vfd commissioning dept
TRANSCRIPT
-
7/31/2019 VFD Commissioning Dept
1/63
WELCOME TO APRESENTATION ON
LCI TYPE VFD- BY COMMISSIONING GROUP
PROFESSIONAL CIRCLE
-
7/31/2019 VFD Commissioning Dept
2/63
INTRODUCTION
-
7/31/2019 VFD Commissioning Dept
3/63
WHAT IS A VFD ?
VFD means Variable Frequency Drive, i.e.,adjustable speed AC motor drive system to
control and/or optimize processes.
AC Line frequency power is converted to DC& again inverted to AC power of required
frequency to be applied to the motor stator to
get speed as per process requirement.
AC to DC conversion & again DC to AC
inversion are done by semiconductor devices
(this case it is Thyristors) & electronic control.
-
7/31/2019 VFD Commissioning Dept
4/63
There are different methods of
adjustable speed system such asCycloconverter, phase-controlled
switches, stator power control of
synchronous motor with Load-commutated inverter system (LCI).
LCI drive system is most effective &
common in compressor, pump & fan
applications
-
7/31/2019 VFD Commissioning Dept
5/63
WHAT IS LCI ?
LCI means Load Commutated Inverter.
Commutation is the process whereby
changing voltage cause one cell to stop
conducting and another to begin.
In Other words Control can turn ON a
thyristor, but we need the changingvoltage relationship to turn it OFF
Commutation takes place.
-
7/31/2019 VFD Commissioning Dept
6/63
WHAT IS LCI ? In case of rectifier bridge, the power system
provides the voltage & energy for commutation,so it is called a line commuted bridge
In case of Inverter bridge, the requirement is
same , but a synchronous motor with leadingpower factor ( current leading voltage) shall be
able to provide the voltage (back e.m.f of the
motor) & energy for commutation. Hence, the
Load (Synchronous machine) helpscommutation required for inverting DC to AC.
That is why it is called Load commuted
inverter.
-
7/31/2019 VFD Commissioning Dept
7/63
Why a synchronous motor, not an
induction motor IN LCI?
A synchronous machine is used
because of its ability to deliverleading VARs which commutate
the inverter bridge. And
induction motor cannot do this.
-
7/31/2019 VFD Commissioning Dept
8/63
LCI TYPE VFD
LCI type VFD can be either 6-pulse single
channel type or 12-pulse dual channel type . Each
channel consists of an isolating transformer,
source converter, DC link inductor and loadconverter, in a single channel type VFD, the
synchronous motor will have one winding
whereas in dual channel type VFD, the
synchronous motor will have two windings, one
for each channel. The source side converter
operates in rectifier mode whereas the load side
converter operates in inverter mode.
-
7/31/2019 VFD Commissioning Dept
9/63
The DC link inductor effectively isolates load
side frequency and source side frequency and
smoothens the DC link current.
The demand signal received from the control
system prompts the source side converter to
provide the required current to the DC link
inductor at the DC voltage level set by the load
side converter. Thus the source side converter
plus the DC link inductor become currentsource controller to the motor and the motor
torque, frequency (hence speed) and voltage
level get adjusted to the load requirements.
-
7/31/2019 VFD Commissioning Dept
10/63
he choice of six pulse, single channel, or 12
pulse dual channel VFD depends on the.
Harmonics that are allowed to beinjected into the grid
Whether redundant fan/pump isavailable.
2-pulse system is recommended where lower
-
7/31/2019 VFD Commissioning Dept
11/63
--Saving in operational cost due to reduced power
consumption .
-- Absence of voltage dip problems associated with DOL
starting of large motors since the starting current in this driveis limited to about 120% of the motor full load current (soft
start).
-- Increased motor life due to the lower thermal andmechanical stresses in view of the absence of starting inrush
currents(6-7 times FLC) , reduced speed operation.
-- No limitation on the number of starts.
ADVANTAGES OF LCI TYPE
VFD
-
7/31/2019 VFD Commissioning Dept
12/63
-
7/31/2019 VFD Commissioning Dept
13/63
VARIABLE FREQUENCY DRIVES :VARIABLE FREQUENCY DRIVES :
APPLICATION AREASAPPLICATION AREAS
LCI HSLCI IMD
BOILER ID/FD/PA FANS X - X
GAS TURBINE STARTER X - X
COMPRESSOR / BOILER FEED
PUMPX X X
EXTRUDER / MIXER X - X
BOILER CONDENSATE PUMP X - X
CIRCULATING WATER PUMP X - X
CEMENT MILL FAN / PIPELINE
PUMPSX X X
-
7/31/2019 VFD Commissioning Dept
14/63
VARIABLE FREQUENCY DRIVES :VARIABLE FREQUENCY DRIVES :
APPLICATION AREASAPPLICATION AREAS
LCI HSLCI IMD
HIGH SPEED BLOWERS /
PUMPS- X -
SLURRY PUMPS / SEWAGE
PUMPSX - X
FREQUENCY CONVERTER /
MOTOR STARTERX - -
X = SYSTEM SUITABLE AND APPLICATION
DATA AVAILABLE
- = SYSTEM NOT SUITABLE AND / ORAPPLICATION DATA NOT AVAILABLE
-
7/31/2019 VFD Commissioning Dept
15/63
RATINGS AVAILABLE with BHEL Design :RATINGS AVAILABLE with BHEL Design :
LOAD COMMUTATED INVERTER : 1000 KW TO 15000
KW
HIGH SPEED LOAD COMMUTATED : 4500 KW TO 45000
KW INVERTER
INDUCTION MOTOR DRIVE : 150 KW TO
2000 KW
-
7/31/2019 VFD Commissioning Dept
16/63
6 PULSE CONVERTER6 PULSE CONVERTER
-
7/31/2019 VFD Commissioning Dept
17/63
-
7/31/2019 VFD Commissioning Dept
18/63
CONVENTIONAL BOILER FEED PUMPCONVENTIONAL BOILER FEED PUMP
GEAR BOX +
HYDRAULIC
COUPLING
INDUCTION
MOTOR
BOOSTER
PUMP
INDUCTION MOTOR
150KW
SUPER
SYNCHRONOUS
MOTOR
BOILER
FEED
PUMPVFD
UPTO
100 Hz
50 Hz GRID
50 Hz GRID
ARRANGEMENT WITH VFDARRANGEMENT WITH VFD
BOOSTER
PUMP
-
7/31/2019 VFD Commissioning Dept
19/63
TECHNO-ECONOMIC ANALYSIS OF 6 PULSE VFD OVER HYDRAULICTECHNO-ECONOMIC ANALYSIS OF 6 PULSE VFD OVER HYDRAULIC
COUPLING FOR 250MW BOILER FEED PUMP DRIVESCOUPLING FOR 250MW BOILER FEED PUMP DRIVES
MOTOR RATING: 3900 KW ,5300 RPM NO.OF PUMPS PER BOILER :3MOTOR RATING: 3900 KW ,5300 RPM NO.OF PUMPS PER BOILER :3
SL. GEN ENERGY CONSUMED ENERGY PAYBACK
NO. MW PER Yr IN MW.Hr SAVED DUE PERIOD
HYD. VFD TO VFDCOUP.
1. 150 9000 7575
2. 200 10426 9101 9.39 6YrsMILLION Rs
3. 250 12423 11415
-
7/31/2019 VFD Commissioning Dept
20/63
RECTIFIER INVERTER
REACTOR
BRUSH
LESS
Exciter
SYNC.
Motor
AC Line
DC Link
1 3 5
4 6 2
2 6 4
135
-
7/31/2019 VFD Commissioning Dept
21/63
2
5
6 4
3 1
Fld.WdgExciter
Phase
controlle
d
switches
415 V Power
LCI BRUSHLESS EXCITER
Exciter is an induction
frequency changer
-
7/31/2019 VFD Commissioning Dept
22/63
EFFECIENCY CURVE OF VARIOUS FLOW
CONTROL DRIVES
100 % Efficiency
80
60
40
20
0 20 40 60 80 100
% Speed / Flow
Hydraulic Coupling
Inlet Guide Vane
Outlet Damper Throttling
LCI or VFD Drive
-
7/31/2019 VFD Commissioning Dept
23/63
CONTROL SYSTEM
AC MACHINE TORQUE EQUATION
T = (1/w)*q*E*I*cos
q = no.of phases in armature winding
E = r.m.s induced voltage of armature
I = r.m.s current per phase of armature
= phase angle between E & I
w = mechanical angular velocity is related to electrical angularvelocity by 4**f / p , p = no.of poles, f = frequency.
So, T E*I*cos / f , that is * I * cos
-
7/31/2019 VFD Commissioning Dept
24/63
CONTROL SYSTEM
The speed reference from the process controller is a
compared to a speed feedback derived from theintegrated motor voltage & error is fed to a speed
regulator.
The output of speed regulator is a torque command.
This torque command is sent to the field controller and
to a current controller as a current command.
By proper control of stator current & field excitation ,
the machine has a fairly linear torque-per-ampere
characteristic.
The most straight forward approach is a speed controller
with a V/f controller for field excitation.
-
7/31/2019 VFD Commissioning Dept
25/63
CONTROL SYSTEMThere are three controllable element which can
be used to control the power to the motor:
- The source side converter
- The load side converter
- the field exciter.
All three of these use phase control of thyristor
gating angle to control output.
Major function of load side converter control is
to keep the power to the motor at the highest
possible power factor.
-
7/31/2019 VFD Commissioning Dept
26/63
CONTROL SYSTEM
A current feedback signal is derived from theAC current into the source side power
converter.
The output of the current controller is used to
control the gate firing angle of the source side
converter to adjust the DC link voltage
necessary to produce the commanded current.
-
7/31/2019 VFD Commissioning Dept
27/63
How much power saving? A case study
Site: TATA POWER, TROMBAY, 500 MW Units
SITUATION: UNIT 5 with Flue gas controlled by
dampers
UNIT6 Flue gas controlled by VFD
Power consumption of ID fans in both the units were
taken at various generating points and data isoutlined in TABLE 1
H h i ? A d
-
7/31/2019 VFD Commissioning Dept
28/63
How much power saving? A case study
TABLE 1
Gen.MW
U5IDsTotalPower (KW)
U6 Total power(KW) by IDFans
Power Saving
200 3800 850 2950
240 4150 950 3200
280 4450 1050 3100
320 4800 1250 3550
360 5050 1420 3630
400 5350 1850 3500
440 5600 2500 3100
-
7/31/2019 VFD Commissioning Dept
29/63
How much power saving? A case study
From table1 it is seen that power saving
ranging from 2900 KW to 3630 KW at various
gen. Points
Considering an average saving of 3200MW
and 300 days in operation a net saving of
Rs.288 lakhs @ generating costRs.1.25/unit
Capital investment on VFD Rs.500 Lakhs
Payback period less than 02 years.
-
7/31/2019 VFD Commissioning Dept
30/63
How much power saving? A case study
Techno-economical analysis for use of VFDsfor BFPs in 210MW units
Situation : Constant pressure operation
Motor rating: 3500KW, 5300 R.P.M
No.of pumps in a boiler: 3
VFD design: 6 pulseExisting coupling: Hydraulic
Parameters on both the case maintained same
H h i ? A t d
-
7/31/2019 VFD Commissioning Dept
31/63
How much power saving? A case studySl.no Hydrau.coupling VFD system
MCR (%) 60% 80% 100% 60% 80% 100%
Speed rpm 4459 4596 4815 4459 4596 4815
Flow t/h 1780 1860 1965 1780 1860 1965
1 Power drawn bytwo BFPs(KW)
3750 4344 5176 3106 3742 4706
2 Energyconsumed MWhin a yr.
31849 ( considering2400 hrs. operation on eachMCR rating)
28091( considering 2400hrs. operation on each MCRrating)
3 Running cost atRs. 1.25/KWh
398.11 lacks 351.14 lakhs
4 Saving in cost 46.97 lacks/yr.
5 Additional cost
during initial
150 lackhs
-
7/31/2019 VFD Commissioning Dept
32/63
LATEST DEVELOPMENTS IN VFDsLATEST DEVELOPMENTS IN VFDs
IGBT POWER CIRCUIT FOR INDUCTION MOTOR
DRIVES (LACKING IN POWER STATION
EXPERIENCE )
UNITY INPUT POWER FACTOR
MINIMUM INPUT HARMONICS
ALMOST SINE WAVE OUTPUT
SELF TUNING CONTROLLER
DC MOTOR LIKE CONTROL CHARACTERISTICS
-
7/31/2019 VFD Commissioning Dept
33/63
BHEL VFD FORID FANS OF 500
MW UNITS : AN
OVERVIEW
-
7/31/2019 VFD Commissioning Dept
34/63
Panels related to VFD in VFD room
C on trol Pa n
(all externalinterlocks,
alarm s, Pow
supplies
available her
C& E Sectio
(C on trol anexcitation)
Bridge
blow er &Filter
section
LCI,
Section(Converte
& Inve ste
bridges)
Load
breaker (V C B )
Com m on for both chanels in one I
Fans , but interlock ing & tr ip relay
seperately m ounted in this panel f
each c hannel
LCI Panel
-
7/31/2019 VFD Commissioning Dept
35/63
C & E (Control & Excitation) Panel
PSFF
Power
Supplymodule
70V
Gate
Supplymodule
Exciter
Module
SEM Rack
(Microprocesso
& other controlcards)
IOM A
(Input / outputmodule)
-
7/31/2019 VFD Commissioning Dept
36/63
Fan & Filter Panel
AIR
FAN 1
FAN 2
Filter Resistors
and capacitors
Air flow
monitor
sensor
-
7/31/2019 VFD Commissioning Dept
37/63
H P T K X P T N
H P T K X P T N
H P T K X P T N
H P T K X P T N
H P T K X P T N
H P T K X P T N
H P T K X P T N
H P T K X P T N
H P T K X P T N
H P T K X P T N
H P T K X P T N
H P T K X P T N
S
T
M
1
S
T
M
3
S
T
M
5
L
T
M
4
L
T
M
6
L
T
M
2
S
T
M
4
S
T
M
6
S
T
M
2
L
T
M
1
L
T
M
3
L
T
M
5
STM - Source Thyristor Module
LTM - Load Thyristor Module
HPTK - Gate firing card
XPTK - Attennator fead back card
LCI (Load
Commuted
Inverter)
Thyristor
Bridge
-
7/31/2019 VFD Commissioning Dept
38/63
NOTE: In each Thyristor stack there are
three Thyristors in series. Each Thyristor ishaving one indication card with neon lamp.
In case of Thyristor short circuit this neon
lamp will not glow. One Thyristor shortcircuit in a stack is allowed. If two
Thyristors get shorted load / source
commutation failure will arrive dependingupon which thyristors have failed and
channel will get tripped.
-
7/31/2019 VFD Commissioning Dept
39/63
ControlControl
Cooling Fan Cooling Fan
INTER
FACE
INTER
FACE
REACTO
CONTROL &
EXCITA TION
PANEL
CONTROL &
EXCITA TION
PANEL
INTER
FACE
INTER
FACE
REACTO
Control Control
Cooling FanCooling Fan
UA
11kV
B US
UA
11kV
BUS
Transforme
11/ 2.3KV
(D yn), 3kvA
Transforme
11/ 2.3KV
(Ddo), 3kv
ID Ch #
415V 3 Phase
supply form ES
415V 3 Phase
supply form ES
Source
breake
Source
breake
ID Ch # POW ER CONVE RTER BRID
POW ER CONV ERTER BRID Loadbreake
Load
breake
BRUSHLESS
SYNCHRONO
MOTOR
Channel 1
Channel
-
7/31/2019 VFD Commissioning Dept
40/63
THYRISTOR FIRING
1 53
2
1
4 66 2
1 2 3 4 5 6 1 2 3
120 de .
-
7/31/2019 VFD Commissioning Dept
41/63
1 3
4 6
5
2
I
DC
Voltage
Source
Synchronous Motor
Stator Winding
R Ph
Y Ph
B Ph
-
7/31/2019 VFD Commissioning Dept
42/63
1 3
4 6
5
2
I
DC
Voltage
Source
Synchronous Motor
Stator Winding
R Ph
Y Ph
B Ph
-
7/31/2019 VFD Commissioning Dept
43/63
1 3
4 6
5
2
I
DC
Voltage
Source
Synchronous Motor
Stator Winding
R Ph
Y Ph
B Ph
-
7/31/2019 VFD Commissioning Dept
44/63
1 3
4 6
5
2
I
DC
Voltage
Source
Synchronous Motor
Stator Winding
R Ph
Y Ph
B Ph
-
7/31/2019 VFD Commissioning Dept
45/63
1 3
4 6
5
2
I
DC
Voltage
Source
Synchronous Motor
Stator Winding
R Ph
Y Ph
B Ph
-
7/31/2019 VFD Commissioning Dept
46/63
1 3
4 6
5
2
I
DC
Voltage
Source
Synchronous Motor
Stator Winding
R Ph
Y Ph
B Ph
-
7/31/2019 VFD Commissioning Dept
47/63
1 3
4 6
5
2
I
DC
Voltage
Source
Synchronous Motor
Stator Winding
R Ph
Y Ph
B Ph
-
7/31/2019 VFD Commissioning Dept
48/63
R Ph
Y Ph
B Ph
1 2 3 4 5 6 1
FIRING SEQUENCE & PHASE CURRENTS
-
7/31/2019 VFD Commissioning Dept
49/63
VFD Data for Motor:
Base armature current per channel - 580
AmpsBase Voltage(Ac r.m.s) - 2300 V
Base speed / frequency - 530 / 44.2
Base exciter current - 150 Amps
Exciter Data:
Rated EVC Current - 74 Amps
Maximum allowable continuous exciter stator currentat standstill: - 75 Amps
Nominal source voltage - 2300 V AC
-
7/31/2019 VFD Commissioning Dept
50/63
Source breaker tripping initiated through VFD
system:
This is other than protection tripping from HT
S.W.gear)
Source breaker tripping through an aux.
relay (hand resettable flag relay) mounted on
control panel. VAA13 relay on each channel.
In case of source breaker tripping check this
relay has operated on control panel of VFD
room. If this relay has not operated tripping is
from HT breaker tri circuit rela s &
-
7/31/2019 VFD Commissioning Dept
51/63
VAA13 relay can operate on following
conditions:
Through LCI panel source side faultthrough SWGR relay in LCI panel.Through 11KV/2.3KV transformer Oil
temp. trip, winding temperature trip &Buchholz trip. In that case flag relay
(FLAGRY) installed just above VAA13 relay
shall operate & flag will come.
Emergency push button is pressed.Trip command from control panel
[CLOSE-NEUTRAL-TRIP] on VFD room.
-
7/31/2019 VFD Commissioning Dept
52/63
POWER SUPPLIES
In control panel of VFD room there are
following supplies for different
interlocks & distribution:-1.0 3Phase, 415 V AC supplies
02Nos. (1st from Ch # 1 LCI Panel &
2nd from Ch # 2 LCI Panel) which inturn fed from 415V ESP MCC.
-
7/31/2019 VFD Commissioning Dept
53/63
415 V AC supplies stepped down to 110V
AC, 1phase and 220 V AC, 1phase supplies
through transformers.110V supply used for control & interlock
relays of both channels in control panel itself.
220V supply is used for space heaters ofpanels, motor, reactor, cubicle illumination
lamps, door mounted printer and line
drivers, temperature scanner, reactor temp.indicator, motor water leakage defector etc.
-
7/31/2019 VFD Commissioning Dept
54/63
24V DC: 24V AC stepped down from
415V and then rectified to 24V DC for
control panel indication lamp.
Another 24V DC supply from FSSS for
starting / stopping circuit of ID Fan
channels.
220V DC: supply from station battery
supply for source breaker tripping
interlocks.
-
7/31/2019 VFD Commissioning Dept
55/63
Power supplies in LCI Panel:
. 2.3 KV main supply connected to Source Bridge inbridge panel.
. 415 V 3 phase supply to C&E panel which is drawn
from ESP feeder (separate source for each C&E panel forCh # 1&2).
415V supply stepped down to 220V & 110V AC
220V, 10 AC is used for fan flow indicator & SEM rack
fan.
110V AC, 1phase is used for power supplies to all
-
7/31/2019 VFD Commissioning Dept
56/63
SOME MAJOR FAULTS: VFD trips on these faults
Loss of cooling fan
Source Overcurrent
Load overcurrent
Field Loss
Load commutation failure
Source commutation failure
Load overvoltage fault
Bridge differential pressure
Gating supply undervoltage fault
P105 supply undervoltage
SOME MAJOR FAULTS VFD t i th f lt
-
7/31/2019 VFD Commissioning Dept
57/63
SOME MAJOR FAULTS: VFD trips on these faults
Overspeed
Ground Fault
Fan compartment door open
Source Low line or deep undervoltage
SOME MAJOR ALARMS: Attention needed to check
Loss of speed reference
Gating supply undervoltage
Microprocessor alarm
Bridge filter fuse blown
Source undervolts
Transformer alarm
-
7/31/2019 VFD Commissioning Dept
58/63
START PERMISSIVES FOR THE CHANNELS (To be seen
at VFD room):
No emergency stop pressed.
No motor overtemperature trip persisting
Bus supervision 24V DC & 220V DC healthy
Heating & Illumination CB 2 ON
No water leakage in Motor
Water flow healthy in motor
CB3 in control panel ON, all indication lamp circuit healthy
No transformer alarms persisting
No transformer trips persisting
-
7/31/2019 VFD Commissioning Dept
59/63
START PERMISSIVES FOR THE CHANNELS (To be seen
at VFD room):
No reactor alarm persisting
No reactor trip persisting
Motor isolator i.e., VFD breaker (VFD output to motor) not
closed
Source breaker closed
-
7/31/2019 VFD Commissioning Dept
60/63
CLOSE PERMISSIVES FOR THE SOURCE BREAKER
(To be seen at VFD room):
No emergency stop pressed.No motor over temperature trip persisting
Bus supervision 24V DC & 220V DC healthy
Heating & Illumination CB 2 ON
No water leakage in Motor
Water flow healthy in motor
CB3 in control panel ON, all indication lamp circuithealthy
No transformer alarms persisting
No transformer trips persisting
-
7/31/2019 VFD Commissioning Dept
61/63
CLOSE PERMISSIVES FOR THE SOURCE BREAKER
(To be seen at VFD room):
No reactor alarm persistingNo reactor trip persisting
Permit to close source breaker from LCI panel ( from
IOMA card : Swgr. Relay shall not be picked up
-
7/31/2019 VFD Commissioning Dept
62/63
CHANNEL RUN PERMIT (To be seen at VFD room):
No emergency stop pressed.
No motor over temperature trip persisting
Bus supervision 24V DC & 220V DC healthy
Heating & Illumination CB 2 ONNo transformer trips persisting
No reactor trip persisting
Source breaker closed
Motor isolator i.e., VFD breaker (VFD output to motor)
not closed
-
7/31/2019 VFD Commissioning Dept
63/63
THANK YOU