VTX Supervision Relay AREVA T&D Customer Benefits • High stability on external faults • Tuned to rated frequency • 25ms operating time at 5 times current setting VTX relay is used for the continuous supervision of CT secondary wiring and connections of busbar protection schemes. A built in delay of 3 seconds is provided to avoid unwanted alarm during external/internal faults.The relay after operation will short the CT bus wires. Features Consistent accuracy. Reliability. Low burden. Reduced maintenance. Immunity to transients and surges, withstands 5 KV impulse voltage test. Application This relay is used for the continuous supervision of CT secondary wiring and connections of busbar protection schemes. Each protected zone of the busbar installation is equipped with an alarm relay, should the CT secondary wiring develop a fault while load current is flowing, an alarm is given after a time delay of 3 seconds. The delay is given to prevent an alarm in the case of genuine busbar fault when the busbar protection is required to operate and isolate the faulty section. Further, due to its sensitive setting requirement, the relay may be unstable under heavy external fault conditions, the time delay allows the fault to be cleared by the appropriate protection thus preventing unwanted alarms. There are two types: Single phase VTX 11 and three phase VTX 31. The following Table gives the functional details of both the types. PROTECTION Description The relay consists of three stages, pick-up voltage control stage, timing stage and output stage. The block diagram of VTX 11 is shown in Figure 1. The three phase version VTX 31 is same as VTX 11 except that a three phase rectifier bridge is used to convert ac input quantities to dc signal. Under healthy conditions of the protected circuit there is no ac input to the relay and the auxiliary dc supply causes transistor T1 to conduct, shorting out the capacitor in the timing circuit. When a voltage appears across the ac input terminals, the rectified dc output of the bridge tends to bias off the transistor T1, in case the ac input is higher than the voltage setting. With T1 off, the timing circuit capacitor begins to charge up from the stabilised dc supply. After a time delay of 3 seconds, the capacitor voltage reaches a pre- determined value and triggers the transistor T2 which in turn switches on the output transistor T3. The internal electromechanical auxiliary unit, being in the load circuit of transistor T3 picks up and initiates alarm and other functions. Continuous adjustment of the relay voltage setting is provided by a potentiometer in the bridge output circuit. Protective devices have been included in the circuitry to prevent damage due to spikes in the input voltages or reverse connection of the dc auxiliary supply. Single phase used with earth fault schemes Three phase used with phase and earthfault schemes Will detect open circuit of current transformers. Will detect open circuit of current transformers Will detect broken or crossed CT pilots

Upload: hari-krishnam

Post on 08-Nov-2014

1.033 views

Category:

Documents


130 download

DESCRIPTION

VTX

TRANSCRIPT

Page 1: VTX

VTXSupervision Relay

AREVA T&D

Customer Benefits

• High stability on external faults• Tuned to rated frequency• 25ms operating time at 5 times current setting

VTX relay is used for the continuous supervision of CT secondary wiring and connections of busbar protection schemes. A built in delay of 3 seconds is provided to avoid unwanted alarm during external/internal faults.The relay after operation will short the CT bus wires.

Features • Consistentaccuracy. • Reliability. • Lowburden. • Reducedmaintenance. • Immunitytotransientsandsurges, withstands5KVimpulsevoltagetest.

Application

Thisrelayisusedforthecontinuoussupervisionof CT secondary wiring and connections ofbusbar protection schemes. Each protectedzoneofthebusbarinstallationisequippedwithanalarmrelay,shouldtheCTsecondarywiringdevelopafaultwhileloadcurrentisflowing,analarmisgivenafteratimedelayof3seconds.The delay is given to prevent an alarm in thecaseofgenuinebusbar faultwhen thebusbarprotectionisrequiredtooperateandisolatethefaultysection.Further,duetoitssensitivesettingrequirement, the relay may be unstable underheavy external fault conditions, the time delayallowsthefaulttobeclearedbytheappropriateprotectionthuspreventingunwantedalarms.

Therearetwotypes:SinglephaseVTX11andthreephaseVTX31.ThefollowingTablegivesthefunctionaldetailsofboththetypes.

PROTECTION

DescriptionThe relay consists of three stages, pick-upvoltagecontrol stage, timingstageandoutputstage.TheblockdiagramofVTX11isshowninFigure1.ThethreephaseversionVTX31issameas VTX 11 except that a three phase rectifierbridgeisusedtoconvertacinputquantitiestodcsignal.

UnderhealthyconditionsoftheprotectedcircuitthereisnoacinputtotherelayandtheauxiliarydcsupplycausestransistorT1toconduct,shortingout thecapacitor in the timingcircuit.Whenavoltageappearsacross theac input terminals,the rectified dc output of the bridge tends tobiasoffthetransistorT1,incasetheacinputishigherthanthevoltagesetting.WithT1off,thetimingcircuitcapacitorbeginstochargeupfromthestabiliseddcsupply.Afteratimedelayof3seconds, the capacitor voltage reaches a pre-determinedvalueandtriggersthetransistorT2which inturnswitchesontheoutputtransistorT3.Theinternalelectromechanicalauxiliaryunit,being in the load circuit of transistor T3 picksup and initiates alarm and other functions.Continuous adjustment of the relay voltagesetting is provided by a potentiometer in thebridge output circuit. Protective devices havebeenincludedinthecircuitrytopreventdamagedue to spikes in the input voltages or reverseconnectionofthedcauxiliarysupply.

Singlephaseusedwithearthfaultschemes

Threephaseusedwithphaseandearthfaultschemes

Will detect open circuit ofcurrenttransformers.

Will detect open circuit ofcurrenttransformers

WilldetectbrokenorcrossedCTpilots

Page 2: VTX

VTXrelaywithdrawnfromcase

Technical dataVoltage setting

2to14Vcontinuouslyadjustableat50Hz.

Thermal rating • Singlephaserelay: 600Vacrmsat50Hzbetweenthe inputterminalscontinuouslyonanysetting. • Threephaserelay: 300Vacrmsat50Hzbetweenany phaseandneutraloftheinputterminals continuouslyonanysetting.Therelay willalsowithstand2kVacrms50Hz forthreesecondsonanysetting.

Auxiliary supply

Therelaycanbesuppliedsuitableforoperationat30V,110Vand220Vdc.Forvoltagesabove30V, an external dropping resistor is used.Satisfactory operation is maintained over arangeof75%-120%.

Accuracy

• Atratedauxiliarysupplyandrated frequency,therelayhasanaccuracyof ±5%ofthesettingvalueonanysetting.

• Operatingtemperaturerange-5ºCto +50ºC.

Operating time

Nominal3seconds.

Figure1:BlockdiagramforVTX11relay

2>3

Page 3: VTX

BurdenContinuousburdenimposedondcauxiliarysupplyisasshowninthetablebelow:

AuxiliAry voltAge 30V

relAy unoperAted (W)

110V 220V

1.0 3.5 7.0

relAy operAted (W) 1.7 4.0 7.7

Approximateacburdenperphaseforbothtypesofrelaysonanysettingisasfollows:

Applied voltAge 10V

Burden (vA)

300V 1414V

0.002 4.2 86

ContactsTwopairsofnormallyopen,selfresetcontactsareprovidedontheoutputattractedarmatureunit.

Contact ratings

MAke And cArry continuously

AC

MAke And cArry for 0.5 second

BreAk

1250VAwithmaximaof5Aand660V

7500VAwithmaximaof30Aand660V

1250VAwithmaximaof5Aand660V

DC 1250Wwithmaximaof5Aand660V

7500Wwithmaximaof30Aand660V

100W(resisitive)50W(inductive)withmaximaof5Aand660V

Operation indicator

A hand reset mechanical operation indicatoris fitted as standard on the output attractedarmatureunit.

Insulation

The relay will withstand 2.5 kV rms 50 Hz for1secondbetweenall livepartsandearth,andbetweenallcircuitsnotintendedtobeconnectedtogether.Itwillalsowithstand1.25kVrms50Hzfor1sacrossopencontacts.

Impulse withstand level

The relay will withstand 5 kV impulse voltagetestinaccordancewithIECrecommendations.

Page 4: VTX

High frequency disturbance

The relay meets the IEC test recommendationfor the high frequency disturbance test. Therelay accuracy is unaffected by repetitive 1MHz bursts having an initial peak of 1.0 KVsuper-imposedacrossinputcircuitsand2.5KVbetweenindependentcircuitsandearth,withatimedelayof3to6microseconds,withtherelayenergised.

Case

Singlephaseandthreephaserelaysaresuppliedin size 1 drawout (1D) cases suitable for flushmounting and are finished eggshell black andtropicalised. The drawout feature considerablysimplifiesmaintenanceandpermitstestingtobecarriedouteasilyandquickly.Acradlemountedisolatingswitchisprovidedwhichautomaticallyisolatesthetripcircuitwhenthecradleassemblyis withdrawn from the case for maintenance.This prevents any inadvertent tripping of thecircuit breaker. A filter breather is fitted whichequalises the pressure inside and outside thecasewithoutadmittingdust.

Information required with order

1.Typeofrelay

2.Auxiliarydcvoltage

Figure2:Typical connection diagram ofVTX 31 relay in 3 phase buszone protection scheme forphaseandearthfaults.

4>5

Page 5: VTX

Dimensions and weights

relAy cAse size

MAxiMuM overAll diMensions

VTX31

ApproxiMAte gross Weight

kgheightMM

WidthMM

depth* MM

1Dvert. 233 170 203 4.5

* Add76mmformaximumlengthofterminalstuds,alternatively,29mmforterminalscrews. Theapproximategrossweightsgivenaboveisinclusiveofcartons,mountingappendages andterminaldetails. TherelayscomplyfullywiththerequirementsofIS3231andaresuitableforuseinnormal tropicalenvironments.

Page 6: VTX

AREVA T&D

Pallavaram Works19/1, G.S.T. Road,Pallavaram, Chennai - 600 043Tel: 91-44-2264 8000

Fax: 91-44-2264 0040

AREVA T&D Worldwide Contact Centre:http://www.areva-td.com/contactcentre/Tel.: +44 (0) 1785 250 070

www.areva-td.com

Our policy is one of continuous development. Accordingly thedesignofourproductsmaychangeatanytime.Whilsteveryeffortismadetoproduceuptodateliterature.Thisbrochureshouldonlybe regardedasaguideand is intended for informationpurposesonly. Itscontentsdonotconstituteanoffer forsaleoradviseontheapplicationofanyproductreferredtoinit.Wecannotbeheldresponsibleforanyrelianceonanydecisionstakenonitscontentswithoutspecificadvice.

AR

EVA

,the

AR

EVA

logo

and

any

alte

rnat

ive

vers

ion

ther

eofa

ret

rad

emar

ksa

nds

ervi

cem

arks

ofA

RE

VA

MiC

OM

isa

reg

iste

red

tra

dem

ark

ofA

RE

VA.A

lltr

ade

nam

eso

rtr

adem

arks

men

tione

dh

erei

nw

heth

err

egis

tere

do

rno

t,a

ret

hep

rop

erty

oft

heir

owne

rs.