP, AIN2 or AIN4

SP or Target SP

Hysteresis

PV Deviation setpoint

SP or Target SP

Deviation setpoint

PV

Hysteresis Hysteresis

SP or Target SPPVDeviation setpoint

Hysteresis

SP or Target SP

PV

Hysteresis Hysteresis

Deviation setpoint

Closed (unlit)

SP or Target SP

Alarm setpoint

Hysteresis

SP or Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Hysteresis

PV, RSP, AIN2 or AIN4

Alarm setpointOutput

Hysteresis

Hysteresis

Alarm setpoint Output

Setting Display of Alarm Type Stand-by Action

Energized (0) / De-energized (1)

Alarm typeWithout (0) or With (1) Stand-by action

Latch action (0/1/2/3/4)See User’s Manual (IM 05P01C31-01EN).

PV low limit alarm setpoint

Treatedas normal

ºC

Power-on Time

The alarm output does not turn onin this region even if the PV valuleis below PV low limit alarm setpoint.

Normal Abnormal

The alarm outputturns on.

No alarm (00)

Alarm Action (De-energized)

PV high limit (01)Analog input PV high limit (19)Analog input RSP high limit (21)Analog input AIN2 high limit (23)Analog input AIN4 high limit (25)

PV low limit (02)Analog input PV low limit (20)Analog input RSP low limit (22)Analog input AIN2 low limit (24)Analog input AIN4 low limit (26)

SP high limit (03)Target SP high limit (09)

SP low limit (04)Target SP low limit (10)

Deviation high limit (05)Target SP deviation high limit (11)

Deviation low limit (06)Target SP deviation low limit (12)

Deviation high and low limits (07)Target SP deviation high and low limits (13)

Deviation within high and low limits (08) Target SP deviation within high and low limits (14)

Control output high limit (15)Cooling-side control output high limit (17)

Control output low limit (16)Cooling-side control output low limit (18)

Feedback input high limit (27)

Feedback input low limit (28)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint) Alarm Action (Energized)

Open (unlit)

Open (unlit)

Open (lit)

Closed (lit)

Open (unlit)

Open (lit)

Closed (unlit)

Closed (unlit)

Open (lit)

Closed (unlit)

Closed (unlit)

Open (lit)

Open (lit)Closed

(lit)Closed

(lit)

Closed (lit)

Closed (lit)

Closed (lit)

Closed (lit)

Closed (lit)

Closed (lit)

Open (unlit)

Open (unlit)

Open (unlit)

Open (unlit)

Open (unlit)

Open (unlit)

Open (lit)

Open (lit)

Open (lit)

Open (lit)

Open (lit)

Open (lit)

Closed (unlit)

Closed (unlit)

Closed (unlit)

Closed (unlit)

Closed (unlit)

Closed (unlit)

Burnout of PV input, RSP remote input, or AIN2/AIN4 auxiliary analog input. ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.Note 2: Positive setpoint, Negative setpoint

Hysteresis

Alarm setpoint PV, RSP, AIN2 or AIN4

SP or Target SP

Hysteresis

PV Deviation setpoint

SP or Target SP

Deviation setpoint

PV

Hysteresis Hysteresis

Open (unlit)

Closed (lit)

SP or Target SPPVDeviation setpoint

Hysteresis

- -

SP or Target SP

PV

Hysteresis Hysteresis

Deviation setpoint

Open (unlit)

SP or Target SP

Alarm setpoint

Hysteresis

SP or Target SP

Hysteresis

Alarm setpoint

Alarm setpointOutput

Hysteresis

Closed(lit)

Hysteresis

Alarm setpoint Output

Alarm setpoint

Hysteresis

PV, RSP, AIN2 or AIN4

Hysteresis

Alarm setpoint PV, RSP, AIN2 or AIN4

SP or Target SP

Hysteresis

PV Deviation setpoint

SP or Target SP

Deviation setpoint

PV

Hysteresis Hysteresis

SP or Target SPPVDeviation setpoint

Hysteresis

SP or Target SP

PV

Hysteresis Hysteresis

Deviation setpoint

Closed (unlit)

SP or Target SP

Alarm setpoint

Hysteresis

SP or Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Hysteresis

PV, RSP, AIN2 or AIN4

Alarm setpointOutput

Hysteresis

Hysteresis

Alarm setpoint Output

Setting Display of Alarm Type Stand-by Action

Energized (0) / De-energized (1)

Alarm typeWithout (0) or With (1) Stand-by action

Latch action (0/1/2/3/4)See User’s Manual (IM 05P01C31-01EN).

PV low limit alarm setpoint

Treatedas normal

ºC

Power-on Time

The alarm output does not turn onin this region even if the PV valuleis below PV low limit alarm setpoint.

Normal Abnormal

The alarm outputturns on.

No alarm (00)

Alarm Action (De-energized)

PV high limit (01)Analog input PV high limit (19)Analog input RSP high limit (21)Analog input AIN2 high limit (23)Analog input AIN4 high limit (25)

PV low limit (02)Analog input PV low limit (20)Analog input RSP low limit (22)Analog input AIN2 low limit (24)Analog input AIN4 low limit (26)

SP high limit (03)Target SP high limit (09)

SP low limit (04)Target SP low limit (10)

Deviation high limit (05)Target SP deviation high limit (11)

Deviation low limit (06)Target SP deviation low limit (12)

Deviation high and low limits (07)Target SP deviation high and low limits (13)

Deviation within high and low limits (08) Target SP deviation within high and low limits (14)

Control output high limit (15)Cooling-side control output high limit (17)

Control output low limit (16)Cooling-side control output low limit (18)

Feedback input high limit (27)

Feedback input low limit (28)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint) Alarm Action (Energized)

Open (unlit)

Open (unlit)

Open (lit)

Closed (lit)

Open (unlit)

Open (lit)

Closed (unlit)

Closed (unlit)

Open (lit)

Closed (unlit)

Closed (unlit)

Open (lit)

Open (lit)Closed

(lit)Closed

(lit)

Closed (lit)

Closed (lit)

Closed (lit)

Closed (lit)

Closed (lit)

Closed (lit)

Open (unlit)

Open (unlit)

Open (unlit)

Open (unlit)

Open (unlit)

Open (unlit)

Open (lit)

Open (lit)

Open (lit)

Open (lit)

Open (lit)

Open (lit)

Closed (unlit)

Closed (unlit)

Closed (unlit)

Closed (unlit)

Closed (unlit)

Closed (unlit)

Burnout of PV input, RSP remote input, or AIN2/AIN4 auxiliary analog input. ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.Note 2: Positive setpoint, Negative setpoint

6. Setting Alarm SetpointThefollowingoperatingprocedureshowsanexampleofsettingthealarm-1setpointofgroup1to180.0.Beforesettingthealarmsetpoint,checkthealarmtype.Tochangethealarmtype,see“5.SettingAlarmType.”

Press the Right arrow key.

Press the SET/ENTER key.

SP menu is displayed.

Display the parameter and group that need to be changed.

Blinks during the change.

The setpoint has been registered.After the setup is completed, press the DISPLAY key or DISP key onceto return to the Operation Display.

Press the SET/ENTER key.

Press the Down arrow key until A1 appears.

Press the SET/ENTER key.

Show the Operation Display.

Display MODE menu with the same procedure as described in Setting Alarm Type.

1.2.

3.

4.

5.

6.

Group

The parameter A1 is displayed.A1 to A8 represent the alarm-1 to -8 setpoints.

Each parameter and group can be changed in the Parameter Setting Displays of alarmsusing arrow keys.Up/Down arrow keys: parametersLeft/Right arrow keys: groups

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

Initializing parameter valuesParametersthatyouhavechangedcanbeinitializedtofactorydefaultvaluesoruserdefaultvalues.Fordetails,see“Parameter Initialization” in theUser’sManual(IM05P01C31-01EN).

Changing the parameter display levelsThisoperationguidedoesnotexplainalltheparameters.Todisplayalltheparam-eters,youneedtochangetheparameterdisplayleveltoprofessionalsettingmode.Fordetails,see“SettingSecurityFunctions” in theUser’sManual(IM05P01C31-01EN).

Page 7: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 7/12

Contents1. Monitoring-purposeOperationDisplaysAvailableduringOperation2. SettingTargetSetpoint(SP)3. Performing/CancelingAuto-tuning4. SelectingTargetSetpointNumbers(SPNO.)5. SwitchingbetweenAUTOandMAN6. SwitchingbetweenRUNandSTOP7. SwitchingbetweenREM(Remote)andLCL(Local)8. ManipulatingControlOutputinManualMode9. Troubleshooting

1. Monitoring-purpose Operation Displays Available during Operation

Operation Display Switching Diagram for Standard and Posi-tion Proportional Types

• SP Display DisplaysthemeasuredinputvalueonPVdisplay. Displaysthetargetsetpoint(SP)onSetpointdisplay(SPcanbechanged).• OUT Display DisplaysthemeasuredinputvalueonPVdisplay. Displaysthecontroloutputvalue(OUT)onSetpointdisplay(OUTcanbechangedinmanualmode).Displaysthevalve’sfeedback inputvalue(at0 to100%valveopening)inPositionproportionalcontrol.

SP Display(SP can be changed.)

OUT Display(OUT can be changed.)

Operation Display Switching Diagram for Heating/Cooling Type• SP Display DisplaysthemeasuredinputvalueonPVdisplay. Displaysthetargetsetpoint(SP)onSetpointdisplay(SPcanbechanged).• OUT Display DisplaysthemeasuredinputvalueonPVdisplay. Displaysthecontroloutputvalues(C.H.)ofheatingandcoolingsidesonSetpointdisplay(C.H.canbechangedinmanualmode).

SP Display(SP can be changed.)

Heating/cooling OUT Display(OUT can be changed.)

AftershowingtheOUTDisplay,presstheDISPLAYkeyorDISPkeytoshowthefol-lowingdisplaysconditionally.Fordetails,seeUser’sManual(IM05P01C31-01EN).

Standard, Position Proportional, and Heating/Cooling Types• SELECTDisplays1to5(whichappearwhenregistered)• AnalogInputDisplay(displayonly)(factorydefault:non-display)• PositionProportionalComputationOutputDisplay(displayonly)(factorydefault:non-display)• PIDNumberDisplay(displayonly)(factorydefault:non-display)• HeaterBreakAlarm-1CurrentDisplay(displayonly)(forheaterbreakalarmoptiononly)• HeaterBreakAlarm-2CurrentDisplay(displayonly)(forheaterbreakalarmoptiononly)

2. Setting Target Setpoint (SP)

When the required value is displayed, press the SET/ENTER key to register the setpoint.

Show the SP Display (Operation Display).(This is an example of setting the target setpoint to 150.0).

Press the SET/ENTER key to start the last digit of the setpoint blinking.Blinking allows you to change the value.

To set the setpoint, use the Left/Right arrow keys to move between digits and the Up/Down arrow keys to increase and decrease the value.

1.

2.

3.

4.

3. Performing/Canceling Auto-tuningAuto-tuningshouldbeperformedaftersettingatargetsetpoint.Makesurethatthecontrollerisinautomaticmode(AUTO)andinrunmode(RUN)beforeauto-tuning.Forsetting toAUTO,see “5.SwitchingbetweenAUTOandMAN,”andforsettingtoRUN,see“6.SwitchingbetweenRUNandSTOP.”Ifthesetpointisknowninadvanceorauto-tuningdoesnotfindanyappropriatePIDconstants,setthePIDmanually.ForsettingthePIDmanually,seeUser’sManual(IM05P01C31-01EN).

CAUTION

Do not perform auto-tuning for the following processes.Tune PID manually.• Processes with fast response such as flow rate control and pres-

sure control.• Processes which do not allow the output to be turned on and off

even temporarily.• Processes which prohibit severe output changes at control

valves (or other actuators).• Processes in which product quality can be adversely affected if

PV values fluctuate beyond their allowable ranges.

Show the Operation Display.

Hold down the PARAMETER key or PARA key for 3 seconds to display MODE menu.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the Down arrow key until the parameter AT appears.

The parameter AT (auto-tuning switch) is displayed.

1.

2.

3.

4.

The parameter R.L (REMOTE/LOCAL switch) is displayed.

OFF blinks.

Press the Up/Down arrow keys to display the required setpoint.

Blinks during the change.

The setpoint has been registered. This starts auto-tuning.The limiter can be set to the output during auto-tuning. For details, see User’s Manual (IM 05P01C31-01EN).

The MAN lamp goes off, which means that the auto-tuning completed normally.

5.

6.

7.

8.

The setting range is 1 to 8 (represent group numbers) or R.To perform auto-tuning for the PID of group 1, set the parameter AT to 1.To quit the auto-tuning, set the parameter to OFF.

During auto-tuning,• The MAN lamp blinks.• The OUT symbol appears.• The output values at 100.0% and

0% appear alternately.

Press the SET/ENTER key.

4. Selecting Target Setpoint Numbers (SPNO.)Thefollowingoperatingprocedureshowsanexampleofchangingthetargetsetpointnumber(SPNO.)from1to2.EachSPhasitsPIDgroup.ThePIDgroupsetfortheparameterPIDN(PIDnumberselection)isused.

Show the Operation Display.

Hold down the PARAMETER key or PARA key for 3 seconds to display MODE menu.

Press the SET/ENTER key.

SPNO. has been changed to 2.

Blinks during the change.

The setpoint has been registered.Press the DISPLAY key or DISP key once to return to the Operation Display.

Change the setpoint using the Up/Down arrow keys.

Press the Down arrow key until the parameter SPNO. appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

1.

2.

3.

4.

5.

6.

7.

The parameter R.L (REMOTE/LOCAL switch) is displayed.

The parameter SPNO. (SP number selection) is displayed.

OperationGuide

UT55A, UT52ADigital Indicating Controller (Panel Mounting Type)Operation Guide for Single-loop Control

This operation guide describes key entries for operating the UT55A, UT52A.Although the display of UT55A is used in this guide, UT52A can be operated similarly. For operations using external contact inputs, see “DI” of “6. Terminal Wiring Diagrams” in “Installation and Wiring.” If you cannot remember how to carry out an operation during setting, press the DISPLAY key or DISP key once. This brings you to the display (Operation Display) that appears at power-on. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.

Operations

For details of the each function, refer to the electronic manual. Manuals can be downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

«Standard Code Model»

5. Switching between AUTO and MANAUTOandMANswitchingcanbeperformedusinganyofthefollowing:(1)A/Mkey,(2)Contactinput,(3)Communication,and(4)Userfunctionkey.ThefigurebelowshowsadirectoperationusingtheA/Mkey.WhenAUTOandMANswitchingfunction isassignedtothecontact input,andthecontactinputisON,theswitchingbykeyoperationcannotbeperformed.Fordetails,seeUser’sManual(IM05P01C31-01EN).

MAN lamp is lit in MAN mode.

Each time you press the key,AUTO and MAN is switched alternately.

WhenAUTOisswitchedintoMAN,thecontroloutputvalueinAUTOmodeisheld.Thecontrollercanbeoperatedmanuallyfromtheholdvalue.If themanualpresetoutput isset(MPONparameter≠OFF), thecontrollercanbeoperatedmanuallyfromthearbitraryoutputvalue(MPO1toMPO5parameters).

6. Switching between RUN and STOPRUNandSTOPswitchingcanbeperformedusinganyofthefollowing:(1)Contactinput,(2)Parameter,(3)Communication,and(4)Userfunctionkey.Thefollowingshowsanexampleofswitchingusingthecontactinput.(TheswitchingfunctionisassignedtoDI2contactforthefactorydefault.)Fordetailsofotherswitchingmethodsandthedisplayappearingwhentheoperationisstarted,seeUser’sManual(IM05P01C31-01EN).Whenthecontrollerisstopped,inputandoutputsareasfollows:

PVinput DisplaysthePVvalue.Controloutput Displaysthepresetoutputvalue.

ThepresetoutputvalueissetforeachPIDgroup.Alarmoutput Turns the output on in case of an alarm.

Display in STOP mode“STOP” isdisplayedonSymboldisplayand"presetoutputvalue" isdisplayedonDatadisplay.

OFF: Operation RUN

Display in STOP mode210

212

ON: Operation STOP210

212

Preset output (PO)Valve opening (0-100%) for Position proportional type

STOP lamp is lit.

DI2

DI2

Display in STOP mode in Heating/cooling control“Cooling-sidepresetoutputvalue” isdisplayedonthe leftsideof the“ST”symbol,and“Heating-sidepresetoutputvalue”isontherightside.

OFF: Operation RUN

Display in STOP mode210

212

ON: Operation STOP210

212

Heating-side preset output (PO)

STOP lamp is litCooling-side preset output (POc)

.

DI2

DI2

Page 8: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 8/12

7. Switching between REM (Remote) and LCL (Local)Remoteandlocalswitchingcanbeperformedusinganyofthefollowing:(1)Contactinput,(2)Parameter,(3)Communication,and(4)Userfunctionkey.

LCL (Local)Controlisperformedusingthetargetsetpointsetonthecontroller.

REM (Remote)Control isperformedusinganexternalanalogsignalthatisusedasthetargetset-point.Thefollowingshowsanexampleofswitchingfromlocal toremoteusingtheparameter.Fordetailsofotherswitchingmethods,seeUser’sManual(IM05P01C31-01EN).•ThePIDgroupforthelocalSPnumberisusedasPIDinremotemode.

NOTEWhenthecontactinputisON,operationcannotbeperformedusingtheparameter,communication,orkey.Whenthecontact input isOFFandthesetting isswitchedusing theparameter,communication,orkey, the lastswitchingoperation isper-formed.

Show the Operation Display.

Hold down the PARAMETER key or PARA key for 3 seconds to display MODE menu.

Press the SET/ENTER key.

1.

2.

Press the SET/ENTER key.

The REM lamp is lit.

Change the operation mode using the Up/Down arrow keys.Blinks during the change.

Press the SET/ENTER key.

3.

4.

5.

The parameter R.L (REMOTE/LOCAL switch)is displayed.

8. Manipulating Control Output in Manual Mode

NOTEInmanualmode,controloutput ismanipulatedbyoperatingthekeys(thevalue ischangedusingtheUp/Downarrowkeys,thenoutputtedasitis).Even if theSET/ENTERkey isnotpressed, thecontroloutputvaluechangesac-cordingtothedisplayedvalue.Instopmode(whentheSTOPlampislit),controloutputcannotbemanipulated.

MAN lamp is lit.

Up arrow key: increases control output.Down arrow key: decreases control output.

In Position proportional control:Up arrow key; opens the valve.Down arrow key; closes the valve.Output; only while pressing a key. OUT; valve opening (0-100%)

Output manipulation in Position proportional control is not restricted from output limiters (OH, OL).

Manual operation in Heating/cooling control

Symbol of cooling sideTarget setpoint (SP) number

Symbol of heating sideHeating-side control output

Cooling-side control output

Uparrowkey:concurrentlydecreasescooling-sidecontroloutputand increasesheating-sidecontroloutput.

Downarrowkey:concurrently increasescooling-sidecontroloutputanddecreasesheating-sidecontroloutput.

(Eithernoneof theheating-sideandcooling-sideoutputsarepresented,orbothofthemarepresentedaccordingtothedeadbandsetting.)

Actual output (%)

DB=24.8 Dead band: Operation parameter DB

Control computation output Control computation output

12.40-12.4

Manipulated output changewhen a dead band is positive (+)

Actual output (%)100

DB= -24.8

12.40-12.4

Manipulated output changewhen a dead band is negative (-)

100

Cooling-sidemanipulated output

Heating-sidemanipulated output

Heating-sidemanipulated output

Cooling-sidemanipulated output

9. TroubleshootingTroubleshootingFlowIftheOperationDisplaydoesnotappearafterturningonthecontroller’spower,checktheproceduresinthefollowingflowchart.Ifaproblemappearstobecomplicated,contactoursalesrepresentatives.

Is the controllerdefective?

Contact us for repair. Problem solved.

No communicationcapability

Completelyinactive?

Yes

Yes

Yes

No

No

No

Keyoperationfailure?

Yes

No

Yes

Check wiring of thepower terminals.

Check the key locksetting.

Displayfailure?

*Yes

No

Turn off power, andthen turn it on again.

I/O signalfailure?

Yes

No

Check the supply voltage.

Check the specifications and polarity

of connected devices .

Check the communication-related parameters.

Check the specificationsof communication

devices.

Check thecommunication wiring.

Communicationfailure?

No Withcommuni-

cation?

Yes

Yes

Normal?Is the

key locked?

Check the specificationsof the controller.

Yes

NoCorrect?

Correct the error(s).

Cancel the setting.

Check the I/O specificationsof the controller.

* The LCD (a liquid crystal display) is used for a display portion of this product. The LCD has a characteristic that the display action becomes late at the low temperature. Additionally, the luminance and contrast degradation are caused due to aged deterioration. However, the control function is not affected.

Remedies if Power Failure Occurs during Operations• Instantaneouspowerfailurewithin20ms. Apower failure isnotdetected.Normal

operation continues.• Powerfailureforlessthanabout5seconds,orforabout5secondsormore.

Affectsthe"settings"and"operationsta-tus."

For detai ls , see User 's Manual ( IM05P01C31-01EN).

NOTEWritedownthesettingsofparameters forarepairrequest.

n Errors at Power OnTheerrorsshownbelowmayoccurinthefaultdiagnosiswhenthepoweristurnedon.(FordetailsofSetpointdisplayandinput/outputactionwheneacherroroccurs,seeUser’sManual(IM05P01C31-01EN).)

PV display (Operation

Display)Setpoint display

(Operation Display)Status indicator

(Operation Display)Parameter that displays error

details Error description Cause and diagnosis Remedy

Indicationoff Indicationoff — — FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty. Contactusforrepair.

ERR

SYS-----

— System data error System data is corrupted. Faulty. Contactusforrepair.

PAR0004 (foruserdefaultvalueerroronly)

Setupparameter(PA.ER)

User(parameter)defaultvalueerror

Userparameteriscorrupted.Initializedtofactorydefaultvalue.

Checkandreconfiguretheinitializedsettingparameters.Errorindicationiserased when the power is turned on again.

PAR0010(forsetupparametererroronly)

Setup parameter error Setup parameter data is corrupted.Initializedtouserdefaultvalue.

PAR0020(foroperationparametererroronly) Operationparametererror Operationparameterdataiscorrupted.

Initializedtouserdefaultvalue.

SLOT0017(0017:ErroroccurstoallhardwareofE1toE4-terminalareas.)

Setupparameter(OP.ER)Nonrespondinghardwareofextendedfunction(E1toE4-terminalareas)

Inconsistence of system data and hardwareofextendedfunction.Nonrespondingcommunicationbetweenhardwareofextendedfunction(E1toE4-terminalareas).

Faulty.Contactusforrepair.

Normalindication Normalindication

RightmostdecimalpointonPVdisplayblinks.

Setupparameter(PA.ER)Calibrationvalueerror Initializedtocalibrateddefaultvaluebecause

ofcorruptedfactorydefaultvalue. Faulty.Contactusforrepair.Rightmostdecimalpoint

onSymboldisplayblinks. FaultyFRAM Datawriting(storing)toFRAMisimpossible.

Normalindication Normalindication LADDERlampblinks Setupparameter(LA.ER) Corruptedladderprogram Ladderprogramiscorrupted.

Operateswithoutladderprogram. Downloadtheladderprogramagain.

Normalindication

0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)

— Setupparameter(OP.ER) Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.

n Errors during OperationTheerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual(IM05P01C31-01EN).)

PV display (Operation

Display)Setpoint display

(Operation Display)Status indicator

(Operation Display)Parameter that displays

error details Error description Cause and diagnosis Remedy

AD.ERR Normalindication(Note) — Setupparameter(AD1.E)

AnaloginputterminalADCerror•PVinput•RSPinput(E1-terminalarea)•AIN2input(E2-terminalarea)•AIN4input(E4-terminalarea)

AnaloginputterminalADvalueerror Faulty.Contactusforrepair.

RJC.E(DisplaysRJC.EandPValternately.)

Normalindication(Note) — Setupparameter(AD1.E)UniversalinputterminalRJCerror•PVinput•RSPinput(E1-terminalarea)

UniversalinputterminalRJCerror

Faulty.Contactusforrepair.SettheparameterRJCtoOFFtoeraseerror indication.

B.OUT Normalindication(Note) —

Setupparameter(AD1.E)

Analoginputterminalburnouterror•PVinput•RSPinput(E1-terminalarea)•AIN2input(E2-terminalarea)•AIN4input(E4-terminalarea)

AnaloginputterminalsensorburnoutCheckwiringandsensor.Errorindicationiserasedinnormaloperation.

Setupparameter(PV1.E/PV2.E) PVinputburnouterror(Loop1,Loop2) BurnoutofanaloginputconnectedtoPV

Checkwiringandsensorofconnectedanaloginputterminals.Errorindicationiserasedinnormaloperation.

OVER-OVER Normalindication — Setupparameter(PV1.E/PV2.E)

PVinputover-scalePVinputunder-scale(PVvaluesoutof-5to105%)(Loop1,Loop2)

PVinputisoutof-5to105%.Alsooccurswhenthedataoutofrangewhichistheladder calculation result is input.

Checkanaloginputvalueorladderprogram.

Normalindication Normalindication — Setupparameter(PV1.E/PV2.E) RSPinputburnouterror(Loop1,Loop2) BurnoutofanaloginputconnectedtoRSP Checkwiringandsensor.Error

indication is erased in normal operation.Normalindication RSPB.OUT — Setupparameter(PV1.E/PV2.E) BurnouterrorwhenRSPinputisusedforcontrol(Loop1,Loop2)

BurnoutofanaloginputconnectedtoRSPwhenRSPisusedforcontrolcomputation

Checkwiringandsensor.Errorindication is erased in normal operation.

Normalindication OUT----- — Setupparameter(AD2.E) Feedbackinputresistor/current

burnout FeedbackinputburnoutCheckwiringoffeedbackinputresistor/current.Errorindicationiserasedinnormal operation.

Normalindication

Normalindication LADDERlampblinks Setupparameter(LA.ER)

Laddercalculationoverflow Floatingpointcomputationforladdercalculationisinfinite. Checktheladderprogram.

Loadfactorover100%Computationdoesnotendwithinthecontrolperiod(loadfactoris100%ormore).

Changethecontrolperiodorreducethenumberofstepsfortheladderprogram.

Loadfactorover200%(Forcedend)

Computationdoesnotendwithinthecontrolperiod(loadfactoris200%ormore).

Changethecontrolperiodorreducethenumberofstepsfortheladderprogram.

Ladderprogramerror Ladderprogramiscorrupted.Downloadtheladderprogramagain.Iftheerrorindicationisstillnoterased,thereisafault.Contactusforrepair.

0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)

— Setupparameter(OP.ER) Peer-to-peercommunicationerror Peer-to-peercommunicationerrorCheckthatthetargetdevicesareconnected correctly.Recoveryatnormalreceipt.

AT.E Normalindication — Setupparameter(PV1.E/PV2.E) Auto-tuningtime-out(Loop1,Loop2)

Auto-tuningdoesnotendevenwhen24hourshaveelapsedafterthestartoftuning.

Checktheprocess.Holddownanykeytoerase the error indication

VAT.E Normalindication — Setupparameter(AD2.E) Valvepositionautomaticadjustmenterror

Fully-closedvalvepositionisequaltoorlargerthanthefully-openvalvepositionafterautomaticvalvepositionadjustmentisperformed.

Checkwiringandvalve.Holddownanykey to erase the error indication.

Normalindication

0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)

— Setupparameter(OP.ER) Communicationerror(RS-485communication)

FramingparityerrorBufferoverflowInter-charactertime-outChecksumerror(PClinkcommunicationwithchecksum)CRCcheckerror(Modbus/RTU)LRCcheckerror(Modbus/ASCII)

Checkthecommunicationparameters.Recoveryatnormalreceipt.Holddownanykeytostopblinking.

Normalindication

0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)

— Setupparameter(OP.ER) Communicationerror(coordinatedoperation)

Inconsistenceofloopbetweencoordinatedmasterandslaves

Checkthecommunicationparameters.Recoveryatnormalreceipt.Changefromremotetolocalmodetostopblinking.Whenthemodeischangedfromremotetolocal,SPtrackingdoesnotworkevenifitissettoON.

Communicationfromcoordinatedmasterisinterrupted for 2 seconds.

Normalindication

0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)

— Setupparameter(OP.ER) Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.

Normalindication Normalindication Rightmostdecimalpointon

Symboldisplayblinks. Setupparameter(PA.ER) FaultyFRAM Writing(storing)datatoFRAMisimpossible. Faulty.Contactusforrepair.

Undefined Undefined — — FaultyMCU/DCU(ROM/RAMerror,corrupted) MCU/DCUiscorrupted. Faulty.Contactusforrepair.

Note:WhenanerroroccursininputshowninAnaloginputdisplay(Operationdisplay),SetpointdisplayshowsthesamesymbolasthePVdisplay.

Page 9: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 9/12

Operation ParametersHolddownthePARAMETERkeyorPARAkeyfor3secondstomovefromtheOper-ationDisplaytotheOperationParameterSettingDisplay.PresstheDISPLAYkeyorDISPkeyoncetoreturntotheOperationDisplay.

Menu

Hold down PARAMETER key or PARA keyfor 3 sec.

DISPLAY keyor DISP key

SET/ENTER key PARAMETER keyor PARA key

key key key

key key

The parameter groups can be switched using , keys.

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

ParameterEND

Menu

END

Menu END

END

Menu D isp lay and Parameter Set t ing Display are changed in a circular pattern.

Move to the Setup Parameter Setting Display: Hold down the PARAMETER key or PARA key and the Left arrow key simultaneously for 3 sec.

Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.

· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.

Notethattherearesomeparameterswhicharenotdisplayeddependingonthemodelandsuffixcodes,controlmode(CTLM),control type(CNT),etc.Theparametersforprofessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual(IM05P01C31-01EN).

Operation ModeMenusymbol: (MODE)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(S.R)STOP/RUNswitch

STOP:Stopmode RUN:Runmode Presetoutput(PO)isgeneratedinSTOPmode. Default:Notdisplayed.STOP/RUNswitchisassignedtocontactinput.

RUN

EASY

(R.L)REMOTE/LOCALswitch

LCL:Localmode REM:Remotemode Select a remote input method for acquiringthetargetsetpointfromremoteinputorcommunicationusingtheparameterRMS.

LCL

(AT)AUTO-tuningswitch

OFF:Disable 1to8:Performauto-tuning.Tuningresultisstoredinthespecifiednum-beredPID. R:TuningresultisstoredinthePIDforreferencedeviation.

OFF

(SPNO.)SPnumberselection 1to8(Dependsonthesetupparam-

eterSPGR.setting.) 1

(PID)PIDnumber

ThePIDgroupnumberbeingselectedis displayed. 1to8,R:PIDgroupforreferencedeviation

1

SELECT ParameterMenusymbol: (CS)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

Registeredparameter symbol

SELECTparameter10to19

Settingrangeofaregisteredparame-ter.Fordetails,seeUser'sManual(IM05P01C31-01EN).

— Tablebelow EASY

Parameter n=10 n=11 n=12 n=13 n=14 n=15 n=16 n=17 n=18 n=19

CSn

FortheregistrationofSELECTparameters,seeUser'sManual(IM05P01C31-01EN).

SP and Alarm Setpoint Setting ParameterMenusymbol: (SP)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(SP)Targetsetpoint 0.0to100.0%ofPVinputrange(EU)

(Settingrange:SPLtoSPH) SPL

Tablebelow EASY

(SUB)

Sub-targetsetpoint(inTwo-positiontwo-levelcontrol)

SettheoffsetfromSP.-100.0to100.0%ofPVinputrangespan(EUS)

0.0%ofPVinput rangespan

(PIDN)PIDnumberselection

SetaPIDgroupnumbertouse.1to8(Dependsonthesetupparam-eterPIDG.setting.)

1to8

to

(A1toA8)

Alarm-1to-8setpoint

SetadisplayvalueofsetpointofPValarm,SPalarm,deviationalarm,outputalarm,orvelocityalarm.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinput type

0

FortheparameterSP(targetsetpoint),8groupsaredisplayedforthefactorydefault.ThenumberofgroupscanbechangedbythesetupparameterSPGR.(numberofSPgroups).Forthealarmsetpointparameter,alarm-1to-4aredisplayedfor thefactorydefault.Thenumberofalarmscanbechangedusing thesetupparameterALNO.(numberofalarms).TochangethenumberofSPgroupsoralarms,seeUser'sManual(IM05P01C31-01EN).UsethefollowingtabletorecordSPandalarmsetpoints.

Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7 n=8

SP

SUB

PIDN

A1

A2

A3

A4

A5

A6

A7

A8

n:groupnumber

SP-related Setting Parameter Menusymbol: (SPS)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(RMS)Remoteinputmethod

RSP:Viaremote(auxiliaryanalog)input

COM:ViacommunicationRSP

STD

(RFL)Remoteinputfilter OFF,1to120s OFF

(RT)Remoteinputratio

SP=RemoteinputxRT+Remoteinputbias 0.001to9.999

1.000

(RBS)Remoteinputbias -100.0to100.0%ofPVinputrange

span(EUS)

0.0%ofPVinput rangespan

(UPR)SPramp-uprate

UsedtopreventSPfromchangingsuddenly.Setaramp-uprateorramp-downrateper hour or minute. Set a time unit usingtheparameterTMU.OFF,0.0+1digitto100.0%ofPVinputrangespan(EUS)

OFF

EASY(DNR)SPramp-downrate OFF

(TMU)SPramp-ratetimeunit

HOUR:Ramp-uprateorramp-downrate per hourMIN:Ramp-uprateorramp-downrate per minute

HOUR

(SPT)SPtrackingselection

TrackingisperformedwhenthemodechangesfromRemotetoLocal.(Thelocal setpoint keeps track of the remotesetpoint.)OFF,ON

ON

STD

(PVT)PVtrackingselection

CausesthesetpointtokeeptrackofthePVsothesetpointautomaticallyrevertstoitsoriginalvalueatapresetrateofchange.TheUPR,DNR,andTMUareusedincombination.Operatingconditions:1)MAN→AUTO,2)STOP→AUTO,3)Power-on,4)SPnumberchange,5)SPchangeOFF,ON

OFF

Alarm Function Setting ParameterMenusymbol: (ALRM)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

to

(AL1toAL8)

Alarm-1to8typeExample:Alarm-1

Stand-by action

Latch actionEnergized/De-energize

Alarm type

Seta5-digitvalueinthefollowingorder.[Latchaction(0/1/2/3/4)]+[Energized(0)orDe-energized(1)]+[Without(0)orWith(1)Stand-byaction]+[Alarmtype:2digits(seebelow)]Forlatchaction,seeUser'sManual(IM05P01C31-01EN).

AL1, AL3, AL5, AL7: Latchaction (0)

PVhighlimit(01) WithoutStand-by

action (0)

Ener-gized(0)

AL2,AL4, AL6, AL8:Latchaction (0)

Ener-gized(0)

WithoutStand-by

action (0)

PVlowlimit(02)

AL5toAL8:notdisplayed

for factory default

Tablebelow

EASY

Alarmtype:2digits00:Disable01:PVhighlimit02:PVlowlimit03:SPhighlimit04:SPlowlimit05:Deviationhighlimit06:Deviationlowlimit07:Deviationhighandlowlimits08:Deviationwithinhighandlowlimits09:TargetSPhighlimit10:TargetSPlowlimit11:TargetSPdeviationhighlimit12:TargetSPdeviationlowlimit13:TargetSPdeviationhighandlowlimits14:TargetSPdeviationwithinhigh

and low limits15:OUThighlimit16:OUTlowlimit17:Cooling-sideOUThighlimit18:Cooling-sideOUTlowlimit19:AnaloginputPVhighlimit20:AnaloginputPVlowlimit21:AnaloginputRSPhighlimit22:AnaloginputRSPlowlimit23:AnaloginputAIN2highlimit24:AnaloginputAIN2lowlimit25:AnaloginputAIN4highlimit26:AnaloginputAIN4lowlimit27:Feedbackinputhighlimit28:Feedbackinputlowlimit29:PVvelocity30:Faultdiagnosis31:FAIL32:Deviation(%)highlimit33:Deviation(%)lowlimit34:Deviation(%)highandlowlimits35:Deviation(%)withinhighandlow

limits36:TargetSPdeviation(%)highlimit37:TargetSPdeviation(%)lowlimit38:TargetSPdeviation(%)highand

low limits39:TargetSPdeviation(%)withinhigh

and low limits

to

(VT1toVT8)

PVvelocityalarmtimesetpoint1to8 0.01to99.59(minute.second) 1.00

to

(HY1toHY8)

Alarm-1to-8hysteresis

Setadisplayvalueofsetpointofhysteresis.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinputtype.Whenthedecimalpointpositionfortheinputtypeissetto"1",theinitialvalueofthehysteresisis"1.0".

10

to

(DYN1toDYN8)

Alarm-1to-8On-delaytimer

AnalarmoutputisONwhenthedelaytimerexpiresafterthealarmsetpointis reached.0.00to99.59(minute.second)

0.00

STD

(AMD)Alarmmode

0:Alwaysactive1:NotactiveinSTOPmode2:NotactiveinSTOPorMANmode

0

Forthealarmfunctionsettingparameter,4alarmsaredisplayedforthefactorydefault.Thenumberofalarmscanbechangedby thesetupparameterALNO. (numberofalarms).Tochangethenumberofalarms,seeUser'sManual(IM05P01C31-01EN).Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7 n=8

ALn

VTn

HYn

DYNn

n:alarmnumber

PV-related Setting Parameter Menusymbol: (PVS)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(BS)PVinputbias -100.0to100.0%ofPVinputrange

span(EUS)

0.0%ofPVinput rangespan EASY

(FL)PVinputfilter OFF,1to120s OFF

PID Setting ParameterMenusymbol: (PID)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(P)

Proportionalband Heating-sideproportion-alband(inHeating/cool-ingcontrol)

0.0to999.9% When0.0%isset,itoperatesas0.1%. Heating-sideON/OFFcontrolapplieswhen0.0%inHeating/coolingcontrol

5.0%

EASY

(I)

Integraltime Heating-sideintegraltime(inHeating/coolingcontrol)

OFF:Disable 1to6000s 240s

(D)

Derivativetime Heating-sidederivativetime(inHeating/coolingcontrol)

OFF:Disable 1to6000s 60s

(OH)

Controloutputhighlimit Heating-sidecontroloutputhighlimit(inHeating/coolingcontrol)

-4.9to105.0%,(OL<OH) InHeating/coolingcontrol:0.1to105.0%(OL<OH)

100.0%

(OL)

Controloutputlowlimit Heating-sidecontroloutputlowlimit(inHeat-ing/coolingcontrol)

-5.0to104.9%,(OL<OH),SD:Tightshut InHeating/coolingcontrol:0.0to104.9%(OL<OH)

0.0%

(MR)Manual reset

EnabledwhenintegraltimeisOFF. ThemanualresetvalueequalstheoutputvaluewhenPV=SP. -5.0to105.0%

50.0%

(HYS)

Hysteresis(inON/OFFcontrol,Positionproportionalcontrol,orTwo-positiontwo-levelcontrol) Heating-sideON/OFFcontrolhysteresis(inHeating/coolingcontrol)

InON/OFFcontrolorTwo-po-sitiontwo-levelcontrol:0.0to100.0%ofPVinputrangespan(EUS)

InHeating/coolingcontrolorPositionproportionalcontrol:0.0to100.0%

InON/OFFcontrol

or Two-positiontwo-levelcontrol:0.5%ofPVinput

rangespan

InHeating/coolingcontrol

orPosition

proportionalcontrol:0.5%

(SU.HY)

Sub-hysteresis(inTwo-positiontwo-levelcontrol)

0.0to100.0%ofPVinputrangespan(EUS)

0.5%ofPVinput

rangespan

(HY.UP)Upper-sidehysteresis(inON/OFFcontrol)

0.5%ofPVinput

rangespan

(HY.LO)Lower-sidehysteresis(inON/OFFcontrol)

0.5%ofPVinput

rangespan

(DR)Direct/reverseactionswitch

RVS:ReverseactionDIR:Directaction

RVS

STD

(SU.DR)

Sub-direct/reverseactionswitch(inTwo-positiontwo-levelcontrol)

DIR

(Pc)Cooling-sidepropor-tionalband

0.0to999.9% (Cooling-sideON/OFFcontrolapplieswhen0.0%inHeating/coolingcontrol)

5.0%

EASY

(Ic)Cooling-sideintegraltime

OFF:Disable 1to6000s 240s

(Dc)Cooling-sidederivativetime

OFF:Disable 1to6000s 60s

(OHc)Cooling-sidecontroloutputhighlimit 0.1to105.0%,(OLc<OHc) 100.0%

(OLc)Cooling-sidecontroloutput low limit 0.0to104.9%,(OLc<OHc) 0.0%

(HYSc)Cooling-sideON/OFFcontrol hysteresis 0.0to100.0% 0.5%

(DB)

Outputdeadband(inHeating/coolingcontrolor Position proportional control)

InHeating/coolingcontrol:-100.0to50.0% InPositionproportionalcontrol:1.0to10.0%

3.0%

(PO)

Preset output Heating-sidepresetoutput(inHeating/cool-ingcontrol)

InSTOPmode,fixedcontroloutputcanbegenerated.InPositionproportionalcontrol,Valveopeningcanbeset;-5.0to105.0%

0.0%

(SU.PO)

Sub-presetoutput(inTwo-positiontwo-levelcontrol)

InSTOPmode,fixedsub-controloutputcanbegenerated. 0%,100%

0%

(POc)Cooling-sidepresetoutput

InSTOPmode,cooling-sidefixedcontroloutputcanbegenerated. -5.0to105.0%

0.0%

ForthePIDsettingparameter,8groupsaredisplayedforthefactorydefault.ThenumberofgroupscanbechangedbythesetupparameterPIDG.(numberofPIDgroups).Tochange thenumberofPIDgroups,seeUser'sManual (IM05P01C31-01EN).

OperationGuide

UT55A, UT52ADigital Indicating Controller (Panel Mounting Type)Operation Guide for Single-loop Control

Yokogawa Electric Corporation

Parameters

For details of the each function, refer to the electronic manual. Manuals can be downloaded or viewed at the following URL.

Functional

Enhancement

This operation guide describes the functions of parameters briefly. The parameter symbols listed are in the order shown on the display in each group of menu symbols. In addition, each parameter table has a “User Setting” column, where you can record your setpoints when setting them in the controller. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.

http://www.yokogawa.com/ns/ut/im/

«Standard Code Model»

Page 10: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 10/12

IfyouareusingtwoormoregroupsofPIDparameters,usethefollowingtabletorecordtheirsettingvalues.

Parameter n=2 n=3 n=4 n=5 n=6 n=7 n=8 R

P

I

D

OH

OL

MR

HYS

SU.HY

HY.UP

HY.LO

DR

SU.DR

Pc

Ic

Dc

OHc

OLc

HYSc

DB

PO

SU.PO

POc

n:groupnumber

Tuning Parameter Menusymbol: (TUNE)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(SC)Super function

OFF:Disable1:Overshootsuppressingfunction

(normalmode)2:Huntingsuppressingfunction

(stablemode) Enablestoanswerthewidercharacteristicchangescomparedwith response mode.

3:Huntingsuppressingfunction(responsemode) Enablesquickfollow-upandshortconvergingtimeofPVforthechangedSP.

4:Overshootsuppressingfunction(strongsuppressingmode) Note:Setpoints2and3mustbeusedinPIDcontrolorPIcontrol.Disabledinthefollowingcontrols: 1)ON/OFFcontrol,2)PDcontrol,3)Pcontrol,4)Heating/coolingcontrol. Donotusethefunctionforthecontrol processes with response suchasfloworpressurecontrol.

OFF EASY

(AT.TY)Auto-tuningtype 0:Normal

1:Stability 0 STD

(STM)Sample PI sampled time 0to9999s 60s

EASY

(SWD)Sample PI control time span 0to9999s 30s

(AR)

Anti-resetwindup(excessintegrationprevention)

AUTO,50.0to200.0% AUTO

STD

(OPR)Outputvelocitylimiter OFF:Disable

0.1to100.0%/s OFF

(MPON)Manual preset output numberselection

SelecttheoutputusedinMANmodewhenswitchedfromAUTOtoMANmode.OFF:HoldthecontroloutputinAUTO

mode(bumpless)1:Usemanualpresetoutput1(outputbump)2:Usemanualpresetoutput2(outputbump)3:Usemanualpresetoutput3(outputbump)4:Usemanualpresetoutput4(outputbump)5:Usemanualpresetoutput5(outputbump)

OFF

to

(MPO1toMPO5)

Manual preset output 1 to 5

-5.0to105.0%However,outputislimitedtotheoutputhighlimitandlowlimit.

0.0% Tablebelow

Usethefollowingtabletorecordthemanualpresetoutputsettingvalue.

Parameter n=1 n=2 n=3 n=4 n=5

MPOn

Zone Control ParameterMenusymbol: (ZONE)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

to

(RP1toRP7)

Referencepoint1to7

Set reference points at which switch-ingiscarriedoutbetweengroupsofPIDconstantsaccordingtothegiventemperaturezone.0.0to100.0%ofPVinputrange(EU) (RP1≤RP2≤RP3≤RP4≤RP5≤RP6≤RP7)

100.0%ofPVinput range

Tablebelow

STD

(RHY)ZonePIDswitchinghysteresis

Hysteresiscanbesetforswitchingata reference point.0.0to10.0%ofPVinputrangespan(EUS)

0.5%ofPVinput rangespan

(RDV)Referencedeviation

SetadeviationfromSP.ThePIDforreferencedeviationisusedifthereisalargerdeviationthanthepresetreferencedeviation.OFF:Disable0.0+1digitto100.0%ofPVinputrangespan(EUS)

OFF STD

ForZonecontrol,set thesetupparameterZON(zonePIDselection) toZonePID selection.Usethefollowingtabletorecordthereferencepointsettingvalue.

Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7

RPn

P Parameter (for Ladder Program)Menusymbol: (PPAR)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

to

(P01toP10)

P01toP10parameter-19999to30000(SetadecimalpointpositionusingLL50AParameterSet-tingSoftware.)

0 Tablebelow STD

Parameter n=01 n=02 n=03 n=04 n=05 n=06 n=07 n=08 n=09 n=10

Pn

10-segment Linearizer-1, -2 Setting ParameterMenusymbol: (PYS1) (PYS2)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(PYS)10-segmentlinearizerselection

OFF:DisablePV:PVanaloginputRSP:RSPanaloginputAIN2:AIN2analoginputAIN4:AIN4analoginputPVIN:PVinputOUT:OUTanalogoutputOUT2:OUT2analogoutputRET:RETanalogoutput

PV (CTLM:SGL)

STD

(A1)10-segmentlinearizerinput 1

-66.7to105.0%ofinputrange(EU)Outputlinearizer:-5.0to105.0% 0.0%

(B1)10-segmentlinearizeroutput 1

10-segmentlinearizerbias:-66.7to105.0%ofinputrangespan(EUS)10-segmentlinearizerapproximation:-66.7to105.0%ofinputrange(EU)Outputlinearizer:-5.0to105.0%

0.0%

to ,

to

(A2toA11,B2toB11)

10-segmentlinearizerinput 2 to 11 10-segmentlinearizeroutput 2 to 11

SameasA1andB1

Same asA1andB1

(PMD)10-segmentlinearizermode

0:10-segmentlinearizerbias1:10-segmentlinearizer

approximation0

Usethefollowingtabletorecordthe10-segmentlinearizerinputandoutputsettingvalues.

Parameter n=2 n=3 n=4 n=5 n=6 n=7 n=8 n=9 n=10 n=11

An

Bn

Setup ParametersHolddownthePARAMETERkeyorPARAkeyandLeftarrowkeysimultaneouslyfor3secondstomovefromtheOperationDisplayorOperationParameterSettingDisplaytotheSetupParameterSettingDisplay.PresstheDISPLAYkeyorDISPkeyoncetoreturntotheOperationDisplay.

Menu

DISPLAY keyor DISP key

SET/ENTER key PARAMETER keyor PARA key

key key key

key key

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

ParameterEND

Menu

END

Menu END

END

Menu D isp lay and Parameter Set t ing Display are changed in a circular pattern.

Move to the Operation Parameter Setting Display: Hold down the PARAMETER key or PARA key for 3 sec.

Hold down PARAMETER key or PARA key and Left arrow key simultaneously for 3 sec.

Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.

· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.

NotethattherearesomeparameterswhicharenotdisplayeddependingontheModelandSuffixcodes,controlmode(CTLM),control type(CNT),etc.Theparameters forprofessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual(IM05P01C31-01EN).

Control Function Setting ParameterMenusymbol: (CTL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(CTLM)Controlmode

WhenusingthecontrolsotherthanSingle-loopcontrol,seeUser'sManual(IM05P01C31-01EN).

SGL STD

SGL:Single-loopcontrolCAS1:Cascadeprimary-loopcontrolCAS2:Cascadesecondary-loop

controlCAS:CascadecontrolBUM:LoopcontrolforbackupPVSW:LoopcontrolwithPVswitchingPVSEL:LoopcontrolwithPVauto-

selectorPVHD:LoopcontrolwithPV-hold

function

(CNT)Controltype

PID:PIDcontrolONOF:ON/OFFcontrol(1pointofhysteresis)

ONOF2:ON/OFFcontrol(2pointsofhysteresis)

2P2L:Two-positiontwo-levelcontrolH/C:Heating/coolingcontrolS-PI:SamplePIcontrolBATCH:BatchPIDcontrolFFPID:Feedforwardcontrol

PID or H/C (for

Heat-ing/

Coolingtype)

EASY

(SPGR.)NumberofSPgroups SetanumberofSPgroupstouse.

1to8 8

STD(ZON)

ZonePIDselection

Ifsetto“SPgroupnumberselection,”allowsPIDconstantstobeselectedforeachSPgroup. Ifsetto“ZonePIDselection,”automaticallyselectsPIDconstantsaccordingtotherangesetintheReferencepoint.0:SPgroupnumberselection11:ZonePIDselection(selectionbyPV)2:ZonePIDselection(selectionbytargetSP)

3:SPgroupnumberselection24:ZonePIDselection(selectionbySP)

0

(PIDG.)NumberofPIDgroups SetanumberofPIDgroupstouse.

1to8 8

(SMP)Inputsamplingperiod(controlperiod) 50:50ms,100:100ms,200:200ms 100

PV Input Setting ParameterMenusymbol: (PV)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(IN)PVinputtype

OFF:DisableK1:-270.0to1370.00C/-450.0to2500.0 0FK2:-270.0to1000.00C/-450.0to2300.0 0FK3:-200.0to500.00C/-200.0to1000.0 0FJ:-200.0to1200.00C/-300.0to2300.0 0FT1:-270.0to400.00C/-450.0to750.0 0FT2:0.0to400.00C/-200.0to750.0 0FB:0.0to1800.00C/32to3300 0FS:0.0to1700.00C/32to3100 0FR:0.0to1700.00C/32to3100 0FN:-200.0to1300.00C/-300.0to2400.0 0FE:-270.0to1000.00C/-450.0to1800.0 0FL:-200.0to900.00C/-300.0to1600.0 0FU1:-200.0to400.00C/-300.0to750.0 0FU2:0.0to400.00C/-200.0to1000.0 0FW:0.0to2300.00C/32to4200 0FPL2:0.0to1390.00C/32.0to2500.0 0FP2040:0.0to1900.00C/32to3400 0FWRE:0.0to2000.00C/32to3600 0FJPT1:-200.0to500.00C/-300.0to1000.0 0FJPT2:-150.0to150.00C/-200.0to300.0 0FPT1:-200.0to850.00C/-300.0to1560.0 0FPT2:-200.0to500.00C/-300.0to1000.0 0FPT3:-150.00to150.000C/-200.0to300.0 0F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV

OFF

EASY

(UNIT)PVinputunit

-:Nounit,C:DegreeCelsius-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit

C

(RH)MaximumvalueofPVinputrange

Dependsontheinputtype.-Fortemperatureinput-Setthetemperaturerangethatisactuallycontrolled.(RL<RH)-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallycontrolledshouldbesetusingthemaximumvalueofinputscale(SH)andmini-mumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)

Dependson the

input type

(RL)MinimumvalueofPVinputrange

Dependson the

input type

(SDP)PVinputscaledecimalpoint position

0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces

Dependson the

input type

EASY

(SH)MaximumvalueofPVinput scale

-19999to30000,(SL<SH),|SH-SL|≤30000

Dependson the

input type

(SL)MinimumvalueofPVinput scale

Dependson the

input type

(BSL)PVinputburnoutaction

OFF:DisableUP:UpscaleDOWN:Downscale

Dependson the

input type

STD(A.BS)

PVanaloginputbias -100.0to100.0%ofPVinputrangespan(EUS)

0.0%ofPVinputrangespan

(A.FL)PVanaloginputfilter OFF,1to120s OFF

W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988,WRE:W97Re3-W75Re25

RSP Input Setting Parameter (E1-terminal Area)Menusymbol: (RSP)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(IN)RSPremoteinputtype

0.4-2V:0.400to2.000V1-5V:1.000to5.000V0-2V:0.000to2.000V0-10V:0.00to10.00V0-125:0.000to1.250VForoption/DR,RSPremoteinputtypeissameasPVinputtype

1-5V

EASY

(UNIT)RSPremoteinputunit

-:Nounit,C:DegreeCelsius-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit

C

(RH)MaximumvalueofRSPremoteinputrange

Dependsontheinputtype.-Fortemperature(/DRoption)input-Setthetemperaturerangethatisactuallycontrolled.(RL<RH)-Forvoltage/current(/DRoption)input-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallycontrolledshouldbesetusingthemaximumvalueofinputscale(SH)andmini-mumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)

Dependson the

input type

(RL)MinimumvalueofRSPremoteinputrange

Dependson the

input type

(SDP)RSPremoteinputscaledecimal point position

0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces

Dependson the

input type

(SH)MaximumvalueofRSPremote input scale -19999to30000,(SL<SH),

|SH-SL|≤30000

Dependson the

input typeEASY

(SL)MinimumvalueofRSPremote input scale

(BSL)RSPremoteinputburn-out action

OFF:DisableUP:UpscaleDOWN:Downscale

Dependson the

input typeSTD

(RTD.S)RTDwiringsystem

3-W:3-wiresystem4-W:4-wiresystem(TheLL50AParameterSettingSoftwareisrequiredtouseRSPterminalsinputasPV.)

3-W

AIN2/AIN4 Aux. Analog Input Setting Parameter (E2/E4-terminal Area)

Menusymbol: (AIN2) (AIN4)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(IN)AIN2/AIN4aux.analoginput type

0.4-2V:0.400to2.000V1-5V:1.000to5.000V0-2V:0.000to2.000V0-10V:0.00to10.00V0-125:0.000to1.250V

1-5V

EASY

(UNIT)AIN2/AIN4aux.analoginput unit

-:NounitC:DegreeCelsius -:Nounit--:Nounit---:Nounit F:DegreeFahrenheit

C

(RH)

MaximumvalueofAIN2/AIN4aux.analoginputrange

Dependsontheinputtype.Settherangeofavoltagesignalthatis applied.Thescaleacrosswhichthevoltagesignalisactuallycontrolledshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)

Dependson the

input type

(RL)

MinimumvalueofAIN2/AIN4aux.analoginputrange

(SDP)

AIN2/AIN4aux.analoginput scale decimal point position

0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces

Dependson the

input type

(SH)MaximumvalueofAIN2/AIN4aux.analoginputscale -19999to30000,(SL<SH),

|SH-SL|≤30000

Dependson the

input type(SL)

MinimumvalueofAIN2/AIN4aux.analoginputscale

(BSL)AIN2/AIN4aux.analoginputburnoutaction

OFF:DisableUP:UpscaleDOWN:Downscale

Dependson the

input typeSTD

Page 11: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 11/12

Input Range, SP Limiter Setting ParameterMenusymbol: (MPV)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(P.UNI)ControlPVinputunit

-:NounitC:DegreeCelsius-:Nounit--:Nounit---:NounitF:DegreeFahrenheit

Same asPVinput unit

STD

(P.DP)ControlPVinputdecimalpoint position

0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces

Dependson the

input type

(P.RH)MaximumvalueofcontrolPVinputrange -19999to30000,(P.RL<P.RH),

|P.RH-P.RL|≤30000

Dependson the

input type(P.RL)

MinimumvalueofcontrolPVinputrange

(SPH)SPhighlimit

0.0to100.0%ofPVinputrange(EU),(SPL<SPH)

100.0%ofPVinput range

(SPL)SP low limit

0.0%ofPVinput range

Output Setting ParameterMenusymbol: (OUT)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(OT)

Outputtypeselection

Upper two digits

Lower two digits

ControloutputorHeating-sidecontroloutput(Lowertwodigits)00:OFF01:OUTterminals(voltagepulse)02:OUTterminals(current)03:OUTterminals(relay)04:OUT2terminals(voltagepulse)05:OUT2terminals(current)06:OUT2terminals(relay)

Cooling-sidecontroloutput(Uppertwodigits)00:OFF01:OUTterminals(voltagepulse)02:OUTterminals(current)03:OUTterminals(relay)04:OUT2terminals(voltagepulse)05:OUT2terminals(current)06:OUT2terminals(relay)

Standard type:00.03

Heating/coolingtype:06.03

EASY

(CT)

Controloutputcycletime Heating-sidecontroloutputcycletime(inHeating/coolingcontrol)

0.5to1000.0s

30.0s

EASY

(CTc)Cooling-sidecontroloutput cycle time 30.0s

(V.AT)Automaticvalvepositionadjustment

OFF:StopautomaticadjustmentON:Startautomaticadjustment OFF

(V.RS)Valvepositionsettingreset

SettingV.RStoONresetsthevalveadjustmentsettingsandcausestheindication“V.RS”toblink.

OFF

(V.L)Fully-closedvalveposi-tionsetting

PressingtheSET/ENTERkeywithvalvepositionsettothefully-closedpositionbyDownarrowkeycausestheadjustedvaluetobestored.WhenV.Ladjustmentiscomplete,V.Lstopsblinking.

-

(V.H)Fully-openedvalveposi-tionsetting

PressingtheSET/ENTERkeywithvalvepositionsettothefully-openedpositionbyUparrowkeycausestheadjustedvaluetobestored.WhenV.Hadjust-mentiscomplete,V.Hstopsblinking

-

(TR.T)Valvetravelingtime 5to300s 60s

STD

(V.MOD)Valveadjustingmode

0:Valvepositionfeedbacktype1:Valvepositionfeedbacktype(movestotheestimatingtypeifafeedbackinputerrororbreakoccurs.)2:Valvepositionestimatingtype

0

(RTS)RetransmissionoutputtypeofRET

OFF:DisablePV1:PVSP1:SPOUT1:OUT(Valveopening:0to100%inPositionproportionalcontrol)LPS:15VDClooppowersupplyPV2:Loop-2PVSP2:Loop-2SPOUT2:Loop-2OUTTSP1:TargetSPHOUT1:Heating-sideOUTCOUT1:Cooling-sideOUTMV1:Positionproportionaloutput(internalcomputedvalue)TSP2:Loop-2targetSPHOUT2:Loop-2heating-sideOUTCOUT2:Loop-2cooling-sideOUTMV2:Loop-2positionproportionaloutput(internalcomputedvalue)PV:PVterminalsanaloginputRSP:RSPterminalsanaloginputAIN2:AIN2terminalsanaloginputAIN4:AIN4terminalsanaloginput*Loop-2settingvaluesareunavailable inSingle-loopcontrol.

PV1 EASY

(RTH)

Maximumvalueofretransmission output scaleofRET

WhenRTS=PV1,SP1,PV2,SP2,TSP1,TSP2,PV,RSP,AIN2,orAIN4,RTL+1digitto30000-19999toRTH-1digitDecimalpointposition:WhenRTS=PV1,SP1,orTSP1,

decimal point position is same as thatofPVinput.

WhenRTS=PV2,SP2,orTSP2,decimal point position is same as thatofRSPinput.

WhenRTS=PV,decimalpointpositionissameasthatofPVinputscale.

WhenRTS=RSP,decimalpointposi-tionissameasthatofRSPinputscale.

WhenRTS=AIN2,decimalpointposi-tionissameasthatofAIN2scale.

WhenRTS=AIN4,decimalpointposi-tionissameasthatofAIN4scale.

100%ofPVinput range

STD

(RTL)

Minimumvalueofretransmission output scaleofRET

0%ofPVinput range

(O1RS)

RetransmissionoutputtypeofOUTcurrentoutput

SameasRTS OFF

STD

(O1RH)

Maximumvalueofretransmission output scaleofOUTcurrentoutput

WhenO1RS=PV1,SP1,PV2,SP2,TSP1,TSP2,PV,RSP,AIN2,orAIN4,O1RL+1digitto30000-19999toO1RH-1digitDecimalpointposition:WhenO1RS=PV1,SP1,orTSP1,

decimal point position is same as thatofPVinput.

WhenO1RS=PV2,SP2,orTSP2,decimal point position is same as thatofRSPinput.

WhenO1RS=PV,decimalpointpositionissameasthatofPVinputscale.

WhenO1RS=RSP,decimalpointpositionissameasthatofRSPinput scale.

WhenO1RS=AIN2,decimalpointposi-tionissameasthatofAIN2scale.

WhenO1RS=AIN4,decimalpointposi-tionissameasthatofAIN4scale.

-

(O1RL)

Minimumvalueofretransmission output scaleofOUTcurrentoutput

-

(O2RS)

RetransmissionoutputtypeofOUT2currentoutput

SameasRTS OFF

STD

(O2RH)

Maximumvalueofretransmission output scaleofOUT2currentoutput

WhenO2RS=PV1,SP1,PV2,SP2,TSP1,TSP2,PV,RSP,AIN2,orAIN4,O2RL+1digitto30000-19999toO2RH-1digitDecimalpointposition:WhenO2RS=PV1,SP1,orTSP1,

decimal point position is same as thatofPVinput.

WhenO2RS=PV2,SP2,orTSP2,decimal point position is same as thatofRSPinput.

WhenO2RS=PV,decimalpointpositionissameasthatofPVinputscale.

WhenO2RS=RSP,decimalpointpositionissameasthatofRSPinput scale.

WhenO2RS=AIN2,decimalpointpositionissameasthatofAIN2scale.

WhenO2RS=AIN4,decimalpointposi-tionissameasthatofAIN4scale.

-

(O2RL)

Minimumvalueofretransmission output scaleofOUT2currentoutput

-

(OU.A)OUTcurrentoutputrange

4-20:4to20mA 0-20:0to20mA 20-4:20to4mA 20-0:20to0mA

4-20

(OU2.A)OUT2currentoutputrange 4-20

(RET.A)RETcurrentoutputrange 4-20

Heater Break Alarm Setting ParameterMenusymbol: (HBA)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(HB1.S)Heaterbreakalarm-1function selection 0:Heatercurrentmeasurement

1:Heaterbreakalarm

1

EASY

(HB2.S)Heaterbreakalarm-2function selection 1

(HB1)Heaterbreakalarm-1current setpoint

OFF,0.1to300.0Arms

OFF

(HB2)Heaterbreakalarm-2current setpoint OFF

(CT1.T)CT1coilwindingnumberratio

1to3300

800

(CT2.T)CT2coilwindingnumberratio 800

(HDN1)Heaterbreakalarm-1On-delaytimer

0.00to99.59(m.s)

0.00

STD

(HDN2)Heaterbreakalarm-2On-delaytimer 0.00

IncaseswherethecurrenttransformersmanufacturedbyU.R.D.Co.,Ltdareused,setthefollowingvalueforthecoilwindingnumberratio.CTL-6-S-H:800CTL-12L-30:3000

RS-485 Communication Setting Parameter (E1/E3/E4-terminal Area)Menusymbol: (R485)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(PSL)Protocol selection

PCL:PClinkcommunicationPCLSM:PClinkcommunication(withchecksum)LADR:LaddercommunicationCO-M:CoordinatedmasterstationCO-S:CoordinatedslavestationMBASC:Modbus(ASCII)MBRTU:Modbus(RTU)CO-S1:Coordinatedslavestation(Loop-1mode)

CO-S2:Coordinatedslavestation(Loop-2mode)

P-P:Peer-to-peercommunication

MBRTU

EASY(BPS)

Baud rate

600:600bps1200:1200bps2400:2400bps4800:4800bps9600:9600bps19200:19.2kbps38400:38.4kbps*ThebaudrateforRS-485isupto19.2kbpsinE4-terminalarea.

19200

(PRI)Parity

NONE:NoneEVEN:EvenODD:Odd

EVEN

(STP)Stopbit 1:1bit,2:2bits 1

(DLN)Datalength 7:7bits,8:8bits 8

(ADR)Address 1to99 1

Ethernet Communication Setting Parameter (E3-terminal Area)Menusymbol: (ETHR)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(HSR)High-speedresponsemode OFF,1to8 1

EASY

(BPS) Baud rate9600:9600bps19200:19.2kbps38400:38.4kbps

38400

(PRI) ParityNONE:NoneEVEN:EvenODD:Odd

EVEN

to

(IP1toIP4)

IP address 1 to 4

0to255Initialvalue: (IP1).(IP2).(IP3).(IP4) =(192).(168).(1).(1)

See left Tablebelow

to

(SM1toSM4)

Subnetmask1to4

0to255Initialvalue:(SM1).(SM2).(SM3).(SM4) =(255).(255).(255).(0)

See left Tablebelow

to

(DG1toDG4)

Defaultgateway1to4

0to255Initialvalue:(DG1).(DG2).(DG3).(DG4) =(0).(0).(0).(0)

See left Tablebelow

(PRT)Portnumber 502,1024to65535 502

(IPAR)IP access restriction OFF:Disable,ON:Enable OFF

to ,

to

(1.IP1to1.IP4,2.IP1to2.IP4)

PermittedIPaddress1-1to1-4PermittedIPaddress2-1to2-4

0to255Initialvalue: (1.IP1).(1.IP2).(1.IP3).(1.IP4) =(255).(255).(255).(255)(2.IP1).(2.IP2).(2.IP3).(2.IP4) =(255).(255).(255).(255)

See left Tablebelow

(ESW)Ethernetsettingswitch

Settingthisparameterto“ON”enablestheEthernetcommunicationparametersettings.OFF,ON

OFF

UsethefollowingtabletorecordEthernetcommunicationsettingvalue.

Parameter n=1 n=2 n=3 n=4

IPn

SMn

DGn

1.IPn

2.IPn

PROFIBUS-DP Communication Setting Parameter (E3-terminal Area)Menusymbol: (PROF)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(BR)Baud rate

9.6K:9.6kbps19.2K:19.2kbps93.75K:93.75kbps187.5K:187.5kbps0.5M:0.5Mbps1.5M:1.5Mbps3M:3Mbps6M:6Mbps12M:12MbpsAUTO45.45K:45.45kbps

AUTO

EASY

(ADR)Address 0to125 3

(BPS)Baud rate

9600:9600bps19200:19.2kbps38400:38.4kbps

38400

(FILE)Profilenumber 0to5 0

DeviceNet Communication Setting Parameter (E3-terminal Area)Menusymbol: (DNET)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(BR)Baud rate

125K:125kbps250K:250kbps500K:500kbps 125K

EASY(ADR)Address 0to63 63

(BPS)Baud rate

9600:9600bps19200:19.2kbps38400:38.4kbps

38400

(FILE)Profilenumber 0to5 0

CC-Link Communication Setting Parameter (UT55A: E3-terminal Area, UT52A: E1-terminal Area)

Menusymbol: (CC-L)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(BR)Baud rate

156K:156kbps625K:625kbps2.5K:2.5kbps5M:5Mbps10M:10Mbps

10M

EASY

(ADR)Address 1 to 64 1

(BPS)Baud rate

9600:9600bps19200:19.2kbps38400:38.4kbps

38400

(FILE)Profilenumber

UT55A:0to7(0,1,and6:Ver.1.10,2to5,and7:Ver.2.00)UT52A:0to3,and6(0,1,and6:Ver.1.10,2and3:Ver.2.00)

0

KeyActionSettingParameterMenusymbol: (KEY)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(F1)Userfunctionkey-1 actionsetting

OFF:DisableA/M:AUTO/MANswitchC/A/M:CAS/AUTO/MANswitchR/L1:REM/LCLswitchR/L2:Loop-2REM/LCLswitchS/R:STOP/RUNswitchCAS:SwitchtoCASAUTO:SwitchtoAUTOMAN:SwitchtoMANREM1:SwitchtoREMLCL1:SwitchtoLCLREM2:SwitchtoLoop-2REMLCL2:SwitchtoLoop-2LCLSTOP:SwitchtoSTOPRUN:SwitchtoRUNAT:Auto-tuningLTUP:LCDbrightnessUPLTDN:LCDbrightnessDOWNBRI:AdjustLCDbrightnessLCD:LCDbacklightON/OFFswitchLAT:LatchreleasePID:PIDtuningswitch*Loop-2settingvaluesareunavailableinSingle-loopcontrol.

OFF

EASY(F2)

Userfunctionkey-2 actionsetting OFF

(Fn)Userfunctionkey-n actionsetting PID

Page 12: UT55A/UT52A Digital Indication Controller Operation Guide for … · 2020. 4. 11. · tiple indicating controllers, see the external dimensions/panel cutout dimensions which follow

IM 05P01C31-11EN page 12/12

DisplayFunctionSettingParameterMenusymbol: (DISP)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(DVB)Deviationdisplayband

Permitsachangeinthespanofdeviationshownonthefront-paneldeviationmonitor. DisplayedonlyforUT55A. 0.0to100.0%ofPVinputrangespan(EUS).

1.0%ofPVinput rangespan

STD

(PCMD)ActivecolorPVdisplayswitch

0:Fixedinwhite1:Fixedinred2:Linktoalarm1(AlarmOFF:white,AlarmON:red)

3:Linktoalarm1(AlarmOFF:red,AlarmON:white)

4:Linktoalarm1or2(AlarmOFF:white,AlarmON:red)

5:Linktoalarm1or2(AlarmOFF:red,AlarmON:white)

6:PVlimit(Withinrange:white,Outofrange:red)

7:PVlimit(Withinrange:red,Outofrange:white)

8:SPdeviation(Withindeviation:white,Outofdeviation:red)

9:SPdeviation(Withindeviation:red,Outofdeviation:white)

10:LinktoDI(ON:red,OFF:white)

0

EASY

(PCH)PVcolorchangehighlimit

SetadisplayvaluewheninPVlimitorSPdeviation.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsonthe input type.

0

(PCL)PVcolorchangelowlimit 0

(BAR1)Upperbar-graphdisplayregistration

0:Disable1:OUT,Heating-sideOUT,InternalvalueinPositionproportionalcontrol

2:Cooling-sideOUT3:PV4:SP5:Deviation6:Loop-2OUT,Loop-2heating-sideOUT7:Loop-2cooling-sideOUT8:Loop-2PV9:Loop-2SP10:Loop-2deviation11to16:Disable17:Feedbackinput(valveopening)18:PVterminalsanaloginput19:RSPterminalsanaloginput20:AIN2terminalsanaloginput21:AIN4terminalsanaloginput27:TSP28:TSPdeviation29:Loop-2TSP30:Loop-2TSPdeviation

5(Heating/coolingtype:1)

STD

(BAR2)Lowerbar-graphdisplayregistration

1 (Heating/coolingtype:2)(Posi-tion

propor-tional type:17)

(BDV)Bar-graphdeviationdisplayband

0.0to100.0%ofPVinputrangespan(EUS)

1.0%ofPVinput rangespan

STD(GUID)GuidedisplayON/OFF OFF:Nondisplay,ON:Display ON

(ECO)Economymode

OFF:Disable1:EconomymodeON(AllindicationsexceptPVdisplayOFF)2:EconomymodeON(AllindicationsOFF)3:Brightness10%(wholeindication)

OFF

(BRI)Brightness (Dark)1to5(Bright) 3 EASY

(MLSD)LeastsignificantdigitalmaskofPVdisplay

OFF:Withleastsignificantdigit ON:Withoutleastsignificantdigit OFF STD

(MKTP)

Methodforleastsignifi-cantdigitalmaskofPVdisplay

0:Rounding,1:Rounding-off 0 STD

SELECTDisplaySettingParameterMenusymbol: (CSEL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

to

(CS1toCS5)

SELECTDisplay-1to-5registration

Registertheoperationparameter(excepttheOperationMode)thatisfrequentlymodifiedtodisplayitintheOperationDisplay.OFF,2301to5000,6701to6710Forthesettingrange,seeCommuni-cationUser'sManual.

OFF Tablebelow STD

UsethefollowingtabletorecordSELECTDisplaysettingvalue.

Parameter n=1 n=2 n=3 n=4 n=5

CSn

KeyLockSettingParameterMenusymbol: (KLOC)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(COM.W)Communicationwriteenable/disable OFF:Enable,ON:Disable OFF

STD(DATA)

Front panel parameter data(,)keylock

OFF:Unlock,ON:Lock

OFF

(A/M)FrontpanelA/Mkeylock OFF

DIFunctionRegistrationParameterMenusymbol: (DI.SL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(A/M)AUTO/MANswitch

SetanIrelaynumberofcontactinput.Set“OFF”todisablethefunction.

Standard terminals DI1:5025,DI2:5026,DI3:5027

E1-terminalarea DI11:5041,DI12:5042,DI13:5043,DI14:5044,DI15:5045,DI16:5046

E2-terminalarea DI26:5062

E3-terminalarea DI31:5073,DI32:5074,DI33:5075,DI34:5076,DI35:5077

E4-terminalarea DI41:5089,DI42:5090,DI43:5091,DI44:5092,DI45:5093,DI46:5094

5025

STD

(R/L)REMOTE/LOCALswitch 5046

(S/R)STOP/RUNswitch 5026

(CAS)SwitchtoCAS OFF

(AUTO)SwitchtoAUTO OFF

(MAN)SwitchtoMAN OFF

(REM)SwitchtoREMOTE OFF

(LCL)SwitchtoLOCAL OFF

(AT)Auto-tuningSTART/STOPswitch OFF

(LAT)Latchrelease OFF

(LCD)LCDbacklightON/OFFswitch OFF

(PVRW)PVred/whiteswitch OFF

DIFunctionNumberingParameterMenusymbol: (DI.NU)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(SP.B0)Bit-0ofSPnumber

Seenextparagraph.

OFF

EASY(SP.B1)

Bit-1ofSPnumber OFF

(SP.B2)Bit-2ofSPnumber OFF

(SP.B3)Bit-3ofSPnumber OFF

(PN.B0)Bit-0ofPIDnumber SetanIrelaynumberofcontactinput.

Set“OFF”todisablethefunction.

Standard terminals DI1:5025,DI2:5026,DI3:5027

E1-terminalarea DI11:5041,DI12:5042,DI13:5043,DI14:5044,DI15:5045,DI16:5046

E2-terminalarea DI26:5062

E3-terminalarea DI31:5073,DI32:5074,DI33:5075,DI34:5076,DI35:5077

E4-terminalarea DI41:5089,DI42:5090,DI43:5091,DI44:5092,DI45:5093,DI46:5094

OFF

STD

(PN.B1)Bit-1ofPIDnumber OFF

(PN.B2)Bit-2ofPIDnumber OFF

(PN.B3)Bit-3ofPIDnumber OFF

(MP.B0)Bit-0ofmanualpresetoutputnumber OFF

(MP.B1)Bit-1ofmanualpresetoutputnumber OFF

(MP.B2)Bit-2ofmanualpresetoutputnumber OFF

(SP.BC)BitchangingmethodofSPnumber

0:Statusswitch1 1:Statusswitch2 0 STD

AL1-AL3FunctionRegistrationParameterMenusymbol: (ALM)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(AL1.S)AL1functionselection

SetanIrelaynumber.Fortheitemsotherthanbelow,seeCommunicationUser'sManual.Ex.)Setthenumber4353forAL1.Sto use the alarm 1.Set“OFF”todisablethefunction.

Nofunction:OFFAlarm1:4353Alarm2:4354Alarm3:4355Alarm4:4357Alarm5:4358Alarm6:4359Alarm7:4361Alarm8:4362

AUTO(OFF)/MAN(ON)status:4193REM(ON)/LCL(OFF)status:4194STOP(ON)/RUN(OFF)status:4195Outputtracking(ON)switchingsignal:4201FAIL(NormallyON)output:4256

4353

STD

(AL2.S)AL2functionselection 4354

(AL3.S)AL3functionselection 4355

(OR.S)OUTrelayfunctionselection OFF

(OR2.S)OUT2relayfunctionselection OFF

DOSettingParameter(E1/E2/E3-terminalArea)Menusymbol: (DO)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(DO1.S)DO11/DO21/DO31func-tion selection

SameasAL1.SSet“OFF”todisablethefunction.

Initialvalue:DO11,DO12,DO13,DO14,DO15,DO31,DO32,DO33,DO34,andDO35=OFF

DO21=4357,DO22=4358,DO23=4359,DO24=4361,DO25=4362

See left

Tablebelow STD

(DO2.S)DO12/DO22/DO32func-tion selection See left

(DO3.S)DO13/DO23/DO33func-tion selection See left

(DO4.S)DO14/DO24/DO34func-tion selection See left

(DO5.S)DO15/DO25/DO35func-tion selection See left

UsethefollowingtabletorecordDOsettingvalue.

Parameter E1-terminalArea E2-terminalArea E3-terminalArea

DO1.S

DO2.S

DO3.S

DO4.S

DO5.S

SystemSettingParameterMenusymbol: (SYS)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(R.MD)Restartmode

Sethowthecontrollershouldrecoverfrom a power failure of 5 seconds or more.CONT:Continueactionsetbeforepower failure.MAN:StartfromMAN.AUTO:StartfromAUTO.

CONT

STD(R.TM)

Restarttimer

Settimebetweenpoweronandtheinstant where controller starts compu-tation.0to10s

0

(EPO)Input error preset output

SetpresetoutputvaluewhentheinputburnoutorADCerroroccurs.ManualoutputisprioritizedwhentheinputburnoutoccursinMAN.0:Presetoutput1:0%output2:100%output

0

(FREQ)Powerfrequency AUTO,60:60Hz,50:50Hz AUTO

EASY

(QSM)Quicksettingmode OFF:Disable

ON:Enable ON

(LANG)Guidedisplaylanguage

ENG:EnglishFRA:FrenchGER:GermanSPA:Spanish

Depe-nds on the model and suffixcodes

(PASS)Passwordsetting 0(Nopassword)to65535 0

ErrorandVersionConfirmationParameter(fordisplayonly)Menusymbol: (VER)

Parameter symbol Name of Parameter Status record Display

level

(PA.ER)Parameter error status

EASY

(OP.ER)Optionerrorstatus

(AD1.E)A/Dconvertererrorstatus1

(AD2.E)A/Dconvertererrorstatus2

(PV1.E)Loop-1PVinputerrorstatus

(PV2.E)Loop-2PVinputerrorstatus

(LA.ER)Laddererrorstatus

(MCU)MCUversion

(DCU)DCUversion

(ECU1)ECU-1version(E1-terminalarea)

(ECU2)ECU-2version(E2-terminalarea)

(ECU3)ECU-3version(E3-terminalarea)

(ECU4)ECU-4version(E4-terminalarea)

(PARA)Parameterversion

EASY

(H.VER)Productversion

(SER1)Serialnumber1

(SER2)Serialnumber2

(MAC1)MACaddress1(E3-terminalarea)

(MAC2)MACaddress2(E3-terminalarea)

(MAC3)MACaddress3(E3-terminalarea)

*TheparametersforLoop-2areunavailableinSingle-loopcontrol.

ParameterDisplayLevelParameterMenusymbol: (LVL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(LEVL)Parameterdisplaylevel

EASY:EasysettingmodeSTD:StandardsettingmodePRO:Professionalsettingmode

STD EASY

*ForProfessionalsettingmode,seeUser’sManual.

Trademarks Our product names or brand names mentioned in this manual are the trademarks or registered trademarks of Yokogawa Electric Corporation. Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of Adobe Systems Incorporated. Ethernet is a registered trademark of XEROX Corporation in the United States. Modbus is a registered trademark of Schneider Electric. PROFIBUS-DP is a registered trademark of PROFIBUS User Organization. DeviceNet is a registered trademark of Open DeviceNet Vendor Association. CC-Link is a registered trademark of CC-Link Partner Association. We do not use the TM or ® mark to indicate these trademarks or registered trademarks in this manual. All other product names mentioned in this manual are trademarks or registered trademarks of their respective companies.

• AuthorisedRepresentativeintheEEA YokogawaEuropeBV.(Address:Euroweg2,3825HDAmersfoort,TheNetherlands)istheAuthorisedRepresentativeofYokogawaElectricCorporationforthisProductintheEEA.

• Printed ManualsModel Description

UT55A,UT52ADigitalIndicatingController(PanelMountingType)OperationGuide«StandardCodeModel»

IM05P01C31-11EN

UT55A,UT52ADigitalIndicatingControllerOperation(PanelMountingType)Guide«Detailedcodemodel»

IM05P01C31-15EN

UT55A/MDL,UT52A/MDLDigitalIndicatingController(DINRailMountingType)OperationGuide«StandardCodeModel»

IM05P01C81-11EN

PrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN

• ElectronicManuals Youcandownloadthelatestmanualsfromthefollowingwebsite: URL:http://www.yokogawa.com/ns/ut/im/

Model DescriptionUT55A,UT52ADigitalIndicatingController(PanelMountingType)OperationGuide«StandardCodeModel»

IM05P01C31-11EN

UT55A,UT52ADigitalIndicatingController(PanelMountingType)OperationGuide(DetailedCodeModel»

IM05P01C31-15EN

UT55A/MDL,UT52A/MDLDigitalIndicatingController(DINRailMountingType)OperationGuide«StandardCodeModel»

IM05P01C81-11EN

UT55A/UT52ADigitalIndicatingControllerUser’sManual IM05P01C31-01ENUTAdvancedSeriesCommunicationInterface(RS-485,Ethernet)User’sManual IM05P07A01-01ENUTAdvancedSeriesCommunicationInterface(OpenNetwork)User’sManual IM05P07A01-02ENLL50AParameterSettingSoftwareInstallationManual IM05P05A01-01ENLL50AParameterSettingSoftwareUser’sManual IM05P05A01-02ENPrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN

• GeneralSpecificationModel Description

UT55A,UT52ADigitalIndicatingController(PanelMountingType) GS05P01C31-01ENUT55A/MDL,UT52A/MDLDigitalIndicatingController(DINRailMountingType) GS05P01C81-01ENLL50AParameterSettingSoftware GS05P05A01-01EN

* Thelasttwocharactersofthemanualnumberandgeneralspecificationnumberindicatethelanguageinwhichthemanualiswritten.

QR CodeTheproducthasaQRCodepastedforefficientplantmaintenanceworkandassetinformationmanagement. It enables confirming the specificationsof purchasedproductsanduser’smanuals.Formoredetails,pleaserefertothefollowingURL.https://www.yokogawa.com/qr-codeQRCodeisaregisteredtrademarkofDENSOWAVEINCORPORATED.