VOLTAGE STABILITY

Ph.D. Seminar

Indian Institute of Technology, Bombay

Jignesh M. Solanki

Page 2: Vol Stability Slides

2

What is voltage stability ?

maintain steady acceptable voltages at all buses in the system a system enters a state of voltage instability when a disturbance,

increase in load demand inability of a power system to meet the demand for reactive power a criterion for voltage stability stability is that,

bus voltage magnitude increase as reactive

power injection at the same bus increase a system is voltage unstable if, V-Q sensitivity

Page 3: Vol Stability Slides

3

voltage instability is essentially a local phenomenon voltage collapse is more complex than simple voltage

instability

Page 4: Vol Stability Slides

4

ILLUSTRATION OF VOLTAGE INSTABILITY

Limit of satisfactory operation For higher load demand , control of power by varying load

would be unstable if load is supplied by transformers with ULTC, the tap-

changer action try to raise the load voltage. This has lower effective ZLD and due to that VR goes low still further and

It may call pure form of voltage instability.

A simple radial system for illustration of voltage stability phenomenon

Page 5: Vol Stability Slides

5

CLASSIFICATION OF VOLTAGE STABILITY

LARGE DISTURBANCE VOLTAGE STABILITY

SMALL DISTURBANCE VOLTAGE STABILITY

TRANSIENT VOLTAGE STABILITY LONGER TERM VOLTAGE STABILITY

Page 6: Vol Stability Slides

6

LARGE DISTURBANCE VOLTAGE STABILITY (LDVS)

It is concerned with systems ability to control voltages following large disturbances such as system faults, loss of generator or circuit contingency.

Load characteristics and the interaction of both continuous and discrete controls and protections.

Determination of LDVS requires the examination of the non-linear dynamic performance of a system over a period of time (ULTC and generator field current limiter)

Page 7: Vol Stability Slides

7

For analysis long-term dynamic simulations are required. A criterion of large disturbance voltage stability, is that,

following a given disturbance and system control actions, voltage at all buses reach acceptable steady state levels.

Page 8: Vol Stability Slides

8

control voltages following small perturbations load characteristics, continuous control and discrete

control Basic process a steady state nature Stability margin, identifying factors influencing stability,

examine wide range of system conditions and large number of post contingency scenarios.

A criterion for SDVS, V-Q sensitivity

SMALL DISTURBANCE VOLTAGE STABILITY (SDVS)

Page 9: Vol Stability Slides

9

TRANSIENT VOLTAGE STABILITY

0 to 10 seconds, transient rotor angle stability voltage

voltage collapse is caused by unfavorable fast acting load components (IM and DC converters)

For severe voltage dips the reactive power demand of IM increases, contributing to V.C

Electrical islanding and under frequency load shedding resulting V.C. when imbalance is greater than about 50%.

Page 10: Vol Stability Slides

10

Voltage decays faster than frequency under frequency relays may not operate There are incidents where the voltage collapses before

frequency decays to the under frequency load shedding set points

Voltage and frequency for South Florida blackout

Page 11: Vol Stability Slides

11

LONGER TERM VOLTAGE STABILITY

2-3 minutes involves high loads, high power inputs from remote

generation and a sudden large disturbance (lass of generator or loss of major transmission line)

the disturbance causes high reactive power losses and voltage sags in load areas

the tap changer sense low voltages and act to restore disturbance voltages thereby restoring load power levels

Page 12: Vol Stability Slides

12

further sags of transmission voltages. generator farther away must then provide reactive power

this is inefficient and ineffective no longer support by generation and transmission system. partial and complete voltage collapse.

Page 13: Vol Stability Slides

13

RELATION OF VOLTAGE STABILITY AND ROTOR ANGLE STABILITY

VOLTAGE STABILITY

Pure voltage stability transient voltage stability reactive power control concerned with load area and load

characteristics load stability voltage collapse in load area without loss of synchronism of any

generators generator current limiting is very

detrimental to both form of stability

ROTOR ANGLE STABILITY

Pure angle stability

transient RAS

reactive power control

integrating remote power plant to a large

system over a long transmission line

generator stability

voltage collapse in transmission system

remote form loads

Page 14: Vol Stability Slides

14

VOLTAGE INSTABILITY IN MATURE POWER SYSTEM

intensive use of existing generation and transmission. new generation in load areas and transmission lines from

remotely sited generation increased use of shunt capacitor bank. How V.I. can become a problem in Mature power system?

series reactive P.L. = I2 x take loading is I = 1000 amp, one line outage.

other lines peak up 25%

Page 15: Vol Stability Slides

15

losses = (5 lines x 3 phase x 10002 x 80 ohms ) = 1200 MVA

25% peak up so losses = 1500 MVA. after several years load growth assume loading is 1500

Amp. losses = 2700 MVAr

25% increase 3375 MVAr because of these non linear process, V.S. problem develop

only in few years.

Page 16: Vol Stability Slides

16

V-Q CURVES

voltage security is closely related to reactive power and a v-q curves gives reactive power margin at the test bus.

the slope of the V-Q curves indicated the stiffness of the test bus

reactive power of the generators can be plotted on same graph

V-Q curve sketches showing effect of voltage sensitive loads and tap changers on limit

Page 17: Vol Stability Slides

17

the effect of voltage sensitivity loads ( i.e. prior to tap changing ) will have much greater reactive power margins and much lower critical voltages

when tap changer hit limits, the curves tend to flatten out rather then turn up on the left side

Page 18: Vol Stability Slides

18

VOLTAGE STABILITY ANALYSIS

DYNAMIC ANALYSIS

for detailed studies of specific voltage control situations. co-ordination of protection and controls and testing of

remedial measures. dynamic simulations also examine whether and how the

steady-state equilibrium point will be reached.

Page 19: Vol Stability Slides

19

STATIC ANALYSIS

allow examination of a wide range of system conditions nature of the problem and identify the key condition

factors

Page 20: Vol Stability Slides

20

DETERMINATION OF SHORTEST DISTANCE TO INSTABILITY

increase load from Po,Qo in some direction until an eigen

value of a Jacobian is practically zero. surface S represents the locus of all combinations of P and

Q which results in a zero eigen value of Jacobian. P1,Q1 corrosponding to this point is the stability limit

which lies on or extremely near to S.

Page 21: Vol Stability Slides

21

the load on the transmission lines is too high. the voltage sources are too far from the load centres. the source voltages are too low. large distances between generation and load. ULTC action during low voltage conditions. poor co-ordination between various control and protective

systems. insufficient load reactive compensation.

CAUSES OF VOLTAGE COLLAPSE

Page 22: Vol Stability Slides

22

PREVENTION OF VOLTAGE COLLEPSE

application of reactive power compensating devices control of network voltage and generator reactive o/p co-ordination of protection / controls control of transformer tap changers undervoltage load shedding stability margin spinning reserve operators' action

Page 23: Vol Stability Slides

23

GENERIC DYNAMIC LOAD MODEL

Pt = V or Pv = c2V2 + c1V + c0

Ps = P0V or Ps = P0(d2V

2 + d1V + d0)

where V is the per-unit magnitude of the voltage imposed on the load

It can be seen that, at steady-state, state variable x of the model is constant

A generic dynamic model

Page 24: Vol Stability Slides

24

e = Ps – P, must be zero

The transient output is then determined by the transient characteristics P = xPt

The mismatch between the model output and the steady-state load demand is the error signal e

This signal is fed back to the integration block that gradually changes the state variable x

This process is continues until a new steady-state (e=0) is reached

Pt(V) = V, Ps(V) = P0Va; Qt(V) = V, Qs(V) = Q0V

b

Page 25: Vol Stability Slides

25

LOAD MODELLING

ix3 = ixE = ixM + ixC ; iy3 = iyE + iyN + iyC

Exponential load Polynomial load P(V3) = Po (V3/V3o)

P = Po [aP(V/Vo)2 + bP(V/Vo) + CP]

Q(V3) = Qo (V3/V3o) Q = Qo [aQ(V/Vo)2 + bQ(V/Vo) + CQ]

, depends on load ; aP + bP + cP = aQ = bQ = cQ = 1

Po,Qo is consumed power at reference voltage

complex current injected in to the network IE = - (S/V3) = -[ P(V3) – jQ(V3)/Vx3 – j Vy3 ] = ixE + j VyE

Page 26: Vol Stability Slides

26

CONCLUSION

Three key concepts of voltage stability are the load characteristics as seen from the bulk power network the available means for voltage control at generators and in the

network the ability of network to transfer power particularly reactive power

from the point of production to the point of consumption The network steady state loadability limit is not necessarily the voltage

instability limit Static power flow based analyses of the post disturbance steady state is

the useful method of analyzing longer term voltage stability The fundamental cause of voltage instability is identified as

incapability of combined transmission and generation system to meet excessive load demand in either real power or reactive power form

Page 27: Vol Stability Slides

27

Thank You