Pactiv Building Products 2100 River Edge Parkway Suite 175 Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310 www.green-guard.com SKETCH: D SKETCH NO: DATE: 12/1/08 BRICK VENEER CAVITY EXT GYPSUM SHEATHING & LGMF BATTS INSULATION VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control Joint BV CJ-1

Upload: others

Post on 04-Aug-2020

10 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

BRICK VENEER

CAVITY

EXT GYPSUM SHEATHING & LGMF

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GreenGuard® Air Barrier Building Wrap Control Joint

BV CJ-1

Page 2: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Expansion Joint

BV EJ-1

BRICK VENEER

CAVITY

BATTS INSULATION

EXTERIOR GYPSUM SHEATHING & LGMF BU

EXPANSION JOINT ASSEMBLY

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® CONTRACTOR TAPE

Page 3: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Penetration Detail

BV PD-1

BRICK VENEER

CAVITY

BATTS INSULATION

EXTERIOR GYPSUM SHEATHING & LGMF BU

THROUGH WALL PENETRATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® CONTRACTOR TAPE

Page 4: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/01/08

GreenGuard® Air Barrier Building Wrap Brick Relieving Angle

BV RA-1

BRICK VENEER

CAVITY

WEEP

MASONRY VENEER ANCHOR

WEEP BAFFLE

BACKER ROD & SEALANT

HUNG LINTEL SYSTEM FILL JTS IN HUNG LINTEL SYSTEM W/ SPF SEALANT TO TRANSITION AVB

COMPRESSIBLE FILLER

SEMI RIGID FILL AT SHIM SPACE BEHIND RELIEVING ANGLE TO SUPPORT FLASHING ( IF REQ'D )

METAL DRIP EDGE COUNTER FLASHING

EXT GYPSUM SHEATHING & LGMF

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

GREENGUARD® CONTRACTOR TAPE

Page 5: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

BRICK VENEER

VAPOR BARRIER ( IF REQ'D )

CAVITY

EXT GYPSUM SHEATHING & LGMF

ROOF CAP FLASHING

ROOF MEMBRANE

DEFLECTION HEAD

WOOD BLOCKING

BENT PLATE POUR STOP

STEEL BEAM

MASONRY VENEER ANCHOR ON S/A MEMBRANE STRIP

SLAB ON METAL DECK

COVER BOARD

ROOF VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Roof / Wall Detail

BV RF-2

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

Page 6: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

BRICK VENEER

MASONRY VENEER ANCHOR ON S/A MEMBRANE STRIP

LGMF

CAVITY

EXT GYPSUM SHEATHING

ROOF FLASHING

ROOF MEMBRANE

WOOD BLOCKING

BENT PLATE

ROOF UNDERLAYMENT ( IF REQUIRED )

STEEL BEAM

ROOF COUNTER FLASHING

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

DEFLECTION HEAD

ROOF VAPOR BARRIER ( IF REQ'D )

SEAL TOP EDGE OF GREENGUARD® AIR BARRIER BUILDING WRAP WITH GREENGUARD® CONTRACTOR TAPE

GreenGuard® Air Barrier Building Wrap Roof / Wall Detail

BV RF-1

Page 7: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

SKETCH:

DATE:

SKETCH NO:

DATE: 12/01/08

BV BW-2GreenGuard® Air Barrier Building Wrap Brick Veneer Base Wall

Pactiv Building Products 2100 RiverEdge Parkway Suite 175

Atlanta, GA 30328 ( 800 ) 241-4402 Fax ( 847 ) 615-6353

www.green-guard.com

CONCRETE FOUNDATION

METAL DRIP EDGE COUNTER FLASHING

WEEP

WEEP BAFFLE

BRICK VENEER

MASONRY VENEER ANCHOR ON S/A MEMBRANE STRIP

EXT GYPSUM SHEATHING ON LGMF

CAVITY

GROUT FILL

FIBERGLASS BATTS INS.

VAPOR BARRIER ( IF REQUIRED )

INTERIOR GWB

DRAINAGE BOARD

MEMBRANE WATERPROOFING

GREENGUARD® AIR BARRIER BUILDING WRAP

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

GREENGUARD® THRU WALL FLASHING

Page 8: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

SKETCH:

DATE:

SKETCH NO:

DATE: 12/01/08

BV BW-1GreenGuard® Air Barrier Building Wrap Brick Veneer Base Wall

Pactiv Building Products 2100 RiverEdge Parkway Suite 175

Atlanta, GA 30328 ( 800 ) 241-4402 Fax ( 847 ) 615-6353

www.green-guard.com

CONCRETE FOUNDATION

METAL DRIP EDGE COUNTER FLASHING

WEEP

WEEP BAFFLE

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

BRICK VENEER

MASONRY VENEER ANCHOR ON S/A MEMBRANE STRIP

EXT GYPSUM SHEATHING ON LGMF

CAVITY

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQUIRED )

INTERIOR GWB

GREENGUARD® AIR BARRIER BUILDING WRAP

Page 9: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Flanged Window Head

BV WH-3

ALUMINUM WINDOW UNIT

BRICK VENEER

CAVITY

EXT GYPSUM SHEATHING & LGMF

WEEP

LOOSE STEEL LINTEL

BACKER ROD & SEALANT

WEEP BAFFLE

BATTS INSULATION

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® THRU WALL FLASHING

MASONRY VENEER ANCHOR ON S/A MEMBRANE STRIP

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

Page 10: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Head

BV WH-2

ALUMINUM WINDOW UNIT

BRICK VENEER

CAVITY

EXT GYPSUM SHEATHING & LGMF

WEEP

BACKER ROD & SEALANT

WEEP BAFFLE

MASONRY VENEER ANCHOR

HUNG LINTEL SYSTEM FILL JTS IN HUNG LINTEL SYSTEM BEHIND WDW W/ SPF SEALANT

BATTS INSULATION

GREENGUARD® THRU WALL FLASHING

GREENGUARD® THRU WALL FLASHING

VAPOR BARRIER ( IF REQ'D )

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

GREENGUARD® AIR BARRIER BUILDING WRAP

Page 11: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Head

BV WH-1

ALUMINUM WINDOW UNIT

BRICK VENEER

CAVITY

EXT GYPSUM SHEATHING & LGMF

WEEP

LOOSE STEEL LINTEL

BACKER ROD & SEALANT

WEEP BAFFLE

BATTS INSULATION

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® THRU WALL FLASHING

MASONRY VENEER ANCHOR ON S/A MEMBRANE STRIP

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

Page 12: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

BRICK VENEER

CAVITY

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL

ALUMINUM WINDOW

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Flanged Window Jamb

BV WJ-2

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL THE EDGE W/ GREENGUARD® CONTRACTOR TAPE

MASONRY VENEER ANCHOR ON S/A MEMBRANE STRIP

Page 13: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

BRICK VENEER

CAVITY

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

ALUMINUM WINDOW

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Jamb

BV WJ-1

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL THE EDGE W/ GREENGUARD® CONTRACTOR TAPE

MASONRY VENEER ANCHOR ON S/A MEMBRANE STRIP

Page 14: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

BRICK VENEER

SILL PAN

MINERAL WOOL OR ROCK WOOL INSULATION

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT ( EXEND TO WINDOW FLANGE AT JAMBS )

WINDOW SILL

EXTERIOR GYPSUM SHEATHING ON LGMF

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Flanged Window Sill

BV WS-2

GREENGUARD® THRU WALL FLASHING LAP GREENGUARD® THRU WALL FLASHING OVER GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® AIR BARRIER BUILDING WRAP

MASONRY VENEER ANCHOR ON S/A MEMBRANE STRIP

1/8" SHIMS @ 12" O.C. TO CREATE A DRAINAGE SPACE

Page 15: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

BRICK VENEER

LAP GREENGUARD® THRU WALL FLASHING OVER GREENGUARD® AIR BARRIER BUILDING WRAP

SILL PAN

MINERAL WOOL OR ROCK WOOL INSULATION

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT ( AIR BARRIER TRANSITION TO WINDOW FRAME )

WINDOW SILL

EXTERIOR GYPSUM SHEATHING ON LGMF

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Sill

BV WS-1

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

MASONRY VENEER ANCHOR ON S/A MEMBRANE STRIP

Page 16: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

EIFS VENEER ( MECHANICALLY FASTENED )

EXT GYPSUM SHEATHING & LGMF

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GreenGuard® Air Barrier Building Wrap Control Joint

EIFSV CJ-1

Page 17: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Expansion Joint

EIFSV EJ-1

EIFS VENEER ( MECHANICALLY FASTENED )

BATTS INSULATION

EXTERIOR GYPSUM SHEATHING & LGMF BU

EXPANSION JOINT ASSEMBLY

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® CONTRACTOR TAPE

Page 18: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Penetration Detail

EIFSV PD-1

EIFS VENEER ( MECHANICALLY FASTENED )

BATTS INSULATION

EXTERIOR GYPSUM SHEATHING & LGMF BU

THROUGH WALL PENETRATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® CONTRACTOR TAPE

Page 19: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

EIFS VENEER ( MECHANICALLY FASTENED )

VAPOR BARRIER ( IF REQ'D )

EXT GYPSUM SHEATHING & LGMF

ROOF CAP FLASHING

ROOF MEMBRANE

DEFLECTION HEAD

WOOD BLOCKING

BENT PLATE POUR STOP

STEEL BEAM

SLAB ON METAL DECK

COVER BOARD

ROOF VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Roof / Wall Detail

EIFSV RF-2

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

Page 20: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

EIFS VENEER ( MECHANICALLY FASTENED )

EXT GYPSUM SHEATHING ON LGMF

ROOF FLASHING

ROOF MEMBRANE

WOOD BLOCKING

BENT PLATE

ROOF UNDERLAYMENT ( IF REQUIRED )

STEEL BEAM

ROOF COUNTER FLASHING

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

DEFLECTION HEAD

ROOF VAPOR BARRIER ( IF REQ'D )

SEAL TOP EDGE OF GREENGUARD® AIR BARRIER BUILDING WRAP WITH GREENGUARD® CONTRACTOR TAPE

GreenGuard® Air Barrier Building Wrap Roof / Wall Detail

EIFSV RF-1

Page 21: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

SKETCH:

DATE:

SKETCH NO:

DATE: 12/01/08

EIFSV BW-1GreenGuard® Air Barrier Building Wrap EIFS Veneer Base

Pactiv Building Products 2100 RiverEdge Parkway Suite 175

Atlanta, GA 30328 ( 800 ) 241-4402 Fax ( 847 ) 615-6353

www.green-guard.com

CONCRETE FOUNDATION

STARTER TRACK W/ WEEP HOLES

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

EIFS VENEER ( MECHANICALlY FASTENED )

EXT GYPSUM SHEATHING ON LGMF

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQUIRED )

INTERIOR GWB

GREENGUARD® AIR BARRIER BUILDING WRAP

Page 22: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Flanged Window Head

EIFSV WH-2

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

EXT GYPSUM SHEATHING & LGMF

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

EIFS VENEER ( MECHANICALLY FASTENED )

Page 23: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Head

EIFSV WH-1

ALUMINUM WINDOW UNIT

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

BATTS INSULATION

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

EIFS VENEER ( MECHANICALLY FASTENED )

Page 24: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

EIFS VENEER ( MECHANICALLY FASTENED )

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

ALUMINUM WINDOW

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Flanged Window Jamb

EIFSV WJ-2

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL THE EDGE W/ GREENGUARD® CONTRACTOR TAPE

Page 25: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

EIFS VENEER ( MECHANICALLY FASTENED )

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

ALUMINUM WINDOW

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Jamb

EIFSV WJ-1

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL THE EDGE W/ GREENGUARD® CONTRACTOR TAPE

Page 26: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

EIFS VENEER ( MECHANICALLY FASTENED )

SILL PAN

MINERAL WOOL OR ROCK WOOL INSULATION

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT ( EXEND TO WINDOW FLANGE AT JAMBS )

WINDOW SILL

EXTERIOR GYPSUM SHEATHING ON LGMF

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Flanged Window Sill

EIFSV WS-2

GREENGUARD® THRU WALL FLASHING LAP GREENGUARD® THRU WALL FLASHING OVER GREENGUARD® AIR BARRIER BUILDING WRAPGREENGUARD® AIR BARRIER BUILDING WRAP

1/8" SHIMS @ 12" O.C. TO CREATE A DRAINAGE SPACE

Page 27: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

MINERAL WOOL OR ROCK WOOL INSULATION

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT ( AIR BARRIER TRANSITION TO WINDOW FRAME )

WINDOW SILL

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Sill

EIFSV WS-1

EIFS VENEER ( MECHANICALLY FASTENED )

EXTERIOR GYPSUM SHEATHING ON LGMF

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® THRU WALL FLASHING LAP GREENGUARD® THRU WALL FLASHING OVER GREENGUARD® AIR BARRIER BUILDING WRAPGREENGUARD® AIR BARRIER BUILDING WRAP

SILL PAN

Page 28: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

METAL PANEL VENEER

EXT GYPSUM SHEATHING & LGMF

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GreenGuard® Air Barrier Building Wrap Control Joint

MPV CJ-1

Page 29: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Expansion Joint

MPV EJ-1

METAL PANEL VENEER

BATTS INSULATION

EXTERIOR GYPSUM SHEATHING & LGMF BU

EXPANSION JOINT ASSEMBLY

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® CONTRACTOR TAPE

Page 30: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Penetration Detail

MPV PD-1

METAL PANEL VENEER

BATTS INSULATION

EXTERIOR GYPSUM SHEATHING & LGMF BU

THROUGH WALL PENETRATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® CONTRACTOR TAPE

Page 31: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

METAL PANEL VENEER

VAPOR BARRIER ( IF REQ'D )

EXT GYPSUM SHEATHING & LGMF

ROOF CAP FLASHING

ROOF MEMBRANE

DEFLECTION HEAD

WOOD BLOCKING

BENT PLATE POUR STOP

STEEL BEAM

SLAB ON METAL DECK

COVER BOARD

ROOF VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Roof / Wall Detail

MPV RF-2

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

Page 32: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

METAL PANEL VENEER

EXT GYPSUM SHEATHING ON LGMF

ROOF FLASHING

ROOF MEMBRANE

WOOD BLOCKING

BENT PLATE

ROOF UNDERLAYMENT ( IF REQUIRED )

STEEL BEAM

ROOF COUNTER FLASHING

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

DEFLECTION HEAD

ROOF VAPOR BARRIER ( IF REQ'D )

SEAL TOP EDGE OF GREENGUARD® AIR BARRIER BUILDING WRAP WITH GREENGUARD® CONTRACTOR TAPE

GreenGuard® Air Barrier Building Wrap Roof / Wall Detail

MPV RF-1

Page 33: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

SKETCH:

DATE:

SKETCH NO:

DATE: 12/01/08

MPV BW-1GreenGuard® Air Barrier Building Wrap Metal Panel Veneer Base

Pactiv Building Products 2100 RiverEdge Parkway Suite 175

Atlanta, GA 30328 ( 800 ) 241-4402 Fax ( 847 ) 615-6353

www.green-guard.com

CONCRETE FOUNDATION

METAL DRIP EDGE COUNTER FLASHING

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

METAL PANEL VENEER

METAL PANEL VENEER ANCHOR ON S/A MEMBRANE STRIP

EXT GYPSUM SHEATHING ON LGMF

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQUIRED )

INTERIOR GWB

GREENGUARD® AIR BARRIER BUILDING WRAP

Page 34: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Flanged Window Head

EIFSV WH-2

ALUMINUM WINDOW UNIT

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

BATTS INSULATION

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

METAL PANEL VENEER

Page 35: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Head

MPV WH-1

ALUMINUM WINDOW UNIT

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

BATTS INSULATION

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

METAL PANEL VENEER

Page 36: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

METAL PANEL VENEER

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

ALUMINUM WINDOW

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Flanged Window Jamb

MPV WJ-2

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL THE EDGE W/ GREENGUARD® CONTRACTOR TAPE

Page 37: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

METAL PANEL VENEER

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

ALUMINUM WINDOW

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Jamb

MPV WJ-1

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL THE EDGE W/ GREENGUARD® CONTRACTOR TAPE

Page 38: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

METAL PANEL VENEER

SILL PAN

MINERAL WOOL OR ROCK WOOL INSULATION

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT ( EXEND TO WINDOW FLANGE AT JAMBS )

WINDOW SILL

EXTERIOR GYPSUM SHEATHING ON LGMF

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Flanged Window Sill

MPV WS-2

GREENGUARD® THRU WALL FLASHING LAP GREENGUARD® THRU WALL FLASHING OVER GREENGUARD® AIR BARRIER BUILDING WRAPGREENGUARD® AIR BARRIER BUILDING WRAP

METAL PANEL VENEER ANCHOR ON S/A MEMBRANE STRIP SHIM AS REQUIRED

1/8" SHIMS @ 12" O.C. TO CREATE A DRAINAGE SPACE

Page 39: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

MINERAL WOOL OR ROCK WOOL INSULATION

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT ( AIR BARRIER TRANSITION TO WINDOW FRAME )

WINDOW SILL

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Sill

MPV WS-1

METAL PANEL VENEER

EXTERIOR GYPSUM SHEATHING ON LGMF

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® THRU WALL FLASHING LAP GREENGUARD® THRU WALL FLASHING OVER GREENGUARD® AIR BARRIER BUILDING WRAPGREENGUARD® AIR BARRIER BUILDING WRAP

METAL PANEL VENEER ANCHOR ON S/A MEMBRANE STRIP SHIM AS REQUIRED

SILL PAN

Page 40: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

EXT GYPSUM SHEATHING & LGMF

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GreenGuard® Air Barrier Building Wrap Control Joint

SV CJ-1

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

Page 41: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Expansion Joint

SV EJ-1

BATTS INSULATION

EXTERIOR GYPSUM SHEATHING & LGMF BU

EXPANSION JOINT ASSEMBLY

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® CONTRACTOR TAPE

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

Page 42: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Penetration Detail

SV PD-1

BATTS INSULATION

EXTERIOR GYPSUM SHEATHING & LGMF BU

THROUGH WALL PENETRATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® CONTRACTOR TAPE

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

Page 43: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

VAPOR BARRIER ( IF REQ'D )

EXT GYPSUM SHEATHING & LGMF

ROOF CAP FLASHING

ROOF MEMBRANE

DEFLECTION HEAD

WOOD BLOCKING

BENT PLATE POUR STOP

STEEL BEAM

SLAB ON METAL DECK

COVER BOARD

ROOF VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Roof / Wall Detail

SV RF-2

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

CASING BEAD

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

Page 44: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

ROOF FLASHING

ROOF MEMBRANE

WOOD BLOCKING

BENT PLATE

ROOF UNDERLAYMENT ( IF REQUIRED )

STEEL BEAM

ROOF COUNTER FLASHING

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

DEFLECTION HEAD

ROOF VAPOR BARRIER ( IF REQ'D )

SEAL TOP EDGE OF GREENGUARD® AIR BARRIER BUILDING WRAP WITH GREENGUARD® CONTRACTOR TAPE

GreenGuard® Air Barrier Building Wrap Roof / Wall Detail

SV RF-1

EXT GYPSUM SHEATHING & LGMF

CASING BEAD

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

Page 45: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

SKETCH:

DATE:

SKETCH NO:

DATE: 12/01/08

SV BW-1GreenGuard® Air Barrier Building Wrap Stucco Veneer Base

Pactiv Building Products 2100 RiverEdge Parkway Suite 175

Atlanta, GA 30328 ( 800 ) 241-4402 Fax ( 847 ) 615-6353

www.green-guard.com

CONCRETE FOUNDATION

STARTER TRACK W/ WEEP HOLES

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

EXT GYPSUM SHEATHING ON LGMF

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQUIRED )

INTERIOR GWB

GREENGUARD® AIR BARRIER BUILDING WRAP

1/4" GREENGUARD® DC14 DRAINAGE MAT

Page 46: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Flanged Window Head

SV WH-2

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

EXT GYPSUM SHEATHING & LGMF

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

CASING BEAD

Page 47: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Head

SV WH-1

ALUMINUM WINDOW UNIT

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

BATTS INSULATION

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® THRU WALL FLASHING

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL BOTTOM EDGE W/ GREENGUARD® CONTRACTOR TAPE

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

CASING BEAD

Page 48: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

ALUMINUM WINDOW

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Flanged Window Jamb

SV WJ-2

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL THE EDGE W/ GREENGUARD® CONTRACTOR TAPE

1/4" GREENGUARD® DC14 DRAINAGE MAT

CASING BEAD

Page 49: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

EXT GYPSUM SHEATHING & LGMF

BACKER ROD & SEALANT

SPRAY POLYURETHANE FOAM SEALANT OR ROCK WOOL / MINERAL WOOL WITH BACKER ROD & SEALANT FOR AIR BARRIER TRANSITION TO WINDOW FRAME

ALUMINUM WINDOW

BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Jamb

SV WJ-1

GREENGUARD® THRU WALL FLASHING

GREENGUARD® AIR BARRIER BUILDING WRAP

LAP GREENGUARD® AIR BARRIER BUILDING WRAP OVER GREENGUARD® THRU WALL FLASHING 6" MIN. SEAL THE EDGE W/ GREENGUARD® CONTRACTOR TAPE

1/4" GREENGUARD® DC14 DRAINAGE MAT

CASING BEAD

Page 50: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

MINERAL WOOL OR ROCK WOOL INSULATION

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT ( AIR BARRIER TRANSITION TO WINDOW FRAME )

WINDOW SILL

GreenGuard® Air Barrier Building Wrap Flanged Window Sill

SV WS-2

EXTERIOR GYPSUM SHEATHING ON LGMF

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® THRU WALL FLASHING LAP OVER GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® AIR BARRIER BUILDING WRAP

SILL PAN

1/8" SHIMS @ 12" O.C. TO CREATE A DRAINAGE SPACE

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

1/4" GREENGUARD® DC14 DRAINAGE MAT

PERFORATED CASING BEAD

Page 51: VAPOR BARRIER ( IF REQ'D ) EXT GYPSUM SHEATHING Green Guard Max... · VAPOR BARRIER ( IF REQ'D ) GREENGUARD® AIR BARRIER BUILDING WRAP GreenGuard® Air Barrier Building Wrap Control

Pactiv Building Products 2100 River Edge Parkway Suite 175

Atlanta, GA 30328 ( 678 ) 589-7309 Fax ( 678 ) 589-7310

www.green-guard.com

SKETCH:

DATE:

SKETCH NO:

DATE: 12/1/08

MINERAL WOOL OR ROCK WOOL INSULATION

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT ( AIR BARRIER TRANSITION TO WINDOW FRAME )

WINDOW SILL

GreenGuard® Air Barrier Building Wrap Non-Flanged Window Sill

SV WS-1

CEMENTITIOUS STUCCO ON EXPANDED WIRE LATH

EXTERIOR GYPSUM SHEATHING ON LGMF

FIBERGLASS BATTS INSULATION

VAPOR BARRIER ( IF REQ'D )

GREENGUARD® THRU WALL FLASHING LAP OVER GREENGUARD® AIR BARRIER BUILDING WRAP

GREENGUARD® AIR BARRIER BUILDING WRAP

SILL PAN

1/4" GREENGUARD® DC14 DRAINAGE MAT

PERFORATED CASING BEAD