Design Philosophy
Raw Water Design Basis In absence of report we have assumed some parameters as Follows, however we request you to furnish the complete analysis report to offer you the correct scheme/capacity & recovery.
Sl. No. Parameters Designing Data
01 Appearance Clear
02 Colour Colourless
03 Odour Odourless
04 pH 7.0 – 7.5
05 Suspended solids < 5 ppm (Assumed)
06 Turbidity < 2 NTU
07 Total Dissolved Solids 550 ppm as per your sample water
15 Chlorides as Cl 35 ppm (Assumed)
16 P Alkalinity as CaCO3 Nil
17 M Alkalinity as CaCO3 82 ppm (Assumed)
18 Total Hardness as CaCO3 260 ppm as per your sample water
19 Heavy Metals Nil
20 Oil & Grease Nil
We have assumed that raw water does not contain Turbidity, Suspended Solids, free chlorine, colloidal silica, Heavy Metal and Oil & Grease. Any change in above design Data/Parameters will affect the working of the plant.
Equipment Schedule
Dosing Pump Raw Water Tank Raw Water Sand Carbon Micron High Pump Filter Filter Filter Pressure Pump RO Array Product Water
Reject Water Pure Water Storage Tank
Technical Details
1) Raw Water Pump
Description Unit Quantity
Numbers offered Nos. 01
Capacity M3/Hr. 0.6 @ 2.8 bar
Material of construction Cast Iron
Make Crompton/ kirloskar/eq.
2) Pressure Sand Filter Model : BG-PSF-844
Description Unit Quantity
Numbers offered Nos. 01
Max. Flow M3/hr. 0.8
Max. operating pressure Kg/cm2 2.8
Material of construction FRP
Specification & Scope of Supply :
Description Quantity
FRP Vessel with Multiport Valve One set
Set of internal distribution & Frontal pipe work One set
Pressure Gauges to monitor pressure drop across unit One Nos.
Initially charge of sand One Lot
3) Activated Carbon Filter Model : BG-ACF-844
Description Unit Quantity
Numbers offered Nos. 01
Max. Flow M3/hr. 0.8
Max. operating pressure Kg/cm2 2.8
Material of construction FRP
Specification & Scope of Supply :
Description Quantity
FRP Vessel with Multiport Valve One set
Set of internal distribution & Frontal pipe work One set
Pressure Gauges to monitor pressure drop across unit One Nos.
Initially charge of Activated Carbon & Supporting media One set
4) Anti-Scalent Dosing Pump
Description Unit Quantity
Numbers offered Nos. 01
Make e-dose or equivalent
Material of construction Plastic
5) Reverse Osmosis System Model : BG-RO-200
Description Unit Quantity
Numbers offered Nos. 01
Treated water quality TDS PPM 20-50 +-10%
Specification & Scope of Supply :
1) Micron Cartridge Filter
Numbers offered Nos. 01
Max. Flow M3/hr. 1.0
Cartridge porosity Micron 05
2) High Pressure Pump
Numbers offered Nos. 01
Max. flow M3/hr. 0.8
Material of construction SS
Make Shimge / Nanfang / Equi
3) RO Housing / Pressure Tube
Numbers offered Nos. 01
Type 4-300-1E
Make Blueguard / equi.
Material of construction FRP
4) Reverse Osmosis Membrane
Numbers offered Nos. 01
Make Hydranautics/lewabrane/equi.
Type 4040
5) Control Panel
Numbers offered Nos. 01
Designed to ensure fail-safe operation and will be provided with high & low pressure switches for better automation.
6) Rotameter
Numbers offered Nos. 2
Material of construction Acrylic body
7) Conductivity Meter
Numbers offered Nos. 01
Make Aster / equi.
8) Low & High Pressure Switch
Numbers offered Nos. 02
Make Danfoss / equi.
9) Valves
Material of construction uPVC
10) Cleaning in Place System
Numbers offered Nos. 01
11) Skid
Numbers offered Nos. 01
Material of construction MS Powder Coated
12) Inter-connection Pipeline
Numbers offered Nos. One Lot
Material of construction UPVC
Schedule of Exclusion Equipment’s & Service to be provided by Purchaser
All civil work including design and construction of foundation, drains, sumps, neutralization sump, supports of all types platforms, drain channels, plant building and mass concreting of units [if required], [we shall only provide load data] Instrument quality air including air compressor, air drying unit and distribution network. All electrical works like power supply, cables, cabling cable trays, underground earthing, motor/ local control centers, starters push button station and plant lighting including materials Unloading, storage and security of equipment at site. Skilled, unskilled labour, supervisory staff tools and tackle for erection and commissioning of the plant. We shall provide supervision of erection & commissioning of the plant by our engineer on the terms and conditions mentioned in our offer. Laboratory facilities including necessary instruments, chemicals and staff. Lubricants, oils and grease including the first charges. Water supply at the required temperature & pressure at the inlet of the equipment offered relevant connection from termination points given in our offer. Scope of supply & services not specifically mentioned as forming a part of our offer acid alkali proof lining of required areas like neutralizing sump, acid, alkali, handling areas.
Acids / alkali / chemical & any other consumables including the first charge.
Commercial Terms & Conditions Prices The prices Ex – Dombivali.
Validity 30 Days from the date of quotation.
Taxes GST 18.0% Extra.
Octroi & Freight Extra at Actual shall be borne by Client.
Insurance By Client.
Payment Terms 70% Advance along with purchase / work order.
30% Against inspection at our factory prior to dispatch.
Delivery Within 8 to 10 days from the date of purchase order along with 70% advance.
Installation & Commissioning
5, 000.00 lump sum against supervision, to & fro charges, lodging & boarding charges for two people at actual in advance.
Warranty The unit supplied by us is warranted for a period of 12 months from the date of installation & commissioning or 15 months from the date of dispatch whichever is earlier as per the terms & conditions of warranty mentioned in operation manual cum warranty card supplied with unit.
We hope the above is in line with your requirement, thanking you and assuring you the best of services at all times, we remain, If you need any further clarification please feel free to contact us.
General Diagram For Reference Only
Note; Above Given Picture is almost look alike to plant we offered you but actual plant may differ in appearance.